P01- Final DRAWINGS-20240522 589A5-22-122-RelocateOIT Final .pdf

PDF 8 MB Posted

Attached to
Y1DA--589A5-22-122 RELOCATE OIT FROM 6TH FL TO BLDG 21 ME (VA-26-00061111)
Solicitation number
36C25526R0150
Issued by

About this file

This document is a comprehensive set of Construction Documents for a federal renovation project at the Topeka Veterans Affairs Medical Center in Kansas. The project, identified as 589A5-22-122, involves relocating the Office of Information Technology (OIT) off Building 1's 6th floor and renovating the vacated space on the ground floor of Building 21. The construction documents were issued on May 22, 2024, and include architectural, mechanical, electrical, fire protection, and life safety plans prepared by Alesia Architecture P.C. in collaboration with multiple engineering consultants including Shaffer, Stevens & Schaap (mechanical/plumbing), Specialized Engineering Solutions, and Incandescence Life Safety, Inc.

The project scope encompasses selective and blanket demolition of existing systems, installation of new HVAC equipment including fan coil units and diffusers, complete electrical system upgrades with new lighting controls and power distribution, fire alarm system replacement with an addressable system, fire suppression modifications to the existing sprinkler system, and comprehensive interior renovation including new partitions, doors, finishes, and signage. The work area totals approximately 12,080 square feet, with 6,687 square feet (55%) designated for modification work and 5,392 square feet (45%) remaining out of scope. The renovation includes new office spaces for OIT staff with workstations, storage areas, restrooms, and corridors, all designed to maintain continuous operation of existing building utilities. The documents specify compliance with 2021 International Building Code standards, NFPA codes for fire and life safety systems, VA Fire Protection Design Manual requirements, and ADA accessibility standards. Multiple bid deduct alternates are identified, including removal of specific doors and security fence from scope. All construction must coordinate with existing building systems while maintaining essential services, with a minimum 15-day notice requirement for any utility shutdowns.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RICHARD

JOSEPH

ONKEN

A-5125

A

R C H I T E C

T

S T

A T

E

O F N E B

R A

S K

A

05/22/2024

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

PARTIALLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CONSTRUCTION

DOCUMENTS

RELOCATE OIT OFF BLDG 1

6TH FLOOR RENOVATION

589A5-22-122

TOPEKA, KS

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Incandescence Life Safety, Inc.

3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010 RJO IJM05/22/2024

A u to d e s k D o c s

/1

A -1

-1

R e lo c a te O

IT

O ff B ld g th F lo o r a n d R e n o v a te

S p a c e

/5

A

-1

-1

.B

.A rc h

R

-R e lo c a te O

IT

.r v t

/2

/2

:2

:0

P

M

GI001

COVER SHEET

TOPEKA VETERANS AFFAIRS

MEDICAL CENTER

R el oc at e O

IT

O ff B ld g

6t h F lo or a nd

R en ov at e S pa ce

C on st ru ct io n

D oc um en ts

5/

/2

Relocate OIT Off Bldg 1 6th Floor and Renovate Space 2200 SW Gage Blvd, Topeka, KS 66622

Mark Revisions: Date:

RICHARD

JOSEPH

ONKEN

A-5125

A

R C H I T E C

T

S T

A T

E

O F N E B

R A

S K

A

05/22/2024

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

PARTIALLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CONSTRUCTION

DOCUMENTS

RELOCATE OIT OFF BLDG 1

6TH FLOOR RENOVATION

589A5-22-122

TOPEKA, KS

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Incandescence Life Safety, Inc.

3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010 RJO IJM05/22/2024

A u to d e s k D o c s

/1

A -1

-1

R e lo c a te O

IT

O ff B ld g th F lo o r a n d R e n o v a te

S p a c e

/5

A

-1

-1

.B

.A rc h

R

-R e lo c a te O

IT

.r v t

/2

/2

:2

:0

P

M

GI002

INDEX OF DRAWINGS

Index of Drawings

GENERAL INFORMATION

GI001 COVER SHEET

GI002 INDEX OF DRAWINGS

GI004 BUILDING AND LIFE SAFETY CODE ANALYSIS

GI005 LIFE SAFETY PLAN

LIFE SAFETY

FP100 FIRE SUPRESSION SCOPE PLAN

FD101 FIRE ALARM SYSTEM DEMO PLAN

FA100 FIRE ALARM SYSTEM PLAN

FA500 FIRE ALARM SYSTEM DETAILS

HAZARDOUS MATERIAL

HA101 BUILDING 21 FIRST FLOOR - HAZARDOUS MATERIALS - ASBESTOS

AE802 PARTITION AND TRANSITION DETAILS

AE902 FENCE ELEVATIONS AND DETAILS

AE905 INTERIOR ELEVATIONS

INTERIOR DESIGN

MECHANICAL

M000 MECHANICAL SYMBOLS AND ABBREVIATIONS

M101 FIRST FLOOR PLAN - MECHANICAL DEMOLITION

M201 FIRST FLOOR PLAN - MECHANICAL

ARCHITECTURAL

ELECTRICAL

E000 ELECTRICAL SYMBOLS AND ABBREVIATIONS

E101 FIRST FLOOR PLAN - ELECTRICAL DEMOLITION

EL201 FIRST FLOOR PLAN - LIGHTING

EP201 FIRST FLOOR PLAN - POWER & LOW VOLTAGE

E700 ELECTRICAL SCHEDULES

E800 PANEL SCHEDULES

AG001 ARCHITECTURAL ABBREVIATIONS, LEGENDS AND NOTES

AD101 BUILDING 21 - GROUND FLOOR- DEMOLITION PLAN

AE101 BUILDING 21 GROUND FLOOR PLAN

AC101 BUILDING 21 - GROUND FLOOR REFLECTED CEILING PLAN

AE401 LOBBY SECTIONS AND DETAILS

AE701 DOOR AND FRAME TYPES, DETAILS AND DOOR SCHEDULE

AE801 PARTITION TYPES

IN601 ROOM FINISH SCHEDULE AND DETAILS

IN101 GROUND FLOOR - INTERIOR FLOOR FINISH PLAN

QH101 GROUND FLOOR - EQUIPMENT PLAN

1. THE CONTRACTOR SHALL INSPECT THE SITE, STUDY EXISTING CONDITIONS, REVIEW DRAWINGS AND SPECIFICATIONS.

CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE THE GOVT..

2. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR THE WORK AND BE RESPONSIBLE FOR SAME. COORDINATE THE WORK AND SHOP DRAWINGS WITH ALL OTHER TRADES AFFECTED AND MAKE ANY NECESSARY OFFSETS TO CONCEAL PIPING AND DUCTWORK AND TO CLEAR EQUIPMENT, STRUCTURAL MEMBERS AND OTHER OBSTRUCTIONS.

3. ALL UTILITIES AND SERVICES OTHER THAN IT CLOSETS SHALL BE KEPT IN CONTINUOUS OPERATION UNLESS WRITTEN PERMISSION IS OTHERWISE GRANTED BY THE THE GOVT..

CONTRACTOR MUST CONTACT VA'S COR PRIOR TO ANY SHUTDOWNS. CONTRACTOR MUST COORDINATE UTILITY SHUTDOWN AND ACCESS TO IT CLOSETS. ALLOW A MINIMUM OF 15 DAYS' NOTICE FROM THE DATE AN ACCEPTABLE SHUTDOWN DATE HAS BEEN APPROVED BY THE VA.

4. ALL MATERIALS AND EQUIPMENT SHALL BE NEW, OF THE BEST QUALITY AND FREE FROM DEFECTS.

5. MANUFACTURER AND MODEL NUMBERS SPECIFIED ESTABLISH THE TYPE AND QUALITY REQUIRED, UNLESS OTHERWISE NOTED.

6. ALL WORK SHALL COMPLY WITH APPLICABLE REGULATIONS, CODES AND ORDINANCES.

7. THE CONTRACTOR SHALL PERFORM ALL TESTS AS SPECIFIED OR AS NECESSARY TO DEMONSTRATE A COMPLETE AND SATISFACTORY INSTALLATION.

8. INSTALL THE SPECIFIED FIRE STOPPING (SLEEVES, WRAP, CONDUIT, ETC.) AT RATED CONSTRUCTION (NEW OR EXISTING) OR SMOKE PARTITIONS:

A. REPLACE FIRE STOP AT ALL PENETRATIONS WHERE NEW DEVICES/LINES USE EXISTING PENETRATIONS OF RATED BARRIERS.

B. REPLACE FIRE STOP AT ALL EXISTING PENETRATIONS OF RATED BARRIERS WHERE EXISTING LINES HAVE BEEN MODIFIED OR RELOCATED.

C. FIRE STOP ALL NEWLY CREATED PENETRATIONS WHERE NEW DEVICES/LINES PENETRATE EXISTING FLOORS, CEILINGS AND OTHER RATED BARRIERS.

D. FIRE STOP ALL NEW PENETRATIONS WHERE NEW DEVICES/LINES PENETRATE THROUGH NEWLY CONSTRUCTED RATED BARRIERS OR SMOKE PARTITIONS.

E. USE ONLY APPROVED FIRE CAULKING AND FIRE STOPS (SEE SPECIFICATIONS).

9. ALL METAL STUD AND GYPSUM WALLBOARD PARTITIONS ARE DIMENSIONED TO THE OUTSIDE FINISH FACE OF WALL AND TO THE COLUMN GRID UNLESS OTHERWISE NOTED.

