Roseville City Hall Electrical Upgrade_Bid Issue 2025 07 28.pdf

PDF 7 MB Posted

Attached to
City of Roseville City Hall Electrical Upgrade
Solicitation number
AEW No. 0100-0570
Issued by
Macomb County, Michigan

About this file

This document is a comprehensive bid package for the City of Roseville City Hall Electrical Upgrades project, prepared by Anderson, Eckstein and Westrick, Inc. (AEW) in collaboration with TAC Associates, LLC. The project involves electrical system improvements at the Roseville City Hall in Macomb County, Michigan, with bid documents dated July 28, 2025. The scope includes replacing existing electrical panels (Panels B, BB, BBN, BBM, and J), installing new wireless lighting control systems with occupancy sensors, performing circuit tracing, and upgrading electrical infrastructure throughout the building's first floor. The project drawings and specifications cover detailed electrical demolition, new work plans, one-line diagrams, electrical schedules, and technical specifications for various electrical components.

The bid package includes extensive technical specifications covering electrical system requirements, including low-voltage conductors, grounding, raceways, wiring devices, enclosed switches, and motor controllers. The project appears to be funded through municipal capital improvement funds, with a focus on modernizing the city hall's electrical systems for improved energy efficiency and functionality. The specifications outline rigorous installation, testing, and quality control requirements, with provisions for manufacturer warranties and comprehensive field inspections. The electrical upgrade includes advanced features like wireless lighting controls, arc-flash hazard analysis, and short-circuit studies to ensure safety and performance. Bidders are required to provide detailed documentation, including shop drawings, product data, and compliance with various electrical codes and standards.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

-0

PR

O

JE

C

T N

AM

E

City of Roseville Macomb County, Michigan

TITLE SHEET 1

GENERAL PROJECT NOTES A011

FIRST FLOOR PLAN A101

FIRST REFLECTED CEILING PLAN A102

INDEX TO SHEETS

City Hall Electrical Upgrades

KIMBERLY A. NYE, AIA NO. 38689901 DATE

"I HEREBY CERTIFY THESE PLANS HAVE BEEN PREPARED UNDER MY

DIRECT SUPERVISION IN ACCORDANCE WITH ACT 240, PUBLIC ACTS

OF 1937 AS AMENDED- STATE OF MICHIGAN."

ANDERSON, ECKSTEIN AND

WESTRICK, INC.

CIVIL ENGINEERS SURVEYORS ARCHITECTS

MARTIN ROAD

CITY OF EASTPOINTE

C

IT

Y O

F W

AR

R

EN

TEN MILE ROAD

FRAZHO ROAD

GR

OE

SB

EC

K

HW

Y.

(M

-9 7)

H

AY

ES

R

O

AD

ED

SE

L

FO

R D

F W

(I

4)

C

IT

Y O

F S

T.

C

LA

IR

S H

O R

ES

TWELVE MILE ROAD

THIRTEEN MILE ROAD

CITY OF FRASER

G

AR

FI

EL

D

UTICA RO

AD

ED

SE

L

FO

R D

F

4)

KE

LL

Y

R O

AD

MASONIC BLVD.

CLINTON TOWNSHIP

LI

TT

LE

M

AC

K

TWELVE MILE ROADG

RA

TI

O

T A

VE

(M -3

THIRTEEN MILE ROAD

C

IT

Y O

F S

T.

C

LA

IR

S H

O R

ES

TEN MILE ROAD

THIRTEEN MILE ROAD

COMMON ROAD

COMMON ROAD

FOURTEEN MILE ROAD

MARTIN ROAD

I-696 I-696 I-696

FRAZHO ROAD

G

RA

TI

O

T A

VE

(M -3

G

RA

TI

O

T A

VE

(M -3

LI

TT

LE

M

AC

K

ED

SE

L

FO

RD

F

4)

H

AY

ES

R

O

AD

H

AY

ES

R

O

AD

GR

OE

SB

EC

K

HW

(M

7)

UTICA RO

AD

ELECTRICAL

ELECTRICAL DRAWING INDEX, SYMBOL LIST, GENERAL NOTES E001

PARTIAL FIRST FLOOR PLAN- ELECTRICAL DEMOLITION ED100

PARTIAL FIRST FLOOR PLAN- ELECTRICAL DEMOLITION ED101

PARTIAL FIRST FLOOR PLAN- ELECTRICAL NEW WORK E100

PARTIAL FIRST FLOOR PLAN- ELECTRICAL NEW WORK E101

PARTIAL POWER ONE-LINE DIAGRAM- DEMOLITION E200

PARTIAL POWER ONE-LINE DIAGRAM- NEW WORK E201

ELECTRICAL SCHEDULES E210

ELECTRICAL SCHEDULES E211

ELECTRICAL SCHEDULES

MISCELLANEOUS WIRING DIAGRAMS AND DETAILS E300

E301

ELECTRICAL SPECIFICATIONS E400

ELECTRICAL SPECIFICATIONS E401

E212

ELECTRICAL SPECIFICATIONS E402

ELECTRICAL SPECIFICATIONS E403

ELECTRICAL SPECIFICATIONS E404

ARCHITECTURE

MISCELLANEOUS WIRING DIAGRAMS AND DETAILS

AutoCAD SHX Text E

AutoCAD SHX Text W

AutoCAD SHX Text S

AutoCAD SHX Text

NORTH

AutoCAD SHX Text N.T.S.

AutoCAD SHX Text

CITATION DR.

AutoCAD SHX Text

WELLINGTON

AutoCAD SHX Text

WATERMAN DR.

AutoCAD SHX Text

BOWMAN CT.

AutoCAD SHX Text 15,000

AutoCAD SHX Text

SEND

AutoCAD SHX Text

FORTUNA

AutoCAD SHX Text

LEACH

AutoCAD SHX Text

DALE

AutoCAD SHX Text 16,000

AutoCAD SHX Text

LEHNER

AutoCAD SHX Text

WISEMAN

AutoCAD SHX Text

FERN

AutoCAD SHX Text

ROSE

AutoCAD SHX Text

COLE

AutoCAD SHX Text

CURTIS

AutoCAD SHX Text

WATERMAN CT.

AutoCAD SHX Text

PACKARD

AutoCAD SHX Text

BUICK

AutoCAD SHX Text

FORD

AutoCAD SHX Text

DODGE

AutoCAD SHX Text

CHALMERS

AutoCAD SHX Text

COURT

AutoCAD SHX Text

BRYAN

AutoCAD SHX Text

COMPSON

AutoCAD SHX Text

DALE CT.

AutoCAD SHX Text

HILL

AutoCAD SHX Text

COMPSON

AutoCAD SHX Text

BRYAN

AutoCAD SHX Text

MARGARET

AutoCAD SHX Text

LELAND

AutoCAD SHX Text

JUDITH

AutoCAD SHX Text

DALE

AutoCAD SHX Text

DORT

AutoCAD SHX Text

BELLANGER

AutoCAD SHX Text

CLANCY

AutoCAD SHX Text

LETHER

AutoCAD SHX Text

WOODMONT

AutoCAD SHX Text

KATHY

AutoCAD SHX Text

NAGEL

AutoCAD SHX Text

PETRIE

AutoCAD SHX Text

WILDWOOD

AutoCAD SHX Text

RIDGEMONT

AutoCAD SHX Text

ACADEMY

AutoCAD SHX Text

GRANDMONT

AutoCAD SHX Text

BLUMFIELD

AutoCAD SHX Text

ROBERTA

AutoCAD SHX Text

SUPERIOR

AutoCAD SHX Text

GRAND TRUNK RRY.

AutoCAD SHX Text

LEROY

AutoCAD SHX Text

PERRY DR.

AutoCAD SHX Text

W.CRESTMONT

AutoCAD SHX Text

E.CRESTMONT

AutoCAD SHX Text

WOODMONT

AutoCAD SHX Text

ALSIP

AutoCAD SHX Text

LARRY

AutoCAD SHX Text

LARRY

AutoCAD SHX Text

BELANGER

AutoCAD SHX Text

WOODMONT

AutoCAD SHX Text

GRANDMONT

AutoCAD SHX Text

ACADEMY

AutoCAD SHX Text

BARKMAN

AutoCAD SHX Text

BLUM

AutoCAD SHX Text

LOIS DR.

AutoCAD SHX Text

SECRETARIAT AVE

AutoCAD SHX Text

BEVERLY

AutoCAD SHX Text

COLE

AutoCAD SHX Text

EMERY

AutoCAD SHX Text

BETTY CT.

AutoCAD SHX Text

SUSAN CT.

AutoCAD SHX Text

ACADEMY

AutoCAD SHX Text

CHARLESTON

AutoCAD SHX Text

CIRCLE

AutoCAD SHX Text

NORTHVIEW

AutoCAD SHX Text

KENNEDY

AutoCAD SHX Text

GROVELAND

AutoCAD SHX Text

DARTMOUTH

AutoCAD SHX Text

HOFFMEYER

AutoCAD SHX Text

COLLINGWOOD

AutoCAD SHX Text

ARLINGTON

AutoCAD SHX Text

CAMBRIDGE

AutoCAD SHX Text

KOONTZ

AutoCAD SHX Text

NORMANDY

AutoCAD SHX Text

WALDORF

AutoCAD SHX Text

MACKINAC

AutoCAD SHX Text 17,000

AutoCAD SHX Text

BOWMAN DR.

AutoCAD SHX Text

ROBERTS

AutoCAD SHX Text

CAPRI

AutoCAD SHX Text

DOYLE

AutoCAD SHX Text

HUDSON

AutoCAD SHX Text

PAIGE

AutoCAD SHX Text

CAPRI

AutoCAD SHX Text

CT.

AutoCAD SHX Text

LAWN

AutoCAD SHX Text

BLAIR

AutoCAD SHX Text

MACOMB

AutoCAD SHX Text

OAKDALE

AutoCAD SHX Text

PINEHURST

AutoCAD SHX Text

PEARL

AutoCAD SHX Text

LEXINGTON

AutoCAD SHX Text

BARBARA

AutoCAD SHX Text

HURON

AutoCAD SHX Text

CHURCH

AutoCAD SHX Text

KELLY RD.

AutoCAD SHX Text

CHIPPENDALE

AutoCAD SHX Text 25000

AutoCAD SHX Text

BLUE ISLAND

AutoCAD SHX Text

ALLEN

AutoCAD SHX Text

MAYFIELD

AutoCAD SHX Text

JANET CT.

AutoCAD SHX Text

LASALLE

AutoCAD SHX Text

BERKSIRE

AutoCAD SHX Text

DORT

AutoCAD SHX Text

SARMORR

AutoCAD SHX Text

CT.

