M1177147 - Ronald Davies Asbestos and LBP Survey-Final.pdf
PDF 2 MB Posted
- Attached to
- RFP 47PD5326R0046 EQPXAGC-26-0014 Grand Forks Office Buildout Federal contract opportunity
- Solicitation number
- 47PD5326R0046
- Issued by
- Not on record
About this file
This is a limited asbestos and lead-based paint survey report for the Ronald N. Davies Federal Building and U.S. Courthouse located at 102 North 4th Street, Grand Forks, North Dakota 58203. The survey was conducted by Terracon Consultants, Inc. on January 19, 2018 (asbestos) and January 22, 2018 (lead-based paint), with the report issued February 9, 2018. The client-defined survey area comprised approximately 9,000 square feet on the third floor. The building is a three-story structure originally completed in 1906 with a major renovation in 1964, currently utilized as offices and courthouses with plaster and gypsum wallboard walls, carpet tiles and floor tile, and drop-in ceilings.
The survey identified asbestos-containing materials (ACM) requiring remediation prior to renovation or demolition activities. Specifically, three homogeneous areas (HAs) were determined to contain asbestos: 9" x 9" white floor tile (1,732 square feet, 2.1% chrysotile, Category I classification); white joint compound (260 joints, 9.2% chrysotile, RACM classification); and gypsum with joint compound composite (1,900 square feet, 2.0% chrysotile, RACM classification). All regulated asbestos-containing materials (RACM) must be removed by a North Dakota licensed abatement contractor prior to demolition activities in compliance with federal, state, and local regulations. Lead-based paint screening identified three components containing lead: tan/green/white paint on gypsum wallboard above the chair rail (8.0% by weight); tan/white/green paint on cement board above drop ceiling (4.9% by weight); and white/white/grey paint on cement board below the chair rail (12% by weight). The report recommends that contractors be notified of lead presence and prepare a detailed lead management plan per OSHA standards, with all waste requiring characterization for proper disposal.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Unsuccessful Letter_47PD5326R0046 EQPXAGC-26-0014 Grand Forks Office Buildout.pdf | ||
| Amendment 47PD5326R0046_0002 signed.pdf | ||
| Amendment 47PD5326R0046_0002 signed.pdf | ||
| Amendment 47PD5326R0046_0001.pdf | ||
| FO SB Agreement RFP 47PD5326R0046.pdf | ||
| RND Grand Forks ND 3rd Floor TI- Final specifications.pdf | ||
| FO SB Solicitation RFP 47PD5326R0046.pdf | ||
| RFP 47PD5326R0046 Form 1442.pdf | ||
| RND Grand Forks ND 3rd Floor TI - Bid Set.pdf | ||
| Vendor Fitness Determination Training Manual.pdf | ||
| GSA527 Contractors Qualifications and Financial Information.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Limited Asbestos and Lead-Based
Paint Survey
Ronald N. Davies Federal Building and U.S. Courthouse
102 North 4th Street
Grand Forks, North Dakota 58203
February 9, 2018
Terracon Project No. M1177147
Prepared for:
Design Edge, PC
Colorado Springs, Colorado
Prepared by:
Terracon Consultants, Inc.
West Fargo, North Dakota
Terracon Consultants, Inc. 860 9th St. NE Unit K West Fargo, ND 58078
P 701-282-9633 F 701-282-9635 terracon.com
February 9, 2018
Design Edge, PC
711 North Cascade Avenue, Suite 100
Colorado Springs, Colorado 80903
Attn: Ms. Swagata Guha
E: swagata@de-arch.com
Re: Limited (Renovation-Specific) Asbestos and Lead-Based Paint Survey
102 North 4th Street
Grand Forks, North Dakota 58203
Terracon Project No. M1177147
Dear Ms. Guha:
Terracon Consultants, Inc. (Terracon) is pleased to submit the attached report for the above-referenced site to Design Edge, PC. The purpose of this report is to present the results of a limited
(renovation-specific) asbestos and lead-based paint survey performed on January 19, 2018 and
January 22, 2018, respectively. The surveys were conducted in general accordance with Terracon
Proposal No. PM1177147 dated November 14, 2017. We understand that these surveys were requested to identify and locate asbestos-containing materials (ACM) and lead-based paint (LBP) in the client defined survey area, which is scheduled for renovation. We further understand that the client defined survey area did not include building corridors, the building exterior, attic spaces above the offices, or the building roof.
Terracon appreciates the opportunity to provide this service to Design Edge, PC. If you have any questions regarding this report please contact the undersigned at 701-282-9633.
Sincerely, Terracon Consultants, Inc.
