S

N

S

W W

S

W

E

N

S

N

GF-008GF-011

GF-009GF-010

O

A-401

DATE: 11/10/2021

EVAN MIZUE

A-701

O

DATE: 11/10/2021

WATER SUPPLY CONNECTION AT IL 30.29. WATER METER AS

PER PWC NT STANDARD DRAWING W1-1-01A

CH 0.00

INSPECTION OPENING (IO)

CH 0.99

IL 29.49

C044138 6/30/21

No.

Exp.

DN 100 PVC SN8

SWALE DRAIN

STORMWATER STORAGE BASIN (1:4

BATTERS). MINOR STORM EVENT

CAPACITY STORAGE AVAILABLE (5%

AEP STORM EVENT)

2m BASE TABLE DRAIN.

1:4 BATTERS

SAG PIT (P1) SEE DETAIL B4/C-502

HEADWALL (P3) SEE DETAIL C2/C-303

DN 450 CLASS 4 R.C.P INSTALLED IN

ACCORDANCE WITH NTG STD DRG SC 3101

0.8 % FALL

0.5

F

AL

L

INVERT LEVEL

29.479m

2m BASE TABLE DRAIN. 1:4 BATTERS. PLACED

ROCK AS SHOWN FOR SCOUR PROTECTION

JUNCTION PIT (P2) SEE DETAIL B4/C-502

5.857% FALL

LOCALLY FILL EXISTING SWALE

0.5 % FALL

INVERT LEVEL

29.479m

INVERT LEVEL

29.479m

0.85 % FALL

C-104

SANITARY DRAINAGE

POTABLE (DOMESTIC) WATER

FIRE WATER

ELECTRICAL CONDUIT

COMMUNICATIONS CONDUIT

SURFACE DRAINAGE DIRECTION

SITE SELECTION BOARD APPROVAL BOUNDARY

SS

DW

FW

E(LV) E(LV)

COMM

REFER TO DRAWING

G-102 FOR THE

CONNECTION TO

EXISTING MAIN

BATTERS REDUCED TO 1 IN 3 AT LOCALISED

AREAS DUE TO SITE CONSTRAINTS

14° BEND

CH 15.61

90° BEND

CH 31.81

CH 34.69

IL 30.75

CH 32.00

IL 30.00

90° BEND WITH INSPECTION

OPENING TO SURFACE (IOS) IN

ACCORDANCE WITH AS3500

CH 31.08

45° BEND WITH INSPECTION

OPENING TO SURFACE (IOS) IN

ACCORDANCE WITH AS3500

CH 22.16

NEW TYPE 2 SEWER CONNECTION

IN ACCORDANCE WITH PWC STD

DRG W2-1-02

CH 0.00

IL 28.24

INTERSECTION TO BE UPGRADED AS PART OF

SEPERATE WORKS PACKAGE

PAF160600 (P600)

PROJECT IMPACT AREA

45° BEND WITH INSPECTION

OPENING TO SURFACE (IOS) IN

ACCORDANCE WITH AS3500

CH 22.16

150 mm PIPE FROM MAIN TO HYDRANT

DUAL PILLAR EXTERNAL

HYDRANT IN ACCORANCE

WITH AS2419.1-2005 CL 3.2.2

SEE DETAIL C1/C-503

GRASSED AREA

NEW ASPHALT PAVEMENT AREA

UPGRADE WORKS TO ACCESS ROAD

PAVEMENT

NEW CONCRETE

OUTLET PROTECTION

MINIMUM COVER TO TOP OF SUBGRADE 600mm. REFER TO

WSA STANDARD DRAWING WAT-1201 FOR TRENCH DETAILS

BOLLARD, 2 PLACES

SEE DETAIL C2/C-503

DATE: 11/23/2021

C044138 6/30/21

No.

Exp.

G-102

0 7550

SCALE 1:2500 AT ORIGINAL SIZE

25 100 125m

RAAF BASE

DARWIN

RAAF BASE

DARWIN

FW

FW

PROJECT SITE

SQUADRON OPERATIONS FACILITY

DATE: 11/23/2021

FINAL SUBMITTAL MAY 20, 2021

E16929 6/30/23

No.

Exp.

RE

GI

S T

ER

ED PRO F E S S I ON A L E NG I NEER

ST A T E O F C A L I F O R N I A

E R I C M . P E NN

E L E C T R I C A L

SCHEMATICS

CONTACTOR

CIRCUIT BREAKER

EARTH

METER

SURGE DIVERTER

MECHANICAL SERVICES SWITCHBOARD

M

POWER

SINGLE 10A SWITCHED SOCKET OUTLET (SSO)

DOUBLE 10A SWITCHED SOCKET OUTLET (DSO)

IEC 60309 32A 3-PIN CAPTIVE NO SCREW SOCKETS

ISOLATOR

DISTRIBUTION BOARD (DB)

MAIN SWITCHBOARD (MSB)

xN,xA

SEC

FLOOR BOX

2 x DOUBLE GPO 2 x DOUBLE DATA

1x300mm CABLE TRAY

ELECTRICAL CABLE PIT

CLASS D TYPE 99 900mm X 900mm UNLESS SPECIFICALLY

STATED DIFFERENTLY ON DRAWING - SUPPLY PIT RISER TO

ALLOW CONDUITS TO ENTER PIT AT 600mm BELOW GROUND

ELECTRICAL CONDUITS

ABBREVIATIONS

AB ABOVE BENCH

AD ABOVE DOOR

ACCU AIR COOLED CONDENSER UNIT

BP BOOSTER PUMP

CHIL CHILLER

DOAS DEDICATED OUTDOOR AIR SYSTEM

EF EXHAUST FAN

EWH INSTANTANEOUS WATER HEATER

FCU FAN COIL UNIT

FDCIE FIRE DETECTION CONTROL AND INDICATING EQUIPMENT

FR FRIDGE

HD HAND DRYER

HTC HYDRONEUMATIC TANK COMPRESSOR

HWU HOT WATER UNIT

MW MICROWAVE

OWS OCCUPANT WARNING SYSTEM

PA PUBLIC ADDRESS

POC POINT OF CONNECTION

SMOF SINGLEMODE FIBRE OPTIC

TX TRANSFORMER

WWP WASTE WATER PUMP

COMMUNICATIONS

DATA OUTLET

2 DENOTES DOUBLE OUTLET

COMMUNICATIONS RACK

1x300mm COMMUNICATIONS CABLE TRAY

AUSTRALIAN - UNSECURED

1x300mm COMMUNICATIONS CABLE TRAY

USAF - UNSECURED

1x300mm COMMUNICATIONS CABLE TRAY

USAF - SECURED

COMMUNICATION CONDUITS

CLASS D PIT MIN 1250mm x 450mm x 950mm. SCEC ENDORSED WITH SCEC

ENDORSED LID. UNLESS SPECIFICALLY

STATED DIFFERENTLY ON DRAWING.

CONTRACTOR TO SUPPLY ALL

NECESSARY ANCILLARY EQUIPMENT.

