RFB952700-01 - Drawings.pdf

PDF 7 MB Posted

Attached to
HHS Cherokee Mental Health Institute Four Corners Elevator Replacement
Solicitation number
RFB952700-01
Issued by
Carroll County, Iowa

About this file

This file comprises architectural and construction drawings for the Iowa Department of Administrative Services (DAS) at the Cherokee Mental Health Institute (CHMHI) related to an elevator replacement project designated RFB952700-01. The project involves the replacement of Elevator F in the Four Corners area of the CHMHI facility located in Cherokee, Iowa, including associated mechanical, electrical, and plumbing (MEP) upgrades to meet current code requirements. The scope of work encompasses removal and replacement of the existing hydraulic elevator car, operating panels, traveling cables, landing buttons, power unit components, hoistway doors, frames, handrails, flooring, and ceiling, along with new pit switches, door safety devices, emergency signage, and code date plates. The facility is a multi-story healthcare building (I-2 occupancy classification) with four floors, approximately 40 feet in height, requiring compliance with 2024 International Building Code, 2024 International Fire Code, 2012 International Energy Conservation Code, 2024 International Existing Building Code, 2012 NFPA 101 Life Safety Code, and 2010 ADA Standards. The project documents are 100 percent construction documents prepared by CMBA Architects (Adam Van Gorp, AIA, License #07319) with mechanical and plumbing engineering by Chad D. Bass, PE (License #P21397) and electrical engineering by Eric P. Heynen, PE (License #P24706).

The drawings include comprehensive details for architectural, mechanical, electrical, fire alarm, and communication system integration, with the project dated August 6, 2026, and plotted August 19, 2026. The construction scope requires coordination among multiple trades including HVAC, plumbing, electrical, and fire detection systems, with specific requirements for fire-rated wall penetrations, emergency lighting, automatic recall functionality, heat detection during construction with permanent detectors upon completion, and integration with existing building systems. Key mechanical work includes sump pump installation and cleaning, refrigeration system installation with minimum five-year warranty coverage, and condensing unit exterior mounting. Electrical work encompasses new panel installation (Panel EL, 200-amp, 3-phase breaker), dedicated receptacles, emergency systems integration, data cabling for two-way communications, and fire alarm module installation. The project requires field verification of existing conditions, coordination with the elevator manufacturer, temporary enclosures and heating during installation, and adherence to State of Iowa administrative rules governing construction standards and code compliance.

View the file

Other files

File Type Posted
RFB952700-01 - Notice to Bidders.pdf PDF
RFB952700-01 - Addendum 01.pdf PDF
RFB952700-01 - Bid Form.pdf PDF
RFB952700-01 - Project Manual.pdf PDF
IMPACS Electronic Procurement System.html HTML file
1437923-event.pdf PDF
Bid Opening - Microsoft Teams Meeting.html HTML file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EARTH

SITE SPOT ELEVATION

NEW FINISH

SPOT GRADE

NEW / EXISTING WALL CONSTRUCTION COLUMN GRID LINE

NEW AND EXISTING

FINISH SPOT

GRADE

TOP OF CURB

BOT. OF CURB

7.3

N:

7.3

E:

4.8

TC:

7.3

BC:

4.8

EXISTING CONTOUR LINE

NEW CONTOUR LINE

APPROX. TEST BORING LOCATION

PROPERTY LINE

CENTER LINES/ PROJECTED LINES

MATCH LINE

LEVEL LINE

MAIN FLOOR

ELEV. 110'- 0"

ROOM NAME AND NUMBER

DOOR NUMBER

ROOM NUMBER

ALPHABET CHARACTERS USED TO

DISTINGUISH BETWEEN MULTIPLE

DOORS THAT ARE ASSOCIATED WITH

PARTICULAR ROOMS

WINDOW TYPE

KEY NOTES

INDICATES A NOTE FOR A SPECIFIC ITEM

ALL KEY NOTES ARE COMPILED UNDER THE TITLE

BAR "KEY NOTES".

BUILDING SECTION / WALL SECTION

SECTION DIRECTION

DETAIL NUMBER

SHEET NUMBER

DETAILS

DETAIL NUMBER

SHEET NUMBER

EXTERIOR ELEVATION

REVISION MARKER

SHEET NUMBER

ELEVATION NUMBER

ELEVATION DIRECTION

NEW

EXISTING

(SCREENED)

A1.01 1

XX

A

A

A1.01

SIM

NEW

EXISTING

(SCREENED)

OR

INTERIOR ELEVATION

A1.01 1

GRAPHIC SYMBOLS

MATERIAL INDICATIONS

NEW EXISTING

A

A1.01

SIM

SHEET NUMBER

ELEVATION NUMBER

ROOM NAME

150 SF

101 ROOM NUMBER

ROOM SQUARE FOOTAGE

SPOT ELEVATION

8'-0"

TOILET ACCESSORIES TAG

A

WALL TAG ASSEMBLY TYPE TAG

METAL STUDS

METAL SECTION

CMU (STD. WT.)

WOOD STUDS

PLYWOOD

INSULATION

(BLANKET OR BATT)

GLASS FIBER REINFORCED

GYPSUM BOARD

GRAVEL / SAND FILL

CONCRETE

BRICK

STONE

FINISHED WOOD

RIGID INSULATION

SEALANT

GYPSUM BOARD

EXISTING CONSTRUCTION

METAL (LARGE SCALE)

WOOD BLOCKING

ACOUSTICAL CEILING

ELEVATION DIRECTION

W1

101A

B-3

W

B

F

K

ROOM NAME

WALLS

BASE

FLOOR

NOTE

ROOM FINISH TAG

ROOM NAME

ROOM NUMBER

ROOM WALL FINISH

ROOM WALL BASE FINISH

ROOM FLOOR FINISH

ROOM KEYNOTES

MINERAL WOOL SPRAY FOAM AIR SEAL

ABBREVIATIONS

AB AIR BARRIER

AFF ABOVE FINISH FLOOR

ACT ACOUSTICAL CEILING TILE

ALT. ALTERNATE

ALUM. ALUMINUM

APPROX. APPROXIMATE

ARCH. ARCHITECT (URAL)

AVB AIR AND VAPOR BARRIER

BD. BOARD

BES BUILDING ENVELOPE SEALANT

BG BUMPER GUARD

BGW BELOW GRADE WATERPROOFING

MEMBRANE

B.O. BOTTOM OF

BRG. BEARING

CC CUBICLE CURTAIN

CFCI CONTRACTOR FURNISHED-CONTRACTOR

INSTALLED

CG CORNER GUARD

CJ CONTROL JOINT

CL CENTERLINE

CLG. CEILING

CMU CONCRETE MASONRY UNIT

COL. COLUMN

CONC. CONCRETE

CONST. CONSTRUCTION

CONT. CONTINUOUS

CORR. CORRIDOR

CPT. CARPET

CR CHAIR RAIL

CT CERAMIC TILE

DIA. DIAMETER

DIM. DIMENSION

DN. DOWN

DS DOWNSPOUT

DTL. DETAIL

DVB DECK VAPOR BARRIER

DWG. DRAWING

EA. EACH

EG END GUARD

EJ EXPANSION JOINT

ELEC. ELECTRICAL

ELEV. ELEVATOR

EPT EPOXY PAINT

EQ. EQUAL

EQUIP. EQUIPMENT

EW EACH WAY

EXIST. EXISTING

EXP. EXPOSED

EXT. EXTERIOR

FAF FLUID APPLIED FLOORING

FD FLOOR DRAIN

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FIN. FINISH (ED)

FLR. FLOOR

FND. FOUNDATION

FRP FIBERGLASS REINFORCED PANEL

FRT FIRE RETARDANT TREATED

FTG. FOOTING

FV FIELD VERIFY

GA. GAUGE

GALV. GALVANIZED

GC GENERAL CONTRACTOR

GFRG GLASS FIBER REINFORCED GYPSUM

GL GLASS

GYP. GYPSUM

GWB GYPSUM WALL BOARD

HM HOLLOW METAL

HORIZ. HORIZONTAL

HR HANDRAIL

HVAC HEATING, VENTILATING, AIR CONDITIONING

INT. INTERIOR

JST. JOIST

JT. JOINT

KIT. KITCHEN

LAV. LAVATORY

MAX. MAXIMUM

MB MARKER BOARD

MDF MEDIUM DENSITY FIBERBOARD

MECH. MECHANICAL

MFR. MANUFACTURER

MIN. MINIMUM

MISC. MISCELLANEOUS

MTL. METAL

NIC NOT IN CONTRACT

NOM. NOMINAL

NTS NOT TO SCALE

OC ON CENTER

OFOI OWNER FURNISHED-OWNER INSTALLED

OFCI OWNER FURNISHED-CONTRACTOR

INSTALLED

ORD OVERFLOW ROOF DRAIN

PL PLASTIC LAMINATE

PNL PANEL

PT. PAINT

R / RAD. RADIUS

RAF RAISED ACCESS FLOOR

RD ROOF DRAIN

REF. REFERENCE, REFER TO

REFR. REFRIGERATOR

REINF. REINFORCE (D) (ING)

REQ. REQUIRED

REV. REVISION (S), REVISED

RF RESILIENT FLOORING

RM. ROOM

RO ROUGH OPENING

RP RESIN PANEL

RTU ROOF TOP UNIT

SAB SOUND ATTENUATING BATTS

SCHED. SCHEDULE

SF SQUARE FEET

SIM. SIMILAR

SPEC SPECIFICATION

SS SOLID SURFACE

STD. STANDARD

STL. STEEL

SSTL STAINLESS STEEL

STOR. STORAGE

STRUCT. STRUCTURAL

SUSP. SUSPENDED

TB TACK BOARD

TERR. TERRAZZO

T.O. TOP OF

T.O.B. TOP OF BEAM

T.O.C. TOP OF CONCRETE

T.O.F. TOP OF FOOTING

T.O.W. TOP OF WALL

TWP THROUGH-WALL PENETRATION

TYP. TYPICAL

UVB UNDER-SLAB VAPOR BARRIER

VAR. VARIES

VB VAPOR BARRIER

VERT. VERTICAL

WB WALL BASE

WC WALLCOVERING

WD WOOD

WDF WOOD FLOORING

WDB WOOD BASE

WP WALL PROTECTION

WT WINDOW TREATMENT

C M

B A

A R

C H

IT

E

C T

S

G R

A N

D A

V E

S P

E N

C E

R , I

A

(P

) 7

.2

.3

D A

T E

P R

O J

E C

T

PL

O

T D

AT

E

FI

LE

P

AT

H

COPYRIGHT. Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Cannon Moss Brygger & Associates is prohibited by copyright law.