Rhonda L. Olson Kevin M. Troyer
Staff Geologist Senior Industrial Hygienist mailto:swagata@de-arch.com
TABLE OF CONTENTS
1.0 INTRODUCTION
1.1 Project Objective
1.2 Reliance
2.0 BUILDING DESCRIPTION
3.0 FIELD ACTIVITIES
3.1 Asbestos Survey
3.1.1 Visual Assessment
3.1.2 Physical Assessment
3.1.3 Sample Collection
3.2 Painted Surface Coating Assessment
3.3 Sample Analysis
4.0 REGULATORY OVERVIEW
4.1 Asbestos
4.2 Lead-Based Paint (LBP)
5.0 FINDINGS AND RECOMMENDATIONS
5.1 Asbestos Survey
5.2 Painted Surface Findings
6.0 LIMITATIONS/GENERAL COMMENTS
APPENDIX A IDENTIFIED ASBESTOS-CONTAINING MATERIALS BY HOMOGENEOUS AREA (HA)
APPENDIX B ASBESTOS SURVEY SAMPLE LOCATION SUMMARY
APPENDIX C IDENTIFIED LEAD-BASED PAINT LOCATIONS
APPENDIX D INDENTIFIED LEAD-BASED PAINT SCREENING SAMPLE LOCATION SUMMARY
APPENDIX E ANALYTICAL LABORATORY DATA
APPENDIX F LICENSES AND CERTIFICATIONS
APPENDIX G SAMPLE LOCATION DRAWING
Responsive ■ Resourceful ■ Reliable 1
LIMITED ASBESTOS AND LEAD-BASED PAINT SURVEY
Ronald N. Davies Federal Building and U.S. Courthouse
102 North 4th Street
Grand Forks, North Dakota 58203 Terracon Project No. M1177147
February 9, 2018
1.0 INTRODUCTION
Terracon conducted a limited (renovation-specific) asbestos and lead-based paint survey for
Design Edge, PC of the Ronald N. Davies Federal Building and U.S. Courthouse at 102 North 4th
Street, Grand Forks, North Dakota.
The limited asbestos survey was conducted on January 19, 2018, by AHERA1 accredited and
State of North Dakota certified asbestos and lead-based paint inspectors in general accordance with Terracon Proposal No. PM1177147 dated November 14, 2017.
Interior building components were surveyed and homogeneous areas2 (HA) of suspect asbestos-containing materials (ACM) were visually identified and documented. Although reasonable effort was made to survey accessible suspect materials, additional suspect but unsampled materials could be located in walls, in voids, or in other concealed areas. Suspect ACM samples were collected in general accordance with the sampling protocols outlined in United States
Environmental Protection Agency (USEPA) 40 Code of Federal Regulations (CFR) 763.86, Sampling. Samples were delivered to an accredited laboratory for analysis by polarized light microscopy (PLM).
Paint samples were collected from accessible painted surfaces. The paint samples were submitted to an accredited laboratory for analysis of lead by USEPA method 6010C.
1.1 Project Objective
We understand that the project services were requested due to planned renovation of the building.
USEPA regulation 40 CFR 61-National Emission Standards for Hazardous Air Pollutants
(NESHAP), Subpart M-National Emission Standard for Asbestos, prohibits the release of asbestos fibers to the atmosphere during demolition or renovation activities. The asbestos NESHAP requires that potentially regulated asbestos-containing building materials be identified, classified, and quantified prior to planned disturbances.
1 AHERA = Asbestos Hazard Emergency Response Act 2 A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color and texture with consideration given to the date of application.
Limited Asbestos and Lead-Based Paint Survey
Ronald N. Davies Federal Building and U.S. Courthouse ■ Grand Forks, ND
February 9, 2018 ■ Terracon Project No. M1177147
Responsive ■ Resourceful ■ Reliable 2
Paint sampling was completed to identify lead containing paints on painted components so that proper worker protection, environmental protection, and disposal can be completed.
1.2 Reliance
This report is for the exclusive use of Design Edge, PC for the project being discussed. Reliance by any other party on this report is prohibited without written authorization of Terracon and Design
Edge, PC. Reliance on this report by Design Edge, PC and all authorized parties will be subject to the terms, conditions, and limitations stated in the proposal, this report, and Terracon’s
Agreement for Services. The limitations of liability defined in Terracon’s Agreement for Services is the aggregate limit of Terracon’s liability to Design Edge, PC.
2.0 BUILDING DESCRIPTION
Terracon understands the subject building consists of a three-story structure originally completed in 1906, with a large renovation in 1964. The building is currently utilized as offices and courthouses.
The client-defined survey area is approximately 9,000 square-feet (sf) located on the third floor.
Interior walls are primarily plaster and gypsum wallboard (GWB). Flooring consists of carpet tiles and floor tile. Ceilings consist of plaster and drop-in ceilings with interlocking, steel, and/or acoustical ceiling tiles. Ducting connected to air handling units in the plenum space above the drop ceiling are covered in insulation.
3.0 FIELD ACTIVITIES
3.1 Asbestos Survey
The survey was conducted by Mr. Leif Schonteich and Ms. Rhonda Olson, AHERA accredited
North Dakota Department of Health (NDDH) licensed asbestos inspectors. Copies of Mr.
Schonteich’s and Ms. Olson’s asbestos inspector certifications are attached as Appendix D. The survey was conducted in general accordance with the sample collection protocols established in
USEPA 40 CFR 763.86, Sampling. A summary of survey activities is provided in the following subsections.
3.1.1 Visual Assessment
Survey activities were initiated with visual observation of the interior and exterior of the building to identify homogeneous areas of suspect ACM. A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color and texture with consideration given to the date of application. Interior assessment was conducted in visually accessible areas of the
Responsive ■ Resourceful ■ Reliable 3 building proposed for demolition. It should be noted that additional suspect but unsampled materials could be located inside walls, voids, or other concealed areas.
Terracon typically investigated for flooring beneath carpeting by lifting small corner sections of carpet. If tiles were seen, they have been identified in the report. If tiles were not seen at corners under the carpet, it does not imply that there are no tiles beneath the carpets. Terracon sampled accessible flooring materials but did not conduct destructive investigation on floors to identify multi-layered tile/underlayment systems, concealed paper, vapor barriers, or floor tiles/mastics under wood floor systems due to the historical nature of the building.
3.1.2 Physical Assessment
A physical assessment of each HA of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the USEPA as a material which can be crumbled, pulverized or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.
