RFB945900-01 - HHS STS A.E. Sheperd AC Replacement - Drawings.pdf
PDF 2 MB Posted
- Attached to
- HHS STS A. E. Sheperd AC Replacement
- Solicitation number
- RFB945900-01
- Issued by
- Linn County, Iowa
About this file
This is a set of mechanical and electrical design drawings from IMEG Corp. for the Iowa Department of Administrative Services project to replace the air conditioning system at A.E. Sheperd Hall of the State Training School in Eldora, Iowa. The scope includes removing and replacing the existing cooling coil, condensing unit and associated refrigerant piping connected to AHU-2(E) serving the auditorium space. The project is managed by McGough Construction as Construction Manager and includes mechanical work (HVAC modifications) and electrical work to support the new equipment. The drawings are dated January 17, 2025 and labeled as "Bid Documents."
The drawings detail the installation of a new Daikin 288 MBH nominal cooling capacity VRF system with associated electrical power connections from Panel A. The design includes a new cooling coil (CC-1) rated for 6000 CFM airflow and new twinned condensing units (CU-1) with R-410A refrigerant. Electrical modifications include new 50A/3P circuit breakers and associated power wiring. The drawings contain detailed mechanical and electrical plans, diagrams, schedules and sequences of operation for the new equipment installation. All work must comply with applicable codes including IBC 2015, IMC 2021, and NEC 2020 editions.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING CODE: IBC 2015 EDITION
FIRE CODE: IFC 2015 EDITION
PLUMBING CODE: UPC 2021 EDITION
MECHANICAL CODE: IMC 2021 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2020 EDITION
ENERGY CONSERVATION CODE: IECC 2012
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS
INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908
The FUTURE. Built Smarter www.imegcorp.com
PROJECT DIRECTORY
CLIENT:
SCOPE OF WORK
REMOVE AND REPLACE EXISTING COOLING COIL, CONDENSING UNIT AND
ASSOCIATED REFRIGERANT PIPING CONNECTED TO AHU-2(E) SERVING THE
AUDITORIUM SPACE OF SHEPERD HALL OF THE STATE TRAINING SCHOOL
IN ELDORA, IOWA.
MECHANICAL
ENGINEER:
APPLICABLE CODES DRAWING INDEX
IMEG CORP.
2882 106TH STREET
DES MOINES, IA 50322
PHONE: (515) 334-4303
CONTACT: NATE JACQUES
ELECTRICAL
ENGINEER:
IMEG CORP.
2882 106TH STREET
DES MOINES, IA 50322
PHONE: (515) 639-3041
CONTACT: KRISTEN SPINA
VICINITY MAP
AGENCY APPROVAL
REVISIONS
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #24006792.00
IOWA DEPARTMENT OF
ADMINISTRATIVE SERVICES
CONSTRUCTION MANAGER
MCGOUGH CONSTRUCTION
217 E 2ND ST SUITE 120
DES MOINES, IA 50309
/2
/2
:5 :3
A
M
12" = 1'-0"
.0
3211 Edgington Ave Eldora, IA 50627
9459.00 - HHS STS A.E. SHEPERD AC
REPLACEMENT
9459.00 - HHS STS A.E. SHEPERD AC
REPLACEMENT
3211 Edgington Ave Eldora, IA 50627
G000
PROJECT COVERSHEET
NATJAC
PETERN
EVAHAM
24006792.00
01/17/2025
BID DOCUMENTS
9459.00 - HHS STS A.E.
SHEPERD AC
REPLACEMENT
Sheet List Number Name
PROJECT COVERSHEET
G000 PROJECT COVERSHEET
HVAC
M000 HVAC COVERSHEET
M100 FIRST FLOOR DEMOLITION PLAN - MECHANICAL
M201 FLOOR PLAN - MECHANICAL
M500 MECHANICAL DIAGRAMS
M400 MECHANICAL DETAILS AND SCHEDULES
ELECTRICAL
E000 ELECTRICAL COVERSHEET
E101 DEMOLITION FLOOR PLAN - ELECTRICAL
E201 FLOOR PLAN - ELECTRICAL
E400 ELECTRICAL DETAILS
E600 ELECTRICAL SCHEDULES
PROJECT VICINITY
PROJECT LOCATION
CONSTRUCTION MANAGER
MCGOUGH CONSTRUCTION
217 E 2ND ST SUITE 120
DES MOINES, IA 50309
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE
OF IOWA.
DATE
MY LICENSE EXPIRATION DATE IS: 12/31/2026
PAGES OR SHEETS COVERED BY THIS SEAL:
I O W A
S E
D
PROFESS IONA
P21686
L
IC
E N
L E
N G
I N E
E R
NATHANIEL K.
JACQUES
NATHANIEL K. JACQUES
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE
OF IOWA.
DATE
MY LICENSE EXPIRATION DATE IS: 12/31/2025
PAGES OR SHEETS COVERED BY THIS SEAL:
I O W A
S E
D
PROFESS IONA
P21081
L
IC
E N
L E
N G
I N E
E R
KRISTEN L.
SPINA KRISTEN L. SPINA
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE
OF IOWA.
DATE
MY LICENSE EXPIRATION DATE IS: 12/31/2026
PAGES OR SHEETS COVERED BY THIS SEAL:
I O W A
S E
D
PROFESS IONA
P21686
L
IC
E N
L E
N G
I N E
E R
NATHANIEL K.
JACQUES
NATHANIEL K. JACQUES
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE
OF IOWA.
DATE
MY LICENSE EXPIRATION DATE IS: 12/31/2025
PAGES OR SHEETS COVERED BY THIS SEAL:
I O W A
S E
D
PROFESS IONA
P21081
L
IC
E N
L E
N G
I N E
E R
KRISTEN L.
SPINA KRISTEN L. SPINA
01/17/2025
01/17/2025
ALL E - SERIES DRAWINGS
ALL M - SERIES DRAWINGS
1. PIPE DRAIN LINES FROM EQUIPMENT TO NEAREST FLOOR DRAIN.
2. INSTALL ALL REFRIGERANT LIQUID AND SUCTION PIPING SIZED PER EQUIPMENT
MANUFACTURER RECOMMENDATIONS.
PIPING GENERAL NOTES:
1. BEFORE ANY DEMOLITION WORK IS BEGUN A COMPLETE AIR BALANCE TEST SHALL BE
PERFORMED BY THE TESTING, ADJUSTING AND BALANCING (TAB) CONTRACTOR ON
EXISTING AHU-2(E) AND AIR OUTLETS SERVING THE AREAS AFFECTED BY CONSTRUCTION.
EQUIPMENT TO BE DEMOLISHED DOES NOT REQUIRE TESTING. PROVIDE AIR BALANCE
TESTING ONLY ON EQUIPMENT THAT WILL CONTINUE TO BE USED TO SERVE RENOVATED
AREAS AFTER THE CONSTRUCTION PHASE IS COMPLETED.
2. TAB CONTRACTOR SHALL COMPILE AND SUBMIT ONE COPY OF THE FINAL PRE-DEMOLITION
REPORT WITHIN 10 WORKING DAYS AFTER THE FIELD MEASUREMENTS ARE COMPLETED.
FINAL TAB REPORT SHALL BE SUBMITTED FOR REVIEW TO THE ARCHITECT/ENGINEER.
TESTING SHALL INCLUDE ALL ITEMS REQUIRED IN THE SPECIFICATIONS.
