These bid documents detail a renovation project for pharmacy hood ductwork at the James A. Haley VA Hospital in Tampa, Florida. The project (VA Project #673-23-115) involves completely demolishing and remodeling existing compounding pharmacy hood ductwork to ensure compliance with USP 797 and USP 800 standards. The project is valued between $250,000 and $500,000, with a 90-calendar day performance period, and is 100% set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB).
Key procurement details include a site visit scheduled for 06/25/2025, proposal submissions due by the specified deadline, and evaluation based on specialized experience, schedule, past performance, and price. Contractors must demonstrate HVAC/pharmacy project experience in healthcare environments, provide a detailed progress schedule, submit past performance references, and ensure at least 25% of contract costs are performed with their own employees. A payment and performance bond covering 100% of the order price is required, and contractors must have an Experience Modification Rate (EMR) not exceeding 1.0.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24825R0112 0002.pdf | ||
| 36C24825R0112 0001.docx | DOCX document | |
| EMR 1 page.pdf | ||
| WD FL20250208 05232025.pdf | ||
| 36C24825R0112_1.docx | DOCX document | |
| 07- 673-23-115 Specifications update.pdf | ||
| Base Offer Price Breakdown - 1 page.xlsx | XLSX spreadsheet | |
| Past Performance Questionnaire - 4 Pages.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Contact:
VAMC
Eric Richardson Contracting Officer Represenative(COR) James A. Haley 13000 Bruce B Downs Blvd, Tampa, FL 33612 p: 813-503-3657 e: Eric.Richardson7@va.gov
M402 MECHANICAL SECTION VIEWS
550 North Reo Street, Suite 203 Tampa, FL 33609
G101 INFECTION CONTROL RISK ASSESMENT PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
G100
COVER SHEET
A
Fi le
P at h
/1 5/
1:
:0
AM
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD A/E:
STAMP
321 4 5 6 7 8 9 10
GUIDON MES JV II, LLC
1221 N PENNSYLVANIA ST.
INDIANAPOLIS, IN 46202
(317) 800-6388
DAVID KEITH, P.E.
AE RENOVATE PHARMACY HOOD
DUCTWORK
673-23-115
11/12/2024 AO ESRevisions: Date:
BID DOCUMENTS
13000 BRUCE B. DOWNS BOULEVARD
TAMPA, FL 33612
PROJECT
AREA
N
SHEET LIST
SHEET NUMBER SHEET NAME
GENERAL
G100 COVER SHEET
ARCHITECTURE
A101 FLOOR PLAN
MECHANICAL
M001 MECHANICAL LEGEND AND GENERAL NOTES
M101 PARTIAL GROUND FLOOR PLAN - MECHANICAL
DEMOLITION
M401 PARTIAL FIRST FLOOR PLAN - AIR DISTRIBUTION
DEMOLITION
Contact:Contact:
MES Group.
Philip Beauchamp Project Manager
MECHANICAL,ELECTRICAL &PLUMBINGOWNER
GUIDON
Erin Sikorski Architect 1221 North Pennsylvania Street Indianapolis, IN 46202 p: 317.800.6388 e: esikorski@guidon.com
ARCHITECT
p:813-331-5084 ext: 2040 e: Philip.Beauchamp@MESGROUPINC.COM
VICINITY MAP
JAMES A. HALEY VETERANS HOSPITAL
TAMPA, FLORIDA
AE Renovate Pharmacy Hood Ductwork
VA PROJECT #673-23-115
N
PROJECT LOCATION
11/12/2024
STOR
HAZ
ANTE
NON-HAZ
HAZ BUFFER
STERILE NON-HAZ BUFFER
STERILE
MISSING DOSE
1ST DOSE/
STORAGE
ANTE
HAZ
(E) BSC (E) BSC(E) CACI
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
/1 5/
1:
:0
AM
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD A/E:
STAMP
321 4 5 6 7 8 9 10
GUIDON MES JV II, LLC
1221 N PENNSYLVANIA ST.
INDIANAPOLIS, IN 46202
(317) 800-6388
DAVID KEITH, P.E.
AE RENOVATE PHARMACY HOOD
DUCTWORK
673-23-115
11/12/2024 PBJ MANRevisions: Date:
BID DOCUMENTS
13000 BRUCE B. DOWNS BOULEVARD
TAMPA, FL 33612
PROJECT
AREA
KEY PLANN
11/12/2024
G101
INFECTION CONTROL RISK
ASSESSMENT PLAN
G101
1 INFECTION CONTROL RISK ASSESSMENT PLAN
SCALE: 1/4" = 1'-0"N
A. COORDINATE FULL SCOPE OF WORK OF WORK WITH ENGINEERING DRAWINGS AND
FIELD VERIFICATION. CONTRACTOR IS RESPONSIBLE FOR SCOPE OF ABOVE CEILING
WORK REQUIRED WITHIN PROJECT BOUNDARY.
B. COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL (IC) BARRIER WALL
CONSTRUCTION AND INFECTION CONTROL (IC) MEASURES WITH COR AND PATIENT
SAFETY/INFECTION CONTROL REPRESENTATIVE. TEMPORARY IC BARRIER WALL
CONSTRUCTION LOCATIONS IN DRAWING ARE APPROXIMATE. CONTRACTOR SHALL
PROVIDE DRAWING TO COR AND PATIENT SAFETY/INFECTION CONTROL
REPRESENTATIVE ONCE ICRA PROTOCOLS AND PLAN IS APPROVED.
C. SCHEDULE AND TIME OF CONSTRUCTION WORK TO BE APPROVED BY COR AND
PHARMACY STAFF BEFORE CONSTRUCTION MAY BEGIN. PROVIDE INFORMATION FOR
ABOVE CEILING WORK IN THE CONTRACTOR REQUIRED CMP SCHEDULE FOR WORK
REQUIRED WITHIN THE PROJECT BOUNDARY.
