RFB944400-01 - Project Drawings.pdf

PDF 10 MB Posted

Attached to
DOC Clarinda Correctional Facility Tunnel Repair
Solicitation number
005-RFBCON-2227-2026
Issued by
Polk County, Iowa

About this file

This is a comprehensive set of construction documents for a tunnel repair and replacement project for the Iowa Department of Administrative Services (DAS) located at the Clarinda Correctional Facility in Clarinda, Iowa. The project involves repairing and replacing tunnel infrastructure in the main building's southwest wing, specifically focusing on two tunnel sections with project number 9444.00 and bid number RFP944400-01. The documents, dated October 10, 2025, include detailed structural, civil, mechanical, electrical, and plumbing plans for demolition and reconstruction of tunnel systems spanning approximately 600 linear feet across two tunnel segments.

The project involves complete removal and replacement of tunnel components, including concrete lid, pavement, piping systems (chilled water, steam, hot water), electrical conduits, and lighting. Key elements include installing new pipe supports, replacing steam traps and pressure reducing stations, adding sump pumps, and implementing new electrical infrastructure. The construction documents specify Schedule 80 CPVC piping, structural steel supports, and careful coordination between mechanical, electrical, plumbing, and structural contractors. The work requires precise removal of existing systems, protection of adjacent infrastructure, and installation of new systems with minimal disruption to the facility's operations. Structural repairs, concrete restoration, and utility system replacements are comprehensively detailed across multiple plan sheets and technical specifications.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PAGE COUNTY

PAGE COUNTY, IOWA

PROJECT LOCATION

PROJECT NUMBER

DATE

SHEET NO.

SHEET TITLE

400 E COURT AVE.

SUITE 140.

DES MOINES, IOWA 50309

515-243-4477 www.shuck-britson.com

SNYDER & ASSOCIATES, INC.

231 BENNETT AVE.

COUNCIL BLUFFS, IOWA 51503

P: 712-322-3202 www.snyder-associates.com

Project Engineer

Mechanical, Electrical and Plumbing Engineer

ALVINE ENGINEERING

400 E. COURT AVE

SUITE 130

DES MOINES, IA 50309

www.alvine.com

C

U s e rs

\d tr ip p \D o c u m e n ts

\1 .0

.1

T U

N N

E L

(R d tr ip p s h u c k -b ri ts o n .c o m

.r v t

/9 /2

:4

:1

P

M

D O

C C

C F

T U

N N

E L R

E P

A

IR

R

E P

L A

C E

M E

N T

M A

IN

B

L D

G

S W

W

IN

G

10/10/2025

125.0278.10

COVER

N th

S t, C la ri n d a

IA

TITLE SHEET

100% CONSTRUCTION DOCUMENTS

IO

W

A D

E P

A R

T M

E N

T O

F A

D M

IN

IS

T R

A T

IV

E

S E

R V

IC

E

S

D A

S

STRUCTURAL DRAWINGS

S0.00 NOTES

S1.01 TUNNEL PLAN

S1.02 TUNNEL PLANS AND ELEVATIONS

S1.03 TUNNEL PLANS AND ELEVATIONS

S1.04 TUNNEL PLANS AND ELEVATIONS

S1.05 TUNNEL PLANS AND ELEVATIONS

S1.06 TUNNEL PLANS AND ELEVATIONS

S1.07 TUNNEL PLANS AND ELEVATIONS

S2.01 DETAILS

S2.02 DETAILS

S2.03 DETAILS

S3.01 PHOTOS

S3.02 PHOTOS

S3.03 PHOTOS

S3.04 PHOTOS

100% CONSTRUCTION DOCUMENTS

FOR

IOWA DEPARTMENT OF

ADMINISTRATIVE SERVICES (DAS)

DOC CCF TUNNEL REPAIR / REPLACEMENT MAIN

BLDG. SW WING

PAGE COUNTY, IOWA

PROJECT INFORMATION

1 VICINITY MAP

CIVIL DRAWINGS

C100 REMOVAL PLAN

C200 SITE PLAN

MARK REVISION DATE

MECHANICAL, ELECTRICAL & PLUMBING DRAWINGS

MEP0.00 MECHANICAL ELECTRICAL & PLUMBING

SYMBOLS AND ABBREVIATIONS

MD1.02 TUNNEL PLANS AND ELEVATIONS DEMO

MD1.03 TUNNEL PLANS AND ELEVATIONS DEMO

MD1.04 TUNNEL PLANS AND ELEVATIONS DEMO

MD1.05 TUNNEL PLANS AND ELEVATIONS DEMO

MD1.06 TUNNEL PLANS AND ELEVATIONS DEMO

PED1.02 TUNNEL PLANS AND ELEVATIONS -

PLUMBING & ELECTRICAL DEMO

PED1.03 TUNNEL PLANS AND ELEVATIONS DEMO

PED1.04 TUNNEL PLANS AND ELEVATIONS DEMO

PED1.05 TUNNEL PLANS AND ELEVATIONS DEMO

PED1.06 TUNNEL PLANS AND ELEVATIONS DEMO

M1.02 TUNNEL PLANS AND ELEVATIONS

M1.03 TUNNEL PLANS AND ELEVATIONS

M1.04 TUNNEL PLANS AND ELEVATIONS

M1.05 TUNNEL PLANS AND ELEVATIONS

M1.06 TUNNEL PLANS AND ELEVATIONS

M3.01 PICTURES

M3.02 PICTURES

PE1.02 TUNNEL PLANS AND ELEVATIONS

PE1.03 TUNNEL PLANS AND ELEVATIONS

PE1.04 TUNNEL PLANS AND ELEVATIONS

PE1.05 TUNNEL PLANS AND ELEVATIONS

PE1.06 TUNNEL PLANS AND ELEVATIONS

MEP4.00 MECHANICAL ELECTRICAL & PLUMBING

SCHEDULES

PROJECT ADDRESS:

2000 N 16TH ST,

CLARINDA, IA 51632

DAS PROJECT #: 9444.00

RFB#: RFP944400-01

L

AWOI

RI

C E N S E D

PR

OF

ESS IONAL

EN

G

IN

E

ETYLER R.

VONWEIHE

P25351

I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS

PREPARED BY ME OR UNDER MY DIRECT PERSONAL

SUPERVISION AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF IOWA.

SIGNATURE: ____________________________________

NAME:

IOWA REG. NO: EXPIRATION DATE:

PAGES OR SHEETS COVERED BY THIS SEAL:

TYLER R. VONWEIHE. P.E.

P25351 12/31/2026

LISTED AS "STRUCTURAL"

L

AWOI

RI

C E N S E D

PR

OF

ESS IONAL

EN

G

IN

E

EELIZABETH

HUNTER

P18178

I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS

PREPARED BY ME OR UNDER MY DIRECT PERSONAL

SUPERVISION AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF IOWA.

SIGNATURE: ____________________________________

NAME:

IOWA REG. NO: EXPIRATION DATE:

PAGES OR SHEETS COVERED BY THIS SEAL:

ELIZABETH A. HUNTER, P.E.

P18178 12/31/2026

LISTED AS "CIVIL"

L

AWOI

RI

C E N S E D

PR

OF

ESS IONAL

EN

G

IN

E

EJASON P.

JONES

P22600

I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS

PREPARED BY ME OR UNDER MY DIRECT PERSONAL

SUPERVISION AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF IOWA.

SIGNATURE: ____________________________________

NAME:

IOWA REG. NO: EXPIRATION DATE:

PAGES OR SHEETS COVERED BY THIS SEAL:

JASON P. JONES, P.E.

P22600 12/31/2026

LISTED AS "M.E.P." (MECHANICAL AND PLUMBING)

L

AWOI

RI

C E N S E D

PR

OF

ESS IONAL

EN

G

IN

E

ENICHOLAS A.

ANDERA

P22839

I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS

PREPARED BY ME OR UNDER MY DIRECT PERSONAL

SUPERVISION AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF IOWA.

SIGNATURE: ____________________________________

NAME:

IOWA REG. NO: EXPIRATION DATE:

PAGES OR SHEETS COVERED BY THIS SEAL:

NICHOLAS A. ANDERA, P.E.

P22839 12/31/2026

LISTED AS "M.E.P." (ELECTRICAL)

L

AWOI

RI

C E N S E D

PR

OF

ESS IONAL

EN

G

IN

E

ETYLER R.

VONWEIHE

P25351

I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS

PREPARED BY ME OR UNDER MY DIRECT PERSONAL

SUPERVISION AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF IOWA.

SIGNATURE: ____________________________________

NAME:

IOWA REG. NO: EXPIRATION DATE:

PAGES OR SHEETS COVERED BY THIS SEAL:

TYLER R. VONWEIHE. P.E.

P25351 12/31/2026

LISTED AS "STRUCTURAL"

L

AWOI

RI

C E N S E D

PR

OF

ESS IONAL

EN

G

IN

E

EELIZABETH

HUNTER

P18178

I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS

PREPARED BY ME OR UNDER MY DIRECT PERSONAL

SUPERVISION AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF IOWA.

SIGNATURE: ____________________________________

NAME:

IOWA REG. NO: EXPIRATION DATE:

PAGES OR SHEETS COVERED BY THIS SEAL:

ELIZABETH A. HUNTER, P.E.

P18178 12/31/2026

LISTED AS "CIVIL"

L

AWOI

RI

C E N S E D

PR

OF

ESS IONAL

EN

G

IN

E

EJASON P.

JONES

P22600

I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS

PREPARED BY ME OR UNDER MY DIRECT PERSONAL

SUPERVISION AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF IOWA.

SIGNATURE: ____________________________________

NAME:

IOWA REG. NO: EXPIRATION DATE:

PAGES OR SHEETS COVERED BY THIS SEAL:

JASON P. JONES, P.E.

P22600 12/31/2026

LISTED AS "M.E.P." (MECHANICAL AND PLUMBING)

L

AWOI

RI

C E N S E D

PR

OF

ESS IONAL

EN

G

IN

E

ENICHOLAS A.

ANDERA

P22839

I HEREBY CERTIFY THIS ENGINEERING DOCUMENT WAS

PREPARED BY ME OR UNDER MY DIRECT PERSONAL

SUPERVISION AND THAT I AM A DULY LICENSED

PROFESSIONAL ENGINEER UNDER THE LAWS OF THE

STATE OF IOWA.

SIGNATURE: ____________________________________

NAME:

IOWA REG. NO: EXPIRATION DATE:

PAGES OR SHEETS COVERED BY THIS SEAL:

NICHOLAS A. ANDERA, P.E.

P22839 12/31/2026

LISTED AS "M.E.P." (ELECTRICAL)

8/8/20258/8/20258/8/2025 8/8/202510/10/2025 10/10/2025 10/10/202510/10/2025

BM500

F.F.E.=1055.96

AT DOCK

F.F.E.=1051.93

F.F.E.=1049.58

F.F.E.=1049.48

F.F.E.=1052.10

F.F.E.=1051.86

F.F.E.=1051.76

BUILDING F.F.E.=1049.12

CONCRETE

CONCRETE

CONCRETE

CONCRETE

CONCRETE

℄ 8" CONCRETE WALL

CONC. STEPS

RIM=1049.03

FL=1048.25 4" CLAY SW

RIM=1051.76

FL=1049.13 4" CLAY EAST

FL=1047.22 8" CLAY N-SW

RIM=1051.42

FL=1048.42 15" RCP WEST

FL=1049.03 8" HDPE SE

SUMP=1047.62

RIM=1051.34

FL=1048.00 4" PVC EAST

FL=1049.06 4" CLAY SE

FL=1048.49 4" DIP NE

FL=1047.83 4" DIP NW

RIM=1051.05

UNABLE TO OPEN

RIM=1051.04

UNABLE TO OPEN

RAMP

RIM=1051.19

FL=1048.65 6" STEEL EAST

FL=1048.60 6" STEEL WEST

FL=1048.78 4" STEEL SOUTH

FUEL PUMPS

BREATHER

RIM=1051.07

FL=1049.77 4" STEEL SOUTH

FACE OF FOUNDATION(TYP.)

