RFB945900-01 - HHS STS A.E. Sheperd AC Replacement - Drawings.pdf

PDF 2 MB Posted

Attached to
HHS STS A. E. Sheperd AC Replacement
Solicitation number
RFB945900-01
Issued by
Linn County, Iowa

About this file

This is a set of mechanical and electrical design drawings from IMEG Corp. for the Iowa Department of Administrative Services project to replace the air conditioning system at A.E. Sheperd Hall of the State Training School in Eldora, Iowa. The scope includes removing and replacing the existing cooling coil, condensing unit and associated refrigerant piping connected to AHU-2(E) serving the auditorium space. The project is managed by McGough Construction as Construction Manager and includes mechanical work (HVAC modifications) and electrical work to support the new equipment. The drawings are dated January 17, 2025 and labeled as "Bid Documents."

The drawings detail the installation of a new Daikin 288 MBH nominal cooling capacity VRF system with associated electrical power connections from Panel A. The design includes a new cooling coil (CC-1) rated for 6000 CFM airflow and new twinned condensing units (CU-1) with R-410A refrigerant. Electrical modifications include new 50A/3P circuit breakers and associated power wiring. The drawings contain detailed mechanical and electrical plans, diagrams, schedules and sequences of operation for the new equipment installation. All work must comply with applicable codes including IBC 2015, IMC 2021, and NEC 2020 editions.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BUILDING CODE: IBC 2015 EDITION

FIRE CODE: IFC 2015 EDITION

PLUMBING CODE: UPC 2021 EDITION

MECHANICAL CODE: IMC 2021 EDITION

ELECTRICAL CODE: NFPA 70 (NEC) 2020 EDITION

ENERGY CONSERVATION CODE: IECC 2012

APPLICABLE CODES

CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS

INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2024 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908

The FUTURE. Built Smarter www.imegcorp.com

PROJECT DIRECTORY

CLIENT:

SCOPE OF WORK

REMOVE AND REPLACE EXISTING COOLING COIL, CONDENSING UNIT AND

ASSOCIATED REFRIGERANT PIPING CONNECTED TO AHU-2(E) SERVING THE

AUDITORIUM SPACE OF SHEPERD HALL OF THE STATE TRAINING SCHOOL

IN ELDORA, IOWA.

MECHANICAL

ENGINEER:

APPLICABLE CODES DRAWING INDEX

IMEG CORP.

2882 106TH STREET

DES MOINES, IA 50322

PHONE: (515) 334-4303

CONTACT: NATE JACQUES

ELECTRICAL

ENGINEER:

IMEG CORP.

2882 106TH STREET

DES MOINES, IA 50322

PHONE: (515) 639-3041

CONTACT: KRISTEN SPINA

VICINITY MAP

AGENCY APPROVAL

REVISIONS

No. Date Revision / Issue

DISCLAIMER

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #24006792.00

IOWA DEPARTMENT OF

ADMINISTRATIVE SERVICES

CONSTRUCTION MANAGER

MCGOUGH CONSTRUCTION

217 E 2ND ST SUITE 120

DES MOINES, IA 50309

/2

/2

:5 :3

A

M

12" = 1'-0"

.0

3211 Edgington Ave Eldora, IA 50627

9459.00 - HHS STS A.E. SHEPERD AC

REPLACEMENT

9459.00 - HHS STS A.E. SHEPERD AC

REPLACEMENT

3211 Edgington Ave Eldora, IA 50627

G000

PROJECT COVERSHEET

NATJAC

PETERN

EVAHAM

24006792.00

01/17/2025

BID DOCUMENTS

9459.00 - HHS STS A.E.

SHEPERD AC

REPLACEMENT

Sheet List Number Name

PROJECT COVERSHEET

G000 PROJECT COVERSHEET

HVAC

M000 HVAC COVERSHEET

M100 FIRST FLOOR DEMOLITION PLAN - MECHANICAL

M201 FLOOR PLAN - MECHANICAL

M500 MECHANICAL DIAGRAMS

M400 MECHANICAL DETAILS AND SCHEDULES

ELECTRICAL

E000 ELECTRICAL COVERSHEET

E101 DEMOLITION FLOOR PLAN - ELECTRICAL

E201 FLOOR PLAN - ELECTRICAL

E400 ELECTRICAL DETAILS

E600 ELECTRICAL SCHEDULES

PROJECT VICINITY

PROJECT LOCATION

CONSTRUCTION MANAGER

MCGOUGH CONSTRUCTION

217 E 2ND ST SUITE 120

DES MOINES, IA 50309

I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT

WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL

SUPERVISION AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE

OF IOWA.

DATE

MY LICENSE EXPIRATION DATE IS: 12/31/2026

PAGES OR SHEETS COVERED BY THIS SEAL:

I O W A

S E

D

PROFESS IONA

P21686

L

IC

E N

L E

N G

I N E

E R

NATHANIEL K.

JACQUES

NATHANIEL K. JACQUES

I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT

WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL

SUPERVISION AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE

OF IOWA.

DATE

MY LICENSE EXPIRATION DATE IS: 12/31/2025

PAGES OR SHEETS COVERED BY THIS SEAL:

I O W A

S E

D

PROFESS IONA

P21081

L

IC

E N

L E

N G

I N E

E R

KRISTEN L.

SPINA KRISTEN L. SPINA

I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT

WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL

SUPERVISION AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE

OF IOWA.

DATE

MY LICENSE EXPIRATION DATE IS: 12/31/2026

PAGES OR SHEETS COVERED BY THIS SEAL:

I O W A

S E

D

PROFESS IONA

P21686

L

IC

E N

L E

N G

I N E

E R

NATHANIEL K.

JACQUES

NATHANIEL K. JACQUES

I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT

WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL

SUPERVISION AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE

OF IOWA.

DATE

MY LICENSE EXPIRATION DATE IS: 12/31/2025

PAGES OR SHEETS COVERED BY THIS SEAL:

I O W A

S E

D

PROFESS IONA

P21081

L

IC

E N

L E

N G

I N E

E R

KRISTEN L.

SPINA KRISTEN L. SPINA

01/17/2025

01/17/2025

ALL E - SERIES DRAWINGS

ALL M - SERIES DRAWINGS

1. PIPE DRAIN LINES FROM EQUIPMENT TO NEAREST FLOOR DRAIN.

2. INSTALL ALL REFRIGERANT LIQUID AND SUCTION PIPING SIZED PER EQUIPMENT

MANUFACTURER RECOMMENDATIONS.

PIPING GENERAL NOTES:

1. BEFORE ANY DEMOLITION WORK IS BEGUN A COMPLETE AIR BALANCE TEST SHALL BE

PERFORMED BY THE TESTING, ADJUSTING AND BALANCING (TAB) CONTRACTOR ON

EXISTING AHU-2(E) AND AIR OUTLETS SERVING THE AREAS AFFECTED BY CONSTRUCTION.

EQUIPMENT TO BE DEMOLISHED DOES NOT REQUIRE TESTING. PROVIDE AIR BALANCE

TESTING ONLY ON EQUIPMENT THAT WILL CONTINUE TO BE USED TO SERVE RENOVATED

AREAS AFTER THE CONSTRUCTION PHASE IS COMPLETED.

2. TAB CONTRACTOR SHALL COMPILE AND SUBMIT ONE COPY OF THE FINAL PRE-DEMOLITION

REPORT WITHIN 10 WORKING DAYS AFTER THE FIELD MEASUREMENTS ARE COMPLETED.

FINAL TAB REPORT SHALL BE SUBMITTED FOR REVIEW TO THE ARCHITECT/ENGINEER.

TESTING SHALL INCLUDE ALL ITEMS REQUIRED IN THE SPECIFICATIONS.

TAB PRE-DEMOLITION NOTES:

1. AFTER CONSTRUCTION ACTIVITIES ARE COMPLETE, TESTING, ADJUSTING (TAB) AND

BALANCING CONTRACTOR SHALL REBALANCE AIR HANDLING UNITS FANS AS REQUIRED TO

ACHIEVE THE NEW AIRFLOW VALUES SHOWN ON THE CONSTRUCTION DRAWINGS.