LIGHTING

23W 2418 lm RECESSED PANEL 4000K, IP54

22W 2200 lm SURFACE MOUNTED BATTEN 4000K, IP65

12W/m 320lm/m LINEAR LED, 4000K, IP67

TO BE MOUNTED IN COVE IN BATHROOMS. LENGTHS SHOWN

ON E-104.

19.6W 2050 lm LED DOWNLIGHT 4000K IP44

12W 1000 lm EXTERIOR WALL LIGHT 4000K, IP 66, IK10

360° MOTION DETECTOR

PE CELL

EMERGENCY & EXIT LIGHTING

EMERGENCY EXIT SIGN (STRAIGHT AHEAD). 24M VIEWING DISTANCE.

DS DENOTES DOUBLE SIDED.

EMERGENCY EXIT SIGN (DIRECTIONAL). 24M VIEWING DISTANCE.

DS DENOTES DOUBLE SIDED.

EMERGENCY LIGHT (RECESSED) EQUIVALENT TO CLEVERTRONICS

LIFELIGHT.

C0: D40 C90: D40

L1

L2

D1

W1

LIGHTNING PROTECTION

AIR TERMINAL, 600mm IN LENGTH

EARTH ELECTRODE

AIR TERMINAL CONDUCTOR

DOWN CONDUCTOR

EARTH RING CONDUCTOR

EARTH PIT

MAIN EARTH PIT

NOTES

1. DRAWINGS ARE TO BE READ IN CONJUNCTION WITH

THE ELECTRICAL SPECIFICATION AND MIEE

DOCUMENTS.

2. DRAWINGS ARE TO BE READ IN CONJUNCTION WITH

OTHER SERVICES DRAWINGS, INCLUDING BUT NOT

LIMITED TO: STRUCTURAL, CIVIL, MECHANICAL,

HYDRAULIC (PLUMBING), ARCHITECTURE.

SWITCHTING

SWITCH WIRE(NON-ESSENTIAL)

SINGLE 10A LIGHT SWITCH - 1100 AFFL

SINGLE 10A LIGHT SWITCH W/ 1-10V ANALOGUE DIMMER -

1100 AFFL

DRY FIRE

FIRE DETECTION CONTROL AND INDICATING EQUIPMENT

(REFER TO FIRE SERVICES DRAWINGS FOR FIRE DETECTION DETAILS)

SECURITY

ACCESS PANEL

SECURITY PANEL

SPEAKERS

E

C C

E

C

CT1

CT2

CT3

WALL

CONSTRUCTION

INSTALLATION AND CONCEALED

CABLING FACILITES

RENDERED MASONARY

PARTITION

SURFACE MOUNTED BOX WITH CONDUIT CHASED

INTO WALL

FACE BRICK EXTERNAL

CAVITY WALL

SURFACE MOUNTED BOX WITH THERMOPLASTIC

INSULATED CABLES IN CONDUIT RUN IN CAVITY AND

TIED AGAINST INNER BRICK SURFACE, OR

THERMOPLASTIC SHEATHED CABLES RUN IN CAVITY

STUD PARTITION REWIRABLE

ELECTRICAL NOTES

1.GENERAL

1.1 ADDITIONAL WORK

QUALITY

WORKS BEYOND THE SCOPE OF THIS SPECIFICATION: TO THE GENERAL

QUALITY OF THIS FITOUT SPECIFICATION.

1.2 AUTHORITIES

COMPLIANCE

CONFORM TO THE FOLLOWING:

THE BUILDING CODE OF AUSTRALIA.

ANY BUILDING APPROVALS.

THE REQUIREMENTS OF LOCAL AND STATE OR TERRITORY GOVERNMENT

AUTHORITIES.

THE RELEVANT REQUIREMENTS OF THE AUSTRALIAN DEPARTMENT OF

DEFENCE.

SPECIFICATIONS

MIEE & MFPE

ELECTRICAL WORKS: USE ONLY STATE OR TERRITORY LICENSED PERSONNEL.

2.EXECUTION

2.1 SERVICES INSTALLATION

PENETRATIONS AND FIXING

FIXING: IF EQUIPMENT IS NOT SUITABLE FOR FIXING TO NON-STRUCTURAL

BUILDING ELEMENTS, FIX DIRECTLY TO STRUCTURE AND TRIM AROUND HOLES

OR PENETRATIONS IN NON-STRUCTURAL ELEMENTS.

GENERAL: IF IT IS PROPOSED TO PENETRATE OR FIX TO THE FOLLOWING,

SUBMIT DETAILS OF THE METHODS PROPOSED TO MAINTAIN THE REQUIRED

STRUCTURAL, FIRE AND OTHER PROPERTIES:

STRUCTURAL BUILDING ELEMENTS INCLUDING EXTERNAL WALLS, FIRE

WALLS, FIRE DOORS AND ACCESS PANELS, OTHER TESTED AND RATED

ASSEMBLIES OR ELEMENTS, FLOOR SLABS AND BEAMS.

MEMBRANE ELEMENTS INCLUDING DAMP-PROOF COURSES,

WATERPROOFING MEMBRANES AND ROOF COVERINGS. IF PENETRATING

MEMBRANES, PROVIDE A WATERPROOF SEAL BETWEEN THE MEMBRANE

AND THE PENETRATING COMPONENT.

FIRE RATED BUILDING ELEMENTS: SEAL PENETRATIONS WITH A SYSTEM

CONFORMING TO AS 4072.1.

NON-FIRE RATED BUILDING ELEMENTS: SEAL PENETRATIONS AROUND

CONDUITS AND SLEEVES. SEAL AROUND CABLES WITHIN SLEEVES. IF THE

BUILDING ELEMENT IS ACOUSTICALLY RATED, MAINTAIN THE RATING.

PIPE SLEEVES: IF PIPING OR CONDUIT PENETRATES BUILDING ELEMENTS,

PROVIDE METAL OR PVC SLEEVES FORMED FROM OVERSIZE PIPE SECTIONS.

ALL WIRING AND CABLING SHALL BE CONCEALED WITHIN WALLS, CEILING VOIDS

AND FINISHES. ACCESSORIES AND CONDUITS MUST BE INSTALLED AS SURFACE

MOUNTED.

2.2 COMPLETION

PROJECT FOLDER

PROVIDE A PROJECT FOLDER CONTAINING THE FOLLOWING: • RECORD

DRAWINGS OF WORKS AS BUILT.

• PRODUCT DATA WITH MAINTENANCE AND CLEANING INSTRUCTIONS.

• PRODUCT WARRANTIES

ELECTRICAL INSTALL

1.GENERAL

1.1 RESPONSIBILITIES

QUALIFICATION

GENERAL: USE ONLY PERSONS APPROPRIATELY EXPERIENCED AND QUALIFIED

TO UNDERTAKE THE ELECTRICAL DESIGN WORK ON THE SYSTEMS

DOCUMENTED.

PERFORMANCE GENERAL: CARRY OUT VERIFICATION TESTS AND

MEASUREMENTS TO SHOW COMPLIANCE WITH THE SPECIFICATION.

1.2 STANDARDS

GENERAL

ELECTRICAL SYSTEMS: TO AS/NZS 3000 AND SAA HB 301.

