RFB927940-01 WRC Decentralization Phase 4 - Drawings.pdf
PDF 24 MB Posted
- Solicitation number
- RFB927940-01
- Issued by
- Black Hawk County, Iowa
About this file
WRC Decentralization Phase 4 Construction Project - Design Drawings
This document comprises comprehensive construction drawings and specifications for the Woodward Resource Center (WRC) Decentralization Phase 4 project, prepared by the Iowa Department of Administrative Services. The project encompasses mechanical, electrical, architectural, and civil work across multiple campus buildings including Elmcrest, Medical Center, Birches, Powerhouse, Dispatch Garage, and associated utility infrastructure. The scope includes converting existing steam-based heating systems to hot water distribution, installing new chilled water systems with air-cooled chillers at Elmcrest and Medical Center, replacing fire alarm systems, upgrading electrical distribution panels, and installing new unit heaters throughout the affected facilities. The project is issued for construction as of March 14, 2025, with a construction start date of June 23, 2025, and completion date of May 29, 2026. An optional pre-bid conference was scheduled for April 30, 2025, at Stony Construction CP2 location, with project bidding closing on May 14, 2025, through the IMPACS Electronic Procurement System.
The drawings detail mechanical specifications including two 1,500 MBH fire-tube boilers, multiple hot water pumps, air-cooled chillers (185 tons at Elmcrest and 95.3 tons at Medical Center), expansion tanks, and comprehensive piping schedules. Electrical coordination includes new 225-ampere and 600-ampere distribution panels, unit heater control circuits, fire alarm system integration, and interconnected building automation systems. A 5% bid security is required for contract submission. The project involves substantial infrastructure upgrades with equipment replacements at five major buildings, requiring contractors to demonstrate expertise in mechanical systems installation, piping work, electrical distribution, controls integration, and ability to coordinate work across occupied facilities. Davis Bacon wages do not apply to this contract, and the state encourages participation from Targeted Small Businesses in accordance with Iowa Code Chapter 73. Specific budget allocation was not disclosed in the bidding documents reviewed.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL:
PRINTED OR TYPED NAME
SIGNATURE
MY LICENSE RENEWAL DATE IS DECEMBER 31,
DATE
LICENSE NUMBER
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS
OF THE STATE OF IOWA.
John D. Baumhover
M SHEETS
25737
MECHANICAL ENGINEER
PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL:
PRINTED OR TYPED NAME
SIGNATURE
MY LICENSE RENEWAL DATE IS DECEMBER 31,
DATE
LICENSE NUMBER
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS
OF THE STATE OF IOWA.
Kevin J. Bruxvoort
E SHEETS
19927
ELECTRICAL ENGINEER
W
E S
T O
W N
P K
W Y
S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
SHEET INDEX CERTIFICATIONS
H
BA D E FC G H3
/1
/2
:3 :2
P
M
A u to d e s k D o c s /I A
D A
S
W R
C P ro je c ts
/F ir e P u m p H o u s e -M
E P
-C e n t.
rv t
WRC Decentralization Phase 4 & Fire Alarm Phase 3 (#9279.40) Bid Issuance #1
Iowa Department of Administrative Services 1251 334th St, Woodward, IA 50276
00-G000
W R
C D e c e n tr a liz a ti o n P h a s e
F ir e
A la rm P h a s e
.4
B id I s s u a n c e
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s th
S t, W o o d w a rd
IA
P R
O J E
C T
N U
M B
E R
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
IS
S U
E D
A T
E
-1
-2
SHEET NUMBER ELMCREST SHEET INDEX
ARCHITECTURAL
10-AD00 BASEMENT DEMOLITION AND FLOOR PLAN
MECHANICAL
10-MD01 BASEMENT MECHANICAL PIPING DEMOLITION PLAN
10-M100 BASEMENT MECHANICAL PIPING PLAN
10-M500 MECHANICAL CONTROLS
10- M600 MECHANICAL SCHEDULES AND DETAILS
ELECTRICAL
10-E100 BASEMENT LEVEL CHILLER UPGRADES
SHEET NUMBER MEDICAL CENTER INDEX
ARCHITECTURAL
12-AD00 BASEMENT DEMOLITION AND FLOOR PLAN
MECHANICAL
12-MD1 BASEMENT MECHANICAL PIPING DEMOLITION PLAN
12 -M100 BASEMENT MECHANICAL PIPING PLAN
12 -M500 MECHANICAL CONTROLS
12 -M600 MECHANICAL SCHEDULES AND DETAILS
ELECTRICAL
12-E100 BASEMENT LEVEL CHILLER UPGRADES
SHEET NUMBER DISPATCH GARAGE INDEX
MECHANICAL
15-MD101 MECHANICAL DEMOLITION PLANS
15-M100 MECHANICAL PLANS
15-M600 MECHANICAL SCHEDULES & DETAILS
ELECTRICAL
15-ED201 FIRST FLOOR AND MEZZANINE LEVEL POWER DEMOLITION PLAN
15-E201 FIRST FLOOR AND MEZZANINE LEVEL POWER PLAN
15-E600 ELECTRICAL SCHEDULES
SHEET NUMBER GENERAL SHEET INDEX
GENERAL
00-G000 COVER SHEET
00-G001 CAMPUS MAP
CIVIL
00-C101 SITE PLAN
00-C102 SITE PLAN
00-C103 SITE PLAN
00-C501 CONSTRUCTION DETAILS
00-CD01 EXISTING CONDITIONS AND DEMOLITION PLAN
00-CD02 EXISTING CONDITIONS AND DEMOLITION PLAN
00-CD03 EXISTING CONDITIONS AND DEMOLITION PLAN
ARCHITECTURAL
00-A000 ARCHITECTURAL GENERAL INFORMATION
MECHANICAL
00-M000 GENERAL MECHANCIAL AND PLUMBING SYMBOLS & NOTES
ELECTRICAL
00-E000 ELECTRICAL GENERAL INFORMATION
00-E010 ELECTRICAL SITE PLAN - LINDEN COURT
00-E011 ELECTRICAL RISER DIAGRAM
I HEREBY CERTIFY THAT THE PORTION OF THIS TECHNICAL
SUBMISSION DESCRIBED BELOW WAS PREPARED BY ME OR UNDER
MY DIRECT SUPERVISION AND RESPONSIBLE CHARGE. I AM A DULY
LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF IOWA.
PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL
PRINTED OR TYPED NAME
SIGNATURE
MY LICENSE RENEWAL DATE IS JUNE 30,
DATE
ARCHITECT
LICENSE NUMBER
Cameron L. Manley
A SHEETS
06716
SHEET NUMBER BIRCHES SHEET INDEX
ARCHITECTURAL
16-AD01 BASEMENT, FIRST, AND SECOND DEMOLITION PLANS
16-A100 BASEMENT FLOOR PLAN
16-A101 FIRST FLOOR PLAN
16-A102 SECOND FLOOR PLAN AND THIRD FLOOR PLAN
16-A110 BASEMENT AND FIRST FLOOR REFLECTED CEILING PLANS
16-A111 SECOND AND THIRD FLOOR REFLECTED CEILING PLANS
MECHANICAL
16-MD100 BASEMENT MECHANICAL PIPING DEMOLITION PLAN
16-MD101 FIRST FLOOR MECHANICAL PIPING DEMOLITION PLAN
16-MD102 SECOND AND THIRD FLOOR MECHANICAL PIPING DEMOLITION PLAN
16-M100 BASEMENT MECHANICAL PIPING PLAN
16-M101 FIRST FLOOR MECHANICAL PIPING PLAN
16-M102 SECOND AND THIRD FLOOR MECHANICAL PIPING PLAN
16-M300 BASEMENT MECHANICAL THERMOSTAT PLAN
16-M301 FIRST FLOOR MECHANICAL THERMOSTAT PLAN
16-M302 SECOND AND THIRD FLOOR MECHANICAL THERMOSTAT PLAN
16-M400 ENLARGED MECHANICAL PLANS AND SCHEMATICS
16-M500 MECHANICAL DETAILS
16-M501 MECHANICAL CONTROLS
16-M600 MECHANICAL SCHEDULES
ELECTRICAL
16-ED100 BASEMENT ELECTRICAL SYSTEMS DEMOLITION PLAN
16-ED101 FIRST FLOOR ELECTRICAL SYSTEMS DEMOLITION PLAN
16-ED102 SECOND AND THIRD FLOOR ELECTRICAL SYSTEMS DEMOLITION PLAN
16-E100 BASEMENT ELECTRICAL SYSTEMS PLAN
16-E101 FIRST FLOOR ELECTRICAL SYSTEMS PLAN
16-E102 SECOND AND THIRD FLOOR ELECTRICAL SYSTEMS PLAN
16-E400 ELECTRICAL SCHEDULES
SHEET NUMBER POWER HOUSE SHEET INDEX
MECHANICAL
18-MD100 BASEMENT MECHANICAL PIPING DEMOLITION PLAN
18-MD101 FIRST FLOOR MECHANICAL PIPING DEMOLITION PLAN
18-M100 BASEMENT MECHANICAL PLAN
18-M101 FIRST FLOOR MECHANICAL PLAN
18-M102 SECOND FLOOR MECHANICAL PLAN
18-M600 MECHANICAL SCHEDULES
ELECTRICAL
18-ED100 BASEMENT ELECTRICAL SYSTEMS DEMOLITION PLAN
18-ED101 FIRST FLOOR ELECTRICAL SYSTEM DEMOLITION PLAN
18-ED102 SECOND AND THIRD FLOOR ELECTRICAL DEMOLITION PLAN
18-E100 BASEMENT ELECTRICAL SYSTEMS PLAN
18-E101 FIRST FLOOR ELECTRICAL SYSTEMS PLAN
18-E102 SECOND AND THIRD FLOOR ELECTRICAL SYSTEMS PLAN
18-E400 ELECTRICAL SCHEDULES
CIVIL
00-C101 SITE PLAN
00-C102 SITE PLAN
00-C103 SITE PLAN
00-C501 CONSTRUCTION DETAILS
00-CD01 EXISTING CONDITIONS AND DEMOLITION PLAN
00-CD02 EXISTING CONDITIONS AND DEMOLITION PLAN
00-CD03 EXISTING CONDITIONS AND DEMOLITION PLAN
00-C001 GENERAL NOTES
00-C102 SITE PLAN
00-C103 SITE PLAN
00-C501 CONSTRUCTION DETAILS
00-CD02 EXISTING CONDITIONS AND DEMOLITION PLAN
00-CD03 EXISTING CONDITIONS AND DEMOLITION PLAN
00-C203 GRADING PLAN
00-CD02 EXISTING CONDITIONS AND DEMOLITION PLAN00-C501 CONSTRUCTION DETAILS
00-C202 GRADING PLAN
PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL:
PRINTED OR TYPED NAME
SIGNATURE
MY LICENSE RENEWAL DATE IS DECEMBER 31,
DATE
LICENSE NUMBER
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS
OF THE STATE OF IOWA.
John D. Baumhover
M SHEETS
25737
MECHANICAL ENGINEERCIVIL ENGINEER
Chris R. Bauer
19737
G & C SHEETS
PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL:
PRINTED OR TYPED NAME
SIGNATURE
MY LICENSE RENEWAL DATE IS DECEMBER 31,
DATE
LICENSE NUMBER
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS
OF THE STATE OF IOWA.
