RFB936100-01 - Drawings.pdf
PDF 3 MB Posted
- Attached to
- DOC MPCF Building 20 (MWU) Elevator Replacement
- Solicitation number
- RFB936100-01
- Issued by
- Henry County, Iowa
About this file
This document contains drawings, specifications, and other information related to the Iowa Department of Administrative Services' bid for the replacement of elevator "A" at the Mount Pleasant Correctional Facility located at 1200 E. Washington St. Mount Pleasant, Iowa 52641. The project involves the demolition and replacement of the existing elevator, including the cab, controls, drive system, and supporting infrastructure. The work must comply with various building codes and accessibility requirements. Bids are due on 04/25/2024, and the project is issued for bidding.
The drawings and specifications provide detailed information on the demolition and new construction work required, including the mechanical, electrical, and architectural components. Key details include the installation of a new elevator cab and frame, the removal of the existing elevator controller and drive system, and the installation of a new sump pump in the elevator pit. The project also requires the patching and preparation of existing wall and floor openings, as well as the painting of select surfaces.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E. WASHINGTON ST
L
IL
A C
D R
S G
R A
N D
A V
E
HOSPITAL AVE
H O
S P
IT
A
L A
V E
PROJECT LOCATION
PROJECT LOCATION
CONEX BOX LOCATION
DUMPSTER LOCATION
2015 International Building Code 2015 International fire Code 2015 International Existing Building Code 2010 Americans with Disabilities Act State Mechanical Code State Plumbing Code State Electrical Code ASME A17.1 Safety Code for Elevators and Escalators State of Iowa Elevator Safety Rules
IBC Chapter 3 – Use and Occupancy Classification The use and occupancy classification of the existing building will remain unchanged.
IBC Chapter 5 – General Building Heights and Areas Existing building height and area to remain unchanged.
IBC Chapter 6 – Types of Construction The type of construction for the existing building will remain unchanged.
IBC Chapter 7 – Fire and Smoke Protection Features Existing elevator shaft is considered to be 2-hour construction.
IBC Chapter 10 – Means of Egress Means of egress will remain unchanged in the existing building.
APPLICABLE CODES
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
SHEET INDEX CERTIFICATIONS
H
BA D E FC G H
AAuuttooddeesskk RReevviitt 22002233
/2
/2
:3 :5
P
M
A u to d e s k D o c s /2
I A
D A
S
D O
C M
P C
F B ld g
E le v a to r R e p /2
-A
-R .r v t
IA DAS - DOC MPCF Bldg 20 Elevator Rep
Iowa Department of Administrative Services 1200 E Washington St, Mt Pleasant, IA 52641
G000
IA
D
A S
D
O C
M P
C F
B ld g
E le v a to r
R e p
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
C L
IE
N T
P R
O J E
C T
N U
M B
E R
D
A S
.0
E
W a s h in g to n S t, M t P le a s a n t, I A
P R
O J E
C T
N U
M B
E R
IS
S
U E
D F
O R
B
ID
D
IN
G
P R
O J E
C T
I S
S U
E D
A T
E
/2
/2
SHEET LIST
SHEET NAME
GENERAL
G000 COVER SHEET
G001 PROJECT GENERAL INFORMATION
ARCHITECTURAL
AD01 DEMOLITION PLANS
AD02 DEMOLITION PHOTOS
A101 FLOOR PLANS
A310 WALL SECTIONS AND ELEVATIONS
MECHANICAL
M000 MECHANICAL GENERAL INFORMATION
MD100 MECHANICAL DEMO PLAN
M100 MECHANICAL PLAN
M500 MECHANICAL SCHEDULES AND DETAILS
ELECTRICAL
E000 ELECTRICAL GENERAL INFORMATION
ED01 ELECTRICAL DEMOLITION PLANS
E201 ELECTRICAL NEW WORK PLANS
NOT TO SCALEA6
SITE LOCATION
N
DAS # 9361.00
RFB 936100-01
PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL
MY LICENSE RENEWAL DATE IS DECEMBER 31,
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS
OF THE STATE OF IOWA.
PRINTED OR TYPED NAME
SIGNATURE DATE
LICENSE NUMBER
Tyson L. Scheidecker
ALL "M" SERIES SHEETS
21691
MECHANICAL ENGINEER
I HEREBY CERTIFY THAT THE PORTION OF THIS TECHNICAL
SUBMISSION DESCRIBED BELOW WAS PREPARED BY ME OR UNDER
MY DIRECT SUPERVISION AND RESPONSIBLE CHARGE. I AM A DULY
LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF IOWA.
PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL
PRINTED OR TYPED NAME
SIGNATURE
MY LICENSE RENEWAL DATE IS JUNE 30,
DATE
ARCHITECT
LICENSE NUMBER
Cameron L. Manley
ALL "G" AND "A" SERIES SHEETS
06716
PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL
MY LICENSE RENEWAL DATE IS DECEMBER 31,
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS
OF THE STATE OF IOWA.
PRINTED OR TYPED NAME
SIGNATURE DATE
LICENSE NUMBER
Edin Smailovic
ALL "E" SERIES SHEETS
21953
ELECTRICAL ENGINEER
4/25/2024
4/25/2024
4/25/2024
SYMBOLS
& AND
@ AT
# NUMBER or POUND
A
A/E ARCHITECT / ENGINEER
ACP ACOUSTICAL CEILING PANEL
ADA AMERICANS WITH DISABILITIES ACT
ADAAG AMERICANS WITH DISABILITIES ACT
ACCESSIBILITY GUIDELINES
ADD ADDENDUM
ADJ ADJUSTABLE or ADJACENT
ADMIN ADMINISTRATION
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AL or ALUM ALUMINUM
ALT ALTERNATE
AP ACCESS PANEL
APA AMERICAN PLYWOOD ASSOCIATION
APPROX APPROXIMATE (LY)
ASTM AMERICAN SOCIETY FOR TESTING & MATERIALS
AUTO AUTOMATIC (DOOR OPERATOR)
AVE AVENUE
AVG AVERAGE
B
B/O BOTTOM OF
BLDG BUILDING
BLVD BOULEVARD
BRG BEARING
C
CCTV CLOSED CIRCUIT TELEVISION
CG CORNER GUARD
CFCI CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CFOI CONTRACTOR FURNISHED OWNER INSTALLED
CJ CONSTRUCTION/CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG HT CEILING HEIGHT
CLR CLEAR (ANCE)
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONST CONSTRUCTION
CORR CORRIDOR
CPT CARPET
CT CERAMIC TILE
CTRL CONTROL
CF CUBIC FEET
CW COLD WATER
D
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION/ DEMOLISH
DEPT DEPARTMENT
DF DRINKING FOUNTAIN
DIA DIAMETER
DISP DISPENSER
DIV DIVISION
DN DOWN
DTL DETAIL
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
DWGS DRAWINGS
E
EA EACH
EF EPOXY FLOORING or EXHAUST FAN
EJ EXPANSION JOINT
ELEC ELECTRIC / ELECTRICAL
ELEV ELEVATION
EL ELEVATOR
ENGR ENGINEER
EP EPOXY PAINT
EPXY EPOXY
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
F FDN or FNDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FFE FINISH (ED) FLOOR ELEVATION
FHC FIRE HOSE CABINET
FL FLOOR
FLR FLOOR (ING)
FM FM GLOBAL
FRP FIBERGLASS REINFORCED PANEL
FT FOOT (FEET)
FTG FOOTING
FURN FURNITURE
G GA GAGE or GAUGE
GAL GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GWB GYPSUM WALLBOARD
H
HDWD HARDWOOD
HDWR HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR
HT HEIGHT
HVAC HEATING, VENTILATION, AIR CONDITIONING
HW HOT WATER
I
IBC INTERNATIONAL BUILDING CODE
ICC INTERNATIONAL CODE COUNCIL
ID IDENTIFICATION or INSIDE DIAMETER
IN INCHES
INCL INCLUDE
INFO INFORMATION
J
JAN JANITOR
JC JANITOR'S CLOSET
JST JOIST (S)
JT JOINT
ABBREVIATIONS
K
KO KNOCKOUT
L
LAV LAVATORY
LF LINEAR FOOT
LH LEFT HAND
LHR LEFT HAND REVERSE
LLV LONG LEG VERTICAL
LVL LAMINATED VENEER LUMBER
LVT LUXURY VINYL TILE
M
MAINT MAINTENANCE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEZZ MEZZANINE
MFRG MANUFACTURING
MFR MANUFACTURER
MIC MICROPHONE
MIN MINIMUM or MINUTE
MISC MISCELLANEOUS
MO MASONRY OPENING
MTD MOUNTED
MTL METAL
N
N/A NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NIC NOT IN CONTRACT
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENT
NRCA NATIONAL ROOFING CONTRACTORS
ASSOCIATION
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
OPP OPPOSITE
OHD OVERHEAD DOOR
P
P PAINT
PERP PERPENDICULAR
PKWY PARKWAY
PL PLATE or PLASTIC LAMINATE
PLAM PLASTIC LAMINATE
PLWD PLYWOOD
PR PAIR
PREFAB PREFABRICATED
PREFIN PREFINISHED
PREP PREPARE (ATION)
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
R R RAD or RADIUS
RCI ROOF CONSULTANTS INSTITUTE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REINF REINFORCE (D) (ING) (MENT)
REQD REQUIRED
RESIL RESILIENT
RF RADIO FREQUENCY
RH RIGHT HAND
RHR RIGHT HAND REVERSE
RM ROOM
RO ROUGH OPENING
VTR VENT THROUGH ROOF
S
SAN SANITARY
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT
SHT SHEET REFERRING TO PAGES
SIM SIMILAR
SH SHIVE-HATTERY
SOG SLAB ON GRADE
SPEC(S) SPECIFICATION(S)
SQ SQUARE
SQ IN SQUARE INCH
SS SOLID SURFACE or STAINLESS STEEL ST STREET or STONE
STAG STAGGERED
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STRUC STRUCTURE (AL)
SYM SYMMETRICAL
T
T/O TOP OF
T&G TONGUE AND GROOVE
TAN TANGENT
TBD TO BE DETERMINED
TEL TELEPHONE
TEMP TEMPORARY
THRU THROUGH
TV TELEVISION
TYP TYPICAL
U
UL UNDERWRITERS LABORATORIES
UNO UNLESS NOTED OTHERWISE
V
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VT VINYL TILE
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W
W WIDTH
W/ WITH
W/O WITHOUT
WC WATER CLOSET or WALL COVERING WT WALL TILE or WEIGHT
WTR WATER
1. COLOR HAS BEEN USED ON THESE DRAWINGS TO ENHANCE
UNDERSTANDING. PRINTING IN COLOR IS RECOMMENDED TO
ENSURE CLARITY.