10. ALL GYPSUM BOARD SHALL BE TYPE 'X' FIRE CODE GYPSUM BOARD AND SHALL BE MOLD AND MOISTURE RESISTANT.

11. PROVIDE WOOD BLOCKING OR 16 GA. SHEET METAL BACKING PLATES IN ALL WALLS TO RECEIVE WALL HUNG ACCESSORIES, SUCH AS EQUIPMENT, GRAB BARS, MILLWORK, COAT

HOOKS, AND DOOR STOPS, ETC. IF WOOD BLOCKING IS USED, PROVIDE AS FIRE-RESISTANT.

12. THE CONTRACTOR SHALL WORK WITH THE CONDITIONS AS THEY EXIST AT THE SITE. ALL ABOVE CEILING CONDITIONS SHALL BE REVIEWED, AND MODIFICATIONS IDENTIFIED, COORDINATED, AND INCORPORATED INTO THE SHOP DRAWING PROCESS. COORDINATE ALL ABOVE CEILING WORK TO ENSURE A COMPLETE AND OPERATIONAL SYSTEM AT NO ADDITIONAL COST TO THE GOVT.. COORDINATION SHALL INCLUDE, BUT NOT BE LIMITED TO THE FOLLOWING:

A. THE GOVT.'S EQUIPMENT REQUIREMENTS.

B. THE CEILING SUPPORT SYSTEM.

C. THE MECHANICAL DUCTWORK SYSTEM.

D. THE LIGHTING FIXTURES.

E. ELECTRICAL WIRING AND CONDUIT SYSTEMS.

F. THE PLUMBING AND PIPING SYSTEMS.

G. FIRE PROTECTION SYSTEMS

H. THE COMMUNICATIONS AND SPECIAL SYSTEMS.

13. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR SHALL NOT BE ALLOWED EXTRA

COSTS DUE TO FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.

14. ALL NEW STUD WALLS AND GYPSUM BOARD SHALL EXTEND TO STRUCTURE UNLESS NOTED OTHERWISE.

15. WHEN WALL PARTITIONS OF DIFFERENT FIRE RATING INTERSECT, THE HIGHEST RATED PARTITION TAKES PRECEDENT. MAINTAIN RATING BEHIND RECESSED AREAS IN WALLS.

16. ALL CORRIDOR WALLS ARE REQUIRED TO BE SMOKE TIGHT, WHETHER THEY ARE FIRE RATED OR NOT. REPAIR AND EXTEND AT LEAST THE CORRIDOR SIDE OF NON-RATED CORRIDOR

WALLS TO STRUCTURE, UNLESS NOTED OTHERWISE, SEE WALL TYPES.

17. COORDINATE CONSTRUCTION REQUIREMENTS WITH CIVIL, STRUCTURAL, MECHANICAL, FIRE PROTECTION, PLUMBING AND ELECTRICAL DRAWINGS.

18. FURNITURE SHOWN IS N.I.C., UNLESS NOTED OTHERWISE.

19. EQUIPMENT SHALL BE PROVIDED BY THE GOVT. AND INSTALLED BY THE CONTRACTOR AS SCHEDULED, UNLESS NOTED OTHERWISE.

GENERAL ARCHITECTURAL NOTES

SEE SECTION 01 00 00 - GENERAL REQUIREMENTS FOR FULL DESCRIPTION

OF DEDUCT ALTERNATES. REFER TO DRAWINGS FOR ADDITIONAL NOTES

AND DIRECTIONS RELATED TO DEDUCT ALTERNATES.

LIST OF BID DEDUCT ALTERNATES

1. REMOVAL OF NEW DOOR FROM CONNECTING CORRIDOR TO ROOM

100 FROM SCOPE

2. REMOVAL OF NEW DOOR CONNECTING CORRIDOR CDR1 AND CDR2

FROM SCOPE

BID ITEMS & DEDUCT ALTERNATES

FRONT APPROACH, PULL SIDE FRONT APPROACH, PUSH SIDE

NOTE: X=12" MINIMUM IF DOOR HAS

BOTH A CLOSER AND LATCH

HINGE SIDE APPROACHES - SWINGING DOORS

LATCH SIDE APPROACHES - SWINGING DOORS

NOTE:

1. ALL DOORS IN ALCOVES SHALL COMPLY WITH CLEARANCES FOR FRONT APPROACHES.

HINGE APPROACH, PULL SIDE HINGE APPROACH, PUSH SIDE

LATCH APPROACH, PULL SIDE LATCH APPROACH, PUSH SIDE

NOTE: X=36" MINIMUM IF Y=60"; X=42"

MINIMUM IF Y=54".

NOTE: Y=48" MINIMUM IF DOOR HAS

BOTH A LATCH AND CLOSER.

NOTE: Y=54" MINIMUM IF DOOR HAS

CLOSER.

NOTE: Y=48" MINIMUM IF DOOR HAS

CLOSER.

FRONT APPROACHES - SWINGING DOORS

MIN.

18"

M

IN

M

IN

X

54" MIN.

M

IN

.60

X

MIN.

24"

M

IN

M

IN

MIN.

24" X X

Y

Y

Y

PULL SIDE PUSH SIDE

POCKET OR HINGE APPROACH - SLIDING BARN DOORS

POCKET OR HINGE APPROACH STOP OR LATCH APPROACH

FRONT AND SIDE APPROACHES - NO DOORS

M

IN

M

IN

24"42

M

IN

22" MIN. 42

M

IN

GENERAL SYMBOLS

A101

SIM

A101

SIM

1i

A101

SIM

D

SCALE:1 View Name 1/8" = 1'-0"

A

NTRUE

NORTH

A

B

EARTH

EARTH GRAVEL

CONCRETE

METALS

BRICK

CMU

TILE

STONE

WOOD

GYPSUM

GLASS

INSULATION

REGULAR

STEEL ALUMINUM

FACE COMMON

CMU

CERAMIC

MARBLE LIMESTONE

FINISH BLOCKING

PLASTER OR GWB

LARGE SCALE SMALL SCALE

BATT OR LOOSE RIGID

SURFACE

ACTUAL SQ. FT.

PROGRAMMED SQ. FT.

ROOM NUMBER

DOOR NUMBER

KEYNOTE

WALL TYPE

REVISION NUMBER

ELEVATION INDICATION

COLUMN GRID

IDENTIFICATION

NORTH ARROW

XXX WINDOW NUMBER

DETAIL TITLE

BUILDING SECTION

WALL SECTION

EXTERIOR/INTERIOR

ELEVATION

INTERIOR MULTI-VIEW

ELEVATION

ELEVATION NUMBER

SHEET ON WHICH

ELEVATION IS DRAWN

ELEVATION NUMBER

SHEET ON WHICH

ELEVATION IS DRAWN

MATERIALS REFERENCE

Room Name

150 PSF / 150 SF

PROPERTY CORNER

PROPERTY LINE

4" UNDERGROUND COMMUNICATION

(NO. INDICATES NO. OF DUCTS)

4" UNDERGROUND DUCT

(NO. INDICATES NO. OF DUCTS)

TELEPHONE LINE OH

UNDERGROUND ELECTRICAL

CONDUIT

OVERHEAD POWER LINE

ELECTRICAL MANHOLE

P/T = POWER & TELEPHONE

W/ STREET LIGHT

W/ DOWN GUY (NO. INDICATES LENGTH, CLASS

GUY & ANCHOR STRENGTH)

POWER POLE (NO. INDICATES LENGTH &

CLASS)

REMOVE OR ABANDON LINE

VALVE

GAS LINE

IRRIGATION WATER MAIN

FIRE WATER LINE

WATER LINE

STORM SEWER

SANITARY SEWER FORCE MAIN

SANITARY SEWER

CURB LINE

STREET CENTER LINE

BUILDING

EXISTING NEW

SITE

EXISTING NEW

S

MH CO

SFM

SS SS

MH

CLAL

Y.D.

F.H.

W

F

IRM

G

4M

P T

P T

P

UG

T

2-T

P

UG

T

2-T

POLE

4M

45-2

45-2

G

IRM

F

Y.D.

F.H.

W

AL

SS SS

MH

SFM

S

MH CO

GRID COORDINATES

SECTION LINE

CONTOURS

SPOT ELEVATIONS

DRAINAGE DITCH OR SWALE

CONCRETE PAVEMENT (SECTION)

BITUMINOUS PAVEMENT (SECTION)

CONTRACTION JOINT FOR PAVEMENT

BORINGS, TEXT

TREES, DECIDUOUS - WITH

DIAMETER

EVERGREEN - WITH HEIGHT

SHRUBS

CHAIN-LINK FENCE

BARBED WIRE FENCE

SECURITY FENCE XX XX

XX

XX XX

XX

12"

10'

HIGH

12" (TO BE REMOVED)

10' (TO BE REMOVED)

HOLE #3

90 X 10W 90 X 10 W (TOP OF WALL)

90 X 10C 90 X 10 C (TOP OF CURB)

90 X 10P 90 X 10 P (TOP OF PAVEMENT)

90 X 10 90 X 10

SEC 24

SEC 25

290 N

90 W

09 20 00.A1

A101

SIM

DETAIL SECTION

AE201

RICHARD

JOSEPH

ONKEN

A-5125

A

R C H I T E C

T

S T

A T

E

O F N E B

R A

S K

A

05/22/2024

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

PARTIALLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CONSTRUCTION

DOCUMENTS

RELOCATE OIT OFF BLDG 1

6TH FLOOR RENOVATION

589A5-22-122

TOPEKA, KS

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Incandescence Life Safety, Inc.