AutoCAD SHX Text

MAYFIELD

AutoCAD SHX Text

GROVELAND

AutoCAD SHX Text

BLVD

AutoCAD SHX Text

EASTGATE

AutoCAD SHX Text

KAISER

AutoCAD SHX Text

BETTMAR

AutoCAD SHX Text

WENFIELD

AutoCAD SHX Text

LASALLE

AutoCAD SHX Text

HOLLYWOOD

AutoCAD SHX Text

W. PARK

AutoCAD SHX Text

PARKINGTON

AutoCAD SHX Text

OAKLAND

AutoCAD SHX Text

GREENLEAF

AutoCAD SHX Text

WILDWOOD

AutoCAD SHX Text

KERSHAW

AutoCAD SHX Text

E. PARK

AutoCAD SHX Text

BUCKHANNON

AutoCAD SHX Text

SALEM

AutoCAD SHX Text

CARL

AutoCAD SHX Text

PINEHURST

AutoCAD SHX Text

FERNWOOD

AutoCAD SHX Text

HUNTINGTON

AutoCAD SHX Text

MARLENE

AutoCAD SHX Text

PHYLLIS

AutoCAD SHX Text

LINWOOD

AutoCAD SHX Text

BARBARA

AutoCAD SHX Text

HOFFMEYER

AutoCAD SHX Text

KOONTZ

AutoCAD SHX Text

RONALD

AutoCAD SHX Text

HURON

AutoCAD SHX Text

MARQUETTE

AutoCAD SHX Text

ROSEWOOD

AutoCAD SHX Text

FERNWOOD

AutoCAD SHX Text

GLENDALE

AutoCAD SHX Text

LINWOOD

AutoCAD SHX Text

BARBARA

AutoCAD SHX Text

NIEMAN

AutoCAD SHX Text

OAK

AutoCAD SHX Text

ROSEVILLE

AutoCAD SHX Text

TENNYSON

AutoCAD SHX Text

IVANHOE

AutoCAD SHX Text

LOWELL

AutoCAD SHX Text

FLORAL

AutoCAD SHX Text

CHESTNUT

AutoCAD SHX Text

GROVELAND

AutoCAD SHX Text

BOHN

AutoCAD SHX Text

CROSS

AutoCAD SHX Text

EDWARD

AutoCAD SHX Text

DEMERICK

AutoCAD SHX Text

MAPLE

AutoCAD SHX Text

CHARLESTON

AutoCAD SHX Text

BLUM

AutoCAD SHX Text

FOUNTAIN

AutoCAD SHX Text

FLORAL

AutoCAD SHX Text

GROVELAND

AutoCAD SHX Text

HOLLYWOOD

AutoCAD SHX Text

BOHN

AutoCAD SHX Text

NORTHVIEW

AutoCAD SHX Text

WAVERLY

AutoCAD SHX Text

FELICIAN

AutoCAD SHX Text

EDWARD

AutoCAD SHX Text

ROSEMONT

AutoCAD SHX Text

MAPLE

AutoCAD SHX Text

ESSEX

AutoCAD SHX Text

EASTWICK

AutoCAD SHX Text

BEECHURST

AutoCAD SHX Text

WOODLAND

AutoCAD SHX Text

LONGFELLOW

AutoCAD SHX Text

ELMHURST

AutoCAD SHX Text

SYCAMORE

AutoCAD SHX Text

PINEHURST

AutoCAD SHX Text

BEECHWOOD

AutoCAD SHX Text

HAZELWOOD

AutoCAD SHX Text

SPRUCE

AutoCAD SHX Text

BROHL

AutoCAD SHX Text

MEIER

AutoCAD SHX Text

MESLE

AutoCAD SHX Text

PINEHURST

AutoCAD SHX Text

ELIZABETH

AutoCAD SHX Text

HOMER

AutoCAD SHX Text

LINCOLN DR.

AutoCAD SHX Text

HILLVIEW

AutoCAD SHX Text

BIEHL

AutoCAD SHX Text

BAINE

AutoCAD SHX Text

VICTOR

AutoCAD SHX Text

KELLY

AutoCAD SHX Text

MAYWOOD

AutoCAD SHX Text

KELLY

AutoCAD SHX Text

CHIPPENDALE CT.

AutoCAD SHX Text Private St.

AutoCAD SHX Text

BELLEAIR

AutoCAD SHX Text

PATTOW

AutoCAD SHX Text

BARNES

AutoCAD SHX Text

COLLINGWOOD

AutoCAD SHX Text

CHIPPENDALE

AutoCAD SHX Text

BELLEAIR

AutoCAD SHX Text

ELM

AutoCAD SHX Text

PATTOW

AutoCAD SHX Text

NORMANDY

AutoCAD SHX Text

WALDORF

AutoCAD SHX Text

ARLINGTON

AutoCAD SHX Text 27,000

AutoCAD SHX Text

PINEWOOD

AutoCAD SHX Text

RIDGEWOOD

AutoCAD SHX Text

LAWNWOOD

AutoCAD SHX Text

BRINKER

AutoCAD SHX Text

TICHE

AutoCAD SHX Text

VAN HOWE

AutoCAD SHX Text

BOHNHOFF

AutoCAD SHX Text

WALRDORF

AutoCAD SHX Text

O'NEIL

AutoCAD SHX Text

LASSLETT

AutoCAD SHX Text

MELVIN

AutoCAD SHX Text

JAHNS DR.

AutoCAD SHX Text

GINLEY

AutoCAD SHX Text

SCHRAM

AutoCAD SHX Text

VICTOR

AutoCAD SHX Text

ASMUS

AutoCAD SHX Text

O'NEIL

AutoCAD SHX Text

KAUFMAN

AutoCAD SHX Text

GARFIELD

AutoCAD SHX Text

DRIFTWOOD

AutoCAD SHX Text

INDUSTRIAL

AutoCAD SHX Text

DRIFTWOOD

AutoCAD SHX Text

CALLAHAN

AutoCAD SHX Text

HAYES BLVD.

AutoCAD SHX Text

RUDLAND

AutoCAD SHX Text

WELLINGTON AVE.

AutoCAD SHX Text

SANDALWOOD

AutoCAD SHX Text

BARKMAN

AutoCAD SHX Text

CEDARWOOD

AutoCAD SHX Text

LORETO DR.

AutoCAD SHX Text

CANBERRA

AutoCAD SHX Text

FERNTREE

AutoCAD SHX Text

BLOSSOM

AutoCAD SHX Text

CHARMAINE

AutoCAD SHX Text

ROYCROFT

AutoCAD SHX Text

EVERLY

AutoCAD SHX Text

ELDERWOOD

AutoCAD SHX Text

BLOSSOM

AutoCAD SHX Text

CLOVER

AutoCAD SHX Text

CALLAHAN

AutoCAD SHX Text

JO CT.

AutoCAD SHX Text

ANNE CT.

AutoCAD SHX Text

GROVERDALE

AutoCAD SHX Text

CANBERRA

AutoCAD SHX Text

MAYFLOWER

AutoCAD SHX Text

DOLPHIN

AutoCAD SHX Text

LARKSPUR

AutoCAD SHX Text

SPYBROOK

AutoCAD SHX Text

J CARLS

AutoCAD SHX Text

INDIGO

AutoCAD SHX Text

BLUEHILL

AutoCAD SHX Text

FLANNAGAN

AutoCAD SHX Text

DUGAN

AutoCAD SHX Text

HENNIGAN

AutoCAD SHX Text

FLANAGAN

AutoCAD SHX Text

DUGAN

AutoCAD SHX Text

GRAND TRUNK RRY

AutoCAD SHX Text

YEW

AutoCAD SHX Text

CANBERRA

AutoCAD SHX Text

BEACONSFIELD

AutoCAD SHX Text

TERRACE

AutoCAD SHX Text

ROSE

AutoCAD SHX Text

DR.

AutoCAD SHX Text

ROSEMONT

AutoCAD SHX Text

DEMBS DR.

AutoCAD SHX Text

COMMONWEALTH

AutoCAD SHX Text

EASTLAND

AutoCAD SHX Text

PARKWAY

AutoCAD SHX Text

ROSE TERRACE DR.

AutoCAD SHX Text

WILLOW POINT

AutoCAD SHX Text

EAST POINT DR.

AutoCAD SHX Text

DRAGER

AutoCAD SHX Text

DRAGER DR.

AutoCAD SHX Text

GREGG

AutoCAD SHX Text

GREGG

AutoCAD SHX Text

DR.

AutoCAD SHX Text

ROY

AutoCAD SHX Text

VICTOR

AutoCAD SHX Text

BIRMINGHAM

AutoCAD SHX Text

WELLWORTH

AutoCAD SHX Text

GROVE

AutoCAD SHX Text

PETERS

AutoCAD SHX Text

HILLVIEW

AutoCAD SHX Text

PINEHURST

AutoCAD SHX Text

DELAWARE

AutoCAD SHX Text

GALLOWAY

AutoCAD SHX Text

MELVIN

AutoCAD SHX Text

TRANQUIL

AutoCAD SHX Text

PARK

AutoCAD SHX Text

GALLOWAY

AutoCAD SHX Text

PARK

AutoCAD SHX Text

RUTHDALE

AutoCAD SHX Text

GLENHURST

AutoCAD SHX Text

BROADHURST

AutoCAD SHX Text

PINEHURST

AutoCAD SHX Text

WEXFORD

AutoCAD SHX Text

PASADENA

AutoCAD SHX Text

GALLOWAY

AutoCAD SHX Text

JOHN J

AutoCAD SHX Text

EASTLAND

AutoCAD SHX Text

PARK

AutoCAD SHX Text

CASILE

AutoCAD SHX Text

CASILE

AutoCAD SHX Text

SYLVAN

AutoCAD SHX Text

DAWN

AutoCAD SHX Text

SUNBURST

AutoCAD SHX Text

NORMAL

AutoCAD SHX Text

NORMAL

AutoCAD SHX Text

PROGRESS

AutoCAD SHX Text

QUINKERT

AutoCAD SHX Text

KELLY

AutoCAD SHX Text

EASTLAND

AutoCAD SHX Text

WILFRED

AutoCAD SHX Text

FLORENCE

AutoCAD SHX Text

ACHUSETTS

AutoCAD SHX Text

MASS

AutoCAD SHX Text

IRE

AutoCAD SHX Text

CONNECTICUT

AutoCAD SHX Text

BIRMINGHAM

AutoCAD SHX Text

DELAWARE

AutoCAD SHX Text

KAUFMAN

AutoCAD SHX Text

MICHIGAN

AutoCAD SHX Text

PFC WETZEL BLVD

AutoCAD SHX Text

FLORIDA

AutoCAD SHX Text

VFW MEMORIAL

AutoCAD SHX Text

IOWA

AutoCAD SHX Text

MITCHELL

AutoCAD SHX Text

GEORGIA

AutoCAD SHX Text

BIGALOW

AutoCAD SHX Text

WALDRON

AutoCAD SHX Text

GLENN

AutoCAD SHX Text

DRIVE

AutoCAD SHX Text

CONGRESS

AutoCAD SHX Text

SENATOR

AutoCAD SHX Text

LEGION

AutoCAD SHX Text

COOLIDGE

AutoCAD SHX Text

HARDING

AutoCAD SHX Text

MC DONALD

AutoCAD SHX Text

WASHINGTON

AutoCAD SHX Text

GARDEN COURT

AutoCAD SHX Text

BIGALOW

AutoCAD SHX Text

FENTON

AutoCAD SHX Text

WALLACE

AutoCAD SHX Text

MINNESOTA

AutoCAD SHX Text

TENNESSEE

AutoCAD SHX Text

COLORADO

AutoCAD SHX Text

FLORIAN

AutoCAD SHX Text

MARYLAND

AutoCAD SHX Text

ALABAMA

AutoCAD SHX Text

INDIANA

AutoCAD SHX Text

ILLINOIS

AutoCAD SHX Text

ROCKPORT

AutoCAD SHX Text

SKYLINE

AutoCAD SHX Text

SHADOWOODS DR.

