REFERENCES
No. TITLE DRAWING No.
THIS IS A CAD MAINTAINED DRAWING DEVELOPED
IN AUTOCAD R2013 SOFTWARE. CHANGES SHALL BE
INCORPORATED BY THE DESIGN AUTHORITY
UNDER 12" ±1/8"
12" TO 6'-0" ±1/4"
OVER 6'-0" ±1/2"
DISTRIBUTION STATEMENT D
DISTRIBUTION AUTHORIZED TO THE DEPARTMENT
OF DEFENSE AND U.S. DoD CONTRACTORS ONLY;
CRITICAL TECHNOLOGY, 2/23/2011. OTHER U.S.
REQUESTS SHALL BE REFERRED TO COMMANDER,
NAVAL SEA SYSTEMS COMMAND.
KEY PLAN 5A
BLDG 77H - PHILADELPHIA, PA
BUILDING KEY PLAN
SCALE: NONE
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 1 OF 7
D
CONTRACT No.
N00178-04-D-4089
OFFICIAL SIGNATURE DATE
PREPARED
CHECKED
QA
PROJ MGR
APPROVED NSWCPD
PROG MGR
DIMENSIONAL TOLERANCES
UNLESS OTHERWISE SPECIFIED
DIMENSIONS IN FEET & INCHES
DECIMAL DIMENSIONS IN INCHES
TOLERANCE ON ANGLES ±.50°
1 PL ±.2, 2 PL ±.06, 3 PL ±.005
INTERPRET DIMENSIONS AND TOLERANCES
PER ASME Y14.5 - 2009
REVISION HISTORY
DESCRIPTIONREVZONE DATE APPROVED
D
C
B
A
D
C
B
A
12345678
12345678 A C A D F
IL
E N
A M E A C A D E
H P 1/
B U
IL
D
IN
G
H
IP
S T
S D
R A W
IN
G S .D W G
REDUCED SIZE PRINT
DESIGN MGR
REVISION STATUS
REV SH DESCRIPTION
- 1 TITLE SHEET, BUILDING KEY PLAN, REFERENCES, NOTES
- 2 ISOMETRIC VIEW
- 3 PLAN VIEW
- 4 SECTION VIEWS
- 5 DETAILS
- 6 DETAILS
- 7 LIST OF MATERIALS & ONE-LINE DIAGRAM
ELECTRIC DRIVE TEST FACILITY (EDTF)
NSWCPD BUILDING 77H, PHILADELPHIA, PA
GTG-B FACILITY POWER
INTERFACE ARR & DETAILS
T.Campbell 10-05-16
B.Hayden 10-11-16
W.Bachman 10-11-16
M.Lamberto 10-14-16
M. MIMNAGH 10/26/16
M. STAUFFER 10/26/16
89256
GTG-B GENERATOR POWER INTERFACE
ARRANGEMENT & DETAILS
NORTH
NAVAL SURFACE WARFARE CENTER
PHILADELPHIA DIVISION
PHILADELPHIA, PA 19112-5083
LEGEND
EXISTING/REFERENCE
SCOPE OF CURRENT REVISION
XPIPE SUPPORT LOCATION
NOTES:
1. DEVIATIONS FROM THIS DRAWING ARE NOT PERMITTED WITHOUT APPROVAL FROM
THE NSWCPD PROGRAM OFFICE (CODE 211).
2. FOLLOW THE 2014 NATIONAL ELECTRICAL CODE (NEC) FOR ANY INSTALLATION
DETAILS NOT COVERED WITHIN THIS DRAWING.
3. THE INSTALLATION CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING, PURCHASING,
AND INSTALLING ALL MATERIAL AS IDENTIFIED IN THIS DRAWING. MISCELLANEOUS
MATERIAL NOT INCLUDED IN MATERIAL LIST, SUCH AS NUTS, BOLTS, WASHERS,
ETC. SHALL BE REQUIRED TO BE PROVIDED BY THE INSTALLATION CONTRACTOR.
