S02 - 528A6-19-614 Upgrade Ventilation B76 Drawings.pdf
PDF 20 MB Posted
- Attached to
- Z1DA--528A6-17-627 UPGRADE VENTILATION B76 Federal contract opportunity
- Solicitation number
- 36C24220B0064
About this file
This notice summarizes a federal contract opportunity to upgrade ventilation systems in Building 76 at the Bath VA Medical Center. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2 will issue solicitation number 36C24220B0064 on or around October 7, 2020 seeking bids for project number 528A6-17-627. The project scope involves installing a new central air distribution system on the fourth and portions of the fifth floors, constructing a chase way for future ductwork to the third and second floors, and cross connecting certain piping systems. The NAICS code is 238220 for plumbing, heating, and air-conditioning contractors and the small business size standard is $16.5 million. The estimated cost range is $1 million to $5 million. A pre-bid site visit will be scheduled and noted in the solicitation. Bids must include a 20% bid bond and performance and payment bonds will be required from the successful bidder. This procurement is reserved exclusively for Service-Disabled Veteran-Owned Small Businesses.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24220B0064 0004.docx | DOCX document | |
| 528A6-19-614 Upgrade Ventilation B76 Drawings - Revised.zip | ZIP file | |
| 20201130 PreBid RFI Log Response to Contractors Updated.xlsx | XLSX spreadsheet | |
| 36C24220B0064 0003.docx | DOCX document | |
| 528A6-19-614 Upgrade Ventilation B76 Revised Specifications.pdf | ||
| S06 - PreBid RFI Log Response to Contractors.xlsx | XLSX spreadsheet | |
| 36C24220B0064 0002.docx | DOCX document | |
| S06 - 9550-A VA Bath Healthcare Center Additional Limited ACM Survey Revised 6-10-2020_opt.pdf | ||
| 36C24220B0064 0001.docx | DOCX document | |
| S04 - Pre-Bid Attendance Sheet.pdf | ||
| 36C24220B0064_1.docx | DOCX document | |
| S02 - 528A6-19-614 Upgrade Ventilation B76 Specifications.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION, B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
T-101
JWE MPL
GENERAL
T-101 COVER SHEET & DRAWING INDEX
G-101 CONSTRUCTION PHASING PLAN
HAZ-MAT
H-101 HAZARDOUS MATERIALS - THIRD FLOOR SOUTH
H-102
HAZARDOUS MATERIALS - FOURTH FLOOR
SOUTH
H-103
HAZARDOUS MATERIALS - FOURTH FLOOR
NORTH
H-104 HAZARDOUS MATERIALS - SIXTH FLOOR SOUTH
H-105 HAZARDOUS MATERIALS - SIXTH FLOOR NORTH
H-106 HAZARDOUS MATERIALS - ATTIC
STRUCTURAL
S-100
THIRD FLOOR STRUCTURAL DEMOLITION AND
FRAMING PLAN
S-101
FOURTH FLOOR STRUCTURAL DEMOLITION AND
FRAMING PLAN
S-102
FIFTH FLOOR STRUCTURAL DEMOLITION AND
FRAMING PLAN
S-103
SIXTH FLOOR STRUCTURAL DEMOLITION AND
FRAMING PLAN
S-104
ATTIC FLOOR STRUCTURAL DEMOLITION AND
FRAMING PLAN
S-501
SECTIONS, DETAILS & GENERAL NOTES
ARCHITECTURAL
AD-101
ARCHITECTURAL DEMOLITION PLAN - SECOND
FLOOR SOUTH
AD-102
ARCHITECTURAL DEMOLITION PLAN - THIRD
FLOOR SOUTH
AD-103
ARCHITECTURAL DEMOLITION PLAN - FOURTH
FLOOR SOUTH
AD-104
ARCHITECTURAL DEMOLITION PLAN - FIFTH
FLOOR SOUTH
AD-105
ARCHITECTURAL DEMOLITION PLAN - FIFTH
FLOOR NORTH
AD-106
ARCHITECTURAL DEMOLITION PLAN - SIXTH
FLOOR SOUTH
AD-107
ARCHITECTURAL DEMOLITION PLAN - SIXTH
FLOOR NORTH
AD-108 ARCHITECTURAL DEMOLITION PLAN - ATTIC
A-101
ARCHITECTURAL CONSTRUCTION - SECOND
FLOOR SOUTH
A-102
ARCHITECTURAL CONSTRUCTION - THIRD FLOOR
SOUTH
A-103
ARCHITECTURAL CONSTRUCTION - FOURTH
FLOOR SOUTH
A-104
ARCHITECTURAL CONSTRUCTION - FIFTH FLOOR
SOUTH
A-105
ARCHITECTURAL CONSTRUCTION - FIFTH FLOOR
NORTH
A-106
ARCHITECTURAL CONSTRUCTION - SIXTH FLOOR
NORTH
A-107
ARCHITECTURAL CONSTRUCTION - SIXTH FLOOR
SOUTH
A-108 ARCHITECTURAL CONSTRUCTION - ATTIC
A-109
ARCHITECTURAL CONSTRUCTION RCP - FOURTH
FLOOR SOUTH
A-110
ARCHITECTURAL CONSTRUCTION RCP - FOURTH
FLOOR NORTH
A-111
ARCHITECTURAL CONSTRUCTION RCP - FIFTH
FLOOR NORTH
MECHANICAL
M-001 MECHANICAL GENERAL NOTES AND SYMBOLS
MD100
MECHANICAL DEMOLITION PLAN - GROUND
FLOOR
MD101
MECHANICAL DEMOLITION PLAN - FOURTH
FLOOR SOUTH
MD102
MECHANICAL DEMOLITION PLAN - FOURTH
FLOOR NORTH
MD103
MECHANICAL DEMOLITION PLAN - FIFTH FLOOR
NORTH
MD104
MECHANICAL DEMOLITION PLAN - SIXTH FLOOR
SOUTH
MD105 MECHANICAL DEMOLITION PLAN - ATTIC
MH101
MECHANICAL DUCTWORK PLAN - FOURTH FLOOR
SOUTH
MH102
MECHANICAL DUCTWORK PLAN - FOURTH FLOOR
NORTH
MH103
MECHANICAL DUCTWORK PLAN - FIFTH FLOOR
NORTH
MH104 MECHANICAL PLAN - SIXTH FLOOR SOUTH
MH105
MECHANICAL DUCTWORK PLAN - SIXTH FLOOR
NORTH
MH106 MECHANICAL PLAN - ATTIC
MP101
MECHANICAL PIPING PLAN - FOURTH FLOOR
SOUTH
MP102
MECHANICAL PIPING PLAN - FOURTH FLOOR
NORTH
MP103 MECHANICAL PIPING PLAN - FIFTH FLOOR NORTH
MP104 MECHANICAL PIPING PLAN - SIXTH FLOOR NORTH
MP105 MECHANICAL PIPING PLAN - ATTIC
M-301 MECHANICAL DUCTWORK RISER DIAGRAM
M-302 MECHANICAL PIPING RISER DIAGRAM
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES
M-602 MECHANICAL SCHEDULES
M-603 MECHANICAL SCHEDULES
M-701
MECHANICAL CONTROLS SCHEMATICS & POINTS
LIST
M-702
MECHANICAL CONTROLS SCHEMATICS & POINTS
LIST
ELECTRICAL
E-001
ELECTRICAL NOTES, SYMBOLS, ABBREVIATIONS,
AND SCHEDULES
ED-101 ELECTRICAL LIGHTING DEMOLITION PLANS
ED-102 ELECTRICAL LIGHTING DEMOLITION PLANS
E-101 ELECTRICAL FLOOR PLANS
E-102 ELECTRICAL FLOOR PLANS
E-103 ELECTRICAL LIGHTING PLANS
E-104 ELECTRICAL LIGHTING PLANS
E-105 ELECTRICAL LIGHTING PLANS
COVER SHEET
BATH VAMC
AutoCAD SHX Text
DRAWING INDEX
AutoCAD SHX Text DEPARTMENT OF VETERANS AFFAIRS PROJECT NO. 528A6-17-627 BUILDING 76 BATH VAMC, BATH, NEW YORK
AutoCAD SHX Text
SITE PLAN
AutoCAD SHX Text
SITE LOCATION
AutoCAD SHX Text
UPGRADE VENTILATION
AutoCAD SHX Text B-76
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION, B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
G-101
JWE MPL
CONSTRUCTION PHASING PLAN
336 SF
409 SF
FOURTH FLOOR
FIFTH FLOOR
SIXTH FLOOR
6HA3-76
179 SF
21 SF
607A
180 SF
186 SF
183 SF
195 SF
6HA1-76
498 SF
6HA4-76
115 SF
85 SF
611A
615A
13 SF 19 SF
302 SF
224 SF
219 SF
616A
6HA2-76
272 SF
80 SF
617A
665 SF
186 SF
22 SF
OCCUPIABLE SPACE (SF)
SOUTH
NA
NA
CENTER
NA
NORTH
NA
37 SF
623A
170 SF
252 SF
185 SF
605A 184 SF
177 SF
66 SF
189 SF
147 SF
250 SF 624A
23 SF
362 SF
366 SF
229 SF
125 SF
109 SF
SIXTH FLOOR SWING SPACE
245 SF
211 SF
143 SF
106 SF
5HA7-76
117 SF
51 SF
472 SF
71 SF
117 SF
242 SF
244 SF
105 SF
111 SF
813 SF
108 SF
107 SF
115 SF
116 SF
434A
417A
115 SF
425A
116 SF
92 SF
97 SF
351 SF
PHASE 2
83 SF
374 SF
PHASE 1
FIFTH FLOOR PROJECT AREA
132 SF
439B
431A
38 SF
427A
116 SF
120 SF
414B
45 SF
81 SF
138 SF
25 SF
109 SF
432A
240 SF
178 SF
204 SF
432B
414A
732 SF
100 SF
53 SF
413A
34 SF
78 SF
47 SF
269 SF
407A
76 SF
401A
197 SF
253 SF
252 SF
434 SF
109 SF
408A
109 SF
224 SF
199 SF
86 SF
156 SF
216 SF
113 SF
49 SF
265 SF
87 SF
465B
166 SF
173 SF
166 SF
463A
166 SF
299 SF
465A
47 SF
87 SF
464A
107 SF
112 SF
107 SF
92 SF
281 SF
456A
50 SF
456B
44 SF
40 SF
65 SF
4HA3-76
886 SF
217 SF
253 SF
433A
97 SF
96 SF
4HA5-76
276 SF
217 SF
CLOS.EL. CLOS.