2. ANY DAMAGE TO AREAS INSIDE OR OUTSIDE OF THE PROJECT
AREA SHALL BE REPAIRED TO THE STATUS PRIOR TO
CONSTRUCTION AT NO COST TO OWNER.
3. STRUCTURAL STEEL MEMBERS AND DECKING PROFILES, AS
INDICATED ON ARCHITECTURAL DETAILS, ARE DIAGRAMMATIC
AND MAY VARY FROM ACTUAL PROFILES AND SIZES. FIELD
VERIFY EXISTING PROFILE DIMENSIONS WHEN REQUIRED TO
MATCH OR REPLACE EXISTING. NOTE CHANGES REQUIRED TO
ARCHITECTURAL DETAILS IN SHOP DRAWINGS.
4. PROVIDE FOR PROTECTION OF ANY ROOF SURFACES USED
DURING CONSTRUCTION. PROTECTION IS REQUIRED OVER
FULL EXTENT OF THE WORK AREAS. MINIMUM PROTECTION
CONSISTS OF 1/2” PLYWOOD OVER 1” EPS INSULATION.
5. EACH TRADE SHALL PROVIDE TESTED FIRESTOPPING
ASSEMBLIES OR ENGINEERING JUDGMENTS FOR
PENETRATIONS OF THEIR WORK THROUGH FIRE-RATED WALLS
AND FLOOR/CEILING ASSEMBLIES. FIRESTOPPING ASSEMBLIES
ARE TO BE OF DESIGNS THAT PROVIDE THE SCHEDULED FIRE
RATINGS WHEN TESTED IN ACCORDANCE WITH ASTM E119,
ASTM E814, OR UL 1479, AND ARE TO BE INSTALLED BY
INDIVIDUALS TRAINED AND EXPERIENCED WITH INSTALLATION
OF SUCH ASSEMBLIES. PROVIDE SUBMITTALS TO LOCAL
AUTHORITIES AS REQUESTED
6. ALL ELEVATION REFERENCES IN BUILDING DRAWINGS ARE
BASED ON 100’-0” WHICH RELATES TO [XXX.X’] ABOVE SEA
LEVEL ON SITE DRAWINGS.
7. IF COMPLIANCE WITH TWO OR MORE STANDARDS IS SPECIFIED
AND THE STANDARDS ESTABLISH DIFFERENT OR CONFLICTING
REQUIREMENTS FOR MINIMUM QUANTITIES OR QUALITY
LEVELS, COMPLY WITH THE MOST STRINGENT
REQUIREMENT. REFER UNCERTAINTIES AND REQUIREMENTS
THAT ARE DIFFERENT, BUT APPARENTLY EQUAL, TO
ARCHITECT FOR A DECISION BEFORE PROCEEDING.
8. BUILDING CONTAINS HAZARDOUS MATERIAL SUCH AS
ASBESTOS AND LEAD PAINT. SUPPLEMENTAL HAZARDOUS
MATERIAL REPORT IS PROVIDED IN THE BID DOCUMENTS AS A
SEPARATE ATTACHMENT. REFER TO HAZARDOUS MATERIAL
REPORT FOR EXTENTS OF TESTING AND RESULTS. PER
REPORT, ELEVATOR BRAKE PADS ARE PRESUMED TO BE
ASBESTOS-CONTAINING, AND CIRCUIT BREAKER BOARDS IN
PENTHOUSE ARE ASBESTOS-CONTAINING; THESE WILL BE
BAGGED AND REMOVED AS PART OF THE ELEVATOR PACKAGE.
9. ABATEMENT WORK WILL BE UNDER SEPARATE CONTRACT.
OBTAIN AND MAINTAIN ON SITE A COMPLETE SET OF
ABATEMENT DOCUMENTS, INCLUDING ADDENDA AND CHANGES
AFTER START OF CONSTRUCTION, FOR REFERENCE AND
COORDINATION BY ALL TRADES. COORDINATE ALL DEMOLITION
AND CONSTRUCTION WORK WITH THE ABATEMENT
CONTRACTOR.
10. OBTAIN AND MAINTAIN A COMPLETE SET OF OWNER-PROVIDED
EQUIPMENT DOCUMENTS, INCLUDING ADDENDA AND CHANGES
AFTER START OF CONSTRUCTION, FOR REFERENCE AND
COORDINATION BY ALL TRADES. COORDINATE WITH
EQUIPMENT INSTALLER ON INSTALLATION OF ALL EQUIPMENT.
11. THE INDICATION OF TYPE AND LOCATION OF EXISTING
CONDITIONS AND MATERIALS IN THE DRAWINGS IS NOT
INTENDED AS EXACT DOCUMENTATION OF IN-PLACE
CONDITIONS. THE CONTRACTOR IS RESPONSIBLE FOR
VERIFYING EXISTING CONDITIONS BEFORE SUBMISSION OF
BIDS. EXISTING CONDITIONS VARYING FROM THOSE SHOWN IN
THE DRAWINGS WILL NOT BE JUSTIFICATION FOR ADDITIONAL
ALLOWANCE TO THE CONTRACTOR. NOTIFY THE ARCHITECT
IMMEDIATELY IF ANY CONDITIONS CONFLICT WITH THE
DRAWINGS.
12. PROTECT ALL BUILDING SYSTEMS, NEW AND EXISTING. COVER
SUPPLY, RETURN, AND EXHAUST AIR GRILLES, AND PROTECT
OTHER SENSITIVE EQUIPMENT FROM ALL ACTIVITIES RELATED
TO THIS CONTRACT. REMOVE PROTECTION AT END OF
CONSTRUCTION.
13. ALL DISSIMILAR METALS SHALL BE ISOLATED FROM EACH
OTHER EVEN IF NOT SPECIFICALLY IDENTIFIED IN THE
CONTRACT DOCUMENTS.
14. ALL CODE-REQUIRED LABELS SUCH AS "UL", “FACTORY
MUTUAL”, OR ANY EQUIPMENT IDENTIFICATION, PERFORMANCE
RATING, NAME, OR NOMENCLATURE PLATES SHALL REMAIN
READABLE AND NOT PAINTED OR COVERED BY OTHER
CONSTRUCTION.
15. ARCHITECTURAL DIMENSIONS AND DESIGN INTENT ARE
INDICATED ON ARCHITECTURAL DRAWINGS. IF THE
INSTALLATION OF EQUIPMENT FROM OTHER TRADES
INTERFERES WITH COMPLIANCE OF THE DESIGN INTENT,
NOTIFY THE ARCHITECT BEFORE PROCEEDING.
16. DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN LOCATION
OF BUILDING ELEMENTS. IF DIMENSIONS ARE NOT AVAILABLE,
CONTACT THE ARCHITECT.
17. WHEN DIMENSIONS ON SMALL SCALE DRAWINGS CONFLICT
WITH THOSE ON LARGE SCALE DRAWINGS, THE LARGE SCALE
DRAWINGS GOVERN.
PROJECT GENERAL INFORMATION
VIEW NUMBER
GENERAL SYMBOLS LEGEND
A1
VIEW NAME
100'-0"
12" = 1'-0" 12"
VIEW SCALE
NORTH ARROW
VIEW NUMBER
SHEET NUMBER
BUILDING SECTION MARK
VIEW NUMBER
SHEET NUMBER
WALL SECTION MARK
VIEW NUMBER
SHEET NUMBER
DETAIL SECTION MARK
VIEW NUMBER
SHEET NUMBER
EXTERIOR ELEVATION MARK
VIEW NUMBER
SHEET NUMBER
INTERIOR ELEVATION MARK
ENLARGED DETAIL MARK
VIEW NUMBER
SHEET NUMBER
KEYNOTE VALUEA00
REVISION NUMBER
REVISION TYPE
EXISTING GRID ID MARK
NEW GRID ID MARK
IDENTIFIED LEVEL NAME
ELEVATION MARK
SPOT ELEVATION MARK
ROOM NAME
101 ROOM NUMBER
A4/A104
VIEW NUMBER / SHEET NUMBER OF
CONTINUING VIEW
MATCHLINE
A1 A101
A1 A101
A1 A101
A1 A101
A1 A101
A1
A1 A1
A1
A100
A1 A101
RFI
FIRST FLOOR
100'-0"
N
ELEVATOR
A
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2023Autodesk Revit 2023
/2
/2
:3 :5
P
M
A u to d e s k D o c s /2
I A
D A
S
D O
C M
P C
F B ld g
E le v a to r R e p /2
-A
-R .r v t
P R
O J E
C T
G E
N E
R A
L
IN
F O
R M
A T
IO
N
B
ID
D
IN
G
F ie ld B o o k
C L M
R C
B
/2
/2
G001
IA
D
A S
D
O C
M P
C F
B ld g
E le v a to r
R e p
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
C L
IE
N T
P R
O J E
C T
N U
M B
E R
D
A S
.0
E
W a s h in g to n S t, M t P le a s a n t, I A
N
01/16" = 1'-0"6A
OVERALL FIRST FLOOR PLAN
24'
EXISTING WALL PARTITIONS
DEMOLITION PLAN SYMBOLS LEGEND
TEMPORARY WALL PARTITIONS
DEMOLISHED WALL PARTITIONS
EXISTING DOOR
DEMOLISHED DOOR
1. FIELD VERIFY EXISTING CONDITIONS PRIOR TO START OF
DEMOLITION WORK. NOTIFY ARCHITECT IN WRITING OF
DISCREPANCIES BETWEEN WORK SHOWN IN THE DRAWINGS
AND FIELD CONDITIONS ENCOUNTERED.
2. TO PROTECT OWNER AND CONTRACTOR, PHOTOGRAPHICALLY
DOCUMENT EXISTING CONDITIONS TO REMAIN, PRIOR TO
START OF DEMOLITION AND CONSTRUCTION ACTIVITIES. COPY
ARCHITECT AND OWNER ON PHOTOGRAPHIC
DOCUMENTATION.
3. OPEN FLAME EQUIPMENT IS NOT PERMITTED FOR REMOVAL OF
EXISTING WORK WITHOUT SPECIFIC WRITTEN PERMISSION
FROM THE OWNER.
4. COORDINATE WITH OWNER ANY ITEMS TO BE SALVAGED.
5. OWNER WILL REMOVE ALL NON-FIXED FURNISHINGS AND
EQUIPMENT FROM THE CONSTRUCTION AREA PRIOR TO START
OF CONSTRUCTION UNLESS NOTED OTHERWISE.