3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010 RJO IJM05/22/2024

A u to d e s k D o c s

/1

A -1

-1

R e lo c a te O

IT

O ff B ld g th F lo o r a n d R e n o v a te

S p a c e

/5

A

-1

-1

.B

.A rc h

R

-R e lo c a te O

IT

.r v t

/2

/2

:2

:0

P

M

AG001

ARCHITECTURAL ABBREVIATIONS,

LEGENDS AND NOTES

A

A/C AIR CONDITIONING

AB ANCHOR BOLT / AIR BLENDER

ABS ACRYLONITRILE-BUTADIENE-STYRENE

AC ALTERNATING CURRENT / AIR COMPRESSOR

ACP ASBESTOS CEMENT PIPE

ACU AIR CONDITIONING UNIT

AD AREA DRAIN

ADA AMERICANS WITH DISABILITIES ACT

ADJ ADJACENT / ADJUSTABLE

ADR ACCESS DOOR

AFF ABOVE FINISH FLOOR

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AL ALUMINUM

ALT ALTERNATE

APPROX APPROXIMATELY

APT APARTMENT

ARCH ARCHITECT(URAL)

ASPH ASPHALT

AT ACOUSTICAL PANEL CEILING

ATB AIR TERMINAL BOX

ATD AIR TRANSFER DUCT

ATU AIR TERMINAL UNIT

AUX AUXILIARY

AVG AVERAGE

AWC ACOUSTICAL WALLCOVERING

AZ AZIMUTH

B

BB BALLED AND BURLAPPED

BD BOARD

BDD BACK DRAFT DAMPER

BE BOTTOM ELEVATION

BL BUILDING LINE

BLDG BUILDING

BLKG BLOCKING

BM BENCH MARK / BEAM

BR BARE ROOT

BRG BEARING

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C

C/C CENTER TO CENTER

CAB CABINET

CB CIRCUIT BREAKER / CATCH BASIN

CC COOLING UNIT

CE COVER ELEVATION

CEM CEMENT

CFM CUBIC FEET PER MINUTE

CFS CONCRETE FLOOR SEALER

CG CORNER GUARD

CH CHILLER

CI CURB INLET / CAST IRON

CIP CAST IRON PIPE

CJ CONTROL JOINT OR CONTRACTION JOINT

CKT CIRCUIT

CL CENTER LINE

CLG CEILING

CLO CLOSET

CLR CLEAR

CM CENTIMETER

CMH CUBIC METER PER HOUR

CMP CORRUGATED METAL PIPE

CMT CERAMIC MOSAIC TILE

CMU CONCRETE MASONRY UNIT

CO CLEANOUT / CARBON MONOXIDE

CO2 CARBON DIOXIDE

COL COLUMN

COMB COMBINATION / COMBINE

COMP COMPRESSIBLE

CONC CONCRETE

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUOUS / CONTINUATION

CONTR CONTRACTOR

CORR CORRIDOR

CP CEMENT PIPE

CPT CARPET

CSF CUBIC FEET PER SECOND

CT CERAMIC TILE / COOLING TOWER

CTR CENTER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CUYD CUBIC YARD

CW COLD WATER

D

D DRAIN / DIFFUSER

DA DENTAL AIR

DBL DOUBLE

DEPR DEPRESSED

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL

DIFF DIFFUSER

DIP DUCTILE IRON PIPE

DISC DISCONNECT

DISP DISPENSER

DIST DISTRIBUTION

DK DECK

DL DEAD LOAD

DN DOWN

DO DITTO

DPR DAMPER

DR DOOR

DS DOWNSPOUT

DV DENTAL VACUUM

DWG DRAWING

DWL DOWEL

DWP DOMESTIC WATER PUMP

ABBREVIATIONS

K

KC MIL THOUSAND CIRCULAR MILS

KCJ KEYED CONSTRUCTION JOINT

KIT KITCHEN

KPA KILOPASCALS

KS KITCHEN SINK

KV KILOVOLT

KVA KILOVOLT AMPERE

KW KILOWATTS

L

L LITER

LA LABORATORY AIR

LAB LABORATORY

LAM LAMINATE

LAV LAVATORY

LBS POUNDS

LF LINEAR FEET

LIN LINEAR

LL LIVE LOAD

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LMU LIGHTWEIGHT MASONRY UNITS

LONG LONGITUDINAL

LPM LITERS PER MINUTE

LT LIGHT

LT WT LIGHT WEIGHT

LTG LIGHTING

LV LABORATORY VACUUM

LVL LEVEL

LVT LUXURY VINYL TILE

M

M METER

M2 SQUARE METER

M3 CUBIC METER

MA MEDICAL AIR

MAINT MAINTENANCE

MAR MARBLE

MAS MASONRY

MAT MATERIAL / ENTRY CARPET

MAX MAXIMUM

MBH 1000 BTUH

MDO MEDIUM DENSITY OVERLAY

MECH MECHANICAL

MET METAL

MFR MANUFACTURER

MG MOTOR GENERATOR / MEDICAL GAS

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY

MM MILLIMETER

MO MASONRY OPENING

MTD MOUNTED

MTG MOUNTING

MULL MULLION

MV MEDICAL VACUUM

N

N NITROGEN

N2O NITROUS OXIDE

NEC NATIONAL ELECTRICAL CODE

NFPA NATIONAL FIRE PROTECTION

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O

O/S OFFSET

OA OUTSIDE AIR

OBD OPPOSED BLADE DAMPER

OC ON CENTER

OD OUTSIDE DIAMETER

OF OUTSIDE FACE

OPNG OPENING

OPP OPPOSITE

OX OXYGEN

OZ OUNCE

P

P PAINT / PUMP / PENDANT

PA PASCAL

PART PARTITION

PAVT PAVEMENT

PC POINT OF CURVATURE

PCF POUNDS PER CUBIC FOOT

PED PEDESTAL

PERP PERPENDICULAR

PHC PREHEAT COIL

PHVAC PLUMBING, HEATING, VENTILATING AND AIR

CONDITIONING

PI POINT OF INTERSECTION

PIV POST INDICATOR VALVE

PKG PARKING

PL PLASTIC LAMINATE / PROPERTY LINE / PLATE

PLAS PLASTER

PLBG PLUMBING

PLF POUNDS PER LINEAR FOOT

PLYWD PLYWOOD

PNL PANEL

PR PAIR

PROJ PROJECTION

PRV PRESSURE REGULATING VALVE

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT POINT OF TANGENCY / PORCELAIN TILE

PTVC POINT OF VERTICAL CURVATURE

PVC POLYVINYL CHLORIDE

PVI POINT OF VERTICAL INTERSECTION

PVT POINT OF VERTICAL TANGENCY

Q

QT QUARRY TILE

E

E EPOXY

EA EACH / EXHAUST AIR

EF EACH FACE / EXHAUST FAN

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRIC(AL)

