Project 506-21-110 Drawings.pdf
PDF 28 MB Posted
- Solicitation number
- 36C25023B0003
About this file
This federal contract opportunity solicitation seeks a contractor to construct an addition to Building 32 at the Energy Center to house a new emergency generator. The work includes tying the new generator into the existing fuel farm, installing automatic transfer switches for the new standby power system to back up the central chilled water plant, and integrating digital controls with the facility's existing Siemens building management system. The solicitation number is 36C25023B0003 and it was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10. The contractor will have 540 days to complete the work.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
T
ANN ARBOR
VETERANS AFFAIRS MEDICAL CENTER
#506-21-110
DEPARTMENT OF VETERANS AFFAIRS
2215 FULLER ROAD, ANN ARBOR, MI 48105
EMERGENCY POWER CENTRAL CHILLER PLANT
D R A W I N G L I S T
G E N E R A L N O T E S
1. SEE GENERAL PROJECT NOTES FOR NEW WORK FOR ADDITIONAL REQUIREMENTS FOR WORK WITHIN THE EXISTING FACILITY.
2. THE GENERAL CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND FIELD CONDITIONS PRIOR TO DEMOLITION AND CONSTRUCTION. IF PROVIDED, THE GENERAL CONTRACTOR SHALL CAREFULLY EXAMINE EXISTING BUILDING DOCUMENTS. THE CONTRACTOR SHALL BRING ANY DISCREPANCIES TO THE IMMEDIATE ATTENTION OF THE ARCHITECT.
3. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF EXISTING ITEMS TO REMAIN DURING DEMOLITION AND
CONSTRUCTION.
4. MAINTAIN EXIT EGRESS PATHS TO EXISTING EXIT DOORS DURING CONSTRUCTION.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL CONSTRUCTION ROUTES BEYOND THE AREAS OF WORK AND THE ROUTES MUST BE RETURNED TO THEIR ORIGINAL CONDITION AT THE END OF THE PROJECT.
6. MAINTAIN THE BUILDING IN A WEATHER TIGHT CONDITION AT ALL TIMES.
7. ALL DEMOLITION AND CONSTRUCTION ACTIVITIES SHALL BE COORDINATED WITH THE C.O.R. TO MINIMIZE DISRUPTIONS OF
NORMAL FUNCTIONS OF THE VA'S OCCUPIED AREAS.
8. IF CONSTRUCTION NOISE IS ANTICIPATED, SUBMIT A WRITTEN REQUEST TO THE C.O.R. FOR THE SCHEDULED TIME OF THE CONSTRUCTION ACTIVITIES. NO WORK SHALL BE DONE WITHOUT THE WRITTEN APPROVAL OF THE C.O.R. THE C.O.R. RESERVES THE RIGHT TO DISCONTINUE NOISY CONSTRUCTION AT ANY TIME. NO RADIOS SHALL BE PERMITTED AT ANY TIME IN WORK AREAS
ADJACENT TO OCCUPIED SPACES.
9. ALL EXISTING SERVICES AND UTILITIES SHALL BE MAINTAINED TO AREAS THAT ARE IN OPERATION AND SERVED BY THEM.
COORDINATE ALL DISRUPTIONS OR DISCONTINUATIONS OF UTILITIES AND SERVICES WITH C.O.R. NO SHUT DOWN OF EXISTING SERVICES IS ALLOWED TO OCCUR UNTIL RECEIVING THE C.O.R.'S WRITTEN APPROVAL OF THE SHUT DOWN SCHEDULE. PROVIDE TEMPORARY SERVICES AND/OR UTILITIES DURING INTERRUPTIONS AS REQUIRED AND APPROVED BY THE C.O.R.
10. DO NOT OVERLOAD THE EXISTING BUILDING STRUCTURE. MAINTAIN THE STRUCTURAL INTEGRITY OF ALL STRUCTURAL FRAMING
MEMBERS AND SYSTEMS AT ALL TIMES.
11. REMOVAL OF A PARTICULAR ITEM IS TO INCLUDE ALL RELATED ITEMS, SUCH AS REMOVAL OF WALLS WOULD INCLUDE ASSOCIATED DOORS, HARDWARE, ELECTRICAL, PLUMBING, MECHANICAL, ETC. REFER TO DEMOLITION DRAWINGS FOR MORE INFORMATION. FOR ALL REMOVALS, THE GENERAL CONTRACTOR SHALL COORDINATE WITH ALL OTHER DISCIPLINES INCLUDING
BUT NOT LIMITED TO MECHANICAL, ELECTRICAL AND PLUMBING.
12. THE CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT FOR ITEMS NOT DEMOLISHED OR REMOVED AS REQUIRED UNTIL
PERMANENT SUPPORT IS PROVIDED IN THE FINAL CONSTRUCTION.
13. ALL OPENINGS IN EXISTING WALLS, CEILINGS AND FLOORS, WHICH ARE THE RESULT OF REMOVALS AND OTHER NEW CONSTRUCTION ACTIVITY, SHALL BE PATCHED WITH NEW MATERIALS THAT MATCH THE EXISTING MATERIALS OR AS NOTED ON DRAWINGS. IF THE PATCH IS TO BE MADE IN FIRE RATED CONSTRUCTION, THE PATCH MUST ACHIEVE THE REQUIRED FIRE RATING. THE PATCH SHALL BE FINISHED TO A LIKE NEW CONDITION TO MATCH THE EXISTING FINISH.
14. ALL EXISTING OPENINGS IN CEILINGS, FLOORS AND WALLS DISCOVERED IN THE EXISTING STRUCTURE SHALL BE PATCHED WITH NEW MATERIALS THAT MATCH THE EXISTING MATERIALS. IF THE PATCH IS TO BE MADE IN FIRE RATED CONSTRUCTION, THE PATCH MUST ACHIEVE THE REQUIRED FIRE RATING. THE PATCH SHALL BE FINISHED TO A LIKE NEW CONDITION TO MATCH THE
EXISTING FINISH.
15. WHERE EXISTING SURFACES ARE TO BE REFINISHED OR ARE TO SERVE AS SUBSTRATE FOR THE ATTACHMENT OR APPLICATION OF NEW MATERIALS OR CONSTRUCTION, PREPARE OR ALTER THE EXISTING SURFACES AS NECESSARY TO PROPERLY
ACCOMMODATE THE NEW MATERIALS.
16. FIELD VERIFY SIZES AND DIMENSIONS OF ALL EXISTING UTILITIES THAT IMPACT THE NEW WORK. DETERMINE THE SIZE AND LOCATION THE PENETRATIONS FROM THE EXISTING UTILITIES WITHIN THE NEW WORK. SEAL TIGHT TO ALL PENETRATIONS AND
CAULK.
17. PENETRATIONS THROUGH EXISTING FIRE RATED CONSTRUCTION MUST BE PROPERLY CLOSED AND FIRE SAFE'D TO ACHIEVE THE REQUIRED FIRE RATING BY THE END OF CONSTRUCTION OPERATIONS FOR EACH DAY. ALL FIRE STOP MUST BE "HILTI RED" OR
EQUIVALENT IN COLOR.
18. NEW HOLES IN EXISTING ROOF STRUCTURES FOR NEW WORK MUST BE COORDINATED WITH THE EXISTING STRUCTURE SO THAT
CRITICAL STRUCTURAL MEMBERS ARE NOT DAMAGED.
19. NO EXISTING FIREPROOFING IS TO BE REMOVED FROM EXISTING BUILDING STRUCTURE FOR ANY NEW INSTALLATION FOR ANY
REASON.
E X I S T I N G F A C I L I T I E S:
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH APPLICABLE FEDERAL AUTHORITIES, CODES, RULES AND REGULATIONS.
2. THESE DOCUMENTS SHOW THE MINIMUM CONSTRUCTION REQUIREMENTS AND THE MINIMUM QUALITY OF WORK EXPECTED.
MORE STRINGENT REQUIREMENTS STIPULATED WITHIN RELEVANT MANUFACTURER’S INSTALLATION INSTRUCTIONS WILL
SUPERSEDE.
