P01 Section262921-ENCLOSED SWITCHES AND CIRCUIT BREAKERS-Electrical Switchgear Replacement Phase 1.docx

DOCX document 27 KB Posted

Attached to
J061--526-23-110 Electrical Switchgear Replacement Phase 1 Federal contract opportunity
Solicitation number
36C24224B0031
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

This document is a technical specification for Enclosed Switches and Circuit Breakers, part of the Electrical Switchgear Replacement Phase 1 project. The specification covers the requirements for fused and unfused disconnect switches, and separately-enclosed circuit breakers rated 600V and below, including product features, quality assurance, submittals, and installation requirements.

The related federal contract opportunity is Solicitation Number 36C24224B0031, issued by the Department of Veterans Affairs, for the Electrical Switchgear Replacement Phase 1 project. The specification is attached to the solicitation, which describes the overall project. The solicitation does not provide additional details on the products or services required, response dates, award information, pricing terms, or set asides.

View the file

Other files for this federal contract opportunity

Other files attached to J061--526-23-110 Electrical Switchgear Replacement Phase 1, newest first.
File Type Posted
36C24224B0031 0003.docx DOCX document
VA-BRONX-SINGLE-LINE-Electrical Switchgear Replacement Phase 1.pdf PDF
REVISED VA-BRONX-SOW-Electrical Switchgear Replacement Phase 1-rev1.docx DOCX document
S06 IFB 36C24224B0031 Electrical Switchgear Pre-bid walkthrough Sign in Sheet 4-11-2024.pdf PDF
S05 RFI Answers -Electrical Switchgear Replacement 36C24224B0031.pdf PDF
36C24224B0031 0002.docx DOCX document
Arc-Flash_Report_-_-SEPT-15-2021.pdf PDF
S06 Brand Name or Equal Product Salient characteristics - Electrical Switchgear Replacement Phase 1.pdf PDF
36C24224B0031 0001.docx DOCX document
P01 GENERAL REQUIREMENTS-010000-Electrical Switchgear Replacement Phase 1.docx DOCX document
852.219-75 VA NOTICE OF LIMITATIONS ON SUBCONTRACTING-CERTIFICATE OF COMPLIANCE FOR SERVICES AND CONSTRUCTION (DEVIATION).pdf PDF
FAR 52.225-2 BUY AMERICAN CERTIFICATE.docx DOCX document
P07 Wage Determination Electrical Switchgear replacement.pdf PDF
P01 QC-SECTION 01 45 00-Electrical Switchgear Replacement Phase 1.docx DOCX document
P01 SECTION 26 05 11-REQ FOR ELECTR INSTALL -Electrical Switchgear Replacement Phase 1.docx DOCX document
36C24224B0031_1.docx DOCX document
P01 Safety REQUIREMENTS -SECTION 01 35 26-Electrical Switchgear Replacement Phase 1.docx DOCX document
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

11-01-22

SECTION 26 29 21

ENCLOSED SWITCHES AND CIRCUIT BREAKERS

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section specifies the furnishing, installation, and connection of fused and unfused disconnect switches (indicated as switches in this section), and separately-enclosed circuit breakers for use in electrical systems rated 600 V and below.

1.2 qualITY ASSURANCE A. Quality Assurance shall be in accordance with Paragraph, QUALIFICATIONS (PRODUCTS AND SERVICES) in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS.

1.3 SUBMITTALS

A.Submit in accordance with Paragraph, SUBMITTALS in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, and the following requirements:
1.Shop Drawings:
a.Submit sufficient information to demonstrate compliance with drawings and specifications.
b.Submit the following data for approval:
1)Electrical ratings, dimensions, mounting details, materials, required clearances, terminations, weight, fuses, circuit breakers, wiring and connection diagrams, accessories, and device nameplate data.
c.Certification from the manufacturer that representative enclosed switches and circuit breakers have been seismically tested to International Building Code requirements. Certification shall be based upon simulated seismic forces on a shake table or by analytical methods, but not by experience data or other methods.
2.Manuals:
a.Submit complete maintenance and operating manuals including technical data sheets, wiring diagrams, and information for ordering fuses, circuit breakers, and replacement parts.
1)Include schematic diagrams, with all terminals identified, matching terminal identification in the enclosed switches and circuit breakers.
2)Include information for testing, repair, troubleshooting, assembly, and disassembly.
b.If changes have been made to the maintenance and operating manuals originally submitted, submit updated maintenance and operating manuals two weeks prior to the final inspection.
3.Certifications: Two weeks prior to final inspection, submit the following.
a.Certification by the manufacturer that the enclosed switches and circuit breakers conform to the requirements of the drawings and specifications.
b.Certification by the Contractor that the enclosed switches and circuit breakers have been properly installed, adjusted, and tested.

