RND Grand Forks ND 3rd Floor TI - Bid Set.pdf
PDF 10 MB Posted
- Attached to
- RFP 47PD5326R0046 EQPXAGC-26-0014 Grand Forks Office Buildout Federal contract opportunity
- Solicitation number
- 47PD5326R0046
- Issued by
- Not on record
About this file
This is an architectural bid set for a tenant improvement project at the Ronald N. Davies Federal Building in Grand Forks, North Dakota. The project involves the buildout of approximately 2,578 gross square feet on the third floor of the federal office building, owned by the General Services Administration (GSA). The scope encompasses demolition of existing interior partitions, doors, lighting, power, and HVAC systems, followed by construction of new offices with specific security requirements. The project is classified as Occupancy Classification B with Construction Type II-B under the 2024 International Building Code and related codes, with a total occupant load of 40 persons and no sprinkler requirements.
The architectural drawings specify multiple wall types with security-related features, including bullet-resistant Wall Type A2 (UL 752 Level III), secure storage walls, and perimeter security walls with plywood backing and sealant requirements. Interior improvements include office spaces, a break room with appliances, a shower facility, and specialized elements such as a ballistic transaction window with two-way communication device, handcuff bars, magnetic glass marker boards, and sealed windows with blast film. Mechanical, electrical, and plumbing systems require coordination with specialized engineering firms, and the project mandates specific finishes including acoustical ceiling tiles, ceramic and vinyl composition tile flooring, carpet, and hardwood refinishing. The architectural drawings were issued for construction on May 6, 2026, with the design completed through multiple submittal stages from August 2025 through April 2026. General contractor responsibilities include dust control, selective demolition with hazardous materials abatement, protection of existing items to remain, and compliance with fire protection requirements per GSA standards.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Unsuccessful Letter_47PD5326R0046 EQPXAGC-26-0014 Grand Forks Office Buildout.pdf | ||
| Amendment 47PD5326R0046_0002 signed.pdf | ||
| Amendment 47PD5326R0046_0002 signed.pdf | ||
| Amendment 47PD5326R0046_0001.pdf | ||
| FO SB Solicitation RFP 47PD5326R0046.pdf | ||
| FO SB Agreement RFP 47PD5326R0046.pdf | ||
| RND Grand Forks ND 3rd Floor TI- Final specifications.pdf | ||
| RFP 47PD5326R0046 Form 1442.pdf | ||
| M1177147 - Ronald Davies Asbestos and LBP Survey-Final.pdf | ||
| Vendor Fitness Determination Training Manual.pdf | ||
| GSA527 Contractors Qualifications and Financial Information.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A101
LAB
A101
Name
Elevation
N
ROOM NAME AND NUMBER
OPENING NUMBER
CONSTRUCTION NOTE
DETAIL REFERENCE NUMBER
SHEET NUMBER
SECTION/ELEVATION NUMBER
SHEET NUMBER
REVISION NOTE
LEVEL NAME
LEVEL ELEVATION
SPOT ELEVATION
T.O. ------- 100'-0"
STRUCTURAL GRID
FIRE EXTINGUISHER CABINET
FEC
INTERIOR ELEVATION NUMBER
SHEET NUMBER
A3.1
CONTINUOUS GRAY LINE
INDICATES EXISTING WALL
PARTITION
OVERHEAD LINES (ROOF,
ETC.)
NEW METAL STUD
PARTITION
ONE HOUR RATED WALL
CONSTRUCTION
TWO HOUR RATED
WALL CONSTRUCTION
CONCRETE
METAL
STUD
BATT
INSULATION
GYPSUM
BOARD
SHEATHING
RIGID
INSULATION
CMU
OWNER
U.S. GENERAL SERVICES ADMINISTRATION
CONTACT: KEVIN SPRUELL
TEL: 267-253-5981
ARCHITECT
DESIGN EDGE, P.C.
482 S BROADWAY
DENVER, CO 80209
CONTACT: SWAGATA GUHA
TEL: 303.260.7277 X114
MECHANICAL, ELECTRICAL,
PLUMBING
MEP ENGINEERING, INC.
6402 S. TROY CIRCLE, SUITE 100
CENTENNIAL, CO 80111
CONTACT: ROGER CRAWFORD
TEL: 303.936.1633
FIRE PROTECTION
COFFMAN ENGINEERS, INC.
11080 CIRCLE POINT ROAD #220
WESTMINSTER, CO 80020
CONTACT: JENN WOOD
TEL: 720.805.1955
VICINITY MAP
NOT TO SCALE
NORTHPROJECT LOCATION
TENANT AREA
LEVEL 3
CHECKED BY
DRAWN BY
FLOOR NUMBER
SHEET TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
Model Author
PROJECT NUMBER
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NUMBER
CITY/ST./ZIP
ADDRESS
BUILDING NAME
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
24 X 36
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N T
R A
C T
O R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
T A
M P
O R
S E
A L
D E
S
IG
N E
R
ID
E N
T
IF
IC
A
T
IO
N O
W N
E R
ID
E
N T
IF
IC
A T
IO
N
SHEET OF SHEETS
482 S Broadway - Suite 100 Denver, Colorado 80209 Telephone: 303-260-7277
UNCLASSIFIED // FOR OFFICIAL USE ONLY
PROPERTY OF THE UNITED STATES GOVERNMENT
Do not remove this notice. Properly destroy or return documents when no longer needed
TENANT IMPROVEMENT OF 2,578GSF
LEVEL 3
ARCHITECTURE
47PJ0020D0012
47PJ0025F0120
DESIGN EDGE
/2
/2
:3
:5
A
M
G0.0
COVER SHEET AND PROJECT INFORMATION
GSA 3RD FLOOR TI - GRAND FORKS, ND
ISSUED FOR CONSTRUCTION
5/6/2026
3/31/2026TP
SG
23133
General Service Administration
1 49
RONALD N. DAVIES FEDERAL BUILDING
ND0008ZZ
RONALD N. DAVIES FEDERAL BUILDING
102 NORTH 4TH STREET,
GRAND FORKS, ND 58203
DESIGN EDGE
GENERAL NOTES PARTICIPANTS
SHEET LIST
ABBREVIATIONS
KEY PLAN
DRAWING SYMBOLS
GRAPHIC SYMBOLS
SHEET NAME
GENERAL INFORMATION
G0.0 COVER SHEET AND PROJECT INFORMATION
ARCHITECTURAL
A1.1 DEMOLITION FLOOR PLAN
A1.2 DEMOLITION RCP
A1.3 FLOOR PLAN
A1.4 REFLECTED CEILING PLAN
A6.1 DOORS
A6.2 WALL TYPES
A6.3 ENLARGED PLAN, INTERIOR ELEVATIONS, & DETAILS
A6.4 DETAILS
A7.1 FINISH PLAN
MECHANICAL
M0.1 MECHANICAL LEGEND AND SPECIFICATIONS
M0.2 MECHANICAL SCHEDULES
M0.3 MECHANICAL DIAGRAMS
M0.4 MECHANICAL DIAGRAMS
MD1.3 MECHANICAL DEMOLITION PLAN
M1.3 LEVEL 3 MECHANICAL PLAN
M1.4 ATTIC MECHANICAL PLAN
M1.5 ROOF MECHANICAL PLAN
PLUMBING
P0.1 PLUMBING LEGEND
P0.2 PLUMBING SPECIFICATIONS
P0.3 PLUMBING SPECIFICATIONS
P0.4 PLUMBING SCHEDULES
P0.5 PLUMBING DIAGRAMS
PD1.3 PLUMBING DEMOLITION PLAN
P1.2 LEVEL 3 DRAIN WASTE VENT PLUMBING PLAN
P1.3 LEVEL 3 PLUMBING PLAN
P1.4 ATTIC PLUMBING PLAN
P1.5 ROOF PLUMBING PLAN
ELECTRICAL
E0.1 ELECTRICAL LEGEND
E0.2 ELECTRICAL SPECIFICATION
E0.3 ELECTRICAL SPECIFICATION
E0.4 ELECTRICAL SPECIFICATION
E0.5 ONE-LINE DIAGRAM
E0.6 ELECTRICAL SCHEDULES
E0.7 ELECTRICAL DIAGRAMS
ED1.3 ELECTRICAL DEMOLITION PLAN
E1.3 LEVEL 3 POWER PLAN
E1.4 ATTIC POWER PLAN
E1.5 ROOF POWER PLAN
E2.3 LEVEL 3 SPECIAL SYSTEMS PLAN
E2.4 LEVEL 3 CABLE TRAY SECTION VIEW
E3.3 LEVEL 3 LIGHTING PLAN
PH-1 LEVEL 3 PHOTOMETRIC PLAN
PH-2 LEVEL 3 PHOTOMETRIC PLAN - EGRESS
FIRE PROTECTION
FA-001 FIRE ALARM LEGEND, GENERAL NOTES, & SHEET INDEX
FA-100 LEVEL 3 FIRE ALARM DEMOLITION PLAN
FA-200 LEVEL 3 FIRE ALARM PLAN
LIFE SAFETY
LS-001 LIFE SAFETY CODE ANALYSIS
LS-100 LEVEL 3 LIFE SAFTEY PLAN
GSA 3RD FLOOR TI - GRAND FORKS, ND
ACT ACOUSTICAL CEILING TILE
AFF ABOVE FINISH FLOOR
ALUM ALUMINUM
ANOD ANODIZED
< ANGLE
B.O. BOTTOM OF
CJ CONTROL JOINT
CMU CONCRETE MASONRY UNIT
CT CERAMIC TILE
- CENTER LINE
CFCI CONTRACTOR FURISHED,
CONTRACTOR INSTALLED
DIA DIAMETER
DS DOWNSPOUT
(E) EXISTING
EIFS EXTERIOR INSULATION
AND FINISH SYSTEM
EJ EXPANSION JOINT
ELEV ELEVATION
EQ EQUAL
EWC ELECTRIC WATER COOLER
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
CABINET
FRT FIRE RETARDANT
TREATED
FV FIELD VERIFY
GA GAUGE
GC GENERAL CONTRACTOR
HM HOLLOW METAL
LAM LAMINATE
MAX MAXIMUM
MIN MINIMUM
MO MASONRY OPENING
NIC NOT IN CONTRACT
NO NUMBER
NTS NOT TO SCALE
OC ON CENTER
OD OVERFLOW DRAIN
OFCI OWNER FURNISHED,
CONTRACTOR INSTALLED
+/- PLUS OR MINUS
P.J PRECAST PANEL JOINT
RAD RADIUS
RB RUBBER BASE
RD ROOF DRAIN
RE: REFER TO
R.O. ROUGH OPENING
SIM SIMILAR
SPEC SPECIFICATIONS
T.O. TOP OF
TS TUBE STEEL
TYP. TYPICAL
VB VINYL BASE
VCT VINYL COMPOSITION TILE
WD WOOD
C L
1. PRIOR TO ACCEPTANCE OF THIS WORK, THE CONTRACTOR SHALL VISIT
THE SITE AND BE FAMILIAR WITH THE CONDITIONS UNDER WHICH THE
WORK IS TO BE PERFORMED. THE CONTRACTOR SHALL REVIEW,
APPROVE AND SUBMIT TO THE ARCHITECT SAMPLES, PRODUCT DATA,
AND SHOP DRAWINGS PRIOR TO INSTALLATION. BY DOING SO, THE
CONTRACTOR REPRESENTS THAT THEY HAVE VERIFIED FIELD
CONDITIONS AND MEASUREMENTS.