9 SF 17 SF
4HA4-76
900 SF
508 SF
439C
123 SF
175 SF
112 SF
439A
248 SF
122 SF
30 SF
440A
35 SF
143 SF
74 SF
145 SF
75 SF
191 SF
442 SF
238 SF
434B
38 SF
PHASE 3
4HA6-76
S
F
653 SF
103 SF
226 SF
114 SF
FOURTH FLOOR PROJECT AREA
227 SF
75 SF
230 SF
222 SF
112 SF
H
A
S
F
H
A
S
F
H
A
S
F
283 SF
NOTE: CONTRACTOR SHALL COORDINATE WITH VA COR TO
DETERMINE ACTUAL OCCUPANT RELOCATION NEEDS AT
THE TIME OF CONSTRUCTION. CONTRACTOR SHALL SUBMIT
A FINAL PHASING PLAN FOR APPROVAL BY THE COR PRIOR
TO COMMENCING WORK IN ANY OCCUPIED AREA.
82 SF 96 SF
96 SF 24
S
F634 SF
403 SF
616 SF
247 SF
142 SF 121 SF
765 SF
344 SF
122 SF
1256 SF616 SF
103 SF
121 SF
110 SF
125 SF
105 SF
97 SF
88 SF
241 SF
112 SF
105 SF
348 SF
4 S
F
178 SF
189 SF 109 SF
82 SF
35 SF
187 SF
245 SF
111 SF
589 SF
115 SF
238 SF
92 SF
98 SF
98 SF
0 S
F
226 SF
43 SF
201 SF
310A
311A
309B
9A
351311B
305 304
318A 316A
362 353
302A
3H A1
-7
3H A2
-7
3H A3
-7
3HA5-76
350C
321D
319B
319A
320B
320A
307B
616 SF
143 SF
100 SF
62 SF
118 SF
97 SF
3HA4-76
215 SF
321D
DUCT
CHASE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION, B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
H-101
JWE MPL
HAZARDOUS MATERIALS -
THIRD FLOOR SOUTH
KEY NOTES:
1 THERMAL SYSTEM INSULATION CLOTH
PATCH ON A VERTICAL LINE TO BE
ABATED BY CONTRACTOR
SCALE: 1/8" = 1'-0"
HAZARDOUS MATERIALS - THIRD FLOOR SOUTH
E8
HAZARDOUS MATERIAL NOTES:
1. THE CONTRACTOR SHALL REVIEW ALL HAZARDOUS MATERIALS SURVEYS PROVIDED AS PART OF THE CONTRACT DOCUMENTS. IF ANY ADDITIONAL HAZARDOUS MATERIALS ARE ENCOUNTERED, REPORT THEM TO THE COR AND AWAIT FURTHER GUIDANCE - THESE MATERIALS WILL REQUIRE REMOVAL/ABATEMENT IF DISTURBED BY THE CONSTRUCTION.
2. THE “PATH OF CONSTRUCTION SUPPLEMENTAL ASBESTOS-CONTAINING MATERIALS SURVEY” REPORT DATED 06/04/20 PERFORMED BY ECS SHALL BE INCLUDED AND FOLLOWED AS A CONSTRUCTION DOCUMENT. ALL ASBESTOS CONTAINING MATERIAL (ACM) AND PRESUMED ASBESTOS CONTAINING MATERIAL (PACM) SHALL BE ABATED.
3. ASBESTOS ABATEMENT SHALL BE PERFORMED IN ACCORDANCE WITH THE SPECIFICATIONS AND APPLICABLE REGULATIONS. PERSONNEL HOLDING CURRENT NEW YORK STATE DEPARTMENT OF LABOR (NYSDOL) ASBESTOS HANDLER'S CERTIFICATES SHALL PERFORM THE WORK. ADDITIONALLY, THE CONTRACTOR MUST EMPLOY NYSDOL CERTIFIED SUPERVISORS TO BE ON THE WORK SITE FOR ALL ABATEMENT ACTIVITIES. THE CONTRACTOR MUST BE CURRENTLY
LICENSED BY THE NYSDOL.
4. CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND DISPOSAL OF ALL ASBESTOS-CONTAINING MATERIALS AND ASBESTOS-CONTAMINATED MATERIALS WITHIN THE SPECIFIED AREAS.
5. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL QUANTITIES OF ASBESTOS-CONTAINING MATERIALS.
6. CONTRACTOR IS RESPONSIBLE FOR PRECLEANING ANY AND ALL EXISTING ASBESTOS CONTAMINATION, DUST AND DEBRIS WITHIN THE REMOVAL AREAS.
7. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF BUILDING FINISHES. FLOORING SHALL BE PROTECTED WITH 1/8" MASONITE SHEETS. THE CONTRACTOR SHALL REPAIR ANY AND ALL DAMAGES CAUSED BY ABATEMENT
ACTIVITIES OR HIS PERSONNEL.
8. THE CONTRACTOR IS TO REMOVE THE ASBESTOS-CONTAINING MATERIALS (ACM'S) IN ACCORDANCE WITH NEW YORK STATE INDUSTRIAL CODE RULE 56 (12 NYCRR PART 56), THE VA SPECIFICATION AND APPLICABLE FEDERAL OSHA AND EPA REGULATIONS. WHERE THERE IS A DISCREPANCY, THE MOST STRINGENT REGULATION SHALL APPLY.
9. THE CONTRACTOR SHALL COORDINATE THE LOCATION OF HIS REMOTE PERSONNEL AND WASTE DECONTAMINATION UNIT(S), AND WASTE DUMPSTER WITH THE COR.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY AND ALL DAMAGES RESULTING FROM ASBESTOS ABATEMENT ACTIVITIES.
11. SCHEDULING OF WORK SHALL BE COORDINATED WITH THE COR. ASBESTOS ABATEMENT SHALL BE COORDINATED TO AVOID INTERRUPTIONS TO THE NORMAL ACTIVITIES OF THE FACILITY. THE REMOVAL MAY BE SCHEDULED AFTER
NORMAL BUSINESS HOURS AT NO ADDITIONAL COST TO THE OWNER.
12. IN AREAS OF PUBLIC ACCESS, THE CONTRACTOR SHALL ERECT ISOLATION BARRIERS THAT SEPARATE THE WORK AREAS FROM THE REMAINDER OF THE BUILDING. THE BARRIERS SHALL BE CONSTRUCTED OF A FIRE RETARDANT SHEATHING MATERIAL OF AT LEAST 1/2" THICKNESS. THE ISOLATION BARRIER SHALL BE PLASTICIZED WITH TWO (2) LAYERS OF 6-MIL PLASTIC SHEETING. THE ISOLATION BARRIERS SHALL BE CAULKED AT THE SHEATHING SEAMS AND WHERE THE SHEATHING MEETS THE FLOOR, WALLS AND CEILING. THE ISOLATION BARRIER SHALL BE CONSTRUCTED USING 2"X4" FRAMING, 16 INCHES CENTER-TO-CENTER, AND CAULKED AT ALL SEAMS.