2. TAB CONTRACTOR SHALL COMPILE AND SUBMIT ONE COPY OF THE FINAL POST-

CONSTRUCTION TAB REPORT AS REQUIRED BY SECTION 23 05 93.

3. THE FINAL POST CONSTRUCTION REPORT SHALL INCLUDE ALL ITEMS REQUIRED IN THE

SPECIFICATIONS.

TAB POST-CONSTRUCTION NOTES:

MECHANICAL GENERAL NOTES:

THESE NOTES APPLY TO ALL MECHANICAL SHEETS.

1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE

DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.

DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,

AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE

INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING

CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.

2. CATALOG AND MODEL NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN

AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR

IS RESPONSIBLE FOR THE COMPLETE DESCRIPTION OF MATERIAL SCHEDULED ON THESE

DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE

MATERIAL AND SCHEDULED PERFORMANCE TAKES PRECEDENCE OVER THE MODEL

NUMBER. THE FIRST MANUFACTURER SCHEDULED IS THE BASIS OF DESIGN.

3. DETERMINATION OF QUANTITIES OF MATERIAL AND EQUIPMENT REQUIRED SHALL BE MADE

BY THE CONTRACTOR FROM THE DOCUMENTS. WHERE MATERIAL AND/OR QUANTITY

DISCREPANCIES ARISE BETWEEN DRAWINGS, SCHEDULES AND/OR SPECIFICATIONS, THE

HIGHER QUALITY/ GREATER NUMBER SHALL GOVERN.

4. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM

APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING

THOSE OF OTHER TRADES.

5. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE

CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO

VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO

VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES

OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING

WITH FABRICATION OR EQUIPMENT ORDERS.

6. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE

REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER

ACCESS.

7. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO

COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR

EXPENSE TO OTHERS.

8. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL

CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF

DESIGN.

9. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,

FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS

RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND

FINISH.

10. SEAL ALL WALL PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS

PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS SHALL BE SEALED AIRTIGHT

WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR

USE.

11. CAULK ALL PIPE PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL & PARTITION

ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO

ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.

12. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT

MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND

REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF PIPING, DUCTWORK,

ETC.

13. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES.

14. MAINTAIN A MINIMUM WORKING CLEARANCE OF 3’-6” IN FRONT OF ALL ELECTRICAL

EQUIPMENT REQUIRING MAINTENANCE, INSPECTION, AND TESTING INCLUDING BUT NOT

LIMITED TO PANELS, DISTRIBUTION PANELS, SWITCHBOARDS, MOTOR CONTROL CENTERS,

TRANSFORMERS, EQUIPMENT DISCONNECTS AND STARTERS.

15. MAINTAIN THE DEDICATED ELECTRICAL EQUIPMENT SPACE DEFINED BY THE WIDTH / DEPTH

OF ELECTRICAL EQUIPMENT MEASURED FROM THE FLOOR TO A HEIGHT 6’-0” ABOVE THE

EQUIPMENT OR THE STRUCTURAL CEILING, WHICHEVER IS LOWER. SYSTEMS FOREIGN TO

THE ELECTRICAL DISTRIBUTION SYSTEM ARE NOT ALLOWED IN THE DEDICATED

ELECTRICAL SPACE INCLUDING: DUCTWORK, PIPING, ETC.

MECHANICAL RENOVATION NOTES:

THESE NOTES APPLY TO ALL MECHANICAL SHEETS.

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD

SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND

REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS

BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR PIPING BEFORE FABRICATION. RISES AND

DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.

4. EACH CONTRACTOR SHALL CUT AND PATCH WALLS ASSOCIATED WITH THEIR WORK.

5. THIS CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS,

CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL

CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO

BIDDING.

6. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH

NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL

EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT

DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL

SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

7. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY

REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW

SYSTEMS ARE INSTALLED.

8. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR

TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND

CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY

DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.

9. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT

THAT HAS BEEN REMOVED.

10. PROPERLY RECLAIM AND DISPOSE OF ALL REFRIGERANT IN REMOVED EQUIPMENT/

REFRIGERANT PIPING. RECLAIMED REFRIGERANT SHALL HAVE DOCUMENTATION AS

REQUIRED BY THE AUTHORITY HAVING JURISDICTION (AHJ).

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

DETAIL REFERRED TO BY SECTION CUT

SHEET DETAIL IS LOCATED ON

NAME

VIEW NAME

1/8" = 1'-0"

M101

SIMSIM

INDICATES SIMILAR DETAIL REFERENCED

IN MULTIPLE LOCATIONS

LEVEL NAME

10'-0" HEIGHT ABOVE

PROJECT 0'-0"

1 KEYNOTE: INDICATES NOTE USED TO

DESCRIBE ADDITIONAL INFORMATION

ABOUT WORK REQUIRED, SPECIFIC

TO THE SHEET AND/OR DETAIL

N O R

HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

LINE TYPE AND TAG KEY:

NEW WORK BY THIS CONTRACTOR (WIDE LINE)

EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)

HALFTONING DOES NOT MODIFY SCOPE.

'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING

TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL

INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST

INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL

T101

NEW

EXISTING TO BE REMOVED (SHORT DASHED PATTERN)

NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

EXISTING

EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)

EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

BUILDING CODE: IBC 2015 EDITION

FIRE CODE: IFC 2015 EDITION

PLUMBING CODE: UPC 2021 EDITION

MECHANICAL CODE: IMC 2021 EDITION

ELECTRICAL CODE: NFPA 70 (NEC) 2020 EDITION

ENERGY CONSERVATION CODE: IECC 2012

APPLICABLE CODES

CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS

INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:

TEMPERATURE CONTROLS CONTRACTORT.C.C.

GENERAL CONTRACTORG.C.

MECHANICAL CONTRACTORM.C.

ELECTRICAL CONTRACTORE.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

CONSTRUCTION MANAGERC.M.

CONTACT PERSONS:

PROJECT MANAGER

MECHANICAL

ELECTRICAL

NATE JACQUES

EVAN HAMMER

KRISTIN SPINA

DESCRIPTION: PERSON:

HVAC ABBREVIATION KEY

ABBR: DESCRIPTION:

NOT IN CONTRACTNIC

TYPICALTYP

UON UNLESS OTHERWISE NOTED

SCCR SHORT CIRCUIT CURRENT RATING

DN DOWN

MANUAL VOLUME DAMPER

DUCT CAP

DUCT DOWN

DUCT UP

SUPPLY/OUTSIDE AIR DUCT SECTION

RETURN AIR DUCT SECTION

SD-# AIR TERMINAL NAME

HVAC SYMBOL LIST

SYMBOL: DESCRIPTION:

NOT ALL SYMBOLS MAY APPLY.

PITCH PIPE IN DIRECTION

PIPE CAP

PIPE DOWN

PIPE UP OR UP/DOWN

DIRECTION OF FLOW IN PIPE

SHUTOFF VALVE NORMALLY OPEN

SHUTOFF VALVE NORMALLY CLOSED

HEATING WATER RETURNHWR

HEATING WATER SUPPLYHWS

REFRIGERANT LIQUIDLIQ

REFRIGERANT SUCTIONSUC

HVAC SYMBOL LIST

SYMBOL: DESCRIPTION:

NOT ALL SYMBOLS MAY APPLY.

REFRIGERANTREF

TEMPERATURE CONTROLS ABBREVIATION KEY

ABBR: DESCRIPTION:

NO NORMALLY OPEN

HWR HEATING WATER RETURN

HWS HEATING WATER SUPPLY

REF REFRIGERANT

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2024 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908

The FUTURE. Built Smarter www.imegcorp.com

AGENCY APPROVAL

REVISIONS

No. Date Revision / Issue

DISCLAIMER

IOWA DEPARTMENT OF

ADMINISTRATIVE SERVICES

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #24006792.00

CONSTRUCTION MANAGER

MCGOUGH CONSTRUCTION

217 E 2ND ST SUITE 120

DES MOINES, IA 50309

As indicated

/2

/2

:5 :3

A

M

9459.00 - HHS STS A.E.