TELECOMMUNICATIONS CABLING: TO AS/ACIF S008, AS/ACIF S009, AS/NZS 3080

AND SAA HB 29, MANUAL OF INFRASTRUCTURE ENGINEERING - ELECTRICAL

(MIEE).

DEGREES OF PROTECTION (IP CODE): TO AS 60529.

EMC: TO AS/NZS 61000.

EMERGENCY LIGHTING: TO ASS 2293

2. EXECUTION

2.1 GENERAL

LOCATION

ARRANGEMENT: ARRANGE SERVICES SO THAT SERVICES RUNNING TOGETHER

ARE PARALLEL WITH EACH OTHER AND WITH ADJACENT BUILDING ELEMENTS.

FIXING: IF NON-STRUCTURAL BUILDING ELEMENTS ARE NOT SUITABLE FOR

FIXING EQUIPMENT AND SERVICES TO, FIX DIRECTLY TO STRUCTURE AND TRIM

AROUND HOLES OR PENETRATIONS IN NON-STRUCTURAL ELEMENTS.

INSTALLATION: ACCESSORIES AND CONDUITS MUST BE INSTALLED AS SURFACE

MOUNTED. INSTALL EQUIPMENT AND SERVICES PLUMB, FIX SECURELY AND

ORGANISE RETICULATED SERVICES NEATLY. ALLOW FOR MOVEMENT IN BOTH

STRUCTURE AND SERVICES.

2.2 INSTALLATION OF ACCESSORIES

GENERAL

ACCESSORIES: INSTALL ACCESSORIES IN CONFORMANCE WITH THE

INSTALLATION OF ACCESSORIES TABLE.

FLUSH MOUNTING: PROVIDE FLUSH MOUNTED ACCESSORIES.

LOCATION: CONFIRM THE FINAL LOCATION OF ALL OUTLETS AND EQUIPMENT ON

SITE PRIOR TO INSTALLATION.

DEFAULT MOUNTING HEIGHTS TO CENTRE OF ACCESSORY PLATE:

OUTLETS NOT ON SKIRTING DUCT – 300mm SWITCHES AND CONTROLS – 1100mm

RESTRICTED LOCATION: DO NOT INSTALL WALL BOXES ACROSS JUNCTIONS OF

WALL FRAMES INSTALLATION OF ACCESSORIES TABLE

INSTALLATION OF CEILING MOUNTED APPLIANCES

CONNECTIONS – APPLIANCES: PROVIDE FLUSH MOUNTED OUTLETS ON THE

CEILING NEXT TO SUPPORT BRACKETS.

CONNECTIONS – FIXED EQUIPMENT: PROVIDE CONCEALED PERMANENT

CONNECTIONS.

FIXING: PROVIDE SUPPORT BRACKETS FIXED THROUGH CEILING TO THE

BUILDING STRUCTURE. BRACE APPLIANCES THAT HAVE EXCESSIVE BENDING

MOMENTS, ARE HEAVY OR VIBRATE, TO PREVENT HORIZONTAL MOVEMENT.

2.3 LOW VOLTAGE POWER SYSTEMS

GENERAL

GENERAL: DESIGN AND INSTALL FINAL SUBCIRCUITS TO ALL POWER AND

LIGHTING LOADS. COORDINATE WITH ALL OTHER TRADES FOR POWER SUPPLY

AND CABLE CONDUIT / DUCTING REQUIREMENTS, REFER TO MECHANICAL,

HYDRAULIC AND COMMUNICATIONS DESIGN DOCUMENTATION.

SUBMISSIONS

TECHNICAL DATA: SUBMIT DOCUMENTATION TO FULLY DESCRIBE THE

PROPOSED INSTALLATION. AS A MINIMUM PROVIDE:

SINGLE LINE DIAGRAM,

CERTIFY COMPLIANCE WITH AS/NZS 3000, FOR ELECTRICAL SERVICES.

CIRCUIT SCHEDULES / DB SCHEDULES

ACCESSORIES

GENERAL: PROVIDE, AND AS NECESSARY, RELOCATE THE FOLLOWING:

GENERAL POWER OUTLETS.

ISOLATING SWITCHES.

PROVIDE ALL SOFT WIRING FROM SKIRTING DUCT TO TABLE BOXES

WIRING SYSTEMS

STANDARD: TO AS/NZS 3013.

THERMAL INSULATION: IN WALLS FILLED WITH THERMAL INSULATION, INSTALL

CABLES IN PVC CONDUIT.

POWER CABLES

GENERAL: COPPER CABLE GENERALLY, MULTI-STRANDED. MINIMUM SIZE:

LIGHTING SUBCIRCUITS: 2.5mm2 POWER SUBCIRCUITS: 4mm2 .

FAULT LOOP IMPEDANCE: PROVIDE FINAL SUBCIRCUIT CABLES SELECTED TO

SATISFY THE REQUIREMENTS FOR AUTOMATIC DISCONNECTION UNDER

SHORT-CIRCUIT AND EARTH FAULT/TOUCH VOLTAGE CONDITIONS.

2.4 SWITCHBOARD COMPONENTS

GENERAL: PROVIDE PROPRIETARY SWITCHBOARDS TO THE FOLLOWING AND AS

DOCUMENTED.

STANDARDS

STANDARD: TO MIEE CHAPTER 11 & AS/NZS 61439.1

DOORS

GENERAL: PROVIDE LOCKABLE DOORS WITH A CIRCUIT CARD HOLDER UNLESS

ENCLOSED IN CUPBOARDS OR IN AN AREA WHICH IS NOT READILY ACCESSIBLE

TO THE PUBLIC.

FINISHES

INTERIOR: WHITE.

EXTERIOR: MANUFACTURERS STANDARD FINISH.

VENTILATION

GENERAL: REQUIRED TO MAINTAIN DESIGN OPERATING TEMPERATURES AT

FULL LOAD.

DISTRIBUTION BOARD COMPONENTS

PROTECTIVE DEVICES

GENERAL: SELECT AND ADJUST PROTECTIVE DEVICES TO GRADE AND

COORDINATE FOR OVERCURRENT, AND EARTH FAULTS.

REQUIREMENT: AS NECESSARY PROVIDE PROTECTIVE DEVICES WHICH GRADE

AND COORDINATE FOR OVERCURRENT, LET THROUGH ENERGY, AND EARTH

FAULTS.

MOULDED CASE AND MINIATURE CIRCUIT BREAKERS

MOULDED CASE BREAKERS: TO AS/NZS 60947.1, AS 2184 AND AS 60947.2.

MINIATURE CIRCUIT BREAKERS: TO AS/NZS 60898.1 OR AS 3111.

TRIP TYPE

FAULT CAPACITY > 10 KA: TO AS 60947.2 AND AS/NZS 60947.1.

FAULT CAPACITY < 10 KA, CURRENT RATING < 100 A: MINIATURE OVERCURRENT

CIRCUIT BREAKERS TO AS/NZS 60898.1 OR AS 3111 CLIP TRAY CHASSIS.