3. UNLESS OTHERWISE NOTED, ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED PER THE APPLICABLE PROVISIONS OF THESE
DOCUMENTS AND THE MANUFACTURER’S INSTRUCTIONS.
4. ALL MATERIALS USED SHALL BE NEW UNLESS OTHERWISE NOTED AND/OR OF A QUALITY TO MEET OR EXCEED ALL APPLICABLE INDUSTRY STANDARDS. WHERE SPECIFIED PRODUCTS OR MANUFACTURERS ARE NOT NOTED, THE CONTRACTOR IS REQUIRED
TO NOTIFY THE C.O.R. TO OBTAIN A MINIMUM STANDARD OF QUALITY.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL MEANS, METHODS AND TECHNIQUES FOR CONSTRUCTION.
6. COORDINATE ALL WORK WITH ALL OTHER DISCIPLINES, INCLUDING, BUT NOT LIMITED TO MECHANICAL, ELECTRICAL, PLUMBING & SITE DRAWINGS. EXACT SIZE AND LOCATION OF ALL ROOF AND FLOOR OPENINGS SHOWN ON ARCHITECTURAL DRAWINGS SHALL
BE VERIFIED WITH THE ASSOCIATED SUB-CONTRACTORS PRIOR TO CONSTRUCTION.
7. DO NOT SCALE DRAWINGS. DIMENSIONS SHALL GOVERN. ALL PLAN DIMENSIONS ARE TAKEN TO FINISH FACE OF CONSTRUCTION.
8. ALL CONCEALED WOOD SHALL BE FIRE RETARDANT TREATED.
9. THE GENERAL CONTRACTOR SHALL COORDINATE WITH ALL OTHER DISCIPLINES INCLUDING BUT NOT LIMITED TO MECHANICAL, ELECTRICAL, AND PLUMBING. SEAL CONSTRUCTION TIGHT TO ALL PENETRATIONS AND CAULK.
10. ALL PENETRATIONS THROUGH FIRE RATED CONSTRUCTION MUST BE FIRE SAFE'D IN ACCORDANCE WITH THE SPECIFICATIONS.
11. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL EQUIPMENT INSTALLATION AND VERIFYING ALL REQUIRED
ROUGH OPENINGS, AND ROUGH-IN DIMENSIONS PRIOR TO CONSTRUCTION.
12. UNLESS OTHERWISE NOTED, THE GENERAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL EXISTING SALVAGED STOCK
BEFORE ORDERING NEW MATERIAL.
13. ALL FIRE RATED WALL AND FLOOR PENETRATION MUST COMPLY WITH ASTM-E814
14. ALL DOOR OPENINGS SHALL BE 4" FROM A PERPENDICULAR PARTITION TO OUTSIDE FACE OF FRAME, UNLESS NOTED OR
DETAILED OTHERWISE.
15. CONTRACTOR IS TO CLOSE OFF ANY VOIDS LEFT AS A RESULT OF ANY REMOVALS AND NEW CONSTRUCTION, AS WELL AS INFILL ANY EXISTING VOIDS IN NEWLY DESIGNATED FIRE RATED PARTITIONS. ALL PATCHES SHALL MATCH AND ALIGN WITH
SURROUNDING MATERIALS AND SHALL BE IN ACCORDANCE WITH NFPA CODE.
16. CONTRACTOR SHALL SEAL PARTITION WALLS AROUND ALL M.E.P. PENETRATIONS OR OPENINGS, RESULTING FROM M.E.P.
INSTALLATIONS INCLUDING BUT NOT LIMITED TO THE SLAB, ABOVE AND BELOW CEILINGS.
17. ALL NEW MASONRY WORK INCLUDING NEW PARTITIONS, INFILL AND PATCHING; MATCH EXISTING COURSING AND TOOTH IN WITH
EXISTING ADJ. CONSTRUCTION.
18. UNLESS NOTED, THE CONNECTION AT THE TOP OF THE PARTITION TO THE STRUCTURE ABOVE MUST ALLOW FOR 1" MINIMUM VERTICAL MOVEMENT, EITHER UP OR DOWN. AT FIRE RATED METAL STUD PARTITIONS, THE TOP CONNECTION MUST BE A FIRE STOP CONNECTION THAT ALLOWS 1" MINIMUM VERTICAL MOVEMENT, EITHER UP OR DOWN. HOLD GYPSUM WALL BOARD AND STEEL STUDS 1" FROM THE BOTTOM OF THE STRUCTURE ABOVE. DO NOT SCREW-ATTACH STEEL VERTICAL STUDS OR GYPSUM WALL BOARD TO THE TOP TRACK. INSTALL BRIDGING 12" MINIMUM FROM THE TOP OF THE STUDS.
19. LABEL ALL RATED PARTITIONS (FIRE & SMOKE) ABOVE THE CEILING, ON BOTH SIDES OF THE WALL.
20. TRAINING ON ALL EQUIPMENT MUST BE RECORDED BY THE CONTRACTOR.
N E W W O R K:
1. SYSTEM OUTAGES MUST BE COORDINATED AND SCHEDULED WITH THE COR.
2. PARTIAL SYSTEM OUTAGES VIA LOCAL ISOLATION OF CIRCUITS, PUMPS, AND OTHER EQUIPMENT WILL BE REQUIRED SO THAT
SYSTEMS CAN REMAIN AVAILABLE TO THE HOSPITAL.
3. CHILLED WATER SYSTEM OUTAGES SHOULD BE SCHEDULED FROM NOVEMBER THROUGH MAY TO ENSURE THAT EQUIPMENT
THAT REMAINS AVAILABLE CAN MEET POTENTIAL DEMAND.
4. OUTAGES FOR SWITCHOVER AND TESTING RELATED TO THE NEW MOTOR CONTROL CENTER AUTOMATIC TRANSFER SWITCHES
(QTY: 2) WILL NEED TO BE SCHEDULED ON WEEKENDS.
G E N E R A L P H A S I N G N O T E S:
1W
1E
T2
T3
PROJECT LOCATION
BUILDING 32
FULLER CT.
FULLER RD.
