8041_R-_Approved_2016-10-31.pdf
PDF 490 KB Posted
- Attached to
- Rental of gas turbine power generation system
- Solicitation number
- N64498-17-R-0011
About this file
Clearer Drawing 2
View the file
Other files
| File | Type | Posted |
|---|---|---|
| DOC034.pdf | ||
| 8040_R-_Approved_2016-10-31.pdf | ||
| Amendment_04.pdf | ||
| Amendment_3.pdf | ||
| drawings2.pdf | ||
| Amendment_2.pdf | ||
| Amendment_1.pdf | ||
| 8044_RA1_2016-12-13.pdf | ||
| N64498-17-R-0011.docx | DOCX document | |
| N64498-17-R-0011_CDRLs.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B
REFERENCES
No. TITLE DRAWING No.
THIS IS A CAD MAINTAINED DRAWING DEVELOPED
IN AUTOCAD R2013 SOFTWARE. CHANGES SHALL BE
INCORPORATED BY THE DESIGN AUTHORITY
UNDER 12" ±1/8"
12" TO 6'-0" ±1/4"
OVER 6'-0" ±1/2"
DISTRIBUTION STATEMENT D
DISTRIBUTION AUTHORIZED TO THE DEPARTMENT
OF DEFENSE AND U.S. DoD CONTRACTORS ONLY;
CRITICAL TECHNOLOGY, 2/23/2011. OTHER U.S.
REQUESTS SHALL BE REFERRED TO COMMANDER,
NAVAL SEA SYSTEMS COMMAND.
KEY PLAN 5A
BLDG 77H - PHILADELPHIA, PA
BUILDING KEY PLAN
SCALE: NONE
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 1 OF 6
D
CONTRACT No.
N00178-04-D-4089
OFFICIAL SIGNATURE DATE
PREPARED
CHECKED
QA
PROJ MGR
APPROVED NSWCPD
PROG MGR
DIMENSIONAL TOLERANCES
UNLESS OTHERWISE SPECIFIED
DIMENSIONS IN FEET & INCHES
DECIMAL DIMENSIONS IN INCHES
TOLERANCE ON ANGLES ±.50°
1 PL ±.2, 2 PL ±.06, 3 PL ±.005
INTERPRET DIMENSIONS AND TOLERANCES
PER ASME Y14.5 - 2009
REVISION HISTORY
DESCRIPTIONREVZONE DATE APPROVED
D
C
B
A
D
C
B
A
12345678
12345678
A
A C A D F
IL
E N
A M E A C A D E
H P 1/
B U
IL
D
IN
G
H
IP
S T
S D
R A W
IN
G S 1.
D W G
REDUCED SIZE PRINT
DESIGN MGR
REVISION STATUS
REV SH DESCRIPTION
- 1 TITLE SHEET, BUILDING KEY PLAN, REFERENCES, NOTES
- 2 ISOMETRIC VIEW
- 3 PLAN VIEW
- 4 SECTION VIEWS
- 5 DETAILS
- 6 LIST OF MATERIALS
ELECTRIC DRIVE TEST FACILITY (EDTF)
NSWCPD BUILDING 77H, PHILADELPHIA, PA
GTG-B GENERATOR POWER
INTERFACE ARR & DETAILS
8041 -
W.Bachman 10-04-16
B.Hayden 10-05-16
R.Chranowski 10-06-16
M.Lamberto 10-14-16
M. MIMNAGH 10-26-16
M. STAUFFER 10-26-16
89256
D
E
3230282624222018161412108642
343230282624222018161412108642
GTG-B FACILITY POWER INTERFACE
ARRANGEMENT & DETAILS
NORTH
SEE PLAN VIEW 20A
FOR CABLE ROUTING
NAVAL SURFACE WARFARE CENTER
PHILADELPHIA DIVISION
PHILADELPHIA, PA 19112-5083
BLDG 670
LEGEND
EXISTING/REFERENCE
SCOPE OF CURRENT REVISION
XSUPPORT LOCATION
NOTES:
1. DEVIATIONS FROM THIS DRAWING ARE NOT PERMITTED WITHOUT APPROVAL
FROM THE NSWCPD PROGRAM OFFICE (CODE 211).
