RCC 260-B4260-030 Project Drawings (Glenns) 2025-01-09.pdf
PDF 4 MB Posted
- Attached to
- Interior Renovations at Rappahannock Community College, Glenns and Warsaw Campuses, PC#260-B4260-030
- Solicitation number
- 85257
- Issued by
- Frederick County, Rockingham County, Virginia
About this file
This is a set of architectural, mechanical, fire suppression and electrical drawings prepared by Grimm + Parker Architects and 2RW Consultants for interior renovations at Rappahannock Community College's Glenns Campus in Virginia, issued as a bid set on January 9, 2025. The project involves renovating office suites with modifications to walls, ceilings, lighting, HVAC, fire suppression systems and electrical systems. Key work includes new partition walls, acoustical ceiling systems, LED lighting with occupancy sensors and controls, modifications to existing sprinkler heads and branch lines, and power/data infrastructure updates. The drawings indicate construction must maintain operation of existing building systems during renovation.
The drawings provide detailed specifications for all building systems and materials, including wall types, door/hardware schedules, lighting fixture schedules, and mechanical/electrical requirements. The project utilizes primarily existing building infrastructure with targeted modifications and upgrades. All new work must comply with Virginia Building Codes, NFPA standards, and ADA requirements as specified in the drawing notes. The drawings emphasize careful coordination between trades and phasing of work to minimize disruption to adjacent occupied spaces.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EARTH
GRAVEL
CONCRETE
CONCRETE MASONRY UNITS
SOLID CONCRETE
MASONRY UNITS
BRICK
WOOD-FINISHED
WOOD ROUGH
PLYWOOD
GYPSUM BOARD
ACOUSTIC TILE
STEEL - LARGE SCALE
ALL METALS - SMALL SCALE
GLASS - LARGE SCALE
BATT INSULATION
RIGID INSULATION
CERAMIC TILE
CARPET
Above finished floor AFF Acoustic ACST Acoustic Panel Ceiling APC Addendum ADD Alternate ALT Aluminum AL Angle L Approximate APPROX Architecture, ARCH architectural Asbestos ASB Asphalt ASPH Assistant ASST Association ASSN Automatic AUTO Average AVG Base plate BP Basement BSMT Beam BM Bearing BRG Bedroom BR Benchmark BM Board BD Boiler BLR Bottom BOT Brick BRK Building line BL Building BLDG Built-up-roof BUR Cabinet CAB Carpet CPT Catalog CAT Ceiling height CH Ceiling CLG Center CTR Centerline CL Ceramic Tile CT Ceramic CER Chalkboard CB Clear CLR Closet CLO Coated CTD Cold rolled CR Column COL Company CO Composition COMP Concrete Masonry Unit CMU Concrete CONC Construction joint CJ Construction CONSTR "Continue, Continuous" CONT Corridor CORR Countersink CSK Cubic CU Curve(d) CRV Dampproofing DP Degree DEG Department(al) DEPT Detail DET Diagonal DIAG Diameter DIA Dimension DIM Dishwasher DW Dispenser DISP Door DR Double DBL Double-hung DH Down DN Downspout DS Drain DR Drawing DWG Each EA East E Electric Water Cooler EWC "Electric, electrical" ELEC Elevation EL Elevator ELEV Engineer ENGR Entrance ENTR
Maximum MAX Mechanical MECH Membrane MEMB Men M Metal MET, MTL Mezzanine MEZZ Minimum MIN Mirror MIR Miscellaneous MISC Mounted MTD Mounting MTG Necessary NEC Noise-reduction NRC coefficient Nominal NOM Non Combustible NC, NONCOM North N Not in Contract NIC Not to scale NTS Not available NA Number NO Office OFF On center OC Opening OPNG Opposite OPP Outside diameter OD Overall OA Overhead OVHD Page P Painted PTD Pair PR Panel PNL Partition PTN Percent PCT Perforate(d) PERF Permanent PERM Perpendicular PERP Piece PC Plastic Laminate PLAM Plastic Laminate PLAS.LAM Plate PL Plumbing PLMB Plywood PLYWD Point PT Polyvinyl chloride PVC Precast PRCST Prefabricated PREFAB Preliminary PRELIM Preparation, prepare PREP Program PRGM Projection Screen PS Project PROJ Property PROP Public Address PA Quality control QC Quality QUAL Quantity QTY Quarry Tile QT Radius RAD Rain Leader RL Received RCVD Receptacle RCPT Receptionist RECPT Recess(ed) REC Refer, reference REF Refrigerate, refrigerator REFR Reinforce REINF Reinforced concrete RC Remove RMV Repair RPR Required REQD Revise, revision REV Right hand RH Road RD Roof Drain RD Roof RF Roofing RFG Room RM Rubber tile floor RTF
Rubber RBR Schedule SCHED Schematic SCHEM Section SECT Service SVCE "Sheet, sheeting" SHT Shower SH Siding SDG Similar SIM Slope SL Sound-transmission STC class South S Speaker SPKR Specification SPEC Sprinkler SPR Square SQ Stainless steel SS Standard STD Standpipe SP Steel STL Storage STOR Structural Glazed SGFT Facing Tile Structural, structure STRUCT Substitute SUBST Surface SURF Suspend(ed) SUSP Switch SW Symmetrical SYM System SYS Tackboard TB Tackstrip TS Telephone TEL Television TV Temporary TEMP Terrazzo TER Thick THK Through THRU Toilet T Tongue and groove T&G Top and bottom T&B Top chord TC Top of Masonry Parapet TMP Top of Bearing TOFB Top of Steel T.O.S.
Topping TOPG Total TOT Transformer XFMR Transom TR Transparent TRANS Tread TRD Threshold THRESH Typical TYP Underground UG Underwriters UL Laboratories Unfinished UNF Unit Ventilator UV Unless Otherwise Noted UON Urinal UR US Gypsum Company USG Verify in Field VIF Vertical VERT Vestibule VEST, V Vinyl Reducing Strip VRS Vinyl Composite Tile VCT Vinyl asbestos tile VAT Wardrobe WARD Water closet WC Waterproof WP Weight WT Welded WLD Welded Wire Mesh WWM With W/ Without W/O Women W Wood WD Wrought Iron WI
Equal EQ Equipment EQUIP Exhaust EXH Existing EXIST Existing to Remain ETR Expansion joint EXP JT Exposed EXP Exterior EXT Fabricate FAB Face of Stud F. OF S.
Fan Coil Unit FCU Fiberglass-reinforced FRP plastics Finish FIN Finished Floor FF Fire Extinguisher FE Fire Extinguisher & FEC Cabinet Fire Retardant Treated FRT Fireproof FPRF Fixture FXTR Flange FLG Flashing FL Floor FL Floor drain FD Flooring FLG Fluorescent FLUOR Footing FTG Foundation FDN Furnish(ed), furniture FURN Furring FURR Gage (gauge) GA Galvanize(d) GALV Galvanized Iron GALVI Glazed Wall Tile GWT Grab Bar GB Grade GR Gravel GVL Gypsum Wallboard GWB Gypsum GYP Handicapped HC Hardware HDW Heating ventilating and HVAC air conditioning Height HGT High Point HPT High Performance HP High Performance HPC Coating Hollow Metal HM Horizontal HORIZ Include(d), inclusive INCL Incorporated INC Information INFO Inside diameter ID Install(ed), installation INSTL Insulation INSUL Interior INT Janitor JAN Joint JT Joist J, JST Junction box JB Knock down KD Laboratory LAB Lavatory LAV Left Hand LH Left L Length LG Level LVL Light LT Machine MACH Maintenance MAINT Manager MGR Manual MNL Manufacturing MFG Markerboard MB Masonry opening MO Masonry MSNRY Master bedroom MBR Material MATL
B101a
SIM
SIM
A102 A103
DEPT.
ADD
GRID LINES
SECTIONS
VIEW NUMBER
SHEET NUMBER WHERE VIEW IS DRAWN
DETAIL NUMBER
SHEET NUMBER
WHERE VIEW IS
DRAWN
DETAILS IN PLAN/SECTION
ROOM NUMBER
DOOR NO. ON PLAN
H.M. FRAME NO.
ON PLAN
REVISION: TYPE =
A.S.I/P.R./C.C.D./ADD.
CASEWORK
(FURNISHING PLANS ONLY)
ALUM. FRAME/WINDOW
TYPE
WALL TYPEA3ROOM NAME
B101a
SHEET NUMBER WHERE VIEW IS TAKEN
SHEET NUMBER WHERE VIEW IS TAKEN
123456789101112131415161718
123456789101112131415161718
A
B
C
D
E
F
G
H
J
K
L
M
A
B
C
D
E
F
G
H
J
K
L
M w w w .g ri m m a n d p a rk e r.
c o m
E a s t
M a in
S tr e e t n d F lo o r
C h a rl o tt e s v ill e
V A
T e l:
-2
-5
DEB #
260-B4260-030
TS01
TI
TL
E S
H E
E T
RC
C
GL
EN
NS
C
AM
PU
S
IN
TE
RI
OR
R
EN
OV
AT
IO
N
5 C oll eg e D riv e, Gl en ns
, V irg ini a
JANUARY 9, 2025
BID SET
GP #22006.16
LIST OF DRAWINGS
TS01 TITLE SHEET
ARCHITECTURAL
A001 CODE STUDY - DIAGRAMS
A002 OVERALL FIRST FLOOR PLAN
A101 PARTIAL FIRST FLOOR PLAN
A102 PARTIAL FIRST FLOOR PLAN
A301 SCHEDULES & SIGNAGE
MECHANICAL
M000 LEGENDS, ABBREVIATIONS & GENERAL NOTES
MD101 PARTIAL FIRST FLOOR PLAN - DEMOLITION
M101 PARTIAL FIRST FLOOR PLAN - DUCTWORK
M501 DETAILS
M701 SCHEDULES & SPECIFICATIONS
FIRE SUPPRESSION
FX001 GENERAL NOTES, SYMBOLS & ABBREVIATIONS
FX002 SPECIFICATIONS
FX101 OVERALL FIRST FLOOR DEMOLITION PLAN
FX111 OVERALL FIRST FLOOR NEW WORK PLAN
ELECTRICAL
E000 LEGENDS, ABBREVIATIONS & GENERAL NOTES
ED101 PARTIAL FIRST FLOOR PLAN - DEMOLITION
E101 PARTIAL FIRST FLOOR PLAN - LIGHTING
E102 PARTIAL FIRST FLOOR PLAN - POWER AND SPECIAL SYSTEMS
E701 DETAILS, SCHEDULES & SPECIFICATIONS
SYMBOLS OF MATERIALS
ABBREVIATIONS
VIRGINIA COMMUNITY COLLEGE SYSTEM
300 Arboretum Place, Suite 200 Richmond, Virginia 23236
OWNER
ARCHITECT MEP ENGINEER
GRIMM + PARKER ARCHITECTS
123 East Main St, Second Floor Charlottesville, Virginia 22902
2RW CONSULTANTS
100 10th St. NE, Suite 202 Charlottesville, Virginia 22902
VICINITY MAP LOCATION MAP
ASBESTOS DISCLOSURE STATEMENT
LEAD DISCLOSURE STATEMENT
AN ASBESTOS INSPECTION WAS PERFORMED AND ACM WAS FOUND GENERALLY IN THE AREA INDICATED. THE ASBESTOS INSPECTION REPORT IS INCLUDED AS AN APPENDIX TO THE PROJECT SPECIFICATIONS. THE OWNER SHALL SUBMIT AN APPLICATION FOR PERMIT TO HAVE THE ASBESTOS-CONTAINING MATERIALS ABATED BY A LICENSED ASBESTOS CONTRACTOR UNDER A SEPARATE CONTRACT USING APPROVED PROCEDURES PRIOR TO ISSUING A NOTICE TO PROCEED TO THE GENERAL CONTRACTOR. ANY ACM THAT IS TO REMAIN AND THE NEW NON ASBESTOS-CONTAINING MATERIAL SHALL BE LABELED ACCORDINGLY. THE ASBESTOS ABATEMENT CONTRACTOR SHALL MARK UP THE AS-BUILT DRAWINGS RESULTING FROM ITS WORK TO INCLUDE AREAS WHERE ASBESTOS WAS ABATED, AREAS WHERE ASBESTOS WAS ENCAPSULATED, AND AREAS WHERE ACM EXIST BUT WERE LEFT IN PLACE. THE GENERAL CONTRACTOR SHALL REVIEW AND CERTIFY THE LOCATIONS WHERE ACM WAS ABATED, AREAS WHERE ACM WAS ENCAPSULATED AND AREAS WHERE ACM WAS LEFT IN PLACE AS MARKED ON THE AS-BUILT
DRAWINGS AND WILL PROVIDE THE DRAWINGS TO THE ARCHITECT.
AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING COMPONENTS HAS BEEN CONDUCTED AND CAN BE FOUND IN THE PROJECT SPECIFICATIONS. THIS REPORT IS PROVIDED FOR THE CONTRACTOR’S USE AND MAY NOT BE ALL INCLUSIVE. IT IS THE CONTRACTOR’S RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS THEY PERTAIN TO EMPLOYEE EXPOSURES TO LEAD. ALL LEAD AND LEAD-COATED BUILDING COMPONENTS SHALL BE RECYCLED
TO THE EXTENT POSSIBLE.
DRAWING KEY
DATE DESCRIPTION
EXISTING CLASSROOM BUILDING
HIGH PERFORMANCE BUILDNG ACT
IN ACCORD WITH THE HIGH PERFORMANCE BUILDINGS ACT, THE BUILDING IS EXEMPT FROM COMPLIANCE
BECAUSE THE RENOVATED BUILDING AREA IS NOT GREATER THAN 5,000 GROSS SQUARE FEET.
PROJECT NAME AND LOCATION
NAME RAPPAHANNOCK COMMUNITY COLLEGE - OFFICE RENOVATIONS
STREET ADDRESS 12745 COLLEGE DRIVE
COUNTY GLOUCESTER COUNTY
CITY, STATE GLENNS, VA
PROJECT DESCRIPTION: RENOVATION OF EXISTING COMMUNITY COLLEGE OFFICE SUITES
APPLICABLE CODES
BUILDING CODE 2021 VIRGINIA EXISTING BUILDING CODE (VEBC)
2021 VIRGINIA CONSTRUCTION CODE (VCC)
VIRGINIA CONSTRUCTION & PROFESSIONAL SERVICES MANUAL, 2024 (CPSM), REV 1
ISSUED 10/10/24
ACCESSIBILITY ADA90-TITLE II (2010) ASAD CHAPTER 2 FOR SCOPING, ICCA117.1-2017 CHAPTERS 1 AND 3
THROUGH 11 FOR TECHNICAL REQUIREMENTS
BUILDING USE AND CONSTRUCTION CLASSIFICATION
VCC
USE GROUP: B, BUSINESS 304.1
A-3, ASSEMBLY (AREA NOT IN SCOPE) 303.4
BUILDING AREA (PER VCC): 56,446 SF (92,000 SF ALLOWABLE)
PROPOSED CONSTRUCTION TYPE TYPE IIB (EXISTING)
ALLOWABLE BUILDING HEIGHT/STORIES: 75' (VCC TABLE 504.3), 3 STORIES (VCC TABLE 504.4)
ACTUAL BUILDING HEIGHT/STORIES: 20' MAXIMUM, 1 STORY
DESIGN OCCUPANT LOAD Total Occupants: 11 (See Occupant Load Calculation Schedule, A001)
BUILDING VOLUME: 1,103,160 CUBIC FEET (EXISTING)
APPLICABLE CODES AND TABULATIONS
RAPPAHANNOCK
COMMUNITY COLLEGE
E LEWIS B PULLER MEM HWY
COLLEGE DR
HWY 17
C O
LLE
G
E D
R
E LEWIS B PULLER
MEM HWY
HWY 17
RAPPAHANNOCK COMMUNITY COLLEGE
APPROPRIATION ACT NUMBER
D E S I G N T E A M
DEB PROJECT CODE 260-B4260-030
RCC GLENNS CAMPUS INTERIOR
RENOVATION
12745 College Drive, Glenns, Virginia
BID SET
JANUARY 9, 2025
N/A
January 9, 2025
EGRESS WIDTH
Egress width at doors and corridors: 0.15"/OCC. VCC 1005.3.2, Exception 1
PROJECT NAME AND LOCATION
NAME RAPPAHANNOCK COMMUNITY COLLEGE -
OFFICE RENOVATIONS
STREET ADDRESS
COUNTY
CITY, STATE
PROJECT DESCRIPTION: RENOVATION OF EXISTING COMMUNITY COLLEGE OFFICE SUITES
APPLICABLE CODES
Building Code:
BUILDING USE AND CONSTRUCTION CLASSIFICATIONS
VCC
Use Group:
Accessory Use Group:
B A-3
BUSINESS
ASSEMBLY (AREA NOT IN SCOPE)
304.1 303.4
Building Area: First Floor 56,446 SF
Total
Existing Type of Construction: TYPE IIB
Existing Fire Protection: NFPA 13
Allowable Building Height: 75' (VCC TABLE 504.3), 4 Stories (VCC TABLE 504.4)
Actual Building Height: 20' MAXIMUM
NOTES:
MAXIMUM DEAD END DISTANCES
VCC
REMOTENESS OF EXITS
VCC 1007.1.1 Exception 2 - 1/4 the Length of Maximum Room Diagonal (Credit for Sprinklered Building)
NUMBER OF REMOTE EXITS REQUIRED
VCC
1 Exit (Table 1006.2.1) 2 Exits (1006.2.1) 3 Exits (1006.2.1.1) 4 Exits (1006.2.1.1)
FIRE RATING REQUIREMENTS- STRUCTURAL ELEMENTS/ EGRESS COMPONENTS
Rating Required VCC
EMERGENCY LIGHTING REQUIREMENTS
Per VCC 1008: ALL MEANS OF EGRESS
MINIMUM CORRIDOR WIDTH REQUIREMENTS
Width VCC
EXIT CORRIDOR 1020.3 (Non-classroom)
44 IN., CLR. STAIR WIDTH 1011.2
TRAVEL DISTANCE TO EXITS VCC
Maximum Length of Travel in Fully Sprinklered Building (Table 1017.2)
Maximum Length Common Path of Travel in Fully Sprinklered Building
(Table 1006.2.1)
Spaces with One Means of Egress, Maximum Travel Distance to an Exit Access Door
(Table 1006.2.1)
INTERIOR FINISH REQUIREMENTS: VCC TABLE 803.13
OCCUPANCY LOADS AND EGRESS REQUIREMENTS
Location Calculated Area in Sq. Ft.
Sq. Ft.
per
Person Occupa nt Load
Egress Width
Required
Egress Width
Provided
Number Exits
Required
Number Exits
Provided
OFFICE SUITE #1 552 150 GSF 4 32" 34" 1 1
OFFICE SUITE #2 1105 7 32" 34" 1 1
FIRE PROTECTION SYSTEM REQUIREMENTS
System VCC
Automatic Sprinklers YES 903.2.11.6
Fire Alarm System YES 907.2.2 Smoke Detection System NO --
Partial Smoke Detection YES --
Location DOORS WITH HOLD
OPEN DEVICES
1. Mixed use separation walls must have 45 minute rated opening protectives.
2. All fire partitions must comply with Section 708.4 of the VCC. They must extend from the top of the fire resistance rated floor/ ceiling assembly below to the underside of the floor or roof slab or deck above and must be securely attached thereto.
3. Refer to 1/8" plans & coord. w/ MEP drawings for chases thru floor. Enclosure walls around these floor openings must be (1) hour rated & must extend from floor tight to deck above - pack w/ safing insulation. Rating to be as follows: 6" CMU- U.L. #U906 Gyp. Bd. - Gypsum Assoc. assembly WP1110
4. Refer to the Door Schedule for doors with closers required.
5. All rated walls and partitions must be permanently identified with signs or stenciling as follows: SYMBOL KEY
ALLOWABLE # OCC.
REQ'D WIDTH
ACTUAL # OCC.
ACTUAL WIDTH
2 HOUR RATING
1 HOUR RATING
By Room Rooms Less Than 51 Occupants Rooms with 51 - 500 Occupants Rooms with 501 - 1000 Occupants Rooms with More than 1000 Occupants
VCC
2 Exits (Table 1006.3.2) 3 Exits (Table 1006.3.2) 4 Exits (Table 1006.3.2)
By Story 1 - 500 Occupants 501 - 1000 Occupants More than 1000 Occupants
33"
32" 16590
a. Identification markings must be located in accessible concealed floor, floor-ceiling and attic spaces.
b. Identification markings must be located within 15'-0" of the end of each wall and at intervals not exceeding 30'-0" measured horizontally along the wall or partiion.
c. Lettering must not be less than 3" in height with a minimum 3/8" stroke in contrasting color incorporating the following wording: "FIRE AND/OR SMOKE BARRIER - PROTECT ALL OPENINGS".
