PRWI_233645_Bathhouse_5A_DWGS_FINAL_25_0903.pdf
PDF 7 MB Posted
- Attached to
- NCR PRWI: C5 BATHHOUSE & VISITOR ACCESS Federal contract opportunity
- Solicitation number
- 140P2126R0003
About this file
This document is a comprehensive set of architectural and engineering drawings for interior improvements to the Camp 5A Central Bathhouse located within Prince William Forest Park (PRWI) in Triangle, Virginia. The project is administered by the United States Department of the Interior National Park Service and prepared by Alpha Corporation.
The bathhouse improvement project encompasses complete renovation of interior spaces including women's and men's bathrooms, shower areas, laundry facilities, and mechanical/utility rooms. The work includes demolition of existing conditions, installation of new ABAAS-compliant fixtures (water closets, urinals, lavatories, showers), replacement of plumbing and mechanical systems, new ceramic tile finishes throughout wet areas, updated electrical systems with LED lighting, HVAC upgrades including exhaust fans and unit heaters, and structural modifications. Key systems addressed include domestic water distribution with instantaneous liquid propane water heaters set at 110°F, sanitary waste drainage with proper slope provisions, and gas supply for heating. The project specifies ADA accessibility requirements, ABAAS compliance for all plumbing fixtures, and comprehensive hazardous materials abatement including assumed asbestos-containing fire doors and lead-based paint remediation in accordance with federal standards. Material specifications include Daltile ceramic tiles, Benjamin Moore interior paints, solid surface countertops by Corian, HDPE bathroom partitions, and Borrick plumbing fixtures. Construction staging is limited to a defined 20'x30' area, and the contractor must maintain positive site drainage and existing building envelope integrity throughout the project duration.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| PRWI_242861_Camp_5_Access_DWGS_FINAL_24_1101_pg_35_39_0002.pdf | ||
| Sol_140P2126R0003_Amd_0002.pdf | ||
| questions_(1)_0001.docx | DOCX document | |
| B09_PRWI_Sign_in_sheet_3-5-2026_Camp_5_bathrooms_and_visitor_access_0001.pdf | ||
| Sol_140P2126R0003_Amd_0001.pdf | ||
| PRWI_233645_Bathhouse_5A_Spec_FINAL_25_0903.pdf | ||
| Sol_140P2126R0003.pdf | ||
| PRWI_343092_Bathhouse_5B_DWGS_FINAL_25_0903.pdf | ||
| B03_Wage_Determination_.pdf | ||
| PRWI_242861_Camp_5_Access_Drawings_FINAL_APPROVED_25_1218.pdf | ||
| PRWI_242861_Camp_5_Access_Spec_FINAL_25_1218.pdf | ||
| PRWI_343092_Bathhouse_5B_Spec_FINAL_25_0903.pdf | ||
| E15_Deliverables_LmtOnSubconRpt_REQD.xlsx | XLSX spreadsheet |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MAKE IMPROVEMENTS TO INTERIOR OF CAMP 5
ALPHA
CORPORATION
CS1[COVER_5A].DWGN:\JOBS\DULLES\572-160-C PRWI CAMP 5 A&B BATHHOUSE - VC STAFF RESTROOM\5000 CIVIL\DWGS\CAMP 5A UNIT HENDERSONJ OCTOBER 4 2023
21000 ATLANTIC BLVD, S. 400
www.alphacorporation.com
CENTRAL BATHHOUSE IN CAMP 5A UNIT
PRINCE WILLIAM FOREST PARK (PRWI)
PRINCE WILLIAM FOREST PARK
jbello Text Box
Δ1 G1 CLARIFY REQ 9/3/25 JPB
G
G
G
X
X
ALPHA
CORPORATION
G1[SITE ACCESS 5A].DWGN:\JOBS\DULLES\572-160-C PRWI CAMP 5 A&B BATHHOUSE - VC STAFF RESTROOM\5000 CIVIL\DWGS\CAMP 5A UNIT HENDERSONJ OCTOBER 4 2023
21000 ATLANTIC BLVD, S. 400
www.alphacorporation.com
LOCATION OF
CAMP 5A
LOCATION OF
CAMP 5B
LOCATION OF CENTRAL
BATHHOUSE IN CAMP 5A UNIT
CONTRACTOR STAGING
& PARKING AREA
(SEE NOTE 4)
SITE ACCESS ROUTE
MAWAVI ROAD
(GRAVEL SURFACE)
CONTRACTOR STAGING
AREA (20'X30')
(SEE NOTE 4)
jbello Cross-Out jbello Line jbello Text Box
SET OF CONTRACT DOCUMENTS - SEE PRWI 242861.
CORPORATION
A1-5A-GEN.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5A ANNE.KOPF OCTOBER 8 2023
21000 ATLANTIC BLVD, S. 400
DULLES, VA 20166 (703)450-0800
www.alphacorporation.com
A2-5A-DEMO.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5A ANNE.KOPF OCTOBER 9 2023
21000 ATLANTIC BLVD, S. 400
A3-5A-DEMORCP.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5A ANNE.KOPF OCTOBER 9 2023
21000 ATLANTIC BLVD, S. 400
A4-5A-FLRPLN.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5A ANNE.KOPF NOVEMBER 6 2023
21000 ATLANTIC BLVD, S. 400
A5-5A-RCP.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5A ANNE.KOPF OCTOBER 11 2023
21000 ATLANTIC BLVD, S. 400
A6-5A-EXTELEV.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5A ANNE.KOPF NOVEMBER 6 2023
21000 ATLANTIC BLVD, S. 400
A7-5A-INTELEV.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5A ANNE.KOPF OCTOBER 9 2023
21000 ATLANTIC BLVD, S. 400
A8-5A-SCHED.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5A ANNE.KOPF OCTOBER 5 2023
21000 ATLANTIC BLVD, S. 400
A9-5A-DTLS.DWG\\QUINNEVANS.COM\QE\PROJECTS\2022\42240720_NPS_PRWIRESTRMS\05_DWGS\02_AUTOCAD\SHEETS\5A ANNE.KOPF OCTOBER 11 2023
21000 ATLANTIC BLVD, S. 400
ABBREVIATIONS
ABV. ABOVE
A.D. AREA DRAIN/ACCESS DOOR
A.F.F. ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
A.P. ACCESS PANEL
BHP BRAKE HORSEPOWER
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
C.O. CLEANOUT
CONC. CONCRETE
CW DOMESTIC COLD WATER
D DRAIN / DRYER
D.B. DRY BULB
DIA. DIAMETER
DN. DOWN
DW DISHWASHER
DWH DOMESTIC WATER HEATER
(E) EXISTING
EA. EACH
E.A. EXHAUST AIR
ENT. ENTERING
ETPV ELECTRONIC TRAP PRIMING VALVE
E.W.T. ENTERING WATER TEMPERATURE
EXIST. EXISTING
°F DEGREES FAHRENHEIT
F.C.O. FLOOR CLEANOUT
FLA. FULL LOAD AMPS
FL.D. FLOOR DRAIN
FLR. FLOOR
FT. FEET
GAL. GALLON
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HR. HOUR
HW DOMESTIC HOT WATER
Hz HERTZ
IN. INCH(ES)
IW INDIRECT WASTE
JAN. JANITORS CLOSET
L LENGTH
LAV LAVATORY
LBS. POUNDS
LPG LIQUID PROPANE GAS
LVG. LEAVING
L.W.T. LEAVING WATER TEMPERATURE
M.A.V. MANUAL AIR VENT
MAX. MAXIMUM
M.E.R. MECHANICAL EQUIPMENT ROOM
MIN. MINIMUM
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
O.C. ON CENTER
P.D. PRESSURE DROP
PRV PRESSURE RELIEF VALVE
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
RLA RUNNING LOAD AMPS
RPM REVOLUTIONS PER MINUTE
SAN SANITARY
SS SERVICE SINK
TPV TRAP PRIMING VALVE
TYP. TYPICAL
UR URINAL
V VENT/VOLTS
V.S. VENT STACK
VTR VENT THRU ROOF
W WASTE / WIDTH / WASHING MACHINE
W/ WITH
W.B. WET BULB
W.C. WATERCOLUMN
WC WATER CLOSET
W.G. WATER GAUGE
DOMESTIC COLD WATER
CONDENSATE DRAIN PIPING
CW
D
GAS PIPING
DOMESTIC HOT WATER
G
HW
V W
W WASTE/SANITARY PIPE BELOW GRADE
WASTE/SANITARY PIPE
VENT PIPE
PIPE TURN UP
PIPE TURN DOWN
STRAINER
GATE VALVE
PRESSURE REDUCING VALVE
UNION
RELIEF VALVE
GAS COCK
CONCENTRIC REDUCER
DIRECTION OF FLOW
PRESSURE GAUGE
THERMOMETER AND WELL
C.O.
