RFB923901-01_NCF_IPI_HFI_Warehouse_DRAWINGS_12-16-2022.pdf
PDF 6 MB Posted
- Attached to
- DOC NCF IPI Homes For Iowa - Warehouse
- Solicitation number
- RFB923901-01
- Issued by
- Jasper County, Iowa
About this file
The file is a comprehensive set of construction documents for the Newton Correctional Facility Iowa Prison Industries Warehouse project, prepared by Farnsworth Group for the State of Iowa Department of Corrections (DOC). The project involves constructing a new warehouse facility located at the Newton Correctional Facility, with two potential configurations: a base bid and an alternate No. 1 option that includes a building extension. The construction documents are dated 12/16/2022 and include detailed architectural, structural, civil, and electrical plans covering everything from site layout and grading to building foundations, electrical systems, and interior specifications.
The warehouse project appears to be a pre-engineered metal building with approximately 11,929 square feet (base bid) or 9,057 square feet (alternate), featuring wood truss construction, pre-finished metal wall and roof panels, and specific design elements like overhead doors, concrete foundations, and utility connections. The documents indicate careful consideration of site conditions, including existing utilities, potential underground fiber optic lines, and specific engineering requirements for foundations, electrical systems, and structural integrity. The plans include provisions for future expandability, erosion control, and compliance with local and state building codes, suggesting a comprehensive approach to facility development within the correctional infrastructure.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATE:
LOCATION MAP
IMAGE © < COPYRIGHT NOTICE >
PROJECT NO.:
DAS PROJECT NO.:
ARCHITECT
CONSULTANTS
LIST OF DRAWINGS
DAS RFB923901-01
/1
/2
:5
:1
P
M
Newton Correctional Facility Iowa Prison Industries Warehouse
State of Iowa DOC
Newton, Iowa
12/16/2022
S ta te o f Io w a
D O
C
100% CONSTRUCTION DOCUMENTS
N e w to n
C o rr e c ti o n a l F a c ili ty I o w a
P ri s o n
I n d u s tr ie s W a re h o u s e
C
O N
S T
R U
C T
IO
N
D O
C U
M E
N T
S
0220983.00
9239.01
GENERAL
COVER SHEET
CIVIL
C0.1 COVER SHEET
C1.1 EXISTING CONDITIONS & DEMO PLAN
C2.1 LAYOUT PLAN
C3.1 GRADING PLAN
C4.1 UTILITY PLAN
ARCHITECTURAL
A1.1 FLOOR PLANS - BASE BID & ALTERNATE No. 1, SCHEDULES & DETAILS
A2.1 ROOF PLANS - BASE BID & ALTERNATE No. 1, AND DETAILS
A3.1 EXTERIOR ELEVATIONS
A4.1 SECTIONS AND DETAILS
A5.1 REFLECTED CEILING PLANS - BASE BID & ALTERNATE No. 1
STRUCTURAL
S0.1 STRUCTURAL NOTES
S1.1 FOUNDATION PLAN
S5.1 STRUCTURAL DETAILS
ELECTRICAL
E1.1 SITE PLAN - ELECTRICAL
E1.2 OVERALL SITE PLAN - ELECTRICAL
E2.1 FLOOR PLANS - ELECTRICAL
E2.1A FLOOR PLANS - ELECTRICAL - ALTERNATE No. 1
E3.1 ELECTRICAL DETAILS & SCHEDULES
FARNSWORTH GROUP, INC.
14225 UNIVERSITY AVENUE, SUIT 110
WAUKEE, IOWA 50263
P: 515/225.3469 F: 515/225.9649
BISHOP ENGINEERING
3501 104TH STREET
DES MOINES, IOWA 50322
P: 515/276-0467
KPFF ENGINEERING CONSULTANTS
604 LOCUST STREET, SUITE 202
DES MOINES, IOWA 50309
P: 515/279.3900
BLUESTONE ENGINEERING
5518 NW 88TH STREET
JOHNSTON, IOWA 50131
P: 515/727.0700
NATHAN T.
KRESS
21136
L
IC
E N
S E
D P
R
O FESS IONA
L E
N G
I N E
E R
* IO W A *
NATHAN T. KRESS, P.E. Date
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of Iowa.
Signature:
License Expires:
Pages or sheets covered by this seal:
ROBERT C.
RIDGWAY
07570
L
IC
E N
S E
D P
R
OFESS IONA
L A
R C
H
IT
E C
* IO W A *
T ROBERT C. RIDGWAY Date
I hereby certify that the portion of this technical submission described below was prepared by me or under my direct personal supervision and responsible charge. I am a duly licensed architect under the laws of the state of Iowa.
Signature:
License Expires:
Pages or sheets covered by this seal:
SETH V.
SUNDERMAN
23468
L
IC
E N
S E
D P
R
O FESS IONA
L E
N G
I N E
E R
* IO W A *
SETH V. SUNDERMAN, P.E. Date
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of Iowa.
Signature:
License Expires:
Pages or sheets covered by this seal:
CRAIG M.
PHILLIPS
P14060
L
IC
E N
S E
D P
R
O FESS IONA
L E
N G
I N E
E R
* IO W A *
CRAIG M. PHILLIPS, P.E. Date
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of Iowa.
Signature:
License Expires:
Pages or sheets covered by this seal:
Iowa Prison Industries Warehouse Newton Correctional Facility
Iowa Prison Industires Homes for Iowa SE Corner of Intersection Between SW 60th Ave & Public Access Rd.
Newton, Iowa
Newton Correctional Facility 307 S 60th Ave W.
Newton, IA 50208
NEWTON CORRECTIONAL FACILITY
PROJECT DESCRIPTION
IOWA
ONE CALL
1-800-292-8989 www.iowaonecall.com
Know what's below.
Call before you dig.
PROPERTY DESCRIPTION:
THE NORTHEAST QUARTER OF SECTION 28, TOWNSHIP 79 NORTH,
RANGE 19 WEST OF THE 5TH P.M., JASPER COUNTY, IOWA EXCEPT
STREET AND EXCEPT APPROXIMATELY 1.0 ACRES IN THE
NORTHEAST CORNER DEEDED TO THE CENTRAL IOWA WATER
ASSOCIATION IN PATENT RECORDED AS INSTRUMENT # 04-01346.
ADDRESS:
803 S 60TH AVE W
NEWTON, IA 50208
OWNER/PREPARED FOR:
STATE OF IOWA
1007 EAST GRAND AVE
DES MOINES, IA 50319
ZONING:
CLASS: A (AGRICULTURAL)
PER JASPER COUNTY ASSESSOR PAGE
BENCHMARK:
POINT: #9000, MAG NAIL
NORTHING = 594215.79
EASTING = 1758735.35
ELEVATION = 776.85
DESCRIPTION: LOCATED ON THE SE CORNER OF THE
INTERSECTION BETWEEN SW 60TH AVE AND THE PUBLIC ACCESS
ROAD ON WHICH THE PROPERTY LIES
POINT: #9001, MAG NAIL
NORTHING = 592565.48
EASTING = 1759082.31
ELEVATION = 779.68
DESCRIPTION: LOCATED ON THE EAST SIDE OF THE PUBLIC
ACCESS ROAD TOWARDS THE SOUTHERN END OF THE PROPERTY
VICINITY MAP
SCALE: 1' = 400'
COPYRIGHT 2022 BISHOP ENGINEERING. THIS DOCUMENT AND THE INFORMATION CONTAINED MAY NOT BE REPRODUCED OR EXCERPTED WITHOUT THE EXPRESS WRITTEN PERMISSION OF BISHOP ENGINEERING.
UNAUTHORIZED COPYING OR DISCLOSURE OF CONSTRUCTION USE ARE PROHIBITED BY COPYRIGHT LAW.
LEGEND:
SAN SANITARY SEWER
ST STORM SEWER
W WATER LINE
G GAS LINE
U/E UNDERGROUND ELECTRIC
O/E OVERHEAD ELECTRIC
TELE TELEPHONE LINE
F/O FIBER OPTIC
CATV CABLE TV
STORM MANHOLE
CURB INTAKE
SURFACE INTAKE
FLARED END SECTION
SANITARY MANHOLE
CLEANOUT
FIRE HYDRANT
SPRINKLER
IRRIGATION CONTROL VALVE
WATER MANHOLE
WELL
WATER VALVE
WATER SHUT OFF
YARD HYDRANT
ELECTRIC MANHOLE
ELECTRIC METER
ELECTRIC RISER
ELECTRIC VAULT
POWER POLE
TRANSFORMER POLE
LIGHT POLE
ELECTRIC JUNCTION BOX
ELECTRIC PANEL
TRANSFORMER
GROUND LIGHT
GUY WIRE
ELECTRIC HANDHOLE
GAS METER
GAS VALVE
AIR CONDITIONING UNIT
TELEPHONE RISER
TELEPHONE VAULT
TELEPHONE MANHOLE
TRAFFIC SIGNAL MANHOLE
FIBER OPTIC MANHOLE
FIBER OPTIC RISER
FIBER OPTIC VAULT
CABLE TV RISER
SIGN
BOLLARD
7 DENOTES NUMBER OF PARKING STALLS
PROPERTY CORNER - FOUND AS NOTED
PROPERTY CORNER- PLACED AS NOTED
SECTION CORNER - FOUND AS NOTED
D
S
CO
H Y D
ICV
W
WSO
Y A DR
E
EM
E
ELEC
EJ
EP
GM
GV
A/C
T
TEL
T
TS
FO
F/O
TV
W
WV
SHEET INDEX:
C0.1 COVER SHEET
C1.1 EXISTING CONDITIONS & DEMO PLAN
C2.1 LAYOUT PLAN
C3.1 GRADING PLAN
C4.1 UTILITY PLAN
UTILITY CONFLICT NOTES:
1. UTILITY CONFLICTS MAY EXIST ACROSS THE SITE WITH NEW UTILITIES, GRADING, PAVING ETC.
MOST UTILITY CONFLICTS HAVE BEEN CALLED OUT FOR CONTRACTOR CONVENIENCE.
2. CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY CONFLICTS THAT ARE EITHER CALLED OUT ON
THE PLANS OR THAT CAN BE SEEN ON THE PLANS BETWEEN AN EXISTING UTILITY AND
PROPOSED CONSTRUCTION
WETLAND NOTES:
1. BISHOP ENGINEERING DOES NOT PERFORM WETLAND STUDIES OR WETLAND MITIGATION. IT IS
THE OWNER'S RESPONSIBILITY TO DETERMINE IF ANY WETLANDS ARE LOCATED ON THE
PROJECT SITE AND PERFORM ANY NECESSARY MITIGATION PRIOR TO THE COMMENCEMENT OF
CONSTRUCTION ACTIVITIES.