13. THE ABATEMENT CONTRACTOR SHALL PERFORM REMOVAL WITHIN HEPA-FILTERED NEGATIVE AIR PRESSURE TENT ENCLOSURES. ALL ABATEMENT AREAS SHALL HAVE AN AIRLOCK ENTRANCE OR ATTACHED DECON UNIT. THE TENT ENCLOSURE SHALL BE VENTED TO THE OUTDOOR AIR VIA HEPA-FILTERED NEGATIVE AIR MACHINES. TENTS SHALL BE CONSTRUCTED IN ACCORDANCE WITH 12 NYCRR PART 56. IN AREAS OF PUBLIC ACCESS, THE TENT ENCLOSURES SHALL
BE SHEATHED FOR SAFETY.
LEGEND
AREA TO BE ABATED BY CONTRACTOR
AutoCAD SHX Text D.F.
D.F.
DUCT
CHASE
PROV. OFFICE SMITH
TOILET
PROSTHETICS
PROTHETICS
TELEHEALTH
TELEHEALTH WAITING
TELEHEALTH EXAM RM
C&P
TELEHEALTH EXAM ROOM
TELEHEALTH
425A
C&P
417A
C&P
C&P
MENS TOILET
IRM TRAINING ROOM
414A
BREAK ROOM
414B
VESTIBULE
TELEHEALTH
TEMP. P.B.
413A
C&P STORAGE
CORRIDOR
4HA2-76
PAIN MGMT.
PAIN MGMT.
408A
PAIN MGMT.
TELEHEALTH GRP RM
TOILET
E.H. ROOM
TOILET
STORAGE
407A
EMP. HEALTH
DATA CLOSET
INFECTION CONTROL
OFFICE
EQUIP. STRG.
H.A.C.
CHIRO. OFF.
TOILET
431A
WAITING
EXAM ROOM
EXAM ROOM
401A
EXAM ROOM
EXAM RM
MED RM
434A
CHIRO EXAM
432B
MENS TOILET
432A
CORRIDOR
4HA1-76
CORRIDOR
4HA3-76
STERILE SUPPLY
DIRTY
NURSING OFFICE
PODIATRY EXAM
433A
CHIRO EXAM
CHIRO EXAM
TOILET
427A
EMPLOYEE TOILET
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION, B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
H-102
JWE MPL
HAZARDOUS MATERIALS -
FOURTH FLOOR SOUTH
SCALE: 1/8" = 1'-0"
HAZARDOUS MATERIALS - FOURTH FLOOR SOUTH
E8
KEY NOTES:
1 GREY CERAMIC FLOOR TILE GROUT TO BE
ABATED BY CONTRACTOR
2 GREY CERAMIC FLOOR TILE GROUT TO BE
ABATED BY CONTRACTOR
HAZARDOUS MATERIAL NOTES:
1. THE CONTRACTOR SHALL REVIEW ALL HAZARDOUS MATERIALS SURVEYS PROVIDED AS PART OF THE CONTRACT DOCUMENTS. IF ANY ADDITIONAL HAZARDOUS MATERIALS ARE ENCOUNTERED, REPORT THEM TO THE COR AND AWAIT FURTHER GUIDANCE - THESE MATERIALS WILL REQUIRE REMOVAL/ABATEMENT IF DISTURBED BY THE CONSTRUCTION.
2. THE “PATH OF CONSTRUCTION SUPPLEMENTAL ASBESTOS-CONTAINING MATERIALS SURVEY” REPORT DATED 06/04/20 PERFORMED BY ECS SHALL BE INCLUDED AND FOLLOWED AS A CONSTRUCTION DOCUMENT. ALL ASBESTOS CONTAINING MATERIAL (ACM) AND PRESUMED ASBESTOS CONTAINING MATERIAL (PACM) SHALL BE ABATED.
3. ASBESTOS ABATEMENT SHALL BE PERFORMED IN ACCORDANCE WITH THE SPECIFICATIONS AND APPLICABLE REGULATIONS. PERSONNEL HOLDING CURRENT NEW YORK STATE DEPARTMENT OF LABOR (NYSDOL) ASBESTOS HANDLER'S CERTIFICATES SHALL PERFORM THE WORK. ADDITIONALLY, THE CONTRACTOR MUST EMPLOY NYSDOL CERTIFIED SUPERVISORS TO BE ON THE WORK SITE FOR ALL ABATEMENT ACTIVITIES. THE CONTRACTOR MUST BE CURRENTLY
LICENSED BY THE NYSDOL.
4. CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND DISPOSAL OF ALL ASBESTOS-CONTAINING MATERIALS AND ASBESTOS-CONTAMINATED MATERIALS WITHIN THE SPECIFIED AREAS.
5. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL QUANTITIES OF ASBESTOS-CONTAINING MATERIALS.
6. CONTRACTOR IS RESPONSIBLE FOR PRECLEANING ANY AND ALL EXISTING ASBESTOS CONTAMINATION, DUST AND DEBRIS WITHIN THE REMOVAL AREAS.
7. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF BUILDING FINISHES. FLOORING SHALL BE PROTECTED WITH 1/8" MASONITE SHEETS. THE CONTRACTOR SHALL REPAIR ANY AND ALL DAMAGES CAUSED BY ABATEMENT
ACTIVITIES OR HIS PERSONNEL.
8. THE CONTRACTOR IS TO REMOVE THE ASBESTOS-CONTAINING MATERIALS (ACM'S) IN ACCORDANCE WITH NEW YORK STATE INDUSTRIAL CODE RULE 56 (12 NYCRR PART 56), THE VA SPECIFICATION AND APPLICABLE FEDERAL OSHA AND EPA REGULATIONS. WHERE THERE IS A DISCREPANCY, THE MOST STRINGENT REGULATION SHALL APPLY.
9. THE CONTRACTOR SHALL COORDINATE THE LOCATION OF HIS REMOTE PERSONNEL AND WASTE DECONTAMINATION UNIT(S), AND WASTE DUMPSTER WITH THE COR.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY AND ALL DAMAGES RESULTING FROM ASBESTOS ABATEMENT ACTIVITIES.
11. SCHEDULING OF WORK SHALL BE COORDINATED WITH THE COR. ASBESTOS ABATEMENT SHALL BE COORDINATED TO AVOID INTERRUPTIONS TO THE NORMAL ACTIVITIES OF THE FACILITY. THE REMOVAL MAY BE SCHEDULED AFTER
NORMAL BUSINESS HOURS AT NO ADDITIONAL COST TO THE OWNER.
12. IN AREAS OF PUBLIC ACCESS, THE CONTRACTOR SHALL ERECT ISOLATION BARRIERS THAT SEPARATE THE WORK AREAS FROM THE REMAINDER OF THE BUILDING. THE BARRIERS SHALL BE CONSTRUCTED OF A FIRE RETARDANT SHEATHING MATERIAL OF AT LEAST 1/2" THICKNESS. THE ISOLATION BARRIER SHALL BE PLASTICIZED WITH TWO (2) LAYERS OF 6-MIL PLASTIC SHEETING. THE ISOLATION BARRIERS SHALL BE CAULKED AT THE SHEATHING SEAMS AND WHERE THE SHEATHING MEETS THE FLOOR, WALLS AND CEILING. THE ISOLATION BARRIER SHALL BE CONSTRUCTED USING 2"X4" FRAMING, 16 INCHES CENTER-TO-CENTER, AND CAULKED AT ALL SEAMS.
13. THE ABATEMENT CONTRACTOR SHALL PERFORM REMOVAL WITHIN HEPA-FILTERED NEGATIVE AIR PRESSURE TENT ENCLOSURES. ALL ABATEMENT AREAS SHALL HAVE AN AIRLOCK ENTRANCE OR ATTACHED DECON UNIT. THE TENT ENCLOSURE SHALL BE VENTED TO THE OUTDOOR AIR VIA HEPA-FILTERED NEGATIVE AIR MACHINES. TENTS SHALL BE CONSTRUCTED IN ACCORDANCE WITH 12 NYCRR PART 56. IN AREAS OF PUBLIC ACCESS, THE TENT ENCLOSURES SHALL
BE SHEATHED FOR SAFETY.
