Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
PROJECT LOCATION MAP
VOLUME 1 OF 1
70, 91, 102, 111, 112, 113, & 123
8/
/2
:4 0:
P
M C
:\U se rs \w re ed
\D oc um en ts \E
_2 3-
3-
Q
-V A
M ilw au ke e- In st l L tn g
Pr ot
-W I_
R
_w re ed R
G 8R
E.
rv t
GI001
ENG. PROJECT COVER
1 24WSR
INSTALL LIGHTNING
PROTECTION
CLEMENT J. ZABLOCKI VAMC
5000 WEST NATIONAL AVENUE
MILWAUKEE, WI 53295 AUGUST 20, 2024
100% CONSTRUCTION DOCUMENTS
695-22-10623-093
INSTALL LIGHTNING PROTECTION
CLEMENT J. ZABLOCKI VAMC
5000 WEST NATIONAL AVENUE
MILWAUKEE, WI 53295
VA PROJECT #: 695-22-106
KTK
GENERAL
GENERAL GI001 ENG. PROJECT COVER 1 24
ELECTRICAL
ELECTRICAL E-001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 2 24
ELECTRICAL ES101 BUILDING 70 & 123, OVERALL PLANS 3 24
ELECTRICAL ES102 BUILDING 111, OVERALL UPPER AND LOWER ROOF PLANS 4 24
ELECTRICAL ES103 BUILDING 111, EASTERN & NORTHERN LIGHTNING PROTECTION ELEVATIONS 5 24 ELECTRICAL ES104 BUILDING 111, WESTERN & SOUTHERN LIGHTNING PROTECTION ELEVATIONS 6 24 ELECTRICAL 70.E101 BUILDING 70/E & K ROOF, LIGHTNING PROTECTION PLAN, NEW WORK 7 24
ELECTRICAL 70.E102 BUILDING 70/B & A ROOF, LIGHTNING PROTECTION PLANS 8 24
ELECTRICAL 70.E103 BUILDING 70/C ROOF, LIGHTNING PROTECTION PLAN, NEW WORK 9 24
ELECTRICAL 70.E104 BUILDING 70/D ROOF, LIGHTNING PROTECTION PLAN, NEW WORK 10 24
ELECTRICAL 102.E101 BUILDING 91 & 102 ROOF, LIGHTNING PROTECTION PLAN, NEW WORK 11 24 ELECTRICAL 111.E101 BUILDING 111 UPPER A WING ROOF, LIGHTNING PROTECTION PLANS 12 24 ELECTRICAL 111.E102 BUILDING 111 UPPER B WING ROOF, LIGHTNING PROTECTION PLANS 13 24 ELECTRICAL 111.E103 BUILDING 111 UPPER C WING ROOF, LIGHTNING PROTECTION PLANS 14 24 ELECTRICAL 111.E104 BUILDING 111, FLOOR 2 AND 5 ROOF, LIGHTNING PROTECTION PLAN, NEW WORK 15 24
ELECTRICAL 112.E101 BUILDING 112 ROOF, LIGHTNING PROTECTION PLANS 16 24
ELECTRICAL 113.E101 BUILDING 113 ROOF, LIGHTNING PROTECTION PLAN, NEW WORK 17 24
ELECTRICAL 123.E101 BUILDING 123/A ROOF, LIGHTNING PROTECTION PLANS 18 24
ELECTRICAL 123.E102 BUILDING 123/B ROOF, LIGHTNING PROTECTION PLANS 19 24
ELECTRICAL 123.E103 BUILDING 123/C ROOF, LIGHTNING PROTECTION PLANS 20 24
ELECTRICAL 123.E104 BUILDING 123/D ROOF, LIGHTNING PROTECTION PLANS 21 24
ELECTRICAL 123.E105 BUILDING 123/E ROOF, LIGHTNING PROTECTION PLANS 22 24
ELECTRICAL E-501 ELECTRICAL DETAILS 23 24
ELECTRICAL E-502 ELECTRICAL DETAILS 24 24
Docusign Envelope ID: FB232B3D-DB2C-480F-9397-58A7828991F7
8/19/2024
SYMBOL HEIGHT DESCRIPTION
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION CONDUCTOR
LIGHTNING PROTECTION CONDUCTOR TO BE
DEMOLISHED
LIGHTNING PROTECTION AIR TERMINAL TO BE
DEMOLISHED
LIGHTNING PROTECTION GROUND ROD
CONDUCTOR ROOF PENETRATION
ROOF PENETRATION TO BE DEMOLISHED
DOWN CONDUCTOR
BOND CONDUCTOR TO METAL BODY
'T' CONNECTION OF CONDUCTORS
CONDUCTOR BOND TO BE DEMOLISHED
HORIZONTAL THRU-WALL PENETRATION
DOWN CONDUCTOR TO BE DEMOLISHED
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA
STANDARDS.
PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL
ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR
FINAL CONNECTIONS.
ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD
PARTY TESTING AGENCY.
IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE
PROVIDED.
COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
ALL ITEMS AND MATERIALS SHOWN, INDICATED, OR REQUIRED FOR A COMPLETE PROJECT SHALL BE PROVIDED AND
INSTALLED BY THE CONTRACTOR, UNLESS NOTIFIED OTHERWISE.
CONTRACTOR SHALL COORDINATE ANY ELECTRICAL SYSTEM REQUIRED SHUTDOWN WITH THE COR 2 WEEKS IN ADVANCE
AND CONFIRM 48 HOURS PRIOR.
CONTRACTOR SHALL OBTAIN A VA HOSPITAL DIRECTOR ISSUED, HOT WORK PERMIT FROM THE COR OR APPROVED REPRESENTATIVE. CONTRACTOR SHALL OBTAIN THE PERMIT A MINIMUM OF TWO WEEKS PRIOR TO ANY WORK THAT WILL
CAUSE A POWER OUTAGE OR WORK THAT IS CONSIDERED “HOT WORK".
ELECTRICAL GENERAL NOTES
1.
2.
3.
4.
5.
6.
PRIOR TO SUBMITTING PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS.
CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN. ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING AREAS ARE
APPROXIMATE ONLY (FIELD VERIFY).
THE CONTRACTOR SHALL CONCEAL ALL WORK WHERE POSSIBLE.
THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRED PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK.
ALL RESTORATION WORK SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND/OR THE COR/VA.
ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL OR EQUIPMENT NECESSARY TO
MEET THE REQUIREMENTS AND INTENT OF THE PROJECT.
ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT.
CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE COR/VA FACILITIES. NOTIFY COR/VA NO LESS THAN 14 DAYS (TWO WEEKS) IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY COR/VA. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF SERVICE. PROVIDE NECESSARY TEMPORARY FEEDERS TO
ACCOMPLISH THIS REQUIREMENT.
GENERAL ELECTRICAL REMODELING NOTES
L
SSTV SECURITY SURVEILLANCE
TELEVISION
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
UPS UNINTERRUPTIBLE POWER
SUPPLY
V VOLT
VA VOLT-AMPERES
VAMC VETERANS ADMINISTRATION
MEDICAL CENTER
VD VOLTAGE DROP
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHER-PROTECTED
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFSD NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BIPHENYL
PC PHOTOELECTRIC CELL
PDU POWER DISTRIBUTION UNIT
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PV PHOTOVOLTAIC
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
R RELOCATE/RELOCATED
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
2W TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFCI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCT CORRELATED COLOR TEMPERATURE
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
D DEMOLITION
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
E EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FPN FUSED PER NAMEPLATE
FU FUSE
FUSD FUSED SAFETY DISCONNECT
SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
HW HARD WIRED
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MSBD MAIN SWITCHBOARD
MT MOUNT
MV MEDIUM VOLTAGE
L
ELECTRICAL ABBREVIATIONS LIST
1.
