RFB944400-01 - Project Drawings.pdf
PDF 10 MB Posted
- Attached to
- DOC Clarinda Correctional Facility Tunnel Repair
- Solicitation number
- 005-RFBCON-2227-2026
- Issued by
- Polk County, Iowa
About this file
This is a comprehensive set of construction documents for a tunnel repair and replacement project for the Iowa Department of Administrative Services (DAS) located at the Clarinda Correctional Facility in Clarinda, Iowa. The project involves repairing and replacing tunnel infrastructure in the main building's southwest wing, specifically focusing on two tunnel sections with project number 9444.00 and bid number RFP944400-01. The documents, dated October 10, 2025, include detailed structural, civil, mechanical, electrical, and plumbing plans for demolition and reconstruction of tunnel systems spanning approximately 600 linear feet across two tunnel segments.
The project involves complete removal and replacement of tunnel components, including concrete lid, pavement, piping systems (chilled water, steam, hot water), electrical conduits, and lighting. Key elements include installing new pipe supports, replacing steam traps and pressure reducing stations, adding sump pumps, and implementing new electrical infrastructure. The construction documents specify Schedule 80 CPVC piping, structural steel supports, and careful coordination between mechanical, electrical, plumbing, and structural contractors. The work requires precise removal of existing systems, protection of adjacent infrastructure, and installation of new systems with minimal disruption to the facility's operations. Structural repairs, concrete restoration, and utility system replacements are comprehensively detailed across multiple plan sheets and technical specifications.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFB944400-01 - Project Manual.pdf | ||
| Bidding Documents - Drawing Sheets and Project Manual.html | HTML file | |
| Project Specifications and Contract Documents.html | HTML file | |
| 1346802-event.pdf | ||
| RFB944400-01 - Bid Form.pdf | ||
| RFB944400-01 - Notice to Bidders.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PAGE COUNTY
PAGE COUNTY, IOWA
PROJECT LOCATION
PROJECT NUMBER
DATE
SHEET NO.
SHEET TITLE
400 E COURT AVE.
SUITE 140.
DES MOINES, IOWA 50309
515-243-4477 www.shuck-britson.com
SNYDER & ASSOCIATES, INC.
231 BENNETT AVE.
COUNCIL BLUFFS, IOWA 51503
P: 712-322-3202 www.snyder-associates.com
Project Engineer
Mechanical, Electrical and Plumbing Engineer
ALVINE ENGINEERING
400 E. COURT AVE
SUITE 130
DES MOINES, IA 50309
www.alvine.com
C
U s e rs
\d tr ip p \D o c u m e n ts
\1 .0
.1
T U
N N
E L
(R d tr ip p s h u c k -b ri ts o n .c o m
.r v t
/9 /2
:4
:1
P
M
D O
C C
C F
T U
N N
E L R
E P
A
IR
R
E P
L A
C E
M E
N T
M A
IN
B
L D
G
S W
W
IN
G
10/10/2025
125.0278.10
COVER
N th
S t, C la ri n d a
IA
TITLE SHEET
100% CONSTRUCTION DOCUMENTS
IO
W
A D
E P
A R
T M
E N
T O
F A
D M
IN
IS
T R
A T
IV
E
S E
R V
IC
E
S
D A
S
STRUCTURAL DRAWINGS
S0.00 NOTES
S1.01 TUNNEL PLAN
S1.02 TUNNEL PLANS AND ELEVATIONS
S1.03 TUNNEL PLANS AND ELEVATIONS
S1.04 TUNNEL PLANS AND ELEVATIONS
S1.05 TUNNEL PLANS AND ELEVATIONS
S1.06 TUNNEL PLANS AND ELEVATIONS
S1.07 TUNNEL PLANS AND ELEVATIONS
S2.01 DETAILS
S2.02 DETAILS
S2.03 DETAILS
S3.01 PHOTOS
S3.02 PHOTOS
S3.03 PHOTOS
S3.04 PHOTOS
100% CONSTRUCTION DOCUMENTS
FOR
IOWA DEPARTMENT OF
ADMINISTRATIVE SERVICES (DAS)
DOC CCF TUNNEL REPAIR / REPLACEMENT MAIN
BLDG. SW WING
PAGE COUNTY, IOWA
PROJECT INFORMATION
1 VICINITY MAP
CIVIL DRAWINGS
C100 REMOVAL PLAN
C200 SITE PLAN
MARK REVISION DATE
MECHANICAL, ELECTRICAL & PLUMBING DRAWINGS
MEP0.00 MECHANICAL ELECTRICAL & PLUMBING
SYMBOLS AND ABBREVIATIONS
MD1.02 TUNNEL PLANS AND ELEVATIONS DEMO
MD1.03 TUNNEL PLANS AND ELEVATIONS DEMO
MD1.04 TUNNEL PLANS AND ELEVATIONS DEMO
MD1.05 TUNNEL PLANS AND ELEVATIONS DEMO
MD1.06 TUNNEL PLANS AND ELEVATIONS DEMO
PED1.02 TUNNEL PLANS AND ELEVATIONS -
PLUMBING & ELECTRICAL DEMO
PED1.03 TUNNEL PLANS AND ELEVATIONS DEMO
PED1.04 TUNNEL PLANS AND ELEVATIONS DEMO
PED1.05 TUNNEL PLANS AND ELEVATIONS DEMO
PED1.06 TUNNEL PLANS AND ELEVATIONS DEMO
M1.02 TUNNEL PLANS AND ELEVATIONS
M1.03 TUNNEL PLANS AND ELEVATIONS
M1.04 TUNNEL PLANS AND ELEVATIONS
M1.05 TUNNEL PLANS AND ELEVATIONS
M1.06 TUNNEL PLANS AND ELEVATIONS
M3.01 PICTURES
M3.02 PICTURES
PE1.02 TUNNEL PLANS AND ELEVATIONS
PE1.03 TUNNEL PLANS AND ELEVATIONS
PE1.04 TUNNEL PLANS AND ELEVATIONS
PE1.05 TUNNEL PLANS AND ELEVATIONS
PE1.06 TUNNEL PLANS AND ELEVATIONS
MEP4.00 MECHANICAL ELECTRICAL & PLUMBING
SCHEDULES
PROJECT ADDRESS:
2000 N 16TH ST,
CLARINDA, IA 51632
DAS PROJECT #: 9444.00
RFB#: RFP944400-01
L
AWOI
RI
C E N S E D
PR
OF
ESS IONAL
EN
G
IN
E
ETYLER R.
VONWEIHE
P25351
I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF IOWA.
SIGNATURE: ____________________________________
NAME:
IOWA REG. NO: EXPIRATION DATE:
PAGES OR SHEETS COVERED BY THIS SEAL:
TYLER R. VONWEIHE. P.E.
P25351 12/31/2026
LISTED AS "STRUCTURAL"
L
AWOI
RI
C E N S E D
PR
OF
ESS IONAL
EN
G
IN
E
EELIZABETH
HUNTER
P18178
I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF IOWA.
SIGNATURE: ____________________________________
NAME:
IOWA REG. NO: EXPIRATION DATE:
PAGES OR SHEETS COVERED BY THIS SEAL:
ELIZABETH A. HUNTER, P.E.
P18178 12/31/2026
LISTED AS "CIVIL"
L
AWOI
RI
C E N S E D
PR
OF
ESS IONAL
EN
G
IN
E
EJASON P.
JONES
P22600
I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF IOWA.
SIGNATURE: ____________________________________
NAME:
IOWA REG. NO: EXPIRATION DATE:
PAGES OR SHEETS COVERED BY THIS SEAL:
JASON P. JONES, P.E.
P22600 12/31/2026
LISTED AS "M.E.P." (MECHANICAL AND PLUMBING)
L
AWOI
RI
C E N S E D
PR
OF
ESS IONAL
EN
G
IN
E
ENICHOLAS A.
ANDERA
P22839
I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF IOWA.
SIGNATURE: ____________________________________
NAME:
IOWA REG. NO: EXPIRATION DATE:
PAGES OR SHEETS COVERED BY THIS SEAL:
NICHOLAS A. ANDERA, P.E.
P22839 12/31/2026
LISTED AS "M.E.P." (ELECTRICAL)
L
AWOI
RI
C E N S E D
PR
OF
ESS IONAL
EN
G
IN
E
ETYLER R.
VONWEIHE
P25351
I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF IOWA.
SIGNATURE: ____________________________________
NAME:
IOWA REG. NO: EXPIRATION DATE:
PAGES OR SHEETS COVERED BY THIS SEAL:
TYLER R. VONWEIHE. P.E.
P25351 12/31/2026
LISTED AS "STRUCTURAL"
L
AWOI
RI
C E N S E D
PR
OF
ESS IONAL
EN
G
IN
E
EELIZABETH
HUNTER
P18178
I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF IOWA.
SIGNATURE: ____________________________________
NAME:
IOWA REG. NO: EXPIRATION DATE:
PAGES OR SHEETS COVERED BY THIS SEAL:
ELIZABETH A. HUNTER, P.E.
P18178 12/31/2026
LISTED AS "CIVIL"
L
AWOI
RI
C E N S E D
PR
OF
ESS IONAL
EN
G
IN
E
EJASON P.
JONES
P22600
I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF IOWA.
SIGNATURE: ____________________________________
NAME:
IOWA REG. NO: EXPIRATION DATE:
PAGES OR SHEETS COVERED BY THIS SEAL:
JASON P. JONES, P.E.
P22600 12/31/2026
LISTED AS "M.E.P." (MECHANICAL AND PLUMBING)
L
AWOI
RI
C E N S E D
PR
OF
ESS IONAL
EN
G
IN
E
ENICHOLAS A.
ANDERA
P22839
I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL
SUPERVISION AND THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF IOWA.
SIGNATURE: ____________________________________
NAME:
IOWA REG. NO: EXPIRATION DATE:
PAGES OR SHEETS COVERED BY THIS SEAL:
NICHOLAS A. ANDERA, P.E.
P22839 12/31/2026
LISTED AS "M.E.P." (ELECTRICAL)
8/8/20258/8/20258/8/2025 8/8/202510/10/2025 10/10/2025 10/10/202510/10/2025
BM500
F.F.E.=1055.96
AT DOCK
F.F.E.=1051.93
F.F.E.=1049.58
F.F.E.=1049.48
F.F.E.=1052.10
F.F.E.=1051.86
F.F.E.=1051.76
BUILDING F.F.E.=1049.12
CONCRETE
CONCRETE
CONCRETE
CONCRETE
CONCRETE
℄ 8" CONCRETE WALL
CONC. STEPS
RIM=1049.03
FL=1048.25 4" CLAY SW
RIM=1051.76
FL=1049.13 4" CLAY EAST
FL=1047.22 8" CLAY N-SW
RIM=1051.42
FL=1048.42 15" RCP WEST
FL=1049.03 8" HDPE SE
SUMP=1047.62
RIM=1051.34
FL=1048.00 4" PVC EAST
FL=1049.06 4" CLAY SE
FL=1048.49 4" DIP NE
FL=1047.83 4" DIP NW
RIM=1051.05
UNABLE TO OPEN
RIM=1051.04
UNABLE TO OPEN
RAMP
RIM=1051.19
FL=1048.65 6" STEEL EAST
FL=1048.60 6" STEEL WEST
FL=1048.78 4" STEEL SOUTH
FUEL PUMPS
BREATHER
RIM=1051.07
FL=1049.77 4" STEEL SOUTH
FACE OF FOUNDATION(TYP.)