AutoCAD SHX Text

CANDLELIGHT

AutoCAD SHX Text

MERRILY

AutoCAD SHX Text

MILL

AutoCAD SHX Text

GAY

AutoCAD SHX Text

GREENHAVEN

AutoCAD SHX Text

CORNILLE DR.

AutoCAD SHX Text

HOMELAND

AutoCAD SHX Text

ELLIS

AutoCAD SHX Text

CATHERINE

AutoCAD SHX Text

FLORA

AutoCAD SHX Text

ERIN

AutoCAD SHX Text

BEACONSFIELD

AutoCAD SHX Text

MC KINNON

AutoCAD SHX Text

DAVIDSON

AutoCAD SHX Text

JUDILANE

AutoCAD SHX Text

SUSILANE

AutoCAD SHX Text

EASTWAY

AutoCAD SHX Text

SOLON

AutoCAD SHX Text

MULSO

AutoCAD SHX Text

JEROME

AutoCAD SHX Text

BRANDT

AutoCAD SHX Text

ROSEGARDEN DR.

AutoCAD SHX Text

NORTHWAY

AutoCAD SHX Text

IVY DR.

AutoCAD SHX Text

MCGILL

AutoCAD SHX Text

BARRIS

AutoCAD SHX Text

WUREFUL

AutoCAD SHX Text

VOILAND

AutoCAD SHX Text

LAKEWORTH

AutoCAD SHX Text

MACEL

AutoCAD SHX Text 29000

AutoCAD SHX Text

RYMAL

AutoCAD SHX Text

ELMWOOD

AutoCAD SHX Text 30000

AutoCAD SHX Text

FLORA

AutoCAD SHX Text

GARFIELD

AutoCAD SHX Text

ROCK

AutoCAD SHX Text

FRANK

AutoCAD SHX Text

PARK

AutoCAD SHX Text

BELANGER

AutoCAD SHX Text

STURGEON ST

AutoCAD SHX Text

STURGEON CT

AutoCAD SHX Text

EDISON

AutoCAD SHX Text COPYRIGHT, 2025, ANDERSON, ECKSTEIN AND WESTRICK, INC. M:\0100\0100-0570\CAD\DRAWINGS\CONSTRUCTION\ARCH\_COVER.DWG Layout: Roseville Cover 7/26/2025 1:31:57 PM

51301 Schoenherr Road Shelby Township, MI 48315

586.726.1234 | aewinc.com

Engineering Strong Communities

0100-0570

ROSEVILLE CITY

HALL ELECTRICAL

UPGRADES

CITY OF ROSEVILLE

SHEET TITLE:

COPYRIGHT, 2025, ANDERSON, ECKSTEIN AND WESTRICK, INC.

CHECKED BY:DRAWN BY:

SCALE:

PRELIMINARY

DATE SUBMITTALS/REVISIONS

PROJECT NO.

SHEET NO.

CLIENT:

PROJECT NAME:

CONSTRUCTION RECORD

DATE:

A011--7/26/2025 1:24:45 PM

M:\0100\0100-0570\CAD\DRAWINGS\CONSTRUCTION\ARCH\TITLEBLK.DWG

Know what's below.

72 hours before you dig.

Call R

GENERAL NOTES

GENERAL NOTES

A011

SPK JRA JULY 2025

06/23/2025 OWNER REVIEW

07/28/2025 BID ISSUE

1. THE CONTRACTOR IS RESPONSIBLE FOR ALL PERMITS, FEES AND INSPECTIONS.

BUILDING PERMIT FEE WILL BE WAVED BY THE CITY.

2. ALL CONTRACTORS SHALL COORDINATE THE LOCATION OF DUCTS, PIPING, BOXES,

CHASES, CONDUITS, ETC... WITH THE MECHANICAL, ELECTRICAL AND ALL OTHER

TRADES.

3. CAULK ALL JOINTS BETWEEN DOOR FRAMES, WINDOW FRAMES, MASONRY WALLS

AND ALL DISSIMILAR MATERIALS.

4. PROVIDE ALL NECESSARY BLOCKING (USE ONLY NON-COMBUSTIBLE). AS REQUIRED

TO SUPPORT LIGHTING, SIGNS, BRACKETS, ACCESSORIES, ETC

5. ALL DIMENSIONS ARE FROM FACE OF WALL TO FACE OF WALL OR FACE OF BLOCK

TO FACE OF BLOCK.

6. ALL ITEMS NOTED "BY OWNER" OR "N.I.C." ARE NOT IN CONTRACT.

7. CONTRACTOR SHALL CHECK AND VERIFY ALL DIMENSIONS EXISTING AND

PROPOSED ON THE JOB. REPORT ALL DEVIATIONS FROM DRAWINGS PRIOR TO

START OF CONSTRUCTION.

8. ALL CONTRACTORS SHALL CONSTRUCT THIS PROJECT IN ACCORDANCE WITH ALL

STATE, FEDERAL AND LOCAL CODES.

9. ALL CONTRACTORS SHALL REPAIR ANY DAMAGES OR DISTURBANCES TO THE

EXISTING BUILDING AND SITE.

10. ALL MATERIALS USED ARE REQUIRED TO BE OF GOOD QUALITY AND MEET OR

EXCEED ALL APPLICABLE INDUSTRY STANDARDS.

11. ALL WORK IS TO BE DONE WITH THE APPROPRIATE TOOLS AND MATERIALS. THE

ARCHITECT HAS THE RIGHT TO REJECT ANY WORK NOT DONE APPROPRIATELY.

12. REMOVE ALL TRASH AND DEBRIS FROM THE SITE. WASH ALL SURFACES DUST AND

SWEEP TO REMOVE ALL DIRT. REMOVE ALL TEMPORARY LABELS.

13. ALL CONTRACTORS AND SUBCONTRACTORS SHALL PROVIDE ALL WORK SHOWN IN

ANY PART OF THE DOCUMENTS, I.E. HAND DRYER SHOWN ON ARCHITECTURAL

DRAWINGS MUST BE WIRED BY THE ELECTRICIAN WHETHER IT IS OR IS NOT SHOWN

ON THE ELECTRICAL DRAWINGS.

14. THE GENERAL CONTRACTOR SHALL PROVIDE A MIN. 1 YEAR (U.N.O.) WARRANTY ON

ALL MATERIAL, EQUIPMENT AND WORK PERFORMED.

15. RELOCATE ELECTRICAL / PLUMBING AS REQUIRED.

16. COOR. WITH CITY CONTRACTED SECURITY VENDOR.

ABBREVIATIONS

CONST CONSTRUCTION

UNO UNLESS NOTED OTHERWISE

CLASSIFICATION)

AND AIR CONDITIONING

HEATING, VENTILATION,

HOLLOW METAL STEEL

HORIZONTAL

HVAC

H.M.

HOR

HT. HEIGHT

WD.

WWF

W /

WAIT

W/O

VWC

VB

VIF

VWB

VCT

VERT

WOOD

VAPOR BARRIER

VINYL WALL BASE

VINYL COMPOSITE TILE

WELDED WIRE FABRIC

VINYL WALL COVERING

WAITING

WITH OUT

WITH

VERTICAL

VERIFY IN FIELD

CONTINUOUS

COORDINATE

DIAMETER

DOWN SPOUT

DIMENSION

DEMOLISH, DEMOLITION

EXISTING

EXPANSION, EXPOSED

ELEVATION, ELEVATOR

EXTERIOR

ENGINEER

ELECTRICAL

EXPANSION JOINT

PANEL

FABRIC WALL COVERING

FIRE EXTINGUISHER

FIELD VERIFY

FIBERGLASS REINFORCED

FOOTING

GENERAL CONTRACTOR

GAGE, GAUGE

GALVANIZED

FLOOR

ELECTRICAL WATER COOLER

ELECTRICAL CONTRACTOR

GYPSUM DRYWALL (WALLBOARD)

FIRE EXTINGUISHER CABINET

GWB TYPE-X (FIRE RESISTIVE

FTG

GALV

GWB

GWB-X

GC

FLR

GA

FWC

F.R.P.

FEC

FIN

FE

F.V.

FINISH

EWC

ELEV.

ENG

ELEC.

EXT

EXP

EXIST.

EQ

EJ

EC

EQUAL

DEMO

COORD

CONT

DIA

DIM

DR

DS

DN DOWN

DOOR

TOC

TH

TOF

TOW

TYP.

TEL

T T & G

TEMP.

SYS

STL STD

STOR

STRUCT.

SUSP.

STR STL

STL

SPEC

STD

STL JST

SPKLR

TONGUE AND GROOVE

TEMPERED GLAZED

TYPICAL

THRESHOLD

TOP OF WALL

TOP OF FOOTER

TOP OF CURB

TELEPHONE

TEMPERED

SYSTEM

STRUCTURAL STEEL

STEEL JOIST

STEEL STUD

STORAGE

SUSPENDED

STRUCTURE

SPRINKLER

STANDARD

SPECIFICATION

STEEL

SCHED.

SIM.

RO

RD

RM

ROW

REF.

REC

REINF

REP

RE-BAR

REQ

RECPT

RWC

PSI

SCHEDULE

SIMILAR

RIGHT OF WAY

ROOF DRAIN

ROUGH OPENING

ROOM

POUNDS PER SQ. INCH

REPRESENTATIVE

REINFORCING BARS

RAIN WATER CONDUCTOR

RECESSED

REFLECTED

REINFORCING

REQUIRED

RECEPTION

ABOVE FINISH FLOOR

ACCORDANCE

ALTERNATE

ACOUSTICAL

ACCOMMODATE

ARCHITECT

ALUMINUM

ACCESS DOOR

ACOUSTICAL PANEL

BEARING PLATE

BITUMINOUS

BLOCK

BEARING

BOTTOM

BUILDINGS

BOARD

CENTER LINE

CEILING

CIRCULATION

CLOSET

COMPUTER

CONCRETE

COLUMN

CONCRETE MASONRY UNIT

CABINET

CONFERENCE

B PL

CLG.

CIRC

CLO

COL

CMU

CONC.

COMP

CONF.

CL

BIT

BLK

BRD

BOTT

BLDG

CAB

AD

AC.P.

ACOUS

ARCH

ALUM.

ALT

BRG

@ AT

A.F.F.

ACCORD

ACCOM

PL

PLAS.

PLYWD

OD

OPP.

OH

NIC

NTS

NO OR #

OC

MIN

MISC.

MET

N/A

OUTSIDE DIAMETER

PLATE

PLASTIC

PLYWOOD

OPPOSITE

OVERHEAD

NOT APPLICABLE

NOT IN CONTRACT

NUMBER

NOT TO SCALE

ON CENTER

MINIMUM

METAL

MISCELLANEOUS

MC

MAX

MECH.

M.P.E.

LLV

LIN FT

LAV

JST

LAM.