CODE REVIEW
44 IN. / 72 IN.,
50 FT. (1020.4) Exception 2
100'
100'
300'
12745 COLLEGE DRIVE, GLENNS, VA 23149
GLOUCESTER COUNTY
GLENNS, VA
2021 VIRGINIA CONSTRUCTION CODE (VCC)
2021 VIRGINIA EXISTING BUILDING CODE (LEVEL 2 ALTERATION) (VEBC)
VIRGINIA CONSTRUCTION & PROFESSIONAL SERVICES MANUAL, 2024
(CPSM), REV 1 ISSUED 10/10/24
ADA90-TITLE II (2010) ASAD CHAPTER 2 FOR SCOPING, ICCA117.1-2017
CHAPTERS 1 AND 3 THROUGH 11 FOR TECHNICAL REQUIREMENTS
56,446 SF
150 GSF
CPSM
4.1.2.1 #2b (Classroom)
CPSM
4.1.2.1 #3
*No change in Occupancy Classification or Occupancy Load
Allowable Building Area: 92,000 SF 506.2 (B, S1, Type IIB)
Primary Structural Frame 0 TABLE 601 Exterior Bearing Walls 0 TABLE 601, SECTION 704.10, TABLE 705.5 Exterior Non-Bearing Walls 0 TABLE 705.5 Interior Bearing Walls 0 TABLE 601 Floor / Ceiling Assemblies 0 TABLE 601 Roof / Ceiling Assemblies 0 TABLE 601 Columns 0 TABLE 601 Beams 0 TABLE 601 Egress Corridors 0 TABLE 1020.2 Corridor Doors 0 716.1(2) Smoke Barrier 1 709.3 Smoke Partitions 0 710.3 Smoke Barrier Doors 20 MIN. 710.5.2, 716.2.2.1 Mixed Use Separation (B + A) 1 508, TABLE 508.4
Accessibility:
MIXED SEPARATED:
OCCUPANCY LEGEND
BUSINESS AREAS
AREA OF WORK
AREA OF WORK
MAX COMMON PATH OF
TRAVEL
146' - 8"
MAX COMMON PATH OF
TRAVEL
99' - 5"
(300' MAX. ALLOWABLE)
(300' MAX.
ALLOWABLE)
1105 SF
OFFICE SUITE #2
552 SF
OFFICE SUITE #1
1105 SF
OFFICE SUITE #2
MAX COMMON PATH OF
TRAVEL
49' - 2"
EXISTING OFFCE
(NOT IN PROJECT SCOPE)
EXISTING OFFCE
(NOT IN PROJECT SCOPE)
EXISTING OFFCE
(NOT IN PROJECT SCOPE)
OFFICE
105D
OPEN OFFICE
STORAGE
105F
OFFICE
105E
OFFICE
105G
EXISTING OFFCE
(NOT IN PROJECT SCOPE)
EXISTING OPEN OFFCE
(NOT IN PROJECT SCOPE)
MAX COMMON PATH OF
TRAVEL
32' - 4"
552 SF
OFFICE SUITE #1
OFFICE
119C
OFFICE
119B
232 SF
EXISTING
OFFICE
SUITE
EXISTING OFFCE
(NOT IN PROJECT
SCOPE)
EXISTING OFFCE
(NOT IN PROJECT
SCOPE)
EXISTING OFFICE CONFIGURATION
NOTE THERE IS NO CHANGE TO
OCCUPANCY COUNT WITH NEW
CONSTRUCTION
EXISTING OFFICE CUBICLE CONFIGURATION
NOTE THERE IS NO OCCUPANCY COUNT
CHANGE WITH THE NEW CONSTRUCTION
EXISTING OFFCE
(NOT IN PROJECT
SCOPE)
EXISTING OFFCE
(NOT IN PROJECT
SCOPE)
EXISTING OFFCE
(NOT IN PROJECT
SCOPE)
662 SF
EXISTING
OFFICE
SUITE
123456789101112131415161718
123456789101112131415161718
A
B
C
D
E
F
G
H
J
K
L
M
A
B
C
D
E
F
G
H
J
K
L
M w w w .g ri m m a n d p a rk e r.
c o m
E a s t
M a in
S tr e e t n d F lo o r
C h a rl o tt e s v ill e
V A l:
-2
-5
DEB #
260-B4260-030
A001
C O
D E
S
TU
D Y
D
IA
G
R A
M S
RC
C
GL
EN
NS
C
AM
PU
S
IN
TE
RI
OR
R
EN
OV
AT
IO
N
5 C oll eg e D riv e, Gl en ns
, V irg ini a
JANUARY 9, 2025
BID SET
GP #22006.16
1/16" = 1'-0"E18
CODE STUDY PLAN - FIRST FLOOR
1/4" = 1'-0"A12
ENLARGED CODE STUDY PLAN - OFFICE SUITE #2
1/4" = 1'-0"B18
ENLARGED CODE STUDY PLAN - OFFICE SUITE #1
EXISTING PLAN AT OFFICE SUITE #1
1/8" = 1'-0"
EXISTING PLAN AT OFFICE SUITE #2
1/8" = 1'-0"
AREA NOT IN PROJECT SCOPE -
BUSINESS USE
DATE DESCRIPTION
OCCUPANT LOAD CALCULATIONS (AREAS)
AREA NAME
AREA
(SF)
AREA PER
OCCUPANT (SF)
GROSS OR
NET
OCCUPANCY
LOAD
EGRESS WIDTH
REQ'D
BUSINESS AREAS
OFFICE SUITE #1 552 SF 150 SF GROSS 4 0.7
OFFICE SUITE #2 1105 SF 150 SF GROSS 7 1.5
AREA NOT IN PROJECT SCOPE -
ASSEMBLY USE
N
GENERAL NOTE APPLICABLE TO ALL DRAWINGS - ITEMS AND CONDITIONS DETAILED, NOTED
OR OTHERWISE IDENTIFIED ON ONE OF THE SECTIONS OR DETAILS ARE APPLICABLE AND
BINDING TO ALL OTHER SECTIONS AND DETAILS FOR IDENTICAL OR SIMILAR CONDITIONS.
1. ALL CONSTRUCTION AND WORK REPRESENTED IN THE COMPLETE SET OF DOCUMENTS IS
ASSUMED TO BE NEW AND FURNISHED AND INSTALLED BY THE CONTRACTOR UNLESS
OTHERWISE NOTED.
2. THE DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY AND WHAT IS REQUIRED BY
ONE IS REQUIRED BY ALL. NO DRAWING SHALL HAVE PRECEDENCE ONE OVER THE OTHER,
NOR SHALL DRAWINGS OR SPECIFICATIONS HAVE PRECEDENCE ONE OVER THE OTHER. IN
THE EVENT OF A CONFLICT IN THE DOCUMENTS, THE CONTRACTOR SHALL SEEK THE
INTERPRETATION OF THE ARCHITECT. THE CONTRACTOR SHALL NOT PROCEED WITH
WORK UNTIL SUCH INTERPRETATION IS OBTAINED. IF THE CONTRACTOR PROCEEDS
WITHOUT CLARIFICATION, THE CONTRACTOR SHALL BE RESPONSIBLE TO REMOVE AND
REPLACE ANY WORK NOT CONFORMANT TO THE ARCHITECT'S DIRECTION WITHOUT
ADDITIONAL COST TO THE OWNER.
3. IF A CONFLICT EXISTS BETWEEN DRAWINGS OF DIFFERENT SCALES, CONSULT THE
ARCHITECT FOR CLARIFICATION.
4. IN THE ABSENCE OF A WRITTEN DIMENSION, OR IN CASE OF DOUBT AS TO THE PROPER
MEASUREMENT, CONSULT THE ARCHITECT FOR CLARIFICATION.
5. IF AN AREA OR SPACE IS SHOWN, BUT IS NOT CLEARLY DEFINED OR INDICATED BY NOTES, PROVIDE THE SAME MATERIALS AND FINISHES AS SCHEDULED OR DETAILED FOR AREAS
OF SIMILAR USE ELSEWHERE IN THE BUILDING,
6. SECTIONS INDICATED ARE INTENDED TO SHOW THE SPECIFIC CONSTRUCTION WHERE
REFERENCED AS WELL AS ESTABLISH THE GENERAL CONSTRUCTION DETAILS FOR
SECTIONS THROUGHOUT THE PROJECT WHICH DO NOT HAVE SPECIFIC SECTIONS DRAWN.
THE MOST SIMILAR SECTIONS TO BE ADAPTED TO ANY SECTIONS NOT DETAILED. ANY
SPECIFIC QUESTIONS CONCERNING CONSTRUCTION NOT ADEQUATELY COVERED BY THE
ABOVE SHOULD BE DIRECTED TO THE ARCHITECT DURING THE BIDDING.
7. TYPICAL DETAILS THROUGHOUT THE DRAWING SET TO APPLY FOR ALL APPLICABLE
CONDITIONS EVEN IF NOT SPECIFICALLY SHOWN OR REFERENCED.
8. AT ALL OUTSIDE CORNERS OF INTERIOR CMU WALLS, COLUMN ENCLOSURES, PIPE CHASES
OR OTHER WALL PROJECTIONS, PROVIDE MASONRY UNITS WITH BULLNOSED (ROUNDED)
EDGES WITH 1" RADIUS, UNLESS OTHERWISE NOTED OR WHERE SCHEDULED TO RECEIVE
CERAMIC TILE. WHERE MASONRY CORNERS ALIGN WITH BULKHEADS, TRANSITION FROM
BULLNOSE CORNER UNITS TO SQUARE CORNER UNITS.
9. UNLESS SPECIFICALLY NOTED OTHERWISE, ENCLOSE ALL VERTICAL MECHANICAL PIPES,
RAIN LEADERS, ETC. WITH 4" CMU OR GYPSUM BOARD TO MATCH SURROUNDING FINISHES.
10. INCLUDE PROJECTIONS, BEAM ENCLOSURES, RECESSES, BULKHEADS, PILASTERS AND
SIMILAR ENCLOSURES AS PART OF WALL AND CEILING FINISHES AS SCHEDULED.
11. ALL APPURTENANCES BUILT INTO OR THROUGH WALLS, INCLUDING DOORS, DUCTS,
WINDOWS, LOUVERS, GRILLES, MECHANICAL WORK, ETC. TO FIT TIGHT AND BE
THOROUGHLY SEALED AROUND PERIMETERS. WORK AT EXTERIOR WALLS TO BE FLASHED
OR OTHERWISE WATERPROOF SEALED.
12. FIELD CHECK ROUGH AND/OR FINISHED DIMENSIONS FOR ACCURATE FITTING OF
CABINETS, COUNTERS, LOCKERS, DOORS, WINDOWS, FIXTURES, SHELVING, GATES AND
OTHER INSTALLATIONS PRIOR TO SHOP OR FACTORY FABRICATION. PROVIDE FILLER
STRIPS, SCRIBE STRIPS, BASES, CLOSURE FINISHES AND TRIM FOR A COMPLETE
INSTALLATION.
13. PROVIDE APPROPRIATE TRANSITION STRIPS AT CHANGES IN FLOOR ELEVATIONS.
14. EACH CONTRACTOR MUST REFER TO ALL DRAWINGS AND BE RESPONSIBLE FOR WORK
PERTAINING TO THEIR PARTICULAR TRADE. ALL CONTRACTORS MUST COORDINATE THE
WORK OF ALL TRADES AND FIELD CHECK AGAINST ANY CONFLICTS BETWEEN DRAWINGS.
REPORT CONFLICTS TO THE ARCHITECT FOR CLARIFICATION.
