RTU Specs.pdf
PDF 102 KB Posted
- Attached to
- The Oregon Military Museum HVAC Upgrades
- Solicitation number
- S-24800-00006663
- Issued by
- Clackamas County, Oregon
About this file
The document is a set of technical specifications for packaged rooftop units (RTUs) and outdoor air handling units as part of a state and local contract opportunity for The Oregon Military Museum HVAC Upgrades project. The project involves replacing five existing AHU and RTU units with new units that have humidification and dehumidification capabilities for the benefit of the Oregon Military Department (OMD). The specifications cover requirements for the RTUs including refrigeration systems, supply and exhaust fans, cooling coils, controls, and accessories. The contract opportunity is open to the state of Oregon, specifically Clackamas County.
The technical specifications do not include details on pricing, set asides, incumbents, funding sources, or other commercial terms. The focus is on the technical requirements and capabilities of the RTU and outdoor air handling units to be provided under this contract opportunity.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Guide Specifications - Rooftop Units
- Packaged Rooftop Units / Outdoor Air Handling Units
Part 1 - General
1.01 Related Documents
1.02 General Description
A. This section includes the design, controls and installation requirements for packaged rooftop units / outdoor air handling units.
1.03 Quality Assurance
A. Packaged air-cooled condenser units shall be certified in accordance with
ANSI/AHRI Standard 340/360 performance rating of commercial and industrial unitary air-conditioning and heat pump equipment.
B. Unit shall be certified in accordance with UL Standard 1995/CSA C22.2 No. 236, Safety Standard for Heating and Cooling Equipment.
C. Unit and refrigeration system shall comply with ASHRAE 15, Safety Standard for
Mechanical Refrigeration.
D. Unit shall be certified in accordance with ANSI Z21.47b/CSA 2.3b and ANSI
Z83.8/CSA 2.6, Safety Standard Gas-Fired Furnaces.
E. Unit Energy Efficiency Ratio (EER) shall be equal to or greater that prescribed by
ASHRAE 90.1, Energy Efficient Design of New Buildings except Low-Rise
Residential Buildings.
F. Unit shall be safety certified by ETL and ETL US listed. Unit nameplate shall include the ETL/ETL Canada label.
1.04 Submittals
A. Product Data: Literature shall be provided that indicates dimensions, operating and shipping weights, capacities, ratings, fan performance, filter information, factory supplied accessories, electrical characteristics and connection requirements.
Installation, Operation, and Maintenance manual with startup requirements shall be provided.
B. Shop Drawings: Unit drawings shall be provided that indicate assembly, unit dimensions, construction details, clearances and connection details. Computer generated fan curves for each fan shall be submitted with specific design operation point noted. Wiring diagram shall be provided with details for both power and control systems and differentiate between factory installed and field installed wiring.
1.05 Delivery, Storage, and Handling
A. Unit shall be shipped with doors screwed shut and outside air hood closed to prevent damage during transport and thereafter while in storage awaiting installation.
B. Follow Installation, Operation, and Maintenance manual instructions for rigging, moving, and unloading the unit at its final location.
C. Unit shall be stored in a clean, dry place protected from construction traffic in accordance with the Installation, Operation, and Maintenance manual.
1.06 Warranty
A. Manufacturer shall provide a limited “parts only” warranty for a period of 12 months from the date of equipment startup or 18 months from the date of original equipment shipment from the factory, whichever is less. Warranty shall cover material and workmanship that prove defective, within the specified warranty period, provided manufacturer’s written instructions for Installation, Operation, and maintenance have been followed. Warranty excludes parts associated with routine maintenance, such as belts and filters.
