RFB952700-01 - Drawings.pdf
PDF 7 MB Posted
- Solicitation number
- RFB952700-01
- Issued by
- Carroll County, Iowa
About this file
This file comprises architectural and construction drawings for the Iowa Department of Administrative Services (DAS) at the Cherokee Mental Health Institute (CHMHI) related to an elevator replacement project designated RFB952700-01. The project involves the replacement of Elevator F in the Four Corners area of the CHMHI facility located in Cherokee, Iowa, including associated mechanical, electrical, and plumbing (MEP) upgrades to meet current code requirements. The scope of work encompasses removal and replacement of the existing hydraulic elevator car, operating panels, traveling cables, landing buttons, power unit components, hoistway doors, frames, handrails, flooring, and ceiling, along with new pit switches, door safety devices, emergency signage, and code date plates. The facility is a multi-story healthcare building (I-2 occupancy classification) with four floors, approximately 40 feet in height, requiring compliance with 2024 International Building Code, 2024 International Fire Code, 2012 International Energy Conservation Code, 2024 International Existing Building Code, 2012 NFPA 101 Life Safety Code, and 2010 ADA Standards. The project documents are 100 percent construction documents prepared by CMBA Architects (Adam Van Gorp, AIA, License #07319) with mechanical and plumbing engineering by Chad D. Bass, PE (License #P21397) and electrical engineering by Eric P. Heynen, PE (License #P24706).
The drawings include comprehensive details for architectural, mechanical, electrical, fire alarm, and communication system integration, with the project dated August 6, 2026, and plotted August 19, 2026. The construction scope requires coordination among multiple trades including HVAC, plumbing, electrical, and fire detection systems, with specific requirements for fire-rated wall penetrations, emergency lighting, automatic recall functionality, heat detection during construction with permanent detectors upon completion, and integration with existing building systems. Key mechanical work includes sump pump installation and cleaning, refrigeration system installation with minimum five-year warranty coverage, and condensing unit exterior mounting. Electrical work encompasses new panel installation (Panel EL, 200-amp, 3-phase breaker), dedicated receptacles, emergency systems integration, data cabling for two-way communications, and fire alarm module installation. The project requires field verification of existing conditions, coordination with the elevator manufacturer, temporary enclosures and heating during installation, and adherence to State of Iowa administrative rules governing construction standards and code compliance.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFB952700-01 - Notice to Bidders.pdf | ||
| RFB952700-01 - Addendum 01.pdf | ||
| RFB952700-01 - Bid Form.pdf | ||
| RFB952700-01 - Project Manual.pdf | ||
| IMPACS Electronic Procurement System.html | HTML file | |
| 1437923-event.pdf | ||
| Bid Opening - Microsoft Teams Meeting.html | HTML file |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EARTH
SITE SPOT ELEVATION
NEW FINISH
SPOT GRADE
NEW / EXISTING WALL CONSTRUCTION COLUMN GRID LINE
NEW AND EXISTING
FINISH SPOT
GRADE
TOP OF CURB
BOT. OF CURB
7.3
N:
7.3
E:
4.8
TC:
7.3
BC:
4.8
EXISTING CONTOUR LINE
NEW CONTOUR LINE
APPROX. TEST BORING LOCATION
PROPERTY LINE
CENTER LINES/ PROJECTED LINES
MATCH LINE
LEVEL LINE
MAIN FLOOR
ELEV. 110'- 0"
ROOM NAME AND NUMBER
DOOR NUMBER
ROOM NUMBER
ALPHABET CHARACTERS USED TO
DISTINGUISH BETWEEN MULTIPLE
DOORS THAT ARE ASSOCIATED WITH
PARTICULAR ROOMS
WINDOW TYPE
KEY NOTES
INDICATES A NOTE FOR A SPECIFIC ITEM
ALL KEY NOTES ARE COMPILED UNDER THE TITLE
BAR "KEY NOTES".
BUILDING SECTION / WALL SECTION
SECTION DIRECTION
DETAIL NUMBER
SHEET NUMBER
DETAILS
DETAIL NUMBER
SHEET NUMBER
EXTERIOR ELEVATION
REVISION MARKER
SHEET NUMBER
ELEVATION NUMBER
ELEVATION DIRECTION
NEW
EXISTING
(SCREENED)
A1.01 1
XX
A
A
A1.01
SIM
NEW
EXISTING
(SCREENED)
OR
INTERIOR ELEVATION
A1.01 1
GRAPHIC SYMBOLS
MATERIAL INDICATIONS
NEW EXISTING
A
A1.01
SIM
SHEET NUMBER
ELEVATION NUMBER
ROOM NAME
150 SF
101 ROOM NUMBER
ROOM SQUARE FOOTAGE
SPOT ELEVATION
8'-0"
TOILET ACCESSORIES TAG
A
WALL TAG ASSEMBLY TYPE TAG
METAL STUDS
METAL SECTION
CMU (STD. WT.)
WOOD STUDS
PLYWOOD
INSULATION
(BLANKET OR BATT)
GLASS FIBER REINFORCED
GYPSUM BOARD
GRAVEL / SAND FILL
CONCRETE
BRICK
STONE
FINISHED WOOD
RIGID INSULATION
SEALANT
GYPSUM BOARD
EXISTING CONSTRUCTION
METAL (LARGE SCALE)
WOOD BLOCKING
ACOUSTICAL CEILING
ELEVATION DIRECTION
W1
101A
B-3
W
B
F
K
ROOM NAME
WALLS
BASE
FLOOR
NOTE
ROOM FINISH TAG
ROOM NAME
ROOM NUMBER
ROOM WALL FINISH
ROOM WALL BASE FINISH
ROOM FLOOR FINISH
ROOM KEYNOTES
MINERAL WOOL SPRAY FOAM AIR SEAL
ABBREVIATIONS
AB AIR BARRIER
AFF ABOVE FINISH FLOOR
ACT ACOUSTICAL CEILING TILE
ALT. ALTERNATE
ALUM. ALUMINUM
APPROX. APPROXIMATE
ARCH. ARCHITECT (URAL)
AVB AIR AND VAPOR BARRIER
BD. BOARD
BES BUILDING ENVELOPE SEALANT
BG BUMPER GUARD
BGW BELOW GRADE WATERPROOFING
MEMBRANE
B.O. BOTTOM OF
BRG. BEARING
CC CUBICLE CURTAIN
CFCI CONTRACTOR FURNISHED-CONTRACTOR
INSTALLED
CG CORNER GUARD
CJ CONTROL JOINT
CL CENTERLINE
CLG. CEILING
CMU CONCRETE MASONRY UNIT
COL. COLUMN
CONC. CONCRETE
CONST. CONSTRUCTION
CONT. CONTINUOUS
CORR. CORRIDOR
CPT. CARPET
CR CHAIR RAIL
CT CERAMIC TILE
DIA. DIAMETER
DIM. DIMENSION
DN. DOWN
DS DOWNSPOUT
DTL. DETAIL
DVB DECK VAPOR BARRIER
DWG. DRAWING
EA. EACH
EG END GUARD
EJ EXPANSION JOINT
ELEC. ELECTRICAL
ELEV. ELEVATOR
EPT EPOXY PAINT
EQ. EQUAL
EQUIP. EQUIPMENT
EW EACH WAY
EXIST. EXISTING
EXP. EXPOSED
EXT. EXTERIOR
FAF FLUID APPLIED FLOORING
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FIN. FINISH (ED)
FLR. FLOOR
FND. FOUNDATION
FRP FIBERGLASS REINFORCED PANEL
FRT FIRE RETARDANT TREATED
FTG. FOOTING
FV FIELD VERIFY
GA. GAUGE
GALV. GALVANIZED
GC GENERAL CONTRACTOR
GFRG GLASS FIBER REINFORCED GYPSUM
GL GLASS
GYP. GYPSUM
GWB GYPSUM WALL BOARD
HM HOLLOW METAL
HORIZ. HORIZONTAL
HR HANDRAIL
HVAC HEATING, VENTILATING, AIR CONDITIONING
INT. INTERIOR
JST. JOIST
JT. JOINT
KIT. KITCHEN
LAV. LAVATORY
MAX. MAXIMUM
MB MARKER BOARD
MDF MEDIUM DENSITY FIBERBOARD
MECH. MECHANICAL
MFR. MANUFACTURER
MIN. MINIMUM
MISC. MISCELLANEOUS
MTL. METAL
NIC NOT IN CONTRACT
NOM. NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OFOI OWNER FURNISHED-OWNER INSTALLED
OFCI OWNER FURNISHED-CONTRACTOR
INSTALLED
ORD OVERFLOW ROOF DRAIN
PL PLASTIC LAMINATE
PNL PANEL
PT. PAINT
R / RAD. RADIUS
RAF RAISED ACCESS FLOOR
RD ROOF DRAIN
REF. REFERENCE, REFER TO
REFR. REFRIGERATOR
REINF. REINFORCE (D) (ING)
REQ. REQUIRED
REV. REVISION (S), REVISED
RF RESILIENT FLOORING
RM. ROOM
RO ROUGH OPENING
RP RESIN PANEL
RTU ROOF TOP UNIT
SAB SOUND ATTENUATING BATTS
SCHED. SCHEDULE
SF SQUARE FEET
SIM. SIMILAR
SPEC SPECIFICATION
SS SOLID SURFACE
STD. STANDARD
STL. STEEL
SSTL STAINLESS STEEL
STOR. STORAGE
STRUCT. STRUCTURAL
SUSP. SUSPENDED
TB TACK BOARD
TERR. TERRAZZO
T.O. TOP OF
T.O.B. TOP OF BEAM
T.O.C. TOP OF CONCRETE
T.O.F. TOP OF FOOTING
T.O.W. TOP OF WALL
TWP THROUGH-WALL PENETRATION
TYP. TYPICAL
UVB UNDER-SLAB VAPOR BARRIER
VAR. VARIES
VB VAPOR BARRIER
VERT. VERTICAL
WB WALL BASE
WC WALLCOVERING
WD WOOD
WDF WOOD FLOORING
WDB WOOD BASE
WP WALL PROTECTION
WT WINDOW TREATMENT
C M
B A
A R
C H
IT
E
C T
S
G R
A N
D A
V E
S P
E N
C E
R , I
A
(P
) 7
.2
.3
D A
T E
P R
O J
E C
T
PL
O
T D
AT
E
FI
LE
P
AT
H
COPYRIGHT. Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Cannon Moss Brygger & Associates is prohibited by copyright law.
SHEET INDEX
REVISIONS
SHEET
/1
/2
:4 1:
A
M
A u to d e sk
D o c s:
D
A S
H H
S C
H M
H I T u n n e l & E le va to r/
D A
S H
H S
C H
M H
I T u n n e l R e p a ir
R V
T
.r vt
T
IT
L E
DAS HHS CHMHI FOUR CORNERS ELEVATOR REPLACEMENT
IOWA DAS
CHEROKEE, IOWA
T0.00
C H
E R
O K
E E
, I O
W A
D A
S H
H S
C H
M H
I F
O U
R C
O R
N E
R S
E L
E V
A T
O R
R E
P L
A C
E M
E N
T
IO
W
A D
A S
OWNER'S PROJECT NUMBER: 9527.00
RFP 952700-01
N
NOT TO SCALE
REPLACEMENT OF ELEVATOR F IN FOUR CORNERS AREA OF THE FACILITY, AND ASSOCIATED MEP UPGRADES TO MEET CURRENT CODE. REFERENCE FULL BUILDING DRAWINGS FOR CODE INFORMATION
ADDRESSING THE EXISTING BUILDING.
