PW_26-05B_Animal_Shelter_Phase_I_Furnace_plans_bid_set.pdf
PDF 7 MB Posted
- Solicitation number
- PW 26-05B
- Issued by
- Napa County, California
About this file
This is a bid set of construction drawings and specifications for the Napa County Animal Shelter Phase I Furnace Replacement Project (PW 26-05B), prepared by YEI Engineers, Inc. and Brokaw Design for Napa County, California. The project involves demolishing two existing floor-mounted vertical gas furnaces (F-4 and F-5) and installing new high-efficiency, multi-stage condensing gas furnaces complete with insulated return air plenum boxes, supply and return ductwork, combustion air and exhaust vent piping, wall-mounted thermostats with LCD displays, duct smoke detectors, condensate neutralizers, and a new mechanical direct digital control system using BACnet communication protocol. The scope of work includes seismic anchoring of furnaces to the existing concrete floor with rubber pads, installation of a new wall-mounted Carrier Climavision Central Control Unit for real-time performance monitoring, and comprehensive cleaning of existing HVAC air-distribution systems serving heat recovery ventilation units and exhaust fans per National Air Duct Cleaners Association standards. The project also requires testing, adjusting, and balancing of new furnaces and associated ceiling air outlets, with acceptance testing performed by a certified mechanical acceptance test technician and documented on nonresidential certificate of acceptance forms in compliance with the California Energy Code.
The furnace schedule specifies two Carrier 59SU5B units rated at 100 MBH maximum input and 97 MBH minimum output with 95.0 percent AFUE efficiency, serving different facility zones with varying airflow requirements (2,255 CFM maximum and 430 CFM minimum for cooling, with 0.5 inches water gauge external static pressure). The drawings are based on a 60 percent submittal dated December 15, 2025, and a 100 percent submittal dated July 16, 2026, with a registered professional engineer stamp expiring September 30, 2027. Delegated design responsibility is assigned to the contractor for plenum box design, plenum box bracing and anchorage, vertical ductwork bracing, and furnace bracing and anchorage, which must be designed by a California civil or structural engineer and submitted for owner and building department review with allowance for multiple review cycles. The contractor bears responsibility for field verification of existing conditions, coordination with all trades, protection of adjacent surfaces, complete functionality of all equipment including electrical and control items, and maintenance of as-built documentation for all existing and new services. All work shall conform to the 2025 California Building Code, California Mechanical Code, California Plumbing Code, California Energy Code, and latest county adopted codes.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ANIMAL SHELTER PHASE I
NAPA COUNTY
12-15-202560% SUBMITTAL
10-28-2025
FURNACE REPLACEMENT
07-16-2026100% SUBMITTAL2
PROJECT, PW 26-O5B
T002
PW HH
NTS
SHEET INDEX
942 HARTLE COURT, NAPA, CA 94558
MECHANICAL
SHEET
COUNT
SHEET
NUMBER SHEET TITLE
M001 MECHANICAL GENERAL NOTES
M002 MECHANICAL ABBREVIATIONS AND LEGEND
M003 MECHANICAL SCOPE OF WORK AND SEQUENCING
M004 MECHANICAL EQUIPMENT SCHEDULES
M101 MECHANICAL ENLARGED FIRST FLOOR DEMOLITION PLAN
M401 MECHANICAL CONTROL SEQUENCE OF OPERATIONS
M501 MECHANICAL DETAILS
PLUMBING
SHEET
COUNT
SHEET
NUMBER SHEET TITLE
P001 PLUMBING GENERAL NOTES AND SCOPE OF WORK
P002
P101 PLUMBING FIRST FLOOR DEMOLITION PLAN
ELECTRICAL
SHEET
COUNT SHEET TITLE
E001 ELECTRICAL GENERAL NOTES, ABBREVIATIONS AND
SYMBOLS
E002 ELECTRICAL SINGLE LINE
E101 E201
GENERAL
SHEET
COUNT
SHEET
NUMBER SHEET TITLE
1 T001 COVER PAGE
2 T002 SHEET INDEX
SHEET
NUMBER
M102 MECHANICAL ENLARGED FIRST FLOOR DEMOLITION PLAN
M201 MECHANICAL ENLARGED FIRST FLOOR NEW WORK PLAN
M202 MECHANICAL ENLARGED FIRST FLOOR NEW WORK PLAN
M301 MECHANICAL ISOMETRIC VIEWS
PLUMBING LEGEND, ABBREVIATIONS AND SCHEDULE
P201 PLUMBING FIRST FLOOR NEW WORK PLAN
P301 PLUMBING DIAGRAM
P401 PLUMBING TYPICAL DETAILS
ELECTRICAL FIRST FLOOR DEMOLITION PLAN
ELECTRICAL FIRST FLOOR NEW WORK PLAN
E301 ELECTRICAL DETAILS
M100 MECHANICAL GROUND KEY PLAN
M110 MECHANICAL ROOF DEMOLITION PLAN
M210 MECHANICAL ROOF NEW WORK PLAN
STRUCTURAL
SHEET
COUNT
SHEET
NUMBER SHEET TITLE
S501 STRUCTURAL DETAILS3
PROJECT PW 26-05B
NAPA COUNTY ANIMAL SHELTER PHASE I
FURNACE REPLACEMENT PROJECT, PW 26-05B
AutoCAD SHX Text Drawing No.
AutoCAD SHX Text Cad File:
AutoCAD SHX Text Xref:
AutoCAD SHX Text Drawn By
AutoCAD SHX Text Date:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Checked By
AutoCAD SHX Text Sheet Title
AutoCAD SHX Text Description
AutoCAD SHX Text
ADDENDUMS
AutoCAD SHX Text No.
AutoCAD SHX Text Date
AutoCAD SHX Text If this drawing is not 22" x 34", it is a reduced print - scale accordingly. All rights reserved. Material may not be reproduced in any form without permission from YEI engineers, Inc.
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text L
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text
NO. M38106
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text O
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text
EX. 09/30/26
(E) 4" CONC
SLAB
4" THICK CONC PAD;
COORD PLAN GEOMETRY
W/ PURCHASED EQUIP,
SEE MEP DWGS.
PROVIDE 6" MINIMUM
EDGE DISTANCE TO
ANCHORS
8"Ø x 5" HVY DUTY CONC
SCREW ANCHORS @ 12"
OC, EA WAY; 2 12" EMBED
INTO (E) CONC, TYP
#4@ 6" O.C. EACH
WAY CENTERED.
A
F
F
12-15-2025
DATE SIGNED: 7/16/2026
BrokawDesign www.BrokawDesign.com
Tim Lengyel, P.E., S.E.
415-999-0323
ANIMAL SHELTER PHASE I
NAPA COUNTY
12-15-202560% SUBMITTAL1
FURNACE REPLACEMENT
07-16-2026100% SUBMITTAL2
PROJECT, PW 26-O5B
S501
TFL TFL
1/8" = 1'-0"
FURNACE F-4 AND F-5
STRUCTURAL DETAILS
NO SCALE
DETAIL
FURNACE F-5 SEE MECHANICAL DWGS.
(F-4 SIM, SEE MECHANICAL DWGS.)
EXISTING 4" SLAB ON GRADE
4" HOUSEKEEPING PAD SEE 2
S501
MAINTAIN 6" CLEAR TO ANCHORS
MAINTAIN 6" CLEAR TO ANCHORS
A. DESIGN BASIS
A.1. THIS ANCHORAGE AND PAD HAS BEEN DESIGNED IN ACCORDANCE WITH THE 2025 CBC.
A.2. STRUCTURE DESIGNED FOR SEISMIC LOADS BASED ON THE FOLLOWING PARAMETERS:
BUILDING CATEGORY = II = STANDARD
SITE CLASS = D (ASSUMED)
MAX. 0.2 SEC. SPECTRAL RESPONSE ACCELERATION, SS = 2.21g MAX. 1.0 SEC. SPECTRAL RESPONSE ACCELERATION, S1 = 0.77g DESIGN SPECTRAL RESPONSE AT SHORT PERIODS; SDS = 1.54g
SEISMIC DESIGN CATEGORY = D
A.3. PROVIDE SPECIAL INSPECTION OF CONCRETE AND EQUIPMENT ANCHORAGE.
B. GENERAL NOTES
B.1. ALL WORK TO CONFORM TO REQUIREMENTS OF ALL PUBLICATIONS AND NOTES LISTED UNDER "DESIGN BASIS".
B.2. ARCHITECTURAL DRAWINGS, MECHANICAL/ELECTRICAL/PLUMBING DRAWINGS AND ALL OTHER DRAWINGS AS REQUIRED SHALL BE USED IN CONJUNCTION WITH STRUCTURAL DRAWINGS TO DEVELOP DETAILS AND DIMENSIONS FOR SHOP DRAWINGS, FABRICATION, ERECTION AND CONSTRUCTION. CONTRACTOR IS TO COORDINATE EQUIPMENT, SUPPORT CONDITIONS AND DIMENSIONS FOR SUPPORTING BEAMS, FRAMES AND OPENINGS FOR
MECHANICAL EQUIPMENT AND PROVIDE THIS INFORMATION FOR REVIEW.
B.3. DO NOT SCALE DRAWINGS.