SURVEY NOTES:
1. SURVEY WORK WAS COMPLETED BY BISHOP ENGINEERING ON 02-11-20. SEE SITE SURVEY
PROVIDED AS PART OF THIS SET OF PLANS FOR EXISTING SITE CONDITIONS AND BOUNDARY
INFORMATION.
GENERAL NOTES:
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH SUDAS STANDARD SPECIFICATIONS AND ANY AND ALL STATE FIRE MARSHAL SUPPLEMENTAL SPECIFICATIONS. THE
STATE FIRE MARSHALL & CORRECTIONS FACILITY MUST BE NOTIFIED BY ALL CONTRACTORS 72 HOURS PRIOR TO COMMENCING WORK.
2. IN EVENT OF A DISCREPANCY BETWEEN THE QUANTITY ESTIMATES AND THE DETAILED PLANS, THE DETAILED PLANS SHALL GOVERN.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE LOCATION OF ALL UTILITIES. ANY DAMAGE TO SAID UTILITIES SHALL BE REPAIRED AT THE CONTRACTORS EXPENSE.
4. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE CURRENT O.S.H.A. CODES AND STANDARDS. NOTHING INDICATED ON THESE PLANS SHALL RELIEVE THE
CONTRACTOR FROM COMPLYING WITH THE APPROPRIATE SAFETY REGULATIONS.
5. ALL NECESSARY CONSTRUCTION SIGNS, BARRICADES AND OTHER TRAFFIC CONTROL DEVICES REQUIRED DURING CONSTRUCTION WILL BE FURNISHED BY THE
CONTRACTOR. SIGNS, BARRICADES AND OTHER TRAFFIC CONTROL DEVICES MUST BE IN CONFORMANCE WITH THE "MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES
FOR STREETS AND HIGHWAYS."
6. BISHOP ENGINEERING SHALL NOT BE LIABLE FOR ANY INJURIES THAT HAPPEN ON SITE. THIS SHALL INCLUDE BUT NOT BE LIMITED TO TRENCH COLLAPSES FROM VARYING SOIL CONDITIONS OR INJURIES CAUSED BY UNDERGROUND UTILITIES INCLUDING UTILITIES THAT ARE NOT SHOWN ON PLAN.
7. THE CONTRACTOR IS LIABLE FOR ALL DAMAGES TO PUBLIC OR PRIVATE PROPERTY CAUSED BY THEIR ACTION OR INACTION IN PROVIDING FOR STORM WATER FLOW DURING CONSTRUCTION. DO NOT RESTRICT FLOWS IN EXISTING DRAINAGE CHANNELS, STORM SEWER, OR FACILITIES.
8. THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER A SCHEDULE FOR PERFORMANCE OF WORK ITEMS. THIS SCHEDULE SHALL BE PROVIDED BY THE CONTRACTOR AT THE PROJECT PRECONSTRUCTION CONFERENCE. NO WORK SHALL BEGIN UNTIL A SCHEDULE HAS BEEN SUBMITTED AND ACCEPTED. THE CONTRACTOR SHALL THEN
PERFORM WORK TO CONFORM TO THE ACCEPTED SCHEDULE.
9. LABORATORY TESTS SHALL BE PERFORMED BY THE OWNER UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL PROVIDE SAMPLES OF MATERIAL REQUIRED FOR LABORATORY TESTS AND TESTING IN ACCORDANCE WITH THE URBAN STANDARD SPECIFICATIONS FOR PUBLIC IMPROVEMENTS.
10. SOIL IMPORT OR EXPORT ON THIS PROJECT SHALL BE CONSIDERED INCIDENTAL AND WILL NOT BE MEASURED OR PAID FOR SEPARATELY.
11. THE CONTRACTOR SHALL PROTECT ALL STRUCTURES NOT SHOWN AS REMOVALS ON THE PLANS.
12. THE CONTRACTOR SHALL OBTAIN ANY AND ALL NECESSARY PERMITS PRIOR TO ANY CONSTRUCTION. CONTRACTOR SHALL WORK WITH OWNER OR OWNERS
REPRESENTATIVE ON ALL REQUIRED STORM WATER DISCHARGE PERMITS FROM THE IOWA DEPARTMENT OF NATURAL RESOURCES.
13. GRADING AND EROSION CONTROL SHALL BE DONE IN ACCORDANCE WITH THE APPROVED GRADING PLAN, SWPPP, NPDES DOCUMENTS, AND IOWA DEPARTMENT OF
NATURAL RESOURCES REQUIREMENTS.
14. THE CONTRACTOR SHALL PICK UP ANY DEBRIS SPILLED ONTO THE ADJACENT RIGHT OF WAY OR ABUTTING PROPERTIES AS THE RESULT OF CONSTRUCTION, AT THE
END OF EACH WORK DAY.
15. THE CONTRACTOR IS RESPONSIBLE FOR THE PROMPT REMOVAL OF ALL MUD THAT HAS BEEN TRACKED OR WASHED UNTO ADJACENT PROPERTY OR RIGHT OF WAY
UNTIL SUCH TIME THAT PERMANENT VEGETATION HAS BEEN ESTABLISHED.
16. DISPOSE OF ALL EXCESS MATERIALS AND TRASH IN ACCORDANCE WITH FEDERAL, STATE, AND LOCAL REQUIREMENTS. PROVIDE WASTE AREAS OR DISPOSAL SITES
FOR EXCESS MATERIALS NOT DESIRABLE FOR INCORPORATION INTO THE PROJECT.
DESCRIPTION:DATE:#
ISSUE:
100% CD
PROJECT:
DATE:
PROJECT NO.:
DAS #:
State of Iowa
Newton, Iowa Correctional Facility Iowa Prison Industries Warehouse
12/16/2022
0220983.00
DP-9239.00-.01-003
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
L:\
LA
ND
P
RO
JE
CT
S
\22
N
EW
TO
N
CO
RR
EC
TI
ON
AL
F
AC
ILI
TY
\D
W G\
C0 C
OV
ER
.D W
G
/16 /20
8:
:09
A M
UTILITY NOTE:
THE LOCATION OF THE UTILITIES INDICATED ON THE PLANS HAVE BEEN TAKEN FROM THE FIELD SURVEY, EXISTING PUBLIC RECORDS, AND PLANS PROVIDED BY OTHERS. SURFACE UTILITY LOCATIONS HAVE BEEN FIELD LOCATED BY BISHOP ENGINEERING, UNLESS OTHERWISE NOTED. ALL UNDERGROUND UTILITY LOCATIONS ARE APPROXIMATE LOCATIONS ONLY. BISHOP ENGINEERING DOES NOT GUARANTEE THE UNDERGROUND LOCATION OF ANY UTILITIES SHOWN. IT SHALL BE THE DUTY OF THE CONTRACTOR TO DETERMINE THE LOCATION AND DEPTH OF ANY UNDERGROUND UTILITIES SHOWN AND IF ANY ADDITIONAL UTILITIES, OTHER THAN THOSE SHOWN ON THE PLANS, MAY BE PRESENT. A REQUEST WAS MADE TO IOWA ONE CALL FOR UTILITY PROVIDERS TO VERIFY, LOCATE, AND MARK THEIR UTILITIES IN THE FIELD.
ABBREVIATIONS:
AC ACRES
ASPH ASPHALT
BK BOOK
CONC CONCRETE
D DEEDED DISTANCE
EX EXISTING
ENCL ENCLOSURE
FF FINISHED FLOOR
FL FLOW LINE
FRAC FRACTIONAL
M MEASURED DISTANCE
MH MANHOLE
OPC ORANGE PLASTIC CAP
P PLATTED DISTANCE
PG PAGE
POB POINT OF BEGINNING
POC POINT OF COMMENCEMENT
PRA PREVIOUSLY RECORDED AS
PUE PUBLIC UTILITY EASEMENT
ROW RIGHT OF WAY
RPC RED PLASTIC CAP
SF SQUARE FEET
SAN SANITARY
TYP TYPICAL
YPC YELLOW PLASTIC CAP
N NORTH
S SOUTH
E EAST
W WEST
F/O
C0.1, C1.1, C2.1, C3.1 & C4.1
COVER SHEET
C0.1
GEOTECHNICAL REPORT:
1. GEOTECHNICAL REPORT FOR SITE WAS NOT PROVIDED BY OWNER.
2. THE DESIGN AND SPECIFICATIONS IN THE APPROVED CONSTRUCTION DOCUMENTS ARE BASED ON TYPICAL CONDITIONS AND
ARE NOT BASED ON RECOMMENDATIONS FROM SITE SPECIFIC GEOTECHNICAL REPORT.
3. THE RECOMMENDED DESIGN AND SPECIFICATIONS HAVE BEEN APPROVED BY THE OWNER.
4. ANY RECOMMENDATIONS MADE BY THE OWNER'S SELECTED GEOTECHNICAL FIRM SHALL GOVERN.
SPECIFICATIONS NOTES:
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE NEWTON CORRECTIONAL FACILITY PROJECT SPECIFICATIONS, STATE FIRE MARSHAL SPECIFICATIONS AND SUDAS SPECIFICATIONS.
2. FOR ANY DISCREPANCIES BETWEEN THE NEWTON CORRECTIONAL FACILITY PROJECT SPECIFICATIONS AND STATE FIRE
MARSHAL REQUIREMENTS AND SPECIFICATIONS, PLUMBING CODE, AND URBAN STANDARD SPECIFICATIONS FOR PUBLIC IMPROVEMENT (SUDAS 2020), STATE FIRE MARSHAL STANDARD SPECIFICATIONS SHALL GOVERN.
3. FOR ALL SPECIFICATION DISCREPANCIES, PROJECT ENGINEER SHALL BE CONTACTED PRIOR TO PROCEEDING WITH CONSTRUCTION. IF ENGINEER IS NOT CONTACTED, CONTRACTOR SHALL BE RESPONSIBLE FOR ANY PROBLEMS THAT
RESULT FROM SAID DISCREPANCIES.
4. FOR ALL SPECIFICATION DISCREPANCIES, CONTRACTOR MUST OBTAIN WRITTEN APPROVAL FROM NEWTON CORRECTIONS FACILITY FOR ANY CHANGES TO PROPOSED SITE INFRASTRUCTURE OR GRADES PRIOR TO PROCEEDING WITH ANY
CHANGES.
