Pages_from_Reference_project_design_-_abandonded_at_95%CD.pdf
PDF 2 MB Posted
- Solicitation number
- 94844
- Issued by
- Sacramento County, San Francisco City, California
About this file
This file is a reference project design document abandoned at 95% completion for the Sacramento County Rio Cosumnes Correctional Center (RCCC) central chilled water plant project. The document provides architectural and electrical construction plans as technical guidance for the forthcoming design and construction contract to replace twenty rooftop HVAC units at Buildings 555 and 570. The reference design incorporates a chilled water only hydronic plant with new rooftop air handlers using chilled water coils and unit-level gas heating, with the proposed plant to be located between buildings 550 and 570 using the same electrical pathway and existing utility coordination strategies shown in these plans. The design was prepared by AC Engineering Consultants, Inc. at 100% construction document level dated November 19, 2021, with electrical engineering by M. Neil's Engineering and project management by Stuart Lindsay. The 95% construction documents include partial roof plans with electrical remodeling, partial site and roof plans showing electrical infrastructure routing, one-line power diagrams for main switchboards, and AC unit connection details, with notation that rooftop air conditioning replacement is not included in this reference set but shown for reference only.
The reference design documentation provides critical utility coordination information, including guidance on locating and intercepting existing AC unit power circuits, extending electrical service to new AC units, routing new raceway along existing pathways while avoiding conflicts with existing utilities through potholing, and traffic-rated conduit protection across roadways. The design specifies connections to existing electrical panels (HECPA, EMSA, EMSB) and includes details for main switchboard configuration with 277/480 volt, 3-phase, 4-wire systems rated at 4000 amperes with 34kAIC capacity. The document explicitly states that this abandoned design serves as a technical reference showcasing the county's intent to incorporate the same plant location, electrical pathways, and utility coordination methodology in the forthcoming contract award, with proposing consultants directed to reference attachment G content for additional project parameters. No pricing, budget, or financial information is contained within this reference design document.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment H - Reference Project Design - abandoned at 95%CD (page 1 of 4):
Background:
This project design incorporated a chilled water only Hydronic plant with new rooftop air handlers using chilled water coils and unit level gas heating.
The proposed design on the forthcoming contract award will locate the chilled/hot water plant at the same location as shown in this set, and utilize the same electrical pathway.
This set of plans showcases to the proposing consultant that the county wishes to replace these 20 rooftop HVAC units and locate a new HVAC plant between buildings 550 and 570.
Reference also attachment G content.
95% CONSTRUCTION
DOCUMENTS
SCALE : 1/16" = 1'-0"
PARTIAL ROOF PLAN - ELECTRICAL REMODEL
E1.2
CH
(E)
AC
C10
AC
C6
AC
C7
AC
C9
AC
C8
AC
S5
AC
S4
AC
S3
AC
S2
AC
S1
AC
C5
AC
C4
AC
C3
AC
C2
AC
C1
AC
S7
AC
S9
AC
S8
AC
S6
AC
S10
CWP
S2-3
CWP
S2-2
CWP
S2-1
CH
CWP
P2-1
CWP
P2-2
SF
S3
(E)
SF
S1
(E)
RV
S1
(E)
EF
S7
(E)
EF
S10
(E)
(N)
(N)
(N)
(N)
(N)
(N)
(N)
(N)
(N)
(N)
(N)
(N)
(N)(N)(N)
(N)
(N)(N)(N)(N)
(N)
(N)
(N)
(N)
(N)
(N)
(N)
EF
S6
(E)
EF
S2
(E)
EF
S13
(E)
EF
S11
(E)
EF
S9
(E)
EF
S5
(E)
EF
S4
(E)
EF
S2
(E)
EF
S8
(E)
EF
S3
(E)
SF
S4
AC
S11
(E)
SF
C1
(E)
(E)
SF
C1
(E)
RV
C1
(E)
SF
C3
(E)
EF
C7
(E)
EF
C6
(E)
EF
C13
(E)
SF
C2
(E)
EF
C8
(E)
EF
C9
(E)
EF
C10
(E)
EF
C11
(E)
EF
C5
(E)
EF
C4
(E)
SF
C4
(E)
AC
C11
EF
C2
(E)
(E)
SF
C1
(E)
EF
C3
(E)
NUMBERED NOTES
LOCATE AND INTERCEPT (E) AC UNIT POWER CIRCUIT AND EXTEND TO NEW AC UNIT. FAN AND
ECONOMIZER. SEE AC UNIT CONNECTION DETAIL "2/E3-1"
UP EXTERIOR OF WALL.
