RTA DRAWINGS VOL2 of 4.pdf
PDF 30 MB Posted
- Solicitation number
- W9127821R0050
About this file
This document provides details for a federal contract solicitation to construct facilities at Hurlburt Field, Florida. The solicitation is for the construction of a Special Tactics Operations Facility totaling 103,700 square feet, including administrative areas, team rooms, equipment and vehicle maintenance and storage, a covered storage area, rappelling tower, and antenna platform. The project scope includes site utilities and improvements, pavements, communications, force protection measures, and demolition of existing buildings. The facility must meet high performance and sustainable building requirements in accordance with federal laws and executive orders, and incorporate low impact development features and anti-terrorism/force protection measures compliant with DoD standards. The proposed construction duration is 900 calendar days. The solicitation is issued by the Department of the Army Corps of Engineers Engineering District Mobile.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US Army Corps of Engineers®
MOBILE DISTRICT
109 SAINT JOSEPH STREET
MOBILE, AL 36602
SOF SPECIAL TACTICS OPERATIONS FACILITY (23STS)
FTEV103005
HURLBURT FIELD
20 1
Y21001 21R 50
VOLUME 4 OF 4
PAUL
RE
S
E G
SI T
R
A
T
E T
A
I
ADE CR
H
KRIMMEL
TRAVIS
C
E T
T
B
FO LA A
M
A
S o lic it a ti o n
N u m b e r:
I.
S
.O
S h e e t
F ile
N a m e
IDENTIFICATION
SHEET
R e v ie w e d
B y
D ra w n
B y
D e s ig n e d
B y
C h e c k e d
B y
D a te
F ile
N o
S y m b o l D e s c ri p ti o n
R e v is io n s
A p p ro v e d D a te
N o
US Army Corps of Engineers Mobile District
A
B C D
A B C D
E F G H I
E F G
H I
SHEET of
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
C O
R P
S O
F E
N G
IN
E
E R
S M
O B
IL
E
A
L A
B A
M A
W -2
-R
-0
M E
Y
J
U N
E
K C
H
IL
D S
/2
/2
:2
:1
A M
C
U s e rs \K e v in
.C h ild s \D o c u m e n ts \1
S
T S
O P
S H u rl b u rt
K e v in
.C h ild s s s a in c .c o m
.r v t
G-002
IN
D
E X
O F
D R
A W
IN
G
S
T K
R
IM
M E
L
T K
R
IM
M E
L
K C
H
IL
D S
S O
F S
P E
C
IA
L T
A C
T
IC
S O
P E
R A
T
IO
N S
F A
C
IL
IT
Y
H U
R L B
U R
T F
IE
L D
F
L
INDEX OF DRAWINGS
VOLUME 1 OF 4
SHEET
NO. SHEET DESCRIPTION
SHEET
NO. SHEET DESCRIPTION
CE102 INITIAL EROSION & SEDIMENT CONTROL PLAN
CE103 INITIAL EROSION & SEDIMENT CONTROL PLAN
CE104 INITIAL EROSION & SEDIMENT CONTROL PLAN
CE105 INITIAL EROSION & SEDIMENT CONTROL PLAN
CE106 INITIAL EROSION & SEDIMENT CONTROL PLAN
CE107 INITIAL EROSION & SEDIMENT CONTROL PLAN
CE108 INITIAL EROSION & SEDIMENT CONTROL PLAN
CE109 INTERMEDIATE EROSION & SEDIMENT CONTROL PLAN
CE110 INTERMEDIATE EROSION & SEDIMENT CONTROL PLAN
CE111 INTERMEDIATE EROSION & SEDIMENT CONTROL PLAN
CE112 INTERMEDIATE EROSION & SEDIMENT CONTROL PLAN
CE113 INTERMEDIATE EROSION & SEDIMENT CONTROL PLAN
CE114 INTERMEDIATE EROSION & SEDIMENT CONTROL PLAN
CE115 INTERMEDIATE EROSION & SEDIMENT CONTROL PLAN
CE116 INTERMEDIATE EROSION & SEDIMENT CONTROL PLAN
CE117 FINAL EROSION & SEDIMENT CONTROL PLAN
CE118 FINAL EROSION & SEDIMENT CONTROL PLAN
CE119 FINAL EROSION & SEDIMENT CONTROL PLAN
CE120 FINAL EROSION & SEDIMENT CONTROL PLAN
CE121 FINAL EROSION & SEDIMENT CONTROL PLAN
CE122 FINAL EROSION & SEDIMENT CONTROL PLAN
CE123 FINAL EROSION & SEDIMENT CONTROL PLAN
CE124 FINAL EROSION & SEDIMENT CONTROL PLAN
CE501 EROSION & SEDIMENT CONTROL DETAILS
CU001 OVERALL SITE UTILITY PLAN
CU101 SITE UTILITY LAYOUT PLAN
CU102 SITE UTILITY LAYOUT PLAN
CU103 SITE UTILITY LAYOUT PLAN
CU104 SITE UTILITY LAYOUT PLAN
CU105 SITE UTILITY LAYOUT PLAN
CU106 SITE UTILITY LAYOUT PLAN
CU107 SITE UTILITY LAYOUT PLAN
CU108 SITE UTILITY LAYOUT PLAN
CU109 HDD PLAN FOR COMMUNICATION BANK
CU201 STORM SEWER PROFILES
CU202 STORM SEWER PROFILES
CU203 STORM SEWER PROFILES
CU204 STORM SEWER PROFILES
CU205 SANITARY SEWER PROFILES
CU206 SANITARY SEWER PROFILES
CU207 SANITARY SEWER PROFILES
CU403 ADDITIVE ITEM NO 1 SITE UTILITY PLAN
CU404 ADDITIVE ITEM NO 4 & 5 SITE UTILITY PLAN
CU501 UTILITY DETAILS
CU502 UTILITY DETAILS
CU503 UTILITY DETAILS
CU504 SANITARY LIFT STATION DETAILS
CU505 SANITARY LIFT STATION DETAILS
CU506 SANITARY LIFT STATION DETAILS
CU507 UTILITY DETAILS
CU508 GREASE TRAP & DUMP STATION DETAIL
CU509 WASH RACK DETAILS
CU510 WASH RACK DETAILS
CU511 WASH RACK DETAILS
CU512 WASH RACK DETAILS
CU513 WASH RACK DETAILS
CU514 WASH RACK DETAILS
CU515 WASH RACK DETAILS
CU516 WASH RACK DETAILS
CU517 WASH RACK PERFORMANCE SPECIFICATIONS
04 - LANDSCAPE
L-001 LANDSCAPE NOTES & LEGEND
LP001 OVERALL LANDSCAPE PLANTING PLAN
LP101 LANDSCAPE PLANTING PLAN
LP102 LANDSCAPE PLANTING PLAN
LP103 LANDSCAPE PLANTING PLAN
LP104 LANDSCAPE PLANTING PLAN
LP105 LANDSCAPE PLANTING PLAN
LP106 LANDSCAPE PLANTING PLAN
LP107 LANDSCAPE PLANTING PLAN
LP108 LANDSCAPE PLANTING PLAN
LP401 LANDSCAPE PLANTING PLAN - ADDITIVE ITEM NO 1
LP402 LANDSCAPE PLANTING PLAN - ADDITIVE ITEM NO 5
LP501 LANDSCAPE PLANTING DETAILS
LS401 ENTRY PLAZA PAVING PLAN
LS501 LANDSCAPE SITE DETAILS
SHEET
NO. SHEET DESCRIPTION
01 - GENERAL
G-001 COVER SHEET
G-002 INDEX OF DRAWINGS
G-003 INDEX OF DRAWINGS
03 - CIVIL
C-001 SITE VICINITY MAP & PROJECT LOCATION MAP
C-002 GENERAL NOTES
C-003 GENERAL NOTES ABBREVIATIONS & LEGEND
VF001 OVERALL EXISTING SITE CONDITIONS PLAN
VF101 EXISTING SITE CONDITIONS PLAN
VF102 EXISTING SITE CONDITIONS PLAN
VF103 EXISTING SITE CONDITIONS PLAN
VF104 EXISTING SITE CONDITIONS PLAN
VF105 EXISTING SITE CONDITIONS PLAN
VF106 EXISTING SITE CONDITIONS PLAN
VF107 EXISTING SITE CONDITIONS PLAN
VF108 EXISTING SITE CONDITIONS PLAN
CD001 OVERALL SITE DEMOLITION PLAN
CD101 SITE DEMOLITION PLAN
CD102 SITE DEMOLITION PLAN
CD103 SITE DEMOLITION PLAN
CD104 SITE DEMOLITION PLAN
CD105 SITE DEMOLITION PLAN
CD106 SITE DEMOLITION PLAN
CD107 SITE DEMOLITION PLAN
CD108 SITE DEMOLITION PLAN
CD501 SITE DEMOLITION DETAILS
CS001 OVERALL SITE LAYOUT PLAN
CS101 SITE LAYOUT PLAN
CS102 SITE LAYOUT PLAN
CS103 SITE LAYOUT PLAN
CS104 SITE LAYOUT PLAN
CS105 SITE LAYOUT PLAN
CS106 SITE LAYOUT PLAN
CS107 SITE LAYOUT PLAN
CS108 SITE LAYOUT PLAN
CS201 ACCESS ROAD PROFILES
CS202 JOINTING PLAN
CS203 ACCESS ROAD PROFILES
CS401 RIGID PAVEMENT JOINTING PLAN
CS402 RIGID PAVEMENT JOINTING PLAN
CS403 ADDITIVE ITEM NO 1 SITE LAYOUT PLAN
CS404 ADDITIVE ITEM NO 4 & 5 SITE LAYOUT PLAN
CS501 MISCELLANEOUS SITE DETAILS
CS502 RIGID PAVEMENT DETAILS
CS503 MISCELLANEOUS SITE DETAILS
CS504 MISCELLANEOUS SITE DETAILS
CS505 HANDICAPPED PARKING DETAILS
CS506 FENCE DETAILS
CS507 VERTICAL PIVOT GATE DETAIL
CS508 ACCESS DRIVES CROSS SECTIONS