TAB PRE-DEMOLITION NOTES:
1. AFTER CONSTRUCTION ACTIVITIES ARE COMPLETE, TESTING, ADJUSTING (TAB) AND
BALANCING CONTRACTOR SHALL REBALANCE AIR HANDLING UNITS FANS AS REQUIRED TO
ACHIEVE THE NEW AIRFLOW VALUES SHOWN ON THE CONSTRUCTION DRAWINGS.
2. TAB CONTRACTOR SHALL COMPILE AND SUBMIT ONE COPY OF THE FINAL POST-
CONSTRUCTION TAB REPORT AS REQUIRED BY SECTION 23 05 93.
3. THE FINAL POST CONSTRUCTION REPORT SHALL INCLUDE ALL ITEMS REQUIRED IN THE
SPECIFICATIONS.
TAB POST-CONSTRUCTION NOTES:
MECHANICAL GENERAL NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,
AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE
INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. CATALOG AND MODEL NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN
AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR
IS RESPONSIBLE FOR THE COMPLETE DESCRIPTION OF MATERIAL SCHEDULED ON THESE
DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE
MATERIAL AND SCHEDULED PERFORMANCE TAKES PRECEDENCE OVER THE MODEL
NUMBER. THE FIRST MANUFACTURER SCHEDULED IS THE BASIS OF DESIGN.
3. DETERMINATION OF QUANTITIES OF MATERIAL AND EQUIPMENT REQUIRED SHALL BE MADE
BY THE CONTRACTOR FROM THE DOCUMENTS. WHERE MATERIAL AND/OR QUANTITY
DISCREPANCIES ARISE BETWEEN DRAWINGS, SCHEDULES AND/OR SPECIFICATIONS, THE
HIGHER QUALITY/ GREATER NUMBER SHALL GOVERN.
4. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM
APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING
THOSE OF OTHER TRADES.
5. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE
CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO
VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO
VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES
OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING
WITH FABRICATION OR EQUIPMENT ORDERS.
6. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE
REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER
ACCESS.
7. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO
COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR
EXPENSE TO OTHERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL
CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF
DESIGN.
9. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,
FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
10. SEAL ALL WALL PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS
PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS SHALL BE SEALED AIRTIGHT
WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR
USE.
11. CAULK ALL PIPE PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL & PARTITION
ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO
ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.
12. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT
MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND
REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF PIPING, DUCTWORK,
ETC.
13. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES.
14. MAINTAIN A MINIMUM WORKING CLEARANCE OF 3’-6” IN FRONT OF ALL ELECTRICAL
EQUIPMENT REQUIRING MAINTENANCE, INSPECTION, AND TESTING INCLUDING BUT NOT
LIMITED TO PANELS, DISTRIBUTION PANELS, SWITCHBOARDS, MOTOR CONTROL CENTERS,
TRANSFORMERS, EQUIPMENT DISCONNECTS AND STARTERS.
15. MAINTAIN THE DEDICATED ELECTRICAL EQUIPMENT SPACE DEFINED BY THE WIDTH / DEPTH
OF ELECTRICAL EQUIPMENT MEASURED FROM THE FLOOR TO A HEIGHT 6’-0” ABOVE THE
EQUIPMENT OR THE STRUCTURAL CEILING, WHICHEVER IS LOWER. SYSTEMS FOREIGN TO
THE ELECTRICAL DISTRIBUTION SYSTEM ARE NOT ALLOWED IN THE DEDICATED
ELECTRICAL SPACE INCLUDING: DUCTWORK, PIPING, ETC.
MECHANICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS
BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR PIPING BEFORE FABRICATION. RISES AND
DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL CUT AND PATCH WALLS ASSOCIATED WITH THEIR WORK.
5. THIS CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS,
CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
6. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH
NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL
EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT
DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL
SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
7. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY
REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW
SYSTEMS ARE INSTALLED.
8. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR
TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND
CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY
DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
9. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT
THAT HAS BEEN REMOVED.
10. PROPERLY RECLAIM AND DISPOSE OF ALL REFRIGERANT IN REMOVED EQUIPMENT/
REFRIGERANT PIPING. RECLAIMED REFRIGERANT SHALL HAVE DOCUMENTATION AS
REQUIRED BY THE AUTHORITY HAVING JURISDICTION (AHJ).
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 KEYNOTE: INDICATES NOTE USED TO
DESCRIBE ADDITIONAL INFORMATION
ABOUT WORK REQUIRED, SPECIFIC
TO THE SHEET AND/OR DETAIL
N O R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
BUILDING CODE: IBC 2015 EDITION
FIRE CODE: IFC 2015 EDITION
PLUMBING CODE: UPC 2021 EDITION
MECHANICAL CODE: IMC 2021 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2020 EDITION
ENERGY CONSERVATION CODE: IECC 2012
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS
INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:
TEMPERATURE CONTROLS CONTRACTORT.C.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
CONSTRUCTION MANAGERC.M.
CONTACT PERSONS:
PROJECT MANAGER
MECHANICAL
ELECTRICAL
NATE JACQUES
EVAN HAMMER
KRISTIN SPINA
DESCRIPTION: PERSON:
HVAC ABBREVIATION KEY
ABBR: DESCRIPTION:
NOT IN CONTRACTNIC
TYPICALTYP
UON UNLESS OTHERWISE NOTED
SCCR SHORT CIRCUIT CURRENT RATING
DN DOWN
MANUAL VOLUME DAMPER
DUCT CAP
DUCT DOWN
DUCT UP
SUPPLY/OUTSIDE AIR DUCT SECTION
RETURN AIR DUCT SECTION
SD-# AIR TERMINAL NAME
HVAC SYMBOL LIST
SYMBOL: DESCRIPTION:
NOT ALL SYMBOLS MAY APPLY.
PITCH PIPE IN DIRECTION
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
HEATING WATER RETURNHWR
HEATING WATER SUPPLYHWS
REFRIGERANT LIQUIDLIQ
REFRIGERANT SUCTIONSUC
HVAC SYMBOL LIST
SYMBOL: DESCRIPTION:
NOT ALL SYMBOLS MAY APPLY.
REFRIGERANTREF
TEMPERATURE CONTROLS ABBREVIATION KEY
ABBR: DESCRIPTION:
NO NORMALLY OPEN
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
REF REFRIGERANT
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908
The FUTURE. Built Smarter www.imegcorp.com
AGENCY APPROVAL
REVISIONS
No. Date Revision / Issue
DISCLAIMER
IOWA DEPARTMENT OF
ADMINISTRATIVE SERVICES
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #24006792.00
CONSTRUCTION MANAGER
MCGOUGH CONSTRUCTION
217 E 2ND ST SUITE 120
DES MOINES, IA 50309
As indicated
/2
/2
:5 :3
A
M
9459.00 - HHS STS A.E.
SHEPERD AC
REPLACEMENT
3211 Edgington Ave Eldora, IA 50627
M000
HVAC COVERSHEET
NATJAC
PETERN
EVAHAM
24006792.00
01/17/2025
BID DOCUMENTS
.0
HVAC SHEET INDEX
M000 HVAC COVERSHEET
M100 FIRST FLOOR DEMOLITION PLAN - MECHANICAL
M201 FLOOR PLAN - MECHANICAL
M500 MECHANICAL DIAGRAMS
M400 MECHANICAL DETAILS AND SCHEDULES
GRAND TOTAL: 5
DUCT ABBREVIATION KEY
ABBR. DESCRIPTION
OA OUTSIDE AIR
RA RETURN/RELIEF AIR
SA SUPPLY AIR
ENTRY VESTIBULE
STAIR
VEST #1
LOBBY
DN
ø
S A ø
S A ø
S A ø
S A ø
S A ø
S A ø
S A ø
S A ø
S A ø
S A ø
S A ø
S A
SD-E
SD-E
SD-E SD-E
SD-E
SD-E
SD-E
SD-E
SD-E
SD-E
SD-E
SD-E
26ø SA30ø SA 22ø SA
AHU-2(E)
36ø SA24ø SA
LV-E
48x20 RA
66x18 RA
8x66 OA
30x30 OA
42x42 OA
2"V
2"V UP TO VTR
3"HWS
3"HWR
1/2"CWS
1"V
2"CWR
CU-E
CAP REFRIGERANT
PIPING AT WALL.