SHEPERD AC

REPLACEMENT

3211 Edgington Ave Eldora, IA 50627

M000

HVAC COVERSHEET

NATJAC

PETERN

EVAHAM

24006792.00

01/17/2025

BID DOCUMENTS

.0

HVAC SHEET INDEX

M000 HVAC COVERSHEET

M100 FIRST FLOOR DEMOLITION PLAN - MECHANICAL

M201 FLOOR PLAN - MECHANICAL

M500 MECHANICAL DIAGRAMS

M400 MECHANICAL DETAILS AND SCHEDULES

GRAND TOTAL: 5

DUCT ABBREVIATION KEY

ABBR. DESCRIPTION

OA OUTSIDE AIR

RA RETURN/RELIEF AIR

SA SUPPLY AIR

ENTRY VESTIBULE

STAIR

VEST #1

LOBBY

DN

ø

S A ø

S A ø

S A ø

S A ø

S A ø

S A ø

S A ø

S A ø

S A ø

S A ø

S A ø

S A

SD-E

SD-E

SD-E SD-E

SD-E

SD-E

SD-E

SD-E

SD-E

SD-E

SD-E

SD-E

26ø SA30ø SA 22ø SA

AHU-2(E)

36ø SA24ø SA

LV-E

48x20 RA

66x18 RA

8x66 OA

30x30 OA

42x42 OA

2"V

2"V UP TO VTR

3"HWS

3"HWR

1/2"CWS

1"V

2"CWR

CU-E

CAP REFRIGERANT

PIPING AT WALL.

ABANDON

REMAINING PIPING

IN PLACE.

CAP REFRIGERANT

PIPING AT WALL.

ABANDON REMAINING

PIPING IN PLACE.

CAP REFRIGERANT

PIPING AT WALL.

ABANDON REMAINING

PIPING IN WALL IN

PLACE.

CAP REFRIGERANT

PIPING AT WALL.

ABANDON REMAINING

PIPING WITHIN WALL IN

PLACE.

REMOVE EXISTING

REFRIGERANT PIPING

REMOVE EXISTING

REFRIGERANT PIPING

REMOVE THE EXISTING R-22 REFRIGERANT

COOLING COIL AND ASSOCIATED PIPING,

VALVES, SPECIALTIES, AND CONTROLS

FROM THE EXISTING TO REMAIN AHU-2(E).

TAKE CARE IN THE REMOVAL OF THE COIL,

FOR INSTALLATION OF NEW COOLING COIL.

REMOVE EXISTING

CONDENSATE TRAP

EXISTING PAD

UNDER CU-E TO

BE REUSED FOR

NEW CU.

BEFORE ANY DEMOLITION WORK IS BEGUN,

A COMPLETE AIR BALANCE TEST SHALL BE

PERFORMED BY THE TESTING, ADJUSTING

AND BALANCING (TAB) CONTRACTOR ON

EXISTING AHU-2(E) AND AIR OUTLETS

SERVING THE AREAS AFFECTED BY

CONSTRUCTION. EQUIPMENT TO BE

DEMOLISHED DOES NOT REQUIRE TESTING.

CU-E

CU-E

EXISTING CONDENSING

UNITS TO REMAIN

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2024 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908

The FUTURE. Built Smarter www.imegcorp.com

AGENCY APPROVAL

REVISIONS

No. Date Revision / Issue

DISCLAIMER

IOWA DEPARTMENT OF

ADMINISTRATIVE SERVICES

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #24006792.00

CONSTRUCTION MANAGER

MCGOUGH CONSTRUCTION

217 E 2ND ST SUITE 120

DES MOINES, IA 50309

1/4" = 1'-0"

/2

/2

:5 :4

A

M

9459.00 - HHS STS A.E.

SHEPERD AC

REPLACEMENT

3211 Edgington Ave Eldora, IA 50627

M100

FIRST FLOOR DEMOLITION PLAN -

MECHANICAL

NATJAC

PETERN

EVAHAM

24006792.00

01/17/2025

BID DOCUMENTS

.0

N O R

HT

1/4" = 1'-0"1

FIRST FLOOR DEMOLITION PLAN - MECHANICAL

STAIR

VEST #1

LOBBY

WOMEN'S RESTROOM

DN

ø

S A ø

S A ø

S A ø

S A ø

S A ø

S A ø

S A ø

S A ø

S A ø

S A ø

S A ø

S A

SD-E

SD-E

SD-E SD-E

SD-E

SD-E

SD-E

SD-E

SD-E

SD-E

SD-E

SD-E

26ø SA30ø SA 22ø SA

AHU-2(E)

36ø SA 24ø SA

LV-E

48x20 RA

66x18 RA

8x66 OA

30x30 OA

42x42 OA

CONTRACTOR TO INSTALL

MANUAL BALANCING

DAMPER IN EXISITNG SA

DUCT. BALANCE TO 1500

CFM IN DUCT BRANCH.

EXISTING DUCT IS

INTERNALLY LINED FOR

INSULATION.

SIZE & INSTALL REFRIGERANT

PIPING AS PER

MANUFACTURER'S

REQUIREMENTS.

EXISTING REFRIGERANT PIPING

ABANDONED IN PLACE.

EXISTING REFRIGERANT PIPING

ABANDONED IN PLACE.

CONTRACTOR TO INSTALL

MANUAL BALANCING

DAMPER IN EXISITNG SA

DUCT. BALANCE TO 1500

CFM EACH DUCT BRANCH.

EXISTING DUCT IS

INTERNALLY LINED FOR

INSULATION.

MOUNT CONTROL BOX AS

HIGH AS POSSIBLE. INSTALL

PLYWOOD BACKING OVER

EXISTING TRANSFER GRILLE

FOR CONTROL BOX

MOUNTING. PLYWOOD

BACKING SHALL ONLY BE

LARGE ENOUGH TO MOUNT

CONTROL BOXES, AND SHALL

NOT COVER ENTIRE

TRANSFER GRILLE (TYP. 2).

ROUTE REFRIGERANT PIPING UNDER

LIGHTS. WHITE PVC JACKET

REQUIRED ON REFRIGERANT PIPING.

PAINT TO MATCH AUDITORIUM

WALLS.

WHITE PVC JACKET

REQUIRED ON

REFRIGERANT PIPING.

NEW CONDENSING

UNIT ON EXISTING PAD.

CC-1

INSTALL NEW CC-1 IN EXISTING AIR HANDLER

AHU-2(E). BLANK-OFF ANY UN-USED AIR

TUNNEL WITH DOUBLE-WALLED PANELS TO

MATCH EXISTING AHU-2(E) CONSTRUCTION.

CONNECT TWO CIRCUITS OF

REFRIGERANT PIPING TO CC-1 PER

MANUFACTURER'S

RECOMMENDATIONS. NOT ALL

LINES SHOWN CONNECTED TO CC-1

IN PLAN FOR CLARITY.

PROVIDE NEW

P-TRAP PER

DETAIL 2/M400.

2"V UP TO

4" VTR

CU-E

CU-E

PROTECT EXISTING

CONDENSING UNITS

FROM DAMAGE

CORE THROUGH

EXISTING WALL TIGHT

TO UNDERSIDE OF BEAM

CU-1

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2024 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908

The FUTURE. Built Smarter www.imegcorp.com

AGENCY APPROVAL

REVISIONS

No. Date Revision / Issue

DISCLAIMER

IOWA DEPARTMENT OF

ADMINISTRATIVE SERVICES

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #24006792.00

CONSTRUCTION MANAGER

MCGOUGH CONSTRUCTION

217 E 2ND ST SUITE 120

DES MOINES, IA 50309

1/4" = 1'-0"

/2

/2

:5 :4

A

M

9459.00 - HHS STS A.E.