CONNECT TO NEAREST ROOF MOUNTED CONVENIENCE RECEPTACLE.
1 1 1
(N) PANEL "HECPA"
HECPA-1,3,5
HECPA-7,9,11
HECPA-2,4,6
HECPA-8,10,12
HECPA-14,16,18
ROOF MOUNTED AIR CONDITIONING
REPLACEMENT NOT IN CONTRACT. SHOWN
FOR REFERENCE ONLY
ROOF MOUNTED AIR CONDITIONING
REPLACEMENT NOT IN CONTRACT. SHOWN
FOR REFERENCE ONLY
GFCI
GFCI
1/2"C., TO NETWORK
EQUIPMENT ROOM
WP
WP
GFCI
WP
PROVIDE POWER FOR
SERVICE RECEPTACLES
Department of General Services Administrative Services
Sacramento, Ca. 95827 9660 Ecology Lane
P. 916.876.6192
Architectural Services Division
DATE
REVISIONS:
DESIGN BY:
DRAWN BY:
DESCRIPTIONNO.
FACILITY NO.
SHEET NO.
PROJECT TITLE:
SHEET TITLE:
LOG NO.
100% CD
CONSTRUCTION DOCUMENTS
11.19.2021
12500 BRUCEVILLE ROAD
RIO COSUMNES
CORRECTIONAL CENTER
00080
CENTRAL CHILLED
WATER PLANT
SKL
BJ
210513.00
PM - DESIGN TEAM
PROJECT NO.
AC - IS
C A
ENGINEERING CONSULTANTS, INC.
RANCHO CORDOVA, CALIFORNIA
P I T A L
Electrical Engineers Lighting Designers
100 Howe Ave., Suite 235N
Sacramento, CA 95825-8217
PROJECT #:
www.mneilsengineering.com
Tel: (916) 923-4400
PROJECT MGR: STUART LINDSAY
11/19/2021
21146.21
E1.2
Attachment H - Reference Project Design - abandoned at 95%CD (page 2 of 4):
Background:
This project design incorporated a chilled water only Hydronic plant with new rooftop air handlers using chilled water coils and unit level gas heating.
The proposed design on the forthcoming contract award will locate the chilled/hot water plant at the same location as shown in this set, and utilize the same electrical pathway.
This set of plans showcases to the proposing consultant that the county wishes to replace these 20 rooftop HVAC units and locate a new HVAC plant between buildings 550 and 570.
Reference also attachment G content.
SCALE : 1" = 20'-0"
PARTIAL SITE AND ROOF PLAN - ELECTRICAL REMODEL
E1.0
CH
(N)
(N) PANEL "HECPA"
(E) MAIN SWITCHBOARD "EMSA"
(E) MAIN SWITCHBOARD "EMSB"
PB24
PB24
SEE ONE-LINE POWER DIAGRAM
SEE ONE-LINE POWER DIAGRAM
NEW CHILLER
PB24
MAIN ELECTRICAL
SWITCHGEAR
(KBF) (JFK)
STUART
BAIRD
FACILITY
(SBF)
CHRISTOPHER
BOONE
FACILITY
(CBF)
PB24
SEE ONE-LINE
POWER DIAGRAM
NUMBERED NOTES
1 CONTRACTOR SHALL LOCATE EXISTING UTILITIES ALONG PATH OF NEW RACEWAY TO NEW
PANELS. POTHOLE RACEWAY ROUTING. EXISTING ELECTRICAL CIRCUITS ARE ROUTED ACROSS
THE ROADWAY IN VICINITY OF THE MAIN ELECTRICAL SWITCHGEAR
TRAFFIC RATED
TRAFFIC
RATED
TRAFFIC RATED
TRAFFIC RATED
Department of General Services Administrative Services
Sacramento, Ca. 95827 9660 Ecology Lane
P. 916.876.6192
Architectural Services Division
DATE
REVISIONS:
DESIGN BY:
DRAWN BY:
DESCRIPTIONNO.