SECURITY NOTES:
1. CONTRACTOR RESPONSIBLE FOR SECURITY OF THE SITE.
2. TEMPORARY FENCES OR ANY OTHER SECURITY MEASURES ARE THE RESPONSIBILITY OF THE CONTRACTOR.
3. NO SECURITY MEASURES WILL BE ELIGIBLE FOR A CHANGE ORDER AND MUST BE INCLUDED IN THE BASE BID.
STAKING NOTES:
1. CONTRACTOR IS REQUIRED TO HAVE ALL STAKING DONE UNDER THE
SUPERVISION OF A LICENSED LAND SURVEYOR AND IN COORDINATION
WITH THE PROJECT ENGINEER.
2. CONTRACTOR IS REQUIRED TO HAVE ALL STAKING DONE DIRECTLY
UNDER THE CONTRACTOR BY A SINGLE COMPANY.
3. STAKING DOES NOT RELIEVE CONTRACTOR OF ULTIMATE
RESPONSIBILITY TO CONSTRUCT THE PROJECT PER PLAN.
EARTHWORK BALANCE NOTES:
1. SOIL IMPORT OR EXPORT ON THIS PROJECT SHALL BE CONSIDERED
INCIDENTAL AND WILL NOT BE MEASURED OR PAID FOR SEPARATELY.
CONTRACTOR RESPONSIBLE FOR MAKING THE SITE EARTHWORK BALANCE.
2. THIS INCLUDES BUT IS NOT LIMITED TO TOPSOIL, POOR SOILS AND
STRUCTURAL FILL NECESSARY TO MEET PROJECT PLANS AND
SPECIFICATIONS.
AutoCAD SHX Text | lrunciman | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C0 COVER.dwg | 12/12/2022 10:38 AM |lrunciman | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C0 COVER.dwg | 12/12/2022 10:38 AM | | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C0 COVER.dwg | 12/12/2022 10:38 AM |L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C0 COVER.dwg | 12/12/2022 10:38 AM | | 12/12/2022 10:38 AM |12/12/2022 10:38 AM | |
AutoCAD SHX Text
SIGNED:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL SUPERVISION AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF IOWA.
AutoCAD SHX Text
PAGES OR SHEETS COVERED BY THIS SEAL:
AutoCAD SHX Text
SETH V. SUNDERMAN, P.E. 23468
AutoCAD SHX Text
LICENSE RENEWAL DATE: DEC. 31, 2023
AutoCAD SHX Text 23468
AutoCAD SHX Text
SUNDERMAN
AutoCAD SHX Text
SETH V.
EX 18" CMP
TOP=774.30
EX 18" CMP
TOP=773.98
A/CA/C
FF=777.54
U/E
W
W
W
W
W
W
W
W
W
W
W
W
W
W
II
II
II
II
II
II
II
II
II
II
II
II
II
II
II
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
77677
EX LOCATION PER
WINDSTREAM MAP
EX LOCATION PER
ALLIANT MAP
PUBLIC ACCESS RD
( ASPHALT SURFACE)
EX GATE
EX GRAVEL DRIVE
EX
BUILDINGEX
C
ON
CR
ET
E
EX POWER POLE
HEIGHT = 28'
EX POWER POLE
HEIGHT = 28'
EX POWER POLE
HEIGHT = 28'
F/O
F/O
F/O
F/O
F/O
F/O
F/O
EX. GRAVEL
EX. GRAVEL
U/E U/E
U/E U/E U/E
U/E U/E
APPROX. LOCATION OF
EX. SEPTIC FIELD & TANK
CONTRACTOR TO COORDINATE W/
UTILITY PROVIDER & MPE PLAN TO
REROUTE EX. UNDERGROUND
ELECTRIC LINE TO EX. TRANSFORMER
CONTRACTOR TO COORDINATE
W/ MEP PLANS TO PROTECT AND
SLEEVE EX. FIBER OPTIC LINE
REMOVE SECTION OF EX.
GRAVEL FOR PROP.
BUILDING CONSTRUCTION
DEMO NOTES:
1. CONTRACTOR TO LOCATE AND VERIFY ALL EXISTING UTILITY
LOCATIONS AND DEPTH ON SITE PRIOR TO CONSTRUCTION
AND CONTACT ENGINEER/OWNER IF DIFFERENT FROM PLANS
OR IN CONFLICT IN CONSTRUCTION ACTIVITIES.
2. CONTRACTOR TO COORDINATE PERMITTING, SIGNAGE AND
LANE CLOSURE WITH CITY OF NEWTON AS REQUIRED FOR
WORK WITHIN RIGHT OF WAY PRIOR TO START OF
CONSTRUCTION.
3. CONTRACTOR TO PROTECT ALL UTILITIES, PAVEMENTS AND
STRUCTURES THAT ARE NOT SCHEDULED FOR REMOVAL.
CONTRACTOR SHALL REPAIR AND/OR REPLACE ANY
DAMAGED UTILITIES, PAVEMENTS, AND STRUCTURES NOT
SCHEDULED FOR REMOVAL PER CITY/OWNER
SPECIFICATIONS AT THE CONTRACTORS EXPENSE.
4. CONTRACTOR TO REMOVE EXISTING GRANULAR SURFACE
AND UNSUITABLE MATERIALS WITHIN REMOVAL LIMITS SHOWN
AND HAUL OFF TO AN APPROVED LOCATION.
9. CONTRACTOR TO COORDINATE WITH UTILITY OWNERS AND
MEP FOR ANY REQUIRED RELOCATION OR ADJUSTMENT OF
EXISTING FIBER, ELECTRIC AND GAS LINES AS NEEDED TO
AVOID CONFLICT WITH CONSTRUCTION ACTIVITIES AND
IMPROVEMENTS.
DESCRIPTION:DATE:#
ISSUE:
100% CD
Xref C:/Reference/FG-CAD_Systems/FG-CADD/Titleblocks/WAU1_Logo.dwg
PROJECT:
DATE:
PROJECT NO.:
DAS #:
State of Iowa
Newton, Iowa Correctional Facility Iowa Prison Industries Warehouse
12/16/2022
0220983.00
DP-9239.00-.01-003
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
GRAPHIC SCALE
030 15 30 60
L:\
LA
ND
P
RO
JE
CT
S
\22
N
EW
TO
N
CO
RR
EC
TI
ON
AL
F
AC
ILI
TY
\D
W G\
C1 .1
EX
IS
TI
NG
C
ON
DI
TI
ON
S
DE
MO
.D
W G
/12
/20
1:
:41 P
M
EXISTING CONDITIONS
& DEMO PLAN
C1.1
AutoCAD SHX Text
NW 1/4 NE 1/4 SEC 28-T79-R19
| lrunciman | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C1.1 EXISTING CONDITIONS & DEMO.dwg | 12/12/2022 10:39 AM |lrunciman | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C1.1 EXISTING CONDITIONS & DEMO.dwg | 12/12/2022 10:39 AM | | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C1.1 EXISTING CONDITIONS & DEMO.dwg | 12/12/2022 10:39 AM |L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C1.1 EXISTING CONDITIONS & DEMO.dwg | 12/12/2022 10:39 AM | | 12/12/2022 10:39 AM |12/12/2022 10:39 AM | |
A/CA/C
FF=777.54
O/E
O/E
O/E
O/E
O/E
O/E
O/E
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
PUBLIC ACCESS RD
( ASPHALT SURFACE)
EX GRAVEL DRIVE
EX
BUILDINGEX
C
ON
CR
ET
E
EX POWER POLE
HEIGHT = 28'
EX POWER POLE
HEIGHT = 28'
F/O
F/O
F/O
F/O
F/O
F/O
F/O
EX. GRAVEL
9,000 SF W
AREHOUSE
FFE-774.00
60.0'
109.58'
234.52'
109.65'
235.03'
25'
25'
25'
U/E
U/E
U/E
U/E
U/E
60.00'
152.00'
60.00'
152.00'
48.00'
48.00'
ALTERNATE NO. 1:
48 FT BUILDING
EXTENSION
BASE BID GRAVEL
LIMITS. 6" DEPTH
CLASS "A" ROAD
STONE GRAVEL
SURFACE (TYPICAL)
EM
S
S
S
S
FUTURE SANITARY SEWER MAIN.
OWNER WILL INSTALL AND CONNECT BUILDING
SEWER SERVICE IF NEEDED AFTER MAIN HAS
BEEN INSTALLED
ALTERNATE NO. 1:
GRAVEL LIMITS. 6"
DEPTH CLASS "A"
ROAD STONE
GRAVEL SURFACE
(TYPICAL)
N: 593079.99 E: 1759137.31
N:593062.41 E: 1759079.94
N: 593271.22 E: 1759078.74
N: 593253.65 E: 1759021.37
DESCRIPTION:DATE:#
ISSUE:
100% CD
Xref C:/Reference/FG-CAD_Systems/FG-CADD/Titleblocks/WAU1_Logo.dwg
PROJECT:
DATE:
PROJECT NO.:
DAS #:
State of Iowa
Newton, Iowa Correctional Facility Iowa Prison Industries Warehouse
12/16/2022
0220983.00
DP-9239.00-.01-003
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
L:\
LA
ND
P
RO
JE
CT
S
\22
N
EW
TO
N
CO
RR
EC
TI
ON
AL
F
AC
ILI
TY
\D
W G\
C2 .1
LA
YO
UT
.D
W G
/12
/20
1:
:53 P
M
GRAPHIC SCALE
030 15 30 60
LAYOUT PLAN
C2.1
GENERAL NOTES:
1. CONTRACTOR TO PROVIDE GRADATION TESTING FOR GRANULAR
MATERIAL DELIVERED TO THE SITE GRADATION TESTING IS TO BE
CONDUCTED AND REVIEWED BY GEOTECHNICAL FIRM PRIOR TO
GRANULAR MATERIAL BEING INSTALLED.
2. IF GRANULAR MATERIAL ARE INSTALLED THAT DO NOT MEET THE
APPROVED GEOTECHNICAL REPORT AND SPECIFICATIONS. THE
CONTRACTOR, SHALL AT THEIR OWN EXPENSE, REMOVE AND
REPLACE THE DEFICIENT GRANULAR MATERIAL PER SPECIFICATION.
