23R1318-AMD1_Dwgs.pdf
PDF 5 MB Posted
- Attached to
- FY22 MCAF PROJECT PAF160700 SQUADRON OPERATIONS FACILITY, ROYAL AUSTRALIAN AIR FORCE BASE DARWIN, AUSTRALIA
- Solicitation number
- N6274223R1318
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 23r1318-Amd4Dwgs.pdf | ||
| 23R1318-Note5.pdf | ||
| 23R1318-Amd4.pdf | ||
| 23R1318-Note4.pdf | ||
| 23R1318-AMD3.pdf | ||
| 23R1318-Note3.pdf | ||
| 23R1318-AMD2_Dwgs.pdf | ||
| 23R1318-AMD2.pdf | ||
| 23R1318-Note2.pdf | ||
| 23R1318-SiteVisitSignIn.pdf | ||
| 23R1318-Note1.pdf | ||
| 23R1318-AMD1.pdf | ||
| 23R1318-RFP.pdf | ||
| 23R1318-Specs.pdf | ||
| 23R1318-Dwgs.pdf |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S
N
S
W W
S
W
E
N
S
N
GF-008GF-011
GF-009GF-010
O
A-401
DATE: 11/10/2021
EVAN MIZUE
A-701
O
DATE: 11/10/2021
WATER SUPPLY CONNECTION AT IL 30.29. WATER METER AS
PER PWC NT STANDARD DRAWING W1-1-01A
CH 0.00
INSPECTION OPENING (IO)
CH 0.99
IL 29.49
C044138 6/30/21
No.
Exp.
DN 100 PVC SN8
SWALE DRAIN
STORMWATER STORAGE BASIN (1:4
BATTERS). MINOR STORM EVENT
CAPACITY STORAGE AVAILABLE (5%
AEP STORM EVENT)
2m BASE TABLE DRAIN.
1:4 BATTERS
SAG PIT (P1) SEE DETAIL B4/C-502
HEADWALL (P3) SEE DETAIL C2/C-303
DN 450 CLASS 4 R.C.P INSTALLED IN
ACCORDANCE WITH NTG STD DRG SC 3101
0.8 % FALL
0.5
F
AL
L
INVERT LEVEL
29.479m
2m BASE TABLE DRAIN. 1:4 BATTERS. PLACED
ROCK AS SHOWN FOR SCOUR PROTECTION
JUNCTION PIT (P2) SEE DETAIL B4/C-502
5.857% FALL
LOCALLY FILL EXISTING SWALE
0.5 % FALL
INVERT LEVEL
29.479m
INVERT LEVEL
29.479m
0.85 % FALL
C-104
SANITARY DRAINAGE
POTABLE (DOMESTIC) WATER
FIRE WATER
ELECTRICAL CONDUIT
COMMUNICATIONS CONDUIT
SURFACE DRAINAGE DIRECTION
SITE SELECTION BOARD APPROVAL BOUNDARY
SS
DW
FW
E(LV) E(LV)
COMM
REFER TO DRAWING
G-102 FOR THE
CONNECTION TO
EXISTING MAIN
BATTERS REDUCED TO 1 IN 3 AT LOCALISED
AREAS DUE TO SITE CONSTRAINTS
14° BEND
CH 15.61
90° BEND
CH 31.81
CH 34.69
IL 30.75
CH 32.00
IL 30.00
90° BEND WITH INSPECTION
OPENING TO SURFACE (IOS) IN
ACCORDANCE WITH AS3500
CH 31.08
45° BEND WITH INSPECTION
OPENING TO SURFACE (IOS) IN
ACCORDANCE WITH AS3500
CH 22.16
NEW TYPE 2 SEWER CONNECTION
IN ACCORDANCE WITH PWC STD
DRG W2-1-02
CH 0.00
IL 28.24
INTERSECTION TO BE UPGRADED AS PART OF
SEPERATE WORKS PACKAGE
PAF160600 (P600)
PROJECT IMPACT AREA
45° BEND WITH INSPECTION
OPENING TO SURFACE (IOS) IN
ACCORDANCE WITH AS3500
CH 22.16
150 mm PIPE FROM MAIN TO HYDRANT
DUAL PILLAR EXTERNAL
HYDRANT IN ACCORANCE
WITH AS2419.1-2005 CL 3.2.2
SEE DETAIL C1/C-503
GRASSED AREA
NEW ASPHALT PAVEMENT AREA
UPGRADE WORKS TO ACCESS ROAD
PAVEMENT
NEW CONCRETE
OUTLET PROTECTION
MINIMUM COVER TO TOP OF SUBGRADE 600mm. REFER TO
WSA STANDARD DRAWING WAT-1201 FOR TRENCH DETAILS
BOLLARD, 2 PLACES
SEE DETAIL C2/C-503
DATE: 11/23/2021
C044138 6/30/21
No.
Exp.
G-102
0 7550
SCALE 1:2500 AT ORIGINAL SIZE
25 100 125m
RAAF BASE
DARWIN
RAAF BASE
DARWIN
FW
FW
PROJECT SITE
SQUADRON OPERATIONS FACILITY
DATE: 11/23/2021
FINAL SUBMITTAL MAY 20, 2021
E16929 6/30/23
No.
Exp.
RE
GI
S T
ER
ED PRO F E S S I ON A L E NG I NEER
ST A T E O F C A L I F O R N I A
E R I C M . P E NN
E L E C T R I C A L
SCHEMATICS
CONTACTOR
CIRCUIT BREAKER
EARTH
METER
SURGE DIVERTER
MECHANICAL SERVICES SWITCHBOARD
M
POWER
SINGLE 10A SWITCHED SOCKET OUTLET (SSO)
DOUBLE 10A SWITCHED SOCKET OUTLET (DSO)
IEC 60309 32A 3-PIN CAPTIVE NO SCREW SOCKETS
ISOLATOR
DISTRIBUTION BOARD (DB)
MAIN SWITCHBOARD (MSB)
xN,xA
SEC
FLOOR BOX
2 x DOUBLE GPO 2 x DOUBLE DATA
1x300mm CABLE TRAY
ELECTRICAL CABLE PIT
CLASS D TYPE 99 900mm X 900mm UNLESS SPECIFICALLY
STATED DIFFERENTLY ON DRAWING - SUPPLY PIT RISER TO
ALLOW CONDUITS TO ENTER PIT AT 600mm BELOW GROUND
ELECTRICAL CONDUITS
ABBREVIATIONS
AB ABOVE BENCH
AD ABOVE DOOR
ACCU AIR COOLED CONDENSER UNIT
BP BOOSTER PUMP
CHIL CHILLER
DOAS DEDICATED OUTDOOR AIR SYSTEM
EF EXHAUST FAN
EWH INSTANTANEOUS WATER HEATER
FCU FAN COIL UNIT
FDCIE FIRE DETECTION CONTROL AND INDICATING EQUIPMENT
FR FRIDGE
HD HAND DRYER
HTC HYDRONEUMATIC TANK COMPRESSOR
HWU HOT WATER UNIT
MW MICROWAVE
OWS OCCUPANT WARNING SYSTEM
PA PUBLIC ADDRESS
POC POINT OF CONNECTION
SMOF SINGLEMODE FIBRE OPTIC
TX TRANSFORMER
WWP WASTE WATER PUMP
COMMUNICATIONS
DATA OUTLET
2 DENOTES DOUBLE OUTLET
COMMUNICATIONS RACK
1x300mm COMMUNICATIONS CABLE TRAY
AUSTRALIAN - UNSECURED
1x300mm COMMUNICATIONS CABLE TRAY
USAF - UNSECURED
1x300mm COMMUNICATIONS CABLE TRAY
USAF - SECURED
COMMUNICATION CONDUITS
CLASS D PIT MIN 1250mm x 450mm x 950mm. SCEC ENDORSED WITH SCEC
ENDORSED LID. UNLESS SPECIFICALLY
STATED DIFFERENTLY ON DRAWING.