SHEET INDEX

REVISIONS

SHEET

/1

/2

:4 1:

A

M

A u to d e sk

D o c s:

D

A S

H H

S C

H M

H I T u n n e l & E le va to r/

D A

S H

H S

C H

M H

I T u n n e l R e p a ir

R V

T

.r vt

T

IT

L E

DAS HHS CHMHI FOUR CORNERS ELEVATOR REPLACEMENT

IOWA DAS

CHEROKEE, IOWA

T0.00

C H

E R

O K

E E

, I O

W A

D A

S H

H S

C H

M H

I F

O U

R C

O R

N E

R S

E L

E V

A T

O R

R E

P L

A C

E M

E N

T

IO

W

A D

A S

OWNER'S PROJECT NUMBER: 9527.00

RFP 952700-01

N

NOT TO SCALE

REPLACEMENT OF ELEVATOR F IN FOUR CORNERS AREA OF THE FACILITY, AND ASSOCIATED MEP UPGRADES TO MEET CURRENT CODE. REFERENCE FULL BUILDING DRAWINGS FOR CODE INFORMATION

ADDRESSING THE EXISTING BUILDING.

• 2024 IBC: ALL APPLICABLE CHAPTERS

• 2024 International Building Code as adopted by Iowa Administrative Rule chapters 661-201 and 661-301

• 2024 International Fire Code as adopted by Iowa Administrative Rule chapters 661-201

• 2012 International Energy Conservation Code as adopted by Iowa Administrative Rule chapters 661-303

• 2024 International Existing Building Code as adopted by Iowa Administrative Rule chapters 661-301 and 661-350

• 2012 NFPA 101 Life Safety Code as adopted by Iowa Administrative Rule chapter 661-205

• 2010 Americans with Disabilities Act as adopted by Iowa Administrative Rule chapter 661-302

• State Mechanical Code as adopted by the Department of Public Health Iowa Administrative Rule chapter 641-61

• State Plumbing Code as adopted by the Department of Public Health Iowa Administrative Rule chapter 641-25

• State Electrical Code as adopted by the State Electrical Licensing Board Iowa Administrative Rule chapter 661-504

• ANSI 117.1, 2009, ALL APPLICABLE CHAPTERS

Iowa Department of Administrative Services Owner's Representative:

Jennie Elliot State Design & Construction Resources Bureau 109 S.E. 13th Street Des Moines, IA 50319 Office: 515-745-3244

CMBA Architects 505 Grand Avenue Spencer, IA 51301

PH: 712-262-3426

Architect Responsible: Adam Van Gorp, AIA Email: vangorp.a@cmbaarchitects.com

The Iowa Department of Inspections, Appeals, and Licensing, Building & Construction Division

PROJECT SUMMARY

STATE OF IOWA:

OWNER

ARCHITECT

BUILDING OFFICIAL:

On Site Contact:

Maintenance Supervisor:

Jason Pigott 1251 W Cedar Loop Cherokee, IA 51012

PH: 712-229-1505

IBC 2024 REQ / ALLOWED PROVIDED

USE AND OCCUPANCY

CONSTRUCTION TYPE

AUTOMATIC SPRINKLER SYSTEM

BUILDING HEIGHT

BUILDING STORIES

LARGEST FLOOR AREA / STORY /

1ST FLOOR AREA

CHAPTER 3

SECTION 602 / TABLE 601

SECTION 903

TABLE 504.3

TABLE 504.3

TABLE 506.2

YES

85' MAX

2 STORIES

I-3

II-B

YES

Appx. 40'

ADAM DONAVAN

VAN GORP

07319

S

O

N D

RP

IOWA

L

IC

E E

FESSIONAL

A R

C H

IT

E

C T

ADAM DONAVAN VAN GORP

Signature

Pages or sheets covered by this seal:

Printed or typed name:

I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and responsible charge. I am a duly Licensed Architect under the laws of the State of

Date

License Number:

My license renewal date is

ARCHITECT

ALL "T" & "A" SHEETS

07319

JUNE 30TH, 2027

PROJECT LOCATION

ARCHITECTURAL

A1.01 CODE REVIEW INFORMATION

A2.08 FLOOR PLANS AND SECTIONS

GENERAL

T0.00 TITLE

100% CONSTRUCTION DOCUMENTS SET

MECHANICAL

ME0.0 MECHANICAL & ELECTRICAL GENERAL NOTES & SYMBOLS

ME1.1 MECHANICAL & ELECTRICAL DEMOLITION PLANS

ME2.1 MECHANICAL & ELECTRICAL FLOOR PLANS

ME3.1 MECHANICAL & ELECTRICAL DETAILS

NO. DESCRIPTION DATE

License renewal date:

Pages or sheets covered by this seal:

Date Issued:

I hereby certify that this engineering document was pre-pared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of

Signature

Printed name:

Date

ENGINEER

IOWA

CHAD D. BASS

ALL MECHANICAL AND PLUMBING ON "ME" SHEETS

08/06/2026

DECEMBER 31TH, 2027 License renewal date:

Pages or sheets covered by this seal:

Date Issued:

I hereby certify that this engineering document was pre-pared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of

Signature

Printed name:

Date

ENGINEER

IOWA

ERIC HEYNEN

ALL ELECTRICAL ON "ME" SHEETS

08/06/2026

DECEMBER 31TH, 2027

ERIC

P24706

HEYNENL

IC

E N S E D

P

RO

FESSIONA L

E N G

IN

E E R

I O

W A

CHAD D.

P21397

BASSL

IC

E N S E D

P

RO

FESSIONA L

E N G

IN

E E R

I O

W A hebertt Stamp hebertt Text Box 8/6/2026

S

KEYPLAN

N

ELEVATOR

ADMIN

R E

A R

C E

N T

E R

A N

O R

T H

B N

O R

T H

C N

O R

T H

A S

O U

T H

B S

O U

T H

C S

O U

T

HB

O

IL

E

R

P O

W E

R

LAUNDRY

WIRTH

CODE SUMMARY

PROJECT SUMMARY:

REPLACEMENT OF ELEVATOR F AT THE CHMHI FACILITY, LOCATED IN THE "FOUR

CORNERS" AREA BETWEEN ADMIN AND REAR CENTER BUILDINGS.

REPLACEMENT OF EQUIPMENT ONLY, NO RECONFIGURATION OF SPACES OF

CHANGE OF OCCUPANCY.

CODE INFORMATION

2010 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE

FACILITIES

2000 NFPA 101 LIFE SAFETY CODE

2010 ADAAG

2024 INTERNATIONAL BUILDING CODE

2012 INTERNATIONAL ENERGY CONSERVATION CODE

The below references are from the NFPA 2000 Life Safety Code, unless otherwise noted.

OWNER

IOWA DEPARTMENT OF ADMINISTRATIVE SERVICES (DAS)

CHEROKEE MENTAL HEALTH INSTITUTE (CHMHI)

1251 WEST CEDAR LOOP

CHEROKEE, IA, 51012

OWNERS REP: Jennie Elliott email: jennie.elliott@das.iowa.gov

(515) 745-3244

ARCHITECT

CMBA ARCHITECTS

302 JONES ST STE 200

SIOUX CITY, IA 51101

712-535-1833 A/E RESPONSIBLE: ADAM VAN GORP email: vangorp.a@cmbaarchitects.com 712-274-2933

LOCAL AUTHORITY HAVING JURISDICTION

1. BUILDING OFFICIAL: Dan Wood - IOWA STATE FIRE MARSHAL Email: wood@dps.state.ia.us Phone: 515-725-6150

2. STATE REVEIWER: Shaun Sharrard - Senior Construction Design Engineer Email: shaun.sherrard@dia.iowa.gov Phone: 515.725.6157

OCCUPANCY GROUPS:

1. EXISTING HOSPITAL: HEALTH CARE NFPA CH 19 (IBC I-2)

2. NEW ELEVATOR: HEALTH CARE NFPA CH 19 (IBC I-2)

CONSTRUCTION TYPE:

EXISTING BUILDING: UBC/UFC TYPE 1-FR

SPRINKLER:

1. EXISTING HOSPITAL - NFPA TYPE 13

2. NEW ELEVATOR - NFPA TYPE 13

BUILDING HEIGHT:

EXISTING BUILDING: 4 FLOORS, 3 ABOVE GRADE

PROJECT LOCATION: SEE KEYPLAN

ALLOWABLE HEIGHT: N.A.

BUILDING AREA:

NO CHANGE TO EXISTING FLOOR AREA

HAZARDOUS AREA SEPARATION/ PROTECTED BY 1hr FIRE BARRIER: 19.3.2.1

1. ELEVATOR SHAFT - SEE BELOW

REQUIRED FIRE RESISTANCE RATINGS (in hours)

PRIMARY STRUCTURAL FRAME:

BEARING WALLS:

FLOOR CONSTRUCTION:

ROOF CONSTRUCTION:

SHAFT ENCLOSURES:

STAIRWAY ENCLOSURES (EXISTING):

CORRIDOR WALL FIRE RESISTANCE: 19.3.6.2

CORRIDOR WALLS MAY BE NON RATED AND SHALL LIMIT THE TRANSFER OF

SMOKE

TRAVEL DISTANCE TO EXITS BETWEEN EGRESS ELEMENTS (feet) 19.2.6.2

NO CHANGE TO EXISTING TRAVEL DISTANCES

OCCUPANT LOAD FACTOR (sf / person) TABLE 7.3.1.2:

NO CHANGE TO EXISTING TO OCCUPANT LOAD

DEAD END CORRIDOR LIMIT: 18.2.5.10 & TABLE A7.6.1

NO CHANGE TO CORRIDORS

ACTIVE FIRE SAFETY FEATURES

1. FIRE ALARM SYSTEM - SYSTEM PRESENT

2. SMOKE CONTROL SYSTEM - ALL DUCTWORK PENETRATING RATED WALLS

WILL HAVE A SMOKE OR FIRE/ SMOKE DAMPER

3. FIRE SPRINKLER SYSTEM - NOT PRESENT IN THIS AREA OF THE FACILITY

4. EMERGENCY LIGHTING AND POWER - EMERGENCY LIGHTING PRESENT IN THIS

AREA OF FACILITY

5. ILLUMINATED EXIT SIGNS

ELEVATORS & CONVEYING SYSTEMS (IBC 3000)

EMERGENCY SIGNAGE REQUIRED (3002.3)

MACHINE ROOMS (IBC 3005)

INDEPENDENT VENTING REQUIRED (3005.2)

FIRE BARRIERS: SHAFT 1HR RATED (713.4)

OPENINGS: PER 713.7 - 1HR (3005.4)

EQUIPMENT ROOM:PER 707 OR 3005.4 EXCEPTION 2: IF THE BUILDING IS 4

STORIES OR LESS ABOVE GRADE AND THE EQUIPMENT ROOM IS NOT ADJACENT

OR HAS OPENINGS INTO HOISTWAY SERVED, THE ACCESSORY SPACE IS NOT

REQUIRED TO BE FIRE RATED

FIRE BARRIER - 1 HR FIRE RESISTANCE RATING

EXISTING 1HR FIRE RESISTANCE RATING

FIRE EXTINGUISHER WITH BRACKETFE

CODE LEGEND

Floor 01 100' - 0"

Floor 02 113' - 0"

Basement 90' - 7 1/2"

Floor 03 126' - 0"

A2.08

ELEV PIT

86' - 8 1/4"

ROOF CONNECTING

138' - 0"

ELEV. EQUIP.

