Permit_Review_-_Plans_-_BVFES_Bldg_5+6.pdf
PDF 4 MB Posted
- Attached to
- Roof Replacement and Designated Repairs
- Solicitation number
- 25-CR-044
- Issued by
- Pinellas County, Florida
About this file
These technical drawings and specifications are for a roof replacement project at Bay Vista Fundamental Elementary School in St. Petersburg, Florida, prepared by A/R/C Associates for Pinellas County Public Schools. The project involves replacing the existing metal panel roof systems for Buildings 5 and 6, located at 5900 Dr. M.L.K. Jr. Street South. The scope includes removing the existing metal panel roof system down to the metal roof deck, removing sub-framing and insulation, installing a base layer of 1" non-tapered rigid insulation and 5/8" plywood sheathing, priming and applying self-adhered underlayment, and installing a new aluminum metal panel roof system. The project is specified to adhere to a 90-day contract period and requires a Florida licensed Roofing Contractor.
The detailed plans include comprehensive specifications for fastening methods, material requirements, wind zone considerations, and installation techniques. The project documents specify that all work must comply with the State Requirements for Educational Facilities (SREF) within the Florida Building Code. The technical drawings provide extensive details on roof geometry, wind zone mapping, flashing techniques, gutter and downspout installations, and specific materials such as 0.050" mill finish aluminum gutters, 0.040" mill finish aluminum valley flashings, and stainless steel fasteners. The specifications emphasize precise installation methods, including fully welded and epoxied metal fabrications, specific fastener spacing, and requirements for continuous and sealed metal joints.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LIC. NBR AR-007684
Architecture Roof Consulting
Construction Technology
OF SHEET(S)
SHEET NO.:
DATE:
CHECKED BY:
DRAWN BY:
JOB NO.:
COPYRIGHT 2025 A/R/C ASSOCIATES, INC.
REVISIONS
BY:DATENO.
Tel. (407) 896-7875 Fax. (407) 898-6043
601 North Fern Creek Avenue Suite 100, Orlando, FL
32803-4899
DESIGNED BY:
B ay
V is ta F un da m en ta l E le m en ta ry S ch oo l R oo f R ep la ce m en t a t:
Pi ne lla s
C ou nt y
Pu bl ic S ch oo ls
D r.
M .L
.K . J r.
St re et
S ou th , S t.
Pe te rs bu rg
, F L
A00
C O
VE
R
S H
EE
T, S
IT
E
VI
C
IN
IT
Y
M
AP
, A N
D D
R
AW
IN
G
IN
D
EX
24023.00
NVJ
TAH
02/18/2025
TAH
BAY VISTA FUNDAMENTAL
ELEMENTARY SCHOOL
ROOF REPLACEMENT AT:
BUILDING 5 AND BUILDING 6
FOR
5900 Dr. M.L.K. Jr. Street South, St.
Petersburg, FL 32705
SITE VICINITY MAP
SCHOOL BOARD MEMBERS
DRAWING INDEX
Sheet
Number Sheet Name
A00 COVER SHEET, SITE VICINITY MAP, AND DRAWING INDEX
A01 OVERALL SITE PLAN, ROOF SCHEDULES, AND WIND PRESSURE DATA
A02 ROOF PLAN - BUILDING 5
A03 ROOF PLAN - BUILDING 6
A04 FASTENER SCHEDULE, ABBREVIATIONS, AND GENERAL NOTES
A05 ROOFING DETAILS
A06 ROOFING DETAILS
A07 ROOFING DETAILS
A08 ROOFING DETAILS
District #1 Laura T. Hine, Chairperson
PINELLAS COUNTY BOARD MEMBERS
District #2 Lisa N. Cane District #3 Dawn M. Peters District #4 Eileen M. Long District #5 Carol J. Cook, Vice-Chairperson District #6 Stephanie Meyers District #7 Caprice Edmond
2/17/2025
Joe Williams Seal with Signature
D R
. M .L
.K . J
R . S
T.
S
8T H
S T.
S
59TH AVE. S.
60TH AVE. S.
58TH AVE. S.
B
A
A
N.I.C.
N.I.C.
N .I.
C
N.I.C.
N.I.C.
N.I.C. N.I.C.
N.I.C.
N.I.C
N .I.
C
N .I.
C
N .I.
C
N .I.
C
N .I.
C
N .I.
C
N.I.C.
N.I.C.
N .I.
C
N.I.C.N.I.C.
7'-7" 7'-7"
WIND ZONE 2 - EDGE
WIND ZONE 3 - CORNER
WINDZONE LEGEND
WIND ZONE 1 - FIELD EDGE
WIND ZONE 1' - FIELD
7' -7
7'-7"
7' -7
7' -7
7'-7" 7'-7"
7' -7
7' -7
7'-7"
7'-7"
WIND ZONE 2 - EDGE
WIND ZONE 3 - CORNER
WINDZONE LEGEND
WIND ZONE 1 - FIELD EDGE
WIND ZONE 1' - FIELD
LIC. NBR AR-007684
Architecture Roof Consulting
Construction Technology
OF SHEET(S)
SHEET NO.:
DATE:
CHECKED BY:
DRAWN BY:
JOB NO.:
COPYRIGHT 2025 A/R/C ASSOCIATES, INC.
REVISIONS
BY:DATENO.
Tel. (407) 896-7875 Fax. (407) 898-6043
601 North Fern Creek Avenue Suite 100, Orlando, FL
32803-4899
DESIGNED BY:
B ay
V is ta F un da m en ta l E le m en ta ry S ch oo l R oo f R ep la ce m en t a t:
Pi ne lla s
C ou nt y
Pu bl ic S ch oo ls
D r.
M .L
.K . J r.
St re et
S ou th , S t.
Pe te rs bu rg
, F L
A01
O
VE
R
AL
L
SI
TE
P
LA
N
, R O
O F
SC
H
ED
U
LE
S, A N
D W
IN
D
P R
ES
SU
R E
D
AT
A
24023.00
NVJ
TAH
02/18/2025
TAH
PHYSICAL CHARACTERISTICS SCHEDULE
Roof Area Number Area Existing Roof Deck
Type Existing Slope Proposed Slope Existing Roof Type Proposed Roof Type Existing Insulation Proposed Insulation Existing
Flashing Metal Proposed Flashing
Metal N.I.C.
5/A 2,981 SF METAL 4:12 EXISTING METAL PANEL ALUMINUM METAL PANEL FIBERGLASS NON-TAPERED RIGID INSULATION STL. ALUM.
5/B 3,045 SF METAL 4:12 EXISTING METAL PANEL ALUMINUM METAL PANEL FIBERGLASS NON-TAPERED RIGID INSULATION STL. ALUM.
6/A 6,479 SF METAL 4:12 EXISTING METAL PANEL ALUMINUM METAL PANEL FIBERGLASS NON-TAPERED RIGID INSULATION STL. ALUM.
Total Area 12,505 SF
The quantities provided are from the architect's field investigation and are provided for the contractor's use. The information represents what was found on the date the work was peformed at the location. This information may not be consistant at all areas or locations within the scope of work. The contractor is cautioned to confirm the existring conditions to the extent necessary to properly bid and construct the scope of work. Any deviations found should be brought to the attention of the architect
1" = 40'-0"
A01 .1 - OVERALL SITE PLAN
3/64" = 1'-0"
BUILDING 5 - WIND ZONE PLANA01 .2
3/64" = 1'-0"
BUILDING 6 - WIND ZONE PLANA01 .3
2 9
2/17/2025
EXIST.
SLOPE
EXIST.
SLOPE
E X
IS
T.
S L O P E
N.I.C.
N.I.C.
N.I.C.
90'-8"
A
B
2'-0" 2'-0"
2'-0"
18'-4"
A05.1
A05.1
A05.3 A05.3
A05.1
A05.1
A05.1
A05.5
A06.1 A06.1
A05.1
A05.3
333 3
N.
I.C
N.
I.C
A05.3
2 2 2
2 2
A05.1 A05.1
A06.4
A06.4
A06.1
A05.4A05.4
ABOVE
BELOW
ABOVE
BELOW
A06.5A08.3 A08.3
A06.6
A08.3A08.3
SIM. SIM.
BELOW
SIM.SIM.
A06.1
A08.4
A08.4 A08.4
6 6
A05.1
LIC. NBR AR-007684
Architecture Roof Consulting
Construction Technology
OF SHEET(S)
SHEET NO.:
DATE:
CHECKED BY:
DRAWN BY:
JOB NO.:
COPYRIGHT 2025 A/R/C ASSOCIATES, INC.
REVISIONS
BY:DATENO.
Tel. (407) 896-7875 Fax. (407) 898-6043
601 North Fern Creek Avenue Suite 100, Orlando, FL
32803-4899
DESIGNED BY:
B ay
V is ta F un da m en ta l E le m en ta ry S ch oo l R oo f R ep la ce m en t a t:
Pi ne lla s
C ou nt y
Pu bl ic S ch oo ls
D r.
M .L
.K . J r.
St re et
S ou th , S t.
