Pittsylvania Phase 3 Construction_Drawings.pdf
PDF 23 MB Posted
- Attached to
- Pittsylvania County Solid Waste Phase 3
- Solicitation number
- IFB-118549
- Issued by
- Pittsylvania County, Virginia
About this file
This document comprises construction drawings for Pittsylvania County Sanitary Landfill Phase 3 Construction in Pittsylvania County, Virginia, prepared by LaBella Associates and issued for bid on April 20, 2026. The project involves the construction of Cell D at the landfill facility under Solid Waste Management Permit #571. The scope of work includes site preparation with cell base grading, installation of an 18-inch drainage layer with geotextile and 60-mil HDPE geomembrane liner system, construction of a leachate collection system with perforated piping, sump design with dual 7.5-horsepower submersible pumps, and a 4-inch by 8-inch dual containment force main for leachate conveyance. Additional work comprises access road construction over approximately 1,677 linear feet with culvert installations, erosion and sediment control measures throughout the site, electrical infrastructure including a level control panel with telemetry capabilities, and Phase 2 partial closure work for existing cells. The drawings include detailed specifications for liner terminations, geocomposite outlets, and connections to existing facility infrastructure.
The project drawings specify multiple construction details and standards compliance requirements, including adherence to the Virginia Stormwater Management Handbook and Virginia Underground Utility Damage Prevention Act. The contractor is required to contact MISS Utility 48 hours prior to any excavation and shall protect all existing structures and utilities, with repair costs borne by the contractor. Key benchmarks are established at three locations with documented elevations. The electrical work includes installation of a 120/240-volt, three-phase service with dual pump motor starters, a control panel with pump speed controllers, over-temperature and seal-failure monitoring systems, remote terminal unit with wireless cellular reporting capability, and Class 1 Division 2 hazard area classification management with appropriate conduit sealing and equipment specifications per the National Electric Code. The contract documents indicate coordination requirements with Pittsylvania County regarding equipment locations, control panel approval prior to fabrication, and system testing and training responsibilities assigned to the contractor.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Landfill Phase 3 Addendum 1.pdf | ||
| Pittsylvania Phase 3 Construction_Project Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPROXIMATE
PROPERTY
BOUNDARY
USGS MAP SOURCE
7.5 MIN. QUADRANGLE:
PENDLETON, PHOTOREVISED 1989
VICINITY MAP
1" = 2,000'
PITTSYLVANIA COUNTY SANITARY LANDFILL
PHASE 3 CONSTRUCTION DRAWINGS
SOLID WASTE MANAGEMENT PERMIT #571
APRIL 2026
COUNTY LOCATION MAP
VIRGINIA
PITTSYLVANIA
COUNTY
DRAWING INDEX
SHEET DESCRIPTION
1 TITLE SHEET
2 GENERAL NOTES AND LEGEND
3 EXISTING CONDITIONS
4 CELL D BASE GRADES
5 ENGINEERING MODIFICATION GRADES
6 ACCESS ROAD PLAN AND PROFILE
7 LEACHATE COLLECTION SYSTEM DETAILS
8 MISCELLANEOUS DETAILS
9 LINER DETAILS
10 EROSION AND SEDIMENT CONTROL DETAILS
E-01 ELECTRICAL COVER SHEET
E-02 ELECTRICAL DETAILS
E-03 ELECTRICAL PLANS
PHASE 2 PARTIAL CLOSURE DRAWINGS
14 PHASE 2 PARTIAL CLOSURE INTERMEDIATE COVER GRADES
15 PHASE 2 PARTIAL CLOSURE FINAL GRADING PLAN
16 PHASE 2 PARTIAL CLOSURE ACCESS ROAD PLAN AND PROFILE
17 PHASE 2 PARTIAL CLOSURE EROSION AND SEDIMENT CONTROL PLAN
18 PHASE 2 PARTIAL CLOSURE EROSION AND SEDIMENT CONTROL DETAILS
19 PHASE 2 PARTIAL CLOSURE FINAL COVER DETAILS
20 PHASE 2 PARTIAL CLOSURE MISCELLANEOUS DETAILS
Revisions
NO: DATE: DESCRIPTION:
TITLE SHEET
JTG/DAS
JBM
DRAWING NAME:
DRAWING NUMBER:
DATE:
ISSUED FOR:
DRAWN BY:
REVIEWED BY:
PROJECT NUMBER:
© 2026 LaBella Associates
Pittsylvania County PO Box 426, 1 Center Street, Chatham, Virginia
Pittsylvania County Sanitary Landfill Phase 3 Construction 382 Rainbow Lane, Dry Fork, Virginia, 24549
2253619
BID
4/20/2026
1604 Ownby Lane Richmond, VA 23220 804-355-4520 labellapc.com
A pr
0,
- 3
:3 4p m \\c as h.
la b\ u\ Le ga cy
\R
IC
\C
AD
D \L
AN
D
PR
O
JE
C
TS
\P itt sy lv an ia
\2
Ph as e
C el l D
\C ur re nt
W or ki ng
D ra w in gs \P lo t S he et s\
Ti tle
S he et .d w g
La yo ut =T itl e
Sh ee t
AutoCAD SHX Text
ROANOKE
AutoCAD SHX Text
ALLEGHANY
AutoCAD SHX Text
LEE
AutoCAD SHX Text
SMYTH
AutoCAD SHX Text
TAZEWELL
AutoCAD SHX Text
DICKENSON
AutoCAD SHX Text
WISE
AutoCAD SHX Text
SCOTT
AutoCAD SHX Text
WASHINGTON
AutoCAD SHX Text
RUSSELL
AutoCAD SHX Text
BUCHANAN
AutoCAD SHX Text
CARROLL
AutoCAD SHX Text
GRAYSON
AutoCAD SHX Text
WYTHE
AutoCAD SHX Text
BLAND
AutoCAD SHX Text
FLOYD
AutoCAD SHX Text
PATRICK
AutoCAD SHX Text
MONTGOMERY
AutoCAD SHX Text
PULASKI
AutoCAD SHX Text
GILES
AutoCAD SHX Text
CRAIG
AutoCAD SHX Text
SOUTHAMPTON
AutoCAD SHX Text
KING AND QUEEN
AutoCAD SHX Text
CHARLES
AutoCAD SHX Text
CITY
AutoCAD SHX Text
NEW KENT
AutoCAD SHX Text
KING WILLIAM
AutoCAD SHX Text
CHARLOTTE
AutoCAD SHX Text
BUCKINGHAM
AutoCAD SHX Text
ALBEMARLE
AutoCAD SHX Text
APPOMATTOX
AutoCAD SHX Text
PITTSYLVANIA
AutoCAD SHX Text
FRANKLIN
AutoCAD SHX Text
HENRY
AutoCAD SHX Text
BEDFORD
AutoCAD SHX Text
HALIFAX
AutoCAD SHX Text
CAMPBELL
AutoCAD SHX Text
ROCKBRIDGE
AutoCAD SHX Text
BOTETOURT
AutoCAD SHX Text
BATH
AutoCAD SHX Text
AMHERST
AutoCAD SHX Text
NELSON
AutoCAD SHX Text
BRUNSWICK
AutoCAD SHX Text
MECKLENBURG
AutoCAD SHX Text
LUNENBURG
AutoCAD SHX Text
EDWARD
AutoCAD SHX Text
PRINCE
AutoCAD SHX Text
NOTTOWAY
AutoCAD SHX Text
SUSSEX
AutoCAD SHX Text
GREENSVILLE
AutoCAD SHX Text
DINWIDDIE
AutoCAD SHX Text
GEORGE
AutoCAD SHX Text
PRINCE
AutoCAD SHX Text
POWHATAN
AutoCAD SHX Text
GOOCHLAND
AutoCAD SHX Text
CUMBERLAND
AutoCAD SHX Text
AMELIA
AutoCAD SHX Text
FLUVANNA
AutoCAD SHX Text
LOUISA
AutoCAD SHX Text
CHESTERFIELD
AutoCAD SHX Text
HENRICO
AutoCAD SHX Text
HANOVER
AutoCAD SHX Text
CAROLINE
AutoCAD SHX Text
GREENE
AutoCAD SHX Text
PAGE
AutoCAD SHX Text
SHENANDOAH
AutoCAD SHX Text
HIGHLAND
AutoCAD SHX Text
AUGUSTA
AutoCAD SHX Text
ROCKINGHAM
AutoCAD SHX Text
SPOTSYLVANIA
AutoCAD SHX Text
FAUQUIER
AutoCAD SHX Text
CULPEPER
AutoCAD SHX Text
MADISON
AutoCAD SHX Text
ORANGE
AutoCAD SHX Text
RAPPAHAN-
AutoCAD SHX Text
NOCK
AutoCAD SHX Text
STAFFORD
AutoCAD SHX Text
GEORGE
AutoCAD SHX Text
KING
AutoCAD SHX Text
PRINCE
AutoCAD SHX Text
WILLIAM
AutoCAD SHX Text
LOUDOUN
AutoCAD SHX Text
FREDERICK
AutoCAD SHX Text
WARREN
AutoCAD SHX Text
CLARKE
AutoCAD SHX Text
FAIRFAX
AutoCAD SHX Text
JAMES
AutoCAD SHX Text
GLOUCESTER
AutoCAD SHX Text
NORFOLK
AutoCAD SHX Text
CHESAPEAKE
AutoCAD SHX Text
HAMPTON
AutoCAD SHX Text
OF
AutoCAD SHX Text
WIGHT
AutoCAD SHX Text
SUFFOLK
AutoCAD SHX Text
ISLE
AutoCAD SHX Text
CITY
AutoCAD SHX Text
SURRY
AutoCAD SHX Text
YORK
AutoCAD SHX Text
NEWPORT
AutoCAD SHX Text
NEWS
AutoCAD SHX Text
VIRGINIA
AutoCAD SHX Text
BEACH
AutoCAD SHX Text
MATHEWS
AutoCAD SHX Text
MIDDLESEX
AutoCAD SHX Text
RICHMOND
AutoCAD SHX Text
ESSEX
AutoCAD SHX Text
LANCASTER
AutoCAD SHX Text
NORTHUMBERLAND
AutoCAD SHX Text
NORTHAMPTON
AutoCAD SHX Text
ACCOMACK
AutoCAD SHX Text
WESTMORELAND
GROUNDWATER MONITORING WELL
OBSERVATION WELL
NES WELL
PERFORMANCE WELL
SENTINEL WELL
EXTRACTION WELL
WETLANDS PIEZOMETER
PIEZOMETER
LANDFILL GAS PROBE
LFG EXTRACTION WELL WITH PUMP
LFG EXTRACTION WELL
SURFACE WATER MONITORING POINT
LEACHATE MONITORING POINT
BORE HOLE LOCATION
CORING LOCATION
SOIL SAMPLING LOCATION
TEST PIT LOCATION
BENCHMARK
SPRINGHEAD LOCATION
WELL LOCATION
CONTROL POINT
SYMBOLS
PROPERTY LINE / FACILITY BOUNDARY
EASEMENT
FENCE LINE
x
CONVENTIONAL SYMBOLS AND GENERAL NOTES
UTILITY POLE
HYDRANT
LIGHT POLE
TANK (SIZE VARIES)
TRANSFORMER
MANHOLE
CLEANOUT
OVERHEAD ELECTRIC OHE
UNDERGROUND ELECTRIC
OVERHEAD TELEPHONE
UNDERGROUND TELEPHONE
FORCEMAIN
SANITARY SEWER
PROCESS SEWER
RAILROAD
GUARDRAIL
NATURAL GAS
SOLID PIPE (TYPE NOTED)
PERFORATED PIPE (TYPE NOTED)
POTABLE WATER
RESOURCE PROTECTION AREA
RIGHT OF WAY
M
OHT
UGT UGT
PS
G
W
UGE UGE
PAVED ROAD
GRAVEL/DIRT ROAD
WASTE MANAGEMENT BOUNDARY
TREE LINE
SILT FENCE
EROSION AND SEDIMENT CONTROL FEATURES
FROM THE VIRGINIA STORMWATER MANAGEMENT CONTROL HANDBOOK
MAJOR TOPOGRAPHIC CONTOUR
MINOR TOPOGRAPHIC CONTOUR
GROUNDWATER SURFACE CONTOUR
(FT ABOVE MEAN SEA LEVEL)
SPOT ELEVATION
BEDROCK SURFACE CONTOUR
(FT ABOVE MEAN SEA LEVEL)
100 100
CULVERT (SIZE NOTED)
V-3VALVE LOCATION & IDENTIFICATION
CONDENSATE TRAP WITHOUT PUMP
STORMWATER PIPE OUTLET PROTECTION
DIVERSION
STORM WATER CONVEYANCE CHANNEL
IP INLET PROTECTION
PS PERMANENT SEEDING
DV
TEMPORARY SLOPE DRAIN
OP OUTLET PROTECTION
GENERAL EROSION AND SEDIMENT CONTROL NOTES:
ES-1 UNLESS OTHERWISE INDICATED, ALL VEGETATIVE AND STRUCTURAL EROSION AND SEDIMENT
CONTROL PRACTICES WILL BE CONSTRUCTED AND MAINTAINED ACCORDING TO MINIMUM
STANDARDS AND SPECIFICATIONS OF THE LATEST VERSION OF THE VIRGINIA STORMWATER
MANAGEMENT HANDBOOK AND VIRGINIA REGULATIONS 9VAC25-840-10, ET SEQ., EROSION AND
SEDIMENT CONTROL REGULATIONS.
