7320479 Amendment 0003.pdf

PDF 371 KB Posted

Attached to
Overhaul Elevator, Building 4224 (FRCE)
Solicitation number
N442487320479
Issued by

About this file

This document is Amendment 0003 to a solicitation for overhaul of an elevator in Building 4224 at Marine Corps Air Station (MCAS) Cherry Point, North Carolina, issued by CG MCAS Cherry Point Facilities, ROICC on July 23, 2026. The amendment provides responses to pre-award inquiries (PPI) submitted by prospective contractors and confirms that the proposal due date remains July 29, 2026. Contractors must acknowledge receipt of this amendment with their proposals.

The Pre-Award Inquiry Form documents 19 questions and government responses addressing project specifications and requirements. Key technical clarifications include: confirmation that the building's Fire Alarm Panel is a Johnson Controls JCPU2-640 with sufficient capacity for new addressable devices; confirmation that the existing hoist beam is reinforced CMU capable of supporting the new 6,000 lb rated load elevator without additional reinforcement; identification of electrical panel locations (RP2 and PP2) on sheet E101; clarification that condensate from air handlers cannot be connected to industrial waste without Environmental Affairs Division (EAD) approval; confirmation that one qualified person may serve as Superintendent, QC, and SSHO; and guidance that contractors should submit proposals per drawings and specifications for other technical matters. The government declined to provide site photographs, security escorts for secure areas, or additional working hour restrictions, and indicated that laydown area and on-site parking will be very limited with locations to be determined. Indoor air quality requirements are referenced in Section 01 35 26 of the specifications.

View the file

Other files

File Type Posted
7320479 Amendment 0002.pdf PDF
7320479 RFP.pdf PDF
JandA ML 25 03 Class FRCS Cherry Point Redacted.pdf PDF
7320479 Amendment 0001.pdf PDF
FRCE Access Letter Format Example.docx DOCX document
7320479 SpecsAsOne SIGNED.pdf PDF
7320479 Master PPI Form.xlsx XLSX spreadsheet
7320479 DrawingsAsOne SIGNED.pdf PDF
7320479 RFP.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE PAGE OF PAGES 1 5

2. AMENDMENT/MODIFICATION NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicable)

0003 07/23/2026 7320479

6. ISSUED BY Code N40085 7. ADMINISTERED BY (If other than item 6.) Code

CG MCAS Cherry Point

FACILITIES, ROICC

B-87, 748 Roosevelt Blvd.

PSC BOX 8006

CHERRY POINT, NC 28533

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code) 9A. AMENDMENT OF SOLICITATION Overhaul Elevator, Building 4224 FRCE

9B. DATED (SEE ITEM 11)

AMENDMENT MUST BE ACKNOWLEDGED WITH YOUR PROPOSAL 10A. MODIFICATION OF CONTRACT/ORDER NO.

10B. DATED (SEE ITEM 13)

CODE FACILITY CODE

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in item 14. The hour and date specified for receipt of Offers is extended is not extended. Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods: (a) By completing items 8 and 15, and returning 1 copy of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (if required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14. ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATION CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103 (b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER: (specify type of modification and authority)

E. IMPORTANT: Contractor is not is required to sign this document and return original to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

7320479, Overhaul Elevator, Building 4224 FRCE, Marine Corps Air Station Cherry Point, NC

This Amendment is being issued provide PPI responses

The proposal due date remains 29 July 2026.

See Attached.

15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

15B. CONTRACTOR/OFFEROR (Same as Item 8) 15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 16C. DATE SIGNED

BY

(Signature of person authorized to sign) (Signature of Contracting Officer)

NSN 7540-01-152-8070 30-105 STANDARD FORM 30 (REV.1-83) 0224-3(10-90)

PREVIOUS EDITION UNUSABLE Prescribed by GSA

PREAWARD INQUIRY FORM

PAGE SECTI

ON PARAGRAPH

1 6/17/2026 IAW MCAS CP FRCS Standardization for JCI Metasys branded products, please include "J&A ML-25-03 Class FRCS Cherry Point" within the next amendment. (attached)

CJ&A provided to contracting. 0001

2 6/25/2026 M-101 A1 Drawing M-101 detail A1 shows DHP-1 to be mounted above the 2nd floor attached to the wall of the elevator shaft. Is the wall location shown okay to mount this unit?

