REFERENCES

No. TITLE DRAWING No.

THIS IS A CAD MAINTAINED DRAWING DEVELOPED

IN AUTOCAD R2013 SOFTWARE. CHANGES SHALL BE

INCORPORATED BY THE DESIGN AUTHORITY

UNDER 12" ±1/8"

12" TO 6'-0" ±1/4"

OVER 6'-0" ±1/2"

DISTRIBUTION STATEMENT D

DISTRIBUTION AUTHORIZED TO THE DEPARTMENT

OF DEFENSE AND U.S. DoD CONTRACTORS ONLY;

CRITICAL TECHNOLOGY, 2/23/2011. OTHER U.S.

REQUESTS SHALL BE REFERRED TO COMMANDER,

NAVAL SEA SYSTEMS COMMAND.

KEY PLAN 5A

BLDG 77H - PHILADELPHIA, PA

BUILDING KEY PLAN

SCALE: NONE

DWG NO.CAGE CODESIZE REV

SCALE : AS NOTED SHEET 1 OF 7

D

CONTRACT No.

N00178-04-D-4089

OFFICIAL SIGNATURE DATE

PREPARED

CHECKED

QA

PROJ MGR

APPROVED NSWCPD

PROG MGR

DIMENSIONAL TOLERANCES

UNLESS OTHERWISE SPECIFIED

DIMENSIONS IN FEET & INCHES

DECIMAL DIMENSIONS IN INCHES

TOLERANCE ON ANGLES ±.50°

1 PL ±.2, 2 PL ±.06, 3 PL ±.005

INTERPRET DIMENSIONS AND TOLERANCES

PER ASME Y14.5 - 2009

REVISION HISTORY

DESCRIPTIONREVZONE DATE APPROVED

D

C

B

A

D

C

B

A

12345678

12345678 A C A D F

IL

E N

A M E A C A D E

H P 1/

B U

IL

D

IN

G

H

IP

S T

S D

R A W

IN

G S .D W G

REDUCED SIZE PRINT

DESIGN MGR

REVISION STATUS

REV SH DESCRIPTION

- 1 TITLE SHEET, BUILDING KEY PLAN, REFERENCES, NOTES

- 2 ISOMETRIC VIEW

- 3 PLAN VIEW

- 4 SECTION VIEWS

- 5 DETAILS

- 6 DETAILS

- 7 LIST OF MATERIALS & ONE-LINE DIAGRAM

ELECTRIC DRIVE TEST FACILITY (EDTF)

NSWCPD BUILDING 77H, PHILADELPHIA, PA

GTG-B FACILITY POWER

INTERFACE ARR & DETAILS

T.Campbell 10-05-16

B.Hayden 10-11-16

W.Bachman 10-11-16

M.Lamberto 10-14-16

M. MIMNAGH 10/26/16

M. STAUFFER 10/26/16

89256

GTG-B GENERATOR POWER INTERFACE

ARRANGEMENT & DETAILS

NORTH

NAVAL SURFACE WARFARE CENTER

PHILADELPHIA DIVISION

PHILADELPHIA, PA 19112-5083

LEGEND

EXISTING/REFERENCE

SCOPE OF CURRENT REVISION

XPIPE SUPPORT LOCATION

NOTES:

1. DEVIATIONS FROM THIS DRAWING ARE NOT PERMITTED WITHOUT APPROVAL FROM

THE NSWCPD PROGRAM OFFICE (CODE 211).

2. FOLLOW THE 2014 NATIONAL ELECTRICAL CODE (NEC) FOR ANY INSTALLATION

DETAILS NOT COVERED WITHIN THIS DRAWING.

3. THE INSTALLATION CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING, PURCHASING,

AND INSTALLING ALL MATERIAL AS IDENTIFIED IN THIS DRAWING. MISCELLANEOUS

MATERIAL NOT INCLUDED IN MATERIAL LIST, SUCH AS NUTS, BOLTS, WASHERS,

ETC. SHALL BE REQUIRED TO BE PROVIDED BY THE INSTALLATION CONTRACTOR.