B02

ELEV

B01

CLOSET

B04

CLOSET

CLOSET

CLOSET

9'

/2

3'

1/

/4 "Floor 02

13' - 0" Floor 02

13' - 0"

Basement -9' - 4 1/2"

Basement -9' - 4 1/2"

Top of Wall 32' - 0"

Top of Wall 32' - 0"

Floor 03 26' - 0"

Floor 03 26' - 0"

Floor 04 39' - 0"

Floor 04 39' - 0"

ELEV PIT

-13' - 3 3/4"

ELEV PIT

-13' - 3 3/4"

ROOF CONNECTING

38' - 0"

ROOF CONNECTING

38' - 0"

PROJECT SCOPE

ELEV

B01

CORRIDOR

CLOSET

ELEV

B01

ELEV. EQUIP.

B02

CORRIDOR

B03

CLOSET

B04

DATA

B06

ELEC

B07

REAR CENTER

BUILDING

ADMIN

BUILDING

A SOUTH BUILDING

A NORTH BUILDING

PROJECT SCOPE

PROJECT SCOPE

PROJECT SCOPE

DIETARY

STAIRS

STAIRS

STAIRS

STAIRS

ELEV

B01

CORRIDOR

CLOSET

PROJECT SCOPE

ELEV

B01

CLOSET

CORRIDOR

PROJECT SCOPE

C M

B A

A R

C H

IT

E

C T

S

G R

A N

D A

V E

S P

E N

C E

R , I

A

(P

) 7

.2

.3

REVISIONS

SHEET

D A

T E

P R

O J

E C

T

PL

O

T D

AT

E

FI

LE

P

AT

H

COPYRIGHT. Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Cannon Moss Brygger & Associates is prohibited by copyright law.

IF THIS DRAWING IS NOT 30"x42" IT IS NOT TO SCALE

/1

/2

:4 1:

A

M

A u to d e sk

D o c s:

D

A S

H H

S C

H M

H I T u n n e l & E le va to r/

D A

S H

H S

C H

M H

I T u n n e l R e p a ir

R V

T

.r vt

A1.01

C H

E R

O K

E E

, I O

W A

D A

S H

H S

C H

M H

I F

O U

R C

O R

N E

R S

E L

E V

A T

O R

R E

P L

A C

E M

E N

T

IO

W

A D

A S

C O

D E

R E

V

IE

W I

N F

O R

M A

T

IO

N

1/4" = 1'-0"1

ELEVATOR SECTION N/S

1/8" = 1'-0"2

CODE REVIEW - FIRST FLOOR

1/16" = 1'-0"3

CODE REVIEW - BASEMENT

1/8" = 1'-0"4

CODE REVIEW - SECOND FLOOR

1/8" = 1'-0"5

CODE REVIEW THIRD FLOOR

NO. DESCRIPTION DATE

FACP

UP

UP

A2.08

A1.01

FIRE ALARM

PANEL

DATA

B06

ELEC

B07

CORRIDOR

B05

ELEV. EQUIP.

B02

CLOSET

B04

ELEV

B01

CORRIDOR

B03

ADMIN BLDGSECTION A

SOUTH BLDG

SECTION A

NORTH BLDG

REAR

CENTER

BLDG

N

DIETARY

A2.08

A1.01

A2.088

FIELD VERIFY

9' - 10 3/16"

F

IE

L D

V E

R

IF

Y

7'

/8

4' - 10 3/16"

2 3 4

10 13

ELEV

B01

CORRIDOR

CLOSET

8' - 0 3/8"

A2.08

A1.01

CORRIDOR

CLOSET

ELEV

B01

A2.08

Sim

A2.08

A1.01

CORRIDOR

CLOSET

ELEV

B01

A2.08

Sim

Floor 01 100' - 0"

Floor 02 113' - 0"

Basement 90' - 7 1/2"

Floor 03 126' - 0"

Floor 04 139' - 0"

ELEV PIT

86' - 8 1/4"

ROOF CONNECTING

138' - 0"

9'

/2

3'

1/

A1.01

2 10

ELEV

B01

CORRIDOR

B03

CORRIDOR

CORRIDOR

CORRIDOR

F .V

'-5

/2

F .V

'-3

/8

A2.08

A2.08

A1.01

1 5

ELEV. EQUIP.

B02

CORRIDOR

B03

ELEV

B01

CLOSET

B04

A2.08

Sim

8' - 0 3/8"

GENERAL NOTES

KEYNOTES

EXISTING PIT LADDER TO REMAIN

REMOVE AND REPLACE ELEVATOR CAR OPERATING PANEL & CARD

READER INSIDE ELEVATOR CAB

REMOVE AND REPLACE TRAVELING CABLE, SEE ELECTRICAL SHEETS

INSTALL NEW PIT SWITCH

INSTALL DOOR SAFETY DEVICES

REMOVE AND REPLACE LANDING BUTTONS

REMOVE AND REPLACE LANDING CALL BUTTONS AND FIXTURES, TO

BE IN COMPLIANCE WITH ADA 407.2.3.1

INSTALL EMERGENCY SIGNS AT HALL STATIONS

REMOVE AND REPLACE POWER UNIT - MOTOR, PUMP, HYDRAULIC

TANK, VALVE, OIL, GASKETS, ETC

INSTALL CODE DATE PLATES

REMOVE AND REPLACE SIGNAGE

EXISTING SUMP PUMP PIT, F.V. LOCATION AND SIZE

EXISTING ELEVATOR CAB DOORS, FRAMES, HANDRAILS, FLOORING,

CEILING, CAB THRESHOLD, CAB LIGHTING TO BE REPLACED.

NEW CAR DIRECTION INDICATORS

REMOVE EXISTING VENT AND INFILL WITH LIKE MATERIALS

PATCH AND REPAIR HOISTWAY FRAMES

DIMENSIONS ARE TO FACE OF WALL UNLESS NOTED OTHERWISE.

CONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS AND NOTIFY

ARCHITECT OF ANY DISCREPANCIES PRIOR TO BEGINNING THE

AFFECTED WORK.

DO NOT SCALE DRAWINGS, FOLLOW DIMENSIONS.

MECHANICAL AND ELECTRICAL EQUIPMENT / FIXTURES SHOWN FOR

REFERENCE, SEE MECHANICAL AND ELECTRICAL CONSTRUCTION

DOCUMENTS FOR INFORMATION.

ALL PENETRATIONS THROUGH FIRE-RESISTANCE/SMOKE/ SOUND

RATED CONSTRUCTION SHALL BE SEALED WITH APPROVED FIRE-

STOPPING OR SEALANT TO MAINTAIN REQUIRED RATINGS.

PATCH AND REPAIR EXISTING WALLS, FLOORS, CEILINGS, ETC., THAT

ARE SHOWN TO REMAIN BUT ARE DAMAGED DUE TO CONSTRUCTION.

THIS SHALL INCLUDE REPAIRING FINISHES DAMAGED BY THE REMOVAL

OR INSTALLATION OF NEW MECHANICAL, ELECTRICAL, OR FIRE

PROTECTION WORK OR DEVICES.

PATCH AND TOOTH-IN MASONRY ALL NEW OPENINGS, CORNERS,

DOORS, WINDOWS, ETC..

REFER TO ELECTRICAL DEMOLITION PLANS FOR ADDITIONAL

DEMOLITION REQUIRED

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING

AND TEMPORARY SUPPORT OF EXISTING ROOF, WALL AND FLOOR

SURFACES NEAR AND AROUND DEMOLISHED AREAS.

PATCH MECHANICAL AND ELECTRICAL PENETRATIONS IN WALLS,

FLOOR AND CEILINGS/STRUCTURE TO MATCH EXISTING.

FIELD VERIFY STRUCTURAL MEMBER PROFILES INDICATED ON

EXISTING DRAWINGS MAY VARY FROM ACTUAL PROFILES AND SIZES

LOCATED WITHIN THE EXISTING STRUCTURE.

ALL EXISTING COLUMNS REMAIN UNLESS OTHERWISE NOTED.

DOCUMENTS AVAILABLE UPON REQUEST

ALL HAZARDOUS MATERIAL ABATEMENT BY OTHERS.

COORDINATE AREAS OF DEMOLITION WITH OWNERS SCHEDULE

CONTINUOUS SEALANT AT PERIMETER OF ALL FRAMES, BOTH SIDES

OF WALL.

CONTRACTOR TO PROVIDE TEMPORARY ENCLOSURES, HEAT, AND

LIGHTING AS REQUIRED FOR INSTALLATION OF EQUIPMENT.

COORDINATE WITH ELEVATOR MANUFACTURER.

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

NOTES APPLY TO ALL LEVELS OF FACILITY. NOT ALL ELEVATOR COMPONENTS

IDENTIFIED - REFER TO SPECIFICATION FOR ADDITIONAL INFORMATION.

SEE SPECS FOR ALTERNATE 01 - ELEVATOR JACK

"M

IN

'M A

X

EXISTING BASE, CHAIRRAIL, AND TRIM TO REMAIN, VARIES PER LEVEL

KEYPLAN

N

ELEVATOR

ADMIN

R E

A R

C E

N T

E R

A N

O R

T H

B N

O R

T H

C N

O R

T H

A S

O U

T H

B S

O U

T H

C S

O U

T

HB

O

IL

E

R

P O

W E

R

LAUNDRY

WIRTH

PRE-FINISHED DRIP EDGE

PRE-FINISHED DRIP EDGE

EXISTING LINTALS

CMU BLOCK

BRICK

SUSPENDED CEILING

PL PANELS

EMBOSSED STAINLESS

STEEL PANEL

HANDRAIL

WALL FINISH -

STAINLESS STEEL

COORDINATE PANEL SIZES AND CONFIGURATION

WITH ELEVATOR MANUFACTURE

C M

B A

A R

C H

IT

E

C T

S

G R

A N

D A

V E

S P

E N

C E

R , I

A

(P

) 7

.2

.3

REVISIONS

SHEET

D A

T E

P R

O J

E C

T

PL

O

T D

AT

E

FI

LE

P

AT

H

COPYRIGHT. Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Cannon Moss Brygger & Associates is prohibited by copyright law.

IF THIS DRAWING IS NOT 30"x42" IT IS NOT TO SCALE

/1

/2

:4 1:

A

M

A u to d e sk

D o c s:

D

A S

H H

S C

H M

H I T u n n e l & E le va to r/

D A

S H

H S

C H

M H

I T u n n e l R e p a ir

R V

T

.r vt

A2.08

C H

E R

O K

E E

, I O

W A

D A

S H

H S

C H

M H

I F

O U

R C

O R

N E

R S

E L

E V

A T

O R

R E

P L

A C

E M

E N

T

IO

W

A D

A S

F L

O O

R P

L A

N S

A N

D S

E C

T

IO

N S

1/16" = 1'-0"1

BASEMENT FLOOR PLAN

1/8" = 1'-0"2

FIRST FLOOR PLAN

1/8" = 1'-0"3

SECOND FLOOR PLAN

1/8" = 1'-0"4

THIRD FLOOR PLAN

1/4" = 1'-0"5 Elevator Section E/W

1/8" = 1'-0"7

BASEMENT FLOOR PLAN

3/8" = 1'-0"8

TYP LANDING ELEVATION

1 1/2" = 1'-0"6

LOUVER INFILL

NO. DESCRIPTION DATE

3/8" = 1'-0"9

TYP CAB INTERIOR ELEVATION

EQUIPMENT IDENTIFICATION TAG. REFER TO EQUIPMENT CONNECTION SCHEDULE

DETAIL DRAWING REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE

INTERIOR ELEVATION DRAWING REFERENCE TAG

GENERAL SYMBOLS

A101

SIM

A101 1

R e f

KEYNOTE#

XXX

X

SHEET REFERENCE

SECTION CUT REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE

SHEET REFERENCE

JUNCTION BOX, CEILING OR FLOOR MOUNTED.