Pe te rs bu rg
, F L
A02
R O
O F
PL
AN
BU
IL
D
IN
G
24023.00
NVJ
TAH
02/18/2025
TAH
SPECIFIC NOTES
NEW DOWNSPOUT ON TO GRADE AT
EXISTING LOCATION. REFER TO DETAIL
A07.5, SYMBOLS LEGEND
DETAIL TAG1.01
SPECIFIC NOTE TAG1
ROOF AREA I.D. TAG
A
3/16" = 1'-0"
BUILDING 5 - ROOF PLANA02 .1
N.I.C. NOT IN CONTRACT
SANITARY VENT
DOWNSPOUT
GUTTER EXPANSION JOINT
NEW GUTTER EXPANSION JOINTS TO BE
INSTALLED PER SMACNA GUIDELINES
SEE DETAIL A07.4
NEW DOWNSPOUT TO BE RECONNECTED
TO EXISTING STORM DRAIN AT EXISTING
LOCATION. CLEAN OUT EXISTING STORM
DRAIN AS NEEDED TO ENSURE IT IS NOT
BLOCKED. SEE DETAIL A07.6
NEW DOWNSPOUT DRAINING ON TO
CANOPY AT EXISTING LOCATION.
NEW CURVED GUTTER SECTION TO BE
FULLY WELDED SINGLE-PIECE
FABRICATION - SEE DETAIL A07.2 FOR
ASSEMBLY.
PLACE SPLASH BLOCK AT EXISTING
DOWNSPOUT LOCATION. REFER TO
DETAIL A08.4 FOR REFERANCE.
2/17/2025
A
EXIST.
SLOPE
EXIST.
SLOPE
EXIST.
SLOPE
E X
IS
T.
S L O P E
E X
IS
T.
S L O P E
EXIST.
SLOPE
N .I.
C
N.I.C.
49'-4"
32'-0"2'-0"
2'-0"
2'-0"
83'-4"
14'-0"
1'-
A05.1
A05.1
A05.1
A05.1
A05.1
A05.1
A05.1
A05.1
A05.2
A05.2
A05.2
A05.3A05.3
A05.3A05.3
A05.5
A05.5
A05.6
A05.3
A05.3
A06.5
A08.2
A08.1
A08.1
2'-0"
A06.5
A08.3
A08.3
A08.3
A08.3
SIM.
A08.3A06.5A08.3
A05.6
A08.4
A08.4
A08.4
A08.4
SIM.
LIC. NBR AR-007684
Architecture Roof Consulting
Construction Technology
OF SHEET(S)
SHEET NO.:
DATE:
CHECKED BY:
DRAWN BY:
JOB NO.:
COPYRIGHT 2025 A/R/C ASSOCIATES, INC.
REVISIONS
BY:DATENO.
Tel. (407) 896-7875 Fax. (407) 898-6043
601 North Fern Creek Avenue Suite 100, Orlando, FL
32803-4899
DESIGNED BY:
B ay
V is ta F un da m en ta l E le m en ta ry S ch oo l R oo f R ep la ce m en t a t:
Pi ne lla s
C ou nt y
Pu bl ic S ch oo ls
D r.
M .L
.K . J r.
St re et
S ou th , S t.
Pe te rs bu rg
, F L
A03
R O
O F
PL
AN
BU
IL
D
IN
G
24023.00
NVJ
TAH
02/18/2025
TAH
3/16" = 1'-0"
BUILDING 6 - ROOF PLANA03 .1
SPECIFIC NOTES
NEW DOWNSPOUT ON TO GRADE AT
EXISTING LOCATION. REFER TO DETAIL
A07.5, NEW GUTTER EXPANSION JOINTS TO BE
INSTALLED PER SMACNA GUIDELINES
SEE DETAIL A07.4
SYMBOLS LEGEND
DETAIL TAG1.01
SPECIFIC NOTE TAG1
ROOF AREA I.D. TAG
A
N.I.C. NOT IN CONTRACT
SANITARY VENT
DOWNSPOUT
GUTTER EXPANSION JOINT
NEW DOWNSPOUT TO BE RECONNECTED
TO EXISTING STORM DRAIN AT EXISTING
LOCATION. CLEAN OUT EXISTING STORM
DRAIN AS NEEDED TO ENSURE IT IS NOT
BLOCKED. SEE DETAIL A07.6
NEW DOWNSPOUT DRAINING ON TO
CANOPY AT EXISTING LOCATION.
NEW CURVED GUTTER SECTION TO BE
FULLY WELDED SINGLE-PIECE
FABRICATION - SEE DETAIL A07.2 FOR
ASSEMBLY.
PLACE SPLASH BLOCK AT EXISTING
DOWNSPOUT LOCATION. REFER TO
DETAIL A08.4 FOR REFERANCE.
2/17/2025
LIC. NBR AR-007684
Architecture Roof Consulting
Construction Technology
OF SHEET(S)
SHEET NO.:
DATE:
CHECKED BY:
DRAWN BY:
JOB NO.:
COPYRIGHT 2025 A/R/C ASSOCIATES, INC.
REVISIONS
BY:DATENO.
Tel. (407) 896-7875 Fax. (407) 898-6043
601 North Fern Creek Avenue Suite 100, Orlando, FL
32803-4899
DESIGNED BY:
B ay
V is ta F un da m en ta l E le m en ta ry S ch oo l R oo f R ep la ce m en t a t:
Pi ne lla s
C ou nt y
Pu bl ic S ch oo ls
D r.
M .L
.K . J r.
St re et
S ou th , S t.
Pe te rs bu rg
, F L
A04
FA
ST
EN
ER
S C
H
ED
U
LE
, A
BB
R
EV
IA
TI
O N
S, A
N D
G
EN
ER
AL
N O
TE
S
24023.00
NVJ
TAH
02/18/2025
TAH
A. GENERAL NOTES:
1. THIS SCHEDULE AND THE FASTENING METHODS
INDICATED HEREIN ARE INTENDED TO ADDRESS
TYPICAL CONDITIONS, AND MAY NOT APPLY TO
ALL CONDITIONS FOR THIS PROJECT.
2. CONTRACTOR/INSTALLER MUST ALSO REFER TO THE
DETAILS FOR THIS SPECIFIC PROJECT. IN THE CASE OF
CONFLICTING DATA, THE PROJECT SPECIFIC DETAILS
SHALL GOVERN.
3. FOR ALL CONDITIONS NOT COVERED WITHIN
SCHEDULE, REFER TO FASTENER REQUIREMENTS OF
THE WRITTEN SPECIFICATIONS ABOVE OR CONSULT
WITH OWNER OR ARCHITECT.
4. MANUFACTURER OF ALL SPECIALITY FASTENER SHALL
PERFORM FIELD TESTING TO VERIFY WITHDRAWAL
VALUES & FASTENING PATTERNS FOR THE SPECIFIC
PROJECT CONDITIONS PRIOR TO INSTALLATION. REQ'D
A WRITTEN REPORT SHALL BE SUBMITTED TO THE
OWNER & ARCHITECT FOR REVIEW & APPROVAL.
5. ALL FASTENERS SHALL BE STAINLESS STEEL OR
HAVE A CORROSION RESISTANT COATING THAT
EXCEEDS F.M. APPROVAL STANDARD 4470, UNLESS
NOTED OTHERWISE.
B. WOOD BLOCKING (2" NOMINAL THICKNESS):
1. CONCRETE: ã"ø SELF-TAPPING MASONRY ST. STL.
SCREW AT 16" O.C., MAX., LENGTH AS REQ'D FOR 1
é" MIN. EMBEDMENT.-OR- â"ø DEFORMED OR FLUTED NAIL AT 12" O.C. MAX., LENGTH AS REQ'D FOR 1á" MIN.
EMBEDMENT. COUNTERSINK HEADS AS REQ'D.
2. CONCRETE BLOCK (CMU): ã"ø SELF-TAPPING
MASONRY ST. STL. SCREWS AT 12" O.C. MAX., LENGTH
AS REQ'D FOR 1é" MIN. EMBEDMENT. -OR- ã"ø HEAVY
DUTY SLEEVE STYLE EXPANSION BOLT ANCHOR (RAWL-
BOLT) @ 18" O.C., LENGTH AS REQ'D FOR 2" MIN.
EMBEDMENT. COUNTERSINK HEADS AS REQ'D.
3. BRICK: ã"ø SELF-TAPPING MASONRY ST. STL. SCREWS AT 12" O.C. MAX., LENGTH AS REQ'D FOR 1é" MIN.
EMBEDMENT. -OR- ã"ø HEAVY DUTY SLEEVE STYLE
EXPANSION BOLT ANCHOR (RAWL-BOLT) @ 18" O.C.,
LENGTH AS REQ'D FOR 2" MIN. EMBEDMENT.
COUNTERSINK HEADS AS REQ'D
4. STRUCTURAL STEEL: á"ø SELF-DRILLING, SELF-TAPPING
ST. STL. SCREWS WITH "WINGS" @ 16" O.C. MAX., LENGTH
AS REQ'D FOR å" MIN. PENETRATION OF THREADS
THROUGH STL. COUNTERSINK HEADS AS REQ'D.