4. DO NOT EXCEED CABLE MANUFACTURERS LIMIT FOR CABLE PULLING TENSION, SIDE
WALL PRESSURE AND BEND RADIUS. NO MORE THAN 360 DEGREES OF CABLE
BENDING SHALL BE PERMITTED WITHOUT ADDITION OF PULL BOX OR PULL FITTING
TO ENSURE MANUFACTURERS LIMITS ARE NOT EXCEEDED.
5. EACH NEW CABLE INSTALLED SHALL HAVE A PERMANENT, WEATHER RESISTANT
IDENTIFICATION TAG INSTALLED AT EACH END OF THE CABLE PRIOR TO ENTERING
EQUIPMENT. CABLE TAG AND SECURING BAND SHALL BE MADE OF NON-MAGNETIC,
ULTRAVIOLET RESISTANT PLASTIC/NYLON OR ALUMINUM.
6. ALL ELEVATIONS IN THIS DRAWING ARE REFERENCED TO 0'-0" ELEVATION, TOP OF
GRADE.
7. RIGID CONDUIT SHALL BE ASSEMBLED WITH THREADED FITTINGS AND SHALL BE
MADE WRENCH TIGHT. MAINTAIN GROUNDING CONTINUITY OF CONDUIT SYSTEM FROM
SOURCE TO SOURCE.
8. FABRICATION, WELDING AND INSPECTION SPECIFIED ON THIS DRAWING SHALL BE
IN ACCORDANCE WITH AWS D.1.1. WELDS SHALL BE VISUALLY INSPECTED BY A
AWS CERTIFIED INSPECTOR.
9. ELECTRODE SPECIFICATION SHALL BE E70XX.
10. GRIND SMOOTH ALL SHARP CORNERS AND ROUGH EDGES ON NEW STRUCTURAL
STEEL AND CABLE TRAYS LIABLE TO CAUSE INJURY TO PERSONNEL OR DAMAGE
TO EQUIPMENT.
11. ALL NEW STRUCTURAL STEEL SHALL BE CLEANED AND THEN PAINTED WITH AN
ANTI-CORROSION PRIMER UPON COMPLETION OF ALL WELDING AND WELD
INSPECTION. FIELD WELD ON STRUCTURAL MEMBERS SHALL BE CLEANED,
WASHED WITH WATER AND COATED WITH AN ANTI-CORROSION PRIMER. FINISH
ALL STEEL WITH TWO COATS OF LIGHT GRAY (ANSI 61) PAINT.
12. ANCHOR BOLTS (ITEM 24) SHALL BE INSTALLED IN ACCORDANCE WITH
MANUFACTURERS INSTRUCTIONS. SEE DETAIL 47C.
13. ANCHOR SYSTEM SHALL INCLUDE ANCHOR ROD, SCREEN, ADHESIVE, NUTS AND
WASHERS FOR COMPLETE INSTALLATION.
14. TIE-WRAP POWER AND GROUNDING CABLES TO CABLE TRAY RUNGS EVERY 18" IN
VERTICAL RUNS AND EVERY 36" IN HORIZONTAL RUNS. GROUNDING CABLE ONLY
REQUIRES SECURING BETWEEN TRAY BONDING LOCATIONS.
15. POWER CABLES SHALL BE INSTALLED IN A SINGLE LAYER EXCEPT IN SHORT
AREAS WHERE IT WILL BE NECESSARY TO CROSS CABLES.
16. ALL PHASE WIRES SHALL BE MARKED AS FOLLOWS. PHASE A CABLE SHALL BE
BLACK, PHASE B CABLE SHALL BE WHITE AND PHASE C CABLE SHALL BE RED.
POSITIVE PHASE SHALL BLACK, NEGATIVE PHASE SHALL BE WHITE. ALL
GROUNDING CONDUCTORS SHALL BE GREEN.
17. STANDARD THREE-PHASE SEQUENCE FOR THREE-PHASE AC SYSTEMS IN THE
NAVY IS IN THE FOLLOWING ORDER: AB, BC AND CA. FOR GROUNDED SYSTEMS,
THE PHASE SEQUENCE IS AN, BN, CN.
