S06 Brand Name or Equal Product Salient characteristics - Electrical Switchgear Replacement Phase 1.pdf

PDF 143 KB Posted

Attached to
J061--526-23-110 Electrical Switchgear Replacement Phase 1 Federal contract opportunity
Solicitation number
36C24224B0031
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

This document is a list of brand name or equal equipment and salient characteristics for the Electrical Switchgear Replacement Phase 1 project at the James J. Peters VA Medical Center in the Bronx, NY. The key details are:

The document identifies three specific types of Federal Pacific and Federal Pioneer 480V circuit breakers that require direct replacement: 50HL-2 (1600A frame) and 25HL-2 (800A frame) for switchgear MSS1 and MSS2, as well as an optional 3000A Federal Pacific FD75 circuit breaker. The only manufacturer currently producing direct replacement circuit breakers designed to properly and safely fit the existing Federal Pioneer switchgear compartments is Schneider Electric, through their Masterpact MTZ product line. All characteristics are provided for reference, and the VA will consider similar substitutions that meet the project intent and do not violate any standards. This document is related to Solicitation #36C24224B0031 for the J061--526-23-110 Electrical Switchgear Replacement Phase 1 project being procured by the Department of Veterans Affairs.

View the file

Other files for this federal contract opportunity

Other files attached to J061--526-23-110 Electrical Switchgear Replacement Phase 1, newest first.
File Type Posted
36C24224B0031 0003.docx DOCX document
VA-BRONX-SINGLE-LINE-Electrical Switchgear Replacement Phase 1.pdf PDF
REVISED VA-BRONX-SOW-Electrical Switchgear Replacement Phase 1-rev1.docx DOCX document
Arc-Flash_Report_-_-SEPT-15-2021.pdf PDF
36C24224B0031 0002.docx DOCX document
S06 IFB 36C24224B0031 Electrical Switchgear Pre-bid walkthrough Sign in Sheet 4-11-2024.pdf PDF
S05 RFI Answers -Electrical Switchgear Replacement 36C24224B0031.pdf PDF
36C24224B0031 0001.docx DOCX document
P01 GENERAL REQUIREMENTS-010000-Electrical Switchgear Replacement Phase 1.docx DOCX document
852.219-75 VA NOTICE OF LIMITATIONS ON SUBCONTRACTING-CERTIFICATE OF COMPLIANCE FOR SERVICES AND CONSTRUCTION (DEVIATION).pdf PDF
FAR 52.225-2 BUY AMERICAN CERTIFICATE.docx DOCX document
P01 Safety REQUIREMENTS -SECTION 01 35 26-Electrical Switchgear Replacement Phase 1.docx DOCX document
P01 QC-SECTION 01 45 00-Electrical Switchgear Replacement Phase 1.docx DOCX document
P01 SECTION 26 05 11-REQ FOR ELECTR INSTALL -Electrical Switchgear Replacement Phase 1.docx DOCX document
36C24224B0031_1.docx DOCX document
P01 Section262921-ENCLOSED SWITCHES AND CIRCUIT BREAKERS-Electrical Switchgear Replacement Phase 1.docx DOCX document
P07 Wage Determination Electrical Switchgear replacement.pdf PDF
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LIST OF BRAND NAME OR EQUAL EQUIPMENT

MAKE, MODEL AND SALIENT CHARACTERISTICS

REFERENCE:

VA Project # 526-23-110 James J. Peters VA Medical Center the Bronx, NY Electrical Switchgear Replacement Phase 1

ITEM:

Direct Replacement Circuit Breakers for the following devices:

1) Federal Pacific and Federal Pioneer 480 Volt Circuit Breakers 50HL-2 (1600A Frame) within MSS1 and MSS2.

2) Federal Pacific and Federal Pioneer 480 Volt Circuit Breakers 25HL-2 (800A Frame) within MSS1 and MSS2.

3) OPTIONAL ADDITIONAL ITEM: Federal Pacific FD75, 3000 Ampere Circuit Breaker.

VENDOR:

Formerly Federal Pacific and all Patents / Manufacturing purchased by Schneider Electric.

MODEL:

Direct replacement circuit breakers for the above listed Items:

Federal Pacific and Federal Pioneer 480 Volt Circuit Breakers 50HL-2 (1600A Frame) within MSS1 and

MSS2.

Federal Pacific and Federal Pioneer 480 Volt Circuit Breakers 25HL-2 (800A Frame) within MSS1 and

MSS2.

OPTIONAL ADDITIONAL ITEM: Federal Pacific FD75, 3000 Ampere Circuit Breaker.

SALIENT CHARACTERISTICS:

The direct replacement circuit breakers MUST be designed to be installed into the existing Federal Pioneer Switchgear Compartments. This requires the alignment of the primary incoming power electrical “stab” connections, the alignment of the secondary outgoing power electrical “stab” connections, the alignment of the inserting side mechanisms and rails, the alignment of the safety interlocks.

Industry research indicated that the only company currently manufacturing a direct replacement circuit breaker, which would properly and safely be installed into the existing Federal Pioneer Switchgear Compartments was Schneider Electric, by applying their Masterpact MTZ new circuit breaker into a customized structure, which is designed to fit exactly into the existing Federal Pioneer circuit breaker compartments.

All characteristics are for reference purposes only and the VA will consider similar substitutions provided the intent of this project is still met and no federal, state or VA standards are violated.