4. DO NOT EXCEED CABLE MANUFACTURERS LIMIT FOR CABLE PULLING TENSION, SIDE

WALL PRESSURE AND BEND RADIUS. NO MORE THAN 360 DEGREES OF CABLE

BENDING SHALL BE PERMITTED WITHOUT ADDITION OF PULL BOX OR PULL FITTING

TO ENSURE MANUFACTURERS LIMITS ARE NOT EXCEEDED.

5. EACH NEW CABLE INSTALLED SHALL HAVE A PERMANENT, WEATHER RESISTANT

IDENTIFICATION TAG INSTALLED AT EACH END OF THE CABLE PRIOR TO ENTERING

EQUIPMENT. CABLE TAG AND SECURING BAND SHALL BE MADE OF NON-MAGNETIC,

ULTRAVIOLET RESISTANT PLASTIC/NYLON OR ALUMINUM.

6. ALL ELEVATIONS IN THIS DRAWING ARE REFERENCED TO 0'-0" ELEVATION, TOP OF

GRADE.

7. RIGID CONDUIT SHALL BE ASSEMBLED WITH THREADED FITTINGS AND SHALL BE

MADE WRENCH TIGHT. MAINTAIN GROUNDING CONTINUITY OF CONDUIT SYSTEM FROM

SOURCE TO SOURCE.

8. FABRICATION, WELDING AND INSPECTION SPECIFIED ON THIS DRAWING SHALL BE

IN ACCORDANCE WITH AWS D.1.1. WELDS SHALL BE VISUALLY INSPECTED BY A

AWS CERTIFIED INSPECTOR.

9. ELECTRODE SPECIFICATION SHALL BE E70XX.

10. GRIND SMOOTH ALL SHARP CORNERS AND ROUGH EDGES ON NEW STRUCTURAL

STEEL AND CABLE TRAYS LIABLE TO CAUSE INJURY TO PERSONNEL OR DAMAGE

TO EQUIPMENT.

11. ALL NEW STRUCTURAL STEEL SHALL BE CLEANED AND THEN PAINTED WITH AN

ANTI-CORROSION PRIMER UPON COMPLETION OF ALL WELDING AND WELD

INSPECTION. FIELD WELD ON STRUCTURAL MEMBERS SHALL BE CLEANED,

WASHED WITH WATER AND COATED WITH AN ANTI-CORROSION PRIMER. FINISH

ALL STEEL WITH TWO COATS OF LIGHT GRAY (ANSI 61) PAINT.

12. ANCHOR BOLTS (ITEM 24) SHALL BE INSTALLED IN ACCORDANCE WITH

MANUFACTURERS INSTRUCTIONS. SEE DETAIL 47C.

13. ANCHOR SYSTEM SHALL INCLUDE ANCHOR ROD, SCREEN, ADHESIVE, NUTS AND

WASHERS FOR COMPLETE INSTALLATION.

14. TIE-WRAP POWER AND GROUNDING CABLES TO CABLE TRAY RUNGS EVERY 18" IN

VERTICAL RUNS AND EVERY 36" IN HORIZONTAL RUNS. GROUNDING CABLE ONLY

REQUIRES SECURING BETWEEN TRAY BONDING LOCATIONS.

15. POWER CABLES SHALL BE INSTALLED IN A SINGLE LAYER EXCEPT IN SHORT

AREAS WHERE IT WILL BE NECESSARY TO CROSS CABLES.

16. ALL PHASE WIRES SHALL BE MARKED AS FOLLOWS. PHASE A CABLE SHALL BE

BLACK, PHASE B CABLE SHALL BE WHITE AND PHASE C CABLE SHALL BE RED.

POSITIVE PHASE SHALL BLACK, NEGATIVE PHASE SHALL BE WHITE. ALL

GROUNDING CONDUCTORS SHALL BE GREEN.