FACE OF BUILDING(TYP.)
RIM=1052.10
FL=1049.48 4" STEEL SOUTH
SUMP=1048.54 (SILTED)
WINDOW SILL ELEV.=1055.75
WINDOW SILL ELEV.=1053.78
BASKETBALL HOOP
(FOOTING ONLY)
PROBED TOP/EDGE OF TUNNEL
TOP=1050.99+/- SLOT DRAIN
BOTTOM SILTED
RIM=1051.35
FL=1049.42 6" DIP NE
FL=1049.17 6" DIP WEST
RIM=1051.64
TUNNEL FLOOR=1044.12
TUNNEL TOP=1050.96
TOP 9" THICK
TUNNEL 48" WIDE BY 73" TALL
RIM=1051.92
TUNNEL FLOOR=1045.54
TUNNEL 48" WIDE BY 71" TALL
END OF TUNNEL 1.75' SE
RIM=1051.69
TUNNEL FLOOR=1044.44
TUNNEL TOP=1051.26
TOP 9" THICK
TUNNEL 48" WIDE BY 73" TALL
F.F.E.=1052.42
B1
B2
B3
B4
GRAVEL
GRAVEL
CONCRETE
RIM=1053.19
FL=1048.13 8" CLAY E-W
RAMP
+9
5.5
13+72.47
12+99.72
+9
5.1
12+15.19
+0
V:
\P ro je ct s\
\1
.0
8.
\C
AD
D \1
_C
_D
EM
O .d w g
R
AC
H
EL
D
IC
KE
Y, R
EM
O
VA
L
PL
AN
, 2
5/
/0
9, :1
PM
, A
N
SI
F U
LL
B
LE
ED
D (3
4.
X
2.
IN
C
H
ES
FEET
0 20
PROJECT NUMBER
DATE
SHEET NO.
SHEET TITLE
MARK REVISION DATE
400 E COURT AVE.
SUITE 140.
DES MOINES, IOWA 50309
515-243-4477 www.shuck-britson.com
SNYDER & ASSOCIATES, INC.
2727 S.W. SNYDER BLVD.
ANKENY, IOWA 50023
P: 515-964-2020 www.snyder-associates.com
Project Engineer
100% CONSTRUCTION DOCUMENTS
10/10/2025
125.0278
C100
D O
C C
C F
TU
N
N
EL
R
EP
AI
R
/R
EP
LA
C
EM
EN
T M
AI
N
B
LD
G . S
W W
IN
G
REMOVAL PLAN
C
LA
R
IN
D A, IO
W
A
IO
A D
EP
AR
TM
EN
T O
F
AD
M
IN
IS
TR
AT
IV
E
SE
R
VI
C
ES
(D
AS
REMOVAL NOTES
1. ITEMS TO REMAIN, PROTECT THE FOLLOWING. ANY DAMAGE DONE TO
ITEMS NOT PLANNED FOR REMOVAL IS THE RESPONSIBILITY OF THE
CONTRACTOR AND SHALL BE FIXED OR REPAIRED AT NO COST TO THE
OWNER.
A. EXISTING UTILITIES. CONTRACTOR IS RESPONSIBLE FOR
OBTAINING LOCATES PRIOR TO CONSTRUCTION.
B. TUNNEL WALLS & TOP WHERE NOT REMOVING.
C. FUEL PUMPS & TANKS.
D. EXISTING GRASSED AREA AROUND FUEL PUMPS.
E. EXISTING TREES.
F. CONCRETE STEPS AND WALL.
G. EXISTING BUILDINGS.
H. RECESSED DOCK AREA, SLABS, WALL IN PLACE & INLET.
I. ELEVATED DOCK AREA & INLETS.
J. PAVEMENT / ROCK.
K. TUNNEL WALLS, TOP & SIDEWALK WHERE NOT REMOVING.
L. DOCK AREA & WALL IN PLACE.
2. PAVEMENT REMOVALS, REMOVE THE FOLLOWING.
A. PCC PAVEMENT.
B. PCC DRIVE AREA PAVEMENT OVER THE TUNNEL. PROTECT THE
TUNNEL LID.
C. PCC SIDEWALK, DRIVE AREA PAVEMENT AND TUNNEL TOP WHERE
INDICATED. SEE STRUCTURAL PLANS FOR DETAILS.
TUNNEL
TUNNEL LID - PROTECT
UNLESS OTHERWISE NOTED.
PCC PAVEMENT OVER TUNNEL TO
BE REMOVED WHERE NOTED.
C100
PCC PAVEMENT OVER TUNNEL REMOVAL
NO SCALE
1A
1A
1A
1A 1B
1B
1C
1A
1A
1K
1E
1E
1E
1D
1F
1G
1G
1G
1G
1G
1G
LEGEND
- SIDEWALK OR DRIVE AREA PAVEMENT OVER TUNNEL TOP
REMOVAL, REFER TO DETAILS ON STRUCTURAL SHEETS
- PAVEMENT REMOVAL
- 22' WIDE TUNNEL LID REMOVAL FOR CONSTRUCTION
ACCESS, REFER TO DETAILS ON STRUCTURAL SHEETS
- EXISTING GRASSED AREA TO BE PROTECTED FOR FUELING
AREA & UNDERGROUND STORAGE TANKS
2A
2A
2A
2B
2B
2B
2B
2C
2C
2C
2C
1K
SNYDER & ASSOCIATES, INC.
www.snyder-associates.com
Project Engineer www.alvine.com
SNYDER & ASSOCIATES, INC.
231 BENNETT AVE.
COUNCIL BLUFFS, IOWA 51503
P: 712-322-3202
Project Engineer
Mechanical, Electrical and Plumbing Engineer
ALVINE ENGINEERING
400 E. COURT AVE
SUITE 130
DES MOINES, IA 50309
- WATER LINE
- ELECTRICAL LINE
- STORM NETWORK
1H
1I
TO DOCK
1J
1J
1J
1J
2B 1B
1B
GENERAL NOTES
1. NOTIFY UTILITY PROVIDERS AND CLARINDA CORRECTIONAL
FACILITY (CCF) PRIOR TO BEGINNING ANY CONSTRUCTION
ACTIVITIES AND COORDINATE WITH UTILITY PROVIDERS AND
CCF AS NECESSARY DURING CONSTRUCTION.
CONTRACTOR IS RESPONSIBLE FOR DETERMINING
EXISTENCE, EXACT LOCATION, AND DEPTH OF ALL UTILITIES.
PROTECT ALL UTILITY LINES AND STRUCTURES NOT SHOWN
FOR REMOVAL OR MODIFICATION. ANY DAMAGES TO
UTILITY ITEMS NOT SHOWN FOR REMOVAL OR MODIFICATION
SHALL BE REPAIRED TO THE UTILITY OWNER'S
SPECIFICATIONS AT THE CONTRACTOR'S EXPENSE.
2. CONSTRUCTION OF ALL PAVEMENT AND UTILITY
IMPROVEMENTS SHALL CONFORM TO THE IOWA STATEWIDE
URBAN DESIGN & SPECIFICATIONS (SUDAS).
3. ALL TRAFFIC CONTROL SHALL BE PROVIDED IN
ACCORDANCE WITH REQUIREMENTS SET FORTH IN THE
MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES (MUTCD).
COORDINATE ALL TRAFFIC CONTROL WITH CCF.
4. ANY UNDERGROUND PIPING FOUND AFTER PAVEMENT
REMOVAL, THAT WAS NOT IDENTIFIED ON PLANS, NEEDS TO
BE INVESTIGATED BY ENGINEER TO PROVIDE AN ACCURATE
AS-BUILT TO CCF AFTER THE PROJECT. PLEASE PROVIDE
APPROXIMATELY 1-WEEKS NOTICE TO ENGINEER FOR WHEN
THIS WORK IS ANTICIPATED.
5. CONTRACTOR TO LOAD AND TRANSPORT ALL MATERIALS
CONSIDERED TO BE UNDESIRABLE TO AN APPROVED
OFF-SITE WASTE SITE.
6. THE CONTRACTOR IS RESPONSIBLE FOR CLEANING DIRT
AND DEBRIS FROM NEIGHBORING STREETS, DRIVEWAYS,
AND SIDEWALKS CAUSED BY CONSTRUCTION ACTIVITIES IN
A TIMELY MANNER.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING
EROSION CONTROL MEASURES AS NECESSARY.
CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR
MAINTAINING ANY EROSION CONTROL MEASURES ON SITE
THROUGHOUT OF CONSTRUCTION. GRADING AND SOIL
EROSION CONTROL CODE REQUIREMENTS SHALL BE MET BY
CONTRACTOR.
UTILITY WARNING
THE UTILITIES SHOWN HAVE BEEN LOCATED FROM FIELD SURVEY
INFORMATION AND/OR RECORDS OBTAINED. THE SURVEYOR
MAKES NO GUARANTEE THAT THE UTILITIES OR SUBSURFACE
FEATURES SHOWN COMPRISE ALL SUCH ITEMS IN THE AREA,
EITHER IN SERVICE OR ABANDONED. THE SURVEYOR FURTHER
DOES NOT WARRANT THAT THE UTILITIES OR SUBSURFACE
FEATURES SHOWN ARE IN THE EXACT LOCATION INDICATED
EXCEPT WHERE NOTED AS QUALITY LEVEL A.
UTILITY CONTACT INFORMATION
UTILITY CONTACT FOR MAPPING INFORMATION SHOWN AS
RECEIVED FROM THE IOWA ONE CALL DESIGN REQUEST
SYSTEM, TICKET NUMBER 552500962.
( ASW ) ALLIANT ENERGY
COMPANY NAME : ALLIANT ENERGY
DESIGN CONTACT : ALLIANT ENERGY FIELD ENGINEER
PHONE : 800-255-4268
EMAIL : LOCATE_IPL@ALLIANTENERGY.COM
LOCATE REQUESTED: Y
( CRD ) CLARINDA, CITY OF
COMPANY NAME : CLARINDA, CITY OF
DESIGN CONTACT : GARY MCCLARNON
PHONE : 712-542-2136
EMAIL : GMCCLARNON@CITYOFCLARINDA.COM
LOCATE REQUESTED: Y
( FM4 ) FARMERS MUTUAL TELEPHONE
COMPANY NAME : FARMERS MUTUAL TELEPHONE
DESIGN CONTACT : PAT GARLAND
PHONE : 712-829-2111
EMAIL : PLANT@FMTCNET.COM
LOCATE REQUESTED: Y
( MD1E ) MIDAMER-ELEC
COMPANY NAME : MIDAMER-ELEC
DESIGN CONTACT : DAVID FITCH
PHONE : 712-366-5669
EMAIL : DLFITCH@MIDAMERICAN.COM
LOCATE REQUESTED: Y
( T16 ) MEDIACOM CABLE
COMPANY NAME : MEDIACOM CABLE
DESIGN CONTACT : SHANE SCHRADER
PHONE : 712-314-1248
EMAIL : SSCHRADER@MEDIACOMCC.COM
LOCATE REQUESTED: Y
CLARINDA CORRECTIONAL FACILITY
UTILITY CONTACT
GREG GRAHAM
OFFICE PHONE: 712-695-7186
CELL PHONE: 712-370-4448
1L
1F
BM500
F.F.E.=1055.96
AT DOCK
F.F.E.=1051.93
F.F.E.=1049.58
F.F.E.=1049.48
F.F.E.=1052.10
F.F.E.=1051.86
F.F.E.=1051.76
BUILDING F.F.E.=1049.12
CONCRETE
CONCRETE
CONCRETE
CONCRETE
CONCRETE
℄ 8" CONCRETE WALL
CONC. STEPS
RIM=1049.03
FL=1048.25 4" CLAY SW
RIM=1051.76
FL=1049.13 4" CLAY EAST
FL=1047.22 8" CLAY N-SW
RIM=1051.42
FL=1048.42 15" RCP WEST
FL=1049.03 8" HDPE SE
SUMP=1047.62
RIM=1051.34
FL=1048.00 4" PVC EAST
FL=1049.06 4" CLAY SE
FL=1048.49 4" DIP NE
FL=1047.83 4" DIP NW
RIM=1051.05
UNABLE TO OPEN
RIM=1051.04
UNABLE TO OPEN
RAMP
RIM=1051.19
FL=1048.65 6" STEEL EAST
FL=1048.60 6" STEEL WEST
FL=1048.78 4" STEEL SOUTH
FUEL PUMPS
BREATHER
RIM=1051.07
FL=1049.77 4" STEEL SOUTH
FACE OF FOUNDATION(TYP.)