2.
3.
4.
5.
6.
7.
RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. MATERIALS DEEMED NOT SALVAGEABLE SHALL BE
REMOVED FROM THE PREMISES.
ALL EXISTING CONDITIONS, INCLUDING BUT NOT LIMITED TO EQUIPMENT, DEVICES, FIXTURES, CONDUIT AND CIRCUITS, ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.
REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA (ALL ITEMS MAY NOT BE SHOWN). REWORK, AS NECESSARY, CIRCUITING WHICH REQUIRES
CONTINUATION THROUGH THE AREA.
ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING CIRCUIT CONTINUITY IS MAINTAINED.
ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE ELIMINATED DURING DEMOLITION AND
NEW CONSTRUCTION.
ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING
TO REMAIN" FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY THE COR.
EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.
GENERAL ELECTRICAL DEMOLITION NOTES
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.#
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
ELECTRICAL SYMBOL NOTES
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
70, 91, 102, 111, 112, 113, & 123
8/
/2
:4 1:
P
M C
:\U se rs \w re ed
\D oc um en ts \E
_2 3-
3-
Q
-V A
M ilw au ke e- In st l L tn g
Pr ot
-W I_
R
_w re ed R
G 8R
E.
rv t
E-001
ELECTRICAL GENERAL NOTES,
SYMBOL LEGENDS, AND
ABBREVIATIONS
2 24WSR
INSTALL LIGHTNING
PROTECTION
CLEMENT J. ZABLOCKI VAMC
5000 WEST NATIONAL AVENUE
MILWAUKEE, WI 53295 AUGUST 20, 2024
100% CONSTRUCTION DOCUMENTS
695-22-10623-093
KTK
ELECTRICAL SYMBOL LEGEND
A
B
C D
E
123.E101
123.E102
123.E103
123.E104
123.E105
AB
E
K
C
D
70.E101
70.E102
70.E103
70.E104
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
70 & 123
8/
/2
:4 1:
P
M C
:\U se rs \w re ed
\D oc um en ts \E
_2 3-
3-
Q
-V A
M ilw au ke e- In st l L tn g
Pr ot
-W I_
R
_w re ed R
G 8R
E.
rv t
ES101
BUILDING 70 & 123, OVERALL PLANS
3 24WSR
INSTALL LIGHTNING
PROTECTION
CLEMENT J. ZABLOCKI VAMC
5000 WEST NATIONAL AVENUE
MILWAUKEE, WI 53295 AUGUST 20, 2024
100% CONSTRUCTION DOCUMENTS
695-22-10623-093
KTK
Scale: 1" = 30'-0"1 BUILDING 123, OVERALL PLAN
NORTH
0 3015 60
Scale: 1" = 30'-0"2 BUILDING 70, OVERALL PLAN
NO
RT
H0 3015 60
A WING
C WING
B WING
111.E101
111.E102
111.E103
UPPER A WING
SEE SHEET 111.E101
UPPER B WING
SEE SHEET 111.E102
UPPER C WING
SEE SHEET 111.E103
111.E104
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
8/
/2
:4 1:
P
M C
:\U se rs \w re ed
\D oc um en ts \E
_2 3-
3-
Q
-V A
M ilw au ke e- In st l L tn g
Pr ot
-W I_
R
_w re ed R
G 8R
E.
rv t
ES102
BUILDING 111, OVERALL UPPER AND
LOWER ROOF PLANS
4 24WSR
INSTALL LIGHTNING
PROTECTION
CLEMENT J. ZABLOCKI VAMC
5000 WEST NATIONAL AVENUE
MILWAUKEE, WI 53295 AUGUST 20, 2024
100% CONSTRUCTION DOCUMENTS
695-22-10623-093
KTK
NORTH
0 3015 60
NORTH
0 3015 60
Scale: 1" = 30'-0"2 BUILDING 111, OVERALL UPPER ROOF PLAN Scale: 1" = 30'-0"1 BUILDING 111, OVERALL LOWER ROOF PLAN
R
SIXTH FLOOR
EL.= 145'-10 5/8"
FIFTH FLOOR
EL.= 134'-4"
FOURTH FLOOR
EL.= 122'-9 3/8"
THIRD FLOOR
EL.= 111'-2 3/4"
SECOND FLOOR
EL.= 97'-5 3/8"
FIRST FLOOR
EL.= 83'-8"
BASEMENT FLOOR
EL.= 69'-10 5/8"
T. O. ROOF SLAB
EL.= 243'-5"
ROOF SLAB & TANK ROOM FLOOR
EL.= 227'-2 3/8"
ELEV MACHINE ROOM FLOOR
EL.= 217'-2 3/8"
ROOF SLAB
EL.= 203'-7 3/4"
EIGHTH FLOOR
EL.= 168'-11 7/8"
ROOF SLAB
EL.= 203'-7 3/4"
TENTH FLOOR
EL.= 192'-1 1/8"
NINTH FLOOR
EL.= 180'-6 1/2"
SEVENTH FLOOR
EL.= 157'-5 1/4"
Clement J.
Zablocki
T. O. ROOF SLAB
EL.= 243'-5"
ROOF SLAB & TANK ROOM FLOOR
EL.= 227'-2 3/8"
ELEV MACHINE ROOM FLOOR
EL.= 217'-2 3/8"
EIGHTH FLOOR
EL.= 168'-11 7/8"
ROOF SLAB
EL.= 203'-7 3/4"
TENTH FLOOR
EL.= 192'-1 1/8"
NINTH FLOOR
EL.= 180'-6 1/2"
SEVENTH FLOOR
EL.= 157'-5 1/4"
SIXTH FLOOR
EL.= 145'-10 5/8"
FIFTH FLOOR
EL.= 134'-4"
FOURTH FLOOR
EL.= 122'-9 3/8"
THIRD FLOOR
EL.= 111'-2 3/4"
SECOND FLOOR
EL.= 97'-5 3/8"
FIRST FLOOR
EL.= 83'-8"
EIGHTH FLOOR
EL.= 168'-11 7/8"
ROOF SLAB
EL.= 203'-7 3/4"
TENTH FLOOR
EL.= 192'-1 1/8"
NINTH FLOOR
EL.= 180'-6 1/2"
SEVENTH FLOOR
EL.= 157'-5 1/4"
SIXTH FLOOR
EL.= 145'-10 5/8"
FIFTH FLOOR
EL.= 134'-4"
FOURTH FLOOR
EL.= 122'-9 3/8"
THIRD FLOOR
EL.= 111'-2 3/4"
SECOND FLOOR
EL.= 97'-5 3/8"
FIRST FLOOR
EL.= 83'-8"
TANK RM FLR
EL.= 227'-2 3/8"
ROOM FLOOR
EL.= 217'-2 3/8"
ROOF SLAB
EL.= 203'-7 3/4"
ROOF SLAB &
ELEV MACHINE
T/ ROOF SLAB
EL.= 243'-5"
ROOF SLAB & TANK ROOM FLOOR
EL.= 227'-2 3/8"
ELEV MACHINE ROOM FLOOR
EL.= 217'-2 3/8"
ROOF SLAB
EL.= 203'-7 3/4"
EIGHTH FLOOR
EL.= 168'-11 7/8"
ROOF SLAB
EL.= 203'-7 3/4"
TENTH FLOOR
EL.= 192'-1 1/8"
NINTH FLOOR
EL.= 180'-6 1/2"
SEVENTH FLOOR
EL.= 157'-5 1/4"
EL.= 145'-10 5/8"
FIFTH FLOOR
EL.= 134'-4"
FOURTH FLOOR
EL.= 122'-9 3/8"
THIRD FLOOR
EL.= 111'-2 3/4"
SECOND FLOOR
EL.= 97'-5 3/8"
FIRST FLOOR
EL.= 83'-8"
BASEMENT FLOOR
EL.= 69'-10 5/8"
SEVENTH FLOOR
EL.= 157'-5 1/4"
SIXTH FLOOR
EL.= 145'-10 5/8"
111.E102
111.E101
111.E104
111.E102
111.E101
111.E103
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
8/
/2
:4 1:
P
M C
:\U se rs \w re ed
\D oc um en ts \E
_2 3-
3-
Q
-V A
M ilw au ke e- In st l L tn g
Pr ot
-W I_
R
_w re ed R
G 8R
E.