ABANDON
REMAINING PIPING
IN PLACE.
CAP REFRIGERANT
PIPING AT WALL.
ABANDON REMAINING
PIPING IN PLACE.
CAP REFRIGERANT
PIPING AT WALL.
ABANDON REMAINING
PIPING IN WALL IN
PLACE.
CAP REFRIGERANT
PIPING AT WALL.
ABANDON REMAINING
PIPING WITHIN WALL IN
PLACE.
REMOVE EXISTING
REFRIGERANT PIPING
REMOVE EXISTING
REFRIGERANT PIPING
REMOVE THE EXISTING R-22 REFRIGERANT
COOLING COIL AND ASSOCIATED PIPING,
VALVES, SPECIALTIES, AND CONTROLS
FROM THE EXISTING TO REMAIN AHU-2(E).
TAKE CARE IN THE REMOVAL OF THE COIL,
FOR INSTALLATION OF NEW COOLING COIL.
REMOVE EXISTING
CONDENSATE TRAP
EXISTING PAD
UNDER CU-E TO
BE REUSED FOR
NEW CU.
BEFORE ANY DEMOLITION WORK IS BEGUN,
A COMPLETE AIR BALANCE TEST SHALL BE
PERFORMED BY THE TESTING, ADJUSTING
AND BALANCING (TAB) CONTRACTOR ON
EXISTING AHU-2(E) AND AIR OUTLETS
SERVING THE AREAS AFFECTED BY
CONSTRUCTION. EQUIPMENT TO BE
DEMOLISHED DOES NOT REQUIRE TESTING.
CU-E
CU-E
EXISTING CONDENSING
UNITS TO REMAIN
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908
The FUTURE. Built Smarter www.imegcorp.com
AGENCY APPROVAL
REVISIONS
No. Date Revision / Issue
DISCLAIMER
IOWA DEPARTMENT OF
ADMINISTRATIVE SERVICES
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #24006792.00
CONSTRUCTION MANAGER
MCGOUGH CONSTRUCTION
217 E 2ND ST SUITE 120
DES MOINES, IA 50309
1/4" = 1'-0"
/2
/2
:5 :4
A
M
9459.00 - HHS STS A.E.
SHEPERD AC
REPLACEMENT
3211 Edgington Ave Eldora, IA 50627
M100
FIRST FLOOR DEMOLITION PLAN -
MECHANICAL
NATJAC
PETERN
EVAHAM
24006792.00
01/17/2025
BID DOCUMENTS
.0
N O R
HT
1/4" = 1'-0"1
FIRST FLOOR DEMOLITION PLAN - MECHANICAL
STAIR
VEST #1
LOBBY
WOMEN'S RESTROOM
DN
ø
S A ø
S A ø
S A ø
S A ø
S A ø
S A ø
S A ø
S A ø
S A ø
S A ø
S A ø
S A
SD-E
SD-E
SD-E SD-E
SD-E
SD-E
SD-E
SD-E
SD-E
SD-E
SD-E
SD-E
26ø SA30ø SA 22ø SA
AHU-2(E)
36ø SA 24ø SA
LV-E
48x20 RA
66x18 RA
8x66 OA
30x30 OA
42x42 OA
CONTRACTOR TO INSTALL
MANUAL BALANCING
DAMPER IN EXISITNG SA
DUCT. BALANCE TO 1500
CFM IN DUCT BRANCH.
EXISTING DUCT IS
INTERNALLY LINED FOR
INSULATION.
SIZE & INSTALL REFRIGERANT
PIPING AS PER
MANUFACTURER'S
REQUIREMENTS.
EXISTING REFRIGERANT PIPING
ABANDONED IN PLACE.
EXISTING REFRIGERANT PIPING
ABANDONED IN PLACE.
CONTRACTOR TO INSTALL
MANUAL BALANCING
DAMPER IN EXISITNG SA
DUCT. BALANCE TO 1500
CFM EACH DUCT BRANCH.
EXISTING DUCT IS
INTERNALLY LINED FOR
INSULATION.
MOUNT CONTROL BOX AS
HIGH AS POSSIBLE. INSTALL
PLYWOOD BACKING OVER
EXISTING TRANSFER GRILLE
FOR CONTROL BOX
MOUNTING. PLYWOOD
BACKING SHALL ONLY BE
LARGE ENOUGH TO MOUNT
CONTROL BOXES, AND SHALL
NOT COVER ENTIRE
TRANSFER GRILLE (TYP. 2).
ROUTE REFRIGERANT PIPING UNDER
LIGHTS. WHITE PVC JACKET
REQUIRED ON REFRIGERANT PIPING.
PAINT TO MATCH AUDITORIUM
WALLS.
WHITE PVC JACKET
REQUIRED ON
REFRIGERANT PIPING.
NEW CONDENSING
UNIT ON EXISTING PAD.
CC-1
INSTALL NEW CC-1 IN EXISTING AIR HANDLER
AHU-2(E). BLANK-OFF ANY UN-USED AIR
TUNNEL WITH DOUBLE-WALLED PANELS TO
MATCH EXISTING AHU-2(E) CONSTRUCTION.
CONNECT TWO CIRCUITS OF
REFRIGERANT PIPING TO CC-1 PER
MANUFACTURER'S
RECOMMENDATIONS. NOT ALL
LINES SHOWN CONNECTED TO CC-1
IN PLAN FOR CLARITY.
PROVIDE NEW
P-TRAP PER
DETAIL 2/M400.
2"V UP TO
4" VTR
CU-E
CU-E
PROTECT EXISTING
CONDENSING UNITS
FROM DAMAGE
CORE THROUGH
EXISTING WALL TIGHT
TO UNDERSIDE OF BEAM
CU-1
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908
The FUTURE. Built Smarter www.imegcorp.com
AGENCY APPROVAL
REVISIONS
No. Date Revision / Issue
DISCLAIMER
IOWA DEPARTMENT OF
ADMINISTRATIVE SERVICES
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #24006792.00
CONSTRUCTION MANAGER
MCGOUGH CONSTRUCTION
217 E 2ND ST SUITE 120
DES MOINES, IA 50309
1/4" = 1'-0"
/2
/2
:5 :4
A
M
9459.00 - HHS STS A.E.
SHEPERD AC
REPLACEMENT
3211 Edgington Ave Eldora, IA 50627
M201
FLOOR PLAN - MECHANICAL
NATJAC
PETERN
EVAHAM
24006792.00
01/17/2025
BID DOCUMENTS
.0
N O R
HT
1/4" = 1'-0"1
FIRST FLOOR PLAN - MECHANICAL
.5
CLEANOUT PLUG (TYP.)
ROUTE TO FLOOR DRAIN.
FULL SIZE CONDENSATE
DRAIN, CONNECT TO DRAIN
PAN AS RECOMMENDED BY
MANUFACTURER.
.5
INSTALL AN ESCUTCHEON AROUND PIPES
EXPOSED IN FINISHED ROOMS. IN SUCH
INSTANCES WHERE AN ESCUTCHEON IS
REQUIRED AND THE PIPING IS INSULATED,
INSTALL A PLASTIC JACKET EXTENDING 6"
BEYOND THE WALL TO PROTECT INSULATION
FROM DAMAGE FROM THE ESCUTCHEON.