FASTENER SCHEDULE:
J. APPLIED SHEETMETAL (COUNTERFLASHING, TERMINATION
BAR, ETC.):
1. WOOD BLOCKING: 12"ø SELF-TAPPING, STAINLESS
STEEL SCREWS AT 8" O.C. MAX., LENGTH AS REQ'D
FOR 1å" MIN. EMBEDMENT INTO WOOD. IF EXPOSED TO
THE WEATHER PROVIDE METAL BACKED NEOPORENE
SEALING WASHERS OR USE "SCOTS" TYPE SCREW WITH
INTEGRAL SEALING WASHER.
2. SHEETMETAL BACKING: 12"ø SELF-TAPPING STAINLESS
STEEL SCREWS AT 8" O.C. MAX., LENGTH AS REQ'D
FOR å" MIN. PENETRATION OF THREADS THROUGH
STEEL. IF EXPOSED TO THE WEATHER PROVIDE METAL
BACKED NEOPORENE SEALING WASHERS OR USE
"SCOTS" TYPE SCREW WITH INTEGRAL SEALING WASHER.
3. CONCRETE: á"ø SELF-TAPPING STAINLESS STEEL
MASONRY SCREWS AT 8" O.C. MAX. LENGTH AS
REQUIRED FOR á" MIN. EMBEDMENT. -OR- á" x 1å"
ZAMAC "NAILIN" DRIVE PIN, EXPANSION TYPE
FASTENERS @ 8" O.C. MAX., WITH STAINLESS STEEL
DRIVE PIN. IF EXPOSED TO THE WEATHER PROVDE
METAL BACKED NEOPRENE SEALING WASHERS-
INCREASE LENGTH IF REQ'D BY OVERLYING FINISH
FOR 1å" MIN. EMBEDMENT INTO CONCRETE (BLOCK).
4. CONCRETE BLOCK: á"ø SELF-TAPPING STAINLESS
STEEL MASONRY SCREWS AT 8" O.C. MAX. LENGTH AS
REQUIRED FOR 1å" MIN. EMBEDMENT. -OR- á"ø x å"
ZAMAC "NAILIN" DRIVE PIN, EXPANSION TYPE
FASTENERS @ 8" O.C. MAX., WITH STAINLESS STEEL
DRIVE PIN. IF EXPOSED TO THE WEATHER PROVIDE
METAL BACKED NEOPRENE SEALING WASHERS-
INCREASE LENGTH IF REQ'D BY OVERLYING FINISH
FOR 1å" MIN. EMBEDMENT INTO CONCRETE (BLOCK).
5. BRICK : á"ø SELF-TAPPING STAINLESS STEEL
MASONRY SCREWS AT 8" O.C. MAX. LENGTH AS
REQUIRED FOR 1å" MIN. EMBEDMENT. -OR- á"ø x 1å"
ZAMAC "NAILIN" DRIVE PIN, EXPANSION TYPE
FASTENERS @ 8" O.C. MAX., WITH STAINLESS STEEL
DRIVE PIN. IF EXPOSED TO THE WEATHER PROVDE
METAL BACKED NEOPRENE SEALING WASHERS.
ADJ ADJACENT
A/C AIR CONDITIONING
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECT(URAL)
BIT BITUMEINOUS
BLK BLOCK
BD BOARD
BLDG BUILDING
BUR BUILT UP ROOFING
CB CATCH BASIN
CLG CEILING
COL COLUMN
COMP COMPRESS (ED), (ION), (IBLE)
CONC CONCRETE
CMU CONCRETE MASONRY UNIT
CONST CONSRUCTION
CONT CONTINUOUS OR CONTINUE
CTR CENTER
C.F. CUBIC FOOT
DEMO DEMOLISH, DEMOLITION
DET DETAIL
DIAG DIAGONAL
DIA DIAMETER
DIM DIMENSION
DWG DRAWING
E EAST
ELEC ELECTRIC(AL)
EL ELEVATION
EQ EQUAL
EQUIP EQUIPMENT
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FIN FINSH (ED)
FLASH FLASHING
FLEX FELXIBLE
FTG FOOTING
FDN FOUNDATION
GA GAUGE
GALV GALVANIZED
HVAC HEATING/VENTILATION/AIR CONDITIONING
HT HEIGHT
HORZ HORIZONTAL
INCL INCLUDE(D), (ING)
INSUL INSULATE(D), (ION)
INT INTERIOR
JT JOINT
LW LIGHTWEIGHT
MFR MANUFACTURE(ER)
MAX MAXIMUM
MECH MECHANIC(AL)
MTL METAL
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED(ING)
NOM NOMINAL
N NORTH
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NO NUMBER
OC ON CENTER(S)
OPG OPENING
OPP OPPOSITE
OD OUTSIDE DIAMETER/DIM
PTD PAINT(ED)
PR PAIR
PL PLATE
PWD PLYWOOD
PVC POLYVINYL CHLORIDE
PSF POUNDS PER SQUARE FEET
PSI POUNDS PER SQUARE INCH
PC PRECAST CONCRETE
PT PRESSURE TREATED
RAD RADIUS
RWL RAINWATER LEADER
REF REFERENCE
REV REVISION
RD ROOF DRAIN
RO ROUGH OPENING
SCH SCHEDULE
SHT SHEET
SIM SIMILAR
S SOUTH
SPK SPEAKER
SPEC SPECIFICATION(S)
SQ SQUARE
SF SQUARE FEET
ST STL STAINLESS STEEL
STD STANDARD
STL STEEL
STRUCT STRUCTURAL
UNO UNLESS OTHERWISE NOTED
VERT VERTICAL
WWF WELDED WIRE FABRIC
W WEST
W/ WITH
W/O WITHOUT
WD WOOD
ABBREVIATIONS:
5. METAL DECK: á"ø SELF-TAPPING ST. STL. "DECK" SCREWS AT 12" O.C. MAX., LENGTH AS REQ'D FOR å"
MIN. PENETRATION THROUGH UNDERSIDE OF DECK.
COUNTERSINK HEADS AS REQ'D.
6. LIGHT GAGE METAL FRAMING: á"ø SELF-TAPPING ST.
STL. "DECK" SCREWS, 1 MIN. PER FRAMING MEMBER,
LENGTH AS REQ'D FOR å" MIN. PENETRATION
THROUGH FRAMING. COUNTERSINK HEADS AS REQ'D.
7. PLYWOOD DECK: á"ø SELF-TAPPING ST. STL. "DECK"
SCREWS AT 8" O.C. MAX., LENGTH AS REQUIRED FOR
å" MIN. PENETRATION THROUGH UNDERSIDE OF DECK.
COUNTERSINK HEADS AS REQUIRED.
8. WOOD BLOCKING: á"ø SELF-TAPPING ST. STL. "DECK"
SCREWS AT 16" O.C. MAX., LENGTH AS REQ'D FOR 1
å" MIN. EMBEDMENT -OR-TWO CONTINUOUS ã" BEADS
OF CONSTRUCTION ADHESIVE THE FULL LENGTH OF T
HE BOARD TO BE APPLIED AND 12d NAILS @ 4" O.C.
(IN TWO ROWS-STAGGERED).
C. PLYWOOD SHEATHING:
1. CONCRETE: á"ø SELF-TAPPING MASONRY SCREWS AT
12" O.C. MAX. (AT EDGES), AND 16" O.C.MAX. IN THE
FIELD, LENGTH AS REQ'D FOR 1å" MIN. EMBEDMENT,- OR- á"ø RAWL-SPLICE OROLYMPIC FLUTTED NAIL AT
THE SAME SPACING AS NOTED ABOVE, LENGTH AS
REQ'D FOR á" MIN. EMBEDMENT.
2. CONCRETE BLOCK (CMU): ã"ø SELF-TAPPING
MASONRY ST. STL. SCREWS AT 12" O.C. MAX., LENGTH
AS REQ'D FOR 1é" MIN. EMBEDMENT. -OR- ã"ø HEAVY
DUTY SLEEVE STYLE EXPANSION BOLT ANCHOR
(RAWL-BOLT) @ 18" O.C., LENGTH AS REQ'D FOR 2" MIN.
EMBEDMENT. COUNTERSINK HEADS AS REQ'D.
3. BRICK: á"ø SELF-TAPPING MASONRY SCREWS AT 12"
O.C. MAX. (AT EDGES), AND 16" O.C. MAX. IN THE
FIELD, LENGTH ASREQ'D FOR 1å" MIN. EMBEDMENT,- OR- á"ø RAWL-SPLICE OR OLYMPIC FLUTTED NAIL AT
THE SAME SPACING AS NOTED ABOVE, LENGTH AS
REQ'D FOR 1á" MIN. EMBEDMENT.
4. STRUCTURAL STEEL: #10ø SELF-DRILLING, SELF-
TAPPING SCREWS WITH "WINGS" @ 12" O.C. MAX. (AT
EDGES), AND 16" O.C. MAX. IN THE FIELD, LENGTH AS
REQ'D FOR å"MIN. PENETRATION OF THREADS
THROUGH STEEL.
5. METAL DECK: #10ø SELF-TAPPING "DECK" SCREWS AT
12" O.C. MAX. (AT EDGES), AND 16" O.C. MAX. IN THE
FIELD, LENGTH AS REQ'D FOR å" MIN. PENETRATION
THROUGH UNDERSIDE OF DECK.