D. ABOVE CEILING WORK SHALL TAKE PLACE AS DIRECTED BY THE COR. IN AREAS THAT
REQUIRE ABOVE CEILING WORK WHERE CEILINGS ARE TO REMAIN, CEILING TILES
SHALL BE REMOVED AND STORED IN A SAFE MANOR UNTIL CEILING TILES CAN BE
REINSTALLED. DAMAGED AND BROKEN CEILING TILES SHALL BE REPLACED BY
CONTRACTOR. ANY DAMAGED HARD CEILINGS SHALL BE REPAIRED AND PAINTED TO
MATCH EXISTING.
E. EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED DURING
NORMAL BUSINESS HOURS. SEE SPECIFICATION FOR HOURS OF OPERATION.
F. PROVIDE THE FOLLOWING INFECTION CONTROL MEASURES, A 24"x36" STICKY
WALK-OFF MAT, AND HAND SANITIZER AT EACH TEMPORARY DOOR LOCATION. MAT
SHALL BE REPLACED OR CLEANED AS NECESSARY.
G. PROVIDE THE VA AND OSHA REQUIRED TEMPORARY SIGNAGE AT EACH TEMPORARY
DOOR LOCATION.
H. ALL NEW MATERIAL MOVED THROUGH THE FACILITY SHALL BE COVERED WITH 4 MIL.
POLY SHEET.
I. ALL DEMOLITION MATERIAL SHALL BE REMOVED FROM THE PROJECT BOUNDARY
THROUGH THE FACILITY TO DUMPSTER ALONG VA APPROVED ROUTE IN ENCLOSED
DUMPSTER CART DESIGNED FOR SUCH PURPOSE WITH LID.
J. ALL MATERIAL, DEBRIS, AND HAZARDOUS MATERIALS SHALL BE PROPERLY STORED IN
DESIGNATED AREAS AND APPROVED CONTAINERS. FLAMMABLE MATERIALS SHALL
NOT BE STORED IN THE FACILITY.
K. PROVIDE CONTAINMENT CART FOR ABOVE CEILING ACCESS OUTSIDE PROJECT
BOUNDARY.
GENERAL NOTES
KEYNOTES -
EXISTING STERILE HAZARDOUS BUFFER ROOM SLIDING DOORS SHALL BE UTILIZED AS
THE TEMPORARY INFECTION CONTROL BARRIER DOOR DURING CONSTRUCTION.
EXISTING DOORS SHALL REMAIN OPERABLE DURING ENTIRETY OF CONSTRUCTION.
PROVIDE TEMPORARY INFECTION CONTROL BARRIER CONSTRUCTION AROUND
PASS-THROUGH WINDOW OPENING. TEMPORARY BARRIER SHALL BE CONSTRUCTED
PER SPECIFICATIONS AND ICRA GUIDELINES.
N A101
1 FLOOR PLAN
SCALE: 1/2" = 1'-0"
HAZ BUFFER
STERILE
EXISTING CACI
EXISTING 18x18
ACCESS PANEL
EXISTING 18x18
ACCESS PANEL
EXISTING BSC
EXISTING 12x12
ACCESS PANEL
EXISTING CEILING CAVITY.
DEMOLISH CAVITY IN ENTIRETY,
MATCH EXISTING ADJACENT
CEILING ASSEMBLY AND
FRAMING. REPAINT ENTIRE
CEILING. (SEE PHOTOS ABOVE)EXISTING
CHASE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A101
FLOOR PLAN
A
Fi le
P at h
/1 5/
1:
:0
AM
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD A/E:
STAMP
321 4 5 6 7 8 9 10
GUIDON MES JV II, LLC
1221 N PENNSYLVANIA ST.
INDIANAPOLIS, IN 46202
(317) 800-6388
DAVID KEITH, P.E.
AE RENOVATE PHARMACY HOOD
DUCTWORK
673-23-115
11/12/2024 AO ESRevisions: Date:
BID DOCUMENTS
13000 BRUCE B. DOWNS BOULEVARD
TAMPA, FL 33612
PROJECT
AREA
KEY PLANN
GENERAL CONSTRUCTION NOTES
THE CONTRACT DOCUMENT DRAWINGS HAVE BEEN PREPARED USING REVIT®
SOFTWARE IN A MICROSOFT WINDOWS ENVIRONMENT. A BUILDING INFORMATION
MODEL (BIM) HAS BEEN DEVELOPED FOR DESIGN COMMUNICATION. THE MODEL
DOES NOT CONTAIN COMPLETE INFORMATION FOR USE IN COST ESTIMATING,
SYSTEMS PERFORMANCE, COORDINATION, SCHEDULING, OR FACILITIES
MANAGEMENT.
THE CONTRACT DOCUMENT DRAWINGS HAVE BEEN PREPARED USING THE
CONSTRUCTION SPECIFICATIONS INSTITUTE'S UNIFORM DRAWING SYSTEM AND THE
NATIONAL CAD STANDARD AND VA STANDARD AS GUIDES.
DISCREPANCIES IN THE CONTRACT DOCUMENTS SHALL BE IMMEDIATELY BROUGHT
TO THE ATTENTION OF THE ARCHITECT AND OWNER’S REPRESENTATIVE/COR.
CONTRACTOR SHALL PROVIDE THE HIGHER GRADE OF QUALITY AND/OR GREATER
QUANTITY OF WORK WHEN BIDDING IF A CLARIFICATION CAN NOT BE OBTAINED BY
THE BID DUE DATE.
CONTRACTOR IS RESPONSIBLE FOR COORDINATING SCOPE OF WORK WITH OWNER’S
REPRESENTATIVE/COR AND VARIOUS FACILITY PERSONNEL INVOLVED WITH UTILITY
SHUT DOWN, INFECTION CONTROLS, OCCUPANT/EMPLOYEE SAFETY, ACCESS
CONTROL, ETC.
ANY INDICATION OF PROJECT LIMITS OR BOUNDARY OF DEMARCATION ARE SHOWN
FOR THE CONVENIENCE OF THE CONTRACTOR, THE FULL SCOPE OF THE PROJECT
LIMIT OF BOUNDARY REQUIRES COORDINATION WITH THE DESIGN SCOPE OF WORK
AND ACCESS TO EXISTING UTILITIES FOR TIE IN.