ES-2: THE PLAN APPROVING AUTHORITY MUST BE NOTIFIED ONE WEEK PRIOR TO THE
PRE-CONSTRUCTION CONFERENCE, ONE WEEK PRIOR TO THE COMMENCEMENT OF LAND
DISTURBING ACTIVITY, AND ONE WEEK PRIOR TO THE FINAL INSPECTION.
ES-3: EROSION AND SEDIMENT CONTROL MEASURES ARE TO BE PLACED PRIOR TO OR AS THE FIRST
STEP IN CLEARING.
ES-4: A COPY OF THE APPROVED EROSION AND SEDIMENT CONTROL PLAN SHALL BE MAINTAINED ON
THE SITE AT ALL TIMES.
ES-5: PRIOR TO COMMENCING LAND DISTURBING ACTIVITIES IN AREAS OTHER THAN INDICATED ON THESE PLANS (INCLUDING, BUT NOT LIMITED TO, OFF-SITE BORROW AREAS), THE CONTRACTOR
SHALL SUBMIT A SUPPLEMENTARY EROSION CONTROL PLAN TO THE OWNER FOR REVIEW AND
APPROVAL BY THE PLAN APPROVING AUTHORITY.
ES-6: THE CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF ANY ADDITIONAL EROSION CONTROL
MEASURES NECESSARY AS DETERMINED BY THE PLAN APPROVING AUTHORITY.
ES-7: ALL DISTURBED AREAS ARE TO DRAIN TO APPROVED SEDIMENT CONTROL MEASURES AT ALL
TIMES UNTIL FINAL STABILIZATION IS ACHIEVED.
ES-8: DURING DEWATERING OPERATIONS, WATER WILL BE PUMPED INTO AN APPROVED FILTERING
DEVICE.
ES-9: THE CONTRACTOR SHALL INSPECT ALL EROSION CONTROL MEASURES PERIODICALLY AND AFTER EACH SIGNIFICANT RAINFALL EVENT. ANY NECESSARY REPAIRS OR CLEANUP TO MAINTAIN THE
EFFECTIVENESS OF THE EROSION CONTROL DEVICES SHALL BE MADE IMMEDIATELY.
TEMPORARY SEDIMENT TRAP
CT-1
CONDENSATE TRAP WITH PUMP CT/P-1
PASSIVE LFG VENT
SURVEY TIE LINE
SURFACE WATER
APPROXIMATE 100 YEAR FLOODPLAIN F/P
B-X
C-PCM-04
C-ECM-05
C-ECM-09
C-SCM-04
C-SSM-10
C-ECM-12
C-ECM-15
C-SCM-11
CIP CULVERT INLET PROTECTIONC-SCM-05
TEMPORARY SEDIMENT BASINC-SCM-12
CD ROCK CHECK DAMC-SCM-07
TEMPORARY STONE CONSTRUCTION ENTRANCEC-SCM-02CE
BM
EXISTING PROPOSED
V-3
CT-1
CT/P-1
LINES
EXISTING PROPOSED
x
OHE
OHT
UGT UGT
FM
PS
G
W
UGE UGE
CELL LIMITS
SSSS
FM
NAMENO.SYMBOL
WATER METER
VALVE
PIPE FITTINGS
WM WM
CO CO
SIGN
M
TP-X
DEMOLITION
PLAN-VIEW HATCHING
EXISTING PROPOSED
ASPHALT PAVEMENT
GRAVEL
CONCRETE
WETLANDS
PZ-X
PZ-X
GP-X
MW-X
MW-OW-X
MW-PW-X
MW-X
NES-OW-X
MW-OW-X
NES-OW-X
MW-PW-X
MW-X MW-X
EW-X EW-X
GV-X
SMP-X
LMP-X
GV-X
GW-X GW-X
C-X
CP
SS-X
S-X
PZ-X
PZ-X
GP-X
GWP-X GWP-X
SMP-X
LMP-X
BH-X
C-X
SS-X
R/WR/W
GW
BR
14.7014.70B
5SECTION CALL-OUT
SECTION NUMBER
DRAWING NUMBER WHERE
SECTION IS DRAWN
GENERAL NOTES:
1. THE PROJECT DRAWINGS HAVE BEEN PREPARED UTILIZING THE DRAWING SET TITLED "PITTSYLVANIA COUNTY
SANITARY LANDFILL, SOLID WASTE FACILITY PERMIT #571, PART B PERMIT APPLICATION MODIFICATION", DATED JULY 2023, PREPARED BY LABELLA ASSOCIATES AND EDITED TO REFLECT EXISTING CONDITIONS. LABELLA
ASSOCIATES ASSUMES NO RESPONSIBILITY FOR THE INFORMATION THAT REMAINS UNCHANGED.
2. EXISTING TOPOGRAPHIC DATA AND PROPERTY LINES SHOWN WITHIN THE MAPPING LIMITS, ARE FROM A TOPOGRAPHIC SURVEY MAP PREPARED BY SPATIAL DATA CONSULTANTS, INC. OF HIGH POINT, NC, PERFORMED
ON 9/30/2020, EXCEPT AS NOTED ON DRAWING NO. 3, EXISTING CONDITIONS.
3. TOPOGRAPHIC MAPPING CONDUCTED BY LABELLA ASSOCIATES, D.P.C., P.C. 1604 OWNBY LANE, RICHMOND VA, 23220 (804) 355-4520, ON 3/19/2026, WAS GENERATED FROM LOW-ALTITUDE PHOTOGRAMMETRIC STUDY
METHODS, IN GENERAL CONFORMANCE WITH INDUSTRY BEST PRACTICES. THE COLLECTION OF
THREE-DIMENSIONAL DATA AND DEVELOPMENT OF MAPPING INFORMATION IS COMPLETED IN A MANNER THAT MEETS OR EXCEEDS THE PRECISION OF TRADITIONAL FIELD SURVEY METHODS, BUT IS NOT INTENDED TO REPRESENT OR SUBSTITUTE FOR MAPPING PREPARED BY A PROFESSIONAL LICENSED SURVEYOR. ALL TOPOGRAPHIC INFORMATION SHOULD BE VERIFIED BY METHODS ENDORSED BY THE NATIONAL COUNCIL OF EXAMINERS FOR ENGINEERING AND SURVEYING. ANY DETERMINATION OF TOPOGRAPHY OR CONTOURS, OR ANY DEPICTION OF PHYSICAL IMPROVEMENTS, PROPERTY LINES OR BOUNDARIES IS FOR GENERAL INFORMATION ONLY AND SHALL NOT BE USED FOR THE DESIGN, MODIFICATION, OR CONSTRUCTION OF
IMPROVEMENTS TO REAL PROPERTY OR FOR FLOOD PLAIN DETERMINATION.
4. TOPOGRAPHIC CONTOUR INTERVAL = 2 FEET, UNLESS INDICATED OTHERWISE.
5. THE CONTRACTOR SHALL PROTECT STRUCTURES AND APPURTENANCES INCLUDING BUT NOT NECESSARILY LIMITED TO WELLS, DRAINAGE STRUCTURES, PROPERTY CORNERS, ETC. THE CONTRACTOR WILL BE REQUIRED
TO REPAIR ANY DAMAGES AT NO EXPENSE TO THE OWNER.
6. THE CONTRACTOR SHALL CONTACT MISS UTILITY, AT 1-800-552-7001, A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION AND SHALL COMPLY WITH ALL PROVISIONS OF THE VIRGINIA UNDERGROUND UTILITY DAMAGE
PREVENTION ACT.
BENCHMARKS:
NORTHING EASTING ELEVATION DESCRIPTION
BM-01 3438812.174 11215356.090 699.36 CAPPED REBAR
BM-04 3441023.771 11217382.931 689.68 CAPPED REBAR
BM-06 3439601.629 11216291.732 718.23 CAPPED REBAR
4 23
ADETAIL NUMBER
DRAWING NUMBER WHERE
DETAIL IS FIRST REFERENCED
DRAWING NUMBER WHERE
DETAIL IS DRAWN
DETAIL CALL-OUT
SF
LIMITS OF WASTE
SOIL STABILIZATION BLANKETS AND MATTINGC-SSM-05
SLD
SCC
ST
SB
SB
TEMPORARY DIVERSION DIKEC-ECM-04DD
JTG/DAS
JBM
DRAWING NAME:
DRAWING NUMBER:
DATE:
ISSUED FOR:
DRAWN BY:
REVIEWED BY:
PROJECT NUMBER:
© 2026 LaBella Associates
Pittsylvania County PO Box 426, 1 Center Street, Chatham, Virginia
Pittsylvania County Sanitary Landfill Phase 3 Construction 382 Rainbow Lane, Dry Fork, Virginia, 24549
2253619
BID
4/20/2026
1604 Ownby Lane Richmond, VA 23220 804-355-4520 labellapc.com
A pr
0,
- 3
:3 4p m \\c as h.
la b\ u\ Le ga cy
\R
IC
\C
AD
D \L
AN
D
PR
O
JE
C
TS
\P itt sy lv an ia
\2
Ph as e
C el l D
\C ur re nt
W or ki ng
D ra w in gs \P lo t S he et s\
G en er al
N ot es a nd L eg en d.