rv t
ES103
BUILDING 111, EASTERN & NORTHERN
LIGHTNING PROTECTION ELEVATIONS
5 24WSR
INSTALL LIGHTNING
PROTECTION
CLEMENT J. ZABLOCKI VAMC
5000 WEST NATIONAL AVENUE
MILWAUKEE, WI 53295 AUGUST 20, 2024
100% CONSTRUCTION DOCUMENTS
695-22-10623-093
KTK
Scale: No Scale1 BUILDING 111, EASTERN LIGHTNING PROTECTION ELEVATION
Scale: No Scale2 BUILDING 111, NORTHERN LIGHTNING PROTECTION ELEVATION
'-9
3 8"
'-9
3 8"
'-6 5 8"
'-6
5 8"
'-6 5 8"
'-6
5 8"
'-6 5 8"
'-6
5 8"
'-6 5 8"
'-6
5 8"
'-6
5 8"
'-0
'-2
5 8"
EIGHTH FLOOR
EL.= 168'-11 7/8"
T/ ROOF SLAB
EL.= 243'-5"
ROOF SLAB & TANK ROOM FLOOR
EL.= 227'-2 3/8"
ELEV MACHINE ROOM FLOOR
EL.= 217'-2 3/8"
ROOF SLAB
EL.= 203'-7 3/4"
ROOF SLAB
EL.= 203'-7 3/4"
TENTH FLOOR
EL.= 192'-1 1/8"
NINTH FLOOR
EL.= 180'-6 1/2"
SEVENTH FLOOR
EL.= 157'-5 1/4"
SIXTH FLOOR
EL.= 145'-10 5/8"
FIFTH FLOOR
EL.= 134'-4"
FOURTH FLOOR
EL.= 122'-9 3/8"
THIRD FLOOR
EL.= 111'-2 3/4"
SECOND FLOOR
EL.= 97'-5 3/8"
FIRST FLOOR
EL.= 83'-8"
'-9
3 8"
'-9 3 8"
'-6
5 8"
'-6 5 8"
'-6
5 8"
'-6 5 8"
'-6
5 8"
'-6 5 8"
'-6
5 8"
'-6 5 8"
EIGHTH FLOOR
EL.= 168'-11 7/8"
ROOF SLAB
EL.= 203'-7 3/4"
TENTH FLOOR
EL.= 192'-1 1/8"
NINTH FLOOR
EL.= 180'-6 1/2"
SEVENTH FLOOR
EL.= 157'-5 1/4"
SIXTH FLOOR
EL.= 145'-10 5/8"
FIFTH FLOOR
EL.= 134'-4"
FOURTH FLOOR
EL.= 122'-9 3/8"
ROOF SLAB
EL.= 149'-10 5/8"
THIRD FLOOR
EL.= 111'-2 3/4"
SECOND FLOOR
EL.= 97'-5 3/8"
FIRST FLOOR
EL.= 83'-8"
T. O. ROOF SLAB
EL.= 243'-5"
ROOF SLAB & TANK ROOM FLOOR
EL.= 227'-2 3/8"
ELEV MACHINE ROOM FLOOR
EL.= 217'-2 3/8"
'-9
3 8"
'-6 5 8"
'-6
5 8"
'-6 5 8"
'-6
5 8"
'-6 5 8"
'-6
5 8"
'-6 5 8"
'-6
5 8"
'-0
'-2
5 8"
TYP
'-6
'-9 8"
3 8"
EL.= 227'-2 3/8"
EL.= 217'-2 3/8"
T. O. ROOF SLAB
EL.= 243'-5"
EIGHTH FLOOR
EL.= 168'-11 7/8"
ROOF SLAB
EL.= 203'-7 3/4"
TENTH FLOOR
EL.= 192'-1 1/8"
NINTH FLOOR
EL.= 180'-6 1/2"
SEVENTH FLOOR
EL.= 157'-5 1/4"
SIXTH FLOOR
EL.= 145'-10 5/8"
FIFTH FLOOR
EL.= 134'-4"
FOURTH FLOOR
EL.= 122'-9 3/8"
THIRD FLOOR
EL.= 111'-2 3/4"
SECOND FLOOR
EL.= 97'-5 3/8"
FIRST FLOOR
EL.= 83'-8"
'-6
8"
'-0
'-2
5 8"
OR
T. O. ROOF SLAB
EL.= 243'-5"
'-9
3 8"
'-6 5 8"
'-6
5 8"
'-6 5 8"
'-6
5 8"
'-6 5 8"
'-6
5 8
'-6
5 8
'-9
3 8"
EIGHTH FLOOR
EL.= 168'-11 7/8"
ROOF SLAB
EL.= 203'-7 3/4"
TENTH FLOOR
EL.= 192'-1 1/8"
NINTH FLOOR
EL.= 180'-6 1/2"
SEVENTH FLOOR
EL.= 157'-5 1/4"
SIXTH FLOOR
EL.= 145'-10 5/8"
FIFTH FLOOR
EL.= 134'-4"
FOURTH FLOOR
EL.= 122'-9 3/8"
THIRD FLOOR
EL.= 111'-2 3/4"
'-6
5 8"
'-6 5 8"
'-0
'-2 5 8"
ROOF SLAB & TANK ROO
ELEV MACHINE ROOM FL
'-9
3 8"
'-6
5 8"
'-6 5 8"
'-6
5 8"
'-6 5 8"
'-6
5 8"
'-6 5 8"
'-6
5 8"
'-6 5 8"
'-6
5 8"
'-0
'-9
3 8"
SECOND FLOOR
EL.= 97'-5 3/8"
FIRST FLOOR
EL.= 83'-8"
EIGHTH FLOOR
EL.= 168'-11 7/8"
ROOF SLAB
EL.= 203'-7 3/4"
TENTH FLOOR
EL.= 192'-1 1/8"
NINTH FLOOR
EL.= 180'-6 1/2"
SEVENTH FLOOR
EL.= 157'-5 1/4"
SIXTH FLOOR
EL.= 145'-10 5/8"
FIFTH FLOOR
EL.= 134'-4"
FOURTH FLOOR
EL.= 122'-9 3/8"
THIRD FLOOR
EL.= 111'-2 3/4"
ROOF SLAB & TANK ROOM FLOOR
EL.= 227'-2 3/8"
ELEV MACHINE ROOM FLOOR
EL.= 217'-2 3/8"
ROOF SLAB
EL.= 203'-7 3/4"
111.E102
111.E103
111.E102
111.E103
111.E101
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
8/
/2
:4 1:
P
M C
:\U se rs \w re ed
\D oc um en ts \E
_2 3-
3-
Q
-V A
M ilw au ke e- In st l L tn g
Pr ot
-W I_
R
_w re ed R
G 8R
E.