DRAWINGS ARE PREPARED FROM FIELD VERIFICATION, EXISTING FACILITY DRAWING
BASE FILES, AND USING DIMENSIONS, CONFIGURATIONS AND DETAILS OF SPECIFIC
MANUFACTURERS AS A BASIS OF DESIGN. CONTRACTOR IS RESPONSIBLE FOR
VERIFICATION OF ACTUAL DIMENSIONS, THE COORDINATION OF THE DETAILS WITH
THE PRODUCTS WHICH ARE PROVIDED PER THE SCOPE OF THE SPECIFICATIONS AND
THE SURROUNDING CONSTRUCTION. CONTRACTOR SHALL VERIFY DIMENSIONS,
ROUGH-IN DIMENSIONS, CONNECTIONS, AND OVERALL INSTALLATION REQUIREMENTS.
CONTRACTOR IS RESPONSIBLE FOR THE COMPLETION OF THE ENTIRE SCOPE OF
WORK OUTLINED IN THE CONTRACT DOCUMENTS. CONTRACTOR IS RESPONSIBLE FOR
THE COORDINATION OF ALL SUB-CONTRACTORS AND THE SCOPE OF WORK THEY
PROVIDE. SUB-CONTRACTORS ARE RESPONSIBLE FOR THEIR FULL SCOPE OF WORK
WITHIN THE CONTRACT DOCUMENTS, TRADES ARE NOT SEGMENTED TO ONLY
CERTAIN SHEETS AND SPECIFICATIONS, CROSS COORDINATION IS REQUIRED.
CONTRACTOR AND SUB-CONTRACTORS ARE BOTH RESPONSIBLE FOR
UNDERSTANDING INFORMATION OUTLINED IN THE SPECIFICATIONS, KEY NOTES,
GENERAL NOTES, LEGEND, CODES, ETC., PROVIDED IN THE CONTRACT DOCUMENTS.
CONTRACTOR AND SUB-CONTRACTORS ARE BOTH RESPONSIBLE FOR PROVIDING
AND MAINTAINING SMOKE/FIRE RATINGS OF NEW CONSTRUCTION AND EXISTING
CONSTRUCTION AS INDICATED ON DRAWINGS. THIS INCLUDES PATCHING
PENETRATIONS IN SHAFTS, WALLS, SLABS AND ROOF. ONLY U.L. APPROVED
METHODS, MATERIALS AND INSTALLATION ARE ACCEPTABLE.
MECHANICAL DRAWINGS SHOW
INFORMATION IN A DIAGRAMMATIC FASHION WITHOUT DIMENSIONING. THE GENERAL
CONTRACTOR IS TO COORDINATE THE LOCATIONS OF ALL MECHANICAL
EQUIPMENT WITH RESPECT TO THE ARCHITECTURAL
DETAILING OF SHAFTS, CHASES, CEILING CONSTRUCTION, ETC.
CONTRACTOR IS RESPONSIBLE FOR VERIFYING DIMENSIONS IDENTIFIED AND NOT
IDENTIFIED IN THE CONTRACT DOCUMENTS WITH THE EXISTING AND NEW
CONSTRUCTION ELEMENTS. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION
BETWEEN THE CONTRACT DOCUMENTS, INSTALLED AND UNINSTALLED
CONSTRUCTION BEFORE THE ORDERING OF MATERIALS AND EQUIPMENT. NOTIFY
ARCHITECT AND OWNER’S REPRESENTATIVE/COR OF ANY DISCREPANCIES OR
MISSING DIMENSIONS.
DO NOT SCALE THE DRAWINGS. DRAWING SCALES AS INDICATED ARE FOR GENERAL
ORIENTATION AND CONTEXT ONLY.
THE TERM "ALIGN" MEANS TO INSTALL DIFFERENT/SIMILAR COMPONENTS OF
CONSTRUCTION TO PROVIDE A FLUSH FINISH SURFACE.
ALL DIMENSIONS INDICATED ARE TO FACE OF EXISTING MEMBERS, FACE OF NEW
STRUCTURAL MEMBERS, FACE OF NEW MASONRY, FACE OF NEW STUDS OR COLUMN
GRID LINES UNLESS NOTED OTHERWISE.
FIRST FLOOR ELEVATION 0’-0” IS EQUAL TO THE FINISH FLOOR SLAB OF THE EXISTING
SLAB FLOOR CONSTRUCTION UNLESS NOTED OTHERWISE.
ROUGH OPENINGS SHALL ALLOW FOR SHIM SPACE.
CONTRACTOR TO PROVIDE WORK WHERE DETAILS AND NOTES ARE IDENTIFIED AS
“TYPICAL” OR “SIMILAR” EACH INSTANCE THAT IS THE SAME IN NATURE TO THE DETAIL,
AREA, OR ITEM REFERENCED.
PROVIDED WORK SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR.
CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF DELIVERY, MOUNTING,
INSTALLATION, NECESSARY BLOCKING AND ROUGH-IN.
INSTALLED WORK IS THE CONTRACTOR INSTALLING OWNER FURNISHED MATERIALS
AND EQUIPMENT. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF MATERIAL
DELIVERY, MOUNTING, INSTALLATION AND ROUGH IN.
FURNISHED WORK IS THE CONTRACTOR FURNISHING THE MATERIALS AND
EQUIPMENT TO THE OWNER. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF
DELIVERY AND ROUGH-IN.
ALL PROVIDED WORK SHALL BE WITH NEW MATERIALS UNLESS SPECIFICALLY CALLED
OUT AS SALVAGED OR RELOCATED WITHIN THE CONTRACT DOCUMENTS.
