Project_11567_Bay_Area_Drawings_8-13-24.pdf
PDF 9 MB Posted
- Solicitation number
- 0000032849
- Issued by
- Sonoma County, California
About this file
This document is a set of architectural and engineering drawings for an EVSE (Electric Vehicle Supply Equipment) Level II project located at 845 Casa Grande Rd., Petaluma, CA 94954. The project is being managed by the State of California Department of General Services Real Estate Services Division, Project Management and Development Branch. The scope of work includes the installation of 6 new EVSE spaces and upgrading the existing EVSE spaces at the Bay Area District Office. The drawings provide details on the electrical system, site layout, and equipment foundations. The project is approved by the Office of the State Fire Marshal, and construction is planned to begin on 03/30/24.
The drawings indicate that the equipment includes 70A service pedestals and panel boards to be installed. Reinforced concrete foundations will be used to support the EVSE equipment. Special inspections will be required for the concrete and steel construction. The project is located at a State-owned facility, and the work is being funded through State resources. No other pricing, set aside, or incumbent contractor information is provided in the document.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT WORK
AREA - 6 EVSE
TITLE SHEET
E1.0
PROJECT LOCATION
CODES AND PREFERENCES SHEET INDEX
SYMBOLS AND ABBREVIATIONS
EVSE DESCRIPTION SCOPE OF WORK
EXISTING EVSE SPACES NEW EVSE SPACES
FLEET WORKPLACE WORKPLACEFLEET
845 CASA GRANDE RD.,
PETALUMA, CA 94954
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Janelle Goulding 916 823-7059 Phone 916 376-6216 Fax Janelle.Goulding@dgs.ca.gov
EVSE LEVEL II - PARKS
AND RECREATION - BAY
AREA DISTRICT OFFICE
WP JA LG KK
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-0059
Issue Date: 8/14/2024
VOLTAGE DROP CALCS NEW PANEL "EVSE"
CONDUIT/CABLE SCHEDULE(E) MAIN SWITCHBOARD 'MSB'
800A, 120/240V, SINGLE PHASE
30 DAY LOAD RECORDING: PEAK 18.88KW
800A/1P
(E)
TO (E) UTILITY
(E)
600A/1P
(NEW)
400A/1P
(E)
400A/1P
(E)
(E)
PANEL
A 120/240V
400A
(E)
PANEL
B 120/240V
400A
845 CASA GRANDE RD.,
PETALUMA, CA 94954
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Janelle Goulding 916 823-7059 Phone 916 376-6216 Fax Janelle.Goulding@dgs.ca.gov
EVSE LEVEL II - PARKS
AND RECREATION - BAY
AREA DISTRICT OFFICE
WP JA LG KK
SINGLE LINE DIAGRAM
AND PANEL SCHEDULES
E1.1 V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
NO
PARKING
108"
(TYP.)
G G G
G
G G G G
G
DRAWING LIMITS
D R
A W
IN
G
L
IM
IT
S
DRAWING LIMITS
D R
A W
IN
G
L
IM
IT
S
N E1.2
AS NOTED
ELECTRICAL PLAN
845 CASA GRANDE RD.,
PETALUMA, CA 94954
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Janelle Goulding 916 823-7059 Phone 916 376-6216 Fax Janelle.Goulding@dgs.ca.gov
EVSE LEVEL II - PARKS
AND RECREATION - BAY
AREA DISTRICT OFFICE
WP JA LG KK
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
SPECIAL INSPECTIONS REQUIRED
CONCRETE CONSTRUCTION:
STEEL CONSTRUCTION:
GENERAL NOTES:
845 CASA GRANDE RD.,
PETALUMA, CA 94954
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Janelle Goulding 916 823-7059 Phone 916 376-6216 Fax Janelle.Goulding@dgs.ca.gov
EVSE LEVEL II - PARKS
AND RECREATION - BAY
AREA DISTRICT OFFICE
WP JA LG KK
E2.0
NONE
GENERAL NOTES
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
CONDUIT TRENCH HANDHOLES
E2.1
NONE
ELECTRICAL DETAILS
845 CASA GRANDE RD.,
PETALUMA, CA 94954
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Janelle Goulding 916 823-7059 Phone 916 376-6216 Fax Janelle.Goulding@dgs.ca.gov
EVSE LEVEL II - PARKS
AND RECREATION - BAY
AREA DISTRICT OFFICE
WP JA LG KK
EVSE 70A SERVICE PEDESTAL CONDUIT STUB-UP
16302
ELECTRICAL
EQUIPMENT FOUNDATION
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
4' LONG WHEEL STOP
12 GROUND WELL
NONE
1" MIN., 2" MAX. FROM
SOIL. CONDUCTOR SHALL BE
CONTINUOUS; COORDINATE
WITH STRUCTURAL.
#4/0 AWG BARE COPPER.
SLAB CONSTRUCTION
(SEE STRUCTURAL DETAILS)
BARE COPPER CONDUCTOR
TO PANEL EVSE
20 FEET MIN. #4/0
RIGID NON-METALLIC CONDUIT
BARRIER PROHIBITED
BED OR VAPOR
W/EARTH; DRY GRAVEL
IN DIRECT CONTACT
CONC. FOUNDATION
2" MIN
BOND TO GROUND RING 36" BELOW GRADE
UNLESS OTHERWISE NOTED.
