PW_26-05B_Animal_Shelter_Phase_I_Furnace_plans_bid_set.pdf

PDF 7 MB Posted

Attached to
Napa County Animal Shelter Phase I Furnace Replacement
Solicitation number
PW 26-05B
Issued by
Napa County, California

About this file

This is a bid set of construction drawings and specifications for the Napa County Animal Shelter Phase I Furnace Replacement Project (PW 26-05B), prepared by YEI Engineers, Inc. and Brokaw Design for Napa County, California. The project involves demolishing two existing floor-mounted vertical gas furnaces (F-4 and F-5) and installing new high-efficiency, multi-stage condensing gas furnaces complete with insulated return air plenum boxes, supply and return ductwork, combustion air and exhaust vent piping, wall-mounted thermostats with LCD displays, duct smoke detectors, condensate neutralizers, and a new mechanical direct digital control system using BACnet communication protocol. The scope of work includes seismic anchoring of furnaces to the existing concrete floor with rubber pads, installation of a new wall-mounted Carrier Climavision Central Control Unit for real-time performance monitoring, and comprehensive cleaning of existing HVAC air-distribution systems serving heat recovery ventilation units and exhaust fans per National Air Duct Cleaners Association standards. The project also requires testing, adjusting, and balancing of new furnaces and associated ceiling air outlets, with acceptance testing performed by a certified mechanical acceptance test technician and documented on nonresidential certificate of acceptance forms in compliance with the California Energy Code.

The furnace schedule specifies two Carrier 59SU5B units rated at 100 MBH maximum input and 97 MBH minimum output with 95.0 percent AFUE efficiency, serving different facility zones with varying airflow requirements (2,255 CFM maximum and 430 CFM minimum for cooling, with 0.5 inches water gauge external static pressure). The drawings are based on a 60 percent submittal dated December 15, 2025, and a 100 percent submittal dated July 16, 2026, with a registered professional engineer stamp expiring September 30, 2027. Delegated design responsibility is assigned to the contractor for plenum box design, plenum box bracing and anchorage, vertical ductwork bracing, and furnace bracing and anchorage, which must be designed by a California civil or structural engineer and submitted for owner and building department review with allowance for multiple review cycles. The contractor bears responsibility for field verification of existing conditions, coordination with all trades, protection of adjacent surfaces, complete functionality of all equipment including electrical and control items, and maintenance of as-built documentation for all existing and new services. All work shall conform to the 2025 California Building Code, California Mechanical Code, California Plumbing Code, California Energy Code, and latest county adopted codes.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ANIMAL SHELTER PHASE I

NAPA COUNTY

12-15-202560% SUBMITTAL

10-28-2025

FURNACE REPLACEMENT

07-16-2026100% SUBMITTAL2

PROJECT, PW 26-O5B

T002

PW HH

NTS

SHEET INDEX

942 HARTLE COURT, NAPA, CA 94558

MECHANICAL

SHEET

COUNT

SHEET

NUMBER SHEET TITLE

M001 MECHANICAL GENERAL NOTES

M002 MECHANICAL ABBREVIATIONS AND LEGEND

M003 MECHANICAL SCOPE OF WORK AND SEQUENCING

M004 MECHANICAL EQUIPMENT SCHEDULES

M101 MECHANICAL ENLARGED FIRST FLOOR DEMOLITION PLAN

M401 MECHANICAL CONTROL SEQUENCE OF OPERATIONS

M501 MECHANICAL DETAILS

PLUMBING

SHEET

COUNT

SHEET

NUMBER SHEET TITLE

P001 PLUMBING GENERAL NOTES AND SCOPE OF WORK

P002

P101 PLUMBING FIRST FLOOR DEMOLITION PLAN

ELECTRICAL

SHEET

COUNT SHEET TITLE

E001 ELECTRICAL GENERAL NOTES, ABBREVIATIONS AND

SYMBOLS

E002 ELECTRICAL SINGLE LINE

E101 E201

GENERAL

SHEET

COUNT

SHEET

NUMBER SHEET TITLE

1 T001 COVER PAGE

2 T002 SHEET INDEX

SHEET

NUMBER

M102 MECHANICAL ENLARGED FIRST FLOOR DEMOLITION PLAN

M201 MECHANICAL ENLARGED FIRST FLOOR NEW WORK PLAN

M202 MECHANICAL ENLARGED FIRST FLOOR NEW WORK PLAN

M301 MECHANICAL ISOMETRIC VIEWS

PLUMBING LEGEND, ABBREVIATIONS AND SCHEDULE

P201 PLUMBING FIRST FLOOR NEW WORK PLAN

P301 PLUMBING DIAGRAM

P401 PLUMBING TYPICAL DETAILS

ELECTRICAL FIRST FLOOR DEMOLITION PLAN

ELECTRICAL FIRST FLOOR NEW WORK PLAN

E301 ELECTRICAL DETAILS

M100 MECHANICAL GROUND KEY PLAN

M110 MECHANICAL ROOF DEMOLITION PLAN

M210 MECHANICAL ROOF NEW WORK PLAN

STRUCTURAL

SHEET

COUNT

SHEET

NUMBER SHEET TITLE

S501 STRUCTURAL DETAILS3

PROJECT PW 26-05B

NAPA COUNTY ANIMAL SHELTER PHASE I

FURNACE REPLACEMENT PROJECT, PW 26-05B

AutoCAD SHX Text Drawing No.

AutoCAD SHX Text Cad File:

AutoCAD SHX Text Xref:

AutoCAD SHX Text Drawn By

AutoCAD SHX Text Date:

AutoCAD SHX Text Scale:

AutoCAD SHX Text Checked By

AutoCAD SHX Text Sheet Title

AutoCAD SHX Text Description

AutoCAD SHX Text

ADDENDUMS

AutoCAD SHX Text No.

AutoCAD SHX Text Date

AutoCAD SHX Text If this drawing is not 22" x 34", it is a reduced print - scale accordingly. All rights reserved. Material may not be reproduced in any form without permission from YEI engineers, Inc.

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text L

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text

NO. M38106

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text

EX. 09/30/26

(E) 4" CONC

SLAB

4" THICK CONC PAD;

COORD PLAN GEOMETRY

W/ PURCHASED EQUIP,

SEE MEP DWGS.

PROVIDE 6" MINIMUM

EDGE DISTANCE TO

ANCHORS

8"Ø x 5" HVY DUTY CONC

SCREW ANCHORS @ 12"

OC, EA WAY; 2 12" EMBED

INTO (E) CONC, TYP

#4@ 6" O.C. EACH

WAY CENTERED.

A

F

F

12-15-2025

DATE SIGNED: 7/16/2026

BrokawDesign www.BrokawDesign.com

Tim Lengyel, P.E., S.E.

415-999-0323

ANIMAL SHELTER PHASE I

NAPA COUNTY

12-15-202560% SUBMITTAL1

FURNACE REPLACEMENT

07-16-2026100% SUBMITTAL2

PROJECT, PW 26-O5B

S501

TFL TFL

1/8" = 1'-0"

FURNACE F-4 AND F-5

STRUCTURAL DETAILS

NO SCALE

DETAIL

FURNACE F-5 SEE MECHANICAL DWGS.

(F-4 SIM, SEE MECHANICAL DWGS.)

EXISTING 4" SLAB ON GRADE

4" HOUSEKEEPING PAD SEE 2

S501

MAINTAIN 6" CLEAR TO ANCHORS

MAINTAIN 6" CLEAR TO ANCHORS

A. DESIGN BASIS

A.1. THIS ANCHORAGE AND PAD HAS BEEN DESIGNED IN ACCORDANCE WITH THE 2025 CBC.

A.2. STRUCTURE DESIGNED FOR SEISMIC LOADS BASED ON THE FOLLOWING PARAMETERS:

BUILDING CATEGORY = II = STANDARD

SITE CLASS = D (ASSUMED)

MAX. 0.2 SEC. SPECTRAL RESPONSE ACCELERATION, SS = 2.21g MAX. 1.0 SEC. SPECTRAL RESPONSE ACCELERATION, S1 = 0.77g DESIGN SPECTRAL RESPONSE AT SHORT PERIODS; SDS = 1.54g

SEISMIC DESIGN CATEGORY = D

A.3. PROVIDE SPECIAL INSPECTION OF CONCRETE AND EQUIPMENT ANCHORAGE.

B. GENERAL NOTES

B.1. ALL WORK TO CONFORM TO REQUIREMENTS OF ALL PUBLICATIONS AND NOTES LISTED UNDER "DESIGN BASIS".

B.2. ARCHITECTURAL DRAWINGS, MECHANICAL/ELECTRICAL/PLUMBING DRAWINGS AND ALL OTHER DRAWINGS AS REQUIRED SHALL BE USED IN CONJUNCTION WITH STRUCTURAL DRAWINGS TO DEVELOP DETAILS AND DIMENSIONS FOR SHOP DRAWINGS, FABRICATION, ERECTION AND CONSTRUCTION. CONTRACTOR IS TO COORDINATE EQUIPMENT, SUPPORT CONDITIONS AND DIMENSIONS FOR SUPPORTING BEAMS, FRAMES AND OPENINGS FOR

MECHANICAL EQUIPMENT AND PROVIDE THIS INFORMATION FOR REVIEW.