6. MAINTAIN BUILDING IN A WEATHER-TIGHT CONDITION. DO NOT
PERFORM WORK ON EXTERIOR OPENINGS THAT CANNOT BE
COMPLETED OR MADE WEATHER-TIGHT WHEN INCLEMENT
WEATHER IS POSSIBLE.
7. COORDINATE PENETRATION LOCATIONS WITH ASSOCIATED
TRADES.
8. COORDINATE WITH OTHER TRADES CUTTING AND PATCHING
REQUIRED FOR DEMOLITION OR NEW CONSTRUCTION.
9. ANY DEMOLITION OR REMOVAL INDICATED IS SHOWN IN
GENERAL TO PROVIDE THE EXTENT OF DEMOLITION AND IS
NOT TO BE CONSIDERED AS A RECORD DRAWING OF EXISTING
CONDITIONS. THE CONTRACTOR IS RESPONSIBLE FOR IN FIELD
VERIFICATION AND COORDINATION WITH THE ARCHITECT
PRIOR TO COMMENCING WITH STATED WORK.
10. ALL CONSTRUCTION TO REMAIN WHICH IS AFFECTED BY
DEMOLITION SHALL BE PATCHED, BE PROPERLY ALIGNED AND
FINISHED SO AS TO LEAVE NO EVIDENCE OF PATCHING OR
REPAIR. REPAIR OR REPLACE ANY EXISTING CONSTRUCTION,
MATERIALS, OR EQUIPMENT DAMAGED DURING DEMOLITION TO
LIKE NEW CONDITION.
11. THE CONTRACTOR IS TO RETURN SALVAGEABLE MATERIALS,
INCLUDING BUT NOT LIMITED TO DOORS, FRAMES, HARDWARE,
MARBLE, EQUIPMENT, AND LIGHTING FIXTURES TO THE OWNER
AND STOCKPILE THEM IN AN APPROVED CONSTRUCTION AREA.
DISPOSE OF THESE MATERIALS AFTER OWNER'S REVIEW AND
APPROVAL.
12. CONTRACTOR IS RESPONSIBLE FOR PROTECTION OF ALL
FINISHES (TO REMAIN) IN THE PROJECT AREA. COORDINATE
WITH ARCHITECT AND OWNER PRIOR TO DEMOLITION.
13. CONTRACTOR SHALL ENSURE THAT DUST AND DEBRIS ARE
PREVENTED FROM ENTERING THE EXISTING HVAC SYSTEM
AND ADJOINING SPACES WITH TEMPORARY BARRIERS AS
REQUIRED PER THE BUILDING.
14. INDICATION OF NEW MATERIALS SHALL INFER ALL REMOVAL OR
DEMOLITION AND PATCHING REQUIRED OF EXISTING
MATERIALS AND SUBSTRATES FOR PROPER ALIGNMENT.
MATCH EXISTING FINISHES.
15. ALL NEW AND EXISTING PENETRATIONS IN EXISTING WALLS,
FLOORS AND CEILING DECKS SHALL RECEIVE UL AND FACILITY
APPROVED FIRE SEALANT MATERIALS TO MATCH RATING
REQUIREMENT OF AREA BEING PENETRATED.
16. OWNER'S EXISTING DIAMOND PLATE SHEET MAY BE USED BY
CONTRACTOR FOR FLOOR PROTECTION IN EXISTING
ELEVATORS IF NEEDED DURING CONSTRUCTION.
ARCHITECTURAL DEMOLITION NOTES
ELEVATOR
A
E6 A310
G6 A310
AD.04
AD.07
AD.08
AD.09
AD.10
A01.05
AD.11
AD.12
AD.13
AD.14
ELEVATOR
A
E6 A310
G6 A310
AD.04
AD.07
AD.10
AD.11
AD.13
AD.15
ELEVATOR
A
E6 A310
G6 A310
AD.05
AD.10
AD.11
AD.07
AD.13
AD.16
ELEVATOR
A
E6 A310
G6 A310
AD.05
AD.10
AD.11
AD.13
AD.16
E6 A310
G6 A310
ELEVATOR
PENTHOUSE
A&B
AD.03
AD.01
AD.02
AD.06
REMOVE EXISTING EXTERIOR
WINDOW FRAME, PATCH AND
PREPARE OPENING FOR NEW
WORK
REMOVE EXISTING WINDOW,
PATCH AND PREPARE OPENING
FOR NEW WORK
REMOVE EXISTING EXTERIOR
WINDOW FRAME, PATCH AND
PREPARE OPENING FOR NEW
WORK
REMOVE EXISTING EXTERIOR
WINDOW FRAME, PATCH AND
PREPARE OPENING FOR NEW
WORK
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2023Autodesk Revit 2023
/2
/2
:3 :5
P
M
A u to d e s k D o c s /2
I A
D A
S
D O
C M
P C
F B ld g
E le v a to r R e p /2
-A
-R .r v t
D E
M O
L
IT
IO
N
P L A
N S
B
ID
D
IN
G
F ie ld B o o k
C L M
R C
B
/2
/2
AD01
IA
D
A S
D
O C
M P
C F
B ld g
E le v a to r
R e p
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
C L
IE
N T
P R
O J E
C T
N U
M B
E R
D
A S
.0
E
W a s h in g to n S t, M t P le a s a n t, I A
KEYNOTES
KEY NOTE
A01.05 EXISTING GUIDE RAILS TO REMAIN. CLEAN AND
REALIGN RAILS FOR SMOOTHNESS OF RIDE IN NEW
ELEVATOR CAB
AD.01 REMOVE EXISTING EXTERIOR DOOR AND FRAME,
PATCH AND PREPARE OPENING FOR NEW WORK
AD.02 REMOVE EXISTING EXTERIOR WINDOW FRAME, PATCH
AND PREPARE OPENING FOR NEW WORK
AD.03 REMOVE EXISTING LADDER TO ELEVATOR A PLATFORM
AD.04 EXISTING HOISTWAY ENTRANCES TO REMAIN, STRIP
PAINT AND PREP SURFACE FOR NEW WORK
AD.05 EXISTING HOISTWAY ENTRANCES AND HOLLOW METAL
FRAME TO REMAIN, STRIP PAINT AN PREP SURFACE
FOR NEW WORK
AD.06 REMOVE EXISTING WINDOW, PATCH AND PREPARE
OPENING FOR NEW WORK
AD.07 REMOVE EXISTING ELEVATOR CAB AND FRAME, SEE
SPECIFICATIONS FOR FULL SCOPE OF WORK
AD.08 REMOVE EXISTING COUNTERWEIGHTS AND
COUNTERWEIGHT ASSEMBLIES, SEE SPECIFICATION
FOR FULL SCOPE OF WORK
AD.09 REMOVE EXISTING BUFFERS AND PIT CHANNELS, SEE
SPECIFICATIONS FOR FULL SCOPE OF WORK
AD.10 REMOVE EXISTING HOISTWAY DOOR PANELS
AD.11 EXISTING THRESHOLD TO REMAIN, CLEAN
AD.12 REMOVE EXISTING LADDER TO ELEVATOR PIT
AD.13 REMOVE EXISTING KEY SWITCH OPERATOR, REPLACE
WITH ADA COMPLIANT KEY SWITCH OPERATOR
AD.14 REMOVE FLOOR AS NEEDED FOR NEW SUMP PUMP
AD.15 TEMPORARY DUST PROTECTION
AD.16 TEMPORARY WALLS TO BE SUPPORTED FROM WALL
JAMBS. PROTECT FLOOR AND CEILING AT TEMPORARY
WALL LOCATIONS, TEMPORARY WALL ANCHORS ARE
NOT ALLOWED TO CEILING OR FLOOR. WHERE JAMBS
REQUIRE SUPPORT FROM A GLAZED BLOCK WALL
TEMPORARY ANCHORS TO BE MOUNTED IN MORTAR
JOINTS
N
01/8" = 1'-0"6A
BASEMENT - DEMOLITION PLAN
12'
N
01/8" = 1'-0"6C
FIRST FLOOR - DEMOLITION PLAN
12'
N
01/8" = 1'-0"E6
SECOND FLOOR - DEMOLITION PLAN
12'
N
01/8" = 1'-0"4C
THIRD FLOOR - DEMOLITION PLAN
12'
N
01/8" = 1'-0"4E
ROOF - DEMOLITION PLAN
12'
NOT TO SCALEB2
DEMO PHOTO 1
NOT TO SCALEE2
DEMO PHOTO 2
NOT TO SCALED2
DEMO PHOTO 3
REMOVE ELECTRICAL BOX, PATCH OPENINGS
IN SHAFT WALLS WITH LIKE MATERIALS OR
FIRESTOP SYSTEM TO MAINTAIN THE
REQUIRED 2-HR RATING
EXISTING GUIDE RAILS TO REMAIN. CLEAN
AND REALIGN RAILS FOR SMOOTHNESS OF
RIDE IN NEW ELEVATOR CAB
REMOVE CONDUIT AS NECESSARY TO
MEET NEW WIRING REQUIREMENTS
PATCH OPENINGS IN SHAFT WALLS
WITH LIKE MATERIALS OR FIRESTOP
SYSTEM TO MAINTAIN THE REQUIRED
2-HR RATING
REMOVE ELECTRICAL BOX, PATCH OPENINGS
IN SHAFT WALLS WITH LIKE MATERIALS OR
FIRESTOP SYSTEM TO MAINTAIN THE
REQUIRED 2-HR RATING
EXISTING HOISTWAY ENTRANCES
AND HOLLOW METAL FRAME TO
REMAIN, STRIP PAINT AND PREP
SURFACE FOR NEW WORK.
TYPICAL FOR ALL FLOORS
EXISTING THRESHOLD TO REMAIN,
CLEAN. TYPICAL FOR ALL FLOORS
REMOVE EXISTING HOISTWAY
DOOR PANELS
REMOVE EXISTING ELEVATOR CAB
AND FRAME, SEE SPECIFICATIONS
FOR FULL SCOPE OF WORK
REMOVE EXISTING HOISTWAY
DOOR PANELS, TYPICAL FOR ALL
FLOORS
EXISTING HOISTWAY ENTRANCES
AND HOLLOW METAL FRAME TO
REMAIN, STRIP PAINT AND PREP
SURFACE FOR NEW WORK.
TYPICAL FOR ALL FLOORS
SALVAGE FLOOR INDICATOR
PLATE, TO BE REINSTALLED WITH
NEW ELECTRICAL WORK, TYPICAL
FOR ALL FLOORS
REMOVE EXISTING CONTROL
SYSTEM, MOTOR CONTROL, AND
ASSOCIATED ITEMS FOR
ELEVATOR A. SEE SPECIFICATIONS
FOR FULL SCOPE OF WORK.