SHEPERD AC

REPLACEMENT

3211 Edgington Ave Eldora, IA 50627

M201

FLOOR PLAN - MECHANICAL

NATJAC

PETERN

EVAHAM

24006792.00

01/17/2025

BID DOCUMENTS

.0

N O R

HT

1/4" = 1'-0"1

FIRST FLOOR PLAN - MECHANICAL

.5

CLEANOUT PLUG (TYP.)

ROUTE TO FLOOR DRAIN.

FULL SIZE CONDENSATE

DRAIN, CONNECT TO DRAIN

PAN AS RECOMMENDED BY

MANUFACTURER.

.5

INSTALL AN ESCUTCHEON AROUND PIPES

EXPOSED IN FINISHED ROOMS. IN SUCH

INSTANCES WHERE AN ESCUTCHEON IS

REQUIRED AND THE PIPING IS INSULATED,

INSTALL A PLASTIC JACKET EXTENDING 6"

BEYOND THE WALL TO PROTECT INSULATION

FROM DAMAGE FROM THE ESCUTCHEON.

MAKE A SMOOTH ROUND OPENING IN

WALL SLIGHTLY LARGER THAN OUTSIDE

DIAMETER OF THE PIPE AND INSULATION.

ADD A BEAD OF NON-HARDENING

CAULK IN THE ANNULAR SPACE.

NOTES:

1. THIS DETAIL APPLIES TO ALL PIPES. THE INTENTION IS TO

CONTINUE THE INSULATION AND VAPOR BARRIER THROUGH

ALL PENETRATIONS. PERMIT THERMAL EXPANSION WITHOUT

DAMAGING INSULATION, AND TO SEAL AIRTIGHT AROUND

INSULATED AND UNINSULATED PIPES FOR NOISE

TRANSMISSION CONTROL.

2. SEE SPECIFICATION SECTION 23 05 29 FOR ADDITIONAL

INFORMATION.

NOTES:

1. THIS DIAGRAM IS SCHEMATIC IN NATURE. UNIT MANUFACTURER SHALL SUBMIT DETAILED PIPING DIAGRAM SHOWING

RECOMMENDED PIPING ARRANGEMENT IF DIFFERENT FROM ABOVE.

2. ANY ACCESSORIES SUCH AS ACCUMULATORS, RECEIVERS, SEPARATORS AND HEAT TRACING SHALL BE DETERMINED BY

THE COIL SUPPLIER AND SUBMITTED AS SHOP DRAWINGS. NO COMPENSATION WILL BE MADE IF ACTUAL NUMBER OF

PIPES EXCEED WHAT IS SHOWN.

CONDENSING UNIT

CONDENSING UNIT

CONTROL BOX

CONTROL BOX

AIR FLOW

COOLING COIL

CORE THROUGH EXISTING WALL

TIGHT TO UNDERSIDE OF BEAM

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2024 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908

The FUTURE. Built Smarter www.imegcorp.com

AGENCY APPROVAL

REVISIONS

No. Date Revision / Issue

DISCLAIMER

IOWA DEPARTMENT OF

ADMINISTRATIVE SERVICES

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #24006792.00

CONSTRUCTION MANAGER

MCGOUGH CONSTRUCTION

217 E 2ND ST SUITE 120

DES MOINES, IA 50309

12" = 1'-0"

/2

/2

:5 :4

A

M

9459.00 - HHS STS A.E.

SHEPERD AC

REPLACEMENT

3211 Edgington Ave Eldora, IA 50627

M400

MECHANICAL DETAILS AND

SCHEDULES

NATJAC

PETERN

EVAHAM

24006792.00

01/17/2025

BID DOCUMENTS

.0

NO SCALE2

CONDENSATE TRAP - DRAW THROUGH COIL

NOTES:

1.UNITS SHALL BE SELECTED FOR DESIGN COOLING LOAD.

2.COORDINATE ELECTRICAL CONNECTIONS WITH MANUFACTURER UNIT IS SUPPLIED AS MULTIPLE MODULES. EACH MODULE REQUIRES A SEPARATE ELECTRICAL CONNECTION AND DISCONNECT.

3.NOMINAL COOLING CAPACITY RATED AT: INDOOR TEMP = 80°FDB/67°FWB, OUTDOOR TEMP = 95°FDB.

4.DESIGN COOLING CAPACITY SHALL BE RATED AT: INDOOR TEMP = 75°FDB/62.6°FWB, OUTDOOR TEMP = 95°FDB. EFFECTS OF ESTIMATED REFRIGERANT LINE LENGTH SHALL BE INCLUDED IN COMPUTING DESIGN CAPACITY.

5.REFER TO SPECIFICATION SECTION 23 81 45 FOR ADDITIONAL REQUIREMENTS.

6. PROVIDE WITH AN iTM TOUCHSCREEN WITH BACnet INTERFACE FOR INTEGRATION TO EXISTING BUILDING AUTOMATION SYSTEM.

VRF MODULAR OUTDOOR UNIT SCHEDULE

TAG NAME AREA SERVED R

E

F R

IG

E

R A

N T

M A

X R

E F

R

IG

E R

A N

T C

H A

R G

E

L B

S

COOLING

N U

M B

E R

O F

C O

N N

E C

T E

D C

O O

L

IN

G C

O

IL

C O

N N

E C

T

IO

N R

A T

IO

ELECTRICAL MAX. DIMENSIONS (IN.) WEIGHT (LBS)

MANUFACTURER MODEL NOTESN

O

M

IN

A L

M B

H

N O

T E

D E

S

IG

N M

B H

N

O T

E

O P

E R

A T

IN

G

R A

N G

E

F D

B

V O

L T

A G

E

P H

A S

E S

MODULE 1 MODULE 2 DISCONNECT CONTROLLER/STARTER

E M

E R

G E

N C

Y P

O W

E R

L E

N G

T H

W

ID

T H

H E

IG

H

T

D R

Y

O P

E R

A T

IN

G

M C

A

M O

C P

M C

A

M O

C P

B Y

N

O T

E A

T Y

P E

N

O T

E B

B Y

N

O T

E A

S C

C R

CU-1 AUDITORIUM R410A 51.6 288 276 95.0 1 96 208 3 48 50 47.8 50 EC NF MFR 42000 No 98 30 65 1418 1418 DAIKIN RXYQ NOTE 1, 2, 5, & 6

NOTES:

1.PRESSURE DROP BASED ON TOTALLY SATURATED COIL.

2.COIL AND CONDENSING UNIT SHALL BE BY SAME MANUFACTURER.

COIL SCHEDULE - REFRIGERANT

TAG

NAME

AREA

SERVED CFM

MAX. FPM

FACE

VELOCITY

EAT

LAT DB °F

TOTAL

MBH

NUMBER OF

CIRCUITS

A.P.D. IN.

W.C. (NOTE 1)

SUCT.

TEMP °F

LIQ.

TEMP °F REFRIGERANT

MAX. DIMENSIONS WEIGHT

MANUFACTURER

(NOTE 2) MODEL NOTESDB °F WB °F LENGTH WIDTH HEIGHT DRY OPERATING

CC-1 AUDITORIUM 6000 400 82.5 68.9 55.5 288 2 0.47 42.0 110.0 R-410A 76" 8" 38" 247 295 DAIKIN 5EJ0706B NOTE 2

NO SCALE3

WALL PENETRATION - NON-FIRE RATED

B. DISCONNECT TYPE:

NF = NON-FUSED

A. DISCONNECT AND CONTROLLER STARTER FURNISHED AND

INSTALLED BY:

MFR = MANUFACTURER

SCHEDULE GENERAL NOTES:

NO SCALE1

REFRIGERANT - PIPING DIAGRAM W/SINGLE COIL

T

F M

T T

T

H

AO DI DI DI AODI DI DI

RETURN

AIR

ACT

O.A.

HEAT

COIL

HWR

N.O.

HWS

RETURN

AIR

DAMPER

OUTSIDE

AIR

DAMPER

PRE-

FILTER

REF

COOLING

COIL

CS

SEQUENCE OF OPERATION FOR AHU-2:

THE CONSTANT VOLUME AIR HANDLER UNIT CONSISTS OF A MIXED AIR SECTION WITH OUTDOOR AIR, EXHAUST AIR, RETURN AIR DAMPERS, PRE-FILTER, MODULATING DX COOLING COIL, HOT

WATER COIL AND PUMP, AND SUPPLY FAN.