15. ACCESS PANELS, LOUVER OPENINGS, VENTILATORS, GRILLES, VALVE CABINETS, FIRE
DAMPERS OR OTHER APPURTENANCES AFFECTING WALLS, CEILINGS OR FLOORS ARE
SHOWN THROUGHOUT THE DRAWINGS. PROVIDE NECESSARY LINTELS, SUPPORT AND
ANCHORAGE. SEE STRUCTURAL NOTES FOR LINTEL REQUIREMENTS.
16. REFER TO MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR LOCATIONS OF
CONCRETE PADS TO BE PROVIDED BELOW OR AROUND EQUIPMENT.
17. INSTALL ELECTRIC SWITCHES, OUTLETS, THERMOSTATS, CONTROLS, CLOCKS, SPEAKERS,
FLAGPOLE HOLDERS AND OTHER WALL-MOUNTED ACCESSORIES IN LOCATIONS WHICH
ARE UNOBSTRUCTED BY CABINETS, COUNTERS, RACKS, DISPLAY BOARDS, FIXTURES,
SHELVING OR OTHER FURNISHINGS OR EQUIPMENT DESIGNATED FOR SPACES SHOWN ON
DRAWINGS. THESE DEVICES MAY BE SHOWN ON THE ARCHITECTURAL DRAWINGS TO
ALERT OTHER SUB-CONTRACTORS OF THEIR PRESENCE. COORDINATE INSTALLATION
WITH THE ELECTRICAL DRAWINGS. ADVISE THE ARCHITECT OF CONFLICTS IN LOCATION OR
TYPES OF DEVICES SHOWN PRIOR TO INSTALLATION. DO NOT INSTALL WALL-MOUNTED
ITEMS ON, THROUGH OR INTO ANY EQUIPMENT UNLESS INDICATED.
18. MOUNT ELECTRIC SWITCHES, THERMOSTATS AND OTHER ELECTRONIC CONTROLS
LOCATED IN THE SAME VICINITY AT THE SAME HEIGHT ABOVE FINISHED FLOOR IN A
UNIFORM, ORDERLY FASHION UNLESS NOTED OTHERWISE.
19. FOR THE PURPOSES OF BIDDING (UNLESS OTHERWISE NOTED), ALL SYMBOLS (LABELED /
TAGGED OR UNLABELED/UNTAGGED) WHICH ARE LOCATED ON THE
FURNISHING/EQUIPMENT PLANS TO BE CONSIDERED AS IN CONTRACT WORK TO BE
PROVIDED BY THE CONTRACTOR. ALL SYMBOLS LOCATED ON THE PLANS DENOTE EITHER
FURNITURE, EQUIPMENT, CASEWORK OR MILLWORK. WHERE A SYMBOL IS LOCATED ON
THE PLANS BUT IS NOT LABELED OR TAGGED TO A SCHEDULE, THE CONTRACTOR MUST
SEEK CLARIFICATION FROM THE OWNER OR ARCHITECT BEFORE PROCEEDING. FOR
PURPOSES OF BIDDING ONLY, IF CLARIFICATION CANNOT BE OBTAINED FROM THE OWNER
OR ARCHITECT THROUGH ADDENDUM PRIOR TO THE BID DATE, THE CONTRACTOR MUST
NEVERTHELESS INCLUDE THE ITEM IN QUESTION IN THEIR BID, CONSIDERING IT THE SAME
AS THE TAGGED SYMBOL MOST NEARLY RESEMBLING THE UNTAGGED SYMBOL BASED ON
ITS SHAPE, SIZE, LINEWEIGHT(S), LOCATION, AND SCHEDULED USAGE IN SPACES OF
SIMILAR FUNCTION. THE CONTRACTOR MUST OBTAIN CLARIFICATION FROM THE
ARCHITECT PRIOR TO PROCEEDING WITH SHOP DRAWINGS.
GENERAL NOTES
KEY PLAN
AREA A
AREA B
OFFICE
105E
OPEN OFFICE
OFFICE
105D
STORAGE
105F
OFFICE
119C
OFFICE
119B
F11
A002 A101
F10
A002 A102
OFFICE
105G
AREA NOT INCLUDED IN SCOPE OF WORK
RATED WALLS OUTSIDE OF PROJECT SCOPE
123456789101112131415161718
123456789101112131415161718
A
B
C
D
E
F
G
H
J
K
L
M
A
B
C
D
E
F
G
H
J
K
L
M w w w .g ri m m a n d p a rk e r.
c o m
E a s t
M a in
S tr e e t n d F lo o r
C h a rl o tt e s v ill e
V A l:
-2
-5
DEB #
260-B4260-030
A002
O V
E R
A
LL
F
IR
S T
FL
O
O R
P
LA
N
RC
C
GL
EN
NS
C
AM
PU
S
IN
TE
RI
OR
R
EN
OV
AT
IO
N
5 C oll eg e D riv e, Gl en ns
, V irg ini a
JANUARY 9, 2025
BID SET
GP #22006.16
1/16" = 1'-0"A002
B16 OVERALL FIRST FLOOR PLAN
0 8' 16'4'
DATE DESCRIPTION
1. REFER TO SHEET A301 FOR WALL TYPES AS REFERENCED ON PLANS WITH THE DIAMOND
SYMBOL.
2. TYPICAL GYPSUM BOARD / STUD WALL PARTITION TO BE TYPE K1 UNLESS INDICATED
OTHERWISE BY WALL TYPE SYMBOLS, WALL SECTIONS OR OTHER DETAILS.
3. UNLESS NOTED OTHERWISE, WALLS MUST EXTEND TO THE ROOF OR FLOOR DECK
ABOVE AND BE SEALED IN ACCORDANCE WITH THE WALL TERMINATION DETAILS.
4. DIMENSIONS ON PLANS ARE FROM FACE OF MASONRY TO FACE OF MASONRY, FACE OF
MASONRY TO FACE OF GYPSUM BOARD OR FACE OF GYPSUM BOARD TO FACE OF
GYPSUM BOARD.
5. COLUMN GRID LINES ARE FOR REFERENCE ONLY, REFER TO STRUCTURAL DRAWINGS
FOR COLUMN LOCATIONS.
6. FEC - INDICATES A FIRE EXTINGUISHER WITH A RECESSED CABINET. FE - INDICATES A
FIRE EXTINGUISHER WITH A WALL MOUNTING BRACKET.
7. UNLESS SPECIFICALLY INDICATED OTHERWISE, THE SAME WALL TYPE NEXT TO A DOOR
OR OPENING TO CONTINUE OVER THE DOOR OR OPENING.
8. PLAN LOCATION OF DOORS AND FRAMES RELATIVE TO THE PLANE OF THE WALL IS
DIAGRAMMATIC ONLY. REFER TO THE REFERENCED JAMB AND HEAD CONDITION DETAILS
TO DETERMINE ACTUAL PLACEMENT OF DOOR AND FRAME.
9. SIGNAGE N.I.C. PROVIDED BY OWNER.
GENERAL PLAN NOTES2
KL
M
OFFICE
119B
OFFICE
119C
10' - 6"
V.I.F.
11' - 2 1/4"
K1
119C
ROOM NOT IN SCOPE
(ETR)
FURNITURE N.I.C.
KEY PLAN
AREA A
AREA B
KL
M
ROOM NOT IN SCOPE
ROOM NOT IN SCOPE
REMOVE PORTION OF WALL FOR
NEW OPENING. SEE NEW WORK
PLAN FOR SIZE OF OPENING
CENTER FOR BUSINESS AND
WORKER DEVELOPMENT
OFFICE
119B
1' - 1"
KL
M
OFFICE
119C
OFFICE
119B
REPLACE CEILING TILES AND GRID AS NEEDED
1. ALL WORK SHOWN IS EXISTING TO REMAIN UNLESS NOTED OR INDICATED AS DASHED
LINES TO BE REMOVED. THE EXTENT OF DEMOLITION WORK SHALL INCLUDE ALL
INCIDENTAL DEMOLITION WORK NECESSARY TO PROPERLY PROVIDE ALL NEW WORK
SHOWN AND SPECIFIED, TO INCLUDE MECHANICAL, ELECTRICAL, & PLUMBING ITEMS.
2. DEMOLITION WORK SHOWN IS BASED ON EXISTING DRAWINGS AND INSPECTIONS. THE
CONTRACTOR SHALL VISUALLY INSPECT ALL EXISTING CONDITIONS, AND IS RESPONSIBLE
FOR PERFORMING THE INDICATED DEMOLITION WORK EVEN IF ACTUAL CONDITIONS
DIFFER FROM THESE SHOWN ON THE DRAWINGS.
3. DEMOLITION CONTRACTOR SHALL COORDINATE WITH NEW WORK SECTIONS FOR
ADDITIONAL INFORMATION RELATED TO EXTENT OF DEMOLITION.
4. REFER TO ALL OTHER DRAWINGS IN THIS SET FOR INCIDENTAL DEMOLITION WORK NOT
NOTED ON THE DEMOLITION PLANS.
5. THE OWNER HAS FIRST RIGHT OF REFUSAL OF ALL SALVAGE ITEMS. THE CONTRACTOR
SHALL PROPERLY DISPOSE OF ALL CONSTRUCTION DEBRIS. DO NOT STOCKPILE DEBRIS
ON SITE.
6. ITEMS TO BE DEMOLISHED SHALL BE REMOVED COMPLETELY INCLUDING ALL ANCHORS,
HANGERS, FASTENERS, ADHESIVES, SEALANTS, PIPES, CONDUITS, DUCTS, ETC. UNLESS
OTHERWISE INDICATED TO BE ABANDONED IN PLACE, OR WHERE SUCH PIPES, CONDUITS,
DUCTS OR WIRING ARE TO REMAIN FOR CONNECTION TO NEW EQUIPMENT TO BE
INSTALLED IN THE SAME LOCATION (SEE MEP DRAWINGS FOR ADDITIONAL INFORMATION).
FINISHES TO REMAIN SHALL BE PATCHED, PAINTED, AND REPAIRED TO MATCH EXISITNG
ADJACENT FINISHES.
7. CONC. SLABS TO REMAIN SHALL BE PATCHED, SCRAPED, LEVELED, AND CLEANED TO
PROVIDE SURFACE SUITABLE FOR NEW FINISHES.
8. PARTITIONS SHOWN TO BE REMOVED SHALL BE CONFIRMED BY THE CONTRACTOR AS TO
TYPE OF PARTITION AND EXACT LOCATION. COMPLETELY REMOVE PARTITIONS FROM
FLOOR TO STRUCTURE ABOVE INCLUDING BASE, ALL FASTENERS, GROUTS, SEAL ANTS,
ETC., UNLESS NOTED OTHERWISE.
9. REMOVE, PATCH AND REPAIR PORTIONS OF WALL PARTITIONS WHICH CONFLICT WITH NEW
WORK TO BE INSTALLED, EVEN IF NOT SPECIFICALLY NOTED TO BE DEMOLISHED ON
PLANS.