• 2024 IBC: ALL APPLICABLE CHAPTERS
• 2024 International Building Code as adopted by Iowa Administrative Rule chapters 661-201 and 661-301
• 2024 International Fire Code as adopted by Iowa Administrative Rule chapters 661-201
• 2012 International Energy Conservation Code as adopted by Iowa Administrative Rule chapters 661-303
• 2024 International Existing Building Code as adopted by Iowa Administrative Rule chapters 661-301 and 661-350
• 2012 NFPA 101 Life Safety Code as adopted by Iowa Administrative Rule chapter 661-205
• 2010 Americans with Disabilities Act as adopted by Iowa Administrative Rule chapter 661-302
• State Mechanical Code as adopted by the Department of Public Health Iowa Administrative Rule chapter 641-61
• State Plumbing Code as adopted by the Department of Public Health Iowa Administrative Rule chapter 641-25
• State Electrical Code as adopted by the State Electrical Licensing Board Iowa Administrative Rule chapter 661-504
• ANSI 117.1, 2009, ALL APPLICABLE CHAPTERS
Iowa Department of Administrative Services Owner's Representative:
Jennie Elliot State Design & Construction Resources Bureau 109 S.E. 13th Street Des Moines, IA 50319 Office: 515-745-3244
CMBA Architects 505 Grand Avenue Spencer, IA 51301
PH: 712-262-3426
Architect Responsible: Adam Van Gorp, AIA Email: vangorp.a@cmbaarchitects.com
The Iowa Department of Inspections, Appeals, and Licensing, Building & Construction Division
PROJECT SUMMARY
STATE OF IOWA:
OWNER
ARCHITECT
BUILDING OFFICIAL:
On Site Contact:
Maintenance Supervisor:
Jason Pigott 1251 W Cedar Loop Cherokee, IA 51012
PH: 712-229-1505
IBC 2024 REQ / ALLOWED PROVIDED
USE AND OCCUPANCY
CONSTRUCTION TYPE
AUTOMATIC SPRINKLER SYSTEM
BUILDING HEIGHT
BUILDING STORIES
LARGEST FLOOR AREA / STORY /
1ST FLOOR AREA
CHAPTER 3
SECTION 602 / TABLE 601
SECTION 903
TABLE 504.3
TABLE 504.3
TABLE 506.2
YES
85' MAX
2 STORIES
I-3
II-B
YES
Appx. 40'
ADAM DONAVAN
VAN GORP
07319
S
O
N D
RP
IOWA
L
IC
E E
FESSIONAL
A R
C H
IT
E
C T
ADAM DONAVAN VAN GORP
Signature
Pages or sheets covered by this seal:
Printed or typed name:
I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and responsible charge. I am a duly Licensed Architect under the laws of the State of
Date
License Number:
My license renewal date is
ARCHITECT
ALL "T" & "A" SHEETS
07319
JUNE 30TH, 2027
PROJECT LOCATION
ARCHITECTURAL
A1.01 CODE REVIEW INFORMATION
A2.08 FLOOR PLANS AND SECTIONS
GENERAL
T0.00 TITLE
100% CONSTRUCTION DOCUMENTS SET
MECHANICAL
ME0.0 MECHANICAL & ELECTRICAL GENERAL NOTES & SYMBOLS
ME1.1 MECHANICAL & ELECTRICAL DEMOLITION PLANS
ME2.1 MECHANICAL & ELECTRICAL FLOOR PLANS
ME3.1 MECHANICAL & ELECTRICAL DETAILS
NO. DESCRIPTION DATE
License renewal date:
Pages or sheets covered by this seal:
Date Issued:
I hereby certify that this engineering document was pre-pared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of
Signature
Printed name:
Date
ENGINEER
IOWA
CHAD D. BASS
ALL MECHANICAL AND PLUMBING ON "ME" SHEETS
08/06/2026
DECEMBER 31TH, 2027 License renewal date:
Pages or sheets covered by this seal:
Date Issued:
I hereby certify that this engineering document was pre-pared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of
Signature
Printed name:
Date
ENGINEER
IOWA
ERIC HEYNEN
ALL ELECTRICAL ON "ME" SHEETS
08/06/2026
DECEMBER 31TH, 2027
ERIC
P24706
HEYNENL
IC
E N S E D
P
RO
FESSIONA L
E N G
IN
E E R
I O
W A
CHAD D.
P21397
BASSL
IC
E N S E D
P
RO
FESSIONA L
E N G
IN
E E R
I O
W A hebertt Stamp hebertt Text Box 8/6/2026
S
KEYPLAN
N
ELEVATOR
ADMIN
R E
A R
C E
N T
E R
A N
O R
T H
B N
O R
T H
C N
O R
T H
A S
O U
T H
B S
O U
T H
C S
O U
T
HB
O
IL
E
R
P O
W E
R
LAUNDRY
WIRTH
CODE SUMMARY
PROJECT SUMMARY:
REPLACEMENT OF ELEVATOR F AT THE CHMHI FACILITY, LOCATED IN THE "FOUR
CORNERS" AREA BETWEEN ADMIN AND REAR CENTER BUILDINGS.
REPLACEMENT OF EQUIPMENT ONLY, NO RECONFIGURATION OF SPACES OF
CHANGE OF OCCUPANCY.
CODE INFORMATION
2010 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE
FACILITIES
2000 NFPA 101 LIFE SAFETY CODE
2010 ADAAG
2024 INTERNATIONAL BUILDING CODE
2012 INTERNATIONAL ENERGY CONSERVATION CODE
The below references are from the NFPA 2000 Life Safety Code, unless otherwise noted.
OWNER
IOWA DEPARTMENT OF ADMINISTRATIVE SERVICES (DAS)
CHEROKEE MENTAL HEALTH INSTITUTE (CHMHI)
1251 WEST CEDAR LOOP
CHEROKEE, IA, 51012
OWNERS REP: Jennie Elliott email: jennie.elliott@das.iowa.gov
(515) 745-3244
ARCHITECT
CMBA ARCHITECTS
302 JONES ST STE 200
SIOUX CITY, IA 51101
712-535-1833 A/E RESPONSIBLE: ADAM VAN GORP email: vangorp.a@cmbaarchitects.com 712-274-2933
LOCAL AUTHORITY HAVING JURISDICTION
1. BUILDING OFFICIAL: Dan Wood - IOWA STATE FIRE MARSHAL Email: wood@dps.state.ia.us Phone: 515-725-6150
2. STATE REVEIWER: Shaun Sharrard - Senior Construction Design Engineer Email: shaun.sherrard@dia.iowa.gov Phone: 515.725.6157
OCCUPANCY GROUPS:
1. EXISTING HOSPITAL: HEALTH CARE NFPA CH 19 (IBC I-2)
2. NEW ELEVATOR: HEALTH CARE NFPA CH 19 (IBC I-2)
CONSTRUCTION TYPE:
EXISTING BUILDING: UBC/UFC TYPE 1-FR
SPRINKLER:
1. EXISTING HOSPITAL - NFPA TYPE 13
2. NEW ELEVATOR - NFPA TYPE 13
BUILDING HEIGHT:
EXISTING BUILDING: 4 FLOORS, 3 ABOVE GRADE
PROJECT LOCATION: SEE KEYPLAN
ALLOWABLE HEIGHT: N.A.
BUILDING AREA:
NO CHANGE TO EXISTING FLOOR AREA
HAZARDOUS AREA SEPARATION/ PROTECTED BY 1hr FIRE BARRIER: 19.3.2.1
1. ELEVATOR SHAFT - SEE BELOW
REQUIRED FIRE RESISTANCE RATINGS (in hours)
PRIMARY STRUCTURAL FRAME:
BEARING WALLS:
FLOOR CONSTRUCTION:
ROOF CONSTRUCTION:
SHAFT ENCLOSURES:
STAIRWAY ENCLOSURES (EXISTING):
CORRIDOR WALL FIRE RESISTANCE: 19.3.6.2
CORRIDOR WALLS MAY BE NON RATED AND SHALL LIMIT THE TRANSFER OF
SMOKE
TRAVEL DISTANCE TO EXITS BETWEEN EGRESS ELEMENTS (feet) 19.2.6.2
NO CHANGE TO EXISTING TRAVEL DISTANCES
OCCUPANT LOAD FACTOR (sf / person) TABLE 7.3.1.2:
NO CHANGE TO EXISTING TO OCCUPANT LOAD
DEAD END CORRIDOR LIMIT: 18.2.5.10 & TABLE A7.6.1
NO CHANGE TO CORRIDORS
ACTIVE FIRE SAFETY FEATURES
1. FIRE ALARM SYSTEM - SYSTEM PRESENT
2. SMOKE CONTROL SYSTEM - ALL DUCTWORK PENETRATING RATED WALLS
WILL HAVE A SMOKE OR FIRE/ SMOKE DAMPER
3. FIRE SPRINKLER SYSTEM - NOT PRESENT IN THIS AREA OF THE FACILITY
4. EMERGENCY LIGHTING AND POWER - EMERGENCY LIGHTING PRESENT IN THIS
AREA OF FACILITY
5. ILLUMINATED EXIT SIGNS
ELEVATORS & CONVEYING SYSTEMS (IBC 3000)
EMERGENCY SIGNAGE REQUIRED (3002.3)
MACHINE ROOMS (IBC 3005)
INDEPENDENT VENTING REQUIRED (3005.2)
FIRE BARRIERS: SHAFT 1HR RATED (713.4)
OPENINGS: PER 713.7 - 1HR (3005.4)
EQUIPMENT ROOM:PER 707 OR 3005.4 EXCEPTION 2: IF THE BUILDING IS 4
STORIES OR LESS ABOVE GRADE AND THE EQUIPMENT ROOM IS NOT ADJACENT
OR HAS OPENINGS INTO HOISTWAY SERVED, THE ACCESSORY SPACE IS NOT
REQUIRED TO BE FIRE RATED
FIRE BARRIER - 1 HR FIRE RESISTANCE RATING
EXISTING 1HR FIRE RESISTANCE RATING
FIRE EXTINGUISHER WITH BRACKETFE
CODE LEGEND
Floor 01 100' - 0"
Floor 02 113' - 0"
Basement 90' - 7 1/2"
Floor 03 126' - 0"
A2.08
ELEV PIT
86' - 8 1/4"
ROOF CONNECTING
138' - 0"
ELEV. EQUIP.