rv t
ES104
BUILDING 111, WESTERN & SOUTHERN
LIGHTNING PROTECTION ELEVATIONS
6 24WSR
INSTALL LIGHTNING
PROTECTION
CLEMENT J. ZABLOCKI VAMC
5000 WEST NATIONAL AVENUE
MILWAUKEE, WI 53295 AUGUST 20, 2024
100% CONSTRUCTION DOCUMENTS
695-22-10623-093
KTK
Scale: No Scale1 BUILDING 111, WESTERN LIGHTNING PROTECTION ELEVATION
Scale: No Scale2 BUILDING 111, SOUTHERN LIGHTNING PROTECTION ELEVATION
1 1
SEE 2/70.E102 FOR CONTINUATION
OF LIGHTNING PROTECTION
7 7
7 78
NOTE:
ACCESS STAIRWELL ROOF IS
APROXIMATELY 9FT ABOVE
BUILDING ROOF LEVEL.
NOTE:
BOND FALL PROTECTION EVERY 50'
AND AT BEGINNING AND END
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
PARTIALLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
8/
/2
:4 1:
P
M C
:\U se rs \w re ed
\D oc um en ts \E
_2 3-
3-
Q
-V A
M ilw au ke e- In st l L tn g
Pr ot
-W I_
R
_w re ed R
G 8R
E.
rv t
70.E101
BUILDING 70/E & K ROOF, LIGHTNING
PROTECTION PLAN, NEW WORK
7 24WSR
INSTALL LIGHTNING
PROTECTION
CLEMENT J. ZABLOCKI VAMC
5000 WEST NATIONAL AVENUE
MILWAUKEE, WI 53295 AUGUST 20, 2024
100% CONSTRUCTION DOCUMENTS
695-22-10623-093
KTK
Scale: 3/32" = 1'-0"1 BUILDING 70/E & K ROOF LIGHTNING PROTECTION PLAN, NEW WORK
1 CLASS 1 LIGHTNING CONDUCTORS FASTENED
USING ADHESIVE TYPE FASTENERS EVERY 3' OC.
2 BOND EXISTING HANDRAIL TO NEW LIGHTNING
PROTECTION SYSTEM.
3 EXISTING ROOF MOUNTED EXHAUST FANS.
MOUNT AIR TERMINAL TO TOP OF EXHAUST FAN
HOUSING.
4 PROVIDE DOWN CONDUCTOR ALONG EXTERIOR
FACADE OF BUILDING AND CONNECT TO NEW
PROVIDED GROUND ROD. DOWN CONDUCTORS
SHALL BE FASTENED TO BUILDING FAÇADE WITH
FASTENERS DESIGNED FOR BUILDING’S
EXTERIOR MATERIAL. BUILDING ELEVATION =
16FT.
5 PROVIDE DOWN CONDUCTOR ALONG EXTERIOR
FACADE OF BUILDING AND CONNECT TO NEW
PROVIDED GROUND ROD. DOWN CONDUCTORS
SHALL BE FASTENED TO BUILDING FAÇADE WITH
FASTENERS DESIGNED FOR BUILDING’S
EXTERIOR MATERIAL. BUILDING ELEVATION =
40FT.
6 PROVIDE DOWN CONDUCTOR ALONG EXTERIOR
FACADE OF BUILDING AND CONNECT TO NEW
PROVIDED GROUND ROD. DOWN CONDUCTORS
SHALL BE FASTENED TO BUILDING FAÇADE WITH
FASTENERS DESIGNED FOR BUILDING’S
EXTERIOR MATERIAL. BUILDING ELEVATION =
26FT.
7 DOWN CONDUCTOR TO BE PROTECTED TO A
HEIGHT OF 6’ FROM GRADE WITH RIGID
SCHEDULE 80 PVC ATTACHED TO BUILDING.
PAINT PVC IN A COMPLIMENTARY COLOR TO THE
EXISTING FACADE. PROVIDE PAINT SAMPLES TO
COR TO VERIFY FINAL COLOR DECISION.
8 INSTALL LIGHTNING CONDUCTOR ALONG
EXTERIOR TO BOND LOWER ROOF SECTION TO
UPPER ROOF SECTION.
NORTH
0 84 16
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
LIGHTNING PROTECTION SYSTEM SHALL BE
INSTALLED BY A CERTIFIED LIGHTNING
PROTECTION INSTALLATION CONTRACTOR.
THE FINAL INSTALLATION SHALL MEET NFPA 780
AND UL96A REQUIREMENTS FOR LIGHTNING
PROTECTION SYSTEMS.
ACTUAL JOB SITE CONDITIONS MAY
NECESSITATE SLIGHT ALTERNATIONS OF AIR
TERMINAL AND GROUND LOCATIONS. ANY
ALTERATIONS SHALL BE APPROVED BY THE
COR PRIOR TO THEIR EXECUTION.
AIR TERMINALS SHALL BE PLACED AROUND THE
ROOF PERIMETER OR RIDGE AT 20'-0" MAXIMUM
INTERVALS FOR 10" TO 24" AIR TERMINALS AND
EXTEND A MINIMUM OF 10” ABOVE THE OBJECT
OR AREA IT IS TO PROTECT.
AIR TERMINALS SHALL BE PLACED WITHIN 24"
FROM THE OUTSIDE EDGES OF THE OBJECT TO
BE PROTECTED.
MID-ROOF AIR TERMINALS ON FLAT OR GENTLY
SLOPING ROOFS SHALL BE INSTALLED AT
MAXIMUM 50'-0" INTERVALS.
ALL ROOF PROJECTIONS AND/OR OBJECTS
THAT ARE SUBJECT TO A DIRECT LIGHTNING
STRIKE SHALL BE PROVIDED WITH AIR
TERMINALS UNLESS THEY ARE LOCATED
WITHIN A ZONE OF PROTECTION.
METAL BODIES SITUATED WITHIN 6'-0" OF A
LIGHTNING PROTECTION CONDUCTOR SHALL
BE BONDED TO THE LIGHTNING PROTECTION
SYSTEM. HAND/GUARDRAILS SHALL BE
BONDED EVERY 50 LINEAR FEET AND AT
MINIMUM THE BEGINNING AND END OF THE
RAILING.
ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT AS REQUIRED.
ELECTRICAL CONTRACTOR TO DISPOSE OF
REMOVED ELECTRICAL EQUIPMENT.
AIR TERMINALS ARE TO BE MOUNTED TO THE
PARAPET WALL USING ADHESIVE MOUNTS.
CONTRACTOR WILL NOT USE SCREWS OR
ANCHORS INTO WALL TO PREVENT FROST
HEAVE OF HARDWARE AND CRACKING OF
PARAPET.
CONTINUATION OF LIGHTNING
PROTECTION FROM BUILDING 70/E. SEE
1/70.E101 FOR MORE INFORMATION.
