MOUNT PIPING CLOSE
AGAINST EXTERIOR OF WALL.
PIPING SHOWN AWAY FROM
WALL FOR CLARITY ONLY.
\ □ (E)ACU-4 \
®1L ___ rE lA c c
-1
L ___ rE lA c c
-3
'-=, ==LJ============a�
� I I I I I I I I I I I I I
I I I I I I I I I I I
I I I I I I I I I I I
I I I I I I I I I I I
I I I I I I I I I I I
I I I I I I I I I I I I
I I I trn □
I I I I I I I I
DN
DC
MECHANICAL DEMO PLAN
1/8" = 1'-0"
®DUCT ABOVE
�1 G)
76" lt-------122"--------<
EXIST. CRAG FRONT
EXIST. CABINET DIMENSIONS
1/8" = 1'-0"
DEMOLITION PLAN NOTES:
(D REMOVE EXISTING LIEBERT CRAC UNIT #2.
@ EXISTING DUCTWORK TO REMAIN. MODIFY DUCT AS REQUIRED TO RECEIVE NEW
CRAC UNIT.
@ REMOVE EXISTING REFRIGERANT PIPING AS SHOWN. THIS WORK SHALL BE DONE
ONE CIRCUIT AT A TIME AND SCHEDULED WITH CONTRACTING OFFICER
REPRESENTATIVE. SALVAGE R-22 REFRIGERANT, TEST FOR IMPURITIES AND REUSE
AFTER NEW PIPING IS INSTALLED. RETURN EXCESS REFRIGERANT TO KSANG. PATCH
AND SEAL EXISTING WALL PENETRATIONS.
@) SECTION OF EXISTING REFRIGERANT PIPING TO REMAIN.
@ REMOVE EXISTING #2 CONDENSING UNIT. EXISTING HOUSE KEEPING PAD AND
ELECTRICAL TO REMAIN FOR NEW UNIT, MODIFY AS REQUIRED FOR NEW INSTALL
@ EXISTING CONDENSING UNIT SHALL REMAIN
(f) EXISTING DOMESTIC WATER PIPING TO CRAC UNITS TO REMAIN
@ REMOVE CRAC-2 REFRIGERANT LINES. SUPPORTS MAY BE REUSED FOR NEW PIPING
GENERAL NOTES:
1. REPAIR ALL DAMAGE TO WALLS AND CEILING DUE TO DEMOLITION.
2. EXISTING CEILING TO REMAIN IN TACT DURING CONSTRUCTION. MINIMIZE
DIRT IN ROOM BY VACUUMING CEILING CAVITY AROUND AREAS OF DIRECT
WORK WITH HEPA FILTERED VACUUM.
3. FIELD VERIFY ALL EXISTING CONDITIONS.
4. ONCE CONTRACT IS AWARDED AND WORK STARTS, IT IS THE CONTRACTORS
RESPONSIBILITY TO MAINTAIN COOLING IN THE SERVER FARM.
5. PROVIDE A DETAILED PLAN OF HOW THE INSTALLATION OF THE NEW CRAG
UNIT AND RELOCATION OF THE REFRIGERANT LINES WILL OCCUR PRIOR TO
STARTING DEMOLITION.
6. REFER TO THE STATEMENT OF WORK FOR ADDITIONAL REQUIREMENTS.
1-----------122"---------I r 2" f 118"
1" •i----+1----- PLENUM-------___, 35,, 32" FLANGE
PLENUM
L
FLANGE G)
l=::::::::::::
j
EXIST. CRAG TOP
� FLEX DUCT ITYPl
4' 8'
SCALE: 1/8" = 1'
16" EB NORTH
184th CES
Kansas Air National Guard McConnell AFB Wichita KS
Project Name:
BUILDING 54 -
REPLACE CRAG
UNIT#2
Project No.
PRQE222015
ACAD File:
P222015 M-1.DWG
Designer:
Lt. Col. Brock J. Sissel Drawn by: Check by:
J.K.B. D.C.
Date: Scale:
06-15-2022 As Noted Sheet Name:
B54 - DEMO CRAC UNIT
#2 AND COOLANT LINES
Sheet:
M 0_ 1 Sheet No. 1 of2
MOUNT PIPING CLOSE
AGAINST EXTERIOR OF WALL.
PIPING SHOWN AWAY FROM
WALL FOR CLARITY ONLY.
®-0 (E)ACU-4
'-=, ==LJ============a�
� I I I I I I I I I I I I I
I I I I I I I I I I I
� I I I I I I I I I I I I I
I I I I I I I I I I I
� I I I I I I I I I I I I I
� I I I I I I I I I I I I I
I I I trn □
I I I I I I I I DN
DC
MECHANICAL PLAN - WEST MECHANICAL
1/8" = 1'-0"
ANGER ROD TO STRUCTURE I UNISTRUT
EAVY DUTY CLEVIS HANGER
SIZED FOR INSULATION THICKNESS
IPE INSULATION TO MATCH
EXISTING TYPE AND THICKNESS.