2. CONTRACTOR TO NOTIFY ARCHITECT OF ANY CONFLICTS OR
OMISSIONS IMMEDIATELY PRIOR TO THE PERFORMANCE OF THE WORK
IN QUESTION.
3. WHEN THE CONTRACTOR ACCEPTS DELIVERY OF ALL ITEMS NOTED ON
PLANS, WHETHER IN CONTRACT OR NOT IN CONTRACT, THEY SHALL BE
RESPONSIBLE FOR LOSS AND/OR DAMAGE OF THESE ITEMS.
4. ITEMS INDICATED IN THIS SET OF DOCUMENTS ARE NOT TO BE
ALTERED WITHOUT WRITTEN CONSENT FROM THE ARCHITECT OR
ENGINEER. IF ALTERATIONS ARE MADE BY THE OWNER OR
CONTRACTOR, THE ARCHITECT AND/OR ENGINEER ASSUME NO
RESPONSIBILITY FOR SUCH CHANGES.
5. GSA REGIONAL FIRE PROTECTION ENGINEER IS THE DESIGNATION
AUTHORITY HAVING JURISDICTION (AHJ) PER P-100
6. ALL ITEMS INDICATED IN THIS SET SHALL NOT HAVE WIRELESS (WI-FI)
OR BLUETOOTH CAPABILITIES. WHERE EQUIPMENT HAS SUCH
CAPABILITIES, SUCH FUNCTIONS SHOULD BE CAPABLE OF BEING
DISABLED.
PROJECT DESCRIPTION
THE PROJECT IS THE TENANT IMPROVEMENT OF 2578 GSF OF TENANT SPACE ON THE 3RD FLOOR OF THE FEDERAL OFFICE BUILDING. THE PROJECT CONSISTS OF THE DEMOLITION OF EXISTING INTERIOR PARTITIONS, DOORS, LIGHTING, POWER AND HVAC WORK AND THE CONSTRUCTION OF NEW OFFICES IN THE TENANT SPACE. THE PROJECT HAS SPECIFIC
SECURITY REQUIREMENTS THAT ARE DESCRIBED IN THE CONTRACT DOCUMENTS.
CODE DATA - SEE LIFE SAFETY SHEETS FOR DETAILED LIFE SAFETY CODE STUDY
OCCUPANCY CLASSIFICATION: B
CONSTRUCTION TYPE: II-B
SPRINKLERS: NO
FIRE ALARM NOTIFICATION: PER NFPA 72
INTERIOR FINISH RATINGS: PER IBC CH. 8
OCCUPANT LOAD - SEE LIFE SAFETY SHEETS FOR OCCUPANT LOAD BREAKDOWN
TOTAL OCCUPANT LOAD: 40 OCCUPANTS
EXITING REQUIREMENTS - SEE LIFE SAFETY SHEETS FOR EXITING REQUIREMENTS
TOILET ROOM REQUIREMENTS
COMMON AREA TOILET FACILITIES ARE PROVIDED ON EACH FLOOR OF THE BUILDING, ONE TOILET ADDED IN SUITE
GOVERNING CODES:
• 2024 INTERNATIONAL BUILDING CODE (IBC)
• 2024 INTERNATIONAL EXISTING BUILDING CODE (IEBC)
• 2024 INTERNATIONAL MECHANICAL CODE (IMC)
• 2024 INTERNATIONAL PLUMBING CODE (IPC)
• 2024 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
• 2024 INTERNATIONAL FUEL GAS CODE (IFGC)
• 2024 INTERNATIONAL FIRE CODE (IFC)
• 2023 NFPA 70 NATIONAL ELECTRICAL CODE (NEC)
• 2024 NFPA 101 LIFE SAFETY CODE (LSC)
• 2022 NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS
• 2022 NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE
• PROGRAM OF REQUIREMENTS (POR) FOR NEW RESIDENT AGENCY OFFICE CONSTRUCTION (V22.0)
• 2015 ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)
• 2025 PBS CORE BUILDING STANDARDS
CODE STATEMENT
Mark Date Description
8/5/2025 35% Submittal
9/22/2025 65% Submittal
12/5/2025 95% Submittal
3/6/2026 100% Submittal
3/31/2026 Issued for Construction
4/20/2026 Issued for Construction
5/6/2026 Issued for Construction
AREA OF WORK
AC
B
C
C
C
C
C
C
B
B B B B
BBB
BB
B
B B
B A
C
D
5'-10"
18'-5 3/4" 18'-7" 17'-10 1/2" 14'-1 1/2" 11'-1" 12'-6 1/2"
/4
/4
/4
E
E E E E E E E
E
E E E
E
/2
GENERAL DEMOLITION NOTES
1. REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING (MEP) DRAWINGS
FOR ADDITIONAL AREAS OF DISTURBANCE/DEMOLITION WORK
ASSOCIATED WITH MEP WORK INCLUDING WORK ON ROOF AND OTHER
FLOORS. NOT ALL AREAS MAYBE INDICATED IN ARCHITECTURAL
DRAWINGS.
2. THE CONTRACTOR WILL MEET WITH THE BUILDING OWNER TO DISCUSS
SALVAGE OF ANY BUILDING ITEMS.
3. DIVERT AS MUCH DEMOLITION WASTE AS POSSIBLE FROM THE LANDFILL,
BY RECYCLING AND SALVAGING DOORS, WINDOWS, ETC.
4. PROVIDE DUST ENCLOSURES, TO PREVENT DUST FROM MIGRATING TO
OTHER BUILDING AREAS.
5. COORDINATE NOISY OR DUST PRODUCING ACTIVITIES WITH THE BUILDING
OWNER. CONDUCT SELECTIVE DEMOLITION SO OWNER'S OPERATIONS
WILL NOT BE DISRUPTED.
6. NOTIFY ARCHITECT OF DISCREPANCIES BETWEEN EXISTING CONDITIONS
AND DRAWINGS BEFORE PROCEEDING WITH SELECTIVE DEMOLITION.
7. HAZARDOUS MATERIALS: REFER TO HAZARDOUS MATERIAL REPORT, AND
SPECIFICATIONS FOR HAZARDOUS MATERIAL TO BE ABATED.
8. MAINTAIN FIRE-PROTECTION FACILITIES IN SERVICE DURING SELECTIVE
DEMOLITION OPERATIONS.
9. SITE ACCESS AND TEMPORARY CONTROLS, CONDUCT SELECTIVE
DEMOLITION AND DEBRIS-REMOVAL OPERATIONS TO ENSURE MINIMUM
INTERFERENCE WITH ROADS, STREETS, WALKS, WALKWAYS, AND OTHER
ADJACENT OCCUPIED AND USED FACILITIES.
10. TEMPORARY FACILITIES: PROVIDE TEMPORARY BARRICADES AND OTHER
PROTECTION REQUIRED TO PREVENT INJURY TO PEOPLE AND DAMAGE
TO ADJACENT FACILITIES TO REMAIN.
11. DEMOLISH AND REMOVE EXISTING CONSTRUCTION ONLY TO THE EXTENT
REQUIRED BY NEW CONSTRUCTION AND AS INDICATED. USE METHODS
REQUIRED TO COMPLETE THE WORK WITHIN LIMITATIONS OF GOVERNING
REGULATIONS NEATLY CUT OPENINGS AND HOLES PLUMB, SQUARE, AND
TRUE TO DIMENSIONS REQUIRED. USE CUTTING METHODS LEAST LIKELY
TO DAMAGE CONSTRUCTION TO REMAIN OR ADJOINING CONSTRUCTION
USE HAND TOOLS OR SMALL POWER TOOLS DESIGNED FOR SAWING OR
GRINDING, NOT HAMMERING AND CHOPPING, TO MINIMIZE DISTURBANCE
OF ADJACENT SURFACES. TEMPORARILY COVER OPENINGS TO REMAIN.
GENERAL DEMOLITION NOTES
12. CUT OR DRILL FROM THE EXPOSED OR FINISHED SIDE INTO CONCEALED
SURFACES TO AVOID MARRING EXISTING FINISHED SURFACES.
13. DO NOT USE CUTTING TORCHES UNTIL WORK AREA IS CLEARED OF
FLAMMABLE MATERIALS. AT CONCEALED SPACES, SUCH AS DUCT AND
PIPE INTERIORS, VERIFY CONDITION AND CONTENTS OF HIDDEN SPACE
BEFORE STARTING FLAME-CUTTING OPERATIONS. MAINTAIN FIRE WATCH
AND PORTABLE FIRE-SUPPRESSION DEVICES DURING FLAME-CUTTING
OPERATIONS.
14. LOCATE SELECTIVE DEMOLITION EQUIPMENT AND REMOVE DEBRIS AND
MATERIALS SO AS NOT TO IMPOSE EXCESSIVE LOADS ON SUPPORTING
WALLS, FLOORS, OR FRAMING.
15. DISPOSE OF DEMOLISHED ITEMS AND MATERIALS PROMPTLY.
16. EXISTING ITEMS TO REMAIN: PROTECT CONSTRUCTION INDICATED TO
REMAIN AGAINST DAMAGE AND SOILING DURING SELECTIVE DEMOLITION,
WHEN PERMITTED BY ARCHITECT, ITEMS MAY BE REMOVED TO A
SUITABLE, PROTECTED STORAGE LOCATION DURING SELECTIVE
DEMOLITION CLEANED AND REINSTALLED IN THEIR ORIGINAL LOCATIONS
AFTER SELECTIVE DEMOLITION OPERATIONS ARE COMPLETE.
17. EXCEPT FOR ITEMS OR MATERIALS INDICATED TO BE REUSED, SALVAGED,
REINSTALLED, OR OTHERWISE INDICATED TO REMAIN OWNERS'
PROPERTY, REMOVE DEMOLISHED MATERIALS FROM PROJECT SITE AND
LEGALLY DISPOSE OF THEM IN AN EPA-APPROVED LANDFILL. DO NOT
ALLOW DEMOLISHED MATERIALS TO ACCUMULATE ON-SITE.
18. REMOVE AND TRANSPORT DEBRIS IN A MANNER THAT WILL PREVENT
SPILLAGE ON ADJACENT SURFACES AND AREAS.
19. REMOVE DEBRIS FROM ELEVATED PORTIONS OF BUILDING BY CHUTE,
HOIST, OR OTHER DEVICE THAT WILL CONVEY DEBRIS TO GRADE LEVEL IN
A CONTROLLED DESCENT.
20. ENSURE UTILITIES THAT DO NOT SERVE THE SPACE ARE REMOVED OR
MITIGATED PER SECURITY REQUIREMENTS IN THE POR. ITEMS TO BE
CONFIRMED DURING DEMOLITION.
DEMOLITION KEY NOTES
A
B
REMOVE PORTION OF EXISTING WALL AS REQUIRED FOR NEW
CONSTRUCTION. PATCH AND PREPARE ADJACENT WALL IN ITS
ENTIRETY.
REMOVE EXISTING WALL IN ITS ENTIRETY. PATCH AND PREPARE
ADJACENT SURFACES AS REQUIRED FOR NEW CONSTRUCTION.
REMOVE EXISTING DOOR, FRAME AND HARDWARE IN ITS ENTIRETY.