6. LIGHT GAGE METAL FRAMING: #10ø SELF-TAPPING
"DECK" SCREWS AT 12" O.C. MAX. (AT EDGES), AND
16" O.C. MAX. ALONG EACH FRAMING MEMBER,
LENGTH AS REQ'D FOR å" MIN. PENETRATION
THROUGH FRAMING. FRAMING TO BE SPACED AT 24"
O.C. MAX., UNLESS NOTED OTHERWISE BY DETAILS.
7. WOOD FRAMING: #10ø SELF-TAPPING "DECK" SCREWS
AT 12" O.C. MAX. ALONG EACH FRAMING MEMBER,
LENGTH AS REQ'D FOR 1å" MIN. EMBEDMENT -OR- 8d
ANNULAR RING NAILS AT 6" O.C. MAX. (AT EDGES) & 1
2" O.C. MAX. IN FIELD. DECREASE SPACING AT EDGES
& RAKE ZONES TO 4" O.C. MAX. AT EDGES, & 8" O.C.
MAX. IN FIELD.
D. METAL DECK:
1. INSTALL AND SECURE PER STEEL JOIST INSTITUTE (SJI)
GUIDELINES, SEE SPECS OR STRUCTURAL DETAILS FOR
INFO.
E. MINOR STRUCTURAL STEEL:
1. ANCHORAGE OF LOAD BEARING STEEL AND LARGE
STEEL FABRICATIONS, (SUCH AS LADDERS), IS TO BE
AS DEFINED BY THE STRUCTURAL ENGINEERING
DRAWINGS, OR AS ENGINEERED BY THE SUPPLIER.
MINOR STRUCTURAL STEEL WOULD BE CONSIDERED
ITEMS SUCH AS SUPPORT STANDS, WALL LEDGER
ANGLES, ETC.
2. CONCRETE: ã"ø HEAVY-DUTY, SLEEVE STYLE
EXPANSION BOLT ANCHOR (RAWL-BOLT) @ 16" O.C.,
LENGTH AS REQ'D FOR 2" MIN. EMBEDMENT.
3. CONCRETE BLOCK (CMU): ã"ø HEAVY-DUTY, SLEEVE
STYLE EXPANSION BOLT ANCHOR (RAWL-BOLT) @ 16"
O.C., LENGTH AS REQ'D FOR 2" MIN. EMBEDMENT.
IF CMU IS HOLLOW, BREAK INTO BLOCK ABOVE, AND
FILL CELL OF BLOCK TO RECEIVE ANCHOR SOLID,
PERFORM ANY REPAIR AND PATCHING NECESSARY.
4. BRICK: ã"ø HEAVY-DUTY, SLEEVE STYLE EXPANSION
BOLT ANCHOR (RAWL-BOLT) @ 16" O.C., LENGTH AS
REQ'D FOR 2" MIN. EMBEDMENT.
5. STRUCTURAL STEEL: áø SELF-DRILLING, SELF-TAPPING SCREW @ 16" O.C., LENGTH AS REQUIRED FOR å" MIN.
PENETRATION OF THREADS THROUGH STEEL.
F. RIGID INSULATION BOARD:
1. INSTALL AND SECURE PER THE MANUFACTURER'S
RECOMMENDATIONS, TESTING AND APPROVALS TO
COMPLY WITH THE DESIGN REQUIREMENTS OF THIS
PROJECT. SEE PROJECT SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
G. ROOF MEMBRANE SYSTEM:
1. INSTALL AND SECURE PER THE MANUFACTURE'S
RECOMMENDATIONS, TESTING AND APPROVALS TO
COMPLY WITH THE DESIGN REQUIREMENTS OF THIS
PROJECT. SEE PROJECT SPECIFICATIONS FOR
ADDITIONAL INFO.
H. FLANGED SHEETMETAL (EDGE METAL):
1. WOOD BLOCKING: #12ø x 1å" ANNULAR RING ST. SLT.
ROOFING NAILS AT 4" O.C. MAX., STAGGERED IN 2
ROWS AT é"± FROM EDGES OF FLANGE.
2. LIGHTGAGE METAL: #12ø SELF TAPPING, STAINLESS
STEEL, FLAT OR WAFER HEAD SCREWS AT 12" O.C. MAX.
3. CONCRETE: á"ø x 1å"ZAMAC "NAIL-IN" DRIVE PIN, EXPANSION TYPE FASTENER @ 12" O.C., MAX. WITH
STAINLESS STEEL DRIVE PIN.
I. CLEATS FOR SHEET METAL:
1. WOOD BLOCKING: #12ø x 1å" ANNULAR RING STAINLESS
STEEL ROOFING NAILS AT 8" O.C. MAX., (4" O.C. AT
CORNER ZONES OF ROOF)
2. LIGHT GAGE METAL: #12ø SELF TAPPING, STAINLESS
STEEL, FLAT OR WAFER HEAD SCREWS AT 12" O.C. MAX.
3. CONCRETE: á"ø x å" ZAMAC "NAIL-IN" DRIVE PIN, EXPANSION TYPE FASTENER @ 12" O.C., MAX. WITH
STAINLESS STEEL DRIVE PIN.
4. CONCRETE BLOCK: á"ø x å" ZAMAC "NAIL-IN" DRIVE
PIN, EXPANSION TYPE FASTENER @ 12" O.C., MAX. WITH
STAINLESS STEEL DRIVE PIN.
5. BRICK: á"ø x å" ZAMAC "NAIL-IN" DRIVE PIN, EXPANSION TYPE FASTENER @ 12" O.C., MAX. WITH
STAINLESS STEEL DRIVE PIN.
GENERAL NOTES:
1. THE DIMENSIONS SHOWN ON THE ROOF PLANS OF THIS PROJECT WERE
TAKEN FROM THE OWNER'S ARCHITECTURAL DOCUMENTS OR ARE THE
RESULT OF FIELD MEASUREMENTS TAKEN BY A/R/C ASSOCIATES. THIS
INFORMATION IS GIVEN TO ASSIST PROSPECTIVE BIDDERS
ESTABLISHING THE APPROXIMATE SCOPE OF THE PROJECT. AS A PRE-
REQUISITE FOR BIDDING THE PROJECT, HOWEVER, ALL DIMENSIONS
SHALL BE FIELD VERIFIED BY EACH BIDDER SO THAT THE DIMENSIONS
UTILIZED IN BIDDING THE PROJECT WILL BE THOSE DIMENSIONS TAKEN,
CONFIRMED OR CORRECTED BY THE BIDDER. CONTRACTOR SHALL
VERIFY ALL DIMENSIONS, DETAILS, AND EQUIPMENT NOTED AND SHALL
NOTIFY THE ARCHITECT OF ANY DISCREPANCIES PRIOR TO
PROCEEDING WITH THE WORK.
2. THE REROOFING PLAN IS GENERAL IN NATURE AND INDICATES
APPROXIMATE EXISTING CONDITIONS AT THE PROJECT SITE. ALL
BUILDINGS ON THE SITE ARE INCLUDED IN THE PROJECT UNLESS
SPECIFICALLY NOTED OTHERWISE (N.I.C.). THE CONTRACTOR SHALL BE
RESPONSIBLE FOR A VISUAL FIELD SURVEY (PRIOR TO BID) IN REGARD
TO QUANTITIES, AND VERIFICATION OF GENERAL CONFORMANCE WITH
THE FLORIDA BUILDING CODE.
3. PRIOR TO THE START OF ANY WORK, THE CONTRACTOR WITH THE
PROJECT ARCHITECT AND OWNER'S REPRESENTATIVE SHALL VISIT THE
SITE AND VIDEO TAPE THE ROOF AND ALL SPACES UNDERNEATH THAT
MAY BE AFFECTED BY THIS ROOFING PROJECT IN ORDER TO
DETERMINE THE CONTRACTOR'S RESPONSIBILITY IN KEEPING THOSE
ITEMS IN THEIR CURRENT STATUS, SPECIAL ATTENTION SHALL BE GIVEN
TO CEILING TILES, EXISTING LIGHT FIXTURES, EXTERIOR AND INTERIOR
WALL FINISHES, AND SIDEWALKS, ETC. PARTICULARLY IN THOSE AREAS
WHERE EXISTING LEAKS ARE PRESENT, BELOW EXPANSION JOINTS AND
SPECIAL CONDITIONS.
4. IN THE EVENT OF WATER DAMAGE TO THE INTERIOR OF STRUCTURES, A
DAMAGE REPORT, WITH PHOTOGRAPHS SHALL BE COMPLETED BY THE
PROJECT ARCHITECT. THE REPORT SHALL BE SUBMITTED TO THE
OWNER AND THE CONTRACTOR FOR THEIR RECORDS.
5. CONTRACTOR SHALL BE RESPONSIBLE TO REMOVE, REINSTALL, OR
REPLACE ALL CEILING PANELS AND/OR CEILING GRIDS WHICH MAY
HAVE BEEN DISTURBED OR DAMAGED IN THE CONSTRUCTION PROCESS.
6. NOTIFY THE LOCAL POLICE OFFICIALS, THE OWNER OR ARCHITECT BY
TELEPHONE IN EACH INSTANCE OF PROPERTY DAMAGE RESULTING
FROM FIRE, WATER DAMAGE, ILLEGAL ENTRY, VANDALISM, THEFT OR
BURGLARY, OR VEHICLE DAMAGE WITHIN 24 HOURS OF DISCOVERING
THE INCIDENT.