10. ALL EXISTING STRUCTURE SHALL REMAIN, UNLESS NOTED OTHERWISE.
11. TEMPORARILY SUPPORT ALL BEAMS, LINTELS, PORTIONS OF WALLS ETC., TO BE
DISTURBED BY DEMOLITION WORK, UNTIL THEY ARE RE-SUPPORTED BY NEW WORK.
12. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF EXISTING
BUILDING ELEMENTS TO REMAIN THROUGHOUT SEQUENCE OF WORK. ANY DAMAGE TO
EXISTING BUILDING CONDITIONS SHOWN TO REMAIN SHALL BE RESTORED TO NEW WORK
CONDITION AT NO ADDITIONAL COST TO THE OWNER.
13. WHERE FINISHES ARE INDICATED TO BE REMOVED, REMOVAL SHALL INCLUDE ANY GROUT,
ADHESIVES, FASTENERS, AND ALL OTHER ITEMS USED TO ATTACH THE FINISHES TO THE
SURFACES THAT THEY COVER.
14. ANY FLOOR AREAS DAMAGED BY THE DEMOLITION CONTRACTOR SHALL BE PATCHED TO
MATCH EXISTING.
15. WHERE CEILINGS ARE TO BE REMOVED, REMOVE ALL CEILINGS SYSTEMS COMPLETE
INCLUDING GRID, TRIM HANGER, CLIPS, ETC. REUSE SALVAGED COMPONENTS WHERE
INDICATED. WHERE NEW CEILINGS ARE SPECIFIED, NO DOUBLE CEILINGS PERMITTED.
REMOVE ALL ORIGINAL CONCEALED CEILINGS WHERE ENCOUNTERED.
16. ALL EXISTING SURFACES TO REMAIN SHALL BE PROTECTED, PATCHED IF DAMAGED AND
CLEANED PRIOR TO APPLICATION OF FINISHES.
17. CONTRACTOR TO PROTECT ALL EQUIPMENT AND OTHER ELEMENTS IN AREA OF NEW OR
DEMOLITION WORK.
18. REMOVE MECHANICAL, ELECTRICAL AND PLUMBING ITEMS AS NOTED ON MECHANICAL,
ELECTRICAL AND PLUMBING PLANS. COORDINATE WITH CIVIL, STRUCTURAL, MECHANICAL,
ELECTRICAL, AND PLUMBING, FOR ADDITIONAL DEMOLITION NOTES. REMOVAL WORK IS
INTENDED TO INCLUDE ALL ASSOCIATED ITEMS SUCH AS ELECTRICAL OUTLETS,
SWITCHES, CONDUITS, CONTROLS, PIPING, MOUNTING BLOCKS, ETC., AS NOTED. THE
CONTRACTOR SHALL REFER TO ALL CIVIL, STRUCTURAL, MECHANICAL, ELECTRICAL AND
PLUMBING DRAWINGS AND SPECIFICATIONS FOR PROCEDURES CONCERNING RELATED
TRADES IN AREAS WHICH REQUIRE DEMOLITION. REPAIR AND PATCH ANY AREAS
DAMAGED DURING REMOVAL WORK.
GENERAL DEMOLITION NOTES
K
L
M
REMOVE LIGHTING TO BE REUSED AT NEW LOCATION.
REMOVE LIGHT FIXTURES, TYP.
REMOVE AND REINSTALL CEILING
PANELS IN NEW GRID. REMOVE
CEILING GRID AND ASSOC.
SUPPORT MEMBERS.
2X2 CEILING SYSTEM. SEE
FINISH SCHEDULE
2X4 CEILING SYSTEM. SEE
FINISH SCHEDULE
GYPSUM BOARD CEILING
NOTE: SPOT ELEVATION SUFFIX "C.H." INDICATES FLAT CEILING HEIGHT ABOVE
FINISH FLOOR. SUFFIX "L.P." AND "H.P." INDICATE LOW POINT AND HIGH POINT OF
SLOPED CEILING. WHERE ADJACENT, TRANSITION BETWEEN FLAT AND SLOPED
CEILINGS SHALL UTILIZE APPROVED PRE-FINISHED ALUMINUM TRANSITION STRIP.
REFER TO SPECIFICATIONS.
RCP LEGEND
RECESSED DOWNLIGHT - SEE ELEC
1'X4' RECESSED LIGHT FIXTURE - SEE ELEC
2'X4' RECESSED LIGHT FIXTURE - SEE ELEC
1'X4' LIGHT FIXTURE - SEE ELEC
SUPPLY DIFFUSER, REGISTER, OR GRILL
- SEE MECH
RETURN DIFFUSER, REGISTER, OR GRILL
- SEE MECH
EXISTING WALLNEW WALL
WALL LEGEND
CARPET - NEW
CARPET - DEMO
MATERIALS LEGEND
EXISTING CEILING
SYSTEM - DEMO
123456789101112131415161718
123456789101112131415161718
A
B
C
D
E
F
G
H
J
K
L
M
A
B
C
D
E
F
G
H
J
K
L
M w w w .g ri m m a n d p a rk e r.
c o m
E a s t
M a in
S tr e e t n d F lo o r
C h a rl o tt e s v ill e
V A l:
-2
-5
DEB #
260-B4260-030
A101
P A
R
TI
A L
FI
R
S T
FL
O
O R
P
LA
N
RC
C
GL
EN
NS
C
AM
PU
S
IN
TE
RI
OR
R
EN
OV
AT
IO
N
5 C oll eg e D riv e, Gl en ns
, V irg ini a
JANUARY 9, 2025
BID SET
GP #22006.16
0 4' 8'2'
1/4" = 1'-0"A101A002
F11 PARTIAL FIRST FLOOR PLAN - AREA A NEW CONSTRUCTION
1/4" = 1'-0"A101
B11 PARTIAL FIRST FLOOR PLAN - AREA A DEMO
1/4" = 1'-0"A101
F17 PARTIAL REFLECTED CEILING PLAN - AREA A NEW CONSTRUCTION
1/4" = 1'-0"A101
B17 PARTIAL REFLECTED CEILING PLAN - AREA A DEMO DATE DESCRIPTION
B
C
D
E
OFFICE
105D
OFFICE
105E
OPEN OFFICE
STORAGE
105F
105D
105E
105F
105G
K1
K1
K1
ROOM NOT IN
SCOPE
(ETR)
ROOM NOT IN
SCOPE
(ETR)
ROOM NOT IN
SCOPE
(ETR)
/2
9'
10' - 4" 6' - 3 5/8" 10' - 4 7/8"
RELOCATE EXISTING
SIGNAGE FOR 105A
A
LI
G N
1"
OFFICE
105G
FURNITURE N.I.C.
K1
K1
KEY PLAN
AREA A
AREA B
B
C
D
STORAGE
105F
OPEN OFFICE
OFFICE
105E
OFFICE
105D OFFICE
105G
B
C
D
REMOVE LIGHT
FIXTURES, TYP.
REMOVE AND REINSTALL CEILING
PANELS IN NEW GRID. REMOVE CEILING
GRID AND ASSOC. SUPPORT MEMBERS.
B
C
D
OPEN OFFICE
ROOM NOT IN SCOPE ROOM NOT IN SCOPE
ROOM NOT IN SCOPE
REMOVE AND RELOCATE
SIGNAGE. PATCH WALL
TO MATCH ADJACENT
WALL SURFACE.
REMOVE EXISTING
CUBICLES, TYP.
2X2 CEILING SYSTEM. SEE
FINISH SCHEDULE
2X4 CEILING SYSTEM. SEE
FINISH SCHEDULE
GYPSUM BOARD CEILING
NOTE: SPOT ELEVATION SUFFIX "C.H." INDICATES FLAT CEILING HEIGHT ABOVE
FINISH FLOOR. SUFFIX "L.P." AND "H.P." INDICATE LOW POINT AND HIGH POINT OF
SLOPED CEILING. WHERE ADJACENT, TRANSITION BETWEEN FLAT AND SLOPED
CEILINGS SHALL UTILIZE APPROVED PRE-FINISHED ALUMINUM TRANSITION STRIP.
REFER TO SPECIFICATIONS.
RCP LEGEND
RECESSED DOWNLIGHT - SEE ELEC
1'X4' RECESSED LIGHT FIXTURE - SEE ELEC
2'X4' RECESSED LIGHT FIXTURE - SEE ELEC
1'X4' LIGHT FIXTURE - SEE ELEC
SUPPLY DIFFUSER, REGISTER, OR GRILL
- SEE MECH
RETURN DIFFUSER, REGISTER, OR GRILL
- SEE MECH
EXISTING WALLNEW WALL
WALL LEGEND
CARPET - NEW
CARPET - DEMO
MATERIALS LEGEND
EXISTING CEILING
SYSTEM - DEMO
123456789101112131415161718
123456789101112131415161718
A
B
C
D
E
F
G
H
J
K
L
M
A
B
C
D
E
F
G
H
J
K
L
M w w w .g ri m m a n d p a rk e r.
c o m
E a s t
M a in
S tr e e t n d F lo o r
C h a rl o tt e s v ill e
V A l:
-2
-5
DEB #
260-B4260-030
A102
P A
R
TI
A L
FI
R
S T
FL
O
O R
P
LA
N
RC
C
GL
EN
NS
C
AM
PU
S
IN
TE
RI
OR
R
EN
OV
AT
IO
N
5 C oll eg e D riv e, Gl en ns
, V irg ini a
JANUARY 9, 2025
BID SET
GP #22006.16
1/4" = 1'-0"A102A002
F10 PARTIAL FIRST FLOOR PLAN - AREA B NEW CONSTRUCTION
0 4' 8'2'
1/4" = 1'-0"A102
F17 PARTIAL REFLECTED CEILING PLAN - AREA B NEW CONSTRUCTION
1/4" = 1'-0"A102
A17 PARTIAL REFLECTED CEILING PLAN - AREA B DEMOLITION 1/4" = 1'-0"A102
A10 PARTIAL FIRST FLOOR PLAN - AREA B DEMOLITION
1. ROOM SIGNAGE IS BEING PROVIDED UNDER SEPARATE CONTRACT BY OWNER.
CONTRACTOR TO COORDINATE DIRECTLY WITH OWNER TO ENSURE TEMPORARY AND
PERMANENT SIGNAGE IS COMPLETED PRIOR TO SUBSTANTIAL COMPLETION.
2. COORDINATE AND PROVIDE HARDWARE AS DETAILED IN THE SPECIFICATIONS OR, IF NOT
SPECIFIED, PROVIDE HARDWARE (OF EQUAL QUALITY TO THAT SPECIFIED, AND MOST
SIMILAR IN FUNCTION TO TYPE OF DOOR) REQUIRED FOR DOORS TO OPERATE AND APPEAR
AS INTENDED ON DRAWINGS.
3. PROVIDE EXPOSED HARDWARE WITH BRUSHED-IN FINISH AND "SILVER" METALLIC IN COLOR
(ALUMINUM, CHROME, OR STEEL) TO MATCH EXISTING.