PATCH AND PREPARE ADJACENT SURFACES AS REQUIRED FOR NEW
CONSTRUCTION.
REMOVE EXISTING PLUMBING FIXTURE AND ASSOCIATED PIPING. REFER
TO PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
REMOVE EXISTING CARPET IN ITS ENTIRETY. PATCH AND PREPARE
ADJACENT SURFACES AS REQUIRED FOR NEW CONSTRUCTION.
C
D
E
0 4' 8' 1"= 4'
True North
Plan North
CHECKED BY
DRAWN BY
FLOOR NUMBER
SHEET TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
Model Author
PROJECT NUMBER
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NUMBER
CITY/ST./ZIP
ADDRESS
BUILDING NAME
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
24 X 36
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N T
R A
C T
O R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
T A
M P
O R
S E
A L
D E
S
IG
N E
R
ID
E N
T
IF
IC
A
T
IO
N O
W N
E R
ID
E
N T
IF
IC
A T
IO
N
SHEET OF SHEETS
482 S Broadway - Suite 100 Denver, Colorado 80209 Telephone: 303-260-7277
UNCLASSIFIED // FOR OFFICIAL USE ONLY
PROPERTY OF THE UNITED STATES GOVERNMENT
Do not remove this notice. Properly destroy or return documents when no longer needed
TENANT IMPROVEMENT OF 2,578GSF
LEVEL 3
ARCHITECTURE
47PJ0020D0012
47PJ0025F0120
DESIGN EDGE
/2
/2
:3
:5
A
M
A1.1
DEMOLITION FLOOR PLAN
GSA 3RD FLOOR TI - GRAND FORKS, ND
ISSUED FOR CONSTRUCTION
5/6/2026
3/6/2026TP
SG
23133
General Service Administration
2 49
RONALD N. DAVIES FEDERAL BUILDING
ND0008ZZ
RONALD N. DAVIES FEDERAL BUILDING
102 NORTH 4TH STREET,
GRAND FORKS, ND 58203
DESIGN EDGE
1/4" = 1'-0"
LEVEL 3 DEMO PLAN
Mark Date Description
8/5/2025 35% Submittal
9/22/2025 65% Submittal
12/5/2025 95% Submittal
3/6/2026 100% Submittal
3/31/2026 Issued for Construction
A A
A
A
A
A
A
A A
A A
A
A
DEMOLITION RCP KEY NOTES
REMOVE EXISTING CEILING TILES, ASSOCIATED GRID, LIGHT FIXTURES,
AND MECHANICAL GRILLES THROUGHOUT. REFER TO MECHANICAL AND
ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
A
0 4' 8' 1"= 4'
True North
Plan North
CHECKED BY
DRAWN BY
FLOOR NUMBER
SHEET TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
Model Author
PROJECT NUMBER
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NUMBER
CITY/ST./ZIP
ADDRESS
BUILDING NAME
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
24 X 36
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N T
R A
C T
O R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
T A
M P
O R
S E
A L
D E
S
IG
N E
R
ID
E N
T
IF
IC
A
T
IO
N O
W N
E R
ID
E
N T
IF
IC
A T
IO
N
SHEET OF SHEETS
482 S Broadway - Suite 100 Denver, Colorado 80209 Telephone: 303-260-7277
UNCLASSIFIED // FOR OFFICIAL USE ONLY
PROPERTY OF THE UNITED STATES GOVERNMENT
Do not remove this notice. Properly destroy or return documents when no longer needed
TENANT IMPROVEMENT OF 2,578GSF
LEVEL 3
ARCHITECTURE
47PJ0020D0012
47PJ0025F0120
DESIGN EDGE
/2
/2
:3
:5
A
M
A1.2
DEMOLITION RCP
GSA 3RD FLOOR TI - GRAND FORKS, ND
ISSUED FOR CONSTRUCTION
5/6/2026
3/6/2026TP
SG
23133
General Service Administration
3 49
RONALD N. DAVIES FEDERAL BUILDING
ND0008ZZ
RONALD N. DAVIES FEDERAL BUILDING
102 NORTH 4TH STREET,
GRAND FORKS, ND 58203
DESIGN EDGE
1/4" = 1'-0"
DEMO RCP
Mark Date Description
8/5/2025 35% Submittal
9/22/2025 65% Submittal
12/5/2025 95% Submittal
3/6/2026 100% Submittal
3/31/2026 Issued for Construction
5S
5S 4
5S 5S
7a
156 SF
127 SF
95 SF
19A
76 SF
10A
211 SF
8B 220 SF
6a/12/13
795 SF
113 SF
3.1
181 SF
182 SF
1A
34 SF
183 SF
38 SF
1B
167 SF
5A
/8
/2
9'-8 3/4" 5'-11 1/8" 4'-5 1/2" 8'-1 3/4" 2'-11 5/8" 3'-0" 3'-10" 17'-4 3/4" 18'-2 3/8" 7'-6 7/8" 4'-6 7/8" 8'-2 5/8"
/8
/4
/4
/4
/4
/2
11'-8 5/8" 12'-1"
2'-9 1/4" 9'-7 3/8"
15'-7 1/4" 53'-3 3/8"
5S5S
3 4
5S
7a
7a
7a
7a
7a
7a
7a
7a
36"
36"
1Ba
36"
19A
36"
8B
36"
6A/12/13
36"
36"
3.1
36"
36"
1Ab
36"
1Aa
36"
36"
4'-7" 2'-4 1/2"
31 SF
JAN.
/2
D
I
P
P
I P RR
A6.3 2
A6.3
(E) FIRE EXTINGUISHER
11'-8 5/8" 4'-11 1/4"
7a
5'-5 5/8" 13'-0 1/8" 2'-4 3/4" 7'-1"
7a
5S
7a
A6.3
5'-0"A6.3
7b
7b
7b
7b
7b
ALIGN
FEC
SIM
/2
1Bb
36"
PLAN KEY NOTES
PROVIDE FIRE EXTINGUISHER
PROVIDE ALL GLAZING SURFACES OF WINDOWS WITH 7 MIL FRAGMENT
RETENTION FILM. ATTACH FILM TO WINDOW FRAME WITH 3/4" STRUCTURAL
SILICONE WET GLAZE METHOD. IF WINDOW UNIT IS OPERABLE, BOLT SHUT
PERMANENTLY TO RENDER IT INOPERABLE.
PROVIDE LEVEL 3 SEALED BALLISTIC TRANSACTION WINDOW WITH LOCKABLE
FLIP TOP DEAL TRAY, AND COUNTER MOUNTED TWO-WAY COMMUNICATION
DEVICE. PROVIDE APRON BELOW COUNTER ON SECURE SIDE TO MAKE
COUNTER PROJECTION CONFORM TO ADA REQUIREMENTS.
PROVIDE OPAQUE MINI-BLINDS AT ALL WINDOWS.
PROVIDE 36"X36" ADA SHOWER STALL. PROVIDE UNGLAZED CERAMIC TILE
FLOORING AND A FLOOR DRAIN WITH SELF PRIMING TRAP PER PLUMBING.
SHOWER STALL TO MEET REQUIREMENTS OF ABAAS SECTION 608
PROVIDE (3) ROBE HOOKS MOUNTED ON THE ROOM SIDE OF DOOR. MOUNT
(2) ROBE HOOKS AT 60" A.F.F. AND (1) ROBE HOOK MOUNTED AT 48" A.F.F.
RESIDENTIAL GRADE STACKABLE WASHER AND DRYER. REFER TO MEP
DRAWINGS FOR ADDITIONAL INFORMATION.
OWNER FURNISHED, CONTRACTOR INSTALLED
REFER TO EQUIPMENT SCHEDULE SHEET A6.3
WALL MOUNTED TV. PROVIDE POWER AND DATA AT 84" A.F.F. PER
ELECTRICAL. PROVIDE 3/4" FIRE-RESISTANT PLYWOOD BLOCKING.
OWNER FURNISHED, CONTRACTOR INSTALLED.
3/4" PLYWOOD MOUNTING BOARD SECURED TO PARTITION (FULL LENGTH OF
PARTITION). COORDINATE LOCATION WITH OWNER.
CONTRACTOR FURNISHED, CONTRACTOR INSTALLED.
PROVIDE STAINLESS STEEL REFRIGERATOR WITH FREEZER
REFER TO EQUIPMENT SCHEDULE SHEET A6.3
PROVIDE 24" DETENTION GRADE HANDCUFF BAR. PROVIDE BACKING IN WALL
PER DETAIL
REFINISH (E) HARDWOOD FLOORING
PROVIDE MAGNETIC GLASS MARKER BOARD WITH INTEGRATED ACCESSORY
TRAY, 4'-0" H BY LENGTH OF WALL, IN 2'-0" INCREMENTS, MOUNTED SO THE
BOTTOM OF THE BOARD IS 2'-6" A.F.F.
PAINT "CORRIDOR" SIDE ONLY OF THE SECURE A7 WALL CONSTRUCTION
BLACK AT ALL LOCATIONS WHERE THE WALL WILL BE INSTALLED NEXT TO
THE CORRIDOR WALL. EXISTING DOORS, CORRIDOR SIDE WOOD DOOR TRIM
AND SURROUNDS, CHAIR RAIL AND BASE BOARDS / MARBLE BASE TO REMAIN
VISIBLE AND INTACT ON CORRIDOR SIDE. AT EXISTING OPENING LOCATIONS,
DOORS WILL BE SECURED PER TENANT REQUIREMENTS.
PROVIDE MICROWAVE.
REFER TO EQUIPMENT SCHEDULE SHEET A6.3
SYMBOLS LEGEND
KEYED NOTE MARKER
CCTV CAMERA MOUNTING LOCATION. PROVIDE JUNCTION BOX
(JB). PROVIDE (2) 3/4" EMT CONDUIT WILL PULLSTRING FROM JB
UP WITHIN WALL CAVITY THEN STUBBED 24" INTO TENANT
SPACE ABOVE THE CEILING. FINAL LOCATION OF VSS CAMERAS
TO BE DETERMINED BY TENANT'S TECHNICAL PERSONNEL
3/4" PLYWOOD MOUNTING BOARD SECURED TO WALL
(WALL TO WALL)
ACCESS CONTROL KEYPAD
ACCESS CONTROL KEYPAD + REMOTE RELEASE
DOORBELL
INTERCOM
PANIC BUTTON
ALARM CONTROL KEYPAD
AMBUSH MONITOR
REMOTE RELEASE
PMB
KP
KE
D
I
P
AK
AM
RR
INTERIOR PARTITION TYPES
1 WALL TYPE A1 (CEILING HIGH), TYP U.N.O.
2 WALL TYPE A2 (BULLET RESISTANT)
3 WALL TYPE A3 (SECURE STORAGE)
3A WALL TYPE A3 (SECURE STORAGE, ACOUSTICAL)
4 WALL TYPE A4 (SLAB TO SLAB)
5 WALL TYPE A5 (ACOUSTICAL)
7 WALL TYPE A7 (SECURE PERIMETER)
7A WALL TYPE A7A (SECURE PERIMETER AT (E) CORRIDOR
WALLS)
NOTES:
1. ALL EXTERIOR WINDOWS SHALL BE PROVIDED WITH MINIMUM 7 MIL BLAST FILM.
2. DUCTS OR AIR TRANSFER OPENINGS THROUGH TYPE 2,3,6, AND 7 PARTITIONS
THAT ARE LARGER THAN 96 SQUARE INCHES SHALL BE PROTECTED WITH
MANBARS. REFER TO POR FOR SPECIFICATIONS ON MANBARS.