FOR MINIATURE OVERCURRENT CIRCUIT BREAKERS PROVIDE CLIP TRAY

ASSEMBLIES CAPABLE OF ACCEPTING SINGLE, DOUBLE, OR TRIPLE CIRCUIT

BREAKERS, AND RELATED BUSBARS. PROVIDE MOULDED CLIP-ON POLE FILLERS

FOR UNUSED PORTIONS.

RESIDUAL CURRENT DEVICES

INTEGRAL TYPE: INCORPORATE EARTH LEAKAGE IN CIRCUIT BREAKER

PROTECTION OPERATION TO AS/NZS 61009.1.

MAXIMUM TRIPPING CURRENT: 30 mA.

CONTACTORS

STANDARD: TO AS/NZS 60947.4.1.

RATED OPERATIONAL CURRENT: FULL LOAD CURRENT OF THE LOAD

CONTROLLED.

MINIMUM RATING: 16 A.

2.5 LIGHTING

SCOPE

SCOPE: LIGHTING AND LIGHTING CONTROL HAVE BEEN DESIGNED AND

SPECIFIED TO AS 1680, BCA 2019 AND MIEE CHAPTER , CONSIDERING ENERGY

EFFICIENCY, PERFORMANCE, ESD AND ENVIRONMENTAL IMPLICATIONS.

GENERAL

GENERAL: CONTRACTOR TO SUPPLY AND INSTALL NEW LIGHTING AS REQUIRED

TO SUIT SPECIAL FUNCTIONAL REQUIREMENTS.

INTERIOR LIGHTING STANDARD: TO AS/NZS 1680 PARTS 1, 2.1, 2.2, AS 1680.3 AND

AS1680.5.

PROPRIETARY EQUIPMENT: PROVIDE ONLY PROPRIETARY LUMINAIRES,

FITTINGS AND ACCESSORIES.

MINIMUM ENERGY PERFORMANCE STANDARDS

GENERAL: TO AS/NZS 4783.2 AND AS/NZS 4782.2.

LAMPS

LAMPS: PROVIDE ALL LUMINAIRES COMPLETE WITH LAMPS AND ACCESSORIES.

VERIFY OPERATION: INSTALL LAMPS IN ALL LUMINAIRES AND VERIFY CORRECT

OPERATION BEFORE COMPLETION.

COLOUR RENDERING: GROUP 1B TO AS/NZS 1680.1.

COLOUR CORRECTED TEMPERATURE: 4000°K.

LOW VOLTAGE LAMPS: PROVIDE LAMPS IN CONFORMANCE WITH THE LUMINAIRE

MANUFACTURER’S RECOMMENDATION.

INSTALLATION

SUPPORTS: MOUNT LUMINAIRES ON PROPRIETARY SUPPORTS BY MEANS OF

BATTENS, TRIMS, NOGGINGS, ROSES OR PACKING MATERIAL TO SUIT LOCATION.

RECESSED LUMINAIRES SUPPORT: TO AS 2946.

2.6 EMERGENCY AND EVACUATION LIGHTING

GENERAL

GENERAL: EMERGENCY EVACUATION LIGHTING SYSTEM TO MEET THE

REQUIREMENTS OF THE BCA. TEST AND COMMISSION IN CONFORMANCE WITH

AS/NZS 2293.

PROVIDE COMPUTER MONITOR EMERGENCY LIGHTING AND EXIT SIGNS AS

DOCUMENTED TO MEET THE REQUIREMENTS OF THE BCA AND CONNECTION

INTO SITE BMS SYSTEM. TEST AND COMMISSION IN CONFORMANCE WITH

AS/NZS 2293.

LUMINAIRES

EMERGENCY EXIT SIGNS: PROVIDE EMERGENCY EXIT SIGNS AS DOCUMENTED.

GENERAL MAINTAINED AND NON-MAINTAINED LUMINAIRES: PROVIDE

LUMINAIRES AS DOCUMENTED.

OPERATING VOLTAGE: 230V AC.

VISUAL INDICATOR LIGHTS: PROVIDE A RED INDICATOR, READILY VISIBLE WHEN

THE LUMINAIRE IS IN ITS OPERATING LOCATION, WHICH INDICATES THAT THE

BATTERY IS BEING CHARGED.

BATTERIES

TYPE: PROVIDE HIGH TEMPERATURE NICKEL-CADMIUM BATTERIES CAPABLE OF

OPERATING EACH LAMP AT ITS RATED OUTPUT CONTINUOUSLY FOR AT LEAST 2

HOURS DURING COMMISSIONING TESTS AND 1.5 HOURS DURING SUBSEQUENT

TESTS.

BATTERY OPERATED OUTPUT: 70°C.

BATTERY LIFE: AT LEAST 3 YEARS WHEN OPERATING UNDER NORMAL

CONDITIONS AT AN AMBIENT TEMPERATURE OF BETWEEN 10°C AND 40°C AND

SUBJECT TO CHARGING AND DISCHARGING AT 6 MONTHLY INTERVALS.

MARKING: INDELIBLY MARK EACH BATTERY WITH ITS DATE OF MANUFACTURE.

POWER SUPPLY

GENERAL: PROVIDE AN UNSWITCHED ACTIVE SUPPLY TO EACH LUMINAIRE AND

EXIT SIGN, ORIGINATING FROM THE ADJACENT LIGHTING UNSWITCHED ACTIVE

CIRCUIT.

LABELLING

GENERAL: LABEL EACH LUMINAIRE WITH A UNIQUE IDENTIFYING NUMBER.

PROVIDE A LABEL WHICH IS PERMANENTLY FIXED, INDELIBLE AND READABLE AT

A DISTANCE OF 1 M.

EMERGENCY EVACUATION LIGHTING SCHEDULE: RECORD THE NUMBER AND

LUMINAIRE LOCATION IN AN EMERGENCY EVACUATION LIGHTING SCHEDULE

INCLUDED IN THE OPERATION AND MAINTENANCE MANUAL.

TESTS

GENERAL: CARRY OUT TESTS, INCLUDING OUT-OF-HOURS TESTS, TO

DEMONSTRATE THE EMERGENCY AND EVACUATION SYSTEM'S PERFORMANCE.

INCLUDE THE FOLLOWING:

TEST COMPONENTS FOR CORRECT FUNCTION AND OPERATION.

DEMONSTRATE ILLUMINATION PERFORMANCE ON SITE, TO AT LEAST THE

LEVEL STATED IN THE MANUFACTURER'S RECOMMENDATIONS FOR

PERFORMANCE FOR THAT DEVICE.

TEST OPERATION OF BATTERY DISCHARGE TEST AND CONTROL TEST

SWITCH FUNCTIONS, INCLUDING DISCHARGE AND RESTORATION.

DEMONSTRATE SYSTEM FUNCTIONS UNDER MAINS FAIL CONDITION.

DEMONSTRATE OPERATION OF THE BATTERY AND CHARGER INCLUDING A

FULL DISCHARGE/RECHARGE OVER THE DESIGNATED TIME.