JT

LONG LEG VERTICAL

MECHANICAL CONTRACT (OR)

MECHANICAL, PLUMBING, ELECTRICAL

MAXIMUM

MECHANICAL

LINEAR FOOT

LAVATORY (ADA)

LAMINATE

JOINT

JOIST

BRACKETBRKT

COURSESCRS

DIVISIONDIV

FLOOR DRAINFD

EXHAUST FANEF

LH LEFT HAND

MFR MANUFACTURER

KSF KIPS PER SQUARE FOOT

INSIDE DIAMETERID

INCHESINS

LHR LEFT HAND REVERSE

NRC NOISE REDUCTION COEFFICIENT

PO POLYETHYLENE

PSF POUNDS PER SQ. FOOT

PVC POLYVINYL CHLORIDE

RH RIGHT HAND

RHR RIGHT HAND REVERSE

SS STAINLESS STEEL

TOM TOP OF MASONRY

FF FINISHED FLOOR

WC WATER CLOSET (FLUSH VALVE ADA)

UR URINAL

WT WEIGHT

' FOOT, FEET

" INCH, INCHES

# POUNDS

RFM RECESSED FLOOR MAT

COAT RACKCR

NOTE: NOT ALL ABBREVIATIONS USED.

ABBREVIATIONS INCLUDE BUT NOT LIMITED TO THIS LIST.

XXX

XXX

SYMBOL KEY

DETAIL / ENLARGED PLAN

LOCATION

SHEET NUMBER

XXX

XXX

BUILDING SECTION

LOCATION

SHEET NUMBER

XXX

XXX

SECTION CUT

XXX

XXX

LOCATION

SHEET NUMBER

LOCATION

SHEET NUMBER

INTERIOR / EXTERIOR ELEVATION

NORTH

NORTH ARROW

XXXX

XXXX

XXXX

ROOM LABEL

ROOM NAME

ROOM NUMBER

XXX

XX

XX

WINDOW MARK

WALL MARK

DOOR MARK

STUD WALL

MASONRY WALL

BRICK VENEER

STUD PARTITION

EXISTING WALL

DEMOLITION

ELEVATION MARK

NEW DOOR

EXISTING DOOR

1 HR. RATED WALL

RF ROOF FAN

UTILITY INFORMATION, AS SHOWN, INDICATES APPROXIMATE INFORMATION, AS SHOWN, INDICATES APPROXIMATE INFORMATION, AS SHOWN, INDICATES APPROXIMATE AS SHOWN, INDICATES APPROXIMATE AS SHOWN, INDICATES APPROXIMATE SHOWN, INDICATES APPROXIMATE SHOWN, INDICATES APPROXIMATE INDICATES APPROXIMATE INDICATES APPROXIMATE APPROXIMATE APPROXIMATE LOCATIONS AND TYPES OF EXISTING FACILITIES ONLY, AS AND TYPES OF EXISTING FACILITIES ONLY, AS AND TYPES OF EXISTING FACILITIES ONLY, AS TYPES OF EXISTING FACILITIES ONLY, AS TYPES OF EXISTING FACILITIES ONLY, AS OF EXISTING FACILITIES ONLY, AS OF EXISTING FACILITIES ONLY, AS EXISTING FACILITIES ONLY, AS EXISTING FACILITIES ONLY, AS FACILITIES ONLY, AS FACILITIES ONLY, AS ONLY, AS ONLY, AS AS AS DISCLOSED BY RECORDS PROVIDED TO THIS FIRM FROM BY RECORDS PROVIDED TO THIS FIRM FROM BY RECORDS PROVIDED TO THIS FIRM FROM RECORDS PROVIDED TO THIS FIRM FROM RECORDS PROVIDED TO THIS FIRM FROM PROVIDED TO THIS FIRM FROM PROVIDED TO THIS FIRM FROM TO THIS FIRM FROM TO THIS FIRM FROM THIS FIRM FROM THIS FIRM FROM FIRM FROM FIRM FROM FROM FROM THE VARIOUS UTILITY COMPANIES. NO GUARANTEE IS VARIOUS UTILITY COMPANIES. NO GUARANTEE IS VARIOUS UTILITY COMPANIES. NO GUARANTEE IS UTILITY COMPANIES. NO GUARANTEE IS UTILITY COMPANIES. NO GUARANTEE IS COMPANIES. NO GUARANTEE IS COMPANIES. NO GUARANTEE IS NO GUARANTEE IS NO GUARANTEE IS NO GUARANTEE IS GUARANTEE IS GUARANTEE IS IS IS GIVEN OR IMPLIED AS TO THE COMPLETENESS OR OR IMPLIED AS TO THE COMPLETENESS OR OR IMPLIED AS TO THE COMPLETENESS OR IMPLIED AS TO THE COMPLETENESS OR IMPLIED AS TO THE COMPLETENESS OR AS TO THE COMPLETENESS OR AS TO THE COMPLETENESS OR TO THE COMPLETENESS OR TO THE COMPLETENESS OR THE COMPLETENESS OR THE COMPLETENESS OR COMPLETENESS OR COMPLETENESS OR OR OR ACCURACY THEREOF. PRIOR TO CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF TO CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF TO CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF ALL LOCATIONS AND DEPTHS OF ALL LOCATIONS AND DEPTHS OF LOCATIONS AND DEPTHS OF LOCATIONS AND DEPTHS OF AND DEPTHS OF AND DEPTHS OF DEPTHS OF DEPTHS OF OF OF EXISTING OVERHEAD AND UNDERGROUND UTILITIES (IN OVERHEAD AND UNDERGROUND UTILITIES (IN OVERHEAD AND UNDERGROUND UTILITIES (IN AND UNDERGROUND UTILITIES (IN AND UNDERGROUND UTILITIES (IN UNDERGROUND UTILITIES (IN UNDERGROUND UTILITIES (IN UTILITIES (IN UTILITIES (IN (IN (IN (IN CONFLICT WITH THE CONSTRUCTION OF THESE PROPOSED WITH THE CONSTRUCTION OF THESE PROPOSED WITH THE CONSTRUCTION OF THESE PROPOSED THE CONSTRUCTION OF THESE PROPOSED THE CONSTRUCTION OF THESE PROPOSED CONSTRUCTION OF THESE PROPOSED CONSTRUCTION OF THESE PROPOSED OF THESE PROPOSED OF THESE PROPOSED THESE PROPOSED THESE PROPOSED PROPOSED PROPOSED IMPROVEMENTS) SHALL BE VERIFIED IN THE FIELD. DURING SHALL BE VERIFIED IN THE FIELD. DURING SHALL BE VERIFIED IN THE FIELD. DURING BE VERIFIED IN THE FIELD. DURING BE VERIFIED IN THE FIELD. DURING VERIFIED IN THE FIELD. DURING VERIFIED IN THE FIELD. DURING IN THE FIELD. DURING IN THE FIELD. DURING THE FIELD. DURING THE FIELD. DURING FIELD. DURING FIELD. DURING DURING DURING THE CONSTRUCTION, THE CONTRACTOR SHALL PROTECT CONSTRUCTION, THE CONTRACTOR SHALL PROTECT CONSTRUCTION, THE CONTRACTOR SHALL PROTECT THE CONTRACTOR SHALL PROTECT THE CONTRACTOR SHALL PROTECT CONTRACTOR SHALL PROTECT CONTRACTOR SHALL PROTECT SHALL PROTECT SHALL PROTECT PROTECT PROTECT AND SUPPORT ALL UTILITIES THAT ARE ENCOUNTERED. SUPPORT ALL UTILITIES THAT ARE ENCOUNTERED. SUPPORT ALL UTILITIES THAT ARE ENCOUNTERED. ALL UTILITIES THAT ARE ENCOUNTERED. ALL UTILITIES THAT ARE ENCOUNTERED. UTILITIES THAT ARE ENCOUNTERED. UTILITIES THAT ARE ENCOUNTERED. THAT ARE ENCOUNTERED. THAT ARE ENCOUNTERED. ARE ENCOUNTERED. ARE ENCOUNTERED. ENCOUNTERED. ENCOUNTERED. (ALL COSTS FOR UTILITY LOCATION VERIFICATION, SUPPORT COSTS FOR UTILITY LOCATION VERIFICATION, SUPPORT COSTS FOR UTILITY LOCATION VERIFICATION, SUPPORT FOR UTILITY LOCATION VERIFICATION, SUPPORT FOR UTILITY LOCATION VERIFICATION, SUPPORT UTILITY LOCATION VERIFICATION, SUPPORT UTILITY LOCATION VERIFICATION, SUPPORT LOCATION VERIFICATION, SUPPORT LOCATION VERIFICATION, SUPPORT VERIFICATION, SUPPORT VERIFICATION, SUPPORT SUPPORT SUPPORT AND PROTECTION SHALL BE INCLUDED IN THE PROPOSED PROTECTION SHALL BE INCLUDED IN THE PROPOSED PROTECTION SHALL BE INCLUDED IN THE PROPOSED SHALL BE INCLUDED IN THE PROPOSED SHALL BE INCLUDED IN THE PROPOSED BE INCLUDED IN THE PROPOSED BE INCLUDED IN THE PROPOSED INCLUDED IN THE PROPOSED INCLUDED IN THE PROPOSED IN THE PROPOSED IN THE PROPOSED THE PROPOSED THE PROPOSED PROPOSED PROPOSED PAY ITEM CONFLICTING WITH THAT UTILITY). DURING CONSTRUCTION, THE CONTRACTOR SHALL USE CONSTRUCTION, THE CONTRACTOR SHALL USE CONSTRUCTION, THE CONTRACTOR SHALL USE THE CONTRACTOR SHALL USE THE CONTRACTOR SHALL USE CONTRACTOR SHALL USE CONTRACTOR SHALL USE SHALL USE SHALL USE USE USE EXTREME CAUTION WHEN OPERATING NEAR ANY AND ALL CAUTION WHEN OPERATING NEAR ANY AND ALL CAUTION WHEN OPERATING NEAR ANY AND ALL WHEN OPERATING NEAR ANY AND ALL WHEN OPERATING NEAR ANY AND ALL OPERATING NEAR ANY AND ALL OPERATING NEAR ANY AND ALL NEAR ANY AND ALL NEAR ANY AND ALL ANY AND ALL ANY AND ALL AND ALL AND ALL ALL ALL OVERHEAD AND / OR BURIED UTILITIES.

51301 Schoenherr Road Shelby Township, MI 48315

586.726.1234 | aewinc.com

Engineering Strong Communities

0100-0570

ROSEVILLE CITY

HALL ELECTRICAL

UPGRADES

CITY OF ROSEVILLE

SHEET TITLE:

COPYRIGHT, 2025, ANDERSON, ECKSTEIN AND WESTRICK, INC.

CHECKED BY:DRAWN BY:

SCALE:

PRELIMINARY

DATE SUBMITTALS/REVISIONS

PROJECT NO.

SHEET NO.

CLIENT:

PROJECT NAME:

CONSTRUCTION RECORD

DATE:

A101--7/26/2025 1:25:39 PM

M:\0100\0100-0570\CAD\DRAWINGS\CONSTRUCTION\ARCH\TITLEBLK.DWG

Know what's below.

72 hours before you dig.