3. AIR TRANSFER OPENINGS THROUGH TYPE 2, 5, AND 7 PARTITIONS SHALL BE
SOUNDPROOFED USING SOUNDLINED Z-DUCTS. REFER TO POR FOR
SPECIFICATIONS ON Z-DUCTS.
4. ALL CONDUITS, BACKBOXES AND ELECTRICAL DEVICES SHALL BE SURFACE
MOUNTED ON THE SECURE SIDE OF PARTITION TYPES 3, 6, AND 7.
5. WINDOW COVERINGS - ALL INTERIOR, TRANSACTION, AND EXTERIOR WINDOWS
MUST BE PROVIDED WITH OPAQUE HORIZONTAL WINDOW BLINDS, PER
SPECIFICATIONS UNLESS NOTED OTHERWISE.
AREA OF WORK
LEVEL 3
0 4' 8' 1"= 4'
True North
Plan North
CHECKED BY
DRAWN BY
FLOOR NUMBER
SHEET TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
Model Author
PROJECT NUMBER
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NUMBER
CITY/ST./ZIP
ADDRESS
BUILDING NAME
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
24 X 36
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N T
R A
C T
O R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
T A
M P
O R
S E
A L
D E
S
IG
N E
R
ID
E N
T
IF
IC
A
T
IO
N O
W N
E R
ID
E
N T
IF
IC
A T
IO
N
SHEET OF SHEETS
482 S Broadway - Suite 100 Denver, Colorado 80209 Telephone: 303-260-7277
UNCLASSIFIED // FOR OFFICIAL USE ONLY
PROPERTY OF THE UNITED STATES GOVERNMENT
Do not remove this notice. Properly destroy or return documents when no longer needed
TENANT IMPROVEMENT OF 2,578GSF
LEVEL 3
ARCHITECTURE
47PJ0020D0012
47PJ0025F0120
DESIGN EDGE
/2
/2
:3
:5
A
M
A1.3
FLOOR PLAN
GSA 3RD FLOOR TI - GRAND FORKS, ND
ISSUED FOR CONSTRUCTION
5/6/2026
3/31/2026TP
SG
23133
General Service Administration
4 49
RONALD N. DAVIES FEDERAL BUILDING
ND0008ZZ
RONALD N. DAVIES FEDERAL BUILDING
102 NORTH 4TH STREET,
GRAND FORKS, ND 58203
DESIGN EDGE
1/4" = 1'-0"
LEVEL 3 - FINISH PLAN
Mark Date Description
8/5/2025 35% Submittal
9/22/2025 65% Submittal
12/5/2025 95% Submittal
3/6/2026 100% Submittal
3/31/2026 Issued for Construction
156 SF
127 SF
38 SF
1B
95 SF
19A
76 SF
10A
211 SF
8B 220 SF
6a/12/13
34 SF
113 SF
3.1 181 SF
167 SF
5A
795 SF
182 SF
1A
183 SF
9'-4"
9'-4" 9'-4" 9'-4"
9'-4"
9'-4"
9'-4"
5'-10"
3'-1 5/8"
ACT
ACT
ACT
ACTACT
ACTACT
ACT
ACT
ACT 9'-4"
8'-0"
8'-0"
9'-4"
GWB
S
S S S
S
S S
S
ACT
S
S
S
S
S
ACT
9'-4"
SS
S
9'-4"
11'-4"
EXPOSED TO SECURE CEILING
A6.4
7'-11"
GWB BULKHEAD
LEGEND
100'-0"
MAT
FINISHED CEILING HEIGHT AFF
OR OPEN TO STRUCTURE
FINISHED CEILING MATERIAL
1. FIXTURES SHOWN FOR COORDINATION ONLY. REFER TO MECHANICAL AND
ELECTRICAL DRAWINGS FOR DETAILED REQUIREMENTS AND SCHEDULES.
2. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR LOCATION AND
TYPE OF FIXTURES.
3. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR EXISTING
FIXTURES TO BE RELOCATED.
4. ALL ACT CEILINGS TO BE STANDARD 15/16" WHITE METAL TEE GRID.
5. EXISTING ATTIC FLOOR IS 12'-0" ± ABOVE 3RD FLOOR.
6. SHADED AREA INDICATES AREA OF SECURE CEILING CONSTRUCTION
BELOW EXISTING PLASTER CEILING. REFER TO DETAIL 1/A6.4
NOTES
SUPPLY AIR DIFFUSER
CEILING LEGEND
RETURN AIR GRILLE
2X4 RECESSED
FLAT PANEL LED
6" RECESSED DOWNLIGHT
S SMOKE DETECTOR
4"x4' LINEAR LED
PANEL
ASSUMED LOADS:
3-5/8" STUDS WITH LOOSE INSULATION: 1.5 PSF
5/8" FRT PLYWOOD: 2.0 PSF
5/8" GYPSUM BOARD: 2.5 PSF
SUSPENDED ACOUSTIC CEILING ASSEMBLY: 2.0 PSF
MEP: 3.0 PSF
MISC.: 2.0 PSF
AT 15'-0" SPAN, PROVIDE 362S162-54 STUDS AT 16" O.C.
AT SPANS 13'-0" OR LESS, PROVIDE 362S162-54 STUDS AT 24" O.C.
AT END CHANNEL CONNECTION, PROVIDE 3"X3"X12-GA. BEARING ANGLE
FASTENED WITH 1/4" ⌀ BUILDEX TAPCONS AT 16" O.C. PER DETAIL 5/A6.4.
LOAD CALCULATIONS
0 4' 8' 1"= 4'
True North
Plan North
CHECKED BY
DRAWN BY
FLOOR NUMBER
SHEET TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
Model Author
PROJECT NUMBER
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NUMBER
CITY/ST./ZIP
ADDRESS
BUILDING NAME
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
24 X 36
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N T
R A
C T
O R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
T A
M P
O R
S E
A L
D E
S
IG
N E
R
ID
E N
T
IF
IC
A
T
IO
N O
W N
E R
ID
E
N T
IF
IC
A T
IO
N
SHEET OF SHEETS
482 S Broadway - Suite 100 Denver, Colorado 80209 Telephone: 303-260-7277
UNCLASSIFIED // FOR OFFICIAL USE ONLY
PROPERTY OF THE UNITED STATES GOVERNMENT
Do not remove this notice. Properly destroy or return documents when no longer needed
TENANT IMPROVEMENT OF 2,578GSF
LEVEL 3
ARCHITECTURE
47PJ0020D0012
47PJ0025F0120
DESIGN EDGE
/2
/2
:3
:5
A
M
A1.4
REFLECTED CEILING PLAN
GSA 3RD FLOOR TI - GRAND FORKS, ND
ISSUED FOR CONSTRUCTION
5/6/2026
3/6/2026TP
SG
23133
General Service Administration
5 49
RONALD N. DAVIES FEDERAL BUILDING
ND0008ZZ
RONALD N. DAVIES FEDERAL BUILDING
102 NORTH 4TH STREET,
GRAND FORKS, ND 58203
DESIGN EDGE
1/4" = 1'-0"
REFLECTED CEILING PLAN
Mark Date Description
8/5/2025 35% Submittal
9/22/2025 65% Submittal
12/5/2025 95% Submittal
3/6/2026 100% Submittal
3/31/2026 Issued for Construction
HM1
16 GA. HOLLOW METAL
WELDED FRAME FOR
INTERIOR DOORS
PRIME FOR PAINT
HM2
HOLLOW METAL FULLY
WELDED 11 GA. BALLISTIC
STEEL FRAME TO MEET UL752
LEVEL III BULLET RESISTANCE.
PRIMED FOR PAINT
HM3
16 GA. HOLLOW METAL
FULLY WELDED FRAME FOR
INTERIOR DOORS
PRIMED FOR PAINT
AT BUILDING CORRIDOR
WALLS & SECURE STORAGE
WITH SPECIAL HOLLOW
METAL FRAME (WIDER
THROAT)
HM4
16 GA. HOLLOW METAL FLUSH
FULLY WELDED FRAME FOR
BUILDING CORRIDOR DOORS
PRIMED FOR PAINT
3'-0" 2" 2" 3'-0" 2"
2" 3'-0" 2"
2" 3'-0" 2"
WDA
SOLID CORE (SCL)
PREFINISHED WOOD DOOR
WDB
SOLID CORE PREFINISHED
ACOUSTICAL WOOD DOOR. WITH
12Wx12H VIEW WINDOW WITH
INTEGRAL BLINDS - VISION CONTROL
FROM UNICEL CRANKS WILL BE ON
THE OUTSIDE OF ROOM 2
WDC
STC RATED PREFINISHED
WOOD DOOR
WDD
SOLID CORE
(BULLET PROOF LINING)
UL752 LEVEL III, SPSA
BULLET RESISTANT DOOR
MATERIAL
3'-0"
1'-0" 1'-0"
3'-0"
3'-0"
3'-0"
5/8" TYPE 'X' GWB,
EACH SIDE OF WALL
(E) SALVAGED DOOR
CASING REINSTALLED
AS SHOWN
CAULK
FLUSH DOUBLE
RABBETED HOLLOW
METAL DOOR FRAME
PROVIDE FOAM-IN
INSULATION IN FRAME
AT WALL TYPES A2, A5,
A6, & A7
1/4"
5"
(E) SALVAGED DOOR
CASING WILL BE
CAREFULLY STRIPPED
AND REFINISHED TO
MATCH EXISTING CASING
SCHEDULED DOOR
5/8" TYPE 'X' GWB,
EACH SIDE OF WALL
2"
U.N.O.
4" TYP.