SEE 1/70.E103 FOR CONTINUATION
OF LIGHTNING PROTECTION
5 5
22 55
NOTE:
BOND FALL PROTECTION EVERY 50'
AND AT BEGINNING AND END
NOTE:
BOND FALL PROTECTION EVERY 50'
AND AT BEGINNING AND END
Engineers Architects
# DEMO KEY NOTES:
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
PARTIALLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
8/
/2
:4 1:
P
M C
:\U se rs \w re ed
\D oc um en ts \E
_2 3-
3-
Q
-V A
M ilw au ke e- In st l L tn g
Pr ot
-W I_
R
_w re ed R
G 8R
E.
rv t
70.E102
BUILDING 70/B & A ROOF, LIGHTNING
PROTECTION PLANS
8 24WSR
INSTALL LIGHTNING
PROTECTION
CLEMENT J. ZABLOCKI VAMC
5000 WEST NATIONAL AVENUE
MILWAUKEE, WI 53295 AUGUST 20, 2024
100% CONSTRUCTION DOCUMENTS
695-22-10623-093
KTK
NORTH
0 84 16
NORTH
0 84 16
Scale: 3/32" = 1'-0"1 BUILDING 70/B & A ROOF, DEMOLITION PLAN
Scale: 3/32" = 1'-0"2 BUILDING 70/B & A ROOF LIGHTNING PROTECTION PLAN, NEW WORK
1 CLASS 1 LIGHTNING CONDUCTORS FASTENED
USING ADHESIVE TYPE FASTENERS EVERY 3' OC.
2 PROVIDE DOWN CONDUCTOR ALONG EXTERIOR
FACADE OF BUILDING AND CONNECT TO NEW
PROVIDED GROUND ROD. DOWN CONDUCTORS
SHALL BE FASTENED TO BUILDING FAÇADE WITH
FASTENERS DESIGNED FOR BUILDING’S
EXTERIOR MATERIAL. BUILDING ELEVATION =
20FT.
3 PROVIDE DOWN CONDUCTOR ALONG EXTERIOR
FACADE OF BUILDING AND CONNECT TO NEW
PROVIDED GROUND ROD. DOWN CONDUCTORS
SHALL BE FASTENED TO BUILDING FAÇADE WITH
FASTENERS DESIGNED FOR BUILDING’S
EXTERIOR MATERIAL. BUILDING ELEVATION =
36FT.
4 PROVIDE DOWN CONDUCTOR ALONG EXTERIOR
FACADE OF BUILDING AND CONNECT TO NEW
PROVIDED GROUND ROD. DOWN CONDUCTORS
SHALL BE FASTENED TO BUILDING FAÇADE WITH
FASTENERS DESIGNED FOR BUILDING’S
EXTERIOR MATERIAL. BUILDING ELEVATION =
30FT.
5 DOWN CONDUCTOR TO BE PROTECTED TO A
HEIGHT OF 6’ FROM GRADE WITH RIGID
SCHEDULE 80 PVC ATTACHED TO BUILDING.
PAINT PVC IN A COMPLIMENTARY COLOR TO THE
EXISTING FACADE. PROVIDE PAINT SAMPLES TO
COR TO VERIFY FINAL COLOR DECISION.
1 EXISTING LIGHTNING PROTECTION CONDUCTOR
TO BE DEMOLISHED. TYPICAL ALL DASHED LINES
THIS DEMOLITION ROOF PLAN.
2 EXISTING LIGHTNING PROTECTION GROUND ROD
AND DOWN CONDUCTOR TO BE DEMOLISHED.
TYPICAL ALL GROUND ROD SYMBOLS THIS
DEMOLITION ROOF PLAN.
3 EXISTING LIGHTNING PROTECTION AIR TERMINAL
TO BE DEMOLISHED. TYPICAL ALL AIR TERMINALS
THIS DEMOLITION ROOF PLAN.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
LIGHTNING PROTECTION SYSTEM SHALL BE
INSTALLED BY A CERTIFIED LIGHTNING
PROTECTION INSTALLATION CONTRACTOR.
THE FINAL INSTALLATION SHALL MEET NFPA 780
AND UL96A REQUIREMENTS FOR LIGHTNING
PROTECTION SYSTEMS.
ACTUAL JOB SITE CONDITIONS MAY
NECESSITATE SLIGHT ALTERNATIONS OF AIR
TERMINAL AND GROUND LOCATIONS. ANY
ALTERATIONS SHALL BE APPROVED BY THE
COR PRIOR TO THEIR EXECUTION.
AIR TERMINALS SHALL BE PLACED AROUND THE
ROOF PERIMETER OR RIDGE AT 20'-0" MAXIMUM
INTERVALS FOR 10" TO 24" AIR TERMINALS AND
EXTEND A MINIMUM OF 10” ABOVE THE OBJECT
OR AREA IT IS TO PROTECT.
AIR TERMINALS SHALL BE PLACED WITHIN 24"
FROM THE OUTSIDE EDGES OF THE OBJECT TO
BE PROTECTED.
MID-ROOF AIR TERMINALS ON FLAT OR GENTLY
SLOPING ROOFS SHALL BE INSTALLED AT
MAXIMUM 50'-0" INTERVALS.
ALL ROOF PROJECTIONS AND/OR OBJECTS
THAT ARE SUBJECT TO A DIRECT LIGHTNING
STRIKE SHALL BE PROVIDED WITH AIR
TERMINALS UNLESS THEY ARE LOCATED
WITHIN A ZONE OF PROTECTION.
METAL BODIES SITUATED WITHIN 6'-0" OF A
LIGHTNING PROTECTION CONDUCTOR SHALL
BE BONDED TO THE LIGHTNING PROTECTION
SYSTEM. HAND/GUARDRAILS SHALL BE
BONDED EVERY 50 LINEAR FEET AND AT
MINIMUM THE BEGINNING AND END OF THE
RAILING.
ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT AS REQUIRED.
ELECTRICAL CONTRACTOR TO DISPOSE OF
REMOVED ELECTRICAL EQUIPMENT.
DEVICES AND CONDUCTORS INDICATED WITH
HIDDEN/DASHED LINES ARE TO BE REMOVED,
UNLESS NOTED OTHERWISE. SEE ELECTRICAL
SYMBOLS LEGEND ON E-001 FOR REFERENCE.
AIR TERMINALS ARE TO BE MOUNTED TO THE
PARAPET WALL USING ADHESIVE MOUNTS.
CONTRACTOR WILL NOT USE SCREWS OR
ANCHORS INTO WALL TO PREVENT FROST
HEAVE OF HARDWARE AND CRACKING OF
PARAPET.
1 1
CONTINUATION OF LIGHTNING
PROTECTION FROM BUILDING 70/B. SEE
2/70.E102 FOR MORE INFORMATION.
SEE 1/70.E104 FOR
CONTINUATION OF LIGHTNING
PROTECTION
6 6 6
NOTE:
BOND FALL PROTECTION EVERY 50'
AND AT BEGINNING AND END
NOTE:
ACCESS STAIRWELL ROOF IS
APROXIMATELY 9FT ABOVE
BUILDING ROOF LEVEL.
NOTE:
BOND FALL PROTECTION EVERY 50'
AND AT BEGINNING AND END
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
PARTIALLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
8/
/2
:4 1:
P
M C
:\U se rs \w re ed
\D oc um en ts \E
_2 3-
3-
Q
-V A
M ilw au ke e- In st l L tn g
Pr ot
-W I_
R
_w re ed R
G 8R
E.
rv t
70.E103
BUILDING 70/C ROOF, LIGHTNING
PROTECTION PLAN, NEW WORK
9 24WSR
INSTALL LIGHTNING
PROTECTION
CLEMENT J. ZABLOCKI VAMC
5000 WEST NATIONAL AVENUE
MILWAUKEE, WI 53295 AUGUST 20, 2024
100% CONSTRUCTION DOCUMENTS
695-22-10623-093
KTK
NORTH
0 84 16
Scale: 3/32" = 1'-0"1 BUILDING 70/C ROOF LIGHTNING PROTECTION PLAN, NEW WORK
1 CLASS 1 LIGHTNING CONDUCTORS FASTENED
USING ADHESIVE TYPE FASTENERS EVERY 3' OC.