MAKE A SMOOTH ROUND OPENING IN
WALL SLIGHTLY LARGER THAN OUTSIDE
DIAMETER OF THE PIPE AND INSULATION.
ADD A BEAD OF NON-HARDENING
CAULK IN THE ANNULAR SPACE.
NOTES:
1. THIS DETAIL APPLIES TO ALL PIPES. THE INTENTION IS TO
CONTINUE THE INSULATION AND VAPOR BARRIER THROUGH
ALL PENETRATIONS. PERMIT THERMAL EXPANSION WITHOUT
DAMAGING INSULATION, AND TO SEAL AIRTIGHT AROUND
INSULATED AND UNINSULATED PIPES FOR NOISE
TRANSMISSION CONTROL.
2. SEE SPECIFICATION SECTION 23 05 29 FOR ADDITIONAL
INFORMATION.
NOTES:
1. THIS DIAGRAM IS SCHEMATIC IN NATURE. UNIT MANUFACTURER SHALL SUBMIT DETAILED PIPING DIAGRAM SHOWING
RECOMMENDED PIPING ARRANGEMENT IF DIFFERENT FROM ABOVE.
2. ANY ACCESSORIES SUCH AS ACCUMULATORS, RECEIVERS, SEPARATORS AND HEAT TRACING SHALL BE DETERMINED BY
THE COIL SUPPLIER AND SUBMITTED AS SHOP DRAWINGS. NO COMPENSATION WILL BE MADE IF ACTUAL NUMBER OF
PIPES EXCEED WHAT IS SHOWN.
CONDENSING UNIT
CONDENSING UNIT
CONTROL BOX
CONTROL BOX
AIR FLOW
COOLING COIL
CORE THROUGH EXISTING WALL
TIGHT TO UNDERSIDE OF BEAM
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908
The FUTURE. Built Smarter www.imegcorp.com
AGENCY APPROVAL
REVISIONS
No. Date Revision / Issue
DISCLAIMER
IOWA DEPARTMENT OF
ADMINISTRATIVE SERVICES
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #24006792.00
CONSTRUCTION MANAGER
MCGOUGH CONSTRUCTION
217 E 2ND ST SUITE 120
DES MOINES, IA 50309
12" = 1'-0"
/2
/2
:5 :4
A
M
9459.00 - HHS STS A.E.
SHEPERD AC
REPLACEMENT
3211 Edgington Ave Eldora, IA 50627
M400
MECHANICAL DETAILS AND
SCHEDULES
NATJAC
PETERN
EVAHAM
24006792.00
01/17/2025
BID DOCUMENTS
.0
NO SCALE2
CONDENSATE TRAP - DRAW THROUGH COIL
NOTES:
1.UNITS SHALL BE SELECTED FOR DESIGN COOLING LOAD.
2.COORDINATE ELECTRICAL CONNECTIONS WITH MANUFACTURER UNIT IS SUPPLIED AS MULTIPLE MODULES. EACH MODULE REQUIRES A SEPARATE ELECTRICAL CONNECTION AND DISCONNECT.
3.NOMINAL COOLING CAPACITY RATED AT: INDOOR TEMP = 80°FDB/67°FWB, OUTDOOR TEMP = 95°FDB.
4.DESIGN COOLING CAPACITY SHALL BE RATED AT: INDOOR TEMP = 75°FDB/62.6°FWB, OUTDOOR TEMP = 95°FDB. EFFECTS OF ESTIMATED REFRIGERANT LINE LENGTH SHALL BE INCLUDED IN COMPUTING DESIGN CAPACITY.
5.REFER TO SPECIFICATION SECTION 23 81 45 FOR ADDITIONAL REQUIREMENTS.
6. PROVIDE WITH AN iTM TOUCHSCREEN WITH BACnet INTERFACE FOR INTEGRATION TO EXISTING BUILDING AUTOMATION SYSTEM.
VRF MODULAR OUTDOOR UNIT SCHEDULE
TAG NAME AREA SERVED R
E
F R
IG
E
R A
N T
M A
X R
E F
R
IG
E R
A N
T C
H A
R G
E
L B
S
COOLING
N U
M B
E R
O F
C O
N N
E C
T E
D C
O O
L
IN
G C
O
IL
C O
N N
E C
T
IO
N R
A T
IO
ELECTRICAL MAX. DIMENSIONS (IN.) WEIGHT (LBS)
MANUFACTURER MODEL NOTESN
O
M
IN
A L
M B
H
N O
T E
D E
S
IG
N M
B H
N
O T
E
O P
E R
A T
IN
G
R A
N G
E
F D
B
V O
L T
A G
E
P H
A S
E S
MODULE 1 MODULE 2 DISCONNECT CONTROLLER/STARTER
E M
E R
G E
N C
Y P
O W
E R
L E
N G
T H
W
ID
T H
H E
IG
H
T
D R
Y
O P
E R
A T
IN
G
M C
A
M O
C P
M C
A
M O
C P
B Y
N
O T
E A
T Y
P E
N
O T
E B
B Y
N
O T
E A
S C
C R
CU-1 AUDITORIUM R410A 51.6 288 276 95.0 1 96 208 3 48 50 47.8 50 EC NF MFR 42000 No 98 30 65 1418 1418 DAIKIN RXYQ NOTE 1, 2, 5, & 6
NOTES:
1.PRESSURE DROP BASED ON TOTALLY SATURATED COIL.
2.COIL AND CONDENSING UNIT SHALL BE BY SAME MANUFACTURER.
COIL SCHEDULE - REFRIGERANT
TAG
NAME
AREA
SERVED CFM
MAX. FPM
FACE
VELOCITY
EAT
LAT DB °F
TOTAL
MBH
NUMBER OF
CIRCUITS
A.P.D. IN.
W.C. (NOTE 1)
SUCT.
TEMP °F
LIQ.
TEMP °F REFRIGERANT
MAX. DIMENSIONS WEIGHT
MANUFACTURER
(NOTE 2) MODEL NOTESDB °F WB °F LENGTH WIDTH HEIGHT DRY OPERATING
CC-1 AUDITORIUM 6000 400 82.5 68.9 55.5 288 2 0.47 42.0 110.0 R-410A 76" 8" 38" 247 295 DAIKIN 5EJ0706B NOTE 2
NO SCALE3
WALL PENETRATION - NON-FIRE RATED
B. DISCONNECT TYPE:
NF = NON-FUSED
A. DISCONNECT AND CONTROLLER STARTER FURNISHED AND
INSTALLED BY:
MFR = MANUFACTURER
SCHEDULE GENERAL NOTES:
NO SCALE1
REFRIGERANT - PIPING DIAGRAM W/SINGLE COIL
T
F M
T T
T
H
AO DI DI DI AODI DI DI
RETURN
AIR
ACT
O.A.
HEAT
COIL
HWR
N.O.
HWS
RETURN
AIR
DAMPER
OUTSIDE
AIR
DAMPER
PRE-
FILTER
REF
COOLING
COIL
CS
SEQUENCE OF OPERATION FOR AHU-2:
THE CONSTANT VOLUME AIR HANDLER UNIT CONSISTS OF A MIXED AIR SECTION WITH OUTDOOR AIR, EXHAUST AIR, RETURN AIR DAMPERS, PRE-FILTER, MODULATING DX COOLING COIL, HOT
WATER COIL AND PUMP, AND SUPPLY FAN.