MAINS SUPPLY

GENERAL: BEFORE COMMISSIONING, MAKE SURE MAINS SUPPLY HAS BEEN

CONTINUOUSLY CONNECTED FOR AT LEAST 24 HOURS.

2.7 LIGHTING CONTROL

GENERAL

REQUIREMENT: PROVIDE THE FOLLOWING AS DOCUMENTED;

LIGHTING SWITCHES.

AUTOMATIC CONTROL SYSTEMS.

INTERFACE BUILDING LIGHTING CONTROL VIA BMS INTO SITE SYSTEM.

MANUAL CONTROLS

GENERAL: PROVIDE MANUAL CONTROL OF LUMINAIRES INTO GROUPS, ZONES

AND TO INDIVIDUAL DEVICES, AS DOCUMENTED.

DIRECT CURRENT INTERFACE FOR PROXIMITY SENSORS AND AMPLIFIERS: TO

AS/NZS IEC 60947.5.6.

2.8 COMMUNICATION CABLING

GENERAL

GENERAL: PROVIDE A COMPLETE OPERATIONAL TENANCY

TELECOMMUNICATIONS PASSIVE CABLING SYSTEM, TESTED AND

COMMISSIONED IN CONFORMANCE WITH AS/NZS 11801, AS/ACIF S009 AND SAA

HB 29. PROVIDE ACCOMMODATION FOR TELECOMMUNICATIONS CABLING

INFRASTRUCTURE CONFORMING TO AS/NZS 3084 & CIOG REQUIREMENTS.

INCLUDE THE FOLLOWING:

NEW TELECOMMUNICATIONS OUTLETS TO SUIT NEW LAYOUT AND

DESCRIBED SYSTEMS

SYSTEM REQUIREMENTS

APPLICATION CLASS TO AS/NZS 11801 CLAUSE 6.3: E.

BALANCED SYSTEM TO AS/NZS 11801 CLAUSE 7 (DATA): CATEGORY 6.

BALANCED SYSTEM TO AS/NZS 11801 CLAUSE 7 (VOICE): CATEGORY 6.

CONFORMANCE: CERTIFY THE DESIGN AND INSTALLATION FOR CONFORMANCE

WITH AS/NZS 11801 CLAUSE 4.

TESTING OF CABLES TO 'PERMANENT LINK' TO REQUIREMENTS OF AS/NZS 11801

SYSTEM WARRANTY: WARRANT THE SPECIFIED COMMUNICATIONS EQUIPMENT

AND CABLING CHANNEL PERFORMANCE FOR A MINIMUM OF 15 YEARS.

MODULAR CONNECTOR PATCH PANELS

TERMINATIONS: TERMINATE FIXED WIRING DIRECTLY TO THE MODULAR

CONNECTOR.

PATCH CORDS & FLY LEADS: BY IT VENDOR.

EQUIPMENT RACKS

TO BE PROVIDED AND INSTALLED BY CONTRACTOR.

CABLE SEPARATION

LOW VOLTAGE CABLES: SEPARATE TELECOMMUNICATIONS CABLES NOT

ENCLOSED IN CONDUITS OR DUCTS FROM LOW VOLTAGE SERVICES BY AT

LEAST 150mm.

ELECTROMAGNETIC INTERFERENCE (EMI): PROVIDE CLEARANCE TO MINIMISE

THE EFFECT OF EMI WHERE COMMUNICATIONS CABLES ARE INSTALLED

PARALLEL AND ADJACENT TO POWER CABLES CARRYING LOADS IN EXCESS OF

200 A.

INSTALLATION

CROSSOVER: INSTALL CABLES NEATLY AND WITHOUT CROSSOVERS BETWEEN

CABLES.

LOOM SIZE: LOOM CABLES INTO GROUPS NOT EXCEEDING 50 CABLES, AND

HOLD LOOMS IN PLACE USING REUSABLE VELCRO AT LEAST 20 MM WIDE. DO

NOT EXERT COMPRESSIVE FORCE ON THE CABLES WHEN INSTALLING CABLE

STRAPS. PVC CABLE TIES SHALL NOT BE USED.

TELECOMMUNICATIONS OUTLETS

OUTLETS: PROVIDE RJ45 8 WAY MODULAR JACKS EXCEPT WHERE DOCUMENTED

OTHERWISE.

LABELLING

LABEL BOTH ENDS OF ALL CABLES DURING INSTALLATION.

2.9 CABLE SUPPORTS AND DUCT SYSTEM

RESPONSIBILITIES

GENERAL

PROVIDE CABLE SUPPORT, TRUNKING AND DUCT SYSTEMS, AS DOCUMENTED.

PROVIDE FIRE RATED CABLE SUPPORTS FOR LIFE SAFETY SYSTEMS. PROVIDE

TEST CERTIFICATES TO AS/NZS 3013.

CONDUITS

STANDARDS: AS/NZS 2053.1

TYPE: RIGID.

SIZES

CONDUITS: 20 mm.

UNDERGROUND: 25 mm.

CONDUITS FOR TELECOMMUNICATIONS: 25 mm.

FIXINGS

SURFACE MOUNTED: DOUBLE SIDED FIXED.

IN CONCRETE SLABS: TIE TO STRUCTURAL STEEL.

COLOUR

CONDUITS GENERALLY: LIGHT ORANGE.

TELECOMMUNICATIONS SYSTEMS CONDUITS: WHITE.

NON-METALLIC CONDUITS AND FITTINGS

GENERAL

STANDARDS: NON-METALLIC CONDUITS AND FITTINGS: AS/NZS 2053.2, AS/NZS

2053.3, AS/NZS 2053.4, AS/NZS 2053.5 OR AS/NZS 2053.6.

SOLAR RADIATION PROTECTION: REQUIRED FOR CONDUITS AND FITTINGS

EXPOSED TO SUNLIGHT.

FLEXIBLE CONDUIT

GENERAL: PROVIDE FLEXIBLE CONDUIT TO CONNECT WITH EQUIPMENT AND

PLANT SUBJECTED TO VIBRATION. IF REQUIRED, PROVIDE FOR ADJUSTMENT OR

EASE OF MAINTENANCE. PROVIDE THE MINIMUM POSSIBLE LENGTH.

ASSOCIATED FITTINGS

TYPE: PROVIDE ASSOCIATED FITTINGS OF THE SAME TYPE AND MATERIAL AS

THE CONDUIT.

WALL BOXES ON UPVC CONDUITS: PROVIDE PREFABRICATED EARTHED METAL

BOXES, FOR SPECIAL SIZE WALL BOXES NOT AVAILABLE IN UPVC.

INSPECTION FITTINGS

GENERAL: PROVIDE INSPECTION-TYPE FITTINGS ONLY IN ACCESSIBLE

LOCATIONS AND WHERE EXPOSED TO VIEW.

JOINTS

TYPE: CEMENTED OR SNAP-ON JOINTS.

CABLE PITS

GENERAL

CABLE DRAW-IN PITS: PROVIDE CABLE DRAW-IN PITS AS DOCUMENTED. SIZES

GIVEN ARE INTERNAL DIMENSIONS.