B.3. DO NOT SCALE DRAWINGS.

B.4. CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER/OWNER/ENGINEER IMMEDIATELY UPON DISCOVERY OF

CONFLICTS IN THE DRAWINGS AND SPECIFICATIONS.

B.5. THE CONTRACTING OFFICER/OWNER/ENGINEER MAY PERIODICALLY VISIT THE SITE TO OBSERVE THE PROGRESS AND GENERAL QUALITY OF THE CONSTRUCTION. THESE VISITS ARE NOT INTENDED TO REPLACE THE

CONTRACTOR'S RESPONSIBILITY FOR QUALITY CONTROL OR SPECIAL INSPECTION.

B.6. THE CONTRACTOR IS TO VERIFY ALL EXISTING CONDITIONS AND ALL DIMENSIONS IN FIELD PRIOR TO START OF CONSTRUCTION AND PROTECT AND MAINTAIN ALL EXISTING CONSTRUCTION AND ITS CONTENTS IN FULL.

B.7. THE CONTRACTOR SHALL MAINTAIN A SET OF LATEST REVIEWED SHOP DRAWINGS ON JOB SITE.

B.8. THE STRUCTURE HAS BEEN DESIGNED TO BE STABLE AND SELF SUPPORTING AFTER THE CONSTRUCTION IS COMPLETE. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY FOR THE BUILDING'S STABILITY DURING CONSTRUCTION. THIS RESPONSIBILITY ALSO INCLUDES BUT IS NOT LIMITED TO METHOD AND SEQUENCE OF

ERECTION, TEMPORARY SHORING AND TEMPORARY BRACING.

B.9. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO FOLLOW ALL APPLICABLE SAFETY CODES AND REGULATIONS

DURING ALL PHASES OF CONSTRUCTION.

B.10. SHOULD ANY INFORMATION ON THE STRUCTURAL DRAWINGS CONFLICT WITH THE SPECIFICATIONS OR ANY OTHER PART OF THE DRAWINGS, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AND AN INTERPRETATION WILL BE

GIVEN.

B.11. ALL SECTIONS, DETAILS, NOTES, DIMENSIONS AND CONDITIONS ARE APPLICABLE AT ANY OTHER LOCATION WHERE CONDITIONS AND DETAILS ARE SIMILAR BUT ARE NOT SPECIFICALLY NOTED AS SUCH OR ARE NOT SHOWN.

B.12. ALL PROPRIETARY ANCHORING SYSTEMS TO BE INSTALLED INTO CONCRETE OR MASONRY ELEMENTS IN STRICT

ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.

C. CONCRETE NOTES

C.1. ALL WORK TO CONFORM TO THE REQUIREMENTS OF THE FOLLOWING PUBLICATIONS:

C.1.1. ACI "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318-19) AND "DETAILS AND DETAILING

OF CONCRETE REINFORCEMENT" (ACI 315-LATEST EDITION).

C.2. MINIMUM COMPRESSIVE STRENGTH OF CONCRETE AT 28 DAYS:

4000 PSI (NORMAL WEIGHT) AT ALL CONCRETE ELEMENTS.

MAXIMUM SLUMP: 5"

MAXIMUM WATER/CEMENT RATIO: 0.45

NOMINAL MAXIMUM AGGREGATE SIZE: 1/2"

PRIOR TO PLACING CONCRETE, MIX DESIGNS SHALL BE SUBMITTED FOR REVIEW.

C.1. CONCRETE MIXTURE COMPONENTS SHALL CONFORM TO THE FOLLOWING:

C.1.1. CEMENT - ASTM C150 , TYPE II

C.1.2. COURSE AGGREGATE - ASTM C33 (NORMAL WEIGHT)

C.1.3. FINE AGGREGATE - ASTM C33

C.1.4. WATER - SHALL BE POTABLE WATER

C.1.5. ADMIXTURES

C.1.5.1. ASTM C260 AIR ENTRAINMENT

C.1.5.2. ASTM C618 POZZOLAN & FLY ASH

C.1.5.3. ASTM C494 WATER REDUCING, RETARDING, ACCELERATION

C.2. ALL BAR REINFORCING FOR CONCRETE SHALL CONFORM TO ASTM A 615 GRADE 60 (DEFORMED). CERTIFIED MILL TEST REPORTS SHALL BE SUBMITTED TO THE INSPECTOR FOR EACH SHIPMENT OF SUCH REINFORCEMENT.

C.3. UNLESS OTHERWISE SHOWN, LOCATE REINFORCING BARS WITH FOLLOWING CLEAR DIMENSION TO FACE OF

CONCRETE:

INTERIOR SURFACES 1.5"

C.4. CONCRETE ACCESSORIES MUST BE ADEQUATE TO MAINTAIN REINFORCING ACCURATELY IN PLACE AND BE

NON-CORROSIVE, NON-STAINING TYPE.

C.5. LAP ALL BAR REINFORCING IN CONCRETE ELEMENTS 48 BAR DIAMTERS

C.6. LIQUID MEMBRANE FORMING CURING COMPOUNDS SHALL COMPLY WITH ASTM C 309, TYPE I, CLASS A. APPLY AS

SOON AS POSSIBLE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.

D. DELEGATED DESIGN NOTES

D.1. DESIGN, PROVIDE AND INSTALL FULLY FUNCTIONAL PLENUM BOXES, PLENUM BOX BRACING AND ANCHROAGE, DUCTWORK BRACING, FURNACE BRACING AND ANCHORAGE FOR FURNACE F-4 AND FURNACE F-5. DESIGN PER

ENGINEER RETAINED BY THE CONTRACTOR.

D.2. SEE OTHER DRAWINGS FOR INFORMATION NOT SHOWN.

D.3. CONTRACTOR SHALL COORDINATE ACTUAL LAYOUT WITH ACTUAL EQUIPMENT PROVIDED.

D.4. FURNACE BRACING AND ANCHORAGE, PLENUM BOXES, PLENUM BOX BRACING AND ANCHORAGE AND VERTICAL DUCTWORK BRACING AND ANCHORAGE TO BE DESIGNED BY A CALIFORNIA CIVIL OR STRUCTURAL ENGINEER AND CONSTRUCTED IN ACCORDANCE WITH SPECIFICATIONS AND TO SUPPORT IT'S OWN WEIGHT, UNIT WEIGHT, IMPOSED LIVE, WIND, SEISMIC LOADS AS WELL AS ANY OTHER MECHANICAL AND ELECTRICAL EQUIPMENT THAT SHALL BE SUPPORTED FROM IT. SEE "DESIGN BASIS" IN STRUCTURAL GENERAL NOTES FOR STRUCTURAL CRITERIA.

PROVIDED ADDITIONAL CONTRACTOR TO INCLUDE MULTIPLE REVIEWS IN PROJECT SCHEDULE. ALLOW 2 WEEKS

FOR EACH ARCHITECTURAL AND STRUCTURAL REVIEW.

D.5. CONTRACTOR SHALL SUBMIT DESIGN DRAWINGS AND CALCULATIONS. THESE DRAWINGS AND CALCULATIONS WILL CONSTITUTE A DEFERRED SUBMITTAL TO THE BUILDING DEPARTMENT. THE SUBMITTAL MUST BE REVIEWED BY THE OWNER'S ENGINEER PRIOR TO SUBMISSION TO THE BUILDING DEPARTMENT. DESIGNER SHALL RESPOND TO ALL COMMENTS FROM THE BUILDING DEPARTMENT AND OWNER'S REPRESENTATIVE AND MAKE REVISIONS AS REQUIRED BY BUILDING DEPARTMENT AND OWNER'S REPRESENTATIVE. CONTRACTOR SHALL ALLOCATE TIME FOR MULTIPLE BUILDING DEPARTMENT AND OWNER REVIEWS INTO THEIR CONSTRUCTION SCHEDULE. THE STRUCTURAL ENGINEER OF RECORD WILL ISSUE A CONFORMANCE LETTER FOR INCLUSION WITH SUBMISSION TO THE BUILDING

DEPARTMENT. NO SCALE

DETAIL

PLENUM AND BRACING/ANCHORAGE TO

BE A DESIGNED BY CONTRACTOR'S

ENGINEER. SEE GENERAL NOTES THIS

PAGE

NO SCALE

PARTIAL GROUND FLOOR PLAN

A

EQUIPMENT PAD SEE 2

S501

S501

PLENUM AND PLENUM ANCHORAGE DESIGNED BY CONTRACTOR'S ENGINEER BASED ON ACTUAL EQUIPMENT.

SEE GENERAL NOTES AND

S501

S501

EQUIPMENT PAD SEE 2

S501

S501

PLENUM AND PLENUM ANCHORAGE DESIGNED BY

CONTRACTOR'S ENGINEER BASED ON ACTUAL EQUIPMENT.

SEE GENERAL NOTES AND

S501

S501

EXISTING 8" MASONRY WALL,

WHERE OCCURS. VIF. PER

RECORD DRAWINGS

MASONRY IS LIGHT WEIGHT

BLOCK, F'm=1500PSI, REINFORCED WITH #5

VERTICALLY AND

HORIZONTALLY @ 40" O.C.