REMOVE EXISTING MOTOR
GENERATOR SET AND ASSOCIATED
ITEMS FOR ELEVATOR A. SEE
SPECIFICATIONS FOR FULL SCOPE
OF WORK.
REMOVE EXISTING FLOOR
SELECTOR AND ASSOCIATED
ITEMS FOR ELEVATOR A. SEE
SPECIFICATIONS FOR FULL SCOPE
OF WORK.
REMOVE EXISTING DOOR
CONTROLLLER AND ASSOCIATED
ITEMS FOR ELEVATOR A. SEE
SPECIFICATIONS FOR FULL SCOPE
OF WORK.
REMOVE EXISTING
CONTROLLLER, MOTOR
CONTROL, AND ASSOCIATED
ITEMS FOR ELEVATOR A. SEE
SPECIFICATIONS FOR FULL
SCOPE OF WORK.
REMOVE DRIVE MACHINES
AND ASSOCIATED ITEMS FOR
ELEVATOR A. SEE
SPECIFICATIONS FOR FULL
SCOPE OF WORK.
REMOVE EXISTING
LADDER TO ELEVATOR A
PLATFORM. PATCH FLOOR
ON BOTH LEVELS.
REMOVE EXISTING
LADDER TO ELEVATOR A
PLATFORM. PATCH FLOOR
ON BOTH LEVELS.
REMOVE DEFLECTOR SHEAVE
PATCH OPENINGS IN SHAFT WALLS
WITH LIKE MATERIALS OR FIRESTOP
SYSTEM TO MAINTAIN THE REQUIRED
2-HR RATING
PATCH OPENINGS IN SHAFT WALLS
WITH LIKE MATERIALS OR FIRESTOP
SYSTEM TO MAINTAIN THE REQUIRED
2-HR RATING
REMOVE EXISTING BUFFERS AND PIT
CHANNELS, SEE SPECIFICATIONS FOR
FULL SCOPE OF WORK
REMOVE EXISTING PIT LADDER,
REPLACE WITH NEW PIT LADDER
REMOVE EXISTING SUMP PUMP, SEE
MECHANICAL DRAWINGS
REMOVE EXISTING
COUNTERWEIGHTS AND
COUNTERWEIGHT ASSEMBLIES,
SEE SPECIFICATION FOR FULL
SCOPE OF WORK
EXISTING GUIDE RAILS TO
REMAIN. CLEAN AND REALIGN
RAILS FOR SMOOTHNESS OF
RIDE IN NEW ELEVATOR CAB
REMOVE EXISTING
COUNTERWEIGHT GUARD, SEE
SPECIFICATION FOR FULL SCOPE
OF WORK
REMOVE EXISTING HOISTWAY
DOOR PANELS, TYPICAL FOR ALL
FLOORS
EXISTING HOISTWAY ENTRANCES
AND HOLLOW METAL FRAME TO
REMAIN, STRIP PAINT AND PREP
SURFACE FOR NEW WORK.
TYPICAL FOR ALL FLOORS
EXISTING THRESHOLD TO REMAIN,
CLEAN. TYPICAL FOR ALL FLOORS
REMOVE EXISTING KEY SWITCH
OPERATOR, REPLACE WITH ADA
COMPLIANT KEY SWITCH OPERATOR
REMOVE EXISTING GOVENOR
SYSTEM AND ASSOCIATED ITEMS
FOR ELEVATOR A. SEE
SPECIFICATIONS FOR FULL
SCOPE OF WORK.
REMOVE EXISTING CONTROLLLER,
MOTOR CONTROL, AND
ASSOCIATED ITEMS FOR
ELEVATOR A. SEE SPECIFICATIONS
FOR FULL SCOPE OF WORK.
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2023Autodesk Revit 2023
/2
/2
:3 :0
P
M
A u to d e s k D o c s /2
I A
D A
S
D O
C M
P C
F B ld g
E le v a to r R e p /2
-A
-R .r v t
D E
M O
L
IT
IO
N
P H
O T
O S
B
ID
D
IN
G
F ie ld B o o k
C L M
R C
B
/2
/2
AD02
IA
D
A S
D
O C
M P
C F
B ld g
E le v a to r
R e p
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
C L
IE
N T
P R
O J E
C T
N U
M B
E R
D
A S
.0
E
W a s h in g to n S t, M t P le a s a n t, I A
NOT TO SCALED5
DEMO PHOTO - ELEVATOR SHAFT
NOT TO SCALEB5
DEMO PHOTO - ELEVATOR SHAFT
NOT TO SCALEE6
DEMO PHOTO 6
NOT TO SCALEB6
DEMO PHOTO 7
NOT TO SCALED3
DEMO PHOTO - ELEVATOR PENTHOUSE
NOT TO SCALEA3
DEMO PHOTO 9 - ELEVATOR PENTHOUSE
NOT TO SCALEB3
DEMO PHOTO 10 - ELEVATOR PENTHOUSE
NOT TO SCALEG3
DEMO PHOTO - ELEVATOR PENTHOUSE
NOT TO SCALEE3
DEMO PHOTO - ELEVATOR PENTHOUSE
NOT TO SCALEA5
DEMO PHOTO - ELEVATOR SHAFT
NOT TO SCALEA6
DEMO PHOTO - ELEVATOR SHAFT
NOT TO SCALEG5
DEMO PHOTO - ELEVATOR PIT
NOT TO SCALEE5
DEMO PHOTO - ELEVATOR PIT
NOT TO SCALEG6
DEMO PHOTO 17
01" = 10'-0"E2
DEMO PHOTO - ELEVATOR PENTHOUSE
15' 01" = 10'-0"G2
DEMO PHOTO - ELEVATOR PENTHOUSE
15'01" = 10'-0"D2
DEMO PHOTO - ELEVATOR PENTHOUSE
15'
ELEVATOR
A
E6 A310
G6 A310
A09.01
A01.04 TYP
A14.01
DOOR MARK
FLOOR PLAN SYMBOLS LEGEND
1. REFER TO DRAWINGS OF ALL TRADES FOR ADDITIONAL
INFORMATION REGARDING ITEMS PENETRATING FLOORS,
WALLS, AND CEILINGS.
2. EXISTING ELEVATOR SHAFT WALLS ARE CONSIDERED TO HAVE
A 2-HR FIRE RATING.
FLOOR PLAN NOTES
ELEVATOR
A
E6 A310
G6 A310
A09.01
TYPA01.04
A14.02
A14.01
A03.01
A09.02
A03.02 ELEVATOR
A
E6 A310
G6 A310
A09.01
TYPA01.04
A14.01
A09.04
A09.04
ELEVATOR
A
E6 A310
G6 A310
A09.01
A01.04 TYP
A14.01
A09.04
A09.04
ELEVATOR
PENTHOUSE
A&B
E6 A310
G6 A310
A04.01
A05.02 A05.01
A08.01
A04.01
A09.03
A310
G2
1'-0" 5'-4"
A01.06A01.06
A01.06A01.06
2"
SCHEDULE
PER 2"
HM-00 : F2
HOLLOW METAL FRAME
WITH 0 TRANSOM AND 0
SIDELIGHTS
F
P E
R S
C H
E D
U L E
SCHEDULE
PER
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
AAuuttooddeesskk RReevviitt 22002233
/2
/2
:3 :0
P
M
A u to d e s k D o c s /2
I A
D A
S
D O
C M
P C
F B ld g
E le v a to r R e p /2
-A
-R .r v t
F L O
O R
P L A
N S
B
ID
D
IN
G
F ie ld B o o k
C L M
R C
B
/2
/2
A101
IA
D
A S
D
O C
M P
C F
B ld g
E le v a to r
R e p
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
C L
IE
N T
P R
O J E
C T
N U
M B
E R
D
A S
.0
E
W a s h in g to n S t, M t P le a s a n t, I A
01/4" = 1'-0"
DOOR PANEL ELEVATIONS
6'01/4" = 1'-0"
DOOR FRAME ELEVATIONS
6'
N
01/8" = 1'-0"C6
FIRST FLOOR PLAN
12'
KEYNOTES
KEY NOTE
A01.04 PATCH OPENINGS IN SHAFT WALLS WITH LIKE
MATERIALS (I.E. SOLID CLAY BRICK PAVER WITH
MINIMUM EQUIVALENT THICKNESS FOR FIRE
RESISTANCE OF 2 HOURS) OR APPROVED FIRESTOP
SYSTEM TO MAINTAIN THE REQUIRED 2-HR RATING.
ASSUME TEN (10) 12" X 12" OPENINGS TO BE INCLUDED
IN PROJECT SCOPE; SEE SPECIFICATIONS FOR
REQUIREMENTS TO PROVIDE A UNIT PRICE FOR
ADDITIONAL OPENINGS.
A01.06 ALIGN
A03.01 PATCH FLOOR AROUND NEW SUMP PUMP
A03.02 INFILL CONCRETE FLOOR AT REMOVED SUMP PUMP
WITH CONCRETE SLAB REINFORCED WITH
6X6XW2.9XW2.9 WWR ON 6" COMPACTED GRANULAR
FILL. DOWEL AND EPOXY 4" INTO EXISTING SLAB WITH
#4 BARS AT 12" O.C.
A04.01 FACE BRICK INFILL, FACE BRICK PROVIDED BY OWNER
A05.01 GUARDRAIL, FASTEN TO FLOOR SLAB WITH 3/8" Ø
THREADED RODS AND SIMPSON SET-3G EPOXY (2 1/2"
EMBED). USE SIMPSON OPTI-MESH SCREEN TUBES IF
HOLE PENETRATES FLOOR COMPLETELY.
A05.02 PREFABRICATED LADDER, FASTEN TO FLOOR SLAB
SAME AS GUARDRAIL, FASTEN TO BRICK WITH 3/8" Ø
THREADED RODS AND SIMPSON ET-3G EPOXY (3 1/2"
EMBED).
