P530 AIMF_PLANS_DRAFT_20250728_Part5.pdf

PDF 16 MB Posted

Attached to
P530 Aircraft Intermediate Maintenance Facility, Kadena Air Base
Solicitation number
W912HV26Z0007
Issued by

About this file

This file contains a comprehensive set of electrical design and specification documents for the P530 Aircraft Intermediate Maintenance Facility project at Kadena Air Base in Okinawa, Japan. The electrical plans cover multiple aspects of the facility's electrical infrastructure, including lighting plans, power distribution, panelboard schedules, one-line electrical diagrams, equipment requirements, and detailed fixture specifications. Key technical details include a 600-amp main electrical service with a 480/277V, 3-phase, 4-wire system, a 300 kVA pad-mounted transformer, multiple electrical panels (MDP, 1LP1, 2LP1, etc.), and extensive lighting and power configurations across two building floors.

The electrical design incorporates LED lighting fixtures with specific requirements, emergency lighting systems, extensive receptacle and equipment circuits, and comprehensive grounding and lightning protection. The facility includes specialized electrical provisions for various rooms such as maintenance bays, communication rooms, battery shops, and hazardous areas, with specific attention to electrical safety and code compliance. The documents are part of a 65% design submittal dated July 2025, prepared for the US Army Corps of Engineers Japan District, indicating an ongoing design process for a new military maintenance facility.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ACC-1/ACC-2 AIR COOLED CENTRIFUGAL CHILLER INTERFACE (INT-ACC1/INT-ACC2) ALARMING PRIMARY POINT

INFORMATION

NETWORK

DATA

EXCHANGE

OVERRIDES TREND OBJECT

LOCATION (L OR R),

TYPE AND INSTANCE

NUMBER

(PROVIDE DDC ID

FOR REMOTE IN

NOTES)

ALARM INFORMATION

CONFIGURATION

INFORMATION

FUNCTION NAME (DWG

TAG) DESCRIPTION

DDC

HARDWAR

E ID

SETTING

(WITH UNITS)

RANGE

(WITH UNITS)

IO

TYPE

HOA

REQ'D

CONFIG.

TYPE

M&C

VIEW

AND

OVRD

LDP VIEW

AND

OVRD

TREND

REQ'D ALARM CONDITION ALARM

PRIORITY

M&C

ROUTING

OBJECT TYPE AND

INSTANCE NUMBER

(AND PROPERTY ID)

DATA

FROM

DATA

TO

OBJECT TYPE &

INSTANCE

NUMBER OR

COMMANDABLE

ALARM TYPE

(PROVIDE DDC ID

FOR REMOTE IN

NOTES)

NOTIFICATION

CLASS OBJECT

INSTANCE

NUMBER

EVENT

ENROLLMENT

OBJECT

INSTANCE

NUMBER

PROOFS &

SAFTIES

CHLR-S CHILLER STATUS

ON/OFF BI V V CHILLER STATUS NOT EQUAL

TO COMMAND

CRIT [___]

CHLR-SS CHILLER START-

STOP (ON/OFF)

COMMAND

ON/OFF BO ~ V V

CHLR-MOD CHILLER MODE -

OPERATIONAL

CODE <___>

ENABLE/DISABL

E

NET-IN V V ~

CHLR-ALM CHILLER

ALARM/FAULT <___> ALM/NORMAL BI H ALM INFO [___] <___> <___> <___> [___] [___] [___]

CHLR-LOW-

T

CHILLER LOW TEMP

CUTOUT <___> 4 DEG C ALM/NORMAL BI H ALM CRIT [___] <___> <___> <___> [___] [___] [___]

CHLR-LO SYSTEM 1 LOCKOUT <___> ON/OFF NET-IN V V ~ <___> <___> <___> <___> <___>

COMPRESSOR

COMP1-S COMPRESSOR 1

RUN STATUS <___> ON/OFF BI V V Y

Y

COMPRESSOR PUMP PROOF

FAILED

INFO [___] <___> <___> <___> ~ [___] [___] [___]

COMP2-S COMPRESSOR 2

RUN STATUS <___> ON/OFF BI V V Y COMPRESSOR PUMP PROOF

FAILED

INFO [___] <___> <___> <___> ~ [___] [___] [___]

EVAPORATOR

EVAP-PMP-S EVAPORATOR PUMP

STATUS (FLOW

PROOF) (SEE NOTE

6)

ON/OFF BI V V EVAP PUMP PROOF FAILED INFO [___]

CONDENSOR COND-FANS-

S

CONDENSER FAN

STATUS <___> ON/OFF NET-IN V V <___> <___> <___>

SYSTEM

LVG-WATER-

T

CHILLED WATER

TEMP LEAVING

CHILLER

DEG C AI V V ~ [___]

RET-WATER-

T

RETURN CHILLED

WATER

TEMPERATURE

DEG C D V V Y

CONTMODE CONTROL MODE -

LOCAL OR REMOTE <___> LOCAL/REMOT

E

NET-IN V V ~ <___> <___> <___> <___> <___>

CHLR-RUN-H CHILLER RUNTIME

HOURS <___> AI V V

OTHER POINTS

CHLR-CL CURRENT LIMIT <___> <___ AMP> AMP

CHLR-SUC-T SUCTION

TEMPERATURE <___> DEG C AI V V Y <___> <___> <___> <___> <___>

CHLR-DIS-T DISCHARGE

TEMPERATURE <___> DEG C AI V V Y <___> <___> <___> <___> <___>

CHLR-OIL-T OIL TEMPERATURE <___> DEG C AI V V Y <___> <___> <___> <___> <___>

CHLR-OIL-P OIL PRESSURE <___> Pa AI V Y <___> INFO [___] <___> <___> <___> <___> [___] [___] [___]

CHLR-SUC-P SUCTION

PRESSURE <___> Pa AI V Y <___> INFO [___] <___> <___> <___> <___> [___] [___] [___]

CHLR-DIS-P DISCHARGE

PRESSURE <___> Pa AI V Y <___> INFO [___] <___> <___> <___> <___> [___] [___] [___]

CHLR-FL-

AMP

FULL LOAD AMP <___> 0 - <___> kVA ~ Y <___> <___> <___> <___>

CHLR-

SUCSH-T

SUCTION

SUPERHEAT

TEMPERATURE <___>

DEG C AI V V Y

CHLR-

DISSH-T

DISCHARGE

SUPERHEAT

TEMPERATURE

DEG C AI V V Y

OA-T OUTSIDE AIR

AMBIENT

TEMPERATURE <___>

<___DEG C> DEG C AI V V

Notes:

1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THE POINTS SCHEDULE INSTRUCTIONS DRAWING.

2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.

3) UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR CHILLER SERVING THIS SYSTEM.

4) DDC HW ID FOR DEVICE CONTAINING TREND OBJECT FOR REMOTE TRENDING FOR THIS SYSTEM: <_____>

5) DDC HW ID FOR DEVICE CONTAINING EVENT ENROLLMENT OBJECT FOR REMOTE ALARMING FOR THIS SYSTEM: <_____>

6) EACH CHILLER AS 2 PRIMARY PUMPS (ONE IS STAND BY) POWERED FROM THE CHILLER. (CHP-1A/1B AND CHP-2A/2B)

7) SEE SEQUENCE OF OPERATION REGARDING CHILLED WATER SUPPLY TEMPERATURE RESET.

3 F

OU

NT

AI

NS

P

AR

KW

AY

SU

IT

E

FA

IR

VI

EW

H

EI

GH

TS

, I

L

8-

8.6

.70

W

OO

LP

ER

T, In c.

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

FI

LE

N

AM

E:

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

U S

A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

C H

EC

KE

D B

Y:

US Army Corps of Engineers ®

IS

O

A

A

D R

AW

IN

G C

O D

E:

B

C

D

E

F

G

1 2 3 4 5 6

SHEET ID

Japan District

7 8 9 10

H

J

K

L

M

N

P

Q

R

11 12 13 14 15 16 17 18 19 20 21

W

2H V1

9D

A.

D

ET

ME

R

N.

V

AL

DE

Z

R.

K

NO

LL

E

M.

B

EH

RM

AN

N

M-702

C H

IL

LE

R C

O N

TR

O

L

PO

IN

TS

L

IS

T

C O

M

FL

EA

C

T O

KI

N

AW

A

JA

K

AD

EN

A

AF

B, O

KI

N

AW

A, J

AP

AN

P5

A

IR

C

R

AF

T

IN

TE

R

M

ED

IA

TE

M

AI

N

TE

N

AN

C E

FA

C

IL

IT

Y

W

2H V1

9D

JA

PA

N D

IS

TR

IC

T

U ni t 3

AP

O A

P

4-

JU

LY

W

2H V1

9D

_ M

-7

D

ES

IG

N

S U

BM

IT

TA

L

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

DRAFT

CHILLED WATER PLANT (PRIMARY/SECONDARY SYSTEM, IN CONJUNCTION WITH AIR AND/OR WATER COOLED CHILLER)

ALARMING PRIMARY POINT

INFORMATION

NETWORK DATA

EXCHANGE OVERRIDES TREND OBJECT

LOCATION (L OR R),

TYPE AND

INSTANCE NUMBER

(PROVIDE DDC ID

FOR REMOTE IN

NOTES)

ALARM INFORMATION

CONFIGURATION

INFORMATION

FUNCTION NAME DESCRIPTION DDC

HARDWARE ID

SETTING

(WITH UNITS)

RANGE

(WITH UNITS)

IO

TYPE

HOA

REQ'D

CONFIG.