4. IF CONFLICT EXISTS BETWEEN DOOR RATING AS SCHEDULED AND WALL/PARTITION TYPE
FIRE RATING AS SHOWN ON PLANS, PROVIDE DOOR(S) WITH THE GREATER FIRE RATING OF
THE TWO.
5. VERIFY ALL DIMENSIONS AND CLEARANCES, AND COORDINATE UNDERCUTTING REQUIRED
TO CLEAR ADJACENT FLOOR MATERIALS.
6. IF A DISCREPANCY EXISTS BETWEEN THE DOOR SCHEDULE REMARKS AND THE HARDWARE
SCHEDULE IN THE SPECIFICATIONS, PROVIDE THE HARDWARE NEEDED TO MEET THE MORE
STRINGENT OF THE REQUIREMENTS.
7. SEE SPECIFICATIONS FOR SCHEDULED HARDWARE SETS.
DOORS NOT LISTED ON THE SCHEDULE TO HAVE THE TYPICAL FINISHES LISTED BELOW:
DOOR: FRAME:
WIDTH: 3'-0" MATERIAL: HM
HEIGHT: 7'-0" TYPE: 1
THICKNESS: 1-3/4" JAMB: J1
TYPE: F HEAD: H1
MATERIAL: SCWD SILL: NONE
DOOR LABEL: NONE
TYPICAL DETAILS
TYPICAL DOOR NOTES
NOTE: NOT ALL NOTES MAY BE USED ON THIS PROJECT. SEE SPECIFICATIONS FOR ADDITIONAL
DOOR INFORMATION. REFERENCE SPECIFICATIONS FOR DETAILED HARDWARE REQUIREMENTS.
1. PROVIDE WITH HOLD OPEN FEATURE IN CLOSER.
2. PROVIDE HARDWARE WITH PRIVACY SET.
NOTES FOR REMARKS COLUMN
PROVIDE THE FOLLOWING UNDERCUTS AT ALL DOORS:
• DOOR WITH AUTOMATIC DOOR BOTTOMS: AMOUNT REQUIRED BY DOOR BOTTOM MFR
• DOORS WITH THRESHOLD AND AUTOMATIC DOOR BOTTOM: HEIGHT OF THRESHOLD AND
AMOUNT REQUIRED BY DOOR BOTTOM MFR
• ALL OTHER DOORS: 5/8" ABOVE FINISH FLOOR
DOOR UNDERCUTS
F HG
NOTE: (UNLESS OTHERWISE NOTED)
ALL GLASS IN INTERIOR DOORS TO BE G-1
DOOR TYPES
AS SCHED.
A S
S C
H E
D
A S
S C
H E
D
AS SCHED.
VERIFY DIMS IN FIELD TO
MATCH EXISTING DOORS
T.
O
. G
LA
S S
S
TO
P
3'
6" M
A X
6" 6"
8"
WALL THICKNESS
COORD W/
9/16" 9/16"
2" 5/
8"
1 15/16"1 15/16"
METAL STUD TRACK
SCHEDULED GYP BD WALL
SEALANT TYP. BOTH SIDES,
FULL PERIMETER
HOLLOW METAL FRAME
FILL FRAME WITH MINERAL
WOOL INSULATION
W A
LL
T
H
IC
K N
E S
S
C O
O R
D W
9/
9/
UON
4"
2" 5/8"
/1 6"
/1 6"
WALL WHERE SHOWN IN PLAN
HOLLOW METAL FRAME
FILL FRAME WITH MINERAL
WOOL INSULATION
SCHEDULED DOOR WHERE
INDICATED ON PLANS
JAMB ANCHOR
SEALANT TYP. BOTH
SIDES, FULL PERIMETER
SCHEDULED GYP BD WALL
S E
E D
O O
R S
C H
E D
U
LE
4"
2" 2"SCHEDULE
SEE DOOR
K1 ABUSE RESISTANT GYP. BD. WALL (AS SHOWN), STC 49
3-5/8" METAL STUDS @ 16" O.C.
3-1/2" SOUND ATTENUATING
BATT INSULATION
5/8" ABUSE RESISTANT
GYP. BD ON EACH SIDE
NOTES:
1. STAGGER HORIZ. AND VERT. GYP.
BD. JOINTS.
2. OFFSET OPPOSING
PENETRATIONS MIN. ONE STUD BAY
ACOUSTIC SEALANT
(BOTH SIDES, TYP.)
SCHEDULED CEILING
1. REFER TO FLOOR PLANS, CEILING PLANS, INTERIOR ELEVATIONS, SECTIONS AND DETAILS
FOR ADDITIONAL INFORMATION AND EXTENT OF EACH FINISH WHEN MORE THAN ONE
FINISH IS INDICATED FOR ANY SPACE.
2. SEE CEILING PLANS FOR HEIGHTS OF CEILINGS AND LOCATIONS AND HEIGHTS OF
BULKHEADS, SOFFITS, ETC.
3. FIELD PAINT ALL EXPOSED, NON-FACTORY FINISHED STRUCTURAL AND MEP COMPONENTS.
4. PROVIDE SEALANT AT INTERSECTIONS OF DISSIMILAR MATERIALS, COMPLYING WITH
SPECIFICATIONS.
5. REFER TO INTERIOR ELEVATIONS AND SECTIONS FOR ADDITIONAL FINISH INFORMATION.
PROVIDE ALL FINISH MATERIALS SHOWN IN PLANS, ELEVATIONS OR SECTIONS AS NOTED
OR DEPICTED ON THE DRAWINGS AND SPECIFICATIONS.
6. BRING CONFLICTS TO THE ARCHITECTS ATTENTION DURING THE BIDDING PERIOD FOR
CLARIFICATION.
7. WALL AND CEILING FINISHES TO INCLUDE ALL PROJECTIONS, BEAM ENCLOSURES,
RECESSES, BULKHEADS, MATERIAL CHANGES, OR OTHER ENCLOSURES.
8. ELECTRICAL OUTLETS, CLOCKS, P.A. SPEAKERS OR OTHER DEVICES SHOWN ON THE
ARCHITECTURAL DRAWINGS SERVE TO CALL ATTENTION TO THE PRESENCE OF SUCH
DEVICES. NOT ALL DEVICES MAY BE SHOWN ON ARCHITECTURAL DRAWINGS. CONSULT
THE OTHER DRAWINGS FOR FURTHER INFORMATION AND ADVISE ARCHITECT OF ANY
CONFLICT OF LOCATION OR TYPE OF DEVICES SHOWN. COORDINATE ALL WORK, FINISHES
AND DEVICES.
9. FIELD PAINT ELECTRICAL PANELS EXCEPT PANELS LOCATED IN ELECTRICAL CLOSETS AND
MECHANICAL ROOMS.
10. BRING CONFLICTS BETWEEN THE FINISH SCHEDULE AND MATERIALS SHOWN ON OTHER
DRAWINGS (AND/OR SPECIFICATIONS) TO THE ATTENTION OF THE ARCHITECT
IMMEDIATELY. IF A CONFLICT EXISTS IN/BETWEEN DRAWINGS (AND/OR SPECIFICATIONS),
THE MORE STRINGENT AND MORE COSTLY REQUIREMENT TO APPLY.
SPACES NOT LISTED ON THE SCHEDULE TO HAVE THE TYPICAL FINISHES LISTED BELOW:
FLOORS: CPT
BASE: RST
WALLS: PTD
CEILING: APC2
GYP. BD. ABOVE H.M. FRAMES AS INDICATED ON SECTIONS. DETAILS TO RECEIVE SAME TOP
COATS AS ADJACENT WALLS UNLESS OTHERWISE NOTED.
CONC1 CONCRETE WITH HARDENER
CONC2 CONCRETE WITH TRAFFIC COATING
CPT CARPET TILE
CT CERAMIC TILE
PT PORCELAIN TILE
QT QUARRY TILE
RES RESINOUS FLOORING W/ INTEGRAL BASE
RBR RUBBER FLOORING, TREADS, RISERS,
SKIRTINGS
SPORT RUBBER SPORTS FLOOR
VCT VINYL COMPOSITION TILE
WD WOOD FLOOR
HRF1 HYBRID RESILIENT FLOORING, TILE
HRF2 HYBRID RESILIENT FLOORING, SHEET
TYPICAL FINISHES
FINISH MATERIALS
FLOORS
APC1 ACOUSTIC PANEL CLG. - 2'X4'
APC2 ACOUSTIC PANEL CLG. - 2'X2'
EXP EXPOSED CONSTRUCTION - PAINTED
GFC GLASS FIBER SANITARY CEILING
GYP GYPSUM BOARD CEILING - PAINTED
WS WOOD SLAT CEILING
CEILINGS
BASES
NONE NO BASE
CT CERAMIC TILE
PT PORCELAIN TILE
QT QUARRY TILE
RES RESINOUS BASE
RST RESILIENT BASE
VRB VENTED RUBBER BASE
WALLS
CT CERAMIC TILE
PT PORCELAIN TILE
PTD PAINTED
HPC HIGH PERFORMANCE COATING
WALL KEY
WALLS ON FINISH SCHEDULE ARE DENOTED THUS:
AXXX
A
C
D B
TYPICAL UNLESS OTHERWISE NOTED.
TYPICAL NOTES
/1 6"
/1 6"
1/ 2"
1/ 2"
TYPICAL FRAME
NOTE: 9/16" RETURN DIMENSION
INDICATED ON PLANS IS FROM FACE
OF FRAME TO FACE OF WALL
123456789101112131415161718
123456789101112131415161718
A
B
C
D
E
F
G
H
J
K
L
M
A
B
C
D
E
F
G
H
J
K
L
M w w w .g ri m m a n d p a rk e r.
c o m
E a s t
M a in
S tr e e t n d F lo o r
C h a rl o tt e s v ill e
V A l:
-2
-5
DEB #
260-B4260-030
A301
S C
H E
D U
LE
S
S
IG
N
A G
E
RC
C
GL
EN
NS
C
AM
PU
S
IN
TE
RI
OR
R
EN
OV
AT
IO
N
5 C oll eg e D riv e, Gl en ns
, V irg ini a
JANUARY 9, 2025
BID SET
GP #22006.16
DOOR SCHEDULE
DOOR NO.
DOOR FRAME DOOR
LABEL
FIRE
RATING HARDWARE SET REMARKS
NOMINAL SIZE
TYPE MATL MATL TYPE
SECTIONS
WIDTH HEIGHT THK. JAMB HEAD SILL
105D 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J1 H1 - - 2
105E 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J1 H1 - - 2
105F 3' - 0" 7' - 0" 1 3/4" F SCWD HM 1 J1 H1 - - 1
105G 3' - 0" 7' - 0" 1 3/4" HG SCWD HM 1 J1 H1 - - 2
119C 3' - 0" 6' - 8" 1 3/4" HG SCWD HM 1 J1 H1 - - 2
H1 - HEAD DETAIL J1 - JAMB DETAIL
NON-RATED PARTITIONS
FINISH SCHEDULE
RM. NO. NAME
COLOR
SCHEME FLOOR BASE
WALLS CLG.