PROVIDE ANGLE FEET PER

CONTRACTOR'S ENGINEER AND

ACTUAL PLENUM DESIGN

PROVIDE ANCHORAGE TO

WALLS FOR UNIT, PLENUM

AND DUCTWORK

CONTRACTOR'S ENGINEER

AND ACTUAL PLENUM

DESIGN

FURNACE BRACING/ANCHORAGE TO BE

A DESIGNED BY CONTRACTOR'S

ENGINEER. SEE GENERAL NOTES THIS

PAGE

VERTICAL DUCTWORK

BRACING/ANCHORAGE TO BE DESIGNED

BY CONTRACTOR'S ENGINEER. SEE

GENERAL NOTES THIS PAGE

AutoCAD SHX Text

EQUIP.

AutoCAD SHX Text

GET ACQUAINTED

AutoCAD SHX Text

EQUIP.

AutoCAD SHX Text

PUPPIES &

AutoCAD SHX Text

SMALL BREEDS

AutoCAD SHX Text

CAT & DOG

AutoCAD SHX Text

RECEIVING

AutoCAD SHX Text

HALL

AutoCAD SHX Text

HALL

AutoCAD SHX Text F

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text

AutoCAD SHX Text Drawing No.

AutoCAD SHX Text Cad File:

AutoCAD SHX Text Xref:

AutoCAD SHX Text Drawn By

AutoCAD SHX Text Date:

AutoCAD SHX Text Scale:

AutoCAD SHX Text Checked By

AutoCAD SHX Text Sheet Title

AutoCAD SHX Text If this drawing is not 22" x 34", it is a reduced print - scale accordingly. All rights reserved. Material may not be reproduced in any form without permission from YEI engineers, Inc.

AutoCAD SHX Text Description

AutoCAD SHX Text

ADDENDUMS

AutoCAD SHX Text No.

AutoCAD SHX Text Date

AutoCAD SHX Text

STRUCTURAL GENERAL NOTES

AutoCAD SHX Text

SCALE: 1/8" = 1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

20 FT

AutoCAD SHX Text S5196

AutoCAD SHX Text 9/30/27

AutoCAD SHX Text No.

AutoCAD SHX Text Exp.

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text P

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text C

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text M

AutoCAD SHX Text O

AutoCAD SHX Text T

AutoCAD SHX Text H

AutoCAD SHX Text Y

AutoCAD SHX Text F

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text L

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text G

AutoCAD SHX Text Y

AutoCAD SHX Text E

AutoCAD SHX Text L

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text C

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

AutoCAD SHX Text A

L

12-15-202560% SUBMITTAL

10-28-2025

FURNACE REPLACEMENT

07-16-2026100% SUBMITTAL2

PROJECT, PW 26-O5B

M001

AS HH

NTS

MECHANICAL

GENERAL NOTES

AutoCAD SHX Text Drawing No.

AutoCAD SHX Text Cad File:

AutoCAD SHX Text Xref:

AutoCAD SHX Text Drawn By

AutoCAD SHX Text Date:

AutoCAD SHX Text Scale:

AutoCAD SHX Text Checked By

AutoCAD SHX Text Sheet Title

AutoCAD SHX Text Description

AutoCAD SHX Text

ADDENDUMS

AutoCAD SHX Text No.

AutoCAD SHX Text Date

AutoCAD SHX Text If this drawing is not 22" x 34", it is a reduced print - scale accordingly. All rights reserved. Material may not be reproduced in any form without permission from YEI engineers, Inc.