Call R

NORTH

PLAN NOTES

1. REFER TO ELECTRICAL DRAWINGS FOR NEW WORK.

SCALE:

FIRST FLOOR PLAN

3/32" = 1'-0"

A101

A101

SPK JRA JULY 2025

07/28/2025 BID ISSUE

FIRST FLOOR PLAN

OPEN

OFFICE

(CLERKS DEPT)

MENS

CONFERENCE

CITY

MANAGER

OFFICE

OFFICE

OFFICE

SUPPORT

OFFICE

OPEN

OFFICE

OFFICE

OPEN

OFFICE

OPEN

OFFICE

OPEN

OFFICE

(TREASURY

DEPT)

OFFICE

OFFICE

CONFERENCE

OPEN

OFFICE

(ASSESSING

DEPT)

OFFICE

NETWORK

NETWORK

STAIRS

OFFICE

OFFICE

OFFICE

OPEN

OFFICE

(BUILDING

DEPT)

CORRIDOR

WOMENS

MENS

EMPLOYEES

LOUNGE

OPEN

OFFICE

OFFICE

J.C.CONF. RM.

UTILITY INFORMATION, AS SHOWN, INDICATES APPROXIMATE INFORMATION, AS SHOWN, INDICATES APPROXIMATE INFORMATION, AS SHOWN, INDICATES APPROXIMATE AS SHOWN, INDICATES APPROXIMATE AS SHOWN, INDICATES APPROXIMATE SHOWN, INDICATES APPROXIMATE SHOWN, INDICATES APPROXIMATE INDICATES APPROXIMATE INDICATES APPROXIMATE APPROXIMATE APPROXIMATE LOCATIONS AND TYPES OF EXISTING FACILITIES ONLY, AS AND TYPES OF EXISTING FACILITIES ONLY, AS AND TYPES OF EXISTING FACILITIES ONLY, AS TYPES OF EXISTING FACILITIES ONLY, AS TYPES OF EXISTING FACILITIES ONLY, AS OF EXISTING FACILITIES ONLY, AS OF EXISTING FACILITIES ONLY, AS EXISTING FACILITIES ONLY, AS EXISTING FACILITIES ONLY, AS FACILITIES ONLY, AS FACILITIES ONLY, AS ONLY, AS ONLY, AS AS AS DISCLOSED BY RECORDS PROVIDED TO THIS FIRM FROM BY RECORDS PROVIDED TO THIS FIRM FROM BY RECORDS PROVIDED TO THIS FIRM FROM RECORDS PROVIDED TO THIS FIRM FROM RECORDS PROVIDED TO THIS FIRM FROM PROVIDED TO THIS FIRM FROM PROVIDED TO THIS FIRM FROM TO THIS FIRM FROM TO THIS FIRM FROM THIS FIRM FROM THIS FIRM FROM FIRM FROM FIRM FROM FROM FROM THE VARIOUS UTILITY COMPANIES. NO GUARANTEE IS VARIOUS UTILITY COMPANIES. NO GUARANTEE IS VARIOUS UTILITY COMPANIES. NO GUARANTEE IS UTILITY COMPANIES. NO GUARANTEE IS UTILITY COMPANIES. NO GUARANTEE IS COMPANIES. NO GUARANTEE IS COMPANIES. NO GUARANTEE IS NO GUARANTEE IS NO GUARANTEE IS NO GUARANTEE IS GUARANTEE IS GUARANTEE IS IS IS GIVEN OR IMPLIED AS TO THE COMPLETENESS OR OR IMPLIED AS TO THE COMPLETENESS OR OR IMPLIED AS TO THE COMPLETENESS OR IMPLIED AS TO THE COMPLETENESS OR IMPLIED AS TO THE COMPLETENESS OR AS TO THE COMPLETENESS OR AS TO THE COMPLETENESS OR TO THE COMPLETENESS OR TO THE COMPLETENESS OR THE COMPLETENESS OR THE COMPLETENESS OR COMPLETENESS OR COMPLETENESS OR OR OR ACCURACY THEREOF. PRIOR TO CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF TO CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF TO CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF CONSTRUCTION, ALL LOCATIONS AND DEPTHS OF ALL LOCATIONS AND DEPTHS OF ALL LOCATIONS AND DEPTHS OF LOCATIONS AND DEPTHS OF LOCATIONS AND DEPTHS OF AND DEPTHS OF AND DEPTHS OF DEPTHS OF DEPTHS OF OF OF EXISTING OVERHEAD AND UNDERGROUND UTILITIES (IN OVERHEAD AND UNDERGROUND UTILITIES (IN OVERHEAD AND UNDERGROUND UTILITIES (IN AND UNDERGROUND UTILITIES (IN AND UNDERGROUND UTILITIES (IN UNDERGROUND UTILITIES (IN UNDERGROUND UTILITIES (IN UTILITIES (IN UTILITIES (IN (IN (IN (IN CONFLICT WITH THE CONSTRUCTION OF THESE PROPOSED WITH THE CONSTRUCTION OF THESE PROPOSED WITH THE CONSTRUCTION OF THESE PROPOSED THE CONSTRUCTION OF THESE PROPOSED THE CONSTRUCTION OF THESE PROPOSED CONSTRUCTION OF THESE PROPOSED CONSTRUCTION OF THESE PROPOSED OF THESE PROPOSED OF THESE PROPOSED THESE PROPOSED THESE PROPOSED PROPOSED PROPOSED IMPROVEMENTS) SHALL BE VERIFIED IN THE FIELD. DURING SHALL BE VERIFIED IN THE FIELD. DURING SHALL BE VERIFIED IN THE FIELD. DURING BE VERIFIED IN THE FIELD. DURING BE VERIFIED IN THE FIELD. DURING VERIFIED IN THE FIELD. DURING VERIFIED IN THE FIELD. DURING IN THE FIELD. DURING IN THE FIELD. DURING THE FIELD. DURING THE FIELD. DURING FIELD. DURING FIELD. DURING DURING DURING THE CONSTRUCTION, THE CONTRACTOR SHALL PROTECT CONSTRUCTION, THE CONTRACTOR SHALL PROTECT CONSTRUCTION, THE CONTRACTOR SHALL PROTECT THE CONTRACTOR SHALL PROTECT THE CONTRACTOR SHALL PROTECT CONTRACTOR SHALL PROTECT CONTRACTOR SHALL PROTECT SHALL PROTECT SHALL PROTECT PROTECT PROTECT AND SUPPORT ALL UTILITIES THAT ARE ENCOUNTERED. SUPPORT ALL UTILITIES THAT ARE ENCOUNTERED. SUPPORT ALL UTILITIES THAT ARE ENCOUNTERED. ALL UTILITIES THAT ARE ENCOUNTERED. ALL UTILITIES THAT ARE ENCOUNTERED. UTILITIES THAT ARE ENCOUNTERED. UTILITIES THAT ARE ENCOUNTERED. THAT ARE ENCOUNTERED. THAT ARE ENCOUNTERED. ARE ENCOUNTERED. ARE ENCOUNTERED. ENCOUNTERED. ENCOUNTERED. (ALL COSTS FOR UTILITY LOCATION VERIFICATION, SUPPORT COSTS FOR UTILITY LOCATION VERIFICATION, SUPPORT COSTS FOR UTILITY LOCATION VERIFICATION, SUPPORT FOR UTILITY LOCATION VERIFICATION, SUPPORT FOR UTILITY LOCATION VERIFICATION, SUPPORT UTILITY LOCATION VERIFICATION, SUPPORT UTILITY LOCATION VERIFICATION, SUPPORT LOCATION VERIFICATION, SUPPORT LOCATION VERIFICATION, SUPPORT VERIFICATION, SUPPORT VERIFICATION, SUPPORT SUPPORT SUPPORT AND PROTECTION SHALL BE INCLUDED IN THE PROPOSED PROTECTION SHALL BE INCLUDED IN THE PROPOSED PROTECTION SHALL BE INCLUDED IN THE PROPOSED SHALL BE INCLUDED IN THE PROPOSED SHALL BE INCLUDED IN THE PROPOSED BE INCLUDED IN THE PROPOSED BE INCLUDED IN THE PROPOSED INCLUDED IN THE PROPOSED INCLUDED IN THE PROPOSED IN THE PROPOSED IN THE PROPOSED THE PROPOSED THE PROPOSED PROPOSED PROPOSED PAY ITEM CONFLICTING WITH THAT UTILITY). DURING CONSTRUCTION, THE CONTRACTOR SHALL USE CONSTRUCTION, THE CONTRACTOR SHALL USE CONSTRUCTION, THE CONTRACTOR SHALL USE THE CONTRACTOR SHALL USE THE CONTRACTOR SHALL USE CONTRACTOR SHALL USE CONTRACTOR SHALL USE SHALL USE SHALL USE USE USE EXTREME CAUTION WHEN OPERATING NEAR ANY AND ALL CAUTION WHEN OPERATING NEAR ANY AND ALL CAUTION WHEN OPERATING NEAR ANY AND ALL WHEN OPERATING NEAR ANY AND ALL WHEN OPERATING NEAR ANY AND ALL OPERATING NEAR ANY AND ALL OPERATING NEAR ANY AND ALL NEAR ANY AND ALL NEAR ANY AND ALL ANY AND ALL ANY AND ALL AND ALL AND ALL ALL ALL OVERHEAD AND / OR BURIED UTILITIES.

PLAN NOTES

1. REFLECTED CEILING PLAN IS SHOWN FOR REFERENCE ONLY.

CONTRACTOR TO REMOVE AND REINSTALL EXISTING CEILING GRID ,

TILE AND LIGHTING AS REQUIRED FOR DEMOLITION AND

ELECTRICAL NEW WORK. REFER TO ELECTRICAL DRAWINGS.

SCALE:

REFLECTED CEILING PLAN

3/32" = 1'-0"

A102

51301 Schoenherr Road Shelby Township, MI 48315

586.726.1234 | aewinc.com

Engineering Strong Communities

0100-0570

ROSEVILLE CITY

HALL ELECTRICAL

UPGRADES

CITY OF ROSEVILLE

SHEET TITLE:

COPYRIGHT, 2025, ANDERSON, ECKSTEIN AND WESTRICK, INC.

CHECKED BY:DRAWN BY:

SCALE:

PRELIMINARY

DATE SUBMITTALS/REVISIONS

PROJECT NO.

SHEET NO.

CLIENT:

PROJECT NAME:

CONSTRUCTION RECORD

DATE:

A102--7/28/2025 1:25:45 PM

M:\0100\0100-0570\CAD\DRAWINGS\CONSTRUCTION\ARCH\ARCHSHEETS.DWG

Know what's below.

72 hours before you dig.

Call R

NORTH

A102

SPK JRA JULY 2025

07/28/2025 BID ISSUE

REFLECTED CEILING

PLAN

OPEN

OFFICE

(CLERKS DEPT)

MENS

CONFERENCE

CITY

MANAGER

OFFICE

OFFICE

OFFICE

SUPPORT

OFFICE

OPEN

OFFICE

OFFICE

OPEN

OFFICE

OPEN

OFFICE

OPEN

OFFICE

(TREASURY

DEPT)

OFFICE

OFFICE

CONFERENCE

OPEN

OFFICE

(ASSESSING

DEPT)

OFFICE

NETWORK

NETWORK

STAIRS

OFFICE

OFFICE

OFFICE

OPEN

OFFICE

(BUILDING

DEPT)

CORRIDOR

WOMENS

MENS

EMPLOYEES

LOUNGE

OPEN

OFFICE

OFFICE

J.C.