ANN ARBOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /A n n A rb o r V
A
E m r P w r
C e n tr a l C h ill e r
P la n t/ F
F E
A n n
A rb o r
E m e rg e n c y P o w e r_
B rv t
/1
/2
:2
:3
P
M
GI000
COVER SHEET
8/19/2022 PH TD
EMERGENCY POWER CENTRAL
CHILLER PLANT
506-21-110
2215 FULLER RD, ANN ARBOR, MI
BID DOCUMENTS
VA ANN ARBOR
HEALTHCARE
SYSTEM Approved: Veteran's Affairs Medical Center
GENERAL
GI000 COVER SHEET
GI001 ABBREVIATIONS AND GENERAL DETAILS
GI002 LIFE SAFETY PLAN
GI003 LIFE SAFETY CODE REVIEW
CIVIL
VF100 EXISTING SURVEY
C100 CONTRACTOR LAYDOWN
CD100 DEMOLITION PLAN
CS100 SITE PLAN
CG100 GRADING PLAN
CU100 UTILITY PLAN
CS500 DETAILS
CS501 EROSION CONTROL GENERAL NOTES AND DETAILS
STRUCTURAL
S001 GENERAL NOTES
SB101 STRUCTURAL FOUNDATION PLAN AND SLAB PLAN
SF101 STRUCTURAL ROOF FRAMING PLAN
S301 STRUCTURAL SECTIONS
S501 STRUCTURAL DETAILS
ARCHITECTURE
AE100 OVERALL FIRST FLOOR PLAN
AD101 DEMOLITION FLOOR PLAN AND ELEVATION
AE101 GENERATOR ROOM PLANS
AE102 ROOF PLAN
AE103 MEZZANINE PLAN
AE201 EXTERIOR ELEVATIONS
AE301 BUILDING SECTIONS
AE302 BUILDING SECTIONS
AE303 MEZZANINE SECTIONS
AE311 WALL SECTIONS
AE312 WALL SECTIONS
AE401 STAIR DETAILS
AE501 MISC DETAILS
AE502 MISC DETAIL
AE601 DOOR AND WINDOW SCHEDULE
AE800 INTERIOR FINISHES
FIRE PROTECTION
FX101 FIRE SUPPRESSION PLAN
PLUMBING
PL101 PLUMBING PLANS
MECHANICAL
M001 MECHANICAL LEGEND
M101 MECHANICAL FIRST FLOOR PLAN
M301 MECHANICAL SECTIONS
M501 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
M602 MECHANICAL CONTROLS AND FUEL OIL SYSTEM DIAGRAM
ELECTRICAL
E001 LEGEND AND ABBREVIATIONS
ED101 FIRST FLOOR DEMOLITION
EP101 FIRST FLOOR MAIN ELECTRICAL ROOM 113
EP102 FIRST FLOOR NEW WORK
EP103 OVERALL FIRST FLOOR PLAN
EP104 LIGHTNING PROTECTION PLAN - NEW GENERATOR BUILDING
ES100 OVERALL SITE PLAN
E501 ELECTRICAL DETAILS
E502 ELECTRICAL DETAILS
E601 SINGLE LINE DIAGRAM
NTS
PROJECT LOCATION MAP
NTS
VICINITY MAP
N N
No. Revisions: Date:
BID DOCUMENTS 8/19/2022
P1
A101
SIM
A101
SIM
A101
SIM
A101
SIM
A B B R E V I A T I O N S
LEVEL NAME W/ ELEVATION
NEW GRID HEAD
CALL OUT HEAD W/ SHEET NUMBER
ROOM NAME W/ ROOM NUMBER, AREA
& OCCUPANCY
BUILDING SECTION NUMBER W/ SHEET
NUMBER
WALL SECTION NUMBER W/
SHEET NUMBER
DOOR NUMBER
WALL TAG
KEYNOTE
REVISION TAG
FINISH TAG
DETAIL SECTION NUMBER W/
SHEET NUMBER
NORTH ARROW
LEVEL
ELEVATION
ROOM NAME
150 SF
S Y M B O L S
WINDOW TAGA
10'-0" CEILING HEIGHT TAG
A.B. ANCHOR BOLT
A.C.M. ASBESTOS CONTAINING MATERIALS
A.C.P. ASPHALT CONCRETE PAVING
A/C AIR CONDITIONING
ACOUS. ACOUSTIC
A.C.T. ACOUSTICAL CEILING TILE
A.D. AREA DRAIN
ADJ. ADJUSTABLE
AFF ABOVE FINISH FLOOR
AGG. AGGREGATE
AL. ALUMINUM
ALT. ALTERNATE
APPROX. APPROXIMATE
ARCH. ARCHITECT
ASPH. ASPHALT
BD. BOARD
BITUM. BITUMINOUS
BLDG. BUILDING
BLK. BLOCK
BLKG. BLOCKING
BM. BENCH MARK OR BEAM
BOT. BOTTOM
BRG. BEARING
BRK. BRICK
BRZ. BRONZE
BTWN. BETWEEN
B.U.R BUILT-UP ROOFING
CAB. CABINET
CARP. CARPET
C.B. CATCH BASIN
C.B.B. CEMENTITIOUS BACKER BOARD
CEM. CEMENT
CER. CERAMIC
CER.T. CERAMIC TILE
C.F.C.I. CONTRACTOR
FURNISH/CONTRACTOR INSTAL
C.F.O.I. CONTRACTOR FURNISH/OWNER
INSTALL
C.HK. COAT HOOK
C.I. CAST IRON
CIR. CIRCLE
C.J. CONSTRUCTION JOINT
CLG. CEILING
CLG.J. CEILING JOINT
CLKG. CAULKING
CLO. CLOSET
CLR. CLEAR
CLS. CLOSURE
CMU CONCRETE MASONRY UNIT
CNTR. COUNTER
C.O. CLEAN OUT
COL. COLUMN
COMB. COMBINATION
COMP. COMPOSITION
CONC. CONCRETE
CONN. CONNECTION
CONST. CONSTRUCTION
CONT. CONTINUOUS
CONV.O. CONVECTION OVEN
C.O.R. CONTRACTING OFFICER'S
REPRESENTATIVE
CTR. CENTER
C.W. COLD WATER
CW. CURTAINWALL
DET. DETAIL
DF. DOUGLAS FIR
D.F. DRINKING FOUNTAIN
DIA. DIAMETER
DIAG. DIAGONAL
DIM. DIMENSION
DISP. DISPOSAL
DIV. DIVISION
DN. DOWN
D.O. DOOR OPENING
DR. DOOR
D.S. DOWN SPOUT
D.T. DRAIN TILE
D.W. DISHWASHER
DWG(S). DRAWING(S)
DWR. DRAWER
(E) EXISTING
EA. EACH
E.C. ELECTRICAL CONTRACTOR
E.E. EACH END
E.F. EXHAUST FAN
E.J. EXPANSION JOINT
ELEC. ELECTRICAL
ELEV. ELEVATION
E.N. EDGE NAIL
ENCL. ENCLOSURE
EQUIV. EQUIVALENT
E.S. EACH SIDE
E.W. EACH WAY
E.W.C. ELECTRICAL WATER CLOSET
EXP. EXPANSION
EXP.B. EXPANSION BOLT
EXPO. EXPOSURE
EXT. EXTERIOR
F. FACE
F.A. FIRE ALARM
F.B. FACE BRICK
F.BD. FIRE BOARD
F.BELL FIRE BELL
F.B.O. FURNISHED BY OTHERS
F.D. FLOOR DRAIN
FDN. FOUNDATION
F.E. FIRE EXTINGUISHER
F.E.C. FIRE EXTINGUISHER CABINET
F.F. FINISH FLOOR
F.G. FINISH GRADE
FGL. FIBERGLASS
F.H. FIRE HYDRANT
FH.M.S. FLAT HEAD MACHINE SCREW
FIN. FINISH
FIXT. FIXTURE
F.J. FLOOR JOIST
F.L. FLOOR LINE
FLASH FLASHING
FLOUR FLUORESCENT
FLR. FLOOR
F.N. FACE NAIL
F.O.B. FACE OF BUILDING
F.O.C. FACE OF CONCRETE
F.O.F. FACE OF FINISH
F.O.M. FACE OF MASONRY
F.O.S. FACE OF STUD
F.R.T.W. FIRE RETARDANT TREATED WOOD
F.S.C. FIRE SUPPRESSION CONTRACTOR
F.S.E.C. FOOD SERVICE EQUIPMENT
CONTRACTOR
FTG. FOOTING
FUT. FUTURE
F.V.C. FIRE VAULT CABINET
GA. GAUGE
GALV. GALVANIZED
G.C. GENERAL CONTRACTOR
G.B. GRAB BAR
G.D. GARBAGE DISPOSAL
G.E. GRATE ELEVATION
G.I. GALVANIZED IRON
GL. GLASS
GLB. GLUE LAMINATED BEAM
GND. GROUND
GR. GRADE