FACILITY NO.
SHEET NO.
PROJECT TITLE:
SHEET TITLE:
LOG NO.
100% CD
CONSTRUCTION DOCUMENTS
11.19.2021
12500 BRUCEVILLE ROAD
RIO COSUMNES
CORRECTIONAL CENTER
00080
CENTRAL CHILLED
WATER PLANT
SKL
BJ
210513.00
PM - DESIGN TEAM
PROJECT NO.
AC - IS
C A
ENGINEERING CONSULTANTS, INC.
RANCHO CORDOVA, CALIFORNIA
P I T A L
Electrical Engineers Lighting Designers
100 Howe Ave., Suite 235N
Sacramento, CA 95825-8217
PROJECT #:
www.mneilsengineering.com
Tel: (916) 923-4400
PROJECT MGR: STUART LINDSAY
11/19/2021
21146.21
E1.0
Attachment H - Reference Project Design - abandoned at 95%CD (page 3 of 4):
Background:
This project design incorporated a chilled water only Hydronic plant with new rooftop air handlers using chilled water coils and unit level gas heating.
The proposed design on the forthcoming contract award will locate the chilled/hot water plant at the same location as shown in this set, and utilize the same electrical pathway.
This set of plans showcases to the proposing consultant that the county wishes to replace these 20 rooftop HVAC units and locate a new HVAC plant between buildings 550 and 570.
Reference also attachment G content.
NO SCALE
PARTIAL ONE LINE POWER DIAGRAM - "MSA", "MSB", "EMSA", "EMSB"
E3.1
GROUND
NEUTRAL
(E) GND.
U.G. TERMINATION
SERVICE LUGS
U.G. SECONDARY SERVICE.
SEE "MSB" SCHEDULE
SMUD PAD MOUNTED
TRANSFORMER
(E) UNDERGROUND
PRIMARY SERVICE
(E) NEUTRAL
DISCONNECT
LINK
277/480 VOLT, 3 PHASE, 4 WIRE, 4000A BUSSING, 34kAIC
MAIN CIRCUIT BREAKER
PNL
"HA"
PNL
"PA"
DIST
PNL
"DPHS"
(E) MAIN SWITCHBOARD "MSA"
(E) SMUD PAD FOR (F)
TRANSFORMER
(E) 400/3
(E) SMUD #337446
(E) SMUD #670615
(E) VOLT METER
SP
SP
(E) AMP METER
GF MR
(E) 20/2
(E) SWBD
HEATER AND
THERMOSTAT
T
(E) 225/3 (E) 225/3
(E)
SPACE/3
(E)
SPACE/3
(E) 800/3 (E) 800/3
(E) 300KW,
277/480V
3P, 4W
GENERATOR
(E) MAIN SWITCHBOARD "MSB"
N
G
(E) GND.
TO (E) DIST
PANEL "HDP"
(E) 1200/3 (E) 800/3
(E) 400KW,
277/480V
3P, 4W
GENERATOR
(E) PFB/3
(E) 20/3
(E) CONTROL
POWER TO
GENERATOR
(E) PFB/3
(E) 20/3
(E) ATS
SPACE
HEATER
(E) ATS
(E) ATS
(E) 20/2
(E) SWBD
HEATER AND
THERMOSTAT
T
PROVISION FOR FUTURE
EXTENSION
(E) EMERGENCY MAIN SWITCHBOARD "EMSA"
277/480 VOLT, 3 PHASE, 4 WIRE, 4000A BUSSING, 34kAIC
(E) 20/2
(E) SWBD
HEATER AND
THERMOSTAT
T
PNL
"MP"
(E) 70/3
PNL
"AA"
(E) 100/3
PNL
"HEA"
(E) 400/3
PNL
"A"
(E) 225/3
PNL
"HEC"
(E) 400/3
(N)
PANEL
"HECPA"
(N) 400/3
CH
(N) 200/3
(E) EMERGENCY SWITCHBOARD "EMSB"
277/480 VOLT, 3 PHASE, 4 WIRE, 800A BUSSING, 34kAIC
(E) GND.