NSULATION SADDLE SHIELD 14 GA
GALVANIZED x24" LONG
NOTE: FOR EXTERIOR OR WET
LOCATIONS USE GALVANIZED MATERIALS.
PIPE HANGER DETAIL
1/2" = 1'-0"
FLEX DUCT (TYP)
DUCT ABOVE /+") I
�r 132"
FLD J
� [Q] VF'v
G) 76" i I i I � 131"
NEW CRAG CABINET FRONT
(BASED ON LIEBERT DS COOLING SYSTEM)
CABINET DIMENSIONS
1/8" = 1'-0"
Alternate Ref Piping E rigerant ntrance rr=·1
LL
High Volt Conne ction(s)
PLAN NOTES:
())INSTALL NEW CRAC UNIT. CONNECT WATER, CONDENSATE DRAIN, AND DUCT WORK
TO UNIT AND ROUTE NEW REFRIGERANT PIPING TO UNIT. MODIFY EXISTING
ELECTRICAL SERVICE TO UNIT AS REQUIRED AND MAKE FINAL CONNECTION. PULL
NEW WIRES AS REQUIRED TO MEET CODE IF NECESSARY. CONNECT TO DUCT WITH
FLEX DUCT
® MODIFY DUCT AS REQUIRED TO RECEIVE NEW CRAC UNIT. CONNECT WITH FLEX
DUCT
® INSTALL UNISTRUT TO SUPPORT NEW REFRIGERANT PIPING, MOUNT TO EXTERIOR
WALL ABOVE DOORWAYS AND ELECTRICAL EQUIPMENT. PROVIDE FREE STANDING
PIPE STANDS AS REQUIRED.
@) INSTALL NEW REFRIGERANT PIPING ALONG THE EXTERIOR OF THE BUILDING TO
PENETRATE EXTERIOR WALL AT NEW LOCATION. THIS WORK SHALL BE DONE ONE
UNIT AT A TIME AND SCHEDULED WITH CONTRACTING OFFICER REPRESENTATIVE.
@) REATTACH NEW PIPING TO EXISTING PIPING FOR CRAC UNITS #1 AND #3
@) INSTALL NEW CONDENSING UNIT. MODIFY EXISTING ELECTRICAL SERVICE TO UNIT AS
REQUIRED AND MAKE FINAL CONNECTION. PULL NEW WIRES AS REQUIRED TO MEET
CODE IF NECESSARY
(j) NOT USED
@) EXISTING CONDENSING UNIT. CONNECT NEW REFRIGERANT LINES AND RECHARGE
SYSTEM
® CORE DRILL PRECAST WALL AND PROVIDE LINK SEAL AROUND PIPE TO SEAL
PENETRATION AIR TIGHT
@ PROVIDE 3 TEMPERATURE AND HUMIDITY SENSORS IN EACH ROW OF SERVERS.
PROVIDE LINK TO DDC PAGE WITH ALARM NOTIFICATION IF TEMP RISES ABOVE 78°F
(ADJ) OR HUMIDITY IS <30% OR >50%
<D) TIE DDC INTO NEW CRAC-2 AND PROVIDE MAXIMUM DATA AVAILABLE FOR THIS UNIT
ON THE DDC PAGES.
GENERAL NOTES:
1. REPAIR ALL DAMAGE TO WALLS AND CEILING DUE TO DEMOLITION.
2. EXISTING CEILING TO REMAIN IN TACT DURING CONSTRUCTION. MINIMIZE
DIRT IN ROOM BY VACUUMING CEILING CAVITY AROUND AREAS OF DIRECT
WORK WITH HEPA FILTERED VACUUM.
3. FIELD VERIFY ALL EXISTING CONDITIONS.
4. ONCE CONTRACT IS AWARDED AND WORK STARTS, IT IS THE CONTRACTORS
RESPONSIBILITY TO MAINTAIN COOLING IN THE SERVER FARM.
5. PROVIDE A DETAILED PLAN OF HOW THE INSTALLATION OF THE NEW CRAC
UNIT AND RELOCATION OF THE REFRIGERANT LINES WILL OCCUR PRIOR TO
STARTING DEMOLITION.
6. REFER TO THE STATEMENT OF WORK FOR ADDITIONAL REQUIREMENTS.
,__ ______ 105114" ______ ., Handle
Low Volt Connection(s)
NEW CRAG CABINET TOP
4' 8'
SCALE: 1/8" = 1'
16'
5/16" I
EB NORTH
184th CES
Kansas Air National Guard McConnell AFB Wichita KS
Project Name:
BUILDING 54 -
REPLACE CRAG
UNIT#2
Project No.
PRQE222015
ACAD File:
P222015 M-1.DWG
Designer:
Lt. Col. Brock J. Sissel Drawn by: Check by:
J.K.B. D.C.
Date: Scale:
06-15-2022 As Noted Sheet Name:
B54 - REPLACE CRAC
UNIT#2
Sheet:
M-1 Sheet No. 2 of2
1151126746N Typewritten Text
PROVIDE ALUMINUM JACKET ON EXTERIOR PIPING
1151126746N Line
| PRQE 222012 - MD-1 |