17. STANDARD THREE-PHASE SEQUENCE FOR THREE-PHASE AC SYSTEMS IN THE

NAVY IS IN THE FOLLOWING ORDER: AB, BC AND CA. FOR GROUNDED SYSTEMS,

THE PHASE SEQUENCE IS AN, BN, CN.

NOTES:

18. ALL ELECTRICAL CABLES SHALL BE TESTED FOR CONTINUITY IN ACCORDANCE WITH

ANSI/NETA ATS-2013. THE DATE OF THE TEST, TEMPERATURE, HUMIDITY AND THE

TESTER SHALL BE RECORDED. THE TEST INSTRUMENT MANUFACTURER, PART

NUMBER AND CALIBRATION DUE DATES SHALL BE RECORDED IN A TEST REPORT

THAT SHALL BE PROVIDED TO THE GOVERNMENT.

19. ALL ELECTRICAL CABLES SHALL BE TESTED FOR INSULATION RESISTANCE. THE

DATE OF THE TEST, TEMPERATURE, HUMIDITY AND THE TESTER SHALL BE

RECORDED. PERFORM TEST ON WIRING #6AWG AND LARGER CABLE USING

INSTRUMENT WHICH APPLIES VOLTAGE OF APPROXIMATELY 1000 VOLTS TO

PROVIDE DIRECT READING OF RESISTANCE. MINIMUM RESISTANCE SHALL BE 100 MEG

OHM. THE TEST INSTRUMENT MANUFACTURER, PART NUMBER AND CALIBRATION

DUE DATES SHALL BE RECORDED IN A TEST REPORT THAT SHALL BE PROVIDED

TO THE GOVERNMENT PRIOR TO ENERGIZING CIRCUIT.

20. ALL ELECTRICAL CONNECTIONS SHALL BE TORQUED IN ACCORDANCE TO ANSI/NETA

ATS-2013 AND MARKED WITH TORQUE SEAL FOR INSPECTION.

21. ALL CABLE TRAYS/CONDUITS SHALL BE MADE ELECTRICALLY CONTINUOUS FROM

EACH POWER SOURCE GROUND BUS/FRAME FOR ENTIRE LENGTH OF CABLEWAY

UTILIZED BY CIRCUITS SUPPLIED FROM EACH POWER SOURCE. ANY GAPS IN

CABLEWAY (TRAY OR CONDUIT) TO POWER SOURCE GROUND SHALL BE MADE

ELECTRICALLY CONTINUOUS WITH THE INSTALLATION OF 4/0 COPPER BONDING

JUMPERS EXCEPT IN CONNECTION TO CONDUITS 2" OR LESS WHICH REQUIRE A 1/0

COPPER BONDING JUMPER. BONDING BETWEEN CABLEWAY (TRAY OR CONDUIT) AND

EQUIPMENT LOAD ENCLOSURES MAY BE PROVIDED BY VIRTUE OF THE CABLEWAY

INSTALLATION METHOD BUT IS NOT SPECIFICALLY REQUIRED BECAUSE A GROUND

CONDUCTOR IS INCLUDED IN ALL POWER CIRCUITS AND IS TO BE CONNECTED AT

SOURCE AND LOAD GROUND TERMINALS. ANY UNUSED CONDUCTORS IN POWER

CIRCUITS SHALL BE CONNECTED AS EQUIPMENT GROUND CONDUCTORS AT EACH

END. SEE DETAILS 34A AND 34D.

22. CORE DRILL 5" DIAMETER HOLE FOR CONDUIT PENETRATION THROUGH BRICK WALL

AND WEATHER SEAL WITH CAULK OR NON-SHRINK GROUT AS NECESSARY ON

BOTH INSIDE AND OUTSIDE OF WALL. WHERE CONDUIT PASSES FROM INTERIOR TO

EXTERIOR OF BUILDING, FOLLOW NEC GUIDELINES FOR SEALING INTERIOR OF

RACEWAYS EXPOSED TO DIFFERENT TEMPERATURES. INSTALL INTERNAL CONDUIT

SEAL IN CONDUIT BODY ADJACENT TO WALL, SHOWN IN PLAN VIEW 43B.