ALL PERSONS DIRECTLY OR INDIRECTLY ASSOCIATED WITH THE PROJECT SHALL BE
FAMILIAR WITH THE RULES AND REGULATIONS OF THE OCCUPATIONAL SAFETY AND
HEALTH ACT, AND IMPLEMENT THOSE RULES AS THEY APPLY TO THIS PROJECT.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND PROTECTING ALL
UTILITY LINES. LOCATIONS SHOWN ARE APPROXIMATE. REPAIR ALL DAMAGE TO
UTILITY LINES CAUSED BY CONSTRUCTION OPERATIONS AT NO COST TO THE OWNER.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TEMPORARY BRACING AND SHORING
REQUIRED DURING CONSTRUCTION.
CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ADJACENT CONSTRUCTION,
FINISHES, EQUIPMENT, AND TRAVEL ROUTE TO AND FROM THE CONSTRUCTION SITE.
ANY DAMAGE OR UNACCEPTABLE WEAR BY THE CONSTRUCTION TEAM SHALL BE
REPAIRED/REPLACED BY THE CONTRACTOR AT NO COST TO THE OWNER.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
11/12/2024
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
/1 5/
1:
:0
AM
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD A/E:
STAMP
321 4 5 6 7 8 9 10
GUIDON MES JV II, LLC
1221 N PENNSYLVANIA ST.
INDIANAPOLIS, IN 46202
(317) 800-6388
DAVID KEITH, P.E.
AE RENOVATE PHARMACY HOOD
DUCTWORK
673-23-115
11/12/2024 PBJ MANRevisions: Date:
BID DOCUMENTS
13000 BRUCE B. DOWNS BOULEVARD
TAMPA, FL 33612
11/12/2024
M001
GENERAL NOTES, LEGENDS,
ABBREVIATIONS & DETAILS
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
ROOM NAME AND NUMBER
NEW CONNECTION TO EXISTING
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
Room
18"x12"
18"/12"
(E)
18"Ø
EXHAUST AIR
SUPPLY AIR
TYPE (REFER TO SCHEDULES)
CFM
EXISTING DUCT TAG
OVAL DUCT SIZE TAG (WIDTH / HEIGHT)
SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)
RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE
RECTANGULAR RETURN/TRANSFER AIR DUCT RISE
ROUND DUCT SIZE TAG (DIAMETER)
DUCT BEING DEMOLISHED
ROUND SUPPLY/OUTSIDE AIR DUCT RISE
ROUND RETURN/TRANSFER AIR DUCT RISE
RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE
ROUND EXHAUST/RELIEF AIR DUCT RISE
DROP
DROP
DROP
DROP
DROP
DROP
EXISTING HOOD
TO REMAIN (E) BSC
ABV ABOVE
AC AIR CONDITIONING
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BTU BRITISH THERMAL UNITS
BTUH BTU PER HOUR
CAP CAPACITY
CFM CUBIC FEET PER MINUTE
CLG CEILING
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
EAT ENTERING AIR TEMP
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWT ENTERING WATER TEMP
EA EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FL FLOOR
FPM FEET PER MINUTE
FT FOOT/FEET
GAL GALLON
GF GAS-FIRED
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
HP HORSEPOWER
IN INCH
LAT LEAVING AIR TEMP
LWT LEAVING WATER TEMP
MA MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTUH
MCF ONE THOUSAND CUBIC FEET
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MUA MAKE-UP AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
NUM NUMBER
OA OUTSIDE AIR
PD PRESSURE DROP
PLBG PLUMBING
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH
GAUGE
PWR POWER
R
DUCT RISER
RA RETURN AIR
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RLA RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
SF SQUARE FOOT
SA SUPPLY AIR
SF SQUARE FOOT
SP STATIC PRESSURE
THERMOSTAT
TD TEMPERATURE DROP
TEMP TEMPERATURE
TYP TYPICAL
VENT VENTILATION
WB WET BULB
SUPPLY
DIFFUSER
BSC BIOLOGICAL SAFETY CABINET
CACI COMPOUNDING ASEPTIC
CONTAINMENT ISOLATOR
F EXHAUST FAN
EQUIPMENT ABBREVIATIONS
18"x18" SA
18"x18" EA
1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATIVE OF
WORK TO BE PROVIDED (FURNISHED AND INSTALLED) UNDER THIS
CONTRACT. DRAWINGS SHOULD NOT BE SCALED.
2. THE CONTRACTOR IS RESPONSIBLE TO EXAMINE THE EXISTING
CONDITIONS UNDER WHICH THEY SHALL OPERATE AND VERIFY THE
EXTENT OF WORK REQUIRED TO COMPLETE THE WORK UNDER THIS
CONTRACT.
3. PRIOR TO ORDERING AND FABRICATING ANY EQUIPMENT, IT IS THE
RESPONSIBILITY OF THE CONTRACTOR TO EXAMINE THE PHYSICAL
CONDITIONS AT THE PROJECT SITE AND VERIFY SPACE AND SUFFICIENT
CLEARANCES ARE AVAILABLE FOR INSTALLING EQUIPMENT, DUCTWORK,
PIPING, AND APPURTENANCES, AND TO DETERMINE ANY NECESSARY
MODIFICATIONS.
4. PERFORM ALL WORK IN COMPLIANCE WITH ALL APPLICABLE FEDERAL,
STATE, AND LOCAL CODES, REGULATIONS, AND STANDARDS ADOPTED BY
THE AUTHORITY HAVING JURISDICTION. IF CONFLICTS EXIST BETWEEN
THESE ENGINEERING DOCUMENTS AND CODES, THE MOST STRINGENT
REQUIREMENTS SHALL GOVERN.
5. ALL CONSTRUCTION WORK SHALL ALSO MEET THE FOLLOWING CODE
REQUIREMENTS:
· INTERNATIONAL BUILDING CODE (IBC) 2024
· INTERNATIONAL EXISTING BUILDING CODE (IEBC) 2024
· INTERNATIONAL MECHANICAL CODE (IMC) 2024
· INTERNATIONAL ENERGY CONSERVATION CODE (IECC) 2021
· NFPA 1-2024, THE UNIFORM FIRE CODE
· NFPA 101-2024, THE LIFE SAFETY CODE
· NFPA 51B-2024, STANDARD FOR FIRE PREVENTION DURING WELDING,
CUTTING AND OTHER HOT WORK
· NFPA 13-2022, STANDARD FOR THE INSTALLATION OF SPRINKLER
SYSTEMS
· NFPA 70-2023, NATIONAL ELECTRICAL CODE
· NFPA 90A-2024, STANDARD FOR THE INSTALLATION OF AIR
CONDITIONING AND VENTING SYSTEMS.