NOTES:
18. ALL ELECTRICAL CABLES SHALL BE TESTED FOR CONTINUITY IN ACCORDANCE WITH
ANSI/NETA ATS-2013. THE DATE OF THE TEST, TEMPERATURE, HUMIDITY AND THE
TESTER SHALL BE RECORDED. THE TEST INSTRUMENT MANUFACTURER, PART
NUMBER AND CALIBRATION DUE DATES SHALL BE RECORDED IN A TEST REPORT
THAT SHALL BE PROVIDED TO THE GOVERNMENT.
19. ALL ELECTRICAL CABLES SHALL BE TESTED FOR INSULATION RESISTANCE. THE
DATE OF THE TEST, TEMPERATURE, HUMIDITY AND THE TESTER SHALL BE
RECORDED. PERFORM TEST ON WIRING #6AWG AND LARGER CABLE USING
INSTRUMENT WHICH APPLIES VOLTAGE OF APPROXIMATELY 1000 VOLTS TO
PROVIDE DIRECT READING OF RESISTANCE. MINIMUM RESISTANCE SHALL BE 100 MEG
OHM. THE TEST INSTRUMENT MANUFACTURER, PART NUMBER AND CALIBRATION
DUE DATES SHALL BE RECORDED IN A TEST REPORT THAT SHALL BE PROVIDED
TO THE GOVERNMENT PRIOR TO ENERGIZING CIRCUIT.
20. ALL ELECTRICAL CONNECTIONS SHALL BE TORQUED IN ACCORDANCE TO ANSI/NETA
ATS-2013 AND MARKED WITH TORQUE SEAL FOR INSPECTION.
21. ALL CABLE TRAYS/CONDUITS SHALL BE MADE ELECTRICALLY CONTINUOUS FROM
EACH POWER SOURCE GROUND BUS/FRAME FOR ENTIRE LENGTH OF CABLEWAY
UTILIZED BY CIRCUITS SUPPLIED FROM EACH POWER SOURCE. ANY GAPS IN
CABLEWAY (TRAY OR CONDUIT) TO POWER SOURCE GROUND SHALL BE MADE
ELECTRICALLY CONTINUOUS WITH THE INSTALLATION OF 4/0 COPPER BONDING
JUMPERS EXCEPT IN CONNECTION TO CONDUITS 2" OR LESS WHICH REQUIRE A 1/0
COPPER BONDING JUMPER. BONDING BETWEEN CABLEWAY (TRAY OR CONDUIT) AND
EQUIPMENT LOAD ENCLOSURES MAY BE PROVIDED BY VIRTUE OF THE CABLEWAY
INSTALLATION METHOD BUT IS NOT SPECIFICALLY REQUIRED BECAUSE A GROUND
CONDUCTOR IS INCLUDED IN ALL POWER CIRCUITS AND IS TO BE CONNECTED AT
SOURCE AND LOAD GROUND TERMINALS. ANY UNUSED CONDUCTORS IN POWER
CIRCUITS SHALL BE CONNECTED AS EQUIPMENT GROUND CONDUCTORS AT EACH
END. SEE DETAILS 34A AND 34D.
22. CORE DRILL 5" DIAMETER HOLE FOR CONDUIT PENETRATION THROUGH BRICK WALL
AND WEATHER SEAL WITH CAULK OR NON-SHRINK GROUT AS NECESSARY ON
BOTH INSIDE AND OUTSIDE OF WALL. WHERE CONDUIT PASSES FROM INTERIOR TO
EXTERIOR OF BUILDING, FOLLOW NEC GUIDELINES FOR SEALING INTERIOR OF
RACEWAYS EXPOSED TO DIFFERENT TEMPERATURES. INSTALL INTERNAL CONDUIT
SEAL IN CONDUIT BODY ADJACENT TO WALL, SHOWN IN PLAN VIEW 43B.