G.S.M. GALVANIZED SHEET METAL
GYP.BD. GYPSUM BOARD
H.B. HOSE BIB
HC. HANDICAPPED
HDR. HEADER
HDWD. HARDWOOD
HDWE. HARDWARE
HGT. HEIGHT
H.M. HOLLOW METAL
HORIZ. HORIZONTAL
H.P. HIGH POINT
HR. HOUR
H.S.S. HOLLOW STRUCTURAL STEEL
HTG. HEATING
H.V.A.C. HEATING, VENTILATION & AIR
CONDITIONING
H.W. HOT WATER
I.D. INSIDE DIAMETER
INSUL. INSULATION
INT. INTERIOR
INV. INVERT
JAN. JANITOR
J.H. JOIST HANGER
JST. JOIST HANGER
JT. JOINT
KIT. KINTCHEN
LAB LABORATORY
LAM. LAMINATE
LAV. LAVATORY
L.B. LAG BOLT
L.H. LEFT HAND
L.L. LIVE LOAD
L.P. LOW POINT
LT. LIGHT
MAT. MATERIAL
MAX. MAXIMUM
M.B. MACHINE BOLT
M.C. MEDICINE CABINET
MECH. MECHANICAL
MED. MEDIUM
MEMB. MEMBRANE
M.E.P. MECHANICAL, ELECTRICAL,
PLUMBING
MFG. MANUFACTURER
MH. MANHOLE
MIN. MINIMUM
MIR. MIRROR
MISC. MISCELLANEOUS
M.O. MASONRY OPENING
MOD. MODULAR
MP.H. MOP HOLDER
MR. FRAMED MIRROR
M.R. MOISTURE RESISTANT
M.T. METAL THRESHOLD
MTD. MOUNTED
MTL. METAL
(N) NEW
N. NORTH
NAT. NATURAL
N.I.C. NOT IN CONTRACT
(NOT PART OF OSA APPROVAL)
NO. NUMBER
NOM. NOMINAL
NON/COM NON-COMBUSTIBLE
N.T.S. NOT TO SCALE
O/ OVER
O.A. OVERALL
OBS. OBSCURE
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
O.F. OVERFLOW
OFF. OFFICE
O.F.S. OUTSIDE FACE OF STUD
O.H.W.S. OVAL HEAD WOOD SCREW
OPP. OPPOSITE
P. PAINT
P.C. PLUMBING CONTRACTOR
P.C.F. POUNDS PER CUBIC FOOT
P.E.N. PANEL EDGE NAILING
PERF. PERFORATED
PL. PLATE
P.LAM PLASTIC LAMINATE
PLAS. PLASTER
P.L.F. POUNDS PER LINEAR FOOT
PLYWD. PLYWOOD
P.M.F. PRESSED METAL FRAME
PR. PAIR
PROP. PROPERTY
P.S.F. POUNDS PER SQUARE FOOT
P.S.I. POUNDS PER SQUARE INCH
P.STA. PULL STATION
PTD. PAINTED
P.T.D. PAPER TOWEL DISPENSER
PT. POINT
P.T.D.F. PRESSURE TREATED DOUGLAS
FIR
PTN. PARTITION
P.T.R. PAPER TOWEL RECEPTACLE
P.V.C. POLYVINYL-CHLORIDE
Q.T. QUARRY TILE
RAD. RADIUS
R.B. RUBBER BASE
R.C.P. REFLECTED CEILING PLAN
R.D. ROOF DRAIN
RDWD. REDWOOD
REF. REFERENCE
REFR. REFRIGERATOR
REINF. REINFORCING
REQD. REQUIRED
RESIL. RESILIENT
R.H. ROOF HATCH
R.HK. ROBE HOOK
R.H.M.S. ROUND HEAD METAL SCREW
R.H.W.S. ROUND HEAD WOOD SCREW
RM. ROOM
R.O. ROUGH OPENING
R.W.L. RAIN WATER LEADER
S. SOUTH
S.A.B. SOUND ATTENUATION BATT
S.A.D. SEE ARCHITECTURAL DRAWINGS
S.A.F.F. SELF ADHERED FLEXIBLE FLASHING
S.A.S.M. SELF ADHERED FLEXIBLE MEMBRANE
S.BLKG. SOLID BLOCKING
SCWD. SOLID CORE WOOD DOOR
S.C.D. SEE CIVIL DRAWINGS
S.D. STORM DRAIN
S.DISP. SOAP DISPENSER
SEAL. SEALANT
SECT. SECTION
S.E.D. SEE ELECTRICAL DRAWINGS
SHR. SHOWER
SHT. SHEET
SHTG. SHEATHING
SIM. SIMILAR
SL. SLIDING
S.L.D. SEE LANDSCAPE DRAWINGS
S.M.D. SEE MECHANICAL DRAWINGS
S.N.D. SANITARY NAPKIN DISPOSAL
S.N.V. SANITARY NAPKIN DISPENSER
S.P. SOUNDPROOF
SPEC. SPECIFICATION
SQ. SQUARE
SQ.FT. SQUARE FOOT (FEET)
S.S. SANITARY SEWER
S.S.D. SEE STRUCTURAL DRAWINGS
STA. STATION
STD. STANDARD
STL. STEEL
S.STL. STAINLESS STEEL
STO. STORAGE
STRUC. STRUCTRUAL
SUSP. SUSPENDED
T.B. TACKBOARD
T&B. TOP AND BOTTOM
TEL. TELEPHONE
TEMP. TEMPERED
TER. TERRAZZO
T&G. TOUNGE AND GROOVE
THK. THICK
T.J. TOOL JOINT
T.N. TOE NAIL
T.O.C. TOP OF CURB
T.O.P TOP OF PAVEMENT
T.O.PL. TOP OF PLATE
T.O.S. TOP OF SEAT
T.O.W. TOP OF WALL
T.P.D. TOILET PAPER DISPENSER
T.S. TUBE STEEL
T.V. TELEVISION
TYP. TYPICAL
UNF. UNFINISHED
U.N.O. UNLESS NOTED OTHERWISE
UR. URINAL
U/S. UNDERSIDE
V.C.T. VINYL COMPOSITION TILE
VERT. VERTICAL
VEST. VESTIBULE
V.G. VERTICAL GRAIN
V.I.F. VERIFY IN FIELD
V.T. VINYL TILE
V.T.R. VENT TO ROOF
V.W.C. VINYL WALL COVERING
(VC) V.A. FURNISHED / CONTRACTOR
INSTALLED
(VV) V.A. FURNISHED AND INSTALLED
W. WEST
W/ WITH
W/IN WITHIN
W.C. WATER CLOSET
WD. WOOD
WDW. WINDOW
W.F. WATER COOLER
W.H. WATER HEATER
W/O WITHOUT
W.P. WATER PROOF
W.R. WATER RESISTANT
WT. WEIGHT
W.W.F. WELDED WIRE FABRIC
YD. YARD
EXISTING GRID HEAD0
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /A n n A rb o r V
A
E m r P w r
C e n tr a l C h ill e r
P la n t/ F
F E
A n n
A rb o r
E m e rg e n c y P o w e r_
B rv t
/1
/2
:2
:3
P
M
GI001
ABBREVIATIONS AND GENERAL
DETAILS
8/19/2022 PH TD
EMERGENCY POWER CENTRAL
CHILLER PLANT
506-21-110
2215 FULLER RD, ANN ARBOR, MI
BID DOCUMENTS
VA ANN ARBOR
HEALTHCARE
SYSTEM Approved: Veteran's Affairs Medical Center
UP
EX EXIT
EXIT SIGN
FIRE EXTINGUISHER
PATH OF TRAVEL
2 HOUR FIRE BARRIER
L I F E S A F E T Y L E G E N D
G E N E R A L L I F E S A F E T Y N O T E S
A. SEE NFPA 101 CODE REVIEW ON SHEET GI003
B. PER NFPA 110 - 7.2.1.1 THE EMERGENCY POWER SUPPLY ROOM SHALL BE SEPARATED FROM THE REST OF THE BUILDING BY
CONSTRUCTION WITH A 2-HOUR FIRE RESISTANCE RATING.
C. 4" AND 8" ACOUSTIC BLOCK 2 HOUR RATING BASED ON CALCULATED PER EQUIVALENT THICKNESS OF MASONRY: IBC 721.3; NCMA
TEK 7-4 FIRE RESISTANCE RATINGS OF CONCRETE MASONRY ASSEMBLIES
D. CONTRACTOR TO PROVIDE SUBMITTAL SHOWING FIREPROOFING THICKNESSES REQUIRED WITH UL RATINGS, STEEL SIZES AND
SPRAY-APPLIED FIRE RESISTIVE MATERIALS PROVIDED.
E. VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL - LIFE SAFETY. REQUIREMENTS INCLUDE BUT ARE NOT LIMITED TO
INCREASED MASONRY REINFORCING, CONNECTIONS, AND BLAST RESISTANT OPENINGS.