John D. Baumhover
M SHEETS
25737
MECHANICAL ENGINEER
PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL:
PRINTED OR TYPED NAME
SIGNATURE
MY LICENSE RENEWAL DATE IS DECEMBER 31,
DATE
LICENSE NUMBER
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS
OF THE STATE OF IOWA.
Kevin J. Bruxvoort
E SHEETS
19927
ELECTRICAL ENGINEER
CERTIFICATIONS
I HEREBY CERTIFY THAT THE PORTION OF THIS TECHNICAL
SUBMISSION DESCRIBED BELOW WAS PREPARED BY ME OR UNDER
MY DIRECT SUPERVISION AND RESPONSIBLE CHARGE. I AM A DULY
LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF IOWA.
PAGES, SHEETS OR DIVISIONS COVERED BY THIS SEAL
PRINTED OR TYPED NAME
SIGNATURE
MY LICENSE RENEWAL DATE IS JUNE 30,
DATE
ARCHITECT
LICENSE NUMBER
Cameron L. Manley
A SHEETS
06716
3-14-2025
3-14-2025
3-14-2025
3-14-2025
DO NOT PARK
TRUCKS OR
EQUIPMENT OVER
TUNNELS.
DO NOT PARK
TRUCKS OR
EQUIPMENT OVER
TUNNELS.
DO NOT PARK
TRUCKS OR
EQUIPMENT OVER
TUNNELS.
DO NOT PARK
TRUCKS OR
EQUIPMENT OVER
TUNNELS.
18-POWER HOUSE
16-BIRCHES
10-ELMCREST
12- MED CENTER
11-FOOD SERVICE
15-DISPATCH
GARAGE
A P
P R
O V
E D
B Y
D R
A W
N B
Y
IS
S
U E
D F
O R
IS
S
U E
D A
T E
P R
O J E
C T
N U
M B
E R
F
IE
L D
B O
O K
W
E S
T O
W N
P K
W Y
S
U
IT
E
W E
S T
D E
S M
O
IN
E S
IA
.2
.8
S
H
IV
E -H
A T
T E
R Y
.C O
M
BA D E
FC G
H
BA D E FC G H
Autodesk Revit 2022
/1
/2
:2 :2
P
M
A u to d e s k D o c s /I A
D A
S
W R
C P ro je c ts
/F ir e P u m p H o u s e -M
E P
-C e n t.
rv t
C A
M P
U S
M A
P
IS
S
U E
D F
O R
C O
N S
T R
U C
T
IO
N
J D
B
L D
F
-1
-2
00-G001
W R
C D e c e n tr a liz a ti o n P h a s e
F ir e A la rm
P h a s e
.4
Io w a D e p a rt m e n t o f
A d m in is tr a ti v e S e rv ic e s th
S t, W o o d w a rd
IA
NOT TO SCALE1
SITE MAP PH4
C O
N S
T R
U C
T
IO
N
0.
8.
S
H
IV
E- H
AT
TE
R Y.
C O
M
A B C D E F HG
A B C D E F HG
Pr in te d:
D R
AW
N
B Y
AP
PR
O
VE
D B
Y
IS
SU
ED
F
O R
IS
SU
E D
AT
E
FI
EL
D B
O O
K:
PR
O
JE
C
T N
U M
BE
R
\\s h.
sh ive
-h at te ry
.c om
\D
AT
A\ Pr oj ec ts \2
4\
\D el ive ra bl es \D ra wi ng s\
1_ Ci vil \C
G
EN
ER
AL
N O
TE
S.
dw g
3/
/2
:2 0:
A
M
00-C001
G
EN
ER
AL
N O
TE
S
BD
D
C R
B
C O
N
ST
R U
C
TI
O N
-0 3-
40 ---
.4
0) W
R C
D
EC
EN
TR
AL
IZ
AT
IO
N P
H
AS
E
IO
W
A D
EP
AR
TM
EN
T O
F
AD
M
IN
IS
TR
AT
IV
E
SE
R
VI
C
ES
4T
H S
T.
W
O O
D W
AR
D
, I A
GENERAL NOTES
1. THE LOCATIONS OF UTILITY MAINS, STRUCTURES AND SERVICE CONNECTIONS PLOTTED ON THE DRAWINGS ARE
APPROXIMATE ONLY AND WERE OBTAINED FROM RECORDS MADE AVAILABLE TO SHIVE-HATTERY, INC. THERE MAY BE OTHER EXISTING UTILITY MAINS, STRUCTURES AND SERVICE CONNECTIONS NOT KNOWN TO SHIVE-HATTERY, INC.
AND NOT SHOWN ON THE DRAWINGS. THE VERIFICATION OF EXISTENCE OF AND THE DETERMINATION OF THE EXACT LOCATION OF UTILITY MAINS, STRUCTURES AND SERVICE CONNECTIONS SHALL BE THE RESPONSIBILITY OF THE
CONSTRUCTION CONTRACTOR(S).
2. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL UNCOVER EXISTING UTILITIES AT CRITICAL LOCATIONS TO
VERIFY EXACT HORIZONTAL AND VERTICAL LOCATION.
3. THE FACILITY WILL COMPLETE PRIVATE UTILITY LOCATES OF KNOWN FACILITY UTILITIES. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE ALL LOCATES AND CONFIRM THEY ARE COMPLETED PRIOR TO THE START OF
CONSTRUCTION.
4. IOWA CODE 480, UNDERGROUND FACILITIES INFORMATION, REQUIRES VERBAL NOTICE TO IOWA ONE-CALL BY CALLING 811 OR 1-800-292-8989 NOT LESS THAN 48 HOURS BEFORE EXCAVATING, EXCLUDING WEEKENDS AND
HOLIDAYS.
5. NOTIFY UTILITY COMPANIES WHOSE FACILITIES ARE SHOWN ON THE PLANS OR KNOWN TO BE WITHIN THE
CONSTRUCTION LIMITS OF THE SCHEDULE PRIOR TO EACH STAGE OF CONSTRUCTION.
6. UNLESS OTHERWISE SPECIFIED, ALL WORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE MOST RECENT
EDITION OF IOWA STATEWIDE URBAN DESIGN AND SPECIFICATIONS (SUDAS).
7. ALL WORK AND MATERIALS SHALL COMPLY WITH ALL CITY/COUNTY/STATE REGULATIONS/CODES AND OSHA
STANDARDS.
8. THE MEANS OF THE WORK AND THE SAFETY OF THE CONTRACTOR'S EMPLOYEES ARE SOLELY THE RESPONSIBILITY
OF THE CONTRACTOR.
9. NO WORK SHALL BE PERFORMED BEYOND THE PROJECT LIMITS WITHOUT PRIOR AUTHORIZATION FROM THE
OWNER'S REPRESENTATIVE.
10. PROTECT EXISTING UTILITIES DURING CONSTRUCTION.
11. MAINTAIN POSITIVE DRAINAGE ON THE SITE THROUGHOUT THE PROJECT DURATION.
12. SITE CLEAN-UP SHALL BE PERFORMED ON A DAILY BASIS. DRIVES, ROADWAYS, ETC. SHALL BE KEPT CLEAN AT ALL
TIMES.
13. ALL OPEN EXCAVATIONS SHALL BE PROTECTED.
14. REPAIR OR REPLACE DAMAGED SITE FEATURES (WALLS, PAVEMENT, UTILITIES, FENCES, ETC.) TO REMAIN AT NO
ADDITIONAL EXPENSE TO THE STATE.
15. ANY WORK REQUIRED TO COMPLETE THE SCOPE OF THIS PROJECT BUT NOT SPECIFICALLY CALLED OUT SHALL BE CONSIDERED INCIDENTAL TO THE PROJECT. NO ADDITIONAL COMPENSATION TO BE ALLOWED FOR THE COMPLETION
OF THIS WORK.
16. WORK WHICH DOES NOT CONFORM TO THE REQUIREMENTS OF THE CONTRACT WILL BE CONSIDERED UNACCEPTABLE. UNACCEPTABLE WORK, WHETHER THE RESULT OF POOR WORKMANSHIP, USE OF DEFECTIVE MATERIALS, DAMAGE THROUGH CARELESSNESS OR ANY OTHER CAUSE FOUND TO EXIST PRIOR TO THE FINAL ACCEPTANCE OF THE WORK SHALL BE REMOVED AND REPLACED IN AN ACCEPTABLE MANNER AS REQUIRED BY THE OWNER'S REPRESENTATIVE AT THE CONTRACTOR'S EXPENSE. WORK DONE CONTRARY TO THE INSTRUCTIONS OF THE OWNER'S REPRESENTATIVE, WORK DONE BEYOND THE LINES SHOWN ON THE PLANS OR ANY EXTRA WORK DONE
WITHOUT WRITTEN AUTHORIZATION WILL NOT BE PAID FOR.
17. THE CONTRACTOR SHALL MATCH EXISTING GRADES AT THE CONSTRUCTION LIMITS.
18. NO PONDING OF WATER WILL BE ACCEPTED ON ANY NEW PAVEMENT OR OVERLAY AREAS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO IDENTIFY ANY AREAS OF EXISTING OR PROPOSED PAVEMENTS THAT HAVE THE POTENTIAL TO POND WATER AND MAKE ANY ADJUSTMENTS NECESSARY TO ENSURE THAT WATER WILL POSITIVELY DRAIN
ACROSS THE PAVING.
19. STAGING LOCATIONS AND CONSTRUCTION ACCESS ROUTES FOR CONSTRUCTION EQUIPMENT AND MATERIALS SHALL
BE COORDINATED WITH AND APPROVED BY THE FACILITY AND CONSTRUCTION MANAGER.
20. THE CONTRACTOR SHALL PROVIDE EROSION CONTROL MEASURES NECESSARY TO PROTECT AGAINST SILTATION, EROSION AND DUST POLLUTION ON THE PROJECT SITE AND ANY OFF-SITE BORROW OR DISPOSAL AREAS USED FOR THIS PROJECT. COMPLY WITH SOIL EROSION CONTROL REQUIREMENTS OF IOWA CODE, FEDERAL REGULATIONS AND
LOCAL ORDINANCES.
21. ALL AREAS DISTURBED BY CONSTRUCTION NOT DESIGNATED AS PLANTED SHALL BE SEEDED PER SPECIFICATIONS. 6"
OF TOPSOIL SHALL BE PROVIDED PER SPECIFICATIONS.
22. CONTROL DUST SPREADING FROM ALL WORK AND STAGING AREAS.
23. CONTRACTOR TO COORDINATE ANY SITE, UTILITY OR GRADE ADJUSTMENTS WITH THE CONSTRUCTION MANAGER
PRIOR TO PROCEEDING WITH THE WORK.
24. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF WORK OF ALL SUBCONTRACTOR(S)
INVOLVED ON THE PROJECT.
CONSTRUCTION STAGING NOTES
1. CONTRACTOR SHALL COORDINATE ALL STAGING AREAS WITH THE FACILITY AND CONSTRUCTION MANAGER.
2. CONTRACTOR SHALL REPLACE ALL PAVEMENT DAMAGED BY CONSTRUCTION ACTIVITIES AT THE END OF CONSTRUCTION. CONTRACTOR TO PROVIDE PHOTO DOCUMENTATION OF EXISTING CONDITIONS PRIOR TO
BEGINNING WORK.
