RFQ27006826 R5055-042- Drawings Stamped.pdf
PDF 4 MB Posted
- Attached to
- DCAMM Medium Moran Transformer
- Solicitation number
- RFQ27006826
- Issued by
- Providence County, Rhode Island
About this file
This file consists of technical drawings stamped and submitted in response to Request for Quote 27006826 by the Rhode Island Division of Capital Asset Management and Maintenance (DCAMM) for procurement of a transformer at the Moran Medium Security Prison. The drawings provided are stamped engineering documents that depict the specifications and technical requirements for the transformer to be supplied. These stamped drawings serve as the technical basis for vendor quotations and represent the detailed design specifications that vendors must meet in their proposals. The document functions as a critical reference for bidders to understand the exact equipment configuration, dimensions, electrical specifications, and installation requirements necessary to submit compliant bids for this procurement opportunity.
The stamped drawings contain professional engineering certifications and approvals indicating that the technical specifications have been reviewed and validated by qualified engineering professionals. These documents establish the baseline technical requirements that all vendors must reference when preparing their quotes and ensuring their proposed transformer meets the Rhode Island DCAMM's specifications for the Moran Medium Security Prison installation. The drawings serve as enforceable technical standards for the procurement process and will be used to evaluate bidder compliance and equipment suitability during the quote evaluation process.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PREPARED BY:LIST OF DRAWINGS
SHEET NO. DRAWING NO. DRAWING TITLE
1 G-001 COVER
2 E-001 ELECTRICAL LEGEND, GENERAL NOTES, AND DETAILS
3 E-101 SITE PLAN
LOCATION MAP
NO SCALE
PROJECT
LOCATION
COMPLETE SET 3 SHEETS
CONSTRUCTION DOCUMENTS
JUNE 2026
DIVISION OF CAPITAL ASSET MANAGEMENT AND MAINTENANCE
JOHN O. PASTORE CENTER CAMPUS
MEDIUM SECURITY MORAN ELECTRIC CHILLER SERVICE
CRANSTON, RHODE ISLAND
Pl ot te d
O n:
Ju n
-1 :2
2p m
B y:
C O ro sz
La st
S av ed :6
/2 3/
Ti gh e
B on d:
J:
\R \R
S ta te o f R ho de I sl an d\
M ed iu m S ec ur ity M or an
E le ct ri c
C hi lle r
S er vi ce
P ro po sa l\ D ra w in gs
\A ut oC A D
\S he et \R
-0
-G -0
.d w g
14713
JASON CURTIS
MECHANICAL06/24/2026
14326
MICHAEL JAMES ROSSINI
ELECTRICAL06/24/2026
ABBREVIATIONS
A
AF
AFF
AFG
AIC
AL
ARCH
AS
AT
ATS
AWG
BLDG
C
CB
CT
CU
CAT
CIR, CKT
CP
CPT
COL
CU
DISC SW, DS
DWG
E
EC
EM
EPR
EXP
F
FU
FT
FVNR
FVR
G, GND
GC
GFI, GFCI
ID
KCMIL, MCM
KVA
KVAR
KW
LV
MC
MCB
MCC
MISC
MFR
MH
MLO
MV
NC, NC
NEC
NIC
NL
NO
NTS
OL
P
PILC
PH, Ø
PLC
PVC
PT
PVC
R
RGS
RVNR
S
SCCR, SCR
SCH 40
SP
SPD
SS
SW
TEL
TSP
TYP
UG
UPS
V
VFD
VFI
Y
W
WTF
WWTF
WP
XFMR
WIRE SIZE OR IDENTIFICATION NUMBER
AMPERES