AHU-2 OPERATES IN WARM-UP, COOL-DOWN, OCCUPIED, UNOCCUPIED, NIGHT HEATING, NIGHT COOLING, AND SAFETY MODES.

ECONOMIZER OPERATION:

THE ECONOMIZER MODE WILL BE ENABLED WHEN THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE ECONOMIZER SET POINT 60.0 DEG F (ADJUSTABLE).

HEATING/COOLING MODE:

IF THE ROOM TEMPERATURE IS LESS THAN THE ROOM TEMPERATURE SET POINT WITH A 5 DEG F (ADJ.) DEADBAND, THE HEATING MODE SHALL BE ENABLED.

IF THE ROOM TEMPERATURE IS GREATER THAN THE ROOM TEMPERATURE SET POINT WITH A 5 DEG F (ADJ) DEADBAND THE COOLING MODE SHALL BE ENABLED.

WARM UP MODE:

START THE SUPPLY FAN. MODULATE THE HEATING VALVE TO MAINTAIN THE SUPPLY AIR TEMPERATURE SET POINT 110.0 DEG F (ADJUSTABLE). CLOSE THE MIXING DAMPER TO OUTSIDE AIR.

DX TO REMAIN OFF. ENABLE HOT WATER PUMP WHEN SHEPARD BOILERS ARE ENABLED.

COOL DOWN MODE:

START THE SUPPLY FAN. COMMAND THE HEATING VALVE CLOSED, MODULATE THE MIXING DAMPERS, AND STAGE DX TO MAINTAIN THE SUPPLY TEMPERATURE SET POINT (55.0 DEG F

ADJUSTABLE). DISABLE HOT WATER PUMP.

OCCUPIED MODE:

HEATING MODE ENABLED:

START THE SUPPLY FAN. MODULATE THE HEATING VALVE TO MAINTAIN THE SUPPLY TEMPERATURE SET POINT 90.0 DEG F (ADJUSTABLE). MIXING DAMPERS WILL BE CLOSED TO MINIMUM POSITION (10% ADJUSTABLE). DX TO REMAIN OFF. ENABLE HOT WATER PUMP WHEN SHEPARD BOILERS ARE ENABLED. FMCS SHALL SEND A MODULATING SIGNAL TO THE HEATING WATER

CONTROL VALVE MODULATE THE VALVE AS NEEDED TO MAINTAIN THE SPACE TEMPERATURE SETPOINT OF 72.0 DEG F (ADJUSTABLE).

COOLING MODE ENABLED:

START THE SUPPLY FAN. MODULATE MIXING DAMPERS TO MAINTAIN THE MIXED AIR TEMPERATURE SET POINT 55.0 DEG F (ADJUSTABLE). DISABLE HOT WATER PUMP. FMCS SHALL SEND A

MODULATING SIGNAL TO THE CONDENSING UNIT CONTROLLER TO MODULATE THE COMPRESSORS AS NEEDED TO MAINTAIN THE SPACE TEMPERATURE SETPOINT OF 72.0 DEG F

(ADJUSTABLE).

UNOCCUPIED MODE:

STOP THE FAN. CLOSE THE HEATING VALVE. CLOSE THE MIXING DAMPERS TO OUTSIDE AIR. DX TO REMAIN OFF

NIGHT HEATING MODE:

START THE SUPPLY FAN. ENABLE HOT WATER PUMP WHEN SHEPARD BOILERS ARE ENABLED. SET THE HEATING VALVE TO 100% OPEN. CLOSE MIXING DAMPERS TO OUTSIDE AIR.FMCS SHALL

SEND A MODULATING SIGNAL TO THE HEATING WATER CONTROL VALVE MODULATE THE VALVE AS NEEDED TO MAINTAIN THE SPACE TEMPERATURE SETPOINT OF 72.0 DEG F (ADJUSTABLE).

NIGHT COOLING MODE:

START THE SUPPLY FAN. MODULATE MIXING DAMPERS TO MAINTAIN THE MIXED AIR TEMPERATURE SET POINT (55.0 DEG F ADJUSTABLE). DISABLE HOT WATER PUMP. MODULATE DX COOLING

COIL TO MAINTAIN ROOM TEMPERATURE SETPOINT (72.0 DEG F ADJUSTABLE).

SMOKE SAFETY MODE:

STOP THE SUPPLY FAN. STAGE OFF THE DX. CLOSE THE MIXING DAMPERS TO THE OUTSIDE AIR. MODULATE THE HEATING VALVE TO MAINTAIN A SUPPLY TEMPERATURE SET POINT OF (45.0

DEG F ADJUSTABLE).

NOTE:

WHEN AHU-2 IS OCCUPIED, AHU-1 MUST BE OCCUPIED AS WELL. CODE FOR AHU-2 SETS THE OCCUPIED MODE FOR AHU-1.

SUPPLY AIR

TEMP.

SUPPLY

AIR

REMOTE EXTERIOR

TWINNED 12-TON VRV

CONDENSING UNITS.

COMPRESSOR STATUS

FAN STATUS

SYSTEM ALARM

MODULATING

COMPRESSOR STATUS

FAN STATUS

SYSTEM ALARM

MODULATING

CONTROL DIAGRAM NOTE:

DDC CONTROL POINTS THAT ARE EXISTING ARE NOT

INDICATED HERE. DEVICES ARE SHOWN, CONTROL POINTS

FOR THOSE DEVICES ARE NOT. ALL EXISTING DEVICES

AND CONTROL POINTS ARE INTENDED TO REMAIN.

NOTE:

TEXT NOT BOLDED INDICATES EXISTING

SEQUENCE FOR AHU-2(E). BOLD TEXT INDICATES

NEW CONTROL SEQUENCE FOR AHU-2(E).

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2024 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908

The FUTURE. Built Smarter www.imegcorp.com

AGENCY APPROVAL

REVISIONS

No. Date Revision / Issue

DISCLAIMER

IOWA DEPARTMENT OF

ADMINISTRATIVE SERVICES

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #24006792.00

CONSTRUCTION MANAGER

MCGOUGH CONSTRUCTION

217 E 2ND ST SUITE 120

DES MOINES, IA 50309

12" = 1'-0"

/2

/2

:5 :4

A

M

9459.00 - HHS STS A.E.

SHEPERD AC

REPLACEMENT

3211 Edgington Ave Eldora, IA 50627

M500

MECHANICAL DIAGRAMS

NATJAC

PETERN

EVAHAM

24006792.00

01/17/2025

BID DOCUMENTS

.0

NO SCALE1

AIR HANDLING UNIT - AUDITORIUM AHU-2(E)

ELECTRICAL ABBREVIATION KEY

AFF ABOVE FINISHED FLOOR

C CONDUIT (BRANCH CIRCUIT OR FEEDER CONTEXT)

CO CONDUIT AND BOX ROUGH-IN ONLY (ROUGH-IN ONLY)

EG EQUIPMENT GROUND

ABBR: DESCRIPTION:

EGC EQUIPMENT GROUNDING CONDUCTOR

AFG ABOVE FINISHED GRADE

EOL END OF LINE

BC BELOW COUNTER

ASR ARCHITECTURAL SURFACE RACEWAY

ABV ABOVE

AFC ABOVE FINISHED CEILING

EPO EMERGENCY POWER OFF

GFR GROUND FAULT REMOTE

HOA HAND/OFF/AUTO

ITR IT RACK MOUNTED RECEPTACLE

NC NORMALLY CLOSED

NEMA # NEMA RATING

NIC NOT IN CONTRACTED SCOPE

NO NORMALLY OPEN

ROOF EQUIPMENT LOCATED ON ROOF ABOVE

SM SURFACE MOUNTED

TYP TYPICAL

UG UNDERGROUND

UON UNLESS OTHERWISE NOTED

1. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE

WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR

BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH

PHASE.