FACE OF BUILDING(TYP.)
RIM=1052.10
FL=1049.48 4" STEEL SOUTH
SUMP=1048.54 (SILTED)
WINDOW SILL ELEV.=1055.75
WINDOW SILL ELEV.=1053.78
BASKETBALL HOOP
(FOOTING ONLY)
PROBED TOP/EDGE OF TUNNEL
TOP=1050.99+/- SLOT DRAIN
BOTTOM SILTED
RIM=1051.35
FL=1049.42 6" DIP NE
FL=1049.17 6" DIP WEST
RIM=1051.64
TUNNEL FLOOR=1044.12
TUNNEL TOP=1050.96
TOP 9" THICK
TUNNEL 48" WIDE BY 73" TALL
RIM=1051.92
TUNNEL FLOOR=1045.54
TUNNEL 48" WIDE BY 71" TALL
END OF TUNNEL 1.75' SE
RIM=1051.69
TUNNEL FLOOR=1044.44
TUNNEL TOP=1051.26
TOP 9" THICK
TUNNEL 48" WIDE BY 73" TALL
F.F.E.=1052.42
B1
B2
B3
B4
GRAVEL
GRAVEL
CONCRETE
RIM=1053.19
FL=1048.13 8" CLAY E-W
RAMP
1051.26 1051.28
1051.31 1051.20
1051.32 1051.29
1051.40 1051.36
1051.51
1051.54
1051.49
1051.50
1051.83
1051.61
1051.52 1051.55
1051.87 1051.89
1051.88 1051.85
1051.65
1051.60
1051.50
1051.51
1051.52 1051.60
1051.65 1051.60
1051.63 1051.87
1051.77 1051.91
1051.64 1051.66
1051.67 1051.67
LOADING ZONE
V:
\P ro je ct s\
\1
.0
8.
\C
AD
D \1
_C
_S
IT
E.
dw g R
AC
H
EL
D
IC
KE
Y, S
IT
E
PL
AN
, 2
5/
/0 9, :1
PM
, A N
SI
F
U
LL
B
LE
ED
D
(3 4.
X
2.
IN
C H
ES
FEET
0 20
PROJECT NUMBER
DATE
SHEET NO.
SHEET TITLE
MARK REVISION DATE
400 E COURT AVE.
SUITE 140.
DES MOINES, IOWA 50309
515-243-4477 www.shuck-britson.com
SNYDER & ASSOCIATES, INC.
2727 S.W. SNYDER BLVD.
ANKENY, IOWA 50023
P: 515-964-2020 www.snyder-associates.com
Project Engineer
Mechanical, Electrical and Plumbing Engineer
400 E COURT AVE.,
SUITE 130
DES MOINES, IA 50309
www.alvine.com
ALVINE ENGINEERING
100% CONSTRUCTION DOCUMENTS
10/10/2025
125.0278
C200
D O
C C
C F
TU
N
N
EL
R
EP
AI
R
/R
EP
LA
C
EM
EN
T M
AI
N
B
LD
G . S
W W
IN
G
SITE PLAN
C
LA
R
IN
D A, IO
A
IO
A D
EP
AR
TM
EN
T O
F
AD
M
IN
IS
TR
AT
IV
E
SE
R
VI
C
ES
(D
AS
SITE PLAN NOTES
1. TUNNEL IMPROVEMENTS AS FOLLOWS: SEE STRUCTURAL PLANS FOR
DETAILS.
A. REPLACE TUNNEL LID AND INSTALL NEW ACCESS HATCH.
2. PAVEMENT IMPROVEMENTS PROVIDE THE FOLLOWING:
A. 6" PCC PAVEMENT, REFER TO SUDAS STANDARD SPECIFICATIONS
SECTION 7010.
B. 4 TO 6" PCC DRIVE AREA PAVEMENT OVER THE TUNNEL. PROTECT
THE TUNNEL LID.
3. GRADES SHOWN REPRESENT FINISHED GRADE/TOP OF SLAB
ELEVATIONS UNLESS OTHERWISE NOTED. ALL EXISTING AREA INLETS
SHALL BE ADJUSTED TO GRADE.
4. PROVIDE POSITIVE DRAINAGE AWAY FROM BUILDINGS AND TUNNEL
DIRECTED TOWARD THE EXISTING STORM SEWER INLETS.
5. CONTRACTOR IS RESPONSIBLE FOR ANY EXCESS OR NEEDED SOIL FOR
THE SMALL GRADING CHANGES MADE OVER THE SITE. THIS ITEM IS
SUBSIDIARY TO THE 6" PCC PAVING ITEM.
6. SEED ALL DISTURBED AREAS NOT INDICATED FOR PCC INSTALLATION
WITH SUDAS TYPE 1 SEED MIX, REFER TO SUDAS STANDARD
SPECIFICATIONS SECTION 9010. FOLLOW PROPER SOIL PREP INCLUDED
WITHIN THE SPEC.
7. ACCESS TO THE FUELING AREA NEEDS TO BE MAINTAINED AND/OR
COORDINATED WITH CONSTRUCTION PHASING TO ENSURE FUEL IS
AVAILABLE WHEN NEEDED. IF A LONGER HOSE CAN BE INSTALLED
THEN FUELING MAY BE ABLE TO BE COMPLETED FROM THE GRAVEL
AREA.
8. ACCESS TO THE DOCK DELIVERY NEEDS TO BE MAINTAINED AS MUCH
AS POSSIBLE. ANY SHUTDOWNS NEED TO BE COORDINATED WITH CCF.
9. WITHIN THE DRIVE AREA, WHERE NEW PAVEMENT WILL BE INSTALLED
OVER THE UNDISTURBED TUNNEL TOP, A CONSTRUCTION JOINT SHALL
BE USED SO THAT CRACKING ALONG THE TUNNEL LID DOES NOT
FOLLOW THROUGH THE NEW DRIVE AREA PAVEMENT. THE PCC OVER
THE TUNNEL & THE DRIVE AREA PAVEMENT SHALL BE SEPARATE
POURS. THE TUNNEL IS MEANT TO BE THE HIGH POINT OF THE AREA SO
THAT WATER WILL SHED AWAY FROM THE TUNNEL TO THE AREA INLETS.
THE JOINTING LAYOUT SHALL FOLLOW SUDAS CHAPTER 5 SECTION 5G
(PCC PAVEMENT JOINTS), AND SECTION 7010.101 (PV-101). THE
JOINTING PLAN SHALL BE SUBMITTED TO THE ENGINEER AS A SHOP
DRAWING, AT LEAST 48 HOURS PRIOR TO PAVING. THE THICKNESS OF
THE PCC OVER THE TUNNEL MAY VARY SLIGHTLY BASED ON MAKING
THE TUNNEL THE HIGH POINT. ENGINEER SHALL VISIT THE SITE AFTER
FORMS ARE SET AND PRIOR TO POURING CONCRETE.
10. CCF WILL ADJUST DOWNSPOUTS ACCORDINGLY AFTER PAVING.
11. CONTRACTOR TO MATCH EXISTING PAVEMENT MARKINGS.
12. CONTRACTOR TO REMOVE VEGETATION FROM THIS CORNER &
REPLACE WITH 6" PCC OVER 12" PREPARED SUBGRADE. GRADE TO
ENSURE POSITIVE DRAINAGE.
LEGEND
- 4 TO 6" PCC DRIVE AREA PAVEMENT OVER TUNNEL, REFER TO
DETAILS ON STRUCTURAL SHEETS, SEE NOTE 9, THICKNESS TO
BE MATCHED AFTER REMAINING DRIVE AREA IS POURED
- 6" DEPTH PCC PAVEMENT OVER 12" PREPARED
SUBGRADE, SUDAS SECTION 7010
- TUNNEL LID REPLACEMENT AFTER CONSTRUCTION ACCESS
IS COMPLETE
1A
1A
1A
1A
MATCH EXISTING ELEVATION
2A
2B
2B
2B
C200
TYPICAL PAVEMENT CROSS SECTIONS
NO SCALE
PCC PAVEMENT SECTION
PCC SIDEWALK OVER TUNNEL SECTION
6" PCC PAVEMENT, SEE PLANS
FOR THICKNESS & LOCATIONS
12" DEPTH PREPARED SUBGRADE
2 - 6" LIFTS (SCARIFY AND COMPACT TO
95% STANDARD PROCTOR DENSITY),
PER SUDAS SECTION 2010
DRIVE AREA PAVEMENT, SEE PLANS
FOR THICKNESS & LOCATIONS, REFER
TO STRUCTURAL SHEETS FOR
REINFORCING
NEW OR EXISTING TUNNEL LID
SNYDER & ASSOCIATES, INC.
www.snyder-associates.com
Project Engineer www.alvine.com
SNYDER & ASSOCIATES, INC.
231 BENNETT AVE.
COUNCIL BLUFFS, IOWA 51503
P: 712-322-3202
Project Engineer
Mechanical, Electrical and Plumbing Engineer
ALVINE ENGINEERING
400 E. COURT AVE
SUITE 130
DES MOINES, IA 50309
TO DOCK
BOND BREAK - REFER
TO STRUCTURAL SHEETS
PROJECT NUMBER
DATE
SHEET NO.
SHEET TITLE
400 E COURT AVE.
SUITE 140.
DES MOINES, IOWA 50309
515-243-4477 www.shuck-britson.com
SNYDER & ASSOCIATES, INC.
