PRWI_343092_Bathhouse_5B_DWGS_FINAL_25_0903.pdf

PDF 7 MB Posted

Attached to
NCR PRWI: C5 BATHHOUSE & VISITOR ACCESS Federal contract opportunity
Solicitation number
140P2126R0003
Issued by
Department of the Interior National Park Service

About this file

This document is a set of architectural and engineering design drawings for interior improvements to the Camp 5B Central Bathhouse at Prince William Forest Park (PRWI) in Triangle, Virginia, prepared by Alpha Corporation. The project involves renovating the interior of the existing bathhouse structure, which houses men's and women's bathrooms, shower areas, laundry facilities, and mechanical/utility spaces.

The scope of work includes demolition of existing interior elements and installation of new fixtures, finishes, and systems. Key architectural improvements encompass wall and floor tile work, door and frame replacements, interior wall painting, and ceiling treatments. The plumbing scope includes three instantaneous liquid propane domestic water heaters (DWH-1, DWH-2, DWH-3), ABAAS-compliant fixtures (water closets, urinals, lavatories, showers), floor drains, and complete hot and cold water distribution systems with proper trap seals and barrier protection. Mechanical systems include three wall-mounted electric resistance unit heaters (3,600 watts, 1,000 watts, and 1,000 watts respectively) and a powered roof ventilator with occupancy sensor controls. Electrical work comprises a 150-amp panelboard with branch circuits, lighting fixtures (recessed downlights, strip fixtures, and vanity fixtures), occupancy sensors, GFI-protected receptacles, and hand dryers. The drawings note the presence of assumed asbestos-containing materials and a fire door requiring proper handling during construction, with a hazardous materials assessment dated November 23, 2022 available for reference. All work is to conform to current building codes, accessibility standards, and applicable specifications for a federal National Park Service facility.

View the file

Other files for this federal contract opportunity

Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MAKE IMPROVEMENTS TO INTERIOR OF CAMP 5

CS1[COVER_5B].DWGN:\JOBS\DULLES\572-160-C PRWI CAMP 5 A&B BATHHOUSE - VC STAFF RESTROOM\5000 CIVIL\DWGS\CAMP 5B UNIT HENDERSONJ OCTOBER 4 2023

ALPHA

CORPORATION

21000 ATLANTIC BLVD, S. 400

www.alphacorporation.com

CENTRAL BATHHOUSE IN CAMP 5B UNIT

PRINCE WILLIAM FOREST PARK (PRWI)

PRINCE WILLIAM FOREST PARK

jbello Text Box

Δ1 G1 CLARIFY REQ 9/3/25 JPB

G

G

G

X

X

G1[SITE ACCESS 5B].DWGN:\JOBS\DULLES\572-160-C PRWI CAMP 5 A&B BATHHOUSE - VC STAFF RESTROOM\5000 CIVIL\DWGS\CAMP 5B UNIT HENDERSONJ OCTOBER 4 2023

ALPHA

CORPORATION

21000 ATLANTIC BLVD, S. 400

www.alphacorporation.com

LOCATION OF

CAMP 5A

LOCATION OF

CAMP 5B

LOCATION OF CENTRAL

BATHHOUSE IN CAMP 5B UNIT

CONTRACTOR STAGING

& PARKING AREA

SITE ACCESS ROUTE

MAWAVI ROAD

(GRAVEL SURFACE)

CONTRACTOR STAGING

AREA (25'X25')

jbello Line jbello Text Box

SET OF CONTRACT DOCUMENTS - SEE PRWI 242861.

A1-5B-GEN.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5B ANNE.KOPF OCTOBER 8 2023

ALPHA

CORPORATION

21000 ATLANTIC BLVD, S. 400

DULLES, VA 20166 (703)450-0800

www.alphacorporation.com

A2-5B-DEMO.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5B ANNE.KOPF OCTOBER 9 2023

CORPORATION

21000 ATLANTIC BLVD, S. 400

A3-5B-DEMORCP.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5B ANNE.KOPF OCTOBER 9 2023

CORPORATION

21000 ATLANTIC BLVD, S. 400

A4-5B-FLRPLN.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5B ANNE.KOPF NOVEMBER 6 2023

CORPORATION

21000 ATLANTIC BLVD, S. 400

A5-5B-RCP.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5B ANNE.KOPF OCTOBER 5 2023

CORPORATION

21000 ATLANTIC BLVD, S. 400

A6-5B-EXTELEV.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5B ANNE.KOPF NOVEMBER 6 2023

CORPORATION

21000 ATLANTIC BLVD, S. 400

A7-5B-INTELEV.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5B ANNE.KOPF OCTOBER 9 2023

CORPORATION

21000 ATLANTIC BLVD, S. 400

A8-5B-SCHED.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5B ANNE.KOPF OCTOBER 5 2023

CORPORATION

21000 ATLANTIC BLVD, S. 400

A9-5B-DTLS.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5B ANNE.KOPF OCTOBER 24 2023

CORPORATION

21000 ATLANTIC BLVD, S. 400

ABBREVIATIONS

ABV. ABOVE

A.D. AREA DRAIN/ACCESS DOOR

A.F.F. ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

A.P. ACCESS PANEL

BHP BRAKE HORSEPOWER

BTU BRITISH THERMAL UNITS

BTUH BRITISH THERMAL UNITS PER HOUR

C.O. CLEANOUT

CONC. CONCRETE

CW DOMESTIC COLD WATER

D DRAIN / DRYER

D.B. DRY BULB

DIA. DIAMETER

DN. DOWN

DW DISHWASHER

DWH DOMESTIC WATER HEATER

(E) EXISTING

EA. EACH

E.A. EXHAUST AIR

ENT. ENTERING

ETPV ELECTRONIC TRAP PRIMING VALVE

E.W.T. ENTERING WATER TEMPERATURE

EXIST. EXISTING

°F DEGREES FAHRENHEIT

F.C.O. FLOOR CLEANOUT

FLA. FULL LOAD AMPS

FL.D. FLOOR DRAIN

FLR. FLOOR

FT. FEET

GAL. GALLON

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

HR. HOUR

HW DOMESTIC HOT WATER

Hz HERTZ

IN. INCH(ES)

IW INDIRECT WASTE

JAN. JANITORS CLOSET

L LENGTH

LAV LAVATORY

LBS. POUNDS

LPG LIQUID PROPANE GAS

LVG. LEAVING

L.W.T. LEAVING WATER TEMPERATURE

M.A.V. MANUAL AIR VENT

MAX. MAXIMUM

M.E.R. MECHANICAL EQUIPMENT ROOM

MIN. MINIMUM

N.C. NORMALLY CLOSED

N.O. NORMALLY OPEN

O.C. ON CENTER

P.D. PRESSURE DROP

PRV PRESSURE RELIEF VALVE

PSI POUNDS PER SQUARE INCH

PVC POLYVINYL CHLORIDE

RLA RUNNING LOAD AMPS

RPM REVOLUTIONS PER MINUTE

SAN SANITARY

SS SERVICE SINK

TPV TRAP PRIMING VALVE

TYP. TYPICAL

UR URINAL

V VENT/VOLTS

V.S. VENT STACK

VTR VENT THRU ROOF

W WASTE / WIDTH / WASHING MACHINE

W/ WITH

W.B. WET BULB

W.C. WATERCOLUMN

WC WATER CLOSET

W.G. WATER GAUGE

DOMESTIC COLD WATER

CONDENSATE DRAIN PIPING

CW

D

GAS PIPING

DOMESTIC HOT WATER

G

HW

V W

W WASTE/SANITARY PIPE BELOW GRADE

WASTE/SANITARY PIPE

VENT PIPE

PIPE TURN UP

PIPE TURN DOWN

STRAINER

GATE VALVE

PRESSURE REDUCING VALVE

UNION

RELIEF VALVE

GAS COCK

CONCENTRIC REDUCER

DIRECTION OF FLOW

PRESSURE GAUGE

THERMOMETER AND WELL

C.O.

F.C.O.