D
5.5
6.5
5.7
7.2
FE
6.4
6.6
PATH OF EGRESS - 35' < 75'
P A
T H
O F
E G
R E
S S
<7
5'
P A
T H
O F
E G
R E
S S
5'
90 MINUTE DOOR
2 HOUR AREA REQUIRED BETWEEN EXISTING BUILDING AND
GENERATOR BUILDING - ALL MASONRY IS RATED BASED ON THICKNESS
FIRE RATING
4' - 0" MIN
FIRE RATING
4' - 0" MIN
D
IA
G O
N A
L
- 5
4'
EX
EX
UL X772 FIREPROOFING
ON STEEL COLUMNS FROM 8'
TO STRUCTURE ABOVE
1 9/16" SHOWN ON W8X31 COLUMNS
4" CMU EQUIVALENT TO
2HR FIRE PROTECTION
TO 8'
CONCRETE ROOF DECK
SEE STRUCTURAL
NORMAL WEIGHT CONCRETE
2 3/4" MIN WITH 6X6 W2.0X2.0 WWF
PER UL G705
STEEL BEAM SEE STRUCTURAL -
W8X28 MIN. SIZE PER UL G705
SPRAY ON FIREPROOFING
AT A MINIMUM THICKNESS
OF 11/16" SHOWN PER
UL G705 2 HOUR
ROOF ASSEMBLY ABOVE
NOT SHOWN
B.3 B.7 C
7.5
8.5
PATH OF EGRESS - 120' < 250'
PATH OF EGRESS - 120' < 250'
EX
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /A n n A rb o r V
A
E m r P w r
C e n tr a l C h ill e r
P la n t/ F
F E
A n n
A rb o r
E m e rg e n c y P o w e r_
B rv t
/1
/2
:2
:3
P
M
GI002
LIFE SAFETY PLAN
8/19/2022 PH TD
EMERGENCY POWER CENTRAL
CHILLER PLANT
506-21-110
2215 FULLER RD, ANN ARBOR, MI
BID DOCUMENTS
VA ANN ARBOR
HEALTHCARE
SYSTEM Approved: Veteran's Affairs Medical Center
N
1/4" = 1'-0"
LIFE SAFETY PLAN - GENERATOR ROOM
NFPA 10 (2018) – Installation of Portable Fire Extinguishers
5.4.1.3 Extra Hazard
Table 6.2.1.1 Class A - Extra (High) Hazard Occupancy
Min rated extinguisher - 4-A Max floor area for extinguisher per unit of A - 1,000 square feet Max floor area for extinguisher - 11,250 ft Max travel distance - 75 ft
80:B:C required per Mechanical Code Table 6.3.1.1 80-B 50' max. travel distance
All extinguishers shown are 4-A:80B:C minimum
3" = 1'-0"
FIRE RATING DETAILS
N
1/4" = 1'-0"
LIFE SAFETY PLAN - MEZZANINE
NFPA 101 (2021)
6.2 Hazard of Contents.
6.2.1 General.
6.2.1.1 For the purpose of this Code, the hazard of contents shall be the relative danger of the start and spread of fire, the danger of smoke or gases generated, and the danger of explosion or other occurrence potentially endangering the lives and safety of the occupants of the building or structure.
6.2.1.2 Hazard of contents shall be classified by the registered design professional (RDP) or owner and submitted to the authority having jurisdiction for review and approval on the basis of the character of the contents and the processes or operations conducted in the building or structure.
6.2.1.3 For the purpose of this Code, where different degrees of hazard of contents exist in different parts of a building or structure, the most hazardous shall govern the classification, unless hazardous areas are separated or protected as specified in Section 8.7 and the applicable sections of Chapters 11 through 43.
6.2.2 Classification of Hazard of Contents.
6.2.2.4 High hazard contents shall be classified as those that are likely to burn with extreme rapidity or from which explosions are likely. (For means of egress requirements, see Section 7.11.)
7.2.1.5 Locks and Latches.
7.2.1.5.1 Door leaves shall be arranged to be opened readily from the egress side whenever the building is occupied.
7.2.1.5.2 Locks, if provided, shall not require the use of a key, a tool, or special knowledge or effort for operation from the egress side.
All exterior doors will have panic hardware.
7.2.1.5.3 Latch-Release Devices.
All locks, latches, and all other fastening devices on a door leaf shall be provided with a releasing device that has an obvious method of operation and that is readily operated under all lighting conditions.
7.2.1.5.3.1 The releasing mechanism for locks and latches shall be located as follows:
(1) Not less than 34 in. (865 mm) above the finished floor for other than existing installations
(2) Not more than 48 in. (1220 mm) above the finished floor
7.2.1.5.3.3 The releasing mechanism for new installations shall be capable of being operated with one hand and shall not require tight grasping, tight pinching, or twisting of the wrist to operate.
7.2.1.5.3.6 Existing security devices permitted by 7.2.1.5.3.4, other than automatic latching devices, shall be located not more than 60 in. (1525 mm) above the finished floor.
7.7 Discharge from Exits.
7.7.1 Exits shall terminate directly, at a public way or at an exterior exit discharge, unless otherwise provided in 7.7.1.3 through 7.7.1.5.
7.7.3 Arrangement and Marking of Exit Discharge.
7.7.3.1 Where more than one exit discharge is required, exit discharges shall be arranged to meet the remoteness criteria of 7.5.1.3.
7.8.1.3 The floors and other walking surfaces within an exit and within the portions of the exit access and exit discharge designated in 7.8.1.1 shall be illuminated as follows:
(1) During conditions of stair use, the minimum illumination for new stairs shall be at least 10 foot-candles (108 lux), measured at the walking surfaces.
(2) The minimum illumination for floors and other walking surfaces, other than new stairs during conditions of stair use, shall be to values of at least 1 foot-candle (10.8 lux), measured at the floor.
(3) In assembly occupancies, the illumination of the walking surfaces of exit access shall be at least 0.2 foot-candle (2.2 lux) during periods of performances or projections involving directed light.
(4)* The minimum illumination requirements shall not apply where operations or processes require low lighting levels.
7.8.1.4* Required illumination shall be arranged so that the failure of any single lighting unit does not result in an illumination level of less than 0.2 foot-candle (2.2 lux) in any designated area.
7.11 Special Provisions for Occupancies with High-Hazard Contents. See Section 6.2.
7.11.1* Where the contents are classified as high-hazard, exits shall be provided and arranged to allow all occupants to escape from the building or structure, or from the hazardous area thereof, to the outside or to a place of safety with a travel distance of not more than 75 ft (23 m), measured as required in 7.6.1, unless otherwise provided in 7.11.2.
See plan. All travel distances are less than 75 ft.
Existing building travel distances are 250 ft. max. per as built construction documents
7.11.2 The requirement of 7.11.1 shall not apply to storage occupancies as otherwise provided in Chapter 42.
7.11.3 Egress capacity for high-hazard contents areas shall be based on 0.7 in./person (18 mm/person) for stairs or 0.4 in./person (10 mm/person) for level components and ramps in accordance with 7.3.3.1.
7.11.4 Not less than two means of egress shall be provided from each building or hazardous area thereof, unless all of the following criteria are met:
(1) Rooms or spaces do not exceed 200 ft2 (18.6 m2).
(2) Rooms or spaces have an occupant load not exceeding three persons.
(3) Rooms or spaces have a travel distance to the room door not exceeding 25 ft (7620 mm).
All spaces have two means of egress
7.11.5 Means of egress, for rooms or spaces other than those that meet the criteria of 7.11.4(1) through 7.11.4(3), shall be arranged so that there are no dead ends in corridors.
7.11.6 Doors serving high-hazard content areas shall swing in the direction of egress travel.
See plan - doors swing out - in direction of travel.
7.11.7 Doors serving high-hazard contents areas with occupant loads in excess of five shall be permitted to be provided with a latch or lock only if the latch or lock is panic hardware or fire exit hardware complying with 7.2.1.7.
All exit doors have panic hardware.
Chapter 40 Industrial Occupancies (edit to 2021)
40.1 General Requirements.
40.1.1 Application.
40.1.1.1 The requirements of this chapter shall apply to both new and existing industrial occupancies.
40.1.1.2 Administration. The provisions of Chapter 1, Administration, shall apply.
40.1.1.3 General. The provisions of Chapter 4, General, shall apply.
40.1.1.5 Incidental high hazard operations protected in accordance with Section 8.7 and 40.3.2 in occupancies containing low or ordinary hazard contents shall not be the basis for high hazard industrial occupancy classification.