CS509 ACCESS DRIVES CROSS SECTIONS
CG001 OVERALL SITE GRADING AND DRAINAGE PLAN
CG101 SITE GRADING AND DRAINAGE PLAN
CG102 SITE GRADING AND DRAINAGE PLAN
CG103 SITE GRADING AND DRAINAGE PLAN
CG104 SITE GRADING AND DRAINAGE PLAN
CG105 SITE GRADING AND DRAINAGE PLAN
CG106 SITE GRADING AND DRAINAGE PLAN
CG107 SITE GRADING AND DRAINAGE PLAN
CG108 SITE GRADING AND DRAINAGE PLAN
CG401 RIGID PAVEMENT JOINTING PLAN GRADES
CG402 RIGID PAVEMENT JOINTING PLAN GRADES
CG403 ADDITIVE ITEM NO 1 SITE GRADING PLAN
CG404 ADDITIVE ITEM NO 4 & 5 SITE GRADING PLAN
CG405 RIGID PAVEMENT JOINTING PLAN - ADDITIVE ITEM NO 1
CG501 MISCELLANEOUS STORM SEWER DETAILS
CG502 MISCELLANEOUS STORM SEWER DETAILS
CG503 DETENTION BASIN DETAILS
CG504 DETENTION BASIN DETAILS
CG505 DETENTION BASIN DETAILS
CG506 DETENTION BASIN DETAILS
CE001 OVERALL EROSION & SEDIMENT CONTROL PLAN
CE002 EROSION & SEDIMENT CONTROL NOTES AND LEGEND SHEET
CE101 INITIAL EROSION & SEDIMENT CONTROL PLAN
SHEET
NO. SHEET DESCRIPTION
A-610 DOOR DETAILS
A-611 DOOR DETAILS
A-612 ARMORY PASS - THRU DETAILS
A-620 WINDOW TYPES
A-621 WINDOW DETAILS
A-622 WINDOW DETAILS
A-623 WINDOW DETAILS
A-630 LOUVER TYPES & DETAILS
A-640 VIEW PANEL & COUNTER SHUTTER TYPES & DETAILS
A-660 FINISH SCHEDULE
A-661 FINISH SCHEDULE LEGEND
A-680 EQUIPMENT SCHEDULE
A-701 ENLARGED ELEVATOR & STAIR 1 PLANS
A-702 ENLARGED STAIR 2 & 3 PLANS
A-710 ELEVATOR & STAIR 1 SECTIONS
A-711 STAIR 1 SECTIONS & DETAILS
A-712 STAIR 2 SECTIONS
A-713 STAIR 3 SECTIONS
A-720 STAIR DETAILS
A-721 ELEVATOR DETAILS
A-812 FIRST FLOOR RCP - BLOCK 1A
A-813 FIRST FLOOR RCP - BLOCK 1B
A-814 FIRST FLOOR RCP - BLOCK 1C
A-815 FIRST FLOOR RCP - BLOCK 1D
A-816 FIRST FLOOR RCP - BLOCK 1F
A-817 FIRST FLOOR RCP - BLOCK 1G
A-822 SECOND FLOOR RCP - BLOCK 2A
A-823 SECOND FLOOR RCP - BLOCK 2B
AF111 FLOOR PATTERN PLAN - FIRST FLOOR - COMPOSITE
AF112 FLOOR PATTERN PLAN - BLOCK 1A
AF113 FLOOR PATTERN PLAN - BLOCK 1B
AF114 FLOOR PATTERN PLAN - BLOCK 1C
AF115 FLOOR PATTERN PLAN - BLOCK 1D
AF116 FLOOR PATTERN PLAN - BLOCK 1F
AF117 FLOOR PATTERN PLAN - BLOCK 1G
AF118 FLOOR PATTERN PLAN - SECOND FLOOR - COMPOSITE
AF119 FLOOR PATTERN PLAN - BLOCK 2A
AF120 FLOOR PATTERN PLAN - BLOCK 2B
AG111 1ST FLOOR SIGNAGE PLAN
AG131 2ND FLOOR SIGNAGE PLAN
AG601 SIGN TYPES / SIGN DETAILS
AG602 SIGN MESSAGE SCHEDULE / SIGN TYPES
SHEET
NO. SHEET DESCRIPTION
S-606 COLUMN PEDESTAL DETAILS
S-607 COLUMN PEDESTAL DETAILS
06 - ARCHITECTURAL
A-001 ABBREVIATIONS & SYMBOLS
A-002 AIR BARRIER PLANS
A-003 AIR BARRIER SECTIONS
A-111 COMPOSITE FIRST FLOOR PLAN
A-112 FIRST FLOOR PLAN - BLOCK 1A
A-113 FIRST FLOOR PLAN - BLOCK 1B
A-114 FIRST FLOOR PLAN - BLOCK 1C
A-115 FIRST FLOOR PLAN - BLOCK 1D
A-116 FIRST FLOOR PLAN - BLOCK 1F
A-117 FIRST FLOOR PLAN - BLOCK 1G
A-121 COMPOSITE SECOND FLOOR PLAN
A-122 SECOND FLOOR PLAN - BLOCK 2A
A-123 SECOND FLOOR PLAN - BLOCK 2B
A-151 ROOF PLAN - COMPOSITE
A-201 EXTERIOR ELEVATIONS
A-202 EXTERIOR ELEVATIONS
A-210 ENLARGED EXTERIOR ELEVATIONS
A-301 BUILDING SECTIONS
A-302 BUILDING SECTIONS
A-310 WALL SECTIONS
A-311 WALL SECTIONS
A-312 WALL SECTIONS
A-313 WALL SECTIONS
A-314 WALL SECTIONS
A-315 WALL SECTIONS
A-316 WALL SECTIONS
A-317 WALL SECTIONS
A-320 ENTRANCE CANOPY PLANS & DETAILS
A-321 ENTRANCE CANOPY SECTIONS
A-401 EQUIPMENT MOUNTING HEIGHTS & DETAILS
A-402 EQUIPMENT MOUNTING DETAILS
A-410 ENLARGED WET AREA PLANS & ELEVATIONS
A-411 ENLARGED WET AREA PLANS & ELEVATIONS
A-412 ENLARGED WET AREA PLANS & ELEVATIONS
A-413 ENLARGED WET AREA PLANS & ELEVATIONS
A-414 ENLARGED WET AREA PLANS & ELEVATIONS
A-415 ENLARGED WET AREA PLANS & ELEVATIONS
A-416 ENLARGED WET AREA PLANS & ELEVATIONS
A-430 ENLARGED PLANS & CASEWORK ELEVATIONS
A-435 CASEWORK DETAILS
A-440 INTERIOR ELEVATIONS
A-441 INTERIOR ELEVATIONS
A-443 INTERIOR ELEVATIONS
A-444 INTERIOR ELEVATIONS
A-450 ENLARGED WIRE MESH PARTITION PLANS & ELEVATIONS
A-451 ENLARGED WIRE MESH PARTITION PLANS
A-452 ENLARGED WIRE MESH PARTITION ELEVATIONS
A-501 EXTERIOR DETAILS
A-502 EXTERIOR DETAILS
A-503 EXTERIOR DETAILS
A-504 EXTERIOR DETAILS
A-505 EXTERIOR DETAILS
A-506 EXTERIOR DETAILS
A-540 TYPICAL INTERIOR FRAMING DETAILS
A-541 TYPICAL INTERIOR FRAMING DETAILS
A-542 INTERIOR DETAILS
A-543 INTERIOR DETAILS
A-544 INTERIOR DETAILS
A-545 INTERIOR DETAILS
A-550 INTERIOR WALL TYPES
A-551 INTERIOR WALL TYPES
A-552 INTERIOR WALL TYPES
A-553 INTERIOR WALL TYPES
A-554 INTERIOR WALL TYPES
A-560 INTERIOR COLUMN DETAILS
A-561 INTERIOR COLUMN DETAILS
A-562 INTERIOR COLUMN DETAILS
A-563 INTERIOR COLUMN DETAILS
A-601 DOOR SCHEDULE
A-602 DOOR SCHEDULE
A-603 DOOR SCHEDULE
A-605 DOOR, FRAME & THRESHOLD TYPES
SHEET
NO. SHEET DESCRIPTION
05-STRUCTURAL
S-001 GENERAL NOTES
S-002 ABBREVIATIONS & LEGEND
S-003 TYPICAL DETAILS
S-004 TYPICAL DETAILS
S-005 TYPICAL DETAILS
S-006 TYPICAL DETAILS
S-007 TYPICAL DETAILS
S-008 OPEN WEB JOIST UPLIFT DIAGRAM
S-009 TYPICAL DETAILS
S-101 FOUNDATION PLAN - COMPOSITE
S-102 FOUNDATION PLAN - BLOCK 1
S-103 FOUNDATION PLAN - BLOCK 2
S-104 FOUNDATION PLAN - BLOCK 3
S-105 FOUNDATION PLAN - BLOCK 4
S-106 FOUNDATION PLAN - BLOCK 5
S-107 FOUNDATION PLAN - BLOCK 6
S-111 FIRST FLOOR SLAB PLAN - COMPOSITE
S-112 FIRST FLOOR SLAB PLAN - BLOCK 1
S-113 FIRST FLOOR SLAB PLAN - BLOCK 2
S-114 FIRST FLOOR SLAB PLAN - BLOCK 3
S-115 FIRST FLOOR SLAB PLAN - BLOCK 4
S-116 FIRST FLOOR SLAB PLAN - BLOCK 5
S-117 FIRST FLOOR SLAB PLAN - BLOCK 6
S-121 LOW ROOF & SECOND FLOOR FRAMING PLAN - COMPOSITE
S-122 LOW ROOF FRAMING PLAN - BLOCK 1
S-123 LOW ROOF FRAMING PLAN - BLOCK 2
S-124 SECOND FLOOR FRAMING PLAN - BLOCK 3
S-125 SECOND FLOOR FRAMING PLAN - BLOCK 4
S-126 LOW ROOF FRAMING PLAN - BLOCK 5
S-127 LOW ROOF FRAMING PLAN - BLOCK 6 & 7
S-151 HIGH ROOF FRAMING PLAN
S-152 HIGH ROOF FRAMING PLAN
S-201 BRACED FRAME ELEVATIONS
S-202 BRACED FRAME ELEVATIONS
S-301 ELEVATIONS
S-401 ENLARGED PLANS
S-402 ENLARGED PLANS
S-501 DETAILS
S-502 DETAILS
S-503 DETAILS
S-504 DETAILS
S-505 DETAILS
S-506 DETAILS
S-507 DETAILS
S-508 DETAILS
S-511 DETAILS
S-512 DETAILS
S-513 DETAILS
S-514 DETAILS
S-515 DETAILS
S-516 DETAILS
S-517 DETAILS
S-518 DETAILS
S-519 DETAILS
S-520 DETAILS
S-521 DETAILS
S-522 DETAILS
S-523 DETAILS
S-524 DETAILS
S-525 DETAILS
S-526 DETAILS
S-527 DETAILS
S-528 DETAILS
S-529 DETAILS
S-530 DETAILS
S-531 DETAILS
S-532 DETAILS
S-533 DETAILS
S-534 DETAILS
S-601 COLUMN SCHEDULE
S-602 COLUMN SCHEDULE
S-603 COLUMN SCHEDULE
S-604 COLUMN SCHEDULE
S-605 COLUMN SCHEDULE
VOLUME 2 OF 4
PAUL
RE
S
E G
SI T
R
A
T
E T
A
I
ADE CR
H
KRIMMEL
TRAVIS
C
E T
T
B
FO LA A
M
A
S o lic it a ti o n
N u m b e r:
I.