1.4 APPLICABLE PUBLICATIONS

A.Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only.
B.International Code Council (ICC):
IBC-21International Building Code
C.National Electrical Manufacturers Association (NEMA):
FU l-12Low Voltage Cartridge Fuses
KS l-13Heavy Duty Enclosed and Dead-Front Switches (600 Volts Maximum)
D.National Fire Protection Association (NFPA):
70-23National Electrical Code (NEC)
E.Underwriters Laboratories, Inc. (UL):
98-16Enclosed and Dead-Front Switches
248 1-11Low Voltage Fuses
489-16Molded Case Circuit Breakers and Circuit Breaker Enclosures

PART 2 - PRODUCTS

2.1 FUSed SWITCHES RATED 600 AMPERES AND LESS

A.Switches shall be in accordance with NEMA, NEC, UL, as specified, and as shown on the drawings.
B.Shall be NEMA classified General Duty (GD) for 240 V switches, and NEMA classified Heavy Duty (HD) for 480 V switches.
C.Shall be horsepower (HP) rated.
D.Shall have the following features:
1.Switch mechanism shall be the quick-make, quick-break type.
2.Copper blades, visible in the open position.
3.An arc chute for each pole.
4.External operating handle shall indicate open and closed positions and have lockopen padlocking provisions.
5.Mechanical interlock shall permit opening of the door only when the switch is in the open position, defeatable to permit inspection.
6.Fuse holders for the sizes and types of fuses specified.
7.Solid neutral for each switch being installed in a circuit which includes a neutral conductor.
8.Ground lugs for each ground conductor.
9.Enclosures:
a.Shall be the NEMA types shown on the drawings.
b.Where the types of switch enclosures are not shown, they shall be the NEMA types most suitable for the ambient environmental conditions.
c.Shall be finished with manufacturer’s standard gray baked enamel paint over pretreated steel.
10.Electrically operated switches shall only be installed where shown on the drawings.

2.2 UNFUSED SWITCHES RATED 600 AMPERES AND LESS

A. Shall be the same as fused switches, but without provisions for fuses.

2.3 FUSed SWITCHES RATED OVER 600 AMPERES TO 1200 AMPERES

A. Shall be the same as fused switches and shall be NEMA classified Heavy Duty (HD).

2.4 MOTOR RATED TOGGLE SWITCHES

A.Type 1, general purpose for single-phase motors rated up to 1 horsepower.
B.Quick-make, quick-break toggle switch with external reset button and thermal overload protection matched to nameplate full-load current of actual protected motor.

PART 3 - EXECUTION

3.1 INSTALLATION

A.Installation shall be in accordance with the NEC, as shown on the drawings, and manufacturer’s instructions.
B.In seismic areas, enclosed switches and circuit breakers shall be adequately anchored and braced per details on structural contract drawings to withstand the seismic forces at the location where installed.
C.Fused switches shall be furnished complete with fuses. Arrange fuses such that rating information is readable without removing the fuses.

3.2 Acceptance Checks and Tests

A.Perform in accordance with the manufacturer's recommendations. In addition, include the following:
1.Visual Inspection and Tests:
a.Compare equipment nameplate data with specifications and approved shop drawings.
b.Inspect physical, electrical, and mechanical condition.
c.Verify tightness of accessible bolted electrical connections by calibrated torque-wrench method.
d.Vacuum-clean enclosure interior. Clean enclosure exterior.

3.3 SPARE PARTS

A. Two weeks prior to the final inspection, furnish one complete set of spare fuses for each fused disconnect switch installed on the project. Deliver the spare fuses to the COR.

---END---