TYPE

M&C

VIEW

AND

OVRD

LDP VIEW

AND

OVRD

TREND

REQ'D ALARM CONDITION ALARM

PRIORITY

M&C

ROUTING

OBJECT TYPE AND

INSTANCE

NUMBER

(AND PROPERTY

ID)

DATA

FROM

DATA

TO

OBJECT TYPE &

INSTANCE NUMBER

OR

COMMANDABLE

ALARM TYPE

(PROVIDE

DDC ID FOR

REMOTE IN

NOTES)

NOTIFICATION

CLASS OBJECT

INSTANCE

NUMBER

EVENT

ENROLLMENT

OBJECT

INSTANCE

NUMBER

PROOFS &

SAFTIES

CHLR-S CHILLER STATUS <___> ON/OFF BI V V CHILLER STATUS NOT

EQUAL TO COMMAND

[info] [crit] [___] <___> <___> <___> [~] [___] [___] [___]

CHLR-SS CHILLER START-

STOP (ON/OFF)

COMMAND

ON/OFF BO [~] V V

CHLR-MOD CHILLER MODE -

OPERATIONAL

CODE

ENABLE/DISABLE NET-IN V V [ ~ ]

CHLR-ALM CHILLER

ALARM/FAULT <___> ALM/NORMAL BI H ALM [info] [crit] [___] <___> <___> <___> [___] [___] [___]

CHLR-LOW-T CHILLER LOW

TEMP CUTOUT <___> [4 DEG C] ALM/NORMAL BI H ALM [info] [crit] [___] <___> <___> <___> [___] [___] [___]

CHLR-LO SYSTEM 1

LOCKOUT <___> ON/OFF NET-IN V V [ ~ ] <___> <___> <___> <___> <___>

COMPRESSOR

COMP1-S COMPRESSOR 1

RUN STATUS <___> ON/OFF BI V V X COMPRESSOR PUMP

PROOF FAILED

[info] [crit] [___] <___> <___> <___> [~] [___] [___] [___]

COMP2-S COMPRESSOR 2

RUN STATUS <___> ON/OFF BI V V X COMPRESSOR PUMP

PROOF FAILED

[info] [crit] [___] <___> <___> <___> [~] [___] [___] [___]

EVAPORATOR

EVAP-PMP-S EVAPORATOR

PUMP STATUS

(FLOW PROOF)

ON/OFF BI V V EVAP PUMP PROOF

FAILED

[info] [crit] [___]

CONDENSOR COND-FANS-S CONDENSER FAN

STATUS

<___> ON/OFF NET-IN V V <___> <___> <___>

SYSTEM

LVG-WATER-T CHILLED WATER

TEMP LEAVING

CHILLER

[ DEG C] AI V V [ ~ ] [___]

RET-WATER-T RETURN CHILLED

WATER

TEMPERATURE

[ DEG C] AI V V X

CONTMODE CONTROL MODE -

LOCAL OR

REMOTE

LOCAL/REMOTE NET-IN V V [ ~ ]

CWS-T-SP CHILLED WATER

SUPPLY TEMP

SETPOINT

[___DEG C] [ DEG C] AO VO V X

CHLR-RUN-H CHILLER RUNTIME

HOURS <___> AI V V

OTHER POINTS

CHLR-CL CURRENT LIMIT <___> [___ AMP] [ AMP]

CHLR-SUC-T SUCTION

TEMPERATURE <___> [ DEG C] AI V V X <___> <___> <___> <___> <___>

CHLR-DIS-T DISCHARGE

TEMPERATURE <___> [ DEG C] AI V V X <___> <___> <___> <___> <___>

CHLR-OIL-T OIL TEMPERATURE <___> [ DEG C] AI V V X <___> <___> <___> <___> <___>

CHLR-OIL-P OIL PRESSURE <___> [ PSI] AI V X <___> [info] [crit] [___] <___> <___> <___> <___> [___] [___] [___]

CHLR-SUC-P SUCTION

PRESSURE <___> [ PSI] AI V X <___> [info] [crit] [___] <___> <___> <___> <___> [___] [___] [___]

CHLR-DIS-P DISCHARGE

PRESSURE <___> [ PSI] AI V X <___> [info] [crit] [___] <___> <___> <___> <___> [___] [___] [___]

CHLR-FL-AMP FULL LOAD AMP <___> 0 - <___> kVA [~] X <___> <___> <___> <___>

CHLR-SUCSH-T SUCTION

SUPERHEAT

TEMPERATURE

[ DEG C] AI V V X

CHLR-DISSH-T DISCHARGE

SUPERHEAT

TEMPERATURE

[ DEG C] AI V V X

OA-T OUTSIDE AIR

AMBIENT

TEMPERATURE

[___DEG C] [ DEG C] AI V V

Notes:

1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THE POINTS SCHEDULE INSTRUCTIONS DRAWING.

2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.

3) UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR CHILLER SERVING THIS SYSTEM.

4) DDC HW ID FOR DEVICE CONTAINING TREND OBJECT FOR REMOTE TRENDING FOR THIS SYSTEM: <_____>

5) DDC HW ID FOR DEVICE CONTAINING EVENT ENROLLMENT OBJECT FOR REMOTE ALARMING FOR THIS SYSTEM: <_____>

3 F

OU

NT

AI

NS

P

AR

KW

AY

SU

IT

E

FA

IR

VI

EW

H

EI

GH

TS

, I

L

8-

8.6

.70

W

OO

LP

ER

T, In c.

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

FI

LE

N

AM

E:

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

U S

A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

C H

EC

KE

D B

Y:

US Army Corps of Engineers ®

IS

O

A

A

D R

AW

IN

G C

O D

E:

B

C

D

E

F

G

1 2 3 4 5 6

SHEET ID

Japan District

7 8 9 10

H

J

K

L

M

N

P

Q

R

11 12 13 14 15 16 17 18 19 20 21

W

2H V1

9D

A.

D

ET

ME

R

N.

V

AL

DE

Z

R.

K

NO

LL

E

M.

B

EH

RM

AN

N

M-703

C H

IL

LE

D W

AT

ER

P

LA

N T

C O

N

TR

O L

PO

IN

TS

L

IS

T

C O

M

FL

EA

C

T O

KI

N

AW

A

JA

K

AD

EN

A

AF

B, O

KI

N

AW

A, J

AP

AN

P5

A

IR

C

R

AF

T

IN

TE

R

M

ED

IA

TE

M

AI

N

TE

N

AN

C E

FA

C

IL

IT

Y

W

2H V1

9D

JA

PA

N D

IS

TR

IC

T

U ni t 3

AP

O A

P

4-

JU

LY

W

2H V1

9D

_ M

-7

D

ES

IG

N

S U

BM

IT

TA

L

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

OUTSIDE AIR

HS-RA

TS-RAT

CTRL

ELEC COIL

SD-VA

CHW COIL

CHV-CLG

OVFL-SW

TS-CLG

8 9 10

6 TS-VAT

VENTILATION AIR

FAN TEXT

VFD

FAN-SA

VFD-SAF

AFM-OA

M

DPR-OA

(FROM INTAKE HOOD)

EH-SA

PDPD

PRE-FILTER FINAL FILTER

DP-F1-RA DP-F2-RA

3 F

OU

NT

AI

NS

P

AR

KW

AY

SU

IT

E

FA

IR

VI

EW

H

EI

GH

TS

, I

L

8-

8.6

.70

W

OO

LP

ER

T, In c.

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

FI

LE

N

AM

E:

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

U S

A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

C H

EC

KE

D B

Y:

US Army Corps of Engineers ®

IS

O

A

A

D R

AW

IN

G C

O D

E:

B

C

D

E

F

G

1 2 3 4 5 6

SHEET ID

Japan District

7 8 9 10

H

J

K

L

M

N

P

Q

R

11 12 13 14 15 16 17 18 19 20 21

W

2H V1

9D

A.

D

ET

ME

R

N.

V

AL

DE

Z

R.

K

NO

LL

E

M.

B

EH

RM

AN

N

M-704

D O

AS

-1

A

IR

FL

O

W A

N D

C O

N

TR

O L

D

IA

G R

AM

S

C O

M

FL

EA

C

T O

KI

N

AW

A

JA

K

AD

EN

A

AF

B, O

KI

N

AW

A, J

AP

AN

P5

A

IR

C

R

AF

T

IN

TE

R

M

ED

IA

TE

M

AI

N

TE

N

AN

C E

FA

C

IL

IT

Y

W

2H V1

9D

JA

PA

N D

IS

TR

IC

T

U ni t 3

AP

O A

P

4-

JU

LY

W

2H V1

9D

_ M

-7

D

ES

IG

N

S U

BM

IT

TA

L

GENERAL SHEET NOTES:

SHEET KEYNOTES:

NTSN1 DOAS-1

SEQUENCE OF OPERATION FOR DOAS-1

1.

2.

3.

1.

1.

SUPPLY AIR FAN

GENERAL: THE VARIABLE FREQUENCY DRIVE (VFD) SHALL MODULATE FAN SPEED AS REQUIRED TO SATISFY THE

SPACE VENTILATION REQUIREMENTS MEASURED AT THE AIRFLOW MONITORING STATION.

OCCUPIED MODE: THE SUPPLY FAN SHALL RUN CONTINUOUSLY.

UNOCCUPIED MODE: THE SUPPLY FAN SHALL RUN INTERMITTENTLY AT MINIMUM SPEED. THE FAN SHALL BE ACTIVATED WHEN ANY OF THE AHU'S (AHU-1, AHU-2, OR AHU-3) RETURN AIR HUMIDITY IS GREATER THAN 60% RH.

SUPPLY FAN MAY BE DISABLED WHEN ALL UNITS RETURN AIR HUMIDITY IS LESS THAN 55% RH.

CHILLED WATER COIL

THE CHILLED WATER COIL VALVE SHALL MODULATE TO MAINTAIN THE COOLING AIR DISCHARGE SET-POINT.

ELECTRIC REHEAT COIL

THE SCR CONTROLS SHALL MODULATE TO MAINTAIN THE DISCHARGE AIR SET-POINT.

1.

2.

1.

1.

1.

FILTER MONITORING

THE FILTER BANK PRESSURE DIFFERENTIAL SENSOR SHALL CONTINUOUSLY MONITOR FILTER PERFORMANCE WHILE

THE SUPPLY FAN IS RUNNING.

FILTER: WHEN THE FILTER RESISTANCE REACHES SET-POINT, A MAINTENANCE WARNING SHALL BE SENT TO THE DDC.

WHEN THE FILTER RESISTANCE REACHES THE HIGH LIMIT, AN ALARM SHALL SENT TO THE DDC.

DUCT MOUNTED SMOKE DETECTORS

THE DUCT MOUNTED SMOKE DETECTORS SHALL MONITOR THE AIR STREAM FOR THE PRESENCE OF PRODUCTS OF COMBUSTION. WHEN PRODUCTS OF COMBUSTION ARE DETECTED, A SIGNAL SHALL BE SENT TO THE FIRE ALARM SYSTEM AND A HARD WIRE INTERLOCK SHALL SHUT DOWN THE AFFECTED AIR HANDLING UNIT. THE DDC SHALL SHUT DOWN ALL OTHER AIR HANDLING UNIT FANS, FAN COIL UNITS, EXHAUST FANS AND MAKE UP AIR FANS WITHIN THE BUILDING. ALL COMBINATION FIRE/SMOKE DAMPERS, RETURN AIR DAMPERS, EXHAUST DAMPERS AND OUTSIDE AIR

DAMPERS SHALL CLOSE.