S
.O
S h e e t
F ile
N a m e
IDENTIFICATION
SHEET
R e v ie w e d
B y
D ra w n
B y
D e s ig n e d
B y
C h e c k e d
B y
D a te
F ile
N o
S y m b o l D e s c ri p ti o n
R e v is io n s
A p p ro v e d D a te
N o
US Army Corps of Engineers Mobile District
A
B C D
A B C D
E F G H I
E F G
H I
SHEET of
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
C O
R P
S O
F E
N G
IN
E
E R
S M
O B
IL
E
A
L A
B A
M A
W
8-
-R
-0
M E
Y
J
U N
E
K C
H
IL
D S
/2
/2
:2
:1
A M
C
U s e rs \K e v in
.C h ild s \D o c u m e n ts \1
S
T S
O P
S H u rl b u rt
K e v in
.C h ild s s s a in c .c o m
.r v t
G-003
IN
D
E X
O F
D R
A W
IN
G
S
T K
R
IM
M E
L
T K
R
IM
M E
L
K C
H
IL
D S
S O
F S
P E
C
IA
L T
A C
T
IC
S O
P E
R A
T
IO
N S
F A
C
IL
IT
Y
H U
R L B
U R
T F
IE
L D
F
L
INDEX OF DRAWINGS
VOLUME 3 OF 4 VOLUME 4 OF 4
SHEET
NO. SHEET DESCRIPTION
SHEET
NO. SHEET DESCRIPTION
MH117 MECHANICAL 1ST FLOOR PLAN - BLOCK 1G
MH211 MECHANICAL 2ND FLOOR COMPOSITE PLAN
MH212 MECHANICAL 2ND FLOOR PLAN - BLOCK 2A
MH213 MECHANICAL 2ND FLOOR PLAN - BLOCK 2B
MH311 MECHANICAL HIGH ROOF COMPOSITE PLAN
MP111 HYDRONIC 1ST FLOOR COMPOSITE PLAN
MP112 HYDRONIC 1ST FLOOR PLAN - BLOCK 1A
MP113 HYDRONIC 1ST FLOOR PLAN - BLOCK 1B
MP114 HYDRONIC 1ST FLOOR PLAN - BLOCK 1C
MP115 HYDRONIC 1ST FLOOR PLAN - BLOCK 1D
MP116 HYDRONIC 1ST FLOOR PLAN - BLOCK 1F
MP117 HYDRONIC 1ST FLOOR PLAN - BLOCK 1G
MP211 HYDRONIC 2ND FLOOR COMPOSITE PLAN
MP212 HYDRONIC 2ND FLOOR PLAN - BLOCK 2A
MP213 HYDRONIC 2ND FLOOR PLAN - BLOCK 2B
M-301 SECTIONS
M-302 SECTIONS
M-401 ENLARGED 1A18 MECHANICAL ROOM PLAN
M-402 ENLARGED 1D05 MECHANICAL ROOM PLAN
M-403 ENLARGED 2A29 MECHANICAL ROOM PLAN
M-404 ENLARGED 2A04 MECHANICAL ROOM PLAN
M-405 MECHANICAL EQUIPMENT YARD PLAN
M-601 PIPING / FLOW DIAGRAMS
M-701 DETAILS
M-702 DETAILS
M-703 DETAILS
M-704 DETAILS
M-705 DETAILS
M-706 DETAILS
M-801 SCHEDULES
M-802 SCHEDULES
M-901 CONTROLS
M-902 CONTROLS
M-903 CONTROLS
M-904 CONTROLS
M-905 CONTROLS
M-906 CONTROLS
M-907 CONTROLS
SHEET
NO. SHEET DESCRIPTION
7-PLUMBING
P-001 PLUMBING ABBREVIATIONS
PW101 BELOW SLAB WASTE COMPOSITE PLAN
PW102 BELOW SLAB WASTE PLAN - BLOCK 1A
PW103 BELOW SLAB WASTE PLAN - BLOCK 1B
PW104 BELOW SLAB WASTE PLAN - BLOCK 1C
PW105 BELOW SLAB WASTE PLAN - BLOCK 1D
PW106 BELOW SLAB WASTE PLAN - BLOCK 1F
PW107 BELOW SLAB WASTE PLAN - BLOCK 1G
PW111 FIRST FLOOR WASTE COMPOSITE PLAN
PW112 FIRST FLOOR WASTE PLAN - BLOCK 1A
PW113 FIRST FLOOR WASTE PLAN - BLOCK 1B
PW114 FIRST FLOOR WASTE PLAN - BLOCK 1C
PW115 FIRST FLOOR WASTE PLAN - BLOCK 1D
PW116 FIRST FLOOR WASTE PLAN - BLOCK 1F
PW117 FIRST FLOOR WASTE PLAN - BLOCK 1G
PW201 SECOND FLOOR WASTE COMPOSITE PLAN
PW202 SECOND FLOOR WASTE PLAN - BLOCK 2A
PW203 SECOND FLOOR WASTE PLAN - BLOCK 2B
PW301 COMPOSITE PLUMBING ROOF PLAN
PP101 FIRST FLOOR WATER COMPOSITE PLAN
PP102 FIRST FLOOR WATER PLAN - BLOCK 1A
PP103 FIRST FLOOR WATER PLAN - BLOCK 1B
PP104 FIRST FLOOR WATER PLAN - BLOCK 1C
PP105 FIRST FLOOR WATER PLAN - BLOCK 1D
PP106 FIRST FLOOR WATER PLAN - BLOCK 1F
PP107 FIRST FLOOR WATER PLAN - BLOCK 1G
PP201 SECOND FLOOR WATER COMPOSITE PLAN
PP202 SECOND FLOOR WATER PLAN - BLOCK 2A
PP203 SECOND FLOOR WATER PLAN - BLOCK 2B
PM101 FIRST FLOOR GASES COMPOSITE PLAN (AIR, NITROGEN AND
OXYGEN)
PM102 FIRST FLOOR GASES PLAN - BLOCK 1A (AIR, NITROGEN AND
OXYGEN)
PM103 FIRST FLOOR GASES PLAN - BLOCK 1B (AIR, NITROGEN AND
OXYGEN)
PM104 FIRST FLOOR GASES PLAN - BLOCK 1C (AIR, NITROGEN AND
OXYGEN)
PM105 FIRST FLOOR GASES PLAN - BLOCK 1D (AIR, NITROGEN AND
OXYGEN)
PM106 FIRST FLOOR GASES PLAN - BLOCK 1F (AIR, NITROGEN AND
OXYGEN)
PM107 FIRST FLOOR GASES PLAN - BLOCK 1G (AIR, NITROGEN AND
OXYGEN)
P-401 ENLARGED WASTE PLAN
P-402 ENLARGED WASTE PLAN
P-403 ENLARGED WASTE PLAN
P-404 ENLARGED WATER PLAN
P-405 ENLARGED WATER PLAN
P-406 ENLARGED WATER PLAN
P-407 ENLARGED WATER PLAN
P-501 PLUMBING DETAILS
P-502 PLUMBING DETAILS
P-503 PLUMBING DETAILS
P-504 PLUMBING DETAILS
P-505 PLUMBING DETAILS
P-506 PLUMBING DETAILS
P-701 PLUMBING WASTE RISER DIAGRAM
P-702 PLUMBING WASTE RISER DIAGRAM
P-703 PLUMBING WASTE RISER DIAGRAM
P-704 PLUMBING WASTE RISER DIAGRAM
P-705 PLUMBING WASTE RISER DIAGRAM
P-711 PLUMBING WATER RISER DIAGRAM
P-712 PLUMBING WATER RISER DIAGRAM
P-713 PLUMBING WATER RISER DIAGRAM
P-714 PLUMBING WATER RISER DIAGRAM
P-715 PLUMBING WATER RISER DIAGRAM
P-801 PLUMBING SCHEDULES
P-802 PLUMBING SCHEDULES
08-MECHANICAL
M-001 LEGEND AND NOTES
MH111 MECHANICAL 1ST FLOOR COMPOSITE PLAN
MH112 MECHANICAL 1ST FLOOR PLAN - BLOCK 1A
MH113 MECHANICAL 1ST FLOOR PLAN - BLOCK 1B
MH114 MECHANICAL 1ST FLOOR PLAN - BLOCK 1C
MH115 MECHANICAL 1ST FLOOR PLAN - BLOCK 1D
MH116 MECHANICAL 1ST FLOOR PLAN - BLOCK 1F
SHEET
NO. SHEET DESCRIPTION
SHEET
NO. SHEET DESCRIPTION
ET501 TELECOM SINGLE LINE DIAGRAM
ET502 TELECOM SINGLE LINE DIAGRAM
ET503 TELECOM SINGLE LINE DIAGRAMS
ET601 TELECOMMUNICATIONS DETAILS
ET602 TELECOMMUNICATIONS DETAILS
ET603 TELECOM EQUIPMENT RACK ELEVATIONS
ET604 TELECOM EQUIPMENT RACK ELEVATIONS
11 - FIRE PROTECTION
FL-001 LIFE SAFETY ANALYSIS
FL-111 LIFE SAFETY FIRST FLOOR PLAN
FL-112 LIFE SAFETY SECOND FLOOR PLAN
FA-001 REFERENCE SHEET - FIRE ALARM
FA-111 COMPOSITE FIRST FLOOR FIRE ALARM PLAN
FA-112 FIRST FLOOR FIRE ALARM PLAN - BLOCK 1A
FA-113 FIRST FLOOR FIRE ALARM PLAN - BLOCK 1B
FA-114 FIRST FLOOR FIRE ALARM PLAN - BLOCK 1C
FA-115 FIRST FLOOR FIRE ALARM PLAN - BLOCK 1D
FA-116 FIRST FLOOR FIRE ALARM PLAN - BLOCK 1F
FA-117 FIRST FLOOR FIRE ALARM PLAN - BLOCK 1G
FA-121 COMPOSITE SECOND FLOOR FIRE ALARM PLAN
FA-122 SECOND FLOOR FIRE ALARM PLAN - BLOCK 2A
FA-123 SECOND FLOOR FIRE ALARM PLAN - BLOCK 2B
FA-501 FIRE ALARM DETAILS
FA-601 RISER DIAGRAM & SCHEDULES - FIRE ALARM
FX-001 REFERENCE SHEET - SPRINKLER
FX-111 COMPOSITE FIRST FLOOR SPRINKLER PLAN
FX-112 FIRST FLOOR SPRINKLER PLAN - BLOCK 1A
FX-113 FIRST FLOOR SPRINKLER PLAN - BLOCK 1B
FX-114 FIRST FLOOR SPRINKLER PLAN - BLOCK 1C
FX-115 FIRST FLOOR SPRINKLER PLAN - BLOCK 1D
FX-116 FIRST FLOOR SPRINKLER PLAN - BLOCK 1F
FX-117 FIRST FLOOR SPRINKLER PLAN - BLOCK 1G
FX-121 COMPOSITE SECOND FLOOR SPRINKLER PLAN
FX-122 SECOND FLOOR SPRINKLER PLAN - BLOCK 2A
FX-123 SECOND FLOOR SPRINKLER PLAN - BLOCK 2B
FX-501 SPRINKLER DETAILS
FX-601 RISER DIAGRAM & SCHEDULES - SPRINKLER
12- EQUIPMENT
Q-111 COMPOSITE FIRST FLOOR SPECIALTY EQUIPMENT PLAN
Q-112 SPECIALTY EQUIPMENT - BLOCK 1A
Q-113 SPECIALTY EQUIPMENT - BLOCK 1B
Q-114 SPECIALTY EQUIPMENT - BLOCK 1C
Q-115 SPECIALTY EQUIPMENT - BLOCK 1D
Q-116 SPECIALTY EQUIPMENT - BLOCK 1F
Q-117 SPECIALTY EQUIPMENT - BLOCK 1G
Q-121 COMPOSITE SECOND FLOOR SPECIALTY EQUIPMENT PLAN
Q-122 SPECIALTY EQUIPMENT - BLOCK 2A
Q-123 SPECIALTY EQUIPMENT - BLOCK 2B
Q-131 ENLARGED FIRST FLOOR ROOMS