PROPRIETARY CABLE PITS

PITS 1200 X 1200 mm: PROVIDE PROPRIETARY CONCRETE OR POLYMER

MOULDED PITS.

IN SITU CONSTRUCTION

PITS > 1200 X 1200 mm: PROVIDE EITHER:

PROPRIETARY CABLE PITS.

CONSTRUCT WALLS AND BOTTOMS FROM 75 mm THICK REINFORCED

CONCRETE. INCORPORATE A WATERPROOFING AGENT IN THE RENDER OR

CONCRETE.

PIT COVERS

GENERAL: PROVIDE PIT COVERS TO SUIT EXTERNAL LOADS. FIT FLUSH WITH

THE TOP OF THE PIT.

STANDARD: TO AS 3996.

WEIGHT: < 40 KG FOR ANY SECTION OF THE COVER.

LIFTING HANDLES: PROVIDE A LIFTING HANDLE FOR EACH SIZE OF COVER

SECTION.

DRAINAGE

GENERAL: PROVIDE DRAINAGE FROM THE BOTTOM OF CABLE PITS, EITHER TO

ABSORPTION TRENCHES FILLED WITH RUBBLE OR TO THE STORMWATER

DRAINAGE SYSTEM.

ABSORPTION TRENCHES: MINIMUM SIZE 300 x 300 x 2000 mm.

EXECUTION CONDUIT SYSTEMS - INSTALLATION INSPECTION FITTINGS

LOCATION: LOCATE IN ACCESSIBLE POSITIONS.

DRAW CORDS

GENERAL: PROVIDE 5 mm2 POLYPROPYLENE DRAW CORDS IN CONDUITS NOT IN

USE.

DRAW-IN BOXES

GENERAL: FOR CONDUITS IN ACCESSIBLE LOCATIONS PROVIDE DRAW-IN BOXES

AS FOLLOWS:

IN STRAIGHT RUNS AT > 30m: SPACING 30m.

AT CHANGES OF LEVEL OR DIRECTION.

UNDERGROUND DRAW-IN BOXES: PROVIDE GASKETED COVERS AND SEAL

AGAINST MOISTURE. INSTALL IN ACCESSIBLE PITS.

EXPANSION

GENERAL: ALLOW FOR THERMAL EXPANSION/CONTRACTION OF CONDUITS AND

FITTINGS DUE TO CHANGES IN AMBIENT TEMPERATURE CONDITIONS. PROVIDE

EXPANSION COUPLINGS AS REQUIRED.

RIGID CONDUITS

GENERAL: PROVIDE STRAIGHT LONG RUNS, SMOOTH AND FREE FROM RAGS,

BURRS AND SHARP EDGES. SET CONDUITS TO MINIMISE THE NUMBER OF

FITTINGS.

ROUTES

SET OUT: IF EXPOSED TO VIEW, INSTALL CONDUITS IN PARALLEL RUNS WITH

RIGHT ANGLE CHANGES OF DIRECTION.

BENDS: INSTALL CONDUITS WITH NO MORE THAN 2 RIGHT ANGLED BENDS PER

CABLE DRAW-IN RUN.

CONCEALED CONDUITS: RUN CONDUITS CONCEALED IN WALL CHASES,

EMBEDDED IN FLOOR SLABS OR INSTALLED IN INACCESSIBLE LOCATIONS

DIRECTLY BETWEEN POINTS OF TERMINATION, MINIMISING THE NUMBER OF

SETS. DO NOT PROVIDE INSPECTION FITTINGS. USE LARGE RADIUS BENDS OR

ELBOWS.

CONDUITS IN CONCRETE SLABS

ROUTE: DO NOT RUN IN CONCRETE TOPPINGS. DO NOT RUN WITHIN

PRETENSIONING CABLE ZONES. CROSS PRETENSIONING CABLE ZONES AT

RIGHT ANGLES. ROUTE TO AVOID CROSSOVERS AND MINIMISE THE NUMBER OF

CONDUITS IN ANY LOCATION.

PARALLEL CONDUIT SPACING: 50 mm APART.

CONDUITS IN MECHANICAL PLANT ROOM SLABS: AVOID INSTALLATION OF

CONDUITS IN PLANT ROOM SLABS (BOILER ROOMS, MECHANICAL PLANT ROOMS

AND TANK ROOMS) IF CONDUITS AND CABLES ARE LIKELY TO EXPERIENCE HIGH

TEMPERATURES, BE SUBJECT TO CORE HOLE DRILLING, DRILLING OF LARGE

ANCHOR BOLT POINTS OR WHERE EXACT PLANT LOCATIONS ARE UNKNOWN AT

TIME SLAB IS POURED.

MINIMUM COVER: THE GREATER OF THE CONDUIT DIAMETER AND 20 mm.

CONSTRUCTION JOINTS: PROVIDE SLEEVING OVER CONDUIT TO ALLOW

MOVEMENT OF THE CONDUIT ACROSS THE JOINT DUE TO ANY SLAB

MOVEMENT.

FIXING: FIX DIRECTLY TO THE TOP OF THE BOTTOM LAYER OF REINFORCING.

CONDUITS IN HOLLOW-BLOCK FLOORS

LOCATION: LOCATE CONDUITS IN THE CORE-FILLED SECTIONS OF PRECAST

HOLLOW-BLOCK TYPE FLOORS.

CONDUITS IN COLUMNS

NUMBER AND SIZE OF CONDUITS IN COLUMNS: AS DETERMINED BY THE

STRUCTURAL ENGINEER.

BENDS

ENTER COLUMNS WITH RADIUS SWEEP BENDS GREATER THAN OR

EQUAL TO 150 mm. DO NOT USE ELBOWS.

CHASING

DO NOT CHASE COLUMNS.CABLES IN TRENCHES - INSTALLATION

SAND BED AND SURROUND

GENERAL: CONFORM TO THE SERVICE TRENCHING WORKSECTION.

SAND BED AND SURROUNDS: PROVIDE AT LEAST 150 mm CLEAN SHARP SAND

AROUND CABLES AND CONDUITS INSTALLED UNDERGROUND.

SEALING DUCTS AND CONDUITS

GENERAL: SEAL BURIED ENTRIES TO DUCTS AND CONDUITS WITH WATERPROOF

SEALS AS FOLLOWS:

SPARE DUCTS AND CONDUITS: IMMEDIATELY AFTER INSTALLATION.

OTHER DUCTS AND CONDUITS: AFTER CABLE INSTALLATION.

ALL SURFACES ARE TO BE REINSTATED TO A QUALITY EQUAL TO OR BETTER

THAN EXISTING SURFACE QUALITY.

E-001

L3

CO

RE

SP

ON

SE

T O

NA

VF

AC

C

OM

M

EN

TS

.0 6.

C.

S

DATE: 06/21/2023

Keith Hayashi

SEC

AB

E(

LV

E(

LV

E(

LV

E(

LV

E(

LV

E(

LV

E(

LV

AB

ENSURE MINIMUM SEPARATION

OF 300mm BETWEEN LV AND

COMMUNICATIONS SERVICES

PROVIDE 25mm CONDUIT AND JUNCTION

BOXES TO TOP OF DOOR TO ALLOW FOR

FUTURE DOOR REED SWITCH.