HOLLOW METAL DOOR
FRAME-PAINTED. PROVIDE
(3) ANCHORS PER JAMB
PROVIDE FOAM-IN
INSULATION IN FRAME AT
WALL TYPES A2, A5, A6, & A7
METAL STUD FRAMING
SEALANT, BOTH SIDES
5/8" TYPE 'X' GWB EA. SIDE
OF METAL STUD WALL
HOLLOW METAL FRAME
PROVIDE FOAM-IN
INSULATION IN FRAMES AT
WALL TYPES A2, A5, A6, & A7
FLUSH WOOD DOOR
AS SCHEDULED
/8
1/2"
CHECKED BY
DRAWN BY
FLOOR NUMBER
SHEET TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
Model Author
PROJECT NUMBER
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NUMBER
CITY/ST./ZIP
ADDRESS
BUILDING NAME
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
24 X 36
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N T
R A
C T
O R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
T A
M P
O R
S E
A L
D E
S
IG
N E
R
ID
E N
T
IF
IC
A
T
IO
N O
W N
E R
ID
E
N T
IF
IC
A T
IO
N
SHEET OF SHEETS
482 S Broadway - Suite 100 Denver, Colorado 80209 Telephone: 303-260-7277
UNCLASSIFIED // FOR OFFICIAL USE ONLY
PROPERTY OF THE UNITED STATES GOVERNMENT
Do not remove this notice. Properly destroy or return documents when no longer needed
TENANT IMPROVEMENT OF 2,578GSF
LEVEL 3
ARCHITECTURE
47PJ0020D0012
47PJ0025F0120
DESIGN EDGE
/2
/2
:3
:0
A
M
A6.1
DOORS
GSA 3RD FLOOR TI - GRAND FORKS, ND
ISSUED FOR CONSTRUCTION
5/6/2026
3/6/2026TP
SG
23133
General Service Administration
6 49
RONALD N. DAVIES FEDERAL BUILDING
ND0008ZZ
RONALD N. DAVIES FEDERAL BUILDING
102 NORTH 4TH STREET,
GRAND FORKS, ND 58203
DESIGN EDGE
DOOR SCHEDULE
DIMENSIONS
DOOR FRAME
HARDWARE RATING COMMENTSTYPE FINISH TYPE FINISH
3'-0" x 7'-0" x 1 3/4" WDC STAIN HM4 PAINT 9A 20 MIN STC RATED DOOR WITH FOAMED IN INSULATION IN JAMB
3'-0" x 7'-0" x 1 3/4" WDD STAIN HM2 PAINT 6 BULLET RESISTANT DOOR PER SPECIFICATIONS
3'-0" x 7'-0" x 1 3/4" WDC STAIN HM4 PAINT 9B 20 MIN STC RATED DOOR WITH FOAMED IN INSULATION IN JAMB
3'-0" x 7'-0" x 1 3/4" WDC STAIN HM3 PAINT 5B STC RATED DOOR WITH FOAMED IN INSULATION IN JAMB
3'-0" x 7'-0" x 1 3/4" WDB STAIN HM1 PAINT 5A STC RATED DOOR WITH FOAMED IN INSULATION IN JAMB
3'-0" x 7'-0" x 1 3/4" WDC STAIN HM1 PAINT 3 STC RATED DOOR WITH FOAMED IN INSULATION IN JAMB
3'-0" x 7'-0" x 1 3/4" WDC STAIN HM3 PAINT 5
3'-0" x 7'-0" x 1 3/4" WDA STAIN HM1 PAINT 1
3'-0" x 7'-0" x 1 3/4" WDC STAIN HM1 PAINT 3 STC RATED DOOR WITH FOAMED IN INSULATION IN JAMB
3'-0" x 7'-0" x 1 3/4" WDA STAIN HM1 PAINT 4
3'-0" x 7'-0" x 1 3/4" WDA STAIN HM1 PAINT 5
3'-0" x 7'-0" x 1 3/4" WDA STAIN HM1 PAINT 5
3'-0" x 7'-0" x 1 3/4" WDA STAIN HM1 PAINT 2
3/8" = 1'-0"
DOOR AND FRAME TYPES
3" = 1'-0"
JAMB DETAIL AT SUITE ENTRY
3" = 1'-0"
HOLLOW METAL JAMB
3" = 1'-0"
HOLLOW METAL HEAD
QTY DESCRIPTION CATALOG NUMBER MFR
3 EA. HINGE 5BB1 4.5 X 4.5 IVE
1 EA. PASSAGE SET L9010 SCH
1 EA. WALL STOP WS406 IVE
FUNCTION: (F01) PASSAGE LATCH. LATCH RETRACTED BY LEVER EITHER SIDE. BOTH LEVERS ALWAYS
UNLOCKED
HARDWARE SET 1
QTY DESCRIPTION CATALOG NUMBER MFR
3 EA. HINGE 5BB1 4.5 X 4.5 IVE
1 EA. PRIVACY W/DEADBOLT L9440 SCH
1 EA. OH STOP 90S GLY
FUNCTION: (F19) PRIVACY LOCK. LATCHBOLT RETRACTED BY LEVER EITHER SIDE. OUTSIDE LEVER LOCKED BY ROTATING INSIDE THUMB TURN, EXTENDING DEADBOLT. OUTSIDE LEVER UNLOCKED BY ROTATING INSIDE THUMB TURN TO RETRACT DEADBOLT, ROTATING INSIDE LEVER (RETRACTS LATCHBOLT AND DEADBOLT), OR BY OUTSIDE EMERGENCY KEY.
HARDWARE SET 2
QTY DESCRIPTION CATALOG NUMBER MFR
3 EA. HINGE 5BB1 4.5 X 4.5 NRP IVE
1 EA. CLASSROOM LOCK L9070 SCH
1 EA. CYLINDER CORE AS REQUIRED
1 EA. WALL STOP WS406 IVE
1 SET GASKETING 870 ZER
1 EA. DOOR BOTTOM 369 ZER
FUNCTION: (F05) CLASSROOM LOCK. OUTSIDE LEVER LOCKED AND UNLOCKED BY OUTSIDE KEY. INSIDE
LEVER ALWAYS UNLOCKED. AUXILIARY LATCH DEADLOCKS LATCHBOLT WHEN DOOR IS CLOSED.
NOTE: USE 870SPB MOUNTING BRACKET TO MOUNT CLOSERS OR RIM-MOUNTED STRIKES. DO NOT CUT SEALS FOR CLOSERS OR STRIKEDS TO ENSURE CONTINUOUS SEAL AT PERIMETER OF DOOR. ADJUST BACKSET
DIMENSIONS FOR RIM LOCKS AND PANIC HARDWARE TO ACCOMMODATE MOUNTING BRACKET.
HARDWARE SET 3
QTY DESCRIPTION CATALOG NUMBER MFR
3 EA. HINGE 5BB1 4.5 X 4.5 NRP IVE
1 EA. STOREROOM LOCK L9080 SCH
1 EA. CYLINDER CORE AS REQUIRED
1 EA. SURFACE CLOSER 4050A REG IVE
1 EA. KICK PLATE 8400 10" IVE
1 EA. WALL STOP WS406 IVE
FUNCTION: (F07) STOREROOM LOCK. FIXED OUTSIDE TRIM - OUTSIDE KEY RETRACTS LATCH. INSIDE LEVER
ALWAYS UNLOCKED. AUXILIARY LATCH DEADLOCKS LATCH BOLT WHEN DOOR IS CLOSED.
HARDWARE SET 4
QTY DESCRIPTION CATALOG NUMBER MFR
1 EA. CONT. HINGE 112HD EPT IVE
1 EA. POWER TRANSFER EPT 10 VON
1 EA. COMBINATION DEADLOCK KABA MAS CDX-10 KAB
1 EA. EU STOREROOM LOCK L9092EU RX SCH
1 EA. FSIC CYLINDER CORE BY TENANT B/O
1 EA. SURFACE CLOSER 4050A EDA LCN
1 EA. KICK PLATE 8400 10" IVE
1 EA. WALL STOP WS406 IVE
1 SET GASKETING 870 ZER
1 EA. DOOR BOTTOM 369 ZER
2 EA. MOUNTING BRACKET 870SPB ZER
1 EA. KEYPAD BY SECURITY SUPPLIER B/O
1 EA. DOOR POSITION SWITCH BY SECURITY SUPPLIER B/O
1 EA. POWER SUPPLY PS902 900-2RS VON
1 EA. WIRING DIAGRAMS RISER AND POINT-TO-POINT
FUNCTION: ELECTRIFIED STOREROOM LOCK - FAIL SECURE. OUTSIDE KEY OR INSIDE LEVER RETRACTS LATCH. OUTSIDE LEVER UNLOCKED BY CREDENTIAL READER. INSIDE LEVER ALWAYS UNLOCKED. UPON LOSS OF POWER, OUTSIDE LEVER REMAINS LOCKED. COMBINATION DEADLOCK: VALID COMBINATION UNLOCKS DEADBOLT. INSIDE KNOB RETRACTS DEADBOLT FOR EGRESS. WHEN UNLOCKED, LIFE SAFETY SWITCH HOLDS
DEADBOLT RETRACTED FOR AUTHORIZED ENTRY BY ACCESS CONTROL.
NOTE: USE 870SPB MOUNTING BRACKET TO MOUNT CLOSERS OR RIM-MOUNTED STRIKES. DO NOT CUT SEALS FOR CLOSERS OR STRIKES TO ENSURE CONTINUOUS SEAL AT PERIMETER OF DOOR. ADJUST BACKSET
DIMENSIONS FOR RIM LOCKS AND PANIC HARDWARE TO ACCOMMODATE MOUNTING BRACKET.
HARDWARE SET 5B
HARDWARE SET 5A
QTY DESCRIPTION CATALOG NUMBER MFR
3 EA. HINGE 5BB1 4.5 X 4.5 NRP IVE
1 EA. POWER TRANSFER EPT10 VON
1 EA. EU STOREROOM LOCK L9092EU RX SCH
1 EA. CYLINDER CORE AS REQUIRED
1 EA. SURFACE CLOSER 4050A SCUSH LCN
1 EA KICK PLATE 8400 10" IVE
1 SET GASKETING 870 ZER
1 EA. DOOR BOTTOM 369 ZER
1 EA. MOUNTING BRACKET 870SPB ZER
1 EA. KEYPAD BY SECURITY SUPPLIER B/O
1 EA. DOOR POSITION SWITCH BY SECURITY SUPPLIER B/O
1 EA. POWER SUPPLY PS902 900-2RS VON
1 EA. WIRING DIAGRAMS RISER AND POINT-TO-POINT
FUNCTION: ELECTRIFIED STOREROOM LOCK - FAIL SECURE. OUTSIDE KEY OR INSIDE LEVER RETRACTS LATCH. OUTSIDE LEVER UNLOCKED BY CREDENTIAL READER. INSIDE LEVER ALWAYS UNLOCKED. UPON LOSS
OF POWER, OUTSIDE LEVER REMAINS LOCKED.
NOTE: USE 870SPB MOUNTING BRACKET TO MOUNT CLOSERS OR RIM-MOUNTED STRIKES. DO NOT CUT SEALS FOR CLOSERS OR STRIKES TO ENSURE CONTINUOUS SEAL AT PERIMETER OF DOOR. ADJUST BACKSET DIMENSIONS FOR RIM LOCKS AND PANIC HARDWARE TO ACCOMMODATE MOUNTING BRACKET.
QTY DESCRIPTION CATALOG NUMBER MFR
3 EA. HINGE 5BB1 4.5 X 4.5 IVE
1 EA. POWER TRANSFER EPT10 VON
1 EA. EU STOREROOM LOCK L9092EU RX SCH
1 EA. FSIC CYLINDER CORE BY TENANT B/O
1 EA. SURFACE CLOSER 4050A REG LCN
1 EA. KICK PLATE 8400 10" IVE
1 EA. WALL STOP WS406 IVE
1 EA. KEYPAD BY SECURITY SUPPLIER B/O
1 EA. DOOR POSITION SWITCH BY SECURITY SUPPLIER B/O
1 EA. POWER SUPPLY PS902 900-2RS VON
1 EA. WIRING DIAGRAMS RISER AND POINT-TO-POINT
FUNCTION: ELECTRIFIED STOREROOM LOCK - FAIL SECURE. OUTSIDE KEY OR INSIDE LEVER RETRACTS LATCH. OUTSIDE LEVER UNLOCKED BY CREDENTIAL READER. INSIDE LEVER ALWAYS UNLOCKED. UPON
LOSS OF POWER, OUTSIDE LEVER REMAINS LOCKED.