231 BENNETT AVE.
COUNCIL BLUFFS, IOWA 51503
P: 712-322-3202 www.snyder-associates.com
Project Engineer
Mechanical, Electrical and Plumbing Engineer
ALVINE ENGINEERING
400 E. COURT AVE
SUITE 130
DES MOINES, IA 50309
www.alvine.com
C
U s e rs
\d tr ip p \D o c u m e n ts
\1 .0
.1
T U
N N
E L
(R d tr ip p s h u c k -b ri ts o n .c o m
.r v t
/9 /2
:4
:1
P
M
D O
C C
C F
T U
N N
E L R
E P
A
IR
R
E P
L A
C E
M E
N T
M A
IN
B
L D
G
S W
W
IN
G
10/10/2025
125.0278.10
S0.00
N th
S t, C la ri n d a
IA
NOTES
100% CONSTRUCTION DOCUMENTS
IO
W
A D
E P
A R
T M
E N
T O
F A
D M
IN
IS
T R
A T
IV
E
S E
R V
IC
E
S
D A
S
THE QUANTITIES FOR SOME LUMP SUM BID ITEMS ARE INDICATED WITH ROUNDED ESTIMATES FOR THE CONTRACTOR’S CONVENIENCE. DISCREPANCIES IN THE ESTIMATED VS ACTUAL QUANTITIES FOR THESE BID ITEMS WILL NOT CHANGE THE
PRICE PAID IN THE CONTRACT.
THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING THE DOCUMENTS IN FULL INCLUDING ALL THEIR OWN QUANTITIES
FOR ANY AND ALL BID ASSUMPTIONS.
BID ITEMS WITH SF, LF, OR EA ARE SUBJECT TO IN FIELD CONDITIONS AND ARE ALL TO BE APPROVED PRIOR TO WORK
PERFORMED AND PAYMENT TO THE CONTRACTOR.
ALL ITEMS IN CONSTRUCTION DOCUMENTS ARE LISTED HERE OR INCIDENTAL TO THESE ITEMS.
ONLY THE MOST SEVERE CONCRETE REPAIRS AND EPOXY CRACK INJECTION REPAIRS ARE TO BE PERFORMED, AS IDENTIFIED IN THE ESTIMATED QUANTITIES. WHILE MEASURED QUANTITIES ARE SHOWN ON THE PLANS, THE BID ITEM
QUANTITY WILL BE BASED ON THE ACTUAL QUANTITY OF REPAIRS COMPLETED.
ALL CONCRETE REPAIRS TO BE MARKED AND APPROVED FOR QUANTITY BY CM/CCF AND ENGINEER PRIOR TO PERFORMING REPAIRS. CONCRETE ISSUES SHOWN ON THE DRAWINGS DO NOT NECESSARILY CORRELATE TO REPAIRS
THAT WILL BE MADE BUT TO OBSERVATIONS MADE ON EXISTING CONCRETE DETERIORATION.
EPOXY CRACK INJECTION REPAIRS TO BE PRIORITIZED BY CRACK WIDTH, WITH THE WIDEST CRACKS REPAIRED FIRST
CONCRETE REPAIRS TO BE PRIORITIZED TO FILL IN OPENINGS AND PENETRATIONS IN THE WALLS TO SEAL THE TUNNEL
FROM THE EXTERIOR SOIL AND WHERE THERE IS EXPOSED REBAR.
GENERAL
1. THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS PRIOR TO
COMMENCING CONSTRUCTION.
2. ALL OF THE WORK TO BE DONE UNDER THIS CONTRACT SHALL BE DONE
IN ACCORDANCE WITH THE REQUIREMENTS OF THE DRAWINGS, THE
GENERAL REQUIREMENTS OF DIVISION ONE, THE GENERAL CONDITIONS,
THE SPECIFICATIONS, AND ANY ADDENDA THERETO.
3. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ACQUAINT
THEMSELVES AND ALL SUPERVISORY PERSONNEL WITH THE ABOVE-NAMED
DRAWINGS AND DOCUMENTS.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSPECTING THE SITE OF
THE PROPOSED WORK TO SATISFY THEMSELVES AS TO THE EXISTING
CONDITIONS RELATIVE TO THE CONTRACT.
5. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL TEMPORARY
SHORING/BRACING OF WALLS, SLABS, COLUMNS, ETC., AS REQUIRED BY
ALL FEDERAL, STATE AND LOCAL AGENCIES HAVING JURISDICTION,
UNTIL ALL PERMANENT FRAMING IS INSTALLED.
6. UTILITY LOCATIONS ARE SHOWN IN AN APPROXIMATE WAY ONLY. THE
CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING
UTILITIES BEFORE COMMENCING WORK. SHOULD ANY UTILITIES BE
FOUND DIFFERENT THAN LOCATED OR SHOWN ON THE DRAWINGS, THEY
SHALL BE PROTECTED IN PLACE AND THE ENGINEER SHALL BE
IMMEDIATELY NOTIFIED. THE CONTRACTOR SHALL BE FULLY
RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT BE
OCCASIONED BY THEIR FAILURE TO EXACTLY LOCATE AND PRESERVE ANY
AND ALL UTILITIES.
7. ALL CONSTRUCTION SHALL CONFORM TO INTERNATIONAL BUILDING
CODE 2015 UNLESS NOTED OTHERWISE.
8. DIMENSIONS MARKED +/- REQUIRE VERIFICATION BY THE CONTRACTOR.
9. IN ANY CASE OF CONFLICT BETWEEN THE NOTES, DETAILS AND
SPECIFICATIONS, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN.
CONTRACTOR SHALL MAKE NO DEVIATION FROM DESIGN DRAWINGS WITHOUT
WRITTEN APPROVAL OF THE ENGINEER.
10. PROTECT AND SHORE ALL OF THE UTILITIES INSIDE AND OUTSIDE OF THE
TUNNEL AS REQUIRED.
11. PROTECTIVE FENCE TO BE INSTALLED DURING WORK PREVENTING
ENTRANCE TO EXCAVATED AREA. SNOW FENCE TO BE USED AND
MAINTAINED THROUGHOUT CONSTRUCTION.
12. UTILITIES WITHIN THE VAULT MUST BE PROTECTED IN PLACE.
13. ALL PRODUCTS LISTED IN THESE DRAWINGS ARE THE BASIS-OF-DESIGN AND
NOT REQUIRED PRODUCTS, CONTRACTOR MAY USE PRODUCTS THAT ARE
SIMILAR OR BETTER IN PERFORMANCE.
CONCRETE
1. CONCRETE TO BE IN ACCORDANCE WITH "SPECIFICATIONS FOR
STRUCTURAL CONCRETE FOR BUILDINGS (ACI 301 CURRENT EDITION)".
2. REINFORCING STEEL TO BE BENT AND PLACED IN ACCORDANCE WITH
"MANUAL OF STD. PRACTICE FOR DETAILING CONCRETE STRUCTURES
(ACI 315 CURRENT EDITION)".
3. ALL CONCRETE SHALL BE 4000 PSI AT 28 DAYS.
4. CONCRETE EXPOSED TO FREEZE/THAW CONDITIONS SHALL BE AIR
ENTRAINED.
5. COARSE AGGREGATE FOR SLABS AND EXPOSED WALLS TO BE
CRUSHED LIMESTONE.
6. MAXIMUM AGGREGATE SIZE TO BE 1" - U.N.O.
7. ALL AGGREGATE IN ACCORDANCE WITH ASTM C33. LIMIT SHALE,
CHERT, COAL AND IRON OXIDE.
8. 4000 PSI CONCRETE TO HAVE A MIN. 6 SACKS CEMENT/MAX. 5 GAL. OF
WATER/SACK.
9. WATER REDUCER REQUIRED FOR ALL WALLS AND SLABS.
10. CONCRETE WATER-CEMENT RATIO INDICATED FOR DESIGN MIXES TO
HAVE CEMENT CONTENT ADJUSTED TO PROVIDE A WORKABLE MIX.
11. USE OF CALCIUM CHLORIDES PROHIBITED.
12. ALL REINFORCING STEEL TO BE ASTM A615 - GRADE 60.
13. CLEAR DISTANCE FROM FACE OF CONCRETE TO NEAR REINFORCING
BAR TO BE:
3" CAST AGAINST EARTH
2" SLABS ON GRADE (DISTANCE FROM TOP OF SLAB TO NEAR BAR)
1 1/2" STRUCTURAL SLABS
14. ALL REINFORCING STEEL SHALL BE SECURELY WIRED IN PLACE
BEFORE CONCRETE IS PLACED.
15. MAXIMUM SPACING OF BAR SUPPORTS TO BE 3'-0" O.C. EACH WAY.
16. PROVIDE 2-#5 BARS AROUND ALL SIDES OF HOLES THROUGH
CONCRETE WALLS AND SLABS. AT WALLS AND SLABS WITH MULTIPLE
MATS OF REINFORCING, PROVIDE SUPPLEMENTAL REINFORCING BARS
IN EACH FACE OF MEMBER. BARS TO EXTEND 2'-0" BEYOND EDGES OF
OPENINGS. SEE TYPICAL DETAIL.
17. PROVIDE CLASS B TENSION LAP SPLICES FOR CONTINUOUS BARS UNLESS
OTHERWISE SHOWN.
18 ALL SLAB REINFORCING STEEL SHALL CONTINUE THROUGH SLAB
CONSTRUCTION JOINTS.
19. DO NOT SAWCUT STRUCTURAL SLABS, STOOPS, OR SLABS ON METAL
DECK WITHOUT PRIOR APPROVAL OF ENGINEER.
20. THE CONTRACTOR SHALL COORDINATE LOCATIONS OF ALL OPENINGS
IN WALLS, SLABS AND FOUNDATIONS FOR DUCTS, PIPES, UTILITY LINES
AND OTHER PENETRATIONS WITH THE RESPECTIVE TRADES. ALL SUCH
PENETRATIONS SHALL BE FORMED OR SLEEVED IN CONCRETE AND
STEEL LINTELS IN MASONRY WALLS.
21. UNLESS OTHERWISE DETAILED ON PLANS, NO OTHER OBJECTS SHALL
BE PLACED IN STRUCTURAL SLABS WITHOUT PRIOR APPROVAL OF
ENGINEER (I.E. CONDUIT, MECHANICAL LINES, PLUMBING LINES, ETC.).
22. ALL CONCRETE SLABS SHALL BE POURED TO UNIFORM THICKNESS AS
INDICATED ON PLANS.
23. ALL REINFORCING BARS SHALL BE LAPPED AS SPECIFICALLY DETAILED
ON THE STRUCTURAL DRAWINGS. WHERE NOT SPECIFICALLY
INDICATED ON THE DRAWINGS, ALL REINFORCING BARS SHALL BE
LAPPED AS FOLLOWS: LAP WALL/BEAM TOP HORIZONTAL
REINFORCEMENT AT CENTER OF SPAN. LAP WALL/BEAM BOTTOM
HORIZONTAL REINFORCEMENT AT SUPPORT. TERMINATE CONTINUOUS
BARS AT DISCONTINUOUS ENDS WITH STANDARD HOOKS.
24. PROVIDE CONSTRUCTION JOINTS IN ACCORDANCE WITH ACI 318,
CHAPTER 6.4. SUBMIT SHOP DRAWINGS SHOWING CONSTRUCTION
JOINT LOCATIONS ALONG WITH THE SEQUENCE OF POURS FOR
REVIEW.
25. NEW WATERSTOPS TO BE BENTONITE SELF ADHERING STRIPS 1"X3/4"
STEEL
1. STRUCTURAL STEEL TO BE FABRICATED AND ERECTED IN
ACCORDANCE WITH "SPECIFICATION FOR STRUCTURAL STEEL
BUILDINGS" (AISC 360, CURRENT EDITION) AND "CODE OF STANDARD
PRACTICE FOR STEEL BUILDINGS AND BRIDGES" (AISC 303, CURRENT
EDITION).