3. CONTRACTOR SHALL RESTORE ALL DISTURBED AREAS NOT TO BE PAVED TO THEIR ORIGINAL CONDITION AT THE END OF CONSTRUCTION. ALL DISTURBED AREAS SHALL BE SCARIFIED, TILLED AND SEEDED. CONTRACTOR TO PROVIDE
PHOTO DOCUMENTATION PRIOR TO BEGINNING WORK.
4. CONTRACTOR SHALL PROVIDE BARRICADES, FENCING OR OTHER DEVICES TO KEEP UNAUTHORIZED PERSONNEL OUT
OF PROJECT SITE.
TRAFFIC AND PEDESTRIAN CONTROL NOTES
1. CONTRACTOR IS ALLOWED TO CLOSE DOWN PARKING AND DRIVES DURING CONSTRUCTION WITH PRIOR APPROVAL FROM CONSTRUCTION MANAGER AND FACILITY. ACCESS TO ADJACENT BUILDINGS, DRIVES, PARKING AND SIDEWALKS ARE TO BE MAINTAINED THROUGHOUT CONSTRUCTION. PHASING OF UTILITY CONSTRUCTION AND ROAD PATCHING WILL BE REQUIRED TO MAINTAIN VEHICULAR AND PEDESTRIAN TRAFFIC TO ALL BUILDINGS AND SHALL BE
COORDINATED WITH SCHEDULES OF OTHER TRADES, CONTRACTORS AND UTILITY COMPANIES.
2. IT IS THE CONTRACTOR'S RESPONSIBILITY TO CONTROL TRAFFIC DURING CONSTRUCTION AND PROVIDE ADEQUATE TRAFFIC AND PEDESTRIAN CONTROL AND SIGNAGE. AT A MINIMUM, CONTRACTOR TO PROVIDE TYPE III BARRICADES
AT EACH END OF CLOSED ROADS AND DRIVES.
3. CONTRACTOR TO INSTALL AND MAINTAIN CONSTRUCTION FENCE AROUND ALL AREAS OF ACTIVE CONSTRUCTION.
CONTRACTOR SHALL ASSUME PEDESTRIAN TRAFFIC WILL BE IN THE AREA THROUGHOUT THE PROJECT DURATION.
4. PEDESTRIAN ACCESS MUST BE MAINTAINED TO ALL BUILDINGS THROUGHOUT CONSTRUCTION. COORDINATE WITH FACILITY AND CONSTRUCTION MANAGER ON PHASING AND SHUT DOWN OF ALL DRIVES AND SIDEWALKS. TEMPORARY GRANULAR PATCHES WILL BE REQUIRED FOR ANY DRIVES AND SIDEWALKS WHICH ARE NOT PATCHED WITH CONCRETE IN A TIMELY MANNER TO LIMIT DISRUPTIONS TO CAMPUS TRAFFIC AND PEDESTRIAN FLOW.
5. CONTRACTOR TO COORDINATE CONSTRUCTION ACCESS, STAGING AND PARKING AREAS WITH FACILITY AND
CONSTRUCTION MANAGER AND MINIMIZE IMPACTS TO FACILITY'S OPERATIONS.
DEMOLITION NOTES
1. REMOVAL REQUIREMENTS SHOWN ON THE PLANS SHOULD BE CONSIDERED MINIMUM REMOVAL AND REPLACEMENT REQUIREMENTS. CONTRACTORS SHALL ADJUST REMOVAL LIMITS AND DIMENSIONS AS REQUIRED BY CONSTRUCTION MEANS AND METHODS AND ACTUAL SITE CONDITIONS. CONTRACTORS SHOULD FACTOR ADDITIONAL ANTICIPATED REMOVAL AND REPLACEMENT REQUIREMENTS INTO THEIR BIDS AS ADDITIONAL COMPENSATION REQUESTS FOR
ADJUSTED OR EXPANDED REMOVAL LIMITS WILL NOT BE APPROVED.
2. CONTRACTOR SHALL REPLACE AT NO COST TO THE STATE ALL DAMAGED STREETS, DRIVES, SIDEWALKS, CURB AND GUTTER, SIGNS, PAVEMENT MARKINGS, LIGHTS, FENCES AND ALL OTHER SURFACE STRUCTURES NOT SCHEDULED
TO BE REMOVED DURING THE COURSE OF THE WORK.
3. ALL LANDSCAPING, INCLUDING TREES, SHRUBS AND PERENNIALS NOT CALLED OUT TO BE REMOVED OR APPROVED FOR REMOVAL BY CONSTRUCTION MANAGER, SHALL BE PROTECTED AND REPLACED AT NO COST TO THE STATE IF DAMAGED DURING CONSTRUCTION. REPLACE TREES WITH (1) EQUIVALENT TREE UP TO 6" CALIPER AND (1) ADDITIONAL TREE FOR EVERY 6" CALIPER BEYOND THAT. ALL PLANTS THAT ARE DESTROYED OR DAMAGED SHALL BE
REPLACED WITH NEW PLANTS OF THE EQUIVALENT TYPE.
4. WHERE A SECTION OF PAVEMENT, CURB AND GUTTER OR SIDEWALK IS CUT OR OTHERWISE DAMAGED BY THE CONTRACTOR, THE ENTIRE SECTION SHALL BE REMOVED AND REPLACED. PAVEMENT, CURBS AND GUTTERS AND SIDEWALKS SHALL BE REMOVED TO THE NEAREST JOINT A MINIMUM OF TWO FEET BEYOND THE EDGE OF ALL EXCAVATIONS. CONTRACTOR SHALL DOCUMENT (OR PHOTOGRAPH) ALL CRACKED PCC PAVEMENT OR DAMAGED HMA PAVEMENT PRIOR TO CONSTRUCTION. IF NEW CRACKS IN PCC PAVEMENT DEVELOP OR HMA PAVEMENT IS DAMAGED DUE TO CONSTRUCTION TRAFFIC (EXTENDS BEYOND CONSTRUCTION LIMITS), THE CONTRACTOR SHALL REPLACE
THE DAMAGED AREA AT NO ADDITIONAL COST TO STATE.
5. FIRE PROTECTION ACCESS AND FIRE HYDRANTS SHALL BE MAINTAINED THROUGHOUT THE PROJECT. ALL EXISTING FIRE HYDRANTS WHICH ARE NOT CALLED OUT TO BE REMOVED SHALL BE PROTECTED AND MAINTAINED.
6. THE CONTRACTOR SHALL COORDINATE ANY DISRUPTION OF EXISTING UTILITIES SERVING THE FACILITY W
7. ITH THE FACILITY AND CONSTRUCTION MANAGER.
EXCAVATION NOTES
1. EXCAVATE TRENCH AND PROVIDE PIPE BEDDING AND BACKFILL MATERIAL PER IOWA SUDAS SPECIFICATIONS OR AS
SHOWN ON THE DRAWINGS.
2. STRIP, STOCKPILE AND RESPREAD A MINIMUM OF 6” OF TOPSOIL IN ALL SEEDING OR SODDING AREAS DISTURBED BY CONSTRUCTION. DISTURBED AREAS SHALL BE LEFT IN SMOOTH CONDITION READY FOR FINAL SEEDBED PREPARATION. GRADE ALL DISTURBED ARES TO DRAIN, AS PONDING OF WATER WILL NOT BE ACCEPTABLE.
3. CONTRACTOR IS RESPONSIBLE FOR ALL TRENCH AND FILL SETTLEMENT FOR THE PROJECT'S ONE YEAR WARRANTY PERIOD. CONTRACTOR SHALL PROVIDE ADDITIONAL FILL MATERIAL AND IS RESPONSIBLE FOR RESEEDING OF ALL
SETTLEMENT AREAS AFTER SITE RESTORATION HAS BEEN COMPLETED.
GRADING AND EROSION CONTROL NOTES
1. BEST MANAGEMENT PRACTICES (BMPs) AND CONTROLS SHALL CONFORM TO FEDERAL, STATE OR LOCAL REQUIREMENTS OR MANUAL OF PRACTICE, AS APPLICABLE. IMPLEMENT ADDITIONAL CONTROLS AS DIRECTED BY
PERMITTING AGENCY OR OWNER'S REPRESENTATIVE.
2. ALL WASH WATER (CONCRETE TRUCKS, VEHICLE CLEANING, EQUIPMENT CLEANING, ETC.) SHALL BE DETAINED AND
PROPERLY TREATED OR DISPOSED.
3. SUFFICIENT OIL AND GREASE ABSORBING MATERIALS SHALL BE MAINTAINED ON SITE OR READILY AVAILABLE TO
CONTAIN AND CLEAN UP FUEL OR CHEMICAL SPILLS AND LEAKS.
4. DUST ON THE SITE SHALL BE CONTROLLED. THE USE OF MOTOR OILS AND OTHER PETROLEUM BASED OR TOXIC
LIQUIDS FOR DUST SUPPRESSION OPERATIONS IS PROHIBITED.
5. RUBBISH, TRASH, GARBAGE, LITTER OR OTHER SUCH MATERIALS SHALL BE DEPOSITED INTO SEALED CONTAINERS.
MATERIALS SHALL BE PREVENTED FROM LEAVING THE PREMISES THROUGH THE ACTION OF WIND OR STORMWATER
DISCHARGE INTO DRAINAGE DITCHES OR WATERS OF THE STATE.
6. DISTURBED PORTIONS OF THE SITE WHERE CONSTRUCTION ACTIVITY HAS PERMANENTLY STOPPED SHALL BE SEEDED OR SODDED. THESE AREAS SHALL BE SEEDED OR SODDED NO LATER THAN 14 DAYS AFTER THE LAST
CONSTRUCTION ACTIVITY OCCURRING IN THESE AREAS.
7. ALL MATERIALS SPILLED, DROPPED, WASHED OR TRACKED FROM VEHICLES ONTO ROADWAYS OR INTO STORM
DRAINS MUST BE REMOVED IMMEDIATELY.
8. CONTRACTORS OR SUBCONTRACTORS WILL BE RESPONSIBLE FOR REMOVING SEDIMENT THAT MAY HAVE COLLECTED IN THE STORM SEWER DRAINAGE SYSTEMS IN CONJUNCTION WITH THE STABILIZATION OF THE SITE.
9. SLOPES SHALL BE LEFT IN A ROUGHENED CONDITION DURING THE GRADING PHASE TO REDUCE RUNOFF VELOCITIES
AND EROSION.
10. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADJUSTING THE EROSION CONTROL MEASURES (SILT FENCES, WATTLES, INLET PROTECTION, ETC.) TO PREVENT EROSION.
11. ALL STORM SEWER INTAKES THAT RECEIVE STORMWATER RUNOFF FROM DISTURBED AREAS SHALL BE PROVIDED
WITH INLET PROTECTION.
12. CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLATION, PERIODIC CHECKING AND REINSTALLATION OF EROSION
AND SEDIMENTATION CONTROL MEASURES.
13. CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE IOWA DNR, US EPA AND LOCAL REGULATIONS DEALING WITH
STORMWATER RUNOFF AND EROSION CONTROL.