DISCHARGE HIGH AND LOW LIMIT CONTROLS

IF THE DISCHARGE AIR TEMPERATURE FALLS BELOW THE LOW LIMIT SET POINT OR RISES ABOVE THE HIGH LIMIT SET-

POINT, AN ALARM SHALL BE SENT TO THE DDC.

GENERAL ALARMS OR FAILURES

REFER TO THE POINTS LIST FOR OTHER ALARMS TO BE SENT TO THE DDC.

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

1.

2.

REFER TO MANUAFACTURER'S INSTALLATION INSTRUCTIONS

FOR COMPONENTS THAT MAY BE REQUIRED BUT ARE NOT

SHOWN ON THIS DIAGRAM.

SEE ASSOCIATED POINTS SCHEDULES ON ADJACENT M-700

SHEETS.

1 MOTORIZED, 2 POSITION, OPPOSED BLADE, LOW

LEAKAGE CONTROL DAMPER.

2 DUCT MOUNTED, PROBE TYPE, TEMPERATURE

SENSOR

3 DUCT MOUNTED, PROBE TYPE, HUMIDITY SENSOR

4 AIR FLOW MONITORING STATION CAPABLE OF

MEASURING WITH AN ACCURACY OF ±5% OF THE

DESIGN OUTDOOR AIR FLOW RATE/EXHAUST

AIRFLOW RATE OR BETTER.

5 FILTER DIFFERENTIAL PRESSUE SENSOR

6 PLEATED MEDIA FILTERS

7 CONDENSATE PAN OVERFLOW SENSORS

8 MOTORIZED, 2-WAY MODULATING CONTROL VALVE

9 AVERAGING TYPE CAPILLARY TUBE, TEMPERATURE

SENSOR

10 ELECTRIC HEATING COIL WITH SCR CONTROLS

11 VARIABLE FREQUENCY DRIVE

12 DUCT MOUNTED SMOKE DETECTOR, SEE FIRE

ALARM PLANS

13 DUCT MOUNTED, PROBE TYPE, TEMPERATURE

SENSOR

SUPPLY AIRPRIMARY AIR

AFM-SA

TUC-VAV

FROM AHU

M

DPR-VAV

TSTS-ZONE

TO ROOMS

RETURN AIR

HS-RA

TS-RA

PD

MAIN FILTER

DP-F1-RA

SD-SA

CHW COIL

CHV-CLG

OVFL-SW

SUPPLY FAN

VFD

FAN-SA

VFD-SAF

TS-CLG

11 12

9 TS-SAT

SP-SA

17 18

SUPPLY AIR

HT PIPE COIL HT PIPE COIL

HTG-V-C

RETURN AIR

HS-RA

TS-RA

PD

MAIN FILTER

DP-F1-RA

SD-SA

CHW COIL

CHV-CLG

OVFL-SW

SUPPLY FAN

VFD

FAN-SA

VFD-SAF

TS-CLG

11 12

9 TS-SAT

SP-SA

17 18

SUPPLY AIR

3 F

OU

NT

AI

NS

P

AR

KW

AY

SU

IT

E

FA

IR

VI

EW

H

EI

GH

TS

, I

L

8-

8.6

.70

W

OO

LP

ER

T, In c.

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

FI

LE

N

AM

E:

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

U S

A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

C H

EC

KE

D B

Y:

US Army Corps of Engineers ®

IS

O

A

A

D R

AW

IN

G C

O D

E:

B

C

D

E

F

G

1 2 3 4 5 6

SHEET ID

Japan District

7 8 9 10

H

J

K

L

M

N

P

Q

R

11 12 13 14 15 16 17 18 19 20 21

W

2H V1

9D

A.

D

ET

ME

R

N.

V

AL

DE

Z

R.

K

NO

LL

E

M.

B

EH

RM

AN

N

M-705

AH

U

-1 , 2

, 3 A

IR

FL

O W

A N

D C

O N

TR

O

L D

IA

G

R

AM

S

C O

M

FL

EA

C

T O

KI

N

AW

A

JA

K

AD

EN

A

AF

B, O

KI

N

AW

A, J

AP

AN

P5

A

IR

C

R

AF

T

IN

TE

R

M

ED

IA

TE

M

AI

N

TE

N

AN

C E

FA

C

IL

IT

Y

W

2H V1

9D

JA

PA

N D

IS

TR

IC

T

U ni t 3

AP

O A

P

4-

JU

LY

W

2H V1

9D

_ M

-7

D

ES

IG

N

S U

BM

IT

TA

L

GENERAL SHEET NOTES:

SHEET KEYNOTES:

NTSD15 VAV TERMINAL UNITS

NTSN1 AHU-1

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

SEQUENCE OF OPERATION FOR AHU-1/AHU-2/AHU-3

1.

2.

3.

1.

1.

1.

2.

3.

4.

1.

2.

3.

4.

SUPPLY AIR FAN

GENERAL: THE VARIABLE FREQUENCY DRIVE (VFD) SHALL MODULATE FAN SPEED AS REQUIRED TO SATISFY THE AIR FLOW REQUIREMENTS OF THE MOST CRITICAL VAV TERMINAL UNIT (CRITICAL ZONE RESET METHOD).

OCCUPIED MODE: THE SUPPLY FAN SHALL RUN CONTINUOUSLY.

UNOCCUPIED MODE: THE SUPPLY FAN SHALL RUN INTERMITTENTLY. THE FAN SHALL BE ACTIVATED WHEN THE

ZONE TEMPERATURE SENSOR REACHES 2.5°C (ADJ) ABOVE OR BELOW SET-POINT.

CHILLED WATER COIL

THE CHILLED WATER COIL VALVE SHALL MODULATE TO MAINTAIN THE SUPPLY AIR SET-POINT.

REHEAT WRAP AROUND COIL (AHU-1 ONLY)

SYSTEM SHALL MODULATE WRAP AROUND COIL SECTION TO PROVIDE REHEAT / DEHUMIDIFICATION TO SUPPLY AIR.

CRITICAL ZONE STATIC PRESSURE RESET CONTROL

THE DDC SYSTEM SHALL CONTINUOUSLY MONITOR THE DAMPER POSITION OF ALL VAV TERMINAL UNITS. THE DISCHARGE DUCT STATIC PRESSURE SHALL BE SENSED DIRECTLY IN A NON TURBULENT POINT IN THE SUPPLY AIR DUCT AT APPROXIMATELY THE THE ONE THIRD POINT IN THE DUCT SYSTEM (STARTING AT THE FAN).

WHEN ANY DAMPER IS MORE THAN 95% (ADJ.) OPEN, THE SUPPLY FAN DISCHARGE DUCT STATIC PRESSURE SET POINT SHALL BE RESET UPWARD BY 5% (ADJ.) OF THE MAXIMUM SYSTEM STATIC PRESSURE SET POINT AT A FREQUENCY OF 10 MINUTES (ADJ.) UNTIL NO DAMPER IS MORE THAN 95% OPEN OR THE STATIC PRESSURE SET POINT HAS RESET UPWARD TO THE SYSTEM MAXIMUM SETTING OR THE VFD IS AT IT'S MAXIMUM SETTING.

WHEN ALL DAMPERS ARE LESS THAN 85% (ADJ.) OPEN, THE SUPPLY FAN DISCHARGE DUCT STATIC PRESSURE SET POINT SHALL BE RESET DOWNWARD BY 5% (ADJ.) OF THE MAXIMUM SYSTEM STATIC PRESSURE SET POINT AT A FREQUENCY OF 10 MINUTES (ADJ.) UNTIL ANY DAMPER IS MORE THAN 85% OPEN OR THE STATIC PRESSURE SET POINT HAS RESET DOWNWARD TO THE SYSTEM MINIMUM SETTING OR THE VFD IS AT IT'S MINIMUM SETTING.

THE CONTROL BANDS, SET POINT INCREMENT VALUES, SET POINT DECREMENT VALUES AND ADJUSTMENT FREQUENCIES SHALL BE ADJUSTED TO MAINTAIN MAXIMUM STATIC PRESSURE OPTIMIZATION WITH STABLE SYSTEM CONTROL AND MAXIMUM COMFORT CONTROL. VAV TERMINALS THAT SERVE ZONES WITH CONSTANT LOADS, SUCH AS DATA CLOSETS, ETC, SHALL BE OVERRIDDEN WHEN REQUIRED TO ENHANCE STATIC PRESSURE CONTROL.

CRITICAL ZONE SUPPLY AIR TEMPERATURE RESET CONTROL

THE DDC SYSTEM SHALL CONTINUOUSLY MONITOR THE DAMPER POSITION OF ALL VAV TERMINAL UNITS.

WHEN ALL ZONE DAMPER POSITIONS ARE BELOW 85% OPEN, THE SUPPLY AIR TEMP. SET-POINT SHALL BE RESET

UPWARD 0.5°C EVERY THREE MINUTES UNTIL AT LEAST ONE ZONE DAMPER IS 95% OPEN.

IF DURING RESET, ANY ZONE DAMPER IS 100% OPEN AND ITS ZONE TEMP IS NOT SATISFIED, THE SUPPLY AIR TEMP.

SET POINT SHALL BE RESET DOWNWARD 0.5°C EVERY THREE MINUTES UNTIL THE COOLING CRITICAL ZONE DAMPER

IS BELOW 95% OPEN.

THE DDC SHALL BE SET UP TO PROVIDE TREND LOGS OF DAMPER POSITIONS AND OTHER SET POINTS AS REQUIRED

TO FINE TUNE THE RESET PARAMETERS AFTER THE FIRST YEAR OF OPERATION.

1.

2.

1.

1.

1.

1.

2.

1.

FILTER MONITORING

THE FILTER BANK PRESSURE DIFFERENTIAL SENSOR SHALL CONTINUOUSLY MONITOR FILTER PERFORMANCE WHILE

THE SUPPLY FAN IS RUNNING.

FILTER: WHEN THE FILTER RESISTANCE REACHES SET-POINT, A MAINTENANCE WARNING SHALL BE SENT TO THE DDC.

WHEN THE FILTER RESISTANCE REACHES THE HIGH LIMIT, AN ALARM SHALL SENT TO THE DDC.

DUCT MOUNTED SMOKE DETECTORS

THE DUCT MOUNTED SMOKE DETECTORS SHALL MONITOR THE AIR STREAM FOR THE PRESENCE OF PRODUCTS OF COMBUSTION. WHEN PRODUCTS OF COMBUSTION ARE DETECTED, A SIGNAL SHALL BE SENT TO THE FIRE ALARM SYSTEM AND A HARD WIRE INTERLOCK SHALL SHUT DOWN THE AFFECTED AIR HANDLING UNIT. THE DDC SHALL SHUT DOWN ALL OTHER AIR HANDLING UNIT FANS, FAN COIL UNITS, EXHAUST FANS AND MAKE UP AIR FANS WITHIN THE BUILDING. ALL COMBINATION FIRE/SMOKE DAMPERS, RETURN AIR DAMPERS, EXHAUST DAMPERS AND OUTSIDE AIR

DAMPERS SHALL CLOSE.