LIST OF ABBREVIATIONS:
ARR ARRANGEMENT
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
ATR ALL-THREADED ROD
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
AWS AMERICAN WELDING SOCIETY
BLDG BUILDING
CAD COMPUTER AIDED DESIGN
CAT NO. CATALOG NUMBER
DET DETAIL
EDTF ELECTRIC DRIVE TEST FACILITY
ETC ETCETERA
EXST EXISTING
FLG FLANGE
GND GROUND
GTG GAS TURBINE GENERATOR
HTP HEAT TRANSFER PACKAGE
LOM LIST OF MATERIAL
MGR MANAGER
MIN MINIMUM
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NETA INTERNATIONAL ELECTRICAL TESTING ASSOCIATION
NSWCPD NAVAL SURFACE WARFARE CENTER - PHILADELPHIA DIVISION
OD OUTSIDE DIAMETER
PROG PROGRAM
PROJ PROJECT
QA QUALITY ASSURANCE
REF REFERENCE
REV REVISION
REQ'D REQUIRED
TECH TECHNICAL
THK THICK
TYP TYPICAL
W/ WITH
GTG-B CITY WATER & DRAIN PIPING INTERFACE
ARRANGEMENT & DETAILS
GTG-B GAS FUEL SUPPLY PIPING INTERFACE
ARRANGEMENT & DETAILS
GTG-B EQUIPMENT ARRANGEMENT 8044
SEE PLAN VIEW 20A
FOR CABLE ROUTING
BLDG 670
B
D
E
A
3230282624222018161412108642
343230282624222018161412108642
RESERVATIONS:
1. TERMINATION INFORMATION IN GTG-B AUX TRAILER RESERVED
PENDING RECEIPT FROM GTG-B VENDOR.
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 2
D
D
C
B
A
D
C
B
A
910111213141516
910111213141516
REDUCED SIZE PRINT
ISOMETRIC VIEW 13A
LOOKING NORTHWEST
SCALE: NONE GTG-B FAC POWER INTERFACE
ISOMETRIC VIEW
804089256
* NOTE: EXISTING CABLE TRAYS
NOT SHOWN FOR CLARITY.
SCALE : AS NOTED
D
D
C
B
A
D
C
B
A
REDUCED SIZE PRINT
SHEET 3
89256
1718192021222324
1718192021222324
PLAN VIEW 20A
GTG-B 13KV CABLE TRAY
ROUTING
SCALE: 3/16" = 1'-0"
NORTH GTG-B FAC POWER INTERFACE
PLAN VIEW
92'-8"
1'-6"
16'-0"
DET 36A
3X DET 37C
A29 C
C
DET 40D
2X DET 47A
DET 43B
22'-4"
1'-6"
10'-2"
21'-10"
DET 39A
DET 47D
EXST SUPPORTS
SEE REF 1
GTG-B AUX
TRAILER
2'-6"
16'-7"
EXST 4" 450V
CONDUIT
ITEM 9
ITEM 9
GRAPHIC SCALE 3/16"=1'-0"
0 1' 2' 3' 4' 5' 10' 15' 20'
POWER PANEL
GTG-AUX
EAST SUBSTATION
2X DET 45C
5X DET 36C
10'-0" 10'-0"8'-9"
* NOTE: EXISTING CABLE TRAYS
NOT SHOWN FOR CLARITY.