G
TO (E) DIST
PANEL "HDP"
(E) 800/3
277/480 VOLT, 3 PHASE, 4 WIRE, 800A BUSSING, 34kAIC
(E) PFB/3 (E) PFB/3
(E) 20/3
(E) SWBD
HEATER AND
THERMOSTAT
T
(E) (4) 4" C.O.
STUB AND CAP
(E) (4) 4" C.O.
STUB AND CAP
(E) (1) 2"
C.O. TO
TTBC
(E) (E) (E) (E) (E) (E) (E) (E)
400AF
NO SCALE
AC UNIT CONNECTION DETAIL
E3.1
(E) AU/C UNIT CURB.
(E) ROOF
NEW AC UNIT
PROVIDE NEW 30AF FUSED DISCONNECT
SWITCH FOR NEW POWER EXHAUST
ECONOMIZER. COORDINATE FUSE SIZE
WITH AIR CONDITIONER UNIT SCHEDULE
ON SHEET M0.2
PROVIDE NEW 30AF FUSED DISCONNECT
SWITCH FOR AC UNIT FAN. COORDINATE
FUSE SIZE WITH AIR CONDITIONING UNIT
SCHEDULE ON SHEET M0.2
DISCONNECT AND REMOVE (E)
DISCONNECT SWITCH. PROVIDE NEW WP
J-BOX TO INTERCEPT (E) CIRCUIT
(E) AC UNIT FEEDER
J
FLEXIBLE CONDUIT
N GND
PROVIDE ISOLATED
NEUTRAL. DO NOT
BOND NEUTRAL BAR
TO GROUND BAR AT
THIS LOCATION
PROVIDE GROUND
ROD PER DETAIL
"6/E4.1"
ADDITIONAL BUILDING DISCONNECTING
MEANS LOCATION. PROVIDE GROUNDING
PER CEC-250.32 PROVIDE IDENTIFICATION
PER CEC-225.37 AT NEW DISCONNECT
LOCATION AND ALL APPLICABLE EXISTING
DISCONNECT LOCATIONS. COORDINATE
ALL REQUIREMENTS WITH OWNER.
Department of General Services Administrative Services
Sacramento, Ca. 95827 9660 Ecology Lane
P. 916.876.6192
Architectural Services Division
DATE
REVISIONS:
DESIGN BY:
DRAWN BY:
DESCRIPTIONNO.
FACILITY NO.
SHEET NO.
PROJECT TITLE:
SHEET TITLE:
LOG NO.
100% CD
CONSTRUCTION DOCUMENTS
11.19.2021
12500 BRUCEVILLE ROAD
RIO COSUMNES
CORRECTIONAL CENTER
00080
CENTRAL CHILLED
WATER PLANT
SKL
BJ
210513.00
PM - DESIGN TEAM
PROJECT NO.
AC - IS
C A
ENGINEERING CONSULTANTS, INC.
RANCHO CORDOVA, CALIFORNIA
P I T A L
Electrical Engineers Lighting Designers
100 Howe Ave., Suite 235N
Sacramento, CA 95825-8217
PROJECT #:
www.mneilsengineering.com
Tel: (916) 923-4400
PROJECT MGR: STUART LINDSAY
11/19/2021
21146.21
E3.1
Attachment H - Reference Project Design - abandoned at 95%CD (page 4 of 4):
Background:
This project design incorporated a chilled water only Hydronic plant with new rooftop air handlers using chilled water coils and unit level gas heating.
The proposed design on the forthcoming contract award will locate the chilled/hot water plant at the same location as shown in this set, and utilize the same electrical pathway.
This set of plans showcases to the proposing consultant that the county wishes to replace these 20 rooftop HVAC units and locate a new HVAC plant between buildings 550 and 570.
Reference also attachment G content.