3 YELLOW MASTIC TO BE ABATED BY
CONTRACTOR
4 1' X 1' VFT TO BE ABATED BY CONTRACTOR
5 BROWN COVE BASE AND MASTIC TO BE
ABATED BY CONTRACTOR
6 YELLOW/BLACK CARPET MASTIC TO BE
ABATED BY CONTRACTOR
7 VFT AND BLACK/BROWN MASTIC TO BE
ABATED BY CONTRACTOR
8 BLACK HVAC DUCT WRAP TO BE ABATED
BY CONTRACTOR
9 GREEN AND OLIVE VFT TO BE ABATED BY
CONTRACTOR
LEGEND
AREA TO BE ABATED BY CONTRACTOR
EXAM RM
STORAGE
434B
SPECIALTY SUPPORT
EMPLOYEE TOILET
EXAM RM
CLEAN UTIL.
465B
STORAGE
465A
MED RM
464A
EYE EXAM
EYE EXAM
463A
PROG. ASST.
EYE EXAM
DATA CLOSET
WAITING RM
MED INSTR. TECH
MED INSTR. TECH
ECHO ROOM
EMS STR.
456B
STORAGE
456A
FAMTEL BDRM
FAMTEL BDRM
CORRIDOR
4HA7-76
HOPTEL BDRM
HOPTEL BDRM
HOPTEL BDRM
TOILET
TOILET
UNASSIGN
CONFERENCE RM
HOPTEL/FAMTEL LOUNGE
EKG ROOM EXAM TABLE
STORAGE
LACTATION/ COPIER/FAX
TOILET
440A
H.A.C.
PROG. ASST.
WOMENS TOILET
439A
LOW VISION CLINIC
STORAGE
439B
RETHERM. ROOM
EXAM RM
CORRIDOR
4HA6-76
CORRIDOR
4HA4-76
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION, B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
H-103
JWE MPL
HAZARDOUS MATERIALS -
FOURTH FLOOR NORTH
SCALE: 1/8" = 1'-0"
HAZARDOUS MATERIALS - FOURTH FLOOR NORTH
E8
HAZARDOUS MATERIAL NOTES:
1. THE CONTRACTOR SHALL REVIEW ALL HAZARDOUS MATERIALS SURVEYS PROVIDED AS PART OF THE CONTRACT DOCUMENTS. IF ANY ADDITIONAL HAZARDOUS MATERIALS ARE ENCOUNTERED, REPORT THEM TO THE COR AND AWAIT FURTHER GUIDANCE - THESE MATERIALS WILL REQUIRE REMOVAL/ABATEMENT IF DISTURBED BY THE CONSTRUCTION.
2. THE “PATH OF CONSTRUCTION SUPPLEMENTAL ASBESTOS-CONTAINING MATERIALS SURVEY” REPORT DATED 06/04/20 PERFORMED BY ECS SHALL BE INCLUDED AND FOLLOWED AS A CONSTRUCTION DOCUMENT. ALL ASBESTOS CONTAINING MATERIAL (ACM) AND PRESUMED ASBESTOS CONTAINING MATERIAL (PACM) SHALL BE ABATED.
3. ASBESTOS ABATEMENT SHALL BE PERFORMED IN ACCORDANCE WITH THE SPECIFICATIONS AND APPLICABLE REGULATIONS. PERSONNEL HOLDING CURRENT NEW YORK STATE DEPARTMENT OF LABOR (NYSDOL) ASBESTOS HANDLER'S CERTIFICATES SHALL PERFORM THE WORK. ADDITIONALLY, THE CONTRACTOR MUST EMPLOY NYSDOL CERTIFIED SUPERVISORS TO BE ON THE WORK SITE FOR ALL ABATEMENT ACTIVITIES. THE CONTRACTOR MUST BE CURRENTLY
LICENSED BY THE NYSDOL.
4. CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND DISPOSAL OF ALL ASBESTOS-CONTAINING MATERIALS AND ASBESTOS-CONTAMINATED MATERIALS WITHIN THE SPECIFIED AREAS.
5. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL QUANTITIES OF ASBESTOS-CONTAINING MATERIALS.
6. CONTRACTOR IS RESPONSIBLE FOR PRECLEANING ANY AND ALL EXISTING ASBESTOS CONTAMINATION, DUST AND DEBRIS WITHIN THE REMOVAL AREAS.
7. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF BUILDING FINISHES. FLOORING SHALL BE PROTECTED WITH 1/8" MASONITE SHEETS. THE CONTRACTOR SHALL REPAIR ANY AND ALL DAMAGES CAUSED BY ABATEMENT
ACTIVITIES OR HIS PERSONNEL.
8. THE CONTRACTOR IS TO REMOVE THE ASBESTOS-CONTAINING MATERIALS (ACM'S) IN ACCORDANCE WITH NEW YORK STATE INDUSTRIAL CODE RULE 56 (12 NYCRR PART 56), THE VA SPECIFICATION AND APPLICABLE FEDERAL OSHA AND EPA REGULATIONS. WHERE THERE IS A DISCREPANCY, THE MOST STRINGENT REGULATION SHALL APPLY.
9. THE CONTRACTOR SHALL COORDINATE THE LOCATION OF HIS REMOTE PERSONNEL AND WASTE DECONTAMINATION UNIT(S), AND WASTE DUMPSTER WITH THE COR.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY AND ALL DAMAGES RESULTING FROM ASBESTOS ABATEMENT ACTIVITIES.
11. SCHEDULING OF WORK SHALL BE COORDINATED WITH THE COR. ASBESTOS ABATEMENT SHALL BE COORDINATED TO AVOID INTERRUPTIONS TO THE NORMAL ACTIVITIES OF THE FACILITY. THE REMOVAL MAY BE SCHEDULED AFTER
NORMAL BUSINESS HOURS AT NO ADDITIONAL COST TO THE OWNER.
12. IN AREAS OF PUBLIC ACCESS, THE CONTRACTOR SHALL ERECT ISOLATION BARRIERS THAT SEPARATE THE WORK AREAS FROM THE REMAINDER OF THE BUILDING. THE BARRIERS SHALL BE CONSTRUCTED OF A FIRE RETARDANT SHEATHING MATERIAL OF AT LEAST 1/2" THICKNESS. THE ISOLATION BARRIER SHALL BE PLASTICIZED WITH TWO (2) LAYERS OF 6-MIL PLASTIC SHEETING. THE ISOLATION BARRIERS SHALL BE CAULKED AT THE SHEATHING SEAMS AND WHERE THE SHEATHING MEETS THE FLOOR, WALLS AND CEILING. THE ISOLATION BARRIER SHALL BE CONSTRUCTED USING 2"X4" FRAMING, 16 INCHES CENTER-TO-CENTER, AND CAULKED AT ALL SEAMS.
13. THE ABATEMENT CONTRACTOR SHALL PERFORM REMOVAL WITHIN HEPA-FILTERED NEGATIVE AIR PRESSURE TENT ENCLOSURES. ALL ABATEMENT AREAS SHALL HAVE AN AIRLOCK ENTRANCE OR ATTACHED DECON UNIT. THE TENT ENCLOSURE SHALL BE VENTED TO THE OUTDOOR AIR VIA HEPA-FILTERED NEGATIVE AIR MACHINES. TENTS SHALL BE CONSTRUCTED IN ACCORDANCE WITH 12 NYCRR PART 56. IN AREAS OF PUBLIC ACCESS, THE TENT ENCLOSURES SHALL
BE SHEATHED FOR SAFETY.
KEY NOTES:
1 1' X 1' VFT AND MASTIC TO BE ABATED BY
CONTRACTOR
2 1' X 1' VFT TO BE ABATED BY CONTRACTOR
3 1' X 1' BROWN AND WHITE VFT AND MASTIC
TO BE ABATED BY CONTRACTOR
4 GREEN CARPET MASTIC TO BE ABATED BY
CONTRACTOR
5 1' X 1' VFT TO BE ABATED BY CONTRACTOR
6 1' X 1' VFT TO BE ABATED BY CONTRACTOR
7 1' X 1' BROWN AND WHITE VFT AND MASTIC
TO BE ABATED BY CONTRACTOR
SW-6/76
PENTHOUSE
ELEVATOR
NO.1
6ATS1-76
6HA5-76
6ATS1-76
6ATS2-76
6ATS3-76
6HA1-76
DATA CLOSET
ELEV. NO.3
611A
ELEV. NO.2DIRTY UTL.
605 605A 604 606 603
607A
HAC
RESTROOM
GROUP ROOM
OFFICE MNGR.
OFFICE
MED. RM.
OFFICE BREAKRM.