2. STRUCTURAL STEEL WIDE FLANGE AND WT SECTIONS IN ACCORDANCE
WITH ASTM A992.
3. STEEL CHANNELS, PLATES AND ANGLES IN ACCORDANCE WITH ASTM
A36.
4. STEEL TUBES IN ACCORDANCE WITH ASTM A500 GRADE C (Fy = 50 ksi).
5. STEEL PIPE IN ACCORDANCE WITH ASTM A53 GRADE B (Fy = 35 ksi).
6. ALL ELECTRODES E70 SERIES.
7. STAINLESS STEEL TO BE ASTM A304.
8. CONCRETE ANCHORS SHALL BE HILTI HIT-HY 200 OR APPROVED
EQUAL. THREADED RODS SHALL BE HILTI HAS-E STANDARD RODS OR
GRADE 36 THREADED RODS UNLESS NOTED OTHERWISE.
9. SHOP PRIME ALL STRUCTURAL STEEL AND FIELD PAINT ALL STEEL AND
FIELD WELDS PER THE PAINTING NOTES
10. SUMP GRATING TO BE MCNICHOLS 1"X1/8" GW-2
OR APPROVED EQUAL SUFFICIENT TO SUPPORT 100 PSF/300 LB POINT
LOAD OVER 24" SPAN. CONTRACTOR MAY INCREASE THE DEPTH OF THE
GRATING TO FACILITATE IN CONCRETE FORMING AND GUTTER
DRAINAGE COORDINATE DEPTH OF GRATING WITH TOP OF SUMP
CONCRETE POUR TO PROVIDE FLAT TUNNEL PROFILE
DRILLED-IN-DOWELS AND ANCHOR BOLTS
1. HOLES FOR DOWELS SHALL BE DRILLED INTO THE EXISTING CONCRETE
AT THE LOCATIONS AND OF THE SIZE SHOWN ON THE PLANS. EMBED
DRILLED-IN-DOWELS 15 BAR OR ANCHOR BOLT DIAMETERS MINIMUM,
UNLESS NOTED OTHERWISE. AFTER HOLES ARE DRILLED, THEY SHALL BE
BLOWN CLEAN WITH OIL-FREE COMPRESSED AIR BEFORE THE EPOXY
RESIN IS PLACED IN THE HOLE. THE HOLE SHALL BE FILLED WITH EPOXY
RESIN TO A LEVEL SUCH THAT AFTER THE BAR IS INSERTED, THE EPOXY
WILL RISE TO THE SURFACE OF THE HOLE. IN OVERHEAD APPLICATIONS,
WORK AND SECURE ENOUGH EPOXY RESIN INTO THE HOLE SUCH THAT
WHEN THE DOWEL IS INSERTED, THE EPOXY RESIN COMPLETELY FILLS
THE VOID AROUND THE DOWEL. SECURE THE EPOXY RESIN IN PLACE FOR
CURING BY PLUGGING THE HOLE AROUND THE SHANK OF THE DOWEL.
REINFORCING STEEL DOWELS OR ANCHOR BOLTS OF THE SIZE SHOWN ON
THE PLANS SHALL BE INSERTED INTO THE HOLE IMMEDIATELY AFTER
THE EPOXY RESIN IS PLACED. THE EPOXY RESIN SHALL BE PERMITTED TO
SET BEFORE NEW CONCRETE IS PLACED AROUND THE ANCHOR.
DEMOLITION AND SHORING
1. THE CONTRACTOR SHALL TAKE ALL PRECAUTIONS NECESSARY TO
ENSURE THAT PARTS OF THE STRUCTURE TO BE PRESERVED ARE
NOT DAMAGED BY THE APPLICATION OF EXCESSIVE LOADS OR BY
ANY OTHER MEANS, AND THE CONTRACTOR SHALL ASSUME FULL
RESPONSIBILITY FOR ANY DAMAGE CAUSED.
2. ENSURE SAFE PASSAGE OF PERSONS AROUND AREA OF DEMOLITION
AND CONSTRUCTION. CONDUCT OPERATIONS TO PREVENT INJURY
TO ADJACENT BUILDINGS, STRUCTURES, EQUIPMENT AND OTHER
FACILITIES AND PERSONS.
3. EXISTING STRUCTURE SHALL BE TEMPORARILY SHORED AS REQUIRED
TO PERFORM CONSTRUCTION SHOWN HEREIN. MEMBERS SHALL BE
REMOVED IN SUCH A MANNER AS NOT TO DAMAGE EXISTING STRUCTURE.
4. ALL REMOVALS OF EXISTING CONCRETE SHALL BE INITIATED WITH A
NEAT, 3/4" MIN. DEEP STRAIGHT SAW CUT.
5. PROTECT EXISTING REINFORCING STEEL IN PLACE. EXERCISE EXTREME
CARE TO AVOID DAMAGING EXISTING REINFORCEMENT.
6. EXACT LOCATION OF EXISTING REINFORCEMENT IS TO BE DETERMINED
BY THE CONTRACTOR USING A REBAR LOCATOR OR SIMILAR METHOD.
7. LOCATE HOLES FOR BOLTS TO AVOID EXISTING REINFORCEMENT.
8. CONTRACTOR RESPONSIBLE TO REPAIR DAMAGED EXISTING
REINFORCEMENT TO THE SATISFACTION OF THE ENGINEER/OWNER.
CONTRACTOR RESPONSIBLE FOR ALL COSTS AND DELAYS ASSOCIATED
WITH THE REPAIR.
9. IN THE EVENT OF CONFLICTS, NOTIFY ENGINEER PRIOR TO FIELD
MODIFICATIONS OF DETAILS, CONNECTIONS, OR DIMENSIONS SHOWN
ON THE CONTRACT DRAWINGS.
10. CURRENT WALL TEMPORARY SHORING IS DESIGNED FOR 400 LBS /FT.
LATERAL FORCE TO HOLD BACK THE SOIL PRESSURES ON THE UNSUPPORTED
WALL IN ITS TEMPORARY CONDITION. NO HEAVY EQUIPMENT EXCEEDING 100
PSF SHALL BE ALLOWED WITHIN 6FT OF THE FACE OF THE TEMPORARY TUNNEL
LID EXCAVATION WHILE THE STRUCTURAL SLAB IS REMOVED UNTIL AFTER THE
NEW SLAB IS POURED AND CURED. CONTRACTOR MAY PROVIDE ALTERNATE
EXTERIOR TEMPORARY SHORING ALONG THE TOP OF THE WALL WITH STEEL
OR TIEBACKS FOR APPROVAL TO INCREASE THIS ALLOWABLE LOAD.
PAINTING:
1. APPLY PAINTS ONLY WHEN TEMPERATURE OF SURFACES TO BE PAINTED AND
AMBIENT AIR TEMPERATURES ARE BETWEEN 50 AND 95 DEG F.
2. DO NOT APPLY PAINTS IN SNOW, RAIN, FOG, OR MIST; WHEN RELATIVE HUMIDITY
EXCEEDS 85 PERCENT; AT TEMPERATURES LESS THAN 5 DEG F ABOVE THE DEW POINT;
OR TO DAMP OR WET SURFACES.
3. STEEL SUBSTRATES: REMOVE RUST, LOOSE MILL SCALE, AND SHOP PRIMER IF ANY.
CLEAN USING METHODS RECOMMENDED IN WRITING BY PAINT MANUFACTURER PER
SSPC-SP 6.
4. SHOP-PRIMED STEEL SUBSTRATES: CLEAN FIELD WELDS, AND AREAS WHERE SHOP
PAINT IS ABRADED. PAINT EXPOSED AREAS WITH THE SAME MATERIAL AS USED FOR SHOP
PRIMING TO COMPLY WITH SSPC-PA 1 FOR TOUCHING UP SHOP-PRIMED SURFACES.
5. APPLY PAINTS ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS AND
RECOMMENDATIONS IN "MPI ARCHITECTURAL PAINTING SPECIFICATION MANUAL."
6. APPLY PAINTS TO PRODUCE SURFACE FILMS WITHOUT CLOUDINESS, SPOTTING,
HOLIDAYS, LAPS, BRUSH MARKS, ROLLER TRACKING, RUNS, SAGS, ROPINESS, OR OTHER
SURFACE IMPERFECTIONS. CUT IN SHARP LINES AND COLOR BREAKS.
7. FURNISH EXTRA MATERIALS, FROM THE SAME PRODUCT RUN, THAT MATCH
PRODUCTS INSTALLED AND THAT ARE PACKAGED WITH PROTECTIVE COVERING FOR
STORAGE AND IDENTIFIED WITH LABELS DESCRIBING CONTENTS.
8. PAINT PRODUCT: (OR APPROVED EQUAL)
SYSTEM TYPE: EPOXY/EPOXY
SURFACE PREPARATION: SSPC-SP6/NACE 3 COMMERCIAL BLAST CLEANING OR
SSPC-SP3 POWER TOOL CLEANING (SSPC RUST GRADE CONDITION C)
PRIMER: SERIES 394 PERIMEPRIME, DFT 2.5 TO 3.5 MILS
INTERMEDIATE COAT: SERIES N69 HI-BUILD EPOXOLINE II, DFT 3.0 TO 5.0 MILS
FINISH COAT: SERIES N69 HI-BUILD EPOXOLINE II, DFT 4.0 TO 6.0 MILS
TOTAL DFT: 9.5 TO 14.5 MILS
9. PAINT SUBMITTAL:
1. COLOR: TO BE SUBMITTED FOR VERIFICATION TO OWNER.
2. PRODUCT DATA: FOR EACH TYPE OF PRODUCT. INCLUDE PREPARATION
REQUIREMENTS AND APPLICATION INSTRUCTIONS.
3. INCLUDE PRINTOUT OF CURRENT "MPI APPROVED PRODUCTS LIST" FOR EACH
PRODUCT CATEGORY SPECIFIED, WITH THE PROPOSED PRODUCT HIGHLIGHTED.
4. INDICATE VOC CONTENT.
5. SAMPLES FOR VERIFICATION: FOR EACH TYPE OF PAINT SYSTEM AND EACH
COLOR AND GLOSS OF TOPCOAT
CONCRETE REPAIR NOTES:
1. ALL EXISTING CONCRETE TO BE REMOVED IS TO BE REMOVED TO NEAT
LINES. ALL SUCH REMOVALS SHALL BE TO NEAT SAW CUTS TO PROVIDE
CLEAN STRAIGHT SURFACES AT INTERFACES BETWEEN NEW CONCRETE AND
REMAINING CONCRETE. PATCHING REQUIRED DUE TO POOR REMOVAL
PRACTICES WILL BE AT THE DIRECTION OF THE ENGINEER AND AT THE
CONTRACTORS EXPENSE.
2. ALL CONCRETE REMOVALS SHALL COMMENCE WITH A NEAT 3/4” DEEP,
STRAIGHT SAW CUT. ALL SAW CUTS SHALL TERMINATE AT A 90 DEG RIGHT
ANGLE. SAW CUTS SHALL NOT OVERLAP. DO NOT CUT EXISTING
REINFORCING.
3. EXPOSED REINFORCING SHALL BE CLEANED TO BARE METAL BY
SANDBLASTING AND BASF/MASTER BUILDERS MASTEREMACO P124 OR
APPROVED EQUAL APPLIED TO EXPOSED STEEL.