3.1.3 Sample Collection
Based on results of the visual observation, bulk samples of suspect ACM were collected in general accordance with USEPA sampling protocols. Samples of suspect materials were collected from randomly selected locations in each homogeneous area. Bulk samples were collected using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content. Terracon collected 39 bulk samples from 11 HAs. A summary of suspect ACM samples collected during the survey is included as Appendix B. A sample location drawing is included as
Appendix E.
Terracon did not identify HAs assumed as ACM materials. Wood flooring was identified beneath layers of carpet, tile, and mastic. Terracon did not identify additional layers beneath the wood flooring in the areas accessible for inspection.
3.2 Painted Surface Coating Assessment
Terracon collected paint chip samples from painted components utilizing a chisel and sample bags. Terracon collected paint chip samples from the walls, chair rails, plaster ceiling, heat registers, door frames, and window frames and sills. A summary of paint types/colors sampled and locations where samples were collected during the survey are included as Appendix C and
D, respectively.
Responsive ■ Resourceful ■ Reliable 4
3.3 Sample Analysis
Bulk samples were submitted under chain of custody to International Asbestos Testing
Laboratories (IATL) of Mt. Laurel, New Jersey for analysis by PLM with dispersion staining techniques per USEPA’s Method for the Determination of Asbestos in Bulk Building Materials
(600/R-93/116). The percentage of asbestos, if present, was determined by microscopic visual estimation. IATL is accredited under the National Voluntary Laboratory Accreditation Program
(NVLAP) Accreditation No. 101165-0.
The paint chip samples were submitted under chain of custody to International Asbestos Testing
Laboratories (IATL) of Mt. Laurel, New Jersey for analysis of lead by USEPA method 6010C on a 5-day turnaround time (TAT). IATL is accredited under the American Industrial Hygiene
Association (AIHA) Laboratory Accreditation Program (AIHA-LAP) (ID No. 100188) which is recognized by the National Lead Laboratory Accreditation Program.
4.0 REGULATORY OVERVIEW
4.1 Asbestos
The North Dakota Division of Air Quality under the NDDH enforces the asbestos NESHAP as adopted by reference in North Dakota Administrative Code Chapter 33-15-13. The owner or operator must provide NDDH with written notification at least 10 working days prior to the commencement of asbestos abatement activities that will disturb regulated ACM (RACM) in amounts greater than or equal to 160 square feet, 260 linear feet, or 35 cubic feet.
The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized or reduced to powder by hand pressure. All friable ACM is considered
RACM.
The asbestos NESHAP regulation classifies ACM as RACM, Category I nonfriable ACM, or
Category II nonfriable ACM. RACM includes all friable ACM, along with Category I and Category
II nonfriable ACMs that have become friable; will be or have been subjected to sanding, grinding, cutting or abrading; or that have a high probability of becoming or have become crumbled, pulverized, or reduced to powder in the course of renovation or demolition activity. Category I nonfriable ACMs are exclusively asbestos-containing packings, gaskets, resilient floor coverings, resilient floor covering mastics, and asphalt roofing products that contain more than 1% asbestos.
Category II nonfriable ACMs are all other nonfriable materials other than Category I nonfriable
Responsive ■ Resourceful ■ Reliable 5
ACMs that contain more than 1% asbestos. Category II nonfriable ACMs generally include but are not limited to cementitious material such as cement pipes, cement siding, cement panels, glazing, mortar, and grouts.
The Occupational Safety and Health Administration (OSHA) asbestos standard for construction
(29 CFR 1926.1101) regulates workplace exposure to asbestos. The OSHA standard requires that employee exposure to airborne asbestos fibers be maintained below the permissible exposure limits (PELs) of 0.1 asbestos fiber per cubic centimeter of air (0.1 f/cc) as an 8-hour time-weighted average (TWA) or 1.0 f/cc as a 30-minute excursion limit. The OSHA standard classifies construction and maintenance activities that could disturb ACM and specifies work practices and precautions that employers must follow when engaging in each class of regulated work.
4.2 Lead-Based Paint (LBP)
Lead is regulated by the USEPA and OSHA. USEPA regulates lead use, removal, and disposal, and OSHA regulates worker exposure to lead. USEPA defines LBP as paint, varnish, stain or other applied coating that contains lead equal to or greater than 1.0 milligram per square centimeter (mg/cm2), 5,000 milligrams per kilogram (mg/kg), or 0.5% by dry weight as determined by laboratory analysis. For the purpose of the OSHA lead standard, lead includes metallic lead, all inorganic lead compounds, and organic lead soaps. The OSHA standard does not define the amount of lead in paint that constitutes lead-containing paint.
USEPA regulates disposal of hazardous materials. The USEPA has stated that components removed with intact LBP that is not delaminating from the substrate may be disposed as general demolition debris. If the LBP is stripped from components, or if it is delaminating from the substrate, the waste may be subject to hazardous waste rules [i.e., Toxicity Characteristics Leaching
Procedure (TCLP)].
USEPA issued the Renovation, Repair, and Painting (RRP) rule (40 CFR Part 745) requiring the use of lead-safe practices and other actions aimed at preventing lead poisoning. Under the rule, beginning in April 2010, contractors performing renovation, repair, and painting projects that disturb
LBP in homes, childcare facilities, and schools built before 1978 must be certified and must follow specific work practices to prevent lead contamination. The NDDH has adopted similar regulations.