F.C.O.
FL.D. FLOOR DRAIN
FLOOR CLEANOUT
PIPE CLEANOUT
PIPE CAP
(E)
SYMBOLS
NORTH ARROW
BREAKLINE
DEMOLITION LINETYPE
CENTERLINE
EXISTING
POINT OF CONNECTION TO EXISTING
POINT OF TERMINATION OF REMOVAL
NOTE NUMBER
ARROW INDICATES
TRUE NORTH AND/OR
PROJECT NORTH
N
M101
N
8'0 1/8"=1'-0"
UNIQUE PLAN OR
DETAIL NUMBER
ON THIS DRAWING NORTH ARROW
NAME OF PLAN OR DETAIL
ALL DRAWINGS WHERE
DETAIL IS REFERENCED
GRAPHIC SCALE OF
PLAN OR DETAIL
2-PART REFERENCE DETAIL IDENTIFICATION:
SHEET NUMBER WHERE
DETAIL/SECTION IS DRAWN
NUMBER INDICATES
DETAIL/SECTION
FLOOR PLAN
M101, M1022
FLOOR PLAN AND DETAIL TITLES:
INSTANTANEOUS LIQUID PROPANE
DETAIL
DOMESTIC WATER HEATERS
P3 NOT TO SCALE
NOT TO SCALE
LAUNDRY OUTLET BOX (P-9)
DETAIL
P32
2"W P-TRAP
WATER SHUT-OFF
LEVER
WATER HAMMER
ARRESTOR (TYP.)
WASHING MACHINE
SUPPLY AND DRAIN
LAUNDRY BOX.
2"DRAIN OPENING
1/2"CW & HW CONNECTION
FINISHED FLOOR
NON-FREEZE WALL HYDRANTW.H.-1
1-1/2"CW
3/4"LPG
1-1/2"HW-110°F
C.O.
T&P RELIEF
VALVE (TYP.)
PIPE TO
FLOOR SINK
1-1/2" COPPER COLD
WATER HEADER
1-1/2" COPPER HOT
WATER HEADER
3/4"LPG
3/4"LPG(TYP.)3/4"D(TYP.)
GAS COCK (TYP.)
DWH-1
SET @
110°F
DWH-2
SET @
110°F
DWH-3
SET @
110°F
M.E.R. FINISHED FLOOR FL.D.
3"W
PROVIDE FL.D. UNDER
HOT WATER HEATER.
2"
PROVIDE CONDENSATE
NEUTRALIZING CARTRIDGE
2"x4" CONCENTRIC SIDEWALL INTAKE & EXHAUST
VENT SUPPORT AND TERMINATE IN ACCORDANCE
WITH MANUFACTURER'S RECOMMENDATIONS. SEAL
PENETRATIONS WEATHERTIGHT. TOTAL EQUIVALENT
LENGTH OF DIRECT VENT AND NUMBER OF ELBOWS
NOT TO EXCEED MANUFACTURER'S RECOMMENDATIONS
CEILING
1-1/4"D
1-1/4"D
GRADE
SHUTOFF VALVE IN VERTICAL
ALPHA
CORPORATION
203.013 5A P1.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5A BATHHOUSE ROACH OCTOBER 10 2023
21000 ATLANTIC BLVD, S. 400
NDOMESTIC WATER DEMOLITION
CAMP 5A BATHHOUSE -
2"CW
3/4"LPG
DWH
(E)6"EXH.
VENT UP
WC 1 WC 1 WC 1WC 1
WC 1WC 1FL.D. 5
UR 2LAV 3
FL.D. 5
LAV 3 LAV 3
LAV 3LAV 3
LAV 3 LAV 3
(E)3"VTR(E)3"VTR
WC 1WC 1
WC 1
WC 1
WC 1WC 1
UR 2LAV 3
LAV 3
LAV 3
LAV 3
LAV 3
LAV 3
LAV 3
FL.D. 5 5
FL.D. 5
FL.D. 5
FL.D. 5FL.D. 5
(E)3"VTR
C.O.8
4"W
(E)3"VTR
(E)3"VTR
4 4
(E)3"VTR
C.O.
1-1/2"W
(E)MANHOLE
6 3/4"LPG
(E)LPG REGULATOR
IN VERTICAL
(E)HANDHOLE
9 1/2"D 10
AHU 10
NSANITARY WASTE DEMOLITION
CAMP 5A BATHHOUSE -
CONC. PAD 6
TMV 6
FL.D.
ALPHA
CORPORATION
5A BATHHOUSE DEMOLITION.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5A BATHHOUSE ROACH OCTOBER 10 2023
21000 ATLANTIC BLVD, S. 400
www.alphacorporation.com
GENERAL NOTES
1. CAREFULLY REMOVE FLOOR MOUNTED TANK TYPE WATER CLOSET AND
RETURN TO THE PARK. REMOVE ASSOCIATED SUPPORTS AND
APPURTENANCES COMPLETE. REMOVE ASSOCIATED COLD WATER PIPE,
INSULATION, SUPPORTS, AND VALVES COMPLETE. REMOVE ASSOCIATED
WASTE PIPE COMPLETE. REMOVE ASSOCIATED VENT PIPE TO ABOVE
CEILING AND CAP PIPE.
2. REMOVE WALL MOUNTED URINAL, SUPPORTS, AND APPURTENANCES
COMPLETE. REMOVE ASSOCIATED COLD WATER PIPE, INSULATION,
SUPPORTS, AND VALVES COMPLETE. REMOVE ASSOCIATED WASTE PIPE
COMPLETE. REMOVE ASSOCIATED VENT PIPE TO ABOVE CEILING AND
CAP PIPE.
3. REMOVE WALL MOUNTED LAVATORY, SUPPORTS, FAUCET AND
APPURTENANCES COMPLETE. REMOVE ASSOCIATED COLD AND HOT
WATER PIPE, INSULATION, SUPPORTS AND VALVES COMPLETE. REMOVE
ASSOCIATED WASTE PIPE COMPLETE. REMOVE ASSOCIATED VENT PIPE
TO ABOVE CEILING AND CAP PIPE.
4. REMOVE SHOWERHEAD, SUPPORTS, AND VALVE COMPLETE. REMOVE
ASSOCIATED COLD AND HOT WATER PIPE, INSULATION, AND VALVES
COMPLETE. REMOVE ASSOCIATED WASTE PIPE COMPLETE. REMOVE
ASSOCIATED VENT PIPE TO ABOVE CEILING AND CAP PIPE.
5. REMOVE FLOOR DRAIN, STRAINER, SUPPORTS, TRAP, AND ALL
ASSOCIATED WASTE AND VENT PIPING COMPLETE.
6. REMOVE GAS-FIRED DOMESTIC WATER HEATER, SUPPORTS, CONTROLS,
CONCRETE PAD, COLD AND HOT WATER PIPING, MIXING VALVE, AND
APPURTENANCES COMPLETE. REMOVE ASSOCIATED LPG PIPING AFTER
EXISTING EXTERIOR GAS VALVE, SUPPORTS AND APPURTENANCES TO
POINT INDICATED AND CAP GAS VALVE FOR REUSE. REMOVE
ASSOCIATED EXHAUST VENT, ROOF VENT CAP, AND APPURTENANCES
COMPLETE, PROTECT ROOF OPENING FOR REUSE.
7. REMOVE FAUCET, SUPPORTS, COLD AND HOT WATER PIPING,
INSULATION, AND APPURTENANCES COMPLETE.
8. REMOVE CLEANOUT, ASSOCIATED PIPE AND APPURTENANCES
COMPLETE.
9. REMOVE WALL MOUNTED WASHING MACHINE WALL BOX. SUPPORTS,
1-1/2" WASTE PIPE, AND APPURTENANCES COMPLETE.
10. REMOVE WALL MOUNTED AIR CONDITIONER DRAIN PIPE, SUPPORTS AND
APPURTENANCES COMPLETE.
11. REMOVE VENT PIPING TO 6" BELOW ROOF PENETRATION. CAP EXISTING
EXTERIOR VENT TERMINATION WATERTIGHT.
12. REMOVE VENT PIPING TO 6" BELOW ROOF PENETRATION. PROTECT
EXISTING VENT THROUGH ROOF FOR REUSE.
13. SAW-CUT EXISTING CONCRETE AS REQUIRED FOR UTILITY WORK. SEE
STRUCTURAL FOR UTILITY TRENCH DETAIL.