7. ANY EQUIPMENT, VENTS, CURBS, ETC. FOUND UNDER EXISTING ROOF
ARE TO BE BROUGHT TO THE ATTENTION OF THE ARCHITECT IN WRITING
FOR PROPER COORDINATION.
8. VERIFY LOCATIONS OF ALL ROOFTOP EQUIPMENT AND ROOF
PENETRATIONS SO AS TO AVOID CONFLICT WITH WALLS, ROOF EDGES,
AND OTHER PENETRATIONS. RELOCATE ANY SUCH EQUIPMENT OR ROOF
PENETRATIONS A MINIMUM OF TWO FEET AWAY FROM OTHER ROOFTOP
EQUIPMENT, WALLS, ROOF EDGES OR OTHER PENETRATIONS SO AS TO
ELIMINATE THIS CONFLICT.
9. CONTRACTOR SHALL NOT USE ANY HEAVY MACHINERY ON THE ROOF
(BOBCATS, ETC.)
10. REMOVE AND INFILL AS NECESSARY ANY, AND ALL, SMALL ROOF
PENETRATIONS WHICH HAVE BEEN ABANDONED, SUCH AS PITCH PANS,
SMALL CONDUITS, MEMBRANE VENTS, ETC. NOT ALL OF THESE ARE
SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL VERIFY THOSE
CONDITIONS PRIOR TO BIDDING.
11. VERIFY PRECISE LOCATIONS OF EXPANSION JOINTS SHOWN ON THE
ROOF PLANS AND ALSO LOCATIONS OF DECK CHANGES FROM THE
UNDERSIDE OF DECK. TRANSFER LOCATION OF THESE JOINTS TO THE
TOP OF THE ROOF DECK PRIOR TO CONSTRUCTING THE EXPANSION
JOINT CURBS. COORDINATE ANY NEW LOCATIONS WITH ARCHITECT.
12. DETAILS REFERENCED ON THE CONTRACT DRAWINGS ARE "TYPICAL"
AND ARE NOT CUT AT EVERY LOCATION WHERE THE CONDITION
OCCURS. BID AND EXECUTE A COMPLETE PROJECT AS IF DETAILS
WERE "CUT" AT EVERY LOCATION WHERE SUCH CONDITION OR SIMILAR
CONDITION OCCURS.
13. PERIMETER EDGE METAL MAY VARY IN DIMENSIONAL REQUIREMENTS.
VERIFY BLOCKING REQUIREMENTS IN EACH ROOF AREA PRIOR TO
BIDDING.
14. SHEET METAL DETAILS AND TRANSITIONS NOT SHOWN SHALL BE
REQUIRED AS IF SHOWN. PREPARE, AND SUBMIT SHOP DRAWINGS OF
THESE REQUIREMENTS TO THE ARCHITECT FOR APPROVAL PRIOR TO
SHOP FABRICATION.
15. CONTRACTOR SHALL PROVIDE ALL SUPPLEMENTAL MATERIALS
REQUIRED TO PROPERLY INSTALL, SUPPORT AND BRACE ALL ITEMS
AND COMPONENTS WITHIN THE WORK.
16. AT REROOFING OF EXISTING "FLAT" ROOFS, THE PLANS INDICATE
MINIMUM FINISHED ROOF SLOPES TO BE PROVIDED. CONTRACTOR IS
TO PERFORM ANY REMEDIAL WORK REQUIRED TO ELIMINATE ANY
PONDING WATER.
17. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL
NECESSARY PIPE PENETRATIONS, ROOFING CURBS, AND OTHER
MISCELLANEOUS MATERIALS FOR COMPLETE AND FINISHED
INSTALLATION.
18. ALL NEW AND EXISTING ROOF MOUNTED EQUIPMENT, CURBS, PIPE
SUPPORTS, WOODWORK AND SHEET METAL WORK SHALL BE SECURED
WITH FASTENERS AND/OR STAINLESS STEEL CABLE HOLD-DOWNS TO
SAFELY RESIST WIND FORCES AS DESCRIBED BY THE FLORIDA
BUILDING CODE DATA INCLUDED IN THESE DOCUMENTS.
19. PROVIDE WALKWAY PADS AROUND, BUT NOT LIMITED TO, COOLING
TOWERS, ROOF HATCHES, ROOF LADDERS AND ANY EQUIPMENT
REQUIRING PERIODIC MAINTENANCE. WALKWAY PADS SHALL EXTEND
AROUND ALL EQUIPMENT AND SHALL BE INSTALLED IN ACCORDANCE
WITH THE MANUFACTURER'S RECOMMENDATIONS.
20. CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR AND PAINTING /
FINISHING OF ALL SURFACES EXPOSED OR DAMAGED AS A RESULT OF
ROOFING REPLACEMENT. WORK NOT COVERED BY NEWLY INSTALLED
WORK. REPAIRS AND FINISHES SHALL MATCH EXISTING ADJACENT
CONDITIONS TO REMAIN UNCHANGED.
5 9
2/17/2025
421/2"
EXIST. STUCCO
2x4
A07.1
2 1/2
1"
1/ 2"
4"
2"
1/2
3/ 4"
METAL PANEL -
DRIP EDGE
FLASHING / GUTTER
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS
TO FORM ONE CONTINOUS PIECE,
EXCEPT AT ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
45 3 17 42
A
B
EXIST.
STUCCO
3" M
IN
235180
MTL. COUNTER
FLASHING -
SURFACE APPLIED
1/ 2"
1/2
3/ 4"
1/2"
3/4"
1/2" 3 1/2"
3"
1 1/2"
1 1/2"
2"
1 1/2"
BASE MTL.
COUNTER FLASHING
W/ "Z" CLEAT
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS
TO FORM ONE CONTINOUS PIECE,
EXCEPT AT ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
3/
F
45 3 17
5180 23 A
E
EXIST. STUCCO
2X4
METAL PANEL - RAKE
EDGE FLASHING
/4
4 1/4"
1 1/2"
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS
TO FORM ONE CONTINOUS PIECE,
EXCEPT AT ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
1/2"1 1/2"
3/
61 41
EXIST. STUCCO
2X4
4"
2"
METAL PANEL -
DRIP EDGE
FLASHING
3/ 4" 1/2
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS
TO FORM ONE CONTINOUS PIECE,
EXCEPT AT ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
2 1/2
1/2" 1"
36" WIDE STRIP OF SELF
ADHERED MOD. BIT.
MEMBRANE - CENTER ON
VALLEY
0.040" PRE-FINSIHED
ALUM. VALLEY METAL
2X4
0.040" ALUM. 12" WIDE
VALLEY REINFORCEMENT
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS
TO FORM ONE CONTINOUS PIECE,
EXCEPT AT ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
3"
6"
1"
1"
INFILL AIR SPACE
WITH INSULATION
ALONG RIDGE
A
2X6
C
D
6" MAX.
1/2"
1 1/2"
1/2"
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS
TO FORM ONE CONTINOUS PIECE,
EXCEPT AT ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
EDGE METAL
LAP
JOINT
SEALANT
3"
EDGE METAL
LAP
JOINT
SEALANT
3"
EDGE METAL
LAP
JOINT
SEALANT
3"
EDGE METAL
SPLICE JOINT
SEALANT
LIC. NBR AR-007684
Architecture Roof Consulting
Construction Technology
OF SHEET(S)
SHEET NO.:
DATE:
CHECKED BY:
DRAWN BY:
JOB NO.:
COPYRIGHT 2025 A/R/C ASSOCIATES, INC.
REVISIONS
BY:DATENO.
Tel. (407) 896-7875 Fax. (407) 898-6043
601 North Fern Creek Avenue Suite 100, Orlando, FL
32803-4899
DESIGNED BY:
B ay
V is ta F un da m en ta l E le m en ta ry S ch oo l R oo f R ep la ce m en t a t:
Pi ne lla s
C ou nt y
Pu bl ic S ch oo ls
D r.
M .L
.K . J r.
St re et
S ou th , S t.
Pe te rs bu rg
, F L
A05
R O
O
FI
N G
D
ET
AI
LS
24023.00
NVJ
TAH
02/18/2025
TAH
2. EXISTING WALL
3. EXISTING METAL DECK
17. NON-TAPERED RIGID INSULATION
22. COUNTERFLASHING
23. SEALANT
24. BUTYL FLASHING TAPE
32. CONTINUOUS CLEAT
34. NEW GUTTER
40. EXIST. VENT STACK, EXTEND AS REQUIRED
41. P.T. WOOD BLOCKING TO BE FASTENED AT 12" O.C. MAX. AND
STAGGER - COUNTERSINK HEADS
42. 5/8" PLYWOOD - SCREW FASTEN @ 8" O.C. (MAX) TOP & BOTTOM &
STAGGERED - COUNTERSINK HEADS
45. EXISTING STRUCTURE
51. SELF-ADHERING UNDERLAYMENT
54. STRIP-IN FLASHING
61. EDGE METAL
80. METAL ROOF PANEL
A. CLOSED CELL RUBBER CLOSURE - CUT AS REQUIRED FOR
FUNCTION FIT WITHIN EACH PANEL AND SEAL WITH ONE-PART
URETHANE SEALANT
B. STAINLESS STEEL SCREWS OR DRIVE PINS WITH METAL BACKED
NEOPRENE WASHERS
C. 0.040" ALUMINUM CAP FLASHING - SLIDE OVER AN 0.050"
ALUMINUM "Z-CLOSURE" AND SECURE WITH "Z CLOSURE" IN FIELD
WITHOUT CUTTING
D. "BOX" TOP PANEL BEHIND "Z CLOSURE" IN FIELD WITHOUT CUTTING
E. 0.040" ALUMINUM RAKE FLASHING - SLIDE OVER AN 0.050"
ALUMINUM "Z-CLOSURE" AND SECURE WITH BUTTON PUNCH -
PROVIDE SPLICE JOINT CLEAT AT S;ICE JOINT.