LIST OF ABBREVIATIONS:

ARR ARRANGEMENT

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS

ATR ALL-THREADED ROD

AUX AUXILIARY

AWG AMERICAN WIRE GAUGE

AWS AMERICAN WELDING SOCIETY

BLDG BUILDING

CAD COMPUTER AIDED DESIGN

CAT NO. CATALOG NUMBER

DET DETAIL

EDTF ELECTRIC DRIVE TEST FACILITY

ETC ETCETERA

EXST EXISTING

FLG FLANGE

GND GROUND

GTG GAS TURBINE GENERATOR

HTP HEAT TRANSFER PACKAGE

LOM LIST OF MATERIAL

MGR MANAGER

MIN MINIMUM

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NETA INTERNATIONAL ELECTRICAL TESTING ASSOCIATION

NSWCPD NAVAL SURFACE WARFARE CENTER - PHILADELPHIA DIVISION

OD OUTSIDE DIAMETER

PROG PROGRAM

PROJ PROJECT

QA QUALITY ASSURANCE

REF REFERENCE

REV REVISION

REQ'D REQUIRED

TECH TECHNICAL

THK THICK

TYP TYPICAL

W/ WITH

GTG-B CITY WATER & DRAIN PIPING INTERFACE

ARRANGEMENT & DETAILS

GTG-B GAS FUEL SUPPLY PIPING INTERFACE

ARRANGEMENT & DETAILS

GTG-B EQUIPMENT ARRANGEMENT 8044

SEE PLAN VIEW 20A

FOR CABLE ROUTING

BLDG 670

B

D

E

A

3230282624222018161412108642

343230282624222018161412108642

RESERVATIONS:

1. TERMINATION INFORMATION IN GTG-B AUX TRAILER RESERVED

PENDING RECEIPT FROM GTG-B VENDOR.

DWG NO.CAGE CODESIZE REV

SCALE : AS NOTED SHEET 2

D

D

C

B

A

D

C

B

A

910111213141516

910111213141516

REDUCED SIZE PRINT

ISOMETRIC VIEW 13A

LOOKING NORTHWEST

SCALE: NONE GTG-B FAC POWER INTERFACE

ISOMETRIC VIEW

804089256

* NOTE: EXISTING CABLE TRAYS

NOT SHOWN FOR CLARITY.

SCALE : AS NOTED

D

D

C

B

A

D

C

B

A

REDUCED SIZE PRINT

SHEET 3

89256

1718192021222324

1718192021222324

PLAN VIEW 20A

GTG-B 13KV CABLE TRAY

ROUTING

SCALE: 3/16" = 1'-0"

NORTH GTG-B FAC POWER INTERFACE

PLAN VIEW

92'-8"

1'-6"

16'-0"

DET 36A

3X DET 37C

A29 C

C

DET 40D

2X DET 47A

DET 43B

22'-4"

1'-6"

10'-2"

21'-10"

DET 39A

DET 47D

EXST SUPPORTS

SEE REF 1

GTG-B AUX

TRAILER

2'-6"

16'-7"

EXST 4" 450V

CONDUIT

ITEM 9

ITEM 9

GRAPHIC SCALE 3/16"=1'-0"

0 1' 2' 3' 4' 5' 10' 15' 20'

POWER PANEL

GTG-AUX

EAST SUBSTATION

2X DET 45C

5X DET 36C

10'-0" 10'-0"8'-9"

* NOTE: EXISTING CABLE TRAYS

NOT SHOWN FOR CLARITY.