HARDWARE SET 5
QTY DESCRIPTION CATALOG NUMBER MFR
1 EA. CONT. HINGE 112HD EPT IVE
1 EA. POWER TRANSFER EPT10 VON
1 EA. FSIC CYLINDER HOUSING AS REQUIRED SCH
1 EA. ELEC FIRE EXIT HARDWARE RX-QEL-9857-NL-F VON
1 EA. LATCH GUARD LGO-3 VON
1 EA FSIC CYLINDER CORE BY TENANT B/O
1 EA. SURFACE CLOSER 4050A SCUSH LCN
1 EA. KICK PLATE 8400 10" IVE
1 SET GASKETING 870 ZER
1 EA. DOOR BOTTOM 369 ZER
1 EA. THRESHOLD 63A ZER
3 EA. MOUNTING BRACKET 870SPB ZER
1 EA. KEYPAD BY SECURITY SUPPLIER B/O
1 EA. DOOR POSITION SWITCH BY SECURITY SUPPLIER B/O
1 EA. POWER SUPPLY PS902 900-2RS VON
1 EA. WIRING DIAGRAMS RISER AND POINT-TO-POINT
FUNCTION: NIGHT LATCH PANIC HARDWARE WITH ELECTRIC LATCH RETRACTION. FIXED OUTSIDE TRIM -
LATCH RETRACTED BY KEY. INSIDE PUSH PAD RETRACTS LATCH FOR EGRESS.
ELECTRIC LATCH RETRACTED BY ELECTRONIC ACCESS CONTROL SYSTEM FOR PUSH/PULL OPERATION.
NOTE: USE 870SPB MOUNTING BRACKET TO MOUNT CLOSERS OR RIM-MOUNTED STRIKES. DO NOT CUT SEALS FOR CLOSERS OR STRIKES TO ENSURE CONTINUOUS SEAL AT PERIMETER OF DOOR. ADJUST BACKSET DIMENSIONS FOR RIM LOCKS AND PANIC HARDWARE TO ACCOMMODATE MOUNTING BRACKET.
HARDWARE SET 9B
QTY DESCRIPTION CATALOG NUMBER MFR
1 EA. CONT. HINGE 112HD EPT IVE
1 EA. POWER TRANSFER EPT 10 VON
1 EA. ELEC PANIC HARDWARE RX-QEL-9857-DT VON
1 EA. LATCH GUARD LGO-3 VON
1 EA. SURFACE CLOSER 4050A EDA LCN
1 EA. KICK PLATE 8400 10" IVE
1 EA. WALL STOP WS406 IVE
1 SET GASKETING 870 ZER
1 EA. DOOR BOTTOM 369 ZER
1 EA. THRESHOLD 63A ZER
3 EA. MOUNTING BRACKET 870SPB ZER
1 EA. KEYPAD BY SECURITY SUPPLIER B/O
1 EA. DOOR POSITION SWITCH BY SECURITY SUPPLIER B/O
1 EA. POWER SUPPLY PS902 900-2RS VON
1 EA. WIRING DIAGRAMS RISER AND POINT-TO-POINT
FUNCTION: DUMMY TRIM PANIC HARDWARE WITH ELECTRIC LATCH RETRACTION. FIXED OUTSIDE TRIM - NO KEY ACCESS. INSIDE PUSH PAD RETRACTS LATCH FOR EGRESS. ELECTRIC LATCH RETRACTED BY
ELECTRONIC ACCESS CONTROL SYSTEM FOR PUSH/PULL OPERATION.
NOTE: USE 870SPB MOUNTING BRACKET TO MOUNT CLOSERS OR RIM-MOUNTED STRIKES. DO NOT CUR SEALS FOR CLOSERS OR STRIKES TO ENSURE CONTINUOUS SEAL AT PERIMETER OF DOOR. ADJUST BACKSET DIMENSIONS FOR RIM LOCKS AND PANIC HARDWARE TO ACCOMMODATE MOUNTING BRACKET.
HARDWARE SET 6
QTY DESCRIPTION CATALOG NUMBER MFR
1 EA. CONT. HINGE 112HD EPT IVE
1 EA. POWER TRANSFER EPT10 VON
1 EA. ELEC FIRE EXIT HARDWARE RX-QEL-9957-DT-F VON
1 EA. LATCH GUARD LGO-3 VON
1 EA. SURFACE CLOSER 4050A SCUSH LCN
1 EA. KICK PLATE 8400 10" IVE
1 SET GASKETING 870 ZER
1 EA. DOOR BOTTOM 369 ZER
1 EA. THRESHOLD 63A ZER
3 EA. MOUNTING BRACKET 870SPB ZER
1 EA. KEYPAD BY SECURITY SUPPLIER B/O
1 EA. DOOR POSITION SWITCH BY SECURITY SUPPLIER B/O
1 EA. POWER SUPPLY PS902 900-2RS VON
1 EA. WIRING DIAGRAMS RISER AND POINT-TO-POINT
FUNCTION: DUMMY TRIM PANIC HARDWARE WITH ELECTRIC LATCH RETRACTION. FIXED OUTSIDE TRIM - NO KEY ACCESS. INSIDE PUSH PAD RETRACTS LATCH FOR EGRESS. ELECTRIC LATCH RETRACTED BY
ELECTRONIC ACCESS CONTROL SYSTEM FOR PUSH/PULL OPERATION.
NOTE: USE 870SPB MOUNTING BRACKET TO MOUNT CLOSERS OR RIM-MOUNTED STRIKES. DO NOT CUT SEALS FOR CLOSERS OR STRIKES TO ENSURE CONTINUOUS SEAL AT PERIMETER OF DOOR. ADJUST BACKSET DIMENSIONS FOR RIM LOCKS AND PANIC HARDWARE TO ACCOMMODATE MOUNTING BRACKET.
HARDWARE SET 9A
NOTE: AT ALL DOORS REQUIRING GASKETING (870-ZER), GASKETS NEED TO BE EASILY ADJUSTABLE WITH THE TURN OF A SCREW DRIVER, TO MAINTAIN A PROPER SEAL EVEN IF THE DOOR SHIFTS AND WARPS.
PROVIDE Z OR L BRACKETS TO ENSURE THE SEALS MAKE A CONTINUOUS SEAL AROUND THE DOOR AND
CANNOT BE CUT TO MOUNT THE STRIKES.
Mark Date Description
8/5/2025 35% Submittal
9/22/2025 65% Submittal
12/5/2025 95% Submittal
3/6/2026 100% Submittal
3/31/2026 Issued for Construction
WALL TYPE A1
1. DRYWALL FINISH LEVEL 4, ONE (1) PRIMER COAT PLUS TWO (2) FINISH COATS FROM SLAB TO
CEILING, BOTH SIDES.
2. WALLS MAY EXTEND TO 6" ABOVE CEILING FOR EASE OF CONSTRUCTION, BUT IS NOT A TENANT
REQUIREMENT.
WALL TYPE A2 - BULLET RESISTANT LEVEL 3
1. DRYWALL FINISH LEVEL 4 FROM SLAB TO CEILING. DRYWALL FINISH LEVEL 3 FROM CEILING TO SLAB ABOVE, BOTH SIDES. ONE (1) PRIMER COAT PLUS TWO (2) FINISH COATS FROM SLAB TO SLAB ABOVE, BOTH SIDES. JOINTS BETWEEN DRYWALL AND PLYWOOD/BALLISTIC ARMOR MUST BE STAGGERED AT
ALL LOCATIONS.
2. SCRIBE AND SEAL DRYWALL AND PLYWOOD TO FIT CONTOUR OF SLAB AND ALL PENETRATIONS. GAPS, IF PRESENT, MUST BE NO GREATER THAN 1/2" AT ANY LOCATION AND MUST NOT BE CONTINUOUS
ACROSS THE WALL.
3. WALLS MUST BE SEALED CONTINUOUSLY AT PERIMETER WITH ACOUSTICAL SEALANT WHERE THEY
ABUT ANOTHER ELEMENT (E.G., WALLS, COLUMNS, SLAB, CEILING DECK, OR MULLION.
4. PROVIDE SEALANT AT ALL VOIDS IN EXCESS OF 1/2" AT UNDERSIDE OF A BOTTOM TRACK INSTALLED
ON CONCRETE SLAB.
5. IF HVAC IS PLENUM RETURN SYSTEM, PROVIDE Z-DUCT ON THE SLAB-TO-SLAB WALL FOR RETURN AIR.
Z-DUCT MUST BE SIZED IN ACCORDANCE WITH THE LATEST EDITION OF ASHRAE GUIDELINES. IF RETURN AIR IS DUCTED TO THE AHU, Z-DUCT IS NOT REQUIRED, BUT MAN BARS ARE STILL REQUIRED
INSIDE DUCTWORK WHERE DUCT PASSES THROUGH WALL. Z-DUCT IS TO BE LOCATED ON THE
SECURE SIDE OF THE WALL.
6. ALL PENETRATIONS THROUGH WALL MUST BE SEALED ALL AROUND ON BOTH SIDES OF WALL WITH SEALANT TO ELIMINATE GAPS BETWEEN PENETRATION AND WALL. ALL CABLE/WIRE PENETRATIONS
MUST PENETRATE WALL WITH SLEEVE. PENETRATION SIZE MUST BE KEPT TO A MINIMUM.
7. A2 WALLS MUST BE BULLET RESISTANT ARMOR UL 752 LEVEL 3, SPSA.
8. PENETRATIONS OVER 96 SQ. IN. THROUGH WALL MUST BE PROTECTED WITH MAN BARS. IF MAN BARS
ARE PROVIDED, A 12"X12" HINGED INSPECTION PORT MUST BE PROVIDED ON THE DUCT ON THE
SECURE SIDE OF THE WALL.
WALL TYPE A3 - SECURED STORAGE
1. DRYWALL FINISH LEVEL 4 FROM SLAB TO CEILING. DRYWALL FINISH LEVEL 3 FROM CEILING TO SLAB ABOVE, BOTH SIDES. ONE (1) PRIMER COAT PLUS TWO (2) FINISH COATS FROM SLAB TO SLAB ABOVE, BOTH SIDES. JOINTS BETWEEN DRYWALL AND PLYWOOD MUST BE STAGGERED AT ALL LOCATIONS.
2. SCRIBE AND SEAL DRYWALL AND PLYWOOD TO FIT CONTOUR OF SLAB AND ALL PENETRATIONS.
GAPS, IF PRESENT, MUST BE NO GREATER THAN 1/2" AT ANY LOCATION AND MUST NOT BE
CONTINUOUS ACROSS THE WALL.
3. ON THE SECURE SIDE OF WALL, PROVIDE ONE (1) LAYER OF 5/8" PLYWOOD WITH 8'-0" L INSTALLED
VERTICALLY. SECURE PLYWOOD TO METAL FRAMING WITH APPROVED CONSTRUCTION ADHESIVE
AND STEEL #10 SELF-TAPPING SCREWS AT 12" O.C. MAXIMUM VERTICALLY AT EACH STUD AND 12" O.C.
HORIZONTALLY AT TOP AND BOTTOM TRACK. USE FIRE-RATED PLYWOOD WHERE REQUIRED BY
CODE.
4. PENETRATIONS OVER 96 SQ IN THROUGH WALL MUST BE PROTECTED WITH MAN BARS. IF MAN BARS ARE PROVIDED, A 12"X12" HINGED INSPECTION PORT MUST BE PROVIDED ON THE DUCT ON THE
SECURE SIDE OF THE WALL.