FL.D. FLOOR DRAIN

FLOOR CLEANOUT

PIPE CLEANOUT

PIPE CAP

(E)

SYMBOLS

NORTH ARROW

BREAKLINE

DEMOLITION LINETYPE

CENTERLINE

EXISTING

POINT OF CONNECTION TO EXISTING

POINT OF TERMINATION OF REMOVAL

NOTE NUMBER

ARROW INDICATES

TRUE NORTH AND/OR

PROJECT NORTH

N

M101

N

8'0 1/8"=1'-0"

UNIQUE PLAN OR

DETAIL NUMBER

ON THIS DRAWING NORTH ARROW

NAME OF PLAN OR DETAIL

ALL DRAWINGS WHERE

DETAIL IS REFERENCED

GRAPHIC SCALE OF

PLAN OR DETAIL

2-PART REFERENCE DETAIL IDENTIFICATION:

SHEET NUMBER WHERE

DETAIL/SECTION IS DRAWN

NUMBER INDICATES

DETAIL/SECTION

FLOOR PLAN

M101, M1022

FLOOR PLAN AND DETAIL TITLES:

INSTANTANEOUS LIQUID PROPANE

DETAIL

DOMESTIC WATER HEATERS

P3 NOT TO SCALE

1-1/2"CW

3/4"LPG

1-1/2"HW-110°F

C.O.

T&P RELIEF

VALVE (TYP.)

PIPE TO

FLOOR SINK

1-1/2" COPPER COLD

WATER HEADER

1-1/2" COPPER HOT

WATER HEADER

3/4"LPG

3/4"LPG(TYP.)3/4"D(TYP.)

GAS COCK (TYP.)

DWH-1

SET @

110°F

DWH-2

SET @

110°F

DWH-3

SET @

110°F

M.E.R. FINISHED FLOOR FL.D.

3"W

PROVIDE FL.D. UNDER

HOT WATER HEATER.

2"

PROVIDE CONDENSATE

NEUTRALIZING CARTRIDGE

2"x4" CONCENTRIC SIDEWALL INTAKE & EXHAUST

VENT SUPPORT AND TERMINATE IN ACCORDANCE

WITH MANUFACTURER'S RECOMMENDATIONS. SEAL

PENETRATIONS WEATHERTIGHT. TOTAL EQUIVALENT

LENGTH OF DIRECT VENT AND NUMBER OF ELBOWS

NOT TO EXCEED MANUFACTURER'S RECOMMENDATIONS

CEILING

1-1/4"D

1-1/4"D

GRADE

SHUTOFF VALVE IN VERTICAL

SYMBOLS & ABBREVIATIONS.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5B BATHHOUSE ROACH OCTOBER 10 2023

ALPHA

CORPORATION

21000 ATLANTIC BLVD, S. 400

WC 1

WC 1 WC 1WC 1

WC 1

WC 1

FL.D. 5

FL.D.5

FL.D. 5 FL.D. 5

FL.D. 5

FL.D. 5

FL.D. 5

1 8

UR 2LAV 3

LAV3

LAV3

LAV3

LAV 3

LAV 3

LAV 3

11 8

4"W 1

9 4"W

2"CW

6 3/4"LPG

(E)6"EXH.

VENT UP

(E)2"CW

F.C.O. 10F.C.O.10

NDOMESTIC WATER DEMOLITION

CAMP 5B BATHHOUSE -

NSANITARY WASTE DEMOLITION

CAMP 5B BATHHOUSE -

WC 1 WC 1 WC 1

WC 1

UR 2LAV 3

LAV 3 LAV 3

3LAV 3

LAV 3 3

4 4

4"W

(E)3"VTR(E)3"VTR

(E)PROPANE TANK(E)PROPANE TANK

203.013 5B P2.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5B BATHHOUSE ROACH OCTOBER 10 2023

ALPHA

CORPORATION

21000 ATLANTIC BLVD, S. 400

www.alphacorporation.com

GENERAL NOTES

1. CAREFULLY REMOVE FLOOR MOUNTED TANK TYPE WATER CLOSET AND

RETURN TO THE PARK. REMOVE ASSOCIATED SUPPORTS AND

APPURTENANCES COMPLETE. REMOVE ASSOCIATED COLD WATER PIPE,

INSULATION, SUPPORTS, AND VALVES COMPLETE. REMOVE ASSOCIATED

WASTE PIPE COMPLETE. REMOVE ASSOCIATED VENT PIPE TO ABOVE

CEILING AND CAP PIPE.

2. REMOVE WALL MOUNTED URINAL, SUPPORTS, AND APPURTENANCES

COMPLETE. REMOVE ASSOCIATED COLD WATER PIPE, INSULATION,

SUPPORTS, AND VALVES COMPLETE. REMOVE ASSOCIATED WASTE PIPE

COMPLETE. REMOVE ASSOCIATED VENT PIPE TO ABOVE CEILING AND

CAP PIPE.

3. REMOVE WALL MOUNTED LAVATORY, SUPPORTS, FAUCET AND

APPURTENANCES COMPLETE. REMOVE ASSOCIATED COLD AND HOT

WATER PIPE, INSULATION, SUPPORTS AND VALVES COMPLETE. REMOVE

ASSOCIATED WASTE PIPE COMPLETE. REMOVE ASSOCIATED VENT PIPE

TO ABOVE CEILING AND CAP PIPE.

4. REMOVE SHOWERHEAD, SUPPORTS, AND VALVE COMPLETE. REMOVE

ASSOCIATED COLD AND HOT WATER PIPE, INSULATION, AND VALVES

COMPLETE. REMOVE ASSOCIATED WASTE PIPE COMPLETE. REMOVE

ASSOCIATED VENT PIPE TO ABOVE CEILING AND CAP PIPE.

5. REMOVE FLOOR DRAIN, STRAINER, SUPPORTS, TRAP, AND ALL

ASSOCIATED WASTE AND VENT PIPING COMPLETE.

6. REMOVE GAS-FIRED DOMESTIC WATER HEATER, SUPPORTS, CONTROLS,

CONCRETE PAD, COLD AND HOT WATER PIPING, MIXING VALVE AND

APPURTENANCES COMPLETE. REMOVE ASSOCIATED LPG PIPING AFTER

EXISTING EXTERIOR GAS VALVE, SUPPORTS AND APPURTENANCES TO

POINT INDICATED AND CAP GAS VALVE FOR REUSE. REMOVE

ASSOCIATED EXHAUST VENT TO 12" BELOW ROOF AND CAP VENT.

7. REMOVE FAUCET, SUPPORTS, COLD AND HOT WATER PIPING,

INSULATION, AND APPURTENANCES COMPLETE.

8. REMOVE VENT PIPING TO 6" BELOW ROOF PENETRATION. PROTECT

EXISTING VENT TERMINAL THRU ROOF FOR REUSE.

9. REMOVE WASTE PIPING, SUPPORTS AND APPURTENANCES TO POINT

INDICATED AND CAP PIPE FOR REUSE.

10. REMOVE CLEANOUT, ASSOCIATED PIPE AND APPURTENANCES

COMPLETE.

11. SAW-CUT EXISTING CONCRETE AS REQUIRED FOR UTILITY WORK. SEE

STRUCTURAL FOR UTILITY TRENCH DETAIL.

12. REMOVE EXISTING CONCRETE SLAB AS REQUIRED FOR UTILITY WORK.

SEE STRUCTURAL FOR LIMITS OF SLAB REMOVAL AND REPLACEMENT

AND DETAILS.

NOTES

G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND

COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

NDOMESTIC WATER

CAMP 5B BATHHOUSE -

NSANITARY WASTE

CAMP 5B BATHHOUSE -

(E)2"CW

2"CW WITH

VALVE IN

VERTICAL

PROVIDE MIN. 12"x12" A.D.

FOR ACCESS TO VALVE

3/4"LPG

3"V P-6 P-6

P-5

P-5 P-5 P-5

3"W 3"W 3"W

DWH-1,2,3 1

P1

4"W

P-7P-7 3"VTR

F.C.O.