2. FLUSH MOUNT ALL DUPLEX RECEPTACLES AND TECHNOLOGY OUTLETS AT +18" FROM

FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. RECEPTACLES AND

OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED. MOUNT

EXTERIOR LOCATED RECEPTACLES WITH WHILE-IN-USE COVERS AT +20" FROM FINISHED

GRADE (CENTER DIMENSIONS) TO MAINTAIN INSTALLATION ADA COMPLIANCE.

3. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL

BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF

THROUGH-PENETRATION FIRESTOPS.

4. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND

EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES

IN CEILING TILE PATTERN. SMOKE DETECTORS,CARBON MONOXIDE DETECTORS, AND

OCCUPANCY/VACANCY SENSORS SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR

SUPPLY DIFFUSER OR RETURN GRILLE. CARBON MONOXIDE DETECTORS SHALL BE LOCATED

10 PLUS FT FROM FIRE PLACES, COOKING, AND SIMILAR FUEL-BURNING APPLIANCES.

5. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT

LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS.

PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL

ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE

FURNITURE AND/OR EQUIPMENT.

6. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,

OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL

MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT

SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER

CONTRACTOR.

7. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL

OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE

EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR

SEALED INTO OPENINGS.

8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE

WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE

IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND

FINISH.

9. ELECTRICAL IDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR COLOR/LABEL

REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.

ELECTRICAL INSTALLATION NOTES:

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD

SURVEYS, EXISTING BUILDING DOCUMENTS. CONTRACTOR SHALL REVIEW EXISTING

CONDITIONS AND REPORT CONFLICTS.

2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. CONTRACTOR

SHALL REVIEW EXISTING CONDITIONS AND REPORT CONFLICTS.

3. CONTRACTOR SHALL REVIEW EXISTING CONDITIONS PRIOR TO FABRICATION OF CABLE

TRAY, BUSWAY, CONDUIT RACKS, AND OTHER SYSTEMS. RISES AND DROPS MAY BE

NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.

4. ELECTRICAL CONTRACTOR SHALL REVIEW EXISTING CONDITIONS TO VERIFY ACCESSIBILITY

TO THE AREAS OF THEIR WORK INCLUDING WALLS, FLOOR, CEILINGS, CEILING TILES/GRID,

AND ROOF. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE CUTTING, REMOVAL,

PATCHING, AND REINSTALLATION OF AFFECTED AREAS ASSOCIATED WITH THEIR WORK BY

COORDINATING WITH THE GENERAL CONTRACTOR OR QUALIFIED CONTRACTOR.

5. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW

EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER

ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES

NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO

ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

ELECTRICAL RENOVATION NOTES:

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, FIRE ALARM, AND OTHER LOW VOLTAGE SYSTEMS.

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

DETAIL REFERRED TO BY SECTION CUT

SHEET DETAIL IS LOCATED ON

NAME

VIEW NAME

1/8" = 1'-0"

M101

SIMSIM

INDICATES SIMILAR DETAIL REFERENCED

IN MULTIPLE LOCATIONS

LEVEL NAME

10'-0" HEIGHT ABOVE

PROJECT 0'-0"

1 KEYNOTE: INDICATES NOTE USED TO

DESCRIBE ADDITIONAL INFORMATION

ABOUT WORK REQUIRED, SPECIFIC

TO THE SHEET AND/OR DETAIL

N O R

HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

LINE TYPE AND TAG KEY:

NEW WORK BY THIS CONTRACTOR (WIDE LINE)

EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)

HALFTONING DOES NOT MODIFY SCOPE.

'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING

TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL

INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST

INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL

T101

NEW

EXISTING TO BE REMOVED (SHORT DASHED PATTERN)

NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

EXISTING

EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)

EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

TEMPERATURE CONTROLS CONTRACTORT.C.C.

GENERAL CONTRACTORG.C.

MECHANICAL CONTRACTORM.C.

ELECTRICAL CONTRACTORE.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

CONSTRUCTION MANAGERC.M.

CONTACT PERSONS:

PROJECT MANAGER

MECHANICAL

ELECTRICAL

NATE JACQUES

EVAN HAMMER

KRISTIN SPINA

DESCRIPTION: PERSON:

BUILDING CODE: IBC 2015 EDITION

FIRE CODE: IFC 2015 EDITION

PLUMBING CODE: UPC 2021 EDITION

MECHANICAL CODE: IMC 2021 EDITION

ELECTRICAL CODE: NFPA 70 (NEC) 2020 EDITION

ENERGY CONSERVATION CODE: IECC 2012

APPLICABLE CODES

CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS

INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING:

FEEDERS: SWITCHBOARDS, DISTRIBUTION PANELS,

PANELBOARDS, MOTOR CONTROL CENTERS, ETC.

BRANCH CIRCUITS: LIGHTING, RECEPTACLES,

CONTROLS, ETC.

MECHANICAL EQUIPMENT FEEDERS: PUMPS, CHILLERS,

AIR HANDLING UNITS, ETC.

FLOOR MOUNTED EQUIPMENT FEEDERS: PUMPS, ETC.

(INCLUDE NO MORE THAN 6 FEET OF LFMC TO PUMP)

CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)

WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,

INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)

CONDUIT INSTALLATION SCHEDULE

THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION OF APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAWINGS. THE INSTALLATION OF RMC CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT SPECIFIED IN THIS SCHEDULE. REFER TO CONDUIT AND BOXES SPECIFICATION 26 05 33 FOR ADDITIONAL

INFORMATION.

INSTALLATION TYPE RMC IMC EMT PVC

X X

X X

X X

X X

X X

X

ELEVATED CONCRETE SLABS (ABOVE GRADE)

XX

INTERIOR LOCATIONS WITH FINISHED CEILING AND WALLS: CONCEALED

IN WALLS AND ABOVE FINISHED CEILINGS

INTERIOR LOCATIONS WITHOUT FINISHED CEILINGS: CONCEALED IN

WALL, EXPOSED ABOVE CEILINGS

EXISTING INTERIOR LOCATIONS WITH FINISHED CEILINGS AND WALLS:

CONCEALED IN WALLS AND ABOVE FINISHED CEILING UNLESS

OTHERWISE NOTED

X

XX

X

JB 26 05 33 JUNCTION BOX

J

J

ECONN 26 05 33 ELECTRICAL CONNECTION

E

E

PANEL '###' EXISTING PANELBOARD - SURFACE MOUNT

PANEL '###' EXISTING PANELBOARD - RECESS MOUNT

ELECTRICAL SYMBOL LIST

SYMBOL: TAG: SPEC

SECTION:

DESCRIPTION:

REC-DUP 26 27 26 DUPLEX RECEPTACLE, 125V

REC-DUP-GFI 26 27 26 DUPLEX GFI RECEPTACLE, 125V

REC-DUP-WP 26 27 26 DUPLEX GFI WEATHERPROOF RECEPTACLE 125V

W

ELECTRICAL SYMBOL LIST

SYMBOL: TAG: SPEC

SECTION:

DESCRIPTION:

DS-#/FDS-#/DSS-# 26 28 16 DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

INTERLOCKED RECEPTACLE DISCONNECT.

REFER TO DISC/STA SCHEDULE

MS-# EXISTING SURFACE OR RECESS MOUNTED STARTER.