ELEV ELEVATOR

EMBED EMBEDMENT

EMD ESTIMATED MAXIMUM DEMAND

EMT ELECTRICAL METAL TUBING

EQ EQUAL

EQUIP EQUIPMENT

ET EXPANSION TANK

EVAC MEDICAL GAS EVACUATION

EW EACH WAY

EWC ELECTRICAL WATER COOLER

EWH ELECTRICAL WATER HEATER

EXH EXHAUST

EXIST EXISTING

EXP EXPOSED

EXPN EXPANSION

EXT EXTERIOR

F

F FIRE MAIN

FA FIRE ALARM

FCU FAN COIL UNIT

FD FLOOR DRAIN / FIRE DAMPER

FD / SD COMBINATION FIRE AND SMOKE DAMPER

FDC FIRE DEPARTMENT CONNECTION

FDN FOUNDATION

FDR FEEDER

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FH FIRE HYDRANT

FHC FIRE HOSE CABINET

FIN FINISH

FIX FIXTURE

FL FLOOR

FM FORCE MAIN / FACTORY MUTUAL

FP FIREPROOFING / FIRE PUMP

FPM FEET PER MINUTE

FR FIRE RATED

FRP FIBERGLASS REINFORCED PLASTIC

FS FLOW SWITCH

FT FEET

FTG FOOTING

FVC FIRE VALVE CABINET

G

G GAS / GRILLE

GA GAGE

GALV GALVANIZED

GB GRAB BAR

GBD GRAVITY BACKDRAFT DAMPER

GEN GENERATOR

GFRC GLASS FIBER REINFORCED CONCRETE

GI GALVANIZED IRON

GL GLASS

GLB GLASS BLOCK

GP GLAZED PAINT

GPM GALLONS PER MINUTE

GR GRADE

GRV GRAVITY ROOF VENTILATOR

GWB GYPSUM WALLBOARD

GYP GYPSUM

H

HB HOSE BIBB

HC HEATING COIL

HDNR HARDENER

HDW HARDWARE

HDWD HARDWOOD

HK1E HOOK ONE END

HK2E HOOK TWO ENDS

HM HOLLOW METAL

HORIZ HORIZONTAL

HP HORSEPOWER

HPT HIGH POINT

HR HOUR

HS HIGH STRENGTH

HT HEIGHT

HTG HEATING

HTR HEATER

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

HW HOT WATER

HWC HOT WATER CIRCULATING

HZ HERTZ

I

IA INSTRUMENT AIR

IC INTERCOM

ICB INTEGRAL COVE BASE

ID INSIDE DIAMETER

IE INVERT ELEVATION

IF INSIDE FACE

IN INCH

INSUL INSULATION

INT INTERIOR

J

JAN JANITOR

JB JUNCTION BOX

JP JOCKEY PUMP

JST JOIST

JT JOINT

R

R RADIUS / REGISTER

RA RETURN AIR

RB RESILIENT BASE

RCP REINFORCED CONCRETE PIPE

RD ROOF DRAIN

REF REFERENCE

REFL REFLECTED

REG REGISTER

REINF REINFORCED

REQD REQUIRED

REV REVERSE / REVISION

RF RETURN FAN

RGS RIGID GALVANIZED STEEL

RH ROOF HOOD / RELATIVE HUMIDITY / REHEAT

RHC REHEAT COIL

RM ROOM

RO ROUGH OPENING

ROW RIGHT OF WAY

RT RESILIENT TILE

RWC RIGID WALLCOVERING

S

S STAIR / STAIN / SURFACE / SANITARY

SA SUPPLY AIR / SOUND ATTENUATOR

SAN SANITARY

SCH SCHEDULE

SD SMOKE DAMPER / SUB DRAIN

SECT SECTION

SF SUPPLY FAN

SHT SHEET

SIM SIMILAR

SOG SLAB-ON-GRADE

SP SUMP PUMP

SPEC SPECIFICATIONS

SPF SPRAY POLYURETHANE FOAM

SQ SQUARE

SS SERVICE SINK / STORM SEWER

SSO STORM SEWER OVERFLOW

SSTL STAINLESS STEEL

ST STAIR TREAD

STA STATION

STD STANDARD

STE STANDARD TAPERED END

STIFF STIFFENER

STIR STIRRUP

STL STEEL

STOR STORAGE

STR STRUCTURAL

SUSP SUSPENDED

SW SWITCH

SWGR SWITCHGEAR

SYM SYMMETRICAL

T

T TREAD

T&B TOP AND BOTTOM

T&G TONGUE AND GROOVE

TC TOP OF CURB

TE TOP ELEVATION

TEL TELEPHONE

TEMP TEMPERATURE

TER TERRAZZO

TLT TOILET

TOPO TOPOGRAPHY

TOS TOP OF STEEL

TOW TOP OF WALL

TP TOP OF PAVEMENT

TRANS TRANSVERSE

TYP TYPICAL

U

UC UNDERCUT

UG UNDERGROUND

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

UR URINAL

UV UNIT VENTILATOR

V

V VOLT

VAV VARIABLE AIR VOLUME

VB VINYL BASE

VC VERTICAL CURVE

VCP VITRIFIED CLAY PIPE

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VFD VARIABLE FREQUENCY DRIVE

VTR VENT THROUGH ROOF

VWC VINYL WALL COVERING

W

W WATT / WATER

W/ WITH

W/O WITHOUT

WAGD WASTE ANESTHESIA GAS DISPOSAL

WC WATER CLOSET

WD WOOD

WDW WINDOW

WH WATER HEATER / WALL HYDRANT

WP WEATHERPROOF

WPFG WATERPROOFING

WS WATER STOP

WT WEIGHT

WWF WELDED WIRE FABRIC

X

XFMR TRANSFORMER

Y

YD YARD

YH YARD HYDRANT

HAZARDOUS MATERIALS

1. IF THE CONTRACTOR ENCOUNTERS MATERIAL THAT COULD BE HAZARDOUS, THE CONTRACTOR SHALL STOP WORK AND NOTIFY THE GOVERNMENT

IMMEDIATELY FOR DIRECTION.

GENERAL FIREPROFFING NOTES

1. MAINTAIN FIRE RATED CONSTRUCTION AT WALL PENETRATIONS, (CONSTRUCTION TO CONFORM TO MANUFACTURER'S FIRE RATED / TEST ASSEMBLIES.)

2. FIRE CAULK ALL SLEEVES AND PENETRATIONS AT FIRE WALLS / PARTITIONS AND FLOORS. CONFORM WITH THE TESTED / SUBMITTED FIRE RATED ASSEMBLY. USE RED FIRE CAULK AND LABEL WALL WITH U.L. DESIGN NUMBER. FIRE RATED WALLS SHOWN ON PLAN.

3. PATCH AND REPAIR ALL EXISTING FIREPROOFING ON EXISTING STRUCTURAL MEMBERS, INCLUDING THAT WHICH IS UNCOVERED NEEDING REPAIR AND

THAT WHICH IS DISTURBED DURING CONSTRUCTION.

1/4" = 1'-0"1

GUIDE FOR CLEARANCES AT DOORS

BUILDING 21

BUILDING 1

BUILDING 24

BUILDING 20

FIRE SEPARTION DISTANCE

FIRE DEPARTMENT

ACCESS ROUTE

PEDESTRIAN WALKWAY

(IBC §3104)

30'-0"

'-0

30'-0"

'-0

EXISTING FIRE

DEPARTMENT

CONNECTION

R O

A D

N

CONTINUE TO

21ST ST

EXISTING FIRE

HYDRANT

R O

A D

N

VA ACCESS ROAD

PARKING LOT

PARKING

LOT

P A

R K

IN

G

L O

T

FIRE-RESISTANCE RATING REQUIREMENTS FOR

BUILDING ELEMENTS: TYPE II-B

RATING (HOURS)BUILDING ELEMENT

0PRIMARY STRUCTURAL FRAME

NOTE

#2

0 / 2BEARING WALLS: EXTERIOR #3

0BEARING WALLS: INTERIOR -

0 / 2NONBEARING WALLS: EXTERIOR

0NONBEARING WALLS: INTERIOR -

0 FLOOR CONSTRUCTION -

0ROOF CONSTRUCTION #4

NOTES:

1. FIRE-RESISTANCE RATINGS ARE BASED OFF OF IBC TABLES 601

AND 705.5. SEE LIFE SAFETY PLANS FOR LOCATIONS OF RATED

PARTITIONS FOR ACCOMMODATION OF LIFE SAFETY CODE

REQUIREMENTS.

2. PRIMARY STRUCTURAL FRAME CONSISTS OF MEMBERS

HAVING DIRECT CONNECTION TO OTHERS DESIGNED TO

CARRY GRAVITY LOADS. SEE ARCHITECTURAL AND

STRUCTURAL SHEETS FOR SPECIFIC APPLICATION OF EACH

ASSEMBLY.

3. EXTERIOR WALL RATING REQUIREMENTS ARE BASED OFF OF

FIRE SEPARATION DISTANCE AND THE REQUIREMENTS OF IBC

TABLE 705.5.

4. RATING REQUIREMENT FOR FLOOR AND ROOF CONSTRUCTION

INCLUDES SUPPORTING BEAMS AND JOISTS.

#3

1. SITE FIRE PROTECTION FEATURES SHALL BE IN ACCORDANCE WITH VA FPDM AND NFPA 1.

2. REFERENCE GI-SERIES SHEETS FOR BUILDING AND LIFE SAFETY CODE COMPLIANCE

PLANS.

3. REFERENCE FA-SERIES SHEETS FOR FIRE ALARM PLANS.

4. REFERENCE FX-SERIES SHEETS FOR FIRE SUPPRESSION SYSTEM PLANS.

SITE FIRE PROTECTION PLAN - GENERAL NOTES

REHABILITATION CLASSIFICATION

MODIFICATION

NOT IN SCOPE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

PARTIALLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CONSTRUCTION

DOCUMENTS

RELOCATE OIT OFF BLDG 1

6TH FLOOR RENOVATION

589A5-122

TOPEKA, KS

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Incandescence Life Safety, Inc.

3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010

A u to d e s k D o c s /1

A

-1

-1

R e lo c a te

O

IT

O ff B ld g th

F lo o r a n d

R e n o v a te

S p a c e

/5

A

-1

-1

.B

.F P

L S

R

.r v t

/2

/2

:4

:3

P

M

GI004

BUILDING AND LIFE SAFETY CODE

ANALYSIS

TGD GMP05/22/24

N

1" = 50'-0"

BUILDING 21 - SITE FIRE PROTECTION PLAN

Applicable Codes & Standards

Code/Standard Code/Standard Name Code/Standard Year

INTERNATIONAL CODE COUNCIL

IBC INTERNATIONAL BUILDING CODE 2021

NATIONAL FIRE PROTECTION ASSOCIATION

NFPA 1 FIRE CODE 2021

NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS 2022

NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS 2022

NFPA 70 NATIONAL ELECTRICAL CODE 2023

NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE 2022

NFPA 80 STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES 2022

NFPA 90A STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATION SYSTEMS 2021

NFPA 101 LIFE SAFETY CODE 2021

NFPA 220 STANDARD ON TYPES OF BUILDING CONSTRUCTION 2024

U.S. DEPARTMENT OF VETERANS AFFAIRS

VAFPDM FIRE PROTECTION DESIGN MANUAL 8TH EDITION, JUNE 2021

Mark Revisions: Date:

1" = 20'-0"

BLDG 21 GROUND FLOOR REHABILITATION PLAN

REHABILITATION WORK AREA SCHEDULE

REHABILITATION

CLASSIFICATION Area

Percent Work Area

MODIFICATION 6,687 SF 55%

NOT IN SCOPE 5,392 SF 45%

12,080 SF

NTRUE

NORTH

5/22/2024

D E

-1 .0

S S

S S

S S

S S

S S

S S

S S S S S S S S S S S S S S S S S S

DOOR

3' - 4"