14. REMOVE EXISTING CONCRETE SLAB AS REQUIRED FOR UTILITY WORK.
SEE STRUCTURAL FOR LIMITS OF SLAB REMOVAL AND REPLACEMENT
AND DETAILS.
NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
NDOMESTIC WATER
CAMP 5A BATHHOUSE -
1NSANITARY WASTE
CAMP 5A BATHHOUSE -
4"W
F.C.O.
3"V 3"V
(E)MANHOLE
4"W
4"W
3"V
F.C.O.
3"V
P-6 P-6 P-5
P-5 P-5 P-5
P-3
P-1
P-2
FL.D.-1FL.D.-1
P-7 P-7P-8 FL.D.-1
FL.D.-1FL.D.-1
SD-1
3"W 3"W
(E)3"VTR
(E)HANDHOLE
(E)2"CW 2"CW WITH
VALVE IN
VERTICAL
PROVIDE MIN. 12"x12" A.D.
FOR ACCESS TO VALVE.
COORDINATE A.D. LOCATION
WITH VALVE
P-6 P-5P-5P-5P-5 P-6
3/4"CW &
3/4"HW 1
1/2"CW &
1/2"HW
1 1/2"CW &
1/2"HW 1
P-4
P-4
P-4
P-4
P-4
P-4
P-1
P-1
P-2
P-3
P-1
P-2
P-1
P-1
P-2
P-8
1/2"CW&HW DN.1
3/4"LPG3
1/2"CW&HW DN. 1
DWH-1,2,3 1
P1
2"CW
1-1/2"HW
3/4"CW&HW
1/2"CW&HW
2"CW
2"CW
1-1/2"CW
1-1/2"HW
2"W
(E)LPG REGULATOR
IN VERTICAL
DWH-1,2,3 1
P1
2"x4" CONCENTRIC VENT
INSTALL IN EXISTING CONSTRUCTION
PER MANUFACTURER'S
WRITTEN RECOMMENDATIONS
P1
FL.D.-1
F.C.O.
4 4WH-1 WH-1
P-4
P-4
P-4
P-4
P-4
P-4
P-7 P-7
3"V
SD-12 2
F.C.O.
SD-12SD-12
GENERAL NOTES
1. ROUTE DOMESTIC WATER PIPE IN FURRED OUT WALL TO FIXTURE.
2. PROVIDE ASSE 1072 COMPLIANT BARRIER TYPE TRAP SEAL PROTECTION
DEVICE SUITABLE FOR USE WITH FLOOR DRAIN.
3. ROUTE 3/4" PROPANE GAS PIPE AS HIGH AS POSSIBLE THROUGH
JANITOR'S CLOSET.
4. PROVIDE NON-FREEZE, ANTI-SIPHON, AUTOMATIC DRAINING WALL
HYDRANT (WH-1) UNDER LAVATORY COUNTER.
NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
ALPHA
CORPORATION
5A BATHHOUSE PLUMBING.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5A BATHHOUSE DISAVINO OCTOBER 11 2023
PLUMBING FIXTURE SCHEDULE
WATER CLOSETP-1
DESIG. FIXTURE
2"
V
CONNECTION SIZE, INCHES
4"
W
1/2"
CW
HW
REMARKS
NOTES: CONTRACTOR TO INSTALL ALL FIXTURES AND EQUIPMENT IN ACCORDANCE
WITH MANUFACTURER'S RECOMMENDATIONS. PROVIDE PIPING CONNECTIONS
PER FIXTURE CONNECTION SCHEDULE.
ELONGATED, FLOOR MOUNTED, WHITE VITREOUS CHINA, HIGH-EFFICIENCY, PRESSURE-ASSISTED TANK TOILET. PROVIDE WITH WHITE, HEAVY DUTY, ELONGATED, OPEN FRONT, TOILET SEAT LESS
COVER. PROVIDE SLOAN MODEL WETS-8009.8010 WATER CLOSET OR APPROVED EQUAL.
TW
ABAAS URINALP-3 1-1/2"2" 3/4" - -
ABAAS COMPLIANT, WALL MOUNTED, VITREOUS CHINA, WASHDOWN URINAL WITH 3/4" TOP SPUD INLET.
PROVIDE WITH 0.125 GPF, EXPOSED, NON-CLOG, MANUAL, PISTON OPERATED FLUSHOMETER VALVE.
PROVIDE AMERICAN STANDARD MODEL 6002.001 URINAL AND ZURN METROFLUSH MODEL
Z6203-ULF-YB-YC OR APPROVED EQUALS.
SERVICE SINKP-7 1-1/2"3" 1/2" 1/2" -
24"x24"x6"DEEP, FLOOR MOUNTED, MOLDED STONE MOP SERVICE BASIN. PROVIDE WITH EXPOSED, YOKE WALL MOUNTED, 2.2 GPM, CAST BRASS, VANDAL RESISTANT FAUCET WITH HOLD AND MOP HOOKS. PROVIDE FIAT MODEL SB2424 MOP SINK AND AMERICAN STANDARD MODEL 8344.012 FAUCET
OR APPROVED EQUALS.
REFER TO ARCHITECTURAL DRAWINGS FOR ALL ADA RIM MOUNTING HEIGHTS.2
SHOWERP-5 1-1/4"2" 1/2" 1/2" -
PROVIDE SHOWER SYSTEM WITH WALL MOUNTED, VANDAL RESISTANT, POLISHED CHROME PRESSURE
BALANCING VALVE WITH WALL MOUNTED, VANDAL RESISTANT, 1.5 GPM, POLISHED CHROME
SHOWERHEAD. PROVIDE SYMMONS MODEL C-96-1-151-X SHOWER SYSTEM OR APPROVED EQUAL.
LAUNDRY OUTLET BOXP-8 1-1/2"2" 1/2" 1/2" - GALVANIZED STEEL WASHING MACHINE OUTLET BOX WITH SINGLE LEVER VALVE AND WATER HAMMER
ARRESTORS. PROVIDE GUY GRAY MODEL B200HA OR APPROVED EQUAL.
TANKLESS GAS WATER HEATER SCHEDULE
DESIG. REMARKS
NOTES:
BASIS OF DESIGN: RINNAI MODEL CU199i.
PROVIDE WITH MANUFACTURER SIZED SAFETY PRESSURE RELIEF VALVE.
REFER TO DETAIL 1/P1 FOR INSTALLATION.
DWH-1, 2, 3
PROVIDE CONDENSATE NEUTRALIZING CARTRIDGE WITH DRAIN.
PROVIDE INDOOR, CONDENSING STYLE,
TANKLESS WATER HEATER.
PROVIDE EQUIPMENT AND ASSOCIATED
APPURTENANCES IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS.
2 3 4 5 6 7
DRAIN SCHEDULE
FL.D-1
DESIG.
UNIT
GENERAL - FINISHED FLOOR
DRAIN TYPE
MANUFACTURER
JOSAM
BASIS OF DESIGN
MODEL
30000-8A CAST IRON
BODY TYPE STRAINER SIZE(IN.)
8" ROUND
STRAINER TYPE
NOTES
NIKALOY 3"
PROVIDE DRAIN OUTLET TYPE AND SIZE TO MATCH CONNECTING PIPE.1NOTES:
PROVIDE P-TRAP SAME SIZE, MATERIAL AND CONNECTION METHOD AS CONNECTING PIPE.2
LOCATE TOP OF GRATE FLUSH WITH ADJACENT FINISHED FLOOR SURFACE.3
1 2 3
WATER FLOW @
60°F RISE
6.0
GPM (EA.)
FUEL DATA (EA.)
TYPE
LPG
INPUT
MBH
GAS PRESSURE
(IN. W.C.)
8.0 - 13.5
ELECTRICAL DATA (EA.)
NORMAL
WATTS
STANDBY
WATTS
84 1.3
CONNECTION SIZE (IN.)
GAS CW HW CONDENSATE
DRAIN
3/4" 3/4" 3/4" 1/2" 1
SIZE(IN.)
CONNECTION
ELECTRICAL
CONNECTION
120V/1Ø/60Hz
FFAS 25SD-1 INFINITY DRAINSHOWER TRENCH DRAIN 16 GA 304 S.S. 12 GA 316L S.S.NA
ABAAS WATER CLOSETP-2 2"4" 1/2" -
ABAAS COMPLIANT, ELONGATED, FLOOR MOUNTED, WHITE VITREOUS CHINA, HIGH-EFFICIENCY, PRESSURE-ASSISTED TANK TOILET. PROVIDE WITH WHITE, HEAVY DUTY, ELONGATED, OPEN FRONT, TOILET SEAT LESS COVER. PROVIDE SLOAN MODEL WETS-8029.8010 WATER CLOSET OR APPROVED
EQUAL.