B02
ELEV
B01
CLOSET
B04
CLOSET
CLOSET
CLOSET
9'
/2
3'
1/
/4 "Floor 02
13' - 0" Floor 02
13' - 0"
Basement -9' - 4 1/2"
Basement -9' - 4 1/2"
Top of Wall 32' - 0"
Top of Wall 32' - 0"
Floor 03 26' - 0"
Floor 03 26' - 0"
Floor 04 39' - 0"
Floor 04 39' - 0"
ELEV PIT
-13' - 3 3/4"
ELEV PIT
-13' - 3 3/4"
ROOF CONNECTING
38' - 0"
ROOF CONNECTING
38' - 0"
PROJECT SCOPE
ELEV
B01
CORRIDOR
CLOSET
ELEV
B01
ELEV. EQUIP.
B02
CORRIDOR
B03
CLOSET
B04
DATA
B06
ELEC
B07
REAR CENTER
BUILDING
ADMIN
BUILDING
A SOUTH BUILDING
A NORTH BUILDING
PROJECT SCOPE
PROJECT SCOPE
PROJECT SCOPE
DIETARY
STAIRS
STAIRS
STAIRS
STAIRS
ELEV
B01
CORRIDOR
CLOSET
PROJECT SCOPE
ELEV
B01
CLOSET
CORRIDOR
PROJECT SCOPE
C M
B A
A R
C H
IT
E
C T
S
G R
A N
D A
V E
S P
E N
C E
R , I
A
(P
) 7
.2
.3
REVISIONS
SHEET
D A
T E
P R
O J
E C
T
PL
O
T D
AT
E
FI
LE
P
AT
H
COPYRIGHT. Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Cannon Moss Brygger & Associates is prohibited by copyright law.
IF THIS DRAWING IS NOT 30"x42" IT IS NOT TO SCALE
/1
/2
:4 1:
A
M
A u to d e sk
D o c s:
D
A S
H H
S C
H M
H I T u n n e l & E le va to r/
D A
S H
H S
C H
M H
I T u n n e l R e p a ir
R V
T
.r vt
A1.01
C H
E R
O K
E E
, I O
W A
D A
S H
H S
C H
M H
I F
O U
R C
O R
N E
R S
E L
E V
A T
O R
R E
P L
A C
E M
E N
T
IO
W
A D
A S
C O
D E
R E
V
IE
W I
N F
O R
M A
T
IO
N
1/4" = 1'-0"1
ELEVATOR SECTION N/S
1/8" = 1'-0"2
CODE REVIEW - FIRST FLOOR
1/16" = 1'-0"3
CODE REVIEW - BASEMENT
1/8" = 1'-0"4
CODE REVIEW - SECOND FLOOR
1/8" = 1'-0"5
CODE REVIEW THIRD FLOOR
NO. DESCRIPTION DATE
FACP
UP
UP
A2.08
A1.01
FIRE ALARM
PANEL
DATA
B06
ELEC
B07
CORRIDOR
B05
ELEV. EQUIP.
B02
CLOSET
B04
ELEV
B01
CORRIDOR
B03
ADMIN BLDGSECTION A
SOUTH BLDG
SECTION A
NORTH BLDG
REAR
CENTER
BLDG
N
DIETARY
A2.08
A1.01
A2.088
FIELD VERIFY
9' - 10 3/16"
F
IE
L D
V E
R
IF
Y
7'
/8
4' - 10 3/16"
2 3 4
10 13
ELEV
B01
CORRIDOR
CLOSET
8' - 0 3/8"
A2.08
A1.01
CORRIDOR
CLOSET
ELEV
B01
A2.08
Sim
A2.08
A1.01
CORRIDOR
CLOSET
ELEV
B01
A2.08
Sim
Floor 01 100' - 0"
Floor 02 113' - 0"
Basement 90' - 7 1/2"
Floor 03 126' - 0"
Floor 04 139' - 0"
ELEV PIT
86' - 8 1/4"
ROOF CONNECTING
138' - 0"
9'
/2
3'
1/
A1.01
2 10
ELEV
B01
CORRIDOR
B03
CORRIDOR
CORRIDOR
CORRIDOR
F .V
'-5
/2
F .V
'-3
/8
A2.08
A2.08
A1.01
1 5
ELEV. EQUIP.
B02
CORRIDOR
B03
ELEV
B01
CLOSET
B04
A2.08
Sim
8' - 0 3/8"
GENERAL NOTES
KEYNOTES
EXISTING PIT LADDER TO REMAIN
REMOVE AND REPLACE ELEVATOR CAR OPERATING PANEL & CARD
READER INSIDE ELEVATOR CAB
REMOVE AND REPLACE TRAVELING CABLE, SEE ELECTRICAL SHEETS
INSTALL NEW PIT SWITCH
INSTALL DOOR SAFETY DEVICES
REMOVE AND REPLACE LANDING BUTTONS
REMOVE AND REPLACE LANDING CALL BUTTONS AND FIXTURES, TO
BE IN COMPLIANCE WITH ADA 407.2.3.1
INSTALL EMERGENCY SIGNS AT HALL STATIONS
REMOVE AND REPLACE POWER UNIT - MOTOR, PUMP, HYDRAULIC
TANK, VALVE, OIL, GASKETS, ETC
INSTALL CODE DATE PLATES
REMOVE AND REPLACE SIGNAGE
EXISTING SUMP PUMP PIT, F.V. LOCATION AND SIZE
EXISTING ELEVATOR CAB DOORS, FRAMES, HANDRAILS, FLOORING,
CEILING, CAB THRESHOLD, CAB LIGHTING TO BE REPLACED.
NEW CAR DIRECTION INDICATORS
REMOVE EXISTING VENT AND INFILL WITH LIKE MATERIALS
PATCH AND REPAIR HOISTWAY FRAMES
DIMENSIONS ARE TO FACE OF WALL UNLESS NOTED OTHERWISE.
CONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS AND NOTIFY
ARCHITECT OF ANY DISCREPANCIES PRIOR TO BEGINNING THE
AFFECTED WORK.
DO NOT SCALE DRAWINGS, FOLLOW DIMENSIONS.
MECHANICAL AND ELECTRICAL EQUIPMENT / FIXTURES SHOWN FOR
REFERENCE, SEE MECHANICAL AND ELECTRICAL CONSTRUCTION
DOCUMENTS FOR INFORMATION.
ALL PENETRATIONS THROUGH FIRE-RESISTANCE/SMOKE/ SOUND
RATED CONSTRUCTION SHALL BE SEALED WITH APPROVED FIRE-
STOPPING OR SEALANT TO MAINTAIN REQUIRED RATINGS.
PATCH AND REPAIR EXISTING WALLS, FLOORS, CEILINGS, ETC., THAT
ARE SHOWN TO REMAIN BUT ARE DAMAGED DUE TO CONSTRUCTION.
THIS SHALL INCLUDE REPAIRING FINISHES DAMAGED BY THE REMOVAL
OR INSTALLATION OF NEW MECHANICAL, ELECTRICAL, OR FIRE
PROTECTION WORK OR DEVICES.
PATCH AND TOOTH-IN MASONRY ALL NEW OPENINGS, CORNERS,
DOORS, WINDOWS, ETC..
REFER TO ELECTRICAL DEMOLITION PLANS FOR ADDITIONAL
DEMOLITION REQUIRED
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING
AND TEMPORARY SUPPORT OF EXISTING ROOF, WALL AND FLOOR
SURFACES NEAR AND AROUND DEMOLISHED AREAS.
PATCH MECHANICAL AND ELECTRICAL PENETRATIONS IN WALLS,
FLOOR AND CEILINGS/STRUCTURE TO MATCH EXISTING.
FIELD VERIFY STRUCTURAL MEMBER PROFILES INDICATED ON
EXISTING DRAWINGS MAY VARY FROM ACTUAL PROFILES AND SIZES
LOCATED WITHIN THE EXISTING STRUCTURE.
ALL EXISTING COLUMNS REMAIN UNLESS OTHERWISE NOTED.
DOCUMENTS AVAILABLE UPON REQUEST
ALL HAZARDOUS MATERIAL ABATEMENT BY OTHERS.
COORDINATE AREAS OF DEMOLITION WITH OWNERS SCHEDULE
CONTINUOUS SEALANT AT PERIMETER OF ALL FRAMES, BOTH SIDES
OF WALL.
CONTRACTOR TO PROVIDE TEMPORARY ENCLOSURES, HEAT, AND
LIGHTING AS REQUIRED FOR INSTALLATION OF EQUIPMENT.
COORDINATE WITH ELEVATOR MANUFACTURER.
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
NOTES APPLY TO ALL LEVELS OF FACILITY. NOT ALL ELEVATOR COMPONENTS
IDENTIFIED - REFER TO SPECIFICATION FOR ADDITIONAL INFORMATION.
SEE SPECS FOR ALTERNATE 01 - ELEVATOR JACK
"M
IN
'M A
X
EXISTING BASE, CHAIRRAIL, AND TRIM TO REMAIN, VARIES PER LEVEL
KEYPLAN
N
ELEVATOR
ADMIN
R E
A R
C E
N T
E R
A N
O R
T H
B N
O R
T H
C N
O R
T H
A S
O U
T H
B S
O U
T H
C S
O U
T
HB
O
IL
E
R
P O
W E
R
LAUNDRY
WIRTH
PRE-FINISHED DRIP EDGE
PRE-FINISHED DRIP EDGE
EXISTING LINTALS
CMU BLOCK
BRICK
SUSPENDED CEILING
PL PANELS
EMBOSSED STAINLESS
STEEL PANEL
HANDRAIL
WALL FINISH -
STAINLESS STEEL
COORDINATE PANEL SIZES AND CONFIGURATION
WITH ELEVATOR MANUFACTURE
C M
B A
A R
C H
IT
E
C T
S
G R
A N
D A
V E
S P
E N
C E
R , I
A
(P
) 7
.2
.3
REVISIONS
SHEET
D A
T E
P R
O J
E C
T
PL
O
T D
AT
E
FI
LE
P
AT
H
COPYRIGHT. Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Cannon Moss Brygger & Associates is prohibited by copyright law.
IF THIS DRAWING IS NOT 30"x42" IT IS NOT TO SCALE
/1
/2
:4 1:
A
M
A u to d e sk
D o c s:
D
A S
H H
S C
H M
H I T u n n e l & E le va to r/
D A
S H
H S
C H
M H
I T u n n e l R e p a ir
R V
T
.r vt
A2.08
C H
E R
O K
E E
, I O
W A
D A
S H
H S
C H
M H
I F
O U
R C
O R
N E
R S
E L
E V
A T
O R
R E
P L
A C
E M
E N
T
IO
W
A D
A S
F L
O O
R P
L A
N S
A N
D S
E C
T
IO
N S
1/16" = 1'-0"1
BASEMENT FLOOR PLAN
1/8" = 1'-0"2
FIRST FLOOR PLAN
1/8" = 1'-0"3
SECOND FLOOR PLAN
1/8" = 1'-0"4
THIRD FLOOR PLAN
1/4" = 1'-0"5 Elevator Section E/W
1/8" = 1'-0"7
BASEMENT FLOOR PLAN
3/8" = 1'-0"8
TYP LANDING ELEVATION
1 1/2" = 1'-0"6
LOUVER INFILL
NO. DESCRIPTION DATE
3/8" = 1'-0"9
TYP CAB INTERIOR ELEVATION
EQUIPMENT IDENTIFICATION TAG. REFER TO EQUIPMENT CONNECTION SCHEDULE
DETAIL DRAWING REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE
INTERIOR ELEVATION DRAWING REFERENCE TAG
GENERAL SYMBOLS
A101
SIM
A101 1
R e f
KEYNOTE#
XXX
X
SHEET REFERENCE
SECTION CUT REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE
SHEET REFERENCE
JUNCTION BOX, CEILING OR FLOOR MOUNTED.