Q-132 ENLARGED SECOND FLOOR ROOMS
Q-601 EQUIPMENT SCHEDULE
SHEET
NO. SHEET DESCRIPTION
9 - ELECTRICAL
E-001 ELECTRICAL LEGEND
E-002 ELECTRICAL NOTES
ES101 ELECTRICAL SITE PLAN - DEMOLITION
ES102 SITE PLAN - POWER
ES111 SITE PLAN - LIGHTING
ES121 SITE PLAN - TELECOMMUNICATIONS
ES501 SITE DETAILS - ELECTRICAL
ES502 SITE DETAILS - ELECTRICAL
ES503 SITE DETAILS - ELECTRICAL
EL111 LIGHTING FIRST FLOOR COMPOSITE PLAN
EL112 LIGHTING FLOOR PLAN - BLOCK 1A
EL113 LIGHTING FLOOR PLAN - BLOCK 1B
EL114 LIGHTING FLOOR PLAN - BLOCK 1C
EL115 LIGHTING FLOOR PLAN - BLOCK 1D
EL116 LIGHTING FLOOR PLAN - BLOCK 1F
EL117 LIGHTING FLOOR PLAN - BLOCK 1G
EL121 LIGHTING SECOND FLOOR COMPOSITE PLAN
EL122 LIGHTING FLOOR PLAN - BLOCK 2A
EL123 LIGHTING FLOOR PLAN - BLOCK 2B
EL501 LUMINAIRE SCHEDULE
EL502 LUMINAIRE SCHEDULE AND TIME CLOCK SCHEDULES
EL503 LUMINAIRE DETAILS
EL504 LUMINAIRE DETAILS
EP101 POWER FLOOR PLAN - MECHANICAL EQUIPMENT YARD
EP111 POWER FIRST FLOOR COMPOSITE PLAN
EP112 POWER FLOOR PLAN - BLOCK 1A
EP113 POWER FLOOR PLAN - BLOCK 1B
EP114 POWER FLOOR PLAN - BLOCK 1C
EP115 POWER FLOOR PLAN - BLOCK 1D
EP116 POWER FLOOR PLAN - BLOCK 1F
EP117 POWER FLOOR PLAN - BLOCK 1G
EP121 POWER SECOND FLOOR COMPOSITE PLAN
EP122 POWER FLOOR PLAN - BLOCK 2A
EP123 POWER FLOOR PLAN - BLOCK 2B
EP401 ENLARGED PLANS - ELECTRICAL AND TELECOMMUNICATION
ROOMS
EP402 ENLARGED PLANS - MECHANICAL ROOMS
EP403 ENLARGED PLANS - MECHANICAL AND FIRE PUMP ROOMS
EP501 POWER SINGLE LINE DIAGRAM
EP502 POWER SINGLE LINE DIAGRAM
EP503 POWER SINGLE LINE DIAGRAM
EP504 FEEDER SCHEDULE
EP505 POWER DETAILS
EP506 PANELBOARD SCHEDULES
EP507 PANELBOARD SCHEDULES
EP508 PANELBOARD SCHEDULES
EP509 PANELBOARD SCHEDULES
EP510 PANELBOARD SCHEDULES
EP511 PANELBOARD SCHEDULES
EP512 PANELBOARD SCHEDULES
EP513 PANELBOARD SCHEDULES
EP514 PANELBOARD SCHEDULES
EP515 PANELBOARD SCHEDULES
EP516 PANELBOARD SCHEDULES
EP601 GROUNDING WIRING DIAGRAM
EP602 METER DETAILS
EP603 METER DETAILS
EP801 LIGHTNING PROTECTION PLAN
EP802 LIGHTNING PROTECTION SYSTEM - DETAILS
10 - TELECOMMUNICATIONS
ET001 TELECOMMUNICATIONS LEGEND
ET002 TELECOMMUNICATIONS NOTES
ET111 TELECOM FIRST FLOOR COMP PLAN
ET112 TELECOM FLOOR PLAN - BLOCK 1A
ET113 TELECOM FLOOR PLAN - BLOCK 1B
ET114 TELECOM FLOOR PLAN - BLOCK 1C
ET115 TELECOM FLOOR PLAN - BLOCK 1D
ET116 TELECOM FLOOR PLAN - BLOCK 1F
ET117 TELECOM FLOOR PLAN - BLOCK 1G
ET121 TELECOM SECOND FLOOR COMP PLAN
ET122 TELECOM FLOOR PLAN -BLOCK 2A
ET123 TELECOM FLOOR PLAN - BLOCK 2B
ET401 TELECOMMUNICATIONS ENLARGED ROOM PLANS
ET402 TELECOMMUNICATIONS ENLARGED ROOM PLANS
SWITCHES & LIGHTING CONTROLS
WALL SWITCHES
1-POLE, 20A, 120/277V AC ONLY, QUIET TYPE.
3-WAY, 20A, 120/277V AC ONLY, QUIET TYPE.
CONTROLS LIGHT FIXTURE OR OUTLET WITH SUBSCRIPT "a" ETC.
SOLID STATE DIMMER, LED AS REQUIRED FOR LIGHTS PROVIDED.
MULTIZONE SWITCHING. ANNOTATIONS INDICATE WHICH SECTION OF FIXTURE
TO BE CONTROLLED, OR WHICH SET OF LIGHTS CONTROLLED. SHOWN - ZONE
"b" IS CONTROLLED BY 3 WAY SWITCHING FROM A DISTAL LOCATION.
TIMESWITCH - TIME CLOCK 'TC-1' SHOWN.
a
D a b
TC-1
LUMINAIRES
CHAIN HUNG 4' LUMINAIRE.
2' X 4' LED LUMINAIRE - MOUNTING AND TYPE SHOWN IN FIXTURE SCHEDULE
2' X 2' LED LUMINAIRE (SAME AS ABOVE)
1' X 4' LED STRIP OR INDUSTRIAL LUMINAIRE (SAME AS ABOVE)
1' X 2' LED LOW BAY PENDANT HUNG FIXTURE
LED LUMINAIRE WITH EMERGENCY BACKUP VIA INVERTER (SAME AS ABOVE)
WALL MOUNTED LED LUMINAIRE
RECESSED DOWN LIGHT LUMINAIRE
EXIT SIGN, AC ONLY, CEILING OR PENDANT MOUNTED. SHADED PORTION
DENOTES FACE(S). DIRECTIONAL ARROWS AS INDICATED ON LIFE SAFETY
PLAN.
EXIT SIGN, AC ONLY, WALL MOUNTED. SHADED PORTION DENOTES FACE(S).
DIRECTIONAL ARROWS AS INDICATED ON LIFE SAFETY PLAN.
GENERAL RECEPTACLES
SUBSCRIPT MODIFIER LEGEND FOR BASIC RECEPTACLE TYPES:
NOTE: VERIFY WITH CONTRACTING OFFICER THE HEIGHT OF ALL COUNTER TOPS,
BACKSPLASHES, TABLE TOPS OR SINKS WHICH AFFECT THE MOUNTING HEIGHT OF
RECEPTACLES.
CRG - TAMPER RESISTANT GFI RECEPTACLE MOUNTED 4" ABOVE COUNTER
TOP, BACKSPLASH OR SINK TO CENTER OF RECEPTACLE.
CT - RECEPTACLE MOUNTED 4" ABOVE COUNTER TOP, BACKSPLASH OR
TABLE TOP TO CENTER OF RECEPTACLE.
CTG - GFI RECEPTACLE MOUNTED 4" ABOVE COUNTER TOP, BACKSPLASH
OR SINK TO CENTER OF RECEPTACLE.
CTR - SAFETY TYPE, TAMPER RESISTANCE RECEPTACLE MOUNTED 4" ABOVE
COUNTER TOP OR BACKSPLASH TO CENTER OF RECEPTACLE.
CW - RECEPTACLE MOUNTED IN CASEWORK 4" ABOVE COUNTER TOP.
EWC - GFI RECEPTACLE FOR ELECTRIC WATER COOLER. COORDINATE LOCATION
AND HEIGHT WITH PLUMBING. LOCATE RECEPTACLE ADJACENT TO WATER
COOLER HOUSING.
EWG - MECHANICAL EQUIPMENT SERVICE RECEPTACLE, WEATHER RESISTANCE
GFI TYPE WITH WEATHERPROOF IN USE COVER.
GFI - GROUND FAULT INTERRUPTER TYPE RECEPTACLE.
MF - PREWIRED RECEPTACLE PROVIDED WITH MODULAR FURNITURE.
RECEPTACLE MUST BE MARKED PER NFPA 70, 406.3(E). MODULAR
FURNITURE MUST BE PROVIDED WITH WIRED "FLEX WHIP" FOR
CONNECTION TO POWER BY ELECTRICAL.
SCW - SAFETY TYPE, TAMPER RESISTANT RECEPTACLE MOUNTED IN CASEWORK.
SR - SAFETY TYPE, TAMPER RESISTANT RECEPTACLE.
SRG - SAFETY TYPE, TAMPER RESISTANT GFI.
TV - RECEPTACLE FOR FLAT SCREEN TV. MOUNT RECEPTACLE 72" AFF TO
CENTER OF BOX AND ADJACENT TO TV ANTENNA OUTLET UNLESS NOTED
OTHERWISE.
WP - WATER AND/OR WEATHER RESISTANT.
WPG - WEATHER RESISTANT GFI RECEPTACLE WITH WEATHERPROOF IN USE
COVER.
SIMPLEX RECEPTACLE, 20A, 125V, 2P-3 WIRE, NEMA 5-20R.
DUPLEX RECEPTACLE, 20A, 125V, 2P-3 WIRE, NEMA 5-20R.
STUB-UP THRU FLOOR WITH DIE CAST FSD BOX MOUNTED 6" ABOVE FLOOR WITH
DUPLEX RECEPTACLE, 20A, 125V, 2P-3 WIRE, NEMA 5-20R.
DOUBLE DUPLEX RECEPTACLE, 20A, 125V, 2P-3 WIRE, NEMA 5-20R.
EMERGENCY DUPLEX RECEPTACLE, 20A, 125V, 2P-3 WIRE, NEMA 5-20R (RED
COLOR).
EMERGENCY DOUBLE DUPLEX RECEPT, 20A, 125V, 2P-3 WIRE, NEMA 5-20R (RED
COLOR).
DUPLEX RECEPTACLE, CEILING MOUNTED, RECESSED, SUPPORT FROM CEILING
SUSPENSION SYSTEM, 20A, 125V, 2P-3 WIRE, NEMA 5-20R.
NOTE: MOUNT GROUND PIN UP
FLOOR RECEPTACLES & OTHERS
MULTI SERVICE, HAND ACCESS, REACH-IN TYPE, FLUSH, FLOOR BOX WITH
ACTIVATION COVER PLATE. PROVIDE WITH ONE (DUPLEX OR DOUBLE DUPLEX
RESPECTIVELY) RECEPTACLE, 20A, 125V, 2P-3 WIRE, NEMA 5-20R. SEE SUBSCRIPT
MODIFIER LEGEND UNDER GENERAL RECEPTACLES. SEE TELECOMMUNICATIONS
PLANS FOR VOICE/DATA REQUIREMENTS AND NOTES. SEE DETAIL 'F4' ON SHEET
S-004.
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE , 20A, 125V, 2P-3 WIRE, NEMA
5-20R, UNLESS OTHERWISE NOTED.
G
POWER PANELBOARDS & EQUIPMENT
SD
B
22KAIC
GFP
T
TRXXX
PANELBOARD, SURFACE MOUNTED AT 72" AFF TO TOP. SEE PANELBOARD
SCHEDULE.
PANELBOARD, FLUSH MOUNTED AT 72" AFF TO TOP. SEE PANELBOARD
SCHEDULE.
DISTRIBUTION PANELBOARD, SURFACE MOUNTED AT 72" AFF TO TOP. SEE
PANELBOARD SCHEDULE.