2. FOLLOW THE 2014 NATIONAL ELECTRICAL CODE (NEC) FOR ANY INSTALLATION
DETAILS NOT COVERED WITHIN THIS DRAWING.
3. THE INSTALLATION CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING,
PURCHASING, AND INSTALLING ALL MATERIAL AS IDENTIFIED IN THIS DRAWING.
MISCELLANEOUS MATERIAL NOT INCLUDED IN MATERIAL LIST, SUCH AS NUTS,
BOLTS, WASHERS, ETC. SHALL BE REQUIRED TO BE PROVIDED BY THE
INSTALLATION CONTRACTOR.
4. DO NOT EXCEED CABLE MANUFACTURERS LIMIT FOR CABLE PULLING TENSION,
SIDE WALL PRESSURE AND BEND RADIUS. NO MORE THAN 360 DEGREES OF
CABLE BENDING SHALL BE PERMITTED WITHOUT ADDITION OF PULL BOX OR
PULL FITTING TO ENSURE MANUFACTURERS LIMITS ARE NOT EXCEEDED.
5. CONTRACTOR TO PROVIDE TEMPORARY BRACING OF CABLE TRAY AS
REQUIRED DURING CABLE PULLING.
6. EACH NEW CABLE INSTALLED SHALL HAVE A PERMANENT, WEATHER
RESISTANT IDENTIFICATION TAG INSTALLED AT EACH END OF THE CABLE PRIOR
TO ENTERING EQUIPMENT. CABLE TAG AND SECURING BAND SHALL BE MADE OF
NON-MAGNETIC, ULTRAVIOLET RESISTANT PLASTIC/NYLON OR ALUMINUM.
7. ALL ELEVATIONS IN THIS DRAWING ARE REFERENCED TO 0'-0" ELEVATION, TOP
OF GRADE.
8. ANCHOR BOLTS (ITEM 9) SHALL BE INSTALLED IN ACCORDANCE WITH
MANUFACTURERS INSTRUCTIONS. SEE DETAIL 37A.
9. FABRICATION, WELDING AND INSPECTION SPECIFIED ON THIS DRAWING SHALL BE
IN ACCORDANCE WITH AWS D.1.1. WELDS SHALL BE VISUALLY INSPECTED BY A
AWS CERTIFIED INSPECTOR.
10. ELECTRODE SPECIFICATION SHALL BE E70XX.
11. GRIND SMOOTH ALL SHARP CORNERS AND ROUGH EDGES ON NEW STRUCTURAL
STEEL AND CABLE TRAYS LIABLE TO CAUSE INJURY TO PERSONNEL OR
DAMAGE TO EQUIPMENT.
12. ALL NEW STRUCTURAL STEEL SHALL BE CLEANED AND THEN PAINTED WITH AN
ANTI-CORROSION PRIMER UPON COMPLETION OF ALL WELDING AND WELD
INSPECTION. FIELD WELD ON STRUCTURAL MEMBERS SHALL BE CLEANED,
WASHED WITH WATER AND COATED WITH AN ANTI-CORROSION PRIMER. FINISH
ALL STEEL WITH TWO COATS OF LIGHT GRAY (ANSI 61) PAINT.
13. ANCHOR SYSTEM SHALL INCLUDE ANCHOR ROD, SCREEN, ADHESIVE, NUTS AND
WASHERS FOR COMPLETE INSTALLATION.
14. UTILIZE ANTI-OXIDANT JOINT COMPOUND FOR GROUNDING CONNECTIONS WHERE
STEEL AND COPPER OR ALUMINUM AND COPPER SURFACES ARE BOLTED
TOGETHER. PREPARE SURFACES TO BE MATED BY ASSURING THAT DIRT,
CORROSION, PAINT, ETC ARE REMOVED PRIOR TO APPLYING JOINT COMPOUND.