CONTRACTOR TO SUPPLY ALL
NECESSARY ANCILLARY EQUIPMENT.
LIGHTING
23W 2418 lm RECESSED PANEL 4000K, IP54
22W 2200 lm SURFACE MOUNTED BATTEN 4000K, IP65
12W/m 320lm/m LINEAR LED, 4000K, IP67
TO BE MOUNTED IN COVE IN BATHROOMS. LENGTHS SHOWN
ON E-104.
19.6W 2050 lm LED DOWNLIGHT 4000K IP44
12W 1000 lm EXTERIOR WALL LIGHT 4000K, IP 66, IK10
360° MOTION DETECTOR
PE CELL
EMERGENCY & EXIT LIGHTING
EMERGENCY EXIT SIGN (STRAIGHT AHEAD). 24M VIEWING DISTANCE.
DS DENOTES DOUBLE SIDED.
EMERGENCY EXIT SIGN (DIRECTIONAL). 24M VIEWING DISTANCE.
DS DENOTES DOUBLE SIDED.
EMERGENCY LIGHT (RECESSED) EQUIVALENT TO CLEVERTRONICS
LIFELIGHT.
C0: D40 C90: D40
L1
L2
D1
W1
LIGHTNING PROTECTION
AIR TERMINAL, 600mm IN LENGTH
EARTH ELECTRODE
AIR TERMINAL CONDUCTOR
DOWN CONDUCTOR
EARTH RING CONDUCTOR
EARTH PIT
MAIN EARTH PIT
NOTES
1. DRAWINGS ARE TO BE READ IN CONJUNCTION WITH
THE ELECTRICAL SPECIFICATION AND MIEE
DOCUMENTS.
2. DRAWINGS ARE TO BE READ IN CONJUNCTION WITH
OTHER SERVICES DRAWINGS, INCLUDING BUT NOT
LIMITED TO: STRUCTURAL, CIVIL, MECHANICAL,
HYDRAULIC (PLUMBING), ARCHITECTURE.
SWITCHTING
SWITCH WIRE(NON-ESSENTIAL)
SINGLE 10A LIGHT SWITCH - 1100 AFFL
SINGLE 10A LIGHT SWITCH W/ 1-10V ANALOGUE DIMMER -
1100 AFFL
DRY FIRE
FIRE DETECTION CONTROL AND INDICATING EQUIPMENT
(REFER TO FIRE SERVICES DRAWINGS FOR FIRE DETECTION DETAILS)
SECURITY
ACCESS PANEL
SECURITY PANEL
SPEAKERS
E
C C
E
C
CT1
CT2
CT3
WALL
CONSTRUCTION
INSTALLATION AND CONCEALED
CABLING FACILITES
RENDERED MASONARY
PARTITION
SURFACE MOUNTED BOX WITH CONDUIT CHASED
INTO WALL
FACE BRICK EXTERNAL
CAVITY WALL
SURFACE MOUNTED BOX WITH THERMOPLASTIC
INSULATED CABLES IN CONDUIT RUN IN CAVITY AND
TIED AGAINST INNER BRICK SURFACE, OR
THERMOPLASTIC SHEATHED CABLES RUN IN CAVITY
STUD PARTITION REWIRABLE
ELECTRICAL NOTES
1.GENERAL
1.1 ADDITIONAL WORK
QUALITY
WORKS BEYOND THE SCOPE OF THIS SPECIFICATION: TO THE GENERAL
QUALITY OF THIS FITOUT SPECIFICATION.
1.2 AUTHORITIES
COMPLIANCE
CONFORM TO THE FOLLOWING:
THE BUILDING CODE OF AUSTRALIA.
ANY BUILDING APPROVALS.
THE REQUIREMENTS OF LOCAL AND STATE OR TERRITORY GOVERNMENT
AUTHORITIES.
THE RELEVANT REQUIREMENTS OF THE AUSTRALIAN DEPARTMENT OF
DEFENCE.
SPECIFICATIONS
MIEE & MFPE
ELECTRICAL WORKS: USE ONLY STATE OR TERRITORY LICENSED PERSONNEL.
2.EXECUTION
2.1 SERVICES INSTALLATION
PENETRATIONS AND FIXING
FIXING: IF EQUIPMENT IS NOT SUITABLE FOR FIXING TO NON-STRUCTURAL
BUILDING ELEMENTS, FIX DIRECTLY TO STRUCTURE AND TRIM AROUND HOLES
OR PENETRATIONS IN NON-STRUCTURAL ELEMENTS.
GENERAL: IF IT IS PROPOSED TO PENETRATE OR FIX TO THE FOLLOWING,
SUBMIT DETAILS OF THE METHODS PROPOSED TO MAINTAIN THE REQUIRED
STRUCTURAL, FIRE AND OTHER PROPERTIES:
STRUCTURAL BUILDING ELEMENTS INCLUDING EXTERNAL WALLS, FIRE
WALLS, FIRE DOORS AND ACCESS PANELS, OTHER TESTED AND RATED
ASSEMBLIES OR ELEMENTS, FLOOR SLABS AND BEAMS.
MEMBRANE ELEMENTS INCLUDING DAMP-PROOF COURSES,
WATERPROOFING MEMBRANES AND ROOF COVERINGS. IF PENETRATING
MEMBRANES, PROVIDE A WATERPROOF SEAL BETWEEN THE MEMBRANE
AND THE PENETRATING COMPONENT.
FIRE RATED BUILDING ELEMENTS: SEAL PENETRATIONS WITH A SYSTEM
CONFORMING TO AS 4072.1.
NON-FIRE RATED BUILDING ELEMENTS: SEAL PENETRATIONS AROUND
CONDUITS AND SLEEVES. SEAL AROUND CABLES WITHIN SLEEVES. IF THE
BUILDING ELEMENT IS ACOUSTICALLY RATED, MAINTAIN THE RATING.
PIPE SLEEVES: IF PIPING OR CONDUIT PENETRATES BUILDING ELEMENTS,
PROVIDE METAL OR PVC SLEEVES FORMED FROM OVERSIZE PIPE SECTIONS.
ALL WIRING AND CABLING SHALL BE CONCEALED WITHIN WALLS, CEILING VOIDS
AND FINISHES. ACCESSORIES AND CONDUITS MUST BE INSTALLED AS SURFACE
MOUNTED.
2.2 COMPLETION
PROJECT FOLDER
PROVIDE A PROJECT FOLDER CONTAINING THE FOLLOWING: • RECORD
DRAWINGS OF WORKS AS BUILT.