5. ALL UTILITY (POWER AND SIGNAL) DISTRIBUTION ON SECURE SIDE OF WALL WILL BE SURFACE- MOUNTED, CONTAINED IN RACEWAY, OR ADDITIONAL WALL WILL BE CONSTRUCTED USING FURRING
STRIPS AS STANDOFF FROM BASE WALL ASSEMBLY.
WALL TYPE A4 - SLAB TO SLAB
1. DRYWALL FINISH LEVEL 4, ONE (1) PRIMER COAT PLUS TWO (2) FINISH COATS FROM SLAB TO CEILING, BOTH SIDES. DRYWALL FINISH LEVEL 3 FROM CEILING TO SLAB ABOVE, BOTH SIDES.
NO PRIMER OR PAINT REQUIRED ABOVE CEILING.
EXISTING STRUCTURAL SLAB
0"
CEILING
PER RCP
NON-SECURE SIDE SECURE SIDE
FIRE SAFE NON-SHRINK
GROUT OR ACOUSTIC
SEALANT IN ALL VOIDS,
BOTH SIDES OF WALL
16 GA. METAL RUNNER TOP
AND BOTTOM, ANCHORED
WITH PAF AT 16" O.C. AND
BEDDED IN TWO (2)
CONTINUOUS BEADS OF
ACOUSTICAL SEALANT
5/8" TYPE 'X' GWB ON EACH SIDE
OF METAL STUD. WALL FINISH
PER PROJECT REQUIREMENTS
CEILING TILE PER PROJECT
REQUIREMENTS
3-5/8" 16 GA. METAL STUDS AT 16"
O.C. WITH HORIZONTAL BRACING
AS REQUIRED
3" MINERAL WOOL ACOUSTIC
MATERIAL
BASE AND FLOORING PER
PROJECT REQUIREMENTS
FIRE SAFE NON-SHRINK
GROUT OR ACOUSTIC
SEALANT IN ALL VOIDS,
BOTH SIDES OF WALL
WALL TYPE A7 - PERIMETER
1. DRYWALL FINISH LEVEL 4, SLAB TO CEILING. DRYWALL FINISH LEVEL 3 FROM CEILING TO SLAB ABOVE, BOTH SIDES. ONE (1) PRIMER COAT PLUS TWO (2) FINISH COATS FROM SLAB TO SLAB ABOVE, BOTH
SIDES. JOINTS BETWEEN DRYWALL AND PLYWOOD MUST BE STAGGERED AT ALL LOCATIONS.
2. SCRIBE AND SEAL DRYWALL AND PLYWOOD TO FIT CONTOUR OF SLAB AND ALL PENETRATIONS. GAPS, IF PRESENT, MUST BE NO GREATER THAN 1/2" AT ANY LOCATION AND MUST NOT BE CONTINUOUS
ACROSS THE WALL.
3. ON THE SECURE SIDE OF WALL, PROVIDE ONE (1) LAYER OF 5/8" PLYWOOD WITH 8'-0" L INSTALLED VERTICALLY. SECURE PLYWOOD TO METAL FRAMING WITH APPROVED CONSTRUCTION ADHESIVE AND STEEL #10 SELF-TAPPING SCREWS AT 12" O.C. MAXIMUM VERTICALLY AT EACH STUD AND 12" O.C.
HORIZONTALLY AT TOP AND BOTTOM TRACK. USE FIRE-RATED PLYWOOD WHERE REQUIRED BY CODE.
4. WALLS MUST BE SEALED CONTINUOUSLY AT PERIMETER WITH ACOUSTICAL SEALANT WHERE THEY
ABUT ANOTHER ELEMENT (E.G., WALLS, COLUMNS, SLAB, CEILING DECK, OR MULLION).
5. PROVIDE SEALANT AT ALL VOIDS IN EXCESS OF 1/2" AT UNDERSIDE OF A BOTTOM TRACK INSTALLED
ON CONCRETE SLAB.
6. IF HVAC IS PLENUM RETURN SYSTEM, PROVIDE Z-DUCT AT SLAB-TO-SLAB WALL FOR RETURN AIR.
Z-DUCT MUST BE SIZED IN ACCORDANCE WITH THE LATEST EDITION OF ASHRAE GUIDELINES. IF RETURN AIR IS DUCTED TO THE AHU, Z-DUCT IS NOT REQUIRED, BUT MAN BARS STILL ARE REQUIRED
INSIDE DUCTWORK WHERE DUCT PASSES THROUGH WALL.
7. ALL PENETRATIONS THROUGH WALL MUST BE SEALED ALL AROUND ON BOTH SIDES OF WALL WITH SEALANT TO ELIMINATE GAPS BETWEEN PENETRATION AND WALL. ALL CABLE/WIRE PENETRATIONS
MUST PENETRATE WALL WITH SLEEVE. PENETRATION SIZE MUST BE KEPT TO A MINIMUM. GAP
AROUND PENETRATION MUST NOT EXCEED 1/2".
8. PENETRATIONS OVER 96 SQ. IN. THROUGH WALL MUST BE PROTECTED WITH MAN BARS. IF MAN BARS ARE PROVIDED, A 12"X12" HINGED INSPECTION PORT MUST BE PROVIDED ON THE DUCT ON THE
SECURE SIDE OF THE WALL.
9. AT SIM CONDITION, THE EXISTING PLASTER CEILING CONTINUES ACROSS BOTH SIDES OF WALL.
EXISTING STRUCTURAL SLAB
BASE AND FLOORING PER PROJECT
REQUIREMENTS, EACH SIDE
5/8" TYPE 'X' GWB ON EACH SIDE
OF METAL STUD. WALL FINISH
PER PROJECT REQUIREMENTS
3-5/8" 25 GA. METAL STUDS AT 24"
O.C. WITH HORIZONTAL BRACING
AS REQUIRED
25 GA. METAL RUNNER,
TOP AND BOTTOM
CEILING TILE PER PROJECT
REQUIREMENTS
9'-4"
CEILING
NON-SECURE SIDE SECURE SIDE
BASE AND FLOORING PER PROJECT
REQUIREMENTS, EACH SIDE
5/8" TYPE 'X' GWB ON EACH
SIDE. WALL FINISH PER
PROJECT REQUIREMENTS
BULLET RESISTANT ARMOR,
UP TO CEILING TILE
5/8" PLYWOOD
FIRE SAFE NON-SHRINK GROUT
OR ACOUSTIC SEALANT IN ALL
VOIDS, BOTH SIDES OF WALL
3-5/8" 16 GA METAL STUDS AT 16"
O.C. WITH HORIZONTAL BRACING
AT 4'-0" O.C. MAXIMUM
3" MINERAL WOOL ACOUSTIC
MATERIAL
FIRE SAFE NON-SHRINK GROUT
OR ACOUSTIC SEALANT IN ALL
VOIDS, BOTH SIDES OF WALL
16 GA. METAL RUNNER, TOP AND
BOTTOM, ANCHORED WITH PAF
AT 16" O.C. AND BEDDED IN TWO
(2) CONTINUOUS BEADS OF
ACOUSTICAL SEALANT
BASE AND FLOORING PER PROJECT
REQUIREMENTS, EACH SIDE
5/8" TYPE 'X' GWB ON EACH
SIDE. WALL FINISH PER
PROJECT REQUIREMENTS
NON-SECURE SIDE SECURE SIDE
3-5/8" 16 GA. METAL STUDS AT 16"
O.C. WITH HORIZONTAL BRACING
AS REQUIRED
CEILING TILE PER PROJECT
REQUIREMENTS
5/8" PLYWOOD
16 GA. METAL RUNNER, TOP AND
BOTTOM, ANCHORED WITH PAF
AT 16" O.C.
CEILING TILE PER PROJECT
REQUIREMENTS
25 GA. METAL RUNNER, TOP
AND BOTTOM, ANCHORED
WITH PAF AT 32" O.C.
BASE AND FLOORING PER PROJECT
REQUIREMENTS, EACH SIDE
5/8" TYPE 'X' GWB ON EACH
SIDE. WALL FINISH PER
PROJECT REQUIREMENTS
3-5/8" 25 GA. METAL STUDS AT 24"
O.C. WITH HORIZONTAL BRACING
AS REQUIRED
12'-0"
(E) PLASTER CEILING
± A.F.F.
WALL TYPE A7a - AT EXISTING WALL
1. DRYWALL FINISH LEVEL 4, ONE (1) PRIMER COAT PLUS TWO (2) FINISH COATS FROM SLAB TO CEILING, BOTH SIDES. DRYWALL FINISH LEVEL 3 FROM CEILING TO SLAB ABOVE, BOTH SIDES.
2. SCRIBE AND SEAL PLYWOOD AND DRYWALL TO FIT CONTOUR OF SLAB AND ALL PENETRATIONS.
3. WALLS MUST BE SEALED CONTINUOUSLY AT PERIMETER WITH ACOUSTICAL SEALANT WHERE THEY
ABUT ANOTHER ELEMENT (E.G., WALLS, COLUMNS, SLAB, CEILING DECK, OR MULLION).
4. PROVIDE SEALANT AT ALL VOIDS IN EXCESS OF 1/2" AT UNDERSIDE OF A BOTTOM TRACK INSTALLED
ON CONCRETE SLAB.
5. ALL PENETRATIONS THROUGH WALL MUST BE SEALED ALL AROUND ON BOTH SIDES OF WALL WITH
SEALANT TO ELIMINATE GAPS BETWEEN PENETRATION AND WALL. ALL CABLE/WIRE PENETRATIONS
MUST PENETRATE WALL WITH SLEEVE.
CEILING TILE PER PROJECT
REQUIREMENTS
16 GA. METAL RUNNER TOP
AND BOTTOM ANCHORED
WITH PAF AT 16" O.C. AND
BEDDED IN TWO (2)
CONTINUOUS BEADS OF
ACOUSTICAL SEALANT
BASE AND FLOORING PER
PROJECT REQUIREMENTS,
EACH SIDE
5/8" TYPE 'X'. WALL FINISH PER
PROJECT REQUIREMENTS
3-5/8" 16 GA. METAL STUDS AT
16" O.C. WITH HORIZONTAL
BRACING AS REQUIRED
3" MINERAL WOOL
ACOUSTIC MATERIAL
FIRE SAFE NON-SHRINK
GROUT OR ACOUSTIC
SEALANT IN ALL VOIDS, BOTH
SIDES OF WALL
FIRE SAFE NON-SHRINK
GROUT OR ACOUSTIC
SEALANT IN ALL VOIDS,
BOTH SIDES OF WALL
EXISTING CORRIDOR WALL,
TO REMAIN
5/8" PLYWOOD TO DECK
5/8" PLYWOOD TO DECK
AT WALL TYPE 7 AND 7a UTILITIES
MUST BE SURFACE MOUNTED AT
BUILDING CORRIDORS OR ON THE
SECURE SIDE OF WALL IF THE
OPPOSITE SIDE OF WALL IS NOT
EASILY INSPECTABLE BY THE
TENANT.
WALL TYPE A7b - AT EXISTING CORRIDOR DOOR
1. DRYWALL FINISH LEVEL 4, ONE (1) PRIMER COAT PLUS TWO (2) FINISH COATS FROM SLAB TO CEILING, BOTH SIDES. DRYWALL FINISH LEVEL 3 FROM CEILING TO SLAB ABOVE, BOTH SIDES.