3. CONTRACTOR TO COORDINATE WITH OWNER TO MAINTAIN SITE
SECURITY AS NEEDED TO ACCOMMODATE CONSTRUCTION
ACTIVITIES.
AutoCAD SHX Text
NW 1/4 NE 1/4 SEC 28-T79-R19
| lrunciman | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C2.1 LAYOUT.dwg | 12/12/2022 11:14 AM |lrunciman | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C2.1 LAYOUT.dwg | 12/12/2022 11:14 AM | | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C2.1 LAYOUT.dwg | 12/12/2022 11:14 AM |L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C2.1 LAYOUT.dwg | 12/12/2022 11:14 AM | | 12/12/2022 11:14 AM |12/12/2022 11:14 AM | |
A/CA/C
FF=777.54
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
PUBLIC ACCESS RD
( ASPHALT SURFACE)
EX GRAVEL DRIVE
EX
BUILDINGEX
C
ON
CR
ET
E
EX POWER POLE
HEIGHT = 28'
EX POWER POLE
HEIGHT = 28'
F/O
F/O
F/O
F/O
F/O
F/O
F/O
EX. GRAVEL
9,000 SF W
AREHOUSE
FFE-774.00
772.25
772.94 772.45
772.95
774.00FF
774.00FF
774.00FF
774.00FF
773.20
773.00
773.25773.20
0.0%
0.1%
0.1%
0.1%
0.3%
0.3%
772.26
U/E
U/E
U/E
U/E
U/E
PROP 3'
SWALE ALONG
EDGE OF
GRAVEL
PROP 3'
SWALE ALONG
EDGE OF
GRAVEL
MAINTAIN EXISTING DRAINAGE
PATTERN FOR SURFACE
RUNOFF FLOWING NORTH TO
ROAD DITCH.
EM
773.18 773.00
S
S
S
A/CA/C
FF=777.54
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
PUBLIC ACCESS RD
( ASPHALT SURFACE)
EX GRAVEL DRIVE
EX
BUILDINGEX
C
ON
CR
ET
E
EX POWER POLE
HEIGHT = 28'
EX POWER POLE
HEIGHT = 28'
F/O
F/O
F/O
F/O
F/O
F/O
F/O
EX. GRAVEL
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
CONTRACTOR OUTHOUSE,
DUMPSTER & CONC. WASHOUT
(REF. DETAILS ON THIS SHEET)
STAGING
AREA
CONSTRUCTION
ENTRANCE.
SILT FENCE,
TYP.
TOPSOIL NOTES:
1. STRIP AND STOCKPILE THE TOP 8" OF SOIL ON ALL DISTURBED AREAS.
2. RESPREAD TOPSOIL TO A MINIMUM DEPTH OF 8" ON ALL GREEN (NON PAVED)
AREAS. IMPORT TOPSOIL AS NECESSARY TO ACHIEVE A MINIMUM DEPTH OF 6".
3. TOPSOIL SHALL BE FREE OF ALL ROCK AND DEBRIS LARGER THAN 3/4" IN SIZE.
4. TOPSOIL IS DEFINED AS: FERTILE, FRIABLE LOAM, CAPABLE OF SUSTAINING
VIGOROUS PLANT GROWTH, FROM WELL DRAINED SITE FREE FROM FLOODING, NOT
IN FROZEN OR MUDDY CONDITIONS; REASONABLE FREE FROM SUBSOIL, CLAY
LUMPS, ROOTS, GRASS, WEEDS, STONES LARGER THAN 3/4 INCH IN DIAMETER, AND
FOREIGN MATTER; ACIDITY RANGE (PH) OF 5.5 TO 7.5; CONTAINING MINIMUM 4
PERCENT AND MAXIMUM 20 PERCENT ORGANIC MATTER.
5. CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING ALL TOPSOIL
REQUIREMENTS OF NPDES GENERAL PERMIT NO. 2 ARE MET.
6. CONTRACTOR TO COORDINATE WITH GEOTECHNICAL REPORT FOR SUITABLE FILL
MATERIAL AS NEEDED TO ACCOMMODATE PROPOSED GRADING PLAN.
7. CONTRACTOR TO COORDINATE WITH GEOTECHNICAL AND OWNER FOR ANY
REQUIRED TESTING AND OBSERVATIONS.
8. CONTRACTOR TO MAINTAIN POSITIVE DRAINAGE ACROSS SITE TO PROVIDE
DRAINAGE AWAY FROM ANY EXISTING AND PROPOSED BUILDINGS.
DESCRIPTION:DATE:#
ISSUE:
100% CD
PROJECT:
DATE:
PROJECT NO.:
DAS #:
State of Iowa
Newton, Iowa Correctional Facility Iowa Prison Industries Warehouse
12/16/2022
0220983.00
DP-9239.00-.01-003
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
GRADING LEGEND:
EXISTING CONTOUR
PROPOSED CONTOUR
FINISHED GROUND ELEVATION
TOP OF CURB ELEVATION
GUTTER ELEVATION
TOP OF WALL ELEVATION
BOTTOM OF WALL ELEVATION
EDGE OF WALK ELEVATION
TOP OF STAIR ELEVATION
BOTTOM OF STAIR ELEVATION
NOTE: WALL ELEVATIONS SHOWN ON PLAN ARE FINISHED
GROUND GRADES AT THE TOP AND BOTTOM OF THE WALL.
150.50E/W
150.50B/W
150.50T/W
150.50G
150.50T/C
150.50
150.50T/S
150.50B/S
L:\
LA
ND
P
RO
JE
CT
S
\22
N
EW
TO
N
CO
RR
EC
TI
ON
AL
F
AC
ILI
TY
\D
W G\
C3 .1
GR
AD
IN
G.
DW
G
/16
/20
8:
:41 A
M
GRAPHIC SCALE
030 15 30 60
GRADING PLAN
EROSION CONTROL REMOVAL NOTES:
1. AFTER FINAL STABILIZATION HAS OCCURED, AS DEFINED IN NPDES GENERAL
PERMIT NO. 2, CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF
ALL TEMPORARY EROSION CONTROL DEVICES INCLUDING, BUT NOT LIMITED
TO: SILT FENCE, INLET PROTECTION, AND TEMPORARY STANDPIPES.
NOT TO SCALE
SITE ENTRANCE DETAIL
TEMP. ROCK ENTRANCE
(PLAN VIEW)
(PROFILE VIEW)
TEMP. ROCK ENTRANCE
3" CLEAN
LIMESTONE
PLACE ROCK
ON FABRIC
STABILIZED ENTRANCE SHALL BE AT
LEAST 50' LONG AND EXTEND TO THE
PUBLIC ROADWAY.
5'- 0"
M
IN
GROUND LINE
ENGINEERING FABRIC
FLOW
1' ABOVE GROUND LINE VARIABLE
10' MAX. 5' MAX. 5' MAX. 10' MAX.
1' ABOVE GROUND LINE
SECURE TOP OF ENGINEERING FABRIC
ENGINEERING FABRIC TO BE PLACED
TO BOTTOM OF TRENCH.
ENGINEERING
FABRIC
GROUND
LINE
TRENCH BOTTOM
TRENCH BOTTOM
1 1
LINE
GROUND
MIN.
4"
EXCESS FABRIC
COMPACTED BACKFILL
MI
N.
DETAIL OF SILT FENCE AT DITCH OR SWALE
DETAIL OF SILT FENCE
8' SPACING
TO TOP OF STEEL POST.
SEE DETAIL OF ATTACHMENT TO POST.
VERTICAL CUT
WIRE
CORD
CORD
CORD
WIRE
POST
FABRIC
FABRIC
BACK VIEW OF FABRIC
BACK VIEW
ATTACHMENT TO POST
NOTES :
3 MAKE VERTICAL CUT IN TOP OF FABRIC.
PULL OUT AND TWIST CORD.
4 LOOP CORD AROUND POST FORMING A
LOOP. PULL WIRE THROUGH FOLD AREA
OF FABRIC AND SECURE AROUND POST.
'T' STEEL
FENCE POST
NORMAL
FORESLOPE
2" RISE
IN FENCE
31"
MIN.
NORMAL BACKSLOPE
" M
IN
6" TRENCH DEPTH FOR
NORMAL INSTALLATION
(MIN.) 12" TRENCH
DEPTH FOR DITCH
INSTALLATION
NOT TO SCALE
(SECTION VIEW)
(PROFILE VIEW)
SILT FENCE DETAILS
NOT TO SCALE
INLET
5'-0"
5'-0"
'T' FENCE POST, 5' MIN.
NOTES:
1. SECURE TOP OF FABRIC TO
POSTS, USING CABLE TIES OR
WIRE.
2. FABRIC TO BE BURIED 12", AND
FOLDED ALONG BOTTOM.
3. STEEL POSTS TO BE EMBEDDED
28".
(PLAN VIEW)
DROP INLET BASKET
PROTECTION
SILT FENCE FABRIC
IF APPLICABLE
INLET PROTECTION DETAIL
NOT TO SCALE
NOTES:
1. 1 C.Y. CONCRETE BAG SHALL BE REQUIRED AT ANY
LOCATION WHERE CONCRETE IS USED.
2. CONCRETE WASHOUT DUMPSTER W/ HEAVY DUTY
LINER IS AN ACCEPTIBLE ALTERNATIVE
(PLAN VIEW)
1 C.Y. CONCRETE
WASH-OUT BAG
'T' FENCE POST
5' MIN
CONCRETE WASH-OUT BAG DETAIL
(PROFILE VIEW)
1 C.Y. CONCRETE
WASH-OUT BAG
STABILIZED ENTRANCE AT LEAST 50'
LONG-12" DEEP CLASS "A" ROAD STONE
ON GEOTEXTILE
SILT FENCE (TYP)
LEGEND:
EXISTING CONTOUR
PROPOSED CONTOUR120
SFSF SF
GRADING LEGEND:
EXISTING CONTOUR
PROPOSED CONTOUR
FINISHED GROUND ELEVATION
TOP OF CURB ELEVATION
GUTTER ELEVATION 150.50G
150.50T/C
150.50
EROSION CONTROL NOTES:
1. SEE SUPPLEMENTAL DETAIL STORM WATER POLLUTION PLAN NARRATIVE FOR ALL EROSION CONTROL MEASURES, ADDITIONAL
DETAILS AND NOTE. ADDITIONAL NOTES AND MEASURES IN NARRATIVE SHALL BE CONSIDERED INCIDENTAL AND SHALL BE
INCLUDED IN THE ORIGINAL BID.
