This is a power outlet location and electrical infrastructure diagram for a facility's East Wall, spanning 34'6" in length with a designated 22-foot display area for eight monitors. The diagram illustrates the physical placement and circuit specifications for multiple power outlets distributed across the wall, with spacing of approximately 6 feet between outlets.
The facility is equipped with a 20KVA APC UPS system located in Server Room 101, currently operating at 36% load capacity with a 1.5-hour runtime and generator backup support. The UPS infrastructure comprises 16 batteries replaced in 2025 and is maintained by a Schneider Electric certified partner. Room 101's power distribution is segmented into three zones: Rooms R1 and R2 are serviced by two 20-amp circuits (L6-20 UPS 250V, circuits 19, 21, 23, and 25), while Room R3 is serviced by one 20-amp breaker (UPS 120V circuit 20) with a 16-amp PDU. All circuits at the breaker panel are rated at 20 amps, with the UPS main breaker rated at 250 amps. The diagram identifies several outlets with UPS protection on circuits 8, 10, and 12, while four outlets at the bottom of the layout remain unlabeled and are not protected by the UPS system, requiring circuit identification for proper protection mapping.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Estimated not to Scale Power Outlet Locations East Wall
34'6" feet
22' feet Display for 8 Monitors Area
UPS
CKT
UPS
CKT
~2'
~6'
UPS
CKT
UPS
CKT
~6
UPS
CKT
~6'~6'
UPS
CKT
~6'
~1'
UPS
CKT
~1'
~2'
APC UPS Information located in Server Room 101:
-20KVA
-Load currently @36% 1.5Hours run time, building supported by Generator.
-16 Batteries replaced 2025 -UPS is maintained by Shneider Electric certified partner -All Circuits are 20Amps at Breaker panel -Room 101 R1 and R2 Serviced by (2)20 Amp Circuit L6-20 UPS 250V Circuit 19,21 and 23,25.
-Room 101 R3 serviced by (1) 20 Amp breaker UPS 120V circuit 20. PDU is 16Amps.
- UPS Main breaker is 250Amp Circuit
CKT
ID?
CKT
ID?
CKT
ID?
CKT
ID?
~6' ~6' ~6' ~6'
Circuits unlabeled not protected by UPS
| Attachment-2 2026-08-13 Power Outlets.vsdx |
| Page-1 |