REMOVE ANY EXCESS COMPOUND AFTER BOLTS ARE TIGHTENED.
15. CABLE TRAYS SHALL NOT HAVE SHARP EDGES, BURRS OR OTHER PROJECTIONS
WHICH MAY DAMAGE THE INSULATION OR JACKETS OF THE CABLES.
16. REFERENCE NEMA VE 2 (METAL CABLE TRAY INSTALLATION GUIDELINES) FOR
TRAY INSTALLATION REQUIREMENTS NOT COVERED HEREIN. ALSO REFERENCE
MANUFACTURER'S DOCUMENTATION.
NOTES:(CONT)
17. TIE-WRAP POWER AND GROUNDING CABLES TO CABLE TRAY RUNGS EVERY 18"
IN VERTICAL RUNS AND EVERY 36" IN HORIZONTAL RUNS. GROUNDING CABLE
ONLY REQUIRES SECURING BETWEEN TRAY BONDING LOCATIONS.
18. POWER CABLES SHALL BE INSTALLED IN A SINGLE LAYER WITH AT LEAST ONE
CABLE DIAMETER BETWEEN ADJACENT CABLES, EXCEPT IN SHORT AREAS
WHERE IT WILL BE NECESSARY TO CROSS CABLES. EXISTING 3 SETS OF
TRIPLEXED 500MCM CABLE TO BE UTILIZED FOR GTG-B SHALL NOT BE MODIFIED
WITHOUT PRIOR APPROVAL FROM NSWCPD PROGRAM MANAGER (CODE 212) TO
ENSURE FUTURE CONNECTION TO GTG IS NOT COMPROMISED.
19. ALL PHASE WIRES SHALL BE MARKED AS FOLLOWS. PHASE A CABLE SHALL BE
BLACK, PHASE B CABLE SHALL BE WHITE AND PHASE C CABLE SHALL BE RED.
POSITIVE PHASE SHALL BLACK, NEGATIVE PHASE SHALL BE WHITE. ALL
GROUNDING CONDUCTORS SHALL BE GREEN.
20. STANDARD THREE-PHASE SEQUENCE FOR THREE-PHASE AC SYSTEMS IN THE
NAVY IS IN THE FOLLOWING ORDER: AB, BC AND CA. FOR GROUNDED SYSTEMS,
THE PHASE SEQUENCE IS AN, BN, CN.
21. ALL ELECTRICAL CABLES SHALL BE TESTED FOR CONTINUITY IN ACCORDANCE
WITH ANSI/NETA ATS-2013. THE DATE OF THE TEST, TEMPERATURE, HUMIDITY
AND THE TESTER SHALL BE RECORDED. THE TEST INSTRUMENT MANUFACTURER,
PART NUMBER AND CALIBRATION DUE DATES SHALL BE RECORDED IN A TEST
REPORT THAT SHALL BE PROVIDED TO THE GOVERNMENT.
22. ALL ELECTRICAL CABLES SHALL BE TESTED FOR INSULATION RESISTANCE. THE
DATE OF THE TEST, TEMPERATURE, HUMIDITY AND THE TESTER SHALL BE
RECORDED. PERFORM TEST ON WIRING #6AWG AND LARGER CABLE USING
INSTRUMENT WHICH APPLIES VOLTAGE OF APPROXIMATELY 1000 VOLTS TO
PROVIDE DIRECT READING OF RESISTANCE. MINIMUM RESISTANCE SHALL BE
100MEG OHM. THE TEST INSTRUMENT MANUFACTURER, PART NUMBER AND
CALIBRATION DUE DATES SHALL BE RECORDED IN A TEST REPORT THAT SHALL
BE PROVIDED TO THE GOVERNMENT PRIOR TO ENERGIZING CIRCUIT.