P-2P-2

3"V

P-1P-1

P-1 P-3

P-4

P-4

P-4

P-4

P-4

P-4

P-6 P-5P-5P-5P-5 P-6

3/4"CW &

3/4"HW 1

1/2"CW &

1/2"HW

1 1/2"CW &

1/2"HW 1

P-4

P-4

P-4

P-4

P-4

P-4

P-3

P-1

P-2

P-1

P-1

P-2

1/2"CW&HW DN. 1

2"CW

1-1/2"HW

1-1/2"CW&HW

2"CW

2"CW

1-1/2"CW

1-1/2"HW

2"x4" CONCENTRIC VENT

INSTALL IN EXISTING CONSTRUCTION

PER MANUFACTURER'S

WRITTEN RECOMMENDATIONS

1/2"CW&HW DN.1

4 4WH-1 WH-1

F.C.O.

P-7 P-7

C.O.

DWH-1,2,3 1

P1

SD-1 2 SD-1 2

F.C.O.F.C.O.

SD-12SD-12

FL.D.-1FL.D.-1 22

FL.D.-12 FL.D.-1 2

FL.D.-12

FL.D.-12 3

(E)3/4"LPG

(E)PROPANE TANK

5B BATHHOUSE PLUMBING.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5B BATHHOUSE ROACH OCTOBER 10 2023

ALPHA

CORPORATION

21000 ATLANTIC BLVD, S. 400

www.alphacorporation.com

GENERAL NOTES

1. ROUTE DOMESTIC WATER PIPE IN FURRED OUT WALL TO FIXTURE.

2. PROVIDE ASSE 1072 COMPLIANT BARRIER TYPE TRAP SEAL PROTECTION

DEVICE SUITABLE FOR USE WITH FLOOR DRAIN.

3. ROUTE 3/4" PROPANE GAS PIPE AS HIGH AS POSSIBLE THROUGH

JANITOR'S CLOSET.

4. PROVIDE NON-FREEZE, ANTI-SIPHON, AUTOMATIC DRAINING WALL

HYDRANT (WH-1) UNDER LAVATORY COUNTER

NOTES

G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT

UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".

G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND

DRAIN SCHEDULE

FL.D-1

DESIG.

UNIT

GENERAL - FINISHED FLOOR

DRAIN TYPE

MANUFACTURER

JOSAM

BASIS OF DESIGN

MODEL

30000-8A CAST IRON

BODY TYPE STRAINER SIZE(IN.)

8" ROUND

STRAINER TYPE

NOTES

NIKALOY 3"

PROVIDE DRAIN OUTLET TYPE AND SIZE TO MATCH CONNECTING PIPE.1NOTES:

PROVIDE P-TRAP SAME SIZE, MATERIAL AND CONNECTION METHOD AS CONNECTING PIPE.2

LOCATE TOP OF GRATE FLUSH WITH ADJACENT FINISHED FLOOR SURFACE.3

1 2 3

SIZE(IN.)

CONNECTION

FFAS 25SD-1 INFINITY DRAINSHOWER TRENCH DRAIN 16 GA 304 S.S. 12 GA 316L S.S.NA 2" 1 2 3

PLUMBING FIXTURE SCHEDULE

WATER CLOSETP-1

DESIG. FIXTURE

2"

V

CONNECTION SIZE, INCHES

4"

W

1/2"

CW

HW

REMARKS

NOTES: CONTRACTOR TO INSTALL ALL FIXTURES AND EQUIPMENT IN ACCORDANCE

WITH MANUFACTURER'S RECOMMENDATIONS. PROVIDE PIPING CONNECTIONS

PER FIXTURE CONNECTION SCHEDULE.

ELONGATED, FLOOR MOUNTED, WHITE VITREOUS CHINA, HIGH-EFFICIENCY, PRESSURE-ASSISTED TANK TOILET. PROVIDE WITH WHITE, HEAVY DUTY, ELONGATED, OPEN FRONT, TOILET SEAT LESS

COVER. PROVIDE SLOAN MODEL WETS-8009.8010 WATER CLOSET OR APPROVED EQUAL.

TW

ABAAS URINALP-3 1-1/2"2" 3/4" - -

ABAAS COMPLIANT, WALL MOUNTED, VITREOUS CHINA, WASHDOWN URINAL WITH 3/4" TOP SPUD INLET.

PROVIDE WITH 0.125 GPF, EXPOSED, NON-CLOG, MANUAL, PISTON OPERATED FLUSHOMETER VALVE.

PROVIDE AMERICAN STANDARD MODEL 6002.001 URINAL AND ZURN METROFLUSH MODEL

Z6203-ULF-YB-YC FLUSHOMETER VALVE OR APPROVED EQUALS.

SERVICE SINKP-7 1-1/2"3" 1/2" 1/2" -

24"x24"x6"DEEP, FLOOR MOUNTED, MOLDED STONE MOP SERVICE BASIN. PROVIDE WITH EXPOSED, YOKE WALL MOUNTED, 2.2 GPM, CAST BRASS, VANDAL RESISTANT FAUCET WITH HOLD AND MOP HOOKS. PROVIDE FIAT MODEL SB2424 MOP SINK AND AMERICAN STANDARD MODEL 8344.012 FAUCET

OR APPROVED EQUALS.

REFER TO ARCHITECTURAL DRAWINGS FOR ALL ADA RIM MOUNTING HEIGHTS.2

SHOWERP-5 1-1/4"2" 1/2" 1/2" -

PROVIDE SHOWER SYSTEM WITH WALL MOUNTED, VANDAL RESISTANT, POLISHED CHROME PRESSURE

BALANCING VALVE WITH WALL MOUNTED, VANDAL RESISTANT, 1.5 GPM, POLISHED CHROME

SHOWERHEAD. PROVIDE SYMMONS MODEL C-96-1-151-X SHOWER SYSTEM OR APPROVED EQUAL.

ABAAS WATER CLOSETP-2 2"4" 1/2" -

ABAAS COMPLIANT, ELONGATED, FLOOR MOUNTED, WHITE VITREOUS CHINA, HIGH-EFFICIENCY, PRESSURE-ASSISTED TANK TOILET. PROVIDE WITH WHITE, HEAVY DUTY, ELONGATED, OPEN FRONT, TOILET SEAT LESS COVER. PROVIDE SLOAN MODEL WETS-8029.8010 WATER CLOSET OR APPROVED

EQUAL.

ABAAS LAVATORYP-4 1-1/4"1-1/2" 1/2" 1/2" -

ABAAS SHOWERP-6 1-1/4"2" 1/2" 1/2" -

ABAAS COMPLIANT, VANDAL RESISTANT, COMMERCIAL HAND SHOWER SYSTEM WITH WALL MOUNTED, VANDAL RESISTANT, POLISHED CHROME PRESSURE BALANCING VALVE WITH 1.5 GPM, POLISHED

CHROME HAND SHOWERHEAD. PROVIDE WITH CHROME PLATED 30" SLIDE BAR AND 60" LONG

FLEXIBLE METAL HOSE. PROVIDE SYMMONS MODEL C-96-300-B30-V-TRM HAND SHOWER SYSTEM OR

APPROVED EQUAL.

ABAAS COMPLIANT, 19-1/4"x15-3/4" OVAL, UNDERCOUNTER MOUNTED, WHITE VITREOUS CHINA, WITH REAR OVERFLOW LAVATORY. PROVIDE WITH DECK MOUNTED, 8" FIXED CENTERS, VANDAL PROOF, LEAD-FREE, 0.5 GPM FAUCET WITH 4" WRISTBLADE HANDLES, AND COMPRESSION OPERATING

CARTRIDGE. PROVIDE AMERICAN STANDARD OVALYN MODEL9482.000 LAVATORY AND CHICAGO

FAUCETS MODEL 404-VE2805-317ABCP FAUCET OR APPROVED EQUALS.

PROVIDE ASSE 1072 COMPLIANT BARRIER TYPE TRAP SEAL

PROTECTION DEVICE SUITABLE FOR USE WITH DRAIN.

TANKLESS GAS WATER HEATER SCHEDULE

DESIG. REMARKS

NOTES:

BASIS OF DESIGN: RINNAI MODEL CU199i.

PROVIDE WITH MANUFACTURER SIZED SAFETY PRESSURE RELIEF VALVE.

REFER TO DETAIL 1/P1 FOR INSTALLATION.