Existing electrical disconnects in Equipment room are being demolished.

3 6/25/2026 During the site visit it was noticed that there are some electrical disconnects mounted in the location of where DAC- 1 unit is to be located. Will there be sufficient room to mount this unit above the disconnects, and is it approved to do so since this unit may create condensate?

DOR takes no exception to routing condensate to sump pump discharge piping.

4 6/25/2026 M-101 Keynote 6 Drawing M-101 keynote 6 states to provide new condensate pump for air handler condensate. Route condensate lines to exterior of building in most direct path & terminate on grade.

During the site visit it was noticed that there was no exterior wall close to this location. Would it be acceptable to connect this condensate drain to the sump pump discharge piping that is being installed for the elevator sump pump which then routes to drain into an existing trench drain? This is the way the condensate was set up for the Replace Elevator, DLA Distribution, B159 project (the condensate drain teed into the sump pump discharge & was routed to a mop sink located on the 2nd floor of building B159).

We do not believe that condensate can be connected to industrial waste. EAD would have to approve. Submit proposals in accordance with Drawings, Specifications and Amendments.

5 6/26/2026 9 14 24 12.4 Can you please confirm that the elevator is to be installed under the post-1970's code that would require a double wall cylinder?

Submit proposals in accordance with Drawings, Specifications and Amendments.

POSTED ON

AMENDMENT

PPI #

REFERENCE

QUESTION GOVERNMENT RESPONSE

DATE

SUBMITTE

D

July 2011 # DISTRIBUTION: DoW COMMUNITY ONLY

ON PARAGRAPH

AMENDMENT

PPI # QUESTION GOVERNMENT RESPONSE

SUBMITTE

D

6 6/26/2026 P-101 Note 5 The area of Building 4224 where the sump pump discharge work indicated on Drawing P-101, Note 5 is to be installed is in a secure area that could not be accessed during the scheduled Project Site Visit. Will the Government be providing security escorts while work in this area is being performed?

No. Bid per plans and specs.

7 06/22/2026 AD101 Drawi ngs

Keynote Note

Sheet AD101 notes 'Coordinate Red Aisle Encroachment with FRCE.' Please clarify: (1) the extent of permissible encroachment into the red aisle

Dimensions are provided on the Drawings. Submit proposals in accordance with Drawings, 8 06/22/2026 AD301 Drawi ngs

Demo KN

Demo keynote 5 on Sheet AD301 designates the existing hoist beam to remain. Please confirm the existing hoist beam has been structurally evaluated for compatibility with the new 6,000 lb rated load elevator system specified in Section 14 24 13 Para. 2.1.1, and confirm whether any reinforcement or replacement is required.

Reinforcement or replacement are not anticipated. Submit proposals in accordance with Drawings, Specifications and Amendments.

9 06/22/2026 FP101/

FP102

Drawi ngs

Keynotes 3-4

Sheet FP101 identifies an existing Johnson Controls fire alarm control panel (FACP). The new work per FP102 requires control modules, a monitor module, and elevator recall integration per FP501. Please provide the existing FACP model number and confirm sufficient addressable points and module slots are available to support the new devices without requiring panel replacement or expansion.

Bldg. 4224’s Fire Alarm Panel is a Johnson Controls JCPU2-640. There is sufficient capacity for addition of Addressable Devices (Modules and Detectors)

10 06/22/2026 P-101 Drawi ngs / Sec 22 00

KN 5 / 1.3 Sheet P-101 keynote 5 identifies the existing 3" trench drain as piped to the industrial waste system and directs the oil-detecting sump pump (SP-1) to discharge 6" above that drain.