CONF. RM.

0100-0570

ROSEVILLE CITY HALL

ELECTRICAL

UPGRADES

CITY OF ROSEVILLE

Phone 586 726 1234 Fax 586 726 8780

51301 Schoenherr Road Shelby Township Michigan 48315

CIVIL ENGINEERS SURVEYORS ARCHITECTS

ENGINEERING STRONG COMMUNITIES

Know what's below.

72 hours before you dig.

Call R www.aewinc.com

ANDERSON, ECKSTEIN AND

WESTRICK, INC.

TAC ASSOCIATES, LLC

4321 East Camden Road Osseo, MI 49266

Ph. (517) 254-4789 http://www.tac-associates.com

TAC Project No. 25-007

Consulting Engineers

CAD TGC MAY 2025

ELECTRICAL DRAWING INDEX, SYMBOL LIST, GENERAL NOTESE001

SHEET NUMBER SHEET TITLE

ELECTRICAL DRAWING INDEX

PARTIAL POWER ONE-LINE DIAGRAM - DEMOLITIONE200

WALL MOUNTED OCCUPANCY SENSOR. REFER TO SCHEDULE ON LIGHTING DRAWINGS

THREE WAY SWITCH

EM

N.L.

EXISTING ELECTRICAL DEVICE OR FIXTURE TO REMAIN

ABOVE FINISH FLOOR

WEATHER PROOF

GROUND FAULT INTERRUPTERGFI

WP

AFF

(E)

DEVICE OR LIGHTING FIXTURE SERVED FROM EMERGENCY POWER

NIGHT LIGHT

EM

ELECTRICAL SYMBOL LIST

RECESSED ROUND LIGHT FIXTURE

EXIT LIGHT DOUBLE FACE (SHADING INDICATES FACE OF FIXTURE)

SPECIAL PURPOSE OUTLET - TYPE AND SIZE AS INDICATED ON PLAN

WALL MOUNTED COMBINATION TELEPHONE/DATA OUTLET, MOUNTED AT 48" A.F.F.

DUPLEX RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

PANEL BOARD

JUNCTION BOX

CABLE TELEVISION SYSTEM OUTLET

DUPLEX RECEPTACLE MOUNTED AT 6" ABOVE COUNTER TOP

W

EXIT LIGHT, SINGLE FACE

NIGHT LIGHT / EMERGENCY LIGHT FIXTURE

NIGHT LIGHT FIXTURE

WALL MOUNTED LIGHT FIXTURE

SINGLE POLE SWITCH

FOUR WAY SWITCH

2' X 4' LIGHT FIXTURE

1' X 4' LIGHT FIXTURE

2' X 2' LIGHT FIXTURE

SYMBOL DESCRIPTION

N.L.

SITE LIGHTING FIXTURE - BUILDING MOUNTED. SEE FIXTURE SCHEDULE

SITE LIGHTING FIXTURE - POLE MOUNTED (DOUBLE HEAD INDICATED)

TELEPHONE ONLY OUTLET

NEW LOCATION OF RELOCATED ELECTRICAL DEVICE OR FIXTURE(R)

EM

EMERGENCY FIXTURE (2X2 EMERGENCY FIXTURE INDICATED)

COMBINATION TELEPHONE/DATA OUTLET

WALL MOUNTED TELEPHONE ONLY OUTLET, MOUNTED AT 48" A.F.F.W

WALL MOUNTED EMERGENCY BATTERY UNIT (EBU)

CEILING MOUNTED EMERGENCY BATTERY UNIT (EBU)

FIRE ALARM SYSTEM AUDIBLE / VISUAL NOTIFICATION APPLIANCE

FIRE ALARM SYSTEM VISUAL NOTIFICATION APPLIANCE

FIRE ALARM SYSTEM HEAT DETECTOR

FIRE ALARM SYSTEM SMOKE DETECTOR

FIRE ALARM SYSTEM MANUAL PULL STATION

1. EXTENT OF DEMOLITION IS NOT INTENDED TO BE SHOWN IN FULL ON THESE DRAWINGS. FINAL DESIGNED CONDITIONS ARE SHOWN. EACH TRADE/CONTRACTOR IS RESPONSIBLE FOR REMOVAL AS REQUIRED TO ACHIEVE FINAL DESIGN CONDITIONS. REFERENCES TO EXISTING AS IDENTIFIED ARE TO CLARIFY SCOPE OF

NEW CONSTRUCTION.

2. ALL WORK CONDITIONS ARE TO BE FIELD VERIFIED AND DETAILS ADJUSTED AS REQUIRED TO MAINTAIN FIRE RESISTIVE RATINGS. INTEGRITY OF INSTALLED SYSTEMS (EXISTING AND NEW) AND THE MATCHING OF WORK

WITH EXISTING CONDITIONS AND FINISHES.

3. REMOVAL WORK SHALL BE EXECUTED WITH DUE CARE, INCLUDING PROTECTION OF EXISTING MATERIALS/SYSTEMS TO REMAIN SHORING, BRACING, ETC. EACH TRADE/SUBCONTRACTORS WILL BE

RESPONSIBLE FOR ANY DAMAGE THEY CAUSE TO OTHER'S WORK.

4. THE FULL EXTENT OF THE WORK FOR EACH TRADE IS IDENTIFIED THROUGHOUT ALL THE DRAWINGS. DO NOT ASSUME OR OMIT INDIVIDUAL TRADE WORK NOT SHOWN IN THE INDIVIDUAL TRADE DRAWINGS. FAILURE TO REVIEW ALL DRAWINGS FOR AN INDIVIDUAL TRADE’S COMPLETE SCOPE OF WORK WILL RESULT IN DENIAL FOR

ANY CHANGE ORDER REQUESTS FOR MISSED ITEMS DURING BIDDING.

5. SUBCONTRACTORS AND ALL TRADES MUST EXAMINE AREAS, DIMENSIONS CONDITIONS AND SUBSTRATES AFFECTING THE WORK AND THE CONDITIONS UNDER WHICH THE WORK IS TO BE INSTALLED, APPLIED AND COMPLETED. NOTIFY THE ARCHITECT IN WRITING OF UNSATISFACTORY CONDITIONS AND OTHER

CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY COMPLETION OF THE WORK.

A. DO NOT PROCEED WITH THE WORK UNTIL THE UNSATISFACTORY CONDITIONS HAVE BEEN

CORRECTED IN THE MANNER ACCEPTABLE TO THE CONTRACTOR OR TRADE PERFORMING THE

WORK. PROCEED WITH INSTALLATION ONLY AFTER UNSAFE OR UNSATISFACTORY CONDITIONS

HAVE BEEN CORRECTED.

B. BEGINNING WORK MEANS ACCEPTANCE OF THE CONDITIONS.

C. NO CHANGE ORDERS FOR ADDITIONAL WORK WILL BE ACCEPTED FOR CONDITIONS NOT

IDENTIFIED DURING THE EXAMINATION PERIOD PRIOR TO THE COMMENCING OF WORK.

6. CONTRACTOR(S) WARRANTS THEY HAVE EXAMINED THOROUGHLY ALL DRAWINGS AND SPECIFICATIONS DIRECTLY AND INDIRECTLY RELATED TO THEIR WORK. BY BEGINNING THE WORK, CONTRACTOR CERTIFIES THAT ALL NECESSARY ITEMS REQUIRED TO PERFORM HIS WORK HAVE BEEN IDENTIFIED AND DOCUMENTED IN

THE DRAWINGS AND/OR SPECIFICATIONS.

A. NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES, MISSING INFORMATION OR ANY

UNCLEAR ITEMS WHICH WILL AFFECT THE WORK TO BE PERFORMED. DO NOT PROCEED WITH

THE WORK UNTIL THE DISCREPANCIES, MISSING INFORMATION OR ANY UNCLEAR ITEMS HAVE

BEEN CLARIFIED OR CORRECTED TO THE CONTRACTOR OR TRADE PERFORMING THE WORK.

B. BEGINNING THE WORK INDICATES FULL ACCEPTANCE AND CORRECTNESS OF THE

INFORMATION PROVIDED.

C. NO CHANGE ORDERS FOR ADDITIONAL WORK WILL BE ACCEPTED FOR ANY DISCREPANCIES,

MISSING INFORMATION OR UNCLEAR ITEMS OR INFORMATION NOT IDENTIFIED DURING THE

EXAMINATION PERIOD PRIOR TO THE COMMENCING OF WORK.

7. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY FIRESTOPPING AROUND ALL PENETRATIONS OF FIRE RATED WALLS, CEILINGS AND FLOORS. REFER TO ARCHITECTURAL AND ELECTRICAL SPECIFICATIONS FOR ADDITIONAL INFORMATION REGARDING THE SPECIFIC FIRESTOPPING

REQUIREMENTS AND PRODUCT SPECIFICATIONS.

8. ALL ANCHORS FOR ELECTRICAL SYSTEMS SHALL BE STEEL. REFER TO SPECIFICATIONS FOR SPECIFIC APPROVED

PRODUCTS. UNDER NO CIRCUMSTANCES SHALL PLASTIC ANCHORS BE USED.

ELECTRICAL GENERAL NOTES

ELECTRICAL SCHEDULESE210

MISCELLANEOUS DETAILS AND WIRING DIAGRAMSE301

MISCELLANEOUS DETAILS AND WIRING DIAGRAMSE300

ELECTRICAL SCHEDULESE211

PARTIAL FIRST FLOOR PLAN - ELECTRICAL NEW WORKE100

ELECTRICAL SCHEDULESE212

PARTIAL FIRST FLOOR PLAN - ELECTRICAL DEMOLITIONED100

PARTIAL POWER ONE-LINE DIAGRAM - NEW WORKE201

TAMPER RESISTANT DUPLEX RECEPTACLE

PARTIAL FIRST FLOOR PLAN - ELECTRICAL DEMOLITIONED101

Electrical Drawing

Index, Symbol List, General Electrical

Notes

E001

PARTIAL FIRST FLOOR PLAN - ELECTRICAL NEW WORKE101

ELECTRICAL SPECIFICATIONSE400

ELECTRICAL SPECIFICATIONSE401

ELECTRICAL SPECIFICATIONSE402

ELECTRICAL SPECIFICATIONSE403

ELECTRICAL SPECIFICATIONSE404

ELECTRICAL

UPGRADES

CITY OF ROSEVILLE

Phone 586 726 1234 Fax 586 726 8780

51301 Schoenherr Road Shelby Township Michigan 48315

CIVIL ENGINEERS SURVEYORS ARCHITECTS

ENGINEERING STRONG COMMUNITIES

Know what's below.

72 hours before you dig.

Call R www.aewinc.com

ANDERSON, ECKSTEIN AND

WESTRICK, INC.