GTG PAD
D
D
C
B
A
D
C
B
A
REDUCED SIZE PRINT
SHEET 4
89256
GRAPHIC SCALE 1/4"=1'-0"
0 2'1' 3' 4' 5' 10' 15'
2526272829303132
2526272829303132
ITEM 3
SECTION VIEW 29A
LOOKING WEST
TEMPORARY GTG 450V
CABLE TRAY ROUTING
SCALE: 1/4" = 1'-0"
6"
EXST SUPPORT
STRUCTURE
7'-0"
SECTION VIEW 30C
LOOKING NORTH
TEMPORARY GTG 450V
CABLE TRAY ROUTING
SCALE: 1/4" = 1'-0"
22'-4"
10'-1"
EXST CONTROL TRAY
2X ITEM 2
EXST CONTROL TRAY
10'-1"
DET 39A
EXST CONCRETE
SUPPORT (REF 1)
SECTION VIEW 26C
LOOKING NORTH
TEMPORARY GTG 450V
CABLE TRAY ROUTING
SCALE: 1/4" = 1'-0"
ITEM 4
ITEM 3
17'-1"
GTG-B FAC POWER INTERFACE
SECTION VIEWS
13KV CABLE
TRAY (REF 1)
13KV CABLE
TRAY (REF 1)
7'-0"
3'-4"
DET 37C
DET 36A DET 40D
ITEM 4
5X ITEM 1 2X ITEM 2
3X DET 37C
ITEM 1
1'-5"
3'-4"
3'-1"
SEE DET 45D
ITEM 1
2X SEE DET 47A
ITEM 2
3X ITEM 1
ITEM 3
ITEM 4
C
5X DET 36C
DET 45C
DET 45D
DET 47D
SEE DET 43B
SEE DET 36A
D
D
C
B
A
D
C
B
A
REDUCED SIZE PRINT
SHEET 5
89256
3334353637383940
3334353637383940
GTG-B FAC POWER INTERFACE
DETAILS
GRAPHIC SCALE 3/4"=1'-0"
0 6" 2' 3' 4' 5'1'
DETAIL 37C
LOOKING NORTH
GTG-B CABLE TRAY SUPPORT
SCALE: 3/4" = 1'-0"
3/16
3/16
450V CABLE TRAY
4'-6"
1'-5"
1"
2X 4"x4"x1/4" ANGLE, ITEM 7
2X ITEM 6
2'-6" 2'-6"
1'-3"
2"
2'-6"4'-0"
450V CABLE TRAY 450V CABLE TRAY
ITEM 25
1'-5"
2'-0" 2'-6"
5'-3"
5'-9"
7'-0"
11X 4"x4"x1/4" ANGLE, ITEM 7
11X 4"x4"x1/4" ANGLE, ITEM 7
DETAIL 36A
LOOKING WEST
450V CABLE TRAY SUPPORT STAND
SCALE: 3/4" = 1'-0"
1/2" PLATE, ITEM 21
1/2" PLATE, ITEM 20
1'-4"
ITEM 25
1'-4"
1'-4"
3/164X
3/16
2X3/16
8X3/16
DETAIL 40D
LOOKING NORTH
GTG-B CABLE TRAY SUPPORT
SCALE: 3/4" = 1'-0"
2'-9" 9"
1'-5"
DETAIL 39A
LOOKING WEST
450V CABLE TRAY SUPPORT STAND
SCALE: 3/4" = 1'-0"
2'-0"
8'-0"
2'-1"
3/16 3/16
3/16
3/16
5X 4"x4"x1/4" ANGLE, ITEM 7
DETAIL 34A
TYPICAL CABLE TRAY TO
CABLE TRAY GROUND CONNECTION
SCALE: NONE
CABLE TRAY
2X ITEMS 13, 15, 16
CABLE TRAY
2X ITEMS 13, 14, 15, 16
GROUND WIRE, ITEM 19.