• PRODUCT DATA WITH MAINTENANCE AND CLEANING INSTRUCTIONS.
• PRODUCT WARRANTIES
ELECTRICAL INSTALL
1.GENERAL
1.1 RESPONSIBILITIES
QUALIFICATION
GENERAL: USE ONLY PERSONS APPROPRIATELY EXPERIENCED AND QUALIFIED
TO UNDERTAKE THE ELECTRICAL DESIGN WORK ON THE SYSTEMS
DOCUMENTED.
PERFORMANCE GENERAL: CARRY OUT VERIFICATION TESTS AND
MEASUREMENTS TO SHOW COMPLIANCE WITH THE SPECIFICATION.
1.2 STANDARDS
GENERAL
ELECTRICAL SYSTEMS: TO AS/NZS 3000 AND SAA HB 301.
TELECOMMUNICATIONS CABLING: TO AS/ACIF S008, AS/ACIF S009, AS/NZS 3080
AND SAA HB 29, MANUAL OF INFRASTRUCTURE ENGINEERING - ELECTRICAL
(MIEE).
DEGREES OF PROTECTION (IP CODE): TO AS 60529.
EMC: TO AS/NZS 61000.
EMERGENCY LIGHTING: TO ASS 2293
2. EXECUTION
2.1 GENERAL
LOCATION
ARRANGEMENT: ARRANGE SERVICES SO THAT SERVICES RUNNING TOGETHER
ARE PARALLEL WITH EACH OTHER AND WITH ADJACENT BUILDING ELEMENTS.
FIXING: IF NON-STRUCTURAL BUILDING ELEMENTS ARE NOT SUITABLE FOR
FIXING EQUIPMENT AND SERVICES TO, FIX DIRECTLY TO STRUCTURE AND TRIM
AROUND HOLES OR PENETRATIONS IN NON-STRUCTURAL ELEMENTS.
INSTALLATION: ACCESSORIES AND CONDUITS MUST BE INSTALLED AS SURFACE
MOUNTED. INSTALL EQUIPMENT AND SERVICES PLUMB, FIX SECURELY AND
ORGANISE RETICULATED SERVICES NEATLY. ALLOW FOR MOVEMENT IN BOTH
STRUCTURE AND SERVICES.
2.2 INSTALLATION OF ACCESSORIES
GENERAL
ACCESSORIES: INSTALL ACCESSORIES IN CONFORMANCE WITH THE
INSTALLATION OF ACCESSORIES TABLE.
FLUSH MOUNTING: PROVIDE FLUSH MOUNTED ACCESSORIES.
LOCATION: CONFIRM THE FINAL LOCATION OF ALL OUTLETS AND EQUIPMENT ON
SITE PRIOR TO INSTALLATION.
DEFAULT MOUNTING HEIGHTS TO CENTRE OF ACCESSORY PLATE:
OUTLETS NOT ON SKIRTING DUCT – 300mm SWITCHES AND CONTROLS – 1100mm
RESTRICTED LOCATION: DO NOT INSTALL WALL BOXES ACROSS JUNCTIONS OF
WALL FRAMES INSTALLATION OF ACCESSORIES TABLE
INSTALLATION OF CEILING MOUNTED APPLIANCES
CONNECTIONS – APPLIANCES: PROVIDE FLUSH MOUNTED OUTLETS ON THE
CEILING NEXT TO SUPPORT BRACKETS.
CONNECTIONS – FIXED EQUIPMENT: PROVIDE CONCEALED PERMANENT
CONNECTIONS.
FIXING: PROVIDE SUPPORT BRACKETS FIXED THROUGH CEILING TO THE
BUILDING STRUCTURE. BRACE APPLIANCES THAT HAVE EXCESSIVE BENDING
MOMENTS, ARE HEAVY OR VIBRATE, TO PREVENT HORIZONTAL MOVEMENT.
2.3 LOW VOLTAGE POWER SYSTEMS
GENERAL
GENERAL: DESIGN AND INSTALL FINAL SUBCIRCUITS TO ALL POWER AND
LIGHTING LOADS. COORDINATE WITH ALL OTHER TRADES FOR POWER SUPPLY
AND CABLE CONDUIT / DUCTING REQUIREMENTS, REFER TO MECHANICAL,
HYDRAULIC AND COMMUNICATIONS DESIGN DOCUMENTATION.
SUBMISSIONS
TECHNICAL DATA: SUBMIT DOCUMENTATION TO FULLY DESCRIBE THE
PROPOSED INSTALLATION. AS A MINIMUM PROVIDE:
SINGLE LINE DIAGRAM,
CERTIFY COMPLIANCE WITH AS/NZS 3000, FOR ELECTRICAL SERVICES.
CIRCUIT SCHEDULES / DB SCHEDULES
ACCESSORIES
GENERAL: PROVIDE, AND AS NECESSARY, RELOCATE THE FOLLOWING:
GENERAL POWER OUTLETS.
ISOLATING SWITCHES.
PROVIDE ALL SOFT WIRING FROM SKIRTING DUCT TO TABLE BOXES
WIRING SYSTEMS
STANDARD: TO AS/NZS 3013.
THERMAL INSULATION: IN WALLS FILLED WITH THERMAL INSULATION, INSTALL
CABLES IN PVC CONDUIT.
POWER CABLES
GENERAL: COPPER CABLE GENERALLY, MULTI-STRANDED. MINIMUM SIZE:
LIGHTING SUBCIRCUITS: 2.5mm2 POWER SUBCIRCUITS: 4mm2 .
FAULT LOOP IMPEDANCE: PROVIDE FINAL SUBCIRCUIT CABLES SELECTED TO
SATISFY THE REQUIREMENTS FOR AUTOMATIC DISCONNECTION UNDER
SHORT-CIRCUIT AND EARTH FAULT/TOUCH VOLTAGE CONDITIONS.
2.4 SWITCHBOARD COMPONENTS
GENERAL: PROVIDE PROPRIETARY SWITCHBOARDS TO THE FOLLOWING AND AS
DOCUMENTED.
STANDARDS
STANDARD: TO MIEE CHAPTER 11 & AS/NZS 61439.1
DOORS
GENERAL: PROVIDE LOCKABLE DOORS WITH A CIRCUIT CARD HOLDER UNLESS
ENCLOSED IN CUPBOARDS OR IN AN AREA WHICH IS NOT READILY ACCESSIBLE
TO THE PUBLIC.
FINISHES
INTERIOR: WHITE.
EXTERIOR: MANUFACTURERS STANDARD FINISH.
VENTILATION
GENERAL: REQUIRED TO MAINTAIN DESIGN OPERATING TEMPERATURES AT
FULL LOAD.
DISTRIBUTION BOARD COMPONENTS
PROTECTIVE DEVICES
GENERAL: SELECT AND ADJUST PROTECTIVE DEVICES TO GRADE AND
COORDINATE FOR OVERCURRENT, AND EARTH FAULTS.
REQUIREMENT: AS NECESSARY PROVIDE PROTECTIVE DEVICES WHICH GRADE
AND COORDINATE FOR OVERCURRENT, LET THROUGH ENERGY, AND EARTH
FAULTS.