TAC ASSOCIATES, LLC

4321 East Camden Road Osseo, MI 49266

Ph. (517) 254-4789 http://www.tac-associates.com

TAC Project No. 25-007

Consulting Engineers

CAD TGC MAY 2025

Partial First Floor

Plan - Electrical

Demolition

ED100

SCALE:

ED100

PARTIAL FIRST FLOOR PLAN - ELECTRICAL DEMOLITION

3/16" = 1'-0"

OPEN OFFICE

OFFICE

OFFICE

OPEN OFFICE

OPEN OFFICE

OFFICE

OFFICE

CITY MANAGER

CONFERENCE

MEN'S

REST. RM

SUPPORT OFFICE

OFFICE

MATCHLINE

SEE SHEET ED101 FOR

CONTINUATION

OFFICE

OFFICE

OFFICE

OPEN OFFICE

CONFERENCE

EXISTING PANEL "BB"

208Y / 120V - 3Ø - 4W

TO BE REPLACED.

EXISTING PANEL "BBN"

208Y / 120V - 3Ø - 4W

TO BE REPLACED.

EXISTING PANEL "BBM"

208Y / 120V - 3Ø - 4W

TO BE REPLACED.

EXISTING PANEL "B"

480Y / 277V - 3Ø - 4W

TO BE REPLACED.

EXISTING PANEL "J"

208Y / 120V - 3Ø - 4W

TO BE REPLACED.

(Assessing Dept.)(Treasury Dept.)(Clerks Dept.)

B-5

B-3

B-6

B-4

B-2

B-9

B-11

1 1 1 1 1

1 1 1 1

1 1 11

1 1

1 1

1 1 1

1 1 1

1111111

1 1 1 1

33 3

2 2 2 2 2 2

2 2 2 2 2 2 2

2 2 2

2 2 2

4 4

3 333

CONTRACTORS PRE-BID NOTIFICATION:

ALL EXISTING ITEMS INDICATED IN THE CONTRACT DRAWINGS HAVE BEEN TAKEN FROM THE OWNER'S LIMITED RECORD DRAWINGS AND SUBSTANTIAL FIELD OBSERVATIONS AND VERIFICATION. THIS CONTRACTOR AND ALL RELATED SUB-CONTRACTORS SHALL VISIT THE SITE AND COMPLETELY UNDERSTAND THE CONDITIONS UNDER WHICH THE WORK MUST BE PERFORMED. IF A DEPARTURE FROM THE DESIGN INTENT OF THE DOCUMENTS IS REQUIRED DUE TO THE ACTUAL FIELD CONDITIONS OBSERVED BY THE CONTRACTOR, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IN WRITING FOR RESOLUTION PRIOR TO SUBMITTING FINAL BID OR ENTERING INTO A CONTRACT FOR CONSTRUCTION. FAILURE TO PROVIDE THE ARCHITECT WITH NOTIFICATION SHALL RESULT IN THE CONTRACTOR BEING HELD RESPONSIBLE TO COMPLETE ALL WORK TO

MEET THE DESIGN INTENT WITH NO ADDITIONAL COST BEING INCURRED BY THE OWNER.

1.

2.

ALL DEVICES INDICATED WITH SOLID LIGHT LINES ARE EXISTING DEVICES TO REMAIN.

ALL DEVICES AND FIXTURES INDICATED WITH SOLID DARK CROSS-HATCHED LINES ARE EXISTING TO BE

REMOVED OR RELOCATED BY THIS ELECTRICAL CONTRACTOR.

ELECTRICAL CONTRACTOR SHALL PROVIDE DEMOLITION OF ELECTRICAL DEVICES, CONDUIT, WIRING, FIXTURES, EQUIPMENT, ETC. AS REQUIRED TO ACCOMMODATE ARCHITECTURAL, MECHANICAL AND ELECTRICAL REVISIONS. ELECTRICAL DEMOLITION SHEET PROVIDES A GENERAL GUIDELINE AS TO THE SCOPE OF THE WORK. HOWEVER, ALL DEMOLITION REQUIREMENTS MAY NOT BE INDICATED. PROVIDE

DEMOLITION AS REQUIRED TO ACCOMMODATE PROJECT REVISIONS.

COORDINATE DEMOLITION REQUIREMENTS WITH THE WORK OF OTHER TRADES.

PRIOR TO START OF CONSTRUCTION, AND PRIOR TO ANY DEMOLITION WORK THE ELECTRICAL

CONTRACTOR SHALL PERFORM CIRCUIT TRACING TO IDENTIFY ALL EXISTING BRANCH CIRCUITS SERVING THE RENOVATION AREA, AND TO IDENTIFY THE AVAILABLE BRANCH CIRCUITS THAT MAY BE RE-USED AS PART OF THE PROPOSED RENOVATION, AS WELL AS CIRCUITS THAT SERVE EXISTING

LIGHTING FIXTURES OR DEVICES OUTSIDE OF THE WORK AREA THAT ARE TO REMAIN AND BE

MAINTAINED.

3.

ELECTRICAL GENERAL NOTES

4.

5.

1 EXISTING CEILING MOUNTED RECESSED 2X4 LIGHT FIXTURE TO REMAIN.

EXISTING CEILING MOUNTED RECESSED DOWN LIGHT FIXTURE TO REMAIN.

EXISTING BRANCH CIRCUIT CONDUIT AND WIRING BETWEEN FIXTURES TO REMAIN.

EXISTING EXIT LIGHT FIXTURE TO REMAIN.

EXISTING EMERGENCY BATTERY UNIT (OR COMBINATION EXIT / EMERGENCY BATTERY UNIT AS

INDICATED) TO REMAIN.

EXISTING WALL BOX OCCUPANCY SENSOR SWITCHING CONTROL TO REMAIN.

ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING BRANCH CIRCUIT HOMERUN SERVING GROUP OF LIGHTING FIXTURES INDICATED TO ALLOW FOR THE INSTALLATION OF NEW CEILING MOUNTED OCCUPANCY SENSOR(S) IN THE ROOM TO CONTROL THE LIGHTING, AS WELL AS PROVIDE MANUAL ON/OFF CONTROL LOCAL TO THE ROOM. MODIFICATION OF THE BRANCH CIRCUIT

CONDUIT AND WIRING HOMERUN SHALL BE AS REQUIRED FOR INSTALLING THE NEW OCCUPANCY

SENSOR CONTROL FOR THE GROUP OF LIGHTING FIXTURES INDICATED. NOTE THAT THE GROUPING OF

FIXTURES SHOWN, AND THE ASSOCIATED BRANCH CIRCUIT HOMERUN NOTED IS BASED ON THE

OWNERS RECORD DRAWING INFORMATION, WHICH MAY OR MAY NOT BE ACCURATE. THE ELECTRICAL CONTRACTOR SHALL PERFORM CIRCUIT TRACING PRIOR TO START OF CONSTRUCTION TO IDENTIFY THE BRANCH CIRCUIT SERVING EACH AREA AND GROUP OF LIGHTING FIXTURES, AS WELL AS THE GROUPING OF LIGHTING FIXTURES ON EACH BRANCH CIRCUIT HOMERUN. NOTE THAT THERE ARE MULTIPLE BRANCH CIRCUIT HOMERUNS THAT SERVE INDIVIDUAL AREAS. THE INTENT OF THE PROJECT IS FOR THESE HOMERUNS TO REMAIN AND BE MODIFIED TO ALLOW FOR THE INSTALLATION OF THE

OCCUPANCY SENSOR AND MANUAL ON/OFF CONTROL AS INDICATED ON THE NEW WORK LIGHTING

PLANS.

ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING BRANCH CIRCUIT HOMERUN SERVING GROUP OF LIGHTING FIXTURES INDICATED TO ALLOW FOR THE INSTALLATION OF NEW CEILING MOUNTED OCCUPANCY SENSOR(S) IN THE ROOM TO CONTROL THE LIGHTING, AS WELL AS

PROVIDE MANUAL ON/OFF CONTROL LOCAL TO THE ROOM. BASED ON THE OWNER'S RECORD

DRAWING INFORMATION, THERE IS ONLY ONE LIGHT FIXTURE ON THE HOMERUN. THE ELECTRICAL

CONTRACTOR SHALL REMOVE THE BRANCH CIRCUIT CONDUIT AND WIRING HOMERUN BACK TO

SOURCE AND LABEL EXISTING CIRCUIT BREAKER AS "SPARE". THE EXISTING LIGHT FIXTURE SHALL BE

CIRCUITED TO THE ADJACENT EXISTING LIGHTING FIXTURE AS INDICATED ON THE NEW WORK

LIGHTING PLAN. NOTE THAT THE GROUPING OF FIXTURES SHOWN, AND THE ASSOCIATED BRANCH CIRCUIT HOMERUN NOTED IS BASED ON THE OWNERS RECORD DRAWING INFORMATION, WHICH MAY OR MAY NOT BE ACCURATE. THE ELECTRICAL CONTRACTOR SHALL PERFORM CIRCUIT TRACING PRIOR TO START OF CONSTRUCTION TO IDENTIFY THE BRANCH CIRCUIT SERVING EACH AREA AND GROUP OF LIGHTING FIXTURES, AS WELL AS THE GROUPING OF LIGHTING FIXTURES ON EACH BRANCH CIRCUIT HOMERUN. IF THE ELECTRICAL CONTRACTOR FINDS THAT THE EXISTING BRANCH CIRCUIT HOMERUN SERVES EXISTING FIXTURES THAT ARE TO REMAIN, THE ELECTRICAL CONTRACTOR SHALL PROVIDE NEW BRANCH CIRCUIT CONDUIT AND WIRING AS REQUIRED TO MAINTAIN SERVICE TO THE EXISTING FIXTURES THAT ARE TO REMAIN. REFLECT ALL REVISIONS, AND RESULTS OF CIRCUIT TRACING ON THE

"AS-BUILT" RECORD DRAWINGS AT THE COMPLETION OF THE PROJECT.

ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING TOGGLE SWITCH SERVING

LIGHTING IN ROOM; EXISTING SWITCH LEG WIRING TO REMAIN FOR RE-USE TO CONNECT TO NEW WALL BOX OCCUPANCY SENSOR SWITCH TO BE INSTALLED IN THE SAME LOCATION AS INDICATED ON

THE NEW WORK LIGHTING PLAN.

ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING BRANCH CIRCUIT CONDUIT AND WIRING BETWEEN FIXTURES TO ALLOW FOR SEPARATION OF THE FIXTURES IN EACH ROOM AND

INSTALLATION OF NEW OCCUPANCY SENSOR CONTROL AS INDICATED ON THE NEW WORK PLANS.

NOTE THAT THE POINTS OF INTERCONNECTION SHOWN IS DIAGRAMMATIC ONLY, AND MAY NOT

REFLECT THE ACTUAL INTERCONNECTION BETWEEN ROOMS. THE DRAWINGS ARE INTENDED TO

CONVEY THE GENERAL SCOPE OF REVISIONS THAT ARE NECESSARY TO SEPARATE THE WIRING BETWEEN ROOMS TO ALLOW FOR EACH OPEN OFFICE AREA TO HAVE SEPARATE OCCUPANCY SENSOR CONTROL

WITH MANUAL OVERRIDE CONTROL FOR EACH AREA. THE EXACT SCOPE MAY REQUIRE MULTIPLE

DISCONNECTION OF BRANCH CIRCUIT CONDUIT AND WIRING BETWEEN FIXTURES, AND INSTALLATION OF NEW BRANCH CIRCUIT "HOMERUNS" TO THE EXISTING LIGHTING PANEL AS PART OF THE NEW

WORK ASSOCIATED WITH THE NEW OCCUPANCY SENSOR CONTROL. NOTE THAT THE EXISTING

FIXTURES ARE 277-VOLT FIXTURES, SERVED FROM THE EXISTING PANEL "B".