AHU-2 OPERATES IN WARM-UP, COOL-DOWN, OCCUPIED, UNOCCUPIED, NIGHT HEATING, NIGHT COOLING, AND SAFETY MODES.
ECONOMIZER OPERATION:
THE ECONOMIZER MODE WILL BE ENABLED WHEN THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE ECONOMIZER SET POINT 60.0 DEG F (ADJUSTABLE).
HEATING/COOLING MODE:
IF THE ROOM TEMPERATURE IS LESS THAN THE ROOM TEMPERATURE SET POINT WITH A 5 DEG F (ADJ.) DEADBAND, THE HEATING MODE SHALL BE ENABLED.
IF THE ROOM TEMPERATURE IS GREATER THAN THE ROOM TEMPERATURE SET POINT WITH A 5 DEG F (ADJ) DEADBAND THE COOLING MODE SHALL BE ENABLED.
WARM UP MODE:
START THE SUPPLY FAN. MODULATE THE HEATING VALVE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SET POINT 110.0 DEG F (ADJUSTABLE). CLOSE THE MIXING DAMPER TO OUTSIDE AIR.
DX TO REMAIN OFF. ENABLE HOT WATER PUMP WHEN SHEPARD BOILERS ARE ENABLED.
COOL DOWN MODE:
START THE SUPPLY FAN. COMMAND THE HEATING VALVE CLOSED, MODULATE THE MIXING DAMPERS, AND STAGE DX TO MAINTAIN THE SUPPLY TEMPERATURE SET POINT (55.0 DEG F
ADJUSTABLE). DISABLE HOT WATER PUMP.
OCCUPIED MODE:
HEATING MODE ENABLED:
START THE SUPPLY FAN. MODULATE THE HEATING VALVE TO MAINTAIN THE SUPPLY TEMPERATURE SET POINT 90.0 DEG F (ADJUSTABLE). MIXING DAMPERS WILL BE CLOSED TO MINIMUM POSITION (10% ADJUSTABLE). DX TO REMAIN OFF. ENABLE HOT WATER PUMP WHEN SHEPARD BOILERS ARE ENABLED. FMCS SHALL SEND A MODULATING SIGNAL TO THE HEATING WATER
CONTROL VALVE MODULATE THE VALVE AS NEEDED TO MAINTAIN THE SPACE TEMPERATURE SETPOINT OF 72.0 DEG F (ADJUSTABLE).
COOLING MODE ENABLED:
START THE SUPPLY FAN. MODULATE MIXING DAMPERS TO MAINTAIN THE MIXED AIR TEMPERATURE SET POINT 55.0 DEG F (ADJUSTABLE). DISABLE HOT WATER PUMP. FMCS SHALL SEND A
MODULATING SIGNAL TO THE CONDENSING UNIT CONTROLLER TO MODULATE THE COMPRESSORS AS NEEDED TO MAINTAIN THE SPACE TEMPERATURE SETPOINT OF 72.0 DEG F
(ADJUSTABLE).
UNOCCUPIED MODE:
STOP THE FAN. CLOSE THE HEATING VALVE. CLOSE THE MIXING DAMPERS TO OUTSIDE AIR. DX TO REMAIN OFF
NIGHT HEATING MODE:
START THE SUPPLY FAN. ENABLE HOT WATER PUMP WHEN SHEPARD BOILERS ARE ENABLED. SET THE HEATING VALVE TO 100% OPEN. CLOSE MIXING DAMPERS TO OUTSIDE AIR.FMCS SHALL
SEND A MODULATING SIGNAL TO THE HEATING WATER CONTROL VALVE MODULATE THE VALVE AS NEEDED TO MAINTAIN THE SPACE TEMPERATURE SETPOINT OF 72.0 DEG F (ADJUSTABLE).
NIGHT COOLING MODE:
START THE SUPPLY FAN. MODULATE MIXING DAMPERS TO MAINTAIN THE MIXED AIR TEMPERATURE SET POINT (55.0 DEG F ADJUSTABLE). DISABLE HOT WATER PUMP. MODULATE DX COOLING
COIL TO MAINTAIN ROOM TEMPERATURE SETPOINT (72.0 DEG F ADJUSTABLE).
SMOKE SAFETY MODE:
STOP THE SUPPLY FAN. STAGE OFF THE DX. CLOSE THE MIXING DAMPERS TO THE OUTSIDE AIR. MODULATE THE HEATING VALVE TO MAINTAIN A SUPPLY TEMPERATURE SET POINT OF (45.0
DEG F ADJUSTABLE).
NOTE:
WHEN AHU-2 IS OCCUPIED, AHU-1 MUST BE OCCUPIED AS WELL. CODE FOR AHU-2 SETS THE OCCUPIED MODE FOR AHU-1.
SUPPLY AIR
TEMP.
SUPPLY
AIR
REMOTE EXTERIOR
TWINNED 12-TON VRV
CONDENSING UNITS.
COMPRESSOR STATUS
FAN STATUS
SYSTEM ALARM
MODULATING
COMPRESSOR STATUS
FAN STATUS
SYSTEM ALARM
MODULATING
CONTROL DIAGRAM NOTE:
DDC CONTROL POINTS THAT ARE EXISTING ARE NOT
INDICATED HERE. DEVICES ARE SHOWN, CONTROL POINTS
FOR THOSE DEVICES ARE NOT. ALL EXISTING DEVICES
AND CONTROL POINTS ARE INTENDED TO REMAIN.
NOTE:
TEXT NOT BOLDED INDICATES EXISTING
SEQUENCE FOR AHU-2(E). BOLD TEXT INDICATES
NEW CONTROL SEQUENCE FOR AHU-2(E).
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908
The FUTURE. Built Smarter www.imegcorp.com
AGENCY APPROVAL
REVISIONS
No. Date Revision / Issue
DISCLAIMER
IOWA DEPARTMENT OF
ADMINISTRATIVE SERVICES
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #24006792.00
CONSTRUCTION MANAGER
MCGOUGH CONSTRUCTION
217 E 2ND ST SUITE 120
DES MOINES, IA 50309
12" = 1'-0"
/2
/2
:5 :4
A
M
9459.00 - HHS STS A.E.
SHEPERD AC
REPLACEMENT
3211 Edgington Ave Eldora, IA 50627
M500
MECHANICAL DIAGRAMS
NATJAC
PETERN
EVAHAM
24006792.00
01/17/2025
BID DOCUMENTS
.0
NO SCALE1
AIR HANDLING UNIT - AUDITORIUM AHU-2(E)
ELECTRICAL ABBREVIATION KEY
AFF ABOVE FINISHED FLOOR
C CONDUIT (BRANCH CIRCUIT OR FEEDER CONTEXT)
CO CONDUIT AND BOX ROUGH-IN ONLY (ROUGH-IN ONLY)
EG EQUIPMENT GROUND
ABBR: DESCRIPTION:
EGC EQUIPMENT GROUNDING CONDUCTOR
AFG ABOVE FINISHED GRADE
EOL END OF LINE
BC BELOW COUNTER
ASR ARCHITECTURAL SURFACE RACEWAY
ABV ABOVE
AFC ABOVE FINISHED CEILING
EPO EMERGENCY POWER OFF
GFR GROUND FAULT REMOTE
HOA HAND/OFF/AUTO
ITR IT RACK MOUNTED RECEPTACLE
NC NORMALLY CLOSED
NEMA # NEMA RATING
NIC NOT IN CONTRACTED SCOPE
NO NORMALLY OPEN
ROOF EQUIPMENT LOCATED ON ROOF ABOVE
SM SURFACE MOUNTED
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
1. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH
PHASE.