MOULDED CASE AND MINIATURE CIRCUIT BREAKERS
MOULDED CASE BREAKERS: TO AS/NZS 60947.1, AS 2184 AND AS 60947.2.
MINIATURE CIRCUIT BREAKERS: TO AS/NZS 60898.1 OR AS 3111.
TRIP TYPE
FAULT CAPACITY > 10 KA: TO AS 60947.2 AND AS/NZS 60947.1.
FAULT CAPACITY < 10 KA, CURRENT RATING < 100 A: MINIATURE OVERCURRENT
CIRCUIT BREAKERS TO AS/NZS 60898.1 OR AS 3111 CLIP TRAY CHASSIS.
FOR MINIATURE OVERCURRENT CIRCUIT BREAKERS PROVIDE CLIP TRAY
ASSEMBLIES CAPABLE OF ACCEPTING SINGLE, DOUBLE, OR TRIPLE CIRCUIT
BREAKERS, AND RELATED BUSBARS. PROVIDE MOULDED CLIP-ON POLE FILLERS
FOR UNUSED PORTIONS.
RESIDUAL CURRENT DEVICES
INTEGRAL TYPE: INCORPORATE EARTH LEAKAGE IN CIRCUIT BREAKER
PROTECTION OPERATION TO AS/NZS 61009.1.
MAXIMUM TRIPPING CURRENT: 30 mA.
CONTACTORS
STANDARD: TO AS/NZS 60947.4.1.
RATED OPERATIONAL CURRENT: FULL LOAD CURRENT OF THE LOAD
CONTROLLED.
MINIMUM RATING: 16 A.
2.5 LIGHTING
SCOPE
SCOPE: LIGHTING AND LIGHTING CONTROL HAVE BEEN DESIGNED AND
SPECIFIED TO AS 1680, BCA 2019 AND MIEE CHAPTER , CONSIDERING ENERGY
EFFICIENCY, PERFORMANCE, ESD AND ENVIRONMENTAL IMPLICATIONS.
GENERAL
GENERAL: CONTRACTOR TO SUPPLY AND INSTALL NEW LIGHTING AS REQUIRED
TO SUIT SPECIAL FUNCTIONAL REQUIREMENTS.
INTERIOR LIGHTING STANDARD: TO AS/NZS 1680 PARTS 1, 2.1, 2.2, AS 1680.3 AND
AS1680.5.
PROPRIETARY EQUIPMENT: PROVIDE ONLY PROPRIETARY LUMINAIRES,
FITTINGS AND ACCESSORIES.
MINIMUM ENERGY PERFORMANCE STANDARDS
GENERAL: TO AS/NZS 4783.2 AND AS/NZS 4782.2.
LAMPS
LAMPS: PROVIDE ALL LUMINAIRES COMPLETE WITH LAMPS AND ACCESSORIES.
VERIFY OPERATION: INSTALL LAMPS IN ALL LUMINAIRES AND VERIFY CORRECT
OPERATION BEFORE COMPLETION.
COLOUR RENDERING: GROUP 1B TO AS/NZS 1680.1.
COLOUR CORRECTED TEMPERATURE: 4000°K.
LOW VOLTAGE LAMPS: PROVIDE LAMPS IN CONFORMANCE WITH THE LUMINAIRE
MANUFACTURER’S RECOMMENDATION.
INSTALLATION
SUPPORTS: MOUNT LUMINAIRES ON PROPRIETARY SUPPORTS BY MEANS OF
BATTENS, TRIMS, NOGGINGS, ROSES OR PACKING MATERIAL TO SUIT LOCATION.
RECESSED LUMINAIRES SUPPORT: TO AS 2946.
2.6 EMERGENCY AND EVACUATION LIGHTING
GENERAL
GENERAL: EMERGENCY EVACUATION LIGHTING SYSTEM TO MEET THE
REQUIREMENTS OF THE BCA. TEST AND COMMISSION IN CONFORMANCE WITH
AS/NZS 2293.
PROVIDE COMPUTER MONITOR EMERGENCY LIGHTING AND EXIT SIGNS AS
DOCUMENTED TO MEET THE REQUIREMENTS OF THE BCA AND CONNECTION
INTO SITE BMS SYSTEM. TEST AND COMMISSION IN CONFORMANCE WITH
AS/NZS 2293.
LUMINAIRES
EMERGENCY EXIT SIGNS: PROVIDE EMERGENCY EXIT SIGNS AS DOCUMENTED.
GENERAL MAINTAINED AND NON-MAINTAINED LUMINAIRES: PROVIDE
LUMINAIRES AS DOCUMENTED.
OPERATING VOLTAGE: 230V AC.
VISUAL INDICATOR LIGHTS: PROVIDE A RED INDICATOR, READILY VISIBLE WHEN
THE LUMINAIRE IS IN ITS OPERATING LOCATION, WHICH INDICATES THAT THE
BATTERY IS BEING CHARGED.
BATTERIES
TYPE: PROVIDE HIGH TEMPERATURE NICKEL-CADMIUM BATTERIES CAPABLE OF
OPERATING EACH LAMP AT ITS RATED OUTPUT CONTINUOUSLY FOR AT LEAST 2
HOURS DURING COMMISSIONING TESTS AND 1.5 HOURS DURING SUBSEQUENT
TESTS.
BATTERY OPERATED OUTPUT: 70°C.
BATTERY LIFE: AT LEAST 3 YEARS WHEN OPERATING UNDER NORMAL
CONDITIONS AT AN AMBIENT TEMPERATURE OF BETWEEN 10°C AND 40°C AND
SUBJECT TO CHARGING AND DISCHARGING AT 6 MONTHLY INTERVALS.
MARKING: INDELIBLY MARK EACH BATTERY WITH ITS DATE OF MANUFACTURE.
POWER SUPPLY
GENERAL: PROVIDE AN UNSWITCHED ACTIVE SUPPLY TO EACH LUMINAIRE AND
EXIT SIGN, ORIGINATING FROM THE ADJACENT LIGHTING UNSWITCHED ACTIVE
CIRCUIT.
LABELLING
GENERAL: LABEL EACH LUMINAIRE WITH A UNIQUE IDENTIFYING NUMBER.
PROVIDE A LABEL WHICH IS PERMANENTLY FIXED, INDELIBLE AND READABLE AT
A DISTANCE OF 1 M.
EMERGENCY EVACUATION LIGHTING SCHEDULE: RECORD THE NUMBER AND
LUMINAIRE LOCATION IN AN EMERGENCY EVACUATION LIGHTING SCHEDULE
INCLUDED IN THE OPERATION AND MAINTENANCE MANUAL.
TESTS
GENERAL: CARRY OUT TESTS, INCLUDING OUT-OF-HOURS TESTS, TO
DEMONSTRATE THE EMERGENCY AND EVACUATION SYSTEM'S PERFORMANCE.
INCLUDE THE FOLLOWING:
TEST COMPONENTS FOR CORRECT FUNCTION AND OPERATION.
DEMONSTRATE ILLUMINATION PERFORMANCE ON SITE, TO AT LEAST THE
LEVEL STATED IN THE MANUFACTURER'S RECOMMENDATIONS FOR
PERFORMANCE FOR THAT DEVICE.