B.4. CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER/OWNER/ENGINEER IMMEDIATELY UPON DISCOVERY OF
CONFLICTS IN THE DRAWINGS AND SPECIFICATIONS.
B.5. THE CONTRACTING OFFICER/OWNER/ENGINEER MAY PERIODICALLY VISIT THE SITE TO OBSERVE THE PROGRESS AND GENERAL QUALITY OF THE CONSTRUCTION. THESE VISITS ARE NOT INTENDED TO REPLACE THE
CONTRACTOR'S RESPONSIBILITY FOR QUALITY CONTROL OR SPECIAL INSPECTION.
B.6. THE CONTRACTOR IS TO VERIFY ALL EXISTING CONDITIONS AND ALL DIMENSIONS IN FIELD PRIOR TO START OF CONSTRUCTION AND PROTECT AND MAINTAIN ALL EXISTING CONSTRUCTION AND ITS CONTENTS IN FULL.
B.7. THE CONTRACTOR SHALL MAINTAIN A SET OF LATEST REVIEWED SHOP DRAWINGS ON JOB SITE.
B.8. THE STRUCTURE HAS BEEN DESIGNED TO BE STABLE AND SELF SUPPORTING AFTER THE CONSTRUCTION IS COMPLETE. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY FOR THE BUILDING'S STABILITY DURING CONSTRUCTION. THIS RESPONSIBILITY ALSO INCLUDES BUT IS NOT LIMITED TO METHOD AND SEQUENCE OF
ERECTION, TEMPORARY SHORING AND TEMPORARY BRACING.
B.9. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO FOLLOW ALL APPLICABLE SAFETY CODES AND REGULATIONS
DURING ALL PHASES OF CONSTRUCTION.
B.10. SHOULD ANY INFORMATION ON THE STRUCTURAL DRAWINGS CONFLICT WITH THE SPECIFICATIONS OR ANY OTHER PART OF THE DRAWINGS, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AND AN INTERPRETATION WILL BE
GIVEN.
B.11. ALL SECTIONS, DETAILS, NOTES, DIMENSIONS AND CONDITIONS ARE APPLICABLE AT ANY OTHER LOCATION WHERE CONDITIONS AND DETAILS ARE SIMILAR BUT ARE NOT SPECIFICALLY NOTED AS SUCH OR ARE NOT SHOWN.
B.12. ALL PROPRIETARY ANCHORING SYSTEMS TO BE INSTALLED INTO CONCRETE OR MASONRY ELEMENTS IN STRICT
ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.
C. CONCRETE NOTES
C.1. ALL WORK TO CONFORM TO THE REQUIREMENTS OF THE FOLLOWING PUBLICATIONS:
C.1.1. ACI "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318-19) AND "DETAILS AND DETAILING
OF CONCRETE REINFORCEMENT" (ACI 315-LATEST EDITION).
C.2. MINIMUM COMPRESSIVE STRENGTH OF CONCRETE AT 28 DAYS:
4000 PSI (NORMAL WEIGHT) AT ALL CONCRETE ELEMENTS.
MAXIMUM SLUMP: 5"
MAXIMUM WATER/CEMENT RATIO: 0.45
NOMINAL MAXIMUM AGGREGATE SIZE: 1/2"
PRIOR TO PLACING CONCRETE, MIX DESIGNS SHALL BE SUBMITTED FOR REVIEW.
C.1. CONCRETE MIXTURE COMPONENTS SHALL CONFORM TO THE FOLLOWING:
C.1.1. CEMENT - ASTM C150 , TYPE II
C.1.2. COURSE AGGREGATE - ASTM C33 (NORMAL WEIGHT)
C.1.3. FINE AGGREGATE - ASTM C33
C.1.4. WATER - SHALL BE POTABLE WATER
C.1.5. ADMIXTURES
C.1.5.1. ASTM C260 AIR ENTRAINMENT
C.1.5.2. ASTM C618 POZZOLAN & FLY ASH
C.1.5.3. ASTM C494 WATER REDUCING, RETARDING, ACCELERATION
C.2. ALL BAR REINFORCING FOR CONCRETE SHALL CONFORM TO ASTM A 615 GRADE 60 (DEFORMED). CERTIFIED MILL TEST REPORTS SHALL BE SUBMITTED TO THE INSPECTOR FOR EACH SHIPMENT OF SUCH REINFORCEMENT.
C.3. UNLESS OTHERWISE SHOWN, LOCATE REINFORCING BARS WITH FOLLOWING CLEAR DIMENSION TO FACE OF
CONCRETE:
INTERIOR SURFACES 1.5"
C.4. CONCRETE ACCESSORIES MUST BE ADEQUATE TO MAINTAIN REINFORCING ACCURATELY IN PLACE AND BE
NON-CORROSIVE, NON-STAINING TYPE.
C.5. LAP ALL BAR REINFORCING IN CONCRETE ELEMENTS 48 BAR DIAMTERS
C.6. LIQUID MEMBRANE FORMING CURING COMPOUNDS SHALL COMPLY WITH ASTM C 309, TYPE I, CLASS A. APPLY AS
SOON AS POSSIBLE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
D. DELEGATED DESIGN NOTES
D.1. DESIGN, PROVIDE AND INSTALL FULLY FUNCTIONAL PLENUM BOXES, PLENUM BOX BRACING AND ANCHROAGE, DUCTWORK BRACING, FURNACE BRACING AND ANCHORAGE FOR FURNACE F-4 AND FURNACE F-5. DESIGN PER
ENGINEER RETAINED BY THE CONTRACTOR.
D.2. SEE OTHER DRAWINGS FOR INFORMATION NOT SHOWN.
D.3. CONTRACTOR SHALL COORDINATE ACTUAL LAYOUT WITH ACTUAL EQUIPMENT PROVIDED.
D.4. FURNACE BRACING AND ANCHORAGE, PLENUM BOXES, PLENUM BOX BRACING AND ANCHORAGE AND VERTICAL DUCTWORK BRACING AND ANCHORAGE TO BE DESIGNED BY A CALIFORNIA CIVIL OR STRUCTURAL ENGINEER AND CONSTRUCTED IN ACCORDANCE WITH SPECIFICATIONS AND TO SUPPORT IT'S OWN WEIGHT, UNIT WEIGHT, IMPOSED LIVE, WIND, SEISMIC LOADS AS WELL AS ANY OTHER MECHANICAL AND ELECTRICAL EQUIPMENT THAT SHALL BE SUPPORTED FROM IT. SEE "DESIGN BASIS" IN STRUCTURAL GENERAL NOTES FOR STRUCTURAL CRITERIA.
PROVIDED ADDITIONAL CONTRACTOR TO INCLUDE MULTIPLE REVIEWS IN PROJECT SCHEDULE. ALLOW 2 WEEKS
FOR EACH ARCHITECTURAL AND STRUCTURAL REVIEW.
D.5. CONTRACTOR SHALL SUBMIT DESIGN DRAWINGS AND CALCULATIONS. THESE DRAWINGS AND CALCULATIONS WILL CONSTITUTE A DEFERRED SUBMITTAL TO THE BUILDING DEPARTMENT. THE SUBMITTAL MUST BE REVIEWED BY THE OWNER'S ENGINEER PRIOR TO SUBMISSION TO THE BUILDING DEPARTMENT. DESIGNER SHALL RESPOND TO ALL COMMENTS FROM THE BUILDING DEPARTMENT AND OWNER'S REPRESENTATIVE AND MAKE REVISIONS AS REQUIRED BY BUILDING DEPARTMENT AND OWNER'S REPRESENTATIVE. CONTRACTOR SHALL ALLOCATE TIME FOR MULTIPLE BUILDING DEPARTMENT AND OWNER REVIEWS INTO THEIR CONSTRUCTION SCHEDULE. THE STRUCTURAL ENGINEER OF RECORD WILL ISSUE A CONFORMANCE LETTER FOR INCLUSION WITH SUBMISSION TO THE BUILDING
DEPARTMENT. NO SCALE
DETAIL
PLENUM AND BRACING/ANCHORAGE TO
BE A DESIGNED BY CONTRACTOR'S
ENGINEER. SEE GENERAL NOTES THIS
PAGE
NO SCALE
PARTIAL GROUND FLOOR PLAN
A
EQUIPMENT PAD SEE 2
S501
S501
PLENUM AND PLENUM ANCHORAGE DESIGNED BY CONTRACTOR'S ENGINEER BASED ON ACTUAL EQUIPMENT.
SEE GENERAL NOTES AND
S501
S501
EQUIPMENT PAD SEE 2
S501
S501
PLENUM AND PLENUM ANCHORAGE DESIGNED BY
CONTRACTOR'S ENGINEER BASED ON ACTUAL EQUIPMENT.
SEE GENERAL NOTES AND
S501
S501
EXISTING 8" MASONRY WALL,
WHERE OCCURS. VIF. PER
RECORD DRAWINGS
MASONRY IS LIGHT WEIGHT
BLOCK, F'm=1500PSI, REINFORCED WITH #5
VERTICALLY AND
HORIZONTALLY @ 40" O.C.