· NFPA 99-2024, STANDARD FOR HEALTH CARE FACILITIES
· NFPA 241-2022, STANDARD FOR SAFEGUARDING CONSTRUCTION,
ALTERATION AND DEMOLITION OPERATIONS.
· VA TECHNICAL INFORMATION LIBRARY (TIL)
· USP-797 & 800
6. CONTRACTOR SHALL COORDINATE AND SEQUENCE DEMOLITION,
CLEANING, AND CONSTRUCTION WORK.
7. CONTRACTOR SHALL NOTE ANY SPECIAL REQUIREMENTS FOR
INSTALLATION OF WORK UNDER THIS CONTRACT. DISMANTLE AND
REASSEMBLE EQUIPMENT AS NECESSARY FOR ENTRY INTO THE BUILDING
AND THE LOCATION OF INSTALLATION.
8. THE CONTRACTOR SHALL MAINTAIN A COMPLETE PROJECT SCHEDULE AND
SHALL UPDATE THIS SCHEDULE WEEKLY. ANY CHANGES SHALL BE NOTED
AND AN UPDATED SCHEDULE SHALL BE PROVIDED TO THE OWNER.
9. ALL PERMITS, FEES, TAXES, ETC SHALL BE PAID BY CONTRACTOR AS PART
OF THE TOTAL PROJECT COST.
10. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS,
PARTITIONS, CEILINGS, AND FLOORS. SEAL ALL PENETRATIONS THROUGH
RATED ASSEMBLIES WITH FIRESTOP MATERIAL IN ACCORDANCE WITH U.L.
REQUIREMENTS TO MAINTAIN THE ASSEMBLY RATING.
11. CONTRACTOR SHALL FURNISH U.L. APPROVED DRAWINGS FOR EACH TYPE
OF FIRE AND SMOKE RATED ASSEMBLY PENETRATION BY DUCTS, PIPES, OR
CONDUITS, AND SHALL DISPLAY THESE DRAWINGS ON THE JOB SITE AT ALL
TIMES DURING CONSTRUCTION.
12. CONTRACTOR SHALL REFER TO ALL DETAILS FOR PROPER GUIDANCE.
13. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT
SUBMITTALS FOR ALL PRODUCTS USED ON PROJECT.
14. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE
CONTRACTOR OF RESPONSIBILITY FOR DEVIATIONS FROM THE
REQUIREMENTS OF CONTRACT DOCUMENTS UNLESS THE CONTRACTOR
HAS RECEIVED WRITTEN APPROVAL FROM THE ENGINEER TO THE SPECIFIC
DEVIATION. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT
RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR ERRORS OR
OMISSIONS IN HIS OR HER SUBMITTAL DATA.
15. THE CONTRACTOR IS REQUIRED TO SUBMIT THREE COMPLETE O&M
MANUALS IN THREE RING BINDERS AT SUBSTANTIAL COMPLETION.
MANUALS SHALL INCLUDE INSTALLATION AND MAINTENANCE DATA ON ALL
NEW EQUIPMENT AND MATERIALS, CERTIFIED TECHNICAL PRODUCT DATA,
EQUIPMENT SHOP DRAWINGS, SPARE PARTS DATA, ETC. PROVIDE AN
INDEX AND ASSOCIATED DIVIDERS.
16. CLOSE OUT DOCUMENTS: THE CONTRACTOR IS TO MAINTAIN ONE SET OF
CONSTRUCTION DRAWINGS ON SITE AND KEEP CURRENT WITH MARK UP
AS-BUILT CONDITIONS DURING CONSTRUCTION OF THE PROJECT. THIS SET
IS TO INCLUDE ALL CONTRACT CHANGES, MODIFICATIONS, AND
CLARIFICATIONS. THIS SET ALONG WITH ALL SHOP DRAWINGS SHALL BE
TURNED OVER TO THE ARCHITECT/ENGINEER AFTER CONSTRUCTION
COMPLETION.
17. IT IS THE RESPONSIBILITY OF ALL BIDDERS TO THOROUGHLY REVIEW AND
UNDERSTAND ALL CONSTRUCTION DOCUMENTS. THIS INCLUDES BUT IS
NOT LIMITED TO ALL DRAWINGS, SPECIFICATION SECTIONS, ETC. THE
DRAWINGS ARE SCHEMATIC IN NATURE. THEREFORE BEFORE STARTING
ANY WORK, THE CONTRACTOR SHALL REVIEW ALL OTHER CONSTRUCTION
DOCUMENTS, VERIFY FIELD CONDITIONS AND SHALL MAKE ANY REQUIRED
MINOR ADJUSTMENTS WITHOUT EXTRA COST TO THE OWNER. ANY MAJOR
DISCREPANCIES FOUND SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT/ENGINEER. THE BASE BID SHALL REFLECT THE TOTAL COST OF
NEW EQUIPMENT INSTALLATION. THIS INCLUDES LABOR, EQUIPMENT AND
MATERIALS. NO CHANGE ORDERS SHALL BE ISSUED WITHOUT WRITTEN
CONSENT AND APPROVAL FROM ENGINEER AND ARCHITECT.
1. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF FIELD CONDITIONS
PRIOR TO BEGINNING WORK AND ORDERING EQUIPMENT, AND FOR
COORDINATING NEW EQUIPMENT DIMENSIONS AND MEANS AND
METHODS FOR INSTALLATION WITH FIELD CONDITIONS.
2. CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH EXISTING
EQUIPMENT TO ENSURE ALL INLET/OUTLET CONNECTIONS COORDINATE
WITH FIELD INSTALLED DUCTWORK AND MAKE ANY NECESSARY DUCT
MODIFICATIONS TO ENSURE PROPER OPERATION OF MECHANICAL
EQUIPMENT.