dw g La yo ut
=G en er al
N ot es a nd L eg en d
Revisions
NO: DATE: DESCRIPTION:
GENERAL NOTES
AND LEGEND
W
F/P F/P F/P
F/P
F/P
F/P
F/P
F/ P
F/P F/P
F/P
F/P
F/P
F/P
F/P
F/P
F/P
F/P
F/P
F/P
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
G G
G G
G G
MW-1A
MW-101
MW-109A
MW-102
MW-104A
MW-108
MW-109A NES
MW-103
MW-105
GP-7
GP-9
GP-10
GP-11
GP-13
GP-14
MW-109C
MW-109B(D)
PZ-8
PZ-7
PZ-10
PZ-9
GP-12
MW-109B(S)
GP-15
M
BORROW
AREA
SEDIMENT
BASIN
50' GAS LINE EASEMENT
100' TRANSMISSION LINE EASEMENT
SEDIMENT
BASIN
CELL D
FUTURE
CELL E
FUTURE
CELL F
TOPOGRAPHIC MAPPING SHOWN WITHIN
THIS LINE WAS GENERATED FROM
LOW-ALTITUDE PHOTOGRAMMETRIC
STUDY METHODS CONDUCTED BY
LABELLA ASSOCIATES, D.P.C., P.C., ON
3/19/2026
100 YEAR FLOODPLAIN
WASTE MANAGEMENT BOUNDARY
CEMETERY
BORROW
AREA
BORROW
AREA
LEACHATE POND
PROPERTY LINE
PHASE 2
CELL C2
PHASE 2
CELL C1
PHASE 2
CELL B
PHASE 2
CELL A
EXISTING CONDITIONS
JTG/DAS
JBM
DRAWING NAME:
DRAWING NUMBER:
DATE:
ISSUED FOR:
DRAWN BY:
REVIEWED BY:
PROJECT NUMBER:
© 2026 LaBella Associates
Pittsylvania County PO Box 426, 1 Center Street, Chatham, Virginia
Pittsylvania County Sanitary Landfill Phase 3 Construction 382 Rainbow Lane, Dry Fork, Virginia, 24549
2253619
BID
4/20/2026
1604 Ownby Lane Richmond, VA 23220 804-355-4520 labellapc.com
A pr
0,
- 3
:3 4p m \\c as h.
la b\ u\ Le ga cy
\R
IC
\C
AD
D \L
AN
D
PR
O
JE
C
TS
\P itt sy lv an ia
\2
Ph as e
C el l D
\C ur re nt
W or ki ng
D ra w in gs \P lo t S he et s\
Ex is tin g
C on di tio ns .d w g
La yo ut =E xi st in g
C on di tio ns
(FEET)
GRAPHIC SCALE
20010050
NOTES:
1. EXISTING TOPOGRAPHIC DATA AND PROPERTY LINES SHOWN WITHIN THE
MAPPING LIMITS, ARE FROM A TOPOGRAPHIC MAPPING CONDUCTED BY
LABELLA ASSOCIATES PERFORMED ON 9/30/2020, EXCEPT AS NOTED ON
DRAWING NO. 3, EXISTING CONDITIONS.
Revisions
NO: DATE: DESCRIPTION:
F/P
F/P
F/P
F/P
F/ P
F/P F/P
F/P
F/P
F/P
F/P
F/P
F/P
F/P
F/P
F/P
F/P
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
G G
G G
G G
MW-1A
MW-101
MW-109A
MW-102
MW-104A
MW-108
MW-109A NES
MW-103
MW-105
GP-9
GP-10
GP-11
GP-13
GP-14
MW-109C
MW-109B(D)
PZ-8
PZ-7
PZ-10
PZ-9
GP-12
MW-109B(S)
GP-15
M
600600
66066
66066
067067
68068
700700
700700
700700
CELL D
FUTURE
CELL E
PHASE 3
SEDIMENT
BASIN
LIMITS OF WASTE
EXISTING LIMITS OF WASTE
EXISTING CELL LIMITS
WASTE MANAGEMENT BOUNDARY
LEACHATE POND
SEDIMENT
BASIN
4 8 E
ACCESS ROAD 4 8
B
LIMITS OF GRADING
FUTURE
CELL F
FM
FM
FM
FM
FM
FM
FM
FM
10'
DD
DD
CULVERT C-3
24" RCP
INV IN = 640
INV OUT = 624
LENGTH = 150'
TEMPORARY CULVERT
24" HDPE OR CMP
INV IN = 662
INV OUT = 652
LENGTH = 126'
CULVERT C-2
2-30" RCP
INV IN = 652
INV OUT = 648
LENGTH = 60'
48" RISER'
NOTE:
BASE GRADES IN FUTURE CELL E SHOWN FOR
REFERENCE ONLY, CONTRACTOR SHALL GRADE TO
TWO (2) FEET ABOVE THE CELL E BASE GRADE,
SEED, AND STABILIZE IN ACCORDANCE WITH VSMH.
PHASE 2
CELL C2
PHASE 2
CELL C1
PHASE 2
CELL B
PHASE 2
CELL A
CEMETERY
CELL D BASE GRADES
(FEET)
GRAPHIC SCALE
20010050
JTG/DAS
JBM
DRAWING NAME:
DRAWING NUMBER:
DATE:
ISSUED FOR:
DRAWN BY:
REVIEWED BY:
PROJECT NUMBER:
© 2026 LaBella Associates
Pittsylvania County PO Box 426, 1 Center Street, Chatham, Virginia
Pittsylvania County Sanitary Landfill Phase 3 Construction 382 Rainbow Lane, Dry Fork, Virginia, 24549
2253619
BID
4/20/2026
1604 Ownby Lane Richmond, VA 23220 804-355-4520 labellapc.com
A pr
0,
- 3
:3 4p m \\c as h.
la b\ u\ Le ga cy
\R
IC
\C
AD
D \L
AN
D
PR
O
JE
C
TS
\P itt sy lv an ia
\2
Ph as e
C el l D
\C ur re nt
W or ki ng
D ra w in gs \P lo t S he et s\
C el l D B as e
G ra de s.
dw g
La yo ut =C el l D
B as e G ra de s
NOTES:
1. PROPOSED CONTOURS WITHIN LIMITS OF LINER REPRESENT TOP OF
PREPARED SUBGRADE.
2. ALL DISTURBED SLOPES SHALL BE COVERED WITH SOIL STABILAZTION
BLANKET.
· TREATMENT 1 (EC-2) FOR SLOPES SHALLOWER THAN 3:1.
· TREATMENT 2 (EC-3) FOR SLOPES 3:1 AND STEEPER.
3. BASE GRADES IN FUTURE CELL E SHOWN FOR REFERENCE ONLY,
CONTRACTOR SHALL GRADE TO TWO (2) FEET ABOVE THE CELL E BASE
GRADE, SEED, AND STABILIZE IN ACCORDANCE WITH VSMH.
F/P
F/P
F/P
F/P
F/ P
F/P F/P
F/P
F/P
F/P
F/P
F/P
F/P
F/P
F/P
F/P
F/P
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
O
HE
G G
G G
G G
MW-1A
MW-101
MW-109A
MW-102
MW-104A
MW-108
MW-109A NES
MW-103
MW-105
GP-9
GP-10
GP-11
GP-13
GP-14
MW-109C
MW-109B(D)
PZ-8
PZ-7
PZ-10
PZ-9
GP-12
MW-109B(S)
GP-15
CO
COCO
CO
CO
CO
CO
CO
CO
CO
M
CELL D
PHASE 3
SEDIMENT
BASIN
LIMITS OF WASTE
EXISTING LIMITS OF WASTE
EXISTING CELL LIMITS
LINER TERMINATION AT
INTERIOR CELL LIMITS
WASTE MANAGEMENT BOUNDARY
LEACHATE POND
5 7 A
CO
FM
FM
FM
FM
FM
FM
FM
FM
CO
CO
CO
CO
5 8
CCLEANOUT
LEACHATE SUMP AND
SIDE SLOPE RISER
5 9 A
5 9 C
PERFORATED
LEACHATE
COLLECTION PIPING
5 8 D
CELL E
LINER TIE-IN AT
INTERIOR CELL LIMITS5 9
D
5 9
ETYPICAL LINER
ANCHOR TRENCH
5 8
FFORCE MAIN
SCHEMATIC
10' STUB w/ END CAP FOR FUTURE
TANK CONNECTION
LAGOON LINER PENETRATION w/ BOOT
WELDED TO LINER (FIELD LOCATE)
PHASE 2
CELL A
PHASE 2
CELL B
PHASE 2
CELL C1
PHASE 2
CELL C2
ENGINEERING MODIFICATION
GRADES
(FEET)
GRAPHIC SCALE
20010050
JTG/DAS
JBM
DRAWING NAME:
DRAWING NUMBER:
DATE:
ISSUED FOR:
DRAWN BY:
REVIEWED BY:
PROJECT NUMBER:
© 2026 LaBella Associates
Pittsylvania County PO Box 426, 1 Center Street, Chatham, Virginia
Pittsylvania County Sanitary Landfill Phase 3 Construction 382 Rainbow Lane, Dry Fork, Virginia, 24549
2253619
BID
4/20/2026
1604 Ownby Lane Richmond, VA 23220 804-355-4520 labellapc.com
A pr
0,
- 3
:3 4p m \\c as h.
la b\ u\ Le ga cy
\R
IC
\C
AD
D \L
AN
D
PR
O
JE
C
TS
\P itt sy lv an ia
\2
Ph as e
C el l D
\C ur re nt
W or ki ng
D ra w in gs \P lo t S he et s\
En gi ne er in g
M od ifi ca tio n
G ra de s.
dw g
La yo ut =L ea ch at e
C ol le ct io n
Pl an
NOTES:
1. PROPOSED CONTOURS WITHIN LIMITS OF LINER REPRESENT TOP OF
PREPARED SUBGRADE.
2. ALL DISTURBED SLOPES SHALL BE COVERED WITH SOIL STABILAZTION
BLANKET.
· TREATMENT 1 (EC-2) FOR SLOPES SHALLOWER THAN 3:1.
· TREATMENT 2 (EC-3) FOR SLOPES 3:1 AND STEEPER.
MW-10
GP-9
GP-10
GP-11GP-13
GP-14
PZ-9
GP-12
FM
FM
FM
FM
FM
FM
FM
FM
DD
OP
IP
OP
IP
0+00 1+00
2+00
3+00 4+00
5+00
6+00
7+00
8+00 9+00 10+00 11+00 12+00 13+00 14+00
15+00
16+00
16+76
660660
OP
4 8 B
CELL D
FUTURE
CELL E
FUTURE
CELL F
PHASE 3
SEDIMENT BASIN
CELL LIMITS
LEACHATE POND
CULVERT C-3
24" RCP
INV IN = 640
INV OUT = 624
LENGTH = 150'
TEMPORARY CULVERT
24" HDPE OR CMP
INV IN = 662
INV OUT = 652
LENGTH = 126'
CULVERT C-2
2-30" RCP
INV IN = 652
INV OUT = 648
LENGTH = 60'
ACCESS ROAD
48" RISER'
STA 0+00
TIE IN TO EXISTING
PERIMETER ACCESS ROAD
STA 16+75
TERMINATE ROAD WITH 10 L.F.
MINIMUM GEOTEXTILE FOLDED
AND COVERED WITH STONE FOR
FUTURE ROAD TIE-IN
1+00 2+00 3+00 4+00 5+00 6+00 7+00 8+00 9+00 10+00 11+00 12+00 13+00 14+00 15+00 16+00
-0.65% -0.96%
-0.26% 1.63%
2.56%
4 8 B
2' MIN. COVER (TYP)
CULVERT C-2
2-30" RCP
INV IN = 652
INV OUT = 648
LENGTH = 60'
TEMPORARY CULVERT
24" HDPE OR CMP
INV IN = 662
INV OUT = 652
LENGTH = 126'
STA 0+00
TIE IN TO EXISTING
PERIMETER ACCESS ROAD
EXISTING GRADE
STA 16+75
TERMINATE ROAD WITH 10 L.F.