(AS REQ'D)
DETAIL 34D
TYPICAL CABLE TRAY TO
CABLE TRAY CONNECTION
SCALE: NONE
CABLE TRAY
2X ITEMS 13, 14, 15, 16
GROUND WIRE, ITEM 19
(AS REQ'D)
CABLE TRAY
2X ITEM 5
C8x11.5 CHANNEL ANGLE, ITEM 23
CONCRETE SUPPORT
BARRIER, ITEM 22
2X DRILL 9/16"∅ HOLE
FOR ITEM 24
6"
450V CABLE TRAY
DETAIL 36C
LOOKING NORTH
GTG-B CABLE TRAY SUPPORT
SCALE: 3/4" = 1'-0"
EXST SUPPORT
SEE REF 1
5X 4"x4"x1/4" ANGLE, ITEM 7
2X ITEM 6
2X
3/16
1'-8
D
D
C
B
A
D
C
B
A
REDUCED SIZE PRINT
SHEET 6
89256
4142434445464748
4142434445464748
GTG-B FAC POWER INTERFACE
DETAILS
DETAIL 43B
CONDUIT SUPPORT THRU
BUILDING WALL
SCALE: NONE
3/16 2X
4" CONDUIT (ITEM 9)
2X ITEM 10
2X 4"x4"x1/4" ANGLE, ITEM 7
2X DRILL 9/16"∅ HOLE
THRU BLDG WALL
FOR ITEM 12
BLDG 633
EXTERIOR WALL
2X 4"x4"x1/4"
ANGLE, ITEM 7
BLDG 633
INTERIOR WALL
2X ITEM 11
4X ITEMS
13, 15
4" RIGID METAL
CONDUIT (ITEM 9)
2X ITEM 10
4"x4"x1/4" ANGLE, ITEM 7
2"
(TYP)
4" CONDUIT (ITEM 9)
ITEM 11
4X ITEMS 13, 15
2X ITEM 12
ITEM 10
1'-6"
3" (TYP)
DETAIL 45A
CONDUIT SUPPORT BASEPLATE
SCALE: NONE
3/16
2X DRILL 9/16"∅ HOLE
IN ITEM 17 FOR ITEM 24
ITEM 17
ITEM 17,
SEE DET 45A
3/16 3/16
COPE ANGLE FLG TO FIT
DETAIL 47A
CONDUIT SUPPORT OFF
BUILDING WALL
SCALE: NONE
DRILL 9/16"∅ HOLE
THRU BLDG WALL
FOR ITEM 12
2X ITEMS 13, 15
3'-4"
ITEM 7
ITEM 7
2X ITEM 24. FOR ANCHOR INSTALLATION
SEE DETAIL 43A (SEE NOTES 12 AND 13)
2'-11"
ITEM 18
SEE DET 45B
2X ITEMS 13, 15
ITEM 12
8"
4"
8"
4"
ITEM 18
8"
4"
2"
2'-1"
2"
4"
2X
DRILL 9/16"∅ HOLE
THRU BLDG WALL
FOR ITEM 12,
2X ITEMS 13, 15
4"
DETAIL 45B
CONDUIT SUPPORT BACKPLATE
SCALE: NONE
3'-10"
45°
DETAIL 47C
1/2" ANCHOR INSTALLATION
SCALE: NONE
1/2" ADHESIVE ANCHOR,
ITEM 24 (SEE NOTES 12 & 13)
6-3/4" MIN
EMBEDMENT
CONCRETE BARRIER,
ITEM 22
C8x11.5, ITEM 23
3"
4"
DETAIL 47D
CABLE TRAY SUPPORT
SCALE: NONE
3'-4"
DETAIL 45D
CABLE TRAY SUPPORT
SCALE: NONE
2'-8"
ITEM 7
DETAIL 45C
CABLE TRAY SUPPORT
SCALE: NONE
3'-1"
ITEM 7
ITEM 7
DETAIL 43A
ANCHOR INSTALLATION IN WALL
SCALE: NONE
ITEM 24
1/2" ADHESIVE ANCHOR
(SEE NOTES 12 & 13)
PLATE
6-3/4" MIN
EMBEDMENT
BLDG WALL
2X ITEM 7
3/16
3/16
2X3/16
EXST COLUMN (TYP) EXST COLUMN
EXST COLUMN
ITEM 12
CORE DRILL THRU BRICK
WALL FOR 4" RGS CONDUITS.
SEAL HOLES W/NON-SHRINK
GROUT AS REQUIRED.
SEE NOTE 22.