AMPERE FRAME (CIRCUIT BREAKER RATING)
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMPERE INTERRUPTING CAPACITY
ALUMINUM
ARCHITECT
AMPERE SENSOR (CIRCUIT BREAKER RATING)
AMPERE TRIP (CIRCUIT BREAKER RATING)
AUTOMATIC TRANSFER SWITCH
AMERICAN WIRE GAUGE
BUILDING
CONDUIT
CIRCUIT BREAKER
CURRENT TRANSFORMER
COPPER
CATALOG
CIRCUIT
CONTROL PANEL
CONTROL POWER TRANSFORMER
480 VOLTS - 120/240 VOLTS,
UNLESS OTHERWISE INDICATED
COLUMN
DELTA
COPPER
DISCONNECT SWITCH
DRAWING
WIRED ON EMERGENCY CIRCUIT
ELECTRICAL CONTRACTOR
EMERGENCY
ETHYLENE PROPYLENE RUBBER
EXPLOSION PROOF
FLUSH
FUSE
FEET
FULL VOLTAGE NON-REVERSING
FULL VOLTAGE REVERSING
GROUND
GENERAL CONTRACTOR
GROUND FAULT CIRCUIT INTERRUPTER
IDENTIFICATION
ONE THOUSAND CIRCULAR MILS
KILOVOLT-AMPERES
KILOVOLT-AMPERES REACTIVE
KILOWATTS
LOW VOLTAGE
MECHANICAL CONTRACTOR
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MISCELLANEOUS
MANUFACTURER
MANHOLE
MAIN LUGS ONLY
MEDIUM VOLTAGE
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
OVERLOAD
POLE
PAPER INSULATED LEAD COVERED
PHASE
PROGRAMMABLE LOGIC CONTROLLER
POLYVINYL CHLORIDE
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE
RECESSED
RIGID GALVANIZED STEEL CONDUIT
REDUCED-VOLTAGE NON-REVERSING
SURFACE
SHORT CIRCUIT CURRENT INTERRUPTING RATING
SCHEDULE 40 PVC CONDUIT
SPARE
SURGE PROTECTION DEVICE
STAINLESS STEEL
SWITCH
TELEPHONE
TWISTED SHIELDED PAIR CABLE
TYPICAL
UNDERGROUND
UNINTERRUPTABLE POWER SUPPLY
VOLT
VARIABLE FREQUENCY DRIVE (ALSO REFERED
TO AS ADJUSTABLE FREQUENCY DRIVE)
VACUUM FAULT INTERRUPTER
WYE
WATT, WIRE
WATER TREATMENT FACILITY
WASTEWATER TREATMENT FACILITY
WEATHERPROOF
TRANSFORMER
GENERAL NOTES
1. CAUTION: IN NO CASE SHALL THE CONTRACTOR RELY ON THE ACCURACY OF THE
IDENTIFICATION OF THE PRIMARY SWITCHES, SPLICE CABINETS AND CABLE IDENTIFICATION
IN EXISTING MANHOLES. THE CONTRACTOR SHALL VERIFY SWITCH IDENTITIES AND THE
ENERGIZED STATE OF ALL CABLES PRIOR TO ANY WORK. CONTRACTOR SHALL FIELD CONFIRM
EACH CIRCUIT IDENTIFICATION IN EACH MANHOLE AND SPLICE CABINET PRIOR TO ALL WORK.
CIRCUIT IDENTIFICATION INDICATED ON THESE DRAWINGS IS BASED UPON OBSERVATIONS
ONLY.
2. CAUTION: ALWAYS VERIFY EXISTING CONDUCTOR CHARACTERISTICS PRIOR TO PROCUREMENT
OF TERMINATIONS AND SPLICES.
3. REFERENCE THE RESPECTIVE OSHA STANDARDS AND THE SAFETY REQUIREMENTS REGARDING
CONFINED SPACE ENTRY AND LOCKOUT/TAG OUT PROCEDURES.
4. SWITCHING SHALL NOT BE PERFORMED UNDER LOAD WITHOUT OWNER'S APPROVAL.
5. THE CONTRACTOR SHALL PROVIDE TEMPORARY 6 FOOT HIGH, CHAIN LINK FENCING AROUND
ALL AREAS OF WORK IN EACH PHASE, TO INCLUDE LAY DOWN AREAS, CONTRACTOR TRAILERS,
EXCAVATION AND TRENCHING SITES, PROPOSED NEW EQUIPMENT PADS AND EXISTING
EQUIPMENT. FENCING SHALL HAVE PAD LOCKABLE ACCESS GATES, WITH SAFETY SIGNAGE PER
RI DCAMM REQUIREMENTS. FENCING SHALL BE REMOVED FROM ALL AREAS UPON COMPLETION
OF WORK AND FINAL APPROVAL FROM RI DCAMM.