PROVIDE ANGLE FEET PER
CONTRACTOR'S ENGINEER AND
ACTUAL PLENUM DESIGN
PROVIDE ANCHORAGE TO
WALLS FOR UNIT, PLENUM
AND DUCTWORK
CONTRACTOR'S ENGINEER
AND ACTUAL PLENUM
DESIGN
FURNACE BRACING/ANCHORAGE TO BE
A DESIGNED BY CONTRACTOR'S
ENGINEER. SEE GENERAL NOTES THIS
PAGE
VERTICAL DUCTWORK
BRACING/ANCHORAGE TO BE DESIGNED
BY CONTRACTOR'S ENGINEER. SEE
GENERAL NOTES THIS PAGE
AutoCAD SHX Text
EQUIP.
AutoCAD SHX Text
GET ACQUAINTED
AutoCAD SHX Text
EQUIP.
AutoCAD SHX Text
PUPPIES &
AutoCAD SHX Text
SMALL BREEDS
AutoCAD SHX Text
CAT & DOG
AutoCAD SHX Text
RECEIVING
AutoCAD SHX Text
HALL
AutoCAD SHX Text
HALL
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text Drawing No.
AutoCAD SHX Text Cad File:
AutoCAD SHX Text Xref:
AutoCAD SHX Text Drawn By
AutoCAD SHX Text Date:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Checked By
AutoCAD SHX Text Sheet Title
AutoCAD SHX Text If this drawing is not 22" x 34", it is a reduced print - scale accordingly. All rights reserved. Material may not be reproduced in any form without permission from YEI engineers, Inc.
AutoCAD SHX Text Description
AutoCAD SHX Text
ADDENDUMS
AutoCAD SHX Text No.
AutoCAD SHX Text Date
AutoCAD SHX Text
STRUCTURAL GENERAL NOTES
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
20 FT
AutoCAD SHX Text S5196
AutoCAD SHX Text 9/30/27
AutoCAD SHX Text No.
AutoCAD SHX Text Exp.
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text I
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text Y
AutoCAD SHX Text F
AutoCAD SHX Text R
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text Y
AutoCAD SHX Text E
AutoCAD SHX Text L
AutoCAD SHX Text S
AutoCAD SHX Text T
AutoCAD SHX Text R
AutoCAD SHX Text U
AutoCAD SHX Text C
AutoCAD SHX Text T
AutoCAD SHX Text U
AutoCAD SHX Text R
AutoCAD SHX Text A
L
12-15-202560% SUBMITTAL
10-28-2025
FURNACE REPLACEMENT
07-16-2026100% SUBMITTAL2
PROJECT, PW 26-O5B
M001
AS HH
NTS
MECHANICAL
GENERAL NOTES
AutoCAD SHX Text Drawing No.
AutoCAD SHX Text Cad File:
AutoCAD SHX Text Xref:
AutoCAD SHX Text Drawn By
AutoCAD SHX Text Date:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Checked By
AutoCAD SHX Text Sheet Title
AutoCAD SHX Text Description
AutoCAD SHX Text
ADDENDUMS
AutoCAD SHX Text No.
AutoCAD SHX Text Date
AutoCAD SHX Text If this drawing is not 22" x 34", it is a reduced print - scale accordingly. All rights reserved. Material may not be reproduced in any form without permission from YEI engineers, Inc.
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text L
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text
NO. M38106
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text O
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text
EX. 09/30/26
AutoCAD SHX Text
1. CONTRACTOR SHALL BE RESPONSIBLE FOR EXAMINING ALL DRAWINGS, FIELD CONTRACTOR SHALL BE RESPONSIBLE FOR EXAMINING ALL DRAWINGS, FIELD VERIFICATION OF EXISTING CONDITIONS AND COORDINATING WITH ALL OTHER TRADES PRIOR TO START OF WORK AND PURCHASING OF EQUIPMENT. ADVISE THE OWNER IN WRITING IN THE EVENT A CONFLICT OCCURS BETWEEN THE REQUIREMENTS OF THE CONTRACT DOCUMENTS AND ACTUAL FIELD CONDITIONS. THE CONTRACTOR SHALL BEAR ALL COSTS FOR RELOCATION OF EQUIPMENT, PIPING, ETC., FROM FAILURE TO PROPERLY COORDINATE INSTALLATIONS AND ADVISE OF THE CONFLICT IN WRITING PRIOR TO INSTALLATION. 2. IN CASE OF DIFFERENCE BETWEEN BUILDING CODES, SPECIFICATIONS, IN CASE OF DIFFERENCE BETWEEN BUILDING CODES, SPECIFICATIONS, INDUSTRY STANDARDS, UTILITY COMPANY REGULATIONS, FIRE INSURANCE CARRIER'S REQUIREMENTS AND CONTRACT DOCUMENTS, THE MOST STRINGENT SHALL GOVERN. PROMPTLY NOTIFY THE OWNER IN WRITING OF ANY SUCH DIFFERENCE. 3. EQUIPMENT, DUCTWORK AND PIPING AS SHOWN ON DRAWINGS ARE EQUIPMENT, DUCTWORK AND PIPING AS SHOWN ON DRAWINGS ARE SCHEMATIC AND SHALL BE FABRICATED AND INSTALLED ON ACTUAL FIELD MEASUREMENT. DO NOT SCALE DRAWINGS FOR EXACT LOCATION OF EQUIPMENT, DUCTWORK AND PIPING. COORDINATE WITH OTHER TRADES AS REQUIRED. 4. PLANS ARE BASED ON ANTICIPATED EQUIPMENT SIZE AND CONFIGURATION. PLANS ARE BASED ON ANTICIPATED EQUIPMENT SIZE AND CONFIGURATION. CONTRACTOR SHALL MODIFY ARRANGEMENT TO SUIT ACTUAL PURCHASED EQUIPMENT AS REQUIRED FOLLOWING THE CRITERIA ESTABLISHED BY THESE PLANS. DEPARTURES FROM THE CONTRACT DRAWING RESULTING FROM CHANGES IN EQUIPMENT SIZES AND CONFIGURATIONS, OR RE-ARRANGEMENTS TO ACCOMMODATE FIELD CONDITIONS SHALL BE SUBMITTED IN DETAIL FOR THE OWNER'S APPROVAL. 5. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION AND SHALL REPAIR CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION AND SHALL REPAIR ADJACENT EXISTING AND/OR NEW SURFACES, AREAS AND PROPERTY THAT MAY BE DAMAGED AS A RESULT OF ANY DEMOLITION AND/OR NEW WORK. 6. CONFORM TO LATEST NFPA 90A "STANDARD FOR THE INSTALLATION OF AIR CONFORM TO LATEST NFPA 90A "STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS". 7. COORDINATE INSTALLATION OF ALL EQUIPMENT, DUCTWORK AND PIPING WITH COORDINATE INSTALLATION OF ALL EQUIPMENT, DUCTWORK AND PIPING WITH OTHER TRADES PRIOR TO INSTALLATION. ENSURE THAT ALL CONTROL DEVICES, ACCESS PANELS IN FINISHED SPACES, OTHER THAN THAT SHOWN, CONTRACTOR SHALL COORDINATE EXACT LOCATION OF PANELS PRIOR TO INSTALLATION. INSTALL EQUIPMENT, DUCTWORK AND PIPING TO BEST SUIT FIELD CONDITIONS AND COORDINATE WITH OTHER TRADES. 8. DUCT SIZES SHOWN ARE MINIMUM INSIDE DIMENSION. DUCT SIZES SHOWN ARE MINIMUM INSIDE DIMENSION. 9. EXACT LOCATION OF CEILING MOUNTED EQUIPMENT, AIR INLETS AND OUTLETS EXACT LOCATION OF CEILING MOUNTED EQUIPMENT, AIR INLETS AND OUTLETS INCLUDING ACCESS PANELS SHALL BE COORDINATED WITH THE ARCHITECTURAL REFLECTED CEILING PLAN. COORDINATE CEILING MOUNTED EQUIPMENT, AIR INLETS AND OUTLETS WITH CEILING SUPPORTS MEMBERS AND LOCATE CLEAR OF CEILING MEMBERS. 10. ALL NEW MATERIALS AND EQUIPMENT INSTALLED ABOVE CEILING SHALL BE ALL NEW MATERIALS AND EQUIPMENT INSTALLED ABOVE CEILING SHALL BE NON-COMBUSTIBLE AND U.L. APPROVED. ALL NEW WIRING SHALL BE NON-COMBUSTIBLE AND SHALL BE ENCLOSED IN METAL CONDUIT. 