4. ALL SURFACES OF OLD CONCRETE AGAINST WHICH NEW PATCHING MORTAR
OR REPAIR CONCRETE IS TO BE PLACED SHALL BE THOROUGHLY CLEANED
AND ALL LOOSE MATERIAL SHALL BE REMOVED BY DRY SWEEPING AND
BLOWING OUT WITH CLEAN, DRY COMPRESSED AIR AND BASF/MASTER
BUILDERS MASTEREMACO P124 OR APPROVED EQUAL APPLIED TO
SURFACES.
5. ALL EXISTING REINFORCING BARS THAT ARE EXPOSED BY CONCRETE
REMOVAL SHALL BE CLEANED AND CAREFULLY INCORPORATED INTO THE
NEW WORK, EXCEPT WHERE THE REINFORCING SECTION LOSS IS 25% OR
MORE DETERIORATED THEN THE EXISTING REINFORCING SHALL BE
REPLACED AS DIRECTED BY THE ENGINEER.
6. THE CONCRETE ANCHORS REQUIRED SHALL HAVE A MINIMUM PULL OUT OF
5000 LBS. BASED ON 4000 PSI CONCRETE. THE ANCHORS SHALL BE
GALVANIZED AND SHALL BE INCLUDED INSTALLED ACCORDING TO
RECOMMENDATIONS OF THE MANUFACTURER.
7. THE WELDED WIRE FABRIC SHALL BE ASTM A185 AND GALVANIZED AS PER
ASTM A-641. THE WWF WIRES SHALL BE SPACED 3X3 OR 4X4 AND THE WIRES
SHALL HAVE A NOMINAL AREA OF 0.14 TO 0.029 SQUARE INCHES INCLUSIVE,
EXAMPLE “WWF 3X3-W1.4XW2.9”
8. WHERE REINFORCEMENT HAS BEEN EXPOSED AND CLEARANCE AROUND THE
PERIPHERY OF THE EXISTING BAR IS PROVIDED NO SUPPLEMENTAL
REINFORCING IS REQUIRED, EXCEPT WHERE EXISTING REINFORCING
DENSITY AND PATTERN ARE SUCH THAT INDIVIDUAL OPEN SPACES BETWEEN
BARS ARE OF 1.5 SF OR LARGER. FOR THIS CONDITION ½” DIA. CONCRETE
ANCHORS AND WELDED WIRE FABRIC SHALL BE INSTALLED AT THE RATE OF
ONE CONCRETE ANCHOR WITH WWF PER EACH 1.5 SF OF AREA WITHIN EACH
OPEN SPACE.
9. FINISH REPAIR SPALL WITH BASF/MASTER BUILDERS MASTEREMACO N425 OR
APPROVED EQUAL.
10. USE ALL PRODUCTS IN STRICT ACCORDANCE WITH MANUFACTURER’S
RECOMMENDATION INCLUDING ANY AND ALL SURFACE PREPARATION.
EPOXY INJECTION
1. INJECT CRACKS WIDER THAN 0.05 INCH.
2. CLEAN CRACKS WITH OIL-FREE COMPRESSED AIR OR LOW-PRESSURE
WATER TO REMOVE LOOSE PARTICLES OR AS RECOMMENDED BY
MANUFACTURER. CLEAN AREAS TO RECEIVE CAPPING ADHESIVE OF OIL, DIRT,
AND OTHER SUBSTANCES THAT WOULD INTERFERE WITH BOND.
3. PLACE INJECTION PORTS AS RECOMMENDED BY EPOXY MANUFACTURER,
SPACING NO FARTHER APART THAN THICKNESS OF MEMBER BEING INJECTED.
SEAL INJECTION PORTS WITH CAPPING ADHESIVE. USE BASF/MASTER BUILDERS
MASTEREMACO ADH 327 RS OR APPROVED EQUAL FOR INJECTION PORTS.
4. SEAL CRACKS AT EXPOSED SURFACES WITH A RIBBON OF CAPPING
ADHESIVE AT LEAST 1/4 INCH THICK BY 1 INCH WIDER THAN CRACK.
5. INJECT EPOXY ADHESIVE, BEGINNING AT WIDEST PART OF CRACK AND
WORKING TOWARD NARROWER PARTS. INJECT ADHESIVE INTO PORTS TO
REFUSAL, CAPPING ADJACENT PORTS WHEN THEY EXTRUDE EPOXY. CAP
INJECTED PORTS AND INJECT THROUGH ADJACENT PORTS UNTIL CRACK IS
FILLED.
6. AFTER EPOXY ADHESIVE HAS SET, REMOVE INJECTION PORTS AND GRIND
SURFACES SMOOTH.
7. USE BASF/MASTER BUILDERS MASTERINJECT 1380 OR APPROVED EQUAL ON
EPOXY INJECTION REPAIRS.
MARK REVISION DATE
SPECIAL INSPECTION
1. SPECIAL INSPECTION IN ACCORDANCE WITH SECTION 1704 OF THE 2015
INTERNATIONAL BUILDING CODE, AND ICBO MODEL PROGRAM FOR
SPECIAL INSPECTION.
2. THE OWNER WILL EMPLOY AN APPROVED AGENCY TO PERFORM THE
SPECIAL INSPECTION SERVICES.
3. SPECIAL INSPECTION WILL BE PERFORMED IN ACCORDANCE WITH AND IN
ADDITION TO THE INSPECTION AND TESTING REQUIRED BY THE
DRAWINGS AND SPECIFICATIONS.
4. THE FOLLOWING ITEMS ARE INCLUDED IN THE SPECIAL INSPECTION:
CONCRETE: AIR-ENTRAINMENT
SLUMP
COMPRESSIVE STRENGTH TESTING
REINFORCING PLACEMENT
POLYMER MORTAR PLACEMENT VISUAL INSPECTION
SOIL: PAVEMENT SUBGRADE AND FILL COMPACTION.
WATER
WATER
WATER
ELECTRIC
ELECTRIC
ELECTRIC
ELECTRIC
RIM=1049.03
FL=1048.25 4" CLAY SW
RIM=1051.76
FL=1049.13 4" CLAY EAST
FL=1047.22 8" CLAY N-SW
RIM=1051.42
FL=1048.42 15" RCP WEST
FL=1049.03 8" HDPE SE
SUMP=1047.62
RIM=1051.34
FL=1048.00 4" PVC EAST
FL=1049.06 4" CLAY SE
FL=1048.49 4" DIP NE
FL=1047.83 4" DIP NW
RIM=1051.05
UNABLE TO OPEN
RIM=1051.04
UNABLE TO OPEN
RIM=1051.19
FL=1048.65 6" STEEL EAST
FL=1048.60 6" STEEL WEST
FL=1048.78 4" STEEL SOUTH
RIM=1051.07
FL=1049.77 4" STEEL SOUTH
RIM=1052.10
FL=1049.48 4" STEEL SOUTH
SUMP=1048.54 (SILTED)
RIM=1051.35
FL=1049.42 6" DIP NE
FL=1049.17 6" DIP WEST
RIM=1051.64
TUNNEL FLOOR=1044.12
TUNNEL TOP=1050.96
TOP 9" THICK
TUNNEL 48" WIDE BY 73" TALL
RIM=1051.92
TUNNEL FLOOR=1045.54
TUNNEL 48" WIDE BY 71" TALL
END OF TUNNEL 1.75' SE
RIM=1051.69
TUNNEL FLOOR=1044.44
TUNNEL TOP=1051.26
TOP 9" THICK
TUNNEL 48" WIDE BY 73" TALL
RIM=1053.19
FL=1048.13 8" CLAY E-W
CP
CP
CP
CP
CP
CP
G
GG
BM500
F.F.E.=1055.96
AT DOCK
F.F.E.=1051.93
F.F.E.=1049.58
F.F.E.=1049.48
F.F.E.=1052.10
F.F.E.=1051.86
F.F.E.=1051.76
BUILDING F.F.E.=1049.12
CONCRETE
CONCRETE
CONCRETE
CONCRETE
℄ 8" CONCRETE WALL
CONC. STEPS
RAMP
FUEL PUMPS
BREATHER
FACE OF FOUNDATION(TYP.)
FACE OF BUILDING(TYP.)
WINDOW SILL ELEV.=1055.75
WINDOW SILL ELEV.=1053.78
BASKETBALL HOOP
(FOOTING ONLY)
PROBED TOP/EDGE OF TUNNEL
TOP=1050.99+/- SLOT DRAIN
BOTTOM SILTED
F.F.E.=1052.42
B1
B2
B3
B4
G R
A V E L
G R
AV
EL
C O N C R
ETE
RAMP
WW
.0
10+50
11+00 11+00
11+50 11+50
12+00 12+00
12+50 12+50
13+00
13+50
13+50
13+95.56
13+95.56
12+15.19
20+00
12+99.72
13+72.47
20+41.52
20+50
20+50
TUNNEL 1
C/L
TUNNEL 1
C/L
TUNNEL 2
C/L
TUNNEL 2
C/L
S1.02
10+00 10+00
20+95.16
20+95.16
S1.02
S1.03
S1.03
S1.04
S1.04
S1.05
S1.06
S1.07
S3.02
S3.02
S3.01
REMOVAL AND REPLACEMENT
OF 22FT OF STRUCTURAL LID
AND PAVEMENT WITH NEW
HATCH
NEW SUMP PIT FIELD
VERIFY LOW POINT
REMOVAL AND
REPLACEMENT OF 22FT OF
STRUCTURAL LID - NO HATCH
REMOVAL AND REPLACEMENT
OF 22FT OF STRUCTURAL LID
AND PAVEMENT WITH NEW
HATCH
NEW SUMP PIT FIELD
VERIFY LOW POINT
CONSTRUCTION NOTES
1. COORDINATE ALL EQUIPMENT, ENTRY TIMES, AND EXIT TIMES WITH CM/CCF.
2. WHILE WORKING IN YARD, NO OTHER OPENINGS IN THE TUNNEL ARE
PERMITTED TO PREVENT POSSIBLE ESCAPE ROUTES.
3. CONTRACTOR TO TEMPORARILY SEAL ANY HOLES IN TUNNEL AT THE END OF
EACH WORK DAY.
4. CONTRACTOR TO REMOVE ALL TOOLS AND EQUIPMENT AT THE END OF EACH
WORK DAY.
5. COORDINATE ALL WORK AND SECURITY WITH CM/CCF.
6. PROTECT IN PLACE ALL UTILITIES, LIGHT POLES, ETC. AS REQUIRED DURING
CONSTRUCTION.
7. CONTRACTOR TO SOUND TOP OF EXISTING STRUCTURAL SLAB AND VISUALLY
INSPECT FOR DELAMINTIAON, EXPOSED REBAR, OR SPALLING AND REPAIR PER
NOTES PRIOR TO PLACING NEW PAVEMENT
PROJECT NUMBER
DATE
SHEET NO.
SHEET TITLE
400 E COURT AVE.
SUITE 140.
DES MOINES, IOWA 50309
515-243-4477 www.shuck-britson.com
SNYDER & ASSOCIATES, INC.