DOOR

3' - 4"

DOOR

3' - 4"

DOOR

4' - 8"

STAIR

3' - 8"

147 15

T D

-1 .0

TD-1.01

C P

-1 .0

FE-1

F E

-1

FE-1

FE-1 FE-2FE-1

F E

-1

T

T T

T

TD-1.03

T D

-1 .0

2a

3a

A1 B1 C1 D1

1a

FIRE

PROTECTION

109F

RESTROOM

121A

OFFICE

COM

110E

STORAGE

ELECTRICAL

111E

STORAGE

113B

WOMEN'S

RESTROOM

STORAGE

MEN'S

RESTROOM

RESTROOM

119A

STORAGE

118F

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CONFERENCE

ROOM

OFFICE

STORAGE

SHIPPING/BREAKDOWN

STORAGE

STORAGE

113A

EHRM TRAINING

CORRIDOR 1

CDR1

CLOSET

OIT OFFICE

MECHANICAL

109A

STORAGE

LOBBY

OIT SHIPPING/

BREAKDOWN

115A

OCCUPANT LOAD FACTOR USE CATEGORY

Accessory Storage Areas, Mechanical Equipment Rooms

Business Use - General

Educational Use - Classrooms

Storage Use - In Other Occupancies

CORRIDOR 2

CDR2

6'-0"

2-HOUR FIRE RESISTANCE

RATING AT EXTERIOR WALL PER

IBC §3104.5.1.1 & VA FPDM §2.2.B

CORRIDOR 2

CDR2

EHRM

109B

3'-8"

HAZARDOUS AREA SEPARTION (NFPA 101 §38.3.2)

WORK AREA BOUNDARY

LIFE SAFETY NOTES:

EXISTING SMOKE PARTITION

SYMBOL

FOR EXIT LIGHTS AND EMERGENCY LIGHTING, SEE ELECTRICAL

DRAWINGS.

FOR FIRE ALARM SYSTEM, SEE FIRE ALARM DRAWINGS.

THIS BUILDING SHALL BE FULLY SPRINKLERED, SEE FIRE

SUPPRESSION SHEETS FOR DETAILS.

AT FIRE RATED DOOR LOCATIONS FRAMES AND DOORS SHALL BE

LABELED FOR THE INTENDED USE OR EQUIVALENT.

NON-RATED SMOKE PARTITIONS SHALL BE CONSTRUCTED TO

LIMIT THE TRANSFER OF SMOKE. PARTITIONS SHALL EXTEND

FROM FLOOR SLAB TO UNDERSIDE THE FIRE RESISTANCE RATED

HORIZONTAL ASSEMBLY ABOVE (WHERE APPLICABLE). THE SPACE

ADJACENT TO THE DECK AND OTHER SURFACES, AND THE SPACES

AROUND PENETRATING ITEMS SHALL BE CAULKED TO LIMIT THE

FREE PASSAGE OF SMOKE.

ALL FIRE RATED PARTITIONS SHALL EXTEND FROM FLOOR SLAB TO

THE UNDERSIDE OF THE DECK ABOVE AS NOTED ON THE

ARCHITECTURAL DRAWINGS. THE SPACE ADJACENT TO THE DECK

AND OTHER SURFACES, AND THE SPACES AROUND PENETRATING

ITEMS SHALL BE FIRESTOPPED.

LIFE SAFETY SYMBOLS:

DESCRIPTION

EXISTING 1-HOUR FIRE BARRIER

EXISTING 2-HOUR FIRE BARRIER

OCCUPANT LOAD USE LEGEND:

Business Use - General

Mechanical, Electrical, Other Building Equipment Spaces

Storage Use - In Other Occupancies

FE-X

FIRE EXTINGUISHER LOCATION

1: 10 LB. MULTIPURPOSE DRY CHEMICAL

2: 30 LB. WET CHEMICAL

NEW SMOKE PARTITIONS S

Educational Use - Classrooms

OCCUPANCY CLASSIFICATION (NFPA)

BUSINESS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

PARTIALLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CONSTRUCTION

DOCUMENTS

RELOCATE OIT OFF BLDG 1

6TH FLOOR RENOVATION

589A5-122

TOPEKA, KS

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Incandescence Life Safety, Inc.

3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010

A u to d e s k D o c s /1

A

-1

-1

R e lo c a te

O

IT

O ff B ld g th

F lo o r a n d

R e n o v a te

S p a c e

/5

A

-1

-1

.B

.F P

L S

R

.r v t

/2

/2

:4

:4

P

M

GI005

LIFE SAFETY PLAN

TGD GMP05/22/24

1/8" = 1'-0"

BUILDING 21 - GROUND LEVEL LIFE SAFETY PLAN

OCCUPANT LOAD CALCULATION

Occupant Load Factor Use Category Area

Occupant Load Factor

[SF/Person] Occupant

Load

Bldg 21 Ground Floor

Accessory Storage Areas, Mechanical Equipment Rooms 258 SF 300 1

Business Use - General 7,084 SF 150 47

Educational Use - Classrooms 958 SF 20 48

Storage Use - In Other Occupancies 3,780 SF 500 8

12,080 SF 104

MEANS OF EGRESS ARRANGEMENT

Egress Path Name Length

Occupancy Classification

Egress Path Maximum Permitted

Bldg 21 Ground Floor

CP-1.01 20' - 6" Business 75' - 0"

DE-1.01 18' - 6" Business 20' - 0"

TD-1.01 173' - 6" Business 200' - 0"

TD-1.03 96' - 3" Business 300' - 0"

EXIT CAPACITY COMPARISON

Most Restrictive Egress Component Expected Occupant

LoadID Type Clear Width

Capacity Factor (in/Person)

Occupant Capacity

Bldg 21 Ground Floor

100 Door 3' - 4" 0.2 200 17

108 Door 3' - 4" 0.2 200 40

115 Stair 3' - 8" 0.3 147 15

124 Door 3' - 4" 0.2 200 32

747 104

Building 21 Occupancy Classification

(NFPA)

OCCUPANCY CLASSIFICATION

SCHEDULE

Area

Bldg 21 Ground Floor

SINGLE OCCUPANCY BUSINESS

BUSINESS 12,080 SF

12,080 SF

1" = 30'-0"

BLDG 21 - GROUND FLOOR - OCCUPANCY CLASSIFICATION PLAN

NTRUE

NORTH

0' 4' 8' 16' 32'

SCALE: 1/8" = 1'-0"

T

T

T

2a

3a

A1 B1 C1 D1

1a

EHRM TRAINING

OIT OFFICE

MECHANICAL

109A

STORAGE

STORAGE

STORAGE

OIT SHIPPING/

BREAKDOWN

115A

SHIPPING/BREAKDOWN

CORRIDOR 2

CDR2

MEN'S

RESTROOM

OFFICE

CONFERENCE

ROOM

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

101 LOBBY

OFFICE

RESTROOM

121A

CORRIDOR 1

CDR1

RESTROOM

119A

STORAGE

WOMEN'S

RESTROOM

COM

110E

ELECTRICAL

111E

STORAGE

SPRINKLER SYSTEM HAZARD CLASSIFICATION

Light Hazard

Ordinary Hazard (Group 1)

Ordinary Hazard (Group 2)

WORK AREA BOUNDARY

N

D

NNNN

N

N N N N N

11111

N

N

MODIFY EXISTING SYSTEM TO

PROVIDE 0.2 GPM OVER 1500

SQUARE FEET PER

SPECIFICATION SECTION 21 13 13

FIRE SUPPRESSION SCOPE PLAN

B21-FIRST FLOOR

NOT IN SCOPE - EXISTING TO REMAIN

1. MODIFY THE EXISTING FIRE SPRINKLER SYSTEM TO ACCOMODATE BUILDING RENOVATIONS

AS INDICATED WITH ALL NECESSARY EQUIPMENT, APPURTENANCES, AND CONTROLS,

COMPLETELY COORDINATED WITH ALL DISCIPLINES. ALL WORK SHALL BE PERFORMED IN

ACCORDANCE WITH THE AUTHORITY HAVING JURISDICTION (AHJ) REQUIREMENTS, AND

THESE CONTRACT DOCUMENTS (INCLUDING, BUT NOT LIMITED TO NFPA 13, NFPA 24, AND VA

FPDM).

2. ALL COMPONENTS AND ASSEMBLIES SHALL BE U.L. LISTED OR FM APPROVED FOR THEIR

INTENDED APPLICATION.

3. THE ENTIRE PROJECT SHALL BE PROTECTED BY A HYDRAULICALLY DESIGNED WET PIPE

AUTOMATIC FIRE SPRINKLER SYSTEM. SEE SPRINKLER SYSTEM DESIGN CRITERIA THIS

SHEET FOR MORE INFORMATION ON THE BASIS OF DESIGN.

4. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE INTENDED TO CONVEY OVERALL

SYSTEM ARRANGEMENT AS IT PERTAINS TO THIS SCOPE OF WORK. THE CONTRACTOR SHALL

BE RESPONSIBLE FOR FURNISHING AND INSTALLING COMPLETE FIRE SUPPRESSION SYSTEM

AS INDICATED IN THE DESIGN DOCUMENTS AND THE REFERENCED STANDARDS. THE

CONTRACTOR SHALL BE RESPONSIBLE FOR THE FINAL SELECTION AND PLACEMENT OF

SPRINKLER HEADS AND EQUIPMENT.