The OSHA Lead Standard for Construction (29 CFR 1926.62) applies to all construction work where an employee may be occupationally exposed to lead. All work related to construction, alteration or repair (including painting and decorating) is included. The lead-in-construction standard applies to any detectable concentration of lead in paint, as even small concentrations of lead can result in unacceptable employee exposures depending upon on the method of removal and other workplace conditions. Under this standard, construction includes, but is not limited to, the following:
Responsive ■ Resourceful ■ Reliable 6
Demolition or salvage of structures where lead or materials containing lead are present
Removal or encapsulation of materials containing lead
New construction, alteration, repair, or renovation of structures, substrates, or portions containing lead, or materials containing lead
Installation of products containing lead
Lead contamination/emergency clean-up
Transportation, disposal, storage, or containment of lead or materials containing lead on the site or location at which construction activities are performed
Maintenance operations associated with construction activities described above
Employers must assure that no employee will be exposed to lead at concentrations greater than the PEL of 50 micrograms per cubic meter (g/m3) averaged over an eight-hour period without adequate protection. The OSHA standard also establishes an action level of 30 g/m3, which if exceeded, triggers certain requirements, including periodic exposure monitoring and medical monitoring.
5.0 FINDINGS AND RECOMMENDATIONS
5.1 Asbestos Survey
The following ACMs were identified as a result of laboratory analysis or assumed asbestos-containing:
Material Description Material Location
NESHAP
Classification
Estimated
Quantity3
9" x 9" white floor tile 318, 320, 322, 322A, 322B, 324, 324B Category I 1,750 SF
White joint compound 322, 322B, 324, 324A, 324B, 324C, 328, 330, 330A, 330B RACM 260 Joints
Gypsum with joint compound composite
322, 322B, 324, 324A, 324B, 324C, 328, 330, 330A, 330B
RACM 1900 SF
The above listed RACM must be removed by a state of North Dakota licensed abatement contractor prior to any demolition activities that may disturb these materials in accordance with applicable federal, state, and local regulations.
The above listed Category I and Category II nonfriable ACMs that are damaged or could be damaged to the extent that they could be crumbled, pulverized or reduced to powder when dry, 3 Estimated quantities are based on a cursory field evaluation, and actual quantities may vary significantly, especially if ACMs are present in hidden and/or inaccessible areas not evaluated as part of this survey. SF = square feet, LF = linear feet
Responsive ■ Resourceful ■ Reliable 7 making it friable, must be removed in accordance with applicable federal, state, and local regulations prior to any activities (renovation and/or demolition) that may disturb these materials.
Intentionally running over Category I and Category II nonfriable ACMs with tracked vehicles as a means of segregation or compaction, is considered grinding the material, making then friable
RACM and subject to the asbestos NESHAP.
USEPA states that waste consolidation efforts that involve the use of jack hammers or other mechanical devices such as grinders to break up asbestos-containing concrete or other materials covered or coated with Category I nonfriable ACM, are subject to the regulation. If such materials adhering to the concrete are removed before waste consolidation, the waste consolidation is not subject to NESHAP. USEPA’s interpretation is that when manual methods such as axes, hatchets, knives, spud bars, pry bars, and shovels, but not saws or methods that slice, shear, or punch such as a power slicer or power plow to remove roofing materials, are used, assuming the roof material is not friable, that the removal operation is not subject to the asbestos NEHSAP regulation.
Summaries of the classification, condition, and approximate quantity of identified and assumed
ACMs are presented in Appendix A. The summary of sample locations is presented in Appendix B.
Laboratory analytical reports are included in Appendix C.
Terracon can provide Design Edge, PC with a proposal for developing asbestos abatement specifications (project design) and for performing abatement oversight and air monitoring upon request.
5.2 Limited Lead-Based Paint Screening
The painting history of any given location often will vary from point to point due to many factors including variability in paints used, paint film thickness, variable retention of older paint layers before repainting, demolition/installation of walls during renovations, and unknown historic non-homogenous painting schemes. As such, a given color and building component combination that is currently apparent often will not provide consistent testing results for lead.
Terracon attempted to perform lead paint testing in sufficient quantity to establish trends in lead content based on distinguishable characteristics such as color or building component, subject to time and budget constraints. Based on the testing results presented in Appendix E, in Terracon’s opinion the following components are known to contain lead:
Tan/Green/White on gypsum wallboard above the chair rail.
Tan/White/Green on plaster above drop ceiling.
White/White/Grey on plaster below the chair rail.
Responsive ■ Resourceful ■ Reliable 8
The above list is not intended to be an all-inclusive list of all locations where LBP is present throughout the building. Terracon recommends that the contractor(s) involved in the stripping operation be notified of the presence of lead on painted components. OSHA’s lead standards for construction (29 CFR 1926.62) apply regardless of the concentrations and contractor(s) will need to provide appropriate personal protective equipment and conduct personal exposure monitoring, at a minimum. Terracon recommends the contractor(s) review the specified work tasks and methods involved in the demolition process and prepare a detailed lead management plan. The management plan should identify the work procedures and health and safety measures to be used in the lead material removal. It should also be noted that any wastes derived during renovation/demolition activities that contain paints known to contain lead must be characterized for proper waste disposal.
6.0 LIMITATIONS/GENERAL COMMENTS
Terracon did not perform sampling which required demolition or destructive activities such as knocking holes in walls, dismantling of equipment or removal of protective coverings. Reasonable efforts to access suspect materials within known areas of restricted access (e.g., crawl spaces) were made; however, confined spaces or areas which may pose a health or safety risk to Terracon personnel were not sampled. Sampling did not include suspect materials which could not be safely reached with available ladders/man-lifts.
This asbestos survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our survey of the building. The information contained in this report is relevant to the date on which this survey was performed, and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by Design Edge, PC for specific application to their project as discussed.