40.1.2.1.3 High-Hazard Industrial Occupancy. High-hazard industrial occupancies shall include all of the following:
(2) New industrial occupancies that conduct industrial operations that use, process, store, or handle high-hazard contents or hazardous materials in excess of the maximum allowable quantities (MAQ) as permitted by the fire code.
(3) Industrial occupancies in which incidental high-hazard operations in low- or ordinary-hazard occupancies that are protected in accordance with Section 8.7 and 40.3.2 are not required to be the basis for overall occupancy classification.
40.1.4 Definitions.
40.1.4.1 General. For definitions, see Chapter 3, Definitions.
40.1.4.2 Special Definitions. Special terms applicable to this chapter are defined in Chapter 3.
40.1.5 Classification of Hazard of Contents. Classification of hazard of contents shall be in accordance with Section 6.2.
40.1.6 Minimum Construction Requirements. (Reserved.)
40.1.7 Occupant Load. The occupant load, in number of persons for whom means of egress and other provisions are required, shall be determined on the basis of the occupant load factors of Table 7.3.1.2 that are characteristic of the use of the space, or shall be determined as the maximum probable population of the space under consideration, whichever is greater.
7.3.1.2
Industrial Use
General and high hazard industrial:
100 sq ft per person
Generator area 1,265 SF / 100 = 13 occupants
40.2 Means of Egress Requirements.
40.2.1 General.
40.2.1.1 Each required means of egress shall be in accordance with the applicable portions of Chapter 7.
40.2.1.2 Normally unoccupied utility chases that are secured from unauthorized access and are used exclusively for routing of electrical, mechanical, or plumbing equipment shall not be required to comply with the provisions of Chapter 7.
40.2.2 Means of Egress Components.
40.2.2.1 General. Components of means of egress shall be limited to the types described in 40.2.2.2 through 40.2.2.13.
40.2.2.2 Doors.
40.2.2.2.1 Doors complying with 7.2.1 shall be permitted.
40.2.2.2.4 Locks in accordance with 7.2.1.6.3 shall be permitted.
40.2.3 Capacity of Means of Egress. Capacity of means of egress shall comply with either 40.2.3.1 or 40.2.3.2.
40.2.3.1 The capacity of means of egress shall be in accordance with Section 7.3.
40.2.3.2 In industrial occupancies, means of egress shall be sized to accommodate the occupant load as determined in accordance with 40.1.7; spaces not subject to human occupancy because of the presence of machinery or equipment shall not be included in the computation.
40.2.4 Number of Means of Egress. See also Section 7.4.
40.2.4.1 The number of means of egress shall comply with either 40.2.4.1.1 or 40.2.4.1.2.
40.2.4.3 Areas with high hazard contents shall comply with Section 7.11.
40.2.5 Arrangement of Means of Egress.
40.2.5.1 General. Means of egress, arranged in accordance with Section 7.5, shall not exceed that provided by Table 40.2.5.1.
Table 40.2.6.1 Maximum Travel Distance to Exits
High Hazard Industrial Occupancy
Protected throughout by an approved, supervised automatic sprinkler system in accordance with 9.7.1.1 (1).
75 feet
NFPA 37 (2021)
4.1 Engine Location
4.1.1 General Requirements
4.1.1.1 Engines shall be situated so that they are readily accessible for maintenance, repair, and fire fighting.
Provided
4.1.1.2 The air supply shall be designed to meet at least the minimum requirements for combustion, cooling, and ventilation and to prevent flue gas products from being drawn from stacks or flues of boilers or other combustion devices.
4.1.1.3 Combustible materials shall not be stored in rooms or enclosures housing engines, other than those combustible materials required for day-to-day operations/maintenance. Such materials shall be stored properly.
4.1.1.5 Combustion air filters mounted directly on engines or turbines shall be listed in accordance with ANSI/UL 900, Standard for Air Filter Units.
4.1.2 Engines Located in Structures.
4.1.2.1 Engine Rooms.
4.1.2.1.1 Engine rooms located within structures shall have interior walls, floors, and ceilings of at least 1-hour fire resistance rating, unless otherwise permitted by 4.1.2.1.2.
4.1.2.1.2 The ceiling of rooms located on the top floor of a structure shall be permitted to be noncombustible or protected with an automatic fire suppression system.
4.1.2.1.3* Engine rooms shall have ventilation that is adequate to prevent a hazardous accumulation of vapors, gases, or heat, both when the engine is operating and when it is shut down.
4.1.2.1.4 Engine rooms attached to structures shall comply with 4.1.2.2.1 and 4.1.2.2.3 except that the common wall shall have a fire resistance rating of at least 1 hour.
2-hr provided per Electrical Code as noted other sections.
4.1.2.1.5 Openings from an engine room to other sections of the structure shall be provided with automatic or self-closing fire doors or dampers corresponding to the rating of the walls in which they are located.
Door at roof line is above fire wall/fire rated roof.
4.6 General Installation Requirements.
Engines and their appurtenances shall be installed in accordance with the following:
(1) Applicable NFPA codes and standards
(2) Industry standards
(3) User requirements
(4) Manufacturer's installation instructions
(5) Applicable local building codes with respect to wind and seismic design requirements.
6.1 Design and Construction of Liquid Fuel Tanks.
Fuel tanks shall meet one of the following criteria:
(1) Constructed in accordance with the applicable requirements of NFPA 30
(2) Listed as “Steel-Inside Tanks for Oil Burner Fuel”
(3) Listed as “Underground Tanks for Flammable Liquids”
(4) Listed as “Aboveground Tanks for Flammable Liquids”
(5) Constructed in accordance with API STD 650, Welded Tanks for Oil Storage
(6) Constructed in accordance with API STD 620, Design and Construction of Large Welded Low-Pressure Storage Tanks
Exception: Fuel tanks mounted on the engine by the manufacturer for gravity feed to a carburetor.
6.1.1 Metallic tanks shall be liquidtight with welded or brazed joints.
6.3 Installation Criteria for Fuel Tanks Containing Liquid Fuels Other Than Class I Fuels.
6.3.2 Fuel Tank Inside Structures
6.3.2.1 Fuel tanks inside structures shall be securely mounted on noncombustible supports.
6.3.2.2* Fuel tanks not in a room by themselves shall not exceed 2500 L (660 gal) capacity. Fuel tanks larger than 2500 L (660 gal) capacity shall be enclosed in a room in accordance with 6.3.5 or 6.3.6. Not more than one 2500 L (660 gal) capacity tank, or two or more tanks with an aggregate capacity of not more than 2500 L (660 gal), shall be connected to any one engine.
Exception: Fuel tanks of any size shall be permitted within engine rooms or mechanical spaces, provided the engine or mechanical room is designed using recognized engineering practices with suitable fire detection, fire suppression, and containment means to prevent the spread of fire beyond the room of origin.
6.3.2.3 The aggregate capacity of all fuel tanks in a structure shall not exceed 5000 L (1320 gal) unless that portion exceeding 5000 L (1320 gal) is enclosed in a room in accordance with 6.3.5 or 6.3.6.
Exception: Fuel tanks of any size shall be permitted within engine rooms or mechanical spaces, provided the engine or mechanical room is designed using recognized engineering practices with suitable fire detection, fire suppression, and containment means to prevent the spread of fire beyond the room of origin.
6.3.2.4 Fuel tanks within structures shall be provided with spill containment consisting of either a wall, a curb, or a dike having a capacity at least equal to that of the largest tank enclosed.
Exception No. 1: A spill containment system of lesser capacity equipped with an overflow or drainage system that is adequate in size and location to convey any spillage of fuel to a tank (inside or outside) or to a safe area outside the structure.
Exception No. 2: Listed or approved secondary containment tanks shall be considered as meeting this requirement provided piping between fuel tank(s) and engine(s) is double-wall and protected from physical damage.