ABAAS LAVATORYP-4 1-1/4"1-1/2" 1/2" 1/2" -
ABAAS SHOWERP-6 1-1/4"2" 1/2" 1/2" -
PROVIDE CONCENTRIC VENT PER
MANUFACTURERS RECOMMENDATIONS.
2" 1 2 3
ABAAS COMPLIANT, VANDAL RESISTANT, COMMERCIAL HAND SHOWER SYSTEM WITH WALL MOUNTED, VANDAL RESISTANT, POLISHED CHROME PRESSURE BALANCING VALVE WITH 1.5 GPM, POLISHED
CHROME HAND SHOWERHEAD. PROVIDE WITH CHROME PLATED 30" SLIDE BAR AND 60" LONG
FLEXIBLE METAL HOSE. PROVIDE SYMMONS MODEL C-96-300-B30-V-TRM HAND SHOWER SYSTEM OR
APPROVED EQUAL.
ABAAS COMPLIANT, 19-1/4"x15-3/4" OVAL, UNDERCOUNTER MOUNTED, WHITE VITREOUS CHINA, WITH REAR OVERFLOW LAVATORY. PROVIDE WITH DECK MOUNTED, 8" FIXED CENTERS, VANDAL PROOF, LEAD-FREE, 0.5 GPM FAUCET WITH 4" WRISTBLADE HANDLES, AND COMPRESSION OPERATING
CARTRIDGE. PROVIDE AMERICAN STANDARD OVALYN MODEL9482.000 LAVATORY AND CHICAGO
FAUCETS MODEL 404-VE2805-317ABCP FAUCET OR APPROVED EQUALS.
PROVIDE ASSE 1072 COMPLIANT BARRIER TYPE TRAP SEAL
PROTECTION DEVICE SUITABLE FOR USE WITH DRAIN.
ALPHA
CORPORATION
SCHEDULES.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5A BATHHOUSE ROACH OCTOBER 10 2023
NO SCALE
DOMESTIC WATER RISER DIAGRAM1
NO SCALE
SANITARY RISER DIAGRAM2
FIRST FLOOR
ROOF
2"CW
FIRST FLOOR
ROOF
P-5P-5
P-1
P-3
P-1 P-1 P-2 P-2
P-4 P-4P-4 P-4P-4 P-4
3/4"CW &
3/4"HW
3/4"CW &
3/4"HW
DWH-1
P-7
P-8
P-7
2"CW
2"CW 1-1/2"CW1-1/2"HW
P-5P-6P-6P-5
3/4"CW &
3/4"HW
1/2"CW&HW
1/2"CW&HW
1/2"CW&HW
3/4"CW&HW
2"CW 1-1/2"CW
3/4"CW&HW
1/2"CW&HW
1/2"CW&HW
1-1/2"CW&HW
1ST FLOOR
ROOF
FIRST FLOOR
ROOF
F.C.O.
4"W
ATTICATTIC
P-6P-5P-5 P-6 P-5
P-3
P-1 P-1 P-1 P-2 P-2
P-4P-4 P-4P-4 P-4P-4
1-1/4"V
2"W
1-1/4"V 1-1/4"V
P-7FL.D.F.C.O.
(E)3"VTR
2"W
P-8
FL.D.P-7
(E)3"VTR (E)3"VTR (E)3"VTR
4"W
2"W
3"W
3"W
3"W 4"W 4"W 4"W
(E)4"W
3"V
3"W
1-1/2"V
3"W
1-1/2"V1-1/2"V
1-1/2"V
2"V 2"V 2"V
1-1/2"V3"V3"V3"V
WH-1
1/2"CW
WH-1
1/2"CW
(E)3"VTR
3"W
4"W
3"V
DWH-2DWH-3
1-1/2"HW
DWH-1DWH-2DWH-3
1-1/4"D 1-1/4"D
F.C.O. SD-1 SD-1 SD-1 SD-1 SD-1
P-5
SD-1 F.C.O. FL.D.-1 FL.D.-1
ALPHA
CORPORATION
RISER DIAGRAMS.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5A BATHHOUSE ROACH OCTOBER 10 2023
(E)
LC
SYMBOLS
GENERAL SYMBOLS
ABBREVIATIONS
RL
RS
PIPE TURN UP
PIPE TURN DOWN
PIPE CAP
CEILING REGISTER, SIZE PER SCHEDULE UNLESS
OTHERWISE NOTED. NUMBER INDICATES
BALANCING AIRFLOW CFM.
RETURN AIR SYMBOL
NUMBER INDICATES CFM
SUPPLY AIR SYMBOL
NUMBER INDICATES CFM
CR
NORTH ARROW
COLUMN BUBBLE
DESIGNATION
REVISION CLOUD WITH REVISION
NUMBER DESIGNATION
BREAKLINE
MATCHLINE DESIGNATIONM A T C H L I N E A-A
DEMOLITION LINETYPE
CENTERLINE
CENTERLINE SYMBOL
EXISTING
POINT OF CONNECTION TO EXISTING
POINT OF TERMINATION OF REMOVAL
NOTE NUMBER
AHU AIR HANDLING UNIT
BHP BRAKE HORSEPOWER
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CFM CUBIC FEET PER MINUTE
C.G. CEILING GRILLE
D.B. DRY BULB
db DECIBEL
DDC DIRECT DIGITAL CONTROL
(E) EXISTING
E.A.T. ENTERING AIR TEMPERATURE
E.D.B. ENTERING DRY BULB
EFF. EFFICIENCY
E.G. EXHAUST GRILLE
ENT. ENTERING
E.S.P. EXTERNAL STATIC PRESSURE
E.W.B. ENTERING WET BULB
E.W.T. ENTERING WATER TEMPERATURE
EXIST. EXISTING
°F DEGREES FAHRENHEIT
FLA FULL LOAD AMPS
FPM FEET PER MINUTE
FT. FEET
F.V. FACE VELOCITY
GAL. GALLON
GPM GALLONS PER MINUTE
H.C. HEATING COIL
HP HORSEPOWER
HW DOMESTIC HOT WATER
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
Hz HERTZ
IN. INCHES
L.A.T. LEAVING AIR TEMPERATURE
LBS. POUNDS
LBS./HR POUNDS PER HOUR
L.D.B. LEAVING DRY BULB
L.W.T. LEAVING WATER TEMPERATURE
MAX. MAXIMUM
MIN. MINIMUM
NC NOISE CRITERIA
PH PHASE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PVC POLYVINYL CHLORIDE
R.G. RETURN GRILLE
RL REFRIGERANT LIQUID
RLA RUNNING LOAD AMPS
RPM REVOLUTIONS PER MINUTE
S.P. STATIC PRESSURE
TYP. TYPICAL
UH UNIT HEATER
V VOLTS
W.B. WET BULB
ARROW INDICATES
TRUE NORTH AND/OR
PROJECT NORTH
N
M101
N
8'0 1/8"=1'-0"
UNIQUE PLAN OR
DETAIL NUMBER
ON THIS DRAWING NORTH ARROW
NAME OF PLAN OR DETAIL
ALL DRAWINGS WHERE
DETAIL IS REFERENCED
GRAPHIC SCALE OF
PLAN OR DETAIL
SECTION IDENTIFICATION
INDICATES DIRECTION
OF CUTTING PLANE
NUMBER INDICATES SECTION
SHEET NUMBER WHERE
SECTION IS DRAWN
2-PART REFERENCE DETAIL IDENTIFICATION:
SHEET NUMBER WHERE
DETAIL/SECTION IS DRAWN
NUMBER INDICATES
DETAIL/SECTION
FLOOR PLAN
M101, M1022
FLOOR PLAN AND DETAIL TITLES:
M101
REFRIGERANT LIQUID
REFRIGERANT SUCTION
ROOM NUMBER DESIGNATION.1234
FAN SCHEDULE
UNIT
NO.
TYPE
AIRFLOW
(CFM)
E.S.P.
(IN. W.G.) RPM HP BHP
MAX
SOUND
(SONES)
ELEC.
DATA
(V/PH/HZ)
SERVICE LOCATION NOTES
EF-1 PRV 490 0.50 1573 0.10 0.08 7.60 120/1/60 RESTROOMS ROOF
NOTES
B
A. BASIS OF DESIGN: GREENHECK G-090-VG
B. PRV = POWERED ROOF VENTILATOR, PROVIDE WITH MANUFACTURERS CURB AND
COORDINATE COLOR WITH COR.