D
D
C
B
A
D
C
B
A
REDUCED SIZE PRINT
SHEET 7
89256 8040
GTG-B FAC POWER INTERFACE
LOM & ONE-LINE DIAGRAM
LIST OF MATERIAL
ITEM QTY DESCRIPTION MATERIAL SPECIFICATION REMARKS
1 8
CABLE TRAY, 6"W, 6"D, 5" LOADING, STRAIGHT,
LADDER TYPE, 9" RUNG SPACING, 20' LONG
ALUMINUM NEMA 20C+ B-LINE CAT. NO. H46A09-06-240 OR EQUAL
2 3
CABLE TRAY, HORIZONTAL BEND, 90°, 6"W, 6"D, 5"
LOADING, LADDER TYPE, 9" RUNG SPACING, 12" BEND
RADIUS
ALUMINUM NEMA B-LINE CAT. NO. 6A-06-90HB12 OR EQUAL
3 2
CABLE TRAY, VERTICAL INSIDE BEND, 90°, 6"W, 6"D,
5" LOADING, LADDER TYPE, 9" RUNG SPACING,
12" BEND RADIUS
ALUMINUM NEMA B-LINE CAT. NO. 6A-06-90VI12 OR EQUAL
4 2
CABLE TRAY, VERTICAL OUTSIDE BEND, 90°, 6"W, 6"D,
5" LOADING, LADDER TYPE, 9" RUNG SPACING,
12" BEND RADIUS
ALUMINUM NEMA B-LINE CAT. NO. 6A-06-90VO12 OR EQUAL
5 2 PR
SPLICE PLATE, EXPANSION, 6" RAIL HEIGHT,
W/HARDWARE
ALUMINUM COMMERCIAL B-LINE CAT. NO. 9A-1016 OR EQUAL
6 42 BEAM CLAMP, NO-DRILL, FOR CABLE TRAY
ELECTRO-PLATED
ZINC
COMMERCIAL B-LINE CAT. NO. 9ZN-1249HD OR EQUAL
7 100 LF ANGLE, 4" x 4" x 1/4" THK CARBON STEEL ASTM A36 CUT TO SUIT
8 250 LF
BUILDING WIRE, 3C W/ GROUND, 500 MCM, COPPER,
600V, 90°C, 2.26" O.D., TRAY CABLE
VARIOUS COMMERCIAL
HOUSTON W&C CAT. NO. HW15450003
OR EQUAL
9 2
CONDUIT, RIGID, 4", 10' LG, STANDARD THREAD
W/COUPLING
GALVANIZED STEEL COMMERCIAL WESCO CAT. NO. 78001000110 OR EQUAL
10 1 CHANNEL, 1-5/8" x 1-5/8" x 12 GAUGE, 20' LONG
PRE-GALVANIZED
STEEL
COMMERCIAL
B-LINE CAT. NO. B22-GALV-240
OR EQUAL. CUT TO SUIT.
11 2 PIPE CLAMP, STRUT TYPE, 4", W/HARDWARE
ELECTRO-PLATED
ZINC
COMMERCIAL B-LINE CAT.NO. BB2017PAZN OR EQUAL
12 2 1/2" THREADED ROD (ATR), x 12' LONG, 1350 LB DESIGN
LOAD
ELECTRO-PLATED
ZINC
COMMERCIAL
B-LINE CAT. NO. ATR1/2"x144-ZN
OR EQUAL. CUT TO SUIT.
AS
REQ'D
FLAT WASHER, 1/2"
ELECTRO-PLATED
ZINC
COMMERCIAL
B-LINE CAT. NO. 1/2" FW OR EQUAL.
USED W/ITEM 16.
AS
REQ'D
COMPRESSION LUG, ONE HOLE, STRAIGHT,
SHORT BARREL
TIN PLATED
COPPER
COMMERCIAL BURNDY CAT. NO. YAD28M10E38 OR EQUAL
AS
REQ'D
HEX NUT, 1/2-13 UNC ALLOY STEEL ASTM A325
AS
REQ'D
BOLT, 1/2"-13UNC-2A x 1" LG ALLOY STEEL ASTM A325
17 2 PLATE, 8" x 46" x 1/4" THK CARBON STEEL ASTM A36 SEE DETAIL 45A
18 2 PLATE, 8" x 8" x 1/4" THK CARBON STEEL ASTM A36 SEE DETAIL 45B
AS
REQ'D
BUILDING WIRE, 1C, 4/0 AWG, COPPER, 600V, 90°C,
THHN/THWN INSULATION, 0.64" O.D.