FACE OF BUILDING(TYP.)

RIM=1052.10

FL=1049.48 4" STEEL SOUTH

SUMP=1048.54 (SILTED)

WINDOW SILL ELEV.=1055.75

WINDOW SILL ELEV.=1053.78

BASKETBALL HOOP

(FOOTING ONLY)

PROBED TOP/EDGE OF TUNNEL

TOP=1050.99+/- SLOT DRAIN

BOTTOM SILTED

RIM=1051.35

FL=1049.42 6" DIP NE

FL=1049.17 6" DIP WEST

RIM=1051.64

TUNNEL FLOOR=1044.12

TUNNEL TOP=1050.96

TOP 9" THICK

TUNNEL 48" WIDE BY 73" TALL

RIM=1051.92

TUNNEL FLOOR=1045.54

TUNNEL 48" WIDE BY 71" TALL

END OF TUNNEL 1.75' SE

RIM=1051.69

TUNNEL FLOOR=1044.44

TUNNEL TOP=1051.26

TOP 9" THICK

TUNNEL 48" WIDE BY 73" TALL

F.F.E.=1052.42

B1

B2

B3

B4

GRAVEL

GRAVEL

CONCRETE

RIM=1053.19

FL=1048.13 8" CLAY E-W

RAMP

+9

5.5

13+72.47

12+99.72

+9

5.1

12+15.19

+0

V:

\P ro je ct s\

\1

.0

8.

\C

AD

D \1

_C

_D

EM

O .d w g

R

AC

H

EL

D

IC

KE

Y, R

EM

O

VA

L

PL

AN

, 2

5/

/0

9, :1

PM

, A

N

SI

F U

LL

B

LE

ED

D (3

4.

X

2.

IN

C

H

ES

FEET

0 20

PROJECT NUMBER

DATE

SHEET NO.

SHEET TITLE

MARK REVISION DATE

400 E COURT AVE.

SUITE 140.

DES MOINES, IOWA 50309

515-243-4477 www.shuck-britson.com

SNYDER & ASSOCIATES, INC.

2727 S.W. SNYDER BLVD.

ANKENY, IOWA 50023

P: 515-964-2020 www.snyder-associates.com

Project Engineer

100% CONSTRUCTION DOCUMENTS

10/10/2025

125.0278

C100

D O

C C

C F

TU

N

N

EL

R

EP

AI

R

/R

EP

LA

C

EM

EN

T M

AI

N

B

LD

G . S

W W

IN

G

REMOVAL PLAN

C

LA

R

IN

D A, IO

W

A

IO

A D

EP

AR

TM

EN

T O

F

AD

M

IN

IS

TR

AT

IV

E

SE

R

VI

C

ES

(D

AS

REMOVAL NOTES

1. ITEMS TO REMAIN, PROTECT THE FOLLOWING. ANY DAMAGE DONE TO

ITEMS NOT PLANNED FOR REMOVAL IS THE RESPONSIBILITY OF THE

CONTRACTOR AND SHALL BE FIXED OR REPAIRED AT NO COST TO THE

OWNER.

A. EXISTING UTILITIES. CONTRACTOR IS RESPONSIBLE FOR

OBTAINING LOCATES PRIOR TO CONSTRUCTION.

B. TUNNEL WALLS & TOP WHERE NOT REMOVING.

C. FUEL PUMPS & TANKS.

D. EXISTING GRASSED AREA AROUND FUEL PUMPS.

E. EXISTING TREES.

F. CONCRETE STEPS AND WALL.

G. EXISTING BUILDINGS.

H. RECESSED DOCK AREA, SLABS, WALL IN PLACE & INLET.

I. ELEVATED DOCK AREA & INLETS.

J. PAVEMENT / ROCK.

K. TUNNEL WALLS, TOP & SIDEWALK WHERE NOT REMOVING.

L. DOCK AREA & WALL IN PLACE.

2. PAVEMENT REMOVALS, REMOVE THE FOLLOWING.

A. PCC PAVEMENT.

B. PCC DRIVE AREA PAVEMENT OVER THE TUNNEL. PROTECT THE

TUNNEL LID.

C. PCC SIDEWALK, DRIVE AREA PAVEMENT AND TUNNEL TOP WHERE

INDICATED. SEE STRUCTURAL PLANS FOR DETAILS.

TUNNEL

TUNNEL LID - PROTECT

UNLESS OTHERWISE NOTED.

PCC PAVEMENT OVER TUNNEL TO

BE REMOVED WHERE NOTED.

C100

PCC PAVEMENT OVER TUNNEL REMOVAL

NO SCALE

1A

1A

1A

1A 1B

1B

1C

1A

1A

1K

1E

1E

1E

1D

1F

1G

1G

1G

1G

1G

1G

LEGEND

- SIDEWALK OR DRIVE AREA PAVEMENT OVER TUNNEL TOP

REMOVAL, REFER TO DETAILS ON STRUCTURAL SHEETS

- PAVEMENT REMOVAL

- 22' WIDE TUNNEL LID REMOVAL FOR CONSTRUCTION

ACCESS, REFER TO DETAILS ON STRUCTURAL SHEETS

- EXISTING GRASSED AREA TO BE PROTECTED FOR FUELING

AREA & UNDERGROUND STORAGE TANKS

2A

2A

2A

2B

2B

2B

2B

2C

2C

2C

2C

1K

SNYDER & ASSOCIATES, INC.

www.snyder-associates.com

Project Engineer www.alvine.com

SNYDER & ASSOCIATES, INC.

231 BENNETT AVE.

COUNCIL BLUFFS, IOWA 51503

P: 712-322-3202

Project Engineer

Mechanical, Electrical and Plumbing Engineer

ALVINE ENGINEERING

400 E. COURT AVE

SUITE 130

DES MOINES, IA 50309

- WATER LINE

- ELECTRICAL LINE

- STORM NETWORK

1H

1I

TO DOCK

1J

1J

1J

1J

2B 1B

1B

GENERAL NOTES

1. NOTIFY UTILITY PROVIDERS AND CLARINDA CORRECTIONAL

FACILITY (CCF) PRIOR TO BEGINNING ANY CONSTRUCTION

ACTIVITIES AND COORDINATE WITH UTILITY PROVIDERS AND

CCF AS NECESSARY DURING CONSTRUCTION.

CONTRACTOR IS RESPONSIBLE FOR DETERMINING

EXISTENCE, EXACT LOCATION, AND DEPTH OF ALL UTILITIES.

PROTECT ALL UTILITY LINES AND STRUCTURES NOT SHOWN

FOR REMOVAL OR MODIFICATION. ANY DAMAGES TO

UTILITY ITEMS NOT SHOWN FOR REMOVAL OR MODIFICATION

SHALL BE REPAIRED TO THE UTILITY OWNER'S

SPECIFICATIONS AT THE CONTRACTOR'S EXPENSE.

2. CONSTRUCTION OF ALL PAVEMENT AND UTILITY

IMPROVEMENTS SHALL CONFORM TO THE IOWA STATEWIDE

URBAN DESIGN & SPECIFICATIONS (SUDAS).

3. ALL TRAFFIC CONTROL SHALL BE PROVIDED IN

ACCORDANCE WITH REQUIREMENTS SET FORTH IN THE

MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES (MUTCD).

COORDINATE ALL TRAFFIC CONTROL WITH CCF.

4. ANY UNDERGROUND PIPING FOUND AFTER PAVEMENT

REMOVAL, THAT WAS NOT IDENTIFIED ON PLANS, NEEDS TO

BE INVESTIGATED BY ENGINEER TO PROVIDE AN ACCURATE

AS-BUILT TO CCF AFTER THE PROJECT. PLEASE PROVIDE

APPROXIMATELY 1-WEEKS NOTICE TO ENGINEER FOR WHEN

THIS WORK IS ANTICIPATED.

5. CONTRACTOR TO LOAD AND TRANSPORT ALL MATERIALS

CONSIDERED TO BE UNDESIRABLE TO AN APPROVED

OFF-SITE WASTE SITE.

6. THE CONTRACTOR IS RESPONSIBLE FOR CLEANING DIRT

AND DEBRIS FROM NEIGHBORING STREETS, DRIVEWAYS,

AND SIDEWALKS CAUSED BY CONSTRUCTION ACTIVITIES IN

A TIMELY MANNER.

7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING

EROSION CONTROL MEASURES AS NECESSARY.

CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR

MAINTAINING ANY EROSION CONTROL MEASURES ON SITE

THROUGHOUT OF CONSTRUCTION. GRADING AND SOIL

EROSION CONTROL CODE REQUIREMENTS SHALL BE MET BY

CONTRACTOR.

UTILITY WARNING

THE UTILITIES SHOWN HAVE BEEN LOCATED FROM FIELD SURVEY

INFORMATION AND/OR RECORDS OBTAINED. THE SURVEYOR

MAKES NO GUARANTEE THAT THE UTILITIES OR SUBSURFACE

FEATURES SHOWN COMPRISE ALL SUCH ITEMS IN THE AREA,

EITHER IN SERVICE OR ABANDONED. THE SURVEYOR FURTHER

DOES NOT WARRANT THAT THE UTILITIES OR SUBSURFACE

FEATURES SHOWN ARE IN THE EXACT LOCATION INDICATED

EXCEPT WHERE NOTED AS QUALITY LEVEL A.

UTILITY CONTACT INFORMATION

UTILITY CONTACT FOR MAPPING INFORMATION SHOWN AS

RECEIVED FROM THE IOWA ONE CALL DESIGN REQUEST

SYSTEM, TICKET NUMBER 552500962.