14. THE DISTURBED CONSTRUCTION AREA IS LESS THAN 1 ACRE, SO AN NPDES GENERAL PERMIT NO. 2 AND STORMWATER POLLUTION PREVENTION PLAN (SWPPP) ARE NOT REQUIRED. HOWEVER, THE CONTRACTOR IS RESPONSIBLE FOR INSTALLING AND MAINTAINING EROSION CONTROL THROUGHOUT CONSTRUCTION.
UTILITY NOTES
1. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE EXACT LOCATIONS AND DEPTHS OF ALL EXISTING PUBLIC
AND PRIVATE UTILITIES AND WHETHER ADDITIONAL UTILITIES EXIST.
2. CONTRACTOR SHALL COORDINATE WITH ALL UTILITY COMPANIES FOR PROTECTION REQUIREMENTS AND SPECIFICATIONS. PROVIDE TEMPORARY SUPPORT OF EXISTING UTILITIES AS REQUIRED FOR CONSTRUCTION.
3. ALL EXISTING AND PROPOSED UTILITY CROSSINGS/CONFLICTS SHALL MEET OR EXCEED IOWA SUDAS HORIZONTAL
AND VERTICAL SEPARATION REQUIREMENTS.
4. ALL UNDERGROUND LINES SHALL BE INSTALLED, INSPECTED AND APPROVED BEFORE BACKFILLING.
5. WATER TO BE INSTALLED WITH A MINIMUM COVER OF 5.5 FEET DEEP OR LOWER TO ACCOMMODATE UTILITY
CROSSINGS.
6. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH IOWA SUDAS STANDARD SPECIFICATIONS AND IOWA DOT SPECIFICATIONS, STANDARD ROAD PLANS AND ROAD DESIGN DETAILS, UNLESS OTHERWISE NOTED ON THE
DRAWINGS.
7. ALL OPEN EXCAVATIONS SHALL BE PROTECTED WITH SAFETY FENCE, BARRIERS OR BARRICADES IN ACCORDANCE
WITH OSHA.
8. CONTRACTOR TO IMPLEMENT TEMPORARY SHORING OR SUPPORT AT ALL UTILITY CROSSINGS AS REQUIRED BY CONTRACTOR'S MEANS AND METHODS. ALL DAMAGE TO EXISTING UTILITIES SHALL BE REPAIRED AT NO ADDITIONAL
COST TO THE STATE.
PAVEMENT GENERAL NOTES
1. ALL PROPOSED PAVEMENT PATCHES ARE APPROXIMATE ONLY AND SHOULD BE CONSIDERED MINIMUM REMOVAL EXTENTS. EXTEND AND ADJUST PAVEMENT PATCHES AS REQUIRED WITH PRIOR APPROVAL BY ENGINEER.
2. ALL SLOPES IN PAVEMENT SHALL BE UNIFORM TO AVOID PONDING. ANY PONDING ON PAVEMENT PATCHES OR
ADJACENT PATCHES WILL BE CONSIDERED UNACCEPTABLE AND SHALL BE REPLACED.
3. SALVAGE ALL SIGNS WITHIN THE CONSTRUCTION LIMITS AND REINSTALL IN THE SAME LOCATION AND CONDITION AFTER CONSTRUCTION. ANY STREET SIGNS OR POLES DAMAGED DURING THE COURSE OF WORK TO BE REMOVED
AND REPLACED AT NO ADDITIONAL COST TO THE STATE.
4. USE TYPE "A" COMPACTION PER IOWA DOT STANDARD SPECIFICATIONS ON SUBGRADE AND SUBBASE.
SPECIFICATIONS
THE MOST RECENT EDITION OF THE IOWA STATEWIDE URBAN DESIGN AND SPECIFICATIONS (SUDAS) SHALL APPLY TO ALL
SITE WORK PERFORMED ON THIS PROJECT EXCEPT AS MODIFIED HEREIN.
A. CONCRETE PAVING
CONCRETE: MATERIALS AND MIXING FOR ALL CONCRETE WORK, UNLESS OTHERWISE SPECIFIED, SHALL CONFORM TO
IOWA DOT SPECIFICATIONS FOR AIR-ENTRAINED TYPE C-4 MIX WITH TYPE I CEMENT.
FLY ASH (CONTRACTOR'S OPTION): ASTM C618, TYPE C, NOT TO EXCEED 15% OF CEMENTITIOUS MATERIAL.
COARSE AGGREGATE: DURABILITY SHALL BE CLASS III, 3/4" MAX.
COMPRESSIVE STRENGTH: 2800 PSI @ 7 DAYS AND 4000 PSI @ 28 DAYS
SLUMP: 3" ± 1" or 8" MAXIMUM WITH SUPER PLASTICIZER
AIR CONTENT: 7.0% ± 1.0%
WATER/CEMENT RATIO: NOT TO EXCEED 0.53
FINISH: HEAVY BROOM FINISH
TESTING: ONE SET OF TEST CYLINDERS REQUIRED FOR EACH 100 CY, OR PORTION THEREOF, OF CONCRETE POURED PER WORK LOCATION. CONCRETE TESTING TO BE DONE AND PAID FOR BY OWNER. CONTRACTOR SHALL COORDINATE AND
SCHEDULE ALL REQUIRED TESTING AND GEOTECHNICAL WORK WITH CONSTRUCTION MANAGER.
SURFACE CURING: CONTRACTOR SHALL APPLY WHITE PIGMENT LIQUID CURING COMPOUND IN A FINE SPRAY TO FORM CONTINUOUS UNIFORM FILM AFTER FINISHING AND SURFACE MOISTURE HAS DISAPPEARED OR WITHIN 30 MINUTES
AFTER FORMS ARE REMOVED.
SUBMIT CONCRETE MIX DESIGN FOR APPROVAL.
COLD WEATHER CONCRETE: WHEN THE ATMOSPHERIC AIR TEMPERATURE MAY BE EXPECTED TO DROP BELOW 40°F AT THE TIME CONCRETE IS DELIVERED TO THE WORK SITE, DURING PLACEMENT OR AT ANY TIME DURING CURING PERIOD, CONCRETE SHALL BE MIXED, PLACED AND PROTECTED IN ACCORDANCE WITH ACI STANDARD 306, "RECOMMENDED PRACTICE FOR COLD WEATHER CONCRETING." IT IS THE OWNER'S PREFERENCE TO AVOID COLD WEATHER CONCRETE
AND PROVIDE TEMPORARY GRANULAR SURFACING FOR SIDEWALK AND PAVING AS REQUIRED.
B. EXPANSION JOINT FILLER
CLOSED CELL POLYETHYLENE WITH STRIP-OFF CAP FOR SEALANT.
C. JOINT SEALANT
PAVING JOINTS SHALL BE SEALED PER IOWA DOT SPECIFICATIONS. BACKER ROD SHALL NOT BE USED FOR JOINT
SEALING.
D. PAVEMENT REINFORCING STEEL
PAVING REINFORCEMENT SHALL BE ASTM C615 GRADE 60 AND SHALL HAVE A PROTECTIVE EPOXY COATING APPLIED BY
ELECTROSTATIC SPRAY METHOD IN ACCORDANCE WITH THE REQUIREMENTS OF ASTM A775.
E. PAVEMENT JOINTING
PROVIDE IDOT TYPE 'C' JOINTS FOR TRANSVERSE JOINTS. PROVIDE JOINTS AT A MAXIMUM SPACING OF 12 FEET FOR
PAVING OR SQUARE PANELS FOR SIDEWALKS.
PROVIDE IDOT TYPE 'L' JOINTS FOR LONGITUDINAL JOINTS.
PROVIDE IDOT TYPE 'RD' OR TYPE 'BT' JOINTS TO TIE INTO EXISTING PAVING.
PROVIDE IDOT TYPE 'DW' JOINTS FOR END OF DAY PAVING.
SAW CUTTING TO BE COMPLETED A MAXIMUM OF 24 HOURS FROM CONCRETE PLACEMENT. RANDOM CRACKING CAUSED
BY DELAYED SAW CUTTING MAY REQUIRE REMOVAL AND REPLACEMENT.
CONTRACTOR TO PROVIDE OWNER'S REPRESENTATIVE WITH A POURING SEQUENCE AND JOINTING PLAN FOR APPROVAL
PRIOR TO PAVING.
F. TRENCH EXCAVATION AND BACKFILL
BEDDING AND BACKFILL MATERIAL: SHALL COMPLY WITH IOWA SUDAS SECTION 3010.
BACKFILL COMPACTION REQUIREMENTS:
1. AREAS UNDER AND WITHIN FIVE (5) FEET OF PAVEMENT, SIDEWALKS, GRANULAR SURFACING OR OTHER SURFACE
IMPROVEMENTS SHALL BE COMPACTED TO 95% OF MAXIMUM STANDARD PROCTOR DENSITY.
2. AREAS UNDER LANDSCAPING AND LAWN AREAS SHALL BE COMPACTED TO 90% OF MAXIMUM STANDARD PROCTOR
DENSITY.
3. COMPACTION TESTING SHALL BE COMPLETED ON A FREQUENCY OF ONE TEST PER 100 LINEAR FEET AT
APPROXIMATELY EVERY OTHER 8" LIFT OR AT ALTERNATIVE LOCATIONS AND FREQUENCIES AS RECOMMENDED BY TESTING AGENCY. COMPACTION TESTING TO BE DONE BY AN INDEPENDENT TESTING LABORATORY AND PAID FOR BY OWNER. CONTRACTOR SHALL COORDINATE AND SCHEDULE ALL REQUIRED TESTING AND GEOTECHNICAL WORK WITH
CONSTRUCTION MANAGER.
CONTRACTOR IS RESPONSIBLE FOR ALL DEWATERING, WHICH MAY BE REQUIRED INCIDENTAL TO THE PIPE INSTALLATION.
G. TOPSOIL
STRIP, STOCKPILE AND RESPREAD EXISTING TOPSOIL IN ALL AREAS TO BE SEEDED. THE DEPTH OF TOPSOIL SHALL BE A MINIMUM OF 6" AFTER NATURAL SETTLEMENT AND SHALL CONFORM SMOOTHLY TO THE ADJACENT LINES, GRADES AND ELEVATIONS. PROVIDE ADDITIONAL TOPSOIL IF EXISTING TOPSOIL IS NOT PROPERLY HANDLED AND PROTECTED.
H. SITE RESTORATION
HYDRAULIC SEEDING: ALL DISTURBED AREAS ON THE SITE NOT TO BE PAVED OR LANDSCAPED SHALL RECEIVE HYDRAULIC SEEDING. HYDRAULIC SEEDING MATERIALS AND INSTALLATION SHALL MEET SUDAS SPECIFICATIONS.
CONTRACTOR IS RESPONSIBLE FOR PREPARING SEEDBED, APPLYING HYDRAULIC SEEDING AND FIRST AND SECOND
APPLICATIONS OF FERTILIZER.
SEED MIXTURE: SUDAS TYPE 1 SEED MIXTURE (PERMANENT LAWN MIXTURE) OR APPROVED EQUAL.
K. CHAINLINK FENCING AND GATES
PROVIDE FENCING MATERIAL AND INSTAL ACCORDING TO IOWA SUDAS REQUIREMENTS UNLESS OTHERWISE SPECIFIED
ON THE CONSTRUCTION DOCUMENTS.