MATL. REMARKSA B C D
105 OPEN OFFICE ETR ETR/RST PTD PTD PTD PTD APC2
105D OFFICE ETR ETR/RST PTD PTD PTD PTD APC2
105E OFFICE ETR ETR/RST PTD PTD PTD PTD APC2
105F OFFICE ETR ETR/RST PTD PTD PTD PTD APC2
105F STORAGE ETR ETR/RST PTD PTD PTD PTD APC2
105G OFFICE ETR ETR/RST PTD PTD PTD PTD APC2
119B OFFICE ETR ETR/RST PTD PTD PTD PTD APC2
119C OFFICE ETR ETR/RST PTD PTD PTD PTD APC2
DATE DESCRIPTION
TYPICAL HOLLOW METAL
FRAME PROFILE
HOLLOW METAL FRAME TYPES
X
DESIGN CODES/STANDARDS
CODE/STANDARD YEAR/VERSION
VIRGINIA UNIFORM STATEWIDE BUILDING CODE (VUSBC) 2021
VIRGINIA EXISTING BUILDING CODE (VEBC) 2021
VIRGINIA MECHANICAL CODE (VMC) 2021
VIRGINIA PLUMBING CODE (VPC) 2021
VIRGINIA ENERGY CONSERVATION CODE (VECC) 2021
NATIONAL ELECTRICAL CODE (NEC) 2020
NFPA 13 2019
NFPA 72 2019
NOTES:
1. ALL WORK MUST BE PERFORMED IN ACCORDANCE WITH THE
CURRENTLY ENFORCED BUILDING CODES.
1. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH CODES
INDICATED.
2. PROVIDE SINGLE THICKNESS, 1.1/2 INCHES SPACED, TURNING
VANES IN ALL MITERED DUCTWORK ELBOWS AND BULL HEAD DUCT
TEES.
3. COORDINATE LOCATIONS OF ALL DEVICES, ACCESS PANELS,
DIFFUSERS, GRILLES, & LOUVERS WITH ARCHITECTURAL
REFLECTED CEILING PLANS, INTERIOR & EXTERIOR ELEVATIONS.
4. ALL DUCTWORK DIMENSIONS CITED ARE THE INSIDE CLEAR
DIMENSIONS. CONTRACTOR SHALL MAKE ALLOWANCE FOR DOUBLE
WALL AND DUCT LINER.
5. ALL PIPING AND CONTROL WIRING SHALL BE CONCEALED IN WALLS
OR ABOVE CEILINGS OF FINISHED SPACES, UNLESS NOTED
OTHERWISE. IN FINISHED SPACES WITH EXPOSED STRUCTURE
CEILINGS, CONTRACTOR SHALL CLOSELY COORDINATE ROUTING
WITH OTHER TRADES.
6. CONTRACTOR SHALL COORDINATE LOCATION OF ALL EQUIPMENT,
PIPING AND DUCTWORK WITH OTHER TRADES. MAINTAIN REQUIRED
SERVICE ACCESS.
7. PAINT ALL EXPOSED DUCTWORK, PIPING AND ASSOCIATED
COMPONENTS (EXCLUDING MECHANICAL AND STORAGE SPACES)
PER DIVISION 9.
8. AIRFLOW QUANTITIES INDICATED ON THE PLANS ARE FOR
OCCUPIED OPERATING MODE, UNO.
9. UNLESS OTHERWISE NOTED, ALL DUCT & PIPING MAINS SHALL BE
INSTALLED AS HIGH AS POSSIBLE TO UNDERSIDE OF STRUCTURE.
ROUTE DUCTS BETWEEN AND/OR THROUGH STRUCTURE WHERE
INDICATED. VERIFY ROUTING OF DUCTS WITH CEILING HEIGHTS,
STRUCTURAL SYSTEMS AND OTHER TRADES PRIOR TO DUCT
FABRICATION. INSTALL PIPING BELOW DUCTWORK, UNO.
10. HVAC CONTRACTOR(S) SHALL COORDINATE THEIR WORK WITH ALL
OTHER TRADES PRIOR TO FABRICATIONS OF SYSTEMS AND
COMMENCEMENT OF INSTALLATION. IT SHALL BE THE
RESPONSIBILITY OF EACH CONTRACTOR TO REVIEW THE WORK OF
OTHER TRADES (INCLUDING, BUT NOT LIMITED TO ARCHITECTURAL,
CIVIL, ELECTRICAL, EQUIPMENT, FIRE PROTECTION, FIRE ALARM,
PLUMBING, AND STRUCTURAL) AS IT AFFECTS THEIR WORK, AND AS
THEIR WORK AFFECTS OTHER TRADES, TO INSURE THAT THE
CONSTRUCTION DOCUMENTS ARE CLOSELY FOLLOWED. WHERE
DISCREPANCIES ARISE, THEY SHALL BE REFERRED TO THE A/E FOR
RESOLUTION BEFORE PROCEEDING WITH THE WORK.
11. FLEX-DUCT RUNS SHALL BE 3' MINIMUM AND 5' MAXIMUM LENGTH.
PROVIDE STAINLESS STEEL ADJUSTABLE BANDS TO FASTEN FLEX
TO DUCTWORK COLLAR AND EQUIPMENT SERVED. PLASTIC TIES
ARE UNACCEPTABLE.
12. PROVIDE MANUAL BALANCING DAMPERS IN EACH BRANCH OF
SUPPLY, RETURN, VENTILATION, AND EXHAUST DUCTWORK.
13. COORDINATE WORK PRIOR TO INSTALLATION OF ARCHITECTURAL
FINISHES AS REQUIRED.
14. INSTALL ALL DUCTWORK TERMINATING WITH WWM ABOVE FINISHED
CEILING, UNO. TERMINATE DUCT COMPLETE WITH ELBOW
DIRECTED TOWARDS UNDERSIDE OF ROOF DECK, UNO.
15. CONTRACTOR SHALL PROVIDE COORDINATED 3-D SHOP DRAWINGS
OF DIVISION 23 SYSTEMS. SHOP DRAWINGS SHALL BE PREPARED IN
ELECTRONIC FORMAT AND SUBMITTED IN PRINTED FORM.
16. INSTALL ALL HVAC WALL MOUNTED SENSORS 48" AFF, MEASURED
FROM TOP OF OUTLET BOX, UNO.
17. NOMENCLATURE FOR FINAL ROOM NAMES AND NUMBERS MAY
VARY FROM THE CONSTRUCTION DOCUMENTS. FINAL NAMES AND
NUMBERS USED IN THE SHOP DRAWINGS, EQUIPMENT TAGS, BAS
LABELING AND CLOSEOUT DOCUMENTATION SHALL BE
COORDINATED WITH FINAL ROOM NAMES AND NUMBERS ASSIGNED
BY THE OWNER AND ARCHITECT.
1. DOCUMENTATION OF EXISTING SYSTEMS IS BASED ON AVAILABLE
RECORD DRAWINGS AND CASUAL FIELD OBSERVATION. MAJOR
DISCREPANCIES SHALL BE REFERRED TO THE A/E FOR
RESOLUTION PRIOR TO PROCEEDING WITH THE WORK.
2. PRIOR TO BIDDING, THE CONTRACTOR SHALL VISIT THE SITE TO
BECOME FAMILIAR WITH EXISTING CONDITIONS, AND TO VERIFY
LOCATION, SIZE AND QUANTITY OF ITEMS TO BE REMOVED.
SUBMITTAL OF A BID SHALL SIGNIFY WILLINGNESS TO COMPLY
WITH THE DESIGN AND ACCEPTANCE OF ON-SITE CONDITIONS AS
THEY EXIST.
3. CONTRACTOR SHALL COORDINATE DEMOLITION OF MECHANICAL
SYSTEMS WITH OTHER TRADES PRIOR TO REMOVAL.
4. WHERE QUESTIONS OR DISCREPANCIES ARISE, THE A/E SHALL BE
NOTIFIED IMMEDIATELY FOR RESOLUTION PRIOR TO PROCEEDING
WIITH THE WORK.
5. THE CONTRACTOR SHALL AVOID DISRUPTION OF THE ACTIVITIES
OF THE ADJACENT SPACES. COORDINATE NEW WORK
REQUIREMENTS WITH OTHER TRADES TO ACCOMPLISH THE
WORK WHILE THE FACILITY REMAINS IN OPERATION. SCHEDULE
ANY DISRUPTIONS TO THE SPACE ADJACENT TO THE PROJECT
AREA WITH THE PROJECT MANAGER.
6. PRE-TAB ALL EXISTING SYSTEMS INCLUDING BUT NOT LIMITED TO,
AIRSIDE AND WATERSIDE COMPONENTS INSIDE AREA OF SCOPE.
NEW WORK EQUIPMENT SUBMITTALS WILL NOT BE APPROVED
UNTIL PRE-TAB DATA HAS BEEN SUBMITTED TO A/E.
A AMPERE
ABV ABOVE
A/E ARCHITECT/ENGINEER
ACT ACOUSTICAL CEILING TILE
AD ACCESS DOOR
AFF ABOVE FINISHED FLOOR
AFMS AIR FLOW MONITORING STATION
AFR ABOVE FINISHED ROOF
AHU AIR HANDLING UNIT
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APD AIR PRESSURE DROP
APPROX APPROXIMATELY
ARCH ARCHITECT
ARCH'L ARCHITECTURAL
ARI AMERICAN REFRIGERATION INSTITUTE
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING AND
REFRIGERATION AND AIR-CONDITIONING ENGINEERS
ATU AIR TERMINAL UNIT
AUX AUXILIARY
BAS BUILDING AUTOMATION SYSTEM
BC BLOWER COIL
BLDG BUILDING
BTUH BRITISH THERMAL UNITS PER HOUR
CD CEILING DIFFUSER, CONDENSATE DRAIN
CEG CEILING EXHAUST GRILLE
CFM CUBIC FEET PER MINUTE
CKT CIRCUIT
CLG CEILING
CO2 CARBON DIOXIDE
CONC CONCRETE
COND CONDENSATE
CRG CEILING RETURN GRILLE
CV CONSTANT VOLUME
dB DECIBELS
DB DRY BULB
DDC DIRECT DIGITAL CONTROL
DIA DIAMETER
DP DIFFERENTIAL PRESSURE
EA EXHAUST AIR
EAD EXHAUST AIR DUCT
EAL EXHAUST AIR LOUVER
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EQPT EQUIPMENT
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
F DEGREE FAHRENHEIT
FC FAN COIL
FLA FULL LOAD AMPS
FLR FLOOR
FPI FINS PER INCH
FPM FEET PER MINUTE
FT FEET OR FOOT
GAL GALLON
GALV GALVANIZED
GPM GALLONS PER MINUTE
HP HORSEPOWER
HVAC HEATING, VENTILATION & AIR CONDITIONING
IN INCH, INCHES
LAT LEAVING AIR TEMPERATURE
LBS, # POUNDS
LBS/HR POUNDS PER HOUR
LWT LEAVING WATER TEMPERATURE
MA MIXED AIR
MAX MAXIMUM
MBH THOUSAND BTUH
MCA MINIMUM CIRCUIT AMPS
MFR MANUFACTURE
MTD MOUNTED
NTS NOT TO SCALE
OA OUTDOOR AIR
OAU OUTSIDE AIR UNIT
OAD OUTSIDE AIR DUCT
OAL OUTSIDE AIR LOUVER
OBD OPPOSED BLADE DAMPER
OED OPEN END DUCT W/ 1/2" WIRE MESH
NOM NOMINAL
NPT NATIONAL PIPE THREAD
PD PRESSURE DROP
PSI POUNDS PER SQUARE INCH
RTU ROOFTOP UNIT
RA RETURN AIR
RAD RETURN AIR DUCT
RCP REFLECTED CEILING PLAN
RG RETURN GRILLE
SA SUPPLY AIR
SAD SUPPLY AIR DUCT
SENS SENSIBLE
SIM SIMILAR
SP STATIC PRESSURE
SWRG SIDEWALL RETURN GRILLE
SWSG SIDEWALL SUPPLY GRILLE
SWTG SIDEWALL TRANSFER GRILLE
TOD TOP OF DUCT
TRNS TRANSITION
TTL TOTAL
TU TERMINAL UNIT
TYP TYPICAL
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
V-PH VOLTAGE-PHASE
VFD VARIABLE FREQUENCY DRIVE
W WATT
WB WET BULB
WC WATER COLUMN
WWM WOVEN WIRE MESH, 1/2" UNO
VAV VARIABLE AIR VOLUME TERMINAL UNIT
TH
SP
T
SP
TH
X
AD
SD
TEMPERATURE & HUMIDITY SENSOR WITH SET
POINT CONTROL, 48" AFF. COORDINATE EXACT
LOCATION WITH A/E PRIOR TO ROUGH-IN.