This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories, or other third parties supplying information which may have been used in the preparation of this report. No warranty, express or implied is made.
It should be understood that our services may not have identified all ACMs present in inaccessible areas of the buildings. Additional assessment of hidden areas may be necessary during demolition/renovation activities in the event that suspect materials are uncovered.
Responsive ■ Resourceful ■ Reliable A-1
APPENDIX A
Limited Asbestos Survey
Grand Forks, North Dakota
IDENTIFIED ASBESTOS-CONTAINING MATERIALS BY HOMOGENEOUS AREA (HA)
The materials listed in this table have been sampled and determined to contain asbestos in concentrations greater than 1%. When disturbed, various federal, state, and local regulations may apply. Removal may be necessary before renovations and in most cases before a demolition. See Appendix
B for a summary of samples collected. See Appendix C for detailed analytical results.
HA
No.
Material Description Material Location
% and Type
Asbestos1
NESHAP
Classification Condition
Estimated
Quantity2
3 9" x 9" white floor tile 318, 320, 322, 322A, 322B, 324, 324B PC3 2.1% Chrysotile Category I Good 1732 SF
15 White joint compound
322, 322B, 324, 324A, 324B, 324C, 328, 330, 330A, 330B
PC 9.2% Chrysotile RACM Good 260 Joints
Gypsum with joint compound composite
322, 322B, 324, 324A, 324B, 324C, 328, 330, 330A, 330B
PC 2.0% Chrysotile RACM Good 1900 SF
1 % & Type Asbestos - this column contains both the analytical result of the sample with the highest concentration of asbestos detected in the samples that make up the HA and the types of asbestos identified.
2 Estimated quantities are based on a cursory field evaluation, and actual quantities may vary significantly, especially if ACMs are present in hidden and/or inaccessible areas not evaluated as part of this survey. SF = square feet, LF = linear feet 3 Point count
Responsive ■ Resourceful ■ Reliable B-1
APPENDIX B
Limited Asbestos Survey
ASBESTOS SURVEY SAMPLE LOCATION SUMMARY
No.
Material Description
Sample
Number Sample Location Lab Results
1 Grey floor tile 1-FT2-01 Doorway of Room 324C None detected
1 Yellow mastic 1-FT2-01 Doorway of Room 324C None detected
1 Brown mastic 1-FT2-01 Doorway of Room 324C None detected
1 Grey floor tile 1-FT2-02 Doorway of Room 324C None detected
1 Yellow mastic 1-FT2-02 Doorway of Room 324C None detected
1 Brown mastic 1-FT2-02 Doorway of Room 324C None detected
1 Grey floor tile 1-FT2-03 Doorway of Room 324A None detected
1 Yellow mastic 1-FT2-03 Doorway of Room 324A None detected
1 Brown mastic 1-FT2-03 Doorway of Room 324A None detected
2 Green mastic 2-MG6-04 East Wall of Room 328 None detected
2 Grey mastic 2-MG6-04 East Wall of Room 328 None detected
2 Green mastic 2-MG6-05 SW corner of Room 328 None detected
2 Grey mastic 2-MG6-05 SW corner of Room 328 None detected
2 Green mastic 2-MG6-06 N doorway of Room 328 None detected
3 White floor tile 3-FT3-07 SE corner of Room 322 PC 2.1% Chrysotile
3 Yellow mastic 3-FT3-07 SE corner of Room 322 None detected
3 White mastic 3-FT3-07 SE corner of Room 322 None detected
3 Black mastic 3-FT3-07 SE corner of Room 322 None detected
3 Light brown floor tile 3-FT3-08 SE corner of Room 322B None detected
3 White mastic 3-FT3-08 SE corner of Room 322B None detected
3 Yellow mastic 3-FT3-08 SE corner of Room 322B None detected
3 Black mastic 3-FT3-08 SE corner of Room 322B None detected
Ronald N. Davies Federal Building and U.S. Courthouse ■ Grand Forks, North Dakota
Responsive ■ Resourceful ■ Reliable B-2
No.
Material Description
Sample
Number Sample Location Lab Results
3 Grey floor tile 3-FT3-09 SE corner of Room 320 PC 0.25% Chrysotile
3 Yellow mastic 3-FT3-09 SE corner of Room 320 None detected
3 Black mastic 3-FT3-09 SE corner of Room 320 None detected
4 Light brown mastic 4-MG5-10 SE corner of Room 330A None detected
4 Red carpet 4-MG5-10 SE corner of Room 330A None detected
4 Light brown mastic 4-MG5-11 NE corner of Room 330B None detected
4 Light brown mastic 4-MG5-12 SW corner of Room 330 None detected
4 Dark yellow mastic 4-MG5-12 SW corner of Room 330 None detected
4 Brown mastic 4-MG5-12 SW corner of Room 330 None detected
5 Red cove base 5-FC3-13 N wall of Room 330A None detected
5 White joint compound 5-FC3-13 N wall of Room 330A None detected
5 Brown mastic 5-FC3-13 N wall of Room 330A None detected
5 Dark yellow mastic 5-FC3-13 N wall of Room 330A None detected
5 Red cove base 5-FC3-14 SE corner of Room 330B None detected
5 White joint compound 5-FC3-14 SE corner of Room 330B None detected
5 Brown mastic 5-FC3-14 SE corner of Room 330B None detected
5 Red cove base 5-FC3-15 N wall of Room 330B None detected
5 Yellow mastic 5-FC3-15 N wall of Room 330B None detected
6 Grey cove base 6-FC3-16 NW corner of Room 324A None detected
6 Yellow mastic 6-FC3-16 NW corner of Room 324A None detected
6 Grey cove base 6-FC3-17 NW corner of Room 324C None detected
6 Yellow mastic 6-FC3-17 NW corner of Room 324C None detected
6 Grey cove base 6-FC3-18 SW corner of Room 324A None detected
6 Yellow mastic 6-FC3-18 SW corner of Room 324A None detected
6 Brown mastic 6-FC3-18 SW corner of Room 324A None detected
6 White leveling compound 6-FC3-18 SW corner of Room 324A None detected
7 Red cove base 7-FC3-19 Room 324 None detected
7 Light yellow mastic 7-FC3-19 Room 324 None detected
7 Dark yellow mastic 7-FC3-19 Room 324 None detected
7 Red cove base 7-FC3-20 Room 324 None detected
7 Light yellow/dark yellow mastic 7-FC3-20 Room 324 None detected
7 Red cove base 7-FC3-21 Room 324 None detected
7 Light yellow/dark yellow mastic 7-FC3-21 Room 324 None detected
Responsive ■ Resourceful ■ Reliable B-3
No.