VARIOUS COMMERCIAL
HOUSTON W&C CAT. NO. HW00140101
OR EQUAL
20 1 PLATE, 30" x 30" x 1/2" THK CARBON STEEL ASTM A36 SEE DETAIL 40D
21 1 PLATE, 48" x 30" x 1/2" THK CARBON STEEL ASTM A36 SEE DETAIL 36A
22 3 NEW JERSEY BARRIER, 60" LONG CONCRETE ASTM C825
23 15 LF C-CHANNEL, C8x11.5 CARBON STEEL ASTM A36 CUT TO SUIT
24 6
ANCHOR BOLT, 1/2" HAS ROD, 8" LONG, W/HEX NUT &
WASHER. 6-3/4" MINIMUM EMBEDMENT
CARBON STEEL COMMERCIAL
HILTI HIT-HY70 ADHESIVE ANCHOR SYSTEM
CAT. NO. HAS-E 1/2x8 W/SC18X85 SCREENS
OR EQUAL
25 1 CHANNEL, 1-5/8" x 3-1/4" x 12 GAUGE, 20' LONG
PRE-GALVANIZED
STEEL
COMMERCIAL
B-LINE CAT. NO. B22A-GALV-240
OR EQUAL. CUT TO SUIT.
AS
REQ'D
CLAMP/GUIDE, CABLE TRAY, 2-1/4" LG FOR 1/2"
HARDWARE, INSTALLED AS CLAMP
ELECTRO-PLATED
ZINC
COMMERCIAL B-LINE CAT. NO. 9ZN-1205 OR EQUAL
AS
REQ'D
HEX HEAD CAP SCREW, 1/2" x 7/8" LONG
ELECTRO-PLATED
ZINC
COMMERCIAL
B-LINE CAT. NO. 1/2X7/8-HHCS OR EQUAL.
USE TO SECURE TRAY TO CHANNEL.
AS
REQ'D
TWIRL-NUT, 1/2-13, FOR B22/B22A CHANNEL
ELECTRO-PLATED
ZINC
COMMERCIAL
B-LINE CAT. NO. TN225WO-ZN OR EQUAL.
USED W/ITEM 26.
4950515253545556
4950515253545556
13.2KV-480V,
2500-3125KVA
(EXIST)
13.2KV-480V,
2500-3125KVA
(EXIST)
4000AF
4000AT
800AF
600AT, 3P
4000AF
4000AT
4000AF
4000AT
4000A, 480V, 3ɸ, 3W EAST SUBSTATION SWGR (EXIST)
DETAIL 51A
GAS TURBINE GENERATOR
AUXILIARY POWER ONE LINE DIAGRAM
SCALE: NONE
225AF
125AT, 3P
SPACE
MLO
400AF
400AT, 3P
POWER PANEL GTG-AUX
480V, 600A, 3ɸ, 3W
HEAT TRANSFER
EQUIPMENT (HTP-1)
SPACE
TO GTG-B AUX TRAILER
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
2X (3-1/C 250MCM + #1 GND)
1-3/C 500MCM + #2 GND
| 8040 R- Approved 2016-10-26 SH01 (1) |
| 8040 R- Approved 2016-10-26 SH02 (1) |
| 8040 R- Approved 2016-10-26 SH03 (1) |
| 8040 R- Approved 2016-10-26 SH04 (1) |
| 8040 R- Approved 2016-10-26 SH05 (1) |
| 8040 R- Approved 2016-10-26 SH06 (1) |
| 8040 R- Approved 2016-10-26 SH07 (1) |
File details come from the government source that posted it. Updated .