BOND TO GROUND RING
G G G G G G G
G
TO PANEL EVSE
FLEET EVSE SIGNAGE
E2.2
NONE
ELECTRICAL DETAILS
845 CASA GRANDE RD.,
PETALUMA, CA 94954
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
Janelle Goulding 916 823-7059 Phone 916 376-6216 Fax Janelle.Goulding@dgs.ca.gov
EVSE LEVEL II - PARKS
AND RECREATION - BAY
AREA DISTRICT OFFICE
WP JA LG KK
GROUND ROD CONNECTION
PANEL BOARD SUPPORT
UFER GROUNDING ELECTRODE
PERMANENT BOLLARD
BOLLARD SPACING
V3
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/30/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
X-X
VII. REINFORCING STEEL:
1. REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615, GRADE 60.
2. REINFORCING STEEL FOR CAST-IN-PLACE NONPRESTRESSED CONCRETE MEMBERS SHALL HAVE THE
FOLLOWING CONCRETE COVER, SEE ACI 117 FOR TOLERANCES.
A. CONCRETE EXPOSED TO EARTH OR IN CONTACT WITH GROUND:
a. CAST AGAINST AND PERMANENTLY IN CONTACT WITH EARTH 3"
b. EXPOSED TO WEATHER OR IN CONTACT WITH EARTH (#5 AND SMALLER) 1-1/2"
c. EXPOSED TO WEATHER OR IN CONTACT WITH EARTH (#6 AND LARGER) 2"
B. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:
a. SLABS, JOISTS AND WALLS (#11 AND SMALLER) 3/4"
b. SLABS, JOISTS AND WALLS (#14 AND LARGER) 1-1/2"
c. BEAMS, COLUMNS AND PEDESTALS 1-1/2"
3. BAR SPLICES MAY BE DELETED AND CONTINUOUS REINFORCING USED AT CONTRACTORS OPTION. BAR SPLICES SHALL BE MADE AT POINTS OF MINIMUM STRESS. IN FRAMED BEAMS AND SLABS SPLICE TOP
BARS AT MID-SPAN, BOTTOM BARS OVER SUPPORTS.
4. ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE WITH ACI 318 AND THE
'MANUAL OF STANDARD PRACTICE' BY CRSI AS MODIFIED BY THE CONTRACT DOCUMENTS.
5. FIELD BENDING OF REINFORCEMENT SHALL NOT BE PERMITTED WITHOUT SEOR APPROVAL. ALL
REINFORCING BENDS SHALL BE MADE COLD.
IV. REINFORCED CONCRETE:
1. CONCRETE CONSTRUCTION SHALL CONFORM TO ACI 318 AND ACI 301 WITH MODIFICATIONS AS NOTED
ON THE CONTRACT DOCUMENTS.
2. CONCRETE MIXES SHALL BE DESIGNED BY A QUALIFIED TESTING LABORATORY AND BEAR THE WET SEAL OF A CIVIL ENGINEER LICENSED IN THE STATE OF THE PROJECT AND BE PROVIDED TO THE SEOR FOR REVIEW. EACH MIX DESIGN SHALL BEAR THE NAME OF THE PROJECT AND THE SPECIFIC USE.
3. CONCRETE MODULUS OF ELASTICITY SHALL MEET THE MINIMUM PROVIDED IN ACI 318 SECTION 19.2.2 FOR THE 28-DAY STRENGTH SPECIFIED BELOW. TEST SHALL BE IN ACCORDANCE WITH ASTM C469.
4. CONCRETE SHALL HAVE THE FOLLOWING ULTIMATE COMPRESSIVE STRENGTH AT 28 DAYS.
LOCATION STRENGTH, f'c CONCRETE TYPE
A. FOUNDATIONS 4,000 PSI* NORMAL WEIGHT
* INDICATES FOOTING DESIGNED FOR F'c = 2,500 PSI THEREFORE SPECIAL INSPECTIONS NOT
REQUIRED
1. PORTLAND CEMENT SHALL CONFORM TO ASTM C150, TYPE I OR II. CONCRETE EXPOSED TO SOILS
CONTAINING CORROSIVE ELEMENTS (SULFATES) SHALL COMPLY WITH CBC 1904.1.
2. FLY ASH MAY BE USED AS A SUBSTITUTE FOR PORTLAND CEMENT. WEIGHT OF FLY ASH SHALL NOT EXCEED 15% OF CEMENT WEIGHT. FLY ASH SHALL CONFORM TO ASTM C618 CLASS F AND LOSS OF
IGNITION SHALL BE LIMITED TO 2%.
3. MIXING OPERATIONS SHALL CONFORM TO ASTM C94.
4. ALL CONCRETE NOT IN CONTACT WITH EARTH TO HAVE FINISH AS SPECIFIED BY ARCHITECT OR AS
COVERED IN PROJECT SPECIFICATIONS. UNLESS OTHERWISE NOTED, NON-ARCHITECTURAL
CONCRETE COLUMNS AND WALLS SHALL HAVE 3/4”CHAMFERED CORNERS.
5. AGGREGATE FOR NORMALWEIGHT CONCRETE SHALL CONFORM TO ALL REQUIREMENTS AND TESTS
OF ASTM C33 AND PROJECT SPECIFICATIONS.
6. ALL CONCRETE SHALL BE REINFORCED. PROVIDE MINIMUM TEMPERATURE REINFORCEMENT AS REQUIRED BY ACI-318 IN ELEMENTS WHERE NO REINFORCEMENT IS INDICATED ON THE DRAWINGS.
7. DRY PACK OR GROUT UNDER BASE PLATES AND SILL PLATES SHALL BE 7000 PSI MIN AT 28 DAYS.
8. CONCRETE PLACEMENT SHALL CONFORM TO ACI 304 AND PROJECT SPECIFICATIONS. SANDBLAST ALL
CONCRETE SURFACES WHICH NEW CONCRETE WILL BE PLACED AGAINST.
9. TWO HOURS MUST ELAPSE BETWEEN END OF COLUMN OR WALL POURS AND THE BEGINNING OF
FLOOR POURS.