JUNCTION BOX, WALL MOUNTED, ELEVATION AS NOTED.
J
J
A101
SIM
1 DRAWINGS REVISION. REFER TO TITLEBLOCK FOR REVISION NAME AND DATE
RECESSED LIGHT FIXTURE, LETTER INDICATES SWITCH LEG (TYPICAL), SHADING
INDICATES EMERGENCY LIGHT (TYPICAL)
SURFACE MOUNTED STRIP FIXTURE
LINEAR PENDANT MOUNTED FIXTURE
INDUSTRIAL STRIP LIGHT FIXTURE
WALL MOUNTED STRIP LIGHT FIXTURE.
EMERGENCY LIGHT FIXTURE, WALL MOUNT, +96" OR AS NOTED
EMERGENCY LIGHT FIXTURE, CEILING MOUNT
EXIT SIGN, WALL MOUNT +96", SHADED AREAS INDICATE NUMBER OF
FACES, ARROWS INDICATE SIGN ARROWS
EXIT SIGN, CEILING MOUNT, SHADED AREAS INDICATE NUMBER OF FACES,
ARROWS INDICATE SIGN ARROWS
SINGLE POLE SWITCH, WALL MOUNT, LETTER INDICATES SWITCH LEG
THREE WAY SWITCH, WALL MOUNT, LETTER INDICATES SWITCH LEG
LIGHTING SYMBOLS
PILOT LIGHT SWITCH, WALL MOUNT, LETTER INDICATES SWITCH LEG
DIMMER SWITCH, WALL MOUNT, LETTER INDICATES SWITCH LEG
a a b
P c
D d
EMERGENCY TRANSFER DEVICE
ROUND APERTURE RECESSED DOWNLIGHT FIXTURE,
ARROW INDICATES WALLWASH
LIGHTING CONTROLS LOW VOLTAGE SWITCH, WALL MOUNT,
LETTER INDICATES SWITCH LEG, REFER TO LIGHTING CONTROLS SCHEDULE
S1 e
ETD
POWER SYMBOLS
DUPLEX RECEPTACLE, WALL MOUNTED, TAMPER-RESISTANT
DUPLEX GFCI RECEPTACLE, TAMPER-RESISTANT, WALL MOUNT,
PROTECTION INCLUDED IN DEVICE.
DUPLEX GFCI WEATHER RESISTANT RECEPTACLE WITH WEATHER-PROOF
IN-USE COVER, TAMPER-RESISTANT, WALL MOUNT
EQUIPMENT CONNECTION,
REFER TO EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE.
REFER TO PANEL SCHEDULES FOR GFCI PROTECTION WHERE REQUIRED
EQUIPMENT CONNECTION, WALL MOUNT,
REFER TO EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE.
REFER TO PANEL SCHEDULES FOR GFCI PROTECTION WHERE REQUIRED
SINGLE RECEPTACLE, WALL MOUNTED
W
SURGE PROTECTIVE DEVICE
SAFETY DISCONNECT SWITCH
PANELBOARD - SURFACE MOUNTED
PANELBOARD - RECESSED IN WALL
DISTRIBUTION PANELBOARD/SWITCHBOARD - SURFACE MOUNTED AS NOTED.
SPD
MOTOR CONNECTION,
REFER TO EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE.
REFER TO PANEL SCHEDULES FOR GFCI PROTECTION WHERE REQUIRED
M
ELECTRICAL ABBREVIATIONS
A DEVICE MOUNTED +8" ABOVE
COUNTER TOP (VERIFY LOCATION)
AFF ABOVE FINISHED FLOOR
ATS AUTOMATIC TRANSFER SWITCH
C CEILING
CB CIRCUIT BREAKER
CT CURRENT TRANSFORMER
E EXISTING ITEM TO REMAIN
EC ELECTRICAL CONTRACTOR
EM EMERGENCY LIGHT FIXTURE
ER NEW LOCATION OF EXISTING ITEM
F ROUGH IN FOR FUTURE DEVICE
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FSD FIRE SMOKE DAMPER
G GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
KVA KILO-VOLT-AMPERES
KW KILOWATTS
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION PANEL
MLO MAIN LUGS ONLY
N NEW DEVICE IN EXISTING LOCATION
NIC NOT IN CONTRACT
NM NONMETALLIC
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED,
OWNER INSTALLED
R EXISTING ITEM TO BE REMOVED
RR EXISTING ITEM TO BE REMOVED AND
RELOCATED
RN EXISTING ITEM TO BE REMOVED AND
REPLACED WITH NEW
SCCR SHORT CIRCUIT CURRENT RATING
T TAMPER PROOF DEVICE
TCC TEMPERATURE CONTROL CONTRACTOR
TV TELEVISION
TYP TYPICAL
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VA VOLT-AMPERES
WG WIREGUARD COVER
WP WEATHERPROOF DEVICE
WR WEATHER RESISTANT DEVICE
+24" INDICATES MOUNTING HEIGHT CENTER
LINE OF DEVICE TO FINISHED FLOOR
1. PROVIDE ELECTRICAL INSTALLATION IN ACCORDANCE WITH STATE CODES.
2. THE CURRENT ADOPTED EDITION OF THE ELECTRICAL CODE IS THE STANDARD FOR THE
ELECTRICAL INSTALLATION. VERIFY WITH STATE OFFICIALS WHEN PERMITS ARE OBTAINED.
NOTIFY DESIGN TEAM OF ANY DISCREPANCIES BETWEEN THE PROJECT MANUAL OR
DRAWINGS AND THE GOVERNING CODE.
3. INSTALLATION SHALL FOLLOW REQUIREMENTS OF THE ADAAG –AMERICANS WITH
DISABILITIES ACT.
4. REFER TO PROJECT MANUAL AND PROJECT CODE REVIEW SHEET FOR LIST OF APPLICABLE
CODES.
5. PER NEC EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO
ITS CLEAR, EVIDENT AND SPECIFIC PURPOSE OR USE. CONTRACTOR TO PROVIDE FINAL
CIRCUIT IDENTIFICATION FOR ALL NEW AND MODIFIED CIRCUITS AT PROJECT COMPLETION.
CODE NOTES - ELECTRICAL
1. PROVIDE NORMAL WIRING DEVICES AS GRAY UNLESS OTHERWISE NOTED.
2. PROVIDE DEVICES COVER PLATES AS STAINLESS STEEL. MATCH WIRING DEVICES COLOR.
3. PROVIDE GFCI TYPE RECEPTACLES AT ALL LOCATIONS REQUIRED BY THE NEC.
4. INSTALL ABOVE COUNTERTOP RECEPTACLES +8” ABOVE COUNTERTOP OR AS OTHERWISE
INDICATED.
5. AT A COMMON COUNTERTOP, INSTALL ALL RECEPTACLES AND SWITCHES AT THE SAME
HEIGHT UNLESS OTHERWISE SPECIFICALLY INDICATED.
DEVICE INSTALLATION AND MATERIALS - ELECTRICAL
1. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND ELECTRICAL WORK WITH ALL
OTHER TRADES. BEGIN INSTALLATION AND ROUGH-IN ONLY AFTER PROPER AND TIMELY
COORDINATION WITH ALL TRADES ASSOCIATED WITH THE INSTALLATION IS COMPLETE.
COORDINATE WITH BUILDING STRUCTURE, ARCHITECTURE, MECHANICAL SHEET METAL, ALL
PIPING SYSTEMS, LIGHT FIXTURES, CONDUITS, CABLE TRAYS, EQUIPMENT
ACCESS/CLEARANCE, ETC. REFER TO ALL GENERAL, MECHANICAL, AND ELECTRICAL
DRAWINGS AND SPECIFICATIONS FOR THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR
REWORK OF INSTALLED EQUIPMENT RESULTING FROM INSUFFICIENT COORDINATION.
2. ELECTRICAL DRAWINGS ARE ONLY A PORTION OF THE COMPLETE SET OF PLANS AND
CONTRACT DOCUMENTS. THE ELECTRICAL SCOPE OF WORK IS DEFINED BY THE COMPLETE
SET OF CONTRACT DOCUMENTS. THIS INCLUDES BUT IS NOT LIMITED TO REFERENCING;
ARCHITECTURAL PLANS FOR DIMENSIONS AND DETAILS; EQUIPMENT PLANS FOR ROUGH-IN
REQUIREMENTS, MECHANICAL PLANS FOR EQUIPMENT SIZES AND LOCATIONS.
GENERAL NOTES - ELECTRICAL
1. INCREASE CONDUCTOR SIZES ON 20A 120V-1 PHASE CIRCUITS EXCEEDING 100 FEET TO
CENTER OF LOAD TO ACCOUNT FOR VOLTAGE DROP.
2. RACEWAYS AND BOXES ARE SHOWN DIAGRAMMATICALLY ONLY AND INDICATE GENERAL
AND APPROXIMATE LOCATIONS. LAYOUTS DO NOT ALWAYS SHOW THE TOTAL NUMBER
OF RACEWAYS OR BOXES FOR THE CIRCUITS REQUIRED, NOR ARE THE LOCATIONS OF
INDICATED RUNS INTENDED TO SHOW THE ACTUAL ROUTING OF THE RACEWAYS.
3. LIGHT FIXTURES, SWITCHES, DEVICES, ETC. ARE SHOWN IN PREFERRED LOCATION.
MODIFY CONDUIT, HANGERS, CIRCUITING, ETC. TO PROVIDE A COMPLETE AND
OPERATIONAL SYSTEM.
4. PROVIDE A DEDICATED GREEN INSULATED GROUND CONDUCTOR TO ALL DEVICES. DO
NOT USE CONDUIT SYSTEM AS THE ONLY EQUIPMENT GROUNDING METHOD.
5. PROVIDE TYPED PANEL DIRECTORY AT PROJECT COMPLETION FOR NEW PANELS AND
EXISTING PANELS WITH CIRCUITS MODIFIED DURING PROJECT. USE OWNER’S CURRENT
ROOM NUMBERS AND EQUIPMENT NAMES. PROVIDE UNIQUE CIRCUIT IDENTIFICATION
PER NEC 408.4(A)
6. CONTRACTOR IS RESPONSIBLE FOR OPENINGS IN WALLS, FLOORS, CEILINGS, AND
ROOFS THAT ARE REQUIRED TO COMPLETE THEIR SCOPE OF WORK. SEAL
PENETRATIONS IN ACCORDANCE WITH THE RATING OF THE AFFECTED ASSEMBLY.
REFER TO ARCHITECTURAL CODE PLAN FOR RATED WALLS, FLOORS, AND CEILINGS.