2. SWPPP PLAN AND NARRATIVE ARE CONSIDERED A LIVING DOCUMENT AND WILL NEED PERIODIC UPDATES AND ADJUSTMENTS AS NECESSARY DEPENDING ON SITE CONDITIONS TO ASSURE COMPLIANCE WITH NPDES GENERAL PERMIT NO. 2. IT IS THE CONTRACTOR'S RESPONSIBILITY TO UPDATE THE SWPPP AND IMPLEMENT ANY AND ALL MEASURES NECESSARY TO COMPLY WITH
SAID PERMIT NO. 2.
3. INSTALL PERIMETER SILT FENCE AS SHOWN ON PLANS PRIOR TO CONSTRUCTION.
4. INSTALL INTAKE PROTECTION WITH SILT FENCE IMMEDIATELY AFTER STORM SEWER CONSTRUCTION.
5. INSTALL FINISHED PAVING INLET PROTECTION IMMEDIATELY AFTER PAVING IS COMPLETED AROUND INTAKE.
6. OTHER EROSION CONTROL TYPES MAY NOT BE SUBSTITUTED FOR SILT FENCE.
7. CONTRACTOR SHALL BE RESPONSIBLE FOR SUPPLYING A CONCRETE WASHOUT IN ACCORDANCE WITH NPDES GENERAL PERMIT
NO. 2 DURING ALL CONCRETE WORK.
8. MANAGER/OWNER SHALL BE RESPONSIBLE FOR SUPPLYING TEMPORARY DUMPSTERS AND RESTROOM FACILITIES. SANITARY
WASTE SHALL BE DISPOSED OF PER ALL FEDERAL, STATE AND LOCAL REGULATIONS.
9. CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING ALL TOPSOIL REQUIREMENTS OF NPDES GENERAL PERMIT NO. 2 ARE MET.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR REVISING AND/OR INSTALLING ADDITIONAL EROSION CONTROL MEASURES/SEEDING
AS NEEDED TO ACCOMMODATE THE CONSTRUCTION PHASING AND SWPPP INSPECTOR REQUIREMENTS. SUCH CHANGES SHALL BE
INCIDENTAL TO THE PROJECT. ALL CHANGES SHALL BE DOCUMENTED AND RECORDED.
11. THIS PROJECT INCLUDES SAWCUTTING OR CONCRETE GRINDING SO PROTECTION OF STORM SEWERS AND DRAINAGE WAYS WILL NEED TO BE PROVIDED FROM SLURRY FROM THE CONCRETE OPERATIONS TO DISCHARGE OFFSITE. SEE SWPPP SHEET AND
NARRATIVE FOR ADDITIONAL DETAILS.
12. CONTRACTOR SHALL PROVIDE APPROPRIATE CONTROLS TO PREVENT DISCHARGES FROM ANY AND ALL DEWATERING ACTIVITIES.
13. SEE LANDSCAPE PLAN FOR FINAL STABILIZATION INCLUDING SEEDING AND SODDING AREAS.
14. PER NPDES GENERAL PERMIT NO. 2, IF CONSTRUCTION ACTIVITY IS NOT PLANNED FOR AT LEAST 14 DAYS, ALL DISTURBED AREAS
SHALL BE STABILIZED IMMEDIATELY BY TEMPORARY EROSION CONTROL MEASURES.
15. THE FOLLOWING DISCHARGES ARE PROHIBITED: WASTEWATER FROM WASHOUT AND CLEANOUT OF STUCCO, PAINT, FORM
RELEASE OIL, CURING COMPOUNDS AND OTHER CONSTRUCTION MATERIALS, FUEL, OILS OR OTHER POLLUTANTS USED IN VEHICLE AND EQUIPMENT OPERATION AND MAINTENANCE, AND SOAPS OR SOLVENTS USED IN VEHICLE AND EQUIPMENT
WASHING.
16. CONTRACTOR TO INSTALL "TURF REINFORCED MATTING" TRM ON ALL EMBANKMENTS AND DRAINAGE/DETENTION AREAS.
17. ANY ADDITIONAL TRM THAT IS NEEDED TO STABILIZE AREAS THAT ARE IDENTIFIED BY THE OWNER,ENGINEER OR SWPPP
INSPECTOR DURING CONSTRUCTION AND SEEDING SHALL BE CONSIDERED INCIDENTAL.
18. CONTRACTOR IS RESPONSIBLE FOR INSTALLING AND PHASING EROSION CONTROLS AND SILT FENCE, PER SWPPP INSPECTORS
RECOMMENDATIONS, TO MAINTAIN EROSION PROTECTION AND ACCOMMODATE CONSTRUCTION ACTIVITIES AND PHASING. ANY
ADDITIONAL EROSION CONTROLS OR ADJUSTMENTS SHALL BE INCIDENTAL.
19. CONTRACTOR IS RESPONSIBLE FOR CORRECTING ANY SILTING, REELING OR SCOURING TO DESIGN GRADE BEFORE CLOSE OF
PROJECT PER SWPPP INSPECTOR AND OWNER RECOMMENDATIONS.
20. CONTRACTOR TO PROTECT PROPOSED PONDS DURING CONSTRUCTION FROM EROSION AND SILTING. ANY CORRECTIVE WORK TO
RESTORE POND BOTTOMS SHALL BE INCIDENTAL.
DISTURBED AREA = 0.90 ACRES±
C3.1
SEEDING NOTES:
1. CONTRACTOR TO PREPARE AND SEED ALL DISTURBED AREAS OUTSIDE OF
GRAVEL LIMITS WITH UNITED SEED TYPE II MIX,
2. CONTRACTOR TO FOLLOW PRODUCT DATA RECOMMENDATIONS FOR
APPLICATION AND RATES.
AutoCAD SHX Text
NW 1/4 NE 1/4 SEC 28-T79-R19
AutoCAD SHX Text
NW 1/4 NE 1/4 SEC 28-T79-R19
AutoCAD SHX Text | lrunciman | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C3.1 GRADING.dwg | 12/12/2022 10:39 AM |lrunciman | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C3.1 GRADING.dwg | 12/12/2022 10:39 AM | | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C3.1 GRADING.dwg | 12/12/2022 10:39 AM |L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C3.1 GRADING.dwg | 12/12/2022 10:39 AM | | 12/12/2022 10:39 AM |12/12/2022 10:39 AM | |
TRENCH BOTTOM
EX 18" CMP
TOP=774.30
EX 18" CMP
TOP=773.98
A/CA/C
FF=777.54
W W
W
W
W
W
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
EX LOCATION PER
WINDSTREAM MAP
PUBLIC ACCESS RD
( ASPHALT SURFACE)
EX GRAVEL DRIVE
EX
BUILDINGEX
C
ON
CR
ET
E
EX POWER POLE
HEIGHT = 28'
EX POWER POLE
HEIGHT = 28'
F/O
F/O
F/O
F/O
F/O
F/O
F/O
EX. GRAVEL
APPROX. LOCATION OF
EX. SEPTIC FIELD & TANK
9,000 SF W
AREHOUSE
FFE-774.00
U/E
U/E
U/E
U/E
U/E
EM
PROP. 2" CONDUIT FOR FIBER/TELEPHONE
(REF. TO MEP PLANS)
PROP. UNDERGROUND PRIMARY
(REF. TO MEP PLANS)
PROP. UNDERGROUND SECONDARY
(REF. TO MEP PLANS)
S
S
S
S
FUTURE SANITARY SEWER MAIN.
OWNER WILL INSTALL AND CONNECT BUILDING
SEWER SERVICE IF NEEDED AFTER MAIN HAS
BEEN INSTALLED
EXISTING CONDUIT TO BE SLEEVED
UNDERNEATH BUILDING.
REFER TO MEP PLANS.
EX 18" CMP
TOP=774.30
EX 18" CMP
TOP=773.98
A/CA/C
FF=777.54
W W
W
W
W
W
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
TELE
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
O/E
EX LOCATION PER
WINDSTREAM MAP
PUBLIC ACCESS RD
( ASPHALT SURFACE)
EX GRAVEL DRIVE
EX
BUILDINGEX
C
ON
CR
ET
E
EX POWER POLE
HEIGHT = 28'
EX POWER POLE
HEIGHT = 28'
F/O
F/O
F/O
F/O
F/O
F/O
F/O
EX. GRAVEL
APPROX. LOCATION OF
EX. SEPTIC FIELD & TANK
UTILITY NOTES:
1. ALL PROPOSED UTILTIES SHALL BE PRIVATE, UNLESS NOTED OTHERWISE.
2. PROTECT ALL EXISTING UTILITIES NOT CALLED OUT FOR REMOVAL.
3. CONTRACTOR TO COORDINATE WITH UTILITY PROVIDER FOR ALL ROUTING AND CONNECTIONS.
4. CONTRACTOR TO COORDINATE APPROVALS WITH COUNTY FOR ANY WORK WITHIN THE R.O.W.
PRIOR TO CONSTRUCTION.
5. CONTRACTOR TO REFER TO BUILDING AND MEP PLANS FOR BUILDING SERVICE CONNECTIONS.
DESCRIPTION:DATE:#
ISSUE:
100% CD
PROJECT:
DATE:
PROJECT NO.:
DAS #:
State of Iowa
Newton, Iowa Correctional Facility Iowa Prison Industries Warehouse
12/16/2022
0220983.00
DP-9239.00-.01-003
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
L:\
LA
ND
P
RO
JE
CT
S
\22
N
EW
TO
N
CO
RR
EC
TI
ON
AL
F
AC
ILI
TY
\D
W G\
C4 .1
UT
ILI
TY
.D
W G
/12
/20
1:
:50 P
M
GRAPHIC SCALE
030 15 30 60
UTILITY PLAN
C4.1
AutoCAD SHX Text
NW 1/4 NE 1/4 SEC 28-T79-R19
AutoCAD SHX Text
NW 1/4 NE 1/4 SEC 28-T79-R19
| lrunciman | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C4.1 UTILITY.dwg | 12/12/2022 10:39 AM |lrunciman | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C4.1 UTILITY.dwg | 12/12/2022 10:39 AM | | L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C4.1 UTILITY.dwg | 12/12/2022 10:39 AM |L:\Land Projects 2022\220333 Newton Correctional Facility\dwg\C4.1 UTILITY.dwg | 12/12/2022 10:39 AM | | 12/12/2022 10:39 AM |12/12/2022 10:39 AM | |
A3.1
A3.1
A3.1
A3.1
2 3
18'-6" 23'-0" 18'-6"
B
C
D
E
F
G
H
/4
/4
/2
I
J
11929 SF
WAREHOUSE
K
L
P
A
1 4
M
N
O
20'-0" 20'-0" 4'-0" 3'-4" 12'-8"
12'-8" 3'-4" 4'-0" 20'-0" 20'-0"
/2
100-1
100-2
100-5
100-3
100-4
A4.1 _____5
A4.1
A4.1
A4.1
A4.1
A4.1
Q
R
S
T
U
V
W
X
Y
Z
60'-0"
GENERAL NOTE:
FIRE EXTINGISHERS AND BRACKETS PROVIDED BY
OWNER. MAXIMUM TRAVEL DISTANCE SHALL BE 75 FEET.