JUNCTION BOX, WALL MOUNTED, ELEVATION AS NOTED.

J

J

A101

SIM

1 DRAWINGS REVISION. REFER TO TITLEBLOCK FOR REVISION NAME AND DATE

RECESSED LIGHT FIXTURE, LETTER INDICATES SWITCH LEG (TYPICAL), SHADING

INDICATES EMERGENCY LIGHT (TYPICAL)

SURFACE MOUNTED STRIP FIXTURE

LINEAR PENDANT MOUNTED FIXTURE

INDUSTRIAL STRIP LIGHT FIXTURE

WALL MOUNTED STRIP LIGHT FIXTURE.

EMERGENCY LIGHT FIXTURE, WALL MOUNT, +96" OR AS NOTED

EMERGENCY LIGHT FIXTURE, CEILING MOUNT

EXIT SIGN, WALL MOUNT +96", SHADED AREAS INDICATE NUMBER OF

FACES, ARROWS INDICATE SIGN ARROWS

EXIT SIGN, CEILING MOUNT, SHADED AREAS INDICATE NUMBER OF FACES,

ARROWS INDICATE SIGN ARROWS

SINGLE POLE SWITCH, WALL MOUNT, LETTER INDICATES SWITCH LEG

THREE WAY SWITCH, WALL MOUNT, LETTER INDICATES SWITCH LEG

LIGHTING SYMBOLS

PILOT LIGHT SWITCH, WALL MOUNT, LETTER INDICATES SWITCH LEG

DIMMER SWITCH, WALL MOUNT, LETTER INDICATES SWITCH LEG

a a b

P c

D d

EMERGENCY TRANSFER DEVICE

ROUND APERTURE RECESSED DOWNLIGHT FIXTURE,

ARROW INDICATES WALLWASH

LIGHTING CONTROLS LOW VOLTAGE SWITCH, WALL MOUNT,

LETTER INDICATES SWITCH LEG, REFER TO LIGHTING CONTROLS SCHEDULE

S1 e

ETD

POWER SYMBOLS

DUPLEX RECEPTACLE, WALL MOUNTED, TAMPER-RESISTANT

DUPLEX GFCI RECEPTACLE, TAMPER-RESISTANT, WALL MOUNT,

PROTECTION INCLUDED IN DEVICE.

DUPLEX GFCI WEATHER RESISTANT RECEPTACLE WITH WEATHER-PROOF

IN-USE COVER, TAMPER-RESISTANT, WALL MOUNT

EQUIPMENT CONNECTION,

REFER TO EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE.

REFER TO PANEL SCHEDULES FOR GFCI PROTECTION WHERE REQUIRED

EQUIPMENT CONNECTION, WALL MOUNT,

REFER TO EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE.

REFER TO PANEL SCHEDULES FOR GFCI PROTECTION WHERE REQUIRED

SINGLE RECEPTACLE, WALL MOUNTED

W

SURGE PROTECTIVE DEVICE

SAFETY DISCONNECT SWITCH

PANELBOARD - SURFACE MOUNTED

PANELBOARD - RECESSED IN WALL

DISTRIBUTION PANELBOARD/SWITCHBOARD - SURFACE MOUNTED AS NOTED.

SPD

MOTOR CONNECTION,

REFER TO EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE.

REFER TO PANEL SCHEDULES FOR GFCI PROTECTION WHERE REQUIRED

M

ELECTRICAL ABBREVIATIONS

A DEVICE MOUNTED +8" ABOVE

COUNTER TOP (VERIFY LOCATION)

AFF ABOVE FINISHED FLOOR

ATS AUTOMATIC TRANSFER SWITCH

C CEILING

CB CIRCUIT BREAKER

CT CURRENT TRANSFORMER

E EXISTING ITEM TO REMAIN

EC ELECTRICAL CONTRACTOR

EM EMERGENCY LIGHT FIXTURE

ER NEW LOCATION OF EXISTING ITEM

F ROUGH IN FOR FUTURE DEVICE

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FSD FIRE SMOKE DAMPER

G GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

KVA KILO-VOLT-AMPERES

KW KILOWATTS

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MDP MAIN DISTRIBUTION PANEL

MLO MAIN LUGS ONLY

N NEW DEVICE IN EXISTING LOCATION

NIC NOT IN CONTRACT

NM NONMETALLIC

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED

CONTRACTOR INSTALLED

OFOI OWNER FURNISHED,

OWNER INSTALLED

R EXISTING ITEM TO BE REMOVED

RR EXISTING ITEM TO BE REMOVED AND

RELOCATED

RN EXISTING ITEM TO BE REMOVED AND

REPLACED WITH NEW

SCCR SHORT CIRCUIT CURRENT RATING

T TAMPER PROOF DEVICE

TCC TEMPERATURE CONTROL CONTRACTOR

TV TELEVISION

TYP TYPICAL

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLTS

VA VOLT-AMPERES

WG WIREGUARD COVER

WP WEATHERPROOF DEVICE

WR WEATHER RESISTANT DEVICE

+24" INDICATES MOUNTING HEIGHT CENTER

LINE OF DEVICE TO FINISHED FLOOR

1. PROVIDE ELECTRICAL INSTALLATION IN ACCORDANCE WITH STATE CODES.

2. THE CURRENT ADOPTED EDITION OF THE ELECTRICAL CODE IS THE STANDARD FOR THE

ELECTRICAL INSTALLATION. VERIFY WITH STATE OFFICIALS WHEN PERMITS ARE OBTAINED.

NOTIFY DESIGN TEAM OF ANY DISCREPANCIES BETWEEN THE PROJECT MANUAL OR

DRAWINGS AND THE GOVERNING CODE.

3. INSTALLATION SHALL FOLLOW REQUIREMENTS OF THE ADAAG –AMERICANS WITH

DISABILITIES ACT.

4. REFER TO PROJECT MANUAL AND PROJECT CODE REVIEW SHEET FOR LIST OF APPLICABLE

CODES.

5. PER NEC EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO

ITS CLEAR, EVIDENT AND SPECIFIC PURPOSE OR USE. CONTRACTOR TO PROVIDE FINAL

CIRCUIT IDENTIFICATION FOR ALL NEW AND MODIFIED CIRCUITS AT PROJECT COMPLETION.

CODE NOTES - ELECTRICAL

1. PROVIDE NORMAL WIRING DEVICES AS GRAY UNLESS OTHERWISE NOTED.

2. PROVIDE DEVICES COVER PLATES AS STAINLESS STEEL. MATCH WIRING DEVICES COLOR.

3. PROVIDE GFCI TYPE RECEPTACLES AT ALL LOCATIONS REQUIRED BY THE NEC.

4. INSTALL ABOVE COUNTERTOP RECEPTACLES +8” ABOVE COUNTERTOP OR AS OTHERWISE

INDICATED.

5. AT A COMMON COUNTERTOP, INSTALL ALL RECEPTACLES AND SWITCHES AT THE SAME

HEIGHT UNLESS OTHERWISE SPECIFICALLY INDICATED.

DEVICE INSTALLATION AND MATERIALS - ELECTRICAL

1. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND ELECTRICAL WORK WITH ALL

OTHER TRADES. BEGIN INSTALLATION AND ROUGH-IN ONLY AFTER PROPER AND TIMELY

COORDINATION WITH ALL TRADES ASSOCIATED WITH THE INSTALLATION IS COMPLETE.

COORDINATE WITH BUILDING STRUCTURE, ARCHITECTURE, MECHANICAL SHEET METAL, ALL

PIPING SYSTEMS, LIGHT FIXTURES, CONDUITS, CABLE TRAYS, EQUIPMENT

ACCESS/CLEARANCE, ETC. REFER TO ALL GENERAL, MECHANICAL, AND ELECTRICAL

DRAWINGS AND SPECIFICATIONS FOR THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR

REWORK OF INSTALLED EQUIPMENT RESULTING FROM INSUFFICIENT COORDINATION.

2. ELECTRICAL DRAWINGS ARE ONLY A PORTION OF THE COMPLETE SET OF PLANS AND

CONTRACT DOCUMENTS. THE ELECTRICAL SCOPE OF WORK IS DEFINED BY THE COMPLETE

SET OF CONTRACT DOCUMENTS. THIS INCLUDES BUT IS NOT LIMITED TO REFERENCING;

ARCHITECTURAL PLANS FOR DIMENSIONS AND DETAILS; EQUIPMENT PLANS FOR ROUGH-IN

REQUIREMENTS, MECHANICAL PLANS FOR EQUIPMENT SIZES AND LOCATIONS.

GENERAL NOTES - ELECTRICAL

1. INCREASE CONDUCTOR SIZES ON 20A 120V-1 PHASE CIRCUITS EXCEEDING 100 FEET TO

CENTER OF LOAD TO ACCOUNT FOR VOLTAGE DROP.

2. RACEWAYS AND BOXES ARE SHOWN DIAGRAMMATICALLY ONLY AND INDICATE GENERAL

AND APPROXIMATE LOCATIONS. LAYOUTS DO NOT ALWAYS SHOW THE TOTAL NUMBER

OF RACEWAYS OR BOXES FOR THE CIRCUITS REQUIRED, NOR ARE THE LOCATIONS OF

INDICATED RUNS INTENDED TO SHOW THE ACTUAL ROUTING OF THE RACEWAYS.

3. LIGHT FIXTURES, SWITCHES, DEVICES, ETC. ARE SHOWN IN PREFERRED LOCATION.

MODIFY CONDUIT, HANGERS, CIRCUITING, ETC. TO PROVIDE A COMPLETE AND

OPERATIONAL SYSTEM.

4. PROVIDE A DEDICATED GREEN INSULATED GROUND CONDUCTOR TO ALL DEVICES. DO

NOT USE CONDUIT SYSTEM AS THE ONLY EQUIPMENT GROUNDING METHOD.

5. PROVIDE TYPED PANEL DIRECTORY AT PROJECT COMPLETION FOR NEW PANELS AND

EXISTING PANELS WITH CIRCUITS MODIFIED DURING PROJECT. USE OWNER’S CURRENT

ROOM NUMBERS AND EQUIPMENT NAMES. PROVIDE UNIQUE CIRCUIT IDENTIFICATION

PER NEC 408.4(A)

6. CONTRACTOR IS RESPONSIBLE FOR OPENINGS IN WALLS, FLOORS, CEILINGS, AND

ROOFS THAT ARE REQUIRED TO COMPLETE THEIR SCOPE OF WORK. SEAL

PENETRATIONS IN ACCORDANCE WITH THE RATING OF THE AFFECTED ASSEMBLY.