A08.01 NEW 90-MIN RATED HOLLOW METAL DOOR AND FRAME
A09.01 PAINT EXISTING METAL FRAME AT ELEVATOR DOOR
OPENING
A09.02 PAINT ELEVATOR PIT FLOOR
A09.03 PAINT ELEVATOR PENTHOUSE FLOOR AND PLATFORM
FLOOR FOR ELEVATOR A
A09.04 PATCH AND REPAIR TEMPORARY WALL ANCHOR
LOCATIONS ON EXISTING WALLS TO MATCH EXISTING
FINISHES
A14.01 NEW ELEVATOR CAB
A14.02 NEW ELEVATOR PIT LADDER PER ELEVATOR
MANUFACTURER
N
01/8" = 1'-0"E6
SECOND FLOOR PLAN
12'
N
01/8" = 1'-0"E4
ROOF PLAN
12'
N
01/8" = 1'-0"A6
BASEMENT-FLOOR PLAN
12'
N
01/8" = 1'-0"C4
THIRD FLOOR-FLOOR PLAN
12'
DOOR AND FRAME SCHEDULE
MARK ROOM NAME
OPENING SIZE DOOR FRAME
WIDTH HEIGHT THICKNESS TYPE MATERIAL TY HDWR RATING REMARKSPE FINISH
500 ELEVATOR PENTHOUSE 3' - 0" 7' - 0" 1 3/4" F HM HM-00 : F2 PAINT HW-1 90 MIN FIELD VERIFY EXISTING OPENING DIMENSIONS
DOOR HARDWARE BASIS-OF-DESIGN
HARDWARE SET HW-1
-HINGES (HAGER BB 1279 4 1/2" X 4 1/2")
-LOCKSET (SCHLAGE ND-SERIES GRADE 1)
-CLOSER (NORTON CPS7500)
-STOPS (NORTON 891)
-THRESHOLD (PEMKO 171A OR MFR'S EQUAL)
-WEATHERSTRIP (PEMKO 303AV)
-BOTTOM SWEEP (PEMKO 315CN)
-DRIP CAP (PEMKO 346C)
-LATCH PROTECTOR (ROCKWOOD 320/321)
100' - 0"
FIRST FLOOR
111' - 0"
SECOND FLOOR
133' - 10"
ROOF
122' - 0"
THIRD FLOOR
90' - 8"
BASEMENT
146' - 6"
PENTHOUSE ROOF
G6 A310
ELEVATOR
A
ELEVATOR
PENTHOUSE
A&B
GUARDRAIL, FASTEN TO
FLOOR SLAB WITH 3/8" Ø
THREADED RODS AND
SIMPSON SET-3G EPOXY (2
1/2" EMBED). USE SIMPSON
OPTI-MESH SCREEN TUBES IF
HOLE PENETRATES FLOOR
COMPLETELY.
PREFABRICATED LADDER,
FASTEN TO FLOOR SLAB SAME
AS GUARDRAIL, FASTEN TO
BRICK WITH 3/8" Ø THREADED
RODS AND SIMPSON ET-3G
EPOXY (3 1/2" EMBED).
NEW ELEVATOR PIT LADDER
PER ELEVATOR
MANUFACTURER
4"
100' - 0"
FIRST FLOOR
111' - 0"
SECOND FLOOR
133' - 10"
ROOF
122' - 0"
THIRD FLOOR
90' - 8"
BASEMENT
146' - 6"
PENTHOUSE ROOF
E6 A310
ELEVATOR
A
GUARDRAIL, FASTEN TO
FLOOR SLAB WITH 3/8" Ø
THREADED RODS AND
SIMPSON SET-3G EPOXY (2
1/2" EMBED). USE SIMPSON
OPTI-MESH SCREEN TUBES IF
HOLE PENETRATES FLOOR
COMPLETELY.
NEW ELEVATOR PIT LADDER
PER ELEVATOR
MANUFACTURER
LADDER GRAB RAILS
5'-4" 1'-0"
EXISTING MASONRY WALL
GUARDRAIL, FASTEN TO
FLOOR SLAB WITH 3/8" Ø
THREADED RODS AND
SIMPSON SET-3G EPOXY (2
1/2" EMBED). USE SIMPSON
OPTI-MESH SCREEN TUBES IF
HOLE PENETRATES FLOOR
COMPLETELY.
PREFABRICATED LADDER,
FASTEN TO FLOOR SLAB SAME
AS GUARDRAIL, FASTEN TO
BRICK WITH 3/8" Ø THREADED
RODS AND SIMPSON ET-3G
EPOXY (3 1/2" EMBED).
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2023Autodesk Revit 2023
/2
/2
:3 :0
P
M
A u to d e s k D o c s /2
I A
D A
S
D O
C M
P C
F B ld g
E le v a to r R e p /2
-A
-R .r v t
W A
L L S
E C
T
IO
N S
A N
D E
L E
V A
T
IO
N S
B
ID
D
IN
G
F ie ld B o o k
C L M
R C
B
/2
/2
A310
IA
D
A S
D
O C
M P
C F
B ld g
E le v a to r
R e p
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
C L
IE
N T
P R
O J E
C T
N U
M B
E R
D
A S
.0
E
W a s h in g to n S t, M t P le a s a n t, I A
01/4" = 1'-0"E6
N-S WALL SECTION
6' 01/4" = 1'-0"G6
E-W WALL SECTION
6'
01/4" = 1'-0"G2
GUARD RAIL ELEVATION
6'
1. PIPING IS SHOWN IN SCHEMATIC FORM, ROUTE AS REQUIRED
FOR CLEARANCE. VERIFY ROUTING AND CLEARANCES AND
COORDINATE WITH OTHER TRADES PRIOR TO FABRICATION.
THE CONTRACTOR SHALL PROVIDE COMPLETE FULLY
FUNCTIONAL SYSTEMS.
2. BREAK CONNECTIONS REQUIRED AT ALL MAJOR EQUIPMENT
AND PIPING ITEMS THAT REQUIRE REMOVAL FOR
MAINTENANCE.
3. PIPE REDUCTIONS ON HORIZONTAL PIPING GOING FROM
LARGER TO SMALLER SHALL BE MADE WITH ECCENTRIC
REDUCERS: TOP FLAT FOR LIQUID SYSTEMS, CONCENTRIC
REDUCERS MAY BE USED FOR FLOW GOING FROM SMALL TO
LARGER SIZE PIPE.
4. FIRE SAFE ALL PIPE PENETRATIONS PER UL AT RATED WALLS.
5. NEW FLOOR/WALL/CEILING PENETRATIONS REQUIRED FOR
MECHANICAL PIPING INSTALLATION SHALL BE CLEANLY BORED
AT RIGHT ANGLES. AS NEW PIPING IS INSTALLED, NEW PIPING
PENETRATIONS SHALL BE NEATLY CAULKED TO FILL VOID.
WALL PENETRATIONS SHALL BE FINISHED WITH
ESCUTCHEONS.
6. ALL NEW PIPING EXPOSED IN OCCUPIED SPACES SHALL HAVE
PVC JACKETS INSTALLED OVER THE PIPING INSULATION. ANY
PIPING REQUIRED TO BE EXPOSED SHALL BE INSTALLED
VERTICALLY OR HORIZONTALLY IN LEAST VISIBLE LOCATION.
7. ALL NEW EQUIPMENT AND ACCESSORIES SHALL BE INSTALLED
SO AS TO BE EASILY ACCESSIBLE.
8. CONTRACTOR SHALL PATCH/REPAIR ALL UNUSED OPENINGS
AND MODIFIED FINISH SURFACES. PATCHING SHALL MATCH
MATERIALS, FINISH AND TEXTURE OF ADJACENT SURFACES.
9. ALL WORK WITHIN THE CONTRACT DOCUMENTS, WHICH
INCLUDE THIS DRAWING, SHALL BE COMPLETED IN A SAFE
WORKMANLIKE MANNER AND IN ACCORDANCE WITH ALL
APPLICABLE STATE, LOCAL AND NATIONAL CODES,
REGULATIONS AND ORDINANCES. IF ANY CONFLICTS ARISE
BETWEEN THE CONTRACT DOCUMENTS AND THE APPLICABLE
CODES, REGULATIONS OR ORDINANCE, THE CONTRACTOR
SHALL BE RESPONSIBLE TO HAVE ALL WORK CONFORM TO
THE STRICTER OF SAID REQUIREMENTS.
10. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL
PERMITS AND INSPECTIONS AS REQUIRED FOR ELECTRICAL,
FIRE PROTECTION, PLUMBING, MECHANICAL AND BACKFLOW
PREVENTION INSTALLATIONS. IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO PROVIDE BOTH A
COMPLETE AND COMPLIANT INSTALLATION AS MAY BE
DETERMINED BY THE AUTHORITY(S) HAVING JURISDICTION.
11. CONTRACTOR SHALL NOT PROCURE OR FABRICATE ANY
PIPING, DUCTWORK OR OTHER EQUIPMENT WITHOUT FIRST
VERIFYING ALL DIMENSIONS AND CONDITIONS WHETHER
CURRENTLY EXISTING OR NOT. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL WORK, INCLUDING ANY REQUIRED
REWORK.
12. MAINTAIN ALL MANUFACTURER RECOMMENDED EQUIPMENT
SERVICE AND SAFETY CLEARANCES. DO NOT LOCATE ANY
EQUIPMENT OR RUN MATERIALS ABOVE ANY ELECTRICAL
PANELS OR SWITCHGEAR. MAINTAIN ALL NFPA/NEC CODE
REQUIRED CLEARANCES.
13. EACH CONTRACTOR SHALL BE RESPONSIBLE FOR
COORDINATING, SCHEDULING AND SEQUENCING OF THEIR
WORK WITH ALL OTHER TRADES. PROVIDE OFFSETS,
EASEMENTS, OR RELOCATE TO AVOID CONFLICTS WITH WORK
OF OTHER TRADES. FURNISH SUFFICIENT RESOURCES TO
MEET ALL PROJECT MILESTONES AND DEADLINES.
14. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE
WATERTIGHT AND WEATHER-PROOF INTEGRITY OF ROOFS,
WALLS AND FLOORS DURING CONSTRUCTION. EACH TRADE
SHALL LOCATE/DIMENSION/COORDINATE THEIR ROOF, FLOOR
AND WALL OPENINGS WITH THE GENERAL CONTRACTOR (GC)
OR CONSTRUCTION MANAGER.
15. PROTECT NEW WORK FROM DAMAGE OR CONTAMINATION.
PROVIDE TEMPORARY PROTECTIVE CAPPING OR TAPED
POLYETHYLENE ENCLOSURES OVER OPEN DUCTWORK AND
PIPING ENDS AND EQUIPMENT. CONTRACTOR SHALL BE
RESPONSIBLE FOR CLEANING MECHANICAL SYSTEMS PRIOR
TO PLACING THEM IN SERVICE.
