View the file

Other files

File Type Posted
Amend-16 Attachment B - PWS PM Repair Services.rtf RTF text file
Amend-16 Attachment F - Price Schedule.xlsx XLSX spreadsheet
Attachment I - Basement Drawing for UPS Amend-15.docx DOCX document
Attachment A - Scope of Work Amend-15.docx DOCX document
Amendment-14 Site Visit Extend Due Date.docx DOCX document
Amend-13 Attachment A SOW Rev_11-16-23.docx DOCX document
Amend-9 Attachment A - Scope of Work RF DR and Portable.docx DOCX document
Amendment 8 Question to KTRs.docx DOCX document
Amend-6 6-29 AND 6-30 VOLTAGE GRAPH.pdf PDF
Amend-6 Jul 1 to July 6.pdf PDF
Amend-6 6-28 VOLTAGE GRAPH.pdf PDF
Amend-6 voltage drops.pdf PDF
Amend-6 Email 8-22-202 Meter.docx DOCX document
Amend-6 June 21 thru June 27.jpg JPG image
Amend-6 June 14 thru June 21.jpg JPG image
Amend-6 June 7 thru June 14.jpg JPG image
Amend-6 6-30 VOLTAGE GRAPH.pdf PDF
Amend-6 July Generator Test.pdf PDF
Amendment 5 Site Visit Grey Market.docx DOCX document
Amend 4 Questions and Responses.docx DOCX document
Attachment B - Performance Work Statement PM and Repair Amend 2.rtf RTF text file
Scope of Work Digital Radiology Refresh.docx DOCX document
Attachment C - VistA Imaging DICOM August 2022.pdf PDF
Attachment D - ISA_DEA Template.pdf PDF
Attachment B - Performance Work Statement PM Repair Services.rtf RTF text file
Attachment G - Clause Admin Data.docx DOCX document
Attachment F - Price Schedule.xlsx XLSX spreadsheet
Attachment H - 2023 AZ Tax Exemption Letter.pdf PDF
Combined Synop-Solicit RFP-23-PHX-25.docx DOCX document
Attachment A - Scope of Work RF DR and Portable.docx DOCX document
Attachment E - Radiology Floor Plan.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

psm

11:00 06/27/22

23:00 06/27/22

11:00 06/28/22

23:00 06/28/22

11:00 06/29/22

23:00 06/29/22

11:00 06/30/22

23:00 06/30/22

Date & Time

275.0

280.0

285.0

290.0

V o lt a g e

V

V1n Max 286.8

V2n Max 287.5

V3n Max 287.6

Data Log View of C:\MYFILES\San Carlos Hospital\PIMC\XRAY 3 POWER SIGHT\PS 7-1-2022\psm.$LO

To: 07/01/22 10:48:08From: 06/27/22 10:16:06

William Hendrix Typewriter This is a graph produced by the power sight metering. I am a little concerned about the sudden drop in voltage (see arrow). The graph shows the maximum voltage from 6-27 to 6/30. I printed out the graph where the arrow points so you can see more. This could be just the utility switching to compensate for less load. I don't know when SRP would do that. The drop in voltage is not all that much. About 4 volts over about 5 minutes. I don't imagine this small change in voltage could have any bad affects on the Xray. You will see there is a similar voltage change that happens late in the evening.

William Hendrix Arrow

File details come from the government source that posted it. Updated .