STORAGE
LAUNDRY CHUTE
OFFICE
PATIENT RM.
PATIENT RM.
PATIENT RM.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION, B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
H-104
JWE MPL
HAZARDOUS MATERIALS -
SIXTH FLOOR SOUTH
SCALE: 1/8" = 1'-0"
HAZARDOUS MATERIALS - SIXTH FLOOR SOUTH
E8
HAZARDOUS MATERIAL NOTES:
1. THE CONTRACTOR SHALL REVIEW ALL HAZARDOUS MATERIALS SURVEYS PROVIDED AS PART OF THE CONTRACT DOCUMENTS. IF ANY ADDITIONAL HAZARDOUS MATERIALS ARE ENCOUNTERED, REPORT THEM TO THE COR AND AWAIT FURTHER GUIDANCE - THESE MATERIALS WILL REQUIRE REMOVAL/ABATEMENT IF DISTURBED BY THE CONSTRUCTION.
2. THE “PATH OF CONSTRUCTION SUPPLEMENTAL ASBESTOS-CONTAINING MATERIALS SURVEY” REPORT DATED 06/04/20 PERFORMED BY ECS SHALL BE INCLUDED AND FOLLOWED AS A CONSTRUCTION DOCUMENT. ALL ASBESTOS CONTAINING MATERIAL (ACM) AND PRESUMED ASBESTOS CONTAINING MATERIAL (PACM) SHALL BE ABATED.
3. ASBESTOS ABATEMENT SHALL BE PERFORMED IN ACCORDANCE WITH THE SPECIFICATIONS AND APPLICABLE REGULATIONS. PERSONNEL HOLDING CURRENT NEW YORK STATE DEPARTMENT OF LABOR (NYSDOL) ASBESTOS HANDLER'S CERTIFICATES SHALL PERFORM THE WORK. ADDITIONALLY, THE CONTRACTOR MUST EMPLOY NYSDOL CERTIFIED SUPERVISORS TO BE ON THE WORK SITE FOR ALL ABATEMENT ACTIVITIES. THE CONTRACTOR MUST BE CURRENTLY
LICENSED BY THE NYSDOL.
4. CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND DISPOSAL OF ALL ASBESTOS-CONTAINING MATERIALS AND ASBESTOS-CONTAMINATED MATERIALS WITHIN THE SPECIFIED AREAS.
5. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL QUANTITIES OF ASBESTOS-CONTAINING MATERIALS.
6. CONTRACTOR IS RESPONSIBLE FOR PRECLEANING ANY AND ALL EXISTING ASBESTOS CONTAMINATION, DUST AND DEBRIS WITHIN THE REMOVAL AREAS.
7. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF BUILDING FINISHES. FLOORING SHALL BE PROTECTED WITH 1/8" MASONITE SHEETS. THE CONTRACTOR SHALL REPAIR ANY AND ALL DAMAGES CAUSED BY ABATEMENT
ACTIVITIES OR HIS PERSONNEL.
8. THE CONTRACTOR IS TO REMOVE THE ASBESTOS-CONTAINING MATERIALS (ACM'S) IN ACCORDANCE WITH NEW YORK STATE INDUSTRIAL CODE RULE 56 (12 NYCRR PART 56), THE VA SPECIFICATION AND APPLICABLE FEDERAL OSHA AND EPA REGULATIONS. WHERE THERE IS A DISCREPANCY, THE MOST STRINGENT REGULATION SHALL APPLY.
9. THE CONTRACTOR SHALL COORDINATE THE LOCATION OF HIS REMOTE PERSONNEL AND WASTE DECONTAMINATION UNIT(S), AND WASTE DUMPSTER WITH THE COR.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY AND ALL DAMAGES RESULTING FROM ASBESTOS ABATEMENT ACTIVITIES.
11. SCHEDULING OF WORK SHALL BE COORDINATED WITH THE COR. ASBESTOS ABATEMENT SHALL BE COORDINATED TO AVOID INTERRUPTIONS TO THE NORMAL ACTIVITIES OF THE FACILITY. THE REMOVAL MAY BE SCHEDULED AFTER
NORMAL BUSINESS HOURS AT NO ADDITIONAL COST TO THE OWNER.
12. IN AREAS OF PUBLIC ACCESS, THE CONTRACTOR SHALL ERECT ISOLATION BARRIERS THAT SEPARATE THE WORK AREAS FROM THE REMAINDER OF THE BUILDING. THE BARRIERS SHALL BE CONSTRUCTED OF A FIRE RETARDANT SHEATHING MATERIAL OF AT LEAST 1/2" THICKNESS. THE ISOLATION BARRIER SHALL BE PLASTICIZED WITH TWO (2) LAYERS OF 6-MIL PLASTIC SHEETING. THE ISOLATION BARRIERS SHALL BE CAULKED AT THE SHEATHING SEAMS AND WHERE THE SHEATHING MEETS THE FLOOR, WALLS AND CEILING. THE ISOLATION BARRIER SHALL BE CONSTRUCTED USING 2"X4" FRAMING, 16 INCHES CENTER-TO-CENTER, AND CAULKED AT ALL SEAMS.
13. THE ABATEMENT CONTRACTOR SHALL PERFORM REMOVAL WITHIN HEPA-FILTERED NEGATIVE AIR PRESSURE TENT ENCLOSURES. ALL ABATEMENT AREAS SHALL HAVE AN AIRLOCK ENTRANCE OR ATTACHED DECON UNIT. THE TENT ENCLOSURE SHALL BE VENTED TO THE OUTDOOR AIR VIA HEPA-FILTERED NEGATIVE AIR MACHINES. TENTS SHALL BE CONSTRUCTED IN ACCORDANCE WITH 12 NYCRR PART 56. IN AREAS OF PUBLIC ACCESS, THE TENT ENCLOSURES SHALL
BE SHEATHED FOR SAFETY.
KEY NOTES:
1 BLACK HVAC DUCT WRAP TO BE ABATED BY
CONTRACTOR
2 JOINT COMPOUND TO BE ABATED BY
CONTRACTOR
6ATN1-76
6ATN3-76
6HA6-76 6ATN5-76
6H A7
-7
6ATN4-76
6HA2-76
615615A
623A 624A
622 621 620
617A617
616A
6186HA3-76
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION, B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
H-105
JWE MPL
HAZARDOUS MATERIALS -
SIXTH FLOOR NORTH
SCALE: 1/8" = 1'-0"
HAZARDOUS MATERIALS - SIXTH FLOOR NORTH
E8
HAZARDOUS MATERIAL NOTES:
1. THE CONTRACTOR SHALL REVIEW ALL HAZARDOUS MATERIALS SURVEYS PROVIDED AS PART OF THE CONTRACT DOCUMENTS. IF ANY ADDITIONAL HAZARDOUS MATERIALS ARE ENCOUNTERED, REPORT THEM TO THE COR AND AWAIT FURTHER GUIDANCE - THESE MATERIALS WILL REQUIRE REMOVAL/ABATEMENT IF DISTURBED BY THE CONSTRUCTION.
2. THE “PATH OF CONSTRUCTION SUPPLEMENTAL ASBESTOS-CONTAINING MATERIALS SURVEY” REPORT DATED 06/04/20 PERFORMED BY ECS SHALL BE INCLUDED AND FOLLOWED AS A CONSTRUCTION DOCUMENT. ALL ASBESTOS CONTAINING MATERIAL (ACM) AND PRESUMED ASBESTOS CONTAINING MATERIAL (PACM) SHALL BE ABATED.
3. ASBESTOS ABATEMENT SHALL BE PERFORMED IN ACCORDANCE WITH THE SPECIFICATIONS AND APPLICABLE REGULATIONS. PERSONNEL HOLDING CURRENT NEW YORK STATE DEPARTMENT OF LABOR (NYSDOL) ASBESTOS HANDLER'S CERTIFICATES SHALL PERFORM THE WORK. ADDITIONALLY, THE CONTRACTOR MUST EMPLOY NYSDOL CERTIFIED SUPERVISORS TO BE ON THE WORK SITE FOR ALL ABATEMENT ACTIVITIES. THE CONTRACTOR MUST BE CURRENTLY
LICENSED BY THE NYSDOL.
4. CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND DISPOSAL OF ALL ASBESTOS-CONTAINING MATERIALS AND ASBESTOS-CONTAMINATED MATERIALS WITHIN THE SPECIFIED AREAS.
5. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL QUANTITIES OF ASBESTOS-CONTAINING MATERIALS.
6. CONTRACTOR IS RESPONSIBLE FOR PRECLEANING ANY AND ALL EXISTING ASBESTOS CONTAMINATION, DUST AND DEBRIS WITHIN THE REMOVAL AREAS.
7. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF BUILDING FINISHES. FLOORING SHALL BE PROTECTED WITH 1/8" MASONITE SHEETS. THE CONTRACTOR SHALL REPAIR ANY AND ALL DAMAGES CAUSED BY ABATEMENT
ACTIVITIES OR HIS PERSONNEL.
8. THE CONTRACTOR IS TO REMOVE THE ASBESTOS-CONTAINING MATERIALS (ACM'S) IN ACCORDANCE WITH NEW YORK STATE INDUSTRIAL CODE RULE 56 (12 NYCRR PART 56), THE VA SPECIFICATION AND APPLICABLE FEDERAL OSHA AND EPA REGULATIONS. WHERE THERE IS A DISCREPANCY, THE MOST STRINGENT REGULATION SHALL APPLY.
9. THE CONTRACTOR SHALL COORDINATE THE LOCATION OF HIS REMOTE PERSONNEL AND WASTE DECONTAMINATION UNIT(S), AND WASTE DUMPSTER WITH THE COR.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY AND ALL DAMAGES RESULTING FROM ASBESTOS ABATEMENT ACTIVITIES.
11. SCHEDULING OF WORK SHALL BE COORDINATED WITH THE COR. ASBESTOS ABATEMENT SHALL BE COORDINATED TO AVOID INTERRUPTIONS TO THE NORMAL ACTIVITIES OF THE FACILITY. THE REMOVAL MAY BE SCHEDULED AFTER
NORMAL BUSINESS HOURS AT NO ADDITIONAL COST TO THE OWNER.
12. IN AREAS OF PUBLIC ACCESS, THE CONTRACTOR SHALL ERECT ISOLATION BARRIERS THAT SEPARATE THE WORK AREAS FROM THE REMAINDER OF THE BUILDING. THE BARRIERS SHALL BE CONSTRUCTED OF A FIRE RETARDANT SHEATHING MATERIAL OF AT LEAST 1/2" THICKNESS. THE ISOLATION BARRIER SHALL BE PLASTICIZED WITH TWO (2) LAYERS OF 6-MIL PLASTIC SHEETING. THE ISOLATION BARRIERS SHALL BE CAULKED AT THE SHEATHING SEAMS AND WHERE THE SHEATHING MEETS THE FLOOR, WALLS AND CEILING. THE ISOLATION BARRIER SHALL BE CONSTRUCTED USING 2"X4" FRAMING, 16 INCHES CENTER-TO-CENTER, AND CAULKED AT ALL SEAMS.
13. THE ABATEMENT CONTRACTOR SHALL PERFORM REMOVAL WITHIN HEPA-FILTERED NEGATIVE AIR PRESSURE TENT ENCLOSURES. ALL ABATEMENT AREAS SHALL HAVE AN AIRLOCK ENTRANCE OR ATTACHED DECON UNIT. THE TENT ENCLOSURE SHALL BE VENTED TO THE OUTDOOR AIR VIA HEPA-FILTERED NEGATIVE AIR MACHINES. TENTS SHALL BE CONSTRUCTED IN ACCORDANCE WITH 12 NYCRR PART 56. IN AREAS OF PUBLIC ACCESS, THE TENT ENCLOSURES SHALL
BE SHEATHED FOR SAFETY.
KEY NOTES:
1 BLACK HVAC DUCT WRAP TO BE ABATED BY
CONTRACTOR
2 HVAC VIBRATION DAMPENER TO BE
ABATED BY CONTRACTOR
3 BLACK DUCT WRAP AND INSULATION ON PIPE
HANGERS TO BE ABATED BY CONTRACTOR
LEGEND
AREA TO BE ABATED BY CONTRACTOR
6ATN2-76
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION, B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
H-106
JWE MPL
HAZARDOUS MATERIALS -
ATTIC
SCALE: 1/8" = 1'-0"
HAZARDOUS MATERIALS - ATTIC
D6
HAZARDOUS MATERIAL NOTES:
1. THE CONTRACTOR SHALL REVIEW ALL HAZARDOUS MATERIALS SURVEYS PROVIDED AS PART OF THE CONTRACT DOCUMENTS. IF ANY ADDITIONAL HAZARDOUS MATERIALS ARE ENCOUNTERED, REPORT THEM TO THE COR AND AWAIT FURTHER GUIDANCE - THESE MATERIALS WILL REQUIRE REMOVAL/ABATEMENT IF DISTURBED BY THE CONSTRUCTION.
2. THE “PATH OF CONSTRUCTION SUPPLEMENTAL ASBESTOS-CONTAINING MATERIALS SURVEY” REPORT DATED 06/04/20 PERFORMED BY ECS SHALL BE INCLUDED AND FOLLOWED AS A CONSTRUCTION DOCUMENT. ALL ASBESTOS CONTAINING MATERIAL (ACM) AND PRESUMED ASBESTOS CONTAINING MATERIAL (PACM) SHALL BE ABATED.
3. ASBESTOS ABATEMENT SHALL BE PERFORMED IN ACCORDANCE WITH THE SPECIFICATIONS AND APPLICABLE REGULATIONS. PERSONNEL HOLDING CURRENT NEW YORK STATE DEPARTMENT OF LABOR (NYSDOL) ASBESTOS HANDLER'S CERTIFICATES SHALL PERFORM THE WORK. ADDITIONALLY, THE CONTRACTOR MUST EMPLOY NYSDOL CERTIFIED SUPERVISORS TO BE ON THE WORK SITE FOR ALL ABATEMENT ACTIVITIES. THE CONTRACTOR MUST BE CURRENTLY
LICENSED BY THE NYSDOL.
4. CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND DISPOSAL OF ALL ASBESTOS-CONTAINING MATERIALS AND ASBESTOS-CONTAMINATED MATERIALS WITHIN THE SPECIFIED AREAS.
5. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL QUANTITIES OF ASBESTOS-CONTAINING MATERIALS.
6. CONTRACTOR IS RESPONSIBLE FOR PRECLEANING ANY AND ALL EXISTING ASBESTOS CONTAMINATION, DUST AND DEBRIS WITHIN THE REMOVAL AREAS.
7. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF BUILDING FINISHES. FLOORING SHALL BE PROTECTED WITH 1/8" MASONITE SHEETS. THE CONTRACTOR SHALL REPAIR ANY AND ALL DAMAGES CAUSED BY ABATEMENT
ACTIVITIES OR HIS PERSONNEL.
8. THE CONTRACTOR IS TO REMOVE THE ASBESTOS-CONTAINING MATERIALS (ACM'S) IN ACCORDANCE WITH NEW YORK STATE INDUSTRIAL CODE RULE 56 (12 NYCRR PART 56), THE VA SPECIFICATION AND APPLICABLE FEDERAL OSHA AND EPA REGULATIONS. WHERE THERE IS A DISCREPANCY, THE MOST STRINGENT REGULATION SHALL APPLY.
9. THE CONTRACTOR SHALL COORDINATE THE LOCATION OF HIS REMOTE PERSONNEL AND WASTE DECONTAMINATION UNIT(S), AND WASTE DUMPSTER WITH THE COR.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY AND ALL DAMAGES RESULTING FROM ASBESTOS ABATEMENT ACTIVITIES.
11. SCHEDULING OF WORK SHALL BE COORDINATED WITH THE COR. ASBESTOS ABATEMENT SHALL BE COORDINATED TO AVOID INTERRUPTIONS TO THE NORMAL ACTIVITIES OF THE FACILITY. THE REMOVAL MAY BE SCHEDULED AFTER
NORMAL BUSINESS HOURS AT NO ADDITIONAL COST TO THE OWNER.
12. IN AREAS OF PUBLIC ACCESS, THE CONTRACTOR SHALL ERECT ISOLATION BARRIERS THAT SEPARATE THE WORK AREAS FROM THE REMAINDER OF THE BUILDING. THE BARRIERS SHALL BE CONSTRUCTED OF A FIRE RETARDANT SHEATHING MATERIAL OF AT LEAST 1/2" THICKNESS. THE ISOLATION BARRIER SHALL BE PLASTICIZED WITH TWO (2) LAYERS OF 6-MIL PLASTIC SHEETING. THE ISOLATION BARRIERS SHALL BE CAULKED AT THE SHEATHING SEAMS AND WHERE THE SHEATHING MEETS THE FLOOR, WALLS AND CEILING. THE ISOLATION BARRIER SHALL BE CONSTRUCTED USING 2"X4" FRAMING, 16 INCHES CENTER-TO-CENTER, AND CAULKED AT ALL SEAMS.