TEMPERATURE SENSOR WITH SET POINT
CONTROL, 48" AFF. COORDINATE EXACT
LOCATION WITH A/E PRIOR TO ROUGH-IN.
TEMPERATURE & HUMIDITY SENSOR WITHOUT
SET POINT CONTROL, 48" AFF. COORDINATE
EXACT LOCATION WITH A/E PRIOR TO ROUGH-
IN.
EXISTING TO BE REMOVED
EXISTING TO REMAIN
POINT OF CONNECTION, NEW-TO-EXISTING
POINT OF DISCONNECTION FOR DEMOLITION
X/X
X"Ø
DUCTWORK
RECTANGULAR DUCT, FIRST DIMENSION
IS SIDE SHOWN. DIMENSION IN INCHES
ROUND DUCT, DIMENSION IN INCHES
FLEXIBLE CONNECTION
TRANSITION, SLOPE NOT TO EXCEED
4-TO-1. FOT = FLAT ON TOP, FOB = FLAT
ON BOTTOM
CHANGE OF ELEVATION IN DIRECTION OF
AIR FLOW (R = RISE, D = DROP)
TURNING VANES
STANDARD BRANCH, SUPPLY OR
RETURN, NO SPLITTER
MANUAL VOLUME DAMPER
SMOKE DETECTOR
DUCT ACCESS DOOR
RECTANGULAR DUCT SECTION
(SUPPLY)
RECTANGULAR DUCT SECTION
(RETURN)
RECTANGULAR DUCT SECTION
(EXHAUST)
RECTANGULAR ELBOW TURNING UP
(SUPPLY)
RECTANGULAR ELBOW TURNING UP
(RETURN)
RECTANGULAR ELBOW TURNING UP
(EXHAUST)
RECTANGULAR ELBOW TURNING DOWN
(SUPPLY)
RECTANGULAR ELBOW TURNING DOWN
(RETURN)
RECTANGULAR ELBOW TURNING DOWN
(EXHAUST)
ROUND DUCT SECTION (SUPPLY)
ROUND DUCT SECTION (RETURN)
ROUND DUCT SECTION (EXHAUST)
ROUND ELBOW TURNING UP
(SUPPLY)
ROUND ELBOW TURNING UP
(RETURN)
ROUND ELBOW TURNING UP
(EXHAUST)
ROUND ELBOW TURNING DOWN
(SUPPLY)
ROUND ELBOW TURNING DOWN
(RETURN)
ROUND ELBOW TURNING DOWN
(EXHAUST)
RETURN GRILLE, TYPE AS INDICATED
EXHAUST GRILLE, TYPE AS INDICATED
RECTANGULAR CEILING SUPPLY DIFFUSER,
ROUND CONNECTION, TYPE AS INDICATED
SIDEWALL SUPPLY REGISTER
SIDEWALL RETURN GRILLE
FLEXIBLE DUCT
SP
STATIC PRESSURE SENSOR
1. THE DESIGN IS BASED ON MANUFACTURERS AND MODELS
INDICATED, AND IS INTENDED TO SHOW THE GENERAL SIZE,
CONFIGURATION, LOCATION, CONNECTIONS AND/OR SUPPORT FOR
EQUIPMENT OR SYSTEM OR SYSTEMS SPECIFIED WITH RELATION
TO THE OTHER BUILDING/SYSTEMS. SEE SPECIFICATION SECTIONS
FOR TECHNICAL REQUIREMENTS.
NO. 51922
MATTHEW R. LEWISC
O
M M
O
N W
EALTH OF V
IR
G
IN
IA
P R
O
F
ESS I O N A L E N G
I N
E R
E
123456789101112131415161718
123456789101112131415161718
A
B
C
D
E
F
G
H
J
K
L
M
A
B
C
D
E
F
G
H
J
K
L
M w w w .g ri m m a n d p a rk e r.
c o m
E a s t
M a in
S tr e e t n d F lo o r
C h a rl o tt e s v ill e
V A l:
-2
-5
DEB #
260-B4260-030
M000
LE
G
E N
D S
, A B
B R
E V
IA
TI
O N
S
G E
N E
R A
L N
O
TE
S
RC
C
GL
EN
NS
C
AM
PU
S
IN
TE
RI
OR
R
EN
OV
AT
IO
N Gl en ns
, V irg ini a
JANUARY 9, 2025
BID SET
GP #22006.15/ 20166.02
1/9/2025
GENERAL NOTES (NEW WORK)GENERAL NOTES (DEMO)ABBREVIATIONSMECHANICAL LEGENDBASIS OF DESIGN
SHEET LIST - MECHANICAL
SHEET NO SHEET NAME
M000 LEGENDS, ABBREVIATIONS & GENERAL NOTES
MD101 PARTIAL FIRST FLOOR PLAN - DEMOLITION
M101 PARTIAL FIRST FLOOR PLAN - DUCTWORK
M501 DETAILS
M701 SCHEDULES & SPECIFICATIONS
1 2 3 4 5 6 7 8 9 10 11 12 13
A
B
C
D
E
F
G
H
J
K
L
M
8"Ø
.175 CFM
TYP 2
CD-1
12/1212"Ø
.375 CFM
CD-1
.75 CFM
CD-1
.375 CFM
CD-1
"Ø
TB-309
TB-311
/1
24/16
26/16
30/16
6" Ø
8/8
/1
10/14
.125 CFM
CD-2
.225 CFM
CD-2
TYP 2
150 CFM
CD-2
8"Ø
8"Ø
12/12
/1
.350 CFM
CRG-1
1 1
OFFICE
OFFICE
OFFICE
EXISTING
OFFICE SUITE
EXISTING
OFFICE SUITE
/8
/8
TH
SP
CRG-1
300 CFM
T
SP
CRG-E
290 CFM
NO. 51922
MATTHEW R. LEWISC
O
M M
O
N W
EALTH OF V
IR
G
IN
IA
P R
O
F
ESS I O N A L E N G
I N
E R
E
123456789101112131415161718
123456789101112131415161718
A
B
C
D
E
F
G
H
J
K
L
M
A
B
C
D
E
F
G
H
J
K
L
M w w w .g ri m m a n d p a rk e r.
c o m
E a s t
M a in
S tr e e t n d F lo o r
C h a rl o tt e s v ill e
V A l:
-2
-5
DEB #
260-B4260-030
MD101
P A
R
TI
A L
FI
R
S T
FL
O
O R
P
LA
N
D E
M O
LI
TI
O N
RC
C
GL
EN
NS
C
AM
PU
S
IN
TE
RI
OR
R
EN
OV
AT
IO
N Gl en ns
, V irg ini a
JANUARY 9, 2025
BID SET
GP #22006.15/ 20166.02
1/9/2025
GENERAL NOTES (DEMO)
1. VAV BOXES ARE EXISTING TO REMAIN WITH HYDRONIC REHEAT
COILS.
# KEY NOTES (DEMO)
1. DISTRIBUTION DUCTWORK CONNECTED TO NEW AHU-5.
2. DISTRIBUTION DUCTWORK CONNECTED TO RTU-4.
3. SALVAGE EXISTING SPACE SENSOR FOR RELOCATION IN NEW
WORK.
4. FIELD VERIFY LOCATION OF EXISTING SPACE SENSOR. SALVAGE
EXISTING SPACE SENSOR FOR RELOCATION IN NEW WORK.
2' 4' 16'8'0
1/8" = 1'-0"---- MD101 SCALE: 1/8" = 1'-0"
DEMOLITION PLAN - MECHANICAL1
1 2 3 4 5 6 7 8 9 10 11 12 13
B
C
D
E
F
G
H
J
K
L
M
.70 CFM
CD-1
.70 CFM
CD-1
.70 CFM
CD-1
.70 CFM
CD-1
.70 CFM
CD-1
8/8
6" Ø
6" Ø
TB-309
TB-311
/1
12/1212"Ø
.75 CFM
CD-1
.375 CFM
CD-1
.375 CFM
CD-1
"Ø
6" Ø
/1
24/16
26/16
30/16
12/12
/8
/8
/1
8"Ø
8"Ø
.150 CFM
CD-2
.125 CFM
CD-2
TYP 2
150 CFM
CD-2
10/14
.60 CFM
CRG-1
6/
.60 CFM
CRG-1
.60 CFM
CRG-1
.50 CFM
CRG-1
8/
6/
/1
.150 CFM
CRG-1
.150 CFM
CRG-1
.350 CFM
CRG-1
.225 CFM
CD-2
.60 CFM
CRG-1
1 1
.360 CFM
CRG-1
.65 CFM
CRG-1
.360 CFM
CRG-1
OPEN
OFFICE
119B
OFFICE
105E
OFFICE
105D
OFFICE
105F
STORAGE
119C
OFFICE
105G
OFFICE
TH
SP
TH
SP
8/8
8/6
NO. 51922
MATTHEW R. LEWISC
O
M M
O
N W
EALTH OF V
IR
G
IN
IA
P R
O
F
ESS I O N A L E N G
I N
E R
E
123456789101112131415161718
123456789101112131415161718
A
B
C
D
E
F
G
H
J
K
L
M
A
B
C
D
E
F
G
H
J
K
L