DWH-1, 2, 3

PROVIDE CONDENSATE NEUTRALIZING CARTRIDGE WITH DRAIN.

PROVIDE INDOOR, CONDENSING STYLE,

TANKLESS WATER HEATER.

PROVIDE EQUIPMENT AND ASSOCIATED

APPURTENANCES IN ACCORDANCE WITH

MANUFACTURER'S RECOMMENDATIONS.

2 3 4 5 6 7

WATER FLOW @

60°F RISE

6.0

GPM (EA.)

FUEL DATA (EA.)

TYPE

LPG

INPUT

MBH

GAS PRESSURE

(IN. W.C.)

8.0 - 13.5

ELECTRICAL DATA (EA.)

NORMAL

WATTS

STANDBY

WATTS

84 1.3

CONNECTION SIZE (IN.)

GAS CW HW CONDENSATE

DRAIN

3/4" 3/4" 3/4" 1/2" 1

ELECTRICAL

CONNECTION

120V/1Ø/60Hz

PROVIDE CONCENTRIC VENT PER

MANUFACTURERS RECOMMENDATIONS.

SCHEDULES.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5B BATHHOUSE ROACH OCTOBER 10 2023

ALPHA

CORPORATION

NO SCALE

DOMESTIC WATER RISER DIAGRAM1

NO SCALE

SANITARY RISER DIAGRAM2

FIRST FLOOR

ROOF

FIRST FLOOR

ROOF

C.O.

4"W

ATTICATTIC

(E)3"VTR

(E)4"W

(E)3"VTR (E)3"VTR

2"V

FIRST FLOOR

ROOF

2"CW

FIRST FLOOR

ROOF

P-5P-5

P-1

P-3

P-1 P-1 P-2 P-2

P-4 P-4P-4 P-4P-4 P-4

3/4"CW &

3/4"HW

3/4"CW &

3/4"HW

P-7

2"CW

2"CW 1-1/2"CW1-1/2"HW

P-5P-6P-6P-5

3/4"CW &

3/4"HW

1/2"CW&HW

1/2"CW&HW

1/2"CW&HW

3/4"CW&HW

2"CW 1-1/2"CW

1/2"CW&HW

1/2"CW&HW

FL.D.

3"W

P-7

P-4P-4

FL.D.

3"W

P-7F.C.O.

P-4P-4 P-4P-4

P-2 P-2 FL.D. FL.D. P-1

P-3

2"V

4"W

2"V

2"W 3"W

4"W 4"W 4"W

1-1/4"V1-1/4"V1-1/4"V

3"V3"V3"V 1-1/2"V

1-1/2"V

2"V

1-1/2"V

WH-1

1/2"CW

WH-1

1/2"CW

DWH-1

P-7

1/2"CW&HW

1-1/2"CW&HW

DWH-2DWH-3

DWH-1 DWH-2 DWH-3

1-1/4"D 1-1/4"D

C.O.

P-6P-5P-5 P-6 P-5

2"W

3"W

2"V

F.C.O. SD-1 SD-1 SD-1 SD-1 SD-1

P-5

SD-1 F.C.O.

3"W

3"W

RISER DIAGRAMS.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5B BATHHOUSE ROACH OCTOBER 10 2023

ALPHA

CORPORATION

(E)

LC

SYMBOLS

GENERAL SYMBOLS

ABBREVIATIONS

CEILING REGISTER, SIZE PER SCHEDULE UNLESS

OTHERWISE NOTED. NUMBER INDICATES

BALANCING AIRFLOW CFM.

RETURN AIR SYMBOL

NUMBER INDICATES CFM

SUPPLY AIR SYMBOL

NUMBER INDICATES CFM

CR

NORTH ARROW

COLUMN BUBBLE

DESIGNATION

REVISION CLOUD WITH REVISION

NUMBER DESIGNATION

BREAKLINE

MATCHLINE DESIGNATIONM A T C H L I N E A-A

DEMOLITION LINETYPE

CENTERLINE

CENTERLINE SYMBOL

EXISTING

POINT OF CONNECTION TO EXISTING

POINT OF TERMINATION OF REMOVAL

NOTE NUMBER

AHU AIR HANDLING UNIT

BHP BRAKE HORSEPOWER

BTU BRITISH THERMAL UNITS

BTUH BRITISH THERMAL UNITS PER HOUR

CFM CUBIC FEET PER MINUTE

C.G. CEILING GRILLE

D.B. DRY BULB

db DECIBEL

DDC DIRECT DIGITAL CONTROL

(E) EXISTING

E.A.T. ENTERING AIR TEMPERATURE

E.D.B. ENTERING DRY BULB

EFF. EFFICIENCY

E.G. EXHAUST GRILLE

ENT. ENTERING

E.S.P. EXTERNAL STATIC PRESSURE

E.W.B. ENTERING WET BULB

E.W.T. ENTERING WATER TEMPERATURE

EXIST. EXISTING

°F DEGREES FAHRENHEIT

FLA FULL LOAD AMPS

FPM FEET PER MINUTE

FT. FEET

F.V. FACE VELOCITY

GAL. GALLON

GPM GALLONS PER MINUTE

H.C. HEATING COIL

HP HORSEPOWER

HW DOMESTIC HOT WATER

HWR HEATING WATER RETURN

HWS HEATING WATER SUPPLY

Hz HERTZ

IN. INCHES

L.A.T. LEAVING AIR TEMPERATURE

LBS. POUNDS

LBS./HR POUNDS PER HOUR

L.D.B. LEAVING DRY BULB

L.W.T. LEAVING WATER TEMPERATURE

MAX. MAXIMUM

MIN. MINIMUM

NC NOISE CRITERIA

PH PHASE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PVC POLYVINYL CHLORIDE

R.G. RETURN GRILLE

RLA RUNNING LOAD AMPS

RPM REVOLUTIONS PER MINUTE

S.P. STATIC PRESSURE

TYP. TYPICAL

UH UNIT HEATER

V VOLTS

W.B. WET BULB

ARROW INDICATES

TRUE NORTH AND/OR

PROJECT NORTH

N

M101

N

8'0 1/8"=1'-0"

UNIQUE PLAN OR

DETAIL NUMBER

ON THIS DRAWING NORTH ARROW

NAME OF PLAN OR DETAIL

ALL DRAWINGS WHERE

DETAIL IS REFERENCED

GRAPHIC SCALE OF

PLAN OR DETAIL

SECTION IDENTIFICATION

INDICATES DIRECTION

OF CUTTING PLANE

NUMBER INDICATES SECTION

SHEET NUMBER WHERE

SECTION IS DRAWN

2-PART REFERENCE DETAIL IDENTIFICATION:

SHEET NUMBER WHERE

DETAIL/SECTION IS DRAWN

NUMBER INDICATES

DETAIL/SECTION

FLOOR PLAN

M101, M1022

FLOOR PLAN AND DETAIL TITLES:

M101

ROOM NUMBER DESIGNATION.1234

DOOR LOUVERL

ROUND DUCT UP

ROUND DUCT DOWN

M

SYMBOLS & ABREVIATIONS

MOTOR

NORMALLY OPEN CONTACTS

NORMALLY CLOSED CONTACTS

RELAY COIL

STARTER HOLDING COIL

THERMAL MOTOR SWITCH

MOTOR STARTER

FAN OR PUMP, BY APPLICATION

R#

AIR OR WATER FLOW PATH

GENERAL

FAN WILL BE CONTROLLED BY AN OCCUPANCY SENSOR AND SWITCH. SENSOR WILL HAVE A 30 MIN

DELAY OFF.

120 VAC

OS-2

NL1

EF-1

FLOW DIAGRAM

WIRING DIAGRAM

OS-1

GENERAL NOTES

G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT

UNLESS SPECIFICALLY MARKED "EXISTING"," EXIST.", OR "(E)".

G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND

COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

ALUMINUM BIRDSCREEN AT

PERIMETER OF FAN DISCHARGE.