2 MOUNT LIGHTNING PROTECTION AIR TERMIAL TO
OUTSIDE CAP ON TOP OF CHIMNEY STACK. TOP
OF CHIMNEY STACK IS 10’ ABOVE ROOF LINE.
3 MOUNT LIGHTNING PROTECTION AIR TERMIALS
TO TOP OF THE OUTSIDE FACE OF THE
CONDENSER TO PREVENT BUILD UP OF COPPER
PATINA ON TOP OF UNIT. TYPICAL ALL TERMINALS
FOR THESE UNITS.
4 PROVIDE DOWN CONDUCTOR ALONG EXTERIOR
FACADE OF BUILDING AND CONNECT TO NEW
PROVIDED GROUND ROD. DOWN CONDUCTORS
SHALL BE FASTENED TO BUILDING FAÇADE WITH
FASTENERS DESIGNED FOR BUILDING’S
EXTERIOR MATERIAL. BUILDING ELEVATION =
26FT.
5 PROVIDE DOWN CONDUCTOR ALONG EXTERIOR
FACADE OF BUILDING AND CONNECT TO NEW
PROVIDED GROUND ROD. DOWN CONDUCTORS
SHALL BE FASTENED TO BUILDING FAÇADE WITH
FASTENERS DESIGNED FOR BUILDING’S
EXTERIOR MATERIAL. BUILDING ELEVATION =
40FT.
6 DOWN CONDUCTOR TO BE PROTECTED TO A
HEIGHT OF 6’ FROM GRADE WITH RIGID
SCHEDULE 80 PVC ATTACHED TO BUILDING.
PAINT PVC IN A COMPLIMENTARY COLOR TO THE
EXISTING FACADE. PROVIDE PAINT SAMPLES TO
COR TO VERIFY FINAL COLOR DECISION.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
LIGHTNING PROTECTION SYSTEM SHALL BE
INSTALLED BY A CERTIFIED LIGHTNING
PROTECTION INSTALLATION CONTRACTOR.
THE FINAL INSTALLATION SHALL MEET NFPA 780
AND UL96A REQUIREMENTS FOR LIGHTNING
PROTECTION SYSTEMS.
ACTUAL JOB SITE CONDITIONS MAY
NECESSITATE SLIGHT ALTERNATIONS OF AIR
TERMINAL AND GROUND LOCATIONS. ANY
ALTERATIONS SHALL BE APPROVED BY THE
COR PRIOR TO THEIR EXECUTION.
AIR TERMINALS SHALL BE PLACED AROUND THE
ROOF PERIMETER OR RIDGE AT 20'-0" MAXIMUM
INTERVALS FOR 10" TO 24" AIR TERMINALS AND
EXTEND A MINIMUM OF 10” ABOVE THE OBJECT
OR AREA IT IS TO PROTECT.
AIR TERMINALS SHALL BE PLACED WITHIN 24"
FROM THE OUTSIDE EDGES OF THE OBJECT TO
BE PROTECTED.
MID-ROOF AIR TERMINALS ON FLAT OR GENTLY
SLOPING ROOFS SHALL BE INSTALLED AT
MAXIMUM 50'-0" INTERVALS.
ALL ROOF PROJECTIONS AND/OR OBJECTS
THAT ARE SUBJECT TO A DIRECT LIGHTNING
STRIKE SHALL BE PROVIDED WITH AIR
TERMINALS UNLESS THEY ARE LOCATED
WITHIN A ZONE OF PROTECTION.
METAL BODIES SITUATED WITHIN 6'-0" OF A
LIGHTNING PROTECTION CONDUCTOR SHALL
BE BONDED TO THE LIGHTNING PROTECTION
SYSTEM. HAND/GUARDRAILS SHALL BE
BONDED EVERY 50 LINEAR FEET AND AT
MINIMUM THE BEGINNING AND END OF THE
RAILING.
ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT AS REQUIRED.
ELECTRICAL CONTRACTOR TO DISPOSE OF
REMOVED ELECTRICAL EQUIPMENT.
AIR TERMINALS ARE TO BE MOUNTED TO THE
PARAPET WALL USING ADHESIVE MOUNTS.
CONTRACTOR WILL NOT USE SCREWS OR
ANCHORS INTO WALL TO PREVENT FROST
HEAVE OF HARDWARE AND CRACKING OF
PARAPET.
1 1
CONTINUATION OF LIGHTNING
PROTECTION FROM BUILDING 70/C. SEE
1/70.E103 FOR MORE INFORMATION.
5 6
6 6 6
NOTE:
ACCESS STAIRWELL ROOF IS
APROXIMATELY 9FT ABOVE
BUILDING ROOF LEVEL.
NOTE:
TOP OF CHIMNEY STACK IS
APROXIMATELY 11FT ABOVE
BUILDING ROOF LEVEL.
NOTE:
BOND FALL PROTECTION EVERY 50'
AND AT BEGINNING AND END
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
PARTIALLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
8/
/2
:4 1:
P
M C
:\U se rs \w re ed
\D oc um en ts \E
_2 3-
3-
Q
-V A
M ilw au ke e- In st l L tn g
Pr ot
-W I_
R
_w re ed R
G 8R
E.
rv t
70.E104
BUILDING 70/D ROOF, LIGHTNING
PROTECTION PLAN, NEW WORK
10 24WSR
INSTALL LIGHTNING
PROTECTION
CLEMENT J. ZABLOCKI VAMC
5000 WEST NATIONAL AVENUE
MILWAUKEE, WI 53295 AUGUST 20, 2024
100% CONSTRUCTION DOCUMENTS
695-22-10623-093
KTK
NORTH
0 84 16
1 CLASS 1 LIGHTNING CONDUCTORS FASTENED
USING ADHESIVE TYPE FASTENERS EVERY 3' OC.
2 MOUNT LIGHTNING PROTECTION AIR TERMIAL TO
OUTSIDE CAP ON TOP OF CHIMNEY STACK. TOP
OF CHIMNEY STACK IS 11’ ABOVE ROOF LINE.
3 MOUNT LIGHTNING PROTECTION AIR TERMIAL TO
TOP OF THE OUTSIDE FACE OF THE CONDENSER
TO PREVENT BUILD UP OF COPPER PATINA ON
TOP OF UNIT.
4 EXISTING ROOF MOUNTED RF ANTENNA. BOND TO
EXISTING ANTENNA BASE. COORDINATE WORK
WITH COR TO PREVENT EXCESSIVE RF/EMF
EMISSIONS.
5 PROVIDE DOWN CONDUCTOR ALONG EXTERIOR
FACADE OF BUILDING AND CONNECT TO NEW
PROVIDED GROUND ROD. DOWN CONDUCTORS
SHALL BE FASTENED TO BUILDING FAÇADE WITH
FASTENERS DESIGNED FOR BUILDING’S
EXTERIOR MATERIAL. BUILDING ELEVATION =
40FT.
6 DOWN CONDUCTOR TO BE PROTECTED TO A
HEIGHT OF 6’ FROM GRADE WITH RIGID
SCHEDULE 80 PVC ATTACHED TO BUILDING.