C. FAN WILL BE CONTROLLED BY A OCCUPANCY SENSOR AND SWITCH. SENSOR WILL HAVE
A 30 MIN DELAY OFF.
D. INSTALL PER DETAIL 1/M1.
A C
UNIT HEATER SCHEDULE
UNIT
NO.
TYPE
HEATING
CAP.
(WATTS)
AREA
SERVED NOTES
UH-1 WALL 3600 RESTROOMS
UH-2 WALL 1000 STORE RM
UH-3 WALL 1000 MECH
NOTES
A. WALL - ELECTRIC RESISTANCE WALL HEATER
B. 240V/1PH/60HZ
C. 120V/1PH/60HZ
D. PROVIDE WITH STANDALONE ADJUSTABLE DIAL CONTROL
INTERFACE.
E. EQUIPMENT SHALL BE VANDAL-PROOF.
F. RECESS-MOUNTED
G. SURFACE MOUNTED
A
B C
D D
C D
E E
E
DOOR LOUVERL
ROUND DUCT UP
ROUND DUCT DOWN
M
SYMBOLS & ABREVIATIONS
MOTOR
NORMALLY OPEN CONTACTS
NORMALLY CLOSED CONTACTS
RELAY COIL
STARTER HOLDING COIL
THERMAL MOTOR SWITCH
MOTOR STARTER
FAN OR PUMP, BY APPLICATION
R#
AIR OR WATER FLOW PATH
GENERAL
FAN WILL BE CONTROLLED BY AN OCCUPANCY SENSOR AND SWITCH. SENSOR WILL HAVE A 30 MIN
DELAY OFF.
120 VAC
OS-2
NL1
EF-1
FLOW DIAGRAM
WIRING DIAGRAM
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
UNLESS SPECIFICALLY MARKED "EXISTING"," EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
OS-1
AIR DEVICE SCHEDULE
SYMBOL DESIG.
AIRFLOW
(CFM)
NECK
SIZE
(INCHES)
OVERALL
SIZE
(INCHES)
MAX. S.P.
DROP
(IN. W.G.)
MAX.
N.C. FACE TYPE NOTES
R-1 230 10x10 14x14 0.10 30 GRILLE EXHAUST
R-2 20 6x6 10x10 0.04 20 GRILLE EXHAUST
NOTES
A
A. ALL AIR DEVICES TO BE PAINTED. COORDINATE EXACT
PAINT COLOR WITH DPW.
ALUMINUM BIRDSCREEN AT
PERIMETER OF FAN DISCHARGE.
SECURE ROOF CAP
TO CURB WITH
STAINLESS STEEL
SHEET METAL
SCREWS
ROOF
RUN POWER SUPPLY
LEADS IN CORNER
INSIDE CURB
DUCT, SEE FLOOR
PLAN FOR SIZE
SPUN ALUMINUM
DISCHARGE APRON
CURB CAP
MANUFACTURERS
CURB
FOAM RUBBER
GASKET
FULL SIZE FAN OPENING MOTOR
OPERATED DAMPER INSTALL
PER MANUFACTURERS
RECOMMENDATIONS & MINIMUM
DISTANCE FROM FAN.
NO SCALE
POWER ROOF VENTILATOR
DETAIL
OS-1
OS-2
G
G
F
OS-X COMBINATION OCCUPANCY
SENSOR AND SWITCH
D-1
D-1 N.C.
ALPHA
CORPORATION
SYMBOLS & ABBREVIATIONS.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5A BATHHOUSE ROACH OCTOBER 6 2023
NCAMP 5A BATHHOUSE - DEMOLITION1NCAMP 5A BATHHOUSE2
8"H CONC. PAD
REFRIGERANT
PIPING 1
CONDENSING UNIT 1
EXHAUST FAN3 EXHAUST FAN 3
EXHAUST FAN3 EXHAUST FAN 3
AHUAHU 11
UNIT HEATER 2 UNIT HEATER2
UNIT HEATER 2 UNIT HEATER2
UNIT HEATER 2
UNIT HEATER4
EXHAUST VENT
TERMINAL
UH-1 UH-1
EXHAUST VENT
TERMINAL
UH-2 UH-3
UH-1 UH-1
LL 1111
OS-1 OS-2
10x10
14x10
6x6
6x6
10x10
16x16 UP, TRANSITION TO 10x10 IN VERT
R1
R2
R2
R1
4Ø
EF-1 ON ROOF
L L12 12
T T
T T
ALPHA
CORPORATION
5A BATHOUSE FLOOR PLAN.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5A BATHHOUSE ROACH OCTOBER 6 2023
21000 ATLANTIC BLVD, S. 400
www.alphacorporation.com
GENERAL NOTES
1. DEENERGIZE, DISCONNECT, AND RECOVER REFRIGERANT. REMOVE
SPLIT SYSTEM HEAT PUMP CONDENSING UNIT, INDOOR WALL
MOUNTED AIR HANDLING UNIT, SUPPORTS, CONTROLS, ASSOCIATED
REFRIGERANT PIPING, DRAIN PIPING, HANGERS, SUPPORTS AND
APPURTENANCES COMPLETE. EXISTING CONCRETE PAD TO REMAIN.
CONCRETE PAD REMOVAL TO TAKE PLACE UNDER A SEPARATE
CONTRACT.
2. DISCONNECT AND REMOVE ELECTRIC WALL MOUNTED FORCED FAN
UNIT HEATER, SUPPORTS, ELECTRICAL CONNECTIONS, AND
APPURTENANCES COMPLETE.
3. DISCONNECT AND REMOVE CEILING MOUNTED EXHAUST FAN,
SUPPORTS CONTROLS, DUCTWORK, AND APPURTENANCES
COMPLETE.
4. DISCONNECT AND REMOVE ELECTRIC CEILING MOUNTED FORCED
FAN UNIT HEATER, SUPPORTS, CONTROLS, AND APPURTENANCES
COMPLETE.
5. CAREFULLY DISCONNECT, REMOVE, STORE AND PROTECT DRYER
FOR REUSE. REMOVE 4"Ø FLEXIBLE EXHAUST DUCT.
6. CAREFULLY DISCONNECT, REMOVE, STORE, AND PROTECT WASHING
MACHINE FOR REUSE.
7. REMOVE EXHAUST VENT TERMINAL, SUPPORTS, AND 4"Ø RIGID DUCT
COMPLETE. PATCH WALL TO MATCH SURROUNDING.
8. REINSTALL DRYER STORED FOR REUSE.
9. REINSTALL WASHING MACHINE STORED FOR REUSE.
10. PROVIDE DUCTWORK ABOVE CEILING IN ATTIC SPACE.
11. PROVIDE 16x16 DOOR LOUVER.
12. PROVIDE 12x6 DOOR LOUVER.
NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
UNLESS SPECIFICALLY MARKED "EXISTING"," EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
J
OS
EM2
1,3,5
#10
#10
1,3,5
EM2
#10
EM2
1,3,5
SYMBOLS
EM2
1,3,5
#10
EX
EC
W
S
SYMBOLS
S
SC
SC
SM
A AMPERES.
AF FRAME SIZE IN AMPERES.
AHU AIR HANDLING UNIT.
AT TRIP SIZE IN AMPERES.
AWG. AMERICAN WIRE GAUGE.
BATT BATTERY BACK-UP.
BLDG. BUILDING.
C/B CIRCUIT BREAKER.
EMT ELECTRICAL METALLIC TUBING.
FLA FULL LOAD AMPERES.
GFI GROUND FAULT INTERRUPTER.
GRD. GROUND CONDUCTOR.
KAIC THOUSAND AMPERE INTERRUPTING CAPACITY.
KW KILO-WATTS.
M.L.O. MAIN LUGS ONLY.
N.E.C. NATIONAL ELECTRICAL COSE.
NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION.
NFSS NON-FUSED SAFETY SWITCH.
P NUMBER OF POLES.
PH. NUMBER OF PHASES.
RGS RIGID GALVANIZED STEEL.
U.L. UNDERWRITER'S LABORATORIES.
V VOLTAGE.
WP WEATHERPROOF, OR NEMA 3R ENCLOSURE.