MSB

EWH

3N,63A

ACCU 2

1N,10A

DOAS-1

3N,32A

ACCU-5

1N,32A

ACCU 3

1N,32A

HWU

1N,10A

FDCIE

1N,10A

SEC

1N,10A

MDB

AB

EF

1N,10A

EF

1N,10A

BP

1N,10A

BP

1N,10A

ACCU 1

3N,40A

WP WP

WP

IBT

BUSBAR

(NOTE 12)

EF

1N,10A

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

DB-TEF

E(

LV

E(

LV

E(

LV

E(

LV

E(

LV

E(

LV

E(

LV

AD

TX

ACCU-4

1N,32A

WWP

1N,10A

DOAS-1

CONTROL

PANEL

FR MW

SEALED CONDUIT RACEWAY

THROUGH SECURE WALL FOR

CABLE ACCESS BETWEEN

SEGREGATED AREAS

MS

SB

-P

MS

SB

-P

MS

SB

-P

MS

SB

-P

MD

B-

P8

MD

B-

P9

MD

B-

P1

MS

SB

-P

MS

B-

FI

P

DB

-T

EF

-P

DB

-T

EF

-P

DB

-T

EF

-P

MS

B-

SE

C

MS

SB

-P

MS

SB

-P

MD

B-

P1

MD

B-

P2

MD

B-

P3

MD

B-

P4

MD

B-

P5

MD

B-

P6

MD

B-

P1

MD

B-

P1

MD

B-

P1

MD

B-

P1

MD

B-

P1

MD

B-

P1

MD

B-

P1

MS

SB

-P

MS

SB

-P

MS

SB

-P

MS

SB

-P

MS

SB

-P

MS

SB

-P

DB

-T

EF

-P

MD

B-

P7

MS

SB

-P

MD

B-

P1

DB

-T

EF

-P

CO

DB

-T

EF

-P

DB

-T

EF

-P

DB

-T

EF

-P

1N,32A

MD

B-

P1

(NOTE 17)

DDS

PANEL

PROVIDE 25mm CONDUIT IN WALL FOR FUTURE

INCOMING CARD READER. CAP OFF CONDUIT.

PROVIDE 20mm CONDUIT AND JUNCTION

BOX TO DOOR FRAME FOR FUTURE

ELECTRIC STRIKE. CAP OFF CONDUIT.

(NOTE 17)

COMMUNICATIONS RACKS

50mm CONDUIT FOR SATCOM

POWER

(NOTE 18)

(NOTE 17)

(NOTE 16)

(NOTE 17)

PROVIDE 2x25mm CONDUIT AND JUNCTION

BOXES TO DOOR FRAME FOR FUTURE

ELECTRIC STRIKE AND ELECTRIC LOCK. CAP

OFF CONDUIT.

PROVIDE 25mm CONDUIT TO DOOR FRAME

FOR MICROSWITCH MONITORING

SECONDARY DEADBOLT. CAP OFF CONDUIT.

PROVIDE 25mm CONDUIT AND JUNCTION BOX TO DOOR

FRAME(INACTIVE LEAF HINGE SIDE) FOR FUTURE

DOOR ELECTRIC STRIKE. CAP OFF CONDUIT.

(NOTE 17)

PROVIDE 25mm CONDUIT IN WALL FOR FUTURE

INCOMING CARD READER, ELECTRIC LOCK AND

DOOR REED SWITCH. CAP OFF CONDUIT

PROVIDE 2x25mm CONDUIT TO DOOR

FRAME FOR FUTURE ELECTRIC STRIKE

AND ELECTRIC LOCK. CAP OFF

CONDUIT.

PROVIDE 25mm CONDUIT TO DOOR

FRAME FOR MICROSWITCH

MONITORING SECONDARY DEADBOLT.

CAP OFF CONDUIT.

PROVIDE 25mm CONDUIT IN WALL FOR FUTURE

INCOMING CARD READER, ELECTRIC LOCK AND

DOOR REED SWITCH. CAP OFF CONDUIT

ACCU-1/AHU-1

CONTROL PANEL

SEE E-101 FOR

CONTINUATION

COMM COMM COMM COMM COMM COMM COMM COMM COMM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

2x100mm

COMMUNICATION CONDUITS FROM

SATCOM

E(

LV

E(

LV

E(

LV

E(

LV

E(

LV

E(

LV

E(

LV

E(

LV

6RU CABINET FOR DESN

AND FIDCIE SERVICES.

COMMUNICATIONS PIT

SPECS PER E-001 LEGEND

ZONE 2 FIT FOR BUT NOT

WITH ZONE 4 PROVISIONS

ZONE 2

CO

CO

CO

CO

CO

FINAL SUBMITTAL MAY 20, 2021

E16929 6/30/23

No.

Exp.

RE

GI

S T

ER

ED PRO F E S S I ON A L E NG I NEER

ST A T E O F C A L I F O R N I A

E R I C M . P E NN

E L E C T R I C A L

N

SCALE 1:50 AT ORIGINAL SIZE

500 2000 2500mm15001000

POWER AND SECURITY LAYOUT

SCALE 1:50

NOTES:

1. DRAWING TO BE READ IN CONJUNCTION WITH ARCHITECTURAL AND OTHER SERVICES

DRAWINGS.

2. FINAL LOCATIONS OF ELECTRICAL EQUIPMENT, POWER SUPPLIES AND ISOLATORS SHALL

BE DETERMINED ON SITE BY ELECTRICAL CONTRACTOR IN CO-ORDINATION WITH THE

RESPECTIVE TRADE TO SUIT EQUIPMENT AND INSTALLATION CONDITIONS.

3. THE CONTRACTOR SHALL LIAISE WITH THE MECHANICAL, HYDRAULIC, FIRE

CONTRACTORS AND THE ARCHITECT TO CONFIRM FINAL LOCATION OF

4. ALL CABLING SYSTEMS SHALL BE INSTALLED ON TENSION WIRE/TRAY, IN FALSE CEILINGS, IN SUITABLE DUCT UNDER BENCHES.

5. ALL POWER OUTLETS SHALL BE LABELED TO INDICATE TO WHICH DISTRIBUTION BOARD

AND CIRCUIT IT IS CONNECTED.

6. POWER CABLE TRAY SHALL BE 600mm.

7. FLOOR BOX TO BE SUPPLIED VIA 25mm² CONDUIT FROM WALL.

8. CONTRACTOR SHALL PROVIDE BOXES WITH 25mm² CONDUIT TO TOP OF WALL WHERE

NOTED FOR FUTURE CARD READERS NEXT TO EACH DOOR AT VESTIBULE FOR ADF LEVEL

4 SECURITY.

9. REFER TO MECHANICAL SPECIFICATION FOR FAN COIL UNITS & POWER CONNECTIONS.

10. SUPPLY POWER TO VAV BOXES. CABLE SHALL BE NO LESS THEN 4mm² PVC.

11. GPOS IN TOILETS ROOMS TO BE INSTALLED AT COUNTER HEIGHT.

12. PRIMARY BUS BAR TO BE INSTALLED WITHIN DB-TEF. ALL TELECOMMUNICATIONS DEVICES

TO BE CONNECT TO THE THE BONDING BUS BAR.

