Original Drawings - Main Entry Control Point - Alpena CRTC.pdf

PDF 635 KB Posted

Attached to
TDVG242001 Repair Main Entry Control Point (ECP) Driving Lane Overhang - Alpena CRTC, MI
Solicitation number
W50S8624R0002
Issued by

About this file

This document appears to be the original drawings for the Main Entry Control Point (ECP) at Alpena CRTC in Alpena, MI. The drawings provide detailed structural and architectural plans for the renovation of the existing ECP covered drive, including foundation, framing, roof, and exterior elevation details.

The related federal contract opportunity is a solicitation (W50S8624R0002) issued by the Department of the Army National Guard to repair the existing Main ECP driving lane overhang at Alpena CRTC. The scope of work includes providing all required personnel, equipment, tools, materials, supervision, and quality control to replace the damaged overhead drive entrance structure. This requirement is set aside for Small Business concerns under NAICS code 238160 (Sheet Metal Roofing Installation), with a size standard of $19.0M. Proposals are due by April 30, 2024 at 11:00 AM EST, and a site visit is highly encouraged on April 11, 2024 at 1:00 PM EST. The contract award will be made to the responsible offeror whose proposal is most advantageous to the Government, considering price and non-price related factors.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CRIPPLE STUD

TRACK PIECE

BASE TRACK

ADDITIONAL

ANCHORAGE

HEADER TRACKS

INFILL STUD

JAMB

THICKNESS

43 mil MIN.

COLD-ROLLED

CHANNEL

CLIP ANGLE

[LENGTH = 80% OF STUD DEPTH (d)]

SCREW

ATTACHMENT

STUD

BASE TRACK

LOW VELOCITY FASTENER

WALL SECTION

NO SCALE

DOOR DETAIL

NO SCALE

LATERAL BRACING DETAIL

NO SCALE

STRUCTURAL PLAN

SCALE: 14" = 1'-0"

'-0

'-0

1'-0"4'-0"

'-0

'-0

'-0

1'-0"4'-0"1'-0"

'-0

'-0

2'-0"

1'-0"

'-0

'-0 " D

O R M

ER

'-0

4'-0"

L-1

L -4

L -2

L-3

L-3

B -1

W 8x15 W/ 38"x11" PLATE W 8x15 W/ 38"x11" PLATE W 8x15 W/ 38"x11" PLATE

NOTE'S:

- ALL BEAMS SHALL BEAR A MIN. OF 8" ON MASONRY WALL

L-3 L-2

NO.

W 8x15B-1

L-1

SIZE REMARKS

107'-4" B.O.S.

110'-0" T.O.S.

ELEVATION

BEAM SCHEDULE

STRUCTURAL LOADS

ROOF LL = 20psf ROOF DL = 18 psf FLOOR LL = 100psf OR 2,000#

CONCENTRATED LOAD

WIND HORIZ. - WALL = 18psf WIND VERT. - ROOF = -15psf WIND VERT. - OVERHANG = -22psf SNOW - GROUND = 50psf Ce = 1.0 Ct = 1.1 SNOW - FLAT = 39psf SNOW - SLOPED = 33psf SNOW - UNBALANCED = 49psf

FLOODING = NOT APPLICABLE

SEISMIC BASE SHEAR = NOT APPLICABLE

LOAD COMBINATIONS:

D + S + L D + S + W 0.6D + W

STRUCTURAL STEEL SPECIFICATIONS

13'-4"

15'-4"

'-8

PR

E-

EN

G

IN

EE

R

ED

L

IG

H T

G A U G

E M

ET

A L

TR

U S S

TY

PE

'A

'-0

" O .C

PR

E-

EN

G

IN

EE

R

ED

L

IG

H T

G A U G

E M

ET

A L

TR

U S S

TY

PE

'B

'-0

" O .C

107'-4" B.O.S.

107'-4" B.O.S.

INSTALL #8 VERTICAL RE-ROD

GROUTED SOLID IN EACH CELL

(TYP. 2 LOCATIONS)

INSTALL #5 VERTICAL RE-ROD

GROUTED SOLID @ 4'-0" O.C.

& AT ALL OPENINGS (U.N.O.)

AND ALL CORNERS

INSTALL (1) #5

VERTICAL RE-ROD

GROUTED SOLID

'-0

'-0

1'-0" 1'-0"

22'-0"

B-2

B-2

F -1

B-1 T.S. 12x6x12" 110'-0" T.O.S.

F-1 T.S. 6"x6"x1

4" TUBE STEEL FRAME - SEE ELEV. THIS SHEET

PRE-ENGINEERED LIGHT GAUGE METAL TRUSS

TYPE 'C' @ 2'-0" O.C.

L-4 W 8x24 W/ 38"x11" PLATE 107'-4" B.O.S.

2"x7

2"x

8" BEARING PLATE

2"x7

2"x

8" BEARING PLATE

2"x7

2"x

8" BEARING PLATE

2"x7

2"x

8" BEARING PLATE

2"x7

2"x

8" BEARING PLATE

2"x7

2"x

8" BEARING PLATE

3/8" x 7 1/2" SQ. BEARING PL.