GENERAL SYMBOLS
NORTH ARROW
COLUMN BUBBLE
DESIGNATION
REVISION CLOUD WITH REVISION
NUMBER DESIGNATION
BREAKLINE
MATCHLINE DESIGNATION
DEMOLITION LINETYPE
NOTE NUMBER
ARROW INDICATES
TRUE NORTH AND/OR
PROJECT NORTH
N
E-101
N
8'0 1/8"=1'-0"
UNIQUE PLAN OR
DETAIL NUMBER
ON THIS DRAWING NORTH ARROW
NAME OF PLAN OR DETAIL
ALL DRAWINGS WHERE
DETAIL IS REFERENCED
GRAPHIC SCALE OF
PLAN OR DETAIL
SECTION IDENTIFICATION
INDICATES DIRECTION
OF CUTTING PLANE
NUMBER INDICATES SECTION
SHEET NUMBER WHERE
SECTION IS DRAWN
2-PART REFERENCE DETAIL IDENTIFICATION:
SHEET NUMBER WHERE
DETAIL/SECTION IS DRAWN
NUMBER INDICATES
DETAIL/SECTION
FLOOR PLAN
E-101, E-1022
FLOOR PLAN AND DETAIL TITLES:
E-101
DN
UP
Ø
AA
PHASE.
WYE GROUNDING CONFIGURATION.
DELTA CONFIGURATION.
CONDUIT DOWN.
CONDUIT UP.
EQUIPMENT IDENTIFICATION NUMBER.
FEEDER DESIGNATION.CEILING MOUNTED OCCUPANCY SENSOR, COMBINATION
ULTRASONIC/ PASSIVE INFRARED (PIR) DEVICE WITH ADJUSTABLE
TIME DELAY 5 TO 30 MINUTES.
JUNCTION BOX, 4" SQUARE x 2-1/8" DEEP GALVANIZED PRESSED
STEEL, RECESS MOUNTED AT 18" ABOVE FINISHED FLOOR, WITH
BLANK COVER PLATE.
SPECIAL DEDICATED OUTLET, NEMA CONFIGURATION AS NOTED
ON FLOOR PLAN, SURFACE MOUNTED IN 4" SQUARE x 2-1/8" DEEP
PRESSED STEEL JUNCTION BOX AT 18" ABOVE FINISHED FLOOR.
SPECIAL DEDICATED OUTLET, NEMA CONFIGURATION AS NOTED
ON FLOOR PLAN, RECESS MOUNTED IN 4" SQUARE x 2-1/8" DEEP
PRESSED STEEL JUNCTION BOX AT 18" ABOVE FINISHED FLOOR.
DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE,
NEMA 5-20R CONFIGURATION, SURFACE MOUNTED IN 4" SQUARE x
2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18" ABOVE
FINISHED FLOOR.
DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE,
NEMA 5-20R CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x
2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18" ABOVE
FINISHED FLOOR.
CIRCUIT BREAKER TYPE PANELBOARD.
M A T C H L I N E A-A
LIGHT SWITCH, TOGGLE SWITCH, SINGLE POLE, 20 AMPERE,
120/277V, A.C. ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED
FLOOR UNLESS OTHER MOUNTING HEIGHT IS NOTED.
COMBINATION 2-BUTTON "ON/OFF" LIGHT SWITCH AND
OCCUPANCY SENSOR, IN CAST DEVICE BOX SURFACE MOUNTED
ON WALL AT 48" ABOVE THE FINISHED FLOOR, SINGLE POLE, 20
AMPERE, 120/277V, A.C. ONLY. PROVIDE WITH WHITE PLASTIC
DECORA STYLE COVER PLATE.
SAME AS COMBINATION 2-BUTTON "ON/OFF" LIGHT SWITCH ABOVE,
EXCEPT SURFACE MOUNTED.
MANUAL MOTOR STARTER WITH THERMAL OVERLOAD RELAY,
SURFACE MOUNTED IN DEVICE BOX ON UNIT UNLESS OTHERWISE
NOTED.
RECESSED DOWNLIGHT FIXTURE, TYPE AS NOTED.
2'-0" LONG STRIP LIGHT FIXTURE, TYPE AS NOTED.
1'x4' LIGHTING FIXTURE, TYPE AS NOTED.
LIGHTING FIXTURE TYPE.
SAME AS LIGHT SWITCH ABOVE, EXCEPT SURFACE MOUNTED.
SURFACE METAL RACEWAY, WIREMOLD SERIES 700 UNLESS
SPECIFICALLY NOTED OTHERWISE.
BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN CONCEALED IN
CONCRETE, ALL OTHER CHARACTERISTICS SAME AS SHOWN
ABOVE.
BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN CONCEALED IN
WALLS AND CEILING, ALL OTHER CHARACTERISTICS SAME AS
SHOWN ABOVE.
NUMBER OF SLASH MARKS INDICATE THE NUMBER OF
CONDUCTORS IN RACEWAY. NO SLASH MARKS INDICATE 2
CIRCUIT CONDUCTORS PLUS A GROUND CONDUCTOR.
HOME RUN TO PANEL. NUMBER OF ARROWS INDICATE THE
NUMBER OF CIRCUITS.
BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN EXPOSED. SIZE
IN ACCORDANCE WITH N.E.C. RACEWAY SHALL BE MINIMUM 3/4"
CONDUIT, AND WIRE SHALL BE MINIMUM SIZE #12 AWG COPPER,
UNLESS OTHER SIZES ARE SPECIFICALLY NOTED.
EMPTY 1" CONDUIT WITH NYLON PULL STRING.
EXISTING CONDUIT AND CONDUCTORS TO REMAIN.
WIRE SIZE IN AWG. SIZE NOT SHOWN INDICATES #12 AWG.
CIRCUIT BREAKERS IN PANEL SERVING THESE CIRCUITS.
PANEL NAME TO WHICH CIRCUITS RUN.
GREEN GROUND CONDUCTOR RUN IN RACEWAY.
EMT CONDUIT.
ROOM NUMBER DESIGNATION.1234
ABBREVIATIONS
VERTICAL VANITY FIXTURE, TYPE AS NOTED.
PANEL CAMP 5A SCHEDULE
MAIN BUS SIZE (AMPS): 150 INTERRUPT. RATING (KAIC): 10 NEUTRAL BUS SIZE: 100% MOUNTING TYPE: SURFACE MAIN BUS MATERIAL: COPPER VOLTAGE: 120 / 240 SECTION NO.: 1 OF 1 LOCATION: MECHANICAL ROOM MAIN CIRCUIT BREAKER (AMPS): 150 PHASE: 1 WIRE: 3 ENCLOSURE TYPE: NEMA 1 BOLT ON BRANCH CIRCUIT BREAKERS
CKT
NO. DESCRIPTION LOAD
TYPE
LOAD
(KVA)
BREAKER BREAKER LOAD
(KVA)
LOAD
TYPE DESCRIPTION CKT NO.
AMPS POLES POLES AMPS
UH-1 WEST
C 1.80
20 2 A
2 20
1.80 C
UH-1 EAST
3 C 1.80 B 1.80 C 4
UH-1 WEST
C 1.80
20 2 A
2 20
1.80 C
UH-1 EAST
7 C 1.80 B 1.80 C 8
9 EF-1 WEST M 0.07 20 1 A 1 20 0.08 N DWH-3 10
11 UH-2 C 1.00 30 1 B 1 30 1.00 C UH-3 12
13 LAUNDRY GFI RECEPT R 0.36 20 1 A 1 20 0.51 N LIGHTS 14
15 DWH-2 N 0.08 20 1 B 1 20 0.20 N HAND DRYER EAST 16
17 GFI RECEPT WEST BATH R 0.54 20 1 A 1 20 0.72 R WASHER RECPT. 18
19 HAND DRYER WEST N 0.20 20 1 B 1 20 0.20 N OUTSIDE LIGHTS 20
21 DWH-1 N 0.08 20 1 A 1 20 0.18 R OUTSIDE GFI 22
DRYER
C 2.50
30 2
B 1 20 0.36 R MECH GFI RECEPT 24
25 C 2.50 A 1 20 0.36 N POWER ENTRY DOORS 26
27 SPARE N 0.00 20 1 B 1 20 0.54 R GFI RECEPT EAST BATH 28
29 SPARE N 0.00 20 1 A 1 20 0.00 N SPARE 30
31 SPARE N 0.00 20 1 B 1 20 0.00 N SPARE 32
33 SPARE N 0.00 20 1 A 1 20 0.00 N SPARE 34
35 SPACE N 0.00 -- 1 B 1 -- 0.00 N SPACE 36
37 SPACE N 0.00 -- 1 A 1 -- 0.00 N SPACE 38
39 SPACE N 0.00 -- 1 B 1 -- 0.00 N SPACE 40
CONNECTED LOAD PER PHASE (kVA) = 12.6 13.3 TOTAL CONNECTED LOAD = 25.9 KVA 107.9 AMPS
(AMPS) = 105.0 110.7 TOTAL DEMAND LOAD = 31.3 KVA 130.2 AMPS
LOAD TYPES: C = CONTINUOUS, R = RECEPTACLE, M = MOTOR, N = NON-CONTINUOUS
CEILING MOUNTED LIGHTING FIXTURE, TYPE AS
NOTED.