TEST OPERATION OF BATTERY DISCHARGE TEST AND CONTROL TEST
SWITCH FUNCTIONS, INCLUDING DISCHARGE AND RESTORATION.
DEMONSTRATE SYSTEM FUNCTIONS UNDER MAINS FAIL CONDITION.
DEMONSTRATE OPERATION OF THE BATTERY AND CHARGER INCLUDING A
FULL DISCHARGE/RECHARGE OVER THE DESIGNATED TIME.
MAINS SUPPLY
GENERAL: BEFORE COMMISSIONING, MAKE SURE MAINS SUPPLY HAS BEEN
CONTINUOUSLY CONNECTED FOR AT LEAST 24 HOURS.
2.7 LIGHTING CONTROL
GENERAL
REQUIREMENT: PROVIDE THE FOLLOWING AS DOCUMENTED;
LIGHTING SWITCHES.
AUTOMATIC CONTROL SYSTEMS.
INTERFACE BUILDING LIGHTING CONTROL VIA BMS INTO SITE SYSTEM.
MANUAL CONTROLS
GENERAL: PROVIDE MANUAL CONTROL OF LUMINAIRES INTO GROUPS, ZONES
AND TO INDIVIDUAL DEVICES, AS DOCUMENTED.
DIRECT CURRENT INTERFACE FOR PROXIMITY SENSORS AND AMPLIFIERS: TO
AS/NZS IEC 60947.5.6.
2.8 COMMUNICATION CABLING
GENERAL
GENERAL: PROVIDE A COMPLETE OPERATIONAL TENANCY
TELECOMMUNICATIONS PASSIVE CABLING SYSTEM, TESTED AND
COMMISSIONED IN CONFORMANCE WITH AS/NZS 11801, AS/ACIF S009 AND SAA
HB 29. PROVIDE ACCOMMODATION FOR TELECOMMUNICATIONS CABLING
INFRASTRUCTURE CONFORMING TO AS/NZS 3084 & CIOG REQUIREMENTS.
INCLUDE THE FOLLOWING:
NEW TELECOMMUNICATIONS OUTLETS TO SUIT NEW LAYOUT AND
DESCRIBED SYSTEMS
SYSTEM REQUIREMENTS
APPLICATION CLASS TO AS/NZS 11801 CLAUSE 6.3: E.
BALANCED SYSTEM TO AS/NZS 11801 CLAUSE 7 (DATA): CATEGORY 6.
BALANCED SYSTEM TO AS/NZS 11801 CLAUSE 7 (VOICE): CATEGORY 6.
CONFORMANCE: CERTIFY THE DESIGN AND INSTALLATION FOR CONFORMANCE
WITH AS/NZS 11801 CLAUSE 4.
TESTING OF CABLES TO 'PERMANENT LINK' TO REQUIREMENTS OF AS/NZS 11801
SYSTEM WARRANTY: WARRANT THE SPECIFIED COMMUNICATIONS EQUIPMENT
AND CABLING CHANNEL PERFORMANCE FOR A MINIMUM OF 15 YEARS.
MODULAR CONNECTOR PATCH PANELS
TERMINATIONS: TERMINATE FIXED WIRING DIRECTLY TO THE MODULAR
CONNECTOR.
PATCH CORDS & FLY LEADS: BY IT VENDOR.
EQUIPMENT RACKS
TO BE PROVIDED AND INSTALLED BY CONTRACTOR.
CABLE SEPARATION
LOW VOLTAGE CABLES: SEPARATE TELECOMMUNICATIONS CABLES NOT
ENCLOSED IN CONDUITS OR DUCTS FROM LOW VOLTAGE SERVICES BY AT
LEAST 150mm.
ELECTROMAGNETIC INTERFERENCE (EMI): PROVIDE CLEARANCE TO MINIMISE
THE EFFECT OF EMI WHERE COMMUNICATIONS CABLES ARE INSTALLED
PARALLEL AND ADJACENT TO POWER CABLES CARRYING LOADS IN EXCESS OF
200 A.
INSTALLATION
CROSSOVER: INSTALL CABLES NEATLY AND WITHOUT CROSSOVERS BETWEEN
CABLES.
LOOM SIZE: LOOM CABLES INTO GROUPS NOT EXCEEDING 50 CABLES, AND
HOLD LOOMS IN PLACE USING REUSABLE VELCRO AT LEAST 20 MM WIDE. DO
NOT EXERT COMPRESSIVE FORCE ON THE CABLES WHEN INSTALLING CABLE
STRAPS. PVC CABLE TIES SHALL NOT BE USED.
TELECOMMUNICATIONS OUTLETS
OUTLETS: PROVIDE RJ45 8 WAY MODULAR JACKS EXCEPT WHERE DOCUMENTED
OTHERWISE.
LABELLING
LABEL BOTH ENDS OF ALL CABLES DURING INSTALLATION.
2.9 CABLE SUPPORTS AND DUCT SYSTEM
RESPONSIBILITIES
GENERAL
PROVIDE CABLE SUPPORT, TRUNKING AND DUCT SYSTEMS, AS DOCUMENTED.
PROVIDE FIRE RATED CABLE SUPPORTS FOR LIFE SAFETY SYSTEMS. PROVIDE
TEST CERTIFICATES TO AS/NZS 3013.
CONDUITS
STANDARDS: AS/NZS 2053.1
TYPE: RIGID.
SIZES
CONDUITS: 20 mm.
UNDERGROUND: 25 mm.
CONDUITS FOR TELECOMMUNICATIONS: 25 mm.
FIXINGS
SURFACE MOUNTED: DOUBLE SIDED FIXED.
IN CONCRETE SLABS: TIE TO STRUCTURAL STEEL.
COLOUR
CONDUITS GENERALLY: LIGHT ORANGE.
TELECOMMUNICATIONS SYSTEMS CONDUITS: WHITE.
NON-METALLIC CONDUITS AND FITTINGS
GENERAL
STANDARDS: NON-METALLIC CONDUITS AND FITTINGS: AS/NZS 2053.2, AS/NZS
2053.3, AS/NZS 2053.4, AS/NZS 2053.5 OR AS/NZS 2053.6.
SOLAR RADIATION PROTECTION: REQUIRED FOR CONDUITS AND FITTINGS
EXPOSED TO SUNLIGHT.
FLEXIBLE CONDUIT
GENERAL: PROVIDE FLEXIBLE CONDUIT TO CONNECT WITH EQUIPMENT AND
PLANT SUBJECTED TO VIBRATION. IF REQUIRED, PROVIDE FOR ADJUSTMENT OR
EASE OF MAINTENANCE. PROVIDE THE MINIMUM POSSIBLE LENGTH.
ASSOCIATED FITTINGS
TYPE: PROVIDE ASSOCIATED FITTINGS OF THE SAME TYPE AND MATERIAL AS
THE CONDUIT.
WALL BOXES ON UPVC CONDUITS: PROVIDE PREFABRICATED EARTHED METAL
BOXES, FOR SPECIAL SIZE WALL BOXES NOT AVAILABLE IN UPVC.
INSPECTION FITTINGS
GENERAL: PROVIDE INSPECTION-TYPE FITTINGS ONLY IN ACCESSIBLE
LOCATIONS AND WHERE EXPOSED TO VIEW.