REFER TO ARCHITECTURAL CODE PLAN FOR RATED WALLS, FLOORS, AND CEILINGS.

INSTALLATION NOTES - ELECTRICAL

SECURITY - ACCESS CONTROL:

SECURITY MANAGEMENT SYSTEM - HEAD END COMPONENTS

SECURITY MANAGEMENT SYSTEM - FIELD DEVICES

SECURITY MANAGEMENT SYSTEM - ELECTRIFIED DOOR HARDWARE

ROUGH-IN, PATHWAYS AND SLEEVES

ROUGH-IN, PATHWAYS AND SLEEVES

SECURITY - VIDEO SURVEILLANCE:

CAMERA(S)

HEAD END EQUIPMENT AND COMPONENTS

SECURITY MANAGEMENT SYSTEM - ALL CABLING

OFOI

OFCI

CFCI

OWNER FURNISHED & OWNER INSTALLED

OWNER FURNISHED & CONTRACTOR INSTALLED

CONTRACTOR FURNISHED & CONTRACTOR INSTALLED

GENERAL NOTE:

A. MATRIX IS NOT INTENDED TO BE EXHAUSTIVE TO COVER ALL MATERIALS NECESSARY FOR

SCOPE AND SHOULD ONLY BE USED TO QUICKLY IDENTIFY SYSTEMS AND RELATED

INFRASTRUCTURE INSIDE AND OUTSIDE THE BID OF THIS PROJECT. ANY ITEMS FURNISHED OR

INSTALLED BY THE BIDDING CONTRACTOR SHALL COVER ALL REQUIRED APPERTUNANCES

NECESSARY FOR A COMPLETE SYSTEM. THIS SHALL INCLUDE BUT NOT BE LIMITED TO,

EQUIPMENT, ACCESSORIES, TERMINATIONS, TERMINATION COMPONENTS, ALL FINAL

CORDAGE CONNECTIVITY, SOFTWARE, PROGRAMMING, AND THE LABOR TO INSTALL.

B. ACCESS CONTROL VENDOR TO INSTALL CABLING, FIELD DEVICES, ETC. COORDINATE EXACT

DEVICE LOCATIONS AND PATHWAYS WITH VENDOR AND CM ONSITE.

SAFETY - FIRE DETECTION AND ALARM:

ROUGH-IN, PATHWAYS AND SLEEVES

INITIATING FIELD DEVICES (SMOKE, MANUAL PULL, MONITOR MODULES)

NOTIFICATION APPLIANCES (HORNS, STROBES, SPEAKERS)

MISCELLANEOUS DEVICES (RELAYS, TEST STATION, ANNUNCIATOR)

N/A N/A N/A

N/A N/A N/A

N/A N/A N/A

OFOI OFCI CFCI

TECHNOLOGY RESPONSIBILITY MATRIX

PROVISION RESPONSIBILITIES DEFINED

RACKS, FRAMES AND ENCLOSURES

COPPER HORIZONTAL CABLING

DATA COMMUNICATIONS SWITCHES AND HUBS

ROUGH-IN, PATHWAYS AND SLEEVES

COMMUNICATIONS - TELECOM SYSTEMS:

REUSE EXISTING

REUSE EXISTING

1. MECHANICAL DEMOLITION DRAWINGS SHOWING EXISTING CONDITIONS HAVE BEEN

PREPARED BASED ON NON-DESTRUCTIVE FIELD OBSERVATION AND AS-BUILT DRAWINGS

PROVIDED BY THE OWNER. FIELD VERIFY EXISTING SYSTEMS BEFORE BEGINNING WORK.

NOTIFY ARCHITECT/ENGINEER IF EXISTING CONDITIONS ARE MATERIALLY DIFFERENT THAN

THOSE SHOWN ON THE PLANS.

2. BE FAMILIAR WITH EXISTING MECHANICAL SYSTEMS THAT WILL BE AFFECTED BY THE

DEMOLITION WORK. OBTAIN PERMISSION FROM THE OWNER'S REPRESENTATIVE TO SHUT

OFF SERVICES OR SYSTEMS THAT AFFECT AREAS BEYOND THE LIMITS OF THE IMMEDIATE

DEMOLITION AREA. INFORM THE OWNER’S REPRESENTATIVE OF THE REASON FOR AND

DURATION OF THE SHUTDOWN. MINIMIZE IMPACT TO OTHER AREAS. PROCEED WITH THE

SHUT-DOWN AFTER PERMISSION FROM THE OWNER IS GRANTED.

3. REMOVE PIPING, HANGERS, DUCTWORK, GRILLES, REGISTERS, DIFFUSERS, ETC. THAT ARE

INDICATED TO BE REMOVED IN A TIMELY MANNER IN ACCORDANCE WITH THE GENERAL

DEMOLITION SPECIFICATIONS. COORDINATE WITH THE OWNER AND OTHER CONTRACTORS.

MECHANICAL – DEMOLITION NOTES

1. COORDINATE MECHANICAL AND ELECTRICAL WORK WITH ALL OTHER TRADES. BEGIN

INSTALLATION AND ROUGH-IN AFTER COORDINATION WITH ALL TRADES ASSOCIATED WITH

THE INSTALLATION IS COMPLETE. COORDINATE BUILDING STRUCTURE, ARCHITECTURAL

ASSEMBLIES, SHEET METAL, ALL PIPING SYSTEMS, LIGHT FIXTURES, CONDUITS, CABLE

TRAYS, ETC. REFER TO ALL GENERAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND

SPECIFICATIONS FOR THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR REWORK

ASSOCIATED WITH FAILURE TO COORDINATE.

2. INCORPORATE MECHANICAL SPECIFICATIONS, DRAWINGS, STATE AND LOCAL CODES, AND

OWNER STANDARDS INTO WORK.

3. REFER TO ARCHITECTURAL SPECIFICATIONS FOR THROUGH-PENETRATION FIRESTOPPING

AND TO ARCHITECTURAL CODE PLAN FOR FIRE RATED WALLS, FLOORS, AND CEILINGS. EACH

TRADE IS RESPONSIBLE TO FIRESTOP PENETRATIONS THROUGH RATED ASSEMBLIES.

4. EACH TRADE IS RESPONSIBLE FOR MAKING PENETRATIONS WHERE REQUIRED IN EXISTING

WALLS, FLOORS, CEILINGS, AND ROOFS. MAKE PENETRATIONS NEAT. PATCH, CONCEAL, OR

CAULK OVERCUT.

5. PROVIDE MECHANICAL EQUIPMENT, SUPPORTS, HANGERS, AND ALL APPURTENANCES.

INSTALL ALL EQUIPMENT PER MANUFACTURER'S RECOMMENDATIONS. INSTALL SYSTEM TO

MEET ALL CITY AND STATE CODES AND REQUIREMENTS.

6. COVER EXPOSED WALL PENETRATIONS WITH ESCUTCHEONS OR SHEET METAL AS

APPROPRIATE.

7. CAULK ALL CONCEALED AND EXPOSED PIPING AND DUCT WALL PENETRATIONS TO PREVENT

NOISE TRANSFER BETWEEN SPACES.

8. PROVIDE FIRE CAULKING ASSEMBLIES FOR PENETRATIONS OF RATED ASSEMBLIES. REFER

TO ARCHITECTURAL DRAWINGS FOR ASSEMBLY RATINGS.

9. CONTINUE PIPE INSULATION THROUGH WALLS, FLOORS, AND CEILING PENETRATIONS

UNBROKEN.

10. ON COMPLETION OF THE INSTALLATION, COOPERATE WITH THE OWNER TO PROVIDE

TESTING, ADJUSTING, AND BALANCING TO OBTAIN PROPER OPERATION OF ALL EQUIPMENT

AND SYSTEMS. PROVIDE ALL FACILITIES AND EQUIPMENT AND COMPLETE ALL TESTS

REQUIRED FOR ADJUSTMENTS AND BALANCING TO ESTABLISH THE PROPER PERFORMANCE

OF EQUIPMENT.

11. PROVIDE WARRANTIES FOR ALL EQUIPMENT AND INSTALLATION PER THE CONTRACT

DOCUMENTS. CONDITIONING REFRIGERATION SYSTEMS SHALL BE WARRANTED FOR A

MINIMUM OF 5 YEARS, PARTS ONLY, NON-PRORATED, FROM THE DATE OF OCCUPANCY OR

SUBSTANTIAL COMPLETION, OR WHICHEVER OCCURS FIRST. THE WARRANTY SHALL COVER

COMPRESSORS, EVAPORATORS, CONDENSER COILS, HIGH AND LOW SIDE PIPING, AND

PIPING SPECIALTIES INCLUDING EXPANSION AND SOLENOID VALVES, RELIEF VALVES, FILTER

DRYER,AND SIGHT GLASSES. PRESSURE GAUGES AND PRESSURE SWITCHES ARE NOT

UNDER THE EXTENDED WARRANTY EXCEPT FOR LOSS OF REFRIGERANT AND

CONSEQUENTIAL DAMAGE TO THE SYSTEM WHICH WILL BE AN EXTENDED WARRANTY

OBLIGATION. ALL DEFECTS THAT BECOME APPARENT WITHIN THE WARRANTY PERIOD SHALL

BE REPAIRED BY THE MECHANICAL CONTRACTOR AS DIRECTED BY THE ENGINEER THROUGH

THE OWNER’S REPRESENTATIVE. WARRANTY DOES NOT OBLIGATE THE MECHANICAL

CONTRACTOR TO REPAIR DAMAGE RESULTING FROM THE OWNER’S ACCIDENT, IMPROPER

OPERATION, OR FAILURE TO PROVIDE MAINTENANCE. WARRANTY COVERS DEFECTIVE

MATERIAL AND INSTALLATION. REFER TO SPECIFICATIONS FOR ADDITIONAL DETAILS AND

OTHER WARRANTY INFORMATION.

MECHANICAL - GENERAL NOTES

1. INSTALL HEAT DETECTORS IN WORK AREAS DURING CONSTRUCTION TO MINIMIZE

FALSE TRIPS. INSTALL PERMANENT DETECTORS IN LOCATIONS SHOWN UPON

CONSTRUCTION COMPLETION.

2. INSTALL MODULES AT ELEVATOR EQUIPMENT TO PROVIDE PRIMARY RECALL,

SECONDARY RECALL, FIRE HAT AND SHUNT TRIP. PROVIDE PROGRAMMING AS

NECESSARY FOR FUNCTION SYSTEM.

3. FIRE ALARM ITEMS AND DEVICES ARE SHOWN IN SUGGESTED LOCATIONS. FINAL

LAYOUTS, LOCATIONS, AND QUANTITIES SHALL BE IN ACCORDANCE WITH APPLICABLE

CODES, MANUFACTURER’S RECOMMENDATIONS, AND EQUIPMENT LISTINGS.

COORDINATE LOCATIONS WITH LIGHTING AND AIR HANDLING SYSTEMS.

4. ALL FIRE ALARM CIRCUITRY IN EXPOSED CEILING SPACES SHALL BE IN ¾” CONDUIT PER

SPECIFICATIONS. EXPOSED CABLING SHALL NOT BE ACCEPTED.