Part 2 - Products
2.01 Manufacturer
A. Products shall be provided by the following manufacturers:
1. AAON, Or approved equal.
2. Substitute equipment may be considered for approval that includes at a minimum:
a. R-410A refrigerant
b. Variable capacity compressor with 10-100% capacity control
c. Direct drive supply fans
d. Double wall cabinet construction
e. Insulation with a minimum R-value of 13
f. Stainless steel drain pans
2.02 Rooftop Units
A. General Description
1. Packaged rooftop unit shall include compressors, evaporator coils, filters, supply fans, dampers, air-cooled condenser coils, condenser fans, reheat coil, gas heaters, exhaust fans, and unit controls.
2. Outdoor air handling unit shall include filters, supply fans, dampers, DX evaporator coils, exhaust fans, and unit controls.
3. Unit shall be factory assembled and tested including leak testing of the DX coils, pressure testing of the refrigeration circuit, and run testing of the completed unit.
Run test report shall be supplied with the unit in the service compartment’s literature pocket.
4. Unit shall have decals and tags to indicate lifting and rigging, service areas and caution areas for safety and to assist service personnel.
5. Unit components shall be labeled, including refrigeration system components, and electrical and controls components.
6. Estimated sound power levels (dB) shall be shown on the unit ratings sheet.
7. Installation, Operation, and Maintenance manual shall be supplied within the unit.
8. Laminated color-coded wiring diagram shall match factory installed wiring and shall be affixed to the interior of the control compartment’s hinged access door.
9. Unit nameplate shall be provided in two locations on the unit, affixed to the exterior of the unit and affixed to the interior of the control compartment’s hinged access door.
B. Construction
1. All cabinet walls, access doors, and roof shall be fabricated of double wall, impact resistant, rigid polyurethane foam panels.
2. Unit insulation shall have a minimum thermal resistance R-value of 13. Foam insulation shall have a minimum density of 2 pounds/cubic foot and shall be tested in accordance with ASTM D1929-11 for a minimum flash ignition temperature of 610°F.
3. Unit construction shall be double wall with G90 galvanized steel on both sides and a thermal break. Double wall construction with a thermal break prevents moisture accumulation on the insulation, provides a cleanable interior, reduces heat transfer through the panel, and prevents exterior condensation on the panel.
4. Unit shall be designed to reduce air leakage and infiltration through the cabinet.
Cabinet leakage shall not exceed 1% of total airflow when tested at 3 times the minimum external static pressure provided in AHRI Standard 340/360. Panel deflection shall not exceed L/240 ratio at 125% of design static pressure, at a maximum 8 inches of positive or negative static pressure, to reduce air leakage.
Deflection shall be measured at the midpoint of the panel height and width.
Continuous sealing shall be included between panels and between access doors and openings to reduce air leakage. Piping and electrical conduit through cabinet panels shall include sealing to reduce air leakage.
5. Roof of the air tunnel shall be sloped to provide complete drainage. Cabinet shall have rain break overhangs above access doors.
6. Access to filters, dampers, cooling coils, reheat coil, heaters, compressors, and electrical and controls components shall be through hinged access doors with quarter turn, zinc cast, lockable handles. Full length stainless steel piano hinges shall be included on the doors.
7. Exterior paint finish shall be capable of withstanding at least 2,500 hours, with no visible corrosive effects, when tested in a salt spray and fog atmosphere in accordance with ASTM B 117-95 test procedure.
8. Units with cooling coils shall include double sloped 304 stainless steel drain pans.
9. Unit shall be provided with base discharge and return air openings. All openings through the base pan of the unit shall have upturned flanges of at least 1/2 inch in height around the opening.
10. Unit shall include lifting lugs on the top of the unit.
11. Unit base shall be fabricated of 1 inch thick double wall, impact resistant, rigid polyurethane foam panels.
C. Electrical
1. Unit shall have a 5kAIC SCCR.
2. Unit shall be provided with factory installed and factory wired, non-fused disconnect switch.
3. Unit shall be provided with phase and brown out protection which shuts down all motors in the unit if the electrical phases are more than 10% out of balance on voltage, the voltage is more than 10% under design voltage or on phase reversal.