MINIMUM GEOTEXTILE FOLDED
AND COVERED WITH STONE
FOR FUTURE ROAD TIE-INACCESS ROAD AT
CENTERLINE
(FEET)
GRAPHIC SCALE
1206030
ACCESS ROAD
PLAN AND PROFILE
JTG/DAS
JBM
DRAWING NAME:
DRAWING NUMBER:
DATE:
ISSUED FOR:
DRAWN BY:
REVIEWED BY:
PROJECT NUMBER:
© 2026 LaBella Associates
Pittsylvania County PO Box 426, 1 Center Street, Chatham, Virginia
Pittsylvania County Sanitary Landfill Phase 3 Construction 382 Rainbow Lane, Dry Fork, Virginia, 24549
2253619
BID
4/20/2026
1604 Ownby Lane Richmond, VA 23220 804-355-4520 labellapc.com
A pr
0,
- 3
:3 4p m \\c as h.
la b\ u\ Le ga cy
\R
IC
\C
AD
D \L
AN
D
PR
O
JE
C
TS
\P itt sy lv an ia
\2
Ph as e
C el l D
\C ur re nt
W or ki ng
D ra w in gs \P lo t S he et s\
PH
A cc es s
R oa d pr of ile
.d w g La yo ut
=P H
A cc es s R oa d pr of ile
NOTES:
1. ACCESS ROAD GRADE REPRESENTS TOP OF STONE PAVING.
2. MAINTAIN 2.0' COVER, MIN. OVER STORMWATER CULVERTS. CONTRACTOR
MAY USE STONE TO INCREASE COVER , BUT THE ROADWAY SHALL BE
TAPERED SMOOTHLY TO MEET THE DESIGN GRADES.
3. TIE-IN TO EXISTING ROADS SHALL PRODUCE A SMOOTH TRANSITION.
4. NOTIFY THE ENGINEER IF THERE ARE ANY CONDITIONS THAT ARE NOT IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS.
ACCESS ROAD PROFILE
SCALE: HORIZONTAL 1" = 60'
VERTICAL: 1" = 12'
ACCESS ROAD PLAN
SCALE: 1" = 60'
SECTION B-B
N.T.S.
8'-0"
6" (TYP)
N.T.S.
ELEVATION D-D
N.T.S.
D
D
1" THICK x 18" DIA.
PERFORATED HDPE
END PLATE
6" (TYP)
PERFORATION DETAIL
FOR HDPE SIDE SLOPE RISER
POWER AND
CONTROL
CONDUIT
A
B
B
VA
R
IE
S:
VARIES:1
A
PLAN VIEW
SECTION A-A
N.T.S.
B
B
10'-0"
TO LEACHATE TANK/POND
TO LEACHATE TANK/POND
3:1
3/8" DIA. HOLES
12" CONTROLLED
SUBGRADE
10' MIN.
NOTE:
ONE OF THE TWO 18" Ø RISER PIPES INSTALLED IS
TO BE RESERVED FOR EMERGENCY USE. A SUMP
PUMP IS TO BE INSTALLED ONLY IN THE RISER PIPE
USED ON A REGULAR BASIS.
VA
R
IE
S:
LEACHATE COLLECTION SUMP INFORMATION
SUMP ID BOTTOM
ELEVATION
DEPTH
(FT)
APPROX. LIQUID
VOLUME (FT3)
PUMP ON
ELEVATION
PUMP OFF
ELEVATION
CELL D - SUMP 2 640 2 911 640.8 641.0
10'
VARIES SEE GRADING PLAN
12" INTERMEDIATE COVER
24" SOIL COVER /
VEGETATIVE
SUPPORT LAYER
GCL
40 MIL. TEXTURED LLDPE
GEOCOMPOSITE
12" CONTROLLED SUBGRADE
BASE GRADE
40 MIL. TEXTURED LLDPE
GEOCOMPOSITE
7 7 B
7 7 B
N.T.S.
LEACHATE SUMP
SIDE SLOPE RISER 5 7
A
HDPE RUB SHEET
VA
R
IE
S
SE
E
G R
AD
IN
G P
LA
N
1'-6"
GCL
60 MIL HDPE TEXTURED
GEOMEMBRANE
16 OZ/SY GEOTEXTILE
DRAINAGE LAYER
K > 0.3 CM/SEC
18" DIA. SDR-17
SIDE SLOPE RISER
8'-0"
ANCHOR TRENCH w/
COMPACTED BACKFILL
4x8 DUAL CONTAINMENT
FORCE MAIN
GCL
60 MIL HDPE TEXTURED
GEOMEMBRANE
16 OZ/SY GEOTEXTILE
TURN DOWN
GEOCOMPOSITE
DRAINAGE LAYER INTO
EXISTING WASTE LAYER
SUMP PUMP
10' x 3' x 3/8" HDPE FRICTION
PAD UNDER EACH
PERFORATED SUMP
GCL
60 MIL HDPE TEXTURED
GEOMEMBRANE
16 OZ/SY GEOTEXTILE
VARIES
GCL
60 MIL HDPE TEXTURED
GEOMEMBRANE
16 OZ/SY GEOTEXTILE
1" THICK x 18" DIA. PERFORATED HDPE END
PLATE, EXTRUSION WELDED TO END OF PIPE
18" DRAINAGE LAYER
K > 0.3 CM/SEC
18" DIA. x 8' PERFORATED
HORIZONTAL SECTION OF
HDPE PIPE
18" DIA. SDR-17 SOLID HDPE
SIDE SLOPE RISER
WASTE
BASE GRADE
2" DIA. SUMP PUMP FLEXIBLE
PIPING DISCHARGE LINE
GEOMEMBRANE RUB SHEET
BASE GRADE
BOLTED BLIND FLANGE w/ S.S.
HARDWARE
MIN. 36" DIA. SDR-17 HDPE 4'
TALL VALVE VAULT WITH LID
PITLESS ADAPTER
18" DIA. SDR-17 HDPE SOLID
WALL SIDE SLOPE RISER
POWER AND
CONTROL CABLES
2" DIA. SUMP PUMP
FLEXIBLE PIPING
DISCHARGE LINE
(WHEN NEEDED)
2" DIA. SUMP PUMP
FLEXIBLE PIPING
DISCHARGE LINE
7 7 B 18" DIA. x 8' PERFORATED
HORIZONTAL SECTION OF
HDPE PIPE
10' x 3' x 3/8" HDPE FRICTION
PAD UNDER EACH
PERFORATED SUMP
SUMP LINED WITH 60 MIL HDPE
TEXTURED GEOMEMBRANE
ELEVATION
DROP = 2'
PUMP CONTROL PANEL
4x8 DUAL CONTAINMENT
FORCE MAIN
10' x 20' 6" THICK
CONC. SLAB
EYEBOLT (TYP)
1/4" STAINLESS STEEL
PULL CABLE
2 - 90° ELBOWS
MIN. 36" DIA. SDR-17
HDPE 4' TALL VALVE
VAULT WITH LID
BALL VALVE WITH
EXTENSION HANDLE
CHECK VALVE
PADDLE WHEEL
FLOW METER
PITLESS ADAPTER
POWER AND CONTROL
CONDUIT
GCL
GEOCOMPOSITE
EYEBOLT (TYP)
1/4" STAINLESS STEEL
PULL CABLE
BASE
GRADE
JTG/DAS
JBM
DRAWING NAME:
DRAWING NUMBER:
DATE:
ISSUED FOR:
DRAWN BY:
REVIEWED BY:
PROJECT NUMBER:
© 2026 LaBella Associates
Pittsylvania County PO Box 426, 1 Center Street, Chatham, Virginia
Pittsylvania County Sanitary Landfill Phase 3 Construction 382 Rainbow Lane, Dry Fork, Virginia, 24549
2253619
BID
4/20/2026
1604 Ownby Lane Richmond, VA 23220 804-355-4520 labellapc.com
A pr
0,
- 3
:3 4p m \\c as h.
la b\ u\ Le ga cy
\R
IC
\C
AD
D \L
AN
D
PR
O
JE
C
TS
\P itt sy lv an ia
\2
Ph as e
C el l D
\C ur re nt
W or ki ng
D ra w in gs \P lo t S he et s\
LE
AC
H
AT
E C
O
LL
EC
TI
O N
S
YS
TE
M
D
ET
AI
LS
.d w g La yo ut
=L
EA
C H
AT
E
C O
LL
EC
TI
O
N S
YS
TE
M D
ET
AI
LS
LEACHATE COLLECTION
SYSTEM DETAILS
SECTION A - A
A
A
PERFORATED LEACHATE COLLECTION HEADER PIPE DETAIL
N.T.S.
6"
(TYP)
1.0'
LI
M
IT
S O
F
LI
N
ER
2.0'
6" SOLID PIPE
N.T.S.
CLEAN-OUT DETAIL
12' INTERMEDIATE COVER
GEOTEXTILE
TYPICAL ACCESS ROAD
N.T.S.
30'-0"
12" AGGREGATE (VDOT #21, #21A, OR
CRUSHED CONCRETE)
2% SLOPE TOWARDS DITCH
12" MIN.
3" MIN BEDDING
BACKFILL
4x8 DUAL CONTAINMENT PIPE
SDR 11 HDPE CARRIER
SDR 17 HDPE CONTAINMENT
SELECT BACKFILL
1' MIN TYP.
36" MIN.
SEDIMENT CLEANOUT POINT
67 C.Y./ AC.
RISER CREST
MIN. 1.0'
DESIGN HIGH WATER
67 C.Y./ AC.
MIN. 1.0'
TO 34 C.Y./ ACRE)
DRY STORAGE
WET STORAGE
0.5'
(WET STORAGE REDUCED
(25-YR. STORM ELEV.)
SEDIMENT BASIN SB-2
DRAINAGE AREA (AC) 55.8
WET STORAGE VOLUME REQUIRED (CY) 3,744
WET STORAGE VOLUME PROVIDED (CY) 17,592
DRY STORAGE VOLUME REQUIRED (CY) 3,744
DRY STORAGE VOLUME PROVIDED (CY) 7,407
BOTTOM ELEVATION 640
RISER CREST ELEVATION 650
DEWATERING DEVICE ELEVATION 647
EMERGENCY SPILLWAY ELEVATION 652
25-YEAR STORM ELEVATION 650.79
TOP OF DAM ELEVATION 654
RISER DIAMETER 48"
DEWATERING DEVICE DIAMETER 8"
ANTI-VORTEX DIAMETER 84"
BARREL DIAMETER 24"
BARREL LENGTH 121'
BARREL INVERT IN 640
BARREL INVERT OUT 634
SEDIMENT BASIN SCHEMATIC ELEVATIONS
N.T.S.
18" DRAINAGE LAYER
0.3 CM/S MIN.
GEOMEMBRANE
GCL
CONTROLLED SUBGRADE
5 8 A
4 8 B
5 8 D
4 8 E
5 8 C
OUTFALL BARREL
CREST OF EMERGENCY
SPILLWAY
DEWATERING
DEVICE
N.T.S.
FORCE MAIN SCHEMATIC
5 8 F
10' STUB w/ END CAP FOR
FUTURE TANK CONNECTION
4x8 HDPE DUAL CONTAINMENT WYE
OPEN LAGOON DISCHARGE
LAGOON LINER PENETRATION
w/ BOOT WELDED TO LINER
(FIELD LOCATE)
FR
O
M C
EL
L
D
SU
M P
PU
M
P
4x8 HDPE DUAL
CONTAINMENT FORCE MAIN
4x8 HDPE DUAL
CONTAINMENT FORCE MAIN
BACKFLOW
PREVENTER
10' STUB w/ END CAP FOR
FUTURE CELL F CONNECTION
CONTRACTOR MAY USE FITTINGS OR
GRADUAL BENDS TO ADJUST ALIGNMENT
FORCE MAIN NOTES:
1. SCHEMATIC IS PROVIDED TO ILLUSTRATE KEY FEATURES OF THE FORCE
MAIN. SEE PLAN FOR FORCE MAIN ALIGNMENT.
2. THE CONTRACTOR MAY MAKE CHANGES IN ALIGNMENT USING FITTINGS OR
GRADUAL BENDS.
3. CONTRACTOR SHALL SUBMIT A FORCE MAIN LAYOUT AND TESTING PLAN
TO THE ENGINEER FOR REVIEW AND ACCEPTANCE.
4. GATE VALVES AND BACKFLOW PREVENTERS SHALL BE INSTALLED IN
VALVE BOXES WITH MINIMUM DIMENSIONS 36"x48"x30" DEEP.