Material Description
Sample
Number Sample Location Lab Results
7 Brown mastic 7-FC3-21 Room 324 None detected
8 Light brown cove base 8-FC3-22 Room 324B None detected
8 Brown mastic 8-FC3-22 Room 324B None detected
8 Yellow mastic 8-FC3-22 Room 324B None detected
8 Light brown cove base 8-FC3-23 Room 324B None detected
8 Brown mastic 8-FC3-23 Room 324B None detected
8 Yellow mastic 8-FC3-23 Room 324B None detected
8 Light brown cove base 8-FC3-24 Room 324B None detected
8 Brown mastic 8-FC3-24 Room 324B None detected
8 Yellow mastic 8-FC3-24 Room 324B None detected
8 White mastic 8-FC3-24 Room 324B None detected
9 Beige ceiling tile 9-CT4-25 Room 324 None detected
9 Beige ceiling tile 9-CT4-26 Room 328 None detected
9 Beige ceiling tile 9-CT4-27 Room 330 None detected
10 Off-white drywall 10-WB1-28 Room 330 None detected
10 White joint compound 10-WB1-28 Room 330 None detected
10 Composite 10-WB1-28 Room 330 None detected
10 White woven material 10-WB1-28 Room 330 None detected
10 Off-white drywall 10-WB1-29 Room 330 None detected
10 White joint compound 10-WB1-29 Room 330 None detected
10 Composite 10-WB1-29 Room 330 None detected
10 White woven material 10-WB1-29 Room 330 None detected
10 Off-white drywall 10-WB1-30 Room 328 None detected
10 White joint compound 10-WB1-30 Room 328 None detected
10 Composite 10-WB1-30 Room 328 None detected
10 Off-white drywall 10-WB1-31 Room 324 None detected
10 Off-white drywall 10-WB1-32 Room 324A None detected
10 White joint compound 10-WB1-32 Room 324A PC 9.2% Chrysotile
10 Composite 10-WB1-32 Room 324A PC 2.0% Chrysotile
11 Beige plaster 11-HP2-33 Room 330 ceiling None detected
11 White plaster 11-HP2-33 Room 330 ceiling None detected
11 Beige plaster 11-HP2-34 Room 330 wall None detected
11 White plaster 11-HP2-34 Room 330 wall None detected
Responsive ■ Resourceful ■ Reliable B-4
No.
Material Description
Sample
Number Sample Location Lab Results
11 Beige plaster 11-HP2-35 Room 328 wall None detected
11 White plaster 11-HP2-35 Room 328 wall None detected
11 Beige plaster 11-HP2-36 Room 324 wall None detected
11 White plaster 11-HP2-36 Room 324 wall None detected
11 Beige plaster 11-HP2-37 Room 324 ceiling None detected
11 White plaster 11-HP2-37 Room 324 ceiling None detected
11 Beige plaster 11-HP2-38 Room 320 wall None detected
11 White plaster 11-HP2-38 Room 320 wall None detected
11 Beige plaster 11-HP2-39 Room 320 ceiling None detected
11 White plaster 11-HP2-39 Room 320 ceiling None detected
Responsive ■ Resourceful ■ Reliable C-1
APPENDIX C
Limited Lead-Based Paint Screening
IDENTIFIED LEAD-BASED PAINT LOCATIONS
Paint Color Location Substrate Analytical Result
(% by weight)
Tan/green/ white Upper wall (above chair rail) GWB 8.0
Tan/white Upper wall/ceiling above drop ceiling Cement board 4.9
White/white
/grey Lower wall (below chair rail) Cement board 12
GWB = gypsum wall board
Responsive ■ Resourceful ■ Reliable D-1
APPENDIX D
Limited Lead-Based Paint Screening
LEAD-BASED PAINT SCREENING SAMPLE LOCATION SUMMARY
Room Color Substrate Condition Lead Content1 Notes
1 Tan/green/white GWB Intact 8.0 Upper wall (above chair rail)
2 Tan/white/green Wood Intact 0.10 Chair rail
3 Tan/white Cement board Intact 4.9 Upper wall/ceiling above drop ceiling
4 White/white Metal Intact 0.0059 Heat registers
5 White/white/grey Cement board Poor 12 Lower wall (below chair rail)
6 Brown/tan/green Wood Intact 0.33 Door frames
7 Tan/green Wood Intact 0.18 Window frames/sills
GWB = gypsum wall board 1 = Percent by weight
APPENDIX E
ANALYTICAL LABORATORY DATA
Lab No.: 6429597 Client No.: 1-FT2-01
Analyst Observation: Grey Floor Tile Client Description: 12x12 Grey Floor Tile
Location: Doorway Of Room 324C Facility:
Percent Asbestos:
None Detected
Percent Non-Asbestos Fibrous Material:
Percent Non-Fibrous Material:
Lab No.: 6429597(L2)
Analyst Observation: Yellow Mastic
Lab No.: 6429597(L3)
Analyst Observation: Brown Mastic
8 Cellulose 3 Synthetic
Lab No.: 6429598 Client No.: 1-FT2-02
Lab No.: 6429598(L2)
5 Cellulose
Lab No.: 6429598(L3)
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Rev #2, 1/30/2018
Dated : 1/30/2018 4:54:24 Page 1 of 20
Lab No.: 6429599 Client No.: 1-FT2-03
Location: Doorway Of Room 324A
Lab No.: 6429599(L2)
Lab No.: 6429599(L3)
Lab No.: 6429600 Client No.: 2-MG6-04