23. ALL ELECTRICAL CONNECTIONS SHALL BE TORQUED IN ACCORDANCE TO
ANSI/NETA ATS-2013 AND MARKED WITH TORQUE SEAL FOR INSPECTION.
NOTES:(CONT)
24. ALL CABLE TRAYS/CONDUITS SHALL BE MADE ELECTRICALLY CONTINUOUS
FROM EACH POWER SOURCE GROUND BUS/FRAME FOR ENTIRE LENGTH OF
CABLEWAY UTILIZED BY CIRCUITS SUPPLIED FROM EACH POWER SOURCE TO
LOAD GROUND BUS. ANY GAPS IN CABLEWAY (TRAY OR CONDUIT) TO POWER
SOURCE GROUND SHALL BE MADE ELECTRICALLY CONTINUOUS WITH THE
INSTALLATION OF CONTINUOUS 250 MCM GROUND CABLE BONDED IN 20 FOOT
INTERVALS WITH AT LEAST ONE CONNECTION TO EACH PIECE OF TRAY, MARKED
WITH GREEN ELECTRICAL TAPE, UTILIZING ITEM 15.
25. SECURE ALL TRAY USING CLAMPING METHOD EXCEPT AS INDICATED IN SECTION
VIEWS 26C AND 29A.
LIST OF ABBREVIATIONS:
ARR ARRANGEMENT
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AWG AMERICAN WIRE GAUGE
AWS AMERICAN WELDING SOCIETY
BLDG BUILDING
CAD COMPUTER AIDED DESIGN
CAT NO. CATALOG NUMBER
CONT CONTINUED
DET DETAIL
EDTF ELECTRIC DRIVE TEST FACILITY
EQPT EQUIPMENT
ETC ETCETERA
EXST EXISTING
GEN GENERATOR
GND GROUND
GTG GAS TURBINE GENERATOR
MGR MANAGER
MIN MINIMUM
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NETA INTERNATIONAL ELECTRICAL TESTING ASSOCIATION
NSWCPD NAVAL SURFACE WARFARE CENTER - PHILADELPHIA DIVISION
OD OUTSIDE DIAMETER
PROG PROGRAM
PROJ PROJECT
QA QUALITY ASSURANCE
REF REFERENCE
REV REVISION
REQ'D REQUIRED
SECT SECTION
TECH TECHNICAL
W/ WITH
GTG-B CITY WATER & DRAIN PIPING INTERFACE
ARRANGEMENT & DETAILS
GTG-B GAS FUEL SUPPLY PIPING INTERFACE
ARRANGEMENT & DETAILS
GTG-B EQUIPMENT ARRANGEMENT 8044
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 2
D
D
C
B
A
D
C
B
A
910111213141516
910111213141516
REDUCED SIZE PRINT
ISOMETRIC VIEW 13A
LOOKING NORTHWEST
SCALE: NONE GTG-B POWER INTERFACE
ISOMETRIC VIEW
8041 -89256
SCALE : AS NOTED
D
D
C
B
A
D
C
B
A
REDUCED SIZE PRINT
SHEET 3
89256
1718192021222324
1718192021222324
PLAN VIEW 20A
GTG-B 13KV CABLE TRAY
ROUTING
SCALE: 1/8" = 1'-0"
NORTH
GRAPHIC SCALE 1/8"=1'-0"
0 2' 5' 10' 15' 20' 30'
5X ITEM 1
70'-6"
5'-10"
GTG-B POWER INTERFACE
PLAN VIEW
30'-5"
36'-3"
63'-2"
24'-4"
3X ITEM 2
17'-6"
7'-1"
EXST CONTROL
TRAY
DET 39A
5X DET 34B
5X DET 36B
A29
C
C
CRANE (REF)