2. SCRIBE AND SEAL PLYWOOD AND DRYWALL TO FIT CONTOUR OF SLAB AND ALL PENETRATIONS.
3. WALLS MUST BE SEALED CONTINUOUSLY AT PERIMETER WITH ACOUSTICAL SEALANT WHERE THEY
ABUT ANOTHER ELEMENT (E.G., WALLS, COLUMNS, SLAB, CEILING DECK, OR MULLION).
4. PROVIDE SEALANT AT ALL VOIDS IN EXCESS OF 1/2" AT UNDERSIDE OF A BOTTOM TRACK INSTALLED ON
CONCRETE SLAB.
5. ALL PENETRATIONS THROUGH WALL MUST BE SEALED ALL AROUND ON BOTH SIDES OF WALL WITH
SEALANT TO ELIMINATE GAPS BETWEEN PENETRATION AND WALL. ALL CABLE/WIRE PENETRATIONS
MUST PENETRATE WALL WITH SLEEVE.
CEILING TILE PER PROJECT
REQUIREMENTS
16 GA. METAL RUNNER TOP
AND BOTTOM ANCHORED
WITH PAF AT 16" O.C. AND
BEDDED IN TWO (2)
CONTINUOUS BEADS OF
ACOUSTICAL SEALANT
BASE AND FLOORING PER
PROJECT REQUIREMENTS,
EACH SIDE
5/8" TYPE 'X'. WALL FINISH PER
PROJECT REQUIREMENTS
3-5/8" 16 GA. METAL STUDS AT
16" O.C. WITH HORIZONTAL
BRACING AS REQUIRED
3" MINERAL WOOL
ACOUSTIC MATERIAL
FIRE SAFE NON-SHRINK
GROUT OR ACOUSTIC
SEALANT IN ALL VOIDS,
BOTH SIDES OF WALL
FIRE SAFE NON-SHRINK
GROUT OR ACOUSTIC
SEALANT IN ALL VOIDS, BOTH
SIDES OF WALL
EXISTING CORRIDOR WALL,
TO REMAIN
12'-0"
(E) PLASTER CEILING
5/8" PLYWOOD TO DECK
EXISTING DOOR,
SECURED PER TENANT
REQUIREMENTS
WALL TYPE A5S - ACOUSTICAL
1. DRYWALL FINISH LEVEL 4, ONE (1) PRIMER COAT PLUS TWO (2) FINISH COATS FROM SLAB TO CEILING, BOTH SIDES. DRYWALL FINISH LEVEL 3 FROM CEILING TO SLAB ABOVE, BOTH SIDES.
2. SCRIBE AND SEAL DRYWALL TO FIT CONTOUR OF SLAB AND ALL PENETRATIONS.
3. WALLS MUST BE SEALED CONTINUOUSLY AT PERIMETER WITH ACOUSTICAL SEALANT WHERE THEY
ABUT ANOTHER ELEMENT (E.G., WALLS, COLUMNS, SLAB, CEILING DECK, OR MULLION).
4. PROVIDE SEALANT AT ALL VOIDS IN EXCESS OF 1/2" AT UNDERSIDE OF A BOTTOM TRACK INSTALLED
ON CONCRETE SLAB.
5. ALL PENETRATIONS THROUGH WALL MUST BE SEALED ALL AROUND ON BOTH SIDES OF WALL WITH
SEALANT TO ELIMINATE GAPS BETWEEN PENETRATION AND WALL. ALL CABLE/WIRE PENETRATIONS
MUST PENETRATE WALL WITH SLEEVE.
CEILING TILE PER PROJECT
REQUIREMENTS
25 GA. METAL RUNNER, TOP AND
BOTTOM, ANCHORED WITH PAF AT
32" O.C. AND BEDDED IN TWO (2)
CONTINUOUS BEADS OF ACOUSTICAL
SEALANT
BASE AND FLOORING PER
PROJECT REQUIREMENTS,
EACH SIDE
5/8" TYPE 'X' GWB ON EACH
SIDE. WALL FINISH PER
PROJECT REQUIREMENTS
3-5/8" 25 GA. METAL STUDS AT
24" O.C. WITH HORIZONTAL
BRACING AS REQUIRED
3" MINERAL WOOL
ACOUSTIC MATERIAL
FIRE SAFE NON-SHRINK
GROUT OR ACOUSTIC
SEALANT IN ALL VOIDS,
BOTH SIDES OF WALL
FIRE SAFE NON-SHRINK
GROUT OR ACOUSTIC
SEALANT IN ALL VOIDS,
BOTH SIDES OF WALL
12'-0"
(E) PLASTER CEILING
0"
CEILING
PER RCP
9'-4"
CEILING
12'-0"
(E) PLASTER CEILING
PER RCP PER RCP
± A.F.F.
CEILING TILE PER PROJECT
REQUIREMENTS
CHECKED BY
DRAWN BY
FLOOR NUMBER
SHEET TITLE
SHEET
NUMBER
SUBMISSION DATE
SUBMISSION STAGE
Model Author
PROJECT NUMBER
PROJECT
DESCRIPTION
PROJECT TITLE
BUILDING NUMBER
CITY/ST./ZIP
ADDRESS
BUILDING NAME
PRIME CONTR. NO.
PRIME ORDER NO.
CONST. CONTR.
A/E
SUB A/E
CONST. CONTR. NO.
SHEET SIZE:
DATE DRAWN:
24 X 36
S H
E E
T
ID
E N
TI
FI
C A
TI
O
N
DISCIPLINE
P R
O
JE
C T
ID
E
N
TI
FI
C
A
TI
O N
B U
IL
D
IN
G
BIM FILE NAME
C O
N T
R A
C T
O R
S R
E V
IS
IO
N B
LO
C
K G
R A
P H
IC
S
C A
LE
K
E Y
P
LA
N S
T A
M P
O R
S E
A L
D E
S
IG
N E
R
ID
E N
T
IF
IC
A
T
IO
N O
W N
E R
ID
E
N T
IF
IC
A T
IO
N
SHEET OF SHEETS
482 S Broadway - Suite 100 Denver, Colorado 80209 Telephone: 303-260-7277
UNCLASSIFIED // FOR OFFICIAL USE ONLY
PROPERTY OF THE UNITED STATES GOVERNMENT
Do not remove this notice. Properly destroy or return documents when no longer needed
TENANT IMPROVEMENT OF 2,578GSF
LEVEL 3
ARCHITECTURE
47PJ0020D0012
47PJ0025F0120
DESIGN EDGE
/2
/2
:3
:0
A
M
A6.2
WALL TYPES
GSA 3RD FLOOR TI - GRAND FORKS, ND
ISSUED FOR CONSTRUCTION
5/6/2026
3/6/2026TP
SG
23133
General Service Administration
7 49
RONALD N. DAVIES FEDERAL BUILDING
ND0008ZZ
RONALD N. DAVIES FEDERAL BUILDING
102 NORTH 4TH STREET,
GRAND FORKS, ND 58203
DESIGN EDGE
1" = 1'-0"
WALL TYPES
Mark Date Description
8/5/2025 35% Submittal
9/22/2025 65% Submittal
12/5/2025 95% Submittal
3/6/2026 100% Submittal
3/31/2026 Issued for Construction
1" FILLER 2'-4" 2'-0" 2'-4" 1'-3" 1" FILLER
PLAM UPPER CABINETS WITH
(2) ADJUSTABLE SHELVES
AND 4" ALUM. PULLS
CT-1 BACKSPLASH
PLAM BASE CABINETS
AND DRAWERS
PLAM CLAD COUNTERTOP
GWB - PAINT PT-1
MICROWAVE
TOE KICK
PAPER TOWEL DISPENSER
SOAP DISPENSER
" 1 1/2" 2"
4'-0"
2" 1 1/2"
PROVIDE LEVEL 3, SEALED
BALLISTIC TRANSACTION
WINDOW WITH LOCKABLE FLIP
TOP DEAL TRAY, AND
COUNTER MOUNTED TWO-
WAY COMMUNICATION
DEVICE. PROVIDE APRON
BELOW COUNTER ON SECURE
SIDE TO MAKE COUNTER
PROJECTION CONFORM TO
ADA REQUIREMENTS
A6.3
BULLET RESISTANT
WALL PER WALL TYPE
THREE SIDED STAINLESS
STEEL FRAME WITH
NEOPRENE SETTING
BLOCKS AT GLAZING 1X1
GLAZING STOP
SECURE SIDE
UL LISTED BULLET
RESISTANT GLAZING
PER SPECIFICATION
PLASTIC LAMINATE
COUNTERTOP WITH
ARMORTEX DIP TRAY
RMDT 1416
ARMORTEX RMDT 1416
DIP TRAY WITH HAVEN
SC300 SPEAKERS
NOTE:
THE BULLET RESISTANCE
RATING OF THE ACCOMPANYING
FRAME, COUNTER AND
ASSOCIATED ACCESSORIES
SHALL BE EQUAL TO OR BETTER
THAN THE GLAZING
BULLET RESISTANT
FIBERGLASS COMPOSITE
6"x36"x3/16" BACKPLATE
BOLTED OR WELDED TO
DOUBLE STUDS
DOUBLE 16 GA. STEEL
STUDS BOLTED OR TACK
WELDED TOGETHER AND
DIAGONALLY BRACED TO
DECK ABOVE
6"x36"x3/16" EXPOSED
STAINLESS FACEPLATE
3-1/4" DIA BOLTS
COUNTERSUNK WITH
TAMPER PROOF HEADS
PER FLANGE APPLIED
BEFORE DRYWALL ON
OPPOSITE SIDE
2'-0"
DOUBLE 16 GA. STEEL
STUDS AT 12" O.C.
6"x36"x3/16" ANCHOR
PLATES. EXPOSED
STAINLESS FACEPLATE
24" L x 1-1/2" DIA STAINLESS
GRAB BAR. FIELD VERIFY
WITH OWNER FOR EXACT
LOCATION PRIOR TO
INSTALLATION
HANDCUFF BAR TO BE
PROVIDED AND
INSTALLED BY GC
A6.3
EXISTING EXTERIOR
MASONRY WALL
CONSTRUCTION
REMOVE EXISTING
GYPSUM AND FURRING AT
WALL INTERSECTION TO
EXPOSE EXTERIOR WALL.
EXTEND NEW PARTITION
CONSTRUCTION TO
EXTERIOR MASONRY WALL
NEW INTERIOR WALL
CONSTRUCTION PER WALL
TYPE
DRYWALL J-MOLD
AT GWB EDGE
WALL PER WALL TYPE
(E) WINDOW SYSTEM
TOILET ACCESSORY SCHEDULE
DESCRIPTION: MANUFACTURER: MODEL NO. PROVIDED BY / INSTALLED BY: QUANTITY: NOTES:
TOILET TISSUE DISPENSER BOBRICK B-4388 CONTRACTOR / CONTRACTOR 1
PAPER TOWEL DISPENSER BOBRICK B-369 CONTRACTOR / CONTRACTOR
AND WASTE DISPOSAL
PAPER TOWEL DISPENSER BOBRICK B-26212 CONTRACTOR / CONTRACTOR 1 SURFACE MOUNTED
SANITARY NAPKIN DISPOSAL BOBRICK B-35303 CONTRACTOR / CONTRACTOR 1