Please confirm that discharge from an oil-detecting sump pump to the industrial waste system is authorized by the installation's environmental and public works authority, and advise whether a permit, pretreatment determination, or oil-water separator upstream of the trench drain is required prior to commencing work.

This configuration is as directed by EAD during design. Submit proposals in accordance with Drawings, Specifications and Amendments.

ON PARAGRAPH

AMENDMENT

11 06/22/2026 P-501 Drawi ngs / Sec 01 57

SP-1 /

Para 3.12

The specified sump pump is an oil-detecting type (SP-1, Sheet P-501), indicating recognition of hydraulic oil history in the elevator pit. Please confirm whether the Government has existing environmental data on hydraulic oil accumulation in the pit, and whether any pre-construction pit cleaning or environmental assessment is required prior to sump pump installation, or whether the contractor proceeds under the inadvertent discovery protocol of Specification Section 01 57 19 Para. 3.12 if oil is encountered during construction.

No existing environmental data on hydraulic oil accumulation in the pit.

Bid per plans and specs.

12 06/22/2026 M-101 / M-

Drawi ngs / Sec

KN 2,4 /

Sched

Sheet M-101 shows ductless condensing unit DHP-1 (100 lbs per M-601 schedule) mounted high on the hangar wall with a wall-suspended platform and drain pan. Please provide: (1) the existing hangar wall construction type and thickness at the proposed DHP-1 mounting location; (2) confirmation that the wall can support the platform and unit weight without additional structural reinforcement; and (3) identification of who is responsible for the wall penetration, flashing, and weather seal for the refrigerant line routing.

(1) Existig wall is reinforced CMU; (2) No additional reinforcing is anticipated; (2) The KTR is responsible for a complete installation.

13 06/22/2026 ED101 Drawi ngs / Sec

KN 4 & 5 Sheet ED101 keynotes 4 and 5 require removal of existing disconnects with conductors and conduit back to source panels RP2 and PP2, respectively. These panels are not identified on the partial electrical riser diagram (Sheet E-602) or elsewhere in the drawing set. Please provide the locations of panels RP2 and PP2 within Building 4224 so demolition conduit and conductor removal runs can be properly scoped and priced.

Panel locations are shown on sheet E- 101.

ON PARAGRAPH

AMENDMENT

14 06/22/2026 AD101 Drawi ngs / Sec 01 14

General / Para 1.3.2

Section 01 14 00 Para. 1.3.2 establishes regular working hours as 7:00 a.m. to 3:30 p.m., Monday through Friday. The building remains occupied and operational throughout construction per Para. 1.2.b. Please confirm whether FRCE flight operations or production schedules impose additional restrictions on noise-generating activities (demolition, concrete saw cutting, jackhammering) beyond the standard working hours, and whether a formal FRCE phasing or noise coordination plan submittal is required prior to commencing such work.

Bid per plans and specs

15 6/22/2026 Please confirm if one qualified person can act as Superintendent, QC, and SSHO?

Yes as described in Section 01 45

00.00 20 Paragraph 1.5.1.1 and 01 30 00 paragraph 1.5.1

16 6/25/2026 No photos were allowed to be captured at the site visit. Can you provide photos of the equipment room, elevator pit, area above the second floor in the elevator shaft, and the surrounding area of the elevator enterance?

No. Bid per plans and specs

17 6/25/2026 Will a laydown area be available to the contractor at this site?

Additionally, will on-site parking be provided for contractors?

Very limited/temporary laydown area may be approved on a case by case basis. On-site parking will be limited, location TBD.

18 6/25/2026 Will the contractor be required to provide negative air filtration in this work area?

Reference Section 01 35 26 for Indoor Air Quality (IAQ) requirements.

19 6/25/2026 Will there be any interference with existing operations that will limit the contractor's access to the space?

No. Bid per plans and specs