16. IN A NEAT AND WORKMANLIKE MANNER: PATCH ANY
REMAINING OPENINGS AND FILL EXCESSIVE GAPS; REWORK
AND REFINISH TO MATCH ADJACENT STRUCTURES; FLASH
AND SEAL ALL MECHANICAL AND ELECTRICAL PENETRATIONS
THRU WALLS, CEILINGS, AND FLOORS WITH METAL
FRAMEWORK OR ESCUTCHEONS. ALL OPENINGS SHALL BE
PROPERLY SEALED SO AS TO MEET FIRE RATING NEEDS.
MECHANICAL PIPING
1. THIS DRAWING DIAGRAMMATICALLY REPRESENTS THE
LAYOUT OF EXISTING CONDITIONS WITH MAJOR MECHANICAL
AND ELECTRICAL COMPONENTS. THEY ARE NOT INTENDED TO
SHOW ACCESSORIES OR INCIDENTALS COMMON TO
EQUIPMENT INDICATED, THOUGH THESE ITEMS ARE TO BE
REMOVED, ACCESSIBILITY TO DEMOLITION ITEMS SHALL NOT
BE INFERRED. THE CONTRACTOR SHALL BE RESPONSIBLE
FOR FIELD VERIFICATION OF BUILDING AND EXISTING
CONDITIONS, PRIOR TO BID SUBMISSION.
2. DEMOLITION SHALL INCLUDE ALL HANGERS, FITTINGS,
DAMPERS, VALVES, ETC.
3. REPAIR ANY INSULATION DAMAGED DURING REMOVAL. REPAIR
WORK TO BE SAME AS NEW.
4. COORDINATE WALL AND FLOOR PATCHING REQUIREMENTS
WITH THE GENERAL CONTRACTOR. PATCHWORK SHALL
MATCH MATERIALS, FINISH AND TEXTURE OF ADJACENT
SURFACES. REFERENCE ARCHITECTURAL PLANS.
5. CONTRACTOR SHALL PATCH/REPAIR ALL UNUSED OPENINGS
AND MODIFIED FINISH SURFACES. PATCH SHALL MATCH
MATERIALS, FINISH AND TEXTURE OF ADJACENT SURFACES.
6. OWNER SHALL RETAIN FIRST SALVAGE RIGHTS TO ALL
REMOVED EQUIPMENT AND MATERIALS. UNLESS NOTED
OTHERWISE, CONTRACTOR SHALL BE RESPONSIBLE FOR
PROPER AND TIMELY DISPOSAL OF ALL CONSTRUCTION
DEBRIS INCLUDING BUT NOT LIMITED TO EQUIPMENT AND
MATERIALS NOT CLAIMED BY OWNER TO AN EPA APPROVED,
ENVIRONMENTALLY RESPONSIBLE, RECYCLE FACILITY OR
LANDFILL.
7. IT IS ESSENTIAL TO MINIMIZE DISRUPTIONS. COORDINATE ALL
DEMOLITION WITH OWNER, GENERAL CONTRACTOR OR
CONSTRUCTION MANAGER BEFORE SHUTTING DOWN ANY
UTILITY OR SIMILAR SYSTEM. SHUTDOWNS FOR UTILITIES OR
SIMILAR SYSTEMS SHALL BE REQUESTED WELL IN ADVANCE
AND PRE-APPROVED BY THE PROPER AUTHORITY(S) HAVING
JURISDICTION BEFORE BEGINNING WORK.
8. ALL WORK WITHIN THE CONTRACT DOCUMENTS, WHICH
INCLUDE THIS DRAWING, SHALL BE COMPLETED IN A SAFE
WORKMANLIKE MANNER AND IN ACCORDANCE WITH ALL
APPLICABLE STATE, LOCAL AND NATIONAL CODES,
REGULATIONS AND ORDINANCES. IF ANY CONFLICTS ARISE
BETWEEN THE CONTRACT DOCUMENTS AND THE APPLICABLE
CODES, REGULATIONS OR ORDINANCE, THE CONTRACTOR
SHALL BE RESPONSIBLE TO HAVE ALL WORK CONFORM TO
THE STRICTER OF SAID REQUIREMENTS.
9. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL
PERMITS AND INSPECTIONS AS REQUIRED FOR ELECTRICAL,
FIRE PROTECTION, PLUMBING, MECHANICAL AND BACKFLOW
PREVENTION INSTALLATIONS. IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO PROVIDE BOTH A
COMPLETE AND COMPLIANT INSTALLATION AS MAY BE
DETERMINED BY THE AUTHORITY(S) HAVING JURISDICTION.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE
WATERTIGHT AND WEATHER-PROOF INTEGRITY OF ROOFS,
WALLS AND FLOORS DURING CONSTRUCTION. EACH TRADE
SHALL LOCATE/DIMENSION/COORDINATE THEIR ROOF, FLOOR
AND WALL OPENINGS WITH THE GC OR CONSTRUCTION
MANAGER.
MECHANICAL DEMOLITION
CD-A
8ø
DIFFUSER, GRILLE, REGISTER NOTATIONS
CD = CEILING DIFFUSER RR = RETURN REGISTER
EG = EXHAUST DIFFUSER SG = SUPPLY GRILLE
ER = EXHAUST REGISTER SR = SUPPLY REGISTER
LD = LINEAR DIFFUSER TG = TRANSFER GRILLE
RG = RETURN GRILLE
BUTTERFLY VALVE
SOLENOIDVALVE
PRESSURE REDUCING VALVE
THREE-WAY VALVE
CHECK VALVE
BALL VALVE
BALANCING VALVE
M
S
M
MOTORIZED CONTROLVALVE
THREE-WAY MOTORIZED CONTROLVALVE
ELBOW UP
ELBOW DOWN
PIPE OFFSET UP
PIPE OFFSET DOWN
PIPE CAP
PIPE TEE TURNED UP
PIPE TEE TURNED DOWN
PIPE TEE
PIPE UNION
PIPE TRANSITION
SOLAR HOT WATER SUPPLYSHWS
SOLAR HOT WATER RETURNSHWR
REFRIGERANT - SUCTIONRS
REFRIGERANT - LIQUIDRL
REFRIGERANT - HOT GASRHG
PUMP DISCHARGEPD
LOW PRESSURE STEAMLPS
LOW PRESSURE CONDENSATELPC
HIGH PRESSURE STEAMHPS
HIGH PRESSURE CONDENSATEHPC
HEATING WATER SUPPLYHWS
HEATING WATER RETURNHWR
GEOTHERMAL SUPPLYGTS
GEOTHERMAL RETURNGTR
CONDENSER WATER SUPPLYCDWS
CONDENSER WATER RETURNCDWR
CONDENSATECOND
CHILLED WATER SUPPLYCHWS
CHILLED WATER RETURNCHWR
TO BE DEMOLISHEDCHWS
EXISTING TO REMAINCHWS
8" CHWS PIPE SIZE, SYSTEM AND FLOW TAG (DIA)
A
G
S
DETAIL NUMBER
SHEET NUMBER ON
WHICH THE DETAIL
RESIDES
SUPPORT
GUIDE
ANCHOR
PRESSURE GAUGE
THERMOMETER
NEW CONNECTION INTO EXISTING PIPE OR DUCT
CAP EXISTING PIPE OR DUCT
KEYNOTE
HUMIDISTAT OR HUMIDITY SENSOR
PRESSURE SENSOR
TEMPERATURE SENSOR
THERMOSTAT
NITROGEN DIOXIDESENSOR
CARBON MONOXIDESENSOR
CARBON DIOXIDESENSOR
H
T
TS
P
NO₂
CO₂
CO
AIR FLOW ARROW POSITIVE PRESSURE
AIR FLOW ARROW NEGATIVE PRESSURE
TYPE = SEE BELOW
ID. NO. - SEE SCHEDULE
NECK SIZE IN INCHES (ROUND SHOWN)
AIR FLOW (CFM)
F
S
FS
M
12x12
12ø
12x12 SA UP
12x12 SA DN
12ø SA UP
12ø SA DN
DUCT SMOKE DETECTOR
MOTORIZED DAMPER
FIRE/SMOKE DAMPER
SMOKE DAMPER
FIRE DAMPER
MANUAL VOLUME DAMPER
RADIUS ELBOW (45° AND 90°)
SQ. OR RECT. TEE WITH TURNING VANES
SQ. OR RECT.ELBOW WITH TURNING VANES
(45° AND 90°)
SINGLE SIDED TRANSITION
DOUBLE SIDED TRANSITION
CONICAL TAP ROUND BRANCH TAKE-OFF
W/ MANUAL VOLUME DAMPER
CONICAL TAP ROUND BRANCH TAKE-OFF
45° TAP BRANCH TAKE-OFF
FLEXIBLE DUCT
ROUND ELBOW TURNED DOWN
W/ TAG
ROUND ELBOW TURNED UP
W/ TAG
SQ. OR RECT. ELBOW TURNED DOWN
W/ TAG
SQ. OR RECT. ELBOW TURNED UP
W/ TAG
EXHAUST DUCT (EA)
RETURN DUCT (RA)
SUPPLY DUCT (SA)
TO BE DEMOLISHED
EXISTING TO REMAIN
DUCT SIZE TAG (ROUND)
DUCT SIZE TAG (SQ. OR RECT.)