10. ALL REINFORCEMENT, ANCHOR BOLTS AND OTHER EMBEDDED ITEMS SHALL BE SECURELY HELD IN PLACE WHILE CONCRETE IS POURED. ADDITIONAL BARS TO BE PROVIDED BY THE CONTRACTOR FOR
SUPPORT AS NEEDED.
11. MECHANICAL, ELECTRICAL AND PLUMBING OPENINGS AND SLEEVES ARE SHOWN INDICATIVELY AND
SMALL OPENINGS AND SLEEVES ARE NOT SHOWN. SEE SLAB EDGE, MECHANICAL, ELECTRICAL,
PLUMBING AND OTHER TRADES FOR SIZE AND LOCATION OF ALL SLAB AND WALL OPENINGS AND SLEEVES. CONTRACTOR TO DEVELOP AND SUBMIT A SINGLE COORDINATION DRAWING COMBINING ALL TRADES INDICATING ALL SLAB OPENINGS AND SLEEVES PRIOR TO POURING CONCRETE FOR REVIEW
BY STRUCTURAL ENGINEER.
12. ALL PIPE AND CONDUIT OPENINGS SHALL BE SLEEVED AND CAST IN PLACE UNLESS OTHERWISE
NOTED. DO NOT SAWCUT, CORE OR CORE DRILL STRUCTURAL CONCRETE WITHOUT EXPLICIT
DIRECTION FROM THE STRUCTURAL ENGINEER. DRILL BITS THAT CAN CUT OR DAMAGE REINFORCING
ARE NOT PERMITTED TO BE USED ON STRUCTURAL CONCRETE.
13. CONDUITS AND PIPES SHALL NOT BE PERMITTED IN STRUCTURAL CONCRETE ELEMENTS UNLESS SPECIFICALLY REVIEWED BY THE STRUCTURAL ENGINEER. ALL CONDUITS TO BE EMBEDDED IN THE
STRUCTURAL CONCRETE SHALL BE SUBMITTED FOR STRUCTURAL REVIEW ON A SINGLE
COORDINATED CONDUIT DRAWING COMBINING ALL TRADES DEVELOPED AND COORDINATED BY THE
CONTRACTOR. COORDINATED CONDUITS/PIPES MUST BE PLACED IN ONE LAYER AVOIDING
CROSSOVER AND SPACED AT THE GREATER OF 3" OR 3 DIAMETERS. DRAWINGS SHALL SHOW STUB-UP LOCATIONS, BEND RADIUS AND DETAILS OF CONDUIT/PIPE INSTALLATION. ALL CONDUITS AND PIPES
SHALL BE INSTALLED PER THE REQUIREMENTS OF ACI 318 SECTIONS 20.7 AND 26.8.2.
A. ELECTRICAL CONDUIT SHALL BE RIGID STEEL CONDUIT OR FLEXIBLE PLASTIC CONDUIT. ALUMINUM
CONDUIT IS PROHIBITED. CONDUIT OUTSIDE DIAMETER SHALL NOT EXCEED 2" OR 1/6 SLAB
THICKNESS, WHICHEVER IS LESSER. CONDUIT SHALL BE FIRMLY CHAIRED AND TIED TO PREVENT
DISPLACEMENT DURING POURING.
II. DESIGN LOADS:
1. DEAD LOAD: EQUIPMENT SELF WEIGHT.
2. WIND LOAD
A. ULTIMATE DESIGN BASIC WIND SPEED V(ult) = 92 MPH
B. WIND IMPORTANCE FACTOR = 1.00
C. WIND EXPOSURE CATEGORY = C
3. SEISMIC LOAD
A. SITE CLASS = D (DEFAULT)
B. RISK CATEGORY = II
C. SEISMIC IMPORTANCE FACTOR = 1.00
D. MAPPED SPECTRAL RESPONSE
a. SHORT PERIOD SS = 1.76 g
b. 1-SECOND PERIOD S1 = 0.67 g
E. DESIGN SPECTRAL RESPONSE (5% DAMPED)
a. SHORT PERIOD SDS = 1.41 g
I. GENERAL NOTES:
1. ALL STRUCTURAL WORK SHALL CONFORM TO THE DRAWINGS, THE PROJECT SPECIFICATIONS, ALL
DRAWING NOTES, AND THE 2022 CALIFORNIA BUILDING CODE (CBC).
2. ALL APPLICABLE REFERENCE STANDARDS, AS MODIFIED BY THE BUILDING CODE, INCLUDE:
A. ASCE/SEI 7-16: MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
B. ACI 318-19: BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
C. AISC 360-16: SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
D. ACI 117-10: STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE
CONSTRUCTION AND MATERIAL
E. AISI SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL
MEMBERS, 2016
3. THE SCOPE OF WORK IS NOT SOLELY DEFINED BY THESE DOCUMENTS.
4. TYPICAL DETAILS APPLY THROUGHOUT THE PROJECT, EVEN IF NOT SPECIFICALLY REFERENCED IN PLANS OR DETAILS. DETAILS OF CONSTRUCTION NOT FULLY SHOWN OR NOTED ON THE DRAWINGS NOR CALLED OUT IN THE SPECIFICATIONS SHALL BE OF THE SAME SIZE AND CHARACTER AS FOR
SIMILAR CONDITIONS WHICH ARE SHOWN AND NOTED.
5. ALL FORCES INDICATED IN THE STRUCTURAL DRAWINGS ARE SERVICE LOADS AS DEFINED BY ASCE-7, UNLESS NOTED OTHERWISE.
6. DO NOT USE SCALED DIMENSIONS; USE ONLY WRITTEN DIMENSIONS. WHERE NO DIMENSION IS
PROVIDED, CONSULT THE ARCHITECT FOR CLARIFICATIONS BEFORE PROCEEDING WITH WORK.