6. THE CONTRACTOR SHALL PROVIDE TEMPORARY POWER TO CRITICAL FACILITIES DURING
SCHEDULED OUTAGES, AS REQUIRED AND DIRECTED BY RI DCAMM. THIS SHALL INCLUDE ROLL
UP GENERATORS AND TEMPORARY CABLING AND CONNECTIONS TO EXISTING BUILDING
DEEMED ESSENTIAL FOR 24/7/365 OPERATION. THE CONTRACTOR SHALL COORDINATE WITH
RI DCAMM DURING BIDDING AND CONSTRUCTION FOR A LIST OF ALL TEMPORARY POWER
REQUIREMENTS. THE CONTRACTOR SHALL PROVIDE REFUELING AND PERSONNEL TO ENSURE
CONTINUOUS OPERATION OF TEMPORARY POWER SOURCES FOR THE DURATION OF
SCHEDULED OUTAGES.
7. THE CONTRACTOR SHALL PROVIDE PERSONNEL DURING OFF HOURS/NORMAL BUSINESS
HOURS FOR SCHEDULED OUTAGES, CUTOVERS AND WORK RELATED TO EACH PHASE, AS
COORDINATED AND SCHEDULED WITH RI DCAMM.
8. THE CONTRACTOR SHALL PROVIDE MEDIUM VOLTAGE QUALIFIED PERSONNEL FOR THE WORK
IN EACH PHASE. REFER TO SPECIFICATIONS FOR TYPED WRITTEN MEDIUM VOLTAGE RESUME
AND PROJECT EXPERIENCE REQUIREMENTS FOR ALL PERSONNEL ASSIGNED TO WORK ON THE
PASTORE CENTER CAMPUS FOR EACH PHASE. PERSONNEL FOR THIS PROJECT SHALL PROVIDE
WRITTEN PROOF OF TRAINING AND EXPERIENCE IN THE INSTALLATION OF MEDIUM VOLTAGE
CABLE, SPLICES, LOADBREAK AND DEADBREAK ELBOWS, MEDIUM VOLTAGE PADMOUNTED
SWITCHGEAR, VACUUM FAULT INTERRUPTERS, PROTECTION RELAY INSTALLATION AND
ADJUSTMENT, PHASE ROTATION METERING AND ASSOCIATED STICKS, GROUNDING SYSTEMS,
MEDIUM VOLTAGE CABLE TRAY, UNDERGROUND CONDUIT SEALING AND UNDERGROUND
ELECTRIC UTILITY SYSTEM INFRASTRUCTURE.
9. TERMINATIONS OF MEDIUM VOLTAGE CABLES (LOADBREAK ELBOWS, DEADBREAK ELBOWS,
HOT SHRINK SPLICE KITS) SHALL BE COMPLETED BY THE SELECTED CONTRACTOR QUALIFIED
TO PERFORM THIS WORK AND NOT SUBCONTRACTED TO A THIRD PARTY CONTRACTOR FOR
COMPLETION, PER RI DCAMM.
10. EXISTING EQUIPMENT TO REMAIN IS SHOWN WITH A LIGHT LINE; NEW EQUIPMENT IS SHOWN
WITH A BOLD LINE.
11. PROVIDE A SINGLE SET OF SPLICES FOR EACH TAP FROM MANHOLE OR SPLICE CABINET; TWO
OR MORE SETS OF SPLICES ON THE SAME FEEDER OR TAP PER MANHOLE IS PROHIBITED,
TYPICAL.
12. REFER TO ENLARGED MANHOLE LOCATIONS PLANS FOR EQUIPMENT LOCATIONS.
13. REFER TO EXISTING CONDITIONS DETAIL SHEETS FOR MANHOLE KEY PLANS AND CONDUIT
ARRANGEMENTS.