EXACT LOCATION TO BE DETEMINED BY ARCHITECT
F.E.
F.E.
2 3
18'-6" 23'-0" 18'-6"
60'-0"
B
C
D
E
F
G
H
/4
/4
/2
I
J
9057 SF
WAREHOUSE
K
L
T
A
1 4
M
N
O
20'-0" 20'-0" 4'-0" 3'-4" 12'-8"
12'-8" 3'-4" 4'-0" 20'-0" 20'-0"
(M A
X C
O L
U M
N S
P A
C
IN
G
O
.C
P
Q
R
S
A4.1
100-3
100-4
100-5
100-1
100-2
A3.1
A3.1
A3.1
A3.1
A4.1
A4.1
A4.1
A4.1 _____ 5
A4.1
F.E.
F.E.
GENERAL NOTE:
FIRE EXTINGISHERS AND BRACKETS PROVIDED
BY OWNER. MAXIMUM TRAVEL DISTANCE SHALL
BE 75 FEET. EXACT LOCATION TO BE DETEMINED
BY ARCHITECT
WEATHERSTRIPPING
- TYPICAL @ ALL JAMBS
INSUL. STEEL
SECTIONAL DOOR
- SEE DOOR SCHEDULE
PRE-FINISHED
METAL WALL PANEL
TRACK
ATTACH TRACK
BRACKETS TO WOOD
FRAMING/BLOCKING
PRE-FIN. METAL WRAP
@ DOOR OPENING
PRE-FIN. MTL. "J" TRIM
1 1/2" 7"
8 1/2"
PRE-FINISHED
METAL WALL PANEL
PRE-FINISHED
METAL FLASHING
PRE-FINISHED
METAL RAIN DRIP
EXTERIOR H.M.
DOOR & FRAME
- SEE DOOR SCHEDULE
CONTINUOUS
BLOCKING (TYPICAL)
(4) 2x12 HEADER
1 1/2" 7"
3/4"
B.O. HEADER
ELEV. 7'-2"
ALUM THRESHOLD - BELOW
PRE-FIN. METAL
WALL PANEL
DOUBLE 2x6 @ JAMBS
INSUL. EXT. HM DOOR
& FRAME - SEE DOOR
SCHEDULE
1 1/2" 7"
8 1/2"
3/4"
6"
PRE-FIN. MTL. "J" TRIM
1/2" EXPANSION JOINT
EXT. HM DOOR &
FRAME - SEE DOOR
SCHEDULE
REINF. CONCRETE SLAB
OVER GRANULAR FILL
- SEE STRUCT. DWGS
REINF. CONC. STOOP
OVER VOID FORM
- SEE STRUCTURAL DWGS
ALUMINUM THRESHOLD
- SET IN MASTIC
REINF. CONCRETE
FOUNDATION
- SEE STRUCT. DWGS.
8 1/2"
3/4"
2"x2"x1/4" STEEL TUBE w/ 1/4" DIA. x4" ANCHOR
BOLT WELDED TO TUBE
WEATHERSTRIPPING
OVERHEAD DOOR
TRACK
INSUL. STEEL
SECTIONAL DOOR
PREFIN. METAL
DRIP FLASHING
PRE-FINISHED
METAL WALL PANEL
PRE-FIN. METAL WRAP
@ DOOR OPENING
BLOCKING TYPICAL
(4) 2x12 TRANSFER BEAMS
8 1/2"
1 1/2" 7"
B.O. HEADER
ELEV. 14'-0"
FACE OF METAL (BEYOND)
DOOR TRACK (TYP)
O.H. STEEL SECTIONAL
DOOR - SEE SCHEDULE
REINF. CONCRETE STOOP
- SEE STRUCT. DWGS.
REINF. CONCRETE SLAB
OVER GRANULAR FILL
- SEE STRUCT. DWGS.
REINF. CONCRETE
FOUNDATION WALL
- SEE STRUCT. DWGS.
3"Ø STD. STEEL GALV.
PIPE - w/ EMBED ANCHORS
/2
8 1/2"
1/2" EXPANSION JOINT
7" x 7" PRE-FINISHED
METAL GUTTER
PRE-FINISHED METAL ROOF PANEL
PRE-ENGINEERED
WOOD TRUSS
2x ROOF PURLINS
FASCIA TRIM
4"x6" PRE-FINISHED
METAL DOWNSPOUT
PRE-FINISHED
METAL EVE TRIM
PRE-FINISHED
METAL WALL PANEL
WOOD COLUMN
PRE-FINISHED
METAL WALL PANEL
PRE-FININISHED METAL ROOF PANEL
PRE-ENGINEERED
WOOD TRUSS
- SEE ROOF
FRAMING PLAN
PRE-FINISHED
METAL RAKE TRIM
2x ROOF PURLINS
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:5
:1
P
M A1.1
FLOOR PLANS - BASE
BID AND ALTERNATE
No. 1, SCHEDULES &
DETAILS
LS
LS
0220983.00
Newton Correctional Facility Iowa Prison Industries Warehouse
State of Iowa DOC
Newton, Iowa
12/16/2022
LS
100% CONSTRUCTION
DOCUMENTS
SCALE: 1/16" = 1'-0"
OVERALL FLOOR PLAN - ALTERNATE No. 1
DOOR SCHEDULE
NO. LEAFS
DOOR FRAME
DETAILS
(A1.1 U.N.O.) HARDWARE
SEE SPEC. NOTESWIDTH HEIGHT MATERIAL FINISH TYPE MATERIAL FINISH TYPE HEAD JAMB THRESHOLD
100-1 1 3' - 0" 7' - 0" IHM P F HM P
100-2 20' - 0" 14' - 0" - FF OHSD - FF
100-3 1 3' - 0" 7' - 0" IHM P F HM P
100-4 20' - 0" 14' - 0" - FF OHSD - FF
100-5 2 6' - 0" 7' - 0" IHM P F HM P
SCALE: 1/16" = 1'-0"
OVERALL FLOOR PLAN - BASE BID
NORTH
TRUE
0 8 16 32
NORTH
PLAN
SCALE: 1 1/2" = 1'-0"
SECTIONAL DOOR JAMB DETAIL
SCALE: 1 1/2" = 1'-0"
EXTERIOR H.M. DOOR HEAD DETAIL
SCALE: 1 1/2" = 1'-0"
EXT. HOLLOW METAL DOOR JAMB DETAIL
SCALE: 1 1/2" = 1'-0"
EXT. HOLLOW METAL DOOR & FRAME
THRESHOLD
SCALE: 1 1/2" = 1'-0"
O.H. SECTIONAL DOOR HEAD DETAIL
SCALE: 1 1/2" = 1'-0"
SECTIONAL DOOR SILL DETAIL
SCALE: 1 1/2" = 1'-0"
ROOF GUTTER DETAIL
SCALE: 1 1/2" = 1'-0"
ROOF RAKE DETAIL
A. ALL ROOF SURFACES TO SLOPE AT A MINIMUM 4" PER FOOT UNLESS OTHERWISE
NOTED OR SHOWN.
B. COORDINATE ALL ROOF PENETRATION REQUIREMENTS, INCLUDING THOSE THAT
MAY NOT BE SHOWN, WITH ROOFING CONTRACTOR, AND MECHANICAL,
ELECTRICAL, AND PLUMBING DRAWINGS.
C. ALL ROOF PENETRATIONS TO BE IN COMPLIANCE WITH MANUFACTURER AND
NRCA REQUIREMENTS.
D. ROOFING COMPONENTS MAY VARY DEPENDING ON ROOFING MANUFACTURER.
CONTRACTOR SHALL INSTALL A COMPLETE CODE COMPLIANT AND WARRANTIED
ROOFING SYSTEM BASED ON THE SPECIFIED ROOFING MANUFACTURERS
WRITTEN INSTRUCTIONS AND INSTALLATION GUIDELINES.
E. ONCE ROOF WORK BEGINS, THE CONTRACTOR IS ACCEPTING ALL CONDITIONS
AND WILL BE RESPONSIBLE FOR ALL DEMOLITION AND NEW WORK REQUIRED TO
PROVIDE A WATERTIGHT ROOF SYSTEM.
F. THE CONTRACTOR SHALL ENSURE THAT UPON COMPLETION OF ROOF WORK, ALL
GUTTERS, DOWNSPOUTS AND ROOF DRAINS ARE CLEAN AND CLEAR OF DEBRIS
TO PROVIDE AN UNOBSTRUCTED, FREE FLOW OF WATER.
ROOF GENERAL NOTES
A3.1
A3.1
A3.1
A3.1
A4.1
A4.1
A4.1
A4.1
10'-0" 10'-0"
A2.1
D.S.D.S.
D.S.D.S.
D.S.D.S.
D.S.D.S.
D.S.D.S.
D.S.D.S.
PREFABRICATED
SMOKE / HEAT VENT
- SEE SPEC. (TYPICAL)
PRE-FINISHED METAL
ROOF PANEL
(TYPICAL)
7" x 7" PRE-FINISHED
METAL GUTTER
(TYPICAL)
10'-0" 10'-0"
10'-0" 10'-0" 4" x 6" PRE-FINISHED
METAL DOWNSPOUT
(TYPICAL)
10'-0" 10'-0"
A3.1
A3.1
A3.1
A3.1
D.S. D.S.
D.S. D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
D.S.
SMOKE HEAT VENT
(TYPICAL
4" / 1'-0" 4" / 1'-0"
PRE-FINISHED METAL
ROOF PANEL
7" x 7" PRE-FINISHED
METAL GUTTER
(TYPICAL)
A2.1
A4.1
A4.1
A4.1
A4.1
PRE-FINISHED METAL WALL PANEL
2x GIRT (TYPICAL)
PRE-FINISHED METAL
ROOF PANEL (TYPICAL)
2x ROOF PURLINS (TYPICAL)
PREFABICATED SMOKE / HEAT VENT
- SEE SPEC.