GTG PAD

D

D

C

B

A

D

C

B

A

REDUCED SIZE PRINT

SHEET 4

89256

GRAPHIC SCALE 1/4"=1'-0"

0 2'1' 3' 4' 5' 10' 15'

2526272829303132

2526272829303132

ITEM 3

SECTION VIEW 29A

LOOKING WEST

TEMPORARY GTG 450V

CABLE TRAY ROUTING

SCALE: 1/4" = 1'-0"

6"

EXST SUPPORT

STRUCTURE

7'-0"

SECTION VIEW 30C

LOOKING NORTH

TEMPORARY GTG 450V

CABLE TRAY ROUTING

SCALE: 1/4" = 1'-0"

22'-4"

10'-1"

EXST CONTROL TRAY

2X ITEM 2

EXST CONTROL TRAY

10'-1"

DET 39A

EXST CONCRETE

SUPPORT (REF 1)

SECTION VIEW 26C

LOOKING NORTH

TEMPORARY GTG 450V

CABLE TRAY ROUTING

SCALE: 1/4" = 1'-0"

ITEM 4

ITEM 3

17'-1"

GTG-B FAC POWER INTERFACE

SECTION VIEWS

13KV CABLE

TRAY (REF 1)

13KV CABLE

TRAY (REF 1)

7'-0"

3'-4"

DET 37C

DET 36A DET 40D

ITEM 4

5X ITEM 1 2X ITEM 2

3X DET 37C

ITEM 1

1'-5"

3'-4"

3'-1"

SEE DET 45D

ITEM 1

2X SEE DET 47A

ITEM 2

3X ITEM 1

ITEM 3

ITEM 4

C

5X DET 36C

DET 45C

DET 45D

DET 47D

SEE DET 43B

SEE DET 36A

D

D

C

B

A

D

C

B

A

REDUCED SIZE PRINT

SHEET 5

89256

3334353637383940

3334353637383940

GTG-B FAC POWER INTERFACE

DETAILS

GRAPHIC SCALE 3/4"=1'-0"

0 6" 2' 3' 4' 5'1'

DETAIL 37C

LOOKING NORTH

GTG-B CABLE TRAY SUPPORT

SCALE: 3/4" = 1'-0"

3/16

3/16

450V CABLE TRAY

4'-6"

1'-5"

1"

2X 4"x4"x1/4" ANGLE, ITEM 7

2X ITEM 6

2'-6" 2'-6"

1'-3"

2"

2'-6"4'-0"

450V CABLE TRAY 450V CABLE TRAY

ITEM 25

1'-5"

2'-0" 2'-6"

5'-3"

5'-9"

7'-0"

11X 4"x4"x1/4" ANGLE, ITEM 7

11X 4"x4"x1/4" ANGLE, ITEM 7

DETAIL 36A

LOOKING WEST

450V CABLE TRAY SUPPORT STAND

SCALE: 3/4" = 1'-0"

1/2" PLATE, ITEM 21

1/2" PLATE, ITEM 20

1'-4"

ITEM 25

1'-4"

1'-4"

3/164X

3/16

2X3/16

8X3/16

DETAIL 40D

LOOKING NORTH

GTG-B CABLE TRAY SUPPORT

SCALE: 3/4" = 1'-0"

2'-9" 9"

1'-5"

DETAIL 39A

LOOKING WEST

450V CABLE TRAY SUPPORT STAND

SCALE: 3/4" = 1'-0"

2'-0"

8'-0"

2'-1"

3/16 3/16

3/16

3/16

5X 4"x4"x1/4" ANGLE, ITEM 7

DETAIL 34A

TYPICAL CABLE TRAY TO

CABLE TRAY GROUND CONNECTION

SCALE: NONE

CABLE TRAY

2X ITEMS 13, 15, 16

CABLE TRAY

2X ITEMS 13, 14, 15, 16

GROUND WIRE, ITEM 19.