ELECTRICAL MOUNTING SUBSCRIPT KEY:

A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH

C MOUNT AT CEILING (DEVICE OR ROUGH-IN CONTEXT)

H MOUNT ORIENTED HORIZONTALLY

L MOUNT IN CASEWORK

M MOUNT IN MODULAR FURNITURE

O WIRING DEVICE, OCCUPANCY CONTROLLED

R MOUNT IN SURFACE RACEWAY

S SURFACE MOUNTED

W WEATHERPROOF WIRING DEVICE, NEMA 3R WHILE-IN-USE COVER, WR LISTED

WG WIRE GUARD

WP WEATHERPROOF

RECEPTACLE SUBSCRIPT KEY:

DEVICE

# = MOUNTING (IF APPLICABLE)

1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: A / 1

DEVICE KEY:

ELECTRICAL SHEET INDEX

E000 ELECTRICAL COVERSHEET

E101 DEMOLITION FLOOR PLAN - ELECTRICAL

E201 FLOOR PLAN - ELECTRICAL

E400 ELECTRICAL DETAILS

E600 ELECTRICAL SCHEDULES

GRAND TOTAL: 5

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2024 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908

The FUTURE. Built Smarter www.imegcorp.com

AGENCY APPROVAL

REVISIONS

No. Date Revision / Issue

DISCLAIMER

IOWA DEPARTMENT OF

ADMINISTRATIVE SERVICES

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #24006792.00

CONSTRUCTION MANAGER

MCGOUGH CONSTRUCTION

217 E 2ND ST SUITE 120

DES MOINES, IA 50309

As indicated

/2

/2

:5 :4

A

M

9459.00 - HHS STS A.E.

SHEPERD AC

REPLACEMENT

3211 Edgington Ave Eldora, IA 50627

E000

ELECTRICAL COVERSHEET

KRISPI

TONDEL

CHRMAR

24006792.00

01/17/2025

BID DOCUMENTS

.0

TUNEL

STAIR

MECH/ ELEC

UP

S

S

F

M M

M M

C M

S

ENTRY VESTIBULE

STAIR

VEST #1

LOBBY

WOMEN'S RESTROOM

DN

E

E

E

E

E

EXISTING MDP

EXISTING PANEL C

EXISTING PANEL PANEL B

FACP

MS-HCCP

DS-HCCP-2

MS-AHU-2(E)

EXISTING PANEL A

AHU-2(E)

HCCP-2

CU-E

DS-CU-E

DS-ACCU-3B

DS-ACCU-3A

ACCU-3B

ACCU-3A

E101

DS-AHU-2(E)

N O R

HT

1/4" = 1'-0"1

FIRST FLOOR DEMOLITION PLAN - ELECTRICAL

N O R

HT

3/16" = 1'-0"2

BASEMENT FLOOR DEMOLITION PLAN - ELECTRICAL

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2024 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908

The FUTURE. Built Smarter www.imegcorp.com

AGENCY APPROVAL

REVISIONS

No. Date Revision / Issue

DISCLAIMER

IOWA DEPARTMENT OF

ADMINISTRATIVE SERVICES

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #24006792.00

CONSTRUCTION MANAGER

MCGOUGH CONSTRUCTION

217 E 2ND ST SUITE 120

DES MOINES, IA 50309

As indicated

/2

/2

:5 :4

A

M

9459.00 - HHS STS A.E.

SHEPERD AC

REPLACEMENT

3211 Edgington Ave Eldora, IA 50627

E101

DEMOLITION FLOOR PLAN -

ELECTRICAL

KRISPI

TONDEL

CHRMAR

24006792.00

01/17/2025

BID DOCUMENTS

.0

KEYNOTES:

1. REMOVE EXISTING ELECTRICAL CONNECTION

FOR EXISTING CONDENSING UNIT.

2. REMOVE EXISTING DISCONNECT SERVING

EXISTING CONDENSING UNIT.

STAIR

VEST #1

LOBBY

WOMEN'S RESTROOM

DN

E

E

E

E

E

E

E

E E

EXISTING PANEL A

EXISTING PANEL PANEL B

FACP

BCU-3

HCCP-2 AHU-2(E)

EF-1

ACCU-3A

ACCU-3B

DS-ACCU-3B

DS-ACCU-3A

MS-HCCP

DS-HCCP-2

DS-AHU-2(E)

MS-AHU-2(E)

DS-ACCU-1

DS-CU-1CU-1

MDP-5

DS-CU-1

MECH CONTROL BOX

A-38

MECH CONTROL BOX

A-40

W

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2024 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908

The FUTURE. Built Smarter www.imegcorp.com

AGENCY APPROVAL

REVISIONS

No. Date Revision / Issue

DISCLAIMER

IOWA DEPARTMENT OF

ADMINISTRATIVE SERVICES

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #24006792.00

CONSTRUCTION MANAGER

MCGOUGH CONSTRUCTION

217 E 2ND ST SUITE 120

DES MOINES, IA 50309

1/4" = 1'-0"

/2

/2

:5 :4

A

M

9459.00 - HHS STS A.E.

SHEPERD AC

REPLACEMENT

3211 Edgington Ave Eldora, IA 50627

E201

FLOOR PLAN - ELECTRICAL

KRISPI

TONDEL

CHRMAR

24006792.00

01/17/2025

BID DOCUMENTS

.0

N O R

HT

1/4" = 1'-0"1

FIRST FLOOR PLAN - ELECTRICAL

KEYNOTES:

1. EXTEND #12 THWN CONDUCTORS IN 3/4'

CONDUIT TO NEAREST 120V CIRCUIT.

120/208V,3Ø4W

600A MCB

SCCR 42 kA

MDP

120/208V,3Ø4W

200A MLO

C

120/208V,3Ø4W

200A MLO

A

120/208V,3Ø4W

100A MLO

PANEL B

E

CU-EDS-CU-E

120/208V,3Ø4W

600A MCB

SCCR 42 kA

MDP

120/208V,3Ø4W

200A MLO

C

120/208V,3Ø4W

200A MLO

A

120/208V,3Ø4W

100A MLO

PANEL B

DS-CU-1

E

CU-1

ISC 0.00 kA

13.83 kVA

DS-CU-1

E

CU-1

ISC 0.00 kA

13.83 kVA

3#6 & 1#10 EGC IN 3/4" C.

FROM 50A/3P

3#6 & 1#10 EGC IN 3/4" C.

FROM 50A/3P

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2024 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908

The FUTURE. Built Smarter www.imegcorp.com

AGENCY APPROVAL

REVISIONS

No. Date Revision / Issue

DISCLAIMER

IOWA DEPARTMENT OF

ADMINISTRATIVE SERVICES

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #24006792.00

CONSTRUCTION MANAGER

MCGOUGH CONSTRUCTION

217 E 2ND ST SUITE 120

DES MOINES, IA 50309

12" = 1'-0"

/2

/2

:5 :4

A

M

9459.00 - HHS STS A.E.

SHEPERD AC

REPLACEMENT

3211 Edgington Ave Eldora, IA 50627

E400

ELECTRICAL DETAILS

KRISPI

TONDEL

CHRMAR

24006792.00

01/17/2025

BID DOCUMENTS

.0

NO SCALE1

RISER DIAGRAM - DEMO

NO SCALE2

RISER DIAGRAM - NEW

IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO

THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT

BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.

©2024 IMEG CONSULTANTS CORP.

REF. SCALE IN INCHES

0 1 2 3

2882 106TH STREET

DES MOINES, IA 50322

P: 515.334.9906 F: 515.334.9908

The FUTURE. Built Smarter www.imegcorp.com

AGENCY APPROVAL

REVISIONS

No. Date Revision / Issue

DISCLAIMER

IOWA DEPARTMENT OF

ADMINISTRATIVE SERVICES

SHEET INFORMATION

Date

Project #

Drawn

Checked

Approved

SHEET TITLE

SCALE

Scale:

SHEET NUMBER

Issue

PROJECT #24006792.00

CONSTRUCTION MANAGER

MCGOUGH CONSTRUCTION

217 E 2ND ST SUITE 120

DES MOINES, IA 50309

/2

/2

:5 :4

A

M

9459.00 - HHS STS A.E.