4'-2"
8'-0"
DET 38B
DET 42A
CONNECT DET 38B TO DET 42A
USING (2) 4"x4"x1/4" ANGLES, ITEM 7
10'-0" 10'-0" 10'-0"
7'-6" 5'-3"
10'-0"
D
D
C
B
A
D
C
B
A
REDUCED SIZE PRINT
SHEET 4
89256
GRAPHIC SCALE 1/4"=1'-0"
0 2'1' 3' 4' 5' 10' 15'
2526272829303132
2526272829303132
4X ITEM 1
SECTION VIEW 29A
LOOKING WEST
TEMPORARY GTG 13KV
CABLE TRAY ROUTING
SCALE: 1/4" = 1'-0"
1'-8"
EXST SUPPORT
STRUCTURE
4'-2"
SECTION VIEW 30C
LOOKING NORTH
TEMPORARY GTG 13KV
CABLE TRAY ROUTING
SCALE: 1/4" = 1'-0"
4'-3"
15'-6"
DET 38B
ITEM 2
EXST CONTROL TRAY
DET 39A
ITEM 1
ITEM 18
4'-9"
EXST CONTROL TRAY
4'-9"
2X ITEM 2
DET 39A
EXST CONCRETE PIPE
SUPPORT (REF 3)
SECTION VIEW 26C
LOOKING NORTH
TEMPORARY GTG 13KV
CABLE TRAY ROUTING
SCALE: 1/4" = 1'-0"
DET 34B
DET 36B USING
ITEM 5
ITEM 2
ITEM 1
EXST CONCRETE PIPE
SUPPORT (REF 3)
4'-2"
7'-1" 24'-3"
GTG-B POWER INTERFACE
SECTION VIEWS
450V CABLE
TRAY (REF 1)
450V CABLE TRAY (REF 1)
450V CABLE TRAY (REF 1)
ITEM 1
SUPPORT USING
EXST STRUCTURES
ITEM 4. SET GAP PER INSTALLATION
TEMPERATURE AND NEMA STD VE2.
ITEM 2
3'-6"
DET 38B
DET 42A
2'-6"
2'-6"
ITEM 4. SET GAP PER INSTALLATION
TEMPERATURE AND NEMA STD VE2.
ITEM 17
DET 36B USING
ITEM 16
DET 38B USING
ITEM 5
DET 38B USING
ITEM 16
DET 38B USING
ITEM 16
DET 34B USING
ITEM 16
DET 34B USING
ITEM 5
DET 34B
USING ITEM 16
DET 34B USING
ITEM 16
DET 38B USING
ITEM 16
DET 34B USING
ITEM 5
DET 36B USING
ITEM 16
D
D
C
B
A
D
C
B
A
REDUCED SIZE PRINT
SHEET 5
89256 -
3334353637383940
3334353637383940
3/16 3/16 3/16 2X
2X
CONCRETE BARRIER,
ITEM 6
2X DRILL 9/16"∅ HOLE
FOR ITEM 9
C8x11.5, ITEM 8 6"
4'-2"
5'-0"
1'-6"
3X 4"x4"x1/4" ANGLE, ITEM 7
GTG-B POWER INTERFACE
DETAILS
2'-8"
4'-2"
4"
3/16
3/16 3/16
3X 4"x4"x1/4" ANGLE, ITEM 7
C8x11.5, ITEM 8
CONCRETE BARRIER,
ITEM 6
CABLE TRAY
DETAIL 34B
LOOKING NORTH
GTG-B CABLE TRAY SUPPORT
SCALE: 3/4" = 1'-0"
3/16 3/16
3/16 2X
3X
1'-6"
4X 4"x4"x1/4" ANGLE, ITEM 7CABLE
TRAY
2'-10"
4'-6"
1'-5"
4'-2"
3/16
3/16 3/16
2X
3X 4"x4"x1/4" ANGLE, ITEM 7
450V CABLE TRAY (REF 1)
GRAPHIC SCALE 3/4"=1'-0"
0 6" 2' 3' 4' 5'1'
DETAIL 36A
TYPICAL CABLE TRAY TO
CABLE TRAY BOLTING CONNECTION
SCALE: NONE
CABLE TRAY
CABLE TRAY
DETAIL 33A
TYPICAL CABLE TRAY TO
CABLE TRAY CONNECTION
SCALE: NONE
CABLE TRAY