7. SEE ARCHITECTURAL DRAWINGS FOR SITE POSITIONING AND PROJECT DATUM, REFERENCE IS (0'-0")
AS SHOWN ON ARCHITECTURAL DRAWINGS.
8. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE CONDITIONS OF THE JOB SITE
INCLUDING SAFETY OF PERSONS AND PROPERTY AND THE MEANS AND METHODS OF CONSTRUCTION.
9. STRUCTURAL ELEMENTS SHALL BE CENTERED ABOUT GRIDLINES OR DIMENSION LINES, UNLESS
OTHERWISE NOTED.
10. THE CONTRACTOR SHALL PROVIDE ENGINEERED DESIGNS OF TEMPORARY SHORING AND BRACING AND MAKE SAFE ALL FLOORS, ROOFS, WALLS, EXCAVATIONS AND ADJACENT PROPERTY AS PROJECT
CONDITIONS AND LOCAL BUILDING CODE REQUIRE.
11. ALL STRUCTURAL WORK SHALL BE COORDINATED WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, ETC. REQUIREMENTS. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS NOT
SHOWN ON PLAN. DISCREPANCIES AND/OR INTERFERENCES SHALL BE REPORTED TO THE ARCHITECT
IMMEDIATELY.
12. OPENINGS SHALL NOT BE MADE IN ANY STRUCTURAL MEMBER UNLESS SPECIFICALLY SHOWN ON THE
STRUCTURAL DRAWINGS OR APPROVED BY THE STRUCTURAL ENGINEER.
13. DEFICIENT WORK AND WORK NOT IN CONFORMANCE WITH THE CONTRACT DOCUMENTS AS IDENTIFIED
BY THE ARCHITECT OR INSPECTOR SHALL BE REPAIRED AT THE CONTRACTOR'S EXPENSE.
CONTRACTOR SHALL COMPENSATE OWNER FOR SERVICES ARISING FROM DEFICIENT WORK.
14. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ANY REQUIRED DEWATERING OF THE SITE
DURING CONSTRUCTION.
15. THE CONTRACTOR SHALL PREPARE ENGINEERED DESIGN AND SHALL BE RESPONSIBLE FOR
CONFIRMING ADEQUACY OF AS BUILT STRUCTURE FOR ALL SURCHARGE LOADS RESULTING FROM
COMPACTION AS WELL AS CRANES TRUCKS, BULLDOZERS OR ANY OTHER CONSTRUCTION
EQUIPMENT. ENGINEERED DESIGNS SHALL BE PREPARED, SIGNED AND SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE JURISDICTION AND SUBMITTED TO ENGINEER OF RECORD FOR REVIEW.
16. THE STRUCTURAL COMPONENTS BY THEMSELVES ARE A NON-SELF-SUPPORTING STRUCTURE.
LATERAL FORCES DUE TO WIND, EARTHQUAKE, OR SOIL ARE CARRIED BY THE ROOF AND FLOOR DIAPHRAGMS TO THE LATERAL SYSTEM. CERTAIN ELEMENTS SHOWN ON THE STRUCTURAL DRAWINGS
(SUCH AS BRACING, ROOF AND FLOOR SLABS, AND CONCRETE IN COMPOSITE COLUMNS) ARE
REQUIRED FOR OVERALL OR LOCAL STABILITY OF OTHER ELEMENTS (SUCH AS BEAMS, COLUMNS, AND WALLS). IF DUE TO SEQUENCING OF CONSTRUCTION, THESE STABILITY ELEMENTS ARE NOT IN PLACE, THE CONTRACTOR SHALL RETAIN A STRUCTURAL ENGINEER LICENSED TO PERFORM THE WORK IN THE JURISDICTION WHERE THE PROJECT IS LOCATED, WHO SHALL INVESTIGATE WHERE TEMPORARY
SHORING/BRACING IS REQUIRED AND SHALL DESIGN THIS TEMPORARY SHORING/BRACING. THE
CONTRACTOR SHALL PROVIDE THIS SHORING/BRACING UNTIL THE REQUIRED STRUCTURAL ELEMENTS AND THEIR CONNECTIONS HAVE BEEN INSTALLED AND REACH THEIR FINAL DESIGN STRENGTHS.
17. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT WHEN PLACED ON FRAMED FLOORS OR ROOFS.
THE CONSTRUCTION MATERIAL LOAD SHALL NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT.
CONTRACTOR SHALL BE RESPONSIBLE FOR SHORING WHERE STRUCTURE IS NOT COMPLETE OR HAS
NOT ATTAINED DESIGN STRENGTH.
18. BUILDING TOLERANCES: STANDARD TOLERANCES SHALL BE BASED ON THE REQUIREMENTS OF THE AISC CODE OF STANDARD PRACTICE AND ACI 117, STANDARD SPECIFICATIONS FOR TOLERANCES FOR
CONCRETE CONSTRUCTION AND MATERIALS.
III. FOUNDATIONS:
1. FOUNDATION DESIGN CRITERIA ARE BASED ON CODE MINIMUM VALUES AS SPECIFIED IN CHAPTER 18
"SOILS AND FOUNDATIONS" OF THE 2022 CALIFORNIA BUILDING CODE (CBC).
2. FOOTINGS ARE DESIGNED BASED ON AN ALLOWABLE SOIL BEARING PRESSURE OF 1,500 PSF.
3. LATERAL BEARING PRESSURE FOR FOOTING DESIGN IS 100 PSF.
4. SOIL PREPARATION OF THE SITE SHALL FOLLOW THE RECOMMENDATIONS DESCRIBED IN CHAPTER 18 OF 2021 CBC. THIS INCLUDES REMOVAL OF EXISTING STRUCTURES/UTILITIES, REMOVAL OF EXISTING FILL WHERE DEEMED NECESSARY, PREPARATION OF THE SUBGRADE & COMPACTION, EXCAVATIONS
FOR NEW FOUNDATIONS & SLABS, AND BACKFILLING TO RETAINING WALLS.