D. Supply Fans
1. Unit shall include direct drive, unhoused, backward curved, plenum supply fans.
2. Blowers and motors shall be dynamically balance and mounted on rubber isolators.
3. Motors shall be premium efficiency ODP with ball bearings rated for 200,000 hours service with external lubrication points.
4. Variable frequency drives shall be factory wired and mounted in the unit. Fan motors shall be premium efficiency.
5. Motors shall be premium efficiency ODP with ball bearings rated for 200,000 hours service with external lubrication points.
6. Variable frequency drives shall be factory wired and mounted in the unit.
E. Exhaust Fans
1. Exhaust dampers shall be sized for 100% relief.
2. Fans and motors shall be dynamically balanced.
3. Unit shall include barometric relief dampers.
4. Motors shall be premium efficiency ODP with ball bearings rated for 200,000 hours service with external lubrication points.
5. Motors shall be premium efficiency ODP with ball bearings rated for 200,000 hours service with external lubrication points.
6. Access to exhaust fans shall be through double wall, hinged access doors with quarter turn lockable handles.
7. Variable frequency drives shall be factory wired and mounted in the unit. Fan motors shall be premium efficiency.
8. Unit shall include direct drive, axial flow exhaust fans. Blades shall be adjustable pitch.
9. Variable frequency drives shall be factory wired and mounted in the unit.
F. Cooling Coils
1. Evaporator Coils
a. Coils shall be designed for use with R-410A refrigerant and constructed of copper tubes with aluminum fins mechanically bonded to the tubes and galvanized steel end casings. Fin design shall be sine wave rippled.
b. Coil shall be standard capacity.
c. Coils shall have interlaced circuitry and shall be standard capacity.
d. Coils shall be 6 row high capacity.
e. Coils shall be hydrogen or helium leak tested.
f. Coils shall be furnished with factory installed expansion valves.
G. Refrigeration System
1. Unit shall be factory charged with R-410A refrigerant.
2. Compressors shall be scroll type with thermal overload protection and carry a 5 year non-prorated warranty, from the date of original equipment shipment from the factory.
3. Compressors shall be mounted in an isolated service compartment which can be accessed without affecting unit operation. Lockable hinged compressor access doors shall be fabricated of double wall, rigid polyurethane foam injected panels to prevent the transmission of noise outside the cabinet.
4. Compressors shall be isolated from the base pan with the compressor manufacturer’s recommended rubber vibration isolators, to reduce any transmission of noise from the compressors into the building area.
5. Each refrigeration circuit shall be equipped with expansion valve type refrigerant flow control.
6. Each refrigeration circuit shall be equipped with automatic reset low pressure and manual reset high pressure refrigerant safety controls, Schrader type service fittings on both the high pressure and low pressure sides and a factory installed liquid line filter driers.
7. Unit shall include a variable capacity scroll compressor on the refrigeration circuit which shall be capable of modulation from 10-100% of its capacity.
8. Unit shall include a variable capacity scroll compressor on the lead refrigeration circuit which shall be capable of modulation from 10-100% of its capacity and a two-stage compressor on the lag circuit that shall modulate between two capacity settings, 67% and 100%.
9. Refrigeration circuit shall be provided with hot gas reheat coil, modulating valves, electronic controller, supply air temperature sensor and a control signal terminal which allow the unit to have a dehumidification mode of operation, which includes supply air temperature control to prevent supply air temperature swings and overcooling of the space.
10. Lead refrigeration circuit shall be provided with hot gas reheat coil, modulating valves, electronic controller, supply air temperature sensor and a control signal terminal which allow the unit to have a dehumidification mode of operation, which includes supply air temperature control to prevent supply air temperature swings and overcooling of the space.