PAINT PVC IN A COMPLIMENTARY COLOR TO THE
EXISTING FACADE. PROVIDE PAINT SAMPLES TO
COR TO VERIFY FINAL COLOR DECISION.
Scale: 3/32" = 1'-0"1 BUILDING 70/D ROOF LIGHTNING PROTECTION PLAN, NEW WORK
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
LIGHTNING PROTECTION SYSTEM SHALL BE
INSTALLED BY A CERTIFIED LIGHTNING
PROTECTION INSTALLATION CONTRACTOR.
THE FINAL INSTALLATION SHALL MEET NFPA 780
AND UL96A REQUIREMENTS FOR LIGHTNING
PROTECTION SYSTEMS.
ACTUAL JOB SITE CONDITIONS MAY
NECESSITATE SLIGHT ALTERNATIONS OF AIR
TERMINAL AND GROUND LOCATIONS. ANY
ALTERATIONS SHALL BE APPROVED BY THE
COR PRIOR TO THEIR EXECUTION.
AIR TERMINALS SHALL BE PLACED AROUND THE
ROOF PERIMETER OR RIDGE AT 20'-0" MAXIMUM
INTERVALS FOR 10" TO 24" AIR TERMINALS AND
EXTEND A MINIMUM OF 10” ABOVE THE OBJECT
OR AREA IT IS TO PROTECT.
AIR TERMINALS SHALL BE PLACED WITHIN 24"
FROM THE OUTSIDE EDGES OF THE OBJECT TO
BE PROTECTED.
MID-ROOF AIR TERMINALS ON FLAT OR GENTLY
SLOPING ROOFS SHALL BE INSTALLED AT
MAXIMUM 50'-0" INTERVALS.
ALL ROOF PROJECTIONS AND/OR OBJECTS
THAT ARE SUBJECT TO A DIRECT LIGHTNING
STRIKE SHALL BE PROVIDED WITH AIR
TERMINALS UNLESS THEY ARE LOCATED
WITHIN A ZONE OF PROTECTION.
METAL BODIES SITUATED WITHIN 6'-0" OF A
LIGHTNING PROTECTION CONDUCTOR SHALL
BE BONDED TO THE LIGHTNING PROTECTION
SYSTEM. HAND/GUARDRAILS SHALL BE
BONDED EVERY 50 LINEAR FEET AND AT
MINIMUM THE BEGINNING AND END OF THE
RAILING.
ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT AS REQUIRED.
ELECTRICAL CONTRACTOR TO DISPOSE OF
REMOVED ELECTRICAL EQUIPMENT.
AIR TERMINALS ARE TO BE MOUNTED TO THE
PARAPET WALL USING ADHESIVE MOUNTS.
CONTRACTOR WILL NOT USE SCREWS OR
ANCHORS INTO WALL TO PREVENT FROST
HEAVE OF HARDWARE AND CRACKING OF
PARAPET.
2 3
2 3
1 1
3 3
5 NOTE:
COORDINATE INSTALLATION WITH
GROUND FLOOR MAN DOOR
7 7
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
91 & 102
8/
/2
:4 1:
P
M C
:\U se rs \w re ed
\D oc um en ts \E
_2 3-
3-
Q
-V A
M ilw au ke e- In st l L tn g
Pr ot
-W I_
R
_w re ed R
G 8R
E.
rv t
102.E101
BUILDING 91 & 102 ROOF, LIGHTNING
PROTECTION PLAN, NEW WORK
11 24WSR
INSTALL LIGHTNING
PROTECTION
CLEMENT J. ZABLOCKI VAMC
5000 WEST NATIONAL AVENUE
MILWAUKEE, WI 53295 AUGUST 20, 2024
100% CONSTRUCTION DOCUMENTS
695-22-10623-093
KTK
N O
R
TH0 2 4 8
Scale: 1/4" = 1'-0"
BUILDING 91 ROOF
LIGHTNING PROTECTION
PLAN, NEW WORK2 Scale: 3/32" = 1'-0"1 BUILDING 102 ROOF LIGHTNING PROTECTION PLAN, NEW WORK (FULLY SPRINKLERED)
NORTH
0 84 16
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
LIGHTNING PROTECTION SYSTEM SHALL BE
INSTALLED BY A CERTIFIED LIGHTNING
PROTECTION INSTALLATION CONTRACTOR.
THE FINAL INSTALLATION SHALL MEET NFPA 780
AND UL96A REQUIREMENTS FOR LIGHTNING
PROTECTION SYSTEMS.
ACTUAL JOB SITE CONDITIONS MAY
NECESSITATE SLIGHT ALTERNATIONS OF AIR
TERMINAL AND GROUND LOCATIONS. ANY
ALTERATIONS SHALL BE APPROVED BY THE
COR PRIOR TO THEIR EXECUTION.
AIR TERMINALS SHALL BE PLACED AROUND THE
ROOF PERIMETER OR RIDGE AT 20'-0" MAXIMUM
INTERVALS FOR 10" TO 24" AIR TERMINALS AND
EXTEND A MINIMUM OF 10” ABOVE THE OBJECT
OR AREA IT IS TO PROTECT.
AIR TERMINALS SHALL BE PLACED WITHIN 24"
FROM THE OUTSIDE EDGES OF THE OBJECT TO
BE PROTECTED.
MID-ROOF AIR TERMINALS ON FLAT OR GENTLY
SLOPING ROOFS SHALL BE INSTALLED AT
MAXIMUM 50'-0" INTERVALS.
ALL ROOF PROJECTIONS AND/OR OBJECTS
THAT ARE SUBJECT TO A DIRECT LIGHTNING
STRIKE SHALL BE PROVIDED WITH AIR
TERMINALS UNLESS THEY ARE LOCATED
WITHIN A ZONE OF PROTECTION.
METAL BODIES SITUATED WITHIN 6'-0" OF A
LIGHTNING PROTECTION CONDUCTOR SHALL
BE BONDED TO THE LIGHTNING PROTECTION
SYSTEM. HAND/GUARDRAILS SHALL BE
BONDED EVERY 50 LINEAR FEET AND AT
MINIMUM THE BEGINNING AND END OF THE
RAILING.
ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT AS REQUIRED.
ELECTRICAL CONTRACTOR TO DISPOSE OF
REMOVED ELECTRICAL EQUIPMENT.
AIR TERMINALS ARE TO BE MOUNTED TO THE
PARAPET WALL USING ADHESIVE MOUNTS.
CONTRACTOR WILL NOT USE SCREWS OR
ANCHORS INTO WALL TO PREVENT FROST
HEAVE OF HARDWARE AND CRACKING OF
PARAPET.
1 CLASS 1 LIGHTNING CONDUCTORS FASTENED
USING ADHESIVE TYPE FASTENERS EVERY 3' OC.
2 PROVIDE DOWN CONDUCTOR ALONG EXTERIOR
FACADE OF BUILDING AND CONNECT TO NEW
PROVIDED GROUND ROD. DOWN CONDUCTORS
SHALL BE FASTENED TO BUILDING FAÇADE WITH
FASTENERS DESIGNED FOR BUILDING’S
EXTERIOR MATERIAL.
3 DOWN CONDUCTOR TO BE PROTECTED TO A
HEIGHT OF 6’ FROM GRADE WITH RIGID
SCHEDULE 80 PVC ATTACHED TO BUILDING.
PAINT PVC IN A COMPLIMENTARY COLOR TO THE
EXISTING FACADE. PROVIDE PAINT SAMPLES TO
COR TO VERIFY FINAL COLOR DECISION.