6.3.6.5 Ventilation.
6.3.6.5.1 Ventilation for tank rooms shall be sufficient to maintain the concentration of vapors within the room at or below 25 percent of the LFL of the fuel used.
6.3.6.5.2 Ventilation shall be accomplished by mechanical or natural means and shall discharge to a safe location outside the building, without recirculation of the exhaust air.
6.3.6.5.3 Provision shall be made for introduction of make-up air in such a manner as to avoid short-circuiting the ventilation. That introduction of make-up air shall be arranged to include all floor areas or pits where flammable vapors can collect.
6.5 Fuel Flow Control.
6.5.1 Liquid fuel supply systems, including drains from carburetors, shall be designed and installed to minimize, as far as practicable, the accidental discharge of fuel into the engine room or structure.
6.5.2 Alarms, float-controlled valves, or mechanical or remote-reading level gauges or protected sight glass gauges shall be installed to aid personnel in properly operating the fuel system.
6.5.3 Stationary-powered fuel pumps supplying fuel tanks shall have “stop” controls sensitive to a tank's high liquid level.
6.5.4 Fuel tanks supplied by pumps shall be provided with all of the following:
(1) An overflow line
(2) A high-level alarm
(3) A high-level automatic shutoff
6.5.4.1 The overflow line shall be continuous piping, without valves or traps, back to the source tank or to a collection system.
6.5.4.2 The capacity of the overflow line shall exceed the delivery capacity of the supply lines to the fuel tank.
6.5.5 Overflows, vents, fuel piping, and fuel tanks shall not be located at or near engine air intake, exhaust piping, mufflers, or filters.
6.5.6 Pressure relief valves and relief piping shall be provided where the potential exists to overpressurize the fuel system piping.
6.5.6.1 Relief piping shall be routed, without valves or traps, back to the source tank or to a collection system
6.6 Filling.
6.6.3 Piping for fuel tanks, other than engine-mounted tanks, shall be in accordance with the provisions of 6.6.3.1 through 6.6.3.3, except as provided for in 6.6.3.4.
6.6.3.1 Piping for fuel tanks shall meet the applicable requirements of Chapters 21 and 27 of NFPA 30.
6.6.3.2 Tanks shall be filled by a closed piping system.
6.6.3.3 The fill pipe for each tank shall be provided on an exterior wall of the room or structure enclosing the tank at a point at least 600 mm (24 in.) from any building opening at the same or lower level.
6.6.3.4 A fill pipe terminating in accordance with 6.6.3.3 shall not be required for tanks that are filled manually at the fill connection on the tank, provided that the tank and its fill connection are located within the spill containment required by 6.3.2.4, 6.3.5.3, or 6.3.6.3 and the filling operation is constantly attended.
6.7 Vent Piping
6.7.1 Vent piping shall be installed in accordance with Chapter 27 of NFPA 30.
6.7.1.1 Vent pipe shall terminate outside the building at a point at least 24 in. from any building opening at the same or lower level.
6.8 Fuel Piping, Valves, and Fittings.
6.8.1 Piping shall be in accordance with Chapter 27 of NFPA 30, except that piping shall be steel or other metal and the provisions of 6.8.2 shall apply.
6.8.2 Piping systems shall be supported and protected against physical damage and excessive stress in accordance with MSS SP-58, Pipe Hangers and Supports - Materials, Designs, Manufacture, Selection, Application and Installation.
6.8.2.1 Approve metallic or nonmetallic flexible connectors shall be permitted to protect the piping system against damage caused by settlement, vibration, expansion, contraction, or corrosion.
6.8.3 Valves shall be provided to control the flow of liquid fuel in normal operation and to shut off the flow of fuel in the event of a pipe break.
7.4 Reciprocating Engines.
7.4.1 On engines where crankcase explosion can be a hazard, explosion venting shall be provided or means shall be used to maintain a nonflammable atmosphere in the crankcase.
7.4.2 Auxiliary reservoir oil supply chambers, if used, shall be vented through either separate vents or a common venting system.
7.4.3 Engines designed to operate with a negative pressure in the crankcase and equipped with a separate lubricating oil sump shall be provided with check valves in the venting system from the sump.
7.5 Safeguards for Gauging Devices. Sight gauges or feeds for lubricating oil shall be protected against physical damage to prevent the escape of oil.
8.1 Design and Construction
8.1.1 Engine exhaust system shall be designed and constructed such that the system can withstand the anticipated exhaust gas temperatures.
8.1.2 Exhaust systems shall be designed and constructed to withstand the intended service.
8.1.2.1 Exhaust systems shall consist of metal, masonry, or factory-built chimneys where they pass through a floor, ceiling, attic, or concealed space.
8.1.4 Exhaust system shall be designed and constructed to withstand forces caused by the ignition of unburned fuel or shall have provisions to relieve those forces without damaging the exhaust system.
8.1.5 Low points in exhaust system shall have drains.
8.2 Installations.
8.2.1 Exhaust systems shall be connected to the engine to prevent the escape of sparks, flame, or flue gas within the structure.
8.2.2 Engine exhaust systems shall have one or more flexible connectors if necessary to minimize the risk of a leak in the engine exhaust system because of engine vibration or thermal expansion.
8.2.3 Exhaust System Termination
8.2.3.1 Exhaust system shall terminate outside the structure to a point where hot gases, sparks, or products of combustion will discharge to a safe location.
8.2.3.2 Exhaust system terminations shall not be directed toward combustible material or structures or into atmospheres containing flammable gases, flammable vapors, or combustible dusts.
8.3 Clearance from Exhaust Systems with Exhaust Gas Temperatures of Less Than 760°C (1400°F).
Exhaust systems with exhaust gas temperatures of 760°C (1400°F) or less shall comply with NFPA 211.
8.3.1 Unlisted exhaust pipes and ducts shall have clearances of at least 457 mm (18 in.) to adjacent combustible materials, except as specified in 8.3.2 and 8.3.3. The clearance shall be measured from the outside surface of the exhaust pipe or duct and not from any insulation that might be present.
8.3.2 Unlisted exhaust pipes and ducts passing directly through combustible roofs shall be guarded at the point of passage by ventilated metal thimbles that extend not less than 229 mm (9 in.) on each side (above and below) of roof construction and are at least 229 mm (9 in.) in diameter larger than the exhaust pipe or duct.
11.3 Fire Detection and Alarm Systems
11.3.1 Automatic fire detection and alarm systems, where provided, shall comply with NFPA 72.
11.3.2 The electrical installation and required rating of system components shall comply with NFPA 70.
11.3.3 Automatic fuel stop valves, where required by other sections of this standard, shall be arranged to close upon activation of the fire detection system within the fire alarm zone that covers the engine installation, including auxiliary equipment.
11.3.3.1 Where written procedures are in place to direct operator actions upon activation of the detection system, automatic fuel stop valves for engines that are used for emergency use or for engines that are constantly attended shall be permitted to remain open.
11.3.4 Mechanical ventilation systems, where provided, shall be arranged to shut down upon activation of the fire detection system within the engine enclosure.
11.3.4.1 Where procedures are in place to direct operator actions, mechanical ventilation systems for engines that are used for emergency use or for engines that are constantly attended shall be permitted to remain in operation.
11.4.2 General
11.4.2.1 Automatic fuel stop valves, where required by other sections of this standard, shall be arranged to close upon activation of the fire suppression system that covers the engine installation, including auxiliary equipment.
11.4.2.1.1 Where procedures are in place to direct operator actions upon activation of the fire suppression system that covers the engine installation, automatic fuel stop valves for engines that are for emergency use or for engines that are constantly attended shall be permitted to remain open.
11.4.2.2 Mechanical ventilation systems, where provided, shall be arranged to shut down upon activation of the fire suppression system within the engine enclosure.
11.4.2.3 Where procedures are in place to direct operator actions upon activation of the fire suppression system within the engine installation, mechanical ventilation systems for engines that are for emergency use or engines that are constantly attended shall be permitted to remain in operation.
11.4.2.4 The positioning of the fire suppression systems and equipment shall be such that maintenance access to the engine is maintained.