PROVIDE SUBMITTALS FOR ALL GATE AND FENCE MATERIALS
L. GRANULAR SURFACING
MATERIALS AND INSTALLATION TO MEET IDOT SPECIFICATION 4120, CLASS A ROADSTONE OR APPROVED EQUAL
M. WEED BARRIER
PROVIDE A COMMERCIAL GRADE WEED BARRIER FABRIC THAT ALLOWS WATER, AIR AND NUTRIENTS TO PASS THROUGH
C O
N S
T R
U C
T
IO
N
W R
C D e c e n tr a liz a ti o n P h a s e
F ir e
A la rm P h a s e
.4
SIDEWALK
SI
D
EW
AL
K
SI
D
EW
AL
K
CONCRETE
CONCRETE
GAZEBO
(ON CONCRETE PAD)
CONCRETE
CONCRETE
SHED / OUTBUILDING
CONCRETECONCRETE
STAIRWELL
(BELOW GROUND)
54"
(DRONE LOCATE)
(DRONE LOCATE)
STAIRWELL
(BELOW GROUND)
1051.64 IE 8" CLAY (N)
1051.60 IE 8' CLAY (S)
1061.69 IE 2" DIP (S)
NO VISUAL FLOW
CASTING NOT LEVEL
SANITARY CLEANOUT
1060.39 RIM
1054.28 IE WELL
NO DIRECTION FOUND
SANITARY CLEANOUT
1060.48 RIM
1054.38 IE WELL
NO DIRECTION FOUND
STAIRWELL
(BELOW GROUND)
STAIRWELL TO
DOORWAY 1.5 FROM
BUILDING CORNER TO
EDGE OF DOOR
(BELOW GROUND)
DOORWAY AT GRADE
1.25 SOUTH OF BUILDING
CORNER TO EDGE OF DOOR
LINE DRAWN TO DIRECTION
NOT FIELD VERIFIED
LINE DRAWN TO DIRECTION
NOT FIELD VERIFIED
PROTECT EXISTING
BUILDING (TYP)
PROTECT EXISTING
TREE (TYP)
PROTECT EXISTING
SIDEWALK (TYP)
ELMCREST
WOODWARD ACADEMY -
BUILDING C
WOODWARD ACADEMY -
BUILDING D
CONTRACTOR TO POTHOLE TO A
MINIMUM OF 4' DEEP AT THE START OF
PROJECT TO CONFIRM NO
CONFLICTING UTILITIES EXIST. MINIMUM
POTHOLING LOCATION SHOWN.
APPROXIMATE
GRADING LIMITS (TYP)
PROTECT EXISTING
BUILDING (TYP)
REMOVE AND DISPOSE
OF PCC SIDEWALK TO
NEAREST JOINT (TYP)
INSTALL CONSTRUCTION FENCE
AT DRIPLINE OF TREE AND
AVOID CONSTRUCTION TRAFFIC
UNDER THE DRIPLINE (TYP)
.0
REMOVE AND DISPOSE
OF EXISTING TREE
PROTECT
EXISTING TREE
PROTECT EXISTING
SIDEWALK (TYP)
PROTECT EXISTING SANITARY
SEWER (TYP) APPROXIMATE
LOCATION SHOWN BASED ON
RECORD DOCUMENTS
0.
8.
S
H
IV
E- H
AT
TE
R Y.
C O
M
A B C D E F HG
A B C D E F HG
Pr in te d:
D R
AW
N
B Y
AP
PR
O
VE
D B
Y
IS
SU
ED
F
O R
IS
SU
E D
AT
E
FI
EL
D B
O O
K:
PR
O
JE
C
T N
U M
BE
R
\\s h.
sh ive
-h at te ry
.c om
\D
AT
A\ Pr oj ec ts \2
4\
\D el ive ra bl es \D ra wi ng s\
1_ Ci vil \C
D0
- D
EM
O
LI
TI
O
N
PL
AN
.d wg 3/
/2
:2
1:
A M
00-CD02
EX
IS
TI
N
G C
O N
D
IT
IO
N
S
AN
D D
EM
O
LI
TI
O N
PL
AN
BD
D
C R
B
C O
N
ST
R U
C
TI
O N
-0 3-
40 ---
.4
0) W
R C
D
EC
EN
TR
AL
IZ
AT
IO
N P
H
AS
E
IO
W
A D
EP
AR
TM
EN
T O
F
AD
M
IN
IS
TR
AT
IV
E
SE
R
VI
C
ES
4T
H S
T.
W
O O
D W
AR
D
, I A
NORTH
C O
N S
T R
U C
T
IO
N
W R
C D e c e n tr a liz a ti o n P h a s e
F ir e
A la rm P h a s e
.4
CHAINLINK
FENCE
CONCRETE
CONCRETE
CONCRETE
ACCESS VAULT
(STEEL)
ACCESS VAULT
(STEEL)
CONCRETE
CONCRETECONCRETE
INTAKE FANS
STAIRWELL
(BELOW GROUND)
LOADING RAMP
SHED / OUTBUILDING
CHILLER
BUILDING
(D
RO
NE
LO
CA
TE
(D
RO
NE
LO
CA
TE
(DRONE LOCATE)
CONCRETE
STAIRWELL
(BELOW GROUND)
STAIRWELL AND
DOORWAY CENTERED
AT BUILDING IN STAIRWAY
(BELOW GROUND)
STAIRWELL TO
DOORWAY
(ABOVE AND
BELOW GROUND)
STAIRWELL TO
DOORWAY 1.5 FROM
BUILDING CORNER
TO EDGE OF DOOR
(BELOW GROUND)
RAMP AND
DORRWAY
(ABOVE GROUND)
PROTECT EXISTING PCC
STAIRS AND WALL (TYP)
PROTECT EXISTING
PCC PAVING (TYP)
REMOVE AND DISPOSE OF EXISTING
PCC PAVING. SAWCUT FULL DEPTH AND
REMOVE TO NEAREST JOINT (TYP)
WOODWARD ACADEMY -
BUILDING D
MEDICAL CENTER
CONTRACTOR TO POTHOLE TO A MINIMUM OF
4' DEEP AND FIND VERTICAL AND HORIZONTAL
LOCATIONS OF EXISTING FIBER OPTIC AND
ELECTRICAL LINES AT THE START OF PROJECT.
MINIMUM POTHOLING LOCATIONS SHOWN.
APPROXIMATE
GRADING LIMITS (TYP)
PROTECT EXISTING
ELECTRICAL EQUIPMENT
AND PCC PADS (TYP)
PROTECT EXISTING
BOLLARDS (TYP)
14.0'
16.0'
20.0'
PROTECT EXISTING
UNDERGROUND
UTILITIES (TYP)
0.
8.
S
H
IV
E- H
AT
TE
R Y.
C O
M
A B C D E F HG
A B C D E F HG
Pr in te d:
D R
AW
N
B Y
AP
PR
O
VE
D B
Y
IS
SU
ED
F
O R
IS
SU
E D
AT
E
FI
EL
D B
O O
K:
PR
O
JE
C
T N
U M
BE
R
\\s h.
sh ive
-h at te ry
.c om
\D
AT
A\ Pr oj ec ts \2
4\
\D el ive ra bl es \D ra wi ng s\
1_ Ci vil \C
D0
- D
EM
O
LI
TI
O
N
PL
AN
.d wg 3/
/2
:2
2:
A M
00-CD03
EX
IS
TI
N
G C
O N
D
IT
IO
N
S
AN
D D
EM
O
LI
TI
O N
PL
AN
BD
D
C R
B
C O
N
ST
R U
C
TI
O N
-0 3-
40 ---
.4
0) W
R C
D
EC
EN
TR
AL
IZ
AT
IO
N P
H
AS
E
IO
W
A D
EP
AR
TM
EN
T O
F
AD
M
IN
IS
TR
AT
IV
E
SE
R
VI
C
ES
4T
H S
T.
W
O O
D W
AR
D
, I A
PROTECT EXISTING
BUILDING (TYP)
NORTH
C O
N S
T R
U C
T
IO
N
W R
C D e c e n tr a liz a ti o n P h a s e
F ir e
A la rm P h a s e
.4
D
EW
AL
K
SI
D
EW
AL
K
CONCRETE
CONCRETE
GAZEBO
(ON CONCRETE PAD)
CONCRETE
CONCRETE
SHED / OUTBUILDING
CONCRETECONCRETE
STAIRWELL
(BELOW GROUND)
54"
(DRONE LOCATE)
(DRONE LOCATE)
STAIRWELL
(BELOW GROUND)
1051.64 IE 8" CLAY (N)
1051.60 IE 8' CLAY (S)
1061.69 IE 2" DIP (S)
NO VISUAL FLOW
CASTING NOT LEVEL
SANITARY CLEANOUT
1060.39 RIM
1054.28 IE WELL
NO DIRECTION FOUND
SANITARY CLEANOUT
1060.48 RIM
1054.38 IE WELL
NO DIRECTION FOUND
STAIRWELL
(BELOW GROUND)
STAIRWELL TO
DOORWAY 1.5 FROM
BUILDING CORNER TO
EDGE OF DOOR
(BELOW GROUND)
DOORWAY AT GRADE
1.25 SOUTH OF BUILDING
CORNER TO EDGE OF DOOR
LINE DRAWN TO DIRECTION
NOT FIELD VERIFIED
LINE DRAWN TO DIRECTION
NOT FIELD VERIFIED
STRUCTURAL AND MECHANICAL
ELMCREST
WOODWARD ACADEMY -
BUILDING C
WOODWARD ACADEMY -
BUILDING D
PCC EQUIPMENT PAD - EQUIPMENT PAD AND CLEARANCE
DIMENSIONS SHOWN ARE APPROXIMATE AND SHOULD
BE ADJUSTED AS REQUIRED FOR CONTRACTOR
SELECTED EQUIPMENT AND MANUFACTURER
RECOMMENDED SIZE AND CLEARANCE REQUIREMENTS
6' CHAIN LINK
FENCE (TYP)
GRANULAR
SURFACING (TYP)
INSTALL 6' WIDE DOUBLE
SWING MAINTENANCE GATE
5" PCC
SIDEWALK (TYP)
SEED ALL DISTURBED
AREAS NOT TO BE
PAVED (TYP)
CHILLER, SEE
MECHANICAL PLANS
23.3'
9.3' 5.0'
5.0'
35.3'
19.3'
8.0'
4.0' 4.0'
6.0'10.0'
SEE MECHANICAL PLANS
FOR APPROXIMATE PIPE
ROUTING TO BUILDING
SUPPORTS REPRESENTATIVE OF APPROXIMATE REQUIRED
SUPPORTING DISTANCE REQUIREMENTS AND QUANTITY.
CONTRACTOR SHALL VERIFY SUPPORTING REQUIREMENTS WITH
FINAL REFRIGERANT PIPE SIZES AND SPEC SECTION 23 2300.
CONTRACTOR SHALL COORDINATE LOCATIONS OF SUPPORTS
WITH ALL UNDERGROUND UTILITIES AND VERIFY ALL EXISTING
CONDITIONS PRIOR TO EXCAVATION AND CONSTRUCTION.
0.
8.
S
H
IV
E- H
AT
TE
R Y.