11. Unit shall be provided with a fixed 55F compressor lockout.
H. Condensers
1. Air-Cooled Condenser
a. Condenser fans shall be a vertical discharge, axial flow, direct drive fans.
b. Coils shall be designed for use with R-410A refrigerant. Coils shall be multi-pass and fabricated from aluminum microchannel tubes.
c. Coils shall be designed for a minimum of 10°F of refrigerant sub-cooling.
d. Coils shall be hydrogen or helium leak tested.
e. Condenser fans shall be high efficiency electrically commutated motor driven with factory installed head pressure control module. Condenser airflow shall continuously modulate based on head pressure and cooling operation shall be allowed down to 35°F with adjustable compressor lockout.
I. Gas Heating
1. Stainless steel heat exchanger furnace shall carry a 25 year non-prorated warranty, from the date of original equipment shipment from the factory.
2. Gas furnace shall consist of stainless steel heat exchangers with multiple concavities, an induced draft blower and an electronic pressure switch to lockout the gas valve until the combustion chamber is purged and combustion airflow is established.
3. Furnace shall include a gas ignition system consisting of an electronic igniter to a pilot system, which will be continuous when the heater is operating, but will shut off the pilot when heating is not required.
4. Unit shall include a single gas connection and have gas supply piping entrances in the unit base for through-the-curb gas piping and in the outside cabinet wall for across the roof gas piping.
5. Modulating Natural Gas Furnace shall be equipped with modulating gas valves, adjustable speed combustion blowers, stainless steel tubular heat exchangers, and electronic controller. Combustion blowers and gas valves shall be capable of modulation. Electronic controller includes a factory wired, field installed supply air temperature sensor. Sensor shall be field installed in the supply air ductwork.
Supply air temperature setpoint shall be adjustable on the electronic controller within the control compartment. Gas heater shall be capable of capacity turndown ratio as shown on the unit rating sheet.
J. Filters
1. Unit shall include 2 inch thick, pleated panel filters with an ASHRAE MERV rating of 8, upstream of the cooling coil.
2. Unit shall include 1 inch aluminum mesh pre filters upstream of the outside air opening.
3. Unit shall include a clogged filter switch.
4. Unit shall include a Magnehelic gauge mounted in the controls compartment.
K. Outside Air/Economizer
1. Unit shall include 0-100% economizer consisting of a motor operated outside air damper and return air damper assembly constructed of extruded aluminum, hollow core, airfoil blades with rubber edge seals and aluminum end seals.
Damper blades shall be gear driven and designed to have no more than 20 cfm of leakage per sq ft. at 4 in. w.g. air pressure differential across the damper. Low leakage dampers shall be Class 2 AMCA certified, in accordance with AMCA
Standard 511. Damper assembly shall be controlled by spring return DDC actuator. Unit shall include outside air opening bird screen, outside air hood, and relief dampers.
L. Controls
1. Field Installed DDC Controls by Others
a. Unit shall be provided with a terminal block for field installation of DDC controls.
M. Accessories
1. Unit shall be provided with a smoke detector sensing the return air of the unit, wired to shut off the unit’s control circuit.
2. Unit shall be provided with a safety shutdown terminal block for field installation of a smoke detector which shuts off the unit's control circuit.
2.03 Curbs
A. [Curbs shall to be fully gasketed between the curb top and unit bottom with the curb providing full perimeter support, cross structure support and air seal for the unit. Curb gasket shall be furnished within the control compartment of the rooftop unit to be mounted on the curb immediately before mounting of the rooftop unit.]
B. [Knockdown curb (with duct support rails) shall be factory furnished for field assembly.]
C. [Solid bottom curb shall be factory assembled and fully lined with curb rated 1 inch fiberglass insulation and include a wood nailer strip. (Curb shall be adjustable up to 3/4 inch per foot to allow for sloped roof applications.)]
Part 3 - Execution
3.01 Installation, Operation, and Maintenance
A. Installation, Operation, and Maintenance manual shall be supplied with the unit.
B. Installing contractor shall install unit, including field installed components, in accordance with Installation, Operation, and Maintenance manual instructions.
C. Start up and maintenance requirements shall be complied with to ensure safe and correct operation of the unit.