S06 Brand Name or Equal Product Salient characteristics - Electrical Switchgear Replacement Phase 1.pdf
PDF 143 KB Posted
- Attached to
- J061--526-23-110 Electrical Switchgear Replacement Phase 1 Federal contract opportunity
- Solicitation number
- 36C24224B0031
About this file
This document is a list of brand name or equal equipment and salient characteristics for the Electrical Switchgear Replacement Phase 1 project at the James J. Peters VA Medical Center in the Bronx, NY. The key details are:
The document identifies three specific types of Federal Pacific and Federal Pioneer 480V circuit breakers that require direct replacement: 50HL-2 (1600A frame) and 25HL-2 (800A frame) for switchgear MSS1 and MSS2, as well as an optional 3000A Federal Pacific FD75 circuit breaker. The only manufacturer currently producing direct replacement circuit breakers designed to properly and safely fit the existing Federal Pioneer switchgear compartments is Schneider Electric, through their Masterpact MTZ product line. All characteristics are provided for reference, and the VA will consider similar substitutions that meet the project intent and do not violate any standards. This document is related to Solicitation #36C24224B0031 for the J061--526-23-110 Electrical Switchgear Replacement Phase 1 project being procured by the Department of Veterans Affairs.
View the file
Other files for this federal contract opportunity
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LIST OF BRAND NAME OR EQUAL EQUIPMENT
MAKE, MODEL AND SALIENT CHARACTERISTICS
REFERENCE:
VA Project # 526-23-110 James J. Peters VA Medical Center the Bronx, NY Electrical Switchgear Replacement Phase 1
ITEM:
Direct Replacement Circuit Breakers for the following devices:
1) Federal Pacific and Federal Pioneer 480 Volt Circuit Breakers 50HL-2 (1600A Frame) within MSS1 and MSS2.
2) Federal Pacific and Federal Pioneer 480 Volt Circuit Breakers 25HL-2 (800A Frame) within MSS1 and MSS2.
3) OPTIONAL ADDITIONAL ITEM: Federal Pacific FD75, 3000 Ampere Circuit Breaker.
VENDOR:
Formerly Federal Pacific and all Patents / Manufacturing purchased by Schneider Electric.
MODEL:
Direct replacement circuit breakers for the above listed Items:
Federal Pacific and Federal Pioneer 480 Volt Circuit Breakers 50HL-2 (1600A Frame) within MSS1 and
MSS2.
Federal Pacific and Federal Pioneer 480 Volt Circuit Breakers 25HL-2 (800A Frame) within MSS1 and
MSS2.
OPTIONAL ADDITIONAL ITEM: Federal Pacific FD75, 3000 Ampere Circuit Breaker.
SALIENT CHARACTERISTICS:
The direct replacement circuit breakers MUST be designed to be installed into the existing Federal Pioneer Switchgear Compartments. This requires the alignment of the primary incoming power electrical “stab” connections, the alignment of the secondary outgoing power electrical “stab” connections, the alignment of the inserting side mechanisms and rails, the alignment of the safety interlocks.
Industry research indicated that the only company currently manufacturing a direct replacement circuit breaker, which would properly and safely be installed into the existing Federal Pioneer Switchgear Compartments was Schneider Electric, by applying their Masterpact MTZ new circuit breaker into a customized structure, which is designed to fit exactly into the existing Federal Pioneer circuit breaker compartments.
All characteristics are for reference purposes only and the VA will consider similar substitutions provided the intent of this project is still met and no federal, state or VA standards are violated.
BIDDING ON:
MANUFACTURER
NAME:
BRAND:
NO.:
File details come from the government source that posted it. Updated .