2. FLUSH MOUNT ALL DUPLEX RECEPTACLES AND TECHNOLOGY OUTLETS AT +18" FROM
FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. RECEPTACLES AND
OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED. MOUNT
EXTERIOR LOCATED RECEPTACLES WITH WHILE-IN-USE COVERS AT +20" FROM FINISHED
GRADE (CENTER DIMENSIONS) TO MAINTAIN INSTALLATION ADA COMPLIANCE.
3. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS.
4. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND
EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES
IN CEILING TILE PATTERN. SMOKE DETECTORS,CARBON MONOXIDE DETECTORS, AND
OCCUPANCY/VACANCY SENSORS SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR
SUPPLY DIFFUSER OR RETURN GRILLE. CARBON MONOXIDE DETECTORS SHALL BE LOCATED
10 PLUS FT FROM FIRE PLACES, COOKING, AND SIMILAR FUEL-BURNING APPLIANCES.
5. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT
LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS.
PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL
ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE
FURNITURE AND/OR EQUIPMENT.
6. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL
MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT
SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER
CONTRACTOR.
7. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE
WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE
IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
9. ELECTRICAL IDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR COLOR/LABEL
REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.
ELECTRICAL INSTALLATION NOTES:
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS. CONTRACTOR SHALL REVIEW EXISTING
CONDITIONS AND REPORT CONFLICTS.
2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. CONTRACTOR
SHALL REVIEW EXISTING CONDITIONS AND REPORT CONFLICTS.
3. CONTRACTOR SHALL REVIEW EXISTING CONDITIONS PRIOR TO FABRICATION OF CABLE
TRAY, BUSWAY, CONDUIT RACKS, AND OTHER SYSTEMS. RISES AND DROPS MAY BE
NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. ELECTRICAL CONTRACTOR SHALL REVIEW EXISTING CONDITIONS TO VERIFY ACCESSIBILITY
TO THE AREAS OF THEIR WORK INCLUDING WALLS, FLOOR, CEILINGS, CEILING TILES/GRID,
AND ROOF. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE CUTTING, REMOVAL,
PATCHING, AND REINSTALLATION OF AFFECTED AREAS ASSOCIATED WITH THEIR WORK BY
COORDINATING WITH THE GENERAL CONTRACTOR OR QUALIFIED CONTRACTOR.
5. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, FIRE ALARM, AND OTHER LOW VOLTAGE SYSTEMS.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 KEYNOTE: INDICATES NOTE USED TO
DESCRIBE ADDITIONAL INFORMATION
ABOUT WORK REQUIRED, SPECIFIC
TO THE SHEET AND/OR DETAIL
N O R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
TEMPERATURE CONTROLS CONTRACTORT.C.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
CONSTRUCTION MANAGERC.M.
CONTACT PERSONS:
PROJECT MANAGER
MECHANICAL
ELECTRICAL
NATE JACQUES
EVAN HAMMER
KRISTIN SPINA
DESCRIPTION: PERSON:
BUILDING CODE: IBC 2015 EDITION
FIRE CODE: IFC 2015 EDITION
PLUMBING CODE: UPC 2021 EDITION
MECHANICAL CODE: IMC 2021 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2020 EDITION
ENERGY CONSERVATION CODE: IECC 2012
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS
INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:
FEEDERS: SWITCHBOARDS, DISTRIBUTION PANELS,
PANELBOARDS, MOTOR CONTROL CENTERS, ETC.
BRANCH CIRCUITS: LIGHTING, RECEPTACLES,
CONTROLS, ETC.
MECHANICAL EQUIPMENT FEEDERS: PUMPS, CHILLERS,
AIR HANDLING UNITS, ETC.
FLOOR MOUNTED EQUIPMENT FEEDERS: PUMPS, ETC.
(INCLUDE NO MORE THAN 6 FEET OF LFMC TO PUMP)
CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)
WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,
INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)
CONDUIT INSTALLATION SCHEDULE
THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION OF APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAWINGS. THE INSTALLATION OF RMC CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT SPECIFIED IN THIS SCHEDULE. REFER TO CONDUIT AND BOXES SPECIFICATION 26 05 33 FOR ADDITIONAL
INFORMATION.
INSTALLATION TYPE RMC IMC EMT PVC
X X
X X
X X
X X
X X
X
ELEVATED CONCRETE SLABS (ABOVE GRADE)
XX
INTERIOR LOCATIONS WITH FINISHED CEILING AND WALLS: CONCEALED
IN WALLS AND ABOVE FINISHED CEILINGS
INTERIOR LOCATIONS WITHOUT FINISHED CEILINGS: CONCEALED IN
WALL, EXPOSED ABOVE CEILINGS
EXISTING INTERIOR LOCATIONS WITH FINISHED CEILINGS AND WALLS:
CONCEALED IN WALLS AND ABOVE FINISHED CEILING UNLESS
OTHERWISE NOTED
X
XX
X
JB 26 05 33 JUNCTION BOX
J
J
ECONN 26 05 33 ELECTRICAL CONNECTION
E
E
PANEL '###' EXISTING PANELBOARD - SURFACE MOUNT
PANEL '###' EXISTING PANELBOARD - RECESS MOUNT
ELECTRICAL SYMBOL LIST
SYMBOL: TAG: SPEC
SECTION:
DESCRIPTION:
REC-DUP 26 27 26 DUPLEX RECEPTACLE, 125V
REC-DUP-GFI 26 27 26 DUPLEX GFI RECEPTACLE, 125V
REC-DUP-WP 26 27 26 DUPLEX GFI WEATHERPROOF RECEPTACLE 125V
W
ELECTRICAL SYMBOL LIST
SYMBOL: TAG: SPEC
SECTION:
DESCRIPTION:
DS-#/FDS-#/DSS-# 26 28 16 DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
INTERLOCKED RECEPTACLE DISCONNECT.
REFER TO DISC/STA SCHEDULE
MS-# EXISTING SURFACE OR RECESS MOUNTED STARTER.
ELECTRICAL MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
C MOUNT AT CEILING (DEVICE OR ROUGH-IN CONTEXT)
H MOUNT ORIENTED HORIZONTALLY
L MOUNT IN CASEWORK
M MOUNT IN MODULAR FURNITURE
O WIRING DEVICE, OCCUPANCY CONTROLLED
R MOUNT IN SURFACE RACEWAY
S SURFACE MOUNTED
W WEATHERPROOF WIRING DEVICE, NEMA 3R WHILE-IN-USE COVER, WR LISTED
WG WIRE GUARD
WP WEATHERPROOF
RECEPTACLE SUBSCRIPT KEY:
DEVICE
# = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
DEVICE KEY:
ELECTRICAL SHEET INDEX
E000 ELECTRICAL COVERSHEET
E101 DEMOLITION FLOOR PLAN - ELECTRICAL
E201 FLOOR PLAN - ELECTRICAL
E400 ELECTRICAL DETAILS
E600 ELECTRICAL SCHEDULES
GRAND TOTAL: 5
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908
The FUTURE. Built Smarter www.imegcorp.com
AGENCY APPROVAL
REVISIONS
No. Date Revision / Issue
DISCLAIMER
IOWA DEPARTMENT OF
ADMINISTRATIVE SERVICES
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #24006792.00
CONSTRUCTION MANAGER
MCGOUGH CONSTRUCTION
217 E 2ND ST SUITE 120
DES MOINES, IA 50309
As indicated
/2
/2
:5 :4
A
M
9459.00 - HHS STS A.E.