11. PROVIDE READILY VISIBLE NON-FUSIBLE DISCONNECT SWITCHES FOR ALL PROVIDE READILY VISIBLE NON-FUSIBLE DISCONNECT SWITCHES FOR ALL NEW EQUIPMENT. COORDINATE WITH OTHER TRADES. 12. HANDLE, STORE AND INSTALL ALL EQUIPMENT, PIPING AND DUCTWORK PER HANDLE, STORE AND INSTALL ALL EQUIPMENT, PIPING AND DUCTWORK PER MANUFACTURER'S INSTRUCTIONS. ALL EQUIPMENT, PIPING AND DUCTWORK SHALL BE PROTECTED FROM THE WEATHER ELEMENTS. 13. CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETE FUNCTIONALITY OF CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETE FUNCTIONALITY OF THE EQUIPMENT INCLUDING HIGH VOLTAGE, LOW VOLTAGE AND CONTROL ITEMS ASSOCIATED WITH THE PROJECT. 14. PROVIDE EQUIPMENT CLEARANCES IN ACCORDANCE WITH THE PROVIDE EQUIPMENT CLEARANCES IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND INSTRUCTIONS. 15. EQUIPMENT OF HIGHER ELECTRICAL CHARACTERISTICS MAY BE FURNISHED EQUIPMENT OF HIGHER ELECTRICAL CHARACTERISTICS MAY BE FURNISHED PROVIDED SUCH PROPOSED EQUIPMENT IS APPROVED IN WRITING AND CONNECTING ELECTRICAL SERVICES, CIRCUIT BREAKERS, AND CONDUIT SIZES ARE APPROPRIATELY MODIFIED WITHOUT COST TO THE OWNER. IF MINIMUM ENERGY RATINGS OR EFFICIENCIES ARE SPECIFIED, EQUIPMENT SHALL COMPLY WITH REQUIREMENTS. 16. CONTRACTOR IS TO MAINTAIN RECORDED "AS-BUILT" INFORMATION ON ALL CONTRACTOR IS TO MAINTAIN RECORDED "AS-BUILT" INFORMATION ON ALL EXISTING SERVICES UNCOVERED DURING CONSTRUCTION AND ALL NEW SERVICES BEING INSTALLED. "AS-BUILT" INFORMATION SHALL BE CLEARLY MARKED IN COLORED PENCIL ON A PRINT OF THE CONTRACT DRAWING. RECORDED INFORMATION SHALL INCLUDE ROUTING AND INVERT ELEVATIONS. AT THE COMPLETION OF THE CONTRACT, THE CONTRACTOR SHALL TURN RECORDED "AS-BUILT" INFORMATION OVER TO THE OWNER AND CONTRACTOR TO BE COORDINATED WITH AS BUILT REQUIREMENTS IN SPECIFICATION. 17. ARRANGE ALL PIPING WITHIN STRUCTURES NEATLY ALONG WALLS AND/OR IN ARRANGE ALL PIPING WITHIN STRUCTURES NEATLY ALONG WALLS AND/OR IN NEAT, HORIZONTAL GROUPS AND MAINTAIN REQUIRED SLOPES. 18. DO NOT SLEEVE STRUCTURAL MEMBERS WITHOUT CONSENT OF A LICENSED DO NOT SLEEVE STRUCTURAL MEMBERS WITHOUT CONSENT OF A LICENSED STRUCTURAL ENGINEER AND THE OWNER. 19. CONTRACTOR SHALL REMOVE, RELOCATE, REPLACE WITH NEW AND/OR CONTRACTOR SHALL REMOVE, RELOCATE, REPLACE WITH NEW AND/OR RECONNECT ALL EXISTING SERVICES AS REQUIRED BY NEW CONSTRUCTION. 20. INSTALL ALL DUCTS AND PIPING CONCEALED IN FURRED CEILING AND INSTALL ALL DUCTS AND PIPING CONCEALED IN FURRED CEILING AND CHASES UNLESS OTHERWISE INDICATED. 21. PROVIDE A HANGER NOT MORE THAN 12-INCHES FROM THE POINT OF PROVIDE A HANGER NOT MORE THAN 12-INCHES FROM THE POINT OF CHANGE OF DIRECTION OF A DUCT AND PIPE RUN IN BOTH HORIZONTAL AND VERTICAL PLANE. 22. SUPPORTS FOR ALL DUCTWORK AND PIPING SHALL BE IN ACCORDANCE WITH SUPPORTS FOR ALL DUCTWORK AND PIPING SHALL BE IN ACCORDANCE WITH THE LATEST SMACNA "GUIDELINES FOR SEISMIC RESTRAINTS OF MECHANICAL SYSTEMS AND PIPING SYSTEMS" AND MSS SP-58 AND SP-69. DUCTWORK AND PIPING HANGERS SHALL BE DESIGNED TO SUPPORT THE WEIGHT OF DUCTWORK AND PIPING INCLUDING THE WEIGHT OF THE CONTENTS OF THE PIPING. 23. SECURELY FASTEN DUCTWORK AND PIPING WITHIN STRUCTURES TO THE SECURELY FASTEN DUCTWORK AND PIPING WITHIN STRUCTURES TO THE BUILDING CONSTRUCTION BY MEANS OF HANGERS, SUPPORTS, GUIDES, ANCHORS, AND SWAY BRACES TO MAINTAIN DUCTWORK AND PIPING ALIGNMENT, TO PREVENT SAGGING, AND TO PREVENT NOISE AND EXCESSIVE STRAIN ON DUCTWORK AND PIPING DUE TO MOVEMENT UNDER OPERATING CONDITIONS. 24. CERTAIN VERTICAL AND HORIZONTAL OFFSETS ARE SHOWN IN DUCTWORK CERTAIN VERTICAL AND HORIZONTAL OFFSETS ARE SHOWN IN DUCTWORK AND PIPING ON PLANS TO INDICATE THE GENERAL POSITION RELATIONSHIP OF THE SYSTEMS. PROVIDE ADDITIONAL OFFSETS SIMILAR TO THOSE SHOWN, AS REQUIRED TO COORDINATE WITH INSTALLATION REQUIREMENTS OF OTHER SYSTEMS. 25. CONTRACTOR TO PROVIDE SUBMITTALS IN ACCORDANCE WITH THE CONTRACT CONTRACTOR TO PROVIDE SUBMITTALS IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. 26. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF CALIFORNIA BUILDING STANDARDS CODE, INCLUDING BUT NOT LIMITED TO CALIFORNIA BUILDING CODE, CALIFORNIA MECHANICAL CODE, CALIFORNIA PLUMBING CODE, CALIFORNIA ENERGY CODE, CALIFORNIA GREEN BUILDING STANDARDS CODE, AND LATEST COUNTY ADOPTED CODE. 27. PRIOR TO OCCUPANCY, THE HVAC SYSTEMS SHALL BE BALANCED IN PRIOR TO OCCUPANCY, THE HVAC SYSTEMS SHALL BE BALANCED IN ACCORDANCE WITH (AABC) ASSOCIATED AIR BALANCE COUNCIL STANDARDS BY AN INDEPENDENT AIR BALANCE CONTRACTOR. CERTIFICATION SHALL BE PROVIDED BY THE CONTRACTOR FOR AIR BALANCE OF AIR CONDITIONING SYSTEMS. 28. SEQUENCE WORK TO AVOID CUTTING AND PATCHING. IF NECESSARY, REMOVE SEQUENCE WORK TO AVOID CUTTING AND PATCHING. IF NECESSARY, REMOVE AND REPAIR WALL/CEILING FOR ACCESS TO WORK ON THE MECHANICAL SYSTEMS (SEE ARCHITECTURAL PLANS). PATCH AND FINISH TO MATCH ADJACENT SURFACE. 29. PROVIDE ALL TRANSITION IN DUCTWORK REQUIRED TO CROSS PIPING OR PROVIDE ALL TRANSITION IN DUCTWORK REQUIRED TO CROSS PIPING OR OTHER OBSTRUCTIONS. MAINTAIN EQUIVALENT CROSS-SECTIONAL AREA WITH MINIMUM DUCT SIZE 6" INSIDE DIMENSION. DUCT SHALL TRANSITION BACK TO ORIGINAL SIZE UPON PASSING ANY OBSTRUCTIONS. 30. PROVIDE VOLUME DAMPERS FOR EACH BRANCH DUCTWORK. VOLUME PROVIDE VOLUME DAMPERS FOR EACH BRANCH DUCTWORK. VOLUME DAMPERS SHALL BE LOW LEAKAGE WITH SHAFT SEAL, AND REMOVABLE AND REVERSIBLE HANDLE. 31. ALL EQUIPMENT, FIXTURES, ETC. SHALL BE IN ACCORDANCE WITH ALL EQUIPMENT, FIXTURES, ETC. SHALL BE IN ACCORDANCE WITH MANUFACTURERS' INSTRUCTION. 32. DEMOLITION AND NEW INSTALLATION WORK SHALL BE PERFORMED CAREFULLY DEMOLITION AND NEW INSTALLATION WORK SHALL BE PERFORMED CAREFULLY TO AVOID DAMAGE TO SURFACES, STRUCTURES AND EQUIPMENT NOT BEING REMOVED. ANY DAMAGE INCURRED SHALL BE RESTORED TO ORIGINAL CONDITION WITHOUT ANY ADDITIONAL COST. 33. NOT ALL EXISTING SYSTEMS ARE SHOWN TO AID DRAWING INTERPRETATION NOT ALL EXISTING SYSTEMS ARE SHOWN TO AID DRAWING INTERPRETATION CLARITY. 34. THE EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE BASED ON THE EXISTING SYSTEMS SHOWN ON THE DRAWINGS ARE BASED ON INFORMATION CONTAINED IN THE ORIGINAL DESIGN "AS-BUILT" DOCUMENTS AND ON A LIMITED FIELD SURVEY. 35. CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL VERIFICATION AND CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL VERIFICATION AND COORDINATION OF EXISTING CONDITIONS. VERIFY EXISTING CONDITIONS IN THE FIELD PRIOR TO START OF DEMOLITION WORK. 36. PATCH AND REPAIR ALL EXISTING WALL, CEILING, ROOF AND/OR FLOOR PATCH AND REPAIR ALL EXISTING WALL, CEILING, ROOF AND/OR FLOOR OPENINGS FOR EXISTING EQUIPMENT BEING REMOVED, REINSTALLED AND/OR MODIFIED. MATCH EXISTING BUILDING MATERIALS. 37. TITLE 24 IS NOT REQUIRED FOR BUILDING OCCUPANCY TYPE I PER TITLE 24 IS NOT REQUIRED FOR BUILDING OCCUPANCY TYPE I PER CALIFORNIA ENERGY COMMISSION TITLE 24 STANDARDS SECTION 1.7. 38. PROVIDE POLLUTANT CONTROL PER 2013 CGBSC SECTION 5.504. PROVIDE POLLUTANT CONTROL PER 2013 CGBSC SECTION 5.504. 39. FLEXIBLE DUCT SHALL BE 5 FT. MAXIMUM IN LENGTH. DO NOT INSTALL FLEXIBLE DUCT SHALL BE 5 FT. MAXIMUM IN LENGTH. DO NOT INSTALL UCT SHALL BE 5 FT. MAXIMUM IN LENGTH. DO NOT INSTALL ALL BE 5 FT. MAXIMUM IN LENGTH. DO NOT INSTALL RIBBED TYPE FLEXIBLE DUCTWORK. 40. PROVIDE FLEXIBLE CONNECTIONS AT PIECES OF ISOLATED EQUIPMENT ONLY PROVIDE FLEXIBLE CONNECTIONS AT PIECES OF ISOLATED EQUIPMENT ONLY AS SHOWN ON THE DETAILS OR AS SPECIFIED. 41. REFER TO SPECIFICATIONS FOR ADDITIONAL RESPONSIBILITIES AS PART OF REFER TO SPECIFICATIONS FOR ADDITIONAL RESPONSIBILITIES AS PART OF THE CONTRACT DOCUMENTS. 42. VERIFY AT PROJECT SITE EXACT SIZE, LOCATION, INVERT ELEVATION, AND VERIFY AT PROJECT SITE EXACT SIZE, LOCATION, INVERT ELEVATION, AND CLEARANCE OF ALL EXISTING SERVICES BEING EXTENDED, RELOCATED, OR REMOVED. 43. PROVIDE A TIGHT SEAL OF INCOMBUSTIBLE MATERIAL AROUND ALL PIPES PROVIDE A TIGHT SEAL OF INCOMBUSTIBLE MATERIAL AROUND ALL PIPES WHICH PENETRATE FIRE SEPARATIONS. PROVIDE COLLARS OR TRIM RINGS AROUND PIPING TO RETAIN PACKING. 44. BEFORE PROCEEDING WITH ANY WORK THE CONTRACTOR SHALL SUBMIT FOR BEFORE PROCEEDING WITH ANY WORK THE CONTRACTOR SHALL SUBMIT FOR THE OWNER'S REPRESENTATIVE APPROVAL THEIR "SEQUENCE OF WORK PLAN" THAT DESCRIBES ALL THE WORK TO BE ACCOMPLISHED DURING THEIR CONTRACT. THE CONTRACTOR'S PLAN SHALL INCLUDE, BUT NOT NECESSARILY BE LIMITED TO: A. DESCRIPTION OF WHAT SYSTEM/SUBSYSTEM/EQUIPMENT THAT SHALL BE DESCRIPTION OF WHAT SYSTEM/SUBSYSTEM/EQUIPMENT THAT SHALL BE SHUTDOWN/ISOLATED/REPLACED ALONG WITH THE STARTING DATE AND DURATION OF THE SHUTDOWN PERIOD. B. A DETAILED DESCRIPTION OF THE WORK THAT WILL BE ACCOMPLISHED A DETAILED DESCRIPTION OF THE WORK THAT WILL BE ACCOMPLISHED DURING THE SHUTDOWN PERIOD. C. SIGN-OFF SHEET THAT INCLUDES THE OWNER'S REPRESENTATIVE SIGN-OFF SHEET THAT INCLUDES THE OWNER'S REPRESENTATIVE SIGNATURE APPROVING THE PARTICULAR SEQUENCE OF WORK REQUESTED PRIOR TO BEGINNING THE WORK AND THE OWNER'S REPRESENTATIVE SIGNATURE AUTHORIZING THE CONTRACTOR TO PLACE THE SYSTEM/EQUIPMENT BACK IN USE AFTER THE WORK HAS BEEN COMPLETED TO THE OWNER'S REPRESENTATIVE SATISFACTION.
MECHANICAL GENERAL NOTES
12-15-202560% SUBMITTAL
10-28-2025
FURNACE REPLACEMENT
07-16-2026100% SUBMITTAL2
PROJECT, PW 26-O5B
M002
AS HH
NTS
MECHANICAL
ABBREVIATIONS AND
LEGEND
AutoCAD SHX Text Drawing No.
AutoCAD SHX Text Cad File:
AutoCAD SHX Text Xref:
AutoCAD SHX Text Drawn By
AutoCAD SHX Text Date:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Checked By
AutoCAD SHX Text Sheet Title
AutoCAD SHX Text Description
AutoCAD SHX Text
ADDENDUMS
AutoCAD SHX Text No.
AutoCAD SHX Text Date
AutoCAD SHX Text If this drawing is not 22" x 34", it is a reduced print - scale accordingly. All rights reserved. Material may not be reproduced in any form without permission from YEI engineers, Inc.
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text L
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text
NO. M38106
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text O
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text
EX. 09/30/26
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
ABBREV.
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
ROUND DUCTWORK, NET INSIDE DIMENSION
AutoCAD SHX Text 6%%C
AutoCAD SHX Text
DEMOLITION WORK
AutoCAD SHX Text
XX
AutoCAD SHX Text
XX
AutoCAD SHX Text
MECHANICAL EQUIPMENT TAG
AutoCAD SHX Text
POINT OF CONNECTION
AutoCAD SHX Text
POC
AutoCAD SHX Text Y
AutoCAD SHX Text X
AutoCAD SHX Text EXHAUST AIR GRILLE WITH DUCTWORK X-TYPE OF AIR INLET (REFER TO AIR OUTLET & INLET SCHEDULE) Y-EXHAUST AIR FLOW RATE, CFM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DETAIL NUMBER
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
MECHANICAL LEGEND
AutoCAD SHX Text
FD
AutoCAD SHX Text
FIRE DAMPER
AutoCAD SHX Text Y
AutoCAD SHX Text X
AutoCAD SHX Text SUPPLY AIR DIFFUSER WITH DUCTWORK X-TYPE OF AIR OUTLET (REFER TO AIR OUTLET & INLET SCHEDULE) Y-SUPPLY AIR FLOW RATE, CFM
AutoCAD SHX Text Y
AutoCAD SHX Text X
AutoCAD SHX Text RETURN AIR GRILLE WITH DUCTWORK X-TYPE OF AIR INLET (REFER TO AIR OUTLET & INLET SCHEDULE) Y-RETURN AIR FLOW RATE, CFM
AutoCAD SHX Text
POINT OF DEMOLITION
AutoCAD SHX Text
POD
AutoCAD SHX Text
EXHAUST DUCT UP
AutoCAD SHX Text
DUCT SMOKE DETECTOR
AutoCAD SHX Text
DD
AutoCAD SHX Text T
AutoCAD SHX Text
THERMOSTAT
AutoCAD SHX Text
FLEXIBLE DUCT
AutoCAD SHX Text
SUPPLY DUCT UP
AutoCAD SHX Text
RETURN DUCT UP
AutoCAD SHX Text
BUILDING AREAS NOT IN SCOPE
AutoCAD SHX Text
KEY NOTE
AutoCAD SHX Text
MECHANICAL ABBREVIATIONS
AutoCAD SHX Text
SMOKE/FIRE DAMPER
AutoCAD SHX Text
SFD
AutoCAD SHX Text
AABC ASSOCIATED AIR BALANCING COUNCIL
AutoCAD SHX Text
ABBREV ABBREVIATIONS
AutoCAD SHX Text
ACCU AIR-COOLED CONDENSING UNIT
AutoCAD SHX Text
AD/AP ACCESS DOOR/ACCESS PANEL
AutoCAD SHX Text
AFF ABOVE FINISHED FLOOR
AutoCAD SHX Text
AI ANALOG INPUT
AutoCAD SHX Text
AO ANALOG OUTPUT
AutoCAD SHX Text
AMPS AMPERES
AutoCAD SHX Text
ASME AMERICAN SOCIETY OF MECHANICAL
AutoCAD SHX Text
ENGINEERS
AutoCAD SHX Text
AVE AVERAGE
AutoCAD SHX Text
BCU BUILDING CONTROL UNIT
AutoCAD SHX Text
BDD BACKDRAFT DAMPER
AutoCAD SHX Text
BOD BOTTOM OF DUCT / BASIS OF DESIGN
AutoCAD SHX Text
BOP BOTTOM OF PIPE (ABOVE FIN. FLR.)