14. PROVIDE TEMPORARY POWER AND EQUIPMENT AS REQUIRED TO KEEP SYSTEMS OPERATIONAL, SEE SPECIFICATIONS FOR SEQUENCING AND SCHEDULING.
15. REFER TO APPROVED SUBMITTALS FOR COORDINATION OF EQUIPMENT LOCATIONS AND
POWER REQUIREMENTS.
16. COORDINATE ALL EQUIPMENT LOCATIONS PRIOR TO ROUGH-IN. SUBMIT COORDINATION
DRAWINGS INDICATING EXISTING AND NEW SCOPES FOR ENGINEER AND OWNERS APPROVAL
PRIOR TO CONSTRUCTION.
17. ALL CONDUITS, FEEDERS OR OTHER UTILITIES DAMAGED DURING THE CONTRACTOR'S
OPERATIONS SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REPAIR OR REPLACE AT NO
COST TO THE OWNER.
18. SUPPORT ALL UTILITIES AND STRUCTURES DURING CONSTRUCTION AND MAKE REPAIRS IF
DAMAGED.
19. ALL CONCRETE WORK SHALL BE BY THE CONTRACTOR.
20. THE LOCATIONS OF EXISTING UTILITIES AND EQUIPMENT INDICATED HEREIN ARE
APPROXIMATE. DETERMINE THE EXACT LOCATION OF EXISTING UTILITIES AND STRUCTURES
BEFORE COMMENCING WORK USING GROUND PENETRATING RADAR OR OTHER MEANS TO
IDENTIFY AND CONFIRM EXISTING UNDERGROUND UTILITIES. CONTRACTOR SHALL BE FULLY
RESPONSIBLE FOR ANY AND ALL DAMAGE WHICH MIGHT BE OCCASIONED BY FAILURE TO
EXACTLY LOCATE AND PRESERVE AND PROTECT ANY AND ALL UTILITIES AND STRUCTURES.
21. CONDUIT ROUTING IS DIAGRAMMATIC. WHERE ROUTING IS SPECIFICALLY INDICATED,
CONDUITS SHALL BE ROUTED AS INDICATED ON THE DRAWING. NO EXCEPTION WITHOUT
PRIOR WRITTEN PERMISSION FROM THE PROJECT ELECTRICAL ENGINEER. CONTRACTOR SHALL
AVOID EXISTING UNDERGROUND UTILITIES DURING THE INSTALLATION OF NEW
UNDERGROUND STRUCTURES AND DUCT BANKS.
22. CONTRACTOR SHALL COORDINATE WITH EQUIPMENT MANUFACTURERS TO CONFIRM MINIMUM
PAD DIMENSIONS PRIOR TO CONSTRUCTION OF ALL FORMS AND EXCAVATION.
23. CONTRACTOR SHALL COORDINATE EQUIPMENT PLACEMENT AT EACH LOCATION AND ADJUST
PROPOSED LOCATIONS WITH THE OWNER PRIOR TO ALL WORK.
24. CONTRACTOR SHALL INSPECT EACH MANHOLE AND SPLICE CABINET AND VERIFY CABLE SIZES
AND TYPES FOR EACH AFFECTED FEEDER. THE CONTRACTOR SHALL PROVIDE MATCHING
FEEDER SIZE AND TYPE AT EACH MANHOLE AND SPLICE CABINET, FOR INTERCONNECTIONS
AND EXTENSIONS OF FEEDERS TO NEW PAD MOUNTED SWITCHES AND PAD MOUNTED
TRANSFORMER.
25. PREVENT DUST FROM BECOMING A NUISANCE OR HAZARD DURING EXCAVATION. CONTROL
DUST DURING AND AFTER CONSTRUCTION. PRIOR TO ALL WORK, CONTRACTOR SHALL SUBMIT
A CONSTRUCTION MITIGATION TO THE OWNER AND ENGINEER FOR APPROVAL.