5. FOUNDATIONS SHALL BEAR ON UNDISTURBED SOIL OR COMPACTED FILL MATERIAL 12 INHES IN DEPTH WITH THE IN-PLACE DRY DENSITY NOT LESS THAN 90 PERCENT OF THE MAXIMUM DRY DENSITY AT
OPTIMUM MOISTURE CONTENT DETERMINED IN ACCORDANCE WITH ASTM D1557.
6. LOCATION OF ALL UNDERGROUND UTILITIES SHALL BE VERIFIED PRIOR TO CONSTRUCTION OF FOUNDATION TO AVOID ANY INTERFERENCE. CONTRACTOR SHALL EXPOSE EXISTING UTILITY LINES IN THE IMMEDIATE AREA TO DETERMINE THEIR EXACT INVERT ELEVATION, SIZE AND LOCATION RELATIVE TO THE FOUNDATION. NOTIFY THE ENGINEER IMMEDIATELY OF ANY INTERFERENCE WITH PILES, FOOTINGS OR FOUNDATION WALLS.
7. CONTRACTOR SHALL PROVIDE FOR PROPER DEWATERING OF EXCAVATIONS FROM SURFACE WATER, GROUND WATER, AND SEEPAGE. WATER SHALL NOT BE ALLOWED TO STAND IN TRENCHES OR FORMS BEFORE OR AFTER CONCRETE IS PLACED, AND SHALL BE PUMPED OUT. IF BOTTOMS OF TRENCHES
BECOME SOFTENED DUE TO RAIN OR OTHER WATER BEFORE FOUNDATIONS ARE CAST, THE
CONTRACTOR SHALL, AT THEIR OWN EXPENSE, EXCAVATE THE SOFTENED MATERIAL AND REPLACE
WITH CONCRETE.
8. CONTRACTOR SHALL PROVIDE FOR THE DESIGN AND INSTALLATION OF ALL CRIBBING, SHEATHING AND SHORING REQUIRED TO SAFELY AND ADEQUATELY RETAIN THE EARTH BANKS AND ANY EXISTING
STRUCTURE.
9. EXCAVATIONS FOR FOOTINGS SHALL BE APPROVED BY THE GEOTECHNICAL ENGINEER PRIOR TO
PLACING OF CONCRETE AND REINFORCING. CONTRACTOR SHALL NOTIFY THE GEOTECHNICAL
ENGINEER WHEN THE EXCAVATIONS ARE READY FOR INSPECTION. THE GEOTECHNICAL ENGINEER
SHALL SUBMIT A LETTER OF COMPLIANCE TO THE OWNER.
10. ALL EXCAVATIONS SHALL BE PROPERLY BACKFILLED. DO NOT PLACE BACKFILL BEHIND RETAINING
WALLS BEFORE CONCRETE OR MASONRY HAS ATTAINED FULL DESIGN STRENGTH. CONTRACTOR
SHALL BRACE OR PROTECT ALL BUILDING WALLS BELOW GRADE FROM LATERAL LOADS UNTIL
ATTACHING FLOORS ARE COMPLETELY IN PLACE AND HAVE ATTAINED FULL DESIGN STRENGTH.
CONTRACTOR SHALL PROVIDE FOR DESIGNS, PERMITS AND INSTALLATION OF BRACING AND
PROTECTION.
VIII. ANCHOR RODS:
1. ANCHOR RODS SHALL BE ASTM F1554 GRADE 36 WITH CLASS 1A THREADS, UNLESS NOTED
OTHERWISE. FURNISH ANCHOR RODS PREFABRICATED WITH MATCHING DOUBLE HEAVY HEX NUTS
JAMMED AT THE END EMBEDDED IN CONCRETE. FURNISH HARDENED PLATE WASHERS, LOCK
WASHERS, AND MATCHING HEAVY HEX NUTS FOR SECURING THE BASE PLATE TO THE ANCHOR RODS.
A RIGID STEEL TEMPLATE SHALL BE USED TO LOCATE ANCHOR RODS WHILE PLACING CONCRETE.
2. HOOKED ANCHOR RODS SHALL NOT BE USED EXCEPT WHERE NOTED.
3. ANCHOR RODS SHALL HAVE SUFFICIENT LENGTH TO PROVIDE THE MINIMUM EMBEDMENT SHOWN ON THE DRAWINGS, MEASURED FROM THE FACE OF THE CONCRETE TO THE NEAR FACE OF THE DOUBLE NUT, WITH ADEQUATE EXTENSION AS REQUIRED TO RECEIVE THE BASE PLATE WITH FULL THREAD
PROJECTION FOR NUT INSTALLATION.
4. ANCHOR ROD INSTALLATION SHALL BE COORDINATED WITH REINFORCING AND FRAMEWORK.
5. LEVELING NUTS SHALL NOT BE USED EXCEPT AFTER EVALUATION BY THE CONTRACTOR'S ERECTION
ENGINEER.
6. AFTER BASE INSTALLATION, ANCHOR ROD NUTS SHALL BE INSTALLED TO A SNUG-TIGHT CONDITION.
7. NO HEATING OR BENDING OF THE ANCHOR RODS IS PERMITTED. HOLES IN THE BASE
MATERIAL SHALL NOT BE ENLARGED BY BURNING.