(AS REQ'D)

DETAIL 34D

TYPICAL CABLE TRAY TO

CABLE TRAY CONNECTION

SCALE: NONE

CABLE TRAY

2X ITEMS 13, 14, 15, 16

GROUND WIRE, ITEM 19

(AS REQ'D)

CABLE TRAY

2X ITEM 5

C8x11.5 CHANNEL ANGLE, ITEM 23

CONCRETE SUPPORT

BARRIER, ITEM 22

2X DRILL 9/16"∅ HOLE

FOR ITEM 24

6"

450V CABLE TRAY

DETAIL 36C

LOOKING NORTH

GTG-B CABLE TRAY SUPPORT

SCALE: 3/4" = 1'-0"

EXST SUPPORT

SEE REF 1

5X 4"x4"x1/4" ANGLE, ITEM 7

2X ITEM 6

2X

3/16

1'-8

D

D

C

B

A

D

C

B

A

REDUCED SIZE PRINT

SHEET 6

89256

4142434445464748

4142434445464748

GTG-B FAC POWER INTERFACE

DETAILS

DETAIL 43B

CONDUIT SUPPORT THRU

BUILDING WALL

SCALE: NONE

3/16 2X

4" CONDUIT (ITEM 9)

2X ITEM 10

2X 4"x4"x1/4" ANGLE, ITEM 7

2X DRILL 9/16"∅ HOLE

THRU BLDG WALL

FOR ITEM 12

BLDG 633

EXTERIOR WALL

2X 4"x4"x1/4"

ANGLE, ITEM 7

BLDG 633

INTERIOR WALL

2X ITEM 11

4X ITEMS

13, 15

4" RIGID METAL

CONDUIT (ITEM 9)

2X ITEM 10

4"x4"x1/4" ANGLE, ITEM 7

2"

(TYP)

4" CONDUIT (ITEM 9)

ITEM 11

4X ITEMS 13, 15

2X ITEM 12

ITEM 10

1'-6"

3" (TYP)

DETAIL 45A

CONDUIT SUPPORT BASEPLATE

SCALE: NONE

3/16

2X DRILL 9/16"∅ HOLE

IN ITEM 17 FOR ITEM 24

ITEM 17

ITEM 17,

SEE DET 45A

3/16 3/16

COPE ANGLE FLG TO FIT

DETAIL 47A

CONDUIT SUPPORT OFF

BUILDING WALL

SCALE: NONE

DRILL 9/16"∅ HOLE

THRU BLDG WALL

FOR ITEM 12

2X ITEMS 13, 15

3'-4"

ITEM 7

ITEM 7

2X ITEM 24. FOR ANCHOR INSTALLATION

SEE DETAIL 43A (SEE NOTES 12 AND 13)

2'-11"

ITEM 18

SEE DET 45B

2X ITEMS 13, 15

ITEM 12

8"

4"

8"

4"

ITEM 18

8"

4"

2"

2'-1"

2"

4"

2X

DRILL 9/16"∅ HOLE

THRU BLDG WALL

FOR ITEM 12,

2X ITEMS 13, 15

4"

DETAIL 45B

CONDUIT SUPPORT BACKPLATE

SCALE: NONE

3'-10"

45°

DETAIL 47C

1/2" ANCHOR INSTALLATION

SCALE: NONE

1/2" ADHESIVE ANCHOR,

ITEM 24 (SEE NOTES 12 & 13)

6-3/4" MIN

EMBEDMENT

CONCRETE BARRIER,

ITEM 22

C8x11.5, ITEM 23

3"

4"

DETAIL 47D

CABLE TRAY SUPPORT

SCALE: NONE

3'-4"

DETAIL 45D

CABLE TRAY SUPPORT

SCALE: NONE

2'-8"

ITEM 7

DETAIL 45C

CABLE TRAY SUPPORT

SCALE: NONE

3'-1"

ITEM 7

ITEM 7

DETAIL 43A

ANCHOR INSTALLATION IN WALL

SCALE: NONE

ITEM 24

1/2" ADHESIVE ANCHOR

(SEE NOTES 12 & 13)

PLATE

6-3/4" MIN

EMBEDMENT

BLDG WALL

2X ITEM 7

3/16

3/16

2X3/16

EXST COLUMN (TYP) EXST COLUMN

EXST COLUMN

ITEM 12

CORE DRILL THRU BRICK

WALL FOR 4" RGS CONDUITS.

SEAL HOLES W/NON-SHRINK

GROUT AS REQUIRED.

SEE NOTE 22.