C O
M
A B C D E F HG
A B C D E F HG
Pr in te d:
D R
AW
N
B Y
AP
PR
O
VE
D B
Y
IS
SU
ED
F
O R
IS
SU
E D
AT
E
FI
EL
D B
O O
K:
PR
O
JE
C
T N
U M
BE
R
P:
\P ro je ct s\
\2
0\ de liv er ab le s\
Dr aw in gs
\1 _C ivi l\C
SI
TE
P
LA
N.
dw g 4/
/2
3:
:1
PM
00-C102
SI
TE
P
LA
N
BD
D
C R
B
C O
N
ST
R U
C
TI
O N
-0 3-
40 ---
.4
0) W
R C
D
EC
EN
TR
AL
IZ
AT
IO
N P
H
AS
E
IO
W
A D
EP
AR
TM
EN
T O
F
AD
M
IN
IS
TR
AT
IV
E
SE
R
VI
C
ES
4T
H S
T.
W
O O
D W
AR
D
, I A
NORTH
CONCRETE
CONCRETE
CONCRETE
ACCESS VAULT
(STEEL)
ACCESS VAULT
(STEEL)
CONCRETE
CONCRETECONCRETE
INTAKE FANS
STAIRWELL
(BELOW GROUND)
LOADING RAMP
SHED / OUTBUILDING
CHILLER
BUILDING
(D
RO
NE
LO
CA
TE
(D
RO
NE
LO
CA
TE
(DRONE LOCATE)
CONCRETE
STAIRWELL
(BELOW GROUND)
STAIRWELL AND
DOORWAY CENTERED
AT BUILDING IN STAIRWAY
(BELOW GROUND)
STAIRWELL TO
DOORWAY
(ABOVE AND
BELOW GROUND)
STAIRWELL TO
DOORWAY 1.5 FROM
BUILDING CORNER
TO EDGE OF DOOR
(BELOW GROUND)
RAMP AND
DORRWAY
(ABOVE GROUND)
6" BOLLARD (TYP)
COORDINATE EXACT LOCATIONS WITH
CM TO AVOID EXISTING UTILITIES AND
MAINTAIN MAXIMUM SPACING OF 9'
6" PCC
PAVING (TYP)
WOODWARD ACADEMY -
BUILDING D
MEDICAL CENTER
SEE MECHANICAL PLANS
FOR APPROXIMATE PIPE
ROUTING TO BUILDING
6' CHAIN LINK
FENCE (TYP)
GRANULAR
SURFACING (TYP)
PCC EQUIPMENT PAD - EQUIPMENT PAD AND CLEARANCE
DIMENSIONS SHOWN ARE APPROXIMATE AND SHOULD
BE ADJUSTED AS REQUIRED FOR CONTRACTOR
SELECTED EQUIPMENT AND MANUFACTURER
RECOMMENDED SIZE AND CLEARANCE REQUIREMENTS
ADJUST FENCE DIMENSIONS
AND POST LOCATIONS AS
NECESSARY TO AVOID
EXISTING UTILITIES (TYP)
INSTALL 6' WIDE DOUBLE
SWING MAINTENANCE GATE
CHILLER, SEE
MECHANICAL PLANS
CHILLER, SEE
MECHANICAL PLANS
SEED ALL DISTURBED
AREAS NOT TO BE
PAVED (TYP)
INSTALL TYPE 'RD' JOINT
AT ALL CONNECTIONS TO
EXISTING PAVEMENT (TYP)
14.9'
8.0'
14.9'
8.0'
5.5'
30.1'
24.0' 4.1'
6.0'9.8'
6.0' 6.0'
6.0'
9.8'
SUPPORTS REPRESENTATIVE OF APPROXIMATE REQUIRED
SUPPORTING DISTANCE REQUIREMENTS AND QUANTITY.
CONTRACTOR SHALL VERIFY SUPPORTING REQUIREMENTS WITH
FINAL REFRIGERANT PIPE SIZES AND SPEC SECTION 23 2300.
CONTRACTOR SHALL COORDINATE LOCATIONS OF SUPPORTS
WITH ALL UNDERGROUND UTILITIES AND VERIFY ALL EXISTING
CONDITIONS PRIOR TO EXCAVATION AND CONSTRUCTION.
0.
8.
S
H
IV
E- H
AT
TE
R Y.
C O
M
A B C D E F HG
A B C D E F HG
Pr in te d:
D R
AW
N
B Y
AP
PR
O
VE
D B
Y
IS
SU
ED
F
O R
IS
SU
E D
AT
E
FI
EL
D B
O O
K:
PR
O
JE
C
T N
U M
BE
R
P:
\P ro je ct s\
\2
0\ de liv er ab le s\
Dr aw in gs
\1 _C ivi l\C
SI
TE
P
LA
N.
dw g 4/
/2
3:
:1
PM
00-C103
SI
TE
P
LA
N
BD
D
C R
B
C O
N
ST
R U
C
TI
O N
-0 3-
40 ---
.4
0) W
R C
D
EC
EN
TR
AL
IZ
AT
IO
N P
H
AS
E
IO
W
A D
EP
AR
TM
EN
T O
F
AD
M
IN
IS
TR
AT
IV
E
SE
R
VI
C
ES
4T
H S
T.
W
O O
D W
AR
D
, I A
D
EW
AL
K
SI
D
EW
AL
K
CONCRETE
CONCRETE
GAZEBO
(ON CONCRETE PAD)
CONCRETE
CONCRETE
SHED / OUTBUILDING
CONCRETECONCRETE
STAIRWELL
(BELOW GROUND)
54"
(DRONE LOCATE)
(DRONE LOCATE)
STAIRWELL
(BELOW GROUND)
1051.64 IE 8" CLAY (N)
1051.60 IE 8' CLAY (S)
1061.69 IE 2" DIP (S)
NO VISUAL FLOW
CASTING NOT LEVEL
SANITARY CLEANOUT
1060.39 RIM
1054.28 IE WELL
NO DIRECTION FOUND
SANITARY CLEANOUT
1060.48 RIM
1054.38 IE WELL
NO DIRECTION FOUND
STAIRWELL
(BELOW GROUND)
STAIRWELL TO
DOORWAY 1.5 FROM
BUILDING CORNER TO
EDGE OF DOOR
(BELOW GROUND)
DOORWAY AT GRADE
1.25 SOUTH OF BUILDING
CORNER TO EDGE OF DOOR
LINE DRAWN TO DIRECTION
NOT FIELD VERIFIED
LINE DRAWN TO DIRECTION
NOT FIELD VERIFIED
STRUCTURAL AND MECHANICAL
ELMCREST
WOODWARD ACADEMY -
BUILDING C
WOODWARD ACADEMY -
BUILDING D
1061.48
FG
1062.00
TP
1062.00TP
1062.00
TP
1061.50FG
1061.50FG
.47
FG
1060.99 ME
1060.61 ME
1060.12 ME
.80
M E
.25 M
E
.01 M
E
1059.30 ME
1059.73 ME
1059.96 ME
1064.63 ME
1062.40 ME
1062.33
.53 M
E
.46
GRADING
LIMITS (TYP)
1061.84
1061.91
1061.76
1060.09
1060.01
.84
7.69%
3.36%
7.
8.80%
3.55%
5.
5.01%
1061.10
1061.30
1061.08
1061.30
.30
.25
.101060.90
59 1061
1062 1062
.2
1%
7.10%
25.15%
11.28%
601061
1062.30
.95
1061.65
FG
CONTRACTOR TO FIELD
VERIFY ELEVATION OF
EXISTING SIDEWALK PANEL
PRIOR TO CONSTRUCTION
1.50%1.
1.50%
4.70%
1060.96 ME
1062.00TP
0.
8.
S
H
IV
E- H
AT
TE
R Y.
C O
M
A B C D E F HG
A B C D E F HG
Pr in te d:
D R
AW
N
B Y
AP
PR
O
VE
D B
Y
IS
SU
ED
F
O R
IS
SU
E D
AT
E
FI
EL
D B
O O
K:
PR
O
JE
C
T N
U M
BE
R
P:
\P ro je ct s\
\2
0\ de liv er ab le s\
Dr aw in gs
\1 _C ivi l\C
G
RA
DI
NG
P
LA
N.
dw g 4/
/2
3:
:4
PM
00-C202
G R
AD
IN
G P
LA
N
BD
D
C R
B
C O
N
ST
R U
C
TI
O N
-0 3-
40 ---
.4
0) W
R C
D
EC
EN
TR
AL
IZ
AT
IO
N P
H
AS
E
IO
W
A D
EP
AR
TM
EN
T O
F
AD
M
IN
IS
TR
AT
IV
E
SE
R
VI
C
ES
4T
H S
T.
W
O O
D W
AR
D
, I A
CONCRETE
CONCRETE
CONCRETE
ACCESS VAULT
(STEEL)
ACCESS VAULT
(STEEL)
CONCRETE
CONCRETECONCRETE
INTAKE FANS
STAIRWELL
(BELOW GROUND)
LOADING RAMP
SHED / OUTBUILDING
CHILLER
BUILDING
(D
RO
NE
LO
CA
TE
(D
RO
NE
LO
CA
TE
(DRONE LOCATE)
CONCRETE
STAIRWELL
(BELOW GROUND)
STAIRWELL AND
DOORWAY CENTERED
AT BUILDING IN STAIRWAY
(BELOW GROUND)
STAIRWELL TO
DOORWAY
(ABOVE AND
BELOW GROUND)
STAIRWELL TO
DOORWAY 1.5 FROM
BUILDING CORNER
TO EDGE OF DOOR
(BELOW GROUND)
RAMP AND
DORRWAY
(ABOVE GROUND)
WOODWARD ACADEMY -
BUILDING D
MEDICAL CENTER
1058.39 ME
1057.28 ME
1057.98 ME
1058.48 ME
1059.03 ME
GRADING
LIMITS (TYP)
1058.60FG
1058.52FG
.6
FG 10
.5
FG 10
.11
FG 10
.95
FG
1057.95FG
1058.11
FG
.50
TP 10
.50
TP
1058.50TP
1058.50TP
1059.10TP
1059.10TP
.10
TP 10
.10
TP
MATCH EXISTING
GRADES (TYP)
3.
5.33%
5.05%
5.1 1%
1057.90 ME
1059.60 M
E
1058.78 ME
2.5 8%
4.36%
2.35%
1058.11
1058.44
1058.56
.72
1058.82
1058.26
FG
.60
FG
1058.82
FG
3.37%
.90
1058.66
0.
8.
S
H
IV
E- H
AT
TE
R Y.
C O
M
A B C D E F HG
A B C D E F HG
Pr in te d:
D R
AW
N
B Y
AP
PR
O
VE
D B
Y
IS
SU
ED
F
O R
IS
SU
E D
AT
E
FI
EL
D B
O O
K:
PR
O
JE
C
T N
U M
BE
R
\\s h.
sh ive
-h at te ry
.c om
\D
AT
A\ Pr oj ec ts \2
4\
\D el ive ra bl es \D ra wi ng s\
1_ Ci vil \C
G
RA
DI
NG
P
LA
N.
dw g 3/
/2
:2
6:
A M
00-C203
G R
AD
IN
G P
LA
N
BD
D
C R
B
C O
N
ST
R U
C
TI
O N
-0 3-
40 ---
.4
0) W
R C
D
EC
EN
TR
AL
IZ
AT
IO
N P
H
AS
E
IO
W
A D
EP
AR
TM
EN
T O
F
AD
M
IN
IS
TR
AT
IV
E
SE
R
VI
C
ES
4T
H S
T.