5. INDIVIDUAL VALVES SHALL BE SUITABLE FOR BURIED INSTALLATION AND
SHALL BE INSTALLED WITH A CURB BOX AT GRADE, A 1" OPERATING NUT,
AND AN EXTENSION STEM.
6. TRACER WIRE SHALL BE INSTALLED IN THE TRENCH NEXT TO THE FORCE
MAIN, WITH TEST STATIONS AS INDICATED ON THE SCHEMATIC AT A
MINIMUM.
7. TRACER WIRE CONTINUITY SHALL BE TESTED IN THE PRESENCE OF THE
ENGINEER OR REPRESENTATIVE.
8. INSTALL PASSIVE LOCATOR BALL AT ALL BURIED TERMINATIONS, MODEL
1404-XR AS MANUFACTURED BY 3M, OR EQUAL.
BACKFLOW
PREVENTER
PASSIVE LOCATOR BALL
PASSIVE LOCATOR BALL
TS
CONTINUITY TEST STATION , TYP.
TS
TS
4" GATE VALVE (N.O.)
4" GATE VALVE (N.C.)
THREADED PLUG
BACKFILL FOR PIPE SUPPORT
18" LOCAL SOIL
(UNSPECIFIED PERMEABILITY)
WOVEN GEOTEXTILE FABRIC
8" DIA. HDPE SDR 17 PIPE
ALL HOLES 1/4" DIA. AT 6"
CENTER/CENTER
N.T.S.
LEACHATE FORCE MAIN DETAIL
MISCELLANEOUS DETAILS
JTG/DAS
JBM
DRAWING NAME:
DRAWING NUMBER:
DATE:
ISSUED FOR:
DRAWN BY:
REVIEWED BY:
PROJECT NUMBER:
© 2026 LaBella Associates
Pittsylvania County PO Box 426, 1 Center Street, Chatham, Virginia
Pittsylvania County Sanitary Landfill Phase 3 Construction 382 Rainbow Lane, Dry Fork, Virginia, 24549
2253619
BID
4/20/2026
1604 Ownby Lane Richmond, VA 23220 804-355-4520 labellapc.com
A pr
0,
- 3
:3 5p m \\c as h.
la b\ u\ Le ga cy
\R
IC
\C
AD
D \L
AN
D
PR
O
JE
C
TS
\P itt sy lv an ia
\2
Ph as e
C el l D
\C ur re nt
W or ki ng
D ra w in gs \P lo t S he et s\
M
IS
C D
ET
AI
LS
M
IS
C D
ET
AI
LS
.d w g
La yo ut =M
IS
C
D
ET
AI
LS
Revisions
NO: DATE: DESCRIPTION:
AutoCAD SHX Text 60°
AutoCAD SHX Text 60°
120°
18" DRAINAGE LAYER
K > 0.3 CM/SEC 16 OZ/SY
GEOTEXTILE
60 MIL. TEXTURED
HDPE
12" CONTROLLED SUBGRADE
N.T.S.
LINER DETAIL
GCL
LAY PLYWOOD OVER END OF LINER
18" MIN.
HDPE LEACHATE COLLECTION PIPE
16 OZ/SY GEOTEXTILE
LIMITS OF LINER
LEACHATE FLOW
N.T.S.
12" MIN.
TEMPORARY END CAP
EXISTING 60 MIL HDPE GEOMEMBRANE
NOTE:
REMOVE PLYWOOD AND WELD FUTURE CELL
LINER TO THE EXISTING LINER AND OVERLAP
GEOTEXTILES BY A MINIMUM OF 12".
LEACHATE FLOW
EXISTING
LINER
FUTURE
LINER
LINER TIE-IN AT
INTERIOR CELL LIMITS
LINER TERMINATION AT
INTERIOR CELL LIMITS
WASTE
TEMPORARY COMPACTED
EARTH BERM
10'8'
10'
EXTEND BASE GRADES 10' MIN
FROM LIMITS OF LINER
CELL LIMITS
18" DRAINAGE LAYER
K > 0.3 CM/SEC
EXISTING 18" DRAINAGE
LAYER K > 0.3 CM/SEC
18" DRAINAGE LAYER
K > 0.3 CM/SEC
N.T.S.
BASE GRADE
VARIES AS
INDICATED ON
DRAWINGS
EXISTING CONTROLLED
SUBGRADE
EXISTING REMOVABLE END CAP
16 OZ/SY
GEOTEXTILE
GEOMEMBRANE
BASE GRADE
SOIL LINER OR GCL /
CONTROLLED SUBGRADE
TEMPORARY RAIN FLAP
N.T.S.
HEIGHT VARIES
(2 FT. TO 5 FT.)
GEOMEMBRANE RAIN FLAP
COMPACTED SUBGRADE
MIN. 2' OVERLAPMIN. 2' OVERLAP
TEMPORARY
END CAP12" MIN.
EXTRUSION WELD
18" DRAINAGE LAYER
K > 0.3 CM/SEC
18" DRAINAGE LAYER
K > 0.3 CM/SEC
TEMPORARY
END CAP
LEACHATE PIPE
CONNECTOR SLEEVE
(TO BE CONNECTED
AFTER RAIN FLAP IS
REMOVED)
NOTE:
CONTRACTOR TO STORE LEACHATE
PIPE CONNECTOR SLEEVE UP
GRADE FROM RAIN FLAP
LINER ON SLOPES
GEOMEMBRANE
GCL
12" CONTROLLED SUBGRADE
GCL
5 9 A
5 9 C
5 9 B
23 9 E
4 9 D
LEACHATE
COLLECTION PIPE
TYPICAL LINER
ANCHOR TRENCH 5 9
E
16 OZ/SY GEOTEXTILE
1'
12" CONTROLLED
SUBGRADE
18" DRAINAGE LAYER K > 0.3 CM/SEC
2' MIN.
18" DRAINAGE LAYER
K > 0.3 CM/SEC
12" CONTROLLED SUBGRADE
BASE GRADE
16 OZ/SY GEOTEXTILE
60 MIL TEXTURED HDPE
GEOMEMBRANE
GCL
60 MIL TEXTURED HDPE GEOMEMBRANE
GCL
1' MIN.
COMPACTED
STRUCTURAL FILL
CONNECT TO
EXISTING LEACHATE
PIPE & EXTEND
12" MIN.
OVERLAP
EXISTING
LEACHATE PIPING
EXISTING GEOTEXTILE
EXISTING GEOMEMBRANE
EXISTING GCL
EXISTING PLYWOOD
OVER END OF LINER
WELD GEOMEMBRANE
TO EXISTING GEOMEMBRANE
16 OZ/SY GEOTEXTILE
LEACHATE PIPING
60 MIL HDPE
GEOMEMBRANE
GCL
12" CONTROLLED
SUBGRADE
Revisions
NO: DATE: DESCRIPTION:
LINER DETAILS
JTG/DAS
JBM
DRAWING NAME:
DRAWING NUMBER:
DATE:
ISSUED FOR:
DRAWN BY:
REVIEWED BY:
PROJECT NUMBER:
© 2026 LaBella Associates
Pittsylvania County PO Box 426, 1 Center Street, Chatham, Virginia
Pittsylvania County Sanitary Landfill Phase 3 Construction 382 Rainbow Lane, Dry Fork, Virginia, 24549
2253619
BID
4/20/2026
1604 Ownby Lane Richmond, VA 23220 804-355-4520 labellapc.com
A pr
0,
- 3
:3 4p m \\c as h.
la b\ u\ Le ga cy
\R
IC
\C
AD
D \L
AN
D
PR
O
JE
C
TS
\P itt sy lv an ia
\2
Ph as e
C el l D
\C ur re nt
W or ki ng
D ra w in gs \P lo t S he et s\
LI
N
ER
D
ET
AI
LS
.d w g
La yo ut =L
IN
ER
D
ET
AI
LS
3dodo
PLAN VIEW
A
A
(MIN.)
KEY IN 6"-9"; RECOMMENDED FOR ENTIRE PERIMETER
d aL
SECTION A-A
0%
N.T.S.
D
S1 S2
LINER
FINAL COVER
FINAL COVER
EC LINED
DIVERSION
BERM
DIVERSION
BERM CORRUGATED HDPE
SLOPE DRAIN
FLARED
END
SECTION
OUTLET PROTECTION NOTES:
1. APRON LINING MAY BE RIPRAP,
GROUTED RIPRAP, GABION BASKET,
OR CONCRETE. GEOTEXTILE FABRIC
SHALL BE A WOVEN MATERIAL
2. FILTER CLOTH SHALL BE 6OZ./SQ.YD.
WOVEN GEOTEXTILE MEETING THE
MINIMUM REQUIREMENTS OF VSMH
TABLE C-ECM-13-6, INCLUDING BUT
NOT LIMITED TO:
CULVERT OUTLET PROTECTION OP
SCC
PERMANENT SLOPE DRAIN PSD
STORMWATER CONVEYANCE
CHANNEL
N.T.S.
N.T.S.
CROSS OR TEE
W/ FLARED END
SECTION
SCC SCHEDULE
SCC NO. D (FT) S1 S2 LINER
SCC-1 2.0 3.0 3.0 TREATMENT 1
SCC-2 2.0 3.0 3.0 TREATMENT 1
SCC-3 2.0 3.0 3.0 TREATMENT 1
SCC-4 2.0 3.0 3.0 TREATMENT 1
SCC-5 2.0 3.0 3.0 TREATMENT 1
CULVERT SCHEDULE
PIPE NO. do 3do La d INV(IN) INV(OUT) LENGTH SLOPE
PSD-ALL 24" 72" 48' 18"
C-1 24" 72" 22' 14" 634 625 140 5.0%
C-2 2x30" 16' 90' 40" 652 648 60 5.8%
C-3 24" 72" 10' 14" 640 624 140 5.0%
C-4 24" 72" 10' 14" 603 601 64 3.1%
TEMP 24" 72" 10' 14" 662 652 126 7.9%
VDOT #357
1'-6"
FLOW
CULVERTTOE OF FILL
CLASS I RIPRAP
1'-6"
FLOW
IPCULVERT INLET PROTECTION (STONE)
N.T.S.
1 1
2' 1
EC-2 EROSION CONTROL MATTING
TYPICAL DIVERSION BERM DETAIL DVN.T.S.
COMPACTED
SOIL
FINAL GRADE
SLOPE DRAIN ANCHOR DETAIL
N.T.S. SD
24" DIA.
PIPE
CORRUGATED
HDPE PIPE
EARTH FILL
6" MIN.
VEGETATIVE SUPPORT LAYER
TOP OF
VEGETATIVE
COVER
2'-0"
FLOW
2'-0"
2'-0"
FLOW
DOWNSTREAM ELEVATION
2'-0"
CLASS I RIPRAP
6"
6"
STONE CHECK DAM
N.T.S.
VDOT #357 COARSE
AGGREGATE
VDOT #357 COARSE
AGGREGATE
FILTER CLOTH
10 OZ. GEOTEXTILE
FILTER CLOTH
10 OZ. GEOTEXTILE
CD CONSTRUCTION OF A SILT FENCE
FILTER FABRIC
4"
4"
SF
3. BACKFILL AND COMPACT THE
EXCAVATED SOIL.
1. SET POSTS AND EXCAVATE A
4"X4" TRENCH UPSLOPE
ALONG THE LINE OF POSTS.
2. ATTACH THE FILTER FABRIC
TO THE POSTS AND EXTEND IT
INTO THE TRENCH.
4. EXTENSION OF FABRIC INTO THE TRENCH
N.T.S.
D+24" MIN.
4" + MIN. 1/10 D
D/2 + 12"
MIN.
D
PIPE DETAIL PDN.T.S.
FILL MATERIALEXIST. GRADE
NOTES:
1. TRENCH WIDTH SHALL BE MAINTAINED TO TOP OF PIPE.
2. ALL BEDDING AND BACKFILL MATERIALS SHALL BE IN
ACCORDANCE WITH THE SPECIFICATIONS.