VI. MECHANICAL AND ADHESIVE ANCHORS:
1. ADHESIVE ANCHORS AND DOWELS INSTALLED INTO CONCRETE:
A. "SET-XP”BY SIMPSON STRONG TIE (ICC ESR-2508)
B. "HIT-RE 500-SD" BY HILTI, INC. (ICC ESR-3814) EQUIPMENT ANCHORAGE UON
C. "PURE110+BY DEWALT (ICC ESR-3298)
2. EXPANSION ANCHORS INSTALLED INTO CONCRETE:
A. "STRONG-BOLT 2" BY SIMPSON STRONG-TIE (ICC ESR-3037)
B. "KWIK BOLT TZ2 (KB-TZ2)”BY HILTI, INC. (ICC ESR-4266)
C. "POWER-STUD+SD2" BY DEWALT (ICC ESR-2502)
3. ADHESIVE ANCHORS: ASTM A36 THREADED RODS WITH ASTM A 563 GRADE A NUTS AND ANSI B18.22.1
TYPE A WASHERS, UNLESS OTHERWISE NOTED. ANCHORS DESIGNATED AS ASTM A193 GRADE B7
THREADED RODS TO USE ASTM A 563 GRADE DH HEAVY HEX NUTS AND ASTM F 436 WASHERS.
4. ADHESIVE DOWELS: ASTM A615 GRADE 60 REINFORCING STEEL.
5. ALL ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH ICC-ES REPORT AND MANUFACTURERS
RECOMMENDATIONS.
6. UNLESS OTHERWISE NOTED, PROVIDE MINIMUM EMBEDMENT OF ANCHORS PER ICC-ES REPORT &
MANUFACTURERS RECOMMENDATIONS.
7. CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO FABRICATING PLATES, MEMBERS, OR OTHER STEEL
ASSEMBLIES ATTACHED WITH MECHANICAL OR ADHESIVE ANCHORS.
8. PRIOR TO ALL DRILLING OR CORING, THE CONTRACTOR SHALL (1) VERIFY THE EXISTING CONCRETE OR MASONRY THICKNESS TO PREVENT DAMAGE TO THE OPPOSITE FACE OF CONCRETE AND MAINTAIN 1 -1 /2 ”CLEAR COVER U.N.O., AND (2) IDENTIFY EXISTING REINFORCING LOCATIONS BY PACHOMETER, PROBING, CHIPPING, ETC. TO AVOID DAMAGE EXISTING REINFORCING.
9. IF REINFORCEMENT IS ENCOUNTERED DURING DRILLING, ABANDON AND SHIFT THE HOLE LOCATION TO AVOID THE REINFORCEMENT. PROVIDE A MINIMUM OF 2 ANCHOR DIAMETERS OR 1 INCH, WHICHEVER IS
LARGER, OF SOUND CONCRETE BETWEEN THE DOWEL AND THE ABANDONED HOLE. FILL THE
ABANDONED HOLE WITH NON-SHRINK GROUT. IF THE ANCHOR OR DOWEL MAY NOT BE SHIFTED AS
NOTED ABOVE, THE ENGINEER WILL DETERMINE A NEW LOCATION.
10. ADHESIVE ANCHORS INSTALLED IN HORIZONTAL TO VERTICALLY OVERHEAD ORIENTATION TO SUPPORT SUSTAINED TENSION LOADS SHALL BE DONE BY A CERTIFIED ADHESIVE ANCHOR INSTALLER
(AAI) CERTIFIED THROUGH ACI/CRSI OR EQUIVALENT (ACI 318-14 17.8.2.2).
11. ADHESIVE ANCHORS MUST BE INSTALLED IN CONCRETE AGED A MINIMUM OF 21 DAYS (ACI 318-14 17.1.2).
SETTING INFORMATION SYM. UNITS
NOMINAL ANCHOR DIAMTER (IN.)
INSTALLATION TORQUE
CARBON STEEL
INSTALLATION TORQUE
STAINLESS STEEL
TINST
TINST
FT-LB
(Nm)
FT-LB
(Nm)
1/4 3/8 1/2 5/8 3/4
(5)
(41)
(68)
(54)
(149)
(8)
(41)
(54)
(81)
(169)
SLAB STEP/ DEPRESSION
SLOPE UP
SLOPE DOWN
RIDGE
VALLEY
REVISION NUMBER
ELEVATION
SECTION MARK
ELEVATION MARK
GRID BUBBLE
S301
S201
SLAB THICKNESS
CHANGE
DETAIL MARK
S501
THE INSPECTOR SHALL OBSERVE THESE FUNCTIONS ON A RANDOM BASIS.
OPERATIONS NEED NOT BE DELAYED PENDING OBSERVATIONS.
OBSERVE
THESE INSPECTIONS SHALL BE PERFORMED FOR EACH CONNECTION OR MEMBER,
AND COMPLETED PRIOR TO THE FINAL ACCEPTANCE OF THE ITEM.
PERFORM
SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS PRESENT CONTINUOUSLY
WHEN AND WHERE THE WORK TO BE INSPECTED IS BEING PERFORMED
CONTINUOUS
SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS INTERMITTENTLY PRESENT
WHERE THE WORK HAS BEEN OR IS BEING PERFORMED AND AT THE COMPLETION OF
WORK.
PERIODIC
A QUALIFIED PERSON EMPLOYED OR RETAINED BY AN APPROVED AGENCY AND
APPROVED BY THE BUILDING OFFICIAL AS HAVING THE COMPETENCE NECESSARY TO
INSPECT A PARTICULAR TYPE OF CONSTRUCTION REQUIRING SPECIAL INSPECTION.
SPECIAL
INSPECTOR
INSPECTION OF CONSTRUCTION REQUIRING THE EXPERTISE OF AN APPROVED
SPECIAL INSPECTOR IN ORDER TO ENSURE COMPLIANCE WITH THE BUILDING CODE
AND THE APPROVED CONSTRUCTION DOCUMENTS.