ELECTRICAL CONTRACTOR SHALL REMOVE AND REPLACE EXISTING RECEPTACLE PANEL WITH NEW PANEL. CAREFULLY DISCONNECT EXISTING FEEDER CONDUCTORS TO ALLOW REPLACEMENT OF THE EXISTING PANEL WITH A NEW PANEL. REFER TO PARTIAL POWER ONE-LINE DIAGRAM - DEMOLITION ON SHEET E200 FOR ADDITIONAL INFORMATION. EXISTING BRANCH CIRCUITS FED FROM THE PANEL THAT ARE EXISTING TO REMAIN SHALL BE CAREFULLY REMOVED FROM THE EXISTING PANEL TO ALLOW FOR THE REMOVAL OF THE EXISTING PANEL AND INSTALLATION OF THE NEW PANEL. AFTER THE NEW PANEL IS INSTALLED, CAREFULLY REINSTALL THE BRANCH CIRCUIT CONDUCTORS AND TERMINATE AT THE NEW CIRCUIT BREAKERS IN THE NEW PANEL. THE ELECTRICAL CONTRACTOR SHALL DETERMINE IN THE FIELD THE FEASIBILITY OF REMOVING AND REINSTALLING THE EXISTING BRANCH CIRCUIT CONDUCTORS BASED ON THE EXISTING FIELD CONDITIONS AND CONFIGURATION OF THE EXISTING PANEL VERSUS THE NEW PANEL. THE ELECTRICAL CONTRACTORS BID SHALL INCLUDE A SEPARATE LINE-ITEM COST FOR THE REMOVAL OF THE EXISTING BRANCH CIRCUIT CONDUIT AND WIRING BACK TO NEW JUNCTION BOXES MOUNTED ABOVE THE PANEL TO ALLOW FOR EXTENSION TO THE NEW PANEL. REFER TO PANEL SCHEDULE ON THE E210 SERIES DRAWINGS FOR ADDITIONAL INFORMATION. PRIOR TO RE-ENERGIZING THE PANEL FEEDERS AND BRANCH CIRCUIT WIRING THE ELECTRICAL CONTRACTOR SHALL PERFORM AN INSULATION RESISTANCE TEST ON ALL CONDUCTORS TO ENSURE THE INTEGRITY OF THE EXISTING

CONDUCTORS AND IDENTIFY ANY GROUND FAULT CONDITIONS OR DAMAGED CONDUCTORS.

WHERE THERE ARE DAMAGED CONDUCTORS FOUND BY THIS TESTING THE DAMAGED CONDUCTORS

SHOULD BE REPLACED WITH NEW. THE ELECTRICAL CONTRACTOR SHALL INCLUDE A SEPARATE

LINE-ITEM ALLOWANCE IN THEIR BID TO PERFORM THE NOTED TESTING. THE REPLACEMENT OF THE

CONDUCTORS WILL BE A SEPARATE COST, TO BE DETERMINED BASED ON THE RESULTS OF THE

TESTING, AND IS NOT PART OF THE BID COST DUE TO THE UNPREDICTABILITY OF SCOPE OF ANY CONDUCTORS THAT WOULD NEED TO BE REPLACED. THE INTENT OF THE PROJECT IS TO PERFORM THE

PANEL REPLACEMENT IN SUCH A MANNER AS TO AVOID THE NEED TO REPLACE ANY FEEDER OR

BRANCH CIRCUIT CONDUCTORS.

DEMOLITION KEY NOTES

9 9 9 9

ELECTRICAL

UPGRADES

CITY OF ROSEVILLE

Phone 586 726 1234 Fax 586 726 8780

51301 Schoenherr Road Shelby Township Michigan 48315

CIVIL ENGINEERS SURVEYORS ARCHITECTS

ENGINEERING STRONG COMMUNITIES

Know what's below.

72 hours before you dig.

Call R www.aewinc.com

ANDERSON, ECKSTEIN AND

WESTRICK, INC.

TAC ASSOCIATES, LLC

4321 East Camden Road Osseo, MI 49266

Ph. (517) 254-4789 http://www.tac-associates.com

TAC Project No. 25-007

Consulting Engineers

CAD TGC MAY 2025

Partial First Floor

Plan - Electrical

Demolition

ED101

SCALE:

ED101

PARTIAL FIRST FLOOR PLAN - ELECTRICAL DEMOLITION

3/16" = 1'-0"

MATCHLINE

SEE SHEET ED100 FOR

CONTINUATION

OFFICE

OPEN OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

NETWORK

NETWORK

OPEN OFFICE

CONFERENCE

OPEN OFFICE

OFFICE

OPEN OFFICE

CORRIDOR

EMPLOYEE LOUNGE

MEN'S TOILET

WOMEN'S TOILET

STAIR HALL

JANITOR

(Building Dept.)

CONTRACTORS PRE-BID NOTIFICATION:

ALL EXISTING ITEMS INDICATED IN THE CONTRACT DRAWINGS HAVE BEEN TAKEN FROM THE OWNER'S LIMITED RECORD DRAWINGS AND SUBSTANTIAL FIELD OBSERVATIONS AND VERIFICATION. THIS CONTRACTOR AND ALL RELATED SUB-CONTRACTORS SHALL VISIT THE SITE AND COMPLETELY UNDERSTAND THE CONDITIONS UNDER WHICH THE WORK MUST BE PERFORMED. IF A DEPARTURE FROM THE DESIGN INTENT OF THE DOCUMENTS IS REQUIRED DUE TO THE ACTUAL FIELD CONDITIONS OBSERVED BY THE CONTRACTOR, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IN WRITING FOR RESOLUTION PRIOR TO SUBMITTING FINAL BID OR ENTERING INTO A CONTRACT FOR CONSTRUCTION. FAILURE TO PROVIDE THE ARCHITECT WITH NOTIFICATION SHALL RESULT IN THE CONTRACTOR BEING HELD RESPONSIBLE TO COMPLETE ALL WORK TO

MEET THE DESIGN INTENT WITH NO ADDITIONAL COST BEING INCURRED BY THE OWNER.

1.

2.

ALL DEVICES INDICATED WITH SOLID LIGHT LINES ARE EXISTING DEVICES TO REMAIN.

ALL DEVICES AND FIXTURES INDICATED WITH SOLID DARK CROSS-HATCHED LINES ARE EXISTING TO BE

REMOVED OR RELOCATED BY THIS ELECTRICAL CONTRACTOR.

ELECTRICAL CONTRACTOR SHALL PROVIDE DEMOLITION OF ELECTRICAL DEVICES, CONDUIT, WIRING, FIXTURES, EQUIPMENT, ETC. AS REQUIRED TO ACCOMMODATE ARCHITECTURAL, MECHANICAL AND ELECTRICAL REVISIONS. ELECTRICAL DEMOLITION SHEET PROVIDES A GENERAL GUIDELINE AS TO THE SCOPE OF THE WORK. HOWEVER, ALL DEMOLITION REQUIREMENTS MAY NOT BE INDICATED. PROVIDE

DEMOLITION AS REQUIRED TO ACCOMMODATE PROJECT REVISIONS.

COORDINATE DEMOLITION REQUIREMENTS WITH THE WORK OF OTHER TRADES.

PRIOR TO START OF CONSTRUCTION, AND PRIOR TO ANY DEMOLITION WORK THE ELECTRICAL

CONTRACTOR SHALL PERFORM CIRCUIT TRACING TO IDENTIFY ALL EXISTING BRANCH CIRCUITS SERVING THE RENOVATION AREA, AND TO IDENTIFY THE AVAILABLE BRANCH CIRCUITS THAT MAY BE RE-USED AS PART OF THE PROPOSED RENOVATION, AS WELL AS CIRCUITS THAT SERVE EXISTING

LIGHTING FIXTURES OR DEVICES OUTSIDE OF THE WORK AREA THAT ARE TO REMAIN AND BE

MAINTAINED.

3.

ELECTRICAL GENERAL NOTES

4.

5.

1 EXISTING CEILING MOUNTED RECESSED 2X4 LIGHT FIXTURE TO REMAIN.

EXISTING CEILING MOUNTED RECESSED DOWN LIGHT FIXTURE TO REMAIN.

EXISTING BRANCH CIRCUIT CONDUIT AND WIRING BETWEEN FIXTURES TO REMAIN.

EXISTING EXIT LIGHT FIXTURE TO REMAIN.

EXISTING EMERGENCY BATTERY UNIT (OR COMBINATION EXIT / EMERGENCY BATTERY UNIT AS

INDICATED) TO REMAIN.

EXISTING WALL BOX OCCUPANCY SENSOR SWITCHING CONTROL TO REMAIN.

ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING BRANCH CIRCUIT HOMERUN SERVING GROUP OF LIGHTING FIXTURES INDICATED TO ALLOW FOR THE INSTALLATION OF NEW CEILING MOUNTED OCCUPANCY SENSOR(S) IN THE ROOM TO CONTROL THE LIGHTING, AS WELL AS PROVIDE MANUAL ON/OFF CONTROL LOCAL TO THE ROOM. MODIFICATION OF THE BRANCH CIRCUIT

CONDUIT AND WIRING HOMERUN SHALL BE AS REQUIRED FOR INSTALLING THE NEW OCCUPANCY

SENSOR CONTROL FOR THE GROUP OF LIGHTING FIXTURES INDICATED. NOTE THAT THE GROUPING OF

FIXTURES SHOWN, AND THE ASSOCIATED BRANCH CIRCUIT HOMERUN NOTED IS BASED ON THE

OWNERS RECORD DRAWING INFORMATION, WHICH MAY OR MAY NOT BE ACCURATE. THE ELECTRICAL CONTRACTOR SHALL PERFORM CIRCUIT TRACING PRIOR TO START OF CONSTRUCTION TO IDENTIFY THE BRANCH CIRCUIT SERVING EACH AREA AND GROUP OF LIGHTING FIXTURES, AS WELL AS THE GROUPING OF LIGHTING FIXTURES ON EACH BRANCH CIRCUIT HOMERUN. NOTE THAT THERE ARE MULTIPLE BRANCH CIRCUIT HOMERUNS THAT SERVE INDIVIDUAL AREAS. THE INTENT OF THE PROJECT IS FOR THESE HOMERUNS TO REMAIN AND BE MODIFIED TO ALLOW FOR THE INSTALLATION OF THE

OCCUPANCY SENSOR AND MANUAL ON/OFF CONTROL AS INDICATED ON THE NEW WORK LIGHTING

PLANS.

ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING BRANCH CIRCUIT HOMERUN SERVING GROUP OF LIGHTING FIXTURES INDICATED TO ALLOW FOR THE INSTALLATION OF NEW CEILING MOUNTED OCCUPANCY SENSOR(S) IN THE ROOM TO CONTROL THE…