AutoCAD SHX Text
BTUH BRITISH THERMAL UNITS PER HOUR
AutoCAD SHX Text
CD CEILING DIFFUSER/CONDENSATE
AutoCAD SHX Text
CFM CUBIC FEET PER MINUTE
AutoCAD SHX Text
CLG CEILING
AutoCAD SHX Text
CONC CONCRETE
AutoCAD SHX Text
CONT CONTINUATION
AutoCAD SHX Text
CPF CHEMICAL POT FEEDER
AutoCAD SHX Text
°F DEGREES FAHRENHEIT
AutoCAD SHX Text dBA A-WEIGHTED DECIBELS
AutoCAD SHX Text
DD DUCT SMOKE DETECTOR
AutoCAD SHX Text
DI DIGITAL INPUT
AutoCAD SHX Text
DIA DIAMETER
AutoCAD SHX Text
DN DOWN
AutoCAD SHX Text
DWG(S) DRAWING(S)
AutoCAD SHX Text
DB DRY BULB
AutoCAD SHX Text
(E) EXISTING
AutoCAD SHX Text
EA EXHAUST AIR
AutoCAD SHX Text
ER/EG EXHAUST REGISTER/EXHAUST GRILLE
AutoCAD SHX Text
EFF EFFICIENCY
AutoCAD SHX Text
ELECT ELECTRICAL
AutoCAD SHX Text
ELEV ELEVATION
AutoCAD SHX Text
EMCS ENERGY MONITORING AND CONTROL SYSTEM
AutoCAD SHX Text
ENT ENTERING
AutoCAD SHX Text
ESP EXTERNAL STATIC PRESSURE
AutoCAD SHX Text
EWT ENTERING WATER TEMPERATURE
AutoCAD SHX Text
EXH EXHAUST
AutoCAD SHX Text
FCU FAN COIL UNIT
AutoCAD SHX Text
FD FIRE DAMPER
AutoCAD SHX Text
FF FINISHED FLOOR
AutoCAD SHX Text
FLR FLOOR
AutoCAD SHX Text
FPM FEET PER MINUTE
AutoCAD SHX Text
FS FLOW SWITCH
AutoCAD SHX Text
FSD FIRE SMOKE DAMPER
AutoCAD SHX Text
GAL GALLON
AutoCAD SHX Text
GPM GALLON(S) PER MINUTE
AutoCAD SHX Text
HP HORSEPOWER
AutoCAD SHX Text
HVAC HEATING, VENTILATION, AND AIR CONDITIONING
AutoCAD SHX Text
HZ HERTZ
AutoCAD SHX Text
I.D. IDENTIFICATION
AutoCAD SHX Text
IN WG INCHES WATER GAUGE
AutoCAD SHX Text
KW KILO-WATTS
AutoCAD SHX Text
LB(S) POUND(S)
AutoCAD SHX Text
LVG LEAVING
AutoCAD SHX Text
LWT LEAVING WATER TEMPERATURE
AutoCAD SHX Text
MAX MAXIMUM
AutoCAD SHX Text
MBH THOUSAND BRITISH THERMAL UNIT PER HOUR
AutoCAD SHX Text
MECH MECHANICAL
AutoCAD SHX Text
MM MILLIMETER
AutoCAD SHX Text
MIN MINIMUM
AutoCAD SHX Text
MSS MANUFACTURER STANDARDIZATION SOCIETY
AutoCAD SHX Text
MSS SP-58 PIPE HANGERS AND SUPPORTS- MATERIALS,
AutoCAD SHX Text
DESIGN AND MANUFACTURE
AutoCAD SHX Text
MSS SP-69 PIPE HANGERS AND SUPPORTS- SELECTION
AutoCAD SHX Text
AND APPLICATION
AutoCAD SHX Text
MVD MANUAL VOLUME DAMPER
AutoCAD SHX Text
(N) NEW
AutoCAD SHX Text
NC NORMALLY CLOSED/NOISE CRITERIA
AutoCAD SHX Text
NEEB NATIONAL ENVIRONMENTAL BALANCING BUREAU
AutoCAD SHX Text
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
AutoCAD SHX Text
NO NORMALLY OPEN
AutoCAD SHX Text
OA OUTSIDE AIR
AutoCAD SHX Text
PD PRESSURE DROP
AutoCAD SHX Text
PH PHASE
AutoCAD SHX Text
PLBG PLUMBING
AutoCAD SHX Text
POC POINT OF CONNECTION
AutoCAD SHX Text
PTT PRESSURE & TEMPERATURE TEST PLUG
AutoCAD SHX Text
QTY QUANTITY
AutoCAD SHX Text
RF RETURN FAN
AutoCAD SHX Text
RPM REVOLUTIONS PER MINUTE
AutoCAD SHX Text
RA RETURN AIR
AutoCAD SHX Text
SA SUPPLY AIR
AutoCAD SHX Text
SF SUPPLY FAN
AutoCAD SHX Text
SMACNA SHEET METAL AND AIR CONDITIONING
AutoCAD SHX Text
CONTRACTORS NATIONAL ASSOCIATION
AutoCAD SHX Text
SS STAINLESS STEEL
AutoCAD SHX Text
T'STAT THERMOSTAT
AutoCAD SHX Text
TEMP TEMPERATURE
AutoCAD SHX Text
TYP TYPICAL
AutoCAD SHX Text
UL UNDERWRITERS LABORATORIES
AutoCAD SHX Text
UNO UNLESS NOTED OTHERWISE
AutoCAD SHX Text
UTR UP THRU ROOF
AutoCAD SHX Text
V VOLTS
AutoCAD SHX Text
VAV VARIABLE AIR VOLUME
AutoCAD SHX Text
W WATTS
AutoCAD SHX Text
WB WET BULB
AutoCAD SHX Text
WG WATER GAUGE
AutoCAD SHX Text
WT WEIGHT
AutoCAD SHX Text
W/ WITH
AutoCAD SHX Text
ABBREVIATION
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SQUARE/RECTANGULAR ELBOW WITH TURNING VANES
AutoCAD SHX Text
ROUND ELBOW
AutoCAD SHX Text
ROUND DUCT DOWN
AutoCAD SHX Text
EXHAUST AIR DUCT UP
AutoCAD SHX Text
EXHAUST AIR DUCT DOWN
AutoCAD SHX Text
ROUND DUCT UP
AutoCAD SHX Text
RETURN AIR DUCT DOWN
AutoCAD SHX Text
RETURN AIR DUCT UP
AutoCAD SHX Text
SUPPLY AIR DUCT DOWN
AutoCAD SHX Text
SUPPLY AIR DUCT UP
AutoCAD SHX Text
DUCT DROP
AutoCAD SHX Text
DUCT RISE
AutoCAD SHX Text
LINED DUCTWORK (OR PLENUM)
AutoCAD SHX Text
FIRE DAMPER, FIRE SMOKE DAMPER
AutoCAD SHX Text
MANUAL VOLUME DAMPER
AutoCAD SHX Text
DN
AutoCAD SHX Text
UP
AutoCAD SHX Text
BALL VALVE
AutoCAD SHX Text
SUCTION DIFFUSER WITH STRAINER
AutoCAD SHX Text
PSD
AutoCAD SHX Text
THERMOMETER
AutoCAD SHX Text
MOTORIZED ON/OFF CONTROL BUTTERFLY VALVE
AutoCAD SHX Text M
AutoCAD SHX Text
DOMESTIC COLD WATER BACKFLOW PREVENTER ASSEMBLY
AutoCAD SHX Text
PUMP
AutoCAD SHX Text P
AutoCAD SHX Text
PRESSURE GAGE
AutoCAD SHX Text
BUTTERFLY VALVE
AutoCAD SHX Text
BV
AutoCAD SHX Text
NEEDLE VALVE
AutoCAD SHX Text
PRESSURE REDUCING VALVE
AutoCAD SHX Text
DL
AutoCAD SHX Text
DOOR LOUVER
AutoCAD SHX Text
UC
AutoCAD SHX Text
DOOR UNDERCUT
AutoCAD SHX Text
PRV
AutoCAD SHX Text
SW
AutoCAD SHX Text
SWITCH
AutoCAD SHX Text
ABBREV.
AutoCAD SHX Text
POC
AutoCAD SHX Text
POD
12-15-202560% SUBMITTAL
10-28-2025
FURNACE REPLACEMENT
07-16-2026100% SUBMITTAL2
PROJECT, PW 26-O5B
M003
PW HH
NTS
MECHANICAL
SCOPE OF WORK AND
SEQUENCE
AutoCAD SHX Text Drawing No.
AutoCAD SHX Text Cad File:
AutoCAD SHX Text Xref:
AutoCAD SHX Text Drawn By
AutoCAD SHX Text Date:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Checked By
AutoCAD SHX Text Sheet Title
AutoCAD SHX Text Description
AutoCAD SHX Text
ADDENDUMS
AutoCAD SHX Text No.
AutoCAD SHX Text Date
AutoCAD SHX Text If this drawing is not 22" x 34", it is a reduced print - scale accordingly. All rights reserved. Material may not be reproduced in any form without permission from YEI engineers, Inc.