4 CONNECT LPS CONDUCTOR TO GROUNDING BUS
IN SWITCHGEAR ROOM. SEE DETAIL 6/E-502 FOR
MORE INFORMATION.
5 PROVIDE DOWN CONDUCTOR ALONG EXTERIOR
FACADE OF BUILDING AND CONNECT TO NEW
PROVIDED GROUND ROD. CUT HARDSCAPE TO
CREATE TRENCH FOR DOWN CONDUCTOR AND
GROUND ROD. PROVIDE GROUND TESTING WELL
FOR FUTURE INSPECTION. CUT AREA SHALL BE
REPAIRED WITH LIKE MATERIALS TO MATCH
EXISTING. GROUND WELL SHALL BE TIER 15
RATED.
6 ROOF EAVE OF BUILDING 91 IS APPROXIMATELY 8
FEET 6 INCHES ABOVE GROUND.
7 ROOF LEVEL OF BUILDING 102 LOADING BAYS IS
APPROXIMATELY 20 FEET ABOVE GROUND.
8 THE MAIN ROOF OF BUILDING 102 IS
APPROXIMATELY 25 FEET ABOVE GROUND.
9 THE UPPER SECTION OF BUILDING 102 IS
APPROXIMATELY 35 FEET ABOVE GROUND.
2 1
SEE SHEET 111.E102 FOR CONTINUATION OF WORK
3 3
5 5
5 5
5 5 5
5 5
5 5
Engineers Architects
# DEMO KEY NOTES:
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
FULLY SPRINKLERED
8/
/2
:4 1:
P
M C
:\U se rs \w re ed
\D oc um en ts \E
_2 3-
3-
Q
-V A
M ilw au ke e- In st l L tn g
Pr ot
-W I_
R
_w re ed R
G 8R
E.
rv t
111.E101
BUILDING 111 UPPER A WING ROOF,
LIGHTNING PROTECTION PLANS
12 24WSR
INSTALL LIGHTNING
PROTECTION
CLEMENT J. ZABLOCKI VAMC
5000 WEST NATIONAL AVENUE
MILWAUKEE, WI 53295 AUGUST 20, 2024
100% CONSTRUCTION DOCUMENTS
695-22-10623-093
KTK
NORTH
0 84 16
Scale: 3/32" = 1'-0"1 BUILDING 111 UPPER A WING ROOF, DEMOLITION PLAN
Scale: 3/32" = 1'-0"2 BUILDING 111 UPPER A WING ROOF LIGHTNING PROTECTION PLAN, NEW WORK
NORTH
0 84 16
1 CLASS 2 LIGHTNING CONDUCTORS FASTENED
USING ADHESIVE TYPE FASTENERS EVERY 3' OC.
2 TIE IN DOWN CONDUCTORS FROM 111 UPPER B
WING INTO A WING LIGHTNING PROTECTION
SYSTEM. CONTRACTOR SHALL PERFORM A
CONTINUITY TEST ON THE EXISTING DOWN
CONDUCTOR PRIOR TO INSTALLATION, AND ON
THE CONNECTION OF THE NEW CONDUCTOR TO
THE EXISTING CONDUCTOR AFTER INSTALLATION
TO ENSURE PERFORMANCE.
3 EXISTING DOWN CONDUCTOR THROUGH ROOF
PENETRATION TO BE REUSED. TIE IN EXISTING
DOWN CONDUCTOR TO NEW CONDUCTOR.
CONTRACTOR SHALL PERFORM A CONTINUITY
TEST ON THE EXISTING THRU-ROOF CONDUCTOR
PRIOR TO INSTALLATION, AND ON THE
CONNECTION OF THE NEW CONDUCTOR TO THE
EXISTING CONDUCTOR AFTER INSTALLATION TO
ENSURE PERFORMANCE.
4 BOND EXISTING ANTENNA BASE TO LPS
5 BOND TO EXISTING FALL PROTECTION EVERY 50',
THE BEGINNING AND END OF THE FALL
PROTECTION, AND AT EACH CHANGE IN
DIRECTION.
6 BOND TO EXISTING CABLE TRAY.
1 EXISTING LIGHTNING PROTECTION CONDUCTOR
TO BE DEMOLISHED. TYPICAL ALL DASHED LINES
THIS DEMOLITION ROOF PLAN.
2 EXISTING LIGHTNING PROTECTION AIR TERMINAL
TO BE DEMOLISHED. TYPICAL ALL AIR TERMINALS
THIS DEMOLITION ROOF PLAN.
3 EXISTING CONDUCTOR BOND TO BE
DEMOLISHED. TYPICAL ALL CONDUCTOR BONDS
THIS DEMOLITION ROOF PLAN.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
LIGHTNING PROTECTION SYSTEM SHALL BE
INSTALLED BY A CERTIFIED LIGHTNING
PROTECTION INSTALLATION CONTRACTOR.
THE FINAL INSTALLATION SHALL MEET NFPA 780
AND UL96A REQUIREMENTS FOR LIGHTNING
PROTECTION SYSTEMS.
ACTUAL JOB SITE CONDITIONS MAY
NECESSITATE SLIGHT ALTERNATIONS OF AIR
TERMINAL AND GROUND LOCATIONS. ANY
ALTERATIONS SHALL BE APPROVED BY THE
COR PRIOR TO THEIR EXECUTION.
AIR TERMINALS SHALL BE PLACED AROUND THE
ROOF PERIMETER OR RIDGE AT 20'-0" MAXIMUM
INTERVALS FOR 10" TO 24" AIR TERMINALS AND
EXTEND A MINIMUM OF 10” ABOVE THE OBJECT
OR AREA IT IS TO PROTECT.
AIR TERMINALS SHALL BE PLACED WITHIN 24"
FROM THE OUTSIDE EDGES OF THE OBJECT TO
BE PROTECTED.
MID-ROOF AIR TERMINALS ON FLAT OR GENTLY
SLOPING ROOFS SHALL BE INSTALLED AT
MAXIMUM 50'-0" INTERVALS.
ALL ROOF PROJECTIONS AND/OR OBJECTS
THAT ARE SUBJECT TO A DIRECT LIGHTNING
STRIKE SHALL BE PROVIDED WITH AIR
TERMINALS UNLESS THEY ARE LOCATED
WITHIN A ZONE OF PROTECTION.
METAL BODIES SITUATED WITHIN 6'-0" OF A
LIGHTNING PROTECTION CONDUCTOR SHALL
BE BONDED TO THE LIGHTNING PROTECTION
SYSTEM. HAND/GUARDRAILS SHALL BE
BONDED EVERY 50 LINEAR FEET AND AT
MINIMUM THE BEGINNING AND END OF THE
RAILING.
ELECTRICAL CONTRACTOR SHALL FOLLOW
SITE LOCK-OUT/TAG-OUT GUIDELINES TO
DEENERGIZE EQUIPMENT AS REQUIRED.
ELECTRICAL CONTRACTOR TO DISPOSE OF
REMOVED ELECTRICAL EQUIPMENT.
DEVICES AND CONDUCTORS INDICATED WITH
HIDDEN/DASHED LINES ARE TO BE REMOVED,
UNLESS NOTED OTHERWISE. SEE ELECTRICAL
SYMBOLS LEGEND ON E-001 FOR REFERENCE.
AIR TERMINALS ARE TO BE MOUNTED TO THE
PARAPET WALL USING ADHESIVE MOUNTS.
CONTRACTOR WILL NOT USE SCREWS OR
ANCHORS INTO WALL TO PREVENT FROST
HEAVE OF HARDWARE AND CRACKING OF
PARAPET.