4" 1'-0"
2x4 WOOD STUD FRAMING
(TYPICAL)
PRE-FINISHED METAL FLASHING
- ENTIRE PERIMETER
PRE-FINISHED METAL FLASHING
- ENTIRE PERIMETER
FABRICATED
CRICKET
B.O. TRUSS
ELEV. 18'-0"
PRE-ENGINEERED
WOOD TRUSS (TYPICAL)
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:5
:1
P
M A2.1
ROOF PLANS - BASE
BID & ALTERNATE
No. 1, AND DETAILS
LS
LS
0220983.00
Newton Correctional Facility Iowa Prison Industries Warehouse
State of Iowa DOC
Newton, Iowa
12/16/2022
LS
100% CONSTRUCTION
DOCUMENTS
0 8 16 32
NORTH
PLAN
SCALE: 1/16" = 1'-0"
ROOF PLAN - ALTERNATE No. 1
SCALE: 1/16" = 1'-0"
ROOF PLAN - BASE BID 0 8 16 32
NORTH
PLAN
SCALE: 1/2" = 1'-0"
PREFABRICATED SMOKE / HEAT VENT SECTION
MAIN FLOOR
0'-0"
B.O. TRUSS
18'-0"
A4.1 _____4
A4.1
B.O. FOOTING
-3'-6"
T.O. O.H. DOOR
14'-0"
T.O. H.M. FRAME
7'-2"
PRE-FINISHED METAL
WALL PANEL
CONCRETE STEM WALL
- SEE STRUCT. DWGS.
20'-0" W x 14'-0" H OVERHEAD
SECTIONAL DOOR - SEE SCHEDULE
PRE-FINISHED METAL ROOF PANEL
7" x 7" PRE-FINISHED
METAL GUTTER
4" x 6" PRE-FINISHED
METAL DOWNSPOUT
HOLLOW METAL DOOR
& FRAME - SEE SCHEDULE
PREFABRICATED
SMOKE / HEAT VENT
- SEE SPEC. (TYPICAL)
4" 1'-0"
4"
1'-0"
100-2100-1
MAIN FLOOR
0'-0"
B.O. TRUSS
18'-0"
A4.1 _____ 3
A4.1
B.O. FOOTING
-3'-6"
T.O. O.H. DOOR
14'-0"
T.O. H.M. FRAME
7'-2"
A2.1
PRE-FINISHED METAL
WALL PANEL
CONCRETE STEM WALL
- SEE STRUCT. DWGS.
PRE-FINISHED METAL
ROOF PANEL
7" x 7" PRE-FINISHED
METAL GUTTER
4" x 6" PRE-FINISHED
METAL DOWNSPOUT
SMOKE HEAT VENT
(TYPICAL)
100-5
MAIN FLOOR
0'-0"
B.O. TRUSS
18'-0"
A4.1 _____ 4
A4.1
B.O. FOOTING
-3'-6"
T.O. O.H. DOOR
14'-0"
T.O. H.M. FRAME
7'-2"
PRE-FINISHED METAL
WALL PANEL
CONCRETE STEM WALL
- SEE STRUCT. DWGS.
20'-0" W x 14'-0" H OVERHEAD
SECTIONAL DOOR - SEE SCHEDULE
PRE-FINISHED METAL
ROOF PANEL
7" x 7" PRE-FINISHED
METAL GUTTER
4" x 6" PRE-FINISHED METAL
DOWNSPOUT (TYPICAL)
HOLLOW METAL DOOR
& FRAME - SEE SCHEDULE
PREFABRICATED
SMOKE / HEAT VENT
- SEE SPEC. (TYPICAL)
4"
1'-0"
4" 1'-0"
100-3 100-4
MAIN FLOOR
0'-0"
B.O. TRUSS
18'-0"
A4.1 _____3
A4.1
B.O. FOOTING
-3'-6"
T.O. O.H. DOOR
14'-0"
T.O. H.M. FRAME
7'-2"
A2.1
PRE-FINISHED METAL
WALL PANEL
CONCRETE STEM WALL
- SEE STRUCT. DWGS.
PRE-FINISHED METAL
ROOF PANEL
7" x 7" PRE-FINISHED
METAL GUTTER
4" x 6" PRE-FINISHED
METAL DOWNSPOUT
PREFABRICATED SMOKE / HEAT
VENT - SEE SPEC. (TYPICAL)
PRE-FINISHED METAL
WALL PANEL
CONCRETE STEM WALL
- SEE STRUCT. DWGS.
PRE-FINISHED METAL
ROOF PANEL
7" x 7" PRE-FINISHED
METAL GUTTER
4" x 6" PRE-FINISHED
METAL DOWNSPOUT
HOLLOW METAL DOOR & FRAME
- SEE SCHEDULE
PREFABRICATED SMOKE / HEAT
VENT - SEE SPEC. (TYPICAL)
100-5
PRE-FINISHED METAL
WALL PANEL
CONCRETE STEM WALL
- SEE STRUCT. DWGS.
PRE-FINISHED METAL
ROOF PANEL
7" x 7" PRE-FINISHED
METAL GUTTER
4" x 6" PRE-FINISHED
METAL DOWNSPOUT
PREFABRICATED SMOKE / HEAT
VENT - SEE SPEC. (TYPICAL)
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:5
:1
P
M A3.1
EXTERIOR
ELEVATIONS
LS
LS
0220983.00
Newton Correctional Facility Iowa Prison Industries Warehouse
State of Iowa DOC
Newton, Iowa
12/16/2022
LS
100% CONSTRUCTION
DOCUMENTS
SCALE: 1/16" = 1'-0"
BASE BID AND ALTERNATE No. 1 - NORTH ELEVATION
SCALE: 1/16" = 1'-0"
ALTERNATE No. 1 - EAST ELEVATION
SCALE: 1/16" = 1'-0"
BASE BID AND ALTERNATE No. 1 - SOUTH ELEVATION
SCALE: 1/16" = 1'-0"
ALTERNATE No. 1 - WEST ELEVATION
SCALE: 1/16" = 1'-0"
BASE BID - EAST ELEVATION
SCALE: 1/16" = 1'-0"
BASE BID - WEST ELEVATION
MAIN FLOOR
0'-0"
B.O. TRUSS
18'-0"
B.O. FOOTING
-3'-6"
1"
PRE-FINISHED METAL WALL PANEL
WOOD COLUMN
7" x 7" PRE-FINISHED
METAL GUTTER
PRE-FINISHED METAL ROOF PANEL
WOOD TRUSS
CONCRETE STEM WALL
- SEE STRUCT. DWGS.
PACKED DIRT FLOOR SURFACE
CONCRETE TRENCH FOOTING
- SEE STRUCT. DWGS.
2x TREATED SKIRT BOARD
2x GIRT (TYPICAL)
2x ROOF PURLINS (TYPICAL)
A4.1
4"
1'-0"
FASCIA TRIM
A1.1
MAIN FLOOR
0'-0"
A
B.O. FOOTING
-3'-6"
T.O. O.H. DOOR
14'-0"
20'-0" W x 14'-0" H
OVERHEAD SECTIONAL DOOR
CONCRETE STOOP
- SEE STRUCT. DWGS.
PACKED DIRT FLOOR SURFACE
PRE-FINISHED METAL WALL PANEL
2X WOOD FRAMING
WOOD COLUMN
PRE-FINISHED METAL ROOF PANEL
WOOD PURLINS
2x GIRT (TYPICAL)
(4)2x12 MICRO-LAM. BEAMS TYP.
FASCIA TRIM
A1.1
A1.1
A1.1
A1.1
WOOD TRUSS
CONCRETE TRENCH FOOTING
- SEE STRUCT. DWGS.
MAIN FLOOR
0'-0"
B.O. TRUSS
18'-0"
B.O. FOOTING
-3'-6"
T.O. H.M. FRAME
7'-2"
HOLLOW METAL DOOR &
FRAME - SEE SCHEDULE
4"
1'-0"
A1.1
A1.1
A1.1
PRE-FINISHED METAL WALL PANEL
WOOD COLUMN
7" x 7" PRE-FINISHED
METAL GUTTER
PRE-FINISHED METAL ROOF PANEL
WOOD TRUSS
CONCRETE TRENCH FOOTING
- SEE STRUCT. DWGS.
2x GIRT (TYPICAL)
2x ROOF PURLINS (TYPICAL)
FASCIA TRIM
A1.1
PACKED DIRT
FLOOR SURFACE
(4)2x12 MICRO-LAM. BEAMS TYP.
CONCRETE STOOP
- SEE STRUCT. DWGS.
MAIN FLOOR
0'-0"
B.O. FOOTING
-3'-6"
Z
1"
A1.1
A4.1
PRE-FINISHED METAL WALL PANEL
WOOD COLUMN
CONCRETE STEM WALL
- SEE STRUCT. DWGS.
2x TREATED SKIRT BOARD
2x GIRT (TYPICAL)
PACKED DIRT FLOOR SURFACE
PRE-FINISHED METAL ROOF PANEL
WOOD PURLINS
WOOD TRUSS
FASCIA TRIM
CONCRETE TRENCH FOOTING
- SEE STRUCT. DWGS.
MAIN FLOOR
0'-0"
B.O. TRUSS
18'-0"
2 31 4
60'-0"
C L E
A R
20'-0"
A4.1
B.O. FOOTING
-3'-6"
T.O. O.H. DOOR
14'-0"
T.O. H.M. FRAME
7'-2"
4"
1'-0"
4"
1'-0"
MAIN FLOOR
0'-0"
B.O. FOOTING
-3'-6"
CONCRETE STEM WALL
- SEE STRUCT. DWGS.
2x TREATED SKIRT BOARD
PACKED DIRT
FLOOR SURFACE
CONCRETE TRENCH FOOTING
- SEE STRUCT. DWGS.
PRE-FINISHED METAL
WALL PANEL
WOOD COLUMN
"J" ANCHOR BOLT
- SEE STRUCTURAL DWGS.