CABLE TRAY
2X ITEM 4
DETAIL 38B
LOOKING WEST
GTG-B CABLE TRAY SUPPORT
SCALE: 3/4" = 1'-0"
3/16 2X
3X 4"x4"x1/4" ANGLE, ITEM 7CABLE
TRAY
3/16
3/16 3/16
2X
3X 4"x4"x1/4" ANGLE, ITEM 7
4'-9"
2'-6"
EXST SUPPORT
STRUCTURE
CABLE TRAY
3/16 3/16
2X
3X 4"x4"x1/4" ANGLE, ITEM 7
2X ITEM 5
DETAIL 39A
LOOKING WEST
GAS COMPRESSOR PRESSURE
TRANSDUCER CONDUIT ROUTING
SCALE: 3/4" = 1'-0"
DETAIL 37A
1/2" ANCHOR INSTALLATION
SCALE: NONE
1/2" ADHESIVE ANCHOR,
ITEM 9 (SEE NOTES 8 & 13)
6-3/4" MIN
EMBEDMENT
CONCRETE BARRIER,
ITEM 6
C8x11.5, ITEM 8
3'-9"
2X ITEM 5 OR 16
2X ITEM 5 OR 16
2X ITEM 5 OR 16
1'-8"
2X ITEMS 12, 13, 14
DETAIL 36B
LOOKING WEST
GTG-B CABLE TRAY SUPPORT
SCALE: 3/4" = 1'-0"
CONCRETE BARRIER,
ITEM 6
C8x11.5, ITEM 8
CONCRETE BARRIER,
ITEM 6
C8x11.5, ITEM 8
5'-0"5'-0"
2X DRILL 9/16"∅ HOLE
FOR ITEM 9
4'-2"
2X DRILL 9/16"∅ HOLE
FOR ITEM 9
4"
4"
CONCRETE BARRIER,
ITEM 6CONCRETE BARRIER,
ITEM 6
6"
CABLE TRAY
MATCH ANGLE TO
ANGLE OF CABLE TRAY
SCALE : NONE
D
D
C
B
A
D
C
B
A
REDUCED SIZE PRINT
SHEET 6
89256
LIST OF MATERIAL
ITEM QTY DESCRIPTION MATERIAL SPECIFICATION REMARKS
1 6
CABLE TRAY, 24"W, 6"D, 5" LOADING, STRAIGHT,
LADDER TYPE, 9" RUNG SPACING, 20' LONG
ALUMINUM NEMA 20C+ B-LINE CAT. NO. H46A09-24-240 OR EQUAL
2 3
CABLE TRAY, HORIZONTAL BEND, 90°, 24"W, 6"D, 5"
LOADING, LADDER TYPE, 9" RUNG SPACING, 36" BEND
RADIUS
ALUMINUM NEMA B-LINE CAT. NO. 6A-24-90HB36 OR EQUAL
3 2 PR
VERTICAL ADJUSTABLE SPLICE PLATE, 6" RAIL HEIGHT,
PAIRS, W/HARDWARE
ALUMINUM COMMERCIAL B-LINE CAT. NO. 9A-1026 OR EQUAL
4 2 PR
SPLICE PLATE, EXPANSION, 6" RAIL HEIGHT,
W/HARDWARE
ALUMINUM COMMERCIAL B-LINE CAT. NO. 9A-1016 OR EQUAL
5 12 BEAM CLAMP, NO-DRILL, FOR CABLE TRAY
ELECTRO-PLATED
ZINC
COMMERCIAL B-LINE CAT. NO. 9ZN-1249HD OR EQUAL
6 11 NEW JERSEY BARRIER, 60" LONG CONCRETE ASTM C825
LF
ANGLE, 4" x 4" x 1/4" THK CARBON STEEL ASTM A36 CUT TO SUIT
8 55 LF C-CHANNEL, C8x11.5 CARBON STEEL ASTM A36 CUT TO SUIT
9 22
ANCHOR BOLT, 1/2" HAS ROD, 8" LONG, W/HEX NUT &
WASHER. 6-3/4" MINIMUM EMBEDMENT
CARBON STEEL COMMERCIAL
HILTI HIT-HY70 ADHESIVE ANCHOR SYSTEM
CAT. NO. HAS-E 1/2x8 W/SC18X85 SCREENS
OR EQUAL
AS
REQ'D
BUILDING WIRE, 1C, 250 MCM, COPPER, 600V, 90°C,
RHH/RHW-2 INSULATION, 0.76" O.D.