13. THE ABATEMENT CONTRACTOR SHALL PERFORM REMOVAL WITHIN HEPA-FILTERED NEGATIVE AIR PRESSURE TENT ENCLOSURES. ALL ABATEMENT AREAS SHALL HAVE AN AIRLOCK ENTRANCE OR ATTACHED DECON UNIT. THE TENT ENCLOSURE SHALL BE VENTED TO THE OUTDOOR AIR VIA HEPA-FILTERED NEGATIVE AIR MACHINES. TENTS SHALL BE CONSTRUCTED IN ACCORDANCE WITH 12 NYCRR PART 56. IN AREAS OF PUBLIC ACCESS, THE TENT ENCLOSURES SHALL
BE SHEATHED FOR SAFETY.
KEY NOTES:
1 BLACK TAR IN CORK PIPE WRAP INSULATION
TO BE ABATED BY CONTRACTOR
203A
220A
W TOILET
206 SF
AUDIO CONTROL
125 SF
63 SF
34 SF
131 SF
PAT. ADVO.
238 SF
202D
AUDIOLOGY WTG/RECEPTION
214A
203B
HEARING AID. MOD.
AUDIOLOGY
202C
AUDIOLOGY RAMP
M TOILET
170 SF
135 SF
132 SF 156 SF
106 SF
34 SF
130 SF
248 SF
92 SF
205 204
2HA4-76
DATA CLOSET
221B
AUDIO OBSV.
DIRECTOR SEC.
GOSINK
101 SF110 SF
411 SF
246 SF
130 SF
101 SF
PUBLIC AFFAIRS
SPCH. PATHOLOGIST
VACANTEEO SPEC.
DEMO ENTIRE
ACT CEILING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
ARCHITECTURAL DEMOLITION PLAN -
SECOND FLOOR SOUTH
AD-101
EWW LMR
SCALE: 1/4" = 1'-0"
ARCHITECTURAL DEMOLITION PLAN - SECOND FLOOR SOUTH
A1
GENERAL NOTE:
SMOKE DETECTORS, SPRINKLERS AND DIFFUSERS TO BE
INDEPENDENTLY SUPPORTED AND PROTECTED DURING
CEILING REMOVAL, AND REINSTALLED IN NEW CEILING GRID.
REFER TO STRUCTURAL FOR
EXTENT OF FLOOR DEMOLITION
3'-6"
DEMO ACT
CEILING (ALL) AND
FLOOR FINISH
82 SF 96 SF 247 SF
142 SF 121 SF
765 SF
616 SF
348 SF
178 SF
189 SF 109 SF
82 SF
35 SF
187 SF
245 SF
238 SF
92 SF
FOOD SERVICE
VACANTVENDING AREA
UP
EL
EV
. 1
ASST. CHIEF
OT CLINIC
305 STAGE
CHAPEL
E.M.S.
318A
O.D. RM.
316A
TOILET
UNISEX
CONFERENCE RM
DATA CLOSET
SWSW3-76
DN 316
MOD LOUNGE
319B
319A
OFFICE
DIRTY UTIL
307B
OFFICE/STORG.
100 SF
62 SF
3HA4-76
RESP. WRKST.
DEMO EXISTING 42"Wx85"H WINDOW AND INTERIOR
ALUMINUM SILL. EXTERIOR STONE SILL TO REMAIN.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
ARCHITECTURAL DEMOLITION PLAN -
THIRD FLOOR SOUTH
AD-102
EWW LMR
SCALE: 1/4" = 1'-0"
ARCHITECTURAL DEMOLITION PLAN - THIRD FLOOR SOUTH
A1
GENERAL NOTE:
SMOKE DETECTORS, SPRINKLERS AND DIFFUSERS TO BE
INDEPENDENTLY SUPPORTED AND PROTECTED DURING
CEILING REMOVAL, AND REINSTALLED IN NEW CEILING GRID.
AutoCAD SHX Text D.F.
DATA CLOSET
H.A.C.
431A
407A
EXAM RM
TOILET
405 404
TOILET
EL
EV
. 1
427 429
CHIRO OFF.
432A
TOILET
MENS
STORAGE
SWSW4-76
427A
4HA3-76
425A
PAIN MANGMT
CHIRO EXAM
WAITING
EQUIP. STRG.
EMP. HEALTH
TELEHEALTH
TELEHEALTH EXAM RM
INFECT.
OFFICE
DUCT
CONTROL CHASE
DEMO EXISTING 42"Wx85"H WINDOW AND INTERIOR
ALUMINUM SILL. EXTERIOR STONE SILL TO REMAIN.
DEMO ENTIRE ACT CEILING
REFER TO STRUCTURAL FOR EXTENT OF FLOOR DEMOLITION
DEMO PLUMBING FIXTURES
DEMO FLOOR FINISH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
ARCHITECTURAL DEMOLITION PLAN -
FOURTH FLOOR SOUTH
AD-103
EWW LMR
SCALE: 1/4" = 1'-0"
ARCHITECTURAL DEMOLITION PLAN - FOURTH FLOOR SOUTH
A1
GENERAL NOTE:
SMOKE DETECTORS, SPRINKLERS AND DIFFUSERS TO BE
INDEPENDENTLY SUPPORTED AND PROTECTED DURING
CEILING REMOVAL, AND REINSTALLED IN NEW CEILING GRID.
510A
508 507 506
5HA3-76
518I
518J
518K
160 SF
115 SF
119 SF
98 SF
264 SF
45 SF
76 SF
120 SF 114 SF119 SF113 SF
146 SF
25 SF
127 SF
79 SF167 SF
241 SF
92 SF
BVAC
BVAC
BVAC
BVAC
BVAC BVAC
BVAC
BVAC
MVAC
MVAC
IT
MVAC
DEMO EXISTING 42"Wx85"H WINDOW AND INTERIOR
ALUMINUM SILL. EXTERIOR STONE SILL TO REMAIN.
DEMO ACT
CEILING
SALVAGE ROLLER BLINDS, RADIATOR &
GRILLE COVER.TURN OVER TO OWNER
SEE STRUCTURAL FOR EXTENT OF FLOOR REMOVALS.
(FOR FUTURE DUCTWORK)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
ARCHITECTURAL DEMOLITION PLAN -
FIFTH FLOOR SOUTH
AD-104
EWW LMR
SCALE: 1/4" = 1'-0"
ARCHITECTURAL DEMOLITION PLAN - FIFTH FLOOR SOUTH
A1
GENERAL NOTE:
SMOKE DETECTORS, SPRINKLERS AND DIFFUSERS TO BE
INDEPENDENTLY SUPPORTED AND PROTECTED DURING
CEILING REMOVAL, AND REINSTALLED IN NEW CEILING GRID.
AutoCAD SHX Text D.F.
ELEV. NO.3
532532A
LOBBY
DIETICIAN
533A
558A
MENS TOILET
VACANT
534A
535A
UP
KITCHEN
STORE RM
PACT OFFICE
P.T. STOR.
555B
PHARM.
PACT TEAM 4
DATA CLOSET
TOILET
HAC
CORRIDOR
536A
5HA6-76
NO.4
FHR
ELEV.
DN
540A
CORRECTIVE THERAPY
MEETING RM
CHIEF, PM&R
PHYSICAL THERAPY
5HA7-76
SWC5-76
SW
EX
5-
SWNW5-76TOILETTOILET
DN
5H A7
-7
5HA4-76
561A
TOILET
559A
PSA OFFICE
WAITING ROOM
WOUND CLINIC
CLINICAL PHARM.
PATIENT ED.
NURSE STATION
501A 501
EQUIP.
TOILET TOILET
EXAM RM15
EXAM 17
534B
STORAGE
SW OFFICE
NURSE WORK RM.
ELEVATOR
ELEV. NO.2
MENS WOMENS
EXAM RM2
PSA OFFICE
PSA OFFICE
PACT OFFICE
VACANT
WAITING RM
EXAM RM1
AD-105
A2
DEMO ACT CEILING
DEMO ACT CEILING
DEMO ACT CEILING
DEMO ACT CEILING
DEMO ACT CEILING
DEMO ACT CEILING
DEMO ACT CEILING
DEMO ENTIRE ACT
CEILING
DEMO GYPSUM WALL BOARD, VINYL WALL
BASE, AND LGMF STUD CHASE WALLS
DEMO DRYWALL SOFFIT
ABOVE. REFER TO A-111
FOR EXTENT
DEMO ACT CEILING
TO EXTENT
NECESSARY FOR
SHAFT WALL WORK
CUT LOW COUNTERTOP. COORDINATE
EXTENT WITH NEW WALL.