5. ALL CONCEALED, ACCESSIBLE CEILING TILE LOCATIONS SHALL BE ALLOWED TO HAVE

OPEN AIR CABLING INSTALLED. PROVIDE J-HOOKS, BRIDLE RINGS AND ASSOCIATED

CABLE SUPPORTS TO KEEP INFRASTRUCTURE MANAGED AND OFF OF THE CEILING TILE.

6. ELECTRICAL CONTRACTOR SHALL PROVIDE FIRESTOPPING AT ALL PENETRATIONS PER

SPECIFICATION.

FIRE DETECTION & ALARM NOTES

COMMUNICATION NOTES

1. REUSE EXISTING POTS LINE IN THE ELEVATOR EQUIPMENT ROOM FOR THE ELEVATOR

TELEPHONE. REVISE LOCATION AND EXTEND AS NECESSARY FOR NEW EQUIPMENT

LOCATIONS.

2. INSTALL NEW DATA CABLING FROM IDF LOCATIONS SHOWN ON PLANS TO ELEVATOR

EQUIPMENT ROOM FOR NEW 2-WAY COMMUNICATION SYSTEM.

FIRE DETECTION AND ALARM SYMBOLS

SMOKE DETECTOR

DUCT SMOKE DETECTOR

CARBON MONOXIDE DETECTOR

HEAT DETECTOR

COMBINATION HORN WITH STROBE

COMBINATION SPEAKER WITH STROBE

STROBE

SPEAKER

ADDRESSABLE INPUT MODULE; FS - SPRINKLER WATER FLOW SWITCH,

TS - TAMPER SWITCH, PIV - POST INDICATOR VALVE

FIRE ALARM CONTROL PANEL + EMERGENCY COMMUNICATIONS PANEL

COMBINATION FIRE/SMOKE DAMPER

SMOKE DAMPER

S

S

AIM

ADDRESSABLE OUTPUT MODULE; SD - FAN SHUT DOWN RELAY, AM - AUDIO MUTEAOM

H HORN

S

SD

FSD

S

FAA

FACP

XX

XX

COMBINATION CARBON MONOXIDE / SMOKE DETECTORS

FIRE ALARM ANNUNCIATOR PANEL

REVISIONS

P

LO

T D

A T

E

F

IL

E P

A T

H

COPYRIGHT. Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Cannon Moss Brygger & Associates is prohibited by copyright law.

IF THIS DRAWING IS NOT 30"x42" IT IS NOT TO SCALE

SHEET

D A

T E

P R

O J

E C

T

/1

/2

:0 :1

A

M

A u to d e s k D o c s /D

A S

H H

S C

H M

H I T u n n e l

E le v a to r/ M

E P

T C

H M

I E le v a to r_ R

.r v t

ME0.0

C H

E R

O K

E E

, I O

W A

D A

S H

H S

C H

M H

I F

O U

R C

O R

N E

R S

E L

E V

A T

O R

R E

P L

A C

E M

E N

T

IO

W

A D

A S

M E

C H

A N

IC

A

L

E L

E C

T R

IC

A

L G

E N

E R

A L

N O

T E

S

S Y

M B

O L

S S S

S

+46"

S

1 +46"

AOMAOM

E R

RN RN

E

E

B01

ELEV

CLOSET

CORRIDOR

RN

E

E

B01

ELEV

CLOSET

CORRIDOR

E

E

RNB01

ELEV

CORRIDOR

CLOSET

RNE

R

REMOVE EXISTING DETECTOR. INSTALL

HEAT DETECTOR DURING CONSTRUCTION.

INSTALL NEW DETECTOR UPON PROJECT COMPLETION.

TYPICAL FOR EACH ELEVATOR LOBBY/LANDING.

INSUFFICIENT

LIGHTING AT LANDING.

INSTALL NEW FIXTURE

IN EXISTING LOCATION

REMOVE EXISTING CAMERA.

REINSTALL IN CAB UPON PROJECT COMPLETION.

EXITING TERMINATION AND SYSTEM TO REMAIN INTACT

EXISTING CAMERA SYSTEM TO REMAIN

REMOVE EXISTING DETECTOR. INSTALL

HEAT DETECTOR DURING CONSTRUCTION.

INSTALL NEW DETECTOR UPON PROJECT COMPLETION.

TYPICAL FOR EACH ELEVATOR LOBBY/LANDING.

RN

R

R

R

R

RN

RN

R

RN

EXISTING FIXTURE AT PIT LEVEL TO REMAIN

RN

B04

CLOSET

B01

ELEV

B02

ELEV. EQUIP.

B03

CORRIDOR

RR

(x3)

A. DEMOLITION DRAWINGS PRESENT LAYOUT OF EXISTING

CONDITIONS AND MAJOR MECHANICAL/ELECTRICAL ITEMS.

FIELD VERIFY EXISTING CONDITIONS AND BECOME FAMILIAR

WITH EXISTING ELECTRICAL SYSTEM AND DEMOLITION SCOPE

BEFORE WORK BEGINS.

B. ADDITIONAL COMPONENTS MAY EXIST WHICH ARE NOT SHOWN.

HANDLE SUCH ITEMS IN A MANNER SIMILAR TO THOSE ITEMS

WHICH ARE SHOWN.

C. REMOVE ELECTRICAL FACILITIES AND CLEAR THE AREA TO

RECEIVE THE NEW WORK.

a. REMOVE ALL CONDUIT, WIRE, BOXES, ETC., AS

REQUIRED BY WALL AND CEILING DEMOLITION.

b. IDENTIFY THE LOCATION OR ITEMS SERVED FOR ALL

DISCONNECTED BRANCH CIRCUITS BEFORE

DEMOLITION. MAINTAIN CIRCUITS SERVING AREAS

BEYOND THE DEMOLITION AREA.

c. REMOVE AND REINSTALL CEILING TILES AS REQUIRED

TO REMOVE THE ELECTRICAL FACILITIES NOTED.

REPLACE CEILINGS TILES DAMAGED DURING

DEMOLITION.

d. KEEP EXISTING SYSTEMS OPERATIONAL DURING ALL

PHASES OF CONSTRUCTION UNLESS NECCESARY FOR

DEMOLITION.

e. OBTAIN OWNER'S PERMISSION TO SHUT OFF SERVICES

OR SYSTEMS WHICH MAY AFFECT OTHER AREAS

BEYOND DEMOLITION AREA. INFORM OWNER AS TO THE

REASON FOR AND THE DURATION OF THE SHUTDOWN.

f. REPAIR AT CONTRACTORS EXPENSE ANY DAMAGED

CONDUIT OR WIRE NOT IDENTIFIED FOR DEMOLITION.

g. INSTALL BLANK COVERPLATES/COVERS OVER

OPENINGS AT REMOVED DEVICE LOCATIONS.

D. ALL WIRING FOR REMODELED AREAS SHALL BE NEW UNLESS

SPECIFICALLY NOTED OTHERWISE.

E. PROTECT EXISTING DEVICES IDENTIFIED TO REMAIN OR BE

RELOCATED. IF AN EXISTING DEVICE CANNOT BE REINSTALLED

NOTIFY DESIGN TEAM DURING DEMOLITION. REPLACE

FUNCTIONING ITEMS DAMAGED DURING DEMOLITION.

F. REMOVED/DEMOLISHED EQUIPMENT REMAINS THE PROPERTY

OF THE OWNER UNLESS OTHERWISE NOTED. VERIFY OWNERS

SALVAGE SELECTIONS AND DISPOSE ALL OTHER MATERIALS.

G. PLAN ABBREVIATIONS:

E - EXISTING ITEM TO REMAIN

ER - NEW LOCATION OF EXISTING ITEM

N - NEW ITEM IN EXISTING LOCATION

R - EXISTING ITEM TO BE REMOVED, PATCH AND/OR

COVER

RN - REPLACE EXISTING WITH NEW

RR - EXISTING ITEM TO BE REMOVED AND RELOCATED

ELECTRICAL DEMOLITION NOTES

FIELD VERIFY AND REMOVE

2" ELEVATOR SUMP PUMP

DISCHARGE BACK TO MAIN

AND CAP.

2" P

D

P

D REMOVE EXISTING PUMP. REFER TO

MECHANICAL/PLUMBING NOTES FOR SCOPE OF

CLEANING AND REPAIRS NEEDED.

REMOVE ABANDONED SUMP PUMP

DISCHARGE PIPE BACK TO

ELEVATOR PIT FLOOR AND CAP.

REVISIONS

P

LO

T D

A T

E

F

IL

E P

A T

H

COPYRIGHT. Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Cannon Moss Brygger & Associates is prohibited by copyright law.

IF THIS DRAWING IS NOT 30"x42" IT IS NOT TO SCALE

SHEET

D A

T E

P R

O J

E C

T

/1

/2

:0 :1

A

M

A u to d e s k D o c s /D

A S

H H

S C

H M

H I T u n n e l

E le v a to r/ M

E P

T C

H M

I E le v a to r_ R

.r v t

ME1.1

C H

E R

O K

E E

, I O

W A

D A

S H

H S

C H

M H

I F

O U

R C

O R

N E

R S

E L

E V

A T

O R

R E

P L

A C

E M

E N

T

IO

W

A D

A S

M E

C H

A N

IC

A

L

E L

E C

T R

IC

A

L D

E M

O L

IT

IO

N P

L A

N S

1/4" = 1'-0"

ROOF DEMO PLAN

1/4" = 1'-0"

THIRD FLOOR DEMO PLAN

1/4" = 1'-0"

SECOND FLOOR DEMO PLAN

1/4" = 1'-0"

FIRST FLOOR DEMO PLAN

1/4" = 1'-0"

BASEMENT DEMO PLAN

R

1/4" = 1'-0"

BASEMENT PLAN - MECH DEMO

S

S

S

+46"

1 +46"

S

S

W

AOMAOM

FACPFACPFACP

N

F2

EL-1

E

F2

EL-1

N

B01

ELEV

CORRIDOR

CLOSET

F2

EL-1

N

CORRIDOR

B01

ELEV

CLOSET

F2

EL-1

B01

ELEV

CORRIDOR

CLOSET

N

E

E

EXISTING CAMERA REINSTALLED

IN CAB

EXISTING LINEAR FIXTURE TO REMAIN.

CONNECT TO NEW LIGHTING CIRCUIT

AND CONTROLS.

N

N

N

N

F1

DEDICATED SUMP PUMP RECEPTACLE

2-WAY COMMUNICATION

120V CIRCUIT AND FUSED DISCONNECT.

INSTALL RATH SYSTEM AND INTEGRATE

WITH EXISTING SYSTEM ONSITE.

ELEVATOR 120V FUSED

DISCONNECT FOR AUX.

CAB POWER

ELEVATOR BREAKER TO BE PROVIDED

IN PANEL AS LOCKABLE.

F1

EL-7

N

F2

EL-1

SSI

SSO

B04

CLOSET

B03

CORRIDOR

B01

ELEV

B02

ELEV. EQUIP.

INTERCEPT AND

CUT BACK EXISTING

SURFACE MOUNTED CONDUIT

TO FEED NEW FIXTURE

END TO END.