INSTALLATION NOTES - ELECTRICAL
SECURITY - ACCESS CONTROL:
SECURITY MANAGEMENT SYSTEM - HEAD END COMPONENTS
SECURITY MANAGEMENT SYSTEM - FIELD DEVICES
SECURITY MANAGEMENT SYSTEM - ELECTRIFIED DOOR HARDWARE
ROUGH-IN, PATHWAYS AND SLEEVES
ROUGH-IN, PATHWAYS AND SLEEVES
SECURITY - VIDEO SURVEILLANCE:
CAMERA(S)
HEAD END EQUIPMENT AND COMPONENTS
SECURITY MANAGEMENT SYSTEM - ALL CABLING
OFOI
OFCI
CFCI
OWNER FURNISHED & OWNER INSTALLED
OWNER FURNISHED & CONTRACTOR INSTALLED
CONTRACTOR FURNISHED & CONTRACTOR INSTALLED
GENERAL NOTE:
A. MATRIX IS NOT INTENDED TO BE EXHAUSTIVE TO COVER ALL MATERIALS NECESSARY FOR
SCOPE AND SHOULD ONLY BE USED TO QUICKLY IDENTIFY SYSTEMS AND RELATED
INFRASTRUCTURE INSIDE AND OUTSIDE THE BID OF THIS PROJECT. ANY ITEMS FURNISHED OR
INSTALLED BY THE BIDDING CONTRACTOR SHALL COVER ALL REQUIRED APPERTUNANCES
NECESSARY FOR A COMPLETE SYSTEM. THIS SHALL INCLUDE BUT NOT BE LIMITED TO,
EQUIPMENT, ACCESSORIES, TERMINATIONS, TERMINATION COMPONENTS, ALL FINAL
CORDAGE CONNECTIVITY, SOFTWARE, PROGRAMMING, AND THE LABOR TO INSTALL.
B. ACCESS CONTROL VENDOR TO INSTALL CABLING, FIELD DEVICES, ETC. COORDINATE EXACT
DEVICE LOCATIONS AND PATHWAYS WITH VENDOR AND CM ONSITE.
SAFETY - FIRE DETECTION AND ALARM:
ROUGH-IN, PATHWAYS AND SLEEVES
INITIATING FIELD DEVICES (SMOKE, MANUAL PULL, MONITOR MODULES)
NOTIFICATION APPLIANCES (HORNS, STROBES, SPEAKERS)
MISCELLANEOUS DEVICES (RELAYS, TEST STATION, ANNUNCIATOR)
N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
OFOI OFCI CFCI
TECHNOLOGY RESPONSIBILITY MATRIX
PROVISION RESPONSIBILITIES DEFINED
RACKS, FRAMES AND ENCLOSURES
COPPER HORIZONTAL CABLING
DATA COMMUNICATIONS SWITCHES AND HUBS
ROUGH-IN, PATHWAYS AND SLEEVES
COMMUNICATIONS - TELECOM SYSTEMS:
REUSE EXISTING
REUSE EXISTING
1. MECHANICAL DEMOLITION DRAWINGS SHOWING EXISTING CONDITIONS HAVE BEEN
PREPARED BASED ON NON-DESTRUCTIVE FIELD OBSERVATION AND AS-BUILT DRAWINGS
PROVIDED BY THE OWNER. FIELD VERIFY EXISTING SYSTEMS BEFORE BEGINNING WORK.
NOTIFY ARCHITECT/ENGINEER IF EXISTING CONDITIONS ARE MATERIALLY DIFFERENT THAN
THOSE SHOWN ON THE PLANS.
2. BE FAMILIAR WITH EXISTING MECHANICAL SYSTEMS THAT WILL BE AFFECTED BY THE
DEMOLITION WORK. OBTAIN PERMISSION FROM THE OWNER'S REPRESENTATIVE TO SHUT
OFF SERVICES OR SYSTEMS THAT AFFECT AREAS BEYOND THE LIMITS OF THE IMMEDIATE
DEMOLITION AREA. INFORM THE OWNER’S REPRESENTATIVE OF THE REASON FOR AND
DURATION OF THE SHUTDOWN. MINIMIZE IMPACT TO OTHER AREAS. PROCEED WITH THE
SHUT-DOWN AFTER PERMISSION FROM THE OWNER IS GRANTED.
3. REMOVE PIPING, HANGERS, DUCTWORK, GRILLES, REGISTERS, DIFFUSERS, ETC. THAT ARE
INDICATED TO BE REMOVED IN A TIMELY MANNER IN ACCORDANCE WITH THE GENERAL
DEMOLITION SPECIFICATIONS. COORDINATE WITH THE OWNER AND OTHER CONTRACTORS.
MECHANICAL – DEMOLITION NOTES
1. COORDINATE MECHANICAL AND ELECTRICAL WORK WITH ALL OTHER TRADES. BEGIN
INSTALLATION AND ROUGH-IN AFTER COORDINATION WITH ALL TRADES ASSOCIATED WITH
THE INSTALLATION IS COMPLETE. COORDINATE BUILDING STRUCTURE, ARCHITECTURAL
ASSEMBLIES, SHEET METAL, ALL PIPING SYSTEMS, LIGHT FIXTURES, CONDUITS, CABLE
TRAYS, ETC. REFER TO ALL GENERAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND
SPECIFICATIONS FOR THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR REWORK
ASSOCIATED WITH FAILURE TO COORDINATE.
2. INCORPORATE MECHANICAL SPECIFICATIONS, DRAWINGS, STATE AND LOCAL CODES, AND
OWNER STANDARDS INTO WORK.
3. REFER TO ARCHITECTURAL SPECIFICATIONS FOR THROUGH-PENETRATION FIRESTOPPING
AND TO ARCHITECTURAL CODE PLAN FOR FIRE RATED WALLS, FLOORS, AND CEILINGS. EACH
TRADE IS RESPONSIBLE TO FIRESTOP PENETRATIONS THROUGH RATED ASSEMBLIES.
4. EACH TRADE IS RESPONSIBLE FOR MAKING PENETRATIONS WHERE REQUIRED IN EXISTING
WALLS, FLOORS, CEILINGS, AND ROOFS. MAKE PENETRATIONS NEAT. PATCH, CONCEAL, OR
CAULK OVERCUT.
5. PROVIDE MECHANICAL EQUIPMENT, SUPPORTS, HANGERS, AND ALL APPURTENANCES.
INSTALL ALL EQUIPMENT PER MANUFACTURER'S RECOMMENDATIONS. INSTALL SYSTEM TO
MEET ALL CITY AND STATE CODES AND REQUIREMENTS.
6. COVER EXPOSED WALL PENETRATIONS WITH ESCUTCHEONS OR SHEET METAL AS
APPROPRIATE.
7. CAULK ALL CONCEALED AND EXPOSED PIPING AND DUCT WALL PENETRATIONS TO PREVENT
NOISE TRANSFER BETWEEN SPACES.
8. PROVIDE FIRE CAULKING ASSEMBLIES FOR PENETRATIONS OF RATED ASSEMBLIES. REFER
TO ARCHITECTURAL DRAWINGS FOR ASSEMBLY RATINGS.
9. CONTINUE PIPE INSULATION THROUGH WALLS, FLOORS, AND CEILING PENETRATIONS
UNBROKEN.
10. ON COMPLETION OF THE INSTALLATION, COOPERATE WITH THE OWNER TO PROVIDE
TESTING, ADJUSTING, AND BALANCING TO OBTAIN PROPER OPERATION OF ALL EQUIPMENT
AND SYSTEMS. PROVIDE ALL FACILITIES AND EQUIPMENT AND COMPLETE ALL TESTS
REQUIRED FOR ADJUSTMENTS AND BALANCING TO ESTABLISH THE PROPER PERFORMANCE
OF EQUIPMENT.
11. PROVIDE WARRANTIES FOR ALL EQUIPMENT AND INSTALLATION PER THE CONTRACT
DOCUMENTS. CONDITIONING REFRIGERATION SYSTEMS SHALL BE WARRANTED FOR A
MINIMUM OF 5 YEARS, PARTS ONLY, NON-PRORATED, FROM THE DATE OF OCCUPANCY OR
SUBSTANTIAL COMPLETION, OR WHICHEVER OCCURS FIRST. THE WARRANTY SHALL COVER
COMPRESSORS, EVAPORATORS, CONDENSER COILS, HIGH AND LOW SIDE PIPING, AND
PIPING SPECIALTIES INCLUDING EXPANSION AND SOLENOID VALVES, RELIEF VALVES, FILTER
DRYER,AND SIGHT GLASSES. PRESSURE GAUGES AND PRESSURE SWITCHES ARE NOT
UNDER THE EXTENDED WARRANTY EXCEPT FOR LOSS OF REFRIGERANT AND
CONSEQUENTIAL DAMAGE TO THE SYSTEM WHICH WILL BE AN EXTENDED WARRANTY
OBLIGATION. ALL DEFECTS THAT BECOME APPARENT WITHIN THE WARRANTY PERIOD SHALL
BE REPAIRED BY THE MECHANICAL CONTRACTOR AS DIRECTED BY THE ENGINEER THROUGH
THE OWNER’S REPRESENTATIVE. WARRANTY DOES NOT OBLIGATE THE MECHANICAL
CONTRACTOR TO REPAIR DAMAGE RESULTING FROM THE OWNER’S ACCIDENT, IMPROPER
OPERATION, OR FAILURE TO PROVIDE MAINTENANCE. WARRANTY COVERS DEFECTIVE
MATERIAL AND INSTALLATION. REFER TO SPECIFICATIONS FOR ADDITIONAL DETAILS AND
OTHER WARRANTY INFORMATION.
MECHANICAL - GENERAL NOTES
1. INSTALL HEAT DETECTORS IN WORK AREAS DURING CONSTRUCTION TO MINIMIZE
FALSE TRIPS. INSTALL PERMANENT DETECTORS IN LOCATIONS SHOWN UPON
CONSTRUCTION COMPLETION.
2. INSTALL MODULES AT ELEVATOR EQUIPMENT TO PROVIDE PRIMARY RECALL,
SECONDARY RECALL, FIRE HAT AND SHUNT TRIP. PROVIDE PROGRAMMING AS
NECESSARY FOR FUNCTION SYSTEM.
3. FIRE ALARM ITEMS AND DEVICES ARE SHOWN IN SUGGESTED LOCATIONS. FINAL
LAYOUTS, LOCATIONS, AND QUANTITIES SHALL BE IN ACCORDANCE WITH APPLICABLE
CODES, MANUFACTURER’S RECOMMENDATIONS, AND EQUIPMENT LISTINGS.
COORDINATE LOCATIONS WITH LIGHTING AND AIR HANDLING SYSTEMS.
4. ALL FIRE ALARM CIRCUITRY IN EXPOSED CEILING SPACES SHALL BE IN ¾” CONDUIT PER
SPECIFICATIONS. EXPOSED CABLING SHALL NOT BE ACCEPTED.
5. ALL CONCEALED, ACCESSIBLE CEILING TILE LOCATIONS SHALL BE ALLOWED TO HAVE
OPEN AIR CABLING INSTALLED. PROVIDE J-HOOKS, BRIDLE RINGS AND ASSOCIATED
CABLE SUPPORTS TO KEEP INFRASTRUCTURE MANAGED AND OFF OF THE CEILING TILE.