REFER TO STRUCTURAL FOR
EXTENT OF FLOOR DEMOLITION
REMOVE BASE CABINET AND
SALVAGE FOR RE-INSTALLATION
REMOVE
TRANSACTION
COUNTER AND
SCREEN
DEMO HALF WALL TO EXTENT
NECESSARY FOR SHAFT WALL
CONSTRUCTION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
ARCHITECTURAL DEMOLITION PLAN -
FIFTH FLOOR NORTH
AD-105
EWW LMR
SCALE: 1/8" = 1'-0"
ARCHITECTURAL DEMOLITION PLAN - FIFTH FLOOR NORTH
A1
SCALE: 1/2" = 1'-0"
ENLARGED NURSING STATION DEMOLITION PLAN
A2
GENERAL NOTE:
SMOKE DETECTORS, SPRINKLERS AND DIFFUSERS TO BE
INDEPENDENTLY SUPPORTED AND PROTECTED DURING
CEILING REMOVAL, AND REINSTALLED IN NEW CEILING GRID.
AutoCAD SHX Text D.F.
ELEVATOR
NO.1
6ATS1-76
6HA5-76
6ATS2-76
6ATS3-76
607A
HAC
RESTROOM
179 SF 180 SF
252 SF
21 SF
MED. RM.
PATIENT RM.
MVAC
PHARMACY
REFER TO STRUCTURAL FOR EXTENT OF FLOOR REMOVAL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
ARCHITECTURAL DEMOLITION -
SIXTH FLOOR SOUTH
AD-106
EWW LMR
SCALE: 1/4" = 1'-0"
ARCHITECTURAL DEMOLITION PLAN - SIXTH FLOOR SOUTH
A1
SW
EX
6-
UP
ACCESS
PANELS
PANELS
ACCESS
6ATN1-76
PENTHOUSE
NO.4
ELEVATOR
6ATN3-76
6HA6-76 6ATN5-76
6H A7
-7
6ATN4-76
6HA2-76 446 SF
7 S
F
DATA CLOSET
6HA4-76
615R 615A
UTIL.FH
TELE. CLOS. CLOS.
ELEV. NO.3
611A
ELEV. NO.2DIRTY UTL.
UP
CS-6/76
626 624
623A
624A
622 621 620
LINEN
HAC
617A617 616A
CLEAN
RESTROOM
195 SF
85 SF
189 SF
170 SF
147 SF
CORRIDOR
6HA3-76
125 SF
TOILET
66 SF
250 SF
109 SF
37 SF
23 SF
362 SF
409 SF
336 SF
224 SF 219 SF
272 SF 80 SF
186 SF
22 SF
229 SF366 SF
302 SF
115 SF
665 SF
GROUP ROOM
SPACE
PROVIDER OFF.
OFFICE MNGR.
OFFICE
STORAGE
MED RM
NURSES STATION
227 SF
13 SF 19 SF
BREAKRM.
STORAGE
PATIENT RM.
LAUNDRY CHUTE ELECTRICAL CLOSET
PATIENT RM.
PATIENT RM.
PATIENT RM. PATIENT RM. PATIENT RM.
3'-0"
CENTERED ON
WINDOW BELOW
CUT AND REMOVE EXISTING
BRICK WALL WITH CMU
BACKUP TO
ACCOMMODATE NEW
LOUVER. PROVIDE NEW
STL. LINTEL., REFER TO
LINTEL SCHEDULE.
DEMO EXISTING METAL STUD AND
GYP BD WALL CONSTRUCTION
REFER TO STRUCTURAL AND MECHANICAL
FOR EXTENT OF FLOOR REMOVAL
DEMO ACT CEILING
DEMOLISH WINDOW AND REPAIR OPENING TO
RECEIVE LOUVER
REFER TO STRUCTURAL AND
MECHANICAL FOR EXTENT OF
FLOOR REMOVAL
REFER TO STRUCTURAL AND
MECHANICAL FOR EXTENT OF
FLOOR REMOVAL
REFER TO STRUCTURAL AND
MECHANICAL FOR EXTENT OF
FLOOR REMOVAL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
ARCHITECTURAL DEMOLITION -
SIXTH FLOOR NORTH
AD-107
EWW LMR
SCALE: 1/8" = 1'-0"
ARCHITECTURAL DEMOLITION PLAN - SIXTH FLOOR NORTH
A1
GENERAL NOTE:
SMOKE DETECTORS, SPRINKLERS AND DIFFUSERS TO BE
INDEPENDENTLY SUPPORTED AND PROTECTED DURING
CEILING REMOVAL, AND REINSTALLED IN NEW CEILING GRID.
AutoCAD SHX Text
6ATN2-76
AutoCAD SHX Text D.F.
7ATC1-76
7ATC2-76
DEMO EXISTING PLYWOOD DUCT CHASE
CUT AND REMOVE EXISTING BRICK
WALL WITH CMU BACKUP TO
ACCOMMODATE NEW LOUVER.
PROVIDE NEW STL. LINTEL., REFER
TO LINTEL SCHEDULE. COORDINATE
WITH MECHANICAL CONTRACTOR.
DEMO EXISTING WINDOW AND
LOUVER IN DORMERS. PREPARE
OPENINGS TO RECEIVE NEW
LOUVERS. TO BE COORDINATED
WITH MECHANICAL CONTRACTOR.
SEE STRUCTURAL DRAWINGS FOR EXTENT OF FLOOR DEMOLITION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
P
M
100% SUBMISSION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Watson Engineering 1112 State Route 434 Owego, NY 13827 (607)223-4334
Electrical Consultant C&S Companies 499 Col Eileen Collins Blvd Syracuse, NY 13212 (315)455-2000
UPGRADE VENTILATION B-76
BATH VAMC, BATH, NY
528A6-17-627
BUILDING 76
Project Director
7/8/2020Revisions: Date:
Asbestos Consultant ECS Mid-Atlantic, LLC 4507 Metropolitan Ct Frederick, MD 21704 (301)668-4303
Cost Estimating Trophy Point 4588 South Park Ave Buffalo, NY 14219 (716)823-0006
ARCHITECTURAL DEMOLITION PLAN -
ATTIC
AD-108
EWW LMR
SCALE: 1/8" = 1'-0"
ARCHITECTURAL PLAN - ATTIC
A1
125 SF
131 SF
238 SF
5 S
F
AUDIOLOGY WTG/RECEPTION
2H
A2 -7
170 SF
248 SF
92 SF
5 S
F
205 204
2HA4-76
DATA CLOSET
GOSINK
101 SF110 SF130 SF
101 SF
PUBLIC AFFAIRS
SPCH. PATHOLOGIST
VACANTEEO SPEC.
A-101
A3
AUDIOLOGY WTG/RECEPTION
170 SF
248 SF
92 SF
2HA4-76
SPCH. PATHOLOGIST
FLOOR PENETRATION ABOVE,
REFER TO MECHANICAL AND
STRUCTURAL (FOR FUTURE
DUCTWORK)
GENERAL NOTE:
SMOKE DETECTORS, SPRINKLERS AND DIFFUSERS TO BE
INDEPENDENTLY SUPPORTED AND PROTECTED DURING
CEILING REMOVAL, AND REINSTALLED IN NEW CEILING GRID.
A-101
B1
EXISTING WINDOW
OPENING
NEW 4" BRICK VENEER TO
MATCH EXISTING,
RECESS 2" FROM
FACE OF EXISTING
STONE SILL
STONE SILL TO REMAIN
EXISTING BRICK
A-101
A2
METAL C-H (OR E) STUDS 24" OC WITH
TOP DEFLECTION
(2) LAYERS 5/8" TYPE X GYP BD
M
I N
1" GYP BD LINER
PANEL
FIRE STOP AND SEALANT AT
RATED
WALLS
SCHEDULED
CEILING
2 HR RATING - UL DESIGN U497
TYPE MATERIAL DEPTH STUD
FIRE
RATING
UNBRACED
HEIGHT
DESCRIPTION
MD-3 GWB 4-3/4" 2-1/2" 2 HR - -
SCHEDULED
FLOOR/BASE
J-TRACK
J-TRACK
PAINT, MATCH EXISTING
MD
THROUGH WALL FLASHING AND WEEPS
4" BRICK VENEER TO MATCH EXISTING
6" CMU WITH INSULATED CORES
METAL LATH & PLASTER TO
MATCH EXISTING, WHERE
EXPOSED IN OCCUPIED ROOM
2"
EXISTING STONE SILL
EXISTING WALL CONSTRUCTION,
BRICK WITH CMU BACKUP
EXISTING…