VARIOUS COMMERCIAL
HOUSTON W&C CAT. NO. HW00325001
OR EQUAL
AS
REQ'D
COMPRESSION LUG, ONE HOLE, STRAIGHT, LONG
BARREL, FOR 250 MCM WIRE
TIN PLATED
COPPER ALLOY
COMMERCIAL BURNDY CAT. NO. YA29 OR EQUAL
AS
REQ'D
BOLT, 1/2"-13UNC-2A x 1" LG ALLOY STEEL ASTM A325
AS
REQ'D
HEX NUT, 1/2-13 UNC-2B ALLOY STEEL ASTM A563
AS
REQ'D
FLAT WASHER, 1/2"
ZINC-PLATED
STEEL
ASTM F436
AS
REQ'D
GROUND CONNECTOR, FOR CONNECTING ONE COPPER
2/0-250 MCM CABLE TO BAR OR TRAY
TIN PLATED
COPPER ALLOY
COMMERCIAL BURNDY CAT. NO. GB29TN OR EQUAL
16 18 BEAM CLAMP, NO-DRILL, CABLE TRAY GUIDE
ELECTRO-PLATED
ZINC
COMMERCIAL B-LINE CAT. NO. 9ZN-1249 OR EQUAL
17 1
CABLE TRAY, VERTICAL INSIDE BEND, 45°, 24"W, 6"D,
5" LOADING, LADDER TYPE, 9" RUNG SPACING, 24"
BEND RADIUS
ALUMINUM NEMA B-LINE CAT. NO. 6A-24-45VI24 OR EQUAL
18 1
CABLE TRAY, VERTICAL OUTSIDE BEND, 45°, 24"W, 6"D,
5" LOADING, LADDER TYPE, 9" RUNG SPACING, 24"
BEND RADIUS
ALUMINUM NEMA B-LINE CAT. NO. 6A-24-45VO24 OR EQUAL
4142434445464748
4142434445464748
GTG-B POWER INTERFACE
LIST OF MATERIALS & DETAILS
DETAIL 42A
LOOKING WEST
GTG-B CABLE TRAY SUPPORT
SCALE: 3/4" = 1'-0"
3/16 6X
5X 4"x4"x1/4" ANGLE, ITEM 7
CABLE TRAY
3/16
3/16 3/16
2X
3X 4"x4"x1/4" ANGLE, ITEM 7
10'-7"
2X ITEM 5 OR 16
CONCRETE BARRIER,
ITEM 6
C8x11.5, ITEM 8
5'-0"
2X DRILL 9/16"∅ HOLE
FOR ITEM 9
4'-2"
4"
CONCRETE BARRIER,
ITEM 6
6"
CABLE TRAY
MATCH ANGLE TO
ANGLE OF CABLE TRAY
4'-0"
GRAPHIC SCALE 3/4"=1'-0"
0 6" 2' 3' 4' 5'1'
| 8041 SH01 (1) |
| 8041 SH02 (1) |
| 8041 SH03 (1) |
| 8041 SH04 (1) |
| 8041 SH05 (1) |
| 8041 SH06 (1) |
File details come from the government source that posted it. Updated .