26. PROVIDE COMPLETE REPAIR, REGRADING AND REMEDY TO ALL AREAS AND SURFACES
IMPACTED OR DISTURBED DURING EXCAVATION OF DUCT BANKS, INSTALLATION OF
EQUIPMENT PADS OR OPERATING EQUIPMENT ON GRASS AREAS OR BITUMINOUS CONCRETE.
RESEED, REGRADE, REPAVE, REPAIR TO ORIGINAL CONDITION.
27. ALL VERIFICATION OF UNDERGROUND UTILITIES, PIPING AND SERVICES, STRUCTURES AND
SYSTEMS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR, AND DONE PRIOR TO ALL
WORK. CONTRACTOR SHALL COORDINATE ALL PROPOSED WORK IN AND AROUND EXISTING
ELECTRIC, WATER, AND STEAM UTILITIES WITH ENGINEER AND OWNER PRIOR TO PROPOSED
EXCAVATION. PRIOR TO ALL EXCAVATION, CONTRACTOR SHALL PROVIDE OWNER AND
ENGINEER DETAILED SKETCHES OF EACH PART SITE AREA, THAT DETAILS EXISTING UTILITIES
THAT MUST BE SUPPORTED, PROTECTED, MAINTAINED AND AVOIDED DURING ALL WORK.
28. THE ACCURACY AND COMPLETENESS OF SUBSURFACE INFORMATION (E.G., EXISTING
UTILITIES) SHOWN ON THESE DRAWINGS IS NOT GUARANTEED AND SOME SUBSURFACE
INFORMATION MAY NOT BE SHOWN. DETERMINE THE LOCATIONS AND ELEVATIONS OF ALL
SUBSURFACE FEATURES WHICH MAY AFFECT CONSTRUCTION OPERATIONS BY TEST PIT OR
OTHER METHODS, AS NECESSARY TO PREVENT DAMAGE TO UTILITIES AND OTHER
SUBSURFACE FEATURES, AND/OR INTERRUPTIONS IN UTILITY SERVICE. PROVIDE DATA
COLLECTED THROUGH THESE INVESTIGATIONS TO THE ENGINEER PRIOR TO CONSTRUCTING
THE PROPOSED IMPROVEMENTS.
29. THE CONTRACTOR IS RESPONSIBLE FOR NOTIFYING DIGSAFE AT 1-888-344-7233 AND OTHER
UTILITY OWNERS IN THE AREA NOT ON THE DIGSAFE LIST ATLEAST 72 HOURS PRIOR TO ANY
DIGGING, TRENCHING, ROCK REMOVAL, DEMOLITION, BORING, BACKFILLING, GRADING,
LANDSCAPING, OR ANY OTHER EARTH MOVING OPERATIONS.
30. THE CONTRACTOR IS RESPONSIBLE FOR SUPPORT OF EXISTING UTILITIES AND REPAIR OR
REPLACEMENT COSTS OF UTILITIES DAMAGED DURING CONSTRUCTION WHETHER ABOVE OR
BELOW GRADE. REPLACE DAMAGED UTILITIES IMMEDIATELY AT NO ADDITIONAL COST TO THE
OWNER AND AT NO COST TO THE PROPERTY OWNER.
31. NOT ALL UTILITY SERVICES TO THE BUILDING ARE SHOWN. CONTRACTOR SHALL ANTICIPATE
THAT THE PROPERTY HAS SERVICE CONNECTIONS FOR VARIOUS UTILITIES.
32. NOTIFY THE ENGINEER OF ANY UTILITIES IDENTIFIED DURING CONSTRUCTION THAT ARE NOT
SHOWN ON THE DRAWINGS OR THAT DIFFER IN SIZE, DEPTH, OR MATERIAL.
33. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO CONSTRUCTION. IF FIELD CONDITIONS
ARE OBSERVED THAT VERY SIGNIFICANTLY FROM THOSE SHOWN ON THE DRAWINGS,
IMMEDIATELY NOTIFY THE ENGINEER IN WRITING FOR RESOLUTION OF THE CONFLICTING
INFORMATION.