F. 0.040" ALUMINUM SIDE WALL FLASHING - SLIDE OVER AN 0.050"
ALUMINUM "Z-CLOSURE" AND SECURE W/ BUTTON PUNCH.
G. 040.0" MILL FINISH ALUM. VALLEY FLASHING
TYP. DETAIL NOTES:
3" = 1'-0"
TYPICAL DRIP EDGE FLASHING W/ GUTTERA05 .1
3" = 1'-0"
TYPICAL SIDE WALL FLASHINGA05 .4
3" = 1'-0"
TYPICAL RAKE EDGE FLASHINGA05 .33" = 1'-0"
TYPICAL DRIP EDGE FLASHINGA05 .2
3" = 1'-0"
TYPICAL VALLEY FLASHINGA05 .63" = 1'-0"
TYPICAL RIDGE FLASHINGA05 .5
6" = 1'-0"
LAP JOINT
6" = 1'-0"
LAP JOINT
6" = 1'-0"
LAP JOINT
6" = 1'-0"
CONCEALED SPLICE JOINT
2/17/2025
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS TO
FORM ONE CONTINOUS PIECE, EXCEPT AT
ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
METAL PANEL -
RAKE EDGE
FLASHING AT HEAD
WALL
1 1/2" 1/2"
2 3/4"
3/ 4"
1/2
1 1/2"
2"
E
SIM.
2x6
EDGE METAL
SPLICE JOINT
SEALANT
SPLICE JOINT - SEE
DETAIL A05.3
SPLICE
JOINT - SEE
DETAIL A06.1
EDGE
FLASHING -
SEE DETAIL
A05.2
LIC. NBR AR-007684
Architecture Roof Consulting
Construction Technology
OF SHEET(S)
SHEET NO.:
DATE:
CHECKED BY:
DRAWN BY:
JOB NO.:
COPYRIGHT 2025 A/R/C ASSOCIATES, INC.
REVISIONS
BY:DATENO.
Tel. (407) 896-7875 Fax. (407) 898-6043
601 North Fern Creek Avenue Suite 100, Orlando, FL
32803-4899
DESIGNED BY:
B ay
V is ta F un da m en ta l E le m en ta ry S ch oo l R oo f R ep la ce m en t a t:
Pi ne lla s
C ou nt y
Pu bl ic S ch oo ls
D r.
M .L
.K . J r.
St re et
S ou th , S t.
Pe te rs bu rg
, F L
A06
R O
O
FI
N G
D
ET
AI
LS
24023.00
NVJ
TAH
02/18/2025
TAH
2. EXISTING WALL
3. EXISTING METAL DECK
17. NON-TAPERED RIGID INSULATION
22. COUNTERFLASHING
23. SEALANT
24. BUTYL FLASHING TAPE
32. CONTINUOUS CLEAT
34. NEW GUTTER
40. EXIST. VENT STACK, EXTEND AS REQUIRED
41. P.T. WOOD BLOCKING TO BE FASTENED AT 12" O.C. MAX. AND
STAGGER - COUNTERSINK HEADS
42. 5/8" PLYWOOD - SCREW FASTEN @ 8" O.C. (MAX) TOP & BOTTOM &
STAGGERED - COUNTERSINK HEADS
45. EXISTING STRUCTURE
51. SELF-ADHERING UNDERLAYMENT
54. STRIP-IN FLASHING
61. EDGE METAL
80. METAL ROOF PANEL
A. CLOSED CELL RUBBER CLOSURE - CUT AS REQUIRED FOR
FUNCTION FIT WITHIN EACH PANEL AND SEAL WITH ONE-PART
URETHANE SEALANT
B. STAINLESS STEEL SCREWS OR DRIVE PINS WITH METAL BACKED
NEOPRENE WASHERS
C. 0.040" ALUMINUM CAP FLASHING - SLIDE OVER AN 0.050"
ALUMINUM "Z-CLOSURE" AND SECURE WITH "Z CLOSURE" IN FIELD
WITHOUT CUTTING
D. "BOX" TOP PANEL BEHIND "Z CLOSURE" IN FIELD WITHOUT CUTTING
E. 0.040" ALUMINUM RAKE FLASHING - SLIDE OVER AN 0.050"
ALUMINUM "Z-CLOSURE" AND SECURE WITH BUTTON PUNCH -
PROVIDE SPLICE JOINT CLEAT AT S;ICE JOINT.
F. 0.040" ALUMINUM SIDE WALL FLASHING - SLIDE OVER AN 0.050"
ALUMINUM "Z-CLOSURE" AND SECURE W/ BUTTON PUNCH.
G. 040.0" MILL FINISH ALUM. VALLEY FLASHING
TYP. DETAIL NOTES:
TYP. TERMINATION AT RIDGE CAPA06 .5
3" = 1'-0"
EDGE METAL FLASHING AT HALF RIDGEA06 .1
EDGE METAL FLASHING CORNER TRANSITIONA06 .4 RIDGE TERMINATION AT WALLA06 .6
CONCEALED
SPLICE JOINT -
SEE DETAIL
A06.1
6" MIN.
LAP JOINT - SEE
DETAIL A05.3
0.040" MILL FINISH ALUM.
FULLY WELDED / EXPOXIED
SINGLE PIECE FABRICATION
0.040" ALUM.
FULLEY WELDED /
EPOXIED SINGLE -
PIECE FABRICATION
LAP JOINT - SEE
DETAIL A05.5
LAP JOINT -
SEE DETAIL
A05.4
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS TO
FORM ONE CONTINOUS PIECE, EXCEPT AT
ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
SPLICE JOINT -
SEE DETAIL
A05.4
E
A06.1
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS TO
FORM ONE CONTINOUS PIECE, EXCEPT AT
ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
6" = 1'-0"
CONCEALED SPLICE JOINT
EA05.3
C A05.5
SPLICE
JOINT - SEE
DETAIL A05.5
0.040" ALUM. FILLY
WELDED / EPOXIED
SINGLE PIECE
FABRICATION
0.040" ALUM. FILLY
WELDED / EPOXIED
SINGLE PIECE
FABRICATION
C A05.3
LAP JOINT
FLASHING SEE
DETAIL A05.4
22A05.4
LAP JOINT
FLASHING SEE
DETAIL A05.4
B
LAP JOINT -
SEE DETAIL
A05.2
FA05.2
18"
18"
CA05.5
C A05.4
TYP. RAKE EDGE END FLASHING AT DRIP EDGEA06 .2
18"
18"
A 7.
A0 5.3
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS TO
FORM ONE CONTINOUS PIECE, EXCEPT AT
ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
18"
3" MIN.
2/17/2025
NEW 4"x4"x
1/8" MILL
FINISH ALUM.
DOWNSPOUTS
EXIST. STORM
DRAIN PIPE
DOWNSPOUT ATTACHED TO
GUTTER WITH TWO SCREWS W/
NEOPRENE WASHERS - DO NOT
WELD DOWNSPOUT TO GUTTER
3' -0
O .C
M A X
M A X
34A07.1
NEW ALUM.
SQUARE TO
ROUND ADAPTER
COLLAR
1/8" X 1" MILL FINISH
ALUM. BRACKETS @
36" O.C. MIN. -
FASTENERS SHALL BE
ST. STL.
NEW 4"x4"x
1/8" MILL
FINISH ALUM.
DOWNSPOUTS
PROVIDE INTEGRAL
WELDED PLATE TO
DRAIN W/O 45
DEGREE ELBOW
DOWNSPOUT ATTACHED TO
GUTTER WITH TWO SCREWS W/
NEOPRENE WASHERS - DO NOT
WELD DOWNSPOUT TO GUTTER
3' -0
O .C
M A X
M A X
A07.1 34
1/8" X 1" MILL FINISH
ALUM. BRACKETS @
36" O.C. MIN. -
FASTENERS SHALL BE
ST. STL.
3" 1'-
SPLASH BLOCK -
SEE DETAIL A08.4
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS
TO FORM ONE CONTINOUS PIECE,
EXCEPT AT ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
A
A
ROOF PANEL
0.050" 3 -
PIECE FULLY
WELDED MILL
FINISH ALUM.