( ASW ) ALLIANT ENERGY

COMPANY NAME : ALLIANT ENERGY

DESIGN CONTACT : ALLIANT ENERGY FIELD ENGINEER

PHONE : 800-255-4268

EMAIL : LOCATE_IPL@ALLIANTENERGY.COM

LOCATE REQUESTED: Y

( CRD ) CLARINDA, CITY OF

COMPANY NAME : CLARINDA, CITY OF

DESIGN CONTACT : GARY MCCLARNON

PHONE : 712-542-2136

EMAIL : GMCCLARNON@CITYOFCLARINDA.COM

LOCATE REQUESTED: Y

( FM4 ) FARMERS MUTUAL TELEPHONE

COMPANY NAME : FARMERS MUTUAL TELEPHONE

DESIGN CONTACT : PAT GARLAND

PHONE : 712-829-2111

EMAIL : PLANT@FMTCNET.COM

LOCATE REQUESTED: Y

( MD1E ) MIDAMER-ELEC

COMPANY NAME : MIDAMER-ELEC

DESIGN CONTACT : DAVID FITCH

PHONE : 712-366-5669

EMAIL : DLFITCH@MIDAMERICAN.COM

LOCATE REQUESTED: Y

( T16 ) MEDIACOM CABLE

COMPANY NAME : MEDIACOM CABLE

DESIGN CONTACT : SHANE SCHRADER

PHONE : 712-314-1248

EMAIL : SSCHRADER@MEDIACOMCC.COM

LOCATE REQUESTED: Y

CLARINDA CORRECTIONAL FACILITY

UTILITY CONTACT

GREG GRAHAM

OFFICE PHONE: 712-695-7186

CELL PHONE: 712-370-4448

1L

1F

BM500

F.F.E.=1055.96

AT DOCK

F.F.E.=1051.93

F.F.E.=1049.58

F.F.E.=1049.48

F.F.E.=1052.10

F.F.E.=1051.86

F.F.E.=1051.76

BUILDING F.F.E.=1049.12

CONCRETE

CONCRETE

CONCRETE

CONCRETE

CONCRETE

℄ 8" CONCRETE WALL

CONC. STEPS

RIM=1049.03

FL=1048.25 4" CLAY SW

RIM=1051.76

FL=1049.13 4" CLAY EAST

FL=1047.22 8" CLAY N-SW

RIM=1051.42

FL=1048.42 15" RCP WEST

FL=1049.03 8" HDPE SE

SUMP=1047.62

RIM=1051.34

FL=1048.00 4" PVC EAST

FL=1049.06 4" CLAY SE

FL=1048.49 4" DIP NE

FL=1047.83 4" DIP NW

RIM=1051.05

UNABLE TO OPEN

RIM=1051.04

UNABLE TO OPEN

RAMP

RIM=1051.19

FL=1048.65 6" STEEL EAST

FL=1048.60 6" STEEL WEST

FL=1048.78 4" STEEL SOUTH

FUEL PUMPS

BREATHER

RIM=1051.07

FL=1049.77 4" STEEL SOUTH

FACE OF FOUNDATION(TYP.)

FACE OF BUILDING(TYP.)

RIM=1052.10

FL=1049.48 4" STEEL SOUTH

SUMP=1048.54 (SILTED)

WINDOW SILL ELEV.=1055.75

WINDOW SILL ELEV.=1053.78

BASKETBALL HOOP

(FOOTING ONLY)

PROBED TOP/EDGE OF TUNNEL

TOP=1050.99+/- SLOT DRAIN

BOTTOM SILTED

RIM=1051.35

FL=1049.42 6" DIP NE

FL=1049.17 6" DIP WEST

RIM=1051.64

TUNNEL FLOOR=1044.12

TUNNEL TOP=1050.96

TOP 9" THICK

TUNNEL 48" WIDE BY 73" TALL

RIM=1051.92

TUNNEL FLOOR=1045.54

TUNNEL 48" WIDE BY 71" TALL

END OF TUNNEL 1.75' SE

RIM=1051.69

TUNNEL FLOOR=1044.44

TUNNEL TOP=1051.26

TOP 9" THICK

TUNNEL 48" WIDE BY 73" TALL

F.F.E.=1052.42

B1

B2

B3

B4

GRAVEL

GRAVEL

CONCRETE

RIM=1053.19

FL=1048.13 8" CLAY E-W

RAMP

1051.26 1051.28

1051.31 1051.20

1051.32 1051.29

1051.40 1051.36

1051.51

1051.54

1051.49

1051.50

1051.83

1051.61

1051.52 1051.55

1051.87 1051.89

1051.88 1051.85

1051.65

1051.60

1051.50

1051.51

1051.52 1051.60

1051.65 1051.60

1051.63 1051.87

1051.77 1051.91

1051.64 1051.66

1051.67 1051.67

LOADING ZONE

V:

\P ro je ct s\

\1

.0

8.

\C

AD

D \1

_C

_S

IT

E.

dw g R

AC

H

EL

D

IC

KE

Y, S

IT

E

PL

AN

, 2

5/

/0 9, :1

PM

, A N

SI

F

U

LL

B

LE

ED

D

(3 4.

X

2.

IN

C H

ES

FEET

0 20

PROJECT NUMBER

DATE

SHEET NO.

SHEET TITLE

MARK REVISION DATE

400 E COURT AVE.

SUITE 140.

DES MOINES, IOWA 50309

515-243-4477 www.shuck-britson.com

SNYDER & ASSOCIATES, INC.

2727 S.W. SNYDER BLVD.

ANKENY, IOWA 50023

P: 515-964-2020 www.snyder-associates.com

Project Engineer

Mechanical, Electrical and Plumbing Engineer

400 E COURT AVE.,

SUITE 130

DES MOINES, IA 50309

www.alvine.com

ALVINE ENGINEERING

100% CONSTRUCTION DOCUMENTS

10/10/2025

125.0278

C200

D O

C C

C F

TU

N

N

EL

R

EP

AI

R

/R

EP

LA

C

EM

EN

T M

AI

N

B

LD

G . S

W W

IN

G

SITE PLAN

C

LA

R

IN

D A, IO

A

IO

A D

EP

AR

TM

EN

T O

F

AD

M

IN

IS

TR

AT

IV

E

SE

R

VI

C

ES

(D

AS

SITE PLAN NOTES

1. TUNNEL IMPROVEMENTS AS FOLLOWS: SEE STRUCTURAL PLANS FOR

DETAILS.

A. REPLACE TUNNEL LID AND INSTALL NEW ACCESS HATCH.

2. PAVEMENT IMPROVEMENTS PROVIDE THE FOLLOWING:

A. 6" PCC PAVEMENT, REFER TO SUDAS STANDARD SPECIFICATIONS

SECTION 7010.

B. 4 TO 6" PCC DRIVE AREA PAVEMENT OVER THE TUNNEL. PROTECT

THE TUNNEL LID.

3. GRADES SHOWN REPRESENT FINISHED GRADE/TOP OF SLAB

ELEVATIONS UNLESS OTHERWISE NOTED. ALL EXISTING AREA INLETS

SHALL BE ADJUSTED TO GRADE.

4. PROVIDE POSITIVE DRAINAGE AWAY FROM BUILDINGS AND TUNNEL

DIRECTED TOWARD THE EXISTING STORM SEWER INLETS.

5. CONTRACTOR IS RESPONSIBLE FOR ANY EXCESS OR NEEDED SOIL FOR

THE SMALL GRADING CHANGES MADE OVER THE SITE. THIS ITEM IS

SUBSIDIARY TO THE 6" PCC PAVING ITEM.

6. SEED ALL DISTURBED AREAS NOT INDICATED FOR PCC INSTALLATION

WITH SUDAS TYPE 1 SEED MIX, REFER TO SUDAS STANDARD

SPECIFICATIONS SECTION 9010. FOLLOW PROPER SOIL PREP INCLUDED

WITHIN THE SPEC.

7. ACCESS TO THE FUELING AREA NEEDS TO BE MAINTAINED AND/OR

COORDINATED WITH CONSTRUCTION PHASING TO ENSURE FUEL IS

AVAILABLE WHEN NEEDED. IF A LONGER HOSE CAN BE INSTALLED

THEN FUELING MAY BE ABLE TO BE COMPLETED FROM THE GRAVEL

AREA.

8. ACCESS TO THE DOCK DELIVERY NEEDS TO BE MAINTAINED AS MUCH

AS POSSIBLE. ANY SHUTDOWNS NEED TO BE COORDINATED WITH CCF.

9. WITHIN THE DRIVE AREA, WHERE NEW PAVEMENT WILL BE INSTALLED

OVER THE UNDISTURBED TUNNEL TOP, A CONSTRUCTION JOINT SHALL

BE USED SO THAT CRACKING ALONG THE TUNNEL LID DOES NOT

FOLLOW THROUGH THE NEW DRIVE AREA PAVEMENT. THE PCC OVER

THE TUNNEL & THE DRIVE AREA PAVEMENT SHALL BE SEPARATE

POURS. THE TUNNEL IS MEANT TO BE THE HIGH POINT OF THE AREA SO

THAT WATER WILL SHED AWAY FROM THE TUNNEL TO THE AREA INLETS.

THE JOINTING LAYOUT SHALL FOLLOW SUDAS CHAPTER 5 SECTION 5G

(PCC PAVEMENT JOINTS), AND SECTION 7010.101 (PV-101). THE

JOINTING PLAN SHALL BE SUBMITTED TO THE ENGINEER AS A SHOP

DRAWING, AT LEAST 48 HOURS PRIOR TO PAVING. THE THICKNESS OF

THE PCC OVER THE TUNNEL MAY VARY SLIGHTLY BASED ON MAKING

THE TUNNEL THE HIGH POINT. ENGINEER SHALL VISIT THE SITE AFTER

FORMS ARE SET AND PRIOR TO POURING CONCRETE.

10. CCF WILL ADJUST DOWNSPOUTS ACCORDINGLY AFTER PAVING.

11. CONTRACTOR TO MATCH EXISTING PAVEMENT MARKINGS.

12. CONTRACTOR TO REMOVE VEGETATION FROM THIS CORNER &

REPLACE WITH 6" PCC OVER 12" PREPARED SUBGRADE. GRADE TO

ENSURE POSITIVE DRAINAGE.

LEGEND

- 4 TO 6" PCC DRIVE AREA PAVEMENT OVER TUNNEL, REFER TO

DETAILS ON STRUCTURAL SHEETS, SEE NOTE 9, THICKNESS TO

BE MATCHED AFTER REMAINING DRIVE AREA IS POURED

- 6" DEPTH PCC PAVEMENT OVER 12" PREPARED

SUBGRADE, SUDAS SECTION 7010

- TUNNEL LID REPLACEMENT AFTER CONSTRUCTION ACCESS

IS COMPLETE

1A

1A

1A

1A

MATCH EXISTING ELEVATION

2A

2B

2B

2B

C200

TYPICAL PAVEMENT CROSS SECTIONS

NO SCALE

PCC PAVEMENT SECTION

PCC SIDEWALK OVER TUNNEL SECTION

6" PCC PAVEMENT, SEE PLANS

FOR THICKNESS & LOCATIONS

12" DEPTH PREPARED SUBGRADE

2 - 6" LIFTS (SCARIFY AND COMPACT TO

95% STANDARD PROCTOR DENSITY),

PER SUDAS SECTION 2010

DRIVE AREA PAVEMENT, SEE PLANS

FOR THICKNESS & LOCATIONS, REFER

TO STRUCTURAL SHEETS FOR

REINFORCING

NEW OR EXISTING TUNNEL LID

SNYDER & ASSOCIATES, INC.

www.snyder-associates.com

Project Engineer www.alvine.com

SNYDER & ASSOCIATES, INC.

231 BENNETT AVE.

COUNCIL BLUFFS, IOWA 51503

P: 712-322-3202

Project Engineer

Mechanical, Electrical and Plumbing Engineer

ALVINE ENGINEERING

400 E. COURT AVE

SUITE 130

DES MOINES, IA 50309

TO DOCK

BOND BREAK - REFER

TO STRUCTURAL SHEETS

PROJECT NUMBER

DATE

SHEET NO.

SHEET TITLE

400 E COURT AVE.

SUITE 140.

DES MOINES, IOWA 50309

515-243-4477 www.shuck-britson.com

SNYDER & ASSOCIATES, INC.