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text L
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text
NO. M38106
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text O
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text
EX. 09/30/26
AutoCAD SHX Text DEMOLITION: 1. DEMOLISH FLOOR-MOUNTED VERTICAL GAS FURNACES, F-4 AND F-5 AND DEMOLISH FLOOR-MOUNTED VERTICAL GAS FURNACES, F-4 AND F-5 AND ASSOCIATED APPURTENANCES. DEMOLISH PORTIONS OF SUPPLY AND RETURN AIR DUCTWORK INCLUDING THE COMBUSTION AND EXHAUST AIR PIPE RISERS AS SHOWN ON THE MECHANICAL DEMOLITION FLOOR PLANS. 2. REFER TO PLUMBING DRAWINGS FOR NATURAL GAS AND CONDENSATE DRAIN PIPING REFER TO PLUMBING DRAWINGS FOR NATURAL GAS AND CONDENSATE DRAIN PIPING DEMOLITION SCOPE OF WORK ASSOCIATED WITH THE MECHANICAL EQUIPMENT BEING DEMOLISHED. 3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL POWERS SUPPLY DEMOLITION REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL POWERS SUPPLY DEMOLITION SCOPE OF WORK ASSOCIATED WITH THE MECHANICAL EQUIPMENT BEING DEMOLISHED. NEW WORK: 1. INSTALL NEW INDOOR FLOOR MOUNTED VERTICAL GAS FURNACES F-4 AND F-5 INSTALL NEW INDOOR FLOOR MOUNTED VERTICAL GAS FURNACES F-4 AND F-5 COMPLETE WITH INSULATED RETURN AIR PLENUM BOX THAT IS ABLE TO SUPPORT THE OPERATING WEIGHT OF THE FURNACE AND SEISMICALLY ANCHOR TO THE EXISTING CONCRETE FLOOR WITH 1” THICK RUBBER PADS. INSULATED RETURN AIR THICK RUBBER PADS. INSULATED RETURN AIR PLENUM BOX SHALL BE PROVIDED MERV-13 AIR FILTER PRIOR TO CONNECTION TO GAS FURNACE RETURN AIR INTAKE. 2. INSTALL GAS FURNACE F-4 AND F-5 NEW INSULATED SUPPLY AND RETURN INSTALL GAS FURNACE F-4 AND F-5 NEW INSULATED SUPPLY AND RETURN DUCTWORK AND CONNECT TO (E) SUPPLY AND RETURN AIR DUCT ABOVE CEILING COMPLETE WITH FITTINGS AND SUPPORTS. 3. INSTALL NEW DUCT SMOKE DETECTOR AT SUPPLY AIR DUCT SIDE OF GAS FURNACE INSTALL NEW DUCT SMOKE DETECTOR AT SUPPLY AIR DUCT SIDE OF GAS FURNACE F-4, AND INTERFACE TO NEW MECHANICAL DIRECT DIGITAL CONTROL SYSTEM AND (E) MAIN FIRE ALARM PANEL. 4. INSTALL GAS FURNACE F-4 AND F-5 NEW PVC SCHEDULE 40 COMBUSTION AIR INSTALL GAS FURNACE F-4 AND F-5 NEW PVC SCHEDULE 40 COMBUSTION AIR AND EXHAUST VENT PIPE AND CONNECT TO EXISTING COMBUSTION AIR AND EXHAUST VENT PIPE RISERS BELOW CEILING COMPLETE WITH PIPE FITTINGS AND SUPPORTS. 5. INSTALL GAS FURNACE F-4 NEW WALL MOUNTED THERMOSTAT WITH LCD DISPLAY INSTALL GAS FURNACE F-4 NEW WALL MOUNTED THERMOSTAT WITH LCD DISPLAY AT THE SAME LOCATION AS THE EXISTING COMPLETE WITH CONTROL WIRING AND ASSOCIATED APPURTENANCES. 6. INSTALL GAS FURNACE F-5 NEW WALL MOUNTED THERMOSTAT WITH LCD DISPLAY INSTALL GAS FURNACE F-5 NEW WALL MOUNTED THERMOSTAT WITH LCD DISPLAY AT THE SAME LOCATION AS THE EXISTING COMPLETE WITH CONTROL WIRING AND ASSOCIATED APPURTENANCES. 7. INSTALL GAS FURNACE F-4 AND F-5 NEW CONDENSATE NEUTRALIZERS. REFER TO INSTALL GAS FURNACE F-4 AND F-5 NEW CONDENSATE NEUTRALIZERS. REFER TO PLUMBING DRAWINGS FOR CONDENSATE PIPING AND DETAILS. 8. INSTALL NEW MECHANICAL DIRECT DIGITAL CONTROL SYSTEM USING BACNET INSTALL NEW MECHANICAL DIRECT DIGITAL CONTROL SYSTEM USING BACNET COMMUNICATION PROTOCOL AND INTERFACE TO COUNTY FACILITY OPERATION CONTROL CENTER FOR REMOTE MONITORING AND CONTROL. 9. PERFORM TESTING, ADJUSTING, AND BALANCING FOR NEW GAS FURNACES (F-4 PERFORM TESTING, ADJUSTING, AND BALANCING FOR NEW GAS FURNACES (F-4 AND F-5) AND ASSOCIATED CEILING AIR OUTLETS. 10. CLEAN THE EXISTING HRV-2 AND HRV-3 ENTIRE HVAC AIR-DISTRIBUTION DUCTS, CLEAN THE EXISTING HRV-2 AND HRV-3 ENTIRE HVAC AIR-DISTRIBUTION DUCTS, PLENUM, AIR OUTLETS, OUTDOOR AIR INTAKE HOOD, EXHAUST AIR HOOD, AND SYSTEM COMPONENTS PER NATIONAL AIR DUCT CLEANERS ASSOCIATION (NADCA ACR) AND SPECIFICATION 23 01 30.52. EXISTING HRV UNITS CLEANING NOT IN SCOPE. 11. CLEAN THE EXISTING EXHAUST FAN EF-3 SERVING THE DOG KENNELS #139 AND CLEAN THE EXISTING EXHAUST FAN EF-3 SERVING THE DOG KENNELS #139 AND THE ENTIRE VENTILATION AIR-DISTRIBUTION DUCTS, AIR OUTLETS, AND SYSTEM COMPONENTS PER NATIONAL AIR DUCT CLEANERS ASSOCIATION (NADCA ACR) AND SPECIFICATION 23 01 30.52. 12. CLEAN THE TWO EXISTING EXHAUST FANS SERVING THE DOG KENNELS #144 AND CLEAN THE TWO EXISTING EXHAUST FANS SERVING THE DOG KENNELS #144 AND DOG KENNELS #145, AND THE ENTIRE VENTILATION AIR-DISTRIBUTION DUCTS, AIR OUTLETS, AND SYSTEM COMPONENTS PER NATIONAL AIR DUCT CLEANERS ASSOCIATION (NADCA ACR) AND SPECIFICATION 23 01 30.52. 13. PERFORM AND PASS ALL APPLICABLE ACCEPTANCE TESTING FOR MECHANICAL PERFORM AND PASS ALL APPLICABLE ACCEPTANCE TESTING FOR MECHANICAL SYSTEMS REQUIRED BY THE CALIFORNIA ENERGY CODE. ACCEPTANCE TESTING FOR MECHANICAL SYSTEMS MUST BE PERFORMED BY A CERTIFIED MECHANICAL ACCEPTANCE TEST TECHNICIAN (ATT) AND DOCUMENTED ON THE APPLICABLE NONRESIDENTIAL CERTIFICATE OF ACCEPTANCE (NRCA) FORMS.
MECHANICAL SCOPE OF WORK
12-15-202560% SUBMITTAL
10-28-2025
FURNACE REPLACEMENT
07-16-2026100% SUBMITTAL2
PROJECT, PW 26-O5B
M004
AS HH
NTS
MECHANICAL
EQUIPMENT SCHEDULES
AutoCAD SHX Text Drawing No.
AutoCAD SHX Text Cad File:
AutoCAD SHX Text Xref:
AutoCAD SHX Text Drawn By
AutoCAD SHX Text Date:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Checked By
AutoCAD SHX Text Sheet Title
AutoCAD SHX Text Description
AutoCAD SHX Text
ADDENDUMS
AutoCAD SHX Text No.
AutoCAD SHX Text Date
AutoCAD SHX Text If this drawing is not 22" x 34", it is a reduced print - scale accordingly. All rights reserved. Material may not be reproduced in any form without permission from YEI engineers, Inc.
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text L
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text
NO. M38106
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text O
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text O
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text G
AutoCAD SHX Text E
AutoCAD SHX Text
EX. 09/30/26
AutoCAD SHX Text
FURNACE SCHEDULE
AutoCAD SHX Text
EQUIP. I.D.
AutoCAD SHX Text
BUILDING/ LOCATION
AutoCAD SHX Text
AREA SERVE
AutoCAD SHX Text
GAS FURNACE DATA
AutoCAD SHX Text
SUPPLY FAN
AutoCAD SHX Text
AIR FILTER DATA
AutoCAD SHX Text
MIN. CIRCUIT AMPS. @ 115V/1PH/ 60HZ
AutoCAD SHX Text
APPROX. OPER. WT.
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
MANUFACTURER / MODEL OR APPROVED EQUAL
AutoCAD SHX Text
MAX. INPUT HEATING CAPACITY
AutoCAD SHX Text
MIN. OUTPUT HEATING CAPACITY
AutoCAD SHX Text
MIN. AFUE
AutoCAD SHX Text
ENT. AIR TEMP.