2'-0" EMERGENCY LONG STRIP LIGHT FIXTURE, TYPE AS
NOTED.
EMERGENCY RECESSED DOWNLIGHT FIXTURE, TYPE AS
NOTED
J JUNCTION BOX, 4" SQUARE x 2-1/8" DEEP GALVANIZED PRESSED
STEEL, MOUNTED ABOVE CEILING.
CEILING MOUNTED CANOPY FIXTURE, TYPE AS NOTED
ST TIME CLOCK LIGHT SWITCH. IN CAST DEVICE BOX AT 48" ABOVE
FINISHED FLOOR, 20 AMPERE 120/277V A.C. ONLY. PROVIDE WITH
WHITE PLASTIC DECORA STYLE COVER PLATE.
ALPHA
CORPORATION
203.013 5A E1.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5A BATHHOUSE DISAVINO OCTOBER 6 2023
21000 ATLANTIC BLVD, S. 400
www.alphacorporation.com
MOTOR AND EQUIPMENT SCHEDULE
EQUIPMENT NAME HP KW RATED
VOLT. PHASE FLA
MOTOR CONTROLLER FEEDER LOCAL SWITCH
REMARKS
TYPE LOCAL CONTROL
WIRE
CONDUIT
TYPE
SIZE POLES
NO. SIZE GRD.
EF-1 -- -- 115 1Ø 0.6 OCCUPANCY SENSOR AND SWITCH 2 #12 #12 3/4" MRT 20A 1
UH-1 -- 3.6 240 1Ø 15.0 LOCAL SWITCH 2 #12 #12 3/4" INT 20A 2
UH-2 -- 1.0 120 1Ø 8.3 LOCAL SWITCH 2 #12 #12 3/4" MRT 20A 1
UH-3 -- 1.0 120 1Ø 8.3 LOCAL SWITCH 2 #12 #12 3/4" MRT 20A 1
DWH-1,2,3 -- 0.08 120 1Ø 0.7 LOCAL SWITCH 2 #12 #12 3/4" NFSS 30A 1
NOTES:
NFSS - NON FUSED SAFETY SWITCH SEE MECHANICAL DRAWINGS FOR AUXILIARY
FSS - FUSED SAFETY SWITCH CONTACT REQUIREMENTS.
MRT - MOTOR RATED TOGGLE SWITCH
INT - INTEGRAL WITH MOTOR CONTROLLER
GENERAL NOTES
1. CONTRACTOR TO COORDINATE INCREASED LOAD WITH UTILITY
AND PROVIDE LOAD LETTER TO NOVEC.
2. PROVIDE INTEGRAL SURGE PROTECTION FOR PANELBOARD
PER SPECIFICATIONS.
NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING
EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE
START OF CONSTRUCTION.
G2. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS
CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST",
OR "(E)".
G3. DEMOLITION DEFINITION: DISCONNECTION AND REMOVAL OF
ASSOCIATED CONDUCTORS SHALL CONSIST OF THE REMOVAL
OF THE CONDUCTORS BACK TO THE NEXT EXISTING DEVICE TO
REMAIN. NEW CONDUIT AND CONDUCTORS SHALL BE PROVIDED
TO RECONNECT ANY EXISTING TO REMAIN DEVICES
INTERRUPTED BY THE DEMOLITION UNDER THIS PROJECT.
1 2
N5A BATHHOUSE - LIGHTING DEMO1N5A BATHHOUSE - LIGHTING2
S
S
OS
S
C S
C
2 2
2 2
OS
OSOS
S C
S
C
SC
PANEL CAMP 5A
S C
S C
S C
S S
S
1B 1B 1B
1 1
1A 1
2A 2A
1A
1B1B 1B
1A
5A
5A
PANEL CAMP 5A
1A
S C
S C
2 2
S
S T S T
S
T S T S T
S
T
ALPHA
CORPORATION
5A BATHHOUSE LIGHTING.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5A BATHHOUSE DISAVINO OCTOBER 6 2023
21000 ATLANTIC BLVD, S. 400
www.alphacorporation.com
GENERAL NOTES
1. DISCONNECT AND REMOVE LIGHT SWITCH. REMOVE ALL
ASSOCIATED CONDUIT AND CONDUCTORS BACK TO SOURCE.
2. DISCONNECT AND REMOVE LIGHT FIXTURE. REMOVE ALL
ASSOCIATED CONDUIT AND CONDUCTORS BACK TO SOURCE.
3. PROVIDE ASTRONOMICAL CLOCK AND CONNECT TO EXTERIOR
LIGHTING. PROVIDE PROGRAMMING FOR 365 DAYS TO TURN ON
LIGHTING AT DUSK AND TURN OFF LIGHTING AT DAWN.
NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING
EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE
START OF CONSTRUCTION.
G2. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS
CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST",
OR "(E)".
G3. DEMOLITION DEFINITION: DISCONNECTION AND REMOVAL OF
ASSOCIATED CONDUCTORS SHALL CONSIST OF THE REMOVAL
OF THE CONDUCTORS BACK TO THE NEXT EXISTING DEVICE TO
REMAIN. NEW CONDUIT AND CONDUCTORS SHALL BE PROVIDED
TO RECONNECT ANY EXISTING TO REMAIN DEVICES
INTERRUPTED BY THE DEMOLITION UNDER THIS PROJECT.
N5A BATHHOUSE - POWER DEMO1N5A BATHHOUSE - POWER2
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI GFI
GFIGFI
GFI
GFI
GFIGFI
1NEMA 6-30R
GFIGFI
PANEL CAMP 5A
2 2
1 1
2J J
GFI,WP
UH-1 UH-1
UH-1
UH-2
UH-3
5 5
HAND DRYERS
HAND DRYERS
GFI
GFI
DWH-1,2,3
UH-15
5A
5A 5,7
5A
5A 10,15,21
5A
5A
5A 17,26,28
5A 23,25
5A
5A 6,8
5A
PANEL CAMP 5A 6
5A
5A
5A
EF-1 5
5A
5A 13,24
JJ
S M
S M
S M
ALPHA
CORPORATION
5A BATHHOUSE POWER.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5A BATHHOUSE DISAVINO OCTOBER 6 2023
21000 ATLANTIC BLVD, S. 400
www.alphacorporation.com
GENERAL NOTES
1. DISCONNECT AND REMOVE RECEPTACLE. REMOVE ALL
ASSOCIATED CONDUIT AND CONDUCTORS BACK TO SOURCE.
2. DISCONNECT MECHANICAL EQUIPMENT. REMOVE ALL
ASSOCIATED CONDUIT AND CONDUCTORS BACK TO SOURCE.
3. DISCONNECT AND REMOVE HAND DRYER. REMOVE ALL
ASSOCIATED CONDUIT AND CONDUCTORS BACK TO SOURCE.
4. PROVIDE RECEPTACLE 6" ABOVE COUNTERTOP.
5. SEE MOTOR AND EQUIPMENT SCHEDULE FOR MOTOR AND
FEEDER CHARACTERISTICS.
6. DISCONNECT AND REMOVE PANEL BOARD. TAG, PROTECT AND
RETAIN MAIN FEEDER FOR REUSE.
7. PROVIDE PANEL BOARD, CONNECT TO MAIN FEEDER RETAINED
DURING DEMOLITION. SEE ASSOCIATED PANEL SCHEDULE FOR
CIRCUIT QUANTITIES.
8. CORE DRILL FOR CONDUIT PENETRATION, SEAL PENETRATION
WATERTIGHT.
NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING
EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE
START OF CONSTRUCTION.
G2. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS
CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST",
OR "(E)".
G3. DEMOLITION DEFINITION: DISCONNECTION AND REMOVAL OF
ASSOCIATED CONDUCTORS SHALL CONSIST OF THE REMOVAL
OF THE CONDUCTORS BACK TO THE NEXT EXISTING DEVICE TO
REMAIN. NEW CONDUIT AND CONDUCTORS SHALL BE PROVIDED
TO RECONNECT ANY EXISTING TO REMAIN DEVICES
INTERRUPTED BY THE DEMOLITION UNDER THIS PROJECT.
DETAILS.DWGF:\PROJECTS\20\203 NPS NCR (ALPHA)\203.013 PRWI CAMP 5A, 5B, AND VISITOR CENTER IMPROVEMENTS\CAD\CAMP 5A BATHHOUSE DISAVINO OCTOBER 6 2023
21000 ATLANTIC BLVD, S. 400
www.alphacorporation.com
ALUMINUM DIE CAST WITH HIGH-GLOSS BAKED WHITE ENAMEL FINISH.HOUSING:
GENERAL: RECESSED L.E.D. DOWNLIGHT, 6" APERTURE.