6. ELECTRICAL CONTRACTOR SHALL PROVIDE FIRESTOPPING AT ALL PENETRATIONS PER
SPECIFICATION.
FIRE DETECTION & ALARM NOTES
COMMUNICATION NOTES
1. REUSE EXISTING POTS LINE IN THE ELEVATOR EQUIPMENT ROOM FOR THE ELEVATOR
TELEPHONE. REVISE LOCATION AND EXTEND AS NECESSARY FOR NEW EQUIPMENT
LOCATIONS.
2. INSTALL NEW DATA CABLING FROM IDF LOCATIONS SHOWN ON PLANS TO ELEVATOR
EQUIPMENT ROOM FOR NEW 2-WAY COMMUNICATION SYSTEM.
FIRE DETECTION AND ALARM SYMBOLS
SMOKE DETECTOR
DUCT SMOKE DETECTOR
CARBON MONOXIDE DETECTOR
HEAT DETECTOR
COMBINATION HORN WITH STROBE
COMBINATION SPEAKER WITH STROBE
STROBE
SPEAKER
ADDRESSABLE INPUT MODULE; FS - SPRINKLER WATER FLOW SWITCH,
TS - TAMPER SWITCH, PIV - POST INDICATOR VALVE
FIRE ALARM CONTROL PANEL + EMERGENCY COMMUNICATIONS PANEL
COMBINATION FIRE/SMOKE DAMPER
SMOKE DAMPER
S
S
AIM
ADDRESSABLE OUTPUT MODULE; SD - FAN SHUT DOWN RELAY, AM - AUDIO MUTEAOM
H HORN
S
SD
FSD
S
FAA
FACP
XX
XX
COMBINATION CARBON MONOXIDE / SMOKE DETECTORS
FIRE ALARM ANNUNCIATOR PANEL
REVISIONS
P
LO
T D
A T
E
F
IL
E P
A T
H
COPYRIGHT. Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Cannon Moss Brygger & Associates is prohibited by copyright law.
IF THIS DRAWING IS NOT 30"x42" IT IS NOT TO SCALE
SHEET
D A
T E
P R
O J
E C
T
/1
/2
:0 :1
A
M
A u to d e s k D o c s /D
A S
H H
S C
H M
H I T u n n e l
E le v a to r/ M
E P
T C
H M
I E le v a to r_ R
.r v t
ME0.0
C H
E R
O K
E E
, I O
W A
D A
S H
H S
C H
M H
I F
O U
R C
O R
N E
R S
E L
E V
A T
O R
R E
P L
A C
E M
E N
T
IO
W
A D
A S
M E
C H
A N
IC
A
L
E L
E C
T R
IC
A
L G
E N
E R
A L
N O
T E
S
S Y
M B
O L
S S S
S
+46"
S
1 +46"
AOMAOM
E R
RN RN
E
E
B01
ELEV
CLOSET
CORRIDOR
RN
E
E
B01
ELEV
CLOSET
CORRIDOR
E
E
RNB01
ELEV
CORRIDOR
CLOSET
RNE
R
REMOVE EXISTING DETECTOR. INSTALL
HEAT DETECTOR DURING CONSTRUCTION.
INSTALL NEW DETECTOR UPON PROJECT COMPLETION.
TYPICAL FOR EACH ELEVATOR LOBBY/LANDING.
INSUFFICIENT
LIGHTING AT LANDING.
INSTALL NEW FIXTURE
IN EXISTING LOCATION
REMOVE EXISTING CAMERA.
REINSTALL IN CAB UPON PROJECT COMPLETION.
EXITING TERMINATION AND SYSTEM TO REMAIN INTACT
EXISTING CAMERA SYSTEM TO REMAIN
REMOVE EXISTING DETECTOR. INSTALL
HEAT DETECTOR DURING CONSTRUCTION.
INSTALL NEW DETECTOR UPON PROJECT COMPLETION.
TYPICAL FOR EACH ELEVATOR LOBBY/LANDING.
RN
R
R
R
R
RN
RN
R
RN
EXISTING FIXTURE AT PIT LEVEL TO REMAIN
RN
B04
CLOSET
B01
ELEV
B02
ELEV. EQUIP.
B03
CORRIDOR
RR
(x3)
A. DEMOLITION DRAWINGS PRESENT LAYOUT OF EXISTING
CONDITIONS AND MAJOR MECHANICAL/ELECTRICAL ITEMS.
FIELD VERIFY EXISTING CONDITIONS AND BECOME FAMILIAR
WITH EXISTING ELECTRICAL SYSTEM AND DEMOLITION SCOPE
BEFORE WORK BEGINS.
B. ADDITIONAL COMPONENTS MAY EXIST WHICH ARE NOT SHOWN.
HANDLE SUCH ITEMS IN A MANNER SIMILAR TO THOSE ITEMS
WHICH ARE SHOWN.
C. REMOVE ELECTRICAL FACILITIES AND CLEAR THE AREA TO
RECEIVE THE NEW WORK.
a. REMOVE ALL CONDUIT, WIRE, BOXES, ETC., AS
REQUIRED BY WALL AND CEILING DEMOLITION.
b. IDENTIFY THE LOCATION OR ITEMS SERVED FOR ALL
DISCONNECTED BRANCH CIRCUITS BEFORE
DEMOLITION. MAINTAIN CIRCUITS SERVING AREAS
BEYOND THE DEMOLITION AREA.
c. REMOVE AND REINSTALL CEILING TILES AS REQUIRED
TO REMOVE THE ELECTRICAL FACILITIES NOTED.
REPLACE CEILINGS TILES DAMAGED DURING
DEMOLITION.
d. KEEP EXISTING SYSTEMS OPERATIONAL DURING ALL
PHASES OF CONSTRUCTION UNLESS NECCESARY FOR
DEMOLITION.
e. OBTAIN OWNER'S PERMISSION TO SHUT OFF SERVICES
OR SYSTEMS WHICH MAY AFFECT OTHER AREAS
BEYOND DEMOLITION AREA. INFORM OWNER AS TO THE
REASON FOR AND THE DURATION OF THE SHUTDOWN.
f. REPAIR AT CONTRACTORS EXPENSE ANY DAMAGED
CONDUIT OR WIRE NOT IDENTIFIED FOR DEMOLITION.
g. INSTALL BLANK COVERPLATES/COVERS OVER
OPENINGS AT REMOVED DEVICE LOCATIONS.
D. ALL WIRING FOR REMODELED AREAS SHALL BE NEW UNLESS
SPECIFICALLY NOTED OTHERWISE.
E. PROTECT EXISTING DEVICES IDENTIFIED TO REMAIN OR BE
RELOCATED. IF AN EXISTING DEVICE CANNOT BE REINSTALLED
NOTIFY DESIGN TEAM DURING DEMOLITION. REPLACE
FUNCTIONING ITEMS DAMAGED DURING DEMOLITION.
F. REMOVED/DEMOLISHED EQUIPMENT REMAINS THE PROPERTY
OF THE OWNER UNLESS OTHERWISE NOTED. VERIFY OWNERS
SALVAGE SELECTIONS AND DISPOSE ALL OTHER MATERIALS.
G. PLAN ABBREVIATIONS:
E - EXISTING ITEM TO REMAIN
ER - NEW LOCATION OF EXISTING ITEM
N - NEW ITEM IN EXISTING LOCATION
R - EXISTING ITEM TO BE REMOVED, PATCH AND/OR
COVER
RN - REPLACE EXISTING WITH NEW
RR - EXISTING ITEM TO BE REMOVED AND RELOCATED
ELECTRICAL DEMOLITION NOTES
FIELD VERIFY AND REMOVE
2" ELEVATOR SUMP PUMP
DISCHARGE BACK TO MAIN
AND CAP.
2" P
D
P
D REMOVE EXISTING PUMP. REFER TO
MECHANICAL/PLUMBING NOTES FOR SCOPE OF
CLEANING AND REPAIRS NEEDED.
REMOVE ABANDONED SUMP PUMP
DISCHARGE PIPE BACK TO
ELEVATOR PIT FLOOR AND CAP.
REVISIONS
P
LO
T D
A T
E
F
IL
E P
A T
H
COPYRIGHT. Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Cannon Moss Brygger & Associates is prohibited by copyright law.
IF THIS DRAWING IS NOT 30"x42" IT IS NOT TO SCALE
SHEET
D A
T E
P R
O J
E C
T
/1
/2
:0 :1
A
M
A u to d e s k D o c s /D
A S
H H
S C
H M
H I T u n n e l
E le v a to r/ M
E P
T C
H M
I E le v a to r_ R
.r v t
ME1.1
C H
E R
O K
E E
, I O
W A
D A
S H
H S
C H
M H
I F
O U
R C
O R
N E
R S
E L
E V
A T
O R
R E
P L
A C
E M
E N
T
IO
W
A D
A S
M E
C H
A N
IC
A
L
E L
E C
T R
IC
A
L D
E M
O L
IT
IO
N P
L A
N S
1/4" = 1'-0"
ROOF DEMO PLAN
1/4" = 1'-0"
THIRD FLOOR DEMO PLAN
1/4" = 1'-0"
SECOND FLOOR DEMO PLAN
1/4" = 1'-0"
FIRST FLOOR DEMO PLAN
1/4" = 1'-0"
BASEMENT DEMO PLAN
R
1/4" = 1'-0"
BASEMENT PLAN - MECH DEMO
S
S
S
+46"
1 +46"
S
S
W
AOMAOM
FACPFACPFACP
N
F2
EL-1
E
F2
EL-1
N
B01
ELEV
CORRIDOR
CLOSET
F2
EL-1
N
CORRIDOR
B01
ELEV
CLOSET
F2
EL-1
B01
ELEV
CORRIDOR
CLOSET
N
E
E
EXISTING CAMERA REINSTALLED
IN CAB
EXISTING LINEAR FIXTURE TO REMAIN.
CONNECT TO NEW LIGHTING CIRCUIT
AND CONTROLS.
N
N
N
N
F1
DEDICATED SUMP PUMP RECEPTACLE
2-WAY COMMUNICATION
120V CIRCUIT AND FUSED DISCONNECT.
INSTALL RATH SYSTEM AND INTEGRATE
WITH EXISTING SYSTEM ONSITE.
ELEVATOR 120V FUSED
DISCONNECT FOR AUX.
CAB POWER
ELEVATOR BREAKER TO BE PROVIDED
IN PANEL AS LOCKABLE.
F1
EL-7
N
F2
EL-1
SSI
SSO
B04
CLOSET
B03
CORRIDOR
B01
ELEV
B02
ELEV. EQUIP.
INTERCEPT AND
CUT BACK EXISTING
SURFACE MOUNTED CONDUIT
TO FEED NEW FIXTURE
END TO END.
N
EL-9
EL-3
INSTALL NEW
CIRCUIT TO
RECEPTACLE
EL-5
EL-13,15
EL-2
EL-4 E1
EL-7
PRIMARY, SECONDARY RECALL,
AND FIRE HAT. RELOCATE
EXISTING DEVICES AND EXTEND
WIRING AS NECESSARY TO NEW
ELEVATOR CONTROLLER,
INTEGRATE, AND REPROGRAM.