JOINTS
TYPE: CEMENTED OR SNAP-ON JOINTS.
CABLE PITS
GENERAL
CABLE DRAW-IN PITS: PROVIDE CABLE DRAW-IN PITS AS DOCUMENTED. SIZES
GIVEN ARE INTERNAL DIMENSIONS.
PROPRIETARY CABLE PITS
PITS 1200 X 1200 mm: PROVIDE PROPRIETARY CONCRETE OR POLYMER
MOULDED PITS.
IN SITU CONSTRUCTION
PITS > 1200 X 1200 mm: PROVIDE EITHER:
PROPRIETARY CABLE PITS.
CONSTRUCT WALLS AND BOTTOMS FROM 75 mm THICK REINFORCED
CONCRETE. INCORPORATE A WATERPROOFING AGENT IN THE RENDER OR
CONCRETE.
PIT COVERS
GENERAL: PROVIDE PIT COVERS TO SUIT EXTERNAL LOADS. FIT FLUSH WITH
THE TOP OF THE PIT.
STANDARD: TO AS 3996.
WEIGHT: < 40 KG FOR ANY SECTION OF THE COVER.
LIFTING HANDLES: PROVIDE A LIFTING HANDLE FOR EACH SIZE OF COVER
SECTION.
DRAINAGE
GENERAL: PROVIDE DRAINAGE FROM THE BOTTOM OF CABLE PITS, EITHER TO
ABSORPTION TRENCHES FILLED WITH RUBBLE OR TO THE STORMWATER
DRAINAGE SYSTEM.
ABSORPTION TRENCHES: MINIMUM SIZE 300 x 300 x 2000 mm.
EXECUTION CONDUIT SYSTEMS - INSTALLATION INSPECTION FITTINGS
LOCATION: LOCATE IN ACCESSIBLE POSITIONS.
DRAW CORDS
GENERAL: PROVIDE 5 mm2 POLYPROPYLENE DRAW CORDS IN CONDUITS NOT IN
USE.
DRAW-IN BOXES
GENERAL: FOR CONDUITS IN ACCESSIBLE LOCATIONS PROVIDE DRAW-IN BOXES
AS FOLLOWS:
IN STRAIGHT RUNS AT > 30m: SPACING 30m.
AT CHANGES OF LEVEL OR DIRECTION.
UNDERGROUND DRAW-IN BOXES: PROVIDE GASKETED COVERS AND SEAL
AGAINST MOISTURE. INSTALL IN ACCESSIBLE PITS.
EXPANSION
GENERAL: ALLOW FOR THERMAL EXPANSION/CONTRACTION OF CONDUITS AND
FITTINGS DUE TO CHANGES IN AMBIENT TEMPERATURE CONDITIONS. PROVIDE
EXPANSION COUPLINGS AS REQUIRED.
RIGID CONDUITS
GENERAL: PROVIDE STRAIGHT LONG RUNS, SMOOTH AND FREE FROM RAGS,
BURRS AND SHARP EDGES. SET CONDUITS TO MINIMISE THE NUMBER OF
FITTINGS.
ROUTES
SET OUT: IF EXPOSED TO VIEW, INSTALL CONDUITS IN PARALLEL RUNS WITH
RIGHT ANGLE CHANGES OF DIRECTION.
BENDS: INSTALL CONDUITS WITH NO MORE THAN 2 RIGHT ANGLED BENDS PER
CABLE DRAW-IN RUN.
CONCEALED CONDUITS: RUN CONDUITS CONCEALED IN WALL CHASES,
EMBEDDED IN FLOOR SLABS OR INSTALLED IN INACCESSIBLE LOCATIONS
DIRECTLY BETWEEN POINTS OF TERMINATION, MINIMISING THE NUMBER OF
SETS. DO NOT PROVIDE INSPECTION FITTINGS. USE LARGE RADIUS BENDS OR
ELBOWS.
CONDUITS IN CONCRETE SLABS
ROUTE: DO NOT RUN IN CONCRETE TOPPINGS. DO NOT RUN WITHIN
PRETENSIONING CABLE ZONES. CROSS PRETENSIONING CABLE ZONES AT
RIGHT ANGLES. ROUTE TO AVOID CROSSOVERS AND MINIMISE THE NUMBER OF
CONDUITS IN ANY LOCATION.
PARALLEL CONDUIT SPACING: 50 mm APART.
CONDUITS IN MECHANICAL PLANT ROOM SLABS: AVOID INSTALLATION OF
CONDUITS IN PLANT ROOM SLABS (BOILER ROOMS, MECHANICAL PLANT ROOMS
AND TANK ROOMS) IF CONDUITS AND CABLES ARE LIKELY TO EXPERIENCE HIGH
TEMPERATURES, BE SUBJECT TO CORE HOLE DRILLING, DRILLING OF LARGE
ANCHOR BOLT POINTS OR WHERE EXACT PLANT LOCATIONS ARE UNKNOWN AT
TIME SLAB IS POURED.
MINIMUM COVER: THE GREATER OF THE CONDUIT DIAMETER AND 20 mm.
CONSTRUCTION JOINTS: PROVIDE SLEEVING OVER CONDUIT TO ALLOW
MOVEMENT OF THE CONDUIT ACROSS THE JOINT DUE TO ANY SLAB
MOVEMENT.
FIXING: FIX DIRECTLY TO THE TOP OF THE BOTTOM LAYER OF REINFORCING.
CONDUITS IN HOLLOW-BLOCK FLOORS
LOCATION: LOCATE CONDUITS IN THE CORE-FILLED SECTIONS OF PRECAST
HOLLOW-BLOCK TYPE FLOORS.
CONDUITS IN COLUMNS
NUMBER AND SIZE OF CONDUITS IN COLUMNS: AS DETERMINED BY THE
STRUCTURAL ENGINEER.
BENDS
ENTER COLUMNS WITH RADIUS SWEEP BENDS GREATER THAN OR
EQUAL TO 150 mm. DO NOT USE ELBOWS.
CHASING
DO NOT CHASE COLUMNS.CABLES IN TRENCHES - INSTALLATION
SAND BED AND SURROUND
GENERAL: CONFORM TO THE SERVICE TRENCHING WORKSECTION.
SAND BED AND SURROUNDS: PROVIDE AT LEAST 150 mm CLEAN SHARP SAND
AROUND CABLES AND CONDUITS INSTALLED UNDERGROUND.
SEALING DUCTS AND CONDUITS
GENERAL: SEAL BURIED ENTRIES TO DUCTS AND CONDUITS WITH WATERPROOF
SEALS AS FOLLOWS:
SPARE DUCTS AND CONDUITS: IMMEDIATELY AFTER INSTALLATION.
OTHER DUCTS AND CONDUITS: AFTER CABLE INSTALLATION.
ALL SURFACES ARE TO BE REINSTATED TO A QUALITY EQUAL TO OR BETTER
THAN EXISTING SURFACE QUALITY.
E-001
L3
CO
RE
SP
ON
SE
T O
NA
VF
AC
C
OM
M
EN
TS
.0 6.
C.