DISCHARGE HIGH AND LOW LIMIT CONTROLS

IF THE DISCHARGE AIR TEMPERATURE FALLS BELOW THE LOW LIMIT SET POINT OR RISES ABOVE THE HIGH LIMIT SET-

POINT, THE SUPPLY FAN SHALL SHUT DOWN AND AN ALARM SHALL BE SENT TO THE DDC.

GENERAL ALARMS OR FAILURES

REFER TO THE POINTS LIST FOR OTHER ALARMS TO BE SENT TO THE DDC.

SINGLE DUCT VAV TERMINAL UNITS

THE PRIMARY AIR DAMPER SHALL MODULATE BETWEEN ITS MINIMUM AND MAXIMUM SET- POINTS TO SATISFY THE OCCUPIED AND UNOCCUPIED SPACE TEMP. SET-POINTS. THE DAMPER SHALL CLOSE, IF SET-POINT IS 2°C BELOW SET- POINT. NO MINIMUM AIRFLOW IS REQUIRED AT THE VAV EXCEPT TO MAINTAIN MINIMUM AIRFLOW AT THE ASSOCIATED

AHU FAN.

ON A LOSS OF POWER, THE PRIMARY AIR DAMPER SHALL OPEN.

CHILLED WATER COIL (AHU-1)

THE CHILLED WATER CONTROL VALVE SHALL MODULATE TO MAINTAIN THE COOLING COIL SET-POINT.

1.

2.

REFER TO MANUAFACTURER'S INSTALLATION INSTRUCTIONS

FOR COMPONENTS THAT MAY BE REQUIRED BUT ARE NOT

SHOWN ON THIS DIAGRAM.

SEE ASSOCIATED POINTS SCHEDULES ON ADJACENT M-700

SHEETS.

NTSH1 AHU-2/AHU-3

1 VAV TERMINAL AIR FLOW MONITORING STATION

2 VAV TERMINAL PRIMARY AIR DAMPER AND

ACTUATOR

3 NOT USED

4 DDC SYSTEM VAV TERMINAL UNIT CONTROLLER

(TUC)

5 WALL MOUNTED ZONE TEMPERATURE SENSOR

WITH OCCUPANCY OVERRIDE AND ASJUSTMENT

WHEEL

6 DUCT MOUNTED, PROBE TYPE, HUMIDITY SENSOR

7 DUCT MOUNTED, PROBE TYPE, TEMPERATURE

SENSOR

8 FILTER DIFFERENTIAL PRESSUE SENSOR

9 PLEATED MEDIA FILTERS

10 CONDENSATE PAN OVERFLOW SENSORS

11 MOTORIZED, 2-WAY MODULATING CONTROL VALVE

12 AVERAGING TYPE CAPILLARY TUBE, TEMPERATURE

SENSOR

13 WRAP AROUND HEAT PIPE

14 VARIABLE FREQUENCY DRIVE

15 DUCT MOUNTED SMOKE DETECTOR, SEE FIRE

ALARM PLANS.

16 DUCT MOUNTED SMOKE DETECTOR, SEE FIRE

ALARM PLANS.

17 PRESSURE RELIEF DOOR SET TO OPEN 0.87 kPA

18 DUCT MOUNTED STATIC PRESSURE SENSOR

MOUNTED AT THE ONE THIRD POINT IN THE MAIN

SUPPLY AIR DUCTS.

19 HEAT PIPE CIRCUIT SOLENOID VALVE. REFER TO

HEAT PIPE MANUFACTURER FOR EXACT NUMBER

OF VALVES TO BE CONTROLLED.

VAV AHU-1/AHU-2/AHU-3 WITHOUT RETURN FAN ALARMING PRIMARY POINT

INFORMATION

NETWORK

DATA

EXCHANGE

OVERRIDES TREND OBJECT

LOCATION (L OR

R), TYPE AND

INSTANCE

NUMBER

(PROVIDE DDC ID

FOR REMOTE IN

NOTES)

ALARM INFORMATION

CONFIGURATIO

N INFORMATION

FUNCTION NAME (DWG-

TAG) DESCRIPTION

DDC

HARDWARE

ID

SETTING

(WITH UNITS)

RANGE

(WITH UNITS)

IO

TYPE

HOA

REQ'D

CONFIG.

TYPE

M&C

VIEW

AND

OVRD

LDP

VIEW

AND

OVRD

TREND

REQ'D ALARM CONDITION ALARM

PRIORITY

M&C

ROUTIN

G

OBJECT TYPE AND

INSTANCE

NUMBER

(AND PROPERTY

ID)

DATA

FROM

DATA

TO

OBJECT TYPE &

INSTANCE

NUMBER OR

COMMANDABLE

ALARM TYPE

(PROVIDE DDC

ID FOR

REMOTE IN

NOTES)

NOTIFICATION

CLASS

OBJECT

INSTANCE

NUMBER

EVENT

ENROLLME

NT OBJECT

INSTANCE

NUMBER

PROOFS

SAFETIES

SF-S (FAN-SA) SUPPLY FAN STATUS (FAN

SA) <___> ON/OFF BI V V ~ SUPPLY FAN PROOF FAILED CRIT [___] <___> <___> <___> <___> <___> <___> <___> <___>

SA-SMK (SD-SA) SUPPLY AIR SMOKE <___> ALM/NORMAL BI H ~ ~ ~ ALM CRIT [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

SA-P-HL (SP-SA) SUPPLY AIR PRESSURE HIGH

LIMIT <___> 1000 Pa ALM/NORMAL BI ~ ~ ~ ALM INFO [___] <___> <___> <___>

RST-BUT SYSTEM RESET BUTTON

(FOR SAFETIES) <___> BI VO ~ ~ <___> <___> <___> <___> <___> <___>

START/STOP

SYS-OCC OCCUPANCY INPUT (FROM

SYSTEM SCHEDULER) <___> <___> NET-IN V V ~ ~ INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

SF-SS (FAN-SA) SUPPLY FAN START/STOP <___> ON/OFF BO ~ VO V ~ ~ INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

UNIT STATUS UNIT STATUS (HTG AND/OR

CLG REQUEST) (SEE NOTE) <___>

<HVAC_COOL/HVAC_

HEAT/HVAC_OFF>

NET-OUT V ~ ~ ~ INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

SUPPLY FAN

CAPACITY

CONTROL

SA-P (SP-SA) SUPPLY AIR PRESSURE <___> <___> AI V V Y *SA-P MORE THAN 20%

ABOVE OR BELOW SA-P-SP INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

SA-P-SP (SP-SA) SUPPLY AIR PRESSURE

SETPOINT <____kPa> W/ RESET <___> C VO V ~ <___> <___> <___> <___> <___> <___>

SA-P-SP-RT SUPPLY AIR PRESSURE

SETPOINT RATE OF CHANGE 2.5 " Pa./min C V V ~ <___> <___> <___> <___> <___> <___>

SF-C (VFD-SA) SUPPLY FAN VFD COMMAND <___> 0-100% AO ~ VO ~ ~ <___> <___> <___> <___>

SF-C-MIN SUPPLY FAN VFD COMMAND

MINIMUM 25% C VO V ~ <___> <___> <___> <___>

SUPPLY FAN PID

LOOP SETTINGS

PROPORTIONAL CONSTANT <___> <___> C <___>

INTEGRAL CONSTANT <___> <___> C <___>

BIAS <___> <___> C <___>

MAXIMUM OUTPUT <___> <___> C <___>

MINIMUM OUTPUT <___> <___> C <___>

<____> <___> <___> C <___>

SUPPLY AIR

TEMPERATURE

SA-T (TS-SAT) SUPPLY AIR TEMPERATURE <___> <___> AI V V Y <___> <___> <___> <___> <___> <___> <___> <___> <___>

SA-T-SP (TS-SAT) SUPPLY AIR TEMPERATURE

SETPOINT 13 DEG C W/RESET <___> C VO V ~ <___> <___> <___> <___> <___> <___>

CLG-V-C COOLING VALVE COMMAND <___> 0-100% OPEN AO ~ VO V ~ [ ~ ] [INFO]

[CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

HTG-V-C

WRAP-AROUND HEAT PIPE

VALVE COMMAND (AHU-1

ONLY)

<___> 0-100% OPEN AO ~ VO V ~ [ ~ ] [INFO]

[CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

COOLING VALVE

PID LOOP

SETTINGS

PROPORTIONAL CONSTANT <___> <___> C <___>

INTEGRAL CONSTANT <___> <___> C <___>

BIAS <___> <___> C <___>

MAXIMUM OUTPUT <___> <___> C <___>

MINIMUM OUTPUT <___> <___> C <___>

<____> <___> <___> C <___>

HEAT PIPE

REFRIGERANT

VALVE PID LOOP

SETTINGS (AHU-1

ONLY)

PROPORTIONAL CONSTANT <___> <___> C <___>

INTEGRAL CONSTANT <___> <___> C <___>

BIAS <___> <___> C <___>

MAXIMUM OUTPUT <___> <___> C <___>

MINIMUM OUTPUT <___> <___> C <___>

<____> <___> <___> C <___>

OTHER POINTS

RA-T (TS-RA) RETURN AIR TEMPERATURE <___> <___> AI V ~ ~ ~ INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___> RA-H (HS-RA) RETURN AIR HUMIDITY <___> <___> AI V ~ ~ ~ INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

CC-T (TS-CLG) COOLING COIL DISCHARGE

TEMPERATURE <___> <___> AI V V X ~ INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

CC-T-SP (TS-

CLNG)

COOLING COIL DISCHARGE

SETPOINT (AHU-1 ONLY) 11 DEG C <___> C VO V ~ <___> <___> <___> <___> <___> <___>

ZN-D-C-MAX ZONE DAMPER COMMAND

SETPOINT MAXIMUM <__> C VO V ~ <___> <___> <___> <___> <___> <___>

ZN-D-C-MIN ZONE DAMPER COMMAND

SETPOINT MINIMUM <__> C VO V ~ <___> <___> <___> <___> <___> <___>

ZN-D-C-EFF MAXIMUM (EFFECTIVE) ZONE

DAMPER COMMAND 0-100% OPEN V V X <___> <___> <___> <___> <___> <___>

OCFL-SW CONDENSATE OVERFLOW

SENSOR <___> <___> NORMAL/OVERFLOW BO V ~ ~ ALM CRIT [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

RA-FLT-P-HL (DP-

F1-RA)

RETURN AIR FILTER

PRESSURE HIGH LIMIT

SWITCH

<___> <___> ALM/NORMAL BI H V ~ ~ ALM INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

NOTES:

1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THE POINTS SCHEDULE INSTRUCTIONS DRAWING. 4) DDC HW ID FOR DEVICE CONTAINING TREND OBJECT FOR REMOTE TRENDING FOR THIS SYSTEM: <___>

2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW. 5) DDC HW ID FOR DEVICE CONTAINING EVENT ENROLLMENT OBJECT FOR REMOTE ALARMING FOR THIS SYSTEM: <___>

3) UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR CHILLER SERVING THIS SYSTEM.