LENS: PRESSED-IN DIFFUSE LENS.
DRIVER:
LEDS:
ELECTRONIC DIMMABLE DRIVER; HIGH EFFICIENCY, U.L. LISTED, RATED FOR MULTI-VOLT
OPERATION FROM 120-277V, MAXIMUM SYSTEM INPUT WATTAGE OF 15.
1500 LUMEN OUTPUT, 3000K COLOR TEMPERATURE, MINIMUM CRI OF 80,
MINIMUM 70% LUMEN MAINTENANCE AT 60,000 HOURS
LIGHTING FIXTURE TYPE 1
5-3/4"
7" 7-1/2"
LIGHTING FIXTURE TYPE 3
VERTICAL VANITY BATHROOM L.E.D. LIGHTING FIXTURE. 2' LONG RATED FOR
DRIVER:
LEDS:
GENERAL:
HOUSING:
LENS: EXTRUDED ACRYLIC DIFFUSER.
ELECTRONIC DIMMABLE DRIVER; HIGH EFFICIENCY, U.L. LISTED, RATED FOR MULTI-VOLT
OPERATION FROM 120-277V, MAXIMUM SYSTEM INPUT WATTAGE OF 27.
1550 LUMEN OUTPUT, 3000K COLOR TEMPERATURE, MINIMUM 90 CRI,
MINIMUM 70% LUMEN MAINTENANCE AT 50,000 HOURS
ACRYLIC DIFFUSER WITH BRUSHED NICKEL HOUSING.
1A ALL REQUIREMENTS ARE THE SAME AS TYPE 1 WITH 10W CONSTANT POWER
BATTERY PACK AND UL TRANSFER DEVICE.
GENERAL:
HOUSING:
LENS:
2'-0" L.E.D STRIP LIGHT, SURFACE MOUNTED.
STEEL HOUSING WITH ALUMINUM HEAT SINK.
PRISMATIC, SEMI-DIFFUSE LENS.
DRIVER:
LEDS:
ELECTRONIC DIMMABLE DRIVER; HIGH EFFICIENCY, U.L. LISTED, RATED FOR MULTI-VOLT
OPERATION FROM 120-277V, MAXIMUM SYSTEM INPUT WATTAGE OF 25.
3,500 LUMEN OUTPUT, 3000K COLOR TEMPERATURE, MINIMUM 80 CRI,
MINIMUM 70% LUMEN MAINTENANCE AT 90,000 HOURS.
LIGHTING FIXTURE TYPE 2
2A ALL REQUIREMENTS ARE THE SAME AS TYPE 2 WITH 10W CONSTANT POWER
BATTERY PACK AND UL TRANSFER DEVICE.
LIGHTING FIXTURE TYPE 5
SURFACE MOUNTED CANOPY L.E.D. LIGHTING FIXTURE. LISTED FOR WET LOCATIONS.
DRIVER:
LEDS:
GENERAL:
HOUSING:
LENS: TRANSLUCENT POLYCARBONATE LENS.
ELECTRONIC DIMMABLE DRIVER; HIGH EFFICIENCY, U.L. LISTED, RATED FOR MULTI-VOLT
OPERATION FROM 120-277V, MAXIMUM SYSTEM INPUT WATTAGE OF 35.
4500 LUMEN OUTPUT, 4000K COLOR TEMPERATURE, MINIMUM 80 CRI,
MINIMUM 70% LUMEN MAINTENANCE AT 50,000 HOURS
CAST-ALUMINUM HOUSING WITH A POLYESTER POWDER COAT FINISH.
LENS:
HOUSING:
GENERAL:
SINGLE-PIECE DIE-CAST ALUMINUM HOUSING, DIE-CAST DOOR FRAME FULLY GASKETED.
WALL MOUNTED L.E.D FIXTURE FOR OUTDOOR LOCATIONS, MOUNTED AT 8' AFF.
INDIVIDUALLY FORMED ACRYLIC LENS.
LEDS: 3,000 LUMEN OUTPUT, 4000K COLOR TEMPERATURE, MINIMUM 80 CRI,
DRIVER: ELECTRONIC DRIVER; HIGH EFFICIENCY, U.L. LISTED, RATED FOR
MULTI-VOLT OPERATION FROM 120-277V, MAXIMUM SYSTEM INPUT WATTAGE OF 32.
LIGHTING FIXTURE TYPE
MINIMUM 70% LUMEN MAINTENANCE AT 100,00 HOURS.
DARK BRONZE COLOR.
1B ALL REQUIREMENTS ARE THE SAME AS TYPE 1 BUT RATED FOR WET LOCATION.
DAMP LOCATIONS.
MEN'S
BATHROOM
WOMEN'S
BATHROOM
SHOWER
AREA
SHOWER
AREA
LAUNDRY
MECHANICAL
COVERED
PORCH
ASSUMED
ASBESTOS-CONTAINING
FIRE DOOR
- A HAZARDOUS MATERIALS ASSESSMENT WAS PERFORMED
WITHIN THE PROJECT AREA BY ARC ENVIRONMENTAL IN
OCTOBER 2022; CONTRACTOR SHALL REFER TO THE
ASSOCIATED REPORT 'PRE-ALTERATION HAZARDOUS
MATERIALS SURVEY, PRINCE WILLIAM FOREST PARK” DATED
NOVEMBER 23, 2022, FOR DETAILS RELATED TO THE
ASSESSMENT AND SUBSEQUENT ANALYTICAL DATA.
- IT IS NOT THE INTENTION OF THIS PROJECT TO REMOVE ALL
IDENTIFIED REGULATED AND/OR HAZARDOUS MATERIALS FROM
THE PROJECT AREA. REMEDIATION EFFORTS ARE INTENDED TO
ADDRESS HAZARDS DURING CONSTRUCTION EFFORTS AND
SHALL BE LIMITED TO THE REMOVAL OF IDENTIFIED MATERIALS
WHICH MAY BE IMPACTED BY THE PLANNED IMPROVEMENTS
PROJECT. CONTRACTOR SHALL REVIEW DRAWINGS AND
APPLICABLE SPECIFICATIONS FOR APPLICABLE SCOPE DETAILS.
- AN ASSUMED ASBESTOS-CONTAINING MATERIAL (ACM) HAS
BEEN IDENTIFIED WITHIN THE PROJECT AREA. THE IDENTIFIED
ASSUMED ACM IS NOT INTENDED TO BE REMOVED OR
DISTURBED DURING THE COURSE OF THIS PROJECT.
- LEAD-BASED PAINT (LBP) WAS NOT IDENTIFIED WITHIN THE
PROJECT AREA. LEAD-SAFE WORK PRACTICES SHALL BE
EMPLOYED PER 29 CFR 1926.62 FOR AREA WHERE
LEAD-IN-CONSTRUCTION WORK IS SCHEDULED. NO LEAD-BASED
PAINT ABATEMENT IS ANTICIPATED AS PART OF THIS PROJECT.
- GATHER, COLLECT, AND PROPERLY DISPOSE OF IDENTIFIED
MERCURY-CONTAINING LIGHT TUBES, DIELECTRIC
FLUID-CONTAINING LIGHT BALLASTS, AND
MERCURY-CONTAINING THERMOSTATS WITHIN THE PROJECT
AREA AS IDENTIFIED IN THE SCOPE OF WORK. REFER TO
SPECIFICATION SECTION 02 84 16 FOR ADDITIONAL
REQUIREMENTS.
GENERAL HAZARDOUS MATERIAL
NOTES APPLICABLE TO THE
PROJECT AREA
3/8" = 1'-0"
0' 4' 8'
HAZMAT - 5A - 100%.DWGP:\IH\PROJECTS 2022\COMMERCIAL\1017-22 ALPHA - PRWI CAMPS 5A AND 5B BATHHOUSES AND VISITOR CENTER\100% CD AKRICK OCTOBER 2 2023
ALPHA
CORPORATION
21000 ATLANTIC BLVD, S. 400
DULLES, VA 20166 (703)450-0800
www.alphacorporation.com
ARC ENVIRONMENTAL, LLC
1311 HAUBERT STREET
BALTIMORE, MARYLAND 21230
Ph: 410-659-9971 www.arcenvironmental.com
ArcEnvironmental
CAMP 5A BATHHOUSE PLAN - HAZARDOUS MATERIALS
SCALE: 38" = 1'-0"H1
File details come from the government source that posted it. Updated .