5. ALL SPRINKLER HEADS SHALL BE QUICK RESPONSE TYPE.

6. SYSTEM SHALL BE INSTALLED SO NO WET PIPING IS SUBJECTED TO FREEZING CONDITIONS.

THE GENERAL CONTRACTOR SHALL TAKE FULL RESPONSIBILITY FOR LOCATING ALL FIRE

SPRINKLER LINES AND HEADS WITHIN THE BUILDING AT LOCATIONS NOT SUBJECT TO

FREEZING CONDITIONS. FOR AREAS OF BUILDING, WHERE THAT IS NOT DEEMED POSSIBLE, A

"DRY" SYSTEM SHALL BE SUBSTITUTED.

7. IN ELECTRICAL AND COMMUNICATION ROOMS WITH CEILINGS, INSTALL SIDEWALL

SPRINKLERS. HEAD GUARDS SHALL BE PROVIDED IN ALL ELECTRICAL AND COMMUNICATION

ROOMS WITH NO CEILINGS.

8. COORDINATE ALL WORK WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING, AND

ELECTRICAL TRADES. PROVIDE ALL OFFSETS TO AVOID INTERFERENCE WITH EQUIPMENT,

PIPING, DUCTWORK, LIGHTS, CONDUIT, OR STRUCTURAL MEMBERS. THE GENERAL

CONTRACTOR AND SPRINKLER SUBCONTRACTOR SHALL MEET WITH THE

ARCHITECT/ENGINEER TO COORDINATE ROUTING OF ALL PIPING AND HEAD PLACEMENT IN

EXPOSED AREAS PRIOR TO SUBMITTAL OF SHOP DRAWINGS TO ASCERTAIN THE AESTHETIC

REQUIREMENTS IN SUCH AREAS.

9. REFER TO FIRE ALARM SYSTEM PLANS FOR LOCATIONS OF TAMPER AND FLOW SWITCHES.

10. PROVIDE AUTOMATIC AIR VENTS ON WET PIPE SPRINKLER SYSTEM PIPING IN ACCORDANCE

WITH NFPA 13 §8.1.5 AND §16.7. VENT SHALL BE LOCATED NEAR A SYSTEM HIGH POINT IN AN ACCESSIBLE AREA (E.G. AREAS WITHOUT CEILINGS, AREAS WITH LAY-IN CEILING TILES, OR

NEAR AN ACCESS PANEL).

11. THE FIRE SPRINKLER SYSTEM SHALL BE CONNECTED TO THE MUNICIPAL WATER SUPPLY AS

INDICATED ON CIVIL UTILITY PLANS. CONTRACTOR TO PERFORM HYDRANT FLOW TEST TO

VERIFY ADEQUATE CAPACITY IS PROVIDED BY THE NEW WATER SUPPLY BY CONDUCTING

HYDRAULIC CALCULATION ANALYSIS. PRELIMINARY HYDRANT FLOW TEST INFORMATION

OBTAINED NEAR THE PROJECT SITE IS AS FOLLOWS:

FIRE SUPPRESSION GENERAL NOTES

SPRINKLER SYMBOL LEGEND

UPRIGHT SPRINKLER HEAD

ACRONYMS:

'D' DEMOLISH

'N' NEW HEAD

PENDENT SPRINKLER HEAD

1. MAKE CONNECTION AS REQUIRED TO EXISTING SPRINKLER LINE. THE

CONTRACTOR SHALL INSTALL ADAPTERS, FITTINGS, OR TEES AS REQUIRED

FOR A COMPLETE OPERATTIONAL SYSTEM.

2. REMOVE AND CAP SPRINKLER AS REQUIRED. EXISTING HEAD LOCATED LESS

THAN 4" FROM WALL (NFPA 13 §10.2.5.3)

3. EXTEND CONNECTION TO HEAD BELOW OBSTRUCTION AS REQUIRED PER NFPA

13 §10.2.7.3.

FIRE SUPPRESSION KEYNOTES X

2a

3a

D1

TO FIRST FLOOR SYSTEM

EXISTING FIRE

DEPARTMENT CONNECTION

WITH 2" DRAIN BELOW

EXISTING 4" WATER LINE LEAD IN

DOUBLE CHECK VALVE

BACKFLOW ASSEMBLY

TO BASEMENT

SPRINKLERS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

PARTIALLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CONSTRUCTION

DOCUMENTS

RELOCATE OIT OFF BLDG 1

6TH FLOOR RENOVATION

589A5-122

TOPEKA, KS

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Incandescence Life Safety, Inc.

3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010

A u to d e s k D o c s /1

A

-1

-1

R e lo c a te

O

IT

O ff B ld g th

F lo o r a n d

R e n o v a te

S p a c e

/5

A

-1

-1

.B

.F P

L S

R

.r v t

/2

/2

:4

:4

P

M

FP100

FIRE SUPPRESSION SCOPE PLAN

TGD GMP05/22/24

1/8" = 1'-0"

BUILDING 21 - GROUND FLOOR - FIRE SUPPRESSION PLAN

1" = 20'-0"

BLDG 21 FIRE SUPPRESSION SCOPE PLAN

AUTOMATIC SPRINKLER SYSTEM DESIGN CRITERIA

Sprinkler System Hazard Classification

Sprinkler Density

[GPM/SF]

Sprinkler

Design Area

Sprinkler Hose

Allowance [gpm]

Sprinkler Duration

[MIN]

Light Hazard 0.1 1,500 SF 100 30

Ordinary Hazard (Group 1) 0.15 1,500 SF 250 60

Ordinary Hazard (Group 2) 0.2 1,500 SF 250 60

NTRUE

NORTH

0' 4' 8' 16' 32'

SCALE: 1/8" = 1'-0"

Mark Revisions: Date:

1/8" = 1'-0"

BUILDING 21 - BASEMENT FIRE SUPPRESSION PLAN

OPEN CHAIN LINK

FENCE

F

A N

N

F

T

TT

T

NAC

D

2a

3a

A1 B1 C1 D1

1a

C

C

EHRM TRAINING

OIT OFFICE

EHRM

109B

MECHANICAL

109A

STORAGE

STORAGE

OIT SHIPPING/

BREAKDOWN

115A

SHIPPING/BREAKDOWN

CONFERENCE

ROOM

OFFICE

MEN'S

RESTROOM

WOMEN'S

RESTROOM

STORAGE

OFFICE

OFFICE

101 LOBBY

OFFICE

OFFICE

RESTROOM

121A

OFFICE

OFFICE

C

1. ALL ELECTRICAL ITEMS INSTALLED IN WALLS, FLOORS, OR CEILINGS TO BE DEMOLISHED

SHALL BE REMOVED IN THEIR ENTIRETY UNLESS OTHERWISE NOTED OR REQUIRED BY

OTHER CONDITIONS IN THESE DOCUMENTS. SEE DRAWINGS OF ALL OTHER TRADES FOR

EXTENT OF DEMOLITION WORK. ELECTRICAL ITEMS SHALL INCLUDE POWER, LIGHTING, AND

SPECIAL SYSTEMS. REFER ALL QUESTIONS OF APPLICABILITY TO THE A/E PRIOR TO BID FOR

CLARIFICATION; OTHERWISE, FIELD DECISIONS BY THE A/E SHALL BE BINDING.

2. IT IS NOTED THAT THESE DRAWINGS DEPICT THE GENERAL INTENT OF THE SCOPE OF THE

DEMOLITION WORK AND THAT NOT ALL ITEMS OF ELECTRICAL DEMOLITION ARE

NECESSARILY SHOWN. THE CONTRACTOR SHALL BE REQUIRED TO FIELD VERIFY AND FIELD

DETERMINE THE SCOPE OF THE DEMOLITION WORK PRIOR TO BID. REFER ALL QUESTIONS

TO THE A/E PRIOR TO BID FOR CLARIFICATION.

3. PHASING OF ELECTRICAL DEMOLITION SHALL FOLLOW THAT OF THE GENERAL

CONTRACTOR. COORDINATE REMOVAL OF ELECTRICAL WORK WITH OTHER CONSTRUCTION

ACTIVITIES AND THE REQUIREMENTS OF THE OWNER.

4. THE OWNER SHALL HAVE SALVAGE RIGHTS TO ANY ITEMS THAT ARE TO BE DEMOLISHED.

ITEMS SUCH AS SPEAKERS, PANELS, AND OTHER ITEMS THAT THE OWNER WISHES TO

SALVAGE SHALL BE CAREFULLY REMOVED AND STORED IN A LOCATION AS DIRECTED BY

THE OWNER. ALL OTHER ITEMS OF DEMOLITION SHALL BECOME THE PROPERTY OF THE

CONTRACTOR AND SHALL BE REMOVED FROM THE SITE.

5. FIELD VERIFY ALL FIRE ALARM CONDUCTORS AND RACEWAYS WITHIN AREA OF WORK DO

NOT SERVE AREAS OUTSIDE THE SCOPE OF WORK. WHERE DEMOLITION WORK WILL

INTERRUPT CIRCUIT CONTINUITY TO OTHER AREAS OF THE FACILITY THAT ARE TO REMAIN

IN OPERATION, RACEWAYS AND WIRING SHALL BE INSTALLED TO MAINTAIN THOSE AREAS IN

COMPLETE OPERATION. PROVIDE TEMPORARY CONNECTIONS AS REQUIRED. COORDINATE

ANY INTERRUPTIONS WITH THE OWNER AT LEAST TWO WEEKS PRIOR AND ACCOMMODATE

THE OWNER'S NEEDS AS REQUIRED.