3 F

OU

NT

AI

NS

P

AR

KW

AY

SU

IT

E

FA

IR

VI

EW

H

EI

GH

TS

, I

L

8-

8.6

.70

W

OO

LP

ER

T, In c.

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

FI

LE

N

AM

E:

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

U S

A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

C H

EC

KE

D B

Y:

US Army Corps of Engineers ®

IS

O

A

A

D R

AW

IN

G C

O D

E:

B

C

D

E

F

G

1 2 3 4 5 6

SHEET ID

Japan District

7 8 9 10

H

J

K

L

M

N

P

Q

R

11 12 13 14 15 16 17 18 19 20 21

W

2H V1

9D

A.

D

ET

ME

R

N.

V

AL

DE

Z

R.

K

NO

LL

E

M.

B

EH

RM

AN

N

M-706

AH

U

C O

N

TR

O L

PO

IN

TS

L

IS

T

C O

M

FL

EA

C

T O

KI

N

AW

A

JA

K

AD

EN

A

AF

B, O

KI

N

AW

A, J

AP

AN

P5

A

IR

C

R

AF

T

IN

TE

R

M

ED

IA

TE

M

AI

N

TE

N

AN

C E

FA

C

IL

IT

Y

W

2H V1

9D

JA

PA

N D

IS

TR

IC

T

U ni t 3

AP

O A

P

4-

JU

LY

W

2H V1

9D

_ M

-7

D

ES

IG

N

S U

BM

IT

TA

L

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

DEDICATED OUTSIDE AIR UNIT ALARMING PRIMARY POINT INFORMATION NETWORK DATA

EXCHANGE OVERRIDES

TREND OBJECT

LOCATION (L OR R),

TYPE AND INSTANCE

NUMBER

(PROVIDE DDC ID FOR

REMOTE IN NOTES)

ALARM INFORMATION

CONFIGURATION

INFORMATION

FUNCTION NAME DESCRIPTION DDC

HARDWARE ID

SETTING

(WITH UNITS)

RANGE

(WITH UNITS)

IO

TYPE HOA REQ'D CONFIG.

TYPE

M&C VIEW

AND OVRD

LDP VIEW

AND OVRD TREND REQ'D ALARM CONDITION ALARM

PRIORITY

M&C

ROUTING

OBJECT TYPE AND INSTANCE

NUMBER

(AND PROPERTY ID)

DATA

FROM DATA TO

OBJECT TYPE &

INSTANCE NUMBER OR

COMMANDABLE

ALARM TYPE

(PROVIDE DDC ID FOR

REMOTE IN NOTES)

NOTIFICATION CLASS

OBJECT INSTANCE

NUMBER

EVENT ENROLLMENT

OBJECT INSTANCE

NUMBER

PROOFS

SAFETIES

SF-S SUPPLY FAN STATUS

ON/OFF BI V V SUPPLY FAN PROOF FAILED [info] [crit] [___]

EF-S EXHAUST FAN STATUS

ON/OFF BI V V EXHAUST FAN PROOF FAILED [info] [crit] [___]

SA-SMK SUPPLY AIR SMOKE <___> ALM/NORMAL BI H ALM [info] [crit] [___] <___> <___> <___> [___] [___] [___]

EA-SMK EXHAUST AIR SMOKE

ALM/NORMAL BI H

HTG-DA-T-LL HEATING COIL DISCHARGE

TEMPERATURE LOW LIMIT

SWITCH

[4 DEG C] ALM/NORMAL BI H ALM [info] [crit] [___]

RST-BUT SYSTEM RESET BUTTON

(FOR SAFETIES)

BI H

OA-FLT-P-HL AIR FILTER PRESSURE

HIGH LIMIT SWITCH

<___> ALM/NORMAL BI H V [ALM] [info] [crit] [___]

START/STOP

SYS-OCC OCCUPANCY INPUT (FROM

SYSTEM SCHEDULER) <___>

<___> NET-IN V V

MSV <___> <___> <___>

SF-SS SUPPLY FAN START/STOP

ON/OFF BO [~] VO V

EF-SS EXHAUST FAN

START/STOP <___>

ON/OFF BO [~] VO V

UNIT STATUS UNIT STATUS (SEE NOTE)

ON/OFF NET-OUT V

FAN CAPACITY

CONTROL

SA-F SUPPLY AIR FLOW <___> <___> AI X <___> <___> <___> <___> [___] [___] [___]

EA-F EXHAUST AIR FLOW <___> <___> AI X <___> <___> <___> <___> [___] [___] [___]

SUPPLY AIR

TEMPERATURE

SA-T SUPPLY AIR

TEMPERATURE <___>

<___> AI V X *SA-T MORE THAN 6 DEG C ABOVE OR

BELOW SETPOINT

[info] [crit] [___]

SA-T-SP SUPPLY AIR

TEMPERATURE SETPOINT

[13 DEG C] <___> C VO VO

CLG-V-C COOLING VALVE

COMMAND <___>

0-100% OPEN AO [~] VO V

COOLING VALVE PID LOOP

SETTINGS

<___> C

HTG-V-C HEATING VALVE

COMMAND <___>

0-100% OPEN AO [~] VO V

HEATING VALVE PID LOOP

SETTINGS

<___> C

OTHER POINTS

OA-T OUTSIDE AIR

TEMPERATURE <___>

<___> AI V [ ~ ] [ ~ ]

EA-T EXHAUST AIR

TEMPERATURE <___>

<___> AI V [ ~ ] [ ~ ]

NOTES:

1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THE POINTS SCHEDULE INSTRUCTIONS DRAWING.

2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.

3) UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR CHILLER SERVING THIS SYSTEM.

THIS NOTE IS USED ONLY FOR BACNET (NO NIAGARA)

4) DDC HW ID FOR DEVICE CONTAINING TREND OBJECT FOR REMOTE TRENDING FOR THIS SYSTEM: <_____>

THIS NOTE IS USED ONLY FOR BACNET (NO NIAGARA)

5) DDC HW ID FOR DEVICE CONTAINING EVENT ENROLLMENT OBJECT FOR REMOTE ALARMING FOR THIS SYSTEM: <_____>

COOLING ONLY VAV BOX (TUC-VAV) ALARMING PRIMARY POINT

INFORMATION

NETWORK

DATA

EXCHANGE

OVERRIDES TREND OBJECT

LOCATION (L OR

R), TYPE AND

INSTANCE

NUMBER

(PROVIDE DDC ID

FOR REMOTE IN

NOTES)

ALARM INFORMATION

CONFIGURATION

INFORMATION

FUNCTION NAME (DWG

TAG) DESCRIPTION

DDC

HARDWARE

ID

SETTING

(WITH UNITS)

RANGE

(WITH UNITS)

IO

TYPE

HOA

REQ'D

CONFIG.

TYPE

M&C

VIEW

AND

OVRD

LDP

VIEW

AND

OVRD

TREND

REQ'D ALARM CONDITION ALARM

PRIORITY

M&C

ROUTIN

G

OBJECT TYPE AND

INSTANCE

NUMBER

(AND PROPERTY

ID)

DATA

FROM

DATA

TO

OBJECT TYPE &

INSTANCE

NUMBER OR

COMMANDABLE

ALARM TYPE

(PROVIDE DDC ID

FOR REMOTE IN

NOTES)

NOTIFICATION

CLASS OBJECT

INSTANCE

NUMBER

EVENT

ENROLLMENT

OBJECT

INSTANCE

NUMBER

PROOFS &

SAFETIES

<UNIT MANUFACTURER'S

SAFETIES> (SEE NOTES) <___> ALM/NORMAL <BI> ~ H ~ ~ ~ ALM INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

<UNIT MANUFACTURER'S

SAFETIES> (SEE NOTES) <___> ALM/NORMAL <BI> ~ H ~ ~ ~ ALM INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

START/STOP SYS-OCC OCCUPANCY INPUT (FROM

SYSTEM SCHEDULER) <___> <___> NET-IN VO ~ ~ ~ INFP [___] MSV <___> <___> <___> <___> <___> <___> <___> <___> <___>

ZONE

TEMPERATURE

CONTROL

ZN-T (TS-ZONE) ZONE TEMPERATURE <___> <___> AI V ~ Y

** ZN-T IS MORE THAN 20

DEG C ABOVE OR BELOW

ZN-T-SP

INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

ZN-T-SP (TS-

ZONE)

ZONE TEMPERATURE

SETPOINT OCC ADJ 25 DEG C AI C VO ~ ~ ~ INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

VAV-SA-F (AFM-

VAV) VAV SUPPLY AIR FLOW <___> <___ >L/S <0 - ___ >L/S AI V ~ ~ ~ INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

VAV-SA-F-SP

(AFM-VAV)

VAV SUPPLY AIR FLOW

SETPOINT RESET SCHED <0 - ___>L/S C ~ ~ ~ ~ INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

VAV-D-C (DPR-

VAV) VAV DAMPER COMMAND <___> 0-100% OPEN AO ~ V ~ Y ~ INFO [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

VAV DAMPER PID

LOOP SETTINGS

PROPORTIONAL CONSTANT <___> <___> C <___> <___>

INTEGRAL CONSTANT <___> <___> C <___> <___>

BIAS <___> <___> C <___> <___>

MAXIMUM OUTPUT <___> <___> C <___> <___>

MINIMUM OUTPUT <___> <___> C <___> <___>

<____> <___> <___> C <___> <___>

NOTES:

1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS SPECIFIED AND AS DESCRIBED IN THE POINTS SCHEDULE INSTRUCTIONS DRAWING. 4) ALARM CONDITIONS MARKED WITH A DOUBLE ASTERISK (**) SHALL BE ACTIVE ONLY WHEN THE SYSTEM IS IN OCCUPIED MODE AND HAS BEEN IN OCCUPIED MODE FOR MORE

THAN 30 MINUTES.2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.

5) UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR

CHILLER SERVING THIS SYSTEM.

3) SYS-OCC: AS DESCRIBED IN THE POINTS SCHEDULE INSTRUCTIONS, OVERRIDE OF SYS-OCC IS ACCOMPLISHED THROUGH THE SYSTEM SCHEDULER.

3 F

OU

NT

AI

NS

P

AR

KW

AY

SU

IT

E

FA

IR

VI

EW

H

EI

GH

TS

, I

L

8-

8.6

.70

W

OO

LP

ER

T, In c.

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

FI

LE

N

AM

E:

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

U S

A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

C H

EC

KE

D B

Y:

US Army Corps of Engineers ®

IS

O

A

A

D R

AW

IN

G C

O D

E:

B

C

D

E

F

G

1 2 3 4 5 6

SHEET ID

Japan District

7 8 9 10

H

J

K

L

M

N

P

Q

R

11 12 13 14 15 16 17 18 19 20 21

W

2H V1

9D

A.

D

ET

ME

R

N.

V

AL

DE

Z

R.

K

NO

LL

E

M.

B

EH

RM

AN

N

M-707

D O

AS

V

AV

C O

N

TR

O L

PO

IN

TS

L

IS

T

C O

M

FL

EA

C

T O

KI

N

AW

A

JA

K

AD

EN

A

AF

B, O

KI

N

AW

A, J

AP

AN

P5

A

IR

C

R

AF

T

IN

TE

R

M

ED

IA

TE

M

AI

N

TE

N

AN

C E

FA

C

IL

IT

Y

W

2H V1

9D

JA

PA

N D

IS

TR

IC

T

U ni t 3

AP

O A

P

4-

JU

LY

W

2H V1

9D

_ M

-7

D

ES

IG

N

S U

BM

IT

TA

L

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

AC-1

T

TS

AC

AC-3

TS-RM

CU-1 CU-2

CU-3

GRADE

EE-SW

O2

O2-RM

EXHAUST FAN

FAN-EA

M

DPR-EXH

EXHAUST IN

EF-6

EF-10

EF-7

EF-12

EXTERIOR WALL

EXHAUST OUT

EF-14

M DPR-EXH

ROOF

EX

HA

US

T

IN

EF-1

FAN-EA

EXHAUST FAN

FAN-EA

M

EXHAUST IN

EF-2 EF-3

EF-11

SW

EXHAUST OUT

DPR-EXH

EXTERIOR WALL

M DPR-EXH

ROOF

EX

HA

US

T

IN

EF-5

FAN-EA

M DPR-EXH

ROOF

EX

HA

US

T

IN

EF-8

FAN-EA

EF-4

EF-9

EF-13

SW

H2

H2-RM

3 F

OU

NT

AI

NS

P

AR

KW

AY

SU

IT

E

FA

IR

VI

EW

H

EI

GH

TS

, I

L

8-

8.6

.70

W

OO

LP

ER

T, In c.

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

FI

LE

N

AM

E:

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

U S

A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

C H

EC

KE

D B

Y:

US Army Corps of Engineers ®

IS

O

A

A

D R

AW

IN

G C

O D

E:

B

C

D

E

F

G

1 2 3 4 5 6

SHEET ID

Japan District

7 8 9 10

H

J

K

L

M

N

P

Q

R

11 12 13 14 15 16 17 18 19 20 21

W

2H V1

9D

A.

D

ET

ME

R

N.

V

AL

DE

Z

R.

K

NO

LL

E

M.

B

EH

RM

AN

N

M-708

M

IS

C

EL

LA

N

EO

U

S C

O N

TR

O

L D

IA

G

R

AM

S

C O

M

FL

EA

C

T O

KI

N

AW

A

JA

K

AD

EN

A

AF

B, O

KI

N

AW

A, J

AP

AN

P5

A

IR

C

R

AF

T

IN

TE

R

M

ED

IA

TE

M

AI

N

TE

N

AN

C E

FA

C

IL

IT

Y

W

2H V1

9D

JA

PA

N D

IS

TR

IC

T

U ni t 3

AP

O A

P

4-

JU

LY

W

2H V1

9D

_ M

-7

D

ES

IG

N

S U

BM

IT

TA

L

GENERAL SHEET NOTES:

SHEET KEYNOTES:

NTSH1 AC UNIT WITH CONDENSING UNIT GRADE

NTSF1 EMERGENCY SHUT DOWN SWITCH

NTSD1 O2 MONITORS SENSORS

NTSH13 INLINE EXHAUST FANS (EF-6,7,10,12,14)

NTSN1 DOWNBLAST EXHAUST FAN (EF-1)

NTSH7 INLINE EXHAUST FANS (EF-2,3,11)

NTSN13 UPBLAST EXHAUST FAN (EF-5)

NTSN7 UPBLAST EXHAUST FAN (EF-4,8,9,13)

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

1.

2.

REFER TO MANUAFACTURER'S INSTALLATION INSTRUCTIONS

FOR COMPONENTS THAT MAY BE REQUIRED BUT ARE NOT

SHOWN ON THIS DIAGRAM.

SEE ASSOCIATED POINTS SCHEDULES ON ADJACENT M-700

SHEETS.

SEQUENCE OF OPERATION

1.

2.

1.

2.

1.

2.

1.

2.

1.

2.

1.

2.

WALL-MOUNTED DUCTLESS SPLIT A/C UNIT (AC-1A,1B,2,3A,3B / CU-1A,1B,2,3A,3B) HVAC EMERGENCY SHUT-DOWN THE SYSTEM SHALL BE CONTROLLED THROUGH LOCAL SPACE MOUNTED 7-DAY PROGRAMMABLE THERMOSTAT. ON A CALL FOR COOLING FROM THE THERMOSTAT, THE AIR-COOLED CONDENSING UNIT SHALL RUN AND THE INDOOR

FAN SHALL CYCLE ON UNTIL THE SPACE SET POINT IS SATISFIED.

A SEPARATE DDC TEMPERATURE SENSOR SHALL MONITOR THE SPACE TEMPERATURE. AN ALARM SHALL BE SENT

TO THE DDC WHEN THE SPACE TEMPERATURE EXCEEDS 29°C.

INLINE EXHAUST FANS (EF-2,3)

THE FAN SHALL BE ACTIVATED BY A WALL MOUNTED SWITCH. PRIOR TO ACTIVATION OF THE FAN, THE MOTORIZED

DAMPER SHALL OPEN.

THE DDC SHALL MONITOR FAN STATUS (ON/OFF) AND MONITOR DAMPER POSITION (OPEN/CLOSED).

INLINE EXHAUST FANS (EF-6,7,10,11,12,14)

THE FAN SHALL RUN CONTINOUSLY. THE MOTORIZED DISCHARGE DAMPER SHALL BE OPEN.

THE DDC SHALL ENABLE/DISABLE, MONITOR FAN STATUS (ON/OFF), AND MONITOR DAMPER POSITION

(OPEN/CLOSED).

UPBLAST EXHAUST FANS (EF-4,8,9,13)

THE FAN SHALL BE ACTIVATED BY A WALL MOUNTED SWITCH. PRIOR TO ACTIVATION OF THE FAN, THE MOTORIZED

DAMPER SHALL OPEN.

THE DDC SHALL MONITOR FAN STATUS (ON/OFF) AND MONITOR DAMPER POSITION (OPEN/CLOSED).

UPBLAST EXHAUST FAN (EF-5)

THE FAN SHALL RUN CONTINOUSLY. THE MOTORIZED DISCHARGE DAMPER SHALL BE OPEN.

THE DDC SHALL ENABLE/DISABLE, MONITOR FAN STATUS (ON/OFF), AND MONITOR DAMPER POSITION

(OPEN/CLOSED).

DOWNBLAST EXHAUST FAN (EF-1)

THE FAN SHALL BE ENABLED THROUGH THE DDC AND RUN CONTINOUSLY DURING OCCUPIED MODE. PRIOR TO

ACTIVATION OF THE FAN, THE MOTORIZED DISCHARGE DAMPER SHALL OPEN.

THE DDC SHALL ENABLE/DISABLE, MONITOR FAN STATUS (ON/OFF), AND MONITOR DAMPER POSITION

(OPEN/CLOSED).

1.

2.

1.

1.

HVAC EMERGENCY SHUT-DOWN

PROVIDE HVAC EMERGENCY SHUT-OFF PUSH BUTTONS WHERE INDICATED ON THE FLOOR PLANS. THE SWITCH SHALL BE A "RAISE LID" MUSHROOM PUSH-BUTTON TYPE WITH MANUAL RESET AT THE BUTTON . THE BUTTON SHALL BE EASILY ACCESSIBLE BY THE BUILDING OCCUPANTS AND LOCATED NEAR THE MASS NOTIFICATION SYSTEM LOCAL OPERATING CONSOLES (LOC). THE SWITCH SHALL BE LABELED "HVAC

EMERGENCY SHUT DOWN" AND OF A DIFFERENT COLOR THAN THE FIRE ALARM PULL STATIONS.

WHEN AN HVAC EMERGENCY SHUTOFF BUTTON IS ACTIVATED, THE HVAC AIR DISTRIBUTION AND EXHAUST SYSTEM FANS (NOT INCLUDING SMOKE CONTROL EXHAUST FANS) SHALL AUTOMATICALLY SHUT DOWN AND ALL DAMPERS LEADING TO THE OUTSIDE SHALL CLOSE. THE SYSTEM MUST BE CAPABLE OF SHUTTING DOWN ALL REQUIRED HVAC SYSTEMS AND CLOSING ALL REQUIRED DAMPERS, EVEN IF A LOCAL HAND/OFF/AUTO

SWITCH IS IN THE HAND POSITION, WITHIN 30 SECONDS OF ACTIVATION.

O2 MONITOR/SENSORS

O2 SENSORS SHALL MONITOR THE SPACE OXYGEN LEVELS AND ALARM WHENEVER OXYGEN LEVEL RISES ABOVE THE SETPOINT LEVEL. AN AUDIO ALARM SHALL SOUND AND ALARM SHALL BE SENT TO THE MAIN DDC.

H2 MONITOR/SENSORS

H2 SENSORS SHALL MONITOR THE SPACE HYDROGEN LEVELS AND ALARM WHENEVER HYDROGEN LEVEL RISES ABOVE THE SETPOINT LEVEL. AN AUDIO ALARM SHALL SOUND AND ALARM SHALL BE SENT TO THE MAIN

DDC.