Analyst Observation: Green Mastic Client Description: Green Carpet Glue
Location: East Wall Of Room 328
Lab No.: 6429600(L2) Client No.: 2-MG6-04
Analyst Observation: Grey Mastic
Location: East Wall Of Room 328
Lab No.: 6429601 Client No.: 2-MG6-05
Location: SW Corner Of Room 328
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 2 of 20
Lab No.: 6429601(L2) Client No.: 2-MG6-05
Analyst Observation: Grey Mastic
Location: SW Corner Of Room 328
Lab No.: 6429602 Client No.: 2-MG6-06
Location: N Doorway Of Room 328
Lab No.: 6429603 Client No.: 3-FT3-07
Analyst Observation: White Floor Tile Client Description: Carpet Glue & Mastic On Floor Tile
Location: SE Corner Of Room 322
PC 2.1 Chrysotile
97.9
Lab No.: 6429603(L2)
Lab No.: 6429603(L3)
Analyst Observation: White Mastic
Lab No.: 6429603(L4)
Analyst Observation: Black Mastic
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 3 of 20
Lab No.: 6429604 Client No.: 3-FT3-08
Analyst Observation: Lt Brown Floor Tile
Location: SE Corner Of Room 322B
Lab No.: 6429604(L2)
Lab No.: 6429604(L3)
Lab No.: 6429604(L4)
8 Cellulose
Lab No.: 6429605 Client No.: 3-FT3-09
Location: SE Corner Of Room 320
PC 0.25 Chrysotile
99.75
Note: Analyzed by R.Hargrove 1-30-18
Lab No.: 6429605(L2)
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 4 of 20
Lab No.: 6429605(L3)
Lab No.: 6429606 Client No.: 4-MG5-10
Analyst Observation: Lt Brown Mastic Client Description: Green/Grey Mastic
Location: SE Corner Of Room 330A
4 Cellulose
Lab No.: 6429606(L2) Client No.: 4-MG5-10
Analyst Observation: Red Carpet
Location: SE Corner Of Room 330A
98 Synthetic
Lab No.: 6429607 Client No.: 4-MG5-11
Location: NE Corner Of Room 330B
Lab No.: 6429608 Client No.: 4-MG5-12
Location: SW Corner Of Room 330
2 Cellulose
Lab No.: 6429608(L2)
Analyst Observation: Dk Yellow Mastic
4 Cellulose
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 5 of 20
Lab No.: 6429608(L3)
Lab No.: 6429609 Client No.: 5-FC3-13
Analyst Observation: Red Cove Base Client Description: Red 4" Base Cove And Mastic
Location: N Wall Of Room 330A
Lab No.: 6429609(L2)
Analyst Observation: White Joint Compound
Lab No.: 6429609(L3)
Lab No.: 6429609(L4)
Lab No.: 6429610 Client No.: 5-FC3-14
Location: SE Corner Of Room 330B
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 6 of 20
Lab No.: 6429610(L2)
Lab No.: 6429610(L3)
Lab No.: 6429611 Client No.: 5-FC3-15
Location: N Wall Of Room 330B
Lab No.: 6429611(L2) Client No.: 5-FC3-15
Location: N Wall Of Room 330B
Lab No.: 6429612 Client No.: 6-FC3-16
Analyst Observation: Grey Cove Base Client Description: Brown 4" Base Cove And Mastic
Location: NW Corner Of Room 324A
Lab No.: 6429612(L2) Client No.: 6-FC3-16
Location: NW Corner Of Room 324A
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 7 of 20
Lab No.: 6429613 Client No.: 6-FC3-17
Location: NW Corner Of Room 324C
Lab No.: 6429613(L2) Client No.: 6-FC3-17
Location: NW Corner Of Room 324C
Lab No.: 6429614 Client No.: 6-FC3-18
Location: SW Corner Of Room 324A
Lab No.: 6429614(L2)
Lab No.: 6429614(L3)
Lab No.: 6429614(L4)
Analyst Observation: White Leveling Compound
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 8 of 20
Lab No.: 6429615 Client No.: 7-FC3-19
Client Description: Maroon 4" Base Cove And Mastic
Location: Room 324
Lab No.: 6429615(L2)
Analyst Observation: Lt Yellow Mastic
Lab No.: 6429615(L3)
Lab No.: 6429616 Client No.: 7-FC3-20
Lab No.: 6429616(L2) Client No.: 7-FC3-20
Analyst Observation: Lt Yellow/Dk Yellow Mastic
Lab No.: 6429617 Client No.: 7-FC3-21
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 9 of 20
Lab No.: 6429617(L2)
Analyst Observation: Lt Yellow/Dk Yellow Mastic
Lab No.: 6429617(L3)
Lab No.: 6429618 Client No.: 8-FC3-22
Analyst Observation: Lt Brown Cove Base Client Description: Tan 4" Base Cove And Mastic
Location: Room 324B
Lab No.: 6429618(L2)
Lab No.: 6429618(L3)
Lab No.: 6429619 Client No.: 8-FC3-23
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 10 of 20
Lab No.: 6429619(L2)
Lab No.: 6429619(L3)
Lab No.: 6429620 Client No.: 8-FC3-24
Lab No.: 6429620(L2)
Lab No.: 6429620(L3)
Lab No.: 6429620(L4)
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 11 of 20
Lab No.: 6429621 Client No.: 9-CT4-25
Analyst Observation: Beige Ceiling Tile Client Description: 2x4 Ceiling Tile