231 BENNETT AVE.

COUNCIL BLUFFS, IOWA 51503

P: 712-322-3202 www.snyder-associates.com

Project Engineer

Mechanical, Electrical and Plumbing Engineer

ALVINE ENGINEERING

400 E. COURT AVE

SUITE 130

DES MOINES, IA 50309

www.alvine.com

C

U s e rs

\d tr ip p \D o c u m e n ts

\1 .0

.1

T U

N N

E L

(R d tr ip p s h u c k -b ri ts o n .c o m

.r v t

/9 /2

:4

:1

P

M

D O

C C

C F

T U

N N

E L R

E P

A

IR

R

E P

L A

C E

M E

N T

M A

IN

B

L D

G

S W

W

IN

G

10/10/2025

125.0278.10

S0.00

N th

S t, C la ri n d a

IA

NOTES

100% CONSTRUCTION DOCUMENTS

IO

W

A D

E P

A R

T M

E N

T O

F A

D M

IN

IS

T R

A T

IV

E

S E

R V

IC

E

S

D A

S

THE QUANTITIES FOR SOME LUMP SUM BID ITEMS ARE INDICATED WITH ROUNDED ESTIMATES FOR THE CONTRACTOR’S CONVENIENCE. DISCREPANCIES IN THE ESTIMATED VS ACTUAL QUANTITIES FOR THESE BID ITEMS WILL NOT CHANGE THE

PRICE PAID IN THE CONTRACT.

THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING THE DOCUMENTS IN FULL INCLUDING ALL THEIR OWN QUANTITIES

FOR ANY AND ALL BID ASSUMPTIONS.

BID ITEMS WITH SF, LF, OR EA ARE SUBJECT TO IN FIELD CONDITIONS AND ARE ALL TO BE APPROVED PRIOR TO WORK

PERFORMED AND PAYMENT TO THE CONTRACTOR.

ALL ITEMS IN CONSTRUCTION DOCUMENTS ARE LISTED HERE OR INCIDENTAL TO THESE ITEMS.

ONLY THE MOST SEVERE CONCRETE REPAIRS AND EPOXY CRACK INJECTION REPAIRS ARE TO BE PERFORMED, AS IDENTIFIED IN THE ESTIMATED QUANTITIES. WHILE MEASURED QUANTITIES ARE SHOWN ON THE PLANS, THE BID ITEM

QUANTITY WILL BE BASED ON THE ACTUAL QUANTITY OF REPAIRS COMPLETED.

ALL CONCRETE REPAIRS TO BE MARKED AND APPROVED FOR QUANTITY BY CM/CCF AND ENGINEER PRIOR TO PERFORMING REPAIRS. CONCRETE ISSUES SHOWN ON THE DRAWINGS DO NOT NECESSARILY CORRELATE TO REPAIRS

THAT WILL BE MADE BUT TO OBSERVATIONS MADE ON EXISTING CONCRETE DETERIORATION.

EPOXY CRACK INJECTION REPAIRS TO BE PRIORITIZED BY CRACK WIDTH, WITH THE WIDEST CRACKS REPAIRED FIRST

CONCRETE REPAIRS TO BE PRIORITIZED TO FILL IN OPENINGS AND PENETRATIONS IN THE WALLS TO SEAL THE TUNNEL

FROM THE EXTERIOR SOIL AND WHERE THERE IS EXPOSED REBAR.

GENERAL

1. THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS PRIOR TO

COMMENCING CONSTRUCTION.

2. ALL OF THE WORK TO BE DONE UNDER THIS CONTRACT SHALL BE DONE

IN ACCORDANCE WITH THE REQUIREMENTS OF THE DRAWINGS, THE

GENERAL REQUIREMENTS OF DIVISION ONE, THE GENERAL CONDITIONS,

THE SPECIFICATIONS, AND ANY ADDENDA THERETO.

3. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ACQUAINT

THEMSELVES AND ALL SUPERVISORY PERSONNEL WITH THE ABOVE-NAMED

DRAWINGS AND DOCUMENTS.

4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSPECTING THE SITE OF

THE PROPOSED WORK TO SATISFY THEMSELVES AS TO THE EXISTING

CONDITIONS RELATIVE TO THE CONTRACT.

5. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL TEMPORARY

SHORING/BRACING OF WALLS, SLABS, COLUMNS, ETC., AS REQUIRED BY

ALL FEDERAL, STATE AND LOCAL AGENCIES HAVING JURISDICTION,

UNTIL ALL PERMANENT FRAMING IS INSTALLED.

6. UTILITY LOCATIONS ARE SHOWN IN AN APPROXIMATE WAY ONLY. THE

CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING

UTILITIES BEFORE COMMENCING WORK. SHOULD ANY UTILITIES BE

FOUND DIFFERENT THAN LOCATED OR SHOWN ON THE DRAWINGS, THEY

SHALL BE PROTECTED IN PLACE AND THE ENGINEER SHALL BE

IMMEDIATELY NOTIFIED. THE CONTRACTOR SHALL BE FULLY

RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT BE

OCCASIONED BY THEIR FAILURE TO EXACTLY LOCATE AND PRESERVE ANY

AND ALL UTILITIES.

7. ALL CONSTRUCTION SHALL CONFORM TO INTERNATIONAL BUILDING

CODE 2015 UNLESS NOTED OTHERWISE.

8. DIMENSIONS MARKED +/- REQUIRE VERIFICATION BY THE CONTRACTOR.

9. IN ANY CASE OF CONFLICT BETWEEN THE NOTES, DETAILS AND

SPECIFICATIONS, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN.

CONTRACTOR SHALL MAKE NO DEVIATION FROM DESIGN DRAWINGS WITHOUT

WRITTEN APPROVAL OF THE ENGINEER.

10. PROTECT AND SHORE ALL OF THE UTILITIES INSIDE AND OUTSIDE OF THE

TUNNEL AS REQUIRED.

11. PROTECTIVE FENCE TO BE INSTALLED DURING WORK PREVENTING

ENTRANCE TO EXCAVATED AREA. SNOW FENCE TO BE USED AND

MAINTAINED THROUGHOUT CONSTRUCTION.

12. UTILITIES WITHIN THE VAULT MUST BE PROTECTED IN PLACE.

13. ALL PRODUCTS LISTED IN THESE DRAWINGS ARE THE BASIS-OF-DESIGN AND

NOT REQUIRED PRODUCTS, CONTRACTOR MAY USE PRODUCTS THAT ARE

SIMILAR OR BETTER IN PERFORMANCE.

CONCRETE

1. CONCRETE TO BE IN ACCORDANCE WITH "SPECIFICATIONS FOR

STRUCTURAL CONCRETE FOR BUILDINGS (ACI 301 CURRENT EDITION)".

2. REINFORCING STEEL TO BE BENT AND PLACED IN ACCORDANCE WITH

"MANUAL OF STD. PRACTICE FOR DETAILING CONCRETE STRUCTURES

(ACI 315 CURRENT EDITION)".

3. ALL CONCRETE SHALL BE 4000 PSI AT 28 DAYS.

4. CONCRETE EXPOSED TO FREEZE/THAW CONDITIONS SHALL BE AIR

ENTRAINED.

5. COARSE AGGREGATE FOR SLABS AND EXPOSED WALLS TO BE

CRUSHED LIMESTONE.

6. MAXIMUM AGGREGATE SIZE TO BE 1" - U.N.O.

7. ALL AGGREGATE IN ACCORDANCE WITH ASTM C33. LIMIT SHALE,

CHERT, COAL AND IRON OXIDE.

8. 4000 PSI CONCRETE TO HAVE A MIN. 6 SACKS CEMENT/MAX. 5 GAL. OF

WATER/SACK.

9. WATER REDUCER REQUIRED FOR ALL WALLS AND SLABS.

10. CONCRETE WATER-CEMENT RATIO INDICATED FOR DESIGN MIXES TO

HAVE CEMENT CONTENT ADJUSTED TO PROVIDE A WORKABLE MIX.

11. USE OF CALCIUM CHLORIDES PROHIBITED.

12. ALL REINFORCING STEEL TO BE ASTM A615 - GRADE 60.

13. CLEAR DISTANCE FROM FACE OF CONCRETE TO NEAR REINFORCING

BAR TO BE:

3" CAST AGAINST EARTH

2" SLABS ON GRADE (DISTANCE FROM TOP OF SLAB TO NEAR BAR)

1 1/2" STRUCTURAL SLABS

14. ALL REINFORCING STEEL SHALL BE SECURELY WIRED IN PLACE

BEFORE CONCRETE IS PLACED.

15. MAXIMUM SPACING OF BAR SUPPORTS TO BE 3'-0" O.C. EACH WAY.

16. PROVIDE 2-#5 BARS AROUND ALL SIDES OF HOLES THROUGH

CONCRETE WALLS AND SLABS. AT WALLS AND SLABS WITH MULTIPLE

MATS OF REINFORCING, PROVIDE SUPPLEMENTAL REINFORCING BARS

IN EACH FACE OF MEMBER. BARS TO EXTEND 2'-0" BEYOND EDGES OF

OPENINGS. SEE TYPICAL DETAIL.

17. PROVIDE CLASS B TENSION LAP SPLICES FOR CONTINUOUS BARS UNLESS

OTHERWISE SHOWN.

18 ALL SLAB REINFORCING STEEL SHALL CONTINUE THROUGH SLAB

CONSTRUCTION JOINTS.

19. DO NOT SAWCUT STRUCTURAL SLABS, STOOPS, OR SLABS ON METAL

DECK WITHOUT PRIOR APPROVAL OF ENGINEER.

20. THE CONTRACTOR SHALL COORDINATE LOCATIONS OF ALL OPENINGS

IN WALLS, SLABS AND FOUNDATIONS FOR DUCTS, PIPES, UTILITY LINES

AND OTHER PENETRATIONS WITH THE RESPECTIVE TRADES. ALL SUCH

PENETRATIONS SHALL BE FORMED OR SLEEVED IN CONCRETE AND

STEEL LINTELS IN MASONRY WALLS.

21. UNLESS OTHERWISE DETAILED ON PLANS, NO OTHER OBJECTS SHALL

BE PLACED IN STRUCTURAL SLABS WITHOUT PRIOR APPROVAL OF

ENGINEER (I.E. CONDUIT, MECHANICAL LINES, PLUMBING LINES, ETC.).

22. ALL CONCRETE SLABS SHALL BE POURED TO UNIFORM THICKNESS AS

INDICATED ON PLANS.

23. ALL REINFORCING BARS SHALL BE LAPPED AS SPECIFICALLY DETAILED

ON THE STRUCTURAL DRAWINGS. WHERE NOT SPECIFICALLY

INDICATED ON THE DRAWINGS, ALL REINFORCING BARS SHALL BE

LAPPED AS FOLLOWS: LAP WALL/BEAM TOP HORIZONTAL

REINFORCEMENT AT CENTER OF SPAN. LAP WALL/BEAM BOTTOM

HORIZONTAL REINFORCEMENT AT SUPPORT. TERMINATE CONTINUOUS

BARS AT DISCONTINUOUS ENDS WITH STANDARD HOOKS.

24. PROVIDE CONSTRUCTION JOINTS IN ACCORDANCE WITH ACI 318,

CHAPTER 6.4. SUBMIT SHOP DRAWINGS SHOWING CONSTRUCTION

JOINT LOCATIONS ALONG WITH THE SEQUENCE OF POURS FOR

REVIEW.

25. NEW WATERSTOPS TO BE BENTONITE SELF ADHERING STRIPS 1"X3/4"

STEEL

1. STRUCTURAL STEEL TO BE FABRICATED AND ERECTED IN

ACCORDANCE WITH "SPECIFICATION FOR STRUCTURAL STEEL

BUILDINGS" (AISC 360, CURRENT EDITION) AND "CODE OF STANDARD

PRACTICE FOR STEEL BUILDINGS AND BRIDGES" (AISC 303, CURRENT

EDITION).