D

D

C

B

A

D

C

B

A

REDUCED SIZE PRINT

SHEET 7

89256 8040

GTG-B FAC POWER INTERFACE

LOM & ONE-LINE DIAGRAM

LIST OF MATERIAL

ITEM QTY DESCRIPTION MATERIAL SPECIFICATION REMARKS

1 8

CABLE TRAY, 6"W, 6"D, 5" LOADING, STRAIGHT,

LADDER TYPE, 9" RUNG SPACING, 20' LONG

ALUMINUM NEMA 20C+ B-LINE CAT. NO. H46A09-06-240 OR EQUAL

2 3

CABLE TRAY, HORIZONTAL BEND, 90°, 6"W, 6"D, 5"

LOADING, LADDER TYPE, 9" RUNG SPACING, 12" BEND

RADIUS

ALUMINUM NEMA B-LINE CAT. NO. 6A-06-90HB12 OR EQUAL

3 2

CABLE TRAY, VERTICAL INSIDE BEND, 90°, 6"W, 6"D,

5" LOADING, LADDER TYPE, 9" RUNG SPACING,

12" BEND RADIUS

ALUMINUM NEMA B-LINE CAT. NO. 6A-06-90VI12 OR EQUAL

4 2

CABLE TRAY, VERTICAL OUTSIDE BEND, 90°, 6"W, 6"D,

5" LOADING, LADDER TYPE, 9" RUNG SPACING,

12" BEND RADIUS

ALUMINUM NEMA B-LINE CAT. NO. 6A-06-90VO12 OR EQUAL

5 2 PR

SPLICE PLATE, EXPANSION, 6" RAIL HEIGHT,

W/HARDWARE

ALUMINUM COMMERCIAL B-LINE CAT. NO. 9A-1016 OR EQUAL

6 42 BEAM CLAMP, NO-DRILL, FOR CABLE TRAY

ELECTRO-PLATED

ZINC

COMMERCIAL B-LINE CAT. NO. 9ZN-1249HD OR EQUAL

7 100 LF ANGLE, 4" x 4" x 1/4" THK CARBON STEEL ASTM A36 CUT TO SUIT

8 250 LF

BUILDING WIRE, 3C W/ GROUND, 500 MCM, COPPER,

600V, 90°C, 2.26" O.D., TRAY CABLE

VARIOUS COMMERCIAL

HOUSTON W&C CAT. NO. HW15450003

OR EQUAL

9 2

CONDUIT, RIGID, 4", 10' LG, STANDARD THREAD

W/COUPLING

GALVANIZED STEEL COMMERCIAL WESCO CAT. NO. 78001000110 OR EQUAL

10 1 CHANNEL, 1-5/8" x 1-5/8" x 12 GAUGE, 20' LONG

PRE-GALVANIZED

STEEL

COMMERCIAL

B-LINE CAT. NO. B22-GALV-240

OR EQUAL. CUT TO SUIT.

11 2 PIPE CLAMP, STRUT TYPE, 4", W/HARDWARE

ELECTRO-PLATED

ZINC

COMMERCIAL B-LINE CAT.NO. BB2017PAZN OR EQUAL

12 2 1/2" THREADED ROD (ATR), x 12' LONG, 1350 LB DESIGN

LOAD

ELECTRO-PLATED

ZINC

COMMERCIAL

B-LINE CAT. NO. ATR1/2"x144-ZN

OR EQUAL. CUT TO SUIT.

AS

REQ'D

FLAT WASHER, 1/2"

ELECTRO-PLATED

ZINC

COMMERCIAL

B-LINE CAT. NO. 1/2" FW OR EQUAL.

USED W/ITEM 16.