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text L

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text

NO. M38106

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text

EX. 09/30/26

AutoCAD SHX Text

1. CONTRACTOR SHALL BE RESPONSIBLE FOR EXAMINING ALL DRAWINGS, FIELD CONTRACTOR SHALL BE RESPONSIBLE FOR EXAMINING ALL DRAWINGS, FIELD VERIFICATION OF EXISTING CONDITIONS AND COORDINATING WITH ALL OTHER TRADES PRIOR TO START OF WORK AND PURCHASING OF EQUIPMENT. ADVISE THE OWNER IN WRITING IN THE EVENT A CONFLICT OCCURS BETWEEN THE REQUIREMENTS OF THE CONTRACT DOCUMENTS AND ACTUAL FIELD CONDITIONS. THE CONTRACTOR SHALL BEAR ALL COSTS FOR RELOCATION OF EQUIPMENT, PIPING, ETC., FROM FAILURE TO PROPERLY COORDINATE INSTALLATIONS AND ADVISE OF THE CONFLICT IN WRITING PRIOR TO INSTALLATION. 2. IN CASE OF DIFFERENCE BETWEEN BUILDING CODES, SPECIFICATIONS, IN CASE OF DIFFERENCE BETWEEN BUILDING CODES, SPECIFICATIONS, INDUSTRY STANDARDS, UTILITY COMPANY REGULATIONS, FIRE INSURANCE CARRIER'S REQUIREMENTS AND CONTRACT DOCUMENTS, THE MOST STRINGENT SHALL GOVERN. PROMPTLY NOTIFY THE OWNER IN WRITING OF ANY SUCH DIFFERENCE. 3. EQUIPMENT, DUCTWORK AND PIPING AS SHOWN ON DRAWINGS ARE EQUIPMENT, DUCTWORK AND PIPING AS SHOWN ON DRAWINGS ARE SCHEMATIC AND SHALL BE FABRICATED AND INSTALLED ON ACTUAL FIELD MEASUREMENT. DO NOT SCALE DRAWINGS FOR EXACT LOCATION OF EQUIPMENT, DUCTWORK AND PIPING. COORDINATE WITH OTHER TRADES AS REQUIRED. 4. PLANS ARE BASED ON ANTICIPATED EQUIPMENT SIZE AND CONFIGURATION. PLANS ARE BASED ON ANTICIPATED EQUIPMENT SIZE AND CONFIGURATION. CONTRACTOR SHALL MODIFY ARRANGEMENT TO SUIT ACTUAL PURCHASED EQUIPMENT AS REQUIRED FOLLOWING THE CRITERIA ESTABLISHED BY THESE PLANS. DEPARTURES FROM THE CONTRACT DRAWING RESULTING FROM CHANGES IN EQUIPMENT SIZES AND CONFIGURATIONS, OR RE-ARRANGEMENTS TO ACCOMMODATE FIELD CONDITIONS SHALL BE SUBMITTED IN DETAIL FOR THE OWNER'S APPROVAL. 5. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION AND SHALL REPAIR CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION AND SHALL REPAIR ADJACENT EXISTING AND/OR NEW SURFACES, AREAS AND PROPERTY THAT MAY BE DAMAGED AS A RESULT OF ANY DEMOLITION AND/OR NEW WORK. 6. CONFORM TO LATEST NFPA 90A "STANDARD FOR THE INSTALLATION OF AIR CONFORM TO LATEST NFPA 90A "STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS". 7. COORDINATE INSTALLATION OF ALL EQUIPMENT, DUCTWORK AND PIPING WITH COORDINATE INSTALLATION OF ALL EQUIPMENT, DUCTWORK AND PIPING WITH OTHER TRADES PRIOR TO INSTALLATION. ENSURE THAT ALL CONTROL DEVICES, ACCESS PANELS IN FINISHED SPACES, OTHER THAN THAT SHOWN, CONTRACTOR SHALL COORDINATE EXACT LOCATION OF PANELS PRIOR TO INSTALLATION. INSTALL EQUIPMENT, DUCTWORK AND PIPING TO BEST SUIT FIELD CONDITIONS AND COORDINATE WITH OTHER TRADES. 8. DUCT SIZES SHOWN ARE MINIMUM INSIDE DIMENSION. DUCT SIZES SHOWN ARE MINIMUM INSIDE DIMENSION. 9. EXACT LOCATION OF CEILING MOUNTED EQUIPMENT, AIR INLETS AND OUTLETS EXACT LOCATION OF CEILING MOUNTED EQUIPMENT, AIR INLETS AND OUTLETS INCLUDING ACCESS PANELS SHALL BE COORDINATED WITH THE ARCHITECTURAL REFLECTED CEILING PLAN. COORDINATE CEILING MOUNTED EQUIPMENT, AIR INLETS AND OUTLETS WITH CEILING SUPPORTS MEMBERS AND LOCATE CLEAR OF CEILING MEMBERS. 10. ALL NEW MATERIALS AND EQUIPMENT INSTALLED ABOVE CEILING SHALL BE ALL NEW MATERIALS AND EQUIPMENT INSTALLED ABOVE CEILING SHALL BE NON-COMBUSTIBLE AND U.L. APPROVED. ALL NEW WIRING SHALL BE NON-COMBUSTIBLE AND SHALL BE ENCLOSED IN METAL CONDUIT. 11. PROVIDE READILY VISIBLE NON-FUSIBLE DISCONNECT SWITCHES FOR ALL PROVIDE READILY VISIBLE NON-FUSIBLE DISCONNECT SWITCHES FOR ALL NEW EQUIPMENT. COORDINATE WITH OTHER TRADES. 12. HANDLE, STORE AND INSTALL ALL EQUIPMENT, PIPING AND DUCTWORK PER HANDLE, STORE AND INSTALL ALL EQUIPMENT, PIPING AND DUCTWORK PER MANUFACTURER'S INSTRUCTIONS. ALL EQUIPMENT, PIPING AND DUCTWORK SHALL BE PROTECTED FROM THE WEATHER ELEMENTS. 13. CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETE FUNCTIONALITY OF CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETE FUNCTIONALITY OF THE EQUIPMENT INCLUDING HIGH VOLTAGE, LOW VOLTAGE AND CONTROL ITEMS ASSOCIATED WITH THE PROJECT. 14. PROVIDE EQUIPMENT CLEARANCES IN ACCORDANCE WITH THE PROVIDE EQUIPMENT CLEARANCES IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND INSTRUCTIONS. 15. EQUIPMENT OF HIGHER ELECTRICAL CHARACTERISTICS MAY BE FURNISHED EQUIPMENT OF HIGHER ELECTRICAL CHARACTERISTICS MAY BE FURNISHED PROVIDED SUCH PROPOSED EQUIPMENT IS APPROVED IN WRITING AND CONNECTING ELECTRICAL SERVICES, CIRCUIT BREAKERS, AND CONDUIT SIZES ARE APPROPRIATELY MODIFIED WITHOUT COST TO THE OWNER. IF MINIMUM ENERGY RATINGS OR EFFICIENCIES ARE SPECIFIED, EQUIPMENT SHALL COMPLY WITH REQUIREMENTS. 16. CONTRACTOR IS TO MAINTAIN RECORDED "AS-BUILT" INFORMATION ON ALL CONTRACTOR IS TO MAINTAIN RECORDED "AS-BUILT" INFORMATION ON ALL EXISTING SERVICES UNCOVERED DURING CONSTRUCTION AND ALL NEW SERVICES BEING INSTALLED. "AS-BUILT" INFORMATION SHALL BE CLEARLY MARKED IN COLORED PENCIL ON A PRINT OF THE CONTRACT DRAWING. RECORDED INFORMATION SHALL INCLUDE ROUTING AND INVERT ELEVATIONS. AT THE COMPLETION OF THE CONTRACT, THE CONTRACTOR SHALL TURN RECORDED "AS-BUILT" INFORMATION OVER TO THE OWNER AND CONTRACTOR TO BE COORDINATED WITH AS BUILT REQUIREMENTS IN SPECIFICATION. 17. ARRANGE ALL PIPING WITHIN STRUCTURES NEATLY ALONG WALLS AND/OR IN ARRANGE ALL PIPING WITHIN STRUCTURES NEATLY ALONG WALLS AND/OR IN NEAT, HORIZONTAL GROUPS AND MAINTAIN REQUIRED SLOPES. 18. DO NOT SLEEVE STRUCTURAL MEMBERS WITHOUT CONSENT OF A LICENSED DO NOT SLEEVE STRUCTURAL MEMBERS WITHOUT CONSENT OF A LICENSED STRUCTURAL ENGINEER AND THE OWNER. 19. CONTRACTOR SHALL REMOVE, RELOCATE, REPLACE WITH NEW AND/OR CONTRACTOR SHALL REMOVE, RELOCATE, REPLACE WITH NEW AND/OR RECONNECT ALL EXISTING SERVICES AS REQUIRED BY NEW CONSTRUCTION. 20. INSTALL ALL DUCTS AND PIPING CONCEALED IN FURRED CEILING AND INSTALL ALL DUCTS AND PIPING CONCEALED IN FURRED CEILING AND CHASES UNLESS OTHERWISE INDICATED. 21. PROVIDE A HANGER NOT MORE THAN 12-INCHES FROM THE POINT OF PROVIDE A HANGER NOT MORE THAN 12-INCHES FROM THE POINT OF CHANGE OF DIRECTION OF A DUCT AND PIPE RUN IN BOTH HORIZONTAL AND VERTICAL PLANE. 22. SUPPORTS FOR ALL DUCTWORK AND PIPING SHALL BE IN ACCORDANCE WITH SUPPORTS FOR ALL DUCTWORK AND PIPING SHALL BE IN ACCORDANCE WITH THE LATEST SMACNA "GUIDELINES FOR SEISMIC RESTRAINTS OF MECHANICAL SYSTEMS AND PIPING SYSTEMS" AND MSS SP-58 AND SP-69. DUCTWORK AND PIPING HANGERS SHALL BE DESIGNED TO SUPPORT THE WEIGHT OF DUCTWORK AND PIPING INCLUDING THE WEIGHT OF THE CONTENTS OF THE PIPING. 23. SECURELY FASTEN DUCTWORK AND PIPING WITHIN STRUCTURES TO THE SECURELY FASTEN DUCTWORK AND PIPING WITHIN STRUCTURES TO THE BUILDING CONSTRUCTION BY MEANS OF HANGERS, SUPPORTS, GUIDES, ANCHORS, AND SWAY BRACES TO MAINTAIN DUCTWORK AND PIPING ALIGNMENT, TO PREVENT SAGGING, AND TO PREVENT NOISE AND EXCESSIVE STRAIN ON DUCTWORK AND PIPING DUE TO MOVEMENT UNDER OPERATING CONDITIONS. 24. CERTAIN VERTICAL AND HORIZONTAL OFFSETS ARE SHOWN IN DUCTWORK CERTAIN VERTICAL AND HORIZONTAL OFFSETS ARE SHOWN IN DUCTWORK AND PIPING ON PLANS TO INDICATE THE GENERAL POSITION RELATIONSHIP OF THE SYSTEMS. PROVIDE ADDITIONAL OFFSETS SIMILAR TO THOSE SHOWN, AS REQUIRED TO COORDINATE WITH INSTALLATION REQUIREMENTS OF OTHER SYSTEMS. 25. CONTRACTOR TO PROVIDE SUBMITTALS IN ACCORDANCE WITH THE CONTRACT CONTRACTOR TO PROVIDE SUBMITTALS IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. 26. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF CALIFORNIA BUILDING STANDARDS CODE, INCLUDING BUT NOT LIMITED TO CALIFORNIA BUILDING CODE, CALIFORNIA MECHANICAL CODE, CALIFORNIA PLUMBING CODE, CALIFORNIA ENERGY CODE, CALIFORNIA GREEN BUILDING STANDARDS CODE, AND LATEST COUNTY ADOPTED CODE. 27. PRIOR TO OCCUPANCY, THE HVAC SYSTEMS SHALL BE BALANCED IN PRIOR TO OCCUPANCY, THE HVAC SYSTEMS SHALL BE BALANCED IN ACCORDANCE WITH (AABC) ASSOCIATED AIR BALANCE COUNCIL STANDARDS BY AN INDEPENDENT AIR BALANCE CONTRACTOR. CERTIFICATION SHALL BE PROVIDED BY THE CONTRACTOR FOR AIR BALANCE OF AIR CONDITIONING SYSTEMS. 28. SEQUENCE WORK TO AVOID CUTTING AND PATCHING. IF NECESSARY, REMOVE SEQUENCE WORK TO AVOID CUTTING AND PATCHING. IF NECESSARY, REMOVE AND REPAIR WALL/CEILING FOR ACCESS TO WORK ON THE MECHANICAL SYSTEMS (SEE ARCHITECTURAL PLANS). PATCH AND FINISH TO MATCH ADJACENT SURFACE. 29. PROVIDE ALL TRANSITION IN DUCTWORK REQUIRED TO CROSS PIPING OR PROVIDE ALL TRANSITION IN DUCTWORK REQUIRED TO CROSS PIPING OR OTHER OBSTRUCTIONS. MAINTAIN EQUIVALENT CROSS-SECTIONAL AREA WITH MINIMUM DUCT SIZE 6" INSIDE DIMENSION. DUCT SHALL TRANSITION BACK TO ORIGINAL SIZE UPON PASSING ANY OBSTRUCTIONS. 30. PROVIDE VOLUME DAMPERS FOR EACH BRANCH DUCTWORK. VOLUME PROVIDE VOLUME DAMPERS FOR EACH BRANCH DUCTWORK. VOLUME DAMPERS SHALL BE LOW LEAKAGE WITH SHAFT SEAL, AND REMOVABLE AND REVERSIBLE HANDLE. 31. ALL EQUIPMENT, FIXTURES, ETC. SHALL BE IN ACCORDANCE WITH ALL EQUIPMENT, FIXTURES, ETC. SHALL BE IN ACCORDANCE WITH MANUFACTURERS' INSTRUCTION. 32. DEMOLITION AND NEW INSTALLATION WORK SHALL BE PERFORMED CAREFULLY DEMOLITION AND NEW INSTALLATION WORK SHALL BE PERFORMED CAREFULLY TO AVOID DAMAGE TO SURFACES, STRUCTURES AND EQUIPMENT NOT BEING REMOVED. ANY DAMAGE INCURRED SHALL BE RESTORED TO ORIGINAL CONDITION WITHOUT ANY ADDITIONAL COST. 33. NOT ALL EXISTING SYSTEMS ARE SHOWN TO AID DRAWING INTERPRETATION NOT ALL EXISTING SYSTEMS ARE SHOWN TO AID DRAWING INTERPRETATION CLARITY. 34. THE EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE BASED ON THE EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE BASED ON INFORMATION CONTAINED IN THE ORIGINAL DESIGN "AS-BUILT" DOCUMENTS AND ON A LIMITED FIELD SURVEY. 35. CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL VERIFICATION AND CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL VERIFICATION AND COORDINATION OF EXISTING CONDITIONS. VERIFY EXISTING CONDITIONS IN THE FIELD PRIOR TO START OF DEMOLITION WORK. 36. PATCH AND REPAIR ALL EXISTING WALL, CEILING, ROOF AND/OR FLOOR PATCH AND REPAIR ALL EXISTING WALL, CEILING, ROOF AND/OR FLOOR OPENINGS FOR EXISTING EQUIPMENT BEING REMOVED, REINSTALLED AND/OR MODIFIED. MATCH EXISTING BUILDING MATERIALS. 37. TITLE 24 IS NOT REQUIRED FOR BUILDING OCCUPANCY TYPE I PER TITLE 24 IS NOT REQUIRED FOR BUILDING OCCUPANCY TYPE I PER CALIFORNIA ENERGY COMMISSION TITLE 24 STANDARDS SECTION 1.7. 38. PROVIDE POLLUTANT CONTROL PER 2013 CGBSC SECTION 5.504. PROVIDE POLLUTANT CONTROL PER 2013 CGBSC SECTION 5.504. 39. FLEXIBLE DUCT SHALL BE 5 FT. MAXIMUM IN LENGTH. DO NOT INSTALL FLEXIBLE DUCT SHALL BE 5 FT. MAXIMUM IN LENGTH. DO NOT INSTALL UCT SHALL BE 5 FT. MAXIMUM IN LENGTH. DO NOT INSTALL ALL BE 5 FT. MAXIMUM IN LENGTH. DO NOT INSTALL RIBBED TYPE FLEXIBLE DUCTWORK. 40. PROVIDE FLEXIBLE CONNECTIONS AT PIECES OF ISOLATED EQUIPMENT ONLY PROVIDE FLEXIBLE CONNECTIONS AT PIECES OF ISOLATED EQUIPMENT ONLY AS SHOWN ON THE DETAILS OR AS SPECIFIED. 41. REFER TO SPECIFICATIONS FOR ADDITIONAL RESPONSIBILITIES AS PART OF REFER TO SPECIFICATIONS FOR ADDITIONAL RESPONSIBILITIES AS PART OF THE CONTRACT DOCUMENTS. 42. VERIFY AT PROJECT SITE EXACT SIZE, LOCATION, INVERT ELEVATION, AND VERIFY AT PROJECT SITE EXACT SIZE, LOCATION, INVERT ELEVATION, AND CLEARANCE OF ALL EXISTING SERVICES BEING EXTENDED, RELOCATED, OR REMOVED. 43. PROVIDE A TIGHT SEAL OF INCOMBUSTIBLE MATERIAL AROUND ALL PIPES PROVIDE A TIGHT SEAL OF INCOMBUSTIBLE MATERIAL AROUND ALL PIPES WHICH PENETRATE FIRE SEPARATIONS. PROVIDE COLLARS OR TRIM RINGS AROUND PIPING TO RETAIN PACKING. 44. BEFORE PROCEEDING WITH ANY WORK THE CONTRACTOR SHALL SUBMIT FOR BEFORE PROCEEDING WITH ANY WORK THE CONTRACTOR SHALL SUBMIT FOR THE OWNER'S REPRESENTATIVE APPROVAL THEIR "SEQUENCE OF WORK PLAN" THAT DESCRIBES ALL THE WORK TO BE ACCOMPLISHED DURING THEIR CONTRACT. THE CONTRACTOR'S PLAN SHALL INCLUDE, BUT NOT NECESSARILY BE LIMITED TO: A. DESCRIPTION OF WHAT SYSTEM/SUBSYSTEM/EQUIPMENT THAT SHALL BE DESCRIPTION OF WHAT SYSTEM/SUBSYSTEM/EQUIPMENT THAT SHALL BE SHUTDOWN/ISOLATED/REPLACED ALONG WITH THE STARTING DATE AND DURATION OF THE SHUTDOWN PERIOD. B. A DETAILED DESCRIPTION OF THE WORK THAT WILL BE ACCOMPLISHED A DETAILED DESCRIPTION OF THE WORK THAT WILL BE ACCOMPLISHED DURING THE SHUTDOWN PERIOD. C. SIGN-OFF SHEET THAT INCLUDES THE OWNER'S REPRESENTATIVE SIGN-OFF SHEET THAT INCLUDES THE OWNER'S REPRESENTATIVE SIGNATURE APPROVING THE PARTICULAR SEQUENCE OF WORK REQUESTED PRIOR TO BEGINNING THE WORK AND THE OWNER'S REPRESENTATIVE SIGNATURE AUTHORIZING THE CONTRACTOR TO PLACE THE SYSTEM/EQUIPMENT BACK IN USE AFTER THE WORK HAS BEEN COMPLETED TO THE OWNER'S REPRESENTATIVE SATISFACTION.