S
DATE: 06/21/2023
Keith Hayashi
SEC
AB
E(
LV
E(
LV
E(
LV
E(
LV
E(
LV
E(
LV
E(
LV
AB
ENSURE MINIMUM SEPARATION
OF 300mm BETWEEN LV AND
COMMUNICATIONS SERVICES
PROVIDE 25mm CONDUIT AND JUNCTION
BOXES TO TOP OF DOOR TO ALLOW FOR
FUTURE DOOR REED SWITCH.
MSB
EWH
3N,63A
ACCU 2
1N,10A
DOAS-1
3N,32A
ACCU-5
1N,32A
ACCU 3
1N,32A
HWU
1N,10A
FDCIE
1N,10A
SEC
1N,10A
MDB
AB
EF
1N,10A
EF
1N,10A
BP
1N,10A
BP
1N,10A
ACCU 1
3N,40A
WP WP
WP
IBT
BUSBAR
(NOTE 12)
EF
1N,10A
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
DB-TEF
E(
LV
E(
LV
E(
LV
E(
LV
E(
LV
E(
LV
E(
LV
AD
TX
ACCU-4
1N,32A
WWP
1N,10A
DOAS-1
CONTROL
PANEL
FR MW
SEALED CONDUIT RACEWAY
THROUGH SECURE WALL FOR
CABLE ACCESS BETWEEN
SEGREGATED AREAS
MS
SB
-P
MS
SB
-P
MS
SB
-P
MS
SB
-P
MD
B-
P8
MD
B-
P9
MD
B-
P1
MS
SB
-P
MS
B-
FI
P
DB
-T
EF
-P
DB
-T
EF
-P
DB
-T
EF
-P
MS
B-
SE
C
MS
SB
-P
MS
SB
-P
MD
B-
P1
MD
B-
P2
MD
B-
P3
MD
B-
P4
MD
B-
P5
MD
B-
P6
MD
B-
P1
MD
B-
P1
MD
B-
P1
MD
B-
P1
MD
B-
P1
MD
B-
P1
MD
B-
P1
MS
SB
-P
MS
SB
-P
MS
SB
-P
MS
SB
-P
MS
SB
-P
MS
SB
-P
DB
-T
EF
-P
MD
B-
P7
MS
SB
-P
MD
B-
P1
DB
-T
EF
-P
CO
DB
-T
EF
-P
DB
-T
EF
-P
DB
-T
EF
-P
1N,32A
MD
B-
P1
(NOTE 17)
DDS
PANEL
PROVIDE 25mm CONDUIT IN WALL FOR FUTURE
INCOMING CARD READER. CAP OFF CONDUIT.
PROVIDE 20mm CONDUIT AND JUNCTION
BOX TO DOOR FRAME FOR FUTURE
ELECTRIC STRIKE. CAP OFF CONDUIT.
(NOTE 17)
COMMUNICATIONS RACKS
50mm CONDUIT FOR SATCOM
POWER
(NOTE 18)
(NOTE 17)
(NOTE 16)
(NOTE 17)
PROVIDE 2x25mm CONDUIT AND JUNCTION
BOXES TO DOOR FRAME FOR FUTURE
ELECTRIC STRIKE AND ELECTRIC LOCK. CAP
OFF CONDUIT.
PROVIDE 25mm CONDUIT TO DOOR FRAME
FOR MICROSWITCH MONITORING
SECONDARY DEADBOLT. CAP OFF CONDUIT.
PROVIDE 25mm CONDUIT AND JUNCTION BOX TO DOOR
FRAME(INACTIVE LEAF HINGE SIDE) FOR FUTURE
DOOR ELECTRIC STRIKE. CAP OFF CONDUIT.
(NOTE 17)
PROVIDE 25mm CONDUIT IN WALL FOR FUTURE
INCOMING CARD READER, ELECTRIC LOCK AND
DOOR REED SWITCH. CAP OFF CONDUIT
PROVIDE 2x25mm CONDUIT TO DOOR
FRAME FOR FUTURE ELECTRIC STRIKE
AND ELECTRIC LOCK. CAP OFF
CONDUIT.
PROVIDE 25mm CONDUIT TO DOOR
FRAME FOR MICROSWITCH
MONITORING SECONDARY DEADBOLT.
CAP OFF CONDUIT.
PROVIDE 25mm CONDUIT IN WALL FOR FUTURE
INCOMING CARD READER, ELECTRIC LOCK AND
DOOR REED SWITCH. CAP OFF CONDUIT
ACCU-1/AHU-1
CONTROL PANEL
SEE E-101 FOR
CONTINUATION
COMM COMM COMM COMM COMM COMM COMM COMM COMM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
CO
MM
2x100mm
COMMUNICATION CONDUITS FROM
SATCOM
E(
LV
E(
LV
E(
LV
E(
LV
E(
LV
E(
LV
E(
LV
E(
LV
6RU CABINET FOR DESN
AND FIDCIE SERVICES.
COMMUNICATIONS PIT
SPECS PER E-001 LEGEND
ZONE 2 FIT FOR BUT NOT
WITH ZONE 4 PROVISIONS
ZONE 2
CO
CO
CO
CO
CO
FINAL SUBMITTAL MAY 20, 2021
E16929 6/30/23
No.
Exp.
RE
GI
S T
ER
ED PRO F E S S I ON A L E NG I NEER
ST A T E O F C A L I F O R N I A
E R I C M . P E NN
E L E C T R I C A L
N
SCALE 1:50 AT ORIGINAL SIZE
500 2000 2500mm15001000
POWER AND SECURITY LAYOUT
SCALE 1:50
NOTES:
1. DRAWING TO BE READ IN CONJUNCTION WITH ARCHITECTURAL AND OTHER SERVICES
DRAWINGS.
2. FINAL LOCATIONS OF ELECTRICAL EQUIPMENT, POWER SUPPLIES AND ISOLATORS SHALL
BE DETERMINED ON SITE BY ELECTRICAL CONTRACTOR IN CO-ORDINATION WITH THE
RESPECTIVE TRADE TO SUIT EQUIPMENT AND INSTALLATION CONDITIONS.
3. THE CONTRACTOR SHALL LIAISE WITH THE MECHANICAL, HYDRAULIC, FIRE
CONTRACTORS AND THE ARCHITECT TO CONFIRM FINAL LOCATION OF
4. ALL CABLING SYSTEMS SHALL BE INSTALLED ON TENSION WIRE/TRAY, IN FALSE CEILINGS, IN SUITABLE DUCT UNDER BENCHES.
5. ALL POWER OUTLETS SHALL BE LABELED TO INDICATE TO WHICH DISTRIBUTION BOARD
AND CIRCUIT IT IS CONNECTED.
6. POWER CABLE TRAY SHALL BE 600mm.
7. FLOOR BOX TO BE SUPPLIED VIA 25mm² CONDUIT FROM WALL.
8. CONTRACTOR SHALL PROVIDE BOXES WITH 25mm² CONDUIT TO TOP OF WALL WHERE
NOTED FOR FUTURE CARD READERS NEXT TO EACH DOOR AT VESTIBULE FOR ADF LEVEL
4 SECURITY.
9. REFER TO MECHANICAL SPECIFICATION FOR FAN COIL UNITS & POWER CONNECTIONS.
10. SUPPLY POWER TO VAV BOXES. CABLE SHALL BE NO LESS THEN 4mm² PVC.
11. GPOS IN TOILETS ROOMS TO BE INSTALLED AT COUNTER HEIGHT.
12. PRIMARY BUS BAR TO BE INSTALLED WITHIN DB-TEF. ALL TELECOMMUNICATIONS DEVICES
TO BE CONNECT TO THE THE BONDING BUS BAR.