3. ALL DUCT CONSTRUCTION, INSTALLATION, AND SUPPORTS ARE TO
COMPLY WITH LATEST EDITION OF SMACNA'S HVAC DUCT
CONSTRUCTION STANDARDS METAL AND FLEXIBLE DUCT. ALL
DUCTWORK SHALL BE 2" PRESSURE CLASS UNLESS OTHERWISE NOTED.
4. ROUND DUCTS AND FITTINGS SHALL BE 18 GAUGE STAINLESS STEEL, ALL
WELDED.
5. CONTRACTOR SHALL PROVIDE A COPY OF THE TEST AND BALANCE
REPORT BY AN AABC OR NEBB CERTIFIED AGENCY. THIS REPORT MUST
BE REVIEWED AND APPROVED BY THE ENGINEER PRIOR TO THE FINAL
INSPECTION. THE CONTRACTOR MUST ALSO PROVIDE ALL REPORTS
REQUIRED BY THE SPECIFICATION. OUTDOOR TEMPERATURE (DB);
OUTSIDE AIR (DB/WB & CFM); SUPPLY AIR AT UNIT DISCHARGE (DB/WB &
CFM); RETURN AIR {MIXED} (DB/WB & CFM); LEAVING COIL (DB/WB);
DIFFUSER/GRILLE (DB/WB); EQUIPMENT (EWT/LWT); EQUIPMENT
(EAT/LAT); EQUIPMENT (GPM); EQUIPMENT (PRESSURES). OUTSIDE AIR
CFM SHALL BE MEASURED DIRECTLY AND NOT CALCULATED FROM THE
DIFFERENCE BETWEEN SUPPLY AIR CFM AND RETURN AIR CFM.
6. CONTRACTOR SHALL MAKE NECESSARY ADJUSTMENTS DURING TEST
AND BALANCE AS REQUIRED TO ENSURE EQUIPMENT IS OPERATING
WITHIN 10% OF THE SPECIFIED CRITERIA. THIS INCLUDES, BUT IS NOT
LIMITED TO, ADJUSTING BELTS, SHEAVES, PULLEYS, AND IMPELLERS.
7. INTENT OF MECHANICAL NOTES ON DRAWINGS IS TO CLARIFY THE
SCOPE OF WORK AND ALERT CONTRACTOR OF EXISTING CONDITIONS.
CONTRACTOR IS TO VISIT THE SITE AND VERIFY ALL CLEARANCES
BEFORE FABRICATION OF DUCTWORK, AND PROVIDE ADDITIONAL
OFFSET AND/OR CHANGES IN DUCT SIZES TO MEET FIELD CONDITIONS.
8. CONTRACTOR SHALL PROVIDE ALL SUPPLEMENTARY STEEL,
STRUCTURES, INSERTS, SLEEVES, AND HANGING DEVICES REQUIRED TO
INSTALL AND ADEQUATELY SUPPORT MECHANICAL EQUIPMENT AND
COMPONENTS IN A MANNER WHICH WILL NOT OVERLOAD BUILDING
STRUCTURE. CONTRACTOR SHALL COORDINATE WITH GENERAL
CONTRACTOR AND ALL BUILDING TRADES TO AVOID CONFLICTS AND TO
MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY.
9. DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE
DIMENSIONS (FREE AREA).
10. CONTRACTOR SHALL THOROUGHLY CLEAN AND ENSURE PROPER
OPERATION OF ANY EXISTING HVAC EQUIPMENT. ANY CHANGE TO THE
SYSTEM SHALL RESULT IN EQUIPMENT MODIFICATIONS (AS REQUIRED)
INCLUDING BUT NOT LIMITED TO REPLACING MOTORS, VFDS, PULLEYS,
SHEAVES, BELTS, ETC.
11. ALL EXHAUST DUCT WORK SHALL BE NON-INSULATED SHEET METAL,
UNLESS NOTED OTHERWISE.
12. PRIOR TO FINAL INSPECTION, PROVIDE RECORD DRAWINGS, SYSTEM
BALANCING REPORT, AND FINAL COMMISSIONING REPORT TO OWNER.
13. FINAL CERTIFICATION SHALL BE PROVIDED BY PROPER HOOD TESTING
AGENCY. COMMISSIONING AGENT, OWNER, AND CONTRACTOR SHALL
ALL BE PRESENT DURING FINAL CERTIFICATION. CONTRACTOR SHALL BE
RESPONSIBLE FOR APPROPRIATELY FIXING ANY ISSUES THAT MAY
PREVENT FINAL CERTIFICATION OF PHARMACY HOODS.
ABBREVIATIONS
GENERAL MECHANICAL SYMBOLS
LIMIT OF DEMOLITION
HVAC SYMBOLS
CD-XX
XXX CFM
RETURN
GRILLE
TYPE (REFER TO SCHEDULES)
CFM
RG-XX
XXX CFM
EXHAUST
GRILLE
TYPE (REFER TO SCHEDULES)
CFM
EG-XX
XXX CFM
SIDEWALL
SUPPLY GRILLE
TYPE (REFER TO SCHEDULES)
CFM
SG-XX
XXX CFM
LINEAR SLOT
DIFFUSER
TYPE (REFER TO SCHEDULES)
CFM
LSD-XX
XXX CFM
GRILLES, REGISTERS & DIFFUSERS TAG
MECHANICAL EQUIPMENT TAGS
GENERAL NOTESMECHANICAL NOTES
N.T.S.
1 EXHAUST OR RETURN BRANCH DUCTWORK
N.T.S.
2 EXHAUST DUCT CONNECTION DETAIL (BSC)
3 EXHAUST DUCT CONNECTION DETAIL (CACI)
N.T.S.