231 BENNETT AVE.
COUNCIL BLUFFS, IOWA 51503
P: 712-322-3202 www.snyder-associates.com
Project Engineer
Mechanical, Electrical and Plumbing Engineer
ALVINE ENGINEERING
400 E. COURT AVE
SUITE 130
DES MOINES, IA 50309
www.alvine.com
C
U s e rs
\d tr ip p \D o c u m e n ts
\1 .0
.1
T U
N N
E L
(R d tr ip p s h u c k -b ri ts o n .c o m
.r v t
/9 /2
:4
:1
P
M
D O
C C
C F
T U
N N
E L R
E P
A
IR
R
E P
L A
C E
M E
N T
M A
IN
B
L D
G
S W
W
IN
G
10/10/2025
125.0278.10
S1.01
N th
S t, C la ri n d a
IA
TUNNEL PLAN
100% CONSTRUCTION DOCUMENTS
IO
W
A D
E P
A R
T M
E N
T O
F A
D M
IN
IS
T R
A T
IV
E
S E
R V
IC
E
S
D A
S
N
1" = 20'-0"
1 TUNNEL PLAN
MARK REVISION DATE
. 0
11+00
11+00
TUNNEL 1
C/L
TUNNEL 1
C/L
B-1 B-1
A-1A-1
10+00
10+00
10+10 10+20 10+30 10+40 10+60 10+70 10+80 10+90
EXISTING BUILDING
" 2 /S1.02
3 /S1.02
S1.02
S3.04
TUNNEL LID AND CONCRETE
PAVEMENT TOPPING SLAB TO
REMAIN PROTECTED IN PLACE
WHERE SURROUNDED BY GRASS -
TYP REFER TO CIVIL
10+50
10+50
11+00
11+00
TUNNEL 1
C/L
TUNNEL 1
C/L
B-1 B-1
A-1A-1
10+00
10+00
10+10 10+20 10+30 10+40 10+60 10+70 10+80 10+90
EXISTING BUILDING
2 /S1.02
3 /S1.02
S1.02
CROSSING BEAM
EXISTING 16" DIA. PIPE
S3.01
S2.03
10+50
10+50
11+00
11+00
10+00
10+00 10+10 10+20 10+30 10+40 10+60 10+70 10+80 10+90
EXISTING BUILDING WALL
S1.02
1044.44
EXISTING 2' WIDE X 3'
TALL CONCRETE BEAM
EXISTING 16" DIA. PIPE
10+50
10+50
11+00
11+00
10+00
10+0010+1010+2010+3010+4010+6010+7010+8010+90
EXISTING BUILDING WALL5
S1.02
NO REPAIR REQUIRED HERE
REPAIR KEY
EXISTING CRACK - PREPARE AND
REPAIR CONCRETE CRACK (SEE
DETAILS)
EXISTING SPALL - PREPARE AND
REPAIR CONCRETE SPALL (SEE
DETAILS)
EXISTING SCALING AND
HONEYCOMB - PREPARE AND REPAIR
CONCRETE CONSOLIDATION OR
SCALING (SEE DETAILS)
EXISTING CONSTRUCTION JOINT
PROVIDE CRACK REPAIRS WHERE
CRACKS EXCEED 0.05" WIDTH (SEE
DETAILS)
NOTES:
REMOVE AND REPLACE ALL EXISTING PIPE
SUPPORTS.
CLEAN THE FLOOR OF ALL DIRT, DEBRIS, TRASH,
ETC.
REMOVE ALL ABANDONED UTILITIES AND
SUPPORTS OR ANY OTHER ITEMS WITHIN THE
TUNNEL THAT ARE NO LONGER BEING USED- TYP.
ALL CONCRETE REPAIRS TO BE MARKED AND
APPROVED FOR QUANTITY BY CM/CCF AND
ENGINEER PRIOR TO PERFORMING REPAIRS.
CONCRETE ISSUES SHOWN ON THE DRAWINGS
DO NOT NECESSARILY CORRELATE TO REPAIRS
THAT WILL BE MADE BUT TO OBSERVATIONS
MADE ON EXISTING CONCRETE DETERIORATION
TUNNEL 1
C/L
B-1 A-1
(+/-) 4' - 0"
(+/-) 2' - 0" (+/-) 2' - 0"
(+/-) 8"(+/-) 8"
SIDEWALK / PAVEMENT / GRADE
(SEE CIVIL)
PROJECT NUMBER
DATE
SHEET NO.
SHEET TITLE
400 E COURT AVE.
SUITE 140.
DES MOINES, IOWA 50309
515-243-4477 www.shuck-britson.com
SNYDER & ASSOCIATES, INC.
231 BENNETT AVE.
COUNCIL BLUFFS, IOWA 51503
P: 712-322-3202 www.snyder-associates.com
Project Engineer
Mechanical, Electrical and Plumbing Engineer
ALVINE ENGINEERING
400 E. COURT AVE
SUITE 130
DES MOINES, IA 50309
www.alvine.com
C
U s e rs
\d tr ip p \D o c u m e n ts
\1 .0
.1
T U
N N
E L
(R d tr ip p s h u c k -b ri ts o n .c o m
.r v t
/9 /2
:4
:1
P
M
D O
C C
C F
T U
N N
E L R
E P
A
IR
R
E P
L A
C E
M E
N T
M A
IN
B
L D
G
S W
W
IN
G
10/10/2025
125.0278.10
S1.02
N th
S t, C la ri n d a
IA
TUNNEL PLANS AND ELEVATIONS
100% CONSTRUCTION DOCUMENTS
IO
W
A D
E P
A R
T M
E N
T O
F A
D M
IN
IS
T R
A T
IV
E
S E
R V
IC
E
S
D A
S
3/16" = 1'-0"
4 TUNNEL 1 - LID 10+00 TO 11+00
3/16" = 1'-0"
1 TUNNEL 1 - FLOOR 10+00 TO 11+00
3/16" = 1'-0"
2 TUNNEL 1 - WEST WALL 10+00 TO 11+00
3/16" = 1'-0"
3 TUNNEL 1 - EAST WALL 10+00 TO 11+00
1/2" = 1'-0"
5 TUNNEL 1 - 10+00 TO 11+00 (LOOKING NE)
N N
11+00
11+00
11+50
11+50
12+00
12+00
TUNNEL 1
C/L
TUNNEL 1
C/L
B-1 B-1
A-1A-1
11+20 11+30 11+40 11+60 11+70 11+80 11+9011+10
2 /S1.03
3 /S1.03
4' - 6"4' - 0"1' - 6"
OPEN
EXISTING 4" DIA. PIPE
S3.04
S3.03
22' - 0"
HATCH REMOVAL AND
REPLACEMENT
LID REMOVAL AND
REPLACEMENT
TUNNEL LID AND CONCRETE
PAVEMENT TOPPING SLAB TO
REMAIN PROTECTED IN PLACE
WHERE SURROUNDED BY
GRASS - TYP REFER TO CIVIL
S1.03
S2.02
S2.02
S2.02
S2.02 2
S2.02
TUNNEL LID AND CONCRETE
PAVEMENT TOPPING SLAB TO BE
REMOVED AND REPLACED ONLY AS
NEEDED FOR THE CONSTRUCTION
ACCESS REMOVALS BACK TO THE
NEAREST SIDEWALK PANEL POINT
OR AS NEEDED FOR DAMAGE
RESULTING FROM CONSTRUCTION
MIN. 2' - 0"
S2.02
LL7x4x3/8 L.L.H. x 24'0"
LL7x4x3/8 L.L.H. x 24'0"
CURRENT WALL TEMPORARY SHORING IS DESIGNED FOR 400 LBS /FT.
LATERAL FORCE TO HOLD BACK THE SOIL PRESSURES ON THE
UNSUPPORTED WALL IN ITS TEMPORARY CONDITION. NO HEAVY
EQUIPMENT EXCEEDING 100 PSF SHALL BE ALLOWED WITHIN 6FT OF THE
FACE OF THE TEMPORARY TUNNEL LID EXCAVATION WHILE THE
STRUCTURAL SLAB IS REMOVED UNTIL AFTER THE NEW SLAB IS POURED
AND CURED.
1' - 0"
1' - 0"
11+00
11+00
11+50
11+50
12+00
12+00
TUNNEL 1
C/L
TUNNEL 1
C/L
B-1 B-1
A-1A-1
S1.03
11+20 11+30 11+40 11+60 11+70 11+80 11+9011+10
2 /S1.03
3 /S1.03
EXISTING 4" DIA. PIPE
S3.04
EXISTING 6" DIA. PIPE
14" X14" CONC. BEAM
S2.03
11+00
11+00 11+50 12+00
1052.02
1044.44
S1.03
11+20 11+30 11+40 11+60 11+70 11+80 11+9011+10
11" 5' - 0" 4' - 1"
1051.26 1051.69
11+00
11+0011+5012+00
S1.03
11+2011+3011+4011+6011+7011+8011+90 11+10
11"5' - 0"4' - 1"
REPAIR KEY
EXISTING CRACK - PREPARE AND
REPAIR CONCRETE CRACK (SEE
DETAILS)
EXISTING SPALL - PREPARE AND
REPAIR CONCRETE SPALL (SEE
DETAILS)
EXISTING SCALING AND
HONEYCOMB - PREPARE AND REPAIR
CONCRETE CONSOLIDATION OR
SCALING (SEE DETAILS)
EXISTING CONSTRUCTION JOINT
PROVIDE CRACK REPAIRS WHERE
CRACKS EXCEED 0.05" WIDTH (SEE
DETAILS)
NOTES:
REMOVE AND REPLACE ALL EXISTING PIPE
SUPPORTS.
CLEAN THE FLOOR OF ALL DIRT, DEBRIS, TRASH,
ETC.
REMOVE ALL ABANDONED UTILITIES AND
SUPPORTS OR ANY OTHER ITEMS WITHIN THE
TUNNEL THAT ARE NO LONGER BEING USED- TYP.
ALL CONCRETE REPAIRS TO BE MARKED AND
APPROVED FOR QUANTITY BY CM/CCF AND
ENGINEER PRIOR TO PERFORMING REPAIRS.
CONCRETE ISSUES SHOWN ON THE DRAWINGS
DO NOT NECESSARILY CORRELATE TO REPAIRS
THAT WILL BE MADE BUT TO OBSERVATIONS
MADE ON EXISTING CONCRETE DETERIORATION
TUNNEL 1
C/L
B-1 A-1
(+/-) 4' - 0"
(+/-) 2' - 0" (+/-) 2' - 0" (+/-) 8"
(+/-) 8"
SIDEWALK / PAVEMENT / GRADE
(SEE CIVIL)
PROJECT NUMBER
DATE
SHEET NO.
SHEET TITLE
400 E COURT AVE.
SUITE 140.
DES MOINES, IOWA 50309
515-243-4477 www.shuck-britson.com
SNYDER & ASSOCIATES, INC.
