This document is a floor plan and equipment schedule for a kitchen renovation at the Malcolm Randall VA Medical Center in Gainesville, FL. The equipment schedule details six primary kitchen equipment items: an electric countertop griddle, a refrigerated equipment stand, two electric tilting skillet braising pans (two full-size and three countertop models), a rapid cook oven, and five electric combi ovens. The schedule provides comprehensive technical specifications for each item, including electrical requirements (voltage, phase, amperage), plumbing connections, and specific manufacturer models such as Vulcan and Rational.
The document includes detailed plumbing and electrical legends and notes, specifying installation requirements for the kitchen equipment. Key plumbing specifications include maintaining water pressure under 35 PSI, providing pressure reducing valves, and ensuring all lines are concealed within walls where possible. Electrical requirements include specific voltage, phase, and amperage for each piece of equipment, with connection types ranging from junction box (JB) to cord and plug. The drawing is dated 05/03/23, drawn at 1/4" = 1'-0" scale, and is associated with the VA Medical Center kitchen upgrade project.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EQUIPMENT SCHEDULE
PLUMBING
ItemNo
Quantity
Unit
Category Cold Water (in) Cold Water Conn. Height(in) Hot Water (in) Hot Water Conn. Height(in)
Indirect Waste Size Direct Waste Size
Direct Waste Conn. Height(in) Equipment Remarks
1 1 ea
Griddle, Electric, Countertop
2 1 ea
Equipment Stand, Refrigerated Base
3 2 ea
Tilting Skillet Braising Pan, Electric
3/4" STUB UP 6" FLOOR TROUGH
4 3 ea
Tilting Skillet Braising Pan, Countertop, Electric
3/4" STUB UP 6" FLOOR TROUGH
5 1 ea Rapid Cook Oven
6 5 ea Combi Oven, Electric
3/4" STUB UP 6" 2"
EQUIPMENT SCHEDULE
ELECTRICAL
ItemNo
Quantity
Unit
Category Voltage
Phase
Amps Cycle Hp
Kw
ConnectionType
NEMA
ElectricalConnectionHeight Equipment Remarks
1 1 ea Griddle, Electric, Countertop (2) 480 (2) 3 (2) 19.5 (2) 60 (2) 19.5 (2) JB
STUB UP 12"
2 1 ea
Equipment Stand, Refrigerated Base
115 1 6.7 60 1/3
Cord & Plug
5-15P STUB UP 12"
3 2 ea
Tilting Skillet Braising Pan, Electric
440/480 3 53 60 44 JB STUB UP 12"
4 3 ea
Tilting Skillet Braising Pan, Countertop, Electric
440/480 3 27 60 22 JB STUB UP 12"
5 1 ea
Rapid Cook Oven
208-240 3 50 60
Cord & Plug
15-50P STUB UP 12"
6 5 ea Combi Oven, Electric
440/480 3 60 22.4 JB STUB UP 12"
EQUIPMENT SCHEDULE
ItemNo Quantity
Unit Category
Mfr Model Equipment Remarks
1 1 ea Griddle, Electric, Countertop
Vulcan HEG72E
2 1 ea
Equipment Stand, Refrigerated Base
Vulcan ARS72
3 2 ea
Tilting Skillet Braising Pan, Electric
Rational
IVARIOPRO XL 440/480V 3PH (LMX100DE)
4 3 ea
Tilting Skillet Braising Pan, Countertop, Electric
Rational
IVARIOPRO 2-S 440/480V 3PH (LMX100BE)
5 1 ea Rapid Cook Oven
TurboChef PLE-9500-1-DL-CIR
6 5 ea Combi Oven, Electric
Rational ICP 6-FULL ON 6-FULL E 480V 3 PH
JOB NO.:
DATE:
SCALE:
DRAWN:
APPROVED:
DRAWING REV:..
REVISIONS
F L O
O R
P
L A
N
O
R
F
L O
O
P
A
N
A N
D
E
Q U
I P
M E
N T
S
C H
E D
U L E
G A
I N
E S
V I L L E
F
L
M A
L C
O
M
A N
D A
L L
V
A M
C
OF 1 SHEETS
SHEET 1
FS-1
CAR
CAR
1/4" = 1'-0"
05/03/23
1 2 3 4 3 4 4
5 6 6 6 66
DISTANCE ABOVE FINISHED FLOOR+AFF
AMPERES
KILOWATT
HORSE POWER
SINGLE RECEPTACLE
ELECTRICAL LEGEND
VOLTS
PHASE
JUNCTION BOX
DUPLEX RECEPTACLE
SWITCH
A
V
KW
Ø
HP
SR
SW $
DR
JB
J
PLUMBING LEGEND
INDIRECT WASTE
FUNNEL FLOOR DRAIN
G
HW
CW
FS
W
IW
FFD
FD
HOT WATER
COLD WATER
GAS
FLOOR SINK
TIGHT WASTE
FLOOR DRAIN
PLUMBING REQUIREMENTS.