N

EL-9

EL-3

INSTALL NEW

CIRCUIT TO

RECEPTACLE

EL-5

EL-13,15

EL-2

EL-4 E1

EL-7

PRIMARY, SECONDARY RECALL,

AND FIRE HAT. RELOCATE

EXISTING DEVICES AND EXTEND

WIRING AS NECESSARY TO NEW

ELEVATOR CONTROLLER,

INTEGRATE, AND REPROGRAM.

PANEL EL

EL-11

LABEL FRONT OF PANEL

"PANEL IS FOR ELEVATOR

EQUIPMENT ONLY"

SSI

SSO

REF LINES. SIZE AND ROUTE PER MFR

RECOMMENDATIONS. SINGLE LINE

SHOWN REPRESENTS A LINE SET

(2 PIPES).

1-1/2" PD TO DAYLIGHT OUTSIDE,

TERMINATE WITH DOWNTURNED

ELBOW WITH BUG SCREEN.

PROVIDE NEW SUMP PUMP SP-1

TO GO IN EXISTING SUMP PIT.

EXISTING SUMP PIT GRATE TO

REMAIN. PUMP SHALL ALARM THE

DDC SYSTEM WHEN OPERATING.

T

OFFSET UNIT OFF THE

WALL WITH UNISTRUT

B01

ELEV

B02

ELEV. EQUIP.

B03

CORRIDOR

B04

CLOSET

CONDENSING UNIT TO BE

WALL MOUNTED, INSTALL

MINIMUM 3' ABOVE GROUND.

2" PD TO DAYLIGHT OUTSIDE,

TERMINATE WITH DOWNTURNED

ELBOW WITH BUG SCREEN.

2" PD

SP

CLEAN SUMP PIT FROM ALL

DEBRIS AND EXISTING WATER.

CYCLE THE SUMP PUMP

THROUGH 3 CLEAN WATER

CYCLES. WATER MUST BE

DUMPED BY CONTRACTOR SINCE

IT WILL HAVE HYDRAULIC FLUID

MIXED IN.

OIL ALERT CONTROL PANEL

OIL ALERT ALARM PANEL

ME2.1

EXISTING NOTIFIER

FIRE ALARM CONTROL

PANEL

EXISTING IDF ROOM.

EXISTING PANEL LOCATION OF PANEL 1

AND RC-B-SP2.

INSTALL NEW CIRCUITS FROM PANEL 1.

REUSE EXISTING CIRCUITS IN SPACES

11, 13, 21, 23, 25.

EXISTING PANEL LOCATION

RCB.P1 FEEDING ELEVATOR.

REMOVE CONDUCTORS, OPEN BREAKER

AND LABEL AS SPARE.

B07

ELEC

B02

ELEV. EQUIP.

B01

ELEV

B04

CLOSET

B03

CORRIDOR

B05

CORRIDOR

B06

DATA

B03

CORRIDOR

APPROXIMATE LOCATION OF

2000A DISTRIBUTION PANEL

APPROXIMATE FEEDER ROUTING

THROUGH THE BUILDING. VERIFY

ROUTING AND COORDINATE

EXACT LOCATION WITH OWNER

IN THE FIELD.

INSTALL (4) #3/0 CU + (1) #4 GND IN 2" CONDUIT

FROM DISTRIBUTION TO NEW PANEL EL.

POWER GENERAL NOTES

A. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND

ELECTRICAL WORK WITH ALL OTHER TRADES. NO ASPECT OF A

SYSTEM INSTALLATION OR ITS ROUGH-IN SHALL COMMENCE UNTIL

PROPER AND TIMELY COORDINATION WITH ALL TRADES ASSOCIATED

WITH THE INSTALLATION HAS TRANSPIRED. ITEMS TO BE

COORDINATED SHALL INCLUDE BUT NOT BE LIMITED TO: BUILDING

STRUCTURE, SHEET METAL, PIPING SYSTEMS, LIGHT FIXTURES,

CONDUITS, CABLE TRAYS, ETC. REFER TO ALL GENERAL,

MECHANICAL, AND ELECTRICAL DRAWINGS AND SPECIFICATIONS FOR

THIS PROJECT.

B. COORDINATE ELECTRICAL REQUIREMENTS FOR MECHANICAL UNITS

WITH MECHANICAL CONTRACTOR AND FINAL MECHANICAL SHOP

DRAWINGS.

C. PROVIDE PENETRATIONS REQUIRED FOR ROUTING RACEWAYS

THROUGH THE BUILDING. COORDINATE FIRE RATED WALL

PENETRATIONS AND PROVIDE CONDUIT SLEEVES AND FIRE

STOPPING TO MAINTAIN RATING.

A. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND

ELECTRICAL WORK WITH ALL OTHER TRADES. NO ASPECT OF A

SYSTEM INSTALLATION OR ITS ROUGH-IN SHALL COMMENCE

UNTIL PROPER AND TIMELY COORDINATION WITH ALL TRADES

ASSOCIATED WITH THE INSTALLATION HAS TRANSPIRED. ITEMS

TO BE COORDINATED SHALL INCLUDE BUT NOT BE LIMITED TO:

BUILDING STRUCTURE, SHEET METAL, ALL PIPING SYSTEMS,

LIGHT FIXTURES, CONDUITS, CABLE TRAYS, ETC. REFER TO ALL

GENERAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND

SPECIFICATIONS FOR THIS PROJECT

B. UNLESS NOTED OTHERWISE, CONNECT ALL EMERGENCY

BATTERY FIXTURES WITH AN UN-SWITCHED LEG OF THE

LIGHTING CIRCUIT THAT SERVES THE FIXTURES SPACE.

MAINTAIN NORMAL SWITCHING SCHEME OF EMERGENCY

FIXTURES UNDER NORMAL OPERATION.

LIGHTING GENERAL NOTES

REVISIONS

P

LO

T D

A T

E

F

IL

E P

A T

H

COPYRIGHT. Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Cannon Moss Brygger & Associates is prohibited by copyright law.

IF THIS DRAWING IS NOT 30"x42" IT IS NOT TO SCALE

SHEET

D A

T E

P R

O J

E C

T

/1

/2

:0 :2

A

M

A u to d e s k D o c s /D

A S

H H

S C

H M

H I T u n n e l

E le v a to r/ M

E P

T C

H M

I E le v a to r_ R

.r v t

ME2.1

C H

E R

O K

E E

, I O

W A

D A

S H

H S

C H

M H

I F

O U

R C

O R

N E

R S

E L

E V

A T

O R

R E

P L

A C

E M

E N

T

IO

W

A D

A S

M E

C H

A N

IC

A

L

E L

E C

T R

IC

A

L F

L O

O R

P L

A N

S

1/4" = 1'-0"

ROOF CONNECTING

1/4" = 1'-0"

THIRD FLOOR PLAN

1/4" = 1'-0"

SECOND FLOOR PLAN

1/4" = 1'-0"

FIRST FLOOR PLAN

1/4" = 1'-0"

BASEMENT PLAN

1/4" = 1'-0"

BASEMENT PLAN - MECH

1/16" = 1'-0"

BASEMENT AREA ELECTRICAL PLAN

NO. DESCRIPTION DATE

NOT TO SCALE

DISTRIBUTION PANEL

INSTALL NEW 200A 3P BREAKER

IN PANEL FOR NEW ELEVATOR

BRANCH PANEL

COORDINATE DOWNTIME OF DISTRIBUTION PANEL WITH DCI GROUP AND OWNER A MINIMUM OF 7 DAYS IN ADVANCE. CONTRACTOR IS ALLOWED UP TO (1) 2 HOUR SHUTDOWNS OF THE DISTRIBUTION PANEL DURING THE COURSE OF CONSTRUCTION. SHUTDOWNS TO TAKE

PLACE BETWEEN THE HOURS OF 5AM AND 7AM ON A WEEKDAY.

ROUTE LINE SETS AND ELECTRICAL WIRES THROUGH WALL.

SEAL PENETRATIONS WATERTIGHT.

BOLTED OR WELDED 2X2-1/4" STEEL ANGLE. ANCHOR TO EXTERIOR WALL.

BUILDING EXTERIOR

CONDENSING UNIT

SECURE CONDENSING UNIT

TO ANGLE BRACING. PROVIDE

NECESSARY SUPPORT AS NEEDED.

MAINTAIN MFR'S RECOMMENDED

CLEARANCES (TYP.)

SECURE/ANCHOR WIRING AND LINE

SETS OFF EXTERIOR OF BUILDING PER

MFR'S RECOMMENDATIONS

NOTE:

REFER TO MANUFACTURER'S RECOMMENDATIONS FOR MOUNTING AND BRACING INSTALLATION. DETAIL IS CONCEPTUAL. PROVIDE APPROPRIATE ANCHORING HARDWARE FASTENERS FOR MOUNTING OF ANGLE TO

EXTERIOR SURFACE.

1"

PIPE SUPPORT

SEAL PIPE PENETRATION PER

SPECIFICATIONS

PUMPED CONDENSATE DRAIN PIPE FROM

SPLIT SYSTEM. SEE DRAWINGS FOR PIPE

SIZE AND LOCATION

STANDARD SHORT RADIUS ELBOW

FINE MESH STAINLESS STEEL

SCREEN. FASTEN TO PIPE WITH

STAINLESS STEEL HOSE CLAMP.

FINISHED GRADE

M

IN

CONCRETE SPLASH PAD

ELEVATOR PIT

BOTTOM FLOOR CEILING

TOP FLOOR

TOP FLOOR CEILING

KEY NOTES:

FUSED, LOCKABLE MAIN DISCONNECT SWITCH AND DEDICATED

CAT6 DATA TERMINATION TO SERVE ELEVATOR MAIN POWER.

PROVIDED WITH NO/NC LOW VOLTAGE CONTACTS.

FUSED, LOCKABLE 120V/1POLE DISCONNECT SWITCH TO SERVE

ELEVATOR AUXILLIARY LIGHTING/VENTILATION,

DEDICATED CIRCUIT 120V DUPLEX GFCI MAINTENANCE

RECEPTACLE WITHIN MACHINE ROOM SPACE ADJACENT TO

DISCONNECTS.

FIRE ALARM SYSTEM HAT FLASH, PRIMARY RECALL, SECONDARY

RECALL.

S

HEAT & SMOKE DETECTORS INSTALLED AT TOP OF HOISTWAY.

ELEVATOR HOISTWAY LIGHTING. TYP.

PROVIDE HOISTWAY LIGHTING CONTROLS THREE WAY SWITCHES AT

BOTTOM AND TOP FLOOR HOISTWAY ENTRIES. WHERE MULTIPLE CARS

SHARE A COMMON HOISTWAY, PROVIDE 4 WAY SWITCHES AND PROVIDE

SWITCH AT EACH CARS BOTTOM AND TOP FLOORS. SWITCH SHALL

CONTROLS ALL LIGHTING IN HOISTWAY AND PIT

S

LOBBY, TOP FLOOR

TOP OF HOISTWAY

HOISTWAY LIGHTING SWITCH

S

ELEVATOR LOBBY SMOKE DECTOR.

<21' FROM CENTERLINE OF ELEVATOR

DOOR. TYP FOR EVERY LOBBY.