11.4.5 Automatic Sprinkler and Water Spray Systems.
11.4.5.1 Automatic sprinkler systems shall be designed to provide a density of 12.2 mm/min (0.3 gpm/ft2) over the most remote 230 m2 (2500 ft2).
11.4.5.1.1 Sprinklers and spray nozzles shall be spaced at a 9 m2 (100 ft2) maximum area of coverage per sprinkler or spray nozzle.
11.4.5.1.2 Sprinkler and water spray system coverage shall be provided to all areas within the enclosure located within 6 m (20 ft) of the following:
1. The engine.
2. The lubricating oil system.
3. The fuel system.
11.4.5.2 Sprinklers and water spray nozzles shall not be directed at engine components that are susceptible to thermal shock or deformation.
A6.2.2 Fuel tanks shall be installed in accordance with NFPA 30.
A.11.1 The fire risk evaluation should include, but not be limited to, the following:
(1) Characteristics of the engine
(2) Layout of the engine installation, including engine auxiliary equipment
(3) Adjacent exposures, including structures, operations, and other engine installations
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /A n n A rb o r V
A
E m r P w r
C e n tr a l C h ill e r
P la n t/ F
F E
A n n
A rb o r
E m e rg e n c y P o w e r_
B rv t
/1
/2
:2
:4
P
M
GI003
LIFE SAFETY CODE REVIEW
8/19/2022 PH PH
EMERGENCY POWER CENTRAL
CHILLER PLANT
506-21-110
2215 FULLER RD, ANN ARBOR, MI
BID DOCUMENTS
VA ANN ARBOR
HEALTHCARE
SYSTEM Approved: Veteran's Affairs Medical Center
VF100
EXISTING
SURVEY
N
0 20'10'
C:\Users\dunnt\FFE Inc\Ann Arbor VA - Emrg Pwr Central Chiller Plant - Documents\04 External\02 KZF\01 Transmitted to KZF\FFE_AnnArbor-EmergencyPower_B32(2022)-FFELogo-Titleblock-2582110.jpg
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
F:
\P ro je ct s\
\0
5_ D el iv er ab le s\
D ra w in gs \8
0-
VF
0.
dw gF
:\P ro je ct s\
\0 5_
D el iv er ab le s\ D ra w in gs
\8
0-
VF
0.
dw g 3/
/2
4:
:3
PM
08/19/2022 MAM SCR
EMERGENCY POWER CENTRAL
CHILLER PLANT
506-21-110
2215 FULLER RD, ANN ARBOR, MI
BID DOCUMENTS
VA ANN ARBOR
HEALTHCARE
SYSTEM Approved: Veteran's Affairs Medical Center
No. Revisions: Date:
BID DOCUMENTS 08/19/2022
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text St.MH
AutoCAD SHX Text St.MH
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text These standard symbols will
AutoCAD SHX Text be found in the drawing.
AutoCAD SHX Text
RIP RAP
AutoCAD SHX Text
OXYGEN LINE UNDERGROUND
AutoCAD SHX Text
BUILDING
AutoCAD SHX Text
FENCE
AutoCAD SHX Text
GAS LINE
AutoCAD SHX Text
TREE - CONIFER
AutoCAD SHX Text
BOLLARD
AutoCAD SHX Text
CATCH BASIN
AutoCAD SHX Text
CATCH BASIN
AutoCAD SHX Text C.O.
AutoCAD SHX Text
CLEANOUT
AutoCAD SHX Text E
AutoCAD SHX Text
ELECTRIC BOX
AutoCAD SHX Text
ELEC
AutoCAD SHX Text
MH
AutoCAD SHX Text
ELECTRIC MANHOLE
AutoCAD SHX Text H
AutoCAD SHX Text Y
AutoCAD SHX Text D
AutoCAD SHX Text
FIRE HYDRANT
AutoCAD SHX Text
GV
AutoCAD SHX Text
GAS VALVE
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text
LIGHT POLE
AutoCAD SHX Text
MANHOLE
AutoCAD SHX Text
PIV
AutoCAD SHX Text
FIRE DEPT. INDICATOR POST
AutoCAD SHX Text
DOUBLE GUTTER INLET
AutoCAD SHX Text
SMH
AutoCAD SHX Text
SANITARY MANHOLE
AutoCAD SHX Text St.MH
AutoCAD SHX Text
STORM MANHOLE
AutoCAD SHX Text
TELEPHONE BOX
AutoCAD SHX Text
WV
AutoCAD SHX Text
WATER VALVE
AutoCAD SHX Text
ELECTRIC LINE UNDERGROUND
AutoCAD SHX Text
WATER LINE
AutoCAD SHX Text
TREE - DECIDUOUS
AutoCAD SHX Text
TELEPHONE LINE UNDERGROUND
AutoCAD SHX Text
SANITARY LINE
AutoCAD SHX Text
STORM LINE
AutoCAD SHX Text
GRAVEL
AutoCAD SHX Text
WALL
AutoCAD SHX Text
ASPHALT
AutoCAD SHX Text
SIGN
Fuller Court
C-100
CONTRACTOR
LAYDOWN
N
0 20'10'
DRAWING NOTES
LEGEND
GENERAL NOTES
A. CONTRACTOR DAMAGE TO LANDSCAPING SHALL BE
RESTORED TO THE SATISFACTION OF THE COR AT
NO COST TO THE OWNER.
B. CONTRACTOR LAYDOWN AREA PROVIDED FOR
WORK TO BE PERFORMED. UPON AWARD,
CONTRACTOR TO SUBMIT LAYDOWN, STOCKPILE,
CONTRACTOR PARKING, AND EQUIPMENT STORAGE
DETAILS FOR COORDINATION WITH THE COR
C01 LANDSCAPING TO BE PROTECTED, REFER TO NOTE A.
C02 CONTRACTOR LAYDOWN AREA ENTRANCE
CONTRACTOR FENCE PER SPECIFICATION 01 00 00
HAUL ROUTE
C02
C02
C02
CO
NT
RA
CT
OR
LA
YD
OW
N
AR
EA
C:\Users\dunnt\FFE Inc\Ann Arbor VA - Emrg Pwr Central Chiller Plant - Documents\04 External\02 KZF\01 Transmitted to KZF\FFE_AnnArbor-EmergencyPower_B32(2022)-FFELogo-Titleblock-2582110.jpg
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
F:
\P ro je ct s\
\0
5_ D el iv er ab le s\
D ra w in gs \8
0- C
-1
.d w gF :\P ro je ct s\
\0
5_ D el iv er ab le s\
D ra w in gs \8
0- C
-1
.d w g 3/
/2
4:
:4
PM
08/19/2022 MAM SCR
EMERGENCY POWER CENTRAL
CHILLER PLANT
506-21-110
2215 FULLER RD, ANN ARBOR, MI
BID DOCUMENTS
VA ANN ARBOR
HEALTHCARE
SYSTEM Approved: Veteran's Affairs Medical Center
No. Revisions: Date:
BID DOCUMENTS 08/19/2022
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text
GV
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text
SMH
AutoCAD SHX Text St.MH
St.MH
CD100
DEMOLITION
PLAN
N
0 20'10'
DRAWING NOTES
LEGEND
GENERAL NOTES
A. PROTECT UTILITIES TO REMAIN
B. ALL EXISTING UTILITIES ARE TO REMAIN IN SERVICE
FOR THE DURATION OF CONSTRUCTION.
C. ALL DEMOLITION TO BE COMPLETED IN ACCORDANCE
WITH LOCAL REGULATIONS WITHIN THE LIMITS OF
PROPOSED CONSTRUCTION UNLESS OTHERWISE
NOTED.
D. CONTRACTOR TO VERIFY LOCATION OF
UNDERGROUND UTILITIES PRIOR TO CONSTRUCTION.
E. CONTRACTOR TO REMOVE ALL EXTRA WORK SPOILS
FROM SITE. DISPOSAL OF SPOILS AT APPROPRIATE
LOCATION SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
F. ROOF DRAIN CONNECTIONS TO BE…