2. STRUCTURAL STEEL WIDE FLANGE AND WT SECTIONS IN ACCORDANCE

WITH ASTM A992.

3. STEEL CHANNELS, PLATES AND ANGLES IN ACCORDANCE WITH ASTM

A36.

4. STEEL TUBES IN ACCORDANCE WITH ASTM A500 GRADE C (Fy = 50 ksi).

5. STEEL PIPE IN ACCORDANCE WITH ASTM A53 GRADE B (Fy = 35 ksi).

6. ALL ELECTRODES E70 SERIES.

7. STAINLESS STEEL TO BE ASTM A304.

8. CONCRETE ANCHORS SHALL BE HILTI HIT-HY 200 OR APPROVED

EQUAL. THREADED RODS SHALL BE HILTI HAS-E STANDARD RODS OR

GRADE 36 THREADED RODS UNLESS NOTED OTHERWISE.

9. SHOP PRIME ALL STRUCTURAL STEEL AND FIELD PAINT ALL STEEL AND

FIELD WELDS PER THE PAINTING NOTES

10. SUMP GRATING TO BE MCNICHOLS 1"X1/8" GW-2

OR APPROVED EQUAL SUFFICIENT TO SUPPORT 100 PSF/300 LB POINT

LOAD OVER 24" SPAN. CONTRACTOR MAY INCREASE THE DEPTH OF THE

GRATING TO FACILITATE IN CONCRETE FORMING AND GUTTER

DRAINAGE COORDINATE DEPTH OF GRATING WITH TOP OF SUMP

CONCRETE POUR TO PROVIDE FLAT TUNNEL PROFILE

DRILLED-IN-DOWELS AND ANCHOR BOLTS

1. HOLES FOR DOWELS SHALL BE DRILLED INTO THE EXISTING CONCRETE

AT THE LOCATIONS AND OF THE SIZE SHOWN ON THE PLANS. EMBED

DRILLED-IN-DOWELS 15 BAR OR ANCHOR BOLT DIAMETERS MINIMUM,

UNLESS NOTED OTHERWISE. AFTER HOLES ARE DRILLED, THEY SHALL BE

BLOWN CLEAN WITH OIL-FREE COMPRESSED AIR BEFORE THE EPOXY

RESIN IS PLACED IN THE HOLE. THE HOLE SHALL BE FILLED WITH EPOXY

RESIN TO A LEVEL SUCH THAT AFTER THE BAR IS INSERTED, THE EPOXY

WILL RISE TO THE SURFACE OF THE HOLE. IN OVERHEAD APPLICATIONS,

WORK AND SECURE ENOUGH EPOXY RESIN INTO THE HOLE SUCH THAT

WHEN THE DOWEL IS INSERTED, THE EPOXY RESIN COMPLETELY FILLS

THE VOID AROUND THE DOWEL. SECURE THE EPOXY RESIN IN PLACE FOR

CURING BY PLUGGING THE HOLE AROUND THE SHANK OF THE DOWEL.

REINFORCING STEEL DOWELS OR ANCHOR BOLTS OF THE SIZE SHOWN ON

THE PLANS SHALL BE INSERTED INTO THE HOLE IMMEDIATELY AFTER

THE EPOXY RESIN IS PLACED. THE EPOXY RESIN SHALL BE PERMITTED TO

SET BEFORE NEW CONCRETE IS PLACED AROUND THE ANCHOR.

DEMOLITION AND SHORING

1. THE CONTRACTOR SHALL TAKE ALL PRECAUTIONS NECESSARY TO

ENSURE THAT PARTS OF THE STRUCTURE TO BE PRESERVED ARE

NOT DAMAGED BY THE APPLICATION OF EXCESSIVE LOADS OR BY

ANY OTHER MEANS, AND THE CONTRACTOR SHALL ASSUME FULL

RESPONSIBILITY FOR ANY DAMAGE CAUSED.

2. ENSURE SAFE PASSAGE OF PERSONS AROUND AREA OF DEMOLITION

AND CONSTRUCTION. CONDUCT OPERATIONS TO PREVENT INJURY

TO ADJACENT BUILDINGS, STRUCTURES, EQUIPMENT AND OTHER

FACILITIES AND PERSONS.

3. EXISTING STRUCTURE SHALL BE TEMPORARILY SHORED AS REQUIRED

TO PERFORM CONSTRUCTION SHOWN HEREIN. MEMBERS SHALL BE

REMOVED IN SUCH A MANNER AS NOT TO DAMAGE EXISTING STRUCTURE.

4. ALL REMOVALS OF EXISTING CONCRETE SHALL BE INITIATED WITH A

NEAT, 3/4" MIN. DEEP STRAIGHT SAW CUT.

5. PROTECT EXISTING REINFORCING STEEL IN PLACE. EXERCISE EXTREME

CARE TO AVOID DAMAGING EXISTING REINFORCEMENT.

6. EXACT LOCATION OF EXISTING REINFORCEMENT IS TO BE DETERMINED

BY THE CONTRACTOR USING A REBAR LOCATOR OR SIMILAR METHOD.

7. LOCATE HOLES FOR BOLTS TO AVOID EXISTING REINFORCEMENT.

8. CONTRACTOR RESPONSIBLE TO REPAIR DAMAGED EXISTING

REINFORCEMENT TO THE SATISFACTION OF THE ENGINEER/OWNER.

CONTRACTOR RESPONSIBLE FOR ALL COSTS AND DELAYS ASSOCIATED

WITH THE REPAIR.

9. IN THE EVENT OF CONFLICTS, NOTIFY ENGINEER PRIOR TO FIELD

MODIFICATIONS OF DETAILS, CONNECTIONS, OR DIMENSIONS SHOWN

ON THE CONTRACT DRAWINGS.

10. CURRENT WALL TEMPORARY SHORING IS DESIGNED FOR 400 LBS /FT.

LATERAL FORCE TO HOLD BACK THE SOIL PRESSURES ON THE UNSUPPORTED

WALL IN ITS TEMPORARY CONDITION. NO HEAVY EQUIPMENT EXCEEDING 100

PSF SHALL BE ALLOWED WITHIN 6FT OF THE FACE OF THE TEMPORARY TUNNEL

LID EXCAVATION WHILE THE STRUCTURAL SLAB IS REMOVED UNTIL AFTER THE

NEW SLAB IS POURED AND CURED. CONTRACTOR MAY PROVIDE ALTERNATE

EXTERIOR TEMPORARY SHORING ALONG THE TOP OF THE WALL WITH STEEL

OR TIEBACKS FOR APPROVAL TO INCREASE THIS ALLOWABLE LOAD.

PAINTING:

1. APPLY PAINTS ONLY WHEN TEMPERATURE OF SURFACES TO BE PAINTED AND

AMBIENT AIR TEMPERATURES ARE BETWEEN 50 AND 95 DEG F.

2. DO NOT APPLY PAINTS IN SNOW, RAIN, FOG, OR MIST; WHEN RELATIVE HUMIDITY

EXCEEDS 85 PERCENT; AT TEMPERATURES LESS THAN 5 DEG F ABOVE THE DEW POINT;

OR TO DAMP OR WET SURFACES.

3. STEEL SUBSTRATES: REMOVE RUST, LOOSE MILL SCALE, AND SHOP PRIMER IF ANY.

CLEAN USING METHODS RECOMMENDED IN WRITING BY PAINT MANUFACTURER PER

SSPC-SP 6.

4. SHOP-PRIMED STEEL SUBSTRATES: CLEAN FIELD WELDS, AND AREAS WHERE SHOP

PAINT IS ABRADED. PAINT EXPOSED AREAS WITH THE SAME MATERIAL AS USED FOR SHOP

PRIMING TO COMPLY WITH SSPC-PA 1 FOR TOUCHING UP SHOP-PRIMED SURFACES.

5. APPLY PAINTS ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS AND

RECOMMENDATIONS IN "MPI ARCHITECTURAL PAINTING SPECIFICATION MANUAL."

6. APPLY PAINTS TO PRODUCE SURFACE FILMS WITHOUT CLOUDINESS, SPOTTING,

HOLIDAYS, LAPS, BRUSH MARKS, ROLLER TRACKING, RUNS, SAGS, ROPINESS, OR OTHER

SURFACE IMPERFECTIONS. CUT IN SHARP LINES AND COLOR BREAKS.

7. FURNISH EXTRA MATERIALS, FROM THE SAME PRODUCT RUN, THAT MATCH

PRODUCTS INSTALLED AND THAT ARE PACKAGED WITH PROTECTIVE COVERING FOR

STORAGE AND IDENTIFIED WITH LABELS DESCRIBING CONTENTS.

8. PAINT PRODUCT: (OR APPROVED EQUAL)

SYSTEM TYPE: EPOXY/EPOXY

SURFACE PREPARATION: SSPC-SP6/NACE 3 COMMERCIAL BLAST CLEANING OR

SSPC-SP3 POWER TOOL CLEANING (SSPC RUST GRADE CONDITION C)

PRIMER: SERIES 394 PERIMEPRIME, DFT 2.5 TO 3.5 MILS

INTERMEDIATE COAT: SERIES N69 HI-BUILD EPOXOLINE II, DFT 3.0 TO 5.0 MILS

FINISH COAT: SERIES N69 HI-BUILD EPOXOLINE II, DFT 4.0 TO 6.0 MILS

TOTAL DFT: 9.5 TO 14.5 MILS

9. PAINT SUBMITTAL:

1. COLOR: TO BE SUBMITTED FOR VERIFICATION TO OWNER.

2. PRODUCT DATA: FOR EACH TYPE OF PRODUCT. INCLUDE PREPARATION

REQUIREMENTS AND APPLICATION INSTRUCTIONS.

3. INCLUDE PRINTOUT OF CURRENT "MPI APPROVED PRODUCTS LIST" FOR EACH

PRODUCT CATEGORY SPECIFIED, WITH THE PROPOSED PRODUCT HIGHLIGHTED.

4. INDICATE VOC CONTENT.

5. SAMPLES FOR VERIFICATION: FOR EACH TYPE OF PAINT SYSTEM AND EACH

COLOR AND GLOSS OF TOPCOAT

CONCRETE REPAIR NOTES:

1. ALL EXISTING CONCRETE TO BE REMOVED IS TO BE REMOVED TO NEAT

LINES. ALL SUCH REMOVALS SHALL BE TO NEAT SAW CUTS TO PROVIDE

CLEAN STRAIGHT SURFACES AT INTERFACES BETWEEN NEW CONCRETE AND

REMAINING CONCRETE. PATCHING REQUIRED DUE TO POOR REMOVAL

PRACTICES WILL BE AT THE DIRECTION OF THE ENGINEER AND AT THE

CONTRACTORS EXPENSE.

2. ALL CONCRETE REMOVALS SHALL COMMENCE WITH A NEAT 3/4” DEEP,

STRAIGHT SAW CUT. ALL SAW CUTS SHALL TERMINATE AT A 90 DEG RIGHT

ANGLE. SAW CUTS SHALL NOT OVERLAP. DO NOT CUT EXISTING

REINFORCING.

3. EXPOSED REINFORCING SHALL BE CLEANED TO BARE METAL BY

SANDBLASTING AND BASF/MASTER BUILDERS MASTEREMACO P124 OR

APPROVED EQUAL APPLIED TO EXPOSED STEEL.