PLUMBING CONTRACTOR TO PROVIDE 8" SCH 40 PVC CHASE FOR SODA LINES
WITH LONG SWEEP 90°NO FACTORY ELL OR PIPE JOINTS IN SWEEPS ARE
PERMITTED. ALL JOINTS TO BE SMOOTH & BURR FREE.
VALVE FOR INSTALLATION BY PLUMBING CONTRACTOR IN ACCORDANCE
FIRE PROTECTION SYSTEM CONTRACTORS SHALL PROVIDE GAS SHUT OFF
ABOVE FINISHED FLOORS; (UNLESS OTHERWISE NOTED).
ALL DIMENSIONS SHOWN ARE FROM THE FACE OF FINISHED WALLS AND
INSTALLATION BY THE PLUMBING CONTRACTOR.
EQUIPMENT FAUCETS FOR NEW EQUIPMENT FURNISHED BY P.S.C.I. FOR
KITCHEN EQUIPMENT CONTRACTOR SHALL PROVIDE ALL FIXTURES AND
INSTALLED BY THE PLUMBING CONTRACTOR.
CONNECTED THRU A GREASE TRAP, WHICH WILL BE FURNISHED AND
IF NECESSARY TO COMPLY WITH LOCAL CODES, SINKS WILL BE
ROUGH-IN OUTLETS ARE SHOWN, ALLOWANCES HAVE NOT BEEN MADE
STUBBED OUT OF WALLS AT HEIGHT SHOWN.
WHERE POSSIBLE ALL LINES SHALL BE CONCEALED WITHIN WALLS AND
PLUMBING CONTRACTOR TO PROVIDE ROUGH-IN AND FINAL CONNECTION
PLUMBING CONTRACTOR TO PROVIDE PRESSURE REDUCING VALVES.
GENERAL WATER PRESSURE IN KITCHEN SHALL NOT EXCEED 35 P.S.I.:
WITH N.F.P.A. PAMPHLET #96.
10.
9.
FOR TRAPS, VALVES, ETC.
TO FOOD SERVICE EQUIPMENT.
7.
6.
5.
4.
3.
2.
8.
ONLY; DO NOT SCALE DRAWING, SEE ARCHITECTS PLAN FOR ADDITIONAL
ALL ROUGH-INS SHOWN ARE RELATIVE TO FOOD FACILITIES EQUIPMENT
1.
J J J J
CW CWCW CWCW
J J JJ J J J J
CW CW CW CW CW
36"48"60"60"60"48"36" 12"12"
1 12 3 4 3 4 4
48"60"60"60"60"48"36"
5 6 6 6 6 6
72" 24" 36" 24" 36" 24" 36" 24" 36" 48"
12"
24"48"60"60"60"
3 34 4 4
6 6 6 6 6 6 6 6 6 6
53"
3 4
C
L
C
L
C
L
C
L
AutoCAD SHX Text Chris.Rearick@REWonline.com
AutoCAD SHX Text WWW.REWonline.com
AutoCAD SHX Text
PIERCE SALES COMPANY, INC.
AutoCAD SHX Text
RESTAURANT EQUIPMENT WORLD, LLC 2
AutoCAD SHX Text
TM
AutoCAD SHX Text
(RESTAURANT EQUIPMENT WORLD)
AutoCAD SHX Text
2413 FORSYTH ROAD
AutoCAD SHX Text
ORLANDO, FL 32807
AutoCAD SHX Text
(407) 679-9004
AutoCAD SHX Text
(407) 679-1699
AutoCAD SHX Text PLEASE NOTE THAT THIS DRAWING IS INTENDED FOR USE BY THIS CUSTOMER ONLY FOR THE SINGLE PURPOSE OF THIS PARTICULAR PROPERTY. THESE DESIGNS, SPECIFICATIONS, &/OR LAYOUTS ARE NOT ARCHITECTURAL, INTERIOR DESIGN, OR ENGINEERING DESIGNS, SPECIFICATIONS, OR LAYOUTS & MAY NOT BE USED FOR CONSTRUCTION UNLESS REVIEWED & APPROVED BY A LICENSED ARCHITECT OR ENGINEER. DRAWING MAY BE COPIED FOR USE WITH ARCHITECTURAL/ENGINEERING DRAWING BUT WHEN A COPY IS MADE THE PIERCE SALES CO. INC. TITLE BLOCK & DATES MUST BE INCLUDED. NO ALTERATIONS ARE TO BE MADE TO THIS DRAWING & ELEMENTS ARE NOT TO BE PICKED UP OR ALTERED BY OTHERS FOR THIS OR OTHER PROJECTS. IF ANY DRAWING IS ALTERED, PIERCE SALES CO. INC. WILL NOT BE RESPONSIBLE FOR ANY RESULTING ERRORS IN MEASUREMENTS OR OTHER ERRORS OR MISUNDERSTANDINGS THAT MAY OCCUR. COMPENSATION FOR THIS DRAWING IS TO BE DETERMINED BY PIERCE SALES CO. INC. ALL RIGHTS RESERVED. PIERCE SALES CO. INC., d/b/a RESTAURANT EQUIPMENT WORLD.