W
O O
D W
AR
D
, I A
NORTH
C O
N S
T R
U C
T
IO
N
W R
C D e c e n tr a liz a ti o n P h a s e
F ir e
A la rm P h a s e
.4
0.
8.
S
H
IV
E- H
AT
TE
R Y.
C O
M
A B C D E F HG
A B C D E F HG
Pr in te d:
D R
AW
N
B Y
AP
PR
O
VE
D B
Y
IS
SU
ED
F
O R
IS
SU
E D
AT
E
FI
EL
D B
O O
K:
PR
O
JE
C
T N
U M
BE
R
P:
\P ro je ct s\
\2
0\ de liv er ab le s\
Dr aw in gs
\1 _C ivi l\C
CO
NS
TR
UC
TI
O
N
DE
TA
IL
S.
dw g 4/
/2
3:
:4
PM
00-C501
C O
N
ST
R U
C
TI
O N
D
ET
AI
LS
BD
D
C R
B
C O
N
ST
R U
C
TI
O N
-0 3-
40 ---
.4
0) W
R C
D
EC
EN
TR
AL
IZ
AT
IO
N P
H
AS
E
IO
W
A D
EP
AR
TM
EN
T O
F
AD
M
IN
IS
TR
AT
IV
E
SE
R
VI
C
ES
4T
H S
T.
W
O O
D W
AR
D
, I A
6" 5"
EXISTING SUBGRADE OR
COMPACTED FILL (95%
STANDARD PROCTOR DENSITY)
SUBGRADE PREPARATION
(95% STANDARD PROCTOR DENSITY)
P.C.C.
SIDEWALK
6"
SUBGRADE PREPARATION
(95% STANDARD PROCTOR
DENSITY) (TWO 6" LIFTS)
EXISTING SUBGRADE OR
COMPACTED FILL (95%
STANDARD PROCTOR DENSITY)
P.C.C.
P.C.C. PAVING
F6 CROSS SECTIONS
6" BOLLARDF5
3' -6
9"9" 6"
24"
4' -0
PLAN VIEW
6" OD SCH 40 STEEL PIPE BOLLARD FILLED
SOLID WITH CONCRETE. PAINT YELLOW OR
PROVIDE SUBMITTAL FOR AN ALTERNATIVE
YELLOW PLASTIC SLEEVE COVER
SLOPE CONCRETE TOP
FOR POSITIVE WATER
RUNOFF
ISOLATION JOINT
IF ABUTTING PCC
PAVEMENT
24" DIA CONCRETE
BASE
ISOLATION JOINT
PCC PAVING OR
TOPSOIL
BACKFILL
(2) #4 AROUND
PERIMETER
1'-0" THICK CONCRETE
SLAB REINFORCED w/ #6
AT 8" E.W., BOTTOM.
3/4" CHAMFER
GRANULAR
SURFACING
8" CONCRETE WALL
REINF. w/ #4 AT 12" O.C. E.W.
B6 PCC EQUIPMENT PAD
PER PLAN
8"
3.
6'
3"
1 2"
F4 TYPICAL 6' CHAIN LINK FENCE
6" M
IN
" M
IN
12" CONCRETE FOOTING (TYP)
SLOPE TOP OF CONCRETE
FOOTINGS FOR POSITIVE DRAINAGE
RAIL END
2 3/4" OD SS 40 GALV STEEL
CORNER POST WITH CAP
2 1/4" OD SS 40
GALV STEEL
LINE POST
2 1/4" OD SS 40
GALV STEEL
LINE POST
9 GA HOT DIPPED
GALV 2" WIRE
NOTE: IF PREFERRED, CONTRACTOR MAY CHOOSE
TO EXTEND FOOTING DEPTH TO 48" AND LEAVE
POST FOOTING 8" BELOW FINISH GRADE TO ALLOW
PLACEMENT OF SOIL/PAVING ABOVE FOOTING. IF
PAVING IS PLACED OVER TOP OF FOOTING,
GRANULAR SUBBASE SHALL BE PLACED BETWEEN
TOP OF FOOTING AND BOTTOM OF PAVING.
EXPANSION MATERIAL AND JOINT SEALANT SHALL
ALSO BE PLACED BETWEEN POST AND PAVING.
3' ACCESS
GATE
PADLOCK LOCKING
CAPABILITY REQUIRED
POST CAP
(TYPICAL)
GATE POST FOOTING
4" OD CORNER POST &
GATE POST (TYP.)
6" GAP BETWEEN
FIN. GRADE AND
BTM. RAIL, TYP.
6' 3' 3'
GRANULAR SURFACING/FINISH GRADE
12"
12"
F3 6' WIDE DOUBLE SWING CHAIN LINK MAINTENANCE GATE
6' N
O M
IN
AL
VA
R
IE
S"
ELEVATE EQUIPMENT PAD 3-8"
ABOVE ADJACENT GRADES. SEE
GRADING PLAN (TYP)
4"
SUBGRADE PREPARATION
(95% STANDARD PROCTOR
DENSITY) (TWO 6" LIFTS)
GRANULAR
MATERIAL
GRANULAR
SURFACE
WEED BARRIER
BROOM FINISH
EQUIPMENT PADS (TYP)
'DW'
DAY'S WORK JOINT(Non-working)
Hole Diameter 18'' Larger than Dowel 18'' Long Dowel at 12'' Centers
'RD'
ABUTTING PAVEMENT JOINT
4''
Tie Bar Size
Dowel Diameter
B4 JOINTING DETAILS
HSS2x2x3/16 w/ PL1/2x6x0'-6" BASEPLATE w/ (4)-3/8"Ø HILTI
KB-TZ (STAINLESS STEEL)
w/ 3 1/2" EMBEDMENT
3/16
HSS2x2x3/16 w/ 1/4" END CAP PL
3/4" CHAMFER
(4)-#3 VERTICALS
w/ #3 HOOPS AT 12" O.C.
ALL PIPE BRIDGE STEEL SHALL
BE HOT DIP GALVANIZED
B3 PIPE BRIDGE DETAILS
1.0' Ø
2.
0'
SEE MECHANICAL PLANS
FOR PIPE BRIDGE WIDTH
CONTRACTOR TO VERIFY ALL
EXISTING CONDITIONS AND
UNDERGROUND UTILITIES PRIOR TO
EXCAVATION AND CONSTRUCTION
6" 1.
0'
NORTH ARROW
VIEW NUMBER
DRAWING SCALE
TRUE NORTH
NORTH
PLAN
SHEET NUMBER
BUILDING SECTION MARK
A1 A101
A000
A1
A1
A1
A1
A1 A101
A1 A101
A1 A101
INTERIOR ELEVATION MARK
VIEW NUMBER
SHEET NUMBER
A00 KEYNOTE VALUE
RFI
REVISION NUMBER
100'-0"
FIRST FLOOR
IDENTIFIED LEVEL NAME
ELEVATION MARK
SPOT ELEVATION MARK
100'-0"
ROOM NAME
101 ROOM NUMBER
VIEW NUMBER
SHEET NUMBER
WALL SECTION MARK
VIEW NUMBER
SHEET NUMBER
DETAIL SECTION MARK
VIEW NUMBER
SHEET NUMBER
ENLARGED DETAIL MARK
VIEW NUMBER
SHEET NUMBER
EXTERIOR ELEVATION MARK
VIEW NUMBER
0A1
VIEW NAME
1/8" = 1'-0" 12" Contributor 1 / Contributor 2 / Contributor 3
A00
REVISION TYPE
RFI
A1 A101
A1 A101
GENERAL SYMBOLS LEGEND
D E
F L E
C T
IO
N
S P
A C
E
/2
SEE WALLTYPE
BASE AS SCHEDULED
CEILING - SEE REFLECTED
CEILING PLAN
STRUCTURE
METAL STUD RUNNER - SEE
WALL TYPE SCHEDULE FOR
SIZES
METAL STUD - SEE WALL TYPE
SCHEDULE FOR SIZES
METAL DEFLECTION TRACK -
SEE WALL TYPE SCHEDULE
FOR SIZES
FIRE SEALANT AT RATED
WALLS. ACOUSTICAL SEALANT
AT SOUND RATED WALLS -
BOTH SIDES OF WALL
FIRE SEALANT AT RATED
WALLS. ACOUSTICAL SEALANT
AT SOUND RATED WALLS -
BOTH SIDES OF WALL
ACOUSTICAL BATT INSULATION
WHERE SCHEDULED
BASE
PLAN
CEILING
STRUCTURE
WALL SHEATHING PER SPECS
PER FINISH - BOTH SIDES
ACOUSTICAL BATT INSULATION
WHERE SCHEDULED BY WALL
TYPE
SYMBOLS
& AND
# NUMBER or POUND
A
A/E ARCHITECT / ENGINEER
ACP ACOUSTICAL CEILING PANEL
ADA AMERICANS WITH DISABILITIES ACT
ADD ADDENDUM
ADMIN ADMINISTRATION
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AL or ALUM ALUMINUM
APPROX APPROXIMATE (LY)
ASSY ASSEMBLY
ASTM AMERICAN SOCIETY FOR TESTING & MATERIALS
AUTO AUTOMATIC (DOOR OPERATOR)
AVG AVERAGE
B
B/O BOTTOM OF
BLDG BUILDING
C
CG CORNER GUARD
CFCI CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CFOI CONTRACTOR FURNISHED OWNER INSTALLED
CL CENTER LINE
CLR CLEAR (ANCE)
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
D
DBL DOUBLE
DEMO DEMOLITION/ DEMOLISH
DEPT DEPARTMENT
DN DOWN
DTL DETAIL
DWG DRAWING
DWGS DRAWINGS
E
EA EACH
EJ EXPANSION JOINT
ELEC ELECTRIC / ELECTRICAL
ELEV ELEVATION
ENGR ENGINEER
EP EPOXY PAINT
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
F
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FFE FINISH (ED) FLOOR ELEVATION
FT FOOT (FEET)
FTG FOOTING
G GA GAGE or GAUGE
GC GENERAL CONTRACTOR
GWB GYPSUM WALLBOARD
H
HDWD HARDWOOD
HDWR HARDWARE
HM HOLLOW METAL
HVAC HEATING, VENTILATION, AIR CONDITIONING
HW HOT WATER
I
IBC INTERNATIONAL BUILDING CODE
ICC INTERNATIONAL CODE COUNCIL
IN INCHES
INFO INFORMATION
J
JAN JANITOR
JC JANITOR'S CLOSET
L
LAV LAVATORY
LF LINEAR FOOT
M
MAINT MAINTENANCE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFRG MANUFACTURING
MFR MANUFACTURER
MIN MINIMUM or MINUTE
MISC MISCELLANEOUS
N
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
O
OC ON CENTER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
OHD OVERHEAD DOOR
P
P PAINT
PLWD PLYWOOD
PR PAIR
PREFAB PREFABRICATED
PREFIN PREFINISHED
PREP PREPARE (ATION)
R R RAD or RADIUS
RCP REFLECTED CEILING PLAN
RM ROOM
RO ROUGH OPENING
S
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT
SIM SIMILAR
SH SHIVE-HATTERY
SOG SLAB ON GRADE
SPEC(S) SPECIFICATION(S)
STC SOUND TRANSMITTANCE CLASS
STD STANDARD
STL STEEL
STRUC STRUCTURE (AL)
SYM SYMMETRICAL
T
TEMP TEMPORARY
THRU THROUGH
TYP TYPICAL
U
UL UNDERWRITERS LABORATORIES
UNO UNLESS NOTED OTHERWISE
V
VERT VERTICAL
VIF VERIFY IN FIELD
W
W WIDTH
W/ WITH
W/O WITHOUT
WC WATER CLOSET or WALL COVERING
ABBREVIATIONS
1. COLOR HAS BEEN USED ON THESE DRAWINGS TO ENHANCE
UNDERSTANDING. PRINTING IN COLOR IS RECOMMENDED TO
ENSURE CLARITY.