MECHANICAL GENERAL NOTES

12-15-202560% SUBMITTAL

10-28-2025

FURNACE REPLACEMENT

07-16-2026100% SUBMITTAL2

PROJECT, PW 26-O5B

M002

AS HH

NTS

MECHANICAL

ABBREVIATIONS AND

LEGEND

AutoCAD SHX Text Drawing No.

AutoCAD SHX Text Cad File:

AutoCAD SHX Text Xref:

AutoCAD SHX Text Drawn By

AutoCAD SHX Text Date:

AutoCAD SHX Text Scale:

AutoCAD SHX Text Checked By

AutoCAD SHX Text Sheet Title

AutoCAD SHX Text Description

AutoCAD SHX Text

ADDENDUMS

AutoCAD SHX Text No.

AutoCAD SHX Text Date

AutoCAD SHX Text If this drawing is not 22" x 34", it is a reduced print - scale accordingly. All rights reserved. Material may not be reproduced in any form without permission from YEI engineers, Inc.

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text L

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text

NO. M38106

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text

EX. 09/30/26

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

ABBREV.

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

ROUND DUCTWORK, NET INSIDE DIMENSION

AutoCAD SHX Text 6%%C

AutoCAD SHX Text

DEMOLITION WORK

AutoCAD SHX Text

XX

AutoCAD SHX Text

XX

AutoCAD SHX Text

MECHANICAL EQUIPMENT TAG

AutoCAD SHX Text

POINT OF CONNECTION

AutoCAD SHX Text

POC

AutoCAD SHX Text Y

AutoCAD SHX Text X

AutoCAD SHX Text EXHAUST AIR GRILLE WITH DUCTWORK X-TYPE OF AIR INLET (REFER TO AIR OUTLET & INLET SCHEDULE) Y-EXHAUST AIR FLOW RATE, CFM

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DETAIL NUMBER

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

MECHANICAL LEGEND

AutoCAD SHX Text

FD

AutoCAD SHX Text

FIRE DAMPER

AutoCAD SHX Text Y

AutoCAD SHX Text X

AutoCAD SHX Text SUPPLY AIR DIFFUSER WITH DUCTWORK X-TYPE OF AIR OUTLET (REFER TO AIR OUTLET & INLET SCHEDULE) Y-SUPPLY AIR FLOW RATE, CFM

AutoCAD SHX Text Y

AutoCAD SHX Text X

AutoCAD SHX Text RETURN AIR GRILLE WITH DUCTWORK X-TYPE OF AIR INLET (REFER TO AIR OUTLET & INLET SCHEDULE) Y-RETURN AIR FLOW RATE, CFM

AutoCAD SHX Text

POINT OF DEMOLITION

AutoCAD SHX Text

POD

AutoCAD SHX Text

EXHAUST DUCT UP

AutoCAD SHX Text

DUCT SMOKE DETECTOR

AutoCAD SHX Text

DD

AutoCAD SHX Text T

AutoCAD SHX Text

THERMOSTAT

AutoCAD SHX Text

FLEXIBLE DUCT

AutoCAD SHX Text

SUPPLY DUCT UP

AutoCAD SHX Text

RETURN DUCT UP

AutoCAD SHX Text

BUILDING AREAS NOT IN SCOPE

AutoCAD SHX Text

KEY NOTE

AutoCAD SHX Text

MECHANICAL ABBREVIATIONS

AutoCAD SHX Text

SMOKE/FIRE DAMPER

AutoCAD SHX Text

SFD

AutoCAD SHX Text

AABC ASSOCIATED AIR BALANCING COUNCIL

AutoCAD SHX Text

ABBREV ABBREVIATIONS

AutoCAD SHX Text

ACCU AIR-COOLED CONDENSING UNIT

AutoCAD SHX Text

AD/AP ACCESS DOOR/ACCESS PANEL

AutoCAD SHX Text

AFF ABOVE FINISHED FLOOR

AutoCAD SHX Text

AI ANALOG INPUT

AutoCAD SHX Text

AO ANALOG OUTPUT

AutoCAD SHX Text

AMPS AMPERES

AutoCAD SHX Text

ASME AMERICAN SOCIETY OF MECHANICAL

AutoCAD SHX Text

ENGINEERS

AutoCAD SHX Text

AVE AVERAGE

AutoCAD SHX Text

BCU BUILDING CONTROL UNIT

AutoCAD SHX Text

BDD BACKDRAFT DAMPER

AutoCAD SHX Text

BOD BOTTOM OF DUCT / BASIS OF DESIGN

AutoCAD SHX Text

BOP BOTTOM OF PIPE (ABOVE FIN. FLR.)