SHEPERD AC

REPLACEMENT

3211 Edgington Ave Eldora, IA 50627

E600

ELECTRICAL SCHEDULES

KRISPI

TONDEL

CHRMAR

24006792.00

01/17/2025

BID DOCUMENTS

.0

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 2.8

TOTAL CONNECTED AMPS: 2.78 A

TOTAL ESTIMATED DEMAND LOAD: 1 kVA

TOTAL CONNECTED LOAD: 1.00 kVA

Power 1 kVA 100.00% 1 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 4.81 4.81 0.00

Total Load: 0.50 kVA 0.50 kVA 0.00 kVA

-- 41 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 42 --

39 0 0.5 1.27 12 12 12 1 15 CONTROL BOX 40 *NB

RECEPT. 50 2 -- -- --

0 0.5 1.25 12 12 12 1 15 CONTROL BOX 38 *NB

-- 35 POPCORN POPPER 50 1 -- -- -- 0 0 -- -- -- 1 20 NORTH BLACK OUT SCREEN 36 --

-- 33 RECEPT. 20 1 -- -- -- 0 0 -- -- -- 1 20 WINDOW LAMP 34 --

-- 31 EMS CABINET 20 1 -- -- -- 0 0 -- -- -- 1 20 PROJECTOR 32 --

-- 29 RECEPT. 20 1 -- -- -- 0 0 -- -- -- 1 20 VIDIO SCREEN 30 --

-- 27 RECEPT. 20 1 -- -- -- 0 0 28

-- 25 RECEPT. 20 1 -- -- -- 0 0 26

23 0 0

-- -- -- 3 45 AHU-2(E)

21 0 0 -- -- -- 1 15 SPARE 22 ----

HCCP-2 20 3 -- -- --

0 0 -- -- -- 1 15 FRONT SPEAKERS 20 --

-- 17 RECEPT. 20 1 -- -- -- 0 0 -- -- -- 1 15 TIME CLOCK 18 --

-- 15 RECEPT. 20 1 -- -- -- 0 0 -- -- -- 1 20 RECEPT. 16 --

-- 13 RECEPT. 20 1 -- -- -- 0 0 -- -- -- 1 20 RECEPT. 14 --

-- 11 RECEPT. 20 1 -- -- -- 0 0 -- -- -- 1 20 RECEPT. 12 --

-- 9 RECEPT. 20 1 -- -- -- 0 0 -- -- -- 1 20 RECEPT. 10 --

-- 7 LIGHTS 20 1 -- -- -- 0 0 -- -- -- 1 20 RECEPT. 8 --

-- 5 LIGHTS 20 1 -- -- -- 0 0 -- -- -- 1 20 LIGHTS 6 --

-- 3 LIGHTS 20 1 -- -- -- 0 0 -- -- -- 1 20 LIGHTS 4 --

-- 1 LIGHTS 20 1 -- -- -- 0 0 -- -- -- 1 20 LIGHTS 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

VD

A B C VD

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

SCCR: 10 kA

LOCATION: WIRE: 4

FED FROM: 200/3P @ MDP GROUND BUS PHASE: 3

ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE SINGLE TUB MAIN: 200 MLO

EXISTING PANEL A

AMS-ASSEMBLED MOTOR STARTER

FS - FUSED SWITCH

MX - MANUAL SWITCH

MS - MANUAL STARTER

SS - SOLID STATE

RV - REDUCED VOLTAGE AUTOXFMR

SW - 2 SPEED, 1 WINDING

TW - 2 SPEED, 2 WINDING

RE - REVERSING HL - HANDLE PADLOCK HASP

YD - WYE - DELTA S/N - INSULATED NEUTRAL ASSEMBLY SS - START-STOP PUSHBUTTON IN DOOR

FV - FULL VOLTAGE *TA - TWO CONVERTIBLE AUXILIARY CONTACTS EI - ELECTRICAL INTERLOCK (2)-N.O. & (2)-N.C.

STARTER TYPE: *RP - RED (RUN) PILOT LIGHT IN DOOR FA - 4-CONVERTIBLE AUXILIARY CONTACTS

*HA - HAND-OFF-AUTO IN DOOR GP - GREEN (OFF) PILOT LIGHT IN DOOR

CB - CIRCUIT BREAKER *EO - ELECTRONIC OVERLOAD (3 PHASE MOTORS) TS - 2 SPEED SELECTOR SWITCH IN DOOR

NF - NON-FUSED *CT - CONTROL TRANSFORMER, FUSED 120V TO - MELTING THERMAL OVERLOADS (1 PHASE)

FU - FUSED SA - STANDARD ACCESSORIES (INCLUDES * ITEMS) PF - PHASE LOSS PROTECTION (5 HP OR GREATER, 3 PHASE MOTOR)

DISCONNECT TYPE: ACCESSORIES & OPTIONS

NOTE: ALL DISCONNECTS (EXCEPT MANUAL STARTERS) SHALL BE HEAVY DUTY TYPE.

DISCONNECT AND STARTER SCHEDULE

ITEM

DISCONNECT TYPE &

RATING

VOLTAGE POLES ENCLOSURE

REQUIRED

ACCESSORIES &

OPTIONS COMMENTSTYPE RATING

TRIP

RATING

DS-CU-1 NF 60 208 3 NEMA 3R

DS-CU-1 NF 60 208 3 NEMA 3R

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 79.6

TOTAL CONNECTED AMPS: 79.58 A

TOTAL ESTIMATED DEMAND LOAD: 28.668 kVA

TOTAL CONNECTED LOAD: 28.67 kVA

Power 28.668 kVA 100.00% 28.668 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY (INCLUDES ALL TUBS IN THIS PANEL)

16 SPACE -- 1 -- -- -- -- -- --

15 SPACE -- 1 -- -- -- -- -- --

14 SPACE -- 1 -- -- -- -- -- --

13 SPACE -- 1 -- -- -- -- -- --

12 SPACE -- 1 -- -- -- -- -- --

11 SPACE -- 1 -- -- -- -- -- --

10 SPACE -- 1 -- -- -- -- -- --

9 SPACE -- 1 -- -- -- -- -- --

8 SPACE -- 1 -- -- -- -- -- --

7 SPACE -- 1 -- -- -- -- -- --

6 CU-1, CIRCUIT 2 13.83 kVA 3 150 50 3#6 & 1#10 EGC IN 3/4" C. *NB

5 CU-1 CIRCUIT 1 13.83 kVA 3 150 50 3#6 & 1#10 EGC IN 3/4" C. *NB

4 ACCU-2 0 kVA 1 250 250 -- -- -- --

3 EXISTING PANEL C 0 kVA 3 250 200 4#3/0 & 1#6 EGC IN 2" C. *EB

2 EXISTING PANEL B 0 kVA 3 150 100 4#2 & 1#6 EGC IN 1 1/4" C. *EB

1 EXISTING PANEL A 1 kVA 3 250 200 4#3/0 & 1#6 EGC IN 2" C. *EB

CKT LOAD DESCRIPTION Load POLES FRAME TRIP TYPE ACC. WIRE AND RACEWAY

CIRCUIT

KEY

NOTES: SEE ELECTRICAL DISTRIBUTION AND PANEL SCHEDULE NOTES FOR PANEL KEY.

SCCR: 42 kA

LOCATION: WIRE: 4

FED FROM: 0/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MAIN: 600 MCB

EXISTING MDP

ELECTRICAL DISTRIBUTION AND PANEL

SCHEDULE NOTES:

1. BRANCH PANEL KEY:

a. *A = ARC FAULT CIRCUIT INTERRUPT

b. *G = GROUND FAULT CIRCUIT INTERRUPT

c. *I = ISOLATED GROUND

d. *P = PADLOCK HASP

e. *R = RED HANDLE

f. *S = SHUNT TRIP

g. *NB = NEW BREAKER (NEW BREAKER TO MATCH EXISTING PANEL

CHARACTERISTICS)

h. *RB = REPLACE EXISTING BREAKER WITH NEW BREAKER

i. *EB = EXISTING BREAKER

Sheets
E000 - ELECTRICAL COVERSHEET
E101 - DEMOLITION FLOOR PLAN - ELECTRICAL
E201 - FLOOR PLAN - ELECTRICAL
E400 - ELECTRICAL DETAILS
E600 - ELECTRICAL SCHEDULES
G000 - PROJECT COVERSHEET
M000 - HVAC COVERSHEET
M100 - FIRST FLOOR DEMOLITION PLAN - MECHANICAL
M201 - FLOOR PLAN - MECHANICAL
M400 - MECHANICAL DETAILS AND SCHEDULES
M500 - MECHANICAL DIAGRAMS