1 LOW LEAKAGE, MOTORIZED, TWO POSITION

DAMPER.

2 WALL MOUNTED, DDC TEMPERATURE SENSOR FOR

MONITORING PURPOSES.

3 7-DAY PROGRAMMABLE THERMOSTAT PROVIDED

WITH SPLIT SYSTEM UNIT.

4 WALL MOUNTED, DDC TEMPERATURE SENSOR FOR

MONITORING PURPOSES.

5 HVAC EMERGENCY SHUT-OFF SWITCH IN ROOMS

101, 109, 120, AND 200. SEE FLOOR PLANS FOR

EXACT LOCATIONS.

6 WALL MOUNTED OXYGEN MONITORING STATION

WITH DIGITAL DISPLAY AND TWO ADJUSTABLE

ALARM RELAY SETPOINTS WITH OUTPUT TO

BUILDING'S DDC SYSTEM.

7 OXYGEN SENSORS FOR THE O2 ROOM. SEE FLOOR

PLANS FOR LOCATION AND QUANTITIES.

8 WALL MOUNTED HYDROGEN MONITORING STATION

WITH DIGITAL DISPLAY AND TWO ADJUSTABLE

ALARM RELAY SETPOINTS WITH OUTPUT TO

BUILDING'S DDC SYSTEM.

9 HYDROGEN SENSORS FOR THE H2 ROOM. SEE

FLOOR PLANS FOR LOCATION AND QUANTITIES.

NTSB1 H2 MONITORS SENSORS

ELECTRIC METER

INFORMATION

NETWORK

DATA

EXCHANGE

OVERRIDES TREND OBJECT

LOCATION (L OR R),

TYPE AND

INSTANCE NUMBER

(PROVIDE DDC ID

FOR REMOTE IN

NOTES)

ALARM INFORMATION

CONFIGURATION

INFORMATION

FUNCTION NAME DESCRIPTION

DDC

HARDWARE

ID

SETTING

(WITH

UNITS)

RANGE

(WITH UNITS)

IO

TYPE

HOA

REQ'D

CONFIG

TYPE

M&C

VIEW

AND

OVRD

LDP

VIEW

AND

OVRD

TREND

REQ'D ALARM CONDITION ALARM

PRIORITY

M&C

ROUTIN

G

OBJECT TYPE AND

INSTANCE NUMBER

(AND PROPERTY ID)

DATA

FROM

DATA

TO

OBJECT TYPE &

INSTANCE

NUMBER OR

COMMANDABLE

ALARM TYPE

(PROVIDE DDC ID

FOR REMOTE IN

NOTES)

NOTIFICATION

CLASS OBJECT

INSTANCE

NUMBER

EVENT

ENROLLMENT

OBJECT

INSTANCE

NUMBER

REQUIRED

POINTS

PWR-TOT REAL POWER (TOTAL) <___> 0 - <___> WATTS V [~] X [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___> KWH-TOT TOTAL kWh (TOTAL ENERGY) <___> 0 - <___> kWh V [~] X [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

PWR-DEMAND-

PEAK

HISTORICAL PEAK DEMAND

POWER <___> 0 - <___> WATTS V [~] X [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

PWR-DEMAND DEMAND POWER <___> 0 - <___> WATTS V [~] X [___][~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___> VOLT-A RMS VOLTAGE FOR PHASE A <___> 0 - <___> VOLTS RMS <AI> V [~] X VOLT-A < [0.9*NOMINAL] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___> VOLT-B RMS VOLTAGE FOR PHASE B <___> 0 - <___> VOLTS RMS <AI> V [~] X VOLT-B < [0.9*NOMINAL] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___> VOLT-C RMS VOLTAGE FOR PHASE C <___> 0 - <___> VOLTS RMS <AI> V [~] X VOLT-C < [0.9*NOMINAL] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___> AMP-A RMS CURRENT FOR PHASE A <___> 0 - <___> AMPS RMS <AI> V [~] X [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___> AMP-B RMS CURRENT FOR PHASE B <___> 0 - <___> AMPS RMS <AI> V [~] X [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___> AMP-C RMS CURRENT FOR PHASE C <___> 0 - <___> AMPS RMS <AI> V [~] X [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___> HZ-AVG AVERAGE LINE FREQUENCY <___> 0 - <___> HZ V [~] X [~] [INFO] [CRIT] [___] <___> <___> <___> <___>

OPTIONAL

POINTS

PWR-A REAL POWER FOR PHASE A <___> 0 - <___> WATTS [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___> PWR-B REAL POWER FOR PHASE B <___> 0 - <___> WATTS [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> PWR-C REAL POWER FOR PHASE C <___> 0 - <___> WATTS [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> HZ-A FREQUENCY FOR PHASE A <___> 0 - <___> HZ [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> HZ-B FREQUENCY FOR PHASE B <___> 0 - <___> HZ [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> HZ-C FREQUENCY FOR PHASE C <___> 0 - <___> HZ [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> KVA-TOT TOTAL kVA <___> 0 - <___> kVA [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> KVA-A kVA FOR PHASE A <___> 0 - <___> kVA [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> KVA-B kVA FOR PHASE B <___> 0 - <___> kVA [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___> KVA-C kVA FOR PHASE C <___> 0 - <___> kVA [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___> KVAR-TOT TOTAL REACTIVE POWER <___> 0 - <___> kVA [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

KVAR-A REACTIVE POWER FOR PHASE

A <___> 0 - <___> kVA [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

KVAR-B REACTIVE POWER FOR PHASE

B <___> 0 - <___> kVA [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

KVAR-C REACTIVE POWER FOR PHASE

C <___> 0 - <___> kVA [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

KVARH-TOT TOTAL kVARh (TOTAL REACTIVE ENERGY) <___> 0 - <___> kVAh [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

KVARH-A kVARh (TOTAL REACTIVE ENERGY) FOR PHASE A <___> 0 - <___> kVAh [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

KVARH-B kVARh (TOTAL REACTIVE ENERGY) FOR PHASE B <___> 0 - <___> kVAh [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

KVARH-C kVARh (TOTAL REACTIVE ENERGY) FOR PHASE C <___> 0 - <___> kVAh [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

PF-AVG AVERAGE POWER FACTOR <___> -1 TO 1 [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___> PF-A POWER FACTOR FOR PHASE A <___> -1 TO 1 [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___> PF-B POWER FACTOR FOR PHASE B <___> -1 TO 1 [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> PF-C POWER FACTOR FOR PHASE C <___> -1 TO 1 [~] [~] [~] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

Notes:

1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THE POINTS SCHEDULE

INSTRUCTIONS DRAWING.

2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.

3) UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR CHILLER SERVING THIS SYSTEM.

4) DDC HW ID FOR DEVICE CONTAINING TREND OBJECT FOR REMOTE TRENDING FOR THIS SYSTEM: <___>

5) DDC HW ID FOR DEVICE CONTAINING EVENT ENROLLMENT OBJECT FOR REMOTE ALARMING FOR THIS SYSTEM: <___>

WATER METER

ALARMING PRIMARY POINT

INFORMATION

NETWORK DATA

EXCHANGE OVERRIDES TREND OBJECT

LOCATION (L OR

R), TYPE AND

INSTANCE

NUMBER

(PROVIDE DDC ID

FOR REMOTE IN

NOTES)

ALARM INFORMATION

CONFIGURATION

INFORMATION

FUNCTION NAME DESCRIPTION

DDC

HARDWARE

ID

SETTING

(WITH

UNITS)

RANGE

(WITH UNITS)

IO

TYPE

HOA

REQ'D

CONFIG.

TYPE

M&C

VIEW AND

OVRD

LDP VIEW

AND

OVRD

TREND

REQ'D ALARM CONDITION ALARM

PRIORITY

M&C

ROUTING

OBJECT TYPE AND

INSTANCE NUMBER

(AND PROPERTY ID)

DATA

FROM

DATA

TO

OBJECT TYPE &

INSTANCE

NUMBER OR

COMMANDABLE

ALARM TYPE

(PROVIDE

DDC ID FOR

REMOTE IN

NOTES)

NOTIFICATION

CLASS OBJECT

INSTANCE

NUMBER

EVENT

ENROLLMENT

OBJECT

INSTANCE

NUMBER

Flow

WATER-F WATER FLOW RATE <___> 0 - <___> [CU L /

MIN][LPS] [LPM] <PULSE><AI> V X <EXCESSIVE FLOW> CRIT [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

WATER-F-TOT TOTAL WATER FLOW <___> 0 - <___> [CU M] [L] <PULSE><AI> V <___> <___> <___> <___> <___>

FLOW RATE CONFIGURATION <___> <<___> [CU M] PER

PULSE><___> <PULSE><AI> C <___>

Notes:

1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THE POINTS SCHEDULE INSTRUCTIONS DRAWING.

2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.

3) UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR CHILLER SERVING THIS SYSTEM.

THIS NOTE IS USED ONLY FOR BACNET (NO NIAGARA) 4) DDC HW ID FOR DEVICE CONTAINING TREND OBJECT FOR REMOTE TRENDING FOR THIS SYSTEM: <___> THIS NOTE IS USED ONLY FOR BACNET (NO NIAGARA) 5) DDC HW ID FOR DEVICE CONTAINING EVENT ENROLLMENT OBJECT FOR REMOTE ALARMING FOR THIS SYSTEM: <___>

3 F

OU

NT

AI

NS

P

AR

KW

AY

SU

IT

E

FA

IR

VI

EW

H

EI

GH

TS

, I

L

8-

8.6

.70

W

OO

LP

ER

T, In c.

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

FI

LE

N

AM

E:

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

U S

A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

C H

EC

KE

D B

Y:

US Army Corps of Engineers ®

IS

O

A

A

D R

AW

IN

G C

O D

E:

B

C

D

E

F

G

1 2 3 4 5 6

SHEET ID

Japan District

7 8 9 10

H

J

K

L

M

N

P

Q

R

11 12 13 14 15 16 17 18 19 20 21

W

2H V1

9D

A.

D

ET

ME

R

N.

V

AL

DE

Z

R.

K

NO

LL

E

M.