AS

REQ'D

COMPRESSION LUG, ONE HOLE, STRAIGHT,

SHORT BARREL

TIN PLATED

COPPER

COMMERCIAL BURNDY CAT. NO. YAD28M10E38 OR EQUAL

AS

REQ'D

HEX NUT, 1/2-13 UNC ALLOY STEEL ASTM A325

AS

REQ'D

BOLT, 1/2"-13UNC-2A x 1" LG ALLOY STEEL ASTM A325

17 2 PLATE, 8" x 46" x 1/4" THK CARBON STEEL ASTM A36 SEE DETAIL 45A

18 2 PLATE, 8" x 8" x 1/4" THK CARBON STEEL ASTM A36 SEE DETAIL 45B

AS

REQ'D

BUILDING WIRE, 1C, 4/0 AWG, COPPER, 600V, 90°C,

THHN/THWN INSULATION, 0.64" O.D.

VARIOUS COMMERCIAL

HOUSTON W&C CAT. NO. HW00140101

OR EQUAL

20 1 PLATE, 30" x 30" x 1/2" THK CARBON STEEL ASTM A36 SEE DETAIL 40D

21 1 PLATE, 48" x 30" x 1/2" THK CARBON STEEL ASTM A36 SEE DETAIL 36A

22 3 NEW JERSEY BARRIER, 60" LONG CONCRETE ASTM C825

23 15 LF C-CHANNEL, C8x11.5 CARBON STEEL ASTM A36 CUT TO SUIT

24 6

ANCHOR BOLT, 1/2" HAS ROD, 8" LONG, W/HEX NUT &

WASHER. 6-3/4" MINIMUM EMBEDMENT

CARBON STEEL COMMERCIAL

HILTI HIT-HY70 ADHESIVE ANCHOR SYSTEM

CAT. NO. HAS-E 1/2x8 W/SC18X85 SCREENS

OR EQUAL

25 1 CHANNEL, 1-5/8" x 3-1/4" x 12 GAUGE, 20' LONG

PRE-GALVANIZED

STEEL

COMMERCIAL

B-LINE CAT. NO. B22A-GALV-240

OR EQUAL. CUT TO SUIT.

AS

REQ'D

CLAMP/GUIDE, CABLE TRAY, 2-1/4" LG FOR 1/2"

HARDWARE, INSTALLED AS CLAMP

ELECTRO-PLATED

ZINC

COMMERCIAL B-LINE CAT. NO. 9ZN-1205 OR EQUAL

AS

REQ'D

HEX HEAD CAP SCREW, 1/2" x 7/8" LONG

ELECTRO-PLATED

ZINC

COMMERCIAL

B-LINE CAT. NO. 1/2X7/8-HHCS OR EQUAL.

USE TO SECURE TRAY TO CHANNEL.

AS

REQ'D

TWIRL-NUT, 1/2-13, FOR B22/B22A CHANNEL

ELECTRO-PLATED

ZINC

COMMERCIAL

B-LINE CAT. NO. TN225WO-ZN OR EQUAL.

USED W/ITEM 26.

4950515253545556

4950515253545556

13.2KV-480V,

2500-3125KVA

(EXIST)

13.2KV-480V,

2500-3125KVA

(EXIST)

4000AF

4000AT

800AF

600AT, 3P

4000AF

4000AT

4000AF

4000AT

4000A, 480V, 3ɸ, 3W EAST SUBSTATION SWGR (EXIST)

DETAIL 51A

GAS TURBINE GENERATOR

AUXILIARY POWER ONE LINE DIAGRAM

SCALE: NONE

225AF

125AT, 3P

SPACE

MLO

400AF

400AT, 3P

POWER PANEL GTG-AUX

480V, 600A, 3ɸ, 3W

HEAT TRANSFER

EQUIPMENT (HTP-1)

SPACE

TO GTG-B AUX TRAILER

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

2X (3-1/C 250MCM + #1 GND)

1-3/C 500MCM + #2 GND

8040 R- Approved 2016-10-26 SH01 (1)
8040 R- Approved 2016-10-26 SH02 (1)
8040 R- Approved 2016-10-26 SH03 (1)
8040 R- Approved 2016-10-26 SH04 (1)
8040 R- Approved 2016-10-26 SH05 (1)
8040 R- Approved 2016-10-26 SH06 (1)
8040 R- Approved 2016-10-26 SH07 (1)

File details come from the government source that posted it. Updated .