SHEPERD AC
REPLACEMENT
3211 Edgington Ave Eldora, IA 50627
E000
ELECTRICAL COVERSHEET
KRISPI
TONDEL
CHRMAR
24006792.00
01/17/2025
BID DOCUMENTS
.0
TUNEL
STAIR
MECH/ ELEC
UP
S
S
F
M M
M M
C M
S
ENTRY VESTIBULE
STAIR
VEST #1
LOBBY
WOMEN'S RESTROOM
DN
E
E
E
E
E
EXISTING MDP
EXISTING PANEL C
EXISTING PANEL PANEL B
FACP
MS-HCCP
DS-HCCP-2
MS-AHU-2(E)
EXISTING PANEL A
AHU-2(E)
HCCP-2
CU-E
DS-CU-E
DS-ACCU-3B
DS-ACCU-3A
ACCU-3B
ACCU-3A
E101
DS-AHU-2(E)
N O R
HT
1/4" = 1'-0"1
FIRST FLOOR DEMOLITION PLAN - ELECTRICAL
N O R
HT
3/16" = 1'-0"2
BASEMENT FLOOR DEMOLITION PLAN - ELECTRICAL
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908
The FUTURE. Built Smarter www.imegcorp.com
AGENCY APPROVAL
REVISIONS
No. Date Revision / Issue
DISCLAIMER
IOWA DEPARTMENT OF
ADMINISTRATIVE SERVICES
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #24006792.00
CONSTRUCTION MANAGER
MCGOUGH CONSTRUCTION
217 E 2ND ST SUITE 120
DES MOINES, IA 50309
As indicated
/2
/2
:5 :4
A
M
9459.00 - HHS STS A.E.
SHEPERD AC
REPLACEMENT
3211 Edgington Ave Eldora, IA 50627
E101
DEMOLITION FLOOR PLAN -
ELECTRICAL
KRISPI
TONDEL
CHRMAR
24006792.00
01/17/2025
BID DOCUMENTS
.0
KEYNOTES:
1. REMOVE EXISTING ELECTRICAL CONNECTION
FOR EXISTING CONDENSING UNIT.
2. REMOVE EXISTING DISCONNECT SERVING
EXISTING CONDENSING UNIT.
STAIR
VEST #1
LOBBY
WOMEN'S RESTROOM
DN
E
E
E
E
E
E
E
E E
EXISTING PANEL A
EXISTING PANEL PANEL B
FACP
BCU-3
HCCP-2 AHU-2(E)
EF-1
ACCU-3A
ACCU-3B
DS-ACCU-3B
DS-ACCU-3A
MS-HCCP
DS-HCCP-2
DS-AHU-2(E)
MS-AHU-2(E)
DS-ACCU-1
DS-CU-1CU-1
MDP-5
DS-CU-1
MECH CONTROL BOX
A-38
MECH CONTROL BOX
A-40
W
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908
The FUTURE. Built Smarter www.imegcorp.com
AGENCY APPROVAL
REVISIONS
No. Date Revision / Issue
DISCLAIMER
IOWA DEPARTMENT OF
ADMINISTRATIVE SERVICES
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #24006792.00
CONSTRUCTION MANAGER
MCGOUGH CONSTRUCTION
217 E 2ND ST SUITE 120
DES MOINES, IA 50309
1/4" = 1'-0"
/2
/2
:5 :4
A
M
9459.00 - HHS STS A.E.
SHEPERD AC
REPLACEMENT
3211 Edgington Ave Eldora, IA 50627
E201
FLOOR PLAN - ELECTRICAL
KRISPI
TONDEL
CHRMAR
24006792.00
01/17/2025
BID DOCUMENTS
.0
N O R
HT
1/4" = 1'-0"1
FIRST FLOOR PLAN - ELECTRICAL
KEYNOTES:
1. EXTEND #12 THWN CONDUCTORS IN 3/4'
CONDUIT TO NEAREST 120V CIRCUIT.
120/208V,3Ø4W
600A MCB
SCCR 42 kA
MDP
120/208V,3Ø4W
200A MLO
C
120/208V,3Ø4W
200A MLO
A
120/208V,3Ø4W
100A MLO
PANEL B
E
CU-EDS-CU-E
120/208V,3Ø4W
600A MCB
SCCR 42 kA
MDP
120/208V,3Ø4W
200A MLO
C
120/208V,3Ø4W
200A MLO
A
120/208V,3Ø4W
100A MLO
PANEL B
DS-CU-1
E
CU-1
ISC 0.00 kA
13.83 kVA
DS-CU-1
E
CU-1
ISC 0.00 kA
13.83 kVA
3#6 & 1#10 EGC IN 3/4" C.
FROM 50A/3P
3#6 & 1#10 EGC IN 3/4" C.
FROM 50A/3P
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908
The FUTURE. Built Smarter www.imegcorp.com
AGENCY APPROVAL
REVISIONS
No. Date Revision / Issue
DISCLAIMER
IOWA DEPARTMENT OF
ADMINISTRATIVE SERVICES
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #24006792.00
CONSTRUCTION MANAGER
MCGOUGH CONSTRUCTION
217 E 2ND ST SUITE 120
DES MOINES, IA 50309
12" = 1'-0"
/2
/2
:5 :4
A
M
9459.00 - HHS STS A.E.
SHEPERD AC
REPLACEMENT
3211 Edgington Ave Eldora, IA 50627
E400
ELECTRICAL DETAILS
KRISPI
TONDEL
CHRMAR
24006792.00
01/17/2025
BID DOCUMENTS
.0
NO SCALE1
RISER DIAGRAM - DEMO
NO SCALE2
RISER DIAGRAM - NEW
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
2882 106TH STREET
DES MOINES, IA 50322
P: 515.334.9906 F: 515.334.9908
The FUTURE. Built Smarter www.imegcorp.com
AGENCY APPROVAL
REVISIONS
No. Date Revision / Issue
DISCLAIMER
IOWA DEPARTMENT OF
ADMINISTRATIVE SERVICES
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #24006792.00
CONSTRUCTION MANAGER
MCGOUGH CONSTRUCTION
217 E 2ND ST SUITE 120
DES MOINES, IA 50309
/2
/2
:5 :4
A
M
9459.00 - HHS STS A.E.