PANEL EL
EL-11
LABEL FRONT OF PANEL
"PANEL IS FOR ELEVATOR
EQUIPMENT ONLY"
SSI
SSO
REF LINES. SIZE AND ROUTE PER MFR
RECOMMENDATIONS. SINGLE LINE
SHOWN REPRESENTS A LINE SET
(2 PIPES).
1-1/2" PD TO DAYLIGHT OUTSIDE,
TERMINATE WITH DOWNTURNED
ELBOW WITH BUG SCREEN.
PROVIDE NEW SUMP PUMP SP-1
TO GO IN EXISTING SUMP PIT.
EXISTING SUMP PIT GRATE TO
REMAIN. PUMP SHALL ALARM THE
DDC SYSTEM WHEN OPERATING.
T
OFFSET UNIT OFF THE
WALL WITH UNISTRUT
B01
ELEV
B02
ELEV. EQUIP.
B03
CORRIDOR
B04
CLOSET
CONDENSING UNIT TO BE
WALL MOUNTED, INSTALL
MINIMUM 3' ABOVE GROUND.
2" PD TO DAYLIGHT OUTSIDE,
TERMINATE WITH DOWNTURNED
ELBOW WITH BUG SCREEN.
2" PD
SP
CLEAN SUMP PIT FROM ALL
DEBRIS AND EXISTING WATER.
CYCLE THE SUMP PUMP
THROUGH 3 CLEAN WATER
CYCLES. WATER MUST BE
DUMPED BY CONTRACTOR SINCE
IT WILL HAVE HYDRAULIC FLUID
MIXED IN.
OIL ALERT CONTROL PANEL
OIL ALERT ALARM PANEL
ME2.1
EXISTING NOTIFIER
FIRE ALARM CONTROL
PANEL
EXISTING IDF ROOM.
EXISTING PANEL LOCATION OF PANEL 1
AND RC-B-SP2.
INSTALL NEW CIRCUITS FROM PANEL 1.
REUSE EXISTING CIRCUITS IN SPACES
11, 13, 21, 23, 25.
EXISTING PANEL LOCATION
RCB.P1 FEEDING ELEVATOR.
REMOVE CONDUCTORS, OPEN BREAKER
AND LABEL AS SPARE.
B07
ELEC
B02
ELEV. EQUIP.
B01
ELEV
B04
CLOSET
B03
CORRIDOR
B05
CORRIDOR
B06
DATA
B03
CORRIDOR
APPROXIMATE LOCATION OF
2000A DISTRIBUTION PANEL
APPROXIMATE FEEDER ROUTING
THROUGH THE BUILDING. VERIFY
ROUTING AND COORDINATE
EXACT LOCATION WITH OWNER
IN THE FIELD.
INSTALL (4) #3/0 CU + (1) #4 GND IN 2" CONDUIT
FROM DISTRIBUTION TO NEW PANEL EL.
POWER GENERAL NOTES
A. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND
ELECTRICAL WORK WITH ALL OTHER TRADES. NO ASPECT OF A
SYSTEM INSTALLATION OR ITS ROUGH-IN SHALL COMMENCE UNTIL
PROPER AND TIMELY COORDINATION WITH ALL TRADES ASSOCIATED
WITH THE INSTALLATION HAS TRANSPIRED. ITEMS TO BE
COORDINATED SHALL INCLUDE BUT NOT BE LIMITED TO: BUILDING
STRUCTURE, SHEET METAL, PIPING SYSTEMS, LIGHT FIXTURES,
CONDUITS, CABLE TRAYS, ETC. REFER TO ALL GENERAL,
MECHANICAL, AND ELECTRICAL DRAWINGS AND SPECIFICATIONS FOR
THIS PROJECT.
B. COORDINATE ELECTRICAL REQUIREMENTS FOR MECHANICAL UNITS
WITH MECHANICAL CONTRACTOR AND FINAL MECHANICAL SHOP
DRAWINGS.
C. PROVIDE PENETRATIONS REQUIRED FOR ROUTING RACEWAYS
THROUGH THE BUILDING. COORDINATE FIRE RATED WALL
PENETRATIONS AND PROVIDE CONDUIT SLEEVES AND FIRE
STOPPING TO MAINTAIN RATING.
A. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND
ELECTRICAL WORK WITH ALL OTHER TRADES. NO ASPECT OF A
SYSTEM INSTALLATION OR ITS ROUGH-IN SHALL COMMENCE
UNTIL PROPER AND TIMELY COORDINATION WITH ALL TRADES
ASSOCIATED WITH THE INSTALLATION HAS TRANSPIRED. ITEMS
TO BE COORDINATED SHALL INCLUDE BUT NOT BE LIMITED TO:
BUILDING STRUCTURE, SHEET METAL, ALL PIPING SYSTEMS,
LIGHT FIXTURES, CONDUITS, CABLE TRAYS, ETC. REFER TO ALL
GENERAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND
SPECIFICATIONS FOR THIS PROJECT
B. UNLESS NOTED OTHERWISE, CONNECT ALL EMERGENCY
BATTERY FIXTURES WITH AN UN-SWITCHED LEG OF THE
LIGHTING CIRCUIT THAT SERVES THE FIXTURES SPACE.
MAINTAIN NORMAL SWITCHING SCHEME OF EMERGENCY
FIXTURES UNDER NORMAL OPERATION.
LIGHTING GENERAL NOTES
REVISIONS
P
LO
T D
A T
E
F
IL
E P
A T
H
COPYRIGHT. Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Cannon Moss Brygger & Associates is prohibited by copyright law.
IF THIS DRAWING IS NOT 30"x42" IT IS NOT TO SCALE
SHEET
D A
T E
P R
O J
E C
T
/1
/2
:0 :2
A
M
A u to d e s k D o c s /D
A S
H H
S C
H M
H I T u n n e l
E le v a to r/ M
E P
T C
H M
I E le v a to r_ R
.r v t
ME2.1
C H
E R
O K
E E
, I O
W A
D A
S H
H S
C H
M H
I F
O U
R C
O R
N E
R S
E L
E V
A T
O R
R E
P L
A C
E M
E N
T
IO
W
A D
A S
M E
C H
A N
IC
A
L
E L
E C
T R
IC
A
L F
L O
O R
P L
A N
S
1/4" = 1'-0"
ROOF CONNECTING
1/4" = 1'-0"
THIRD FLOOR PLAN
1/4" = 1'-0"
SECOND FLOOR PLAN
1/4" = 1'-0"
FIRST FLOOR PLAN
1/4" = 1'-0"
BASEMENT PLAN
1/4" = 1'-0"
BASEMENT PLAN - MECH
1/16" = 1'-0"
BASEMENT AREA ELECTRICAL PLAN
NO. DESCRIPTION DATE
NOT TO SCALE
DISTRIBUTION PANEL
INSTALL NEW 200A 3P BREAKER
IN PANEL FOR NEW ELEVATOR
BRANCH PANEL
COORDINATE DOWNTIME OF DISTRIBUTION PANEL WITH DCI GROUP AND OWNER A MINIMUM OF 7 DAYS IN ADVANCE. CONTRACTOR IS ALLOWED UP TO (1) 2 HOUR SHUTDOWNS OF THE DISTRIBUTION PANEL DURING THE COURSE OF CONSTRUCTION. SHUTDOWNS TO TAKE
PLACE BETWEEN THE HOURS OF 5AM AND 7AM ON A WEEKDAY.
ROUTE LINE SETS AND ELECTRICAL WIRES THROUGH WALL.
SEAL PENETRATIONS WATERTIGHT.
BOLTED OR WELDED 2X2-1/4" STEEL ANGLE. ANCHOR TO EXTERIOR WALL.
BUILDING EXTERIOR
CONDENSING UNIT
SECURE CONDENSING UNIT
TO ANGLE BRACING. PROVIDE
NECESSARY SUPPORT AS NEEDED.
MAINTAIN MFR'S RECOMMENDED
CLEARANCES (TYP.)
SECURE/ANCHOR WIRING AND LINE
SETS OFF EXTERIOR OF BUILDING PER
MFR'S RECOMMENDATIONS
NOTE:
REFER TO MANUFACTURER'S RECOMMENDATIONS FOR MOUNTING AND BRACING INSTALLATION. DETAIL IS CONCEPTUAL. PROVIDE APPROPRIATE ANCHORING HARDWARE FASTENERS FOR MOUNTING OF ANGLE TO
EXTERIOR SURFACE.
1"
PIPE SUPPORT
SEAL PIPE PENETRATION PER
SPECIFICATIONS
PUMPED CONDENSATE DRAIN PIPE FROM
SPLIT SYSTEM. SEE DRAWINGS FOR PIPE
SIZE AND LOCATION
STANDARD SHORT RADIUS ELBOW
FINE MESH STAINLESS STEEL
SCREEN. FASTEN TO PIPE WITH
STAINLESS STEEL HOSE CLAMP.
FINISHED GRADE
M
IN
CONCRETE SPLASH PAD
ELEVATOR PIT
BOTTOM FLOOR CEILING
TOP FLOOR
TOP FLOOR CEILING
KEY NOTES:
FUSED, LOCKABLE MAIN DISCONNECT SWITCH AND DEDICATED
CAT6 DATA TERMINATION TO SERVE ELEVATOR MAIN POWER.
PROVIDED WITH NO/NC LOW VOLTAGE CONTACTS.
FUSED, LOCKABLE 120V/1POLE DISCONNECT SWITCH TO SERVE
ELEVATOR AUXILLIARY LIGHTING/VENTILATION,
DEDICATED CIRCUIT 120V DUPLEX GFCI MAINTENANCE
RECEPTACLE WITHIN MACHINE ROOM SPACE ADJACENT TO
DISCONNECTS.
FIRE ALARM SYSTEM HAT FLASH, PRIMARY RECALL, SECONDARY
RECALL.
S
HEAT & SMOKE DETECTORS INSTALLED AT TOP OF HOISTWAY.
ELEVATOR HOISTWAY LIGHTING. TYP.
PROVIDE HOISTWAY LIGHTING CONTROLS THREE WAY SWITCHES AT
BOTTOM AND TOP FLOOR HOISTWAY ENTRIES. WHERE MULTIPLE CARS
SHARE A COMMON HOISTWAY, PROVIDE 4 WAY SWITCHES AND PROVIDE
SWITCH AT EACH CARS BOTTOM AND TOP FLOORS. SWITCH SHALL
CONTROLS ALL LIGHTING IN HOISTWAY AND PIT
S
LOBBY, TOP FLOOR
TOP OF HOISTWAY
HOISTWAY LIGHTING SWITCH
S
ELEVATOR LOBBY SMOKE DECTOR.
<21' FROM CENTERLINE OF ELEVATOR
DOOR. TYP FOR EVERY LOBBY.
ELEVATOR LOBBY SMOKE DECTOR.
<21' FROM CENTERLINE OF ELEVATOR
DOOR. TYP FOR EVERY LOBBY.