4. ALL SURFACES OF OLD CONCRETE AGAINST WHICH NEW PATCHING MORTAR

OR REPAIR CONCRETE IS TO BE PLACED SHALL BE THOROUGHLY CLEANED

AND ALL LOOSE MATERIAL SHALL BE REMOVED BY DRY SWEEPING AND

BLOWING OUT WITH CLEAN, DRY COMPRESSED AIR AND BASF/MASTER

BUILDERS MASTEREMACO P124 OR APPROVED EQUAL APPLIED TO

SURFACES.

5. ALL EXISTING REINFORCING BARS THAT ARE EXPOSED BY CONCRETE

REMOVAL SHALL BE CLEANED AND CAREFULLY INCORPORATED INTO THE

NEW WORK, EXCEPT WHERE THE REINFORCING SECTION LOSS IS 25% OR

MORE DETERIORATED THEN THE EXISTING REINFORCING SHALL BE

REPLACED AS DIRECTED BY THE ENGINEER.

6. THE CONCRETE ANCHORS REQUIRED SHALL HAVE A MINIMUM PULL OUT OF

5000 LBS. BASED ON 4000 PSI CONCRETE. THE ANCHORS SHALL BE

GALVANIZED AND SHALL BE INCLUDED INSTALLED ACCORDING TO

RECOMMENDATIONS OF THE MANUFACTURER.

7. THE WELDED WIRE FABRIC SHALL BE ASTM A185 AND GALVANIZED AS PER

ASTM A-641. THE WWF WIRES SHALL BE SPACED 3X3 OR 4X4 AND THE WIRES

SHALL HAVE A NOMINAL AREA OF 0.14 TO 0.029 SQUARE INCHES INCLUSIVE,

EXAMPLE “WWF 3X3-W1.4XW2.9”

8. WHERE REINFORCEMENT HAS BEEN EXPOSED AND CLEARANCE AROUND THE

PERIPHERY OF THE EXISTING BAR IS PROVIDED NO SUPPLEMENTAL

REINFORCING IS REQUIRED, EXCEPT WHERE EXISTING REINFORCING

DENSITY AND PATTERN ARE SUCH THAT INDIVIDUAL OPEN SPACES BETWEEN

BARS ARE OF 1.5 SF OR LARGER. FOR THIS CONDITION ½” DIA. CONCRETE

ANCHORS AND WELDED WIRE FABRIC SHALL BE INSTALLED AT THE RATE OF

ONE CONCRETE ANCHOR WITH WWF PER EACH 1.5 SF OF AREA WITHIN EACH

OPEN SPACE.

9. FINISH REPAIR SPALL WITH BASF/MASTER BUILDERS MASTEREMACO N425 OR

APPROVED EQUAL.

10. USE ALL PRODUCTS IN STRICT ACCORDANCE WITH MANUFACTURER’S

RECOMMENDATION INCLUDING ANY AND ALL SURFACE PREPARATION.

EPOXY INJECTION

1. INJECT CRACKS WIDER THAN 0.05 INCH.

2. CLEAN CRACKS WITH OIL-FREE COMPRESSED AIR OR LOW-PRESSURE

WATER TO REMOVE LOOSE PARTICLES OR AS RECOMMENDED BY

MANUFACTURER. CLEAN AREAS TO RECEIVE CAPPING ADHESIVE OF OIL, DIRT,

AND OTHER SUBSTANCES THAT WOULD INTERFERE WITH BOND.

3. PLACE INJECTION PORTS AS RECOMMENDED BY EPOXY MANUFACTURER,

SPACING NO FARTHER APART THAN THICKNESS OF MEMBER BEING INJECTED.

SEAL INJECTION PORTS WITH CAPPING ADHESIVE. USE BASF/MASTER BUILDERS

MASTEREMACO ADH 327 RS OR APPROVED EQUAL FOR INJECTION PORTS.

4. SEAL CRACKS AT EXPOSED SURFACES WITH A RIBBON OF CAPPING

ADHESIVE AT LEAST 1/4 INCH THICK BY 1 INCH WIDER THAN CRACK.

5. INJECT EPOXY ADHESIVE, BEGINNING AT WIDEST PART OF CRACK AND

WORKING TOWARD NARROWER PARTS. INJECT ADHESIVE INTO PORTS TO

REFUSAL, CAPPING ADJACENT PORTS WHEN THEY EXTRUDE EPOXY. CAP

INJECTED PORTS AND INJECT THROUGH ADJACENT PORTS UNTIL CRACK IS

FILLED.

6. AFTER EPOXY ADHESIVE HAS SET, REMOVE INJECTION PORTS AND GRIND

SURFACES SMOOTH.

7. USE BASF/MASTER BUILDERS MASTERINJECT 1380 OR APPROVED EQUAL ON

EPOXY INJECTION REPAIRS.

MARK REVISION DATE

SPECIAL INSPECTION

1. SPECIAL INSPECTION IN ACCORDANCE WITH SECTION 1704 OF THE 2015

INTERNATIONAL BUILDING CODE, AND ICBO MODEL PROGRAM FOR

SPECIAL INSPECTION.

2. THE OWNER WILL EMPLOY AN APPROVED AGENCY TO PERFORM THE

SPECIAL INSPECTION SERVICES.

3. SPECIAL INSPECTION WILL BE PERFORMED IN ACCORDANCE WITH AND IN

ADDITION TO THE INSPECTION AND TESTING REQUIRED BY THE

DRAWINGS AND SPECIFICATIONS.

4. THE FOLLOWING ITEMS ARE INCLUDED IN THE SPECIAL INSPECTION:

CONCRETE: AIR-ENTRAINMENT

SLUMP

COMPRESSIVE STRENGTH TESTING

REINFORCING PLACEMENT

POLYMER MORTAR PLACEMENT VISUAL INSPECTION

SOIL: PAVEMENT SUBGRADE AND FILL COMPACTION.

WATER

WATER

WATER

ELECTRIC

ELECTRIC

ELECTRIC

ELECTRIC

RIM=1049.03

FL=1048.25 4" CLAY SW

RIM=1051.76

FL=1049.13 4" CLAY EAST

FL=1047.22 8" CLAY N-SW

RIM=1051.42

FL=1048.42 15" RCP WEST

FL=1049.03 8" HDPE SE

SUMP=1047.62

RIM=1051.34

FL=1048.00 4" PVC EAST

FL=1049.06 4" CLAY SE

FL=1048.49 4" DIP NE

FL=1047.83 4" DIP NW

RIM=1051.05

UNABLE TO OPEN

RIM=1051.04

UNABLE TO OPEN

RIM=1051.19

FL=1048.65 6" STEEL EAST

FL=1048.60 6" STEEL WEST

FL=1048.78 4" STEEL SOUTH

RIM=1051.07

FL=1049.77 4" STEEL SOUTH

RIM=1052.10

FL=1049.48 4" STEEL SOUTH

SUMP=1048.54 (SILTED)

RIM=1051.35

FL=1049.42 6" DIP NE

FL=1049.17 6" DIP WEST

RIM=1051.64

TUNNEL FLOOR=1044.12

TUNNEL TOP=1050.96

TOP 9" THICK

TUNNEL 48" WIDE BY 73" TALL

RIM=1051.92

TUNNEL FLOOR=1045.54

TUNNEL 48" WIDE BY 71" TALL

END OF TUNNEL 1.75' SE

RIM=1051.69

TUNNEL FLOOR=1044.44

TUNNEL TOP=1051.26

TOP 9" THICK

TUNNEL 48" WIDE BY 73" TALL

RIM=1053.19

FL=1048.13 8" CLAY E-W

CP

CP

CP

CP

CP

CP

G

GG

BM500

F.F.E.=1055.96

AT DOCK

F.F.E.=1051.93

F.F.E.=1049.58

F.F.E.=1049.48

F.F.E.=1052.10

F.F.E.=1051.86

F.F.E.=1051.76

BUILDING F.F.E.=1049.12

CONCRETE

CONCRETE

CONCRETE

CONCRETE

℄ 8" CONCRETE WALL

CONC. STEPS

RAMP

FUEL PUMPS

BREATHER

FACE OF FOUNDATION(TYP.)

FACE OF BUILDING(TYP.)

WINDOW SILL ELEV.=1055.75

WINDOW SILL ELEV.=1053.78

BASKETBALL HOOP

(FOOTING ONLY)

PROBED TOP/EDGE OF TUNNEL

TOP=1050.99+/- SLOT DRAIN

BOTTOM SILTED

F.F.E.=1052.42

B1

B2

B3

B4

G R

A V E L

G R

AV

EL

C O N C R

ETE

RAMP

WW

.0

10+50

11+00 11+00

11+50 11+50

12+00 12+00

12+50 12+50

13+00

13+50

13+50

13+95.56

13+95.56

12+15.19

20+00

12+99.72

13+72.47

20+41.52

20+50

20+50

TUNNEL 1

C/L

TUNNEL 1

C/L

TUNNEL 2

C/L

TUNNEL 2

C/L

S1.02

10+00 10+00

20+95.16

20+95.16

S1.02

S1.03

S1.03

S1.04

S1.04

S1.05

S1.06

S1.07

S3.02

S3.02

S3.01

REMOVAL AND REPLACEMENT

OF 22FT OF STRUCTURAL LID

AND PAVEMENT WITH NEW

HATCH

NEW SUMP PIT FIELD

VERIFY LOW POINT

REMOVAL AND

REPLACEMENT OF 22FT OF

STRUCTURAL LID - NO HATCH

REMOVAL AND REPLACEMENT

OF 22FT OF STRUCTURAL LID

AND PAVEMENT WITH NEW

HATCH

NEW SUMP PIT FIELD

VERIFY LOW POINT

CONSTRUCTION NOTES

1. COORDINATE ALL EQUIPMENT, ENTRY TIMES, AND EXIT TIMES WITH CM/CCF.

2. WHILE WORKING IN YARD, NO OTHER OPENINGS IN THE TUNNEL ARE

PERMITTED TO PREVENT POSSIBLE ESCAPE ROUTES.

3. CONTRACTOR TO TEMPORARILY SEAL ANY HOLES IN TUNNEL AT THE END OF

EACH WORK DAY.

4. CONTRACTOR TO REMOVE ALL TOOLS AND EQUIPMENT AT THE END OF EACH

WORK DAY.

5. COORDINATE ALL WORK AND SECURITY WITH CM/CCF.

6. PROTECT IN PLACE ALL UTILITIES, LIGHT POLES, ETC. AS REQUIRED DURING

CONSTRUCTION.

7. CONTRACTOR TO SOUND TOP OF EXISTING STRUCTURAL SLAB AND VISUALLY

INSPECT FOR DELAMINTIAON, EXPOSED REBAR, OR SPALLING AND REPAIR PER

NOTES PRIOR TO PLACING NEW PAVEMENT

PROJECT NUMBER

DATE

SHEET NO.

SHEET TITLE

400 E COURT AVE.

SUITE 140.

DES MOINES, IOWA 50309

515-243-4477 www.shuck-britson.com

SNYDER & ASSOCIATES, INC.