SHEPERD AC
REPLACEMENT
3211 Edgington Ave Eldora, IA 50627
E600
ELECTRICAL SCHEDULES
KRISPI
TONDEL
CHRMAR
24006792.00
01/17/2025
BID DOCUMENTS
.0
CIRCUIT KEY NOTES:
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 2.8
TOTAL CONNECTED AMPS: 2.78 A
TOTAL ESTIMATED DEMAND LOAD: 1 kVA
TOTAL CONNECTED LOAD: 1.00 kVA
Power 1 kVA 100.00% 1 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
LOAD SUMMARY
Total Amps: 4.81 4.81 0.00
Total Load: 0.50 kVA 0.50 kVA 0.00 kVA
-- 41 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 42 --
39 0 0.5 1.27 12 12 12 1 15 CONTROL BOX 40 *NB
RECEPT. 50 2 -- -- --
0 0.5 1.25 12 12 12 1 15 CONTROL BOX 38 *NB
-- 35 POPCORN POPPER 50 1 -- -- -- 0 0 -- -- -- 1 20 NORTH BLACK OUT SCREEN 36 --
-- 33 RECEPT. 20 1 -- -- -- 0 0 -- -- -- 1 20 WINDOW LAMP 34 --
-- 31 EMS CABINET 20 1 -- -- -- 0 0 -- -- -- 1 20 PROJECTOR 32 --
-- 29 RECEPT. 20 1 -- -- -- 0 0 -- -- -- 1 20 VIDIO SCREEN 30 --
-- 27 RECEPT. 20 1 -- -- -- 0 0 28
-- 25 RECEPT. 20 1 -- -- -- 0 0 26
23 0 0
-- -- -- 3 45 AHU-2(E)
21 0 0 -- -- -- 1 15 SPARE 22 ----
HCCP-2 20 3 -- -- --
0 0 -- -- -- 1 15 FRONT SPEAKERS 20 --
-- 17 RECEPT. 20 1 -- -- -- 0 0 -- -- -- 1 15 TIME CLOCK 18 --
-- 15 RECEPT. 20 1 -- -- -- 0 0 -- -- -- 1 20 RECEPT. 16 --
-- 13 RECEPT. 20 1 -- -- -- 0 0 -- -- -- 1 20 RECEPT. 14 --
-- 11 RECEPT. 20 1 -- -- -- 0 0 -- -- -- 1 20 RECEPT. 12 --
-- 9 RECEPT. 20 1 -- -- -- 0 0 -- -- -- 1 20 RECEPT. 10 --
-- 7 LIGHTS 20 1 -- -- -- 0 0 -- -- -- 1 20 RECEPT. 8 --
-- 5 LIGHTS 20 1 -- -- -- 0 0 -- -- -- 1 20 LIGHTS 6 --
-- 3 LIGHTS 20 1 -- -- -- 0 0 -- -- -- 1 20 LIGHTS 4 --
-- 1 LIGHTS 20 1 -- -- -- 0 0 -- -- -- 1 20 LIGHTS 2 --
K E Y
CKT
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
VD
A B C VD
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CKT
NO.
K E Y
NOTES:
SCCR: 10 kA
LOCATION: WIRE: 4
FED FROM: 200/3P @ MDP GROUND BUS PHASE: 3
ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: SURFACE SINGLE TUB MAIN: 200 MLO
EXISTING PANEL A
AMS-ASSEMBLED MOTOR STARTER
FS - FUSED SWITCH
MX - MANUAL SWITCH
MS - MANUAL STARTER
SS - SOLID STATE
RV - REDUCED VOLTAGE AUTOXFMR
SW - 2 SPEED, 1 WINDING
TW - 2 SPEED, 2 WINDING
RE - REVERSING HL - HANDLE PADLOCK HASP
YD - WYE - DELTA S/N - INSULATED NEUTRAL ASSEMBLY SS - START-STOP PUSHBUTTON IN DOOR
FV - FULL VOLTAGE *TA - TWO CONVERTIBLE AUXILIARY CONTACTS EI - ELECTRICAL INTERLOCK (2)-N.O. & (2)-N.C.
STARTER TYPE: *RP - RED (RUN) PILOT LIGHT IN DOOR FA - 4-CONVERTIBLE AUXILIARY CONTACTS
*HA - HAND-OFF-AUTO IN DOOR GP - GREEN (OFF) PILOT LIGHT IN DOOR
CB - CIRCUIT BREAKER *EO - ELECTRONIC OVERLOAD (3 PHASE MOTORS) TS - 2 SPEED SELECTOR SWITCH IN DOOR
NF - NON-FUSED *CT - CONTROL TRANSFORMER, FUSED 120V TO - MELTING THERMAL OVERLOADS (1 PHASE)
FU - FUSED SA - STANDARD ACCESSORIES (INCLUDES * ITEMS) PF - PHASE LOSS PROTECTION (5 HP OR GREATER, 3 PHASE MOTOR)
DISCONNECT TYPE: ACCESSORIES & OPTIONS
NOTE: ALL DISCONNECTS (EXCEPT MANUAL STARTERS) SHALL BE HEAVY DUTY TYPE.
DISCONNECT AND STARTER SCHEDULE
ITEM
DISCONNECT TYPE &
RATING
VOLTAGE POLES ENCLOSURE
REQUIRED
ACCESSORIES &
OPTIONS COMMENTSTYPE RATING
TRIP
RATING
DS-CU-1 NF 60 208 3 NEMA 3R
DS-CU-1 NF 60 208 3 NEMA 3R
CIRCUIT KEY NOTES:
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 79.6
TOTAL CONNECTED AMPS: 79.58 A
TOTAL ESTIMATED DEMAND LOAD: 28.668 kVA
TOTAL CONNECTED LOAD: 28.67 kVA
Power 28.668 kVA 100.00% 28.668 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
LOAD SUMMARY (INCLUDES ALL TUBS IN THIS PANEL)
16 SPACE -- 1 -- -- -- -- -- --
15 SPACE -- 1 -- -- -- -- -- --
14 SPACE -- 1 -- -- -- -- -- --
13 SPACE -- 1 -- -- -- -- -- --
12 SPACE -- 1 -- -- -- -- -- --
11 SPACE -- 1 -- -- -- -- -- --
10 SPACE -- 1 -- -- -- -- -- --
9 SPACE -- 1 -- -- -- -- -- --
8 SPACE -- 1 -- -- -- -- -- --
7 SPACE -- 1 -- -- -- -- -- --
6 CU-1, CIRCUIT 2 13.83 kVA 3 150 50 3#6 & 1#10 EGC IN 3/4" C. *NB
5 CU-1 CIRCUIT 1 13.83 kVA 3 150 50 3#6 & 1#10 EGC IN 3/4" C. *NB
4 ACCU-2 0 kVA 1 250 250 -- -- -- --
3 EXISTING PANEL C 0 kVA 3 250 200 4#3/0 & 1#6 EGC IN 2" C. *EB
2 EXISTING PANEL B 0 kVA 3 150 100 4#2 & 1#6 EGC IN 1 1/4" C. *EB
1 EXISTING PANEL A 1 kVA 3 250 200 4#3/0 & 1#6 EGC IN 2" C. *EB
CKT LOAD DESCRIPTION Load POLES FRAME TRIP TYPE ACC. WIRE AND RACEWAY
CIRCUIT
KEY
NOTES: SEE ELECTRICAL DISTRIBUTION AND PANEL SCHEDULE NOTES FOR PANEL KEY.
SCCR: 42 kA
LOCATION: WIRE: 4
FED FROM: 0/0P @ GROUND BUS PHASE: 3
ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MAIN: 600 MCB
EXISTING MDP
ELECTRICAL DISTRIBUTION AND PANEL
SCHEDULE NOTES:
1. BRANCH PANEL KEY:
a. *A = ARC FAULT CIRCUIT INTERRUPT
b. *G = GROUND FAULT CIRCUIT INTERRUPT
c. *I = ISOLATED GROUND
d. *P = PADLOCK HASP
e. *R = RED HANDLE
f. *S = SHUNT TRIP
g. *NB = NEW BREAKER (NEW BREAKER TO MATCH EXISTING PANEL
CHARACTERISTICS)
h. *RB = REPLACE EXISTING BREAKER WITH NEW BREAKER
i. *EB = EXISTING BREAKER
| Sheets |
| E000 - ELECTRICAL COVERSHEET |
| E101 - DEMOLITION FLOOR PLAN - ELECTRICAL |
| E201 - FLOOR PLAN - ELECTRICAL |
| E400 - ELECTRICAL DETAILS |
| E600 - ELECTRICAL SCHEDULES |
| G000 - PROJECT COVERSHEET |
| M000 - HVAC COVERSHEET |
| M100 - FIRST FLOOR DEMOLITION PLAN - MECHANICAL |
| M201 - FLOOR PLAN - MECHANICAL |
| M400 - MECHANICAL DETAILS AND SCHEDULES |
| M500 - MECHANICAL DIAGRAMS |
File details come from the government source that posted it. Updated .