13. OUTLET SHALL BE ABOVE DOOR FOR POTENTIAL ESS.

14. ALLOW FOR CONDUIT, CABLE AND CONNECTION OF LIGHTNING PROTECTION MASS EARTH

INTO MSB MEN SYSTEM.

15. CONTRACTOR SHALL PROVIDE 25mm CONDUITS IN THE CEILING FOR FUTURE ALARMS AT

EACH DOOR IN VESTIBULES. DOORS ENTERING THE ELECTRICAL, MECHANICAL AND TEF

ROOMS. THE DOOR LEAVING THE SECURE ZONE OUTSIDE. EACH CONDUIT SHALL HAVE A

DRAW WIRE. COORDINATE WITH ARCHITECTURE ELEVATIONS FOR LOCATIONS OF

CONDUITS AND JUNCTION BOXES FOR FUTURE SECURITY EQUIPMENT .

16. PRESTIGE TYPE GPO SWITCHES TO BE USED FOR THE PWD TOLIET, INSTALLED AT 800

AFFL.

17. SUPPLY POWER TO MECHANICAL CONTROL PANELS FROM MECHANICAL SERVICES

SWITCH BOARD

E-102

RE

SP

ON

SE

T O

NA

VF

AC

C

OM

M

EN

TS

.0 6.

C.

S

DIAL OUT TO DPN BASE

NETWORK

SECURITY

PANEL

ACCESS PANEL

SECURITY SYSTEM - BLOCK DIAGRAM

NOT TO SCALE

DOOR SWITCHES

USAF

RACK 1

SECURE

USAF

RACK 2

UNSECURE

AUS

RACK 3

UNSECURE

TYPICAL

DATA

OUTLETS

SECURED AREA

UNSECURED AREA

DPN

CONNECTION TO

BASE NETWORK

(NOTE 3)

TO SATELLITE

PAD

TO SATELLITE

PAD

TELECOMMUNICATIONS - BLOCK DIAGRAM

NOT TO SCALE

TYPICAL VAV POWER CIRCUIT

NO SCALE

CB 'A'

16A

CB 'A' VAV BOX

LOCAL VAV SWITCH

(INSTALLED NEAR VAV BOX)

TYPICAL FOR ALL DISTRIBUTION BOARDS

EMERGENCY LIGHTING ACTIVATION & TEST CIRCUIT

NOT TO SCALE

CB 'A'

16A

CONTACTOR

TIMER

C

T

TEST PUSH

BUTTON

CB 'A'

EMERGENCY

SUPPLY

CB 'A'

SWITCHED

SUPPLY NORMAL

LIGHTING

EMERGENCY LIGHTING TEST SWITCH

(INSTALLED IN DB)

ELCR

DESN/BMS

CONNECTION TO

BASE NETWORK

(NOTE 4) SPARE

NOMINATED SINGLE 48 STRAND

CABLE. ALLOCATE 12 CORES FOR

DESN/BMS SERVICE AND 36

CORES FOR DPN SERVICE

FIRE SAFETY

CONNECTION TO

FUEL FARM #7

(NOTE 5)

FINAL SUBMITTAL MAY 20, 2021

E16929 6/30/23

No.

Exp.

RE

GI

S T

ER

ED PRO F E S S I ON A L E NG I NEER

ST A T E O F C A L I F O R N I A

E R I C M . P E NN

E L E C T R I C A L

NOTES

1. CONTRACTOR TO PROVIDE AND INSTALL 42 RU COMMUNICATIONS RACK.

CLIENT SHALL PROVIDE RACK EQUIPMENT. CONTRACTOR SHALL CONNECT

SPECIFIED OUTLETS TO RACK UPS SUPPLIED BY CLIENT.

2. COORDINATE FDCIE INSTALLATION WITH FIRE PROTECTION AND MECHANICAL

DESIGN AND SPECIFICATIONS.

3. COORDINATE BASE DPN CONNECTION WITH TELSTRA. FIBRE TO TERMINATE

AT DAR-064. REFER TO DRAWING E100 FOR CABLE ROUTE.

4. COORDINATE DESN/BMS WITH BROAD SPECTRUM. FIBRE TO TERMINATE AT

BMS CONTROLLER AT DAR-064. REFER TO DRAWING E100 FOR CABLE ROUTE.

5. CONNECT INTO FUEL FARM #7 EXISTING FIP.

6. ALL DESN/BMS SERVICES CONNECTING IN INTO BASE NETWORK MUST DO SO

VIA BLACK FIBRE TIE AT BUILDING COMMUNICATIONS RACK.

7. OUTLETS SHALL BE APPROPRIATELY LABELLED TO DENOTE WHICH RACK

THEY ARE SUPPLIED BY.

8. COORDINATE POWER SUPPLY TO VAV BOXES AND HVAC EQUIPMENT WITH

MECHANICAL EQUIPMENT CONTRACTOR.

9. CABLES FROM EACH RACK TO BE PHYSICALLY SEPARATED BY DIFFERENT

CABLE TRAYS DESCRIBED IN E-103.

10. DOUBLE DATA OUTLETS INDICATIVELY SHOWN SHARING / SPLITTING TWO

COMMUNICATION SERVICES. EACH DOUBLE DATA OUTLET SHOULD PROVIDE

TWO DESCRIBED SERVICES. USAF SECURE AND UNSECURE WITHIN THE

SECURED AREA. AND USAF UNSECURED AND AUS UNSECURE WITHIN THE

UNSECURED AREA. OUTLETS SHOULD APPROPRIATELY LABEL SERVICES.

11. CONTRACTOR TO FURNISH RACKS AS SHOWN ON PLANS, READY FOR

CUSTOMER DATA EQUIPMENT TO BE INSTALLED. THIS WILL INCLUDE

CABINETS, MOUNTING EQUIPMENT, POWER BOARDS, PDUS, AND POWER

POINTS ABOVE RACKS. CONTRACTOR MUST ALSO FURNISH ALL EQUIPMENT

REQUIRED FOR INTERNAL COMMUNICATIONS CABLING AND EXTERNAL

PASSIVE NETWORK TO BE CONNECTED COMPLETE, READY FOR USER

EQUIPMENT CONNECTION. THIS WILL INCLUDE FOBOTS, PATCH PANELS,

TERMINATIONS, CABLES AND DATA OUTLETS.

E-603

RE

SP

ON

SE

T O

NA

VF

AC

C

OM

M

EN

TS

.0 6.

C.

S

21R1343-AMD4_Dwgs.pdf
C-104 STORMWATER AND UTILITIES LAYOUT PLAN
G-102 HAUL ROUTE, LAYDOWN AND STOCKPILE AREAS
P700_AMD-ELEC DWGS_Signed_Final.pdf
E-001 - LEGENDS & NOTES
E-102 - POWER AND SECURITY LAYOUT
E-603 - DIAGRAM & SCHEMATICS