ELEVATOR LOBBY SMOKE DECTOR.

<21' FROM CENTERLINE OF ELEVATOR

DOOR. TYP FOR EVERY LOBBY.

LOBBY, BOTTOM FLOOR S

HEAT AND SMOKE DETECTOR WITHIN

ELEVATOR MACHINE ROOM.

MACHINE ROOM

HOISTWAY LIGHTING SWITCH

120V DEDICATED CIRCUIT PIT SUMP

PUMP SIMPLEX RECEPTACLE

120V DEDICATED CIRCUIT PIT

MAINTENANCE GFCI DUPLEX RECEPTACLE

BOTTOM FLOOR

TYPICAL ELEVATOR HOISTWAY ELEVATION TYPICAL ELEVATOR MACHINE ROOM

ELEVATOR

MAIN POWER

DISCONNECT

ELEVATOR

CONTROL

PANEL

ELEVATOR MACHINE

ROOM LIGHTING.

DEDICATED CIRCUIT. TYP.

AOM

FIRE ALARM

SYSTEM RELAYS

MACHINE ROOM

LIGHTING SWITCH

ELEVATOR

AUX POWER

DISCONNECT

ELEVATOR CAB

RESCUE ASSISTANCE

SYSTEM DISCONNECT

FUSED, LOCKABLE 120V/1POLE DISCONNECT SWITCH AND

DEDICATED CAT6 DATA TERMINATION TO SERVE ELEVATOR CAB

INTERNAL RESCUE ASSISTANCE SYSTEM.

MAINTENANCE

RECEPTACLE

ELEVATOR HOISTWAY LIGHTING POWERED BY DEDICATED

CIRCUIT. FOR EACH CAR, PROVIDE LIGHT FIXTURE AT TOP OF

HOISTWAY, PIT, AND AT EACH FLOOR. FIXTURES ABOVE PIT

LOCATED TO ILLUMINATE TOP OF CAR AT EACH STOP, TYPICAL 10'

ABOVE EACH LEVEL.

EXISTING FIXTURE TO REMAIN

LOCKABLE ELEVATOR

BREAKER IN PANEL EL

NO/NC LV CONTACTS

208V/3PH

LV

ELEVATOR

CONTROLLER

120V/1PH 120V/1PHELEVATOR AUXILARY

DISCONNECT SWITCH

FUSED/LOCKABLE

20A/1P DEDICATED CIRCUIT

120V/1PH 120V/1PHELEVATOR INTERNAL

RESCUE ASSISTANCE

DISCONNECT SWITCH

FUSED/LOCKABLE

20A/1P DEDICATED CIRCUIT

LV/CAT6POTS LINE FROM

BUILDING MDF

1LV/CAT6

LVFIRE ALARM

CONTROL PANEL

LV

LV/CAT6CAT6 FROM

BUILDING MDF

1LV/CAT6

AOM

HAT FLASH, PRIMARY,

SECONDARY RECALL

HOISTWAY LIGHTINGDEDICATED 20A/1P CIRCUIT

PIT GFCI DUPLEXDEDICATED 20A/1P CIRCUIT

MACHINE ROOM GFCI DUPLEXDEDICATED 20A/1P CIRCUIT

PIT SUMP PUMP SIMPLEXDEDICATED 20A/1P CIRCUIT

MACHINE ROOM LIGHTINGDEDICATED 20A/1P CIRCUIT

MACHINE ROOM HVACDEDICATED 208V-35A/2P CIRCUIT

120V/1PH

120V/1PH

120V/1PH

120V/1PH

120V/1PH

208V/1PH

TYPICAL ELEVATOR SYSTEMS WIRING DIAGRAM

INSTALL NEW CONDUCTORS

(3) #1/0 + (1) #6 GND IN 2" C

SUMP PUMP SCHEDULE

REFERENCE SP-1

MANUFACTURER HYDOMATIC

MODEL # SPD

SERVES ELEVATOR PIT

CONFIGURATION SINGLE

GPM 50

BASIN TYPE EXISTING CONCRETE

BASIN SIZE (DIAM x HEIGHT) EXISTING 36x48

FT HEAD 25

HP 1

VOLTAGE/PH 120/1

NOTES 1,2,3,4

NOTES:

1. PROVIDE WITH WATERPROOF POWER CABLE, VERIFY FINAL LENGTH. MINIMUM 20 FT.

2. PROVIDE WITH INTEGRAL FLOAT SWITCH OR PIGGY BACK FLOAT.

3. INSTALL TO MEET STATE ELEVATOR CODE REQUIREMENTS.

4. PROVIDE WITH OIL MINDER SYSTEM.

SPLIT SYSTEM INDOOR UNIT SCHEDULE

REFERENCE SSI-1

MANUFACTURER MITSUBISHI

MODEL # PKA-A24NL

TYPE WALL MOUNT

WEIGHT (LBS) 46

DIMENSIONS - L x W x D (INCHES) 46 x 12 x 14

NOMINAL CAPACITY (TONS) 2.00

MAX UNIT AIRFLOW (CFM) 775

COOLING CAPACITY - RATED (BTU/H) 24,000

HEATING CAPACITY - RATED (BTU/H) N/A

REFRIGERANT TYPE R454B

VOLTAGE - PH 208 - 1

ELECTRICAL DATA

MCA 1.00

MOCP SEE SSO SCHEDULE

NOTES 1,2,3,4

NOTES:

1. PROVIDE WITH REMOTE WALL MOUNTED THERMOSTAT. WIRING BY M.C.

2. INDOOR UNIT RECEIVES POWER FROM OUTDOOR UNIT BY INTERCONNECTED WIRING

PROVIDED WITH UNIT, WIRING INSTALLATION AND DISCONNECT BY E.C.

3.COOLING RATED CAPACITY IS BASED ON THE FOLLOWING CONDITIONS. INDOOR: 80°F/67°

FF, OUTDOOR: 95°F/75°F

4. PROVIDE FILTER AND CONDENSATE PUMP WITH UNIT.

5. UNIT IS COOLING ONLY.

SPLIT SYSTEM OUTDOOR UNIT SCHEDULE

REFERENCE SSO-1

MANUFACTURER MITSUBISHI

MODEL # PUY-AH24NL

SERVES SSI-1

WEIGHT (LBS) 155

DIMENSIONS W/ CURB & ACCESSORIES - L x W x H (INCHES) 37 x 14 x 38

NOMINAL CAPACITY (TONS) 2.00

COOLING CAPACITY - RATED (BTU/H) 24,000

HEATING CAPACITY - RATED (BTU/H) N/A

REFRIGERANT TYPE R454B

COMPRESSOR QUANTITY 1

EFFICIENCY - SEER2 21.1

ELECTRICAL DATA

VOLTAGE - PH 208 - 1

MCA 22

MOCP 37

NOTES 1,2,3,4

NOTES:

1. DISCONNECT SHALL BE PROVIDED / INSTALLED BY E.C.

2. UNIT TO BE MOUNTED ON EXTERIOR SIDEWALL. REFER TO INSTALLATION DETAIL ON PLANS.

3. REFER TO SPLIT SYSTEM INDOOR UNIT SCHEDULE FOR CAPACITY RATING CONDITIONS.

4. SYSTEM REQUIRES LOW AMBIENT AIR COOLING OPERATION (-20 °F), PROVIDE LOW AMBIENT

WIND BAFFLES, SNOW AND HAIL GUARDS.

REVISIONS

P

LO

T D

A T

E

F

IL

E P

A T

H

COPYRIGHT. Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Cannon Moss Brygger & Associates is prohibited by copyright law.

IF THIS DRAWING IS NOT 30"x42" IT IS NOT TO SCALE

SHEET

D A

T E

P R

O J

E C

T

/1

/2

:0 :2

A

M

A u to d e s k D o c s /D

A S

H H

S C

H M

H I T u n n e l

E le v a to r/ M

E P

T C

H M

I E le v a to r_ R

.r v t

ME3.1

C H

E R

O K

E E

, I O

W A

D A

S H

H S

C H

M H

I F

O U

R C

O R

N E

R S

E L

E V

A T

O R

R E

P L

A C

E M

E N

T

IO

W

A D

A S

M E

C H

A N

IC

A

L

E L

E C

T R

IC

A

L D

E T

A

IL

S

NTS

WALL MOUNTED CONDENSING UNIT

DETAIL

NTS

CONDENSATE DRAIN DISCHARGE

PIPING DETAIL

NOT TO SCALE

ELEVATOR SYSTEM DETAIL

NOT TO SCALE

ELEVATOR SYSTEM DETAIL

HOA HAND-OFF-AUTO VFD VARIABLE FREQUENCY DRIVE 8. INCLUDE AUXILIARY CONTACTS AND LOW-VOLTAGE WIRING TO AUXILIARY EQUIPMENT THAT RUNS IN TANDEM WITH EQUIPMENT, (I.E. 120V DAMPERS WITH 480V MOTORS).

GF GROUND FAULT CIRCUIT INTERRUPTION TS TOGGLE SWITCH 7. VERIFY ALL EQUIPMENT LOCATIONS WITH THE ASSOCIATED SUB-CONTRACTOR.

FDS FUSED DISCONNECT SWITCH, HEAVY DUTY TOR TIME DELAY OFF RELAY 6. PROVIDE HEAVY DUTY DISCONNECTS RATED FOR THE INSTALLED ENVIRONMENT; NEMA 1 INDOORS, MINIMUM NEMA 3R OUTDOORS.

FAR FIRE ALARM SHUTDOWN RELAY ST SHUNT TRIP 5. INSTALL DISCONNECTS TO ALLOW EQUIPMENT REMOVAL WITHOUT DISCONNECT REMOVAL AND TO MINIMIZE WIRE LENGTH.

ECB ENCLOSED CIRCUIT BREAKER SS START/STOP PUSHBUTTON

CP CORD AND PLUG PROVIDED WITH UNIT SSP START/STOP PUSHBUTTON WITH PILOT 4. DO NOT RELEASE ELECTRICAL DISTRIBUTION EQUIPMENT UNTIL ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS HAVE BEEN SUBMITTED AND APPROVED. MAKE MINOR ADJUSTMENTS TO BREAKER SIZES, DISCONNECT SIZES, ETC PRIOR TO SUBMITTAL

RELEASE.

CSD COMBINATION STARTER/DISCONNECT SD SUPPLY AIR DUCT DETECTOR

CB CIRCUIT BREAKER IN PANEL RSR RUN STATUS RELAY , NORMALLY OPEN 3. REVIEW EQUIPMENT SHOP DRAWINGS FOR COMPLIANCE AND COORDINATION WITH ELECTRICAL CONNECTIONS. NOTIFY ENGINEER IF CHANGES TO ELECTRICAL CONNECTIONS, WIRING, AND BREAKER REQUIREMENTS ARE NECESSARY.

BO PROVIDED BY OTHERS RF RETURN AIR DUCT DETECTOR

4X NEMA 4X ENCLOSURE PFS PLUG FUSE WITH INTEGRATED SWITCH

4 NEMA 4 ENCLOSURE NFD NON-FUSED DISCONNECT SWITCH, HEAVY DUTY 2.