231 BENNETT AVE.

COUNCIL BLUFFS, IOWA 51503

P: 712-322-3202 www.snyder-associates.com

Project Engineer

Mechanical, Electrical and Plumbing Engineer

ALVINE ENGINEERING

400 E. COURT AVE

SUITE 130

DES MOINES, IA 50309

www.alvine.com

C

U s e rs

\d tr ip p \D o c u m e n ts

\1 .0

.1

T U

N N

E L

(R d tr ip p s h u c k -b ri ts o n .c o m

.r v t

/9 /2

:4

:1

P

M

D O

C C

C F

T U

N N

E L R

E P

A

IR

R

E P

L A

C E

M E

N T

M A

IN

B

L D

G

S W

W

IN

G

10/10/2025

125.0278.10

S1.01

N th

S t, C la ri n d a

IA

TUNNEL PLAN

100% CONSTRUCTION DOCUMENTS

IO

W

A D

E P

A R

T M

E N

T O

F A

D M

IN

IS

T R

A T

IV

E

S E

R V

IC

E

S

D A

S

N

1" = 20'-0"

1 TUNNEL PLAN

MARK REVISION DATE

. 0

11+00

11+00

TUNNEL 1

C/L

TUNNEL 1

C/L

B-1 B-1

A-1A-1

10+00

10+00

10+10 10+20 10+30 10+40 10+60 10+70 10+80 10+90

EXISTING BUILDING

" 2 /S1.02

3 /S1.02

S1.02

S3.04

TUNNEL LID AND CONCRETE

PAVEMENT TOPPING SLAB TO

REMAIN PROTECTED IN PLACE

WHERE SURROUNDED BY GRASS -

TYP REFER TO CIVIL

10+50

10+50

11+00

11+00

TUNNEL 1

C/L

TUNNEL 1

C/L

B-1 B-1

A-1A-1

10+00

10+00

10+10 10+20 10+30 10+40 10+60 10+70 10+80 10+90

EXISTING BUILDING

2 /S1.02

3 /S1.02

S1.02

CROSSING BEAM

EXISTING 16" DIA. PIPE

S3.01

S2.03

10+50

10+50

11+00

11+00

10+00

10+00 10+10 10+20 10+30 10+40 10+60 10+70 10+80 10+90

EXISTING BUILDING WALL

S1.02

1044.44

EXISTING 2' WIDE X 3'

TALL CONCRETE BEAM

EXISTING 16" DIA. PIPE

10+50

10+50

11+00

11+00

10+00

10+0010+1010+2010+3010+4010+6010+7010+8010+90

EXISTING BUILDING WALL5

S1.02

NO REPAIR REQUIRED HERE

REPAIR KEY

EXISTING CRACK - PREPARE AND

REPAIR CONCRETE CRACK (SEE

DETAILS)

EXISTING SPALL - PREPARE AND

REPAIR CONCRETE SPALL (SEE

DETAILS)

EXISTING SCALING AND

HONEYCOMB - PREPARE AND REPAIR

CONCRETE CONSOLIDATION OR

SCALING (SEE DETAILS)

EXISTING CONSTRUCTION JOINT

PROVIDE CRACK REPAIRS WHERE

CRACKS EXCEED 0.05" WIDTH (SEE

DETAILS)

NOTES:

REMOVE AND REPLACE ALL EXISTING PIPE

SUPPORTS.

CLEAN THE FLOOR OF ALL DIRT, DEBRIS, TRASH,

ETC.

REMOVE ALL ABANDONED UTILITIES AND

SUPPORTS OR ANY OTHER ITEMS WITHIN THE

TUNNEL THAT ARE NO LONGER BEING USED- TYP.

ALL CONCRETE REPAIRS TO BE MARKED AND

APPROVED FOR QUANTITY BY CM/CCF AND

ENGINEER PRIOR TO PERFORMING REPAIRS.

CONCRETE ISSUES SHOWN ON THE DRAWINGS

DO NOT NECESSARILY CORRELATE TO REPAIRS

THAT WILL BE MADE BUT TO OBSERVATIONS

MADE ON EXISTING CONCRETE DETERIORATION

TUNNEL 1

C/L

B-1 A-1

(+/-) 4' - 0"

(+/-) 2' - 0" (+/-) 2' - 0"

(+/-) 8"(+/-) 8"

SIDEWALK / PAVEMENT / GRADE

(SEE CIVIL)

PROJECT NUMBER

DATE

SHEET NO.

SHEET TITLE

400 E COURT AVE.

SUITE 140.

DES MOINES, IOWA 50309

515-243-4477 www.shuck-britson.com

SNYDER & ASSOCIATES, INC.

231 BENNETT AVE.

COUNCIL BLUFFS, IOWA 51503

P: 712-322-3202 www.snyder-associates.com

Project Engineer

Mechanical, Electrical and Plumbing Engineer

ALVINE ENGINEERING

400 E. COURT AVE

SUITE 130

DES MOINES, IA 50309

www.alvine.com

C

U s e rs

\d tr ip p \D o c u m e n ts

\1 .0

.1

T U

N N

E L

(R d tr ip p s h u c k -b ri ts o n .c o m

.r v t

/9 /2

:4

:1

P

M

D O

C C

C F

T U

N N

E L R

E P

A

IR

R

E P

L A

C E

M E

N T

M A

IN

B

L D

G

S W

W

IN

G

10/10/2025

125.0278.10

S1.02

N th

S t, C la ri n d a

IA

TUNNEL PLANS AND ELEVATIONS

100% CONSTRUCTION DOCUMENTS

IO

W

A D

E P

A R

T M

E N

T O

F A

D M

IN

IS

T R

A T

IV

E

S E

R V

IC

E

S

D A

S

3/16" = 1'-0"

4 TUNNEL 1 - LID 10+00 TO 11+00

3/16" = 1'-0"

1 TUNNEL 1 - FLOOR 10+00 TO 11+00

3/16" = 1'-0"

2 TUNNEL 1 - WEST WALL 10+00 TO 11+00

3/16" = 1'-0"

3 TUNNEL 1 - EAST WALL 10+00 TO 11+00

1/2" = 1'-0"

5 TUNNEL 1 - 10+00 TO 11+00 (LOOKING NE)

N N

11+00

11+00

11+50

11+50

12+00

12+00

TUNNEL 1

C/L

TUNNEL 1

C/L

B-1 B-1

A-1A-1

11+20 11+30 11+40 11+60 11+70 11+80 11+9011+10

2 /S1.03

3 /S1.03

4' - 6"4' - 0"1' - 6"

OPEN

EXISTING 4" DIA. PIPE

S3.04

S3.03

22' - 0"

HATCH REMOVAL AND

REPLACEMENT

LID REMOVAL AND

REPLACEMENT

TUNNEL LID AND CONCRETE

PAVEMENT TOPPING SLAB TO

REMAIN PROTECTED IN PLACE

WHERE SURROUNDED BY

GRASS - TYP REFER TO CIVIL

S1.03

S2.02

S2.02

S2.02

S2.02 2

S2.02

TUNNEL LID AND CONCRETE

PAVEMENT TOPPING SLAB TO BE

REMOVED AND REPLACED ONLY AS

NEEDED FOR THE CONSTRUCTION

ACCESS REMOVALS BACK TO THE

NEAREST SIDEWALK PANEL POINT

OR AS NEEDED FOR DAMAGE

RESULTING FROM CONSTRUCTION

MIN. 2' - 0"

S2.02

LL7x4x3/8 L.L.H. x 24'0"

LL7x4x3/8 L.L.H. x 24'0"

CURRENT WALL TEMPORARY SHORING IS DESIGNED FOR 400 LBS /FT.

LATERAL FORCE TO HOLD BACK THE SOIL PRESSURES ON THE

UNSUPPORTED WALL IN ITS TEMPORARY CONDITION. NO HEAVY

EQUIPMENT EXCEEDING 100 PSF SHALL BE ALLOWED WITHIN 6FT OF THE

FACE OF THE TEMPORARY TUNNEL LID EXCAVATION WHILE THE

STRUCTURAL SLAB IS REMOVED UNTIL AFTER THE NEW SLAB IS POURED

AND CURED.

1' - 0"

1' - 0"

11+00

11+00

11+50

11+50

12+00

12+00

TUNNEL 1

C/L

TUNNEL 1

C/L

B-1 B-1

A-1A-1

S1.03

11+20 11+30 11+40 11+60 11+70 11+80 11+9011+10

2 /S1.03

3 /S1.03

EXISTING 4" DIA. PIPE

S3.04

EXISTING 6" DIA. PIPE

14" X14" CONC. BEAM

S2.03

11+00

11+00 11+50 12+00

1052.02

1044.44

S1.03

11+20 11+30 11+40 11+60 11+70 11+80 11+9011+10

11" 5' - 0" 4' - 1"

1051.26 1051.69

11+00

11+0011+5012+00

S1.03

11+2011+3011+4011+6011+7011+8011+90 11+10

11"5' - 0"4' - 1"

REPAIR KEY

EXISTING CRACK - PREPARE AND

REPAIR CONCRETE CRACK (SEE

DETAILS)

EXISTING SPALL - PREPARE AND

REPAIR CONCRETE SPALL (SEE

DETAILS)

EXISTING SCALING AND

HONEYCOMB - PREPARE AND REPAIR

CONCRETE CONSOLIDATION OR

SCALING (SEE DETAILS)

EXISTING CONSTRUCTION JOINT

PROVIDE CRACK REPAIRS WHERE

CRACKS EXCEED 0.05" WIDTH (SEE

DETAILS)

NOTES:

REMOVE AND REPLACE ALL EXISTING PIPE

SUPPORTS.

CLEAN THE FLOOR OF ALL DIRT, DEBRIS, TRASH,

ETC.

REMOVE ALL ABANDONED UTILITIES AND

SUPPORTS OR ANY OTHER ITEMS WITHIN THE

TUNNEL THAT ARE NO LONGER BEING USED- TYP.

ALL CONCRETE REPAIRS TO BE MARKED AND

APPROVED FOR QUANTITY BY CM/CCF AND

ENGINEER PRIOR TO PERFORMING REPAIRS.

CONCRETE ISSUES SHOWN ON THE DRAWINGS

DO NOT NECESSARILY CORRELATE TO REPAIRS

THAT WILL BE MADE BUT TO OBSERVATIONS

MADE ON EXISTING CONCRETE DETERIORATION

TUNNEL 1

C/L

B-1 A-1

(+/-) 4' - 0"

(+/-) 2' - 0" (+/-) 2' - 0" (+/-) 8"

(+/-) 8"

SIDEWALK / PAVEMENT / GRADE

(SEE CIVIL)

PROJECT NUMBER

DATE

SHEET NO.

SHEET TITLE

400 E COURT AVE.

SUITE 140.

DES MOINES, IOWA 50309

515-243-4477 www.shuck-britson.com

SNYDER & ASSOCIATES, INC.