LOBBY, BOTTOM FLOOR S
HEAT AND SMOKE DETECTOR WITHIN
ELEVATOR MACHINE ROOM.
MACHINE ROOM
HOISTWAY LIGHTING SWITCH
120V DEDICATED CIRCUIT PIT SUMP
PUMP SIMPLEX RECEPTACLE
120V DEDICATED CIRCUIT PIT
MAINTENANCE GFCI DUPLEX RECEPTACLE
BOTTOM FLOOR
TYPICAL ELEVATOR HOISTWAY ELEVATION TYPICAL ELEVATOR MACHINE ROOM
ELEVATOR
MAIN POWER
DISCONNECT
ELEVATOR
CONTROL
PANEL
ELEVATOR MACHINE
ROOM LIGHTING.
DEDICATED CIRCUIT. TYP.
AOM
FIRE ALARM
SYSTEM RELAYS
MACHINE ROOM
LIGHTING SWITCH
ELEVATOR
AUX POWER
DISCONNECT
ELEVATOR CAB
RESCUE ASSISTANCE
SYSTEM DISCONNECT
FUSED, LOCKABLE 120V/1POLE DISCONNECT SWITCH AND
DEDICATED CAT6 DATA TERMINATION TO SERVE ELEVATOR CAB
INTERNAL RESCUE ASSISTANCE SYSTEM.
MAINTENANCE
RECEPTACLE
ELEVATOR HOISTWAY LIGHTING POWERED BY DEDICATED
CIRCUIT. FOR EACH CAR, PROVIDE LIGHT FIXTURE AT TOP OF
HOISTWAY, PIT, AND AT EACH FLOOR. FIXTURES ABOVE PIT
LOCATED TO ILLUMINATE TOP OF CAR AT EACH STOP, TYPICAL 10'
ABOVE EACH LEVEL.
EXISTING FIXTURE TO REMAIN
LOCKABLE ELEVATOR
BREAKER IN PANEL EL
NO/NC LV CONTACTS
208V/3PH
LV
ELEVATOR
CONTROLLER
120V/1PH 120V/1PHELEVATOR AUXILARY
DISCONNECT SWITCH
FUSED/LOCKABLE
20A/1P DEDICATED CIRCUIT
120V/1PH 120V/1PHELEVATOR INTERNAL
RESCUE ASSISTANCE
DISCONNECT SWITCH
FUSED/LOCKABLE
20A/1P DEDICATED CIRCUIT
LV/CAT6POTS LINE FROM
BUILDING MDF
1LV/CAT6
LVFIRE ALARM
CONTROL PANEL
LV
LV/CAT6CAT6 FROM
BUILDING MDF
1LV/CAT6
AOM
HAT FLASH, PRIMARY,
SECONDARY RECALL
HOISTWAY LIGHTINGDEDICATED 20A/1P CIRCUIT
PIT GFCI DUPLEXDEDICATED 20A/1P CIRCUIT
MACHINE ROOM GFCI DUPLEXDEDICATED 20A/1P CIRCUIT
PIT SUMP PUMP SIMPLEXDEDICATED 20A/1P CIRCUIT
MACHINE ROOM LIGHTINGDEDICATED 20A/1P CIRCUIT
MACHINE ROOM HVACDEDICATED 208V-35A/2P CIRCUIT
120V/1PH
120V/1PH
120V/1PH
120V/1PH
120V/1PH
208V/1PH
TYPICAL ELEVATOR SYSTEMS WIRING DIAGRAM
INSTALL NEW CONDUCTORS
(3) #1/0 + (1) #6 GND IN 2" C
SUMP PUMP SCHEDULE
REFERENCE SP-1
MANUFACTURER HYDOMATIC
MODEL # SPD
SERVES ELEVATOR PIT
CONFIGURATION SINGLE
GPM 50
BASIN TYPE EXISTING CONCRETE
BASIN SIZE (DIAM x HEIGHT) EXISTING 36x48
FT HEAD 25
HP 1
VOLTAGE/PH 120/1
NOTES 1,2,3,4
NOTES:
1. PROVIDE WITH WATERPROOF POWER CABLE, VERIFY FINAL LENGTH. MINIMUM 20 FT.
2. PROVIDE WITH INTEGRAL FLOAT SWITCH OR PIGGY BACK FLOAT.
3. INSTALL TO MEET STATE ELEVATOR CODE REQUIREMENTS.
4. PROVIDE WITH OIL MINDER SYSTEM.
SPLIT SYSTEM INDOOR UNIT SCHEDULE
REFERENCE SSI-1
MANUFACTURER MITSUBISHI
MODEL # PKA-A24NL
TYPE WALL MOUNT
WEIGHT (LBS) 46
DIMENSIONS - L x W x D (INCHES) 46 x 12 x 14
NOMINAL CAPACITY (TONS) 2.00
MAX UNIT AIRFLOW (CFM) 775
COOLING CAPACITY - RATED (BTU/H) 24,000
HEATING CAPACITY - RATED (BTU/H) N/A
REFRIGERANT TYPE R454B
VOLTAGE - PH 208 - 1
ELECTRICAL DATA
MCA 1.00
MOCP SEE SSO SCHEDULE
NOTES 1,2,3,4
NOTES:
1. PROVIDE WITH REMOTE WALL MOUNTED THERMOSTAT. WIRING BY M.C.
2. INDOOR UNIT RECEIVES POWER FROM OUTDOOR UNIT BY INTERCONNECTED WIRING
PROVIDED WITH UNIT, WIRING INSTALLATION AND DISCONNECT BY E.C.
3.COOLING RATED CAPACITY IS BASED ON THE FOLLOWING CONDITIONS. INDOOR: 80°F/67°
FF, OUTDOOR: 95°F/75°F
4. PROVIDE FILTER AND CONDENSATE PUMP WITH UNIT.
5. UNIT IS COOLING ONLY.
SPLIT SYSTEM OUTDOOR UNIT SCHEDULE
REFERENCE SSO-1
MANUFACTURER MITSUBISHI
MODEL # PUY-AH24NL
SERVES SSI-1
WEIGHT (LBS) 155
DIMENSIONS W/ CURB & ACCESSORIES - L x W x H (INCHES) 37 x 14 x 38
NOMINAL CAPACITY (TONS) 2.00
COOLING CAPACITY - RATED (BTU/H) 24,000
HEATING CAPACITY - RATED (BTU/H) N/A
REFRIGERANT TYPE R454B
COMPRESSOR QUANTITY 1
EFFICIENCY - SEER2 21.1
ELECTRICAL DATA
VOLTAGE - PH 208 - 1
MCA 22
MOCP 37
NOTES 1,2,3,4
NOTES:
1. DISCONNECT SHALL BE PROVIDED / INSTALLED BY E.C.
2. UNIT TO BE MOUNTED ON EXTERIOR SIDEWALL. REFER TO INSTALLATION DETAIL ON PLANS.
3. REFER TO SPLIT SYSTEM INDOOR UNIT SCHEDULE FOR CAPACITY RATING CONDITIONS.
4. SYSTEM REQUIRES LOW AMBIENT AIR COOLING OPERATION (-20 °F), PROVIDE LOW AMBIENT
WIND BAFFLES, SNOW AND HAIL GUARDS.
REVISIONS
P
LO
T D
A T
E
F
IL
E P
A T
H
COPYRIGHT. Permission to reproduce all or part of this drawing is hereby granted solely for the limited purpose of construction of this project or archiving. Unauthorized copying, disclosure or construction use without written permission of Cannon Moss Brygger & Associates is prohibited by copyright law.
IF THIS DRAWING IS NOT 30"x42" IT IS NOT TO SCALE
SHEET
D A
T E
P R
O J
E C
T
/1
/2
:0 :2
A
M
A u to d e s k D o c s /D
A S
H H
S C
H M
H I T u n n e l
E le v a to r/ M
E P
T C
H M
I E le v a to r_ R
.r v t
ME3.1
C H
E R
O K
E E
, I O
W A
D A
S H
H S
C H
M H
I F
O U
R C
O R
N E
R S
E L
E V
A T
O R
R E
P L
A C
E M
E N
T
IO
W
A D
A S
M E
C H
A N
IC
A
L
E L
E C
T R
IC
A
L D
E T
A
IL
S
NTS
WALL MOUNTED CONDENSING UNIT
DETAIL
NTS
CONDENSATE DRAIN DISCHARGE
PIPING DETAIL
NOT TO SCALE
ELEVATOR SYSTEM DETAIL
NOT TO SCALE
ELEVATOR SYSTEM DETAIL
HOA HAND-OFF-AUTO VFD VARIABLE FREQUENCY DRIVE 8. INCLUDE AUXILIARY CONTACTS AND LOW-VOLTAGE WIRING TO AUXILIARY EQUIPMENT THAT RUNS IN TANDEM WITH EQUIPMENT, (I.E. 120V DAMPERS WITH 480V MOTORS).
GF GROUND FAULT CIRCUIT INTERRUPTION TS TOGGLE SWITCH 7. VERIFY ALL EQUIPMENT LOCATIONS WITH THE ASSOCIATED SUB-CONTRACTOR.
FDS FUSED DISCONNECT SWITCH, HEAVY DUTY TOR TIME DELAY OFF RELAY 6. PROVIDE HEAVY DUTY DISCONNECTS RATED FOR THE INSTALLED ENVIRONMENT; NEMA 1 INDOORS, MINIMUM NEMA 3R OUTDOORS.
FAR FIRE ALARM SHUTDOWN RELAY ST SHUNT TRIP 5. INSTALL DISCONNECTS TO ALLOW EQUIPMENT REMOVAL WITHOUT DISCONNECT REMOVAL AND TO MINIMIZE WIRE LENGTH.
ECB ENCLOSED CIRCUIT BREAKER SS START/STOP PUSHBUTTON
CP CORD AND PLUG PROVIDED WITH UNIT SSP START/STOP PUSHBUTTON WITH PILOT 4. DO NOT RELEASE ELECTRICAL DISTRIBUTION EQUIPMENT UNTIL ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS HAVE BEEN SUBMITTED AND APPROVED. MAKE MINOR ADJUSTMENTS TO BREAKER SIZES, DISCONNECT SIZES, ETC PRIOR TO SUBMITTAL
RELEASE.
CSD COMBINATION STARTER/DISCONNECT SD SUPPLY AIR DUCT DETECTOR
CB CIRCUIT BREAKER IN PANEL RSR RUN STATUS RELAY , NORMALLY OPEN 3. REVIEW EQUIPMENT SHOP DRAWINGS FOR COMPLIANCE AND COORDINATION WITH ELECTRICAL CONNECTIONS. NOTIFY ENGINEER IF CHANGES TO ELECTRICAL CONNECTIONS, WIRING, AND BREAKER REQUIREMENTS ARE NECESSARY.
BO PROVIDED BY OTHERS RF RETURN AIR DUCT DETECTOR
4X NEMA 4X ENCLOSURE PFS PLUG FUSE WITH INTEGRATED SWITCH
4 NEMA 4 ENCLOSURE NFD NON-FUSED DISCONNECT SWITCH, HEAVY DUTY 2.