6. ELECTRICAL CIRCUITS THAT ARE TO BE REMOVED SHALL BE REMOVED IN THEIR ENTIRETY.

CONDUCTORS SHALL BE REMOVED FROM THE ITEM TO BE DEMOLISHED TO THE SOURCE

OVERCURRENT DEVICE. RACEWAYS WHICH ARE INSTALLED IN OR BELOW FLOORS OR

WITHIN WALLS MAY BE ABANDONED, BUT ALL OVERHEAD OR EXPOSED RACEWAYS SHALL

BE REMOVED. EXPOSED RACEWAYS TO BE ABANDONED SHALL BE REMOVED AND SHALL BE

CUT OR CHISELED AT LEAST 2" INTO THE WALL OR FLOOR AND THE OPENING GROUTED

SMOOTH.

7. WHERE EXISTING DEVICE OR JUNCTION BOXES MUST REMAIN IN EXISTING WALLS OR

CEILINGS (SUCH AS FOR CIRCUITS THAT MUST BE MAINTAINED TO OTHER AREAS), THEN

THEY SHALL BE FITTED WITH BLANK COVER PLATES.

8. WHERE DISTRIBUTION OR BRANCH CIRCUIT EQUIPMENT (PANELBOARDS, SWITCHBOARDS,

ETC.) IS TO BE REMOVED, THEN ALL CIRCUITS WHICH FEED ITEMS TO REMAIN SHALL BE

RECONNECTED TO NEW DISTRIBUTION OR BRANCH CIRCUIT EQUIPMENT. REFER ALL

QUESTIONS TO THE A/E FOR CLARIFICATION.

9. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN IN OPERATION THROUGHOUT

CONSTRUCTION TO THE GREATEST EXTENT POSSIBLE PRIOR TO DEMOLITION OF THE FIRE

ALARM SYSTEM COMPONENTS.

10. IF HAZARDOUS MATERIALS (I.E. ASBESTOS, PCB's, ETC.) ARE ENCOUNTERED AT ANY TIME

DURING CONSTRUCTION IN THE WORK AREA, STOP WORK IMMEDIATELY AND CONTACT THE

A/E OR THE OWNER.

FIRE ALARM DEMO NOTES

FIRE ALARM SYMBOL LEGEND

FIRE ALARM CONTROL PANELFACP

NOTIFICATION APPLIANCE CIRCUIT EXTENDER

POWER PANEL

NAC

FIRE ALARM SYSTEM ANNUNCIATOR PANELANN

CLEAR STROBE NOTIFICATION APPLIANCE

AUDIBLE NOTIFICATION APPLIANCES

COMBINATION HORN/CLEAR STROBE

WATER FLOW DETECTOR/SWITCH

WF

VALVE SUPERVISORY TAMPER SWITCH

TS

ADDRESSABLE MANUAL PULL STATION

F

ADDRESSABLE INPUT MODULE

AIM

P

ADDRESSABLE PHOTOELECTRIC SMOKE

DETECTOR

D

ADDRESSABLE PHOTOELECTRIC DUCT SMOKE

DETECTOR

ADDRESSABLE CONTROL MODULE RELAY

CM

MAGNETIC DOOR HOLDER

H

(WP) WEATHER PROOF

(C) CEILING MOUNTED

ADDRESSABLE FIXED TEMPERATURE HEAT

DETECTOR

ABBREVIATIONS

REMOTE TEST SWITCH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

PARTIALLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CONSTRUCTION

DOCUMENTS

RELOCATE OIT OFF BLDG 1

6TH FLOOR RENOVATION

589A5-122

TOPEKA, KS

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Incandescence Life Safety, Inc.

3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010

A u to d e s k D o c s /1

A

-1

-1

R e lo c a te

O

IT

O ff B ld g th

F lo o r a n d

R e n o v a te

S p a c e

/5

A

-1

-1

.B

.F P

L S

R

.r v t

/2

/2

:4

:4

P

M

FD101

FIRE ALARM SYSTEM DEMO PLAN

TGD GMP05/22/24

1/8" = 1'-0"

BUILDING 21 - GROUND FLOOR - FIRE ALARM DEMOLITION PLAN

NTRUE

NORTH

0' 4' 8' 16' 32'

SCALE: 1/8" = 1'-0"

ANN

F

F

CM

CM

S

D

D

D

P

F A

C P

W P

N A

C F

AIM

AIM

TS

FS

AIM

AIM TS

CM

2a

3a

A1 B1 C1 D1

1a

EHRM TRAINING

OIT OFFICE

MECHANICAL

109A

SHIPPING/BREAKDOWN

OIT SHIPPING/

BREAKDOWN

115A

STORAGE

STORAGE

CORRIDOR 2

CDR2

OFFICE

CONFERENCE

ROOM

OFFICE

OFFICE

RESTROOM

119A

MEN'S

RESTROOM

WOMEN'S

RESTROOM

STORAGE

OFFICE

RESTROOM

121A

OFFICE

LOBBY

OFFICE

OFFICE

COM

110E

ELECTRICAL

111E

C

C

C

C

EHRM

109B

STORAGE

PROVIDE

MODULE FOR

DOOR CONTROL

C

C

C

C

C

C

CC

C

C

C

FIRE ALARM SYSTEM SCOPE LEGEND

REMOVE ALL COMPONENTS AND REPLACE WITH

AN ADDRESSABLE SYSTEM

NEW BUILDING 21 ADDRESSABLE SYSTEM

1. PROVIDE A COMPLETE FIRE ALARM SYSTEM IN BUILDING 21 WITH ALL

NECESSARY EQUIPMENT, APPURTENANCES, AND CONTROLS, COMPLETELY

COORDINATED WITH ALL DISCIPLINES.

2. ALL EXISTING FIRE ALARM DEVICES TO BE REMOVED AND REPLACED

WITHIN BUILDING 21. NEW PANEL SHALL TIE INTO THE EXISTING CAMPUS

NETWORK EXISTING SIMPLEX WORKSTATION.

3. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL VA DESIGN

GUIDES, AUTHORITY HAVING JURISDICTION (AHJ) REQUIREMENTS, AND

THESE CONTRACT DOCUMENTS (INCLUDING, BUT NOT LIMITED TO NFPA 70,

NFPA 72, NFPA 90A, AND VA FPDM).

4. ALL COMPONENTS AND ASSEMBLIES SHALL BE U.L. LISTED OR FM

APPROVED FOR THEIR INTENDED APPLICATION.

5. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE INTENDED TO

CONVEY OVERALL SYSTEM ARRANGEMENT AS IT PERTAINS TO THIS SCOPE

OF WORK. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING

AND INSTALLING A COMPLETE FIRE ALARM SYSTEM AS INDICATED IN THE

DESIGN DOCUMENTS AND THE REFERENCED STANDARDS.

6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE FINAL SELECTION

AND PLACEMENT OF NOTIFICATION APPLIANCES, INCLUDING

DETERMINATION OF CANDELA RATING AND SPEAKER WATTAGE

REQUIREMENTS.

7. ADDITIONAL DEVICES AND PARTS BEYOND WHAT IS SHOWN ON THESE

PLANS MAY BE REQUIRED; CONTRACTOR SHALL NOT USE THESE PLANS

FOR DEVICE COUNTS.

8. COORDINATE ALL WORK WITH ARCHITECTURAL, STRUCTURAL,

MECHANICAL, PLUMBING, AND ELECTRICAL TRADES. PROVIDE ALL OFFSETS

TO AVOID INTERFERENCE WITH EQUIPMENT, PIPING, DUCTWORK, LIGHTS,

CONDUIT, OR STRUCTURAL MEMBERS. SEE HVAC PLANS FOR SMOKE

DAMPER LOCATIONS.

9. ALL FIRE ALARM CABLES AND WIRING SHALL BE INSTALLED WITHIN METAL

RACEWAYS. ALL RACEWAYS SHALL BE CONCEALED WITHIN FINISHED

AREAS. RACEWAYS SHALL BE PARALLEL OR PERPENDICULAR TO BUILDING

STRUCTURAL ELEMENTS. JUNCTION BOXES SHALL BE PROVIDE AND ALL

CONDUCTORS SHALL BE IDENTIFIED AT EACH JUNCTION BOX, PULL BOX,

ETC. WITH APPROPRIATE INFORMATION (E.G. PANEL NUMBER, CIRCUIT

NUMBER, ETC.).

FIRE ALARM GENERAL NOTES

FIRE ALARM SYMBOL LEGEND

FIRE ALARM CONTROL PANELFACP

NOTIFICATION APPLIANCE CIRCUIT EXTENDER

POWER PANEL

NAC

FIRE ALARM SYSTEM ANNUNCIATOR PANELANN

CLEAR STROBE NOTIFICATION APPLIANCE

AUDIBLE NOTIFICATION APPLIANCES

COMBINATION HORN/CLEAR STROBE

WATER FLOW DETECTOR/SWITCH

WF

VALVE SUPERVISORY TAMPER SWITCH

TS

ADDRESSABLE MANUAL PULL STATION

F

ADDRESSABLE INPUT MODULE

AIM

P

ADDRESSABLE PHOTOELECTRIC SMOKE

DETECTOR

D

ADDRESSABLE PHOTOELECTRIC DUCT SMOKE

DETECTOR

ADDRESSABLE CONTROL MODULE RELAY

CM

MAGNETIC DOOR HOLDER

H

(WP) WEATHER PROOF

(C) CEILING MOUNTED

ADDRESSABLE FIXED TEMPERATURE HEAT

DETECTOR

ABBREVIATIONS

REMOTE TEST SWITCH

2a

3a

D1

EXTERIOR HORN

STROBE ABOVE

EXISTING FDC

PROVIDE MONITOR

MODULE CONNECTION TO

POST INDICATOR VALVE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

PARTIALLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CONSTRUCTION

DOCUMENTS

RELOCATE OIT OFF BLDG 1

6TH FLOOR RENOVATION

589A5-122

TOPEKA, KS

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Incandescence Life Safety, Inc.