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:5
:1
P
M A4.1
SECTIONS
LS
LS
0220983.00
Newton Correctional Facility Iowa Prison Industries Warehouse
State of Iowa DOC
Newton, Iowa
12/16/2022
LS
100% CONSTRUCTION
DOCUMENTS
SCALE: 1/2" = 1'-0"
WALL SECTION @ EAVE SIDE
SCALE: 1/2" = 1'-0"
TYPICAL WALL SECTION
SCALE: 1/2" = 1'-0"
TYPICAL WALL SECTION
SCALE: 1/2" = 1'-0"
TYPICAL WALL SECTION
SCALE: 1/8" = 1'-0"
TYPICAL BUILDING SECTION - EAST/WEST
SCALE: 1" = 1'-0"
CONCRETE STEM WALL
A4.1
A4.1
A4.1
A4.1
A2.1
WOOD TRUSSES
(TYPICAL)
(2)x 2x6 WOOD
FRAMING (TYPICAL)
WOOD TRUSS
(TYPICAL)
A. CEILING MOUNTED LIGHT FIXTURES ARE SHOWN FOR COORDINATION
PURPOSES. EXIT SIGNAGE, SPRINKLER HEADS, SMOKE DETECTORS AND OTHER
DEVICES ARE NOT SHOWN. ALL CEILING MOUNTED DEVICES SHALL BE
CENTERED BETWEEN TRUSSES. COORDINATE WITH MECHANICAL AND
ELECTRICAL DRAWINGS FOR DEVICES NOT SHOWN. CONTRACTOR TO REVIEW
CEILING LAYOUT AND NOTIFY DESIGN PROFESSIONAL OF ANY CONFLICTS
BEFORE PROCEEDING WITH CONSTRUCTION.
REFLECTED CEILING PLAN GENERAL NOTES
SMOKE/HEAT VENT
REFLECTED CEILING PLAN LEGEND
LIGHT FIXTURE
A4.1
A4.1
A4.1
A4.1
WOOD TRUSS
(TYPICAL)
(2)x 2x6 WOOD
FRAMING (TYPICAL)
A2.1
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:5
:1
P
M A5.1
REFLECTED CEILING
PLAN - BASE BID &
ALTERNATE No. 1
LS
LS
0220983.00
Newton Correctional Facility Iowa Prison Industries Warehouse
State of Iowa DOC
Newton, Iowa
12/16/2022
LS
100% CONSTRUCTION
DOCUMENTS
0 8 16 32
NORTH
PLAN
SCALE: 1/16" = 1'-0"
REFLECTED CEILING PLAN - ALTERNATE No. 1
SCALE: 1/16" = 1'-0"
REFLECTED CEILING PLAN - BASE BID 0 8 16 32
NORTH
PLAN
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:5 :0
A
M S0.1
STRUCTURAL NOTES
MAW
NTK
0220983.00
Newton Correctional Facility Iowa Prison Industries Warehouse
Owner
Newton, Iowa
12/16/2022
SMH
LAM LAMINATED
KO KNOCK OUT XX-STRONG DOUBLE EXTRA STRONG
JST JOIST X-STRONG EXTRA STRONG
JT JOINT X-BRACING CROSS BRACING
INT INTERIOR WP WORKING POINT
INSUL INSULATION WD WOOD
IF INSIDE FACE W/ WITH
ID INSIDE DIAMETER WWR WELDED WIRE REINF
IN INCH VERT VERTICAL
HORIZ HORIZONTAL VIF VERIFY IN FILED
HPC HIGH-PERFORMANCE COATING UNO UNLESS NOTED OTHERWISE
HT HEIGHT TYP TYPICAL
HD HEADED TRANS TRANSVERSE
GYP BD GYPSUM BOARD T & G TONGUE & GROVE
GYP GYPSUM THRU THROUGH
GALV GALVANIZED TEMP TEMPERATURE
GA GAGE OR GAUGE STRUCT STRUCTURAL
FRMG FRAMING STIFF STIFFENER
FDN or FOUND FOUNDATION STL STEEL
FTG FOOTING STD STANDARD
FT FOOT SQ SQUARE
FLR FLOOR SPECS SPECIFICATIONS
FIN FINISH SPA SPACE
FV FIELD VERIFY SIM SIMILAR
FS FAR SIDE SSLT SHORT SLOTTED HOLE
EXT EXTERIOR SLBB SHORT LEG BACK-TO-BACK
EXP EXPANSION SHT SHEET
(E) or EXISTG EXISTING SHTHG SHEATHING
ERECT ERECTION SECT SECTION
EQ EQUAL SCHED SCHEDULE
EOR ENGINEER OF RECORD REV REVISION
EMBED EMBEDMENT RTN RETURN
ELEV ELEVATOR REQD REQUIRED
EL ELEVATION REINF REINFORCING
ELECT ELECTRICAL RXN REACTION
EF EACH FACE RAD or R RADIUS
EA EACH PRELIM PRELIMINARY
DWG DRAWING PREFAB PREFABRICATED
DBL DOUBLE PDF POWER DRIVEN FASTENER
DIM DIMENSION PSF POUNDS PER SQ.FT.
ø DIAMETER PSI POUNDS PER SQ. INCH
DIAG DIAGONAL # OR LB POUND
DTL DETAIL PLYWD PLYWOOD
° DEGREE PL PLATE
DEFL DEFLECTION PERP PERPENDICULAR
CW CURTAIN WALL d PENNY
CONTR CONTRACTOR PARL PARALLEL
CONT CONTINUOUS OF OUTSIDE FACE
CONST CONSTRUCTION OD OUTSIDE DIA.
CONN CONNECTION OPP OPPOSITE
CMU CONCRETE MASONRY UNIT OPNG OPENING
CONC CONCRETE OC ON CENTER
COMP COMPOSITE # or NO NUMBER
COL COLUMN NTS NOT TO SCALE
CFMF COLD-FORMED METAL FRAMING NIC NOT IN CONTRACT
CLR CLEAR NOM NOMINAL
CL CENTERLINE NS NEAR SIDE
CNTR CENTER MISC MISCELLANEOUS
CIP CAST-IN-PLACE MIN MINIMUM
BLDG BUILDING MTL METAL
BOT BOTTOM MECH MECHANICAL
BD BOARD MAX MAXIMUM
BLKG BLOCKING MAT MATERIAL
BTWN BETWEEN MAS MASONRY
BRG BEARING MFR MANUFACTURER
BM BEAM LONGIT LONGITUDINAL
@ AT LLV LONG LEG VERT
ARCH ARCHITECTURAL LLH LONG LEG HORIZ
APPROX APPROXIMATE LLBB LONG LEG BACK-TO-BACK
ANCH ANCHOR LDV LONG DIM VERT
ALUM ALUMINUM LDH LONG DIM HORIZ
ALT ALTERNATE LOC LOCATION
ADDED ADDITIONAL LT GA LIGHT GAGE
KPFF ABBREVIATIONS
DESIGN CRITERIA
D1) Codes:
International Building Code, 2015 American Concrete Institute 318-14 American Institute of Steel Construction Specification for Structural Steel Buildings 360-10 American Society of Civil Engineers / Structural Engineering Institute ASCE/SEI 7-10 American Wood Council National Design Specification 2015
D2) Lateral loads:
Wind: Ultimate design wind speed: 115 mph Risk category: I Wind exposure: B Interior pressure coefficient (+/-): GCpi= 0.55 Wall component wind pressure: ASCE/SEI 7-10
Seismic: Design Category: B Risk category: II Importance factor: Ie=1.00 Mapped spectral response acceleration:
Ss=0.064 S1=0.054
Site class: D Spectral response coefficients: Sds=0.068
Sd1=0.087 Basic seismic-force-resisting system: Light frame wood walls sheathed with wood structural panels rated for shear resistance
Design base shear: V=4.8 Response coefficient: Cs=0.0108 Response modification factors: R=6.5 Analysis procedure used: Equivalent Lateral Force Analysis
D3) Live loads:
Snow load:
Ground snow load: 30 psf Flat-roof snow load (minimum): Pf=24 psf Snow exposure factor: Ce=1.0 Thermal factor: Ct=1.0 Snow importance factor: Is=1.00 Snow drift load: ASCE/SEI 7-10 Roof load (minimum): 20 psf
D4) Net allowable soil bearing pressures: (To be field verified by Testing Agency.)
Footings: 1500 psf
D5) Concrete strengths - Minimum 28 day f 'c (145 pcf density unless noted otherwise)
Typical-unless noted otherwise: 4000 psi Footings: 3000 psi Curbs: 4500 psi Slabs on grade: 4500 psi
D6) Reinforcing steel shall be high strength new billet steel conforming to the following:
Deformed bars: ASTM A615, Gr. 60 (unless otherwise noted)
D7) Structural steel:
Pipe: ASTM A53, Gr. B
D8) Wood framing:
a) By Pre-Engineered Wood Building Supplier
SPECIAL INSPECTION REQUIREMENTS
SR1) The following types of work require special inspection based on section 1705 of the 2015 International Building Code. See Specification section 014500 for specific requirements. The owner will employ special inspectors who shall provide special inspections during:
a) Earth Work
b) Cast-in-place Concrete.
GENERAL NOTES
G1) Establish and verify all openings and inserts for mechanical, electrical, and plumbing with appropriate trade contractors. Opening sizes and locations shown for ducts, pipes, inserts, etc., when shown are for general information only and shall be verified prior to forming.
G2) Field verify all existing dimensions, member sizes, and elevations shown on the drawings. All discrepancies shall be immediately brought to the attention of the architect.
G3) Before submitting a proposal for this work, each bidder shall visit the premises and acquaint themselves fully with the existing conditions, temporary construction required, quantities and types of equipment, etc. The bid shall include all sums required to do the work within the existing conditions. Disruption of normal activities in the work area must be kept to a minimum.
G4) Shop drawings prepared by suppliers, subcontractors, etc. shall be reviewed and coordinated prior to submitting to the architect. Each shop drawing submitted shall be stamped, initialed, and dated as being reviewed by the construction manager/general contractor.
G5) Shop drawings prepared by the subcontractors, suppliers, etc. shall be reviewed by the architect for conformance with design concept only. Review by the architect shall not begin without the prior coordination and review by the construction manager/general contractor. Work shall not begin without the review by the architect.
G6) Details and notes on the structural drawings are intended to be typical for similar situations elsewhere. Verify all dimensions with the architectural drawings. Do not scale drawings; use dimensions provided only.
G7) Options are for the contractor's convenience. The contractor shall be responsible for all changes necessary if they choose an option and shall coordinate all details. The cost of additional design work necessitated by selection of an option shall be borne by the contractor.
G8) The cost of additional design work due to errors or omissions in construction shall be borne by the contractor.
G9) Any engineering design provided by…