GRADEGRADE
G
G
G
TYPICAL PRECAST CONCRETE PAD SECTION
GENERAL PAD NOTES:
1. THIS DRAWING IS PROVIDED FOR THE PURPOSE OF PLANNING
CONSTRUCTION. IT IS IMPORTANT TO RECOGNIZE THAT ALL DETAILS SHOWN
ARE VARIABLE AND SUBJECT TO CHANGE TO MEET THE REQUIREMENTS OF
SPECIFIC APPROVED TRANSFORMERS AND EQUIPMENT.
2. ALL CONCRETE SHALL MEET OR EXCEED THE DESIGN AND TEST
SPECIFICATIONS OF THE AMERICAN CONCRETE INSTITUTE (ACI) MINIMUM
STRENGTH OF CONCRETE: 4000 PSI.
3. ALL PADS SHALL BE REINFORCED WITH 6 X 6 - 4/4 WELDED STEEL WIRE
FABRIC. THE SQUARE WELDED WIRE FABRIC SHALL BE INSTALLED TWO (2)
INCHES UP FROM THE BOTTOM OF THE SLAB AND (11
2") INCHES BELOW THE
TOP OF THE SLAB. THE REINFORCEMENT SHALL STOP TWC (2) INCHES FROM
THE SIDES AND OPENINGS OF THE PAD.
4. ALL EXPOSED CONCRETE EDGES SHALL BE CHAMFERED AT A 45° ANGLE WITH
A 34" FLAT SURFACE.
5. THE PAD SHALL BE LEVEL AND SHALL EXTEND 4" ABOVE FINISHED GRADE AND
BE INSTALLED ON 18 INCHES OF CRUSHED STONE ON TOP OF UNDISTRUBED
OR WELL TAMPED EARTH.
6. ALL PRIMARY AND SECONDARY CONDUIT BENDS SHALL BE INSTALLED AND
TERMINATED FLUSH WITH THE TOP OF THE TRANSFORMER PAD. THE CENTER
OF THE OPENINGS OF THE PRIMARY CONDUIT BENDS SHALL BE SIX (6)
INCHES FROM THE FRONT OF THE CONDUIT OPENING.
7. ALL PRIMARY AND SECONDARY CONDUIT BENDS SHALL HAVE GROUNDING
BUSHINGS TERMINATED WITH #2/0 BARE COPPER CABLE WITH 3 FEET OF
SLACK CABLE. CONDUITS SHALL BE INSTALLED AND TERMINATED 3" ABOVE
THE EQUIPMENT PAD.
8. INSTALLATION SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE
NATIONAL ELECTRICAL CODE.
9. DUCT WINDOW SHALL BE FILLED WITH WELL TAMPED SAND AND CAPPED
WITH GROUT. UPON INSTALLATION OF PRIMARY AND SECONDARY CABLES,
CONDUITS SHALL BE CAPPED AND FILLED WITH EXPANDING FOAM .
10. CONTRACTOR SHALL COORDINATE ALL CONCRETE PAD DIMENSIONS AND
CONDUIT ENTRY LOCATIONS WITH APPROVED VENDOR SHOP DRAWINGS.
PAD LEGEND:
3/4" X 10' COPPER CLAD GROUND ROD WITH #4/0
COPPER WHIP AND EXOTHERMIC WELD TO
COPPER WIRE
#4/0 BARE COPPER GROUND WIRE
EXOTHERMIC WELD
#4/0 BARE COPPER WHIP WITH PVC SLEEVE
THROUGH CONCRETE AND MECHANICAL
CONNECTION TO EQUIPMENT AROUND
BUS/TRANSFORMER XO. PROVIDE MINIMUM
5'-0" BARE COPPER GROUNDING WHIP FOR
CONNECTION TO TRANSFORMER
* ADDITIONAL GROUND RODS SHALL BE PROVIDED
AS REQUIRED TO REDUCE THE GROUND
RESISTANCE TO LESS THAN 5 OHMS.