- TYPICAL LIGHTING APPLIANCE PANELBOARD NAMING SCHEME -
FIRST EM - OPTIONAL STANDBY SYSTEM
POSITION (1-2 N - NORMAL POWER SYSTEM
CHARACTERS)
SECOND POSITION 4 - 480Y/277 VOLT
(1 CHARACTER) 2 - 208Y/120 VOLT
THIRD POSITION 1 - FIRST FLOOR
(1 CHARACTER) 2 - SECOND FLOOR
FOURTH POSITION A - ELECTRICAL ROOM 'A'
(1 CHARACTER) B - ELECTRICAL ROOM 'B'
FIFTH POSITION 1 - PANEL #1
(1 CHARACTER) 2 - PANEL #2
3 - PANEL #3
- TYPICAL DISTRIBUTION PANELBOARD NAMING SCHEME -
DPE4
FIRST
POSITION (1-2 DP - DISTRIBUTION PANELBOARD
CHARACTERS)
SECOND N - NORMAL POWER SYSTEM
POSITION (1-2 EM - EMERGENCY POWER SYSTEM
CHARACTERS)
THIRD POSITION 4 - 480Y/277 VOLT
(1 CHARACTER) 2 - 208Y/120 VOLT
- TYPICAL SWITCHBOARD NAMING SCHEME -
SBM
FIRST
POSITION SB - SWITCHBOARD
(2 CHARACTERS)
SECOND M - MAIN (NORMAL)
POSITION (1-2 G - GENERATOR (ALTERNATE)
CHARACTERS)
N21C1
DISCONNECT SWITCH, FUSIBLE, IF DISCONNECT SIZE AND FUSING IS NOT SHOWN
ON PLAN, REFER TO POWER SINGLE LINE DIAGRAM ON SHEET EP500 SERIES.
FUSE SIZE (FM - FUSE PER MANUFACTURER'S RECOMMENDATION; NF - NON
FUSED)
DISCONNECT AMP RATING
# OF POLES
SAME AS ABOVE EXCEPT MOUNTED ON UNISTRUT STAND.
INTEGRAL SAFETY DISCONNECT SWITCH FURNISHED WITH EQUIPMENT. IF
EQUIPMENT IS SHOWN WITH DISCONNECT BUT MANUFACTURER DOES NOT
PROVIDE ONE, CONTRACTOR IS RESPONSIBLE FOR PROVIDING DISCONNECT OF
REQUIRED SIZE AND TYPE. COORDINATE WITH APPROPRIATE TRADE INVOLVED.
DRY TYPE TRANSFORMER; ELEC. PARAMETERS AS SHOWN ON SINGLE LINE
DIAGRAM.
DRY TYPE TRANSFORMER; ELEC. PARAMETERS AS SHOWN ON PLANS. NAMING
SCHEME FOLLOWS PANELBOARD TYPICAL NAMING SCHEMES.
NON-AUTOMATIC TRANSFER SWITCH (NTS).
MOLDED CASE CIRCUIT BREAKER WITH ADJUSTABLE SOLID STATE ELECTRONIC
TRIP (LSI FUNCTIONS).
MOLDED CASE CIRCUIT BREAKER WITH ADJUSTABLE SOLID STATE ELECTRONIC
TRIP AND GROUND FAULT (LSIG).
MOLDED CASE CIRCUIT BREAKER (THERMAL MAGNETIC).
CIRCUIT BREAKER IN NEMA 1 ENCLOSURE - SURFACE MOUNTED, 22,000AIC
SHOWN. (LEGEND: 'F' = FLUSH MOUNTED; 'SS' SOLID STATE ELECTRONIC TRIP
WITH LSI FUNCTIONS; 'GFS' GROUND FAULT SENSING)
GENERATOR DOCKING STATION.
N21A:1,3,5
BRANCH CIRCUITS
1"
10's
INDICATES CONCEALED OVERHEAD OR IN WALLS.
INDICATES CONCEALED IN OR BELOW FLOOR SLAB OR BELOW ROOF IN
ATTIC OR ABOVE CEILING SPACE. SEE SPECIFICATIONS FOR
RESTRICTIONS. CONDUIT BELOW SLAB ON GRADE OR IN SLAB (ALL
FLOORS INCLUDED) SHALL BE PVC COATED RIGID CONDUIT.
INDICATES EXPOSED CONDUIT.
CONDUIT TERMINATION, (C) CAPPED, (B) BUSHED, (G) GROUND BUSHING.
BRANCH CIRCUIT WIRING IN CONDUIT. TICK MARKS INDICATE THE NUMBER
OF #12 AWG PHASE & NEUTRAL CONDUCTORS IN 3/4" CONDUIT, UNLESS
OTHERWISE NOTED. ALSO ALL CONDUITS SHALL HAVE A #12 AWG GROUND
CONDUCTOR, UON. ARROWHEADS INDICATES NUMBER OF CIRCUITS UP TO
THAT POINT (DEVICE, FIXTURE, ETC.). EXAMPLE SHOWN, ONE
ARROWHEAD/CIRCUIT TO RECEPTACLE.
HOMERUN TO PANELBOARD. PANELBOARD AND CIRCUIT DESIGNATIONS AS
INDICATED.
INDICATES SIZE OF CONDUIT OTHER THAN 3/4". SHOWN, 1" CONDUIT.
INDICATES #10 AWG CONDUCTORS FROM JUNCTION BOX WHERE HOMERUN
BEGINS, INCLUDING GROUNDING CONDUCTOR, BACK TO PANELBOARD.
PROVIDE #10 AWG CONDUCTORS DOWNSTREAM OF THE HOMERUN
JUNCTION BOX TO ALL DEVICES.
INDICATES #8 AWG CONDUCTORS FROM JUNCTION BOX WHERE HOMERUN
BEGINS, INCLUDING GROUNDING CONDUCTOR, BACK TO PANELBOARD.
PROVIDE #10 AWG CONDUCTORS DOWNSTREAM OF THE HOMERUN
JUNCTION BOX TO ALL DEVICES. PROVIDE 1"C WHERE MORE THAN 4
CONDUCTORS ARE INSTALLED.
8's
J
J
J
J
J
J
J
EM
WP
MF
JUNCTION BOXES
JUNCTION BOX IN OR ABOVE CEILING.
WEATHERPROOF DIE CAST BOX WITH WEATHERPROOF COVER.
JUNCTION BOX IN WALL - MOUNT AT 18" AFF UNLESS OTHERWISE NOTED.
SAME AS ABOVE EXCEPT WITH FLEXIBLE CONNECTION TO EQUIPMENT.
SAME AS ABOVE EXCEPT WITH EMERGENCY POWER FLEXIBLE CONNECTION TO
EQUIPMENT.
SINGLE GANG FLUSH FLOOR MOUNTED CONCRETE TIGHT CAST IRON POWER
AND/OR COMM FLOOR BOX WITH FLEXIBLE POWER CONNECTION TO PRE-WIRED
MODULAR FURNITURE (MF) OR CASEWORK WITH EMPTY CONDUIT SYSTEMS.
FOR EMPTY CONDUIT SYSTEMS CONTRACTOR SHALL PROVIDE DEVICES SHOWN
ON PLANS WITH WIRING, ETC. AS REQUIRED. FOR MODULAR FURNITURE
PROVIDE 36" OF STEEL FLEX WITH 6" OF SLACK WIRE & 90 DEGREE CONNECTOR
ON EACH END. CAP CIRCUITS FOR FUTURE CONNECTION BY OTHERS. 2MF OR
3MF SUBSCRIPTS INDICATES 2-GANG OR 3-GANG BOXES RESPECTIVELY WITH
DIVIDERS BETWEEN EACH GANG SECTION.
FLUSH FLOOR MOUNTED POWER OR COMMUNICATIONS JUNCTION BOX WITH
BRASS COVER PLATE.
SITE DEMOLITION
EXISTING UNDERGROUND POWER TO BE
DEMOLISHED.
EXISTING UNDERGROUND COMMUNICATIONS TO BE
DEMOLISHED.
EUP
EUC
SITE LEGEND
EUP
UP
ESL
SL
POLE LIGHT - SINGLE LUMINARIE (SEE LIGHT FIXTURE
SCHEDULE)
POLE LIGHT - DOUBLE LUMINARIE (SEE LIGHT
FIXTURE SCHEDULE)
INDICATES CIRCUIT INSTALLED BELOW GRADE.
COMMUNICATIONS MANHOLE
EXISTING UNDERGROUND PRIMARY
UNDERGROUND PRIMARY
UNDERGROUND SECONDARY
UNDERGROUND CONDUIT
EXISTING UNDERGROUND CONCRETE ENCASED
STREET LIGHTING CIRCUIT TO BE DEMOLISHED.
CONCRETE INCASED STREET LIGHTING CIRCUIT. SEE
SITE PLAN FOR CONDUIT AND WIRE SIZE. LOCATE
NEW CIRCUIT MINIMUM 18" BELOW GRADE.
ELECTRICAL HAND HOLE
C
UC
HH
US
S o lic it a ti o n
N u m b e r:
I.
S
.O
S h e e t
F ile
N a m e
IDENTIFICATION
SHEET
R e v ie w e d
B y
D ra w n
B y
D e s ig n e d
B y
C h e c k e d
B y
D a te
F ile
N o
S y m b o l D e s c ri p ti o n
R e v is io n s
A p p ro v e d D a te
N o
US Army Corps of Engineers Mobile District
A
B C D
A B C D
E F G H I
E F G
H I
SHEET of
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
C O
R P
S O
F E
N G
IN
E
E R
S M
O B
IL
E
A
L A
B A
M A
W
8-
-R
-0
M E
Y
J
U N
E
K C
H
IL
D S
/1
/2
:1
:3
A
M
C
U s e rs \a tk is o n m \D o c u m e n ts \2
-E M a tt h e w
.A tk is o n s s a in c .c o m
. r v t
E-001
E L E
C T
R
IC
A L L
E G
E N
D
M A
T K
IS
O
N
M A
T K
IS
O
N
G Y
O S
T
S O
F S
P E
C
IA
L T
A C
T
IC
S O
P E
R A
T
IO
N S
F A
C
IL
IT
Y
H U
R L B
U R
T F
IE
L D
F
L
M
NA
T
T H E W B A T K I S
O
A AL A B A M
L DI C E N S E
NO. 26286
PROFESSIONAL
E RN G I N E E
X
X
SPECIAL RECEPTACLES
SPECIAL SIMPLEX RECEPTACLE - NEMA CONFIGURATION AS SHOWN BELOW
WHERE 'X' EQUALS ONE OF THE SINGLE SUBSCRIPT LETTERS BELOW. NEMA
CONFIGURATION SHOWN ON PLANS ARE FOR BID PURPOSES ONLY. ACTUAL
NEMA CONFIGURATION REQUIRED IN EACH CASE MAY VARY DEPENDING UPON
SPECIFIC MANUFACTURER OF EQUIPMENT BEING SUPPLIED. VERIFY NEMA
CONFIGURATION WITH CONTRACTION OFFICER AND/OR MANUFACTURER.
SPECIAL RECEPTACLE (EMERGENCY POWER).
SUBSCRIPT MODIFIER LEGEND FOR BASIC RECEPTACLE TYPES:
NOTE: VERIFY WITH CONTRACTING OFFICER THE HEIGHT OF ALL COUNTER TOPS,
BACKSPLASHES, TABLE TOPS OR SINKS WHICH AFFECT THE MOUNTING HEIGHT OF
RECEPTACLES.