50 Cellulose 40 Mineral Wool
Lab No.: 6429622 Client No.: 9-CT4-26
Location: Room 328
50 Cellulose 40 Mineral Wool
Lab No.: 6429623 Client No.: 9-CT4-27
Location: Room 330
40 Cellulose 50 Mineral Wool
Lab No.: 6429624 Client No.: 10-WB1-28
Analyst Observation: Off-White Drywall Client Description: Gypsum With Joint Compound
3 Cellulose 3 Fibrous Glass
Lab No.: 6429624(L2)
Lab No.: 6429624(L3)
Analyst Observation: Composite
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 12 of 20
Lab No.: 6429624(L4)
Analyst Observation: White Woven Material
99 Fibrous Glass
Lab No.: 6429625 Client No.: 10-WB1-29
Lab No.: 6429625(L2)
Lab No.: 6429625(L3)
Lab No.: 6429625(L4)
Analyst Observation: White Woven Material
98 Fibrous Glass
Lab No.: 6429626 Client No.: 10-WB1-30
2 Fibrous Glass
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 13 of 20
Lab No.: 6429626(L2)
Lab No.: 6429626(L3)
2 Fibrous Glass
Lab No.: 6429627 Client No.: 10-WB1-31
6 Cellulose
Lab No.: 6429628 Client No.: 10-WB1-32
Location: Room 324A
Lab No.: 6429628(L2)
PC 9.2 Chrysotile
90.8
Lab No.: 6429628(L3)
PC 2.0 Chrysotile
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 14 of 20
Lab No.: 6429629 Client No.: 11-HP2-33
Analyst Observation: Beige Plaster Client Description: Original Plaster Surface
Location: Room 330 Ceiling
Lab No.: 6429629(L2) Client No.: 11-HP2-33
Analyst Observation: White Plaster
Location: Room 330 Ceiling
Lab No.: 6429630 Client No.: 11-HP2-34
Location: Room 330 Wall
Lab No.: 6429630(L2) Client No.: 11-HP2-34
Location: Room 330 Wall
Lab No.: 6429631 Client No.: 11-HP2-35
Location: Room 328 Wall
Lab No.: 6429631(L2) Client No.: 11-HP2-35
Location: Room 328 Wall
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 15 of 20
Lab No.: 6429632 Client No.: 11-HP2-36
Location: Room 324 Wall
Lab No.: 6429632(L2) Client No.: 11-HP2-36
Location: Room 324 Wall
Lab No.: 6429633 Client No.: 11-HP2-37
Location: Room 324 Ceiling
Lab No.: 6429633(L2) Client No.: 11-HP2-37
Location: Room 324 Ceiling
Lab No.: 6429634 Client No.: 11-HP2-38
Location: Room 320 Wall
Lab No.: 6429634(L2) Client No.: 11-HP2-38
Location: Room 320 Wall
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 16 of 20
Lab No.: 6429635 Client No.: 11-HP2-39
Location: Room 320 Ceiling
Lab No.: 6429635(L2) Client No.: 11-HP2-39
Location: Room 320 Ceiling
Laboratory Director
Approved By:
Date Analyzed:
1/23/2018Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Brittney Crisera
01/30/2018 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Terracon
860 9th Street NE, Unit K West Fargo ND 58078
1/30/2018Report Date:
Report No.: 555894 - PLM Project: Ronald Davies Project No.: M1177147
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: TER932
Dated : 1/30/2018 4:54:24 Page 17 of 20
Appendix to Analytical Report Customer Contact:
Analysis: US EPA 600, R93-116
This appendix seeks to promote greater understanding of any observations, exceptions, special instructions, or circumstances that the laboratory needs to communicate to the client concerning the above samples. The information below is used to help promote your ability to make the most informed decisions for you and your customers.
Please note the following points of contact for any questions you may have.
iATL Customer Service: customerservice@iatl.com iATL Office Manager: cdavis@iatl.com iATL Account Representative: Cassie Doherty Sample Login Notes: See Batch Sheet Attached Sample Matrix: Bulk Building Materials Exceptions Noted: See Following Pages
General Terms, Warrants, Limits, Qualifiers:
General information about iATL capabilities and client/laboratory relationships and responsibilities are spelled out in iATL policies that are listed at www.iATL.com and in our Quality Assurance Manual per ISO 17025 standard requirements. The information therein is a representation of iATL definitions and policies for turnaround times, sample submittal, collection media, blank definitions, quantification issues and limit of detection, analytical methods and procedures, sub-contracting policies, results reporting options, fees, terms, and discounts, confidentiality, sample archival and disposal, and data interpretation.
iATL warrants the test results to be of a precision normal for the type and methodology employed for each sample submitted.