SPECIAL
INSPECTION
DEFINITIONS
REFERENCES
CODES/STANDARDS
SPECIAL INSPECTION AND TEST REQUIREMENTS
TYPE REQUIRED INSPECTIONS AND/OR TESTSFREQUENCY
INDICATES SPECIAL INSPECTION OF ITEM IS REQUIRED FOR THE WORK DEFINED IN
THE CONSTRUCTION DOCUMENTS FOR THIS PROJECT.
INSPECTION AND TESTING REQUIREMENTS ON THIS SHEET ARE IN ACCORDANCE
WITH SECTION 1705 OF THE 2022 CALIFORNIA BUILDING CODE (CBC). AND HAVE BEEN
IDENTIFIED AS A STATEMENT OF SPECIAL INSPECTIONS AS REQUIRED BY CBC
SECTION 1704.3. THE OWNER OR THE OWNER'S AUTHORIZED AGENT, OTHER THAN
THE CONTRACTOR, SHALL EMPLOY ONE OR MORE APPROVED AGENCIES TO
PROVIDE THE SPECIAL INSPECTIONS AND TESTS DURING CONSTRUCTION AS
REQUIRED BY CBC SECTION 1705 AND IDENTIFY THE APPROVED AGENCIES TO THE
BUILDING OFFICIAL. THESE SPECIAL INSPECTIONS AND TESTS ARE IN ADDITION TO
THE INSPECTIONS BY THE BUILDING OFFICIAL THAT ARE IDENTIFIED IN CBC SECTION
110. SPECIAL INSPECTORS SHALL BE QUALIFIED IN ACCORDANCE WITH CBC SECTION
1704.2.1, AND ALL OTHER APPLICABLE SECTIONS AND STANDARDS.
SPECIAL INSPECTIONS AND TESTS INDICATED ON THIS SHEET ARE FOR THE
STRUCTURAL WORK, SEE OTHER DISCIPLINES DRAWINGS AND SPECIFICATIONS FOR
REQUIRED NONSTRUCTURAL SPECIAL INSPECTIONS AND TESTS.
STATEMENT OF SPECIAL INSPECTIONS
CONCRETE CBC 1705.3
4. ANCHORS POST-INSTALLED
IN HARDENED CONCRETE
MEMBERS
INSPECT ALL OTHER MECHANICAL OR ADHESIVE ANCHORS THAT ARE NOT ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS - SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSUED BY AN APPROVED SOURCE IN ACCORDANCE WITH ACI318: 17.8.2 OR OTHER QUALIFICATION PROCEDURES.
PERIODIC ACI 318: 17.8.2
GENERAL NOTES ABBREVIATIONS
Issue
Project
Supervisor Designed Drawn
Sheet Title
Sheet Scale
Sheet Number
A x
B C D E F G H I J K L M N O
AB C D E F G H I J K L M N O
File Date
V3
PROFESSIONAL STAMP
Work OrderDSA Building Number
Vault File Number
Address
Checked
N/A
S-001.
IS DK
Stantec Consulting Services Inc.
801 South Figueroa Street Suite 300 Los Angeles, CA 90017-3007 Tel: (213) 955-9775
GENERAL NOTES
AD
S-001
# POUND
& AND
@ AT
AB ANCHOR BOLT
ACS ALL COMMON SIDES
ADDL ADDITIONAL
AESS ARCHITECTURALLY EXPOSED
STRUCTURAL STEEL
ALT ALTERNATE
ARCH,
ARCH'L
ARCHITECT, ARCHITECTURAL
BL BRICKLEDGE
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BN BOUNDARY NAILING
BO BOTTOM OF
BOB BOTTOM OF BEAM
BOD BOTTOM OF DECK
BOS BOTTOM OF STEEL
BOT, BOTT BOTTOM
BP BASE PLATE
BRBF BUCKLING RESTRAINED BRACED
FRAME
BRG BEARING
BTWN BETWEEN
C CHANNEL
CB CONCRETE BEAM
CC CARRIED COLUMN
CEN CENTER
CFMF COLD-FORMED METAL FRAMING
CIP CAST IN PLACE
CJ CONTROL JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECT, CONNECTION
CONT CONTINUOUS
CTR CENTERED
CWI CERTIFIED WELDING INSPECTOR
D, DIA DIAMETER
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DEF DEFORMED, DEFINITION
DEFL DEFLECTION
DET, DTL DETAIL
DIAG DIAGONAL
DN DOWN
DWG DRAWING
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATOR
EMB EMBED
EN EDGE NAILING
EOR ENGINEER OF RECORD
EOS EDGE OF SLAB
EQ EQUAL
EQ SPA EQUAL SPACE
ES EACH SIDE
EW EACH WAY
EXIST, (E) EXISTING
EXT EXTERIOR
FD FLOOR DRAIN
FDN, FNDN FOUNDATION
FF EL FINISH FLOOR ELEVATION
FN FIELD NAILING
FOA FACE OF ANGLE
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FT FEET
FTG FOOTING
Fy YIELD STRESS
GA GAGE, GUAGE
GALV GALVANIZED
GB GRADE BEAM
GLB GLUED-LAMINATED BEAM
GT GIRDER TRUSS
H, HORIZ HORIZONTAL
HC HOLLOW CORE
HI HIGH
HK HOOK
HSS HOLLOW STRUCTURAL STEEL
IN INCHES
INFO INFORMATION
INT INTERIOR
JST JOIST
JT JOINT
K KIPS
KB KNEE BRACE
L ANGLE
LB POUND
LF LINEAR FOOT
LG LENGTH
LLBB LONG LEG BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LO LOW
LT WT LIGHTWEIGHT
LVL LEVEL
MAX MAXIMUM
MC MOMENT CONNECTION
MCJ MASONRY CONTROL JOINT
MECH MECHANICAL
MEZZ MEZZANINE
MFR,
MANUF