A - 125V, 30A, 1Ø (NEMA 5-30R)
B - 125V, 30A, 1Ø (NEMA L5-30R) LOCKING RECEPTACLE
C - 208V, 15A, 1Ø (NEMA 6-15R)
D - 208V, 20A, 3Ø (NEMA 11-30R)
E - 208V, 20A, 1Ø (NEMA 6-20R)
F - 208V, 20A, 1Ø (NEMA L6-20R) LOCKING RECEPTACLE
G - 208V, 20A, 1Ø (NEMA 14-20R)
H - 208V, 20A, 3Ø (NEMA L21-20R) LOCKING RECEPTACLE
J - 208V, 30A, 1Ø (NEMA 6-30R)
K - 208V, 30A, 1Ø (NEMA L6-30R) LOCKING RECEPTACLE
L - 208V, 40A, 1Ø (NEMA 6-50R) ON 40A/2P CIRCUIT BREAKER
M - 208V, 50A, 1Ø (NEMA 14-50R)
N - 208V, 50A, 1Ø (NEMA L14-50R) LOCKING RECEPTACLE
P - 208V, 50A, 3Ø (NEMA 15-50R)
Q - 208V, 60A, 1Ø (NEMA L14-60R) LOCKING RECEPTACLE
R - 208V, 100A, 3Ø , 4 POLE, 5 WIRE (LEGRAND PS5100MIR9-W)
S- 208V, 50A, 1Ø, (NEMA 10-50R)
DCP
CONTROLS & MECHANICAL EQUIPMENT
M
VFD
DISCONNECT & MOTOR CONTROLLER (STARTER) - MAGNETIC WITH THERMAL
OVERLOAD PROTECTION - MAY BE COMBINATION TYPE IN COMMON ENCLOSURE OR
SEPARATE DISCONNECT & STARTER. "VFD" SUBSCRIPT WHEN SHOWN (AS HERE)
INDICATES VARIBLE FREQUENCY DRIVE MOTOR CONTROLLER WITH INTEGRAL
DISCONNECT. COORDINATE EXACT LOCATION WITH MECHANICAL. STAND ALONE
STARTERS SHALL BE FURNISHED BY MECHANICAL, CONNECTED BY ELECTRICAL.
FOR ALL HVAC EQUIPMENT COMBINATION DISCONNECT & STARTERS & VFD'S SHALL
BE FURNISHED & INSTALLED BY MECHANICAL, CONNECTED BY ELECTRICAL. FOR
ALL OTHER EQUIPMENT SAID ITEMS SHALL BE FURNISHED, INSTALLED &
CONNECTED BY ELECTRICAL.
MOTOR RATED TOGGLE SWITCH, MAXIMUM 20 AMP RATING, 120/277V, 1-POLE. 'M2'
OR 'M3' SUBSCRIPT INDICATES 2-POLE OR 3-POLE MANUAL MOTOR
CONTROLLER/SWITCH, RESPECTIVELY WITH 30A RATING MAXIMUM.
MOTOR - ELECTRICAL CHARACTERISTICS AS NOTED.
DIGITAL CONTROL PANEL. (FURNISHED & INSTALLED BY MECHANICAL, POWER
CONNECTION BY ELECTRICAL)
ABBREVIATIONS
A AMPERES
AER ENERGY REDUCTION
MAINTENANCE SWITCH
AFCI ARC-FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AVAILABLE INTERRUPTING CURRENT
RATING
ATS AUTOMATIC TRANSFER SWITCH
BATT BATTERY
BKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CF COMPACT FLUORESCENT
CIRC CIRCUIT
CL CEILING MOUNTED
COMM COMMUNICATIONS
CT COUNTER TOP
CW CASEWORK
DETD DUAL ELEMENT TIME DELAY
EC EMPTY CONDUIT
ECB EMERGENCY CENTRAL BATTERY
SYSTEM
EM EMERGENCY
ENC ENCLOSED
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX EXISTING TO REMAIN
FIO FOR INFORMATION ONLY
FUT FUTURE
GFI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTION
GFR GROUND FAULT RELAY
GFRI GROUND FAULT INDICATION ONLY
GND GROUND
HID HIGH INTENSITY DISCHARGE
HP HORSEPOWER RATING
LCP LIGHTING CONTROL PANEL
LSI LONG, SHORT, INSTANTANEOUS
(TRIPPING)
LSIG LONG, SHORT, INSTANTANEOUS,
GROUND (TRIPPING)
MCB MAIN CIRCUIT BREAKER
MCCB MOLDED CASE CIRCUIT BREAKER
MLO MAIN LUGS ONLY
MT MOUNT
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NL NIGHT LIGHT (DO NOT SWITCH)
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
PDS PREMISES DISTRIBUTION SYSTEM
PNL PANEL, PANELBOARD
PR PAIR
RCPT RECEPTACLE
REF REFRIGERATOR
REQ'D REQUIRED
RS INDICATES FOR ROLL-UP SHUTTER
SLD SINGLE LINE DIAGRAM
SM SURFACE MOUNTED
SS SOLID STATE ADJUSTABLE (LSI)
TRIP
ST SHUNT TRIP
TVSS TRANSIENT VOLTAGE SURGE
SUPPRESSOR
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER
SUPPLY
WG WIREGUARD
WP RAINTIGHT (NEMA 3R
CLASSIFICATION)
WPG INDICATES WEATHERPROOF
EQUIPMENT WITH GROUND
FAULT CAPABILITY
XFMR TRANSFORMER
GENERAL NOTES
1. ALL ITEMS ON PLANS ARE NEW UNLESS NOTED OTHERWISE.
2. MAINTAIN N.E.C. MINIMUM CLEARANCE IN FRONT OF ALL SWITCHBOARDS, SAFETY SWITCHES, PANELBOARDS, TRANSFER SWITCHES, TRANSFORMERS, AND OTHER
ELECTRICAL EQUIPMENT. DETERMINE PROPER CLEARANCE BEFORE INSTALLATION. DIMENSIONS OF EQUIPMENT SHOWN ARE BASED ON A PARTICULAR MANUFACTURER.
IF DIMENSIONS OF EQUIPMENT FURNISHED DIFFER FROM THOSE ON THE DRAWINGS, CONTRACTOR MUST BE RESPONSIBLE TO ENSURE THAT ALL EQUIPMENT FITS IN THE
ROOM OR SPACE ALLOCATED WITH PROPER CLEARANCE.
3. ALL CIRCUIT BREAKERS RATED 1200A OR LARGER MUST INCLUDE ARC ENERGY REDUCTION. PROVIDE ENERGY-REDUCING MAINTENANCE SWITCHING WITH LOCAL STATUS
INDICATOR.
4. PRIOR TO ROUGH-IN, CONTRACTOR MUST PROVIDE SCALED WALL ELEVATIONS WHERE ALL ALARM CABINETS, SIGNAL CABINETS, ETC. ARE INSTALLED IN OTHER THAN
MECHANICAL AND ELECTRICAL ROOMS FOR APPROVAL.
5. PROVIDE AN ARC FLASH STUDY AND COORDINATION STUDY ONCE THE ELECTRICAL SYSTEM (AS-BUILT SYSTEM) IS IN PLACE THAT WILL YIELD THE REQUIRED ARC FLASH WARNING LABELS IN ACCORDANCE WITH NEC 110.16(A) AND NFPA 72E AS WELL AS THE FINAL ADJUSTABLE TRIP ELECTRONIC CIRCUIT BREAKER SETTINGS.
6. ALL NEW SWITCHBOARDS AND PANELBOARDS MUST HAVE A PERMANENT SIGN TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS AND THAT PERSONNEL PROTECTIVE EQUIPMENT (PPE) IS REQUIRED. THE MARKING MUST BE LOCATED SO AS TO BE CLEARLY VISIBLE TO QUALIFIED PERSONS BEFORE SERVICING
THE EQUIPMENT. PROVIDE LABEL IN ACCORDANCE WITH NEC 110.16.
7. THE SERVICE SWITCHBOARD MUST INCLUDE A LAMINATED PLASTIC LABEL TO INDICATE THE MAXIMUM AVAILABLE FAULT CURRENT AT THE SERVICE AND THE DATE THE FAULT CALCULATION WAS PERFORMED IN ACCORDANCE WITH NEC 110.24. SEE SINGLE LINE DIAGRAMS FOR DATA.
8. CONTRACTOR MUST COORDINATE WITH PANELBOARD MANUFACTURER AND PROVIDE CIRCUIT BREAKERS IN THE PANELBOARD SUBMITTAL THAT WILL COORDINATE FROM THE SERVICE ENTRANCE SWITCHBOARD/PANELBOARD TO ALL DOWNSTREAM CIRCUIT BREAKERS (INCLUDING BRANCH PANEL CIRCUIT BREAKERS).
9. ALL RECESSED MOUNTED PANELBOARDS MUST HAVE FOUR (4) 3/4" EMPTY CONDUITS STUBBED UP ABOVE THE CEILING UNLESS OTHERWISE NOTED ON THE PANELBOARD
SCHEDULE.
10. PROVIDE ENGRAVED LAMINATED MELAMINE TYPE LABELS DESCRIBING THE LOAD SERVED FOR EACH CIRCUIT BREAKER IN MAIN SERVICE SWITCHBOARD AND ALL
DISTRIBUTION TYPE PANELBOARDS. ALSO PROVIDE SAME FOR EACH DISCONNECT SWITCH.
11. FLEXIBLE CONDUITS INSTALLED OUT-OF-DOORS, IN ANY MECHANICAL EQUIPMENT ROOM, OR IN NORMALLY WET AREAS, MUST BE LIQUID TIGHT FLEX WITH SUITABLE
FITTINGS.
12. PROVIDE FLEXIBLE CONDUIT FOR ALL CONDUITS PASSING THROUGH EXPANSION JOINTS. SEE ARCHITECTURAL DRAWINGS FOR EXPANSION JOINT LOCATIONS.
13. BRANCH CIRCUITS AND HOMERUNS MUST BE COPPER #12 WIRE AND 1/2" CONDUIT MINIMUM UNLESS OTHERWISE NOTED. EVERY CONDUIT MUST HAVE A GROUND WIRE (#
12 MINIMUM). USE OF ALUMINUM WIRE IS NOT PERMITTED.
14. NO MORE THAN THREE PHASE CONDUCTORS MAY BE INSTALLED IN ONE CONDUIT UNLESS NOTED OTHERWISE.
15. NO CONDUIT CAN BE ROUTED THROUGH ELEVATOR HOIST WAY OR MACHINE ROOM UNLESS IT SPECIFICALLY SERVES EQUIPMENT IN THAT ROOM.
16. ALL UNDERGROUND CONDUIT RUNS ENTERING THE BUILDING AND IN MANHOLES MUST BE SEALED TO PREVENT THE ENTRANCE OF MOISTURE AND GASES.
17. CONDUIT FOR RECEPTACLE CIRCUITS AND OTHER POWER BRANCH CIRCUIT WIRING AS WELL AS COMMUNICATION SYSTEMS CONDUITS MUST BE RUN OVERHEAD UNLESS
NOTED OTHERWISE.
18. PROVIDE CONDUIT FOR DEVICE BOXES AS REQUIRED FOR THERMOSTATS. THERMOSTATS ARE SHOWN ON MECHANICAL DRAWINGS
19. IN ALL ROOMS WITHOUT FINISHED CEILINGS INSTALL ALL ELECTRICAL CONDUITS AS CLOSE TO THE STRUCTURAL CEILING AS POSSIBLE.