T
Sheet List Table Sheet Number Sheet Title
M001 GENERAL NOTES, LEGENDS, ABBREVIATIONS & DETAILS
M101 PARTIAL GROUND FLOOR PLAN - MECHANICAL
M401 ENLARGED PLAN - STERILE HAZ BUFFER - MECHANICAL
M402 MECHANICAL SECTION VIEWS
STOR
HAZ
ANTE
NON-HAZ
HAZ BUFFER
STERILE NON-HAZ BUFFER
STERILE
FLUID STORAGE
RECIEVING/BREAKDOWN
MISSING DOSE
1ST DOSE/
STORAGE
DISPENSING
RESEARCH
ANTE
HAZ
WORKSTATIONS
VAULT
COMPOUNDING
NON-STERILE
PREPACK
OFFICE
R.ROOM
OFFICE
MD MD
(E )2
6x
E A
M401
(E)10x6 EA
(E)9x12 EA DN
(E)26x12 EA
(E )2
6x
E A
(E)32X10 EA
(E)22X14 EA
UP TO (E) F-1B
ON ROOF
(E)32X10 EA
(E)22X14 EA
UP TO (E) F-1A
ON ROOF
M401
(E) BSC (E) BSC(E) CACI
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
/1 5/
1:
:0
AM
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD A/E:
STAMP
321 4 5 6 7 8 9 10
GUIDON MES JV II, LLC
1221 N PENNSYLVANIA ST.
INDIANAPOLIS, IN 46202
(317) 800-6388
DAVID KEITH, P.E.
AE RENOVATE PHARMACY HOOD
DUCTWORK
673-23-115
11/12/2024 PBJ MANRevisions: Date:
BID DOCUMENTS
13000 BRUCE B. DOWNS BOULEVARD
TAMPA, FL 33612
11/12/2024
M101
PARTIAL GROUND FLOOR PLAN -
MECHANICAL
M101
1 PARTIAL GROUND FLOOR PLAN - MECHANICAL
SCALE: 1/4" = 1'-0"N
PROJECT
AREA
KEY PLANN
(E )2
6x
E A
EXISTING 18x18
ACCESS PANEL
(E) EG
300 CFM
M402
(E) 12X12 EA DN TO
EXHAUST GRILLE
(E) CD
500 CFM
(TYP. OF 3)
1 1
EXISTING 18x18
ACCESS PANEL
(E) CACI
300 CFM
(E) BSC
600 CFM
(E) BSC
600 CFM
HAZ BUFFER
STERILE
EXISTING 12x12
ACCESS PANEL
(E)18x12 EA (E)12x10 EA
(E)24x12 SA
2 2
EXISTING 18x18
ACCESS PANEL
EXISTING 12x12
ACCESS PANEL
HAZ BUFFER
STERILE
(E) CD
500 CFM
(TYP. OF 3)
EXISTING 18x18
ACCESS PANEL
(E) 12X12 EA DN TO
EXHAUST GRILLE
M402
(E) EG
300 CFM (E
)2 6x
E
A (E)18x12 EA (E)12x10 EA
EXISTING 18x18
ACCESS PANEL
(E)24x12 SA
(E) CACI
300 CFM
(E) BSC
600 CFM
(E) BSC
600 CFM
4 4
5 5
1'-6"
TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
/1 5/
1:
:0
AM
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD A/E:
STAMP
321 4 5 6 7 8 9 10
GUIDON MES JV II, LLC
1221 N PENNSYLVANIA ST.
INDIANAPOLIS, IN 46202
(317) 800-6388
DAVID KEITH, P.E.
AE RENOVATE PHARMACY HOOD
DUCTWORK
673-23-115
11/12/2024 PBJ MANRevisions: Date:
BID DOCUMENTS
13000 BRUCE B. DOWNS BOULEVARD
TAMPA, FL 33612
PROJECT
AREA
KEY PLANN
11/12/2024
M401
ENLARGED PLAN - STERILE HAZ
BUFFER - MECHANICAL
M401
1 ENLARGED PLAN - MECHANICAL DUCTWORK - DEMOLITION
SCALE: 1/2" = 1'-0"
M401
2 ENLARGED PLAN - MECHANICAL DUCTWORK - NEW WORK
SCALE: 1/2" = 1'-0"N
N
M401
3 IMAGE - EXISTING PHARMACY HOODS LAYOUT
N.T.S.
M401
4 IMAGE - EXISTING FLEXIBLE DUCT IN CEILING CAVITY
N.T.S.
M401
5 IMAGE - EXISTING CLEARANCE BEHIND HOOD TO ADJACENT WALL
N.T.S.
A. EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, GRILLES, AND ASSOCIATED
COMPONENTS SHOWN ON DRAWINGS ARE APPROXIMATE LOCATIONS AND ARE
PROVIDED FOR REFERENCE USE ONLY. FIELD VERIFY AND COORDINATE WITH EXACT
LOCATIONS, ELEVATIONS, SIZES, AND CONDITIONS OF EXISTING COMPONENTS.
B. ALL EXISTING EQUIPMENT TO BE REUSED SHALL BE PRESSURE TESTED, THOROUGHLY
CLEANED, AND SANITIZED TO AVOID POSSIBLE CONTAMINATION.
C. ALL EXISTING EQUIPMENT REMOVED SHALL BE TURNED OVER TO OWNER.
D. CEILING SHALL BE PROPERLY PROTECTED DURING CONSTRUCTION. CONTRACTOR
SHALL REPAIR ANY DAMAGE DURING CONSTRUCTION TO MATCH EXISTING CEILING.
GENERAL NOTES
KEYNOTES -
EXISTING EXHAUST DUCTWORK SHALL BE DEMOLISHED FROM PHARMACY HOOD
TRANSITION PIECE UP TO EXISTING BRANCH DUCT. CAP EXISTING OPENING DURING
CONSTRUCTION. REFER TO SECTION VIEW ON DRAWING M402 FOR MORE
INFORMATION.
CONTRACTOR SHALL REMOVE EXISTING HOOD FROM SPACE DURING DEMOLITION AND
CONSTRUCTION. EXISTING HOOD SHALL BE PROTECTED FROM DAMAGE, DUST, AND
DEBRIS THROUGHOUT ENTIRETY OF CONSTRUCTION WORK.
NEW TELESCOPIC ADJUSTABLE SLEEVE SHALL BE INSTALLED AT CEILING
PENETRATION. CONNECT NEW EXHAUST DUCTWORK TO NEW LOW-PROFILE
TRANSITION AT EXISTING PHARMACY HOOD. REFER TO SECTION VIEW ON DRAWING
M402 FOR MORE INFORMATION.
EXISTING HOOD HEPA FILTER SHALL BE REMOVED AND REPLACED WITH NEW HEPA
FILTER AT COMPLETION OF CONSTRUCTION.
EXISTING SUPPLY GRILLE HEPA FILTER SHALL BE REMOVED AND REPLACED WITH NEW
HEPA FILTER AT COMPLETION OF CONSTRUCTION.
HOODS SHALL HAVE A MINIMUM CLEARANCE OF ~1'-6" BEHIND HOOD TO ADJACENT
WALL TO ALLOW FOR PROPER CLEANING OF SPACE IN ORDER TO COMPLY WITH USP
STANDARDS. CONTRACTOR SHALL OFFSET EXHAUST DUCTWORK ABOVE CEILING AS
REQUIRED TO ALIGN WITH HOOD EXHAUST OPENING. (TYPICAL FOR ALL THREE (3)
PHARMACY HOODS)
(E )8
"Ø E
A
(E)10"Ø EA
(E)12x10 EA(E)26x12 EA (E)18x12 EA
EXISTING BSC EXISTING BSC
EXISTING CACI
(E)12x10 BRANCH
DUCT
(E)12x10 BRANCH
DUCT
(E)12x10 BRANCH
DUCT
CEILING 2 2
3 3
HAZ BUFFER
STERILE 1
8" Ø
E A
(E)12x10 EA(E)26x12 EA (E)18x12 EA
EXISTING BSC
EXISTING CACI
(E)12x10 BRANCH
DUCT
(E)12x10 BRANCH
DUCT
(E)12x10 BRANCH
DUCT
CEILING 4
8" Ø
E A
HAZ BUFFER
STERILE
EXISTING BSC
"Ø
E A
"Ø
E A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
/1 5/
1:
:0
AM
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD A/E:
STAMP
321 4 5 6 7 8 9 10
GUIDON MES JV II, LLC
1221 N PENNSYLVANIA ST.
INDIANAPOLIS, IN 46202
(317) 800-6388
DAVID KEITH, P.E.
AE RENOVATE PHARMACY HOOD
DUCTWORK
673-23-115
11/12/2024 PBJ MANRevisions: Date:
BID DOCUMENTS
13000 BRUCE B. DOWNS BOULEVARD
TAMPA, FL 33612
PROJECT
AREA
KEY PLANN
11/12/2024
M402
MECHANICAL SECTION VIEWS
M402
2 SECTION VIEW - MECHANICAL DUCTWORK - NEW WORK
SCALE: 1/2" = 1'-0"
M402
1 SECTION VIEW - MECHANICAL DUCTWORK - DEMOLITION
SCALE: 1/2" = 1'-0"
A. EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, GRILLES, AND ASSOCIATED
COMPONENTS SHOWN ON DRAWINGS ARE APPROXIMATE LOCATIONS AND ARE
PROVIDED FOR REFERENCE USE ONLY. FIELD VERIFY AND COORDINATE WITH EXACT
LOCATIONS, ELEVATIONS, SIZES, AND CONDITIONS OF EXISTING COMPONENTS.
B. ALL EXISTING EQUIPMENT TO BE REUSED SHALL BE PRESSURE TESTED, THOROUGHLY
CLEANED, AND SANITIZED TO AVOID POSSIBLE CONTAMINATION.
C. ALL EXISTING EQUIPMENT REMOVED SHALL BE TURNED OVER TO OWNER.
D. CEILING SHALL BE PROPERLY PROTECTED DURING CONSTRUCTION. CONTRACTOR
SHALL REPAIR ANY DAMAGE DURING CONSTRUCTION TO MATCH EXISTING CEILING.
DEMOLISH EXISTING EXHAUST DUCTWORK BACK TO EXISTING BRANCH DUCT.
PROTECT EXISTING OPENING DURING CONSTRUCTION.
REMOVE EXISTING HOOD CANOPY TRANSITION PIECE AND RETURN TO OWNER.
STORE EXISTING PHARMACY HOOD IN A PROTECTED AREA AWAY FROM
CONSTRUCTION DUST AND DEBRIS.
STORE EXISTING AIRFLOW ALARM TO PROTECT FROM ANY CONSTRUCTION DUST AND
DEBRIS.
LOCATE EXISTING PHARMACY HOOD IN APPROPRIATE AREA OF EXISTING SPACE.
COORDINATE WITH OWNER. INSTALL GERMFREE "LOW-PROFILE TRANSITION" ON
EXISTING CABINET AND CONNECT TO NEW TELESCOPIC ADJUSTABLE SLEEVE AT
CEILING.
EXISTING AIRFLOW ALARM SHALL BE RE-INSTALLED IN NEW 10"Ø EXHAUST
DUCTWORK BELOW CEILING AND POWER SHALL BE RECONNECTED.
NEW TELESCOPIC ADJUSTABLE SLEEVE SHALL BE INSTALLED IN CEILING AND
CONNECT TO LOW-PROFILE TRANSITION. SLEEVE SHALL BE STAINLESS STEEL.
AIR-TIGHT, HYGIENIC SILICONE FLEXIBLE CEILING SEAL. EQUAL TO CSI "PIPETITE
STANDARD" MODEL.
GENERAL NOTES
KEYNOTES -
| G100 COVER SHEET |
| Model |
| G101 INFECTION CONTROL RISK ASSESSMENT PLAN |
| A101 FLOOR PLAN |
| Model |
| M001 GENERAL NOTES, LEGENDS, ABBREVIATIONS & DETAILS |
| M101 PARTIAL GROUND FLOOR PLAN - MECHANICAL |
| M401 ENLARGED PLAN - STERILE HAZ BUFFER - MECHANICAL |
| M402 MECHANICAL SECTION VIEWS |