2. ANY DAMAGE CAUSED BY CONSTRUCTION TO AREAS INSIDE
OR OUTSIDE OF THE PROJECT AREA SHALL BE REPAIRED TO
THE STATUS PRIOR TO CONSTRUCTION AT NO COST TO
OWNER.
3. THE GENERAL CONTRACTOR SHALL BE ULTIMATELY
RESPONSIBLE FOR ALL CUTTING, SUPPORTING, AND
PATCHING IF NOT COVERED BY A SPECIFIC TRADE.
4. EACH TRADE SHALL PROVIDE TESTED FIRESTOPPING
ASSEMBLIES FOR PENETRATIONS OF THEIR WORK THROUGH
FIRE-RATED WALLS AND FLOOR/CEILING
ASSEMBLIES. FIRESTOPPING ASSEMBLIES ARE TO BE OF
DESIGNS THAT PROVIDE THE SCHEDULED FIRE RATINGS
WHEN TESTED IN ACCORDANCE WITH ASTM E119, ASTM E814,
OR UL 1479, AND ARE TO BE INSTALLED BY INDIVIDUALS
TRAINED AND EXPERIENCED WITH INSTALLATION OF SUCH
ASSEMBLIES. PROVIDE SUBMITTALS TO LOCAL AUTHORITIES
AS REQUESTED
5. IF COMPLIANCE WITH TWO OR MORE STANDARDS IS
SPECIFIED AND THE STANDARDS ESTABLISH DIFFERENT OR
CONFLICTING REQUIREMENTS FOR MINIMUM QUANTITIES OR
QUALITY LEVELS, COMPLY WITH THE MOST STRINGENT
REQUIREMENT. REFER UNCERTAINTIES AND REQUIREMENTS
THAT ARE DIFFERENT, BUT APPARENTLY EQUAL, TO
ARCHITECT FOR A DECISION BEFORE PROCEEDING.
6. ABATEMENT WORK WILL BE UNDER SEPARATE CONTRACT.
OBTAIN AND MAINTAIN ON SITE A COMPLETE SET OF
ABATEMENT DOCUMENTS, INCLUDING ADDENDA AND
CHANGES AFTER START OF CONSTRUCTION, FOR REFERENCE
AND COORDINATION BY ALL TRADES. COORDINATE ALL
DEMOLITION AND CONSTRUCTION WORK WITH THE
ABATEMENT CONTRACTOR.
7. THE INDICATION OF TYPE AND LOCATION OF EXISTING
CONDITIONS AND MATERIALS IN THE DRAWINGS IS NOT
INTENDED AS EXACT DOCUMENTATION OF IN-PLACE
CONDITIONS. THE CONTRACTOR IS RESPONSIBLE FOR
VERIFYING EXISTING CONDITIONS BEFORE SUBMISSION OF
BIDS. EXISTING CONDITIONS VARYING FROM THOSE SHOWN IN
THE DRAWINGS WILL NOT BE JUSTIFICATION FOR ADDITIONAL
ALLOWANCE TO THE CONTRACTOR. NOTIFY THE ARCHITECT
IMMEDIATELY IF ANY CONDITIONS CONFLICT WITH THE
DRAWINGS.
8. PROTECT ALL BUILDING SYSTEMS, NEW AND EXISTING. COVER
SUPPLY, RETURN, AND EXHAUST AIR GRILLES, AND PROTECT
OTHER SENSITIVE EQUIPMENT FROM ALL ACTIVITIES RELATED
TO THIS CONTRACT. REMOVE PROTECTION AT END OF
CONSTRUCTION.
9. ALL DISSIMILAR METALS SHALL BE ISOLATED FROM EACH
OTHER EVEN IF NOT SPECIFICALLY IDENTIFIED IN THE
CONTRACT DOCUMENTS.
10. ALL CODE-REQUIRED LABELS SUCH AS "UL", “FACTORY
MUTUAL”, OR ANY EQUIPMENT IDENTIFICATION,
PERFORMANCE RATING, NAME, OR NOMENCLATURE PLATES
SHALL REMAIN READABLE AND NOT PAINTED OR COVERED BY
OTHER CONSTRUCTION.
11. STRUCTURAL INFORMATION ON ARCHITECTURAL DRAWINGS
IS FOR REFERENCE ONLY.
12. ARCHITECTURAL DIMENSIONS AND DESIGN INTENT ARE
INDICATED ON ARCHITECTURAL DRAWINGS. IF THE
INSTALLATION OF EQUIPMENT FROM OTHER TRADES
INTERFERES WITH COMPLIANCE OF THE DESIGN INTENT,
NOTIFY THE ARCHITECT BEFORE PROCEEDING.
13. DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN LOCATION
OF BUILDING ELEMENTS. IF DIMENSIONS ARE NOT AVAILABLE,
CONTACT THE ARCHITECT.
14. WHEN DIMENSIONS ON SMALL SCALE DRAWINGS CONFLICT
WITH THOSE ON LARGE SCALE DRAWINGS, THE LARGE SCALE
DRAWINGS GOVERN.
PROJECT GENERAL INFORMATION
BASE
CEILING
STRUCTURE
PLAN
BASE AS SCHEDULED
METAL J-TRACK - SEE WALL TYPE FOR SIZE
TESTED FIRESTOP SYSTEM MATCHING FIRE RATING
OF THE ASSEMBLY
METAL C-H STUD - SEE WALL TYPE SCHEDULE FOR
SIZES
CEILING - SEE REFLECTED CEILING PLAN
STRUCTURAL DECK OR BEAM
METAL J-TRACK - SEE WALL TYPE FOR SIZE
TESTED FIRESTOP SYSTEM MATCHING FIRE RATING
OF THE ASSEMBLY
5/8" GYPSUM WALLBOARD
1" SHAFT LINER
5/8" GYPSUM WALLBOARD
1" SHAFT LINER
GYPSUM BOARD
CONTINUES THROUGH
STUD SPACE OF LOWER
PRIORITY
HIGHER PRIORITY
PARTITION
LOWER PRIORITY
PARTITION
PARTITION FIRE RATING
3-HOUR
2-HOUR
1-HOUR
SMOKE PARTITION
NON-RATED PARTITION
PRIORITY
HINGE APPROACH, PULL SIDE
FRONT APPROACH, PULL SIDE FRONT APPROACH, PUSH SIDE
M
IN
M
IN
Y
M
IN
Y
M
IN
X
12" MIN
HINGE APPROACH, PULL SIDE HINGE APPROACH, PUSH SIDE
NOTE Y= 48" MINIMUM IF DOOR
HAS BOTH CLOSER AND LATCH
NOTE X = 12" MINIMUM IF DOOR
HAS BOTH CLOSER AND LATCH
LATCH APPROACH, PULL SIDE LATCH APPROACH, PUSH SIDE
Y
M
IN
NOTE Y= 54" MINIMUM IF
DOOR HAS A CLOSER
NOTE Y= 48" MINIMUM IF
DOOR HAS A CLOSER
X
36" MIN
X
42" MIN Y
M
IN
22" MIN
24" MIN
Y
M
IN
24" MIN18" MIN 5
M
IN
Existing buildings
New buildings
@ DOORS OVER 3'-0" WIDE
3 5/8" METAL STUD RUNNER
CHANNEL
5/8" GYPSUM WALLBOARD
SEALANT; AROUND ENTIRE
FRAME PERIMETR, BOTH
SIDES PRIOR TO PAINTING
HOLLOW METAL DOOR FRAME
DOOR, SEE DOOR SCHEDULE
BOX HEADER
T Y
P E
S E
E F
R A
M E
EACH SIDE
1/2"
5/8" GYPSUM WALLBOARD
SEALANT; AROUND ENTIRE
FRAME PERIMETR, BOTH
SIDES PRIOR TO PAINTING
HOLLOW METAL DOOR FRAME
DOOR, SEE DOOR SCHEDULE
T Y
P E
S E
E F
R A
M E
METAL STUD, SEE WALL TYPE;
DOUBLE STUDS AT JAMB
METAL STUD ANCHOR
TO WALL AT HINGE SIDE TYP,
UNO
WALL OR OBSTRUCTION
WHERE OCCURS
* 18" MIN TO WALL AT LATCH
SIDE, FOR DOORS LESS THAN
42" WIDE, FOR FRONT
APPROACH ADA CLEARANCE
EACH SIDE
1/2"
CODE SUMMARY
Applicable Codes
2015 International Existing Building Code as adopted by Iowa Administrative Rule 661-301 and 661-350 2015 International Building Code as adopted by Iowa Administrative Rule 661-201 and 661-301 2015 International Fire Code as adopted by Iowa Administrative Rule 661-201 2012 International Energy Conservation Code as adopted by Iowa Administrative Rule 661-303 2012 NFPA 101 Life Safety Code as adopted by Iowa Administrative Rule 661-205 2010 Americans with Disabilities Act as adopted by Iowa Administrative Rule 661-302 Smoke Alarms/Detectors as adopted by Iowa Administrative Rule 661-210 (effective July 1, 2021) Carbon Monoxide Alarms as adopted by Iowa Administrative Rule 661-211 State Mechanical Code as adopted by the Department of Public Health Iowa Administrative Rule 641-61 State Plumbing Code as adopted by the Department of Public Health Iowa Administrative Rule 641-25 State Electrical Code as adopted by the State Electrical Licensing Board Iowa Administrative Rule 661-504
Birches Occupancy: F-1 (IBC as referenced from IEBC 302.5); use and occupancy will remain unchanged.
Per 504.1 of IEBC, project will be Level 2 alteration due to addition of Boiler room; work area is under 50%.
Birches is not sprinklered, so the new boiler room will be required to be fire rated per IBC Incidental Uses Table 509.
Elmcrest Occupancy: B (IBC); Business (LSC)
Per previous reviews: According to CMS licensing, Elmcrest falls under ICF/MR. Although LSC Chapter 19 – Existing Health Care Occupancies includes Intermediate Care Facilities (ICF), section
19.1.1.1.9 states that “Facilities that do not provide housing on a 24-hour basis for their occupants shall be classified as other occupancies and shall be covered by other chapters of this Code.” It is our understanding that Elmcrest does not provide sleeping accommodations for occupants, and therefore, it would be classified as an Existing Business Occupancy (Chapter 39 of LSC).
Per LSC 39.3.2.1 for existing Business occupancies: “Hazardous areas, including boiler or furnace rooms, shall be protected in accordance with Section 8.7.”
LSC 8.7.1.1 “Protection…