RFC5_Response.doc
DOC document 35 KB Posted
- Solicitation number
- N4523A18R1065
About this file
Request for Clarification #5 Response
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFC6_Response.doc | DOC document | |
| RFC4_Response.doc | DOC document | |
| RFC1_Pictures.zipx | ZIPX file | |
| RFC3_Response.doc | DOC document | |
| RFC1_Response.doc | DOC document | |
| RFC2_Pictures.zipx | ZIPX file | |
| RFC2_Response.doc | DOC document | |
| RFC3_Picture.zipx | ZIPX file | |
| Exhibit_A_-_CDRLs_and_DIDs_Combined_Edgecumbe_Barge.pdf | ||
| Attachment_J-1_Statement_of_Work_Edgecumbe_Barge_dated_1MAY2018.docx | DOCX document | |
| N4523A18R1065_SolicitationDrawings.zip | ZIP file | |
| Attachment_J-3_Request_for_Clarification_Form_Edgecumbe_Barge.doc | DOC document | |
| Attachment_J-4_Contract_Performance_Data_Sheet_Edgecumbe_Barge.docx | DOCX document | |
| Attachment_J-5_Corporate_Experience_Data_Sheet_Edgecumbe_Barge.docx | DOCX document | |
| N4523A18R1065_Edgecumbe_Barge.pdf | ||
| Edgecumbe_Barge_Draft_SOW.pdf |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR CLARIFICATION
N4523A18R1065 Attachment J-3
| DATE OF REQUEST: 7-16-18 |
| QUESTION NO: 005 |
REQUIREMENT: Edgecumbe Barge
REQUISITION NO.: N4523A18R1065
ITEM NO: 3.3.1 (3.3.1.1)
TITLE: Open, Pump, Clean, Ventilate and Gas Free
PSNS&IMF CONTRACTS POC & PHONE:
See POCs listed on RFP.
| PARA. NO: 3.3.1.1 and 3.3.1.2 |
| PAGE NO: ___28___ |
| CONTRACTOR: |
| PLANNER’S NAME: |
| ATTACH. NO: |
| CONTRACTOR POC & PHONE: |
CONTRACTOR QUESTION: (ONE QUESTION PER PAGE)
Specification does not designate what is stored in tanks of the barge. Drawings provided do not provide the use of the tanks. Specification 3.3.1.1 designated Contractor to meter residual liquids based on Table 1, noting that tanks/voids will be at low suction.
Contractor requests clarification on what is stored in the barges tanks.
DO NOT WRITE BELOW THIS LINE
| SPEC CHG: N |
| DWG/REF CHG. N |
| RQMTS CHG: N |
| MAT'L CHG: N |
| TECHNICAL REVIEW: Langham |
| SERIAL NO: 005 |
Tanks normally maintained dry however there may be some residual ballast water (fresh water).
ALL RFCs MUST BE RECEIVED NO LATER THAN 2:00 P.M. (PST), 25 July 2018.