AutoCAD SHX Text
LVG. AIR TEMP.
AutoCAD SHX Text
GAS CONNECTION SIZE
AutoCAD SHX Text
COMBUSTION AIR SIZE
AutoCAD SHX Text
EXHAUST SIZE
AutoCAD SHX Text
IGNITION SYSTEM TYPE
AutoCAD SHX Text
HEATING STAGES
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
MAX/MIN AIR FLOW RATE FOR HEATING
AutoCAD SHX Text
ESP FOR HEATING
AutoCAD SHX Text
MIN. O.A.
AutoCAD SHX Text
MOTOR RATING @ 115V/1PH/60HZ
AutoCAD SHX Text
FILTER TYPE/ THICKNESS/ ARRESTANCE EFFICIENCY
AutoCAD SHX Text
MAX FACE VELOCITY
AutoCAD SHX Text
MBH
AutoCAD SHX Text
MBH
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text
IN
AutoCAD SHX Text
IN
AutoCAD SHX Text
IN
AutoCAD SHX Text
CFM
AutoCAD SHX Text
IN. W.G.
AutoCAD SHX Text
CFM
AutoCAD SHX Text
HP
AutoCAD SHX Text
INCHES
AutoCAD SHX Text
FPM
AutoCAD SHX Text
LBS.
AutoCAD SHX Text F-4
AutoCAD SHX Text
NAPA ANIMAL SHELTER/ EQUIP #145
AutoCAD SHX Text
DOG KENNELS #146 & DOG ISOLATION #147
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 95.0
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1/2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HOT SURFACE
AutoCAD SHX Text
MULTI STAGE GAS HEAT
AutoCAD SHX Text
CENTRIFUGAL FAN - CONSTANT SPEED
AutoCAD SHX Text
AutoCAD SHX Text 0.2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WASHABLE / 3/4 / -
AutoCAD SHX Text
AutoCAD SHX Text
SEE NOTES BELOW
AutoCAD SHX Text F-5
AutoCAD SHX Text
NAPA ANIMAL SHELTER/ EQUIP #142
AutoCAD SHX Text
DOG KENNELS #143
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 95.0
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1/2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HOT SURFACE
AutoCAD SHX Text
MULTI STAGE GAS HEAT
AutoCAD SHX Text
CENTRIFUGAL FAN - CONSTANT SPEED
AutoCAD SHX Text
AutoCAD SHX Text 0.2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WASHABLE / 3/4 / -
AutoCAD SHX Text
AutoCAD SHX Text
SEE NOTES BELOW
AutoCAD SHX Text NOTES: 1. FURNACE SHALL BE SINGLE PASS, 100% OUTSIDE AIR, VERTICAL, HIGH EFFICIENCY, CONSTANT SPEED, MULTI-STAGE CONDENSING GAS FURNACE. 2. PROVIDE WALL MOUNTED THERMOSTAT WITH LCD DISPLAY. 3. FURNACE SHALL BE PROVIDED WITH FABRICATED RA/OA INSULATED STRUCTURAL PLENUM BOX SHALL BE ABLE TO SUPPORT THE FULL OPERATING WEIGHT OF THE GAS FURNACE, GAS PIPING, AND INSULATED VERTICAL SUPPLY AIR DUCT. 4. PROVIDE CONDENSATE PUMP WITH CONDENSATE NEUTRALIZER (LITTLE GIANT MODEL VCMA-20-NPTC WITH RNTC-500 MEDIA) INCLUDING CONDENSATE DRAIN PIPING. 5. FURNACE SHALL BE PROVIDED WITH DDC BACNET CONTROL CARD FOR BUILDING ENERGY MANAGEMENT AND CONTROL SYSTEM INTERFACE. PROVIDED BY MECHANICAL CONTRACTOR AND INSTALLED BY PLUMBING CONTRACTOR. 6. PROVIDE DUCT SMOKE DETECTOR ON SUPPLY AIR DUCT RISER AND WIRE TO EXISTING BUILDING FIRE ALARM PANEL FOR ALARM NOTIFICATION. DUCT SMOKE DETECTOR SHALL SHUTDOWN THE FURNACE UPON DETECTION OF SMOKE IN ACCORDANCE WITH CMC.
AutoCAD SHX Text
MAX/MIN AIR FLOW RATE FOR COOLING
AutoCAD SHX Text
CFM
AutoCAD SHX Text 430/2255
AutoCAD SHX Text 430/2255
AutoCAD SHX Text
ESP
AutoCAD SHX Text
IN. W.G.
AutoCAD SHX Text 0.5
AutoCAD SHX Text 0.5
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CARRIER/59SU5B
CARRIER/59SU5B
NEW ROAD
123456
PARKING
B
A
A1
B
A
123456
N E
W R
A
IL
R O
A D
A L
IG
N M
E N
T
E X
IS
T
IN
G R
A
IL
R O
A D
ANIMAL SHELTER PHASE I
NAPA COUNTY
12-15-202560% SUBMITTAL
10-28-2025
FURNACE REPLACEMENT
07-16-2026100% SUBMITTAL2
PROJECT, PW 26-O5B
M100
AS HH
NTS
MECHANICAL
GROUND KEY PLAN
AutoCAD SHX Text x
AutoCAD SHX Text x
AutoCAD SHX Text
FUTURE ACCESS ROAD WITH CURB & GUTTER
AutoCAD SHX Text 13.50
AutoCAD SHX Text 12.17
AutoCAD SHX Text 12.17
AutoCAD SHX Text
FUTURE RAILROAD
AutoCAD SHX Text
RIGHT-OF-WAY
AutoCAD SHX Text
WH
AutoCAD SHX Text
ANIMAL RECEIVING
AutoCAD SHX Text C.G.
AutoCAD SHX Text C.G.
AutoCAD SHX Text C.G.
AutoCAD SHX Text C.G.
AutoCAD SHX Text
STRAY CATS
AutoCAD SHX Text
ISO. CATS
AutoCAD SHX Text
TRAINING ROOM
AutoCAD SHX Text
BREAK ROOM
AutoCAD SHX Text
WOMEN
AutoCAD SHX Text
KITCHEN
AutoCAD SHX Text
GROOMING &
AutoCAD SHX Text
CAT
AutoCAD SHX Text
EXERCISE
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
GARAGE
AutoCAD SHX Text
FOOD STORAGE
AutoCAD SHX Text
CLINIC
AutoCAD SHX Text
SPRINKLER
AutoCAD SHX Text
DRY STORAGE
AutoCAD SHX Text
FERAL CATS
AutoCAD SHX Text
LOBBY
AutoCAD SHX Text
RECEPTION
AutoCAD SHX Text
DOG KENNELS
AutoCAD SHX Text
HALL
AutoCAD SHX Text
EQUIP.
AutoCAD SHX Text
GET ACQUAINTED
AutoCAD SHX Text
EQUIP.
AutoCAD SHX Text
CAT
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
CLIENT
AutoCAD SHX Text
FRONT
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
SUPERVISOR'S
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
TELEPHONE CL.
AutoCAD SHX Text
EQUIP.
AutoCAD SHX Text
PUPPIES &
AutoCAD SHX Text
SMALL BREEDS
AutoCAD SHX Text
EUTHANASIA
AutoCAD SHX Text
CAT & DOG
AutoCAD SHX Text
RECEIVING
AutoCAD SHX Text
EQUIP.
AutoCAD SHX Text
HALL
AutoCAD SHX Text
DOG ISOLATION
AutoCAD SHX Text
STAFF HALLWAY
AutoCAD SHX Text
ANIMAL NIGHT DROPS
AutoCAD SHX Text
HALL
AutoCAD SHX Text
GET
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
WALK-IN
AutoCAD SHX Text
FREEZER
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
HALL
AutoCAD SHX Text
AQUT'D
AutoCAD SHX Text
LAUNDRY
AutoCAD SHX Text
JANITOR
AutoCAD SHX Text
MEN
AutoCAD SHX Text
SHOWER
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
COURTYARD
AutoCAD SHX Text
DOG QUARANTINE
AutoCAD SHX Text
HALL
AutoCAD SHX Text
HALL
AutoCAD SHX Text
HALL
AutoCAD SHX Text
HALL
AutoCAD SHX Text C.G.
AutoCAD SHX Text C.G.
AutoCAD SHX Text C.G.
AutoCAD SHX Text C.G.
AutoCAD SHX Text Drawing No.
AutoCAD SHX Text Cad File:
AutoCAD SHX Text Xref:
AutoCAD SHX Text Drawn By
AutoCAD SHX Text Date:
AutoCAD SHX Text Scale:
AutoCAD SHX Text Checked By
AutoCAD SHX Text Sheet Title
AutoCAD SHX Text Description
AutoCAD SHX Text
ADDENDUMS
AutoCAD SHX Text No.
AutoCAD SHX Text Date
AutoCAD SHX Text If this drawing is not 22" x 34", it is a reduced print - scale accordingly. All rights reserved. Material may not be reproduced in any form without permission from YEI engineers, Inc.
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text R
AutoCAD SHX Text M
AutoCAD SHX Text E
AutoCAD SHX Text T
AutoCAD SHX Text A
AutoCAD SHX Text T
AutoCAD SHX Text S
AutoCAD SHX Text N
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text H
AutoCAD SHX Text A
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCA…