RFI 004 - Conduit - 07.21.26.pdf

PDF 463 KB Posted

Attached to
Agricultural Classroom and Barn Construction
Solicitation number
RFP MONT 260000002368 3
Issued by
Oakland County, Michigan

About this file

This is a Request for Information (RFI) document for the Montague Area Public Schools Agricultural Classroom and Barn Construction project (Project #22-136.03) in Michigan, submitted to WinBerg Construction, Inc. The RFI, numbered 004 and dated July 21, 2026, addresses electrical specifications related to underground rigid conduit installation. Allied Electric, the electrical/fire alarm subcontractor, posed the question regarding whether galvanized rigid conduit should be used for single underground conduit runs as specified, and suggested PVC Schedule 40 or 80 as a more cost-effective alternative. The response, provided by Chad Trnka on July 22, 2026, approved Schedule 80 PVC as acceptable for this application.

No specific pricing information, set-asides, incumbent details, or funding sources are documented in this RFI. The document serves as clarification on material specifications rather than a comprehensive bid solicitation or contract award notice. Communication for all RFIs related to this project is directed to Jared Mott at WinBerg Construction, Inc. via email at jared@winbergconstruction.com.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REQUEST FOR INFORMATION

SUB/SUPPLIER: RFI NO.

BY: DATE:

PHONE:

BID CATEGORY NO. BID CATEGORY NAME:

PROJECT: Montague Area Public Schools – Agricultural Classroom and Barn

PROJECT #: 22-136.03

SUBJECT:

REF. SPECIFICATION(S):

REF. DRAWING(S):

REF. DETAIL(S):

TYPE OF QUESTION:

Civil Structural Architectural Mechanical Electrical Other

Question:

Subcontractor / Supplier Recommendation:

RESPONSE BY: WinBerg Construction, Inc. Architect / Engineer

Response:

WinBerg Construction, Inc. Signature: Date:

Architect / Engineer Signature: Date:

Email all RFI’s to WinBerg Construction, Inc. – Attn. Jared Mott at jared@winbergconstruction.com

Allied Electric

Carson Bekins

616-540-8804

12 Electrical/Fire Alarm

Rigid conduit underground

26 0533 (Part 3.1)(A)(3)

7/21/26

X

N/A

N/A

Per the specifications stated above, we are to run galvanized rigid conduit for single conduit runs underground, is this correct?

I'd suggest PVC (sch 40 or 80) for this application as it will be significantly cheaper for the same result.

X

Schedule 80 is acceptable.

Chad Trnka 07-22-2026

7/22/26