3. FOR FLEXIBLE PIPE INSTALLATIONS, SELECT BACKFILL
SHALL BE PLACED TO 12" MINIMUM OVER THE TOP OF
THE PIPE.
4. ALL BACKFILL SHALL BE PLACED IN LOOSE LIFTS NOT
EXCEEDING 8" IN DEPTH AND COMPACTED TO 95%
MAXIMUM DRY DENSITY (STANDARD PROCTOR)
5. PIPE BEDDING AND HAUNCHING IN ACCORDANCE WITH
SECTION 302 OF THE VDOT ROAD AND BRIDGE
SPECIFICATIONS
TOP OF FILL
SELECT BACKFILL
TYPE 1
2 ACRES OR LESS OF DRAINAGE AREA:
A. LP250, AS MANUFACTURED
BY LAYFIELD GROUP OF
COLLIERS, WV;
B. MIRAFI HP270 AS
MANUFACTURED BY SOLMAX
OF HOUSTON, TX;
C. APPROVED EQUAL PRODUCT;
3do
TOE OF FILL
TOP OF FILL
℄ OF BERM
1'-0"
12" MIN.
PIPE BEDDING
TYPE 2
2-10 ACRES OF DRAINAGE AREA
SECTION
SECTION
DOWNSTREAM ELEVATION
GEOTEXTILE FABRIC PER
VSMH TABLE C-ECM-13-6
SCC NOTES:
1. STORMWATER CONVEYANCE CHANNEL MATERIALS AND
METHOD OF CONSTRUCTION SHALL BE IN ACCORDANCE
WITH C-SSM-05 OF THE VIRGINIA STORMWATER
MANAGEMENT HANDBOOK (VSMH).
2. SOIL STABILIZATION USED FOR CHANNEL LINING SHALL
MEET THE MINIMUM REQUIREMENTS OF TABLE
C-SSM-05-3 (TREATMENT 1) OR C-SSM-05-4 (TREATMENT
2) OF THE VSMH AS APPLICABLE.
PIPE OUTLET TO
WELL DEFINED
CHANNEL
SILT FENCE NOTES:
1. SILT FENCE MATERIALS AND METHOD OF CONSTRUCTION
SHALL BE IN ACCORDANCE WITH C-PCM-04 OF THE
VIRGINIA STORMWATER
2. MANAGEMENT HANDBOOK (VSMH). FILTER FABRIC SHALL
MEET THE MINIMUM REQUIREMENTS OF TABLE
C-PCM-04-4 OF THE VSMH.
Revisions
NO: DATE: DESCRIPTION:
EROSION AND SEDIMENT
CONTROL DETAILS
JTG/DAS
JBM
DRAWING NAME:
DRAWING NUMBER:
DATE:
ISSUED FOR:
DRAWN BY:
REVIEWED BY:
PROJECT NUMBER:
© 2026 LaBella Associates
Pittsylvania County PO Box 426, 1 Center Street, Chatham, Virginia
Pittsylvania County Sanitary Landfill Phase 3 Construction 382 Rainbow Lane, Dry Fork, Virginia, 24549
2253619
BID
4/20/2026
1604 Ownby Lane Richmond, VA 23220 804-355-4520 labellapc.com
A pr
0,
- 3
:3 5p m \\c as h.
la b\ u\ Le ga cy
\R
IC
\C
AD
D \L
AN
D
PR
O
JE
C
TS
\P itt sy lv an ia
\2
Ph as e
C el l D
\C ur re nt
W or ki ng
D ra w in gs \P lo t S he et s\
E &S
D
ET
AI
LS
.d w g La yo ut
=E &S
D
ET
GENERAL ELECTRICAL NOTES
1. THE WORK COVERED BY THIS CONTRACT CONSISTS OF FURNISHING ALL LABOR, EQUIPMENT, SUPPLIES, AND MATERIALS AND PERFORMING ALL OPERATIONS, INCLUDING TRENCHING, BACKFILLING, CUTTING, CHANNELING, CHASING AND PATCHING NECESSARY FOR THE INSTALLATION OF THE COMPLETE ELECTRICAL
SYSTEM IN STRICT ACCORDANCE WITH THE PLANS, NOTES AND REFERENCED SPECIFICATIONS.
2. ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST/ADOPTED ISSUE OF THE NATIONAL ELECTRIC CODE (NEC), APPLICABLE LOCAL AND STATE CODES.
SERVICE CONNECTIONS AND METERING SHALL BE IN ACCORDANCE WITH THE UTILITY COMPANY'S STANDARDS.
3. ALL ABOVE GRADE WIRING SHALL BE RUN IN RIGID STEEL OR IMC CONDUIT RACEWAYS. ALL JOINTS SHALL BE THREADED AND SEALED TO DISCOURAGE ENTRANCE OF WATER AND GASES. WHERE INDICATED, PROVIDE SEAL FITTINGS RATED FOR 40% FILL, OR INCREASE CONDUIT/SEAL SIZE SO FILL DOES NOT EXCEED 25%.
4. THE CONDUIT AND THE NEUTRAL CONDUCTOR FOR THE WIRING SYSTEMS, AND ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED. ALL FEEDER AND BRANCH CIRCUIT CONDUITS SHALL CONTAIN A GREEN GROUNDING CONDUCTOR IN ADDITION TO THE CIRCUIT CONDUCTORS. THE GROUNDING SLOT IN ALL RECEPTACLES AND MOTOR FRAMES SHALL BE GROUNDED BY CONNECTION THROUGH A BONDED JUMPER TO THE OUTLET BOX OR CONDUIT AND GROUNDING CONDUCTOR.
5. ALL CONDUCTORS, UNLESS OTHERWISE NOTED, SHALL BE TYPE THWN OR THHN STRANDED COPPER RUN IN CONDUIT. MINIMUM BRANCH CIRCUIT WIRING SHALL BE #12 AWG. CONDUIT SHALL BE SIZED PER NEC. HOWEVER, MINIMUM SIZE SHALL BE 3/4". ALL POWER AND CONTROL CONDUCTORS SHALL BE RATED FOR 600
VAC.
6. ALL EQUIPMENT, EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE, SHALL BE FURNISHED WITH FACTORY APPLIED FINISHED COAT. ALL PRIME COATED EQUIPMENT SHALL BE TOUCHED UP WHERE SCRATCHED, CLEANED, AND LEFT READY FOR PAINTING TO BE DONE BY CONTRACTOR.
7. THE SPECIFICATIONS DETAILING STUDY PROCEDURES, GOALS AND LABELING REQUIREMENTS HAVE BEEN PROVIDED BY LEAD PROFESSIONAL AS PART OF THIS
CONSTRUCTION DOCUMENT PACKAGE.
8. THE ELECTRICAL CONTRACTOR SHALL CONNECT ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTION EXCEPT AS OTHERWISE SPECIFICALLY NOTED. LOW VOLTAGE CONTROL WIRING FOR MECHANICAL EQUIPMENT IS INCLUDED IN THE MECHANICAL WORK. THE EXACT LOCATION OF STUB-UPS AND POINTS OF CONNECTION TO EQUIPMENT FURNISHED BY OTHER TRADES SHALL BE COORDINATED WITH THE TRADE FURNISHING THE EQUIPMENT BEFORE THE CONDUIT IS
INSTALLED.
JJ
J
CONDUIT CONCEALED IN OR ABOVE CEILING, IN OVERHEAD SLAB OR IN WALL, AS APPLICABLE.
CONDUIT CONCEALED IN OR BELOW FLOOR, BELOW GRADE OR IN WALL, AS APPLICABLE.
CONDUIT EXPOSED ON SURFACE OF CEILING, OVERHEAD STRUCTURE OR WALL AS APPLICABLE.
NUMBER OF CURRENT CARRYING CONDUCTORS PLUS NEUTRAL IF REQUIRED. EQUIPMENT GROUNDING CONDUCTORS SIZED PER N.E.C.
ARE NOT INCLUDED IN QUANTITY INDICATED, BUT SHALL BE INCLUDED IN ALL RACEWAYS.
CONDUIT TURNING UP/CONDUIT TURNING DOWN.
CONDUIT STUB UP 6" AFF WITH CONNECTION TO EQUIPMENT.
HOMERUN TO PANELBOARD, MOTOR CONTROL CENTER, OR SWITCHBOARD AS APPLICABLE.
JUNCTION BOX SIZED PER N.E.C. UNLESS OTHERWISE INDICATED.
JUNCTION BOX WITH FLEX CONNECTION TO EQUIPMENT.
THE ELECTRICAL SYMBOLS HEREINAFTER LISTED ARE A BASIC STANDARD FOR ALL PROJECTS AS APPLICABLE. EACH AND EVERY SYMBOL MAY NOT NECESSARILY APPEAR ON THE SPECIFIC PROJECT DRAWINGS. ALL DIMENSIONS ARE TO TOP OF THE OUTLET BOX UNLESS OTHERWISE NOTED. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE EXACT OUTLET HEIGHT WITH COUNTERS, BACKSPLASHES, WAINSCOT, AND EQUIPMENT TO ASSURE
PROPER MOUNTING HEIGHTS.
ELECTRICAL SYMBOLS
NEMA 5-20R DUPLEX CONVENIENCE RECEPTACLE MOUNTED 20", UNLESS NOTED OTHERWISE.
NEMA 5-20R DUPLEX CONVENIENCE RECEPTACLE MOUNTED 48" AFF OR BACKSPLASH.
RECEPTACLE AS SPECIFIED ABOVE EXCEPT WITH INTEGRATED GROUND FAULT CIRCUIT INTERRUPTER (GFCI).
GFCI RECEPTACLE SIMILAR TO THOSE SPECIFIED ABOVE EXCEPT U.L. "WR" (WEATHER-RESISTANT) LISTED AND PROVIDED WITH A
WEATHERPROOF COVER.WP
30/2
30/3F20 F
LIGHTING POWER OR DISTRIBUTION PANELBOARD AS INDICATED AND SCHEDULED.
EQUIPMENT CONTROL PANEL, CABINET, OR MODULE AS APPLICABLE.
FUSIBLE OR NON-FUSIBLE DISCONNECT FURNISHED WITH EQUIPMENT UNDER OTHER DIVISIONS OF THESE SPECIFICATIONS. TERMINATE
WIRING ON LINE SIDE OF DISCONNECT.
NON-FUSIBLE DISCONNECT. NUMERALS INDICATE SIZE AND POLES. WP INDICATES NEMA 3R ENCLOSURE OR WITH OTHER ENCLOSURE AS
INDICATED.
FUSIBLE DISCONNECT. NUMERALS INDICATE SIZE, POLES, AND FUSETRON SIZE. WP INDICATES NEMA 3R ENCLOSURE OR WITH OTHER
ENCLOSURE AS INDICATED.
MANUAL MOTOR STARTER SINGLE PHASE.
MAGNETIC MOTOR STARTER WITHOUT DISCONNECT.
COMBINATION MAGNETIC MOTOR STARTER WITH CIRCUIT BREAKER DISCONNECT (CMCB).
COMBINATION MAGNETIC MOTOR STARTER WITH NON-FUSIBLE DISCONNECT (CMNF).
COMBINATION MAGNETIC MOTOR STARTER WITH FUSIBLE DISCONNECT. NUMERAL INDICATES FUSETRON SIZE (CMFD).
120 OR 240-VOLT, SINGLE PHASE MOTOR, HORSEPOWER AS INDICATED.
208 OR 240-VOLT, THREE PHASE MOTOR, HORSEPOWER AS INDICATED.
480 OR 575-VOLT, 3-PHASE MOTOR, HORSEPOWER AS INDICATED.
DRY TYPE TRANSFORMER, 3-PHASE, 4-WIRE. KVA AS INDICATED.