SECURE ROOF CAP

TO CURB WITH

STAINLESS STEEL

SHEET METAL

SCREWS

ROOF

RUN POWER SUPPLY

LEADS IN CORNER

INSIDE CURB

DUCT, SEE FLOOR

PLAN FOR SIZE

SPUN ALUMINUM

DISCHARGE APRON

CURB CAP

MANUFACTURERS

CURB

FOAM RUBBER

GASKET

FULL SIZE FAN OPENING MOTOR

OPERATED DAMPER INSTALL

PER MANUFACTURERS

RECOMMENDATIONS & MINIMUM

DISTANCE FROM FAN.

NO SCALE

POWER ROOF VENTILATOR

DETAIL

AIR DEVICE SCHEDULE

SYMBOL DESIG.

AIRFLOW

(CFM)

NECK

SIZE

(INCHES)

OVERALL

SIZE

(INCHES)

MAX. S.P.

DROP

(IN. W.G.)

MAX.

N.C. FACE TYPE NOTES

R-1 230 10x10 14x14 0.10 30 GRILLE EXHAUST

R-2 20 6x6 10x10 0.04 20 GRILLE EXHAUST

NOTES

A

A. ALL AIR DEVICES TO BE PAINTED. COORDINATE EXACT

PAINT COLOR WITH DPW.

OS-1

OS-2

FAN SCHEDULE

UNIT

NO.

TYPE

AIRFLOW

(CFM)

E.S.P.

(IN. W.G.) RPM HP BHP

MAX

SOUND

(SONES)

ELEC.

DATA

(V/PH/HZ)

SERVICE LOCATION NOTES

EF-1 PRV 490 0.50 1573 0.10 0.08 7.60 120/1/60 RESTROOMS ROOF

NOTES

B

A. BASIS OF DESIGN: GREENHECK G-090-VG

B. PRV = POWERED ROOF VENTILATOR, PROVIDE WITH MANUFACTURERS CURB AND

COORDINATE COLOR WITH COR.

C. FAN WILL BE CONTROLLED BY A OCCUPANCY SENSOR AND SWITCH. SENSOR WILL HAVE

A 30 MIN DELAY OFF.

D. INSTALL PER DETAIL 1/M1.

A C

UNIT HEATER SCHEDULE

UNIT

NO.

TYPE

HEATING

CAP.

(WATTS)

AREA

SERVED NOTES

UH-1 WALL 3600 RESTROOMS

UH-2 WALL 1000 STORE RM

UH-3 WALL 1000 MECH

NOTES

A. WALL - ELECTRIC RESISTANCE WALL HEATER

B. 240V/1PH/60HZ

C. 120V/1PH/60HZ

D. PROVIDE WITH STANDALONE ADJUSTABLE DIAL CONTROL

INTERFACE.

E. EQUIPMENT SHALL BE VANDAL-PROOF.

F. RECESS-MOUNTED

G. SURFACE MOUNTED

A

B C

D D

C D

E E

E

G

G

F

OS-X COMBINATION OCCUPANCY

SENSOR AND SWITCH

D-1

D-1 N.C.

203.013 5B M1.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5B BATHHOUSE ROACH OCTOBER 6 2023

ALPHA

CORPORATION

N5B BATHHOUSE - DEMO1

N5B BATHHOUSE2

EXHAUST FAN 2

UNIT HEATER1

EXHAUST FAN2

UNIT HEATER 1

UNIT HEATER 1 UNIT HEATER1

UNIT HEATER1

UNIT HEATER3

EXHAUST FAN 4EXHAUST FAN4

UH-1 UH-1

UH-1

UH-2

UH-3

UH-1

L L 55

10x10

10x10

14x10

6x6

6x6 20 R2

R1

R1

R2

OS-1 OS-2

16x16 UP, TRANSITION TO 10x10 IN VERT

EF-1 ON ROOF

L L7 7

T T

T T

5B BATHHOUSE FLOOR PLAN.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5B BATHHOUSE ROACH OCTOBER 6 2023

ALPHA

CORPORATION

21000 ATLANTIC BLVD, S. 400

www.alphacorporation.com

GENERAL NOTES

1. DISCONNECT AND REMOVE ELECTRIC WALL MOUNTED FORCED FAN

UNIT HEATER, SUPPORTS, ELECTRICAL CONNECTIONS, AND

APPURTENANCES COMPLETE.

2. DISCONNECT AND REMOVE WALL MOUNTED EXHAUST FAN,

SUPPORTS, LOUVER, CONTROLS, AND APPURTENANCES COMPLETE.

PATCH WALL TO MATCH SURROUNDING.

3. DISCONNECT AND REMOVE CEILING MOUNTED ELECTRIC

RESISTANCE UNIT HEATER, SUPPORTS, CONTROLS AND

APPURTENANCES COMPLETE.

4. DISCONNECT AND REMOVE WALL MOUNTED EXHAUST FAN,

SUPPORTS, LOUVER, CONTROLS, AND APPURTENANCES COMPLETE.

PATCH WALL TO MATCH SURROUNDING.

5. PROVIDE 16x16 DOOR LOUVER.

6. PROVIDE DUCTWORK ABOVE CEILING IN ATTIC SPACE.

7. PROVIDE 12x6 DOOR LOUVER.

NOTES

G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT

UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".

G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND

J

OS

EM2

1,3,5

#10

#10

1,3,5

EM2

#10

EM2

1,3,5

SYMBOLS

EM2

1,3,5

#10

EX

EC

W

S

S

SC

SC

SM

A AMPERES.

AF FRAME SIZE IN AMPERES.

AHU AIR HANDLING UNIT.

AT TRIP SIZE IN AMPERES.

AWG. AMERICAN WIRE GAUGE.

BATT BATTERY BACK-UP.

BLDG. BUILDING.

C/B CIRCUIT BREAKER.

EMT ELECTRICAL METALLIC TUBING.

FLA FULL LOAD AMPERES.

GFI GROUND FAULT INTERRUPTER.

GRD. GROUND CONDUCTOR.

KAIC THOUSAND AMPERE INTERRUPTING CAPACITY.

KW KILO-WATTS.

M.L.O. MAIN LUGS ONLY.

N.E.C. NATIONAL ELECTRICAL COSE.

NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION.

NFSS NON-FUSED SAFETY SWITCH.

P NUMBER OF POLES.

PH. NUMBER OF PHASES.

RGS RIGID GALVANIZED STEEL.

U.L. UNDERWRITER'S LABORATORIES.

V VOLTAGE.

WP WEATHERPROOF, OR NEMA 3R ENCLOSURE.

GENERAL SYMBOLS

NORTH ARROW

COLUMN BUBBLE

DESIGNATION

REVISION CLOUD WITH REVISION

NUMBER DESIGNATION

BREAKLINE

MATCHLINE DESIGNATION

DEMOLITION LINETYPE

NOTE NUMBER

ARROW INDICATES

TRUE NORTH AND/OR

PROJECT NORTH

N

E-101

N

8'0 1/8"=1'-0"

UNIQUE PLAN OR

DETAIL NUMBER

ON THIS DRAWING NORTH ARROW

NAME OF PLAN OR DETAIL

ALL DRAWINGS WHERE

DETAIL IS REFERENCED

GRAPHIC SCALE OF

PLAN OR DETAIL

SECTION IDENTIFICATION

INDICATES DIRECTION

OF CUTTING PLANE

NUMBER INDICATES SECTION

SHEET NUMBER WHERE

SECTION IS DRAWN

2-PART REFERENCE DETAIL IDENTIFICATION:

SHEET NUMBER WHERE

DETAIL/SECTION IS DRAWN

NUMBER INDICATES

DETAIL/SECTION

FLOOR PLAN

E-101, E-1022

FLOOR PLAN AND DETAIL TITLES:

E-101

DN

UP

Ø

AA

PHASE.

WYE GROUNDING CONFIGURATION.

DELTA CONFIGURATION.

CONDUIT DOWN.

CONDUIT UP.

EQUIPMENT IDENTIFICATION NUMBER.

FEEDER DESIGNATION.

CEILING MOUNTED OCCUPANCY SENSOR, COMBINATION

ULTRASONIC/ PASSIVE INFRARED (PIR) DEVICE WITH ADJUSTABLE

TIME DELAY 5 TO 30 MINUTES.