G
REINFORCING STOPS 2" FROM
SIDES AND OPENING
WELDED WIRE FABRIC 6 x 6 W4.0/4.0
2"
2"
WELDED WIRE
FABRIC 6 x 6 W4.0/4.0
2"
1- 1/
2"
4"
GG
G
G
TYPICAL TRANSFORMER PAD
FRONT ACCESS
1"-1-1/2" DIAMETER
CRUSHED STONE; WELL
TAMPED
2-4 INCH GALVANIZED STEEL
CONDUIT SWEEPS; 36" RADIUS
FOR PRIMARY ELECTRIC SERVICE.
6-4 INCH GALVANIZED STEEL
CONDUIT SWEEPS; 36" RADIUS
FOR SECONDARY ELECTRIC
SERVICE. CAP ALL UNUSED
CONDUITS.
DUCT WINDOW
E-001
ELECTRICAL LEGEND,
GENERAL NOTES, AND
DETAILS
NO SCALE
State of Rhode Island
FILE:
DATE:
PROJECT NO:
Pl ot te d
O n:
Ju n
-1 :2
2p m
B y:
C O ro sz
La st
S av ed :6
/2 3/
Ti gh e
B on d:
J:
\R \R
S ta te o f R ho de I sl an d\
M ed iu m S ec ur ity M or an
E le ct ri c
C hi lle r
S er vi ce
P ro po sa l\ D ra w in gs
\A ut oC A D
\S he et \R
-0
-E -0
.d w g
MARK DATE DESCRIPTION
CONSTRUCTION
DOCUMENTS
R5055-042-E-001.dwg
JUNE 2026
R5055-042
SCALE:
DESIGNED/CHECKED BY:
DRAWN BY:
APPROVED BY:
Cranston, Rhode Island
John O. Pastore Center Campus Medium Security Moran Electric Chiller Service
CTO
CTO, MR
JLC
7 1/2"1' -0
3"
FINISH GRADE
1 2
CONTINUOUS MARKER TAPE
OVER EDGES OF DUCTBANK
CONDUIT
CONCRETE, SEE NOTE 2
CONDUIT SPACERS, 4'-0" ON
CENTER;SECURED TO EACH
OTHER AND RE-BAR WITH
HEAVY DUTY ZIP-TIES.
#5 REBAR,CONTINUOUS BY
GENERAL CONTRACTOR;
SECURED TO CONDUIT
SPACERS WITH HEAVY-DUTY
ZIP TIES
3" 3"
#5 REBAR, CONTINUOUS
TYPICAL CROSS-TIE; 4'-0"
ON CENTER. SECURED
WITH HEAVY- DUTY ZIP
TIES
3"
NTS
2-WAY_DUCTBANK
14713
JASON CURTIS
MECHANICAL06/24/2026
14326
State of Rhode Island
FILE:
DATE:
PROJECT NO:
Pl ot te d
O n:
Ju n
-1 :2
2p m
B y:
C O ro sz
La st
S av ed :6
/2 3/
Ti gh e
B on d:
J:
\R \R
S ta te o f R ho de I sl an d\
M ed iu m S ec ur ity M or an
E le ct ri c
C hi lle r
S er vi ce
P ro po sa l\ D ra w in gs
\A ut oC A D
\S he et \R
-0
-E -1
.d w g
MARK DATE DESCRIPTION
CONSTRUCTION
DOCUMENTS
R5055-042-E-101.dwg
JUNE 2026
R5055-042
SCALE:
DESIGNED/CHECKED BY:
DRAWN BY:
APPROVED BY:
Cranston, Rhode Island
John O. Pastore Center Campus Medium Security Moran Electric Chiller Service
CTO
CTO, MR
JLC
E-101
SITE PLAN
SITE PLAN
SCALE:1-40'
MEDIUM MORAN 2400V SINGLE LINE DIAGRAM
KEYNOTES
PROVIDE (3) SETS OF #4/0AWG PER PHASE USING SC CABLE WITH CAMLOCK
CONNECTORS. COORDINATE WITH CHILLER MANUFACTURER FOR CAMLOCK
CONNECTOR (MALE/FEMALE). ROUTE CABLES FROM DISCONNECT SWITCH TO
CHILLER PACKAGE POWER CONNECTION POINT. PROVIDE DURABLOK
PREMANUFACTURERED SLEEPERS FOR SETS OF CAMLOCK CABLES.