GUTTER
7"
MECH FASTENERS INTO
BLOCKING AND WALL
0.050" MILL FINISH
ALUM. GUTTER SPACER -
3/16" DIA. "POP" RIVET
AT EACH END AND
SPACE ALTERNATELY
BETWEEN BRACKETS
A05.1
1/4" X 1" MILL FINISH
ALUM. GUTTER
BRACKETS X3 PER
10'-0" LENGTH
1/ 2"
/2
1/ 2"
POP RIVET OR ATTACH
SCREW BRACKET W/
NEOPRENE WASHER TO
GUTTER
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS
TO FORM ONE CONTINOUS PIECE,
EXCEPT AT ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
1/4" x 1" MILL FINISHED
ALUMINUM GUTTER
BRACKETS X3 PER
10'-0" LENGTH
EXIST. ROOF
PANEL
1/2" 1"
1"
1"
POP RIVET OR ATTACH
SCREW BRACKET W/
NEOPRENE WASHER TO
GUTTER
MECH FASTENERS INTO
BLOCKING AND DECK
0.050" MILL FINISH
ALUM. GUTTER SPACER -
3/16" DIA. "POP" RIVET
AT EACH END AND
SPACE ALTERNATELY
BETWEEN BRACKETS
0.050" MILL
FINISH ALUM.
GUTTER
7"
1/ 2"
A05.1 61
1/ 2"
/2
"POP"
RIVETS - 4
EA. SIDE
FULLY WELD
SEAMS
EDGE METAL
LAP
JOINT
SEALANT
3"
LIC. NBR AR-007684
Architecture Roof Consulting
Construction Technology
OF SHEET(S)
SHEET NO.:
DATE:
CHECKED BY:
DRAWN BY:
JOB NO.:
COPYRIGHT 2025 A/R/C ASSOCIATES, INC.
REVISIONS
BY:DATENO.
Tel. (407) 896-7875 Fax. (407) 898-6043
601 North Fern Creek Avenue Suite 100, Orlando, FL
32803-4899
DESIGNED BY:
B ay
V is ta F un da m en ta l E le m en ta ry S ch oo l R oo f R ep la ce m en t a t:
Pi ne lla s
C ou nt y
Pu bl ic S ch oo ls
D r.
M .L
.K . J r.
St re et
S ou th , S t.
Pe te rs bu rg
, F L
A07
R O
O
FI
N G
D
ET
AI
LS
24023.00
NVJ
TAH
02/18/2025
TAH
2. EXISTING WALL
3. EXISTING METAL DECK
17. NON-TAPERED RIGID INSULATION
22. COUNTERFLASHING
23. SEALANT
24. BUTYL FLASHING TAPE
32. CONTINUOUS CLEAT
34. NEW GUTTER
40. EXIST. VENT STACK, EXTEND AS REQUIRED
41. P.T. WOOD BLOCKING TO BE FASTENED AT 12" O.C. MAX. AND
STAGGER - COUNTERSINK HEADS
42. 5/8" PLYWOOD - SCREW FASTEN @ 8" O.C. (MAX) TOP & BOTTOM &
STAGGERED - COUNTERSINK HEADS
45. EXISTING STRUCTURE
51. SELF-ADHERING UNDERLAYMENT
54. STRIP-IN FLASHING
61. EDGE METAL
80. METAL ROOF PANEL
A. CLOSED CELL RUBBER CLOSURE - CUT AS REQUIRED FOR
FUNCTION FIT WITHIN EACH PANEL AND SEAL WITH ONE-PART
URETHANE SEALANT
B. STAINLESS STEEL SCREWS OR DRIVE PINS WITH METAL BACKED
NEOPRENE WASHERS
C. 0.040" ALUMINUM CAP FLASHING - SLIDE OVER AN 0.050"
ALUMINUM "Z-CLOSURE" AND SECURE WITH "Z CLOSURE" IN FIELD
WITHOUT CUTTING
D. "BOX" TOP PANEL BEHIND "Z CLOSURE" IN FIELD WITHOUT CUTTING
E. 0.040" ALUMINUM RAKE FLASHING - SLIDE OVER AN 0.050"
ALUMINUM "Z-CLOSURE" AND SECURE WITH BUTTON PUNCH -
PROVIDE SPLICE JOINT CLEAT AT S;ICE JOINT.
F. 0.040" ALUMINUM SIDE WALL FLASHING - SLIDE OVER AN 0.050"
ALUMINUM "Z-CLOSURE" AND SECURE W/ BUTTON PUNCH.
G. 040.0" MILL FINISH ALUM. VALLEY FLASHING
TYP. DETAIL NOTES:
1 1/2" = 1'-0"
DOWNSPOUT DETAIL - DISCHARGE TO STORM DRAINA07 .61 1/2" = 1'-0"
DOWNSPOUT DETAIL - DISCHARGE TO GRADEA07 .5
CURVED GUTTER FABRICATIONA07 .2
GUTTER
RIVET & SEAL W/
EPOXY
COVER PLATESECTION A - A
3" MIN
1/2"3/8"
SLOTTED HOLES FOR
ATTACHMENT AND
EXPANSION COVER PLATE
NOTES:
1. WELD (AS PER METAL TYPE) ALL LAPS AND CORNER
INSERTS TO FORM ONE CONTINUOUS PIECE EXCEPT
FOR EXPANSION JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD VERIFIED
3. MEMBRANE, GUTTER, AND OTHER COMPONENTS NOT
SHOWN FOR CLARITY
4. EXPANSION JOINT IS TYPICAL AND SHOULD BE
APPLIED TO ALL GUTTER TYPES
6" MIN.
COVER PLATE
SLOTTED HOLES
FOR ATTACHMENT
AND EXPANSION
COVER PLATE
SUPPORT BRACKET
GUTTER
TYP. GUTTER EXPANSION JOINT DETAILA07 .4
GUTTER
ENDCLOSURE
1/4" x 1" ALUM.
BRACKET AT
30" O.C.
4" MIN.
M
IN
2 FASTENERS MIN.
4"X4" X 1/8"
THICK
EXTRUDED
ALUM.
DOWNSPOUT
1" WIDE 1/8"
THICK MILL
FINISH ALUM.
BRACKET.
FLASHING TAPE
EXISTING
STRUCTURE
DOWNSPOUT SLIDE
OVER THROAT
AND SECURE WITH
(3) #10 ST. STL.
SHEET METAL
1/8" ST. STL. "POP"
RIVETS - 8 PER
THROAT
SLIT BOTTOM
OF GUTTER
FOLD EARS
AND ATTACH
TO DOWNSOUT
RAISE END
IF AT WALL
OR CORNER
GUTTER
SPACER
GUTTER TERMINATION AND DOWNSPOUT CONNECTION FABRICATIONA07 .36" = 1'-0"
TYP. GUTTER FABRICATION AND METAL EDGE FABRICATIONA07 .1
6" = 1'-0"
CONCEALED SPLICE JOINT
6" = 1'-0"
SPLICE JOINT - OVERLAP
8 9
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS TO
FORM ONE CONTINOUS PIECE, EXCEPT AT
ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
SEE DETAIL A07.1
FULL WELDED
0.050" ALUM.
GUTTER - SEE
PROFILE BELOW
SPICE JOINT
SEE DETAIL
A07.1
A .1
WELD ENDCLOSURE
2/17/2025
SAW CUT
NOTES:
BLOCK SHALL BE SOLID CONCRETE - SET BLOCK ON SOLID. LEVEL SURFACE.
SET ONE SPLASH BLOCK AT EACH DOWNSPOUT LOCATION UNLESS OTHERWISE
NOTED ON THE PLANS.
GRADE
2x2 - 10/10 GALV.
WELDED WIRE MESH
2" M
IN
. 1 1/2" MIN.
ONE PIECE FLASHING "BOOT" UNIT
CONSTRUCTED OF SILICONE
RUBBER
- PROFILE & ANCHOR AS PER
MANUFACTURER (PROVIDE
"RETROFIT"
TYPE BOOT IF REQUIRED - F.V.)
ST. STL. HOOD SOLDER/WELD
PER MTL. TYPE
STANDING SEAM
3/
LIC. NBR AR-007684
Architecture Roof Consulting
Construction Technology
OF SHEET(S)
SHEET NO.:
DATE:
CHECKED BY:
DRAWN BY:
JOB NO.:
COPYRIGHT 2025 A/R/C ASSOCIATES, INC.
REVISIONS
BY:DATENO.
Tel. (407) 896-7875 Fax. (407) 898-6043
601 North Fern Creek Avenue Suite 100, Orlando, FL
32803-4899
DESIGNED BY:
B ay
V is ta F un da m en ta l E le m en ta ry S ch oo l R oo f R ep la ce m en t a t:
Pi ne lla s
C ou nt y
Pu bl ic S ch oo ls
D r.
M .L
.K . J r.
St re et
S ou th , S t.