20. UNLESS NOTED OTHERWISE, THE CONDUIT SIZES SHOWN ON THE DRAWINGS FOR POWER AND LIGHTING ARE BASED ON THHN/THWN-2 CONDUCTORS AND APPLY TO ALL
TYPES OF CONDUIT EXCEPT FOR SCHEDULE 80 PVC. FOR SCHEDULE 80 PVC INCREASE CONDUIT SIZE BY ONE TRADE SIZE OVER THAT WHICH IS SHOWN ON THE DRAWINGS OR CALCULATE THE SIZE PER NATIONAL ELECTRICAL CODE. IF A DIFFERENT TYPE OF CONDUCTOR INSULATION IS USED RATHER THAN TYPE THHN/THWN-2, THE CONTRACTOR IS RESPONSIBLE FOR SIZING CONDUIT PER NEC BEFORE INSTALLATION. ANY INCREASE IN CONDUIT SIZES MUST BE THE RESPONSIBILITY OF THE
CONTRACTOR AT NO ADDITIONAL COST TO THE GOVERNMENT.
21. WHERE PARALLEL RUNS OF CONDUCTORS ARE ROUTED TO AND/OR FROM A PIECE OF ELECTRICAL EQUIPMENT, CONTRACTOR MUST PROVIDE ALL REQUIRED LUGS TO
MATCH THE NUMBER OF CONDUCTORS PER PHASE, NEUTRAL AND GROUND.
22. ALL CONDUIT MUST BE CONCEALED UNLESS SPECIFICALLY SHOWN TO BE EXPOSED. ALL CONDUIT SERVING DEVICES AND EQUIPMENT ON THE EXTERIOR OF THE BUILDING
MUST ALSO BE HIDDEN IN WALLS OR COLUMNS.
23. METAL CLAD CABLE TYPES 'AC' AND 'MC' ARE PROHIBITED ON THIS PROJECT.
24. ELECTRIC WATER COOLER GFI RECEPTACLES INDICATED BY "EWC" MUST BE LOCATED ADJACENT TO THE WATER COOLER ASSEMBLY. COORDINATE WITH PLUMBING
TRADE.
25. MOTOR CONTROL DEVICES FURNISHED IN PLACE BY MECHANICAL TRADE, BUT ELECTRICALLY CONNECTED BY ELECTRICAL TRADE.
26. COORDINATE WITH ALL MECHANICAL AND PLUMBING FOR SPACE REQUIREMENTS IN MECHANICAL ROOMS, CORRIDORS, SHAFTS, ABOVE CEILING, ETC. THIS INCLUDES
SPACE ABOVE PANELS WHERE DUCTS AND PIPING ARE PROHIBITED.
27. FOR EXACT LOCATIONS OF MECHANICAL EQUIPMENT, SEE MECHANICAL PLANS.
28. WHERE PROJECT IS LOCATED IN A SALT WATER AREA, ALL ELECTRICAL EQUIPMENT SUCH AS PAD MOUNTED TRANSFORMERS & DISCONNECT SWITCHES INSTALLED OUT-
OF-DOORS MUST BE PROVIDED WITH NEMA 4X ENCLOSURES.
29. WHERE WALL SWITCHES AND CONTROL DEVICES SUCH AS THERMOSTATS ARE SHOWN AT THE SAME LOCATION IN PLAN VIEW (CONTROL DEVICES SUCH AS THERMOSTATS
ARE SHOWN ON THE MECHANICAL DRAWINGS) THEY MUST BE MOUNTED WITH THE CONTROL DEVICE DIRECTLY IN LINE ABOVE THE SWITCH.
30. THE LOCATION OF LIGHT FIXTURES IN MECHANICAL ROOMS, ELECTRICAL ROOMS, MACHINE ROOMS, ETC. ARE SHOWN FOR BID PURPOSES ONLY. LIGHT FIXTURES MUST BE
INSTALLED SO AS TO COORDINATE WITH ALL TRADES AND MUST BE ARRANGED FOR MAXIMUM LIGHTING DISTRIBUTION OF THE AREA.
31. CONTRACTOR MUST VERIFY AND COORDINATE ALL CONNECTIONS TO EQUIPMENT WITH SPECIFIC EQUIPMENT FURNISHED.
32. IN MANY CASES THROUGHOUT THE PLANS, EQUIPMENT CONNECTIONS ARE IDENTIFIED ON THE PLANS WITH A LETTER AND A FOUR DIGIT NUMBER. EXAMPLE: R7000 IS A
REFRIGERATOR. THE EQUIPMENT SCHEDULE AND ANY SPECIAL CONNECTION INFORMATION FOR THESE ITEMS IS SHOWN ON THE EQUIPMENT SHEET Q-100.
33. CONNECTIONS TO MECHANICAL EQUIPMENT, PLUMBING EQUIPMENT AND ELEVATOR MOTORS ARE BASED ON A PARTICULAR MANUFACTURER. IF CONNECTIONS TO
EQUIPMENT DIFFER FROM THAT SHOWN ON THE DRAWINGS, CONTRACTOR IS RESPONSIBLE FOR PROVIDING THE CORRECT CONNECTIONS.
34. SEE MECHANICAL AND PLUMBING EQUIPMENT SCHEDULES ON MECHANICAL AND PLUMBING DRAWINGS FOR ELECTRICAL REQUIREMENTS. COORDINATE WITH
MANUFACTURER'S DATA IN OWNER APPROVED MECHANICAL AND PLUMBING SUBMITTALS SO AS TO ENSURE THAT THE BRANCH CIRCUIT AND OVERCURRENT PROTECTION ARE PROPERLY SIZED FOR THE EQUIPMENT BEING PROVIDED. PROVIDE (AT NO ADDITIONAL COST TO GOVERNMENT) PROPERLY SIZED ELECTRICAL EQUIPMENT AND CIRCUITS BASED ON THE MANUFACTURER'S DATA IN THE APPROVED EQUIPMENT SUBMITTAL. THE CONTRACTING OFFICER MUST APPROVE ANY PROPOSED CHANGES IN
THE BRANCH CIRCUIT AND OVERCURRENT PROTECTION.
35. VERIFY AND COORDINATE ALL MOUNTING HEIGHTS OF ALL DEVICES MOUNTED IN CASEWORK OR IN OR ABOVE COUNTERS WITH SPECIFIC EQUIPMENT FURNISHED.
36. DEVICE BOXES (RECEPTACLES, LIGHT SWITCHES, TELEPHONE, ETC.) OVER 16 SQUARE INCHES IN SMOKE AND FIRE WALLS MUST BE FIVE SIDED WITH SAME CONSTRUCTION
AS WALL SYSTEM. WHERE OUTLET BOXES ARE ON OPPOSITE SIDES OF A FIRE WALL THERE MUST BE A 24" HORIZONTAL SEPARATION BETWEEN THEM OR BOXES MUST BE
PROTECTED WITH UL LISTED FIRE RESISTANT MATERIAL ON 5 SIDES.
37. DO NOT MOUNT DEVICES BACK-TO-BACK.
38. PROVIDE ALL NORMAL POWER RECEPTACLES, SWITCHES, ETC WITH STAINLESS STEEL COVER PLATES. ALL RECEPTACLES AND LIGHT SWITCHES ON EMERGENCY POWER
MUST BE "RED" AND HAVE "EMERGENCY" ENGRAVED ON THEIR RESPECTIVE DEVICE COVER PLATE. INDICATE PANELBOARD AND CIRCUIT NUMBER PERMANENTLY
IDENTIFIED ON EACH RECEPTACLE COVER PLATE.
39. PROVIDE BARRIERS BETWEEN ALL 277V SWITCHES MOUNTED UNDER THE SAME COVER PLATE WITH OTHER 277V SWITCHES ON DIFFERENT PHASES OR 120V SWITCHES.
40. MOUNTING HEIGHTS OF WALL DEVICES ABOVE FINISHED FLOOR MUST BE AS INDICATED IN THE LEGEND AND IN THE FOLLOWING UNLESS NOTED OTHERWISE ON THE PLANS
(MOUNTING HEIGHTS ARE TO CENTERLINE OF DEVICE): SWITCHES (GENERAL) = 48" RECEPTACLES (GENERAL) = 18"
41. WHERE AN ELECTRICAL RECEPTACLE IS ADJACENT TO A SINK, LOCATE THE RECEPTACLE LEAST 6" HORIZONTALLY AWAY FROM THE SINK'S TOWEL DISPENSER. DO NOT
LOCATE THE RECEPTACLE UNDER A TOWEL DISPENSER.
42. ALL DEVICE BOXES FOR POWER, LIGHTING OR COMMUNICATIONS DEVICES MUST BE FLUSH MOUNTED UNLESS OTHERWISE NOTED.
43. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL CEILING MOUNTED EQUIPMENT.
44. PROVIDE A COMPLETELY CONCEALED U.L. MASTER LABEL LIGHTNING PROTECTION SYSTEM.
45. PROVIDE STRUCTURAL BACKING AS REQUIRED FOR PROPER SUPPORT OF WALL MOUNTED ELECTRICAL EQUIPMENT. SEE ARCHITECTURAL FOR ADDITIONAL WALL
MOUNTED EQUIPMENT REQUIREMENTS.
46. ALL CONFLICTS MUST BE FORWARDED IN THE FORM OF A 'REQUEST FOR INFORMATION' (RFI) BEFORE THE START OF INSTALLATION. A RFI ISSUED AFTER THE START OF
INSTALLATION MUST BE FIELD RESOLVED AT NO ADDITIONAL COST TO THE GOVERNMENT.
47. WHERE CONDUIT PASSES THROUGH CONCRETE FLOOR AND/OR BEAMS, PROVIDE APPROPRIATE SLEEVE AND COORDINATE EXACT LOCATION WITH STRUCTURAL.
48. USE A CALIBRATED TORQUE TOOL IN ACCORDANCE WITH NFPA 70 FOR ELECTRICAL INSTALLATION.
49. DO NOT RUN CONDUIT ON ROOFS. ALL CONDUIT SERVING ROOF MOUNTED EQUIPMENT MUST BE ROUTED ABOVE THE CEILING BELOW THE ROOF. TURN CONDUIT UP
THROUGH THE ROOF AT THE EQUIPMENT SERVED. SEE DETAIL ON ARCHITECTURAL DRAWINGS FOR SEALING OF CONDUIT PENETRATIONS.
50. WHEN INSTALLING RECEPTACLES, MOUNT THE GROUND PIN UP.
51. POWER SHALL ENTER THE SCIF AT A SINGLE POINT. SEAL ALL UTILITY PENETRATIONS TO MITIGATE ACOUSTIC EMANATIONS AND COVERT ENTRY.
52. NO CONDUITS CAN RUN THROUGH OR ABOVE THE SCIF UNLESS THEY SERVE THE SCIF.
53. PROVIDE A DIELECTRIC UNION INSIDE THE SCIF PERIMETER ADJACENT TO THE PENETRATION, OR GROUND THE CONDUIT WITHIN 6 INCHES OF THE PERIMETER
PENETRATION USING A NO. 4 WIRE TO THE BUILDING GROUND.
54. ALL CONDUIT ROUTES SHOWN ARE SUGGESTED ROUTING ONLY. ACTUAL ROUTES SHALL BE COORDINATED BY THE CONTRACTOR. PROVIDE PULL BOXES AS REQUIRED BY
CODE.
55. INSTALL ALL IN-GROUND CONDUITS BEFORE FOOTINGS.
56. ALL CONDUITS AND DUCT BANKS ENTERING THE BUILDNG SHALL BE PLACED TO RUN BELOW THE SCHEDULED REINFORCED CONCRETE BUILDING FOOTINGS. CONDUITS
MAY VERTICALLY PENETRATE FOOTINGS, AS NECESSARY, WITH 4" MINIMUM SEPERATION BETWEEN THEM.