B

EH

RM

AN

N

M-709

M

IS

C

EL

LA

N

EO

U

S C

O N

TR

O

L

PO

IN

TS

L

IS

TS

C O

M

FL

EA

C

T O

KI

N

AW

A

JA

K

AD

EN

A

AF

B, O

KI

N

AW

A, J

AP

AN

P5

A

IR

C

R

AF

T

IN

TE

R

M

ED

IA

TE

M

AI

N

TE

N

AN

C E

FA

C

IL

IT

Y

W

2H V1

9D

JA

PA

N D

IS

TR

IC

T

U ni t 3

AP

O A

P

4-

JU

LY

W

2H V1

9D

_ M

-7

D

ES

IG

N

S U

BM

IT

TA

L

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

EXHAUST FANS

INFORMATION

NETWORK

DATA

EXCHANGE

OVERRIDES TREND OBJECT

LOCATION (L OR R),

TYPE AND INSTANCE

NUMBER

(PROVIDE DDC ID

FOR REMOTE IN

NOTES)

ALARM INFORMATION

CONFIGURATION

INFORMATION

FUNCTION NAME DESCRIPTION

DDC

HARDWARE

ID

SETTING

(WITH

UNITS)

RANGE

(WITH UNITS)

IO

TYPE

HOA

REQ'D

CONFIG.

TYPE

M&C

VIEW

AND

OVRD

LDP

VIEW

AND

OVRD

TREND

REQ'D

ALARM

CONDITION

ALARM

PRIORITY

M&C

ROUTING

OBJECT TYPE AND

INSTANCE NUMBER

(AND PROPERTY ID)

DATA

FROM

DATA

TO

OBJECT TYPE &

INSTANCE NUMBER

OR

COMMANDABLE

ALARM TYPE

(PROVIDE DDC ID

FOR REMOTE IN

NOTES)

NOTIFICATION

CLASS OBJECT

INSTANCE

NUMBER

EVENT

ENROLLMENT

OBJECT

INSTANCE

NUMBER

PROOFS

SAFETIES

EF-S EXHAUST FAN STATUS <___> ON/OFF BI V [ V ] [ ~ ] EXHAUST FAN

PROOF FAILED [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___>

START/STOP SYS-OCC OCCUPANCY INPUT (FROM

SYSTEM SCHEDULER) <___> <___> NET-IN V [ V ] [ ~ ] ~ [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

SF-SS SUPPLY FAN START/STOP <___> ON/OFF BO [~] VO [ V ] [ ~ ] [~] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

EF-DMPR

RETURN AIR FILTER

PRESSURE HIGH LIMIT

SWITCH

<___> <___> OPEN/CLOSED AI H V [ ~ ] [ ~ ] [ALM] [INFO] [CRIT] [___] <___> <___> <___> <___> <___> <___> <___> <___> <___>

Notes:

1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THE POINTS SCHEDULE INSTRUCTIONS DRAWING.

2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.

3) UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR CHILLER SERVING THIS SYSTEM.

4) DDC HW ID FOR DEVICE CONTAINING TREND OBJECT FOR REMOTE TRENDING FOR THIS SYSTEM: <___>

5) DDC HW ID FOR DEVICE CONTAINING EVENT ENROLLMENT OBJECT FOR REMOTE ALARMING FOR THIS SYSTEM: <___>

O2 AND H2 SENSORS ALARMING PRIMARY POINT INFORMATION NETWORK DATA

EXCHANGE OVERRIDES

TREND OBJECT

LOCATION (L OR R),

TYPE AND INSTANCE

NUMBER

(PROVIDE DDC ID FOR

REMOTE IN NOTES)

ALARM INFORMATION

CONFIGURATION

INFORMATION

FUNCTION NAME DESCRIPTION DDC

HARDWARE ID

SETTING

(WITH UNITS)

RANGE

(WITH UNITS)

IO

TYPE HOA REQ'D CONFIG.

TYPE

M&C VIEW

AND OVRD

LDP VIEW

AND OVRD TREND REQ'D ALARM CONDITION ALARM

PRIORITY

M&C

ROUTING

OBJECT TYPE AND INSTANCE

NUMBER

(AND PROPERTY ID)

DATA

FROM DATA TO

OBJECT TYPE &

INSTANCE NUMBER OR

COMMANDABLE

ALARM TYPE

(PROVIDE DDC ID FOR

REMOTE IN NOTES)

NOTIFICATION CLASS

OBJECT INSTANCE

NUMBER

EVENT ENROLLMENT

OBJECT INSTANCE

NUMBER

OTHER POINTS

ZN-O2 ZONE O2

<___> <___> AI V V X ZONE O2 EXCEEDS ZONE O2 MAXIMUM CRIT [__] <___> <___> <___> <___> <___> <___> <___> <___> <___>

ZN-O2-MAX ZONE O2 MAXIMUM

<___> [XX PPM] C VO V [~] <___> <___> <___> <___> <___> <___>

ZN-H2 ZONE H2

<___> <___> AI V V X ZONE H2 EXCEEDS ZONE H2 MAXIMUM CRIT [__] <___> <___> <___> <___> <___> <___> <___> <___> <___>

ZN-H2-MAX ZONE H2 MAXIMUM

<___> [XX PPM] C VO V [~] <___> <___> <___> <___> <___> <___>

Notes:

1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS INDICATED IN THE SPECIFICATION AND IN ACCORDANCE WITH THE POINTS SCHEDULE INSTRUCTIONS DRAWING.

2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.

3) UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A HEATING/COOLING REQUEST TO THE BOILER, HEAT EXCHANGER, AND/OR CHILLER SERVING THIS SYSTEM.

4) DDC HW ID FOR DEVICE CONTAINING TREND OBJECT FOR REMOTE TRENDING FOR THIS SYSTEM: <_____>

5) DDC HW ID FOR DEVICE CONTAINING EVENT ENROLLMENT OBJECT FOR REMOTE ALARMING FOR THIS SYSTEM: <_____>

3 F

OU

NT

AI

NS

P

AR

KW

AY

SU

IT

E

FA

IR

VI

EW

H

EI

GH

TS

, I

L

8-

8.6

.70

W

OO

LP

ER

T, In c.

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

FI

LE

N

AM

E:

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

U S

A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

C H

EC

KE

D B

Y:

US Army Corps of Engineers ®

IS

O

A

A

D R

AW

IN

G C

O D

E:

B

C

D

E

F

G

1 2 3 4 5 6

SHEET ID

Japan District

7 8 9 10

H

J

K

L

M

N

P

Q

R

11 12 13 14 15 16 17 18 19 20 21

W

2H V1

9D

A.

D

ET

ME

R

N.

V

AL

DE

Z

R.

K

NO

LL

E

M.

B

EH

RM

AN

N

M-710

M

IS

C

EL

LA

N

EO

U

S C

O N

TR

O

L

PO

IN

TS

L

IS

TS

C O

M

FL

EA

C

T O

KI

N

AW

A

JA

K

AD

EN

A

AF

B, O

KI

N

AW

A, J

AP

AN

P5

A

IR

C

R

AF

T

IN

TE

R

M

ED

IA

TE

M

AI

N

TE

N

AN

C E

FA

C

IL

IT

Y

W

2H V1

9D

JA

PA

N D

IS

TR

IC

T

U ni t 3

AP

O A

P

4-

JU

LY

W

2H V1

9D

_ M

-7

D

ES

IG

N

S U

BM

IT

TA

L

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

OS

D

OS

PC

J

PB

R

P

EQUIPMENT NOTES:

1. PROVIDE 100 mm HIGH, SMOOTH FINISH CONCRETE HOUSEKEEPING PADS

UNDER ALL TRANSFORMERS (45KVA AND LARGER) AND MAIN DISTRIBUTION

SWITCHBOARDS. PAD SHALL BE 4" LARGER THAN TRANSFORMER AND

SWITCHBOARD IN EACH DIRECTION. USE 3000 PSIG, 28 DAY COMPRESSIVE

STRENGTH CONCRETE. CHAMFER ALL EDGES AND CORNERS OF

CONCRETE PAD. TRANSFORMERS TO BE A MINIMUM OF 6" FROM WALLS.

VERIFY PLACEMENT REQUIREMENTS OF TRANSFORMER WITH

MANUFACTURER PROVIDED.

2. PROVIDE A 6" THICK STRUCTURAL SUPPORT PAD UNDER EACH GRADE

MOUNTED TRANSFORMER. PAD SHALL BE 150 mm LARGER THAN

EQUIPMENT IN EACH DIRECTION. USE 3000 PSIG, 28 DAY COMPRESSIVE

STRENGTH CONCRETE. INSTALL 6X6XW2.9XW2.9 WWF. ROUND ALL EDGES

AND CORNERS OF CONCRETE PAD. SET PAD ON 100 mm OF CLEAN 19 mm

MINUS. PROVIDE FABRIC BARRIER BETWEEN SOIL AND ROCK. PROVIDE

CONDUIT OPENINGS PER TRANSFORMER MANUFACTURER.

TRANSFORMERS TO BE A MINIMUM OF 1.8 m FROM EXTERIOR WALLS.

VERIFY PLACEMENT REQUIREMENTS OF TRANSFORMER WITH

MANUFACTURER PROVIDED.

1P 1 POLE (2P, 3P, 4P, ETC.)

A AMPERE

AC AIR CONDITIONER

AF AMP FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT

INTERRUPTER

AHU AIR HANDLING UNIT

AL ALUMINUM

APPX APPROXIMATELY

ARCH ARCHITECT,

ARCHITECTURAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER

SWITCH

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BLDG BUILDING

BMS BUILDING MANAGEMENT

SYSTEM

C CONDUIT

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT

TELEVISION

CKT CIRCUIT

CLG CEILING

CP CIRCULATING PUMP

CT CURRENT TRANSFORMER

CTR CENTER

CU COPPER

DET DETAIL

DISC DISCONNECT

DIST DISTRIBUTION

DS DISCONNECT SWITCH

DT DOUBLE THROW

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

ELEV ELEVATOR

EM EMERGENCY

EMT ELECTRICAL METALLIC

TUBING

EWC ELECTRIC WATER COOLER

FA FIRE ALARM

FACP FIRE ALARM CONTROL

PANEL

FCU FAN COIL UNIT

FLR FLOOR

GA GAUGE

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT

INTERRUPTER

GND GROUND

GPR GENERAL PURPOSE

RECEPTACLE

GRS GALVANIZED RIGID STEEL

(CONDUIT)

HP HORSEPOWER

HT HEIGHT

HWB HOT WATER BOILER

HWP HOT WATER PUMP

IG ISOLATED GROUND

LTG LIGHTING

LV LOW VOLTAGE

MC MECHANICAL CONTRACTOR

MCA MINIMUM CIRCUIT

AMPACITY

MCB MAIN CIRCUIT BREAKER

MDP MAIN DISTRIBUTION PANEL

MH MANHOLE

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MSB MAIN SWITCHBOARD

MTS…