ELECTRICAL NOTES:
1. 3-1/2", PVC COATED, RMC CONDUITS SHALL BE INSTALLED TO SERVE EACH 7.5 HP PUMP, THESE CONDUITS SHALL CONNECT BETWEEN THE TERMINAL BOX AND PUMP RISER. EACH 3-1/2" CONDUIT IS SIZED TO CONVEY THE MANUFACTURER FURNISHED SUBMERSIBLE PUMPS CABLES BETWEEN THE SUBMERSIBLE PUMP TO THE TERMINAL BOX. WITH MOTORS IN PLACE, SUBMERSIBLE CABLES SHALL BE PULLED INTO TERMINAL CABINET AND TERMINATED. IF ATTACHED CABLES ARE EXCESSIVE, THE EXCESS LENGTH SHALL BE CUT AWAY PRIOR TO MAKING TERMINATION IN THE INTERMEDIATE TERMINAL ENCLOSURE. THWN WIRE SIZES AND QUANTITIES (INDICATED ON PLANS) SHALL BE USED TO CONNECT BETWEEN THE
OUTDOOR TERMINAL CABINET AND TERMINAL BOX.
2. A MINIMUM WORKING CLEARANCE OF 3'-6" FROM EQUIPMENT FACES SHALL BE MAINTAINED PER NEC 110.26. ELECTRICAL AND CONTROL CABINETS SHALL BE MOUNTED SUCH THAT NO OPERABLE HANDLE EXCEEDS 6'-6" ABOVE FINISHED FLOOR
(AFF) WHEN IN THEIR HIGHEST POSITION.
3. THE CONTROL PANEL SHALL COMMAND THE PUMP TO START/STOP BASED ON SUMP LIQUID LEVELS. POWER INPUT SHALL BE 240-VOLT, 3-PHASE. FROM THIS POWER INPUT, POWER QUALITY (OVER/UNDER VOLTAGE, PHASE LOSS/REVERSAL) IS MONITORED AND USED TO POWER THE LEVEL SENSING CONTROLS. CONTROL PANEL SHALL CONTAIN OVER TEMPERATURE AND SEAL FAILURE MONITORING FOR PUMP. SEE SHEET E-02 FOR ANTICIPATED "FIELD WIRING" CONNECTIONS AND
MOUNTING REQUIREMENTS. COORDINATE EXACT LOCATION WITH PITTSYLVANIA COUNTY.
4. THE TERMINAL BOXES SHALL BE CONSTRUCTED OF STAINLESS STEEL. BOX SHALL BE SIZED IN ACCORDANCE WITH NEC; COORDINATE EXACT LOCATION WITH PITTSYLVANIA COUNTY & MOUNT BOX ONTO SUMP CONCRETE HEADWALL ADJACENT TO THE SUMP RISER. COORDINATE EXACT LOCATION WITH INSTALLED HATCH AND VENT OPENING LOCATIONS. ALTERNATE LOCATIONS, IF USED, SHOULD BE >3' (HORIZONTAL DISTANCE) FROM NEAREST EDGE OF SIDE SLOPE RISER HATCH AND
> 5' FROM THE CONCRETE SUMP HEADWALL VENT OPENINGS.
(2) 5/8" X 10' COPPERCLAD GROUND ROD DRIVEN
6" BELOW FINISHED GRADE PER NEC
250.52(A)(5)
SERVICE
ENTRANCE
EQUIPMENT
BOND SERVICE
ENTRANCE ENCLOSURE
GROUNDING ELECTRODE CONDUCTORS SIZED
PER NEC 250.66 (ALL FULL SIZE).
EXOTHERMAL WELDS OR LISTED GROUNDING CLAMPS FOR USE
BELOW GRADE.
BOND GROUNDED ELECTRODE & SERVICE
CONDUITS
GROUND CLAMP
GROUND CLAMP OR WELDED
CONNECTION TO CHAIN-LINK FENCE
ENCLOSURE
CHAIN-LINK
FENCE
ENCLOSURE
CONNECTIONS TO OTHER ELECTRODES IN
ACCORDANCE WITH NEC 250.52(A) WHERE
AVAILABLE, OR DIRECTED BY AHJ.
NEUTRAL BUS
(WHERE APPLICABLE)
EQUIPMENT GROUND BUS
ALTERNATE GROUNDING ELECTRODE CONDUCTOR CONNECTION METHOD,
PROVIDE 2"X1/4" (MINIMUM) COPPER BUS MOUNTED IN AN ACCESSIBLE
LOCATION PER NEC 250.64(C)(2) & 250.64(F)(3)
PANEL RACK 1-5/8" GALVANIZED STEEL
STRUT
NEUTRAL BONDING JUMPER (WHERE
APPLICABLE)
GRADE
CONCRETE SLAB - SEE STRUCTURAL DWGS
ELECTRICAL
CONDUITS
ELECTRICAL
ENCLOSURES
(INSIDE HOOD)
3/16" ALUMINUM SUN/RAIN
HOOD (WELDED TO BACKER
PLATE)
SIDE VIEW
INCLUDE UNISTRUT 3" FROM TOP AND
BOTTOM OF WALL, AND 24" O.C. MAX.
CONCRETE WALL
1/2" EPOXY ANCHORS,
DOWELED 4" INTO WALL
FLA
FLA
FLA
AMPS
AMPS
12.50
5.50
56.50
22.00
22.00
AMPS
AMPS
AMPS27.50
89.5
62.00
120-VOLT CONTROL & RECEPTACLES
MOTOR FLA X .25 =
TOTAL LOAD
MOTOR FLA X 1.25 =
MIN WIRE SIZE AMPS
OVERCURRENT PROTECTION
SERVICE & OVERCURRENT PROTECTION SIZED AT 80 AMP
7.5HP, 230V, 3Ø SUBMERSIBLE PUMP
7.5HP, 230V, 3Ø SUBMERSIBLE PUMP
SERVICE CALCULATIONS @ 120/240V, 3Ø, 4W
SERVICE
DISCONNECT
E.C. TO PROVIDE & INSTALL
METER BASE PER LOCAL
UTILITY STANDARDS
120/240V, 3Ø, 4W (HIGH-LEG)
OVERHEAD SECONDARY BY UTILITY
COMPANY; E.C. TO COORDINATE
POLE LOCATION AND EXTENSION
OF UTILITIES.
#6G BARE COPPER POLE
GROUND STAPLED FROM
BASE TO TOP OF POLE
3#3, 1-1/4"C
25' TREATED WOOD POLE
(CLASS 5 OR BETTER)
BUTT GROUNDING COIL
ATTACHED TO BOTTOM
OF POLE
PHASE 3
LEACHATE
PUMPS LEVEL
CONTROL
PANEL (LCP)
(SEE NOTE 3)
4.28 kA AVAILABLE FAULT (25 kVA @ 1.50 %Z)
COORDINATE ACTUAL FAULT WITH UTILITY
100/3 F80
WP
3#4, 1#8G, 1"C #8SG
CFS
AGR
DRAWING NAME:
DRAWING NUMBER:
DATE:
ISSUED FOR:
DRAWN BY:
REVIEWED BY:
PROJECT NUMBER:
© 2026 LaBella Associates
Pittsylvania County PO Box 426, 1 Center Street, Chatham, Virginia
Pittsylvania County Sanitary Landfill Phase 3 Construction 382 Rainbow Lane, Dry Fork, Virginia, 24549
2253619
BID
4/17/2026
1604 Ownby Lane Richmond, VA 23220 804-355-4520 labellapc.com
A pr
0,
- 1
2:
pm C
:\U se rs \a ra ym on d\
Ap pD at a\
Lo ca l\T em p\ Ac
Pu bl is h_
6\ Pi tts yl va ni a C ou nt y P3
E
LE
C .d w g
La yo ut =E
-0
E-01
ELECTRICAL COVER SHEET
04.17.2026
NOTES (DETAIL 3 - ELECTRICAL EQUIPMENT LAYOUT):
1. EQUIPMENT LAYOUT DETAIL IS NOT TO SCALE. EQUIPMENT LOCATIONS AND (RELATIVE) SIZES ARE ESTIMATED. CONTRACTOR SHALL COORDINATE ELECTRICAL INSTALLATION WITH ACTUAL
EQUIPMENT/SITE CONDITIONS AND MAKE ADJUSTMENTS AS NECESSARY.
2. CONDUITS RACEWAYS CONNECTING TO CLASSIFIED SPACES (i.e., THE SUMP PIT, SUMP ACCESS PIPE, ETC.) SHALL BE PVC COATED RIGID METAL CONDUITS (RMC) BY ROBROY OR EQUIVALENT. CONDUITS SHALL BE ROUTED BELOW GRADE AND HAVE CONDUIT SEALS APPLIED WITHIN 18" OF THEIR EMERGING FROM BELOW GRADE AND PRIOR TO CONDUIT
TERMINATIONS ONTO NON-CLASSIFIED ENCLOSURES, BOXES OR CONDUIT BODIES.
3. ALL RACK MOUNTED ENCLOSURES SHALL BE INSTALLED USING FACTORY DRILLED HOLES, MOUNTING LUGS OR BUSHINGS. PENETRATIONS OF ANY NEMA/U.L. LISTED ENCLOSURE (CONDUITS, MOUNTING HARDWARE, OR PHYSICAL ATTACHMENTS) SHALL NOT DEGRADE THAT ORIGINAL LISTING.
4. CONTROL PANEL IS SHOWN RACK MOUNTED, HOWEVER FREESTANDING UNITS ARE EQUALLY ACCEPTABLE. WHERE FREESTANDING UNITS ARE SPECIFIED THEY SHALL NOT HAVE STRUCTURAL CONNECTIONS TO THE SHELTER. PROVIDE STRUCTURAL BRACING AS NECESSARY TO COMPENSATE FOR ABSENCE OF RACK MOUNTED CONTROL PANEL.
FRONT VIEW
GRADE
6" THICK, 3000 PSI CONCRETE SLAB WITH CHAMFERED EDGES
ALARM
HORN
ALARM
LIGHT
4' LED FIXTURE
4" GALVANIZED PIPE SUPPORT WITH PVC
END CAP. (TYPICAL)
90° BEND AT TOP/SIDE
TRANSITION (TYPICAL)
CONTINUOUS WELD OF TOP &
SIDE PANELS TO THE 1/4"
BACKER PLATE
CONCRETE EXTENDS 6" BEYOND HOOD
ON FRONT, BACK & SIDES
PROVIDE HOOD OF SUFFICIENT WIDTH TO
ACCOMMODATE ALL ELECTRICAL
ENCLOSURES INSTALLED PER THEIR
REGULATIONS. ALTERNATE ARRANGEMENTS
(OR LARGER HOODS) MAY BE REQUIRED.
1/4" ALUMINUM
BACKER PLATE
3/16" ALUMINUM
SUN/RAIN HOOD
(WELDED TO BACKER
PLATE)
GFCI DUPLEX RECEPTACLE
WITH WEATHERPROOF COVER
w/PADLOCK CLASP.
SUMP RISER CONDUITS WITH SEAL
FITTINGS
WIRING TO OTHER SITE EQUIPMENT
AND SERVICES AS INDICATED ON
PLAN
STAINLESS STEEL 4" CHANNEL FOR
ATTACHMENT OF PANELS AND CANOPY
BACKER PLATE (TYPICAL)
NEMA 4X
STAINLESS STEEL
ENCLOSURE
(SEE NOTES 3 & 4)
(NOTE 2)
HINGED INNER PANEL. ALL OPERATORS
SWITCHES AND INDICATORS TO BE MOUNTED TO
INNER PANEL FRONT.
SIDE VIEW
GRADE
7' HEADROOM
(MINIMUM)
4" ALUMINUM CHANNEL
SUPPORT.