DEMOLITION NOTES
1. IT IS STRONGLY RECOMMENDED THAT THE CONTRACTOR VISIT THE SITE PRIOR TO BIDDING TO ASCERTAIN EXISTING CONDITIONS AS HE WILL BE RESPONSIBLE FOR EXISTING CONDITIONS AS REQUIRED IN OTHER
NOTES.
2. ALL ITEMS SHOWN ON DEMOLITION DRAWINGS ARE TO BE REMOVED UNLESS NOTED OTHERWISE. REMOVE ALL ELECTRICAL ITEMS ASSOCIATED WITH ITEMS SHOWN TO BE REMOVED ON THE DEMOLITION DRAWINGS.
THIS MUST INCLUDE, BUT NOT BE LIMITED TO CONDUIT, WIRE, DEVICES, BOXES AND CONDUIT SUPPORTS.
3. THE FOLLOWING REMOVED ELECTRICAL EQUIPMENT MUST REMAIN THE PROPERTY OF THE OWNER AND BE TURNED OVER TO THE OWNER AT A LOCATION DESIGNATED BY THE OWNER ON THE SITE OF THE PROJECT:
PAD MOUNTED TRANSFROMERS AND EXTERIOR PANELBOARDS. CARE MUST BE TAKEN NOT TO DAMAGE THE REMOVED EQUIPMENT. THE REMOVED EQUIPMENT MUST BE STACKED NEATLY INSIDE OR OUTSIDE THE DESIGNATED STORAGE AREA AS DIRECTED BY THE OWNER. EQUIPMENT NOT DESIRED BY THE OWNER MUST BE DISPOSED OF OFF SITE BY THE CONTRACTOR AT NO ADDITIONAL COST. WIRE AND CONDUIT WILL
BECOME PROPERTY OF THE CONTRACTOR AND MUST BE DISPOSED OF OFF SITE.
4. ABANDONED CONDUIT MUST BE REMOVED TO THE EXTENT POSSIBLE. ABANDONED CONDUIT THAT CANNOT
BE REMOVED MUST HAVE ALL WIRING REMOVED FROM THEM.
5. WHERE EXISTING CONDUITS ARE TO BE REUSED, THE OLD WIRES MUST BE REMOVED, THE CONDUIT
SWABBED OUT, AND NEW WIRES PULLED IN.
6. BEFORE DEMOLISHING AND CONDUIT AND WIRE, THE CONTRACTOR MUST VERIFY WHAT IT SERVES TO
ENSURE THAT SERVICE IS NOT LOST TO EQUIPMENT OUTSIDE THE CONSTRUCTION AREA.
S o lic it a ti o n
N u m b e r:
I.
S
.O
S h e e t
F ile
N a m e
IDENTIFICATION
SHEET
R e v ie w e d
B y
D ra w n
B y
D e s ig n e d
B y
C h e c k e d
B y
D a te
F ile
N o
S y m b o l D e s c ri p ti o n
R e v is io n s
A p p ro v e d D a te
N o
US Army Corps of Engineers Mobile District
A
B C D
A B C D
E F G H I
E F G
H I
SHEET of
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
C O
R P
S O
F E
N G
IN
E
E R
S M
O B
IL
E
A
L A
B A
M A
W
8-
-R
-0
M E
Y
J
U N
E
K C
H
IL
D S
/1
/2
:1
:3
A
M
C
U s e rs \a tk is o n m \D o c u m e n ts \2
-E M a tt h e w
.A tk is o n s s a in c .c o m
. r v t
E-002
E L E
C T
R
IC
A L N
O T
E S
M A
T K
IS
O
N
M A
T K
IS
O
N
G Y
O S
T
S O
F S
P E
C
IA
L T
A C
T
IC
S O
P E
R A
T
IO
N S
F A
C
IL
IT
Y
H U
R L B
U R
T F
IE
L D
F
L
M
NA
T
T H E W B A T K I S
O
A AL A B A M
L DI C E N S E
NO. 26286
b b b b bb b bb b b b bb b b b b b b b b b b b
FEC
FE
FE
FEC
FE
25' WETLAND BUFFER
OBS. TWR.
WOOD
BLDG 91625
PORTABLE
WOOD BLDG.
TC/DOOR=42.43'
EXISTING TO REMAIN ABOVE
GROUND 15KV CABLE
JUNCTION PEDESTAL
REMOVE 1000KVA PADMOUNTED
TRANSFORMER 181-2. RETURN TO
GOVERNMENT. MOVE TO A LOCATION
ON BASE AS DIRECTED BY THE
CONTRACTING OFFICER. DEMOLISH
CONCRETE EQUIPMENT PAD.
REMOVE (2) 800A WP PANELBOARDS.
RETURN TO THE GOVERNMENT. MOVE
TO A LOCATION ON BASE AS DIRECTED
BY THE CONTRATING OFFICER.
DEMOLISH CONCRETE EQUIPMENT PAD.
REMOVE 250KVA PADMOUNTED
TRANSFORMER 181-3. RETURN TO
GOVERNMENT. MOVE TO A LOCATION
ON BASE AS DIRECTED BY THE
CONTRACTING OFFICER. DEMOLISH
CONCRETE EQUIPMENT PAD.
EXISTING TO
REMAIN ABOVE
GROUND 15KV
POWER CABLE
JUNCTION
PEDESTAL
EXISTING TO
REMAIN PAD MOUNT
TRANSFROMER
150KVA
EXISTING TO
REMAIN ABOVE
GROUND 15KV
POWER CABLE
JUNCTION
PEDESTAL
DEMOLISH EXSITING DUCTBANK
EUP
E U
P
E U
P
EUP
E U
P
EUP
S o lic it a ti o n
N u m b e r:
I.
S
.O
S h e e t
F ile
N a m e
IDENTIFICATION
SHEET
R e v ie w e d
B y
D ra w n
B y
D e s ig n e d
B y
C h e c k e d
B y
D a te
F ile
N o
S y m b o l D e s c ri p ti o n
R e v is io n s
A p p ro v e d D a te
N o
US Army Corps of Engineers Mobile District
A
B C D
A B C D
E F G H I
E F G
H I
SHEET ofSCALE: 1"=50'-0"
20' 50' 100'
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
C O
R P
S O
F E
N G
IN
E
E R
S M
O B
IL
E
A
L A
B A
M A
W
8-
-R
-0
M E
Y
J
U N
E
K C
H
IL
D S
/1
/2
:1
:3
A
M
C
U s e rs \a tk is o n m \D o c u m e n ts \2
-E M a tt h e w
.A tk is o n s s a in c .c o m
. r v t
SCALE: 1" = 50'-0" ES101
E L E
C T
R
IC
A L S
IT
E
P L A
N
D E
M O
L
IT
IO
N
M A
T K
IS
O
N
A L
O V
V O
R N
G Y
O S
T
S O
F S
P E
C
IA
L T
A C
T
IC
S O
P E
R A
T
IO
N S
F A
C
IL
IT
Y
H U
R L B
U R
T F
IE
L D
F
L
ELECTRICAL SITE PLAN - DEMOLITION
M
NA
T
T H E W B A T K I S
O
A AL A B A M
L DI C E N S E
NO. 26286
b bb b bb b b b bb b b b b b b b b b b b
HT CT
DIRECTION OF TRAVEL
WASH RACK
R A
P P
E L
T O
W E
R
FUTURE
EXPANSION AREA
TT
C H
IL
L E
R
OBS. TWR.
WOOD
BLDG 91625
PORTABLE
WOOD BLDG.
EXISTING TO REMAIN
ABOVE GROUND 15KV
POWER CABLE
JUNCTION 424
EXISTING TO REMAIN
ABOVE GROUND
15KV POWER CABLE
JUNCTION 181
EXISTING TO
REMAIN PAD MOUNT
TRANSFROMER
150KVA
EXISTING TO REMAIN
ABOVE GROUND
15KV POWER CABLE
JUNCTION PEDESTAL
PAD MOUNTED STOF
TRANSFORMER
15KV POWER CABLE JUNCTION
PEDESTAL BASIS OF DESIGN:
POWER DESIGN CJPF-30-50-L2-TAN
UP
EUP
E U
P E
U P
UP
EUP
SEE SINGLE LINE DIAGRAM
SHEET EP501
ES501
A6
ES501
A6
ELEC ROOM 1G09
ELEC ROOM 1D01
ELEC ROOM 1C16
1-2"C (CONDUCTORS
SEE SLD) & 1-2"EC
1-2"EC
1-2"EC
1-3"C (CONDUCTORS
SEE SLD) & 1-3"EC
2-4"EC
SOF SPECIAL TACTICS OPERATIONS FACILITY
TURN CONDUITS UP AND
TERMINATE IN NEW
DISCONNECT SERVING
WASH RACK, COORDINATE
EXACT LOCATION AND
REQUIREMENTS WITH THE
MANUFACTURER.
FIRE PUMP ROOM 1G10
US
US
ES501
D3
ES501
D6
ES503
D6
ES503
D6
MOBILE GENSET PAD.
SEE EP101
PAD MOUNTED FIRE
PUMP TRANSFORMER
STUB UP AND
CAP (TYP)
SANITARY LIFT PUMP
5HP, 208V, 3PH
SANITARY LIFT PUMP
5HP, 208V, 3PH
1-1"C (CONDUCTORS
SEE SLD) & 1-1"EC
1-1"C (CONDUCTORS
SEE SLD) & 1-1"EC
STUB UP AND
CAP (TYP)
STUB UP AND
CAP
SEE EP101 FOR POWER REQUIREMENTS
1G 1F 1D
1C 1B1A
FIRST FLOOR KEY PLANPLAN NORTH
114113112
116117
S o lic it a ti o n
N u m b e r:
I.
S
.O
S h e e t
F ile
N a m e
IDENTIFICATION
SHEET
R e v ie w e d
B y
D ra w n
B y
D e s ig n e d
B y
C h e c k e d
B y
D a te
F ile
N o
S y m b o l D e s c ri p ti o n
R e v is io n s
A p p ro v e d D a te
N o
US Army Corps of Engineers Mobile District
A
B C D
A B C D
E F G H I
E F G
H I
SHEET of
500 1500 3000
SCALE: 1:50
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
C O
R P
S O
F E
N G
IN
E
E R
S M
O B
IL
E
A
L A
B A
M A
W
8-
-R
-0
M E
Y
J
U N
E
K C
H
IL
D S
/1
/2
:1
:4
A
M
C
U s e rs \a tk is o n m \D o c u m e n ts \2
-E M a tt h e w
.A tk is o n s s a in c .c o m
. r v t
SCALE: 1" = 50'-0" ES102
S
IT
E P
L A
N
P O
W E
R
M A
T K
IS
O
N
A L
O V
V O
R N
G Y
O S
T
S O
F S
P E
C
IA
L T
A C
T
IC
S O
P E
R A
T
IO
N S
F A
C
IL
IT
Y
H U
R L B
U R
T F
IE
L D
F
L
SITE PLAN - POWER
GENERAL NOTES:
1. ROUTE ALL ELECTRICAL CONDUITS IN PLACE PRIOR TO PLACEMENT OF
STRUCTURAL FOOTINGS.
2. ALL CONDUITS AND DUCTBANKS ENTERING THE BUILDING…
This is the start of the file's text. The full file is on GovTribe.