(2) 12"Ø x 6" LG. HEADED A.B.

WELDED TO PLATE

FULL MORTAR BED BETWEEN

GROUTED UNITS

FILL 2nd COURSE x 24" WIDE w/GROUT FOR BEAMS 8" DEEP

OR GREATER

FILL 3rd COURSE x 32" WIDE w/GROUT FOR BEAMS 12" DEEP

OR GREATER

(3) GALV. STRAP ANCHORS

FOR BEAMS 12" DEEP OR

GRATER

HORIZ. JOINT REINF. REQ'D

FOR MIN. 3 FT/ FROM EDGE OF

WALL FOR BEAMS 12" DEEP OR

GREATER. (IF NORMAL WALL

HORIZ. JOINT REINF. IS NOT AT

THIS COURSE)

HORIZ. JOINT REINF. REQ'D

FOR MIN. 3 FT. FROM EDGE OF

WALL ON ALL SIZE BEAMS (IF

NORMAL WALL HORIZ. JOINT

REINF. IS NOT AT THIS COURSE

(2) 16 GA. 2"x12" GALV. STRAP

ANCHORS FOR BEAMS 8" DEEP

OR GREATER

FILL TOP COURSE x 16" WIDE

W/ GROUT -ALL BEAMS.

2 - 3

16" FILLET BOTH SIDES (ONE

END OF BEAM ONLY).

BEAM BEARING DETAILS

NO SCALE

1 2

G R O

U T

(2) 12"Ø x 6" LG. HEADED A.B.

WELD TO PLATE

3-3/4" 3-3/4"

-1

/2

-1

/2

BEAM PERPENDICULAR TO WALL

MASONRY WALL -SEE PLAN FOR

SIZE

BEARING PLATE -SEE PLAN OR

SCHEDULE FOR SIZE &

ANCHORAGE. MIN. 7x7x3

8"

BEARING PLATE IF NOT CALLED

OUT IN SCHEDULE

BEAM - SEE FRAMING PLAN

FOR SIZE.

GROUT CORES SOLID UNDER

BRG. PLATE

16 GA. 2"x12" GALV.

MASONRY STRAP ANCHORS

BEAM PARALLEL TO WALL

BEAM - SEE FRAMING PLAN

FOR SIZE.

PLAN

TRUSS TYPE 'A'

TRUSS TYPE 'B'

TRUSS TYPE 'C'

8"1

2"

5'-27 8" 10'-8" 5'-27

8"

2"75

8"

'-2

3 8

H

EE

L

5'-81 8"5'-27

8"

8"

3'-27 8"7'-111

4"

2"

'-2

3 8

H

EE

L

3 8

H

EE

L

1 4

1 4

8'-0" 3'-27 8"

8"

3'-27 8"

8"

1 4

3 8

H

EE

L

TRUSS ELEVATIONS

SCALE: 14" = 1'-0"

SCALE: 12" = 1'-0"

FRAME ELEVATION1

S-100S-100

6"x6"x1

4" T.S. FRAME

12"x12"x 12" BASE PLATE

W/ (2) 34"Ø ANCHOR

BOLTS & HEAVY DUTY 34"

NUT & WASHER

NON-SHRINK GROUT

11 2

1 2

'-4

'-0 " 6" 7'-6" 6"

B-2

'-0

FP

2 REQ.

8" HOLE IN PLATE (TYP. 2)

4"

ISSUED FOR:

CHECKED BY

JOB NUMBER

6 - 20 - 03

SHEET NUMBER

DATE

DRAWN BY

SHEET TITLE

CLIENT AND PROJECT

TDVG022261

S.L. / B.B.

T.B.

UPGRADE BASE MAIN

ENTRANCE

ALPENA CRTC

ALPENA, MI.

147 W. MAIN ST. SUITE 303

GAYLORD, MICHIGAN 49735

989.731.4343 PHONE

989.731.5037 FAX

ARCHITECTURE

BRADLEY J.

BUTCHER AND

PLANNING

www.butcherandassociates.com bjbarchitects@voyager.net

ASSOCIATES, P.C.

COPYRIGHT © 2003

THIS DRAWING AND DESIGN ARE THE PROPERTY OF

BUTCHER & ASSOCIATES, P.C. NO ALTERATIONS

AND/OR TRANSFERS OF WORK ARE PERMITTED,

UNLESS WRITTEN PERMISSION IS GRANTED BY

BUTCHER AND ASSOCIATES, P.C. VIOLATORS WILL BE

PROSECUTED TO THE FULLEST EXTENT OF THE LAW.

CONSTRUCTION DWGS.

PERMITS DWGS.

BIDS DWGS.

PRELIMINARY DWGS.

C I V I L + S T R U C T U R A L

758 ISENHAUER GRAYLING, MICHIGAN 49738

PH. 989-348-5000 FAX: 989-348-5005

LANGSETH

engineering

06-20-03 100 % SUBMITTAL

STRUCTURAL PLAN

MISC. DETAILS

AutoCAD SHX Text S-100

3'-6"

3'-4" M.O.

15'-4"

MECH.

10'-0" M.O.

13'-4"

'-7

5 8

'-8

1'-8"

3'-10"

'-4

" M .O

'-0 3 8

1'-0"

B

3'-8"

1'-0"

R.R.

'-8

SEC.

OP.

'-3 5 8

'-8

5'-10"

1'-8"

'-0

'-4

" M .O

'-0 3 8

'-4

7 8

'-0

A

B

1'-0"

'-0

'-0

'-4

1'-8" 2'-0" M.O. 3'-83

8"

7'-4" 6"

'-0

1'-0"

C

'-4

3 8

'-1

5 8

'-4

1'-43 8"5'-35

8"8'-8"

F.D.

'-0

'-8

FIRE EXT.

CABINET - SEE

DETAIL G/300

F.D.

F.D.

8"

MECH. EQUIP.

M.D.P.

BACK

BOARD

3'-4" HIGH

SCREEN WALL

25'-0"

A A-300

A A-300

B A-301

B A-300

B A-300

2'-0"

SCALE: 14" = 1'-0"

FLOOR PLAN (294.67 S.F.)

INSTALL 2" GROMMET IN

COUNTER AT EACH COMPUTER

STATION

5 8

A-600

A-600

A-600

A-600

8"3'-67

8"

12'-0" 6'-4"

2'-2" 2'-0" 2'-2"

'-0

'-0

'-0

'-2

'-2

'-6

3 8 " R

AD

'-0

E A-302

F A-302

C A-300

C A-300

DOWNSPOUT

DOWNSPOUT

A-600

13'-4"3'-4" 5'-4"

'-4

'-0

'-0

'-0

1'-0"1'-0"

6" 6"

FOUNDATION PLAN

SCALE: 14" = 1'-0"

'-1

A A-300

A A-300

'-4

'-0

'-0

'-0

'-0

'-8

'-8

2'-0"

6'-8"8'-8"

15'-4"

25'-0"

4" CONCRETE SLAB W/ IN-FLOOR

HEAT W/ W.W.F. 6x6 W 2.0xW 2.0

ON 'INSUL-TARP' INSULATION ON 4"

MIN. SAND FILL COMPACTED TO

95% DENSITY ON 15 MIL VAPOR

BARRIER ON 4" OF ADDITIONAL

COMPACTED SAND FILL

6" CONCRETE SLAB W/ SNOW-MELT

HEAT W/ W.W.F. 6x6 W 2.0xW 2.0

ON 'INSUL-TARP' INSULATION ON 6"

MIN. SAND FILL COMPACTED TO

95% DENSITY

F.D.

F.D.

F.D.

B A-301

B A-300

B A-300

'-6

3 8 " R

AD

12'-0" 6'-4"

2'-2" 2'-0" 2'-2"

'-2

'-0

'-2

'-0

'-0

12" POURED CONCRETE

FOUNDATION WALL ON 2'-0"X12"

CONTINUOUS CONCRETE FOOTING

(SEE DETAILS FOR REINFORCING)

'-0

C A-300

C A-300

24"x24" CONC. PIER (TYP. 2

LOCATIONS) W/ (2) # 5

VERTICAL RE-ROD TYP.

36"x36" CONC. FOOTING W/

(3) #5 E.W. BOTTOM ONLY

(TYP. 2 LOCATIONS)

ISSUED FOR:

FOUNDATION PLAN

FLOOR PLAN

147 W. MAIN ST. SUITE 303

GAYLORD, MICHIGAN 49735

989.731.4343 PHONE

989.731.5037 FAX

ARCHITECTURE

BRADLEY J.

BUTCHER AND

PLANNING

UPGRADE BASE MAIN

ENTRANCE

ALPENA CRTC

ALPENA, MI.

CHECKED BY

TDVG022261

JOB NUMBER

6 - 20 - 03

SHEET NUMBER

DATE

B.B.

T.B.

DRAWN BY

SHEET TITLE

CLIENT AND PROJECT

www.butcherandassociates.com bjbarchitects@voyager.net

COPYRIGHT © 2003

THIS DRAWING AND DESIGN ARE THE PROPERTY OF

BUTCHER & ASSOCIATES, P.C. NO ALTERATIONS

AND/OR TRANSFERS OF WORK ARE PERMITTED,

UNLESS WRITTEN PERMISSION IS GRANTED BY

BUTCHER AND ASSOCIATES, P.C. VIOLATORS WILL BE

PROSECUTED TO THE FULLEST EXTENT OF THE LAW.

ASSOCIATES, P.C.

CONSTRUCTION DWGS.

PERMITS DWGS.

BIDS DWGS.

PRELIMINARY DWGS.

06-20-03 100 % SUBMITTAL

http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com

A-100

REFLECTED CEILING PLAN

SCALE: 14" = 1'-0"

8" GYPSUM CEILING

BOARD

VENTILATED METAL

SOFFIT

2'x2' ACOUSTICAL

CEILING TILE

DROPPED BULKHEAD WRAPED W/

STEEL - COLOR TO MATCH ROOF

22"x36" INSULATED

ATTIC ACCESS

DOOR

LINEAR MECHANICAL

S.A. GRILLES

(TYPICAL)

RECESSED CAN

LIGHT FIXTURE

(TYPICAL)

2'x2' LIGHT FIXTURE

(TYPICAL)

MECHANICAL S.A.

GRILLEMECHANICAL

EXHAUST VENT

EXHAUST FAN

SURFACE MOUNT

LIGHT FIXTURE

SCALE: 14" = 1'-0"

ROOF PLAN

SEE SHEET A-301 FOR ROOF

RIDGE, HIP, VALLEY & PENETRATION

DETAILS

STANDING SEAM METAL

ROOFING

LINE OF BUILDING BELOW

- ALL VENT PIPING SHALL BE FLASHED AND SEALED

PER ROOFING MANUFACTURERS RECOMMENDATIONS.

- ALL PENETRATIONS SHALL BE CENTERED BETWEEN

TWO RIBS OF THE NEAREST ROOF PANEL ONLY.

- ALL FLASHING SHALL BE SUPPLIED BY PLUMBING

CONTRACTOR.

- ALL VENT PIPE, FLUES, ETC. PENETRATING THE ROOF

SHALL BE PAINTED TO MATCH THE ROOF COLOR.

5 / 12 SLOPE

S

LO

PE

S

LO

PE

S

LO

PE

S

LO

PE

5 / 12 SLOPE

INSTALL ICE & WATER SHIELD

MIN. 2'-0" EACH SIDE OF

VALLEYS

4'-0" 1'-0"

'-0

'-0

'-0

'-0

'-0

4'-0" 1'-0"2'-0"1'-0"

'-0

'-0

'-0 " D

O R M

ER

'-0

'-0

4'-0"1'-0"

6" STEEL GUTTER - COLOR TO

MATCH ROOF PANELS (TYP.

ALL SIDES)

1'-0"1'-0"

CONTINUOUS RIDGE

VENT (TYPICAL)

'-0

'-0

ISSUED FOR:

ROOF PLAN

REFLECTED CEILING PLAN

147 W. MAIN ST. SUITE 303

GAYLORD, MICHIGAN 49735

989.731.4343 PHONE

989.731.5037 FAX

ARCHITECTURE

BRADLEY J.

BUTCHER AND

PLANNING

UPGRADE BASE MAIN

ENTRANCE

ALPENA CRTC

ALPENA, MI.

CHECKED BY

TDVG022261

JOB NUMBER

6 - 20 - 03

SHEET NUMBER

DATE

B.B.

T.B.

DRAWN BY

SHEET TITLE

CLIENT AND PROJECT

www.butcherandassociates.com bjbarchitects@voyager.net

COPYRIGHT © 2003

THIS DRAWING AND DESIGN ARE THE PROPERTY OF

BUTCHER & ASSOCIATES, P.C. NO ALTERATIONS

AND/OR TRANSFERS OF WORK ARE PERMITTED,

UNLESS WRITTEN PERMISSION IS GRANTED BY

BUTCHER AND ASSOCIATES, P.C. VIOLATORS WILL BE

PROSECUTED TO THE FULLEST EXTENT OF THE LAW.

ASSOCIATES, P.C.

CONSTRUCTION DWGS.

PERMITS DWGS.

BIDS DWGS.

PRELIMINARY DWGS.

06-20-03 100 % SUBMITTAL

A-101

NORTH ELEVATION

EAST ELEVATION

SCALE: 14" = 1'-0"

SCALE: 14" = 1'-0"

WEST ELEVATION

SCALE: 14" = 1'-0"

SOUTH ELEVATION

B

B

A

C

STANDING SEAM METAL

ROOFING

E.I.F.S.

1x8 FRIEZE BOARD WRAPPED

W/ METAL - COLOR TO MATCH

ROOF

BRICK ACCENT BAND

BRICK (FIELD COLOR)

CONTINUOUS RIDGE VENT BY

ROOFING MFG. (TYPICAL)

2" LIMESTONE CAP

STEEL FASCIA - SUPPLIED &

INSTALLED BY ROOFING

CONTRACTOR - COLOR TO

MATCH ROOFING

2" LIMESTONE

CAP

1x8 FRIEZE BOARD WRAPPED

W/ METAL - COLOR TO MATCH

ROOF

BRICK (FIELD COLOR)

BRICK ACCENT BAND

CONTINUOUS RIDGE VENT BY

ROOFING MFG. (TYPICAL)

STANDING SEAM METAL

ROOFING

E.I.F.S.

STEEL FASCIA - SUPPLIED &

INSTALLED BY ROOFING

CONTRACTOR - COLOR TO

MATCH ROOFING

2" LIMESTONE CAP

1x8 FRIEZE BOARD WRAPPED

W/ METAL - COLOR TO MATCH

ROOF

BRICK (FIELD COLOR)

BRICK ACCENT BAND

CONTINUOUS RIDGE VENT BY

ROOFING MFG. (TYPICAL)

STANDING SEAM METAL

ROOFING

E.I.F.S.

STEEL FASCIA - SUPPLIED &

INSTALLED BY ROOFING

CONTRACTOR - COLOR TO

MATCH ROOFING

1x8 FRIEZE BOARD WRAPPED

W/ METAL - COLOR TO MATCH

ROOF

BRICK (FIELD COLOR)

BRICK ACCENT BAND

CONTINUOUS RIDGE VENT BY

ROOFING MFG. (TYPICAL)

STANDING SEAM METAL

ROOFING

E.I.F.S.

BRICK ACCENT BAND

B A-301

10" HIGH CAST ALUMINUM

BUILDING ADDRESS NUMBERS

(VERIFY ADDRESS W/ OWNER) -

SEE DETAIL THIS SHEET

10" HIGH CAST ALUMINUM

BUILDING ADDRESS NUMBERS

(VERIFY ADDRESS W/ OWNER) -

SEE DETAIL THIS SHEET 10" HIGH CAST ALUMINUM

BUILDING ADDRESS NUMBERS

(VERIFY ADDRESS W/ OWNER) -

SEE DETAIL THIS SHEET

E A-300

D A-300

ALPENA BASE LOGO - SEE

SPECIFICATION FOR MORE

INFORMATION

24"Ø 'DRAINABLE' LOUVER FOR

MECHANICAL EQUIPMENT - SEE

MECH. DWG.'S & SPEC.'S

10" HIGH CAST ALUMINUM -

SEE DETAIL THIS SHEET

6" HIGH CAST ALUMINUM - SEE

DETAIL THIS SHEET

8" HIGH STONE SILL - TYP.

3 WINDOWS

8" HIGH STONE SILL - TYP.

3 WINDOWS

6" STEEL GUTTER W/

CONCEALED FASTENERS -

COLOR TO MATCH ROOF

PANELS

6" STEEL DOWNSPOUT -

COLOR TO MATCH ROOF

PANELS

6" STEEL DOWNSPOUT -

COLOR TO MATCH ROOF

PANELS

6" STEEL GUTTER W/

CONCEALED FASTENERS -

COLOR TO MATCH ROOF

PANELS

C.J.

C.J.

SEE DETAIL K/301

NOTE:

ALL MECHANICAL ROOF & WALL

PENETRATIONS SHALL BE PAINTED TO

MATCH ADJACENT COLOR IF ITEM

DOES NOT COME PRE-FINISHED

STEEL FASCIA - SUPPLIED &

INSTALLED BY ROOFING

CONTRACTOR - COLOR TO

MATCH ROOFING

6" STEEL GUTTER W/

CONCEALED FASTENERS -

COLOR TO MATCH ROOF

PANELS

6" STEEL GUTTER W/

CONCEALED FASTENERS -

COLOR TO MATCH ROOF

PANELS

6" STEEL DOWNSPOUT -

COLOR TO MATCH ROOF

PANELS

BRICK ACCENT BAND

BRICK ACCENT

BAND

BRICK ACCENT BAND

ON SOUTH & WEST SIDES OF

COLUMN AND IN COVERED

WALK UP, THE BRICK ACCENT

BANDS SHALL NOT BE

RECESSED

ON SOUTH & WEST SIDES OF

COLUMN AND IN COVERED

WALK UP, THE BRICK ACCENT

BANDS SHALL NOT BE

RECESSED

1'-0"

RAKE (TYP.)

SCALE: 11

2" = 1'-0"

SIGNAGE DETAIL

DARK BRONZE LETTERS

& NUMBERS

2"

WALL LINE

ISSUED FOR:

EXTERIOR ELEVATIONS

147 W. MAIN ST. SUITE 303

GAYLORD, MICHIGAN 49735

989.731.4343 PHONE

989.731.5037 FAX

ARCHITECTURE

BRADLEY J.

BUTCHER AND

PLANNING

UPGRADE BASE MAIN

ENTRANCE

ALPENA CRTC

ALPENA, MI.

CHECKED BY

TDVG022261

JOB NUMBER

6 - 20 - 03

SHEET NUMBER

DATE

B.B.

T.B.

DRAWN BY

SHEET TITLE

CLIENT AND PROJECT

www.butcherandassociates.com bjbarchitects@voyager.net

COPYRIGHT © 2003

THIS DRAWING AND DESIGN ARE THE PROPERTY OF

BUTCHER & ASSOCIATES, P.C. NO ALTERATIONS

AND/OR TRANSFERS OF WORK ARE PERMITTED,

UNLESS WRITTEN PERMISSION IS GRANTED BY

BUTCHER AND ASSOCIATES, P.C. VIOLATORS WILL BE

PROSECUTED TO THE FULLEST EXTENT OF THE LAW.

ASSOCIATES, P.C.

CONSTRUCTION DWGS.

PERMITS DWGS.

BIDS DWGS.

PRELIMINARY DWGS.

06-20-03 100 % SUBMITTAL

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Alpena CRTC

AutoCAD SHX Text Main Gate

A-200

BUILDING SECTIONA

A-300 A-100

D

A-300

BUILDING SECTIONB

A-300 A-100 SCALE: 14" = 1'-0"

TRUSS TYPE 'B' TRUSS TYPE 'A'

D

A-302

CEILING

HUNG

FURNACE

C

A-300 A-100

COVERED DRIVE SECTION

SCALE: 14" = 1'-0"

TRUSS TYPE 'C'

IN COVERED WALK UP, THE

BRICK ACCENT BANDS SHALL

NOT BE RECESSED

3'-0"

OVERHANG

3'-0"

OVERHANG

5'-0"

OVERHANG

3'-0"

OVERHANG

5'-0"

OVERHANG

5'-0"

OVERHANG

F

A-300 A-200 SCALE: 34" = 1'-0"

WALL SECTION WALL SECTIONE

A-300 A-200 SCALE: 34" = 1'-0" SCALE: 34" = 1'-0"

WALL SECTIOND

A-300 A-300

STANDING SEAM METAL ROOFING ON 30#

ROOF FELT ON 2" RIGID INSULATION ON 1 12"

22 GA. METAL DECKING ON PRE-ENGINEERED

LIGHT GAUGE METAL TRUSSES @ 2'-0" O.C.

INSTALL PROPER VENTS BETWEEN EACH

TRUSS

12" R-38 FIBERGLASS BATT INSULATION W/

VAPOR BARRIER

STEEL FASCIA ON MODIFIED STEEL TRACK

BY TRUSS MANUFACTURER - ATTACH PER

TRUSS MANUFACTURER'S WRITTEN

RECOMMENDATIONS

FULLY VENTED STEEL SOFFIT - COLOR TO

MATCH ROOF

1x8 FRIEZE BOARD WRAPPED W/ STEEL -

COLOR TO MATCH ROOF

TREATED WOOD BLOCKING

8" GYPSUM CEILING BOARD - INSTALL

BEFORE INSTALLATION OF INTERIOR

PARTITIONS

SUSPENDED ACOUSTICAL LAY-IN CEILING

TILE

FIREBLOCKING

4" COMMON BRICK - ACCENT COLOR

4" COMMON BRICK - FIELD COLOR

4" AIR SPACE

8" MASONRY WALL W/ #5 VERTICAL REINFORCING

GROUTED SOLID @ 4'-0" O.C. W/ HORIZONTAL TRUSS

TIES EVERY OTHER COURSE

8" GYPSUM WALLBOARD ON 11

2" HAT TRACK

2" RIGID INSULATION (FRICTION FIT)

4" CONCRETE SLAB W/ IN-FLOOR HEAT W/

W.W.F. 6x6 - W2.0xW2.0 ON 'INSUL-TARP'

INSULATION ON 4" MIN. SAND FILL

COMPACTED TO 95% DENSITY ON 15 MIL

VAPOR BARRIER ON 4" OF ADDITIONAL

COMPACTED SAND FILL

2" EXPANSION JOINT MATERIAL

8" CONTINUOUS MASONRY BOND BEAM W/

(1) #5 RE-ROD GROUTED SOLID

ASPHALT PAVING

6" CONCRETE SIDEWALK W/ SNOW-MELT

HEAT W/ W.W.F. 6x6 - W2.0xW2.0 ON

'INSUL-TARP' INSULATION ON 6" MIN. SAND

FILL COMPACTED TO 95% DENSITY

2" RADIUS

4" COMMON BRICK - FIELD COLOR

4" AIR SPACE

8" MASONRY WALL W/ #5 VERTICAL REINFORCING

GROUTED SOLID @ 4'-0" O.C. W/ HORIZONTAL TRUSS

TIES EVERY OTHER COURSE

8" GYPSUM WALLBOARD ON 11

2" HAT TRACK

2" RIGID INSULATION (FRICTION FIT)

4" CONCRETE SLAB W/ IN-FLOOR HEAT W/

W.W.F. 6x6 - W2.0xW2.0 ON 'INSUL-TARP'

INSULATION ON 4" MIN. SAND FILL

COMPACTED TO 95% DENSITY ON 15 MIL

VAPOR BARRIER ON 4" OF ADDITIONAL

COMPACTED SAND FILL

2" EXPANSION JOINT MATERIAL

6" CONCRETE SIDEWALK W/ SNOW-MELT

HEAT W/ W.W.F. 6x6 - W2.0xW2.0 ON

'INSUL-TARP' INSULATION ON 6" MIN. SAND

FILL COMPACTED TO 95% DENSITY

ASPHALT PAVING

2" RADIUS

TREATED WOOD BLOCKING

8" CONTINUOUS MASONRY BOND BEAM W/

(1) #5 RE-ROD GROUTED SOLID

STANDING SEAM METAL ROOFING ON 30#

ROOF FELT ON 2" RIGID INSULATION ON 1 12" 22

GA. METAL DECKING ON PRE-ENGINEERED

LIGHT GAUGE METAL TRUSSES @ 2'-0" O.C.

12" R-38 FIBERGLASS BATT INSULATION W/

VAPOR BARRIER

STEEL FASCIA ON MODIFIED STEEL TRACK

BY TRUSS MANUFACTURER - ATTACH PER

TRUSS MANUFACTURER'S WRITTEN

RECOMMENDATIONS

8" GYPSUM CEILING BOARD - INSTALL

BEFORE INSTALLATION OF INTERIOR

PARTITIONS

1x8 FRIEZE BOARD WRAPPED W/ STEEL -

COLOR TO MATCH ROOF

FULLY VENTED STEEL SOFFIT - COLOR TO

MATCH ROOF

4" COMMON BRICK - FIELD COLOR

4" AIR SPACE

8" MASONRY WALL W/ #5 VERTICAL REINFORCING

GROUTED SOLID @ 4'-0" O.C. W/ HORIZONTAL

TRUSS TIES EVERY OTHER COURSE

8" GYPSUM WALLBOARD ON 11

2" HAT TRACK

2" RIGID INSULATION (FRICTION FIT)

4" CONCRETE SLAB W/ IN-FLOOR HEAT W/

W.W.F. 6x6 - W2.0xW2.0 ON 'INSUL-TARP'

INSULATION ON 4" MIN. SAND FILL

COMPACTED TO 95% DENSITY ON 15 MIL

VAPOR BARRIER ON 4" OF ADDITIONAL

COMPACTED SAND FILL

2" EXPANSION JOINT MATERIAL

6" CONCRETE SIDEWALK W/ SNOW-MELT

HEAT W/ W.W.F. 6x6 - W2.0xW2.0 ON

'INSUL-TARP' INSULATION ON 6" MIN. SAND

FILL COMPACTED TO 95% DENSITY

ASPHALT PAVING

2" RADIUS

TREATED WOOD BLOCKING

8" CONTINUOUS MASONRY BOND BEAM W/

(1) #5 RE-ROD GROUTED SOLID

STANDING SEAM METAL ROOFING ON 30#

ROOF FELT ON 2" RIGID INSULATION ON 1 12" 22

GA. METAL DECKING ON PRE-ENGINEERED LIGHT

GAUGE METAL TRUSSES @ 2'-0" O.C.

12" R-38 FIBERGLASS BATT INSULATION W/

VAPOR BARRIER

SUSPENDED ACOUSTICAL LAY-IN CEILING

TILE

4" COMMON BRICK - ACCENT COLOR

FIREBLOCKING

8" GYPSUM CEILING BOARD - INSTALL

BEFORE INSTALLATION OF INTERIOR

PARTITIONS

1x8 FRIEZE BOARD WRAPPED W/ STEEL -

COLOR TO MATCH ROOF

FULLY VENTED STEEL SOFFIT - COLOR TO

MATCH ROOF

#5 CONTINUOUS HORIZONTAL RE-ROD @

12" O.C.

2x4 CONCRETE KEYWAY

2'-0"x1'-0" CONCRETE FOOTING W/ (2) #5

CONTINUOUS RE-ROD

12" POURED CONCRETE FOUNDATION WALL

#5 CONTINUOUS RE-ROD TOP &

BOTTOM

2" RIGID VERTICAL INSULATION

#5 VERTICAL RE-ROD @ 4'-0" O.C. (ALL

GROUTED CELLS)

BULLET RESISTANT GLAZING & WINDOW

SOLID SURFACE WINDOW SILL

C

A-302

E

A-301

#4 DOWELS @ 12" O.C. (2'-0"x3'-0")

H

A-300

INSULATED HOLLOW METAL DOOR & FRAME

(PAINT TO MATCH ROOF)

EIFS ON PRE-ENGINEERED GABLE ROOF

TRUSS

STANDING SEAM METAL ROOFING ON 30#

ROOF FELT ON 2" RIGID INSULATION ON 1 12" 22

GA. METAL DECKING ON PRE-ENGINEERED LIGHT

GAUGE METAL TRUSSES @ 2'-0" O.C.

FULLY VENTED STEEL SOFFIT - COLOR TO

MATCH ROOF

STEEL FASCIA ON MODIFIED STEEL TRACK

BY TRUSS MANUFACTURER - ATTACH PER

TRUSS MANUFACTURER'S WRITTEN

RECOMMENDATIONS

C

A-302

8" HIGH STONE SILL

6" STEEL GUTTER W/ CONCEALED

FASTENERS - COLOR TO MATCH ROOF

PANELS

6" STEEL GUTTER W/ CONCEALED FASTENERS

- COLOR TO MATCH ROOF PANELS

72"

4"

2'-0"x1'-0" CONCRETE FOOTING W/ (2) #5

CONTINUOUS RE-ROD

#5 CONTINUOUS RE-ROD TOP &

BOTTOM

2" RIGID VERTICAL INSULATION

#5 VERTICAL RE-ROD @ 4'-0" O.C. (ALL

GROUTED CELLS)

#5 CONTINUOUS HORIZONTAL RE-ROD @

12" O.C.

12" POURED CONCRETE FOUNDATION WALL

2x4 CONCRETE KEYWAY

72"

4"

2'-0"x1'-0" CONCRETE FOOTING W/ (2) #5

CONTINUOUS RE-ROD

#5 CONTINUOUS RE-ROD TOP &

BOTTOM

2" RIGID VERTICAL INSULATION

#5 VERTICAL RE-ROD @ 4'-0" O.C. (ALL

GROUTED CELLS)

#5 CONTINUOUS HORIZONTAL RE-ROD @

12" O.C.

12" POURED CONCRETE FOUNDATION WALL

2x4 CONCRETE KEYWAY

72"

4"

8" CONTINUOUS MASONRY BOND BEAM W/

(1) #5 RE-ROD GROUTED SOLID

CONCRETE FLOOR ELEV. = 100'-0"

BOND BEAM ELEV. = 104'-8"

BOND BEAM ELEV. = 110'-0"

CEILING ELEV. = 108'-0"

CONCRETE FLOOR ELEV. = 100'-0"

BOND BEAM ELEV. = 110'-0"

T.O. DOOR ELEV. = 107'-4"

CONCRETE FLOOR ELEV. = 100'-0"

T.O. WINDOW ELEV. = 107'-4"

BOND BEAM ELEV. = 110'-0"

CEILING ELEV. = 108'-0"

BULLET RESISTANT

GLAZING & WINDOW (AT

WINDOW 'A' GLAZING IS

TO HAVE A 5° SLOPE)

T.O. FOOTING ELEV. = 96'-8"

B.O. FOOTING ELEV. = 95'-8" B.O. FOOTING ELEV. = 95'-8"

T.O. FOOTING ELEV. = 96'-8"

B.O. FOOTING ELEV. = 95'-8"

T.O. FOOTING ELEV. = 96'-8"

'-0

6"

'-0

6"

'-0

6"

SLOPE 14" PER FOOT

SLOPE 14" PER FOOTSLOPE 14" PER FOOT

2" TYP.1

2" TYP.

4" COMMON BRICK - ACCENT COLOR

1'-0"

RAKE

FIRE EXTINGUISHER

CABINET DETAILS

SCALE: 11

2" = 1'-0"

G

A-300 A-100

ATTACH CABINET PER

MANUFACTURER'S

RECOMMENDATIONS

8" GYPSUM WALLBOARD ON

6" METAL STUDS

RECESSED FIRE

EXTINGUISHER CABINET

SCALE: 1 12" = 1'-0"

DOOR HEAD

DETAILH

A-300 A-300

1x8 FRIEZE BOARD WRAPPED

W/ STEEL - COLOR TO MATCH

ROOF

TREATED WOOD BLOCKING

STEEL LINTEL - SEE SHEET

S-100 (PAINT ALL EXPOSED

STEEL)

INSULATED HOLLOW METAL

DOOR & FRAME - PAINT TO

MATCH ROOF COLOR

FULLY VENTED STEEL SOFFIT

- COLOR TO MATCH ROOF

CAULK PERIMETER

ONE-PIECE STAINLESS STEEL

METAL FLASHING

GROUT FRAME SOLID

ISSUED FOR:

BUILDING SECTION

WALL SECTIONS

MISC. DETAILS

147 W. MAIN ST. SUITE 303

GAYLORD, MICHIGAN 49735

989.731.4343 PHONE

989.731.5037 FAX

ARCHITECTURE

BRADLEY J.

BUTCHER AND

PLANNING

UPGRADE BASE MAIN

ENTRANCE

ALPENA CRTC

ALPENA, MI.

CHECKED BY

TDVG022261

JOB NUMBER

6 - 20 - 03

SHEET NUMBER

DATE

B.B.

T.B.

DRAWN BY

SHEET TITLE

CLIENT AND PROJECT

www.butcherandassociates.com bjbarchitects@voyager.net

COPYRIGHT © 2003

THIS DRAWING AND DESIGN ARE THE PROPERTY OF

BUTCHER & ASSOCIATES, P.C. NO ALTERATIONS

AND/OR TRANSFERS OF WORK ARE PERMITTED,

UNLESS WRITTEN PERMISSION IS GRANTED BY

BUTCHER AND ASSOCIATES, P.C. VIOLATORS WILL BE

PROSECUTED TO THE FULLEST EXTENT OF THE LAW.

ASSOCIATES, P.C.

CONSTRUCTION DWGS.

PERMITS DWGS.

BIDS DWGS.

PRELIMINARY DWGS.

06-20-03 100 % SUBMITTAL

http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com http://www.ArchT.com

A-300

Sheets and Views
S100
100.pdf
Sheets and Views
100
101.pdf
Sheets and Views
101
200.pdf
Sheets and Views
200
300.pdf
Sheets and Views
300

File details come from the government source that posted it. Updated .