AutoCAD SHX Text

BTUH BRITISH THERMAL UNITS PER HOUR

AutoCAD SHX Text

CD CEILING DIFFUSER/CONDENSATE

AutoCAD SHX Text

CFM CUBIC FEET PER MINUTE

AutoCAD SHX Text

CLG CEILING

AutoCAD SHX Text

CONC CONCRETE

AutoCAD SHX Text

CONT CONTINUATION

AutoCAD SHX Text

CPF CHEMICAL POT FEEDER

AutoCAD SHX Text

°F DEGREES FAHRENHEIT

AutoCAD SHX Text dBA A-WEIGHTED DECIBELS

AutoCAD SHX Text

DD DUCT SMOKE DETECTOR

AutoCAD SHX Text

DI DIGITAL INPUT

AutoCAD SHX Text

DIA DIAMETER

AutoCAD SHX Text

DN DOWN

AutoCAD SHX Text

DWG(S) DRAWING(S)

AutoCAD SHX Text

DB DRY BULB

AutoCAD SHX Text

(E) EXISTING

AutoCAD SHX Text

EA EXHAUST AIR

AutoCAD SHX Text

ER/EG EXHAUST REGISTER/EXHAUST GRILLE

AutoCAD SHX Text

EFF EFFICIENCY

AutoCAD SHX Text

ELECT ELECTRICAL

AutoCAD SHX Text

ELEV ELEVATION

AutoCAD SHX Text

EMCS ENERGY MONITORING AND CONTROL SYSTEM

AutoCAD SHX Text

ENT ENTERING

AutoCAD SHX Text

ESP EXTERNAL STATIC PRESSURE

AutoCAD SHX Text

EWT ENTERING WATER TEMPERATURE

AutoCAD SHX Text

EXH EXHAUST

AutoCAD SHX Text

FCU FAN COIL UNIT

AutoCAD SHX Text

FD FIRE DAMPER

AutoCAD SHX Text

FF FINISHED FLOOR

AutoCAD SHX Text

FLR FLOOR

AutoCAD SHX Text

FPM FEET PER MINUTE

AutoCAD SHX Text

FS FLOW SWITCH

AutoCAD SHX Text

FSD FIRE SMOKE DAMPER

AutoCAD SHX Text

GAL GALLON

AutoCAD SHX Text

GPM GALLON(S) PER MINUTE

AutoCAD SHX Text

HP HORSEPOWER

AutoCAD SHX Text

HVAC HEATING, VENTILATION, AND AIR CONDITIONING

AutoCAD SHX Text

HZ HERTZ

AutoCAD SHX Text

I.D. IDENTIFICATION

AutoCAD SHX Text

IN WG INCHES WATER GAUGE

AutoCAD SHX Text

KW KILO-WATTS

AutoCAD SHX Text

LB(S) POUND(S)

AutoCAD SHX Text

LVG LEAVING

AutoCAD SHX Text

LWT LEAVING WATER TEMPERATURE

AutoCAD SHX Text

MAX MAXIMUM

AutoCAD SHX Text

MBH THOUSAND BRITISH THERMAL UNIT PER HOUR

AutoCAD SHX Text

MECH MECHANICAL

AutoCAD SHX Text

MM MILLIMETER

AutoCAD SHX Text

MIN MINIMUM

AutoCAD SHX Text

MSS MANUFACTURER STANDARDIZATION SOCIETY

AutoCAD SHX Text

MSS SP-58 PIPE HANGERS AND SUPPORTS- MATERIALS,

AutoCAD SHX Text

DESIGN AND MANUFACTURE

AutoCAD SHX Text

MSS SP-69 PIPE HANGERS AND SUPPORTS- SELECTION

AutoCAD SHX Text

AND APPLICATION

AutoCAD SHX Text

MVD MANUAL VOLUME DAMPER

AutoCAD SHX Text

(N) NEW

AutoCAD SHX Text

NC NORMALLY CLOSED/NOISE CRITERIA

AutoCAD SHX Text

NEEB NATIONAL ENVIRONMENTAL BALANCING BUREAU

AutoCAD SHX Text

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

AutoCAD SHX Text

NO NORMALLY OPEN

AutoCAD SHX Text

OA OUTSIDE AIR

AutoCAD SHX Text

PD PRESSURE DROP

AutoCAD SHX Text

PH PHASE

AutoCAD SHX Text

PLBG PLUMBING

AutoCAD SHX Text

POC POINT OF CONNECTION

AutoCAD SHX Text

PTT PRESSURE & TEMPERATURE TEST PLUG

AutoCAD SHX Text

QTY QUANTITY

AutoCAD SHX Text

RF RETURN FAN

AutoCAD SHX Text

RPM REVOLUTIONS PER MINUTE

AutoCAD SHX Text

RA RETURN AIR

AutoCAD SHX Text

SA SUPPLY AIR

AutoCAD SHX Text

SF SUPPLY FAN

AutoCAD SHX Text

SMACNA SHEET METAL AND AIR CONDITIONING

AutoCAD SHX Text

CONTRACTORS NATIONAL ASSOCIATION

AutoCAD SHX Text

SS STAINLESS STEEL

AutoCAD SHX Text

T'STAT THERMOSTAT

AutoCAD SHX Text

TEMP TEMPERATURE

AutoCAD SHX Text

TYP TYPICAL

AutoCAD SHX Text

UL UNDERWRITERS LABORATORIES

AutoCAD SHX Text

UNO UNLESS NOTED OTHERWISE

AutoCAD SHX Text

UTR UP THRU ROOF

AutoCAD SHX Text

V VOLTS

AutoCAD SHX Text

VAV VARIABLE AIR VOLUME

AutoCAD SHX Text

W WATTS

AutoCAD SHX Text

WB WET BULB

AutoCAD SHX Text

WG WATER GAUGE

AutoCAD SHX Text

WT WEIGHT

AutoCAD SHX Text

W/ WITH

AutoCAD SHX Text

ABBREVIATION

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

SQUARE/RECTANGULAR ELBOW WITH TURNING VANES

AutoCAD SHX Text

ROUND ELBOW

AutoCAD SHX Text

ROUND DUCT DOWN

AutoCAD SHX Text

EXHAUST AIR DUCT UP

AutoCAD SHX Text

EXHAUST AIR DUCT DOWN

AutoCAD SHX Text

ROUND DUCT UP

AutoCAD SHX Text

RETURN AIR DUCT DOWN

AutoCAD SHX Text

RETURN AIR DUCT UP

AutoCAD SHX Text

SUPPLY AIR DUCT DOWN

AutoCAD SHX Text

SUPPLY AIR DUCT UP

AutoCAD SHX Text

DUCT DROP

AutoCAD SHX Text

DUCT RISE

AutoCAD SHX Text

LINED DUCTWORK (OR PLENUM)

AutoCAD SHX Text

FIRE DAMPER, FIRE SMOKE DAMPER

AutoCAD SHX Text

MANUAL VOLUME DAMPER

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

AutoCAD SHX Text

BALL VALVE

AutoCAD SHX Text

SUCTION DIFFUSER WITH STRAINER

AutoCAD SHX Text

PSD

AutoCAD SHX Text

THERMOMETER

AutoCAD SHX Text

MOTORIZED ON/OFF CONTROL BUTTERFLY VALVE

AutoCAD SHX Text M

AutoCAD SHX Text

DOMESTIC COLD WATER BACKFLOW PREVENTER ASSEMBLY

AutoCAD SHX Text

PUMP

AutoCAD SHX Text P

AutoCAD SHX Text

PRESSURE GAGE

AutoCAD SHX Text

BUTTERFLY VALVE

AutoCAD SHX Text

BV

AutoCAD SHX Text

NEEDLE VALVE

AutoCAD SHX Text

PRESSURE REDUCING VALVE

AutoCAD SHX Text

DL

AutoCAD SHX Text

DOOR LOUVER

AutoCAD SHX Text

UC

AutoCAD SHX Text

DOOR UNDERCUT

AutoCAD SHX Text

PRV

AutoCAD SHX Text

SW

AutoCAD SHX Text

SWITCH

AutoCAD SHX Text

ABBREV.

AutoCAD SHX Text

POC

AutoCAD SHX Text

POD

12-15-202560% SUBMITTAL

10-28-2025

FURNACE REPLACEMENT

07-16-2026100% SUBMITTAL2

PROJECT, PW 26-O5B

M003

PW HH

NTS

MECHANICAL

SCOPE OF WORK AND

SEQUENCE

AutoCAD SHX Text Drawing No.

AutoCAD SHX Text Cad File:

AutoCAD SHX Text Xref:

AutoCAD SHX Text Drawn By

AutoCAD SHX Text Date:

AutoCAD SHX Text Scale:

AutoCAD SHX Text Checked By

AutoCAD SHX Text Sheet Title

AutoCAD SHX Text Description

AutoCAD SHX Text

ADDENDUMS

AutoCAD SHX Text No.

AutoCAD SHX Text Date

AutoCAD SHX Text If this drawing is not 22" x 34", it is a reduced print - scale accordingly. All rights reserved. Material may not be reproduced in any form without permission from YEI engineers, Inc.