MANUFACTURER
MID MIDDLE
MIL MILLIMETER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MTL METAL
N NORTH
NA NOT APPLICABLE
NDT NON-DESTRUCTIVE TESTING
NEW, (N) NEW
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OC ON CENTER
OH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OWSJ OPEN WEB STEEL JOIST
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
R RADIUS
REF REFER, REFERENCE
REINF REINFORCED, REINFORCEMENT
REM REMAINDER
REQ'D REQUIRED
REQ'MTS,
REQMTS
REQUIREMENTS
REV REVISION
SAD SEE ARCHITECTURAL DRAWINGS
SC SLIP CRITICAL
SCHED SCHEDULE
SCJ SAWN CONTROL JOINT
SECT SECTION
SF SQUARE FEET
SHT SHEET
SHTG SHEATHING
SIM SIMILAR
SOG SLAB ON GRADE
SPA SPACES, SPACING
SQ SQUARE
SSH SHORT SLOTTED HOLE
STD STANDARD
STL STEEL
STRUCT STRUCTURE, STRUCTURAL
SUPP SUPPORT
T&B TOP AND BOTTOM
TEMP TEMPORARY
THK THICK
TO TOP OF
TOC TOP OF CONCRETE
TOF TOP OF FOUNDATION
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOSC TOP OF STRUCTURAL CONCRETE
TOSL TOP OF SLAB
TOT TOTAL
TOW TOP OF WALL
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V, VERT VERTICAL
VIF VERIFY IN FIELD
W WIDE FLANGE
W/ WITH
W/O WITHOUT
WB WIND BRACE
WBBP WIND BRACE BASEPLATE
WHSS WELDED HEADED STEEL STUD
WP WORKING POINT, WORK POINT
WRT WITH RESPECT TO
WT WEIGHT
WWR WELDED-WIRE REINFORCEMENT
YD YARD
SYMBOLS
No. Date Description
09-30-2224
8-8-24
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
08/13/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
2'
1'
1'
PEDESTAL BASE
& FOUNDATION
2' - 0"
1' - 0" 1' - 0"
ANCHOR POINT
PER MFR TYP
(4) TOT
CONDUIT STUB UP PER
MFR REQUIREMENTS
TYP
AA
C
LR3"
TYP
3" CLR
M
IN
1'
BTC POWER SINGLE
PORT 70A PEDESTAL
BY OTHERS
SECTION A-A
FINISHED GRADE
SUBGRADE PER
GENERAL NOTES
(2) #5 EA WAY
EQUIPMENT BASE
BY OTHERS
WT = 78 LBS
4" 3/ 4"
2 1/4"7"
NOTE:
1. FOOTING MAY BE FLUSH WITH ADJACENT PAVING AS REQUIRED.
PAVING PER NOTE 1
CONDUIT
NON SHRINK GROUT
P E R M
F P
11" PER MFR
PEDESTAL BASE
& FOUNDATION
11 1/2"
1/ 2"
M A X
1/ 2"
3/8" DIA AB
CONTRACTOR'S ALT: 3/8" DIA
THREADED ROD W/ HITLI HIT-HY 200
V3 ADHESIVE (ICC ESR - 4868)
W/ 8" EMB
6" E
M B
PANEL BOARD
PER ELEC DWGS
WT = 80 LBS
UNISTRUT P1000
CHANNEL TYP
UNISTRUT P1026 ANGLE
W/ (2) 1/2" BOLT
W/ (2) P1006 SPRING NUT
TYP
ELEVATION
1/2" DIA HILTI KB-TZ2
W/ 2" EMB
UNISTRUT P1047
U-BRACKET TYP
W/ (3) 1/2" BOLT W/
(3) P1010 SPRING NUT
(E) 3 1/4" LIGHT-WT
CONC O/ 3" MTL DECK
UNISTRUT P2548-30 BRACE
W/ 1/2" BOLT & P1010
SPRING NUT EA END
2' - 0"
ALIGN HORIZONTAL
BACKING CHANNEL
W/ MFR PROVIDED
CONNECTION POINTS
AS REQUIRED
CONNECT SWITCH TO
HORIZONTAL CHANNEL
W/ (3) #10 SMS PER STRUT
5 3/4"
TYP
3" 1' - 8"
4' M
IN
.0 0°
1' - 8"
2"
SUBGRADE PER
GENERAL NOTES
6"
TYP
3" CLR
(3) #5 EA WAY
CENTERED IN CONC
TYP
6"
3/8" DIA MB W/ OVERSIZE
PL WASHER TYP (4) TOT
AT MFR ANCHOR POINTS
1' - 3" PER MFR
4' P E R M
F P
5' "42 M
IN
A
A
SECTION A-A
TYP
6"
Issue
Project
Supervisor Designed Drawn
Sheet Title
Sheet Scale
Sheet Number
A x
B C D E F G H I J K L M N O
AB C D E F G H I J K L M N O
File Date
V3
PROFESSIONAL STAMP
Work OrderDSA Building Number
Vault File Number
Address
Checked
N/A
S-002
IS DK
Stantec Consulting Services Inc.
801 South Figueroa Street Suite 300 Los Angeles, CA 90017-3007 Tel: (213) 955-9775
DETAILS
AD
NTSS-002
6 EVSE 70A SERVICE PEDESTAL FOUNDATION PLAN
NTS S-002
8 DISTRIBUTION PANEL SUPPORT FRAME
No. Date Description
09-30-2224
8-8-24
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
08/13/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
| E1.0 Title Sheet |
| E1.1 Single Line Diagram and Panel Schedules |
| E1.2 Electrical Plan |
| E2.0 General Notes |
| E2.1 Electrical Details |
| E2.2 Electrical Details |
| S001 General Notes |
| S002 Details |
File details come from the government source that posted it. Updated .