JUNCTION BOX, 4" SQUARE x 2-1/8" DEEP GALVANIZED PRESSED

STEEL, RECESS MOUNTED AT 18" ABOVE FINISHED FLOOR, WITH

BLANK COVER PLATE.

SPECIAL DEDICATED OUTLET, NEMA CONFIGURATION AS NOTED

ON FLOOR PLAN, SURFACE MOUNTED IN 4" SQUARE x 2-1/8" DEEP

PRESSED STEEL JUNCTION BOX AT 18" ABOVE FINISHED FLOOR.

SPECIAL DEDICATED OUTLET, NEMA CONFIGURATION AS NOTED

ON FLOOR PLAN, RECESS MOUNTED IN 4" SQUARE x 2-1/8" DEEP

PRESSED STEEL JUNCTION BOX AT 18" ABOVE FINISHED FLOOR.

DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE,

NEMA 5-20R CONFIGURATION, SURFACE MOUNTED IN 4" SQUARE x

2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18" ABOVE

FINISHED FLOOR.

DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE,

NEMA 5-20R CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x

2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18" ABOVE

FINISHED FLOOR.

CIRCUIT BREAKER TYPE PANELBOARD.

HEAVY DUTY ENCLOSED SAFETY SWITCH, SEE MOTOR AND

EQUIPMENT SCHEDULE FOR SIZES AND CHARACTERISTICS.

M A T C H L I N E A-A

LIGHT SWITCH, TOGGLE SWITCH, SINGLE POLE, 20 AMPERE,

120/277V, A.C. ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED

FLOOR UNLESS OTHER MOUNTING HEIGHT IS NOTED.

COMBINATION 2-BUTTON "ON/OFF" LIGHT SWITCH AND

OCCUPANCY SENSOR, IN CAST DEVICE BOX SURFACE MOUNTED

ON WALL AT 48" ABOVE THE FINISHED FLOOR, SINGLE POLE, 20

AMPERE, 120/277V, A.C. ONLY. PROVIDE WITH WHITE PLASTIC

DECORA STYLE COVER PLATE.

SAME AS COMBINATION 2-BUTTON "ON/OFF" LIGHT SWITCH ABOVE,

EXCEPT SURFACE MOUNTED.

MANUAL MOTOR STARTER WITH THERMAL OVERLOAD RELAY,

SURFACE MOUNTED IN DEVICE BOX ON UNIT UNLESS OTHERWISE

NOTED.

CEILING MOUNTED LIGHTING FIXTURE, TYPE AS NOTED.

RECESSED DOWNLIGHT FIXTURE, TYPE AS NOTED.

2'-0" LONG STRIP LIGHT FIXTURE, TYPE AS NOTED.

1'x4' LIGHTING FIXTURE, TYPE AS NOTED.

LIGHTING FIXTURE TYPE.

SAME AS LIGHT SWITCH ABOVE, EXCEPT SURFACE MOUNTED.

SURFACE METAL RACEWAY, WIREMOLD SERIES 700 UNLESS

SPECIFICALLY NOTED OTHERWISE.

BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN CONCEALED IN

CONCRETE, ALL OTHER CHARACTERISTICS SAME AS SHOWN

ABOVE.

BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN CONCEALED IN

WALLS AND CEILING, ALL OTHER CHARACTERISTICS SAME AS

SHOWN ABOVE.

NUMBER OF SLASH MARKS INDICATE THE NUMBER OF

CONDUCTORS IN RACEWAY. NO SLASH MARKS INDICATE 2

CIRCUIT CONDUCTORS PLUS A GROUND CONDUCTOR.

HOME RUN TO PANEL. NUMBER OF ARROWS INDICATE THE

NUMBER OF CIRCUITS.

BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN EXPOSED. SIZE

IN ACCORDANCE WITH N.E.C. RACEWAY SHALL BE MINIMUM 3/4"

CONDUIT, AND WIRE SHALL BE MINIMUM SIZE #12 AWG COPPER,

UNLESS OTHER SIZES ARE SPECIFICALLY NOTED.

EMPTY 1" CONDUIT WITH NYLON PULL STRING.

EXISTING CONDUIT AND CONDUCTORS TO REMAIN.

WIRE SIZE IN AWG. SIZE NOT SHOWN INDICATES #12 AWG.

CIRCUIT BREAKERS IN PANEL SERVING THESE CIRCUITS.

PANEL NAME TO WHICH CIRCUITS RUN.

GREEN GROUND CONDUCTOR RUN IN RACEWAY.

EMT CONDUIT.

ROOM NUMBER DESIGNATION.1234

ABBREVIATIONS

VERTICAL VANITY FIXTURE, TYPE AS NOTED.

PANEL CAMP 5B SCHEDULE

MAIN BUS SIZE (AMPS): 150 INTERRUPT. RATING (KAIC): 10 NEUTRAL BUS SIZE: 100% MOUNTING TYPE: SURFACE MAIN BUS MATERIAL: COPPER VOLTAGE: 120 / 240 SECTION NO.: 1 OF 1 LOCATION: MECHANICAL ROOM MAIN CIRCUIT BREAKER (AMPS): 100 PHASE: 1 WIRE: 3 ENCLOSURE TYPE: NEMA 1 BOLT ON BRANCH CIRCUIT BREAKERS

CKT

NO. DESCRIPTION LOAD

TYPE

LOAD

(KVA)

BREAKER BREAKER LOAD

(KVA)

LOAD

TYPE DESCRIPTION CKT NO.

AMPS POLES POLES AMPS

UH-1 WEST

C 1.80

20 2 A

2 20

1.80 C

UH-1 EAST

3 C 1.80 B 1.80 C 4

UH-1 WEST

C 1.80

20 2 A

2 20

1.80 C

UH-1 EAST

7 C 1.80 B 1.70 C 8

9 EF-1 WEST M 0.07 20 1 A 1 20 0.36 R MECH-1 GFI RECEPT 10

11 UH-2 C 1.00 20 1 B 1 20 1.00 C UH-3 12

13 MECH-2 GFI RECEPT R 0.36 20 1 A 1 20 0.51 N LIGHTS 14

15 DWH-2 N 0.08 20 1 B 1 20 0.20 M HAND DRYER EAST 16

17 GFI RECEPT WEST BATH R 0.54 20 1 A 1 20 0.08 N DWH-3 30

19 HAND DRYER WEST M 0.20 20 1 B 1 20 0.13 N OUTSIDE LIGHTS 20

21 DWH-1 N 0.08 20 1 A 1 20 0.18 R OUTSIDE GFI 22

23 SPARE N 0.00 20 1 B 1 20 0.54 R GFI RECEPT EAST BATH 24

25 SPARE N 0.00 20 1 A 1 20 0.36 N POWER ENTRY DOORS 26

27 SPARE N 0.00 20 1 B 1 20 0.00 N SPARE 28

29 SPARE N 0.00 20 1 A 1 20 0.00 N SPARE 30

31 SPARE N 0.00 20 1 B 1 20 0.00 N SPARE 32

33 SPARE N 0.00 20 1 A 1 20 0.00 N SPARE 34

35 SPACE N 0.00 -- 1 B 1 -- 0.00 N SPACE 36

37 SPACE N 0.00 -- 1 A 1 -- 0.00 N SPACE 38

39 SPACE N 0.00 -- 1 B 1 -- 0.00 N SPACE 40

CONNECTED LOAD PER PHASE (kVA) = 9.7 10.3 TOTAL CONNECTED LOAD = 20.0 KVA 83.3 AMPS

(AMPS) = 81.2 85.5 TOTAL DEMAND LOAD = 24.1 KVA 100.6 AMPS

LOAD TYPES: C = CONTINUOUS, R = RECEPTACLE, M = MOTOR, N = NON-CONTINUOUS

2'-0" EMERGENCY LONG STRIP LIGHT FIXTURE, TYPE AS

NOTED.

EMERGENCY RECESSED DOWNLIGHT FIXTURE, TYPE AS

NOTED

J JUNCTION BOX, 4" SQUARE x 2-1/8" DEEP GALVANIZED PRESSED

STEEL, MOUNTED ABOVE CEILING.