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text L

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text

NO. M38106

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text

EX. 09/30/26

AutoCAD SHX Text DEMOLITION: 1. DEMOLISH FLOOR-MOUNTED VERTICAL GAS FURNACES, F-4 AND F-5 AND DEMOLISH FLOOR-MOUNTED VERTICAL GAS FURNACES, F-4 AND F-5 AND ASSOCIATED APPURTENANCES. DEMOLISH PORTIONS OF SUPPLY AND RETURN AIR DUCTWORK INCLUDING THE COMBUSTION AND EXHAUST AIR PIPE RISERS AS SHOWN ON THE MECHANICAL DEMOLITION FLOOR PLANS. 2. REFER TO PLUMBING DRAWINGS FOR NATURAL GAS AND CONDENSATE DRAIN PIPING REFER TO PLUMBING DRAWINGS FOR NATURAL GAS AND CONDENSATE DRAIN PIPING DEMOLITION SCOPE OF WORK ASSOCIATED WITH THE MECHANICAL EQUIPMENT BEING DEMOLISHED. 3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL POWERS SUPPLY DEMOLITION REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL POWERS SUPPLY DEMOLITION SCOPE OF WORK ASSOCIATED WITH THE MECHANICAL EQUIPMENT BEING DEMOLISHED. NEW WORK: 1. INSTALL NEW INDOOR FLOOR MOUNTED VERTICAL GAS FURNACES F-4 AND F-5 INSTALL NEW INDOOR FLOOR MOUNTED VERTICAL GAS FURNACES F-4 AND F-5 COMPLETE WITH INSULATED RETURN AIR PLENUM BOX THAT IS ABLE TO SUPPORT THE OPERATING WEIGHT OF THE FURNACE AND SEISMICALLY ANCHOR TO THE EXISTING CONCRETE FLOOR WITH 1” THICK RUBBER PADS. INSULATED RETURN AIR THICK RUBBER PADS. INSULATED RETURN AIR PLENUM BOX SHALL BE PROVIDED MERV-13 AIR FILTER PRIOR TO CONNECTION TO GAS FURNACE RETURN AIR INTAKE. 2. INSTALL GAS FURNACE F-4 AND F-5 NEW INSULATED SUPPLY AND RETURN INSTALL GAS FURNACE F-4 AND F-5 NEW INSULATED SUPPLY AND RETURN DUCTWORK AND CONNECT TO (E) SUPPLY AND RETURN AIR DUCT ABOVE CEILING COMPLETE WITH FITTINGS AND SUPPORTS. 3. INSTALL NEW DUCT SMOKE DETECTOR AT SUPPLY AIR DUCT SIDE OF GAS FURNACE INSTALL NEW DUCT SMOKE DETECTOR AT SUPPLY AIR DUCT SIDE OF GAS FURNACE F-4, AND INTERFACE TO NEW MECHANICAL DIRECT DIGITAL CONTROL SYSTEM AND (E) MAIN FIRE ALARM PANEL. 4. INSTALL GAS FURNACE F-4 AND F-5 NEW PVC SCHEDULE 40 COMBUSTION AIR INSTALL GAS FURNACE F-4 AND F-5 NEW PVC SCHEDULE 40 COMBUSTION AIR AND EXHAUST VENT PIPE AND CONNECT TO EXISTING COMBUSTION AIR AND EXHAUST VENT PIPE RISERS BELOW CEILING COMPLETE WITH PIPE FITTINGS AND SUPPORTS. 5. INSTALL GAS FURNACE F-4 NEW WALL MOUNTED THERMOSTAT WITH LCD DISPLAY INSTALL GAS FURNACE F-4 NEW WALL MOUNTED THERMOSTAT WITH LCD DISPLAY AT THE SAME LOCATION AS THE EXISTING COMPLETE WITH CONTROL WIRING AND ASSOCIATED APPURTENANCES. 6. INSTALL GAS FURNACE F-5 NEW WALL MOUNTED THERMOSTAT WITH LCD DISPLAY INSTALL GAS FURNACE F-5 NEW WALL MOUNTED THERMOSTAT WITH LCD DISPLAY AT THE SAME LOCATION AS THE EXISTING COMPLETE WITH CONTROL WIRING AND ASSOCIATED APPURTENANCES. 7. INSTALL GAS FURNACE F-4 AND F-5 NEW CONDENSATE NEUTRALIZERS. REFER TO INSTALL GAS FURNACE F-4 AND F-5 NEW CONDENSATE NEUTRALIZERS. REFER TO PLUMBING DRAWINGS FOR CONDENSATE PIPING AND DETAILS. 8. INSTALL NEW MECHANICAL DIRECT DIGITAL CONTROL SYSTEM USING BACNET INSTALL NEW MECHANICAL DIRECT DIGITAL CONTROL SYSTEM USING BACNET COMMUNICATION PROTOCOL AND INTERFACE TO COUNTY FACILITY OPERATION CONTROL CENTER FOR REMOTE MONITORING AND CONTROL. 9. PERFORM TESTING, ADJUSTING, AND BALANCING FOR NEW GAS FURNACES (F-4 PERFORM TESTING, ADJUSTING, AND BALANCING FOR NEW GAS FURNACES (F-4 AND F-5) AND ASSOCIATED CEILING AIR OUTLETS. 10. CLEAN THE EXISTING HRV-2 AND HRV-3 ENTIRE HVAC AIR-DISTRIBUTION DUCTS, CLEAN THE EXISTING HRV-2 AND HRV-3 ENTIRE HVAC AIR-DISTRIBUTION DUCTS, PLENUM, AIR OUTLETS, OUTDOOR AIR INTAKE HOOD, EXHAUST AIR HOOD, AND SYSTEM COMPONENTS PER NATIONAL AIR DUCT CLEANERS ASSOCIATION (NADCA ACR) AND SPECIFICATION 23 01 30.52. EXISTING HRV UNITS CLEANING NOT IN SCOPE. 11. CLEAN THE EXISTING EXHAUST FAN EF-3 SERVING THE DOG KENNELS #139 AND CLEAN THE EXISTING EXHAUST FAN EF-3 SERVING THE DOG KENNELS #139 AND THE ENTIRE VENTILATION AIR-DISTRIBUTION DUCTS, AIR OUTLETS, AND SYSTEM COMPONENTS PER NATIONAL AIR DUCT CLEANERS ASSOCIATION (NADCA ACR) AND SPECIFICATION 23 01 30.52. 12. CLEAN THE TWO EXISTING EXHAUST FANS SERVING THE DOG KENNELS #144 AND CLEAN THE TWO EXISTING EXHAUST FANS SERVING THE DOG KENNELS #144 AND DOG KENNELS #145, AND THE ENTIRE VENTILATION AIR-DISTRIBUTION DUCTS, AIR OUTLETS, AND SYSTEM COMPONENTS PER NATIONAL AIR DUCT CLEANERS ASSOCIATION (NADCA ACR) AND SPECIFICATION 23 01 30.52. 13. PERFORM AND PASS ALL APPLICABLE ACCEPTANCE TESTING FOR MECHANICAL PERFORM AND PASS ALL APPLICABLE ACCEPTANCE TESTING FOR MECHANICAL SYSTEMS REQUIRED BY THE CALIFORNIA ENERGY CODE. ACCEPTANCE TESTING FOR MECHANICAL SYSTEMS MUST BE PERFORMED BY A CERTIFIED MECHANICAL ACCEPTANCE TEST TECHNICIAN (ATT) AND DOCUMENTED ON THE APPLICABLE NONRESIDENTIAL CERTIFICATE OF ACCEPTANCE (NRCA) FORMS.

MECHANICAL SCOPE OF WORK

12-15-202560% SUBMITTAL

10-28-2025

FURNACE REPLACEMENT

07-16-2026100% SUBMITTAL2

PROJECT, PW 26-O5B

M004

AS HH

NTS

MECHANICAL

EQUIPMENT SCHEDULES

AutoCAD SHX Text Drawing No.

AutoCAD SHX Text Cad File:

AutoCAD SHX Text Xref:

AutoCAD SHX Text Drawn By

AutoCAD SHX Text Date:

AutoCAD SHX Text Scale:

AutoCAD SHX Text Checked By

AutoCAD SHX Text Sheet Title

AutoCAD SHX Text Description

AutoCAD SHX Text

ADDENDUMS

AutoCAD SHX Text No.

AutoCAD SHX Text Date

AutoCAD SHX Text If this drawing is not 22" x 34", it is a reduced print - scale accordingly. All rights reserved. Material may not be reproduced in any form without permission from YEI engineers, Inc.

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text L

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text

NO. M38106

AutoCAD SHX Text R

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text L

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text

EX. 09/30/26

AutoCAD SHX Text

FURNACE SCHEDULE

AutoCAD SHX Text

EQUIP. I.D.

AutoCAD SHX Text

BUILDING/ LOCATION

AutoCAD SHX Text

AREA SERVE

AutoCAD SHX Text

GAS FURNACE DATA

AutoCAD SHX Text

SUPPLY FAN

AutoCAD SHX Text

AIR FILTER DATA

AutoCAD SHX Text

MIN. CIRCUIT AMPS. @ 115V/1PH/ 60HZ

AutoCAD SHX Text

APPROX. OPER. WT.

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

MANUFACTURER / MODEL OR APPROVED EQUAL

AutoCAD SHX Text

MAX. INPUT HEATING CAPACITY

AutoCAD SHX Text

MIN. OUTPUT HEATING CAPACITY

AutoCAD SHX Text

MIN. AFUE

AutoCAD SHX Text

ENT. AIR TEMP.