AutoCAD SHX Text
%%UPLUMBING ROUGH-IN NOTES
AutoCAD SHX Text ELECTRICAL CONTRACTOR SHALL PROVIDE PROPERLY GROUNDED AND DEDICATED CIRCUITS AND COMMUNICATION CABLE TO ALL REGISTERS. EACH LOCATION TO HAVE A SEPARATE ISOLATED 15 AMP 120 VOLT RECEPTACLE (VERIFY ABOVE WITH MANUFACTURER).
AutoCAD SHX Text ELECTRICAL CONTRACTOR TO EXAMINE SHOP DRAWINGS FOR HOOD FAN, FIRE PROTECTION SYSTEM & CONTROL CABINET. PROVIDE WIRING & CONDUIT FOR FANS, RELAYS, & SHUNT TRIP EQUIPMENT AS REQUIRED. ALSO INTERCONNECTION OF FIRE SYSTEM, PULL STATION & REQUIRED CONDUIT AS LISTED IN SHOP DRAWINGS. COORDINATE WITH KITCHEN EQUIPMENT CONTRACTOR.
AutoCAD SHX Text ALL ROUGH-INS TO BE IN STRICT ACCORDANCE WITH ALL LOCAL, STATE, AND NATIONAL CODE REQUIREMENTS.
AutoCAD SHX Text ELECTRICAL CONTRACTOR TO PROVIDE ROUGH-IN AND FINAL CONNECTION TO ALL FOOD SERVICE EQUIPMENT.
AutoCAD SHX Text THIS DRAWING LOCATES ELECTRICAL POINTS OF CONNECTION FOR FOOD SERVICE EQUIPMENT PROVIDED BY PIERCE SALES COMPANY, INC. AND DOES NOT INDICATE UTILITY ROUGH-IN LOCATIONS. THE DESIGN OF SYSTEMS TO ACCOMMODATE THESE REQUIREMENTS IS THE RESPONSIBILITY OF OTHERS AND IS TO BE IN ACCORDANCE WITH ALL APPLICABLE CODES AND MEET WITH THE APPROVAL OF ALL GOVERNING AUTHORITIES. LOCATIONS, SIZES AND HEIGHTS ABOVE FLOOR ARE APPROXIMATE AS THEY WILL OCCUR ON EQUIPMENT ITEMS SHOWN.
AutoCAD SHX Text ELECTRICAL CONTRACTOR TO PROVIDE WIRE & CONDUIT FOR CONTROLS BETWEEN WALK-IN COOLER & ICE MAKER CONDENSING UNITS. SEE SHOP DRAWINGS.
AutoCAD SHX Text 10.
AutoCAD SHX Text 6.
AutoCAD SHX Text 5.
AutoCAD SHX Text 8.
AutoCAD SHX Text 9.
AutoCAD SHX Text 7.
AutoCAD SHX Text
WHERE POSSIBLE ALL LINES SHALL BE INSIDE WALLS AND STUBBED OUT AT HEIGHTS SHOWN.
AutoCAD SHX Text
%%UELECTRICAL ROUGH-IN NOTES
AutoCAD SHX Text
DO NO SCALE THIS DRAWING, USE DIMENSIONS SHOWN.
AutoCAD SHX Text
ALL OUTLETS IN FLOORS TO BE STUBBED UP 3" A.F.F.
AutoCAD SHX Text
HEIGHTS SHOWN ARE TO THE CENTER LINE OF BOXES.
AutoCAD SHX Text 1.
AutoCAD SHX Text 3.
AutoCAD SHX Text 4.
AutoCAD SHX Text 2.