13. OUTLET SHALL BE ABOVE DOOR FOR POTENTIAL ESS.
14. ALLOW FOR CONDUIT, CABLE AND CONNECTION OF LIGHTNING PROTECTION MASS EARTH
INTO MSB MEN SYSTEM.
15. CONTRACTOR SHALL PROVIDE 25mm CONDUITS IN THE CEILING FOR FUTURE ALARMS AT
EACH DOOR IN VESTIBULES. DOORS ENTERING THE ELECTRICAL, MECHANICAL AND TEF
ROOMS. THE DOOR LEAVING THE SECURE ZONE OUTSIDE. EACH CONDUIT SHALL HAVE A
DRAW WIRE. COORDINATE WITH ARCHITECTURE ELEVATIONS FOR LOCATIONS OF
CONDUITS AND JUNCTION BOXES FOR FUTURE SECURITY EQUIPMENT .
16. PRESTIGE TYPE GPO SWITCHES TO BE USED FOR THE PWD TOLIET, INSTALLED AT 800
AFFL.
17. SUPPLY POWER TO MECHANICAL CONTROL PANELS FROM MECHANICAL SERVICES
SWITCH BOARD
E-102
RE
SP
ON
SE
T O
NA
VF
AC
C
OM
M
EN
TS
.0 6.
C.
S
DIAL OUT TO DPN BASE
NETWORK
SECURITY
PANEL
ACCESS PANEL
SECURITY SYSTEM - BLOCK DIAGRAM
NOT TO SCALE
DOOR SWITCHES
USAF
RACK 1
SECURE
USAF
RACK 2
UNSECURE
AUS
RACK 3
UNSECURE
TYPICAL
DATA
OUTLETS
SECURED AREA
UNSECURED AREA
DPN
CONNECTION TO
BASE NETWORK
(NOTE 3)
TO SATELLITE
PAD
TO SATELLITE
PAD
TELECOMMUNICATIONS - BLOCK DIAGRAM
NOT TO SCALE
TYPICAL VAV POWER CIRCUIT
NO SCALE
CB 'A'
16A
CB 'A' VAV BOX
LOCAL VAV SWITCH
(INSTALLED NEAR VAV BOX)
TYPICAL FOR ALL DISTRIBUTION BOARDS
EMERGENCY LIGHTING ACTIVATION & TEST CIRCUIT
NOT TO SCALE
CB 'A'
16A
CONTACTOR
TIMER
C
T
TEST PUSH
BUTTON
CB 'A'
EMERGENCY
SUPPLY
CB 'A'
SWITCHED
SUPPLY NORMAL
LIGHTING
EMERGENCY LIGHTING TEST SWITCH
(INSTALLED IN DB)
ELCR
DESN/BMS
CONNECTION TO
BASE NETWORK
(NOTE 4) SPARE
NOMINATED SINGLE 48 STRAND
CABLE. ALLOCATE 12 CORES FOR
DESN/BMS SERVICE AND 36
CORES FOR DPN SERVICE
FIRE SAFETY
CONNECTION TO
FUEL FARM #7
(NOTE 5)
FINAL SUBMITTAL MAY 20, 2021
E16929 6/30/23
No.
Exp.
RE
GI
S T
ER
ED PRO F E S S I ON A L E NG I NEER
ST A T E O F C A L I F O R N I A
E R I C M . P E NN
E L E C T R I C A L
NOTES
1. CONTRACTOR TO PROVIDE AND INSTALL 42 RU COMMUNICATIONS RACK.
CLIENT SHALL PROVIDE RACK EQUIPMENT. CONTRACTOR SHALL CONNECT
SPECIFIED OUTLETS TO RACK UPS SUPPLIED BY CLIENT.
2. COORDINATE FDCIE INSTALLATION WITH FIRE PROTECTION AND MECHANICAL
DESIGN AND SPECIFICATIONS.
3. COORDINATE BASE DPN CONNECTION WITH TELSTRA. FIBRE TO TERMINATE
AT DAR-064. REFER TO DRAWING E100 FOR CABLE ROUTE.
4. COORDINATE DESN/BMS WITH BROAD SPECTRUM. FIBRE TO TERMINATE AT
BMS CONTROLLER AT DAR-064. REFER TO DRAWING E100 FOR CABLE ROUTE.
5. CONNECT INTO FUEL FARM #7 EXISTING FIP.
6. ALL DESN/BMS SERVICES CONNECTING IN INTO BASE NETWORK MUST DO SO
VIA BLACK FIBRE TIE AT BUILDING COMMUNICATIONS RACK.
7. OUTLETS SHALL BE APPROPRIATELY LABELLED TO DENOTE WHICH RACK
THEY ARE SUPPLIED BY.
8. COORDINATE POWER SUPPLY TO VAV BOXES AND HVAC EQUIPMENT WITH
MECHANICAL EQUIPMENT CONTRACTOR.
9. CABLES FROM EACH RACK TO BE PHYSICALLY SEPARATED BY DIFFERENT
CABLE TRAYS DESCRIBED IN E-103.
10. DOUBLE DATA OUTLETS INDICATIVELY SHOWN SHARING / SPLITTING TWO
COMMUNICATION SERVICES. EACH DOUBLE DATA OUTLET SHOULD PROVIDE
TWO DESCRIBED SERVICES. USAF SECURE AND UNSECURE WITHIN THE
SECURED AREA. AND USAF UNSECURED AND AUS UNSECURE WITHIN THE
UNSECURED AREA. OUTLETS SHOULD APPROPRIATELY LABEL SERVICES.
11. CONTRACTOR TO FURNISH RACKS AS SHOWN ON PLANS, READY FOR
CUSTOMER DATA EQUIPMENT TO BE INSTALLED. THIS WILL INCLUDE
CABINETS, MOUNTING EQUIPMENT, POWER BOARDS, PDUS, AND POWER
POINTS ABOVE RACKS. CONTRACTOR MUST ALSO FURNISH ALL EQUIPMENT
REQUIRED FOR INTERNAL COMMUNICATIONS CABLING AND EXTERNAL
PASSIVE NETWORK TO BE CONNECTED COMPLETE, READY FOR USER
EQUIPMENT CONNECTION. THIS WILL INCLUDE FOBOTS, PATCH PANELS,
TERMINATIONS, CABLES AND DATA OUTLETS.
E-603
RE
SP
ON
SE
T O
NA
VF
AC
C
OM
M
EN
TS
.0 6.
C.
S
| 21R1343-AMD4_Dwgs.pdf |
| C-104 STORMWATER AND UTILITIES LAYOUT PLAN |
| G-102 HAUL ROUTE, LAYDOWN AND STOCKPILE AREAS |
| P700_AMD-ELEC DWGS_Signed_Final.pdf |
| E-001 - LEGENDS & NOTES |
| E-102 - POWER AND SECURITY LAYOUT |
| E-603 - DIAGRAM & SCHEMATICS |
File details come from the government source that posted it. Updated .