231 BENNETT AVE.

COUNCIL BLUFFS, IOWA 51503

P: 712-322-3202 www.snyder-associates.com

Project Engineer

Mechanical, Electrical and Plumbing Engineer

ALVINE ENGINEERING

400 E. COURT AVE

SUITE 130

DES MOINES, IA 50309

www.alvine.com

C

U s e rs

\d tr ip p \D o c u m e n ts

\1 .0

.1

T U

N N

E L

(R d tr ip p s h u c k -b ri ts o n .c o m

.r v t

/9 /2

:4

:1

P

M

D O

C C

C F

T U

N N

E L R

E P

A

IR

R

E P

L A

C E

M E

N T

M A

IN

B

L D

G

S W

W

IN

G

10/10/2025

125.0278.10

S1.03

N th

S t, C la ri n d a

IA

TUNNEL PLANS AND ELEVATIONS

100% CONSTRUCTION DOCUMENTS

IO

W

A D

E P

A R

T M

E N

T O

F A

D M

IN

IS

T R

A T

IV

E

S E

R V

IC

E

S

D A

S

3/16" = 1'-0"

4 TUNNEL 1 - LID 11+00 TO 12+00

3/16" = 1'-0"

1 TUNNEL 1 - FLOOR 11+00 TO 12+00

3/16" = 1'-0"

2 TUNNEL 1 - WEST WALL 11+00 TO 12+00

3/16" = 1'-0"

3 TUNNEL 1 - EAST WALL 11+00 TO 12+00

1/2" = 1'-0"

5 TUNNEL 1 - 11+00 TO 12+00 (LOOKING NE)

N

12+00

12+00

12+50

12+50

13+00

13+00

12+15.19

20+00

12+99.72

TUNNEL 1

C/L

TUNNEL 1

C/L

B-1

B-1

A-1

A-1

TUNNEL 2

C/L

TUNNEL 2

C/L

B-2 A-2

S1.04

12+20 12+30 12+40 12+60 12+70 12+80 12+9012+10

2 /S1.04

3 /S1.04

EX.4" DIA. PIPE

EX.4" DIA. PIPE

EX.12" DIA. PIPE

S2.02

SIM.

12+00

12+00

12+50

12+50

13+00

13+00

12+15.19

20+00

12+99.72

TUNNEL 1

C/L

TUNNEL 1

C/L

B-1

B-1

A-1

A-1

TUNNEL 2

C/L

B-2 A-2

2 /S1.04

3 /S1.04

S1.04

12+20 12+30 12+40 12+60 12+70 12+80 12+9012+10

EX.4" DIA. PIPE

EX.4" DIA. PIPE

EX.12" DIA. PIPE

NEW SUMP PIT WITH STEEL

GRATING - FIELD VERIFY LOW

POINT - POUR TOP OF NEW PIT AND

SLAB SHORT OF EXISTING TUNNEL

SLAB BY THICKNESS OF NEW

GRATING

S2.03

PROVIDE GUTTER TROUGH

TO SUMP FROM EXISTING

GUTTERS - TYP.

S2.03

12+00 12+5012+15.19

S1.04

12+20 12+30 12+40 12+60 12+70 12+80 12+9012+10

EX. PATCHEX. 4" DIA. PIPE

EX. 12" DIA. PIPE

EX. 4" DIA. PIPE

EX. 4" DIA. PIPE PATCH

S3.03

S3.02

12+0012+50 12+15.19

S1.04

12+2012+3012+4012+6012+7012+8012+90 12+10

EX. PATCH EX. 4" DIA. PIPE PATCH

S3.03

REPAIR KEY

EXISTING CRACK - PREPARE AND

REPAIR CONCRETE CRACK (SEE

DETAILS)

EXISTING SPALL - PREPARE AND

REPAIR CONCRETE SPALL (SEE

DETAILS)

EXISTING SCALING AND

HONEYCOMB - PREPARE AND REPAIR

CONCRETE CONSOLIDATION OR

SCALING (SEE DETAILS)

EXISTING CONSTRUCTION JOINT

PROVIDE CRACK REPAIRS WHERE

CRACKS EXCEED 0.05" WIDTH (SEE

DETAILS)

NOTES:

REMOVE AND REPLACE ALL EXISTING PIPE

SUPPORTS.

CLEAN THE FLOOR OF ALL DIRT, DEBRIS, TRASH,

ETC.

REMOVE ALL ABANDONED UTILITIES AND

SUPPORTS OR ANY OTHER ITEMS WITHIN THE

TUNNEL THAT ARE NO LONGER BEING USED- TYP.

ALL CONCRETE REPAIRS TO BE MARKED AND

APPROVED FOR QUANTITY BY CM/CCF AND

ENGINEER PRIOR TO PERFORMING REPAIRS.

CONCRETE ISSUES SHOWN ON THE DRAWINGS

DO NOT NECESSARILY CORRELATE TO REPAIRS

THAT WILL BE MADE BUT TO OBSERVATIONS

MADE ON EXISTING CONCRETE DETERIORATION

TUNNEL 1

C/L

B-1 A-1

(+/-) 4' - 0"

(+/-) 2' - 0"

(+/-) 2' - 0"

(+/-) 8" (+/-) 8"

SIDEWALK / PAVEMENT / GRADE

(SEE CIVIL)

PROJECT NUMBER

DATE

SHEET NO.

SHEET TITLE

400 E COURT AVE.

SUITE 140.

DES MOINES, IOWA 50309

515-243-4477 www.shuck-britson.com

SNYDER & ASSOCIATES, INC.

231 BENNETT AVE.

COUNCIL BLUFFS, IOWA 51503

P: 712-322-3202 www.snyder-associates.com

Project Engineer

Mechanical, Electrical and Plumbing Engineer

ALVINE ENGINEERING

400 E. COURT AVE

SUITE 130

DES MOINES, IA 50309

www.alvine.com

C

U s e rs

\d tr ip p \D o c u m e n ts

\1 .0

.1

T U

N N

E L

(R d tr ip p s h u c k -b ri ts o n .c o m

.r v t

/9 /2

:4

:1

P

M

D O

C C

C F

T U

N N

E L R

E P

A

IR

R

E P

L A

C E

M E

N T

M A

IN

B

L D

G

S W

W

IN

G

10/10/2025

125.0278.10

S1.04

N th

S t, C la ri n d a

IA

TUNNEL PLANS AND ELEVATIONS

100% CONSTRUCTION DOCUMENTS

IO

W

A D

E P

A R

T M

E N

T O

F A

D M

IN

IS

T R

A T

IV

E

S E

R V

IC

E

S

D A

S

3/16" = 1'-0"

4 TUNNEL 1 - LID 12+00 TO 13+00

3/16" = 1'-0"

1 TUNNEL 1 - FLOOR 12+00 TO 13+00

3/16" = 1'-0"

2 TUNNEL 1 - WEST WALL 12+00 TO 13+00

3/16" = 1'-0"

3 TUNNEL 1 - EAST WALL 12+00 TO 13+00

1/2" = 1'-0"

5 TUNNEL 1 - 11+00 TO 12+00 (LOOKING NE)

N

1051.0

1052.0

13+00

13+00

13+50

13+50

13+95.56 13+95.56

12+99.72

13+72.47

TUNNEL 1

C/L

TUNNEL 1

C/L

B-1

B-1 A-1

A-1

13+4013+3013+2013+10 13+60

13+70

13+90 13+90

13+80 13+80

2 /S1.05

5 /S1.05

/S

.0

/S

.0

S1.05

EXISTING BUILDING

REPAIR JOINT AT

BUILDING

NEW SUMP PIT WITH STEEL GRATING -

FIELD VERIFY LOW POINT - POUR TOP

OF NEW PIT AND SLAB SHORT OF

EXISTING TUNNEL SLAB BY

THICKNESS OF NEW GRATING

' - 0

S2.03

PROVIDE GUTTER TROUGH

TO SUMP FROM EXISTING

GUTTERS - TYP.

S2.03

S2.03

13+00

13+00

13+50

13+5013+4013+3013+2013+10 13+60 13+70

S1.05

EX. 4" DIA. PIPE

GROUTED

13+95.5613+9013+80

EXISTING BUILDING

REPAIR JOINT AT BUILDING

13+0013+50 13+40 13+30 13+20 13+1013+6013+70

S1.05

EXISTING PIPE UTILITIES TO BLDG.

S3.02

13+95.56 13+90 13+80

EXISTING BUILDING

REPAIR JOINT

AT BUILDING

TUNNEL 1

C/LB-1 A-1

SIDEWALK / PAVEMENT / GRADE

(SEE CIVIL)

(+/-) 4' - 0"

(+/-) 8" (+/-) 8"

(+/-) 2' - 0" (+/-) 2' - 0"

13+00

13+00

13+50

13+50

13+95.56 13+95.56

12+99.72

13+72.47

TUNNEL 1

C/L

TUNNEL 1

C/L

B-1

B-1 A-1

A-1

13+4013+3013+2013+10 13+60

13+70

13+90 13+90

13+80

2 /S1.05

5 /S1.05

/S

.0

/S

.0

S1.05

EXISTING BUILDING

OPEN

PIPE SUPPORT

REPAIR BLDG. JT

CONSTRUCTION JT.

CRACK IN LID

S3.02

S3.01

S3.01

S3.01

22' - 0"

HATCH REMOVAL AND

REPLACEMENT

LID REMOVAL AND

REPLACEMENT

S2.02

SIM.

S2.02

S2.02

S2.02

S2.02

MIN. 2' - 0"

S2.02

LL7x4x3/8 L.L.H. x 24'0"

LL7x4x3/8 L.L.H. x 24'0"

CURRENT WALL TEMPORARY SHORING IS DESIGNED FOR 400 LBS /FT.

LATERAL FORCE TO HOLD BACK THE SOIL PRESSURES ON THE

UNSUPPORTED WALL IN ITS TEMPORARY CONDITION. NO HEAVY

EQUIPMENT EXCEEDING 100 PSF SHALL BE ALLOWED WITHIN 6FT OF THE

FACE OF THE TEMPORARY TUNNEL LID EXCAVATION WHILE THE

STRUCTURAL SLAB IS REMOVED UNTIL AFTER THE NEW SLAB IS POURED

AND CURED.

1' - 0"

1' - 0"

REPAIR KEY

EXISTING CRACK - PREPARE AND

REPAIR CONCRETE CRACK (SEE

DETAILS)

EXISTING SPALL - PREPARE AND

REPAIR CONCRETE SPALL (SEE

DETAILS)

EXISTING SCALING AND

HONEYCOMB - PREPARE AND REPAIR

CONCRETE CONSOLIDATION OR

SCALING (SEE DETAILS)

EXISTING CONSTRUCTION JOINT

PROVIDE CRACK REPAIRS WHERE

CRACKS EXCEED 0.05" WIDTH (SEE

DETAILS)

NOTES:

REMOVE AND REPLACE ALL EXISTING PIPE

SUPPORTS.

CLEAN THE FLOOR OF ALL DIRT, DEBRIS, TRASH,

ETC.

REMOVE ALL ABANDONED UTILITIES AND

SUPPORTS OR ANY OTHER ITEMS WITHIN THE

TUNNEL THAT ARE NO LONGER BEING USED- TYP.

ALL CONCRETE REPAIRS TO BE MARKED AND

APPROVED FOR QUANTITY BY CM/CCF AND

ENGINEER PRIOR TO PERFORMING REPAIRS.

CONCRETE ISSUES SHOWN ON THE DRAWINGS

DO NOT NECESSARILY CORRELATE TO REPAIRS

THAT WILL BE MADE BUT TO OBSERVATIONS

MADE ON EXISTING CONCRETE DETERIORATION

PROJECT NUMBER

DATE

SHEET NO.

SHEET TITLE

400 E COURT AVE.

SUITE 140.

DES MOINES, IOWA 50309

515-243-4477 www.shuck-britson.com

SNYDER & ASSOCIATES, INC.

231 BENNETT AVE.

COUNCIL BLUFFS, IOWA 51503

P: 712-322-3202 www.snyder-associates.com

Project Engineer

Mechanical, Electrical and Plumbing Engineer

ALVINE ENGINEERING

400…

This is the start of the file's text. The full file is on GovTribe.