NEW SKID MOUNTED TEMPORARY 230 TON AIR COOLED CHILLER PACKAGE BY
OTHERS
PROVIDE FENCE PENETRATIONS. COORDINATE FENCE PENETRATIONS WITH RI
DOA.
PROVIDE NEMA 3R, 600A, 480V, 3PH, 3W, FUSED DISCONNECT SWITCH ON
FREESTANDING STRUT ASSEMBLY AND PRECAST CONCRETE PAD. COORDINATE
EXACT LOCATION WITH PORTABLE CHILLER. UTILIZE 2 INCH GALVANIZED STRUT.
WIRING TROUGH SHALL TERMINATE WITHIN 4 FEET OF DISCONNECT SWITCH.
UTILIZE (2) 4 INCH RGS CONDUITS FROM WIRING TROUGH TO SWITCH. PROVIDE
WIRING TROUGH BELOW SWITCH FOR CAMLOCK CABLING TO CHILLER PACKAGE.
PROVIDE (2) 4"PVC CONDUITS WITH SPACERS, A MINIMUM OF 18 INCHES BELOW
GRADE. PROVIDE GPR SCANNING OF PROPOSED ROUTE. AVOID EXISTING
UNDERGROUND CONDUITS AND SYSTEM PIPING. PROVIDE REPAIR OF
DISTURBED SURFACES AND FINISHED ALONG ROUTE. PROVIDE SAW CUTTING IN
AREAS WITH BITUMINOUS CONCRETE.
PROVIDE (2) SETS OF XHHW-1, 600V RATED, (3) 500KCMIL AND (1) 1/0 AWG
GROUND IN CONDUIT. SEE KEYNOTE 5.
PROVIDE (2) 10FT COPPER GROUND RODS INTERCONNECTED BY BARE COPPER
#4/0AWG GROUND LOOP USING COMPRESSION CONNECTIONS. INTERCONNECT
TRANSFORMER X0 AND ENCLOSURE AT (2) OPPOSING CORNERS USING #4/0AWG
CONNECTIONS.
PROVIDE RI DOA STORED 1000KVA TRANSFORMER RATED 2400V-277/480V, 3PH, 4W.
PROVIDE NEW PRECAST CONCRETE PAD FOR THE TRANSFORMER(85" WX85"D).
TRANSFORMER DIMENSIONS: 70 INCHES W X 70 INCHES D. PROVIDE NETA TESTING
TO INCLUDE TRANSFORMER TURNS RATIO TESTING AND DISSOLVED GAS ANALYSIS.
NEW 2400V MEDIUM MORAN FEEDER(ALT) USING (3) 5KV RATED EPR #4/0AWG CU
CONDUCTORS WITH (1) # 4/0AWG 600V RATED GROUND CONDUCTOR IN (1) 5"
SCHEDULE 40 PVC CONCRETE ENCASED DUCTBANK(30 INCHES BELOW GRADE).
INCLUDE (1) 5" SPARE CONDUIT.
PROVIDE GPR SCANNING, SAWCUTTING, TRENCH EXCAVATION, BACKFILL,
COMPACTION, AND BITUMINOUS CONCRETE REPAIR.
EXISTING MANHOLE MH-MM7 WITH 2400V MEDIUM MORAN FEEDERS. IDENTIFY
MEDIUM MORAN ALTERNATE FEEDER FOR USE FOR THIS PROJECT. PROVIDE (3) 5KV
HOT SHRINK SPLICES, SUPPLEMENTAL NON-CONDUCTIVE CABLE RACKS AND MANHOLE
GROUND SYSTEM INTERCONNECTIONS. PROVIDE PERMANENT CIRCUIT LABELS FOR
EACH CABLE IN MANHOLE. SEE SINGLE LINE DIAGRAM.