CEILING MOUNTED CANOPY FIXTURE, TYPE AS NOTED

SYMBOLS

ST TIME CLOCK LIGHT SWITCH. IN CAST DEVICE BOX AT 48" ABOVE

FINISHED FLOOR, 20 AMPERE 120/277V A.C. ONLY. PROVIDE WITH

WHITE PLASTIC DECORA STYLE COVER PLATE.

203.013 5B E1.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5B BATHHOUSE DISAVINO OCTOBER 6 2023

ALPHA

CORPORATION

21000 ATLANTIC BLVD, S. 400

www.alphacorporation.com

MOTOR AND EQUIPMENT SCHEDULE

EQUIPMENT NAME HP KW RATED

VOLT. PHASE FLA

MOTOR CONTROLLER FEEDER LOCAL SWITCH

REMARKS

TYPE LOCAL CONTROL

WIRE

CONDUIT

TYPE

SIZE POLES

NO. SIZE GRD.

EF-1 -- -- 115 1Ø 0.6 OCCUPANCY SENSOR AND SWITCH 2 #12 #12 3/4" MRT 20A 1

UH-1 -- 3.6 240 1Ø 15.0 LOCAL SWITCH 2 #12 #12 3/4" INT 20A 2

UH-2 -- 1.0 120 1Ø 8.3 LOCAL SWITCH 2 #12 #12 3/4" MRT 20A 1

UH-3 -- 1.0 120 1Ø 8.3 LOCAL SWITCH 2 #12 #12 3/4" MRT 20A 1

DWH-1,2,3 -- 0.08 120 1Ø 0.7 LOCAL SWITCH 2 #12 #12 3/4" NFSS 30A 1

NOTES:

NFSS - NON FUSED SAFETY SWITCH SEE MECHANICAL DRAWINGS FOR AUXILIARY

FSS - FUSED SAFETY SWITCH CONTACT REQUIREMENTS.

MRT - MOTOR RATED TOGGLE SWITCH

INT - INTEGRAL WITH MOTOR CONTROLLER

GENERAL NOTES

1. PROVIDE INTEGRAL SURGE PROTECTION FOR PANELBOARD

PER SPECIFICATIONS.

NOTES

G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING

EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE

START OF CONSTRUCTION.

G2. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS

CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST",

OR "(E)".

G3. DEMOLITION DEFINITION: DISCONNECTION AND REMOVAL OF

ASSOCIATED CONDUCTORS SHALL CONSIST OF THE REMOVAL

OF THE CONDUCTORS BACK TO THE NEXT EXISTING DEVICE TO

REMAIN. NEW CONDUIT AND CONDUCTORS SHALL BE PROVIDED

TO RECONNECT ANY EXISTING TO REMAIN DEVICES

INTERRUPTED BY THE DEMOLITION UNDER THIS PROJECT.

1 2

N5B BATHHOUSE - LIGHTING DEMO1

N5B BATHHOUSE - LIGHTING2

S S

SS

2 2

2 2

S

OSOS

OSOS

S C

SC

S S

1B 1B 1B

1B1B 1B

5B

5B

PANEL CAMP 5B PANEL CAMP 5B

1A1A

2A

2A

S C

S C

1 1

1A

1 1

1A

S

TS T S

T S T S T

S

T

1 1

5B BATHHOUSE LIGHTING.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5B BATHHOUSE DISAVINO OCTOBER 6 2023

ALPHA

CORPORATION

21000 ATLANTIC BLVD, S. 400

www.alphacorporation.com

GENERAL NOTES

G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING

EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE

START OF CONSTRUCTION.

G2. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS

CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST",

OR "(E)".

G3. DEMOLITION DEFINITION: DISCONNECTION AND REMOVAL OF

ASSOCIATED CONDUCTORS SHALL CONSIST OF THE REMOVAL

OF THE CONDUCTORS BACK TO THE NEXT EXISTING DEVICE TO

REMAIN. NEW CONDUIT AND CONDUCTORS SHALL BE PROVIDED

TO RECONNECT ANY EXISTING TO REMAIN DEVICES

INTERRUPTED BY THE DEMOLITION UNDER THIS PROJECT.

1. DISCONNECT AND REMOVE LIGHT SWITCH. REMOVE ALL

ASSOCIATED CONDUIT AND CONDUCTORS BACK TO SOURCE.

2. DISCONNECT AND REMOVE LIGHT FIXTURE. REMOVE ALL

ASSOCIATED CONDUIT AND CONDUCTORS BACK TO SOURCE.

3. PROVIDE ASTRONOMICAL CLOCK AND CONNECT TO EXTERIOR

LIGHTING. PROVIDE PROGRAMMING FOR 365 DAYS TO TURN ON

LIGHTING AT DUSK AND TURN OFF LIGHTING AT DAWN.

NOTES

N5B BATHHOUSE - POWER DEMO1

N5B BATHHOUSE - POWER2

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI

GFI GFI

GFIGFI

GFIGFI

J

GFI,WP

UH-1 UH-1

UH-1

UH-2

5 5

HAND DRYERS

HAND DRYERS

GFI

GFI

UH-15

5B

5B

5B 2,4

5B

5B 17,24,26

5B

GFI

GFI

5B 11 5B

15,21,30

PANEL CAMP 5B 7 PANEL CAMP 5B 6

5B

5B

UH-3 5

5B

EF-15

5B

GFI

GFI

DWH-1,2,3 5

5B 10,13

JJ

S M

S M

S M

5B BATHHOUSE POWER.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5B BATHHOUSE DISAVINO OCTOBER 6 2023

ALPHA

CORPORATION

21000 ATLANTIC BLVD, S. 400

www.alphacorporation.com

GENERAL NOTES

1. DISCONNECT AND REMOVE RECEPTACLE. REMOVE ALL

ASSOCIATED CONDUIT AND CONDUCTORS BACK TO SOURCE.

2. DISCONNECT MECHANICAL EQUIPMENT. REMOVE ALL

ASSOCIATED CONDUIT AND CONDUCTORS BACK TO SOURCE.

3. DISCONNECT AND REMOVE HAND DRYER. REMOVE ALL

ASSOCIATED CONDUIT AND CONDUCTORS BACK TO SOURCE.

4. PROVIDE RECEPTACLE 6" ABOVE COUNTERTOP.

5. SEE MOTOR AND EQUIPMENT SCHEDULE FOR MOTOR AND

FEEDER CHARACTERISTICS.

6. DISCONNECT AND REMOVE PANEL BOARD. TAG, PROTECT AND

RETAIN MAIN FEEDER FOR REUSE.

7. PROVIDE PANEL BOARD, CONNECT TO MAIN FEEDER RETAINED

DURING DEMOLITION. SEE ASSOCIATED PANEL SCHEDULE FOR

CIRCUIT QUANTITIES.

8. CORE DRILL FOR CONDUIT PENETRATION, SEAL PENETRATION

WATERTIGHT.

NOTES

G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING

EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE

START OF CONSTRUCTION.

G2. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS

CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST",

OR "(E)".

G3. DEMOLITION DEFINITION: DISCONNECTION AND REMOVAL OF

ASSOCIATED CONDUCTORS SHALL CONSIST OF THE REMOVAL

OF THE CONDUCTORS BACK TO THE NEXT EXISTING DEVICE TO

REMAIN. NEW CONDUIT AND CONDUCTORS SHALL BE PROVIDED

TO RECONNECT ANY EXISTING TO REMAIN DEVICES

INTERRUPTED BY THE DEMOLITION UNDER THIS PROJECT.

DETAILS.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5B BATHHOUSE DISAVINO OCTOBER 6 2023

CORPORATION

21000 ATLANTIC BLVD, S. 400

www.alphacorporation.com

ALUMINUM DIE CAST WITH HIGH-GLOSS BAKED WHITE ENAMEL FINISH.HOUSING:

GENERAL: RECESSED L.E.D. DOWNLIGHT, 6" APERTURE.

LENS: PRESSED-IN DIFFUSE LENS.

DRIVER:

LEDS:

ELECTRONIC DIMMABLE DRIVER; HIGH EFFICIENCY, U.L. LISTED, RATED MULTI-VOLT

OPERATION FROM 120-277V, MAXIMUM SYSTEM INPUT WATTAGE OF 15.