AutoCAD SHX Text

LVG. AIR TEMP.

AutoCAD SHX Text

GAS CONNECTION SIZE

AutoCAD SHX Text

COMBUSTION AIR SIZE

AutoCAD SHX Text

EXHAUST SIZE

AutoCAD SHX Text

IGNITION SYSTEM TYPE

AutoCAD SHX Text

HEATING STAGES

AutoCAD SHX Text

TYPE

AutoCAD SHX Text

MAX/MIN AIR FLOW RATE FOR HEATING

AutoCAD SHX Text

ESP FOR HEATING

AutoCAD SHX Text

MIN. O.A.

AutoCAD SHX Text

MOTOR RATING @ 115V/1PH/60HZ

AutoCAD SHX Text

FILTER TYPE/ THICKNESS/ ARRESTANCE EFFICIENCY

AutoCAD SHX Text

MAX FACE VELOCITY

AutoCAD SHX Text

MBH

AutoCAD SHX Text

MBH

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text

IN

AutoCAD SHX Text

IN

AutoCAD SHX Text

IN

AutoCAD SHX Text

CFM

AutoCAD SHX Text

IN. W.G.

AutoCAD SHX Text

CFM

AutoCAD SHX Text

HP

AutoCAD SHX Text

INCHES

AutoCAD SHX Text

FPM

AutoCAD SHX Text

LBS.

AutoCAD SHX Text F-4

AutoCAD SHX Text

NAPA ANIMAL SHELTER/ EQUIP #145

AutoCAD SHX Text

DOG KENNELS #146 & DOG ISOLATION #147

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 95.0

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1/2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

HOT SURFACE

AutoCAD SHX Text

MULTI STAGE GAS HEAT

AutoCAD SHX Text

CENTRIFUGAL FAN - CONSTANT SPEED

AutoCAD SHX Text

AutoCAD SHX Text 0.2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

WASHABLE / 3/4 / -

AutoCAD SHX Text

AutoCAD SHX Text

SEE NOTES BELOW

AutoCAD SHX Text F-5

AutoCAD SHX Text

NAPA ANIMAL SHELTER/ EQUIP #142

AutoCAD SHX Text

DOG KENNELS #143

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 95.0

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1/2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

HOT SURFACE

AutoCAD SHX Text

MULTI STAGE GAS HEAT

AutoCAD SHX Text

CENTRIFUGAL FAN - CONSTANT SPEED

AutoCAD SHX Text

AutoCAD SHX Text 0.2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

WASHABLE / 3/4 / -

AutoCAD SHX Text

AutoCAD SHX Text

SEE NOTES BELOW

AutoCAD SHX Text NOTES: 1. FURNACE SHALL BE SINGLE PASS, 100% OUTSIDE AIR, VERTICAL, HIGH EFFICIENCY, CONSTANT SPEED, MULTI-STAGE CONDENSING GAS FURNACE. 2. PROVIDE WALL MOUNTED THERMOSTAT WITH LCD DISPLAY. 3. FURNACE SHALL BE PROVIDED WITH FABRICATED RA/OA INSULATED STRUCTURAL PLENUM BOX SHALL BE ABLE TO SUPPORT THE FULL OPERATING WEIGHT OF THE GAS FURNACE, GAS PIPING, AND INSULATED VERTICAL SUPPLY AIR DUCT. 4. PROVIDE CONDENSATE PUMP WITH CONDENSATE NEUTRALIZER (LITTLE GIANT MODEL VCMA-20-NPTC WITH RNTC-500 MEDIA) INCLUDING CONDENSATE DRAIN PIPING. 5. FURNACE SHALL BE PROVIDED WITH DDC BACNET CONTROL CARD FOR BUILDING ENERGY MANAGEMENT AND CONTROL SYSTEM INTERFACE. PROVIDED BY MECHANICAL CONTRACTOR AND INSTALLED BY PLUMBING CONTRACTOR. 6. PROVIDE DUCT SMOKE DETECTOR ON SUPPLY AIR DUCT RISER AND WIRE TO EXISTING BUILDING FIRE ALARM PANEL FOR ALARM NOTIFICATION. DUCT SMOKE DETECTOR SHALL SHUTDOWN THE FURNACE UPON DETECTION OF SMOKE IN ACCORDANCE WITH CMC.

AutoCAD SHX Text

MAX/MIN AIR FLOW RATE FOR COOLING

AutoCAD SHX Text

CFM

AutoCAD SHX Text 430/2255

AutoCAD SHX Text 430/2255

AutoCAD SHX Text

ESP

AutoCAD SHX Text

IN. W.G.

AutoCAD SHX Text 0.5

AutoCAD SHX Text 0.5

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

CARRIER/59SU5B

CARRIER/59SU5B

NEW ROAD

123456

PARKING

B

A

A1

B

A

123456

N E

W R

A

IL

R O

A D

A L

IG

N M

E N

T

E X

IS

T

IN

G R

A

IL

R O

A D

ANIMAL SHELTER PHASE I

NAPA COUNTY

12-15-202560% SUBMITTAL

10-28-2025

FURNACE REPLACEMENT

07-16-2026100% SUBMITTAL2

PROJECT, PW 26-O5B

M100

AS HH

NTS

MECHANICAL

GROUND KEY PLAN

AutoCAD SHX Text x

AutoCAD SHX Text x

AutoCAD SHX Text

FUTURE ACCESS ROAD WITH CURB & GUTTER

AutoCAD SHX Text 13.50

AutoCAD SHX Text 12.17

AutoCAD SHX Text 12.17

AutoCAD SHX Text

FUTURE RAILROAD

AutoCAD SHX Text

RIGHT-OF-WAY

AutoCAD SHX Text

WH

AutoCAD SHX Text

ANIMAL RECEIVING

AutoCAD SHX Text C.G.

AutoCAD SHX Text C.G.

AutoCAD SHX Text C.G.

AutoCAD SHX Text C.G.

AutoCAD SHX Text

STRAY CATS

AutoCAD SHX Text

ISO. CATS

AutoCAD SHX Text

TRAINING ROOM

AutoCAD SHX Text

BREAK ROOM

AutoCAD SHX Text

WOMEN

AutoCAD SHX Text

KITCHEN

AutoCAD SHX Text

GROOMING &

AutoCAD SHX Text

CAT

AutoCAD SHX Text

EXERCISE

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

GARAGE

AutoCAD SHX Text

FOOD STORAGE

AutoCAD SHX Text

CLINIC

AutoCAD SHX Text

SPRINKLER

AutoCAD SHX Text

DRY STORAGE

AutoCAD SHX Text

FERAL CATS

AutoCAD SHX Text

LOBBY

AutoCAD SHX Text

RECEPTION

AutoCAD SHX Text

DOG KENNELS

AutoCAD SHX Text

HALL

AutoCAD SHX Text

EQUIP.

AutoCAD SHX Text

GET ACQUAINTED

AutoCAD SHX Text

EQUIP.

AutoCAD SHX Text

CAT

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

CLIENT

AutoCAD SHX Text

FRONT

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

SUPERVISOR'S

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

TELEPHONE CL.

AutoCAD SHX Text

EQUIP.

AutoCAD SHX Text

PUPPIES &

AutoCAD SHX Text

SMALL BREEDS

AutoCAD SHX Text

EUTHANASIA

AutoCAD SHX Text

CAT & DOG

AutoCAD SHX Text

RECEIVING

AutoCAD SHX Text

EQUIP.

AutoCAD SHX Text

HALL

AutoCAD SHX Text

DOG ISOLATION

AutoCAD SHX Text

STAFF HALLWAY

AutoCAD SHX Text

ANIMAL NIGHT DROPS

AutoCAD SHX Text

HALL

AutoCAD SHX Text

GET

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

WALK-IN

AutoCAD SHX Text

FREEZER

AutoCAD SHX Text

ROOM

AutoCAD SHX Text

HALL

AutoCAD SHX Text

AQUT'D

AutoCAD SHX Text

LAUNDRY

AutoCAD SHX Text

JANITOR

AutoCAD SHX Text

MEN

AutoCAD SHX Text

SHOWER

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text

COURTYARD

AutoCAD SHX Text

DOG QUARANTINE

AutoCAD SHX Text

HALL

AutoCAD SHX Text

HALL

AutoCAD SHX Text

HALL

AutoCAD SHX Text

HALL

AutoCAD SHX Text C.G.

AutoCAD SHX Text C.G.

AutoCAD SHX Text C.G.

AutoCAD SHX Text C.G.

AutoCAD SHX Text Drawing No.

AutoCAD SHX Text Cad File:

AutoCAD SHX Text Xref:

AutoCAD SHX Text Drawn By

AutoCAD SHX Text Date:

AutoCAD SHX Text Scale:

AutoCAD SHX Text Checked By

AutoCAD SHX Text Sheet Title

AutoCAD SHX Text Description

AutoCAD SHX Text

ADDENDUMS

AutoCAD SHX Text No.

AutoCAD SHX Text Date

AutoCAD SHX Text If this drawing is not 22" x 34", it is a reduced print - scale accordingly. All rights reserved. Material may not be reproduced in any form without permission from YEI engineers, Inc.

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text R

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text N

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text H

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text L

AutoCA…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .