NFFN71102201330 SOW FIGURE 1 - Cold Room Electrical With Split System Plan View (1).pdf

PDF 484 KB Posted

Attached to
Installation of Cold Room, Upgrade Electrical Panel, Add Dedicated Electrical Panel & Wire Lights & Outlets for Cold Room, and Install Split System HVAC in Cold Room at NOAA NMFS Galveston, TX
Solicitation number
NF-FN7110-22-01330MWH
Issued by

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FW

E X

H A

U S

T F

A N

E X

H A

U S

T F

A N

V E

N T

F W

V E

N T

240 120

45A Circuit for Split System A/C

100A Panel

Existing 200A Panel

Proposed Location of Cold Room

MDBC CORAL PROPAGATION PILOT STUDY

GALVESTON COLD ROOM

Proposed Location of Cold Room in The Existing Steel Framed WarehouseSCALE 1:152

2/8/2021 BEN HIGGINS

CAD

Figure 1

61'-1 1/4" '-1

99'-8"

32'-1"

'-1

'-2 o 0.4 slope of floor from outer wall to center of building

Approximately 6’-2”

Approximately 23’

8’

To Outer Wall of Steel Building

EXISTING METAL TRUSS

OF METAL WAREHOUSE

BUILDING

MDBC CORAL PROPAGATION PILOT STUDY

GALVESTON COLD ROOM

PROPOSED LOCATION OF COLD ROOMSCALE 1:4

2/8/2021 BEN HIGGINS

CAD

DRAFT

1 100A, 240V, single phase, exterior rated circuit breaker panel

2 4, 120V, 15A light switches

3 120V, 15A, 48” quad bulb, LED fixture

4 120V, 15A, 48” quad bulb, LED fixture

5 120V, 15A, 48” quad bulb, LED fixture

6 120V, 15A, 48” quad bulb, LED fixture

7 240V, 45A, Disconnect

8 36,000 BTU, 240V, 30A, split system heatpump on exterior wall of steel building

9 120V, 15A, wall outlet in splash proof cover each outlet on a separate GFIC breaker to

MDBC CORAL PROPAGATION PILOT STUDY

GALVESTON COLD ROOM

Electrical LayoutSCALE 1:45

2/8/2021 BEN HIGGINS

CAD

DRAFT

9 10 11 1312

4 5 6

AIR HANDLER

18,000 BTU

AIR HANDLER

18,000 BTU

Wall of Steel Building

100A

/4

/4

/4

/1

1 (4) AWG 240V, 100A FEED

6 (3) AWG 240V, 45A PASS THROUGH

25.3% Fill in 2” PVC conduit

2”

1”

6 (3) AWG 240V, 45A

To Split Unit Condenser

ELECTRICAL LAYOUT

1” PVC Conduit

1/2” PVC

Conduit

Two Pairs of Light Switches With Wet Location Covers

To Lights and Fans

Door

Center of Room

Pair of 120V, 15A Outlets Each on Separate GFCI Circuit Breaker

MDBC CORAL PROPAGATION PILOT STUDY

GALVESTON COLD ROOM

Electrical Layout

2/8/2021 BEN HIGGINS

CAD

DRAFT

SCALE 1:45

Page 1
Page 2
Page 3
Page 4