Pe te rs bu rg
, F L
A08
R O
O
FI
N G
D
ET
AI
LS
24023.00
NVJ
TAH
02/18/2025
TAH
2. EXISTING WALL
3. EXISTING METAL DECK
17. NON-TAPERED RIGID INSULATION
22. COUNTERFLASHING
23. SEALANT
24. BUTYL FLASHING TAPE
32. CONTINUOUS CLEAT
34. NEW GUTTER
40. EXIST. VENT STACK, EXTEND AS REQUIRED
41. P.T. WOOD BLOCKING TO BE FASTENED AT 12" O.C. MAX. AND
STAGGER - COUNTERSINK HEADS
42. 5/8" PLYWOOD - SCREW FASTEN @ 8" O.C. (MAX) TOP & BOTTOM &
STAGGERED - COUNTERSINK HEADS
45. EXISTING STRUCTURE
51. SELF-ADHERING UNDERLAYMENT
54. STRIP-IN FLASHING
61. EDGE METAL
80. METAL ROOF PANEL
A. CLOSED CELL RUBBER CLOSURE - CUT AS REQUIRED FOR
FUNCTION FIT WITHIN EACH PANEL AND SEAL WITH ONE-PART
URETHANE SEALANT
B. STAINLESS STEEL SCREWS OR DRIVE PINS WITH METAL BACKED
NEOPRENE WASHERS
C. 0.040" ALUMINUM CAP FLASHING - SLIDE OVER AN 0.050"
ALUMINUM "Z-CLOSURE" AND SECURE WITH "Z CLOSURE" IN FIELD
WITHOUT CUTTING
D. "BOX" TOP PANEL BEHIND "Z CLOSURE" IN FIELD WITHOUT CUTTING
E. 0.040" ALUMINUM RAKE FLASHING - SLIDE OVER AN 0.050"
ALUMINUM "Z-CLOSURE" AND SECURE WITH BUTTON PUNCH -
PROVIDE SPLICE JOINT CLEAT AT S;ICE JOINT.
F. 0.040" ALUMINUM SIDE WALL FLASHING - SLIDE OVER AN 0.050"
ALUMINUM "Z-CLOSURE" AND SECURE W/ BUTTON PUNCH.
G. 040.0" MILL FINISH ALUM. VALLEY FLASHING
TYP. DETAIL NOTES:
TYP. VALLEY EDGE TERMINATIONA08 .1 TYP. RIDGE / VALLEY TERMINATIONA08 .2
9 9
18" 18"
A0 5.
A05.5
SPLICE JOINT -
SEE DETAIL A05.5
0.050" MILL
FIN. RIDGE
COPING
M
IN
80 80
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS TO
FORM ONE CONTINOUS PIECE, EXCEPT AT
ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
NOTES:
1. FULLY EPOXY / WELD (AS PER METAL
TYPE) ALL LAPS & CORNERS INSERTS TO
FORM ONE CONTINOUS PIECE, EXCEPT AT
ALL SPLICE JOINTS
2. DIMENSIONS NOT GIVEN TO BE FIELD
VERIFIED
3. MEMBRANE AND OTHER COMPONETS
NOT SHOWN FOR CLARITY
TYP. SPLASH BLOCKA08 .4
3" = 1'-0"
FRONT ELEVATION
2"
4"
2'-0"
1'-0"
3" = 1'-0"
TYP. VENT STACK FLASHINGA08 .3
A05.5
G
GG
2/17/2025
| 24023 - Sheet - A00 - COVER SHEET, SITE VICINITY MAP, AND DRAWING INDEX |
| Sheets |
| A00 - COVER SHEET, SITE VICINITY MAP, AND DRAWING INDEX |
| A01 - OVERALL SITE PLAN, ROOF SCHEDULES, AND WIND PRESSURE DATA |
| A02 - ROOF PLAN - BUILDING 5 |
| A03 - ROOF PLAN - BUILDING 6 |
| A04 - FASTENER SCHEDULE, ABBREVIATIONS, AND GENERAL NOTES |
| A05 - ROOFING DETAILS |
| A06 - ROOFING DETAILS |
| A07 - ROOFING DETAILS |
| A08 - ROOFING DETAILS |
| 24023 - Sheet - A01 - OVERALL SITE PLAN, ROOF SCHEDULES, AND WIND PRESSURE DATA |
| Sheets |
| A00 - COVER SHEET, SITE VICINITY MAP, AND DRAWING INDEX |
| A01 - OVERALL SITE PLAN, ROOF SCHEDULES, AND WIND PRESSURE DATA |
| A02 - ROOF PLAN - BUILDING 5 |
| A03 - ROOF PLAN - BUILDING 6 |
| A04 - FASTENER SCHEDULE, ABBREVIATIONS, AND GENERAL NOTES |
| A05 - ROOFING DETAILS |
| A06 - ROOFING DETAILS |
| A07 - ROOFING DETAILS |
| A08 - ROOFING DETAILS |
| 24023 - Sheet - A02 - ROOF PLAN - BUILDING 5 |
| Sheets |
| A00 - COVER SHEET, SITE VICINITY MAP, AND DRAWING INDEX |
| A01 - OVERALL SITE PLAN, ROOF SCHEDULES, AND WIND PRESSURE DATA |
| A02 - ROOF PLAN - BUILDING 5 |
| A03 - ROOF PLAN - BUILDING 6 |
| A04 - FASTENER SCHEDULE, ABBREVIATIONS, AND GENERAL NOTES |
| A05 - ROOFING DETAILS |
| A06 - ROOFING DETAILS |
| A07 - ROOFING DETAILS |
| A08 - ROOFING DETAILS |
| 24023 - Sheet - A03 - ROOF PLAN - BUILDING 6 |
| Sheets |
| A00 - COVER SHEET, SITE VICINITY MAP, AND DRAWING INDEX |
| A01 - OVERALL SITE PLAN, ROOF SCHEDULES, AND WIND PRESSURE DATA |
| A02 - ROOF PLAN - BUILDING 5 |
| A03 - ROOF PLAN - BUILDING 6 |
| A04 - FASTENER SCHEDULE, ABBREVIATIONS, AND GENERAL NOTES |
| A05 - ROOFING DETAILS |
| A06 - ROOFING DETAILS |
| A07 - ROOFING DETAILS |
| A08 - ROOFING DETAILS |
| 24023 - Sheet - A04 - FASTENER SCHEDULE, ABBREVIATIONS, AND GENERAL NOTES |
| Sheets |
| A00 - COVER SHEET, SITE VICINITY MAP, AND DRAWING INDEX |
| A01 - OVERALL SITE PLAN, ROOF SCHEDULES, AND WIND PRESSURE DATA |
| A02 - ROOF PLAN - BUILDING 5 |
| A03 - ROOF PLAN - BUILDING 6 |
| A04 - FASTENER SCHEDULE, ABBREVIATIONS, AND GENERAL NOTES |
| A05 - ROOFING DETAILS |
| A06 - ROOFING DETAILS |
| A07 - ROOFING DETAILS |
| A08 - ROOFING DETAILS |
| 24023 - Sheet - A05 - ROOFING DETAILS |
| Sheets |
| A00 - COVER SHEET, SITE VICINITY MAP, AND DRAWING INDEX |
| A01 - OVERALL SITE PLAN, ROOF SCHEDULES, AND WIND PRESSURE DATA |
| A02 - ROOF PLAN - BUILDING 5 |
| A03 - ROOF PLAN - BUILDING 6 |
| A04 - FASTENER SCHEDULE, ABBREVIATIONS, AND GENERAL NOTES |
| A05 - ROOFING DETAILS |
| A06 - ROOFING DETAILS |
| A07 - ROOFING DETAILS |
| A08 - ROOFING DETAILS |
| 24023 - Sheet - A06 - ROOFING DETAILS |
| Sheets |
| A00 - COVER SHEET, SITE VICINITY MAP, AND DRAWING INDEX |
| A01 - OVERALL SITE PLAN, ROOF SCHEDULES, AND WIND PRESSURE DATA |
| A02 - ROOF PLAN - BUILDING 5 |
| A03 - ROOF PLAN - BUILDING 6 |
| A04 - FASTENER SCHEDULE, ABBREVIATIONS, AND GENERAL NOTES |
| A05 - ROOFING DETAILS |
| A06 - ROOFING DETAILS |
| A07 - ROOFING DETAILS |
| A08 - ROOFING DETAILS |
| 24023 - Sheet - A07 - ROOFING DETAILS |
| Sheets |
| A00 - COVER SHEET, SITE VICINITY MAP, AND DRAWING INDEX |
| A01 - OVERALL SITE PLAN, ROOF SCHEDULES, AND WIND PRESSURE DATA |
| A02 - ROOF PLAN - BUILDING 5 |
| A03 - ROOF PLAN - BUILDING 6 |
| A04 - FASTENER SCHEDULE, ABBREVIATIONS, AND GENERAL NOTES |
| A05 - ROOFING DETAILS |
| A06 - ROOFING DETAILS |
| A07 - ROOFING DETAILS |
| A08 - ROOFING DETAILS |
| 24023 - Sheet - A08 - ROOFING DETAILS |
| Sheets |
| A00 - COVER SHEET, SITE VICINITY MAP, AND DRAWING INDEX |
| A01 - OVERALL SITE PLAN, ROOF SCHEDULES, AND WIND PRESSURE DATA |
| A02 - ROOF PLAN - BUILDING 5 |
| A03 - ROOF PLAN - BUILDING 6 |
| A04 - FASTENER SCHEDULE, ABBREVIATIONS, AND GENERAL NOTES |
| A05 - ROOFING DETAILS |
| A06 - ROOFING DETAILS |
| A07 - ROOFING DETAILS |
| A08 - ROOFING DETAILS |
File details come from the government source that posted it. Updated .