Testing and Inspection of Fire Suppression Systems for USAG-Italy Vicenza and Poggio Renatico (FE)
Solicitation number
W912PF24Q0080
Issued by

About this file

This document appears to be a report from a fire alarm and fire extinguisher inspection conducted under Contract W912PF-15-C-0006 at Ederle Building 3 in the USAG-Italy Vicenza area.

The report details the results of various tests and inspections performed on the fire alarm system, including testing smoke/heat detectors, voltage levels, device connectivity, and functionality of the fire alarm and mass notification systems. It also lists the specific fire alarm equipment such as the fire alarm control panel, number of detectors and pull stations, and indicates the mass notification system is connected to the fire department. The report notes several deficiencies that require remediation, such as a missing smoke detector, malfunctioning heat detector, and broken strobe light, as well as issues with the mass notification system battery.

The report also documents the fire extinguisher inspection, including the serial numbers, locations, and service history (inspection, recharge) for the 6kg powder fire extinguishers located throughout the building.

This inspection and report appear to be related to the upcoming federal contract opportunity W912PF24Q0080 for "Testing and Inspection of Fire Suppression Systems for USAG-Italy Vicenza and Poggio Renatico (FE)".

View the file

Other files

File Type Posted
B08_24Q0080_AMD01_Released_20240617.pdf PDF
Poggio R-invent-BAAP_idraulica_fire suppression sys.xlsx XLSX spreadsheet
Poggio Renatico Site-inventario-elpro_elettrica_fire detection sys.xlsx XLSX spreadsheet
Longare-invent-BAAP_idraulica_fire suppression sys.xlsx XLSX spreadsheet
B08-SOL_W912PF24Q0080_Attachment2_SuitabilityKTR.pdf PDF
B08_SOL_W912PF24Q008_VI fire_RELEASED_20240528.pdf PDF
Longare Site-inventario_elettrica_fire detection sys.xlsx XLSX spreadsheet
Torri Site-inventario-elpro_elettrica_fire detection sys.xlsx XLSX spreadsheet
Lerino Site-inventario_elettrica_fire detection sys.xlsx XLSX spreadsheet
Del Din-invent_idraulica_fire suppression sys.xlsx XLSX spreadsheet
ASP7 Site-inventario_idraulica_fire suppression sys.xlsx XLSX spreadsheet
Ederle Site-inventario_elettrica_fire detection sys.xlsx XLSX spreadsheet
B08_SOL_W912PF24Q0080_ATTACHMENT 3_CERTIFICATION 52.222-56.pdf PDF
B08-SOL_W912PF24Q0080_Attachment1_Antimafia.pdf PDF
Ederle-invent_idraulica_fire suppression sys.xlsx XLSX spreadsheet
Del Din Site-inventario_elettrica_fire detection sys.xlsx XLSX spreadsheet
Villaggio-invent-BAAP_idraulica_fire suppression sys.xlsx XLSX spreadsheet
ASP7 Site-inventario_elettrica_fire detection sys.xlsx XLSX spreadsheet
Villaggio Site-inventario-elpro_elettrica_fire detection sys.xlsx XLSX spreadsheet
Torri-invent-BAAP_idraulica_fire suppression sys.xlsx XLSX spreadsheet
Lerino-invent-BAAP_idraulica_fire suppression sys.xlsx XLSX spreadsheet
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE ALARM

ACMEFIRE ALARM SYSTEMContract:W912PF-15-C-0006
Page:1 of 1
Date:21-Nov-16
Area: EderleBLDG: 3Name/lastname:Mario Rossi

ACTIVITY DESCRIPTION Result

1Test and clean the smoke/heat detectorPassNot Pass
2Test voltage level FACPPassNot Pass
3Test voltage level auxiliary external batteries of the FACPPassNot Pass
4Test all the devices connected to the Fire Alarm SystemPassNot Pass
5Test functional fire alarmPassNot Pass
6Test functional mass notificationPassNot Pass
7Test UPS of mass notificationPassNot Pass
8Fault test FACPPassNot Pass
9Test other devicesPassNot Pass
10Test the connection with Fire departmentPassNot Pass
Fire Alarm Panel: NOTIFIER AM 2000N
Number of detectors: 41
Number of pull station: 32
Mass Notification system: Yes
Connection with Fire Department: Yes
Description of the deficiencies: The smoke detector N. L01 M 23 (Model, Type) located in the room 96 is missing, the heat detector N. L01 M 29 (Model, Type) located in the room 105
not working properly need to be replace, the strobe N L01 M 27 (Model, Type) located in the room 1040 is broken need to be replace, the mass notification battery (Model, Type)
not working need to be replace

FIRE EXTINGUISHER

ACMEFIRE EXTINGUISHERContract:W912PF-15-C-0006TYPE OF SERVICE
Page:1 of 1
Date:21-Nov-16
Area: EderleBLDG: 3Name/lastname:Mario Rossi
TYPE OF FIRE EXTINGUISHERSERIAL NUMBERLOCATIONRevisioneCollaudoRicarica
1Estintore a polvere da 6KGSN 124260Piano terra, corridoio lato destro vicino Room 1220172019NO
2Estintore a polvere da 6KGSN 124261Piano terra, stanza elettrica Room 52YES2018NO
3Estintore a polvere da 6KGSN 124262Primo piano, Room 12 Bagno20182020YES

Note: fatto servizio di revisione per 1 estintore e una ricarica, tutti gli estintori risultano essere funzionanti ed in buone condizioni

TOT LIST

EDERLE

BLDG NumberSemesterIssue DescriptionLocationQTYItem
1Arilevatore di fumostanza 11- 2 piano2Notifire NFXI-SMT2
1ALuce di emergenzacorridoio 1 piano8Disano 615 safety
2APressostatostanza sprinkler1Tyco PS-10-2
2ABatteria FAPEntrata piano terra2XX Volt XX Amp