3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010

A u to d e s k D o c s /1

A

-1

-1

R e lo c a te

O

IT

O ff B ld g th

F lo o r a n d

R e n o v a te

S p a c e

/5

A

-1

-1

.B

.F P

L S

R

.r v t

/2

/2

:4

:4

P

M

FA100

FIRE ALARM SYSTEM PLAN

TGD GMP05/22/24

NTRUE

NORTH

1/8" = 1'-0"

BUILDING 21 - GROUND FLOOR - FIRE ALARM SYSTEM PLAN

1" = 20'-0"

BUILDING 21 - GROUND FLOOR FIRE ALARM ZONING PLAN

1/8" = 1'-0"

BUILDING 21 - BASEMENT FIRE ALARM PLAN

0' 4' 8' 16' 32'

SCALE: 1/8" = 1'-0"

Mark Revisions: Date:

AUDIBLE

SYSTEM INPUTS

MANUAL PULL STATION

A U

D

IO

-V

IS

U A

L F

IR

E

A L A

R M

IN

D

IC

A

T

IO

N

B Y

D E

V

IC

E

CONTROL UNIT

ANNUNCIATION

A U

D

IO

-V

IS

U A

L S

U P

E R

V

IS

O R

Y I N

D

IC

A T

IO

N

B

Y D

E V

IC

E

A U

D

IO

-V

IS

U A

L T

R O

U B

L E

ID

E

N T

IF

IC

A T

IO

N

B

Y D

E V

IC

E

F

IR

E A

L A

R M

S

IG

N A

L

B Y

D E

V

IC

E T

Y P

E

G E

N E

R A

L S

U P

E R

V

IS

O R

Y S

IG

N

A L

G E

N E

R A

L T

R O

U B

L E

S

IG

N A

L

TRANSMIT TO

HEAD END FA

NOTIFI-

CATION

TAMPER SWITCH

SYSTEM LOW BATTERY

GROUND FAULT

NOTIFICATION APPLIANCE SHORT CIRCUIT

SYSTEM OUTPUTS

OPEN CIRCUIT

A B C D E F G H I J K M

F

IR

E A

L A

R M

S

IG

N

A L

S

S U

P E

R V

IS

O

Y

N

A L

AC POWER FAILURE

R

O U

B

N A

L S

L

WATER FLOW SWITCH - SPRINKLER SYSTEM ZONE

SMOKE DETECTOR - ABOVE FACP

TAMPER AT POST INDICATOR VALVE

R E

M O

T E

L Y

T R

A N

S M

IT

S

T A

T U

S C

H A

N G

E T

O A

T T

E N

D

O

C A

T

IO

N I N

B U

IL

IN

G

A C

T U

A T

E V

IS

U

A L N

O T

IF

IC

A T

IO

N

A P

P L

IA

N C

(S

R O

B E

S

A C

T U

A T

E A

U D

IB

L E

N O

T

IF

IC

A

T

IO

N A

P P

L

IA

N C

E S

H

O R

N S

M P

O R

A L

T O

N E

A C

T U

A T

E E

X T E

R

IO

R W

A T E

R F

L O

W A

L A

R M

B E

L L

AUXILIARY

FUNCTIONS

N O

A C

T

IV

A T

E R

E L A

Y T

O S

H U

T D

O W

N H

V A

C S

Y S

T

M

Q

U

IP

M E

N T

A C

T

IV

A T

E R

E L A

Y T

O R

E L E

A S

E M

A G

N E

T

IC

D O

H

L D

E R

S

DUCT SMOKE DETECTOR

U N

L O

C K

E G

R E

S S

D O

O R

S

NETWORK TROUBLE

FIRE ALARM CONTROL

PANEL

(NEW)

120 VAC

BATTERIES

ANN

BASEMENT SIGNALING

LINE CIRCUIT (SLC) -

TYPICAL

AIM AIM

TS TS

B A

C K

F

LO

W

IS

LA

T

IO

N

V

A

LV

E S

A N

P

R

IN

K

LE

S T

E M

Z

(W

T

F

P

FIRST FLOOR SIGNALING

LINE CIRCUIT (SLC) -TYPICAL

F

WP

BASEMENT NOTIFICATION

APPLIANCE CIRCUIT(NAC) -

TYPICAL

S

FIRST FLOOR NOTIFICATION

APPLIANCE CIRCUIT(NAC) -

TYPICAL

NEWTWORK FIBER

CONNECTION NODE

BUIDLING 21

(EXISTING)

NAC PANEL

(NEW)

AIM

WF

AIM

TS

P O

S T

-I N

D

IC

A T

A

LV

E

CM

D O

O R

R E

LE

A

IN

E

R F

A C

E

CM

F A

C P

/S E

C U

R

IT

N T

R O

L

IN

T E

R F

A C

E

D

120 VAC

BATTERIES EQUIPMENT CONNECTED BY DATA NETWORK TO CAMPUS

CONNECTION, CONNECT FACP TO WORSTATION IN BUILDING 40

D

FIRE ALARM SYMBOL LEGEND

FIRE ALARM CONTROL PANELFACP

NOTIFICATION APPLIANCE CIRCUIT EXTENDER

POWER PANEL

NAC

FIRE ALARM SYSTEM ANNUNCIATOR PANELANN

CLEAR STROBE NOTIFICATION APPLIANCE

AUDIBLE NOTIFICATION APPLIANCES

COMBINATION HORN/CLEAR STROBE

WATER FLOW DETECTOR/SWITCH

WF

VALVE SUPERVISORY TAMPER SWITCH

TS

ADDRESSABLE MANUAL PULL STATION

F

ADDRESSABLE INPUT MODULE

AIM

P

ADDRESSABLE PHOTOELECTRIC SMOKE

DETECTOR

D

ADDRESSABLE PHOTOELECTRIC DUCT SMOKE

DETECTOR

ADDRESSABLE CONTROL MODULE RELAY

CM

MAGNETIC DOOR HOLDER

H

(WP) WEATHER PROOF

(C) CEILING MOUNTED

ADDRESSABLE FIXED TEMPERATURE HEAT

DETECTOR

ABBREVIATIONS

REMOTE TEST SWITCH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

PARTIALLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

A

B

C

D

E

F o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

CONSTRUCTION

DOCUMENTS

RELOCATE OIT OFF BLDG 1

6TH FLOOR RENOVATION

589A5-122

TOPEKA, KS

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Incandescence Life Safety, Inc.

3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010

A u to d e s k D o c s /1

A

-1

-1

R e lo c a te

O

IT

O ff B ld g th

F lo o r a n d

R e n o v a te

S p a c e

/5

A

-1

-1

.B

.F P

L S

R

.r v t

/2

/2

:4

:4

P

M

FA500

FIRE ALARM SYSTEM DETAILS

TGD GMP05/22/24

Mark Revisions: Date:

1/2" = 1'-0"

FIRE ALARM MATRIX OF OPERATIONS

1/2" = 1'-0"

FIRE ALARM RISER DIAGRAM

A B C D

109F

115A

111F

106B 106C

110E

111E

109A

3A

3B113

116P

CDR1

118F

119A

121A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

HA101

BUILDING 21 FIRST FLOOR -

HAZARDOUS MATERIALS - ASBESTOS

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

CL MET

Mark Revisions: Date:

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001 05/22/24

A

B

C

D

E

F on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

CONSTRUCTION

DOCUMENTS

RELOCATE OIT OFF BLDG 1

6TH FLOOR RENOVATION

589A5-122

TOPEKA, KS

Specialized Engineering Solutions 10360 Ellison Circle Omaha, NE 68134 Phone: (402) 991-5520

Incandescence Life Safety, Inc.

3455 Ringsby Ct, Suite 103 Denver, CO 80216 Phone: (720) 722-3010

GENERAL NOTES:

1. THESE DRAWINGS ARE DIAGRAMMATIC AND FOR GENERAL IDENTIFICATION OF ASBESTOS-CONTAINING MATERIALS. LOCATIONS AND QUANTITIES SHOWN OF ACM ARE REPRESENTATIVE BASED ON RECENT AND PREEXISTING SITE SURVEY INFORMATION.

2. ALL WORK IS TO BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL REGULATIONS; PROJECT SPECIFICATIONS, THE APPROVED WORK PLAN, AND ACCEPTED INDUSTRY PRACTICE. WHEN REQUIREMENTS OVERLAP OR CONFLICT, THE MOST STRINGENT REQUIREMENT SHALL APPLY. ALL WORK SHALL BE SUBJECT TO INSPECTION BY THE OWNER, THE OWNER'S CONSULTANTS, AND REGULATORY

PERSONNEL.

ASBESTOS NOTES:

1. THE PROJECT AREA WAS RECENTLY SURVEYED FOR…