231 BENNETT AVE.
COUNCIL BLUFFS, IOWA 51503
P: 712-322-3202 www.snyder-associates.com
Project Engineer
Mechanical, Electrical and Plumbing Engineer
ALVINE ENGINEERING
400 E. COURT AVE
SUITE 130
DES MOINES, IA 50309
www.alvine.com
C
U s e rs
\d tr ip p \D o c u m e n ts
\1 .0
.1
T U
N N
E L
(R d tr ip p s h u c k -b ri ts o n .c o m
.r v t
/9 /2
:4
:1
P
M
D O
C C
C F
T U
N N
E L R
E P
A
IR
R
E P
L A
C E
M E
N T
M A
IN
B
L D
G
S W
W
IN
G
10/10/2025
125.0278.10
S1.03
N th
S t, C la ri n d a
IA
TUNNEL PLANS AND ELEVATIONS
100% CONSTRUCTION DOCUMENTS
IO
W
A D
E P
A R
T M
E N
T O
F A
D M
IN
IS
T R
A T
IV
E
S E
R V
IC
E
S
D A
S
3/16" = 1'-0"
4 TUNNEL 1 - LID 11+00 TO 12+00
3/16" = 1'-0"
1 TUNNEL 1 - FLOOR 11+00 TO 12+00
3/16" = 1'-0"
2 TUNNEL 1 - WEST WALL 11+00 TO 12+00
3/16" = 1'-0"
3 TUNNEL 1 - EAST WALL 11+00 TO 12+00
1/2" = 1'-0"
5 TUNNEL 1 - 11+00 TO 12+00 (LOOKING NE)
N
12+00
12+00
12+50
12+50
13+00
13+00
12+15.19
20+00
12+99.72
TUNNEL 1
C/L
TUNNEL 1
C/L
B-1
B-1
A-1
A-1
TUNNEL 2
C/L
TUNNEL 2
C/L
B-2 A-2
S1.04
12+20 12+30 12+40 12+60 12+70 12+80 12+9012+10
2 /S1.04
3 /S1.04
EX.4" DIA. PIPE
EX.4" DIA. PIPE
EX.12" DIA. PIPE
S2.02
SIM.
12+00
12+00
12+50
12+50
13+00
13+00
12+15.19
20+00
12+99.72
TUNNEL 1
C/L
TUNNEL 1
C/L
B-1
B-1
A-1
A-1
TUNNEL 2
C/L
B-2 A-2
2 /S1.04
3 /S1.04
S1.04
12+20 12+30 12+40 12+60 12+70 12+80 12+9012+10
EX.4" DIA. PIPE
EX.4" DIA. PIPE
EX.12" DIA. PIPE
NEW SUMP PIT WITH STEEL
GRATING - FIELD VERIFY LOW
POINT - POUR TOP OF NEW PIT AND
SLAB SHORT OF EXISTING TUNNEL
SLAB BY THICKNESS OF NEW
GRATING
S2.03
PROVIDE GUTTER TROUGH
TO SUMP FROM EXISTING
GUTTERS - TYP.
S2.03
12+00 12+5012+15.19
S1.04
12+20 12+30 12+40 12+60 12+70 12+80 12+9012+10
EX. PATCHEX. 4" DIA. PIPE
EX. 12" DIA. PIPE
EX. 4" DIA. PIPE
EX. 4" DIA. PIPE PATCH
S3.03
S3.02
12+0012+50 12+15.19
S1.04
12+2012+3012+4012+6012+7012+8012+90 12+10
EX. PATCH EX. 4" DIA. PIPE PATCH
S3.03
REPAIR KEY
EXISTING CRACK - PREPARE AND
REPAIR CONCRETE CRACK (SEE
DETAILS)
EXISTING SPALL - PREPARE AND
REPAIR CONCRETE SPALL (SEE
DETAILS)
EXISTING SCALING AND
HONEYCOMB - PREPARE AND REPAIR
CONCRETE CONSOLIDATION OR
SCALING (SEE DETAILS)
EXISTING CONSTRUCTION JOINT
PROVIDE CRACK REPAIRS WHERE
CRACKS EXCEED 0.05" WIDTH (SEE
DETAILS)
NOTES:
REMOVE AND REPLACE ALL EXISTING PIPE
SUPPORTS.
CLEAN THE FLOOR OF ALL DIRT, DEBRIS, TRASH,
ETC.
REMOVE ALL ABANDONED UTILITIES AND
SUPPORTS OR ANY OTHER ITEMS WITHIN THE
TUNNEL THAT ARE NO LONGER BEING USED- TYP.
ALL CONCRETE REPAIRS TO BE MARKED AND
APPROVED FOR QUANTITY BY CM/CCF AND
ENGINEER PRIOR TO PERFORMING REPAIRS.
CONCRETE ISSUES SHOWN ON THE DRAWINGS
DO NOT NECESSARILY CORRELATE TO REPAIRS
THAT WILL BE MADE BUT TO OBSERVATIONS
MADE ON EXISTING CONCRETE DETERIORATION
TUNNEL 1
C/L
B-1 A-1
(+/-) 4' - 0"
(+/-) 2' - 0"
(+/-) 2' - 0"
(+/-) 8" (+/-) 8"
SIDEWALK / PAVEMENT / GRADE
(SEE CIVIL)
PROJECT NUMBER
DATE
SHEET NO.
SHEET TITLE
400 E COURT AVE.
SUITE 140.
DES MOINES, IOWA 50309
515-243-4477 www.shuck-britson.com
SNYDER & ASSOCIATES, INC.
231 BENNETT AVE.
COUNCIL BLUFFS, IOWA 51503
P: 712-322-3202 www.snyder-associates.com
Project Engineer
Mechanical, Electrical and Plumbing Engineer
ALVINE ENGINEERING
400 E. COURT AVE
SUITE 130
DES MOINES, IA 50309
www.alvine.com
C
U s e rs
\d tr ip p \D o c u m e n ts
\1 .0
.1
T U
N N
E L
(R d tr ip p s h u c k -b ri ts o n .c o m
.r v t
/9 /2
:4
:1
P
M
D O
C C
C F
T U
N N
E L R
E P
A
IR
R
E P
L A
C E
M E
N T
M A
IN
B
L D
G
S W
W
IN
G
10/10/2025
125.0278.10
S1.04
N th
S t, C la ri n d a
IA
TUNNEL PLANS AND ELEVATIONS
100% CONSTRUCTION DOCUMENTS
IO
W
A D
E P
A R
T M
E N
T O
F A
D M
IN
IS
T R
A T
IV
E
S E
R V
IC
E
S
D A
S
3/16" = 1'-0"
4 TUNNEL 1 - LID 12+00 TO 13+00
3/16" = 1'-0"
1 TUNNEL 1 - FLOOR 12+00 TO 13+00
3/16" = 1'-0"
2 TUNNEL 1 - WEST WALL 12+00 TO 13+00
3/16" = 1'-0"
3 TUNNEL 1 - EAST WALL 12+00 TO 13+00
1/2" = 1'-0"
5 TUNNEL 1 - 11+00 TO 12+00 (LOOKING NE)
N
1051.0
1052.0
13+00
13+00
13+50
13+50
13+95.56 13+95.56
12+99.72
13+72.47
TUNNEL 1
C/L
TUNNEL 1
C/L
B-1
B-1 A-1
A-1
13+4013+3013+2013+10 13+60
13+70
13+90 13+90
13+80 13+80
2 /S1.05
5 /S1.05
/S
.0
/S
.0
S1.05
EXISTING BUILDING
REPAIR JOINT AT
BUILDING
NEW SUMP PIT WITH STEEL GRATING -
FIELD VERIFY LOW POINT - POUR TOP
OF NEW PIT AND SLAB SHORT OF
EXISTING TUNNEL SLAB BY
THICKNESS OF NEW GRATING
' - 0
S2.03
PROVIDE GUTTER TROUGH
TO SUMP FROM EXISTING
GUTTERS - TYP.
S2.03
S2.03
13+00
13+00
13+50
13+5013+4013+3013+2013+10 13+60 13+70
S1.05
EX. 4" DIA. PIPE
GROUTED
13+95.5613+9013+80
EXISTING BUILDING
REPAIR JOINT AT BUILDING
13+0013+50 13+40 13+30 13+20 13+1013+6013+70
S1.05
EXISTING PIPE UTILITIES TO BLDG.
S3.02
13+95.56 13+90 13+80
EXISTING BUILDING
REPAIR JOINT
AT BUILDING
TUNNEL 1
C/LB-1 A-1
SIDEWALK / PAVEMENT / GRADE
(SEE CIVIL)
(+/-) 4' - 0"
(+/-) 8" (+/-) 8"
(+/-) 2' - 0" (+/-) 2' - 0"
13+00
13+00
13+50
13+50
13+95.56 13+95.56
12+99.72
13+72.47
TUNNEL 1
C/L
TUNNEL 1
C/L
B-1
B-1 A-1
A-1
13+4013+3013+2013+10 13+60
13+70
13+90 13+90
13+80
2 /S1.05
5 /S1.05
/S
.0
/S
.0
S1.05
EXISTING BUILDING
OPEN
PIPE SUPPORT
REPAIR BLDG. JT
CONSTRUCTION JT.
CRACK IN LID
S3.02
S3.01
S3.01
S3.01
22' - 0"
HATCH REMOVAL AND
REPLACEMENT
LID REMOVAL AND
REPLACEMENT
S2.02
SIM.
S2.02
S2.02
S2.02
S2.02
MIN. 2' - 0"
S2.02
LL7x4x3/8 L.L.H. x 24'0"
LL7x4x3/8 L.L.H. x 24'0"
CURRENT WALL TEMPORARY SHORING IS DESIGNED FOR 400 LBS /FT.
LATERAL FORCE TO HOLD BACK THE SOIL PRESSURES ON THE
UNSUPPORTED WALL IN ITS TEMPORARY CONDITION. NO HEAVY
EQUIPMENT EXCEEDING 100 PSF SHALL BE ALLOWED WITHIN 6FT OF THE
FACE OF THE TEMPORARY TUNNEL LID EXCAVATION WHILE THE
STRUCTURAL SLAB IS REMOVED UNTIL AFTER THE NEW SLAB IS POURED
AND CURED.
1' - 0"
1' - 0"
REPAIR KEY
EXISTING CRACK - PREPARE AND
REPAIR CONCRETE CRACK (SEE
DETAILS)
EXISTING SPALL - PREPARE AND
REPAIR CONCRETE SPALL (SEE
DETAILS)
EXISTING SCALING AND
HONEYCOMB - PREPARE AND REPAIR
CONCRETE CONSOLIDATION OR
SCALING (SEE DETAILS)
EXISTING CONSTRUCTION JOINT
PROVIDE CRACK REPAIRS WHERE
CRACKS EXCEED 0.05" WIDTH (SEE
DETAILS)
NOTES:
REMOVE AND REPLACE ALL EXISTING PIPE
SUPPORTS.
CLEAN THE FLOOR OF ALL DIRT, DEBRIS, TRASH,
ETC.
REMOVE ALL ABANDONED UTILITIES AND
SUPPORTS OR ANY OTHER ITEMS WITHIN THE
TUNNEL THAT ARE NO LONGER BEING USED- TYP.
ALL CONCRETE REPAIRS TO BE MARKED AND
APPROVED FOR QUANTITY BY CM/CCF AND
ENGINEER PRIOR TO PERFORMING REPAIRS.
CONCRETE ISSUES SHOWN ON THE DRAWINGS
DO NOT NECESSARILY CORRELATE TO REPAIRS
THAT WILL BE MADE BUT TO OBSERVATIONS
MADE ON EXISTING CONCRETE DETERIORATION
PROJECT NUMBER
DATE
SHEET NO.
SHEET TITLE
400 E COURT AVE.
SUITE 140.
DES MOINES, IOWA 50309
515-243-4477 www.shuck-britson.com
SNYDER & ASSOCIATES, INC.
231 BENNETT AVE.
COUNCIL BLUFFS, IOWA 51503
P: 712-322-3202 www.snyder-associates.com
Project Engineer
Mechanical, Electrical and Plumbing Engineer
ALVINE ENGINEERING
400…