1500 LUMEN OUTPUT, 3000K COLOR TEMPERATURE, MINIMUM CRI OF 80,

MINIMUM 70% LUMEN MAINTENANCE AT 60,000 HOURS

LIGHTING FIXTURE TYPE 1

5-3/4"

7" 7-1/2"

LIGHTING FIXTURE TYPE 3

VERTICAL VANITY BATHROOM L.E.D. LIGHTING FIXTURE. 2' LONG RATED FOR

DRIVER:

LEDS:

GENERAL:

HOUSING:

LENS: EXTRUDED ACRYLIC DIFFUSER.

ELECTRONIC DIMMABLE DRIVER; HIGH EFFICIENCY, U.L. LISTED, RATED FOR MULTI-VOLT

OPERATION FROM 120-277V, MAXIMUM SYSTEM INPUT WATTAGE OF 27.

1550 LUMEN OUTPUT, 3000K COLOR TEMPERATURE, MINIMUM 90 CRI,

MINIMUM 70% LUMEN MAINTENANCE AT 50,000 HOURS

ACRYLIC DIFFUSER WITH BRUSHED NICKEL HOUSING.

1A ALL REQUIREMENTS ARE THE SAME AS TYPE 1 WITH 10W CONSTANT POWER

BATTERY PACK AND UL TRANSFER DEVICE.

GENERAL:

HOUSING:

LENS:

2'-0" L.E.D STRIP LIGHT, SURFACE MOUNTED.

STEEL HOUSING WITH ALUMINUM HEAT SINK.

PRISMATIC, SEMI-DIFFUSE LENS.

DRIVER:

LEDS:

ELECTRONIC DIMMABLE DRIVER; HIGH EFFICIENCY, U.L. LISTED, RATED FOR MULTI-VOLT

OPERATION FROM 120-277V, MAXIMUM SYSTEM INPUT WATTAGE OF 25.

3,500 LUMEN OUTPUT, 3000K COLOR TEMPERATURE, MINIMUM 80 CRI,

MINIMUM 70% LUMEN MAINTENANCE AT 90,000 HOURS.

LIGHTING FIXTURE TYPE 2

2A ALL REQUIREMENTS ARE THE SAME AS TYPE 2 WITH 10W CONSTANT POWER

BATTERY PACK AND UL TRANSFER DEVICE.

LIGHTING FIXTURE TYPE 5

SURFACE MOUNTED CANOPY L.E.D. LIGHTING FIXTURE. LISTED FOR WET LOCATIONS.

DRIVER:

LEDS:

GENERAL:

HOUSING:

LENS: TRANSLUCENT POLYCARBONATE LENS.

ELECTRONIC DIMMABLE DRIVER; HIGH EFFICIENCY, U.L. LISTED, RATED FOR MULTI-VOLT

OPERATION FROM 120-277V, MAXIMUM SYSTEM INPUT WATTAGE OF 35.

4500 LUMEN OUTPUT, 4000K COLOR TEMPERATURE, MINIMUM 80 CRI,

MINIMUM 70% LUMEN MAINTENANCE AT 50,000 HOURS

CAST-ALUMINUM HOUSING WITH A POLYESTER POWDER COAT FINISH.

LENS:

HOUSING:

GENERAL:

SINGLE-PIECE DIE-CAST ALUMINUM HOUSING, DIE-CAST DOOR FRAME FULLY GASKETED.

WALL MOUNTED L.E.D FIXTURE FOR OUTDOOR LOCATIONS, MOUNTED AT 8' AFF.

INDIVIDUALLY FORMED ACRYLIC LENS.

LEDS: 3,000 LUMEN OUTPUT, 4000K COLOR TEMPERATURE, MINIMUM 80 CRI,

DRIVER: ELECTRONIC DRIVER; HIGH EFFICIENCY, U.L. LISTED, RATED FOR

MULTI-VOLT OPERATION FROM 120-277V, MAXIMUM SYSTEM INPUT WATTAGE OF 32.

LIGHTING FIXTURE TYPE

MINIMUM 70% LUMEN MAINTENANCE AT 100,00 HOURS.

DARK BRONZE COLOR.

1B ALL REQUIREMENTS ARE THE SAME AS TYPE 1 BUT RATED FOR WET LOCATION.

DAMP LOCATIONS.

ASSUMED

ASBESTOS-CONTAINING

FIRE DOOR

MEN'S

BATHROOM

WOMEN'S

BATHROOM

SHOWER

AREA

SHOWER

AREA

LAUNDRY

MECHANICAL

COVERED

PORCH

- A HAZARDOUS MATERIALS ASSESSMENT WAS PERFORMED

WITHIN THE PROJECT AREA BY ARC ENVIRONMENTAL IN

OCTOBER 2022; CONTRACTOR SHALL REFER TO THE

ASSOCIATED REPORT 'PRE-ALTERATION HAZARDOUS

MATERIALS SURVEY, PRINCE WILLIAM FOREST PARK” DATED

NOVEMBER 23, 2022, FOR DETAILS RELATED TO THE

ASSESSMENT AND SUBSEQUENT ANALYTICAL DATA.

- IT IS NOT THE INTENTION OF THIS PROJECT TO REMOVE ALL

IDENTIFIED REGULATED AND/OR HAZARDOUS MATERIALS FROM

THE PROJECT AREA. REMEDIATION EFFORTS ARE INTENDED TO

ADDRESS HAZARDS DURING CONSTRUCTION EFFORTS AND

SHALL BE LIMITED TO THE REMOVAL OF IDENTIFIED MATERIALS

WHICH MAY BE IMPACTED BY THE PLANNED IMPROVEMENTS

PROJECT. CONTRACTOR SHALL REVIEW DRAWINGS AND

APPLICABLE SPECIFICATIONS FOR APPLICABLE SCOPE DETAILS.

- AN ASSUMED ASBESTOS-CONTAINING MATERIAL (ACM) HAS

BEEN IDENTIFIED WITHIN THE PROJECT AREA. THE IDENTIFIED

ASSUMED ACM IS NOT INTENDED TO BE REMOVED OR

DISTURBED DURING THE COURSE OF THIS PROJECT.

- LEAD-BASED PAINT (LBP) WAS NOT IDENTIFIED WITHIN THE

PROJECT AREA. LEAD-SAFE WORK PRACTICES SHALL BE

EMPLOYED PER 29 CFR 1926.62 FOR AREA WHERE

LEAD-IN-CONSTRUCTION WORK IS SCHEDULED. NO LEAD-BASED

PAINT ABATEMENT IS ANTICIPATED AS PART OF THIS PROJECT.

- GATHER, COLLECT, AND PROPERLY DISPOSE OF IDENTIFIED

MERCURY-CONTAINING LIGHT TUBES, DIELECTRIC

FLUID-CONTAINING LIGHT BALLASTS, AND

MERCURY-CONTAINING THERMOSTATS WITHIN THE PROJECT

AREA AS IDENTIFIED IN THE SCOPE OF WORK. REFER TO

SPECIFICATION SECTION 02 84 16 FOR ADDITIONAL

REQUIREMENTS.

GENERAL HAZARDOUS MATERIAL

NOTES APPLICABLE TO THE

PROJECT AREA

3/8" = 1'-0"

0' 4' 8'

HAZMAT - 5B - 100%.DWGP:\IH\PROJECTS 2022\COMMERCIAL\1017-22 ALPHA - PRWI CAMPS 5A AND 5B BATHHOUSES AND VISITOR CENTER\100% CD AKRICK OCTOBER 2 2023

ALPHA

CORPORATION

21000 ATLANTIC BLVD, S. 400

DULLES, VA 20166 (703)450-0800

www.alphacorporation.com

ARC ENVIRONMENTAL, LLC

1311 HAUBERT STREET

BALTIMORE, MARYLAND 21230

Ph: 410-659-9971 www.arcenvironmental.com

ArcEnvironmental

CAMP 5B BATHHOUSE PLAN - HAZARDOUS MATERIALS

SCALE: 38" = 1'-0"H1