MECHANICAL SYMBOLS LEGEND
EXPANSION JOINTEJ
T STEAM TRAP
SYMBOLS
& AND
@ AT
# NUMBER or POUND
A
A/E ARCHITECT/ENGINEER
AC AIR CONDITIONER(ING)
ACH AIR CHANGES PER HOUR
ACCU AIR COOLED CONDENSING UNIT
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
ADJ ADJUSTABLE/ADJACENT
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
AMB AMBIENT
AP ACCESS PANEL
APPROX APPROXIMATE(LY)
ASD ADJUSTABLE SPEED DRIVE
AS AIR SEPARATOR
ASSY ASSEMBLY
ATM ATMOSPHERE
AUX AUXILIARY
AV AIR VENT
AVG AVERAGE
B
BAS BUILDING AUTOMATION SYSTEM
BCU BLOWER COIL UNIT
BDD BACKDRAFT DAMPER
BFF BELOW FINISHED FLOOR
BFBP BOILER FEED BOOSTER PUMP
BHP BRAKE HORSEPOWER
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNITS PER HOUR
C
CAL CALIBRATE
CAP CAPACITY
CAV CONSTANT AIR VOLUME
CCR CONCENTRIC REDUCER
CCW COUNTER CLOCKWISE
CFM CUBIC FEET PER MINUTE
CFH CUBIC FEET PER HOUR
CH CHILLER
CHP CHILLED WATER PUMP
CHWS CHILLED WATER SUPPLY
CHWR CHILLED WATER RETURN
CHSP CHILLED WATER SECONDARY PUMP
CIP CAST IRON PUMP
CIRC CIRCULATING
CISP CAST IRON SOIL PIPE
CL CENTER LINE
CLG CEILING
CLR CLEAR(ANCE)
CLW CLOCKWISE
CO CARBON MONOXIDE
CO2 CARBON DIOXIDE
COND CONDENSATE
CONSTR CONSTRUCTION
CONT CONTINUATION
CONTR CONTRACTOR
CONV CONVERTER
COORD COORDINATE
CP CONDENSATE PUMP
CT COOLING TOWER
CTRL CONTROL
CU COPPER
CU FT CUBIC FEET
CU IN CUBIC INCH
CUH CABINET UNIT HEATER
CWP CONDENSER WATER PUMP
D
°/DEG DEGREE
°C DEGREES CELSIUS
°F DEGREES FAHRENHEIT
DB DRY BULB
DDC DIRECT DIGITAL CONTROLS
DEMO DEMOLITION
DIA DIAMETER
DIAG DIAGRAM
DIFF DIFFUSER
DIP DUCTILE IRON PIPE
DMPR DAMPER
DN DOWN
DW DISHWASHER
DWG DRAWING
E
EA EXHAUST AIR OR EACH
EAT ENTERING AIR TEMPERATURE
ECCR ECCENTRIC REDUCER
ECON ECONOMIZER
ECU EVAPORATIVE COOLING UNIT
EDB ENTERING DRY BULB (TEMP)
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN / ENERGY FACTOR
EG EXHAUST GRILLE
EH EXHAUST HOOD
ELEV ELEVATION
ELEC ELECTRICAL
EQ EQUAL
EQUIP EQUIPMENT
EQUIV EQUIVALENT
ER EXHAUST REGISTER
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EWB ENTERING WET BULB
EWT ENTERING WATER TEMPERATURE
EX EXISTING
F
FCU FAN COIL UNIT
FD FIRE DAMPER
FOB DUCT FLAT ON BOTTOM
FOT DUCT FLAT ON TOP
FPT FEMALE PIPE THREAD
FS FLOW SWITCH
FSEC FOOD SERVICE EQUIPMENT CONTRACTOR
FSD FIRE/SMOKE DAMPER
FT FINNED TUBE RADIATION
FTHD FOOT HEAD OR PRESSURE DROP
G
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GV GRAVITY VENTILATOR
H
H HUMIDISTAT
HG MERCURY
HORIZ HORIZONTAL
HP HORSEPOWER
HPR HIGH PRESSURE STEAM RETURN
HPS HIGH PRESSURE STEAM SUPPLY
HTG HEATING
HTR HEATER
HVAC HEATING, VENTILATION, AIR CONDITIONING
HX HEAT EXCHANGER
HZ HERTZ (FREQUENCY)
I
ID INSIDE DIAMETER
IE INVERT ELEVATION
IN INCHES
IN WC INCHES (WATER COLUMN)
INS INSULATION
INSTR INSTRUMENT
IP IRON PIPE
IPS IRON PIPE SIZE
IPLV INTEGRATED PART LOAD VALUE
ISO ISOMETRIC
K
K KELVIN
KW KILOWATT
KWH KILOWATT HOUR
L
LAT LEAVING AIR TEMPERATURE
LB(S) POUND(S)
LDB LEAVING DRY BULB (TEMP)
LWB LEAVING WET BULB (TEMP)
LWT LEAVING WATER TEMPERATURE
M
MAINT MAINTENANCE
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MBH BRITISH THERMAL UNIT (1000/HR)
MC MECHANICAL CONTRACTOR
MCC MOTOR CONTROL CENTER
MCA MINIMUM CIRCUIT AMPS
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM OR MINUTE
MISC MISCELLANEOUS
MOD MOTOR OPERATED DAMPER
MOV MOTOR OPERATED VALVE
MPT MALE PIPE THREAD
N
NA NOT APPLICABLE
NC NORMALLY CLOSED OR NOISE CRITERIA
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM NOMINAL
NPLV NON STANDARD PART LOAD VALUE
NPT NATIONAL PIPE THREAD
NTS NOT TO SCALE
O
OA OUTDOOR AIR
OAD OUTDOOR AIR DAMPER
OD OUTER DIAMETER
OFCI OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
P
PG PRESSURE GAUGE
PH PHASE
PRV PRESSURE RELIEF VALVE OR PRESSURE
REGULATING VALVE
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
PUH PROPELLER UNIT HEATER
R
RA RETURN AIR
REFR REFRIGERATION
REQD REQUIRED
RG RETURN AIR GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RPM REVOLUTIONS PER MINUTE
RPZ REDUCED PRESSURE ZONE
RTU ROOFTOP UNIT
S
SA SUPPLY AIR
SCH SCHEDULE
SCHM SCHEMATIC
SD SMOKE DAMPER
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SUPPLY FAN OR SQUARE FEET
SHT SHEET
SP STATIC PRESSURE
SPEC SPECIFICATION(S)
SQ IN SQUARE INCH
SS STAINLESS STEEL
STBY STANDBY
STD STANDARD
STL STEEL
SUCT SUCTION
SV SAFETY VALVE
SYS SYSTEM
SRV SAFETY RELIEF VALVE
T
T THERMOSTAT
TAB TERMINAL AIR BOX
TCC TEMPERATURE CONTROL CONTRACTOR
TEFC TOTALLY ENCLOSED FAN COOLED
TEMP TEMPERATURE OR TEMPORARY
THRU THROUGH
TOD TOP OF DUCT
TOP TOP OF PIPE
TP TOTAL PRESSURE
TYP TYPICAL
U
UL UNDERWRITERS LABORATORIES
UNO UNLESS NOTED OTHERWISE
UTIL UTILITY
UV UNIT VENTILATOR
V
VAV VARIABLE AIR VOLUME
VBX VALVE BOX
VD VOLUME DAMPER
VEL VELOCITY
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
W
W/ WITH
W/O WITHOUT
WB WET BULB
WH WALL HYDRANT
WPD WATER PRESSURE DROP
WT WEIGHT
WTR WATER
MECHANICAL ABBREVIATIONS
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2023Autodesk Revit 2023
/2
/2
:5 :1
A
M
A u to d e s k D o c s /2
I A
D A
S
D O
C M
P C
F B ld g
E le v a to r
R e p /2
-M E
P -R
.r v t
M E
C H
A N
IC
A
L G
E N
E R
A L
IN
F
O R
M A
T
IO
N B
ID
D
IN
G
F ie ld B o o k
T L S
S R
T
/2
/2
M000
IA
D
A S
D
O C
M P
C F
B ld g
E le v a to r R e p
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
C L
IE
N T
P R
O J E
C T
N U
M B
E R
D
A S
.0
E
W a s h in g to n S t, M t P le a s a n t, I A
AC
SP
2" SAN
N
01/4" = 1'-0"F6
ROOF MECHANICAL DEMOLITION PLAN
6'
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2023Autodesk Revit 2023
/2
/2
:5 :1
A
M
A u to d e s k D o c s /2
I A
D A
S
D O
C M
P C
F B ld g
E le v a to r
R e p /2
-M E
P -R
.r v t
M E
C H
A N
IC
A
L D
E M
O P
L A
N
B
ID
D
IN
G
F ie ld B o o k
T L S
S R
T
/2
/2
MD100
IA
D
A S
D
O C
M P
C F
B ld g
E le v a to r R e p
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
C L
IE
N T
P R
O J E
C T
N U
M B
E R
D
A S
.0
E
W a s h in g to n S t, M t P le a s a n t, I A
N
01/4" = 1'-0"C6
BASEMENT MECHANICAL DEMOLITION PLAN
6'
SEE ARCH
SHEETS FOR
INFILL
REMOVE AC UNIT
AND PROVIDE TO
OWNER
ACCU-1
3/4" COND
FCU-1
RL RS
2" SAN
2" SAN 2" SAN2" SAN
2" SAN UP
SUMP
ALARM
LOCATION
P01
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2023Autodesk Revit 2023
/2
/2
:5 :1
A
M
A u to d e s k D o c s /2
I A
D A
S
D O
C M
P C
F B ld g
E le v a to r
R e p /2
-M E
P -R
.r v t
M E
C H
A N
IC
A
L P
L A
N
B
ID
D
IN
G
F ie ld B o o k
T L S
S R
T
/2
/2
M100
IA
D
A S
D
O C
M P
C F
B ld g
E le v a to r R e p
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
C L
IE
N T
P R
O J E
C T
N U
M B
E R
D
A S
.0
E
W a s h in g to n S t, M t P le a s a n t, I A
N
01/4" = 1'-0"C6
BASEMENT NEW CONSTRUCTION SSV PLAN
6'
N
01/4" = 1'-0"F6
ROOF NEW CONSTRUCTION MECHANICAL PLAN
6'
N
01/4" = 1'-0"F4
FIRST FLOOR NEW CONSTRUCTION SSV PLAN
6'
KEYNOTES
KEY NOTE
P01 NEW COWTONGUE FITTING. 18" ABOVE GRADE.
DISCHARGE ONTO NEW SPLASHPAD
CUT SMOOTH HOLE
THROUGH WALL
CEMENT GROUT TROWEL SMOOTH
SCHEDULE 20 BLACK STEEL PIPE SLEEVE
SIZE TO SUIT INSULATION CUT SMOOTH WITH WALL
PIPING WITH
INSULATION AND COVER
POLYURETHANE SEALANT
CONTINUOUS BACKER ROD
+- 1/4" CLEARANCE BETWEEN
COLLAR AND INSULATION ON PIPE
INSULATION AS SPECIFIED
PASSES THRU PIPE SLEEVE
(CHILLED WATER)
ELEVATOR PIT
FIBERGLASS SUMP
BASIN
ALARM
PANEL
SEE PLAN
FOR
LOCATION
DISCHARGE
PIPING
TYPE-A
8" OR LARGER
TYPE-B
6" OR SMALLER
TYPICAL ELEVATION
ROD
HANGER
INSULATION
~C PIPE
SHEET METAL SHIELD
PIPE AND HANGER
6" LONG HARDWOOD
BLOCKS SHAPED TO FIT
HANGER
ROD
~C PIPE
~C PIPE
2" AND SMALLER:
2 1/2" TO 6":
8" AND LARGER:
LENGTH OF SHIELD TO BE AT
LEAST 6" LONGER THAN THE
OUTSIDE DIAMETER OF THE
INSULATION
12 GAGE
14 GAGE
16 GAGE
SHIELD SCHEDULE
6" LONG HARDWOOD
BLOCKS SHAPED TO
FIT PIPE AND HANGER
REMARKS
MINIMUM
PIPE
SIZE
3/4"
1 1/4"
1"
OVER 20 TONS AND UP TO 90 TONS OF REFRIGERATION
OVER 3 TONS AND UP TO 20 TONS OF REFRIGERATION
UP TO 3 TONS OF REFRIGERATION
CONDENSATE DRAIN PIPE SCHEDULE
EQUIPMENT CAPACITY
NOTE:
1. PIPING SHALL SLOPED
IN THE DIRECTION OF
FLOW AT 1/8" PER FOOT
MINIMUM.
2. PIPING SHALL BE
SUPPORTED
INDEPENDENTLY OF THE
COILS.
3. DRAIN LINES SHALL BE
RUN FULL SIZE (MINIMUM)
FROM THE DRAIN PAN
CONNECTION.
COORDINATE SIZE
REQUIREMENTS WITH
SCHEDULE ABOVE.
4. "TRAP DEPTH" AND "THE
DISTANCE BETWEEN THE
TRAP AND TRAP OUTLET"
SHALL BE TWICE
(MINIMUM) THE STATIC
PRESSURE IN THE DRAIN
PAN SECTION.
CLEANOUT
PRESSURE (P) AT DRAIN PAN
P
P
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P A
R K
W A
Y S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
AAuuttooddeesskk RReevviitt 22002233
/2
/2
:5 :1
A
M
A u to d e s k D o c s /2
I A
D A
S
D O
C M
P C
F B ld g
E le v a to r
R e p /2
-M E
P -R
.r v t
M E
C H
A N
IC
A
L S
C H
E D
U L E
S A
N D
D E
T A
IL
S
B
ID
D
IN
G
F ie ld B o o k
T L S
S R
T
/2
/2
M500
IA
D
A S
D
O C
M P
C F
B ld g
E le v a to r R e p
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s
C L
IE
N T
P R
O J E
C T
N U
M B
E R
D
A S
.0
E
W a s h in g to n S t, M t P le a s a n t, I A
2. PROVDE WITH MANUFACTURER'S WIND BAFFLES WB-PA5, WB-RE5, WB-SD5
1. PROVIDE WITH MANUFACTURER'S CONDENSER WALL BRACKET QSWB2000M-1
REMARKS:
AIR COOLED CONDENSING UNIT SCHEDULE
MARK
CAPACITY
(MBH)
COND
AMBIENT AIR
TEMP (°F)
MINIMUM
OPERATING
AMBIENT
TEMPERATURE
NUMBER OF
CIRCUITS
NUMBER OF
COMPRESSORS SEER
ELECTRICAL DATA
OPERATING
WEIGHT
REFRIGERANT
TYPEVOLTS PHASE MCA DESIGN BASIS REMARKS
ACCU-1 24 95 -13 1 1 21.6 208 1 17 190 410A PUZ-HA24NHA1 1,2
1. XXX
REMARKS:
DUCTLESS AIR CONDITIONER SCHEDULE
MARK CFM
COOLING
(MBH)
HEATING
(MBH)
OPERATING
WEIGHT
REFRIGERANT
USED
ELECTRICAL DATA
VOLTS PHASE MCA DESIGN BASIS REMARKS
FCU-1 810 24 28 56 410A 208 1 0.6 PLA-A24EA7 XXX
3. PROVIDE WITH 15' 13AMP SINGLE PIGGYBACK VARIABLE LEVEL FLOAT SWITCH
2. INSTALL PUMP IN NEW FIBERGLASS SUMP BASIN, COORDINATE WITH ELEVATOR EQUIPMENT
1. 10-4014 Z CONTROL ALARM WITH FLOAT SWITCH
REMARKS:
SUMP PUMP SCHEDULE
MARK GPM HEAD (FT)
SHUTOFF
HEAD (FT)
MOTOR DATA ELECTRICAL DATA SUMP BASIN
HP VOLTS PHASE DIAMETER DEPTH DESIGN BASIS REMARKS
SP-1 53 22 44 1/2 120 1 1' - 0 1/4" 1' - 3 1/2" ZOELLER 153 1,2
NOT TO SCALEF6
Exterior Wall Pipe Penetration Detail
NOT TO SCALEE6
ELEVATOR PIT Sump Pump Detail
NOT TO SCALEC6
Insulated Pipe Hanger Detail
NOT TO SCALEF5
Drain Pan Piping Detail
R
S
FS
TS
VFD
B
L
L S
FACP
FARP
FSCP
DR
FR
E
J
WALL MOUNTED LIGHT
EMERGENCY LIGHT
EXIT SIGN
LIGHT FIXTURE ON EMERGENCY CIRCUIT
SINGLE POLE SWITCH
3-WAY SWITCH
4-WAY SWITCH
PUSH BUTTON
DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
BRANCH PANEL WITH CLEARANCE
(SURFACE OR RECESS MOUNTED)
TRANSFORMER
DISCONNECT SWITCH
VARIABLE FREQUENCY DRIVE
RELAY
CONDUIT CONCEALED IN WALL OR OVERHEAD
CONDUIT CONCEALED BELOW FLOOR
CONDUIT TRANSITION UP
CONDUIT TRANSITION DOWN
CONDUIT STUBBED OUT
BRANCH CIRCUIT HOME RUN
VOICE/DATA OUTLET (WALL OR CEILING)
# - QUANTITY OF RJ-45 JACKS/CABLES.
ONE, UNLESS SHOWN OTHERWISE
W - DENOTES WALL PHONE
SPEAKER (WALL OR CEILING MOUNT)
KEYNOTE (SEE SCHEDULE)E#
SPRINKLER FLOW SWITCH
SPRINKLER VALVE TAMPER SWITCH
AUDIO NOTIFICATION DEVICE - CEILING MOUNTED
B = BELL
C = CHIME
H = HORN
S = SPEAKER
AUDIO NOTIFICATION DEVICE - WALL MOUNTED
B = BELL
C = CHIME
H = HORN
S = SPEAKER
VISUAL NOTIFICATION DEVICE - CEILING MOUNTED
VISUAL NOTIFICATION DEVICE - WALL MOUNTED
AUDIO/VISUAL NOTIFICATION DEVICE -
CEILING MOUNTED
B = BELL
C = CHIME
H = HORN
S = SPEAKER
AUDIO/VISUAL NOTIFICATION DEVICE -
WALL MOUNTED
B = BELL
C = CHIME
H = HORN
S = SPEAKER
FIRE ALARM CONTROL PANEL
FIRE ALARM RELAY PANEL
FIRE SUPPRESSION CONTROL PANEL
DOOR HOLDER/HOLD OPEN
SMOKE DAMPER RELEASE
FIRE ALARM SHUT DOWN RELAY
SMOKE DETECTOR
HEAT DETECTOR
FIREFIGHTER PHONE
EMERGENCY EXIT SIGN
SPECIAL RECEPTACLE
(CEILING, WALL, AND FLOOR MOUNTED)
DIRECT POWER CONNECTION -
WALL AND EQUIPMENT
JUNCTION BOX
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE ON EMERGENCY CIRCUIT
DOUBLE DUPLEX RECEPTACLE ON EMERGENCY CIRCUIT
RECEPTACLE ON DROP CORD (DUPLEX SHOWN)
RECEPTACLE ON CORD REEL (DUPLEX SHOWN)
J
ENCLOSED CIRCUIT BREAKER
DOOR SIGNAL - APARTMENT UNIT
BUZZER
D
BELL
CHIME
SYMBOL DESCRIPTION
LIGHTING/CONTROLS
GENERAL
POWER
COMMUNICATION/DATA
SECURITY
FIRE ALARM
ELECTRICAL SYMBOLS LEGEND
FUSED DISCONNECT SWITCH
EXAMPLE RECEPTACLE TAG
##" - MOUNTING HEIGHT AS INDICATED.
IF OMITTED, 18" OR ABOVE COUNTER
XX - INDICATES RECEPTACLE CONFIGURATION:
XX
AC
GFI
HZ
IG
OC
USB
WP
XP
ABOVE COUNTER (COORDINATE HEIGHT)
GROUND FAULT CIRCUIT INTERRUPTER
HORIZONTALLY MOUNTED
ISOLATED GROUND
OCCUPANCY CONTROLLED
INTEGRAL USB CHARGER
WEATHERPROOF
EXPLOSION PROOF
XX
XX
FIRE ALARM - CONTINUED
MANUAL PULL STATION
ANN FIRE ALARM REMOTE ANNUNCIATOR
EMERGENCY POWER OFF
SURFACE MOUNTED RECEPTACLE, VARIES PER TYPE
MX MOTOR HORSEPOWER RATED SWITCH
F
L S
L
B
DH
S
E
J
DESCRIPTIONSYMBOL
POWER (CONTINUED)
SYMBOL DESCRIPTION
C CAMERA
1. ALL WORK SHALL BE IN CONFORMANCE WITH THE NATIONAL
ELECTRICAL CODE - LATEST EDITION ADOPTED BY THE STATE,
THE STATE AMENDMENTS, LOCAL/MUNICIPAL CODES AND
ORDINANCES, AND THE AUTHORITY HAVING JURISDICTION.
THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE
WITH THE ADAAG (AMERICANS WITH DISABILITIES ACT
ACCESSIBILITY GUIDELINES).
2. IT IS THE INTENT OF THESE DOCUMENTS TO COMPLY WITH
THE APPLICABLE CODES. WHERE DISCREPANCIES OCCUR,
NOTIFY THE ENGINEER/ARCHITECT IN WRITING FOR
INTERPRETATION. CORRECT ANY INSTALLATION THAT FAILS
TO COMPLY WITH THE CODES AND STANDARDS AT NO
ADDITIONAL COST TO THE OWNER.
3. CONTRACTOR SHALL PROVIDE ALL WORK NECESSARY
INCLUDING ALL LABOR, MATERIALS, PERMITS, TAXES, FEES,
INSPECTIONS, HARDWARE, AND COST FOR INSTALLATION FOR
A COMPLETE AND OPERATIONAL SYSTEM.
4. ALL MATERIALS FURNISHED BY THE CONTRACTOR SHALL BE
NEW, COMPLETE WITH MANUFACTURER’S GUARANTEE OR
WARRANTY AND SHALL BE LISTED BY A NATIONALLY
RECOGNIZED TESTING LABORATORY (NRTL).
5. COORDINATE ELECTRICAL INSTALLATION WITH ALL TRADES
PRIOR TO INSTALLATION. IF ELECTRICAL WORK INSTALLED
INTERFERES WITH OTHER TRADES AFTER INSTALLATION, THE
CONTRACTOR SHALL MAKE ALL…