48"
6" THICK CONCRETE SLAB
36"
(MIN)
3000 PSI CONCRETE
(TYPICAL)
ELECTRICAL
CONDUITS
15"
(MIN)
ELECTRICAL
ENCLOSURES
(INSIDE HOOD)
HORN
LIGHT
3/16" ALUMINUM SUN/RAIN
HOOD (WELDED TO BACKER
PLATE)
LINEAR LED FIXTURE U.L LISTED FOR
WET LOCATIONS
PHASE 3 LEACHATE PUMPS LEVEL
CONTROL PANEL (LCP)
UL 698A INDUSTRIAL
CONTROL PANEL IN NEMA 4X,
STAINLESS STEEL ENCLOSURE
120/240-VOLT, 3Ø, 4W
SERVING (2) 7.5 HP, 230V, 3Ø PUMPS
7.5 HP
EXTRA HARD USE
SUBMERSIBLE PUMP
CABLE FOR PUMP POWER
AND MONITORING
PUMP
7.5 HP, 230 V, 3Ø
PUMP OVER TEMP &
SEAL FAILURE
PUMP SITE
PRESSURE
TRANSDUCER
SUBMERSIBLE ANALOG SIGNAL
CABLE TO PRESSURE TRANSDUCER
(FURNISHED WITH TRANSDUCER)
SEPARATE OR ISOLATE PER NEC
504.30.A INTRINSICALLY SAFE WIRING
PUMP SITE
INTRINSICALLY
SAFE 4-20mA
LEVEL SENSING
EQUIPMENT AT PUMP SITE #1
SEE DETAIL 2/E-02 FOR ELECTRICAL
EQUIPMENT & WIRING REQUIREMENTS
ANALOG SIGNAL CABLE TO
FLOW SENSOR ELEMENT
120 V RECPT
FEEDER PER POWER RISER
DIAGRAM
FLOW
XMITTER
120V RECEPT &
FLOW METER FLOW SENSOR
PUMP
POWER
PUMP
OVER TEMP
PUMP
SEAL FAILURE
3#10, 4#14, 1#10G, 1"C
(1/PUMP)
NEMA 5-20R DUPLEX, GFCI, "WR" RATED
IN WEATHERPROOF OUTLET BOX WITH
WEATHERPROOF COVER. ONE FOR
CONNECTION TO HEAT TRACE
4-20mA SIGNAL WIRING IN 2(1")C TO
CONTROL PANEL, FURNISHED &
INSTALLED BY E.C. (SEE NOTE 4)
2#12, 1#12G, 3/4"C
NEMA 4X, JUNCTION BOX OUTSIDE
HAZARD AREA (FOR TERMINATION
OF PUMP CABLES)
CONDUIT SEAL
FITTING
NEMA 4X, JUNCTION BOX
OUTSIDE HAZARD AREA
(FOR TERMINATION OF
PUMP CABLES)
CONDUIT SEAL FITTING
SEAL FITTINGS
PUMP SITE
PRESSURE
TRANSDUCER
INTRINSICALLY SAFE
4-20mA LEVEL
SENSING
(NOTE 2, 3)PUMP SITE
INTRINSICALLY
SAFE 4-20mA
LEVEL SENSING
RISER #1
RISER #2
FLOW
XMITTER
120V RECEPT &
FLOW METER FLOW SENSOR
RISER #1
RISER #2
7.5 HP
PUMP
7.5 HP, 230 V, 3Ø
PUMP OVER TEMP &
SEAL FAILURE
PUMP
POWER
PUMP
OVER TEMP
PUMP
SEAL FAILURE
PUMP #2 SEAL
FAILURE
PUMP #2 OVER
TEMP
PUMP #2
POWER
PUMP #1 SEAL
FAILURE
PUMP #1 OVER
TEMP
PUMP #1
POWER
CONTAINMENT DIKE
(CL 1, DIV 2)
TERMINAL BOX(ES)
(NOTE 4)HAZARD BOUNDARY LEGEND
UNCLASSIFIED
CLASS 1, DIVISION 2
CLASS 1, DIVISION 1
7.5 HP, 230 V, 3Ø
SUBMERSIBLE PUMP
PRESURE TRANSDUCER
SUMP PIT PUMPING EQUIPMENT
ACCESS/REMOVAL PIPE.
SUMP PIT
(CL 1, DIV 1)
SUMP ACCESS PIPE IN
TERIOR
(CL 1, DIV 1)
SUMP ACCESS PIPE IN
TERIOR
(CL 1, DIV 1)
3/4" EC
CONDUIT
SEALS
CLASS 1, DIVISION 2, GROUP D
HAZARD CLASSIFICATION WITHIN 3'
OF FLANGE OPENINGS USED FOR
MAINTENANCE AND PUMP REMOVAL
FORCEMAIN
HEAT TRACE (CLASS 1, DIV 2
PER SPECIFICATIONS)
FLOW SENSOR
NEMA 4X, JUNCTION BOX OUTSIDE
HAZARD AREA (FOR TERMINATION
OF PUMP/METER CABLES)
CONDUIT
SEALS
WP IN-USE OUTLET FOR CONNECTION TO HEAT
TRACE INSTALL OUTSIDE HAZARD AREA
2#12,1#12G,3/4"C
1" EC FOR SUBMERSIBLE PRESSURE
TRANSDUCER CABLE
3-1/2" CONDUIT
CONCRETE
HEADWALL
(NOTE 5)
TO CONTROL PANEL
NOTES (DETAILS 1 AND 2):
1. FIELD WIRING DETAIL SHOWS THE ANTICIPATED EXTERNAL "FIELD WIRED" CONNECTIONS TO AND BETWEEN THE TERMINAL BOX AND CONNECTIONS TO PUMPING AND LEVEL SENSING EQUIPMENT AT EACH SUMP PUMP SITE. E.C. SHALL VERIFY WIRING REQUIREMENTS WITH FINAL, APPROVED SHOP DRAWING/SCHEMATICS AND WIRE COMPLETE. ALL WIRING NECESSARY TO ACHIEVE AUTOMATIC, PUMP DOWN OPERATION AT EACH SUMP PUMP SITE. CONTROL PANEL SHALL BE UL 698A LISTED AND SHALL BE APPROVED BY PITTSYLVANIA COUNTY OFFICIALS (OR ASSIGNED OTHERS) PRIOR TO FABRICATION.
2. UNLESS OTHERWISE DIRECTED, CONTROL WIRING FOR EQUIPMENT INDICATED SHALL BE #14 THWN COPPER CONDUCTORS RUN IN A PROPERLY SIZED (PER NEC) ELECTRICAL CONDUIT. COORDINATE EXACT REQUIREMENTS AND WIRE COMPLETE. MINIMUM CONDUIT SIZE SHALL BE 3/4".
3. ANALOG, RF SIGNAL OR OTHER "SHIELDED" TYPE CABLES SHALL BE SELECTED TO MEET SYSTEM & COMPONENT REQUIREMENTS. E.C. TO COORDINATE REQUIREMENTS, INSTALL CABLES, CONDUIT SLEEVES (WHERE APPLICABLE) AND MAKE FINAL CONNECTIONS.
4. ALL WIRING BETWEEN THE TERMINAL BOX(ES) AND PUMPING EQUIPMENT/SENSORS SHALL BE ROUTED TO AVOID TRAVELING THROUGH OR BENEATH AREAS THAT ARE CLASSIFIED AS HAVING POTENTIAL FOR HAZARDOUS GASES OR VAPORS. INSTALL TERMINAL BOX NEAR TOP OF SIDE SLOPE RISER BUT OUTSIDE HAZARD ZONES INDICATED ON DETAIL 2/E-02 (OR THOSE DIRECTED BY LOCAL AHJ, IF MORE SEVERE). TERMINAL BOX ENCLOSURE SHALL BE NEMA 4X, STAINLESS STEEL, SIZED PER NEC. E.C. SHALL VERIFY EQUIPMENT CABLE/CONDUCTOR SIZES, AMPERE RATINGS, CABLE TYPES, ETC. AND PROVIDE WIRE TERMINALS AND POWER LUGS TO ACCOMMODATE POWER, DIGITAL AND ANALOG SIGNAL CONNECTIONS REQUIRED. CABLES SHALL BE LISTED, LABELED (FOR THEIR INTENDED APPLICATION) AND CORRECTLY SIZED (PER NEC) TO SUPPLY THE CONNECTED LOADS/EQUIPMENT THEY SERVE. USE ONLY
FACTORY DRILLED HOLES FOR TERMINAL BOX SUPPORTS.
5. MOUNT CONTROL PANEL TO FREE STANDING ELECTRICAL EQUIPMENT RACK (SEE 3/E-02 FOR MORE INFORMATION). COORDINATE EXACT LOCATION SO THAT ELECTRICAL ENCLOSURES (INCLUDING TERMINAL BOX) ARE NOT WITHIN OR ABOVE ANY HAZARDOUS AREA - SEE 2/E-02 FOR CLASSIFIED AREAS FOR THIS INSTALLATION. TERMINAL BOX SHALL BE AFFIXED TO WALL VIA CORROSION RESISTANT FASTENERS RATED FOR FINAL PANEL WEIGHT AND USE IN CONCRETE. SEE DETAIL 2/E-01.
6. CONTROL PANEL SHALL BE PROVIDED WITH (EITHER INTEGRATED WITHIN OR IN SEPARATE ENCLOSURE) A REMOTE TERMINAL UNIT (RTU). RTU (MISSION MYDRO 850 - OR APPROVED EQUAL) SHALL BE PROVIDED WITH WIRELESS CELLULAR CARD, AND REPORT THE FOLLOWING CONDITIONS TO A WEB BASED INTERFACE: POWER FAILURE, PUMP RUNNING, PUMP FAIL, PUMP SEAL FAILURE, FLOW (ANALOG). RTU SHALL HAVE AT LEAST 2 SPARE DIGITAL INPUTS, AN INTEGRATED BATTERY BACKUP, AND ANTENNA(S) AS REQUIRED FOR SIGNAL STRENGTH. CONTRACTOR (AND/OR THEIR PANEL FABRICATOR) SHALL BE RESPONSIBLE FOR MAKING ALL TELEMETRY CONNECTIONS, SYSTEM TESTING, START-UP, AS WELL AS SYSTEM TRAINING FOR THE OWNER'S REPRESENTATIVE.
CFS
AGR
DRAWING NAME:
DRAWING NUMBER:
DATE:
ISSUED FOR:
DRAWN BY:
REVIEWED BY:
PROJECT NUMBER:
© 2026 LaBella Associates
Pittsylvania County PO Box 426, 1 Center Street, Chatham, Virginia
Pittsylvania County Sanitary Landfill Phase 3 Construction 382 Rainbow Lane, Dry Fork, Virginia, 24549
2253619
BID
4/17/2026
1604 Ownby Lane Richmond, VA 23220 804-355-4520 labellapc.com
A pr
0,
- 1
2:
pm C
:\U se rs \a ra ym on d\
Ap pD at a\
Lo ca l\T em p\ Ac
Pu bl is h_
6\ Pi tts yl va ni a C ou nt y P3
E
LE
C .d w g
La yo ut =E
-0
E-02
ELECTRICAL DETAILS
TERMINAL STRIP
ALL EQUIPMENT & WIRING INSTALLED IN SUMP PIT SHALL
BE RATED SUITABLE FOR CL. 1, DIV. 1, GRP. D HAZARDOUS
ENVIRONMENTS. NG SHALL BE MAINTAINED PER NEC 504.
21 3 4 9 10
PUMP SEAL
PROBE
LEACHATE FIELD
RECEPTACLE & FLOW METER
4 15/1
15/1
20/1
120/240-VOLT,
3Ø, 4W INPUT
500 VA LOAD
L3
GLIGHTNING
ARRESTER
LA
L2
L1
1 C
NOTE:
THE BELOW SCHEMATIC IS PROVIDED AS A GUIDE AND SHOWS BASIC ELEMENTS THAT MUST BE PROVIDED (AT A MINIMUM).
PANEL SHALL BE U.L. APPROVED AS A COMPLETE ASSEMBLY AND LISTED AS…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .