This document is an amendment to a solicitation for the construction of a library at Marine Corps Air Station Cherry Point, North Carolina. Amendment 0002 addresses responses to pre-award requests for information (RFIs) and revises certain drawings.
The key details are:
- The deadline to submit pre-award RFIs has passed, and no further RFIs will be answered.
- The proposal due date of June 18, 2024 at 3:00 PM local time remains unchanged.
- Revised drawings 12907822 and 12907829 dated June 11, 2024 are provided to address questions on the precast concrete scope, water table panels, and the courtyard area.
- Section 10 23 39 Folding Panel Partitions is deleted.
- Information is provided on window shades, railing finishes, door fire ratings, and impact-resistant exterior doors.
- The contract opportunity is restricted to the General MACC contractors listed in the RFP.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 0004.pdf | ||
| AMENDMEND 0003.pdf | ||
| Amendment 0001 7394134.pdf | ||
| RFP - 7394134.pdf | ||
| 7394134 SpecAsOne - Vol 2 Appendix A.pdf | ||
| 7394134 DrawingsAsOne SIGNED.pdf | ||
| 7394134 SpecAsOne - Vol 1 SIGNED.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NAVFAC
SPECIFICATION
7394134 P253 Library
MCAS Cherry Point, NC AMENDMENT
#0002
IMPORTANT
This amendment should be acknowledged when your proposal is submitted. Failure to acknowledge the amendment may constitute grounds for rejection of the proposal.
If your proposal has been submitted prior to the receipt of this amendment, acknowledgement should be made by telegram, which should state whether the price contained in your proposal is to remain unchanged, is to be decreased by an amount, or is to be increased by an amount. The acknowledgement must be received prior to proposal opening time.
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE PAGE OF PAGES
1 2
2. AMENDMENT/MODIFICATION NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicable)
0002 6/11/2024 7394134
6. ISSUED BY Code N40085 7. ADMINISTERED BY (If other than item 6.) Code
CG MCAS Cherry Point
FACILITIES, ROICC
B-163, CURTIS ROAD
PSC BOX 8006
CHERRY POINT, NC 28533
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code) 9A. AMENDMENT OF
P253 Library
9B. DATED (SEE ITEM 11)
AMENDMENT MUST BE ACKNOWLEDGED WITH YOUR PROPOSAL 10A. MODIFICATION OF CONTRACT/ORDER NO.
10B. DATED (SEE ITEM 13)
CODE FACILITY CODE
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in item 14. The hour and date specified for receipt of Offers is extended is not extended. Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods: (a) By completing items 8 and 15, and returning 1 copy of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (if required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14. ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATION CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103 (b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER: (specify type of modification and authority)
E. IMPORTANT: Contractor is not is required to sign this document and return original to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
7394134 P253 Library, Marine Corps Air Station Cherry Point, NC
Amendment 0002 is being issued to respond to pre-award RFI.
The deadline to submit pre-award RFI’s HAS PASSED. No further RFI will be answered.
The proposal due date of 18 June 2024 at 3:00 PM local time REMAINS unchanged.
See Attached.
15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
15B. CONTRACTOR/OFFEROR (Same as Item 8) 15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 16C. DATE SIGNED
BY
(Signature of person authorized to sign) (Signature of Contracting Officer)
NSN 7540-01-152-8070 30-105 STANDARD FORM 30 (REV.1-83) 0224-3(10-90)
PREVIOUS EDITION UNUSABLE Prescribed by GSA
Amendment 0002 7394134 P253 Library
RFI Responses:
Specification Section 03 45 00 - Precast Architectural Concrete - Plans do not provide enough information to determine the scope of the required precast work:
1. See Detail A1/A-507, Detail A4/A-107 and Detail B4/A-502 - Please confirm the column bases consist of modular brick that bear on the porch slab with a 2" thick precast adhered to the brick (no detail of columns is provided on structural sheets therefore not able to determining if the masonry goes down to top of footing or not).
Response:
See revised Drawings 12907822 and 12907829, dated 11 June 2024
2. East Elevation A3/A-201 and West Elevation A2/A-202 indicate precast water table panels at gable entry areas. No cross section is shown for these panel areas. A cross section (or more information of some type) will be required. How thick are the panels? Will they have brick or block backup? Will the panels go down to the top of footing or be supported by a unit masonry stem, etc.?
See revised Drawings 12907822 and 12907829, dated 11 June 2024
3. Sheet A-101 Courtyard, located at plan northeast, is not addressed at all on structural plans. North Elevation C3/A-201 and West Elevation A2/A-202 seem to imply that precast panels may be required at this location, but more details will be required in order to determine the scope.
Response:
See Drawings 12907825 and 12907826. Submit proposals in accordance with RFP, Specifications, Drawings, and all amendments.
4. Please share sign in sheet from the site visit.
See attached Site Visit Log
5. Is this project US Citizen only?
No. Submit proposals in accordance with RFP, Specifications, Drawings and all amendments.
6. 10 23 39 On the P253 Library job there are specs for Folding Panel Partitions (102239), however, I do not see one on the plans. Can you confirm whether a folding partition is required?
Response:
Section 10 23 39 is deleted. Submit proposals in accordance with RFP, Specifications, Drawings, and all amendments.
7. 12 00 00 I have window sizes and quantities. I don't know which windows get what.
I am guessing the exterior windows are getting the single shades and meeting rooms are getting the double shades. But I don't know the sizes of the windows in the meeting rooms or exterior either."
Response:
See Drawings 12907848 and 12907872. Submit proposals in accordance with RFP, Specifications, Drawings, and all amendments.
8. 05 00 00 The are no indicators or specs as to what type of finish if any is applied to exterior or interior railings could this be clarified? Structural steel columns l-502 have no indicators or specs as how to finish please clarify?
Response:
Reference Amendment 0001. Submit proposals in accordance with RFP, Specifications, Drawings, and all amendments.
9. 08 00 00 Per the Bid Documents, Fire Rating is missing in the Door Schedule (Reference Sheet number A-601 dated 08/25/2020). Please provide updated information.
Response:
See Drawing 12907843. Submit proposals in accordance with RFP, Specifications, Drawings, and all amendments.
10. 08 00 00 Per the Bid Documents, Division 8 Specifications, (Reference Section 08 41 13, Aluminum Doors and Frames, Page 5) show Impact Resistant Doors. Please clarify Exterior Doors are considered as Impact Resistant or Not.
Response:
See Specification Section 08 41 13. Submit proposals in accordance with RFP, Specifications,
11. Per the Bid Documents, Fire Rating is missing in the Door Schedule (Reference Sheet number A-601 dated 08/25/2020).
Response:
See Drawing 12907843. Submit proposals in accordance with RFP, Specifications, Drawings, and all amendments.
12. Per the Bid Documents, Division 8 Specifications, (Reference Section 08 41 13, Aluminum Doors and Frames, Page 5) show Impact Resistant Doors.
Please clarify Exterior Doors are considered as Impact Resistant or Not.
Response:
See Specification Section 08 41 13. Submit proposals in accordance with RFP, Specifications, Subj: AMENDMENT TO WO 7394134, P253 CONSTRUCT LIBRARY, MCAS CHERRY POINT NC
CONTINUATION SHEET
SITE VISIT LOG
DOCUMENT 00 01 15
1.2 CONTRACT DRAWINGS
The following drawings are revised as of 11 JUNE 2024:
NAVFAC DWG NO. TITLE
12907822 FLOOR PLAN – ENLARGED AREAS F & G, 11 JUNE 2024
12907629 TYPICAL WALL SECTIONS, 11 JUNE 2024
These drawings accompany this Amendment.
AREA F
AREA A
AREA E
AREA D
AREA G
AREA C
AREA B
AA
BB
C3
A-301
C3
A-301
VESTIBULE
BB
101A 101B
C
2'-0" 8'-0" 2'-0" 8'-0" 2'-0" 8'-0" 2'-0"
8"
9' -4
2'
-0
2 1/2"
7"
2 1/2"
2'-11"
2 1/2"
2'-10 1/2"
2 1/2"
7"
2 1/2"
2 1/2"
7"
2 1/2"
2'-11"
2 1/2"
2'-10 1/2"
2 1/2"
7"
2 1/2"
2 1/2"
7"
2 1/2"
2'-11"
2 1/2"
2'-10 1/2"
2 1/2"
7"
2 1/2"
1/
2"1' -3
1/
2"
6' -0
1/
2"
1' -3
1/
2"A A
FFF
A-107 C4
CJ CJ CJ CJ CJ CJ
CJ CJ CJ
A-507 A1
A5
A-302
A5
A-302
SIM
C3
A-301
C3
A-301
SS
TT
B
B
2'-0" 8'-0" 2'-0" 8'-0" 2'-0" 8'-0" 2'-0"
8" 9'
-4
2' -0
A A A
EQ EQEQ EQ
A-107 A4
CJCJ CJ CJ CJ CJ CJ CJ
CJ CJ CJ
CJCJCJ
A-507 A1
A5
A-302
A5
A-302
SIM
1. REFERENCE SHEET G-002 FOR SYMBOL LEGEND
2. REFERENCE SHEET A-501 FOR WALL TYPES
3. REFERENCE SHEET A-601 FOR DOOR AND FRAME SCHEDULE
4. REFERENCE SHEET A-603 FOR WINDOW SCHEDULE
5. REFERENCE INTERIOR DESIGN DRAWINGS FOR FINISH
SCHEDULE
6. REFERENCE INTERIORS DRAWINGS FOR CASEWORK
DIMENSIONS AND DETAILS
7. REFERENCE THE LIFE SAFETY DRAWINGS FOR LOCATIONS OF
RATED WALLS AND SMOKE PARTITIONS
D4
A-502
D4
A-502
2'-10"
E Q
E Q
1'-0" 3'-0" 3'-0"
B4
A-502
B4
A-502
EQ EQ
2' -9
3/
2' -9
1'
-0
SATISFACTORY TO
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
STA. PROJ. NO.:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
D E S
IG
N A
N D
C O
N S T R U
C T
IO
N
D C
C O
R E
N A V A L S
T A T
IO
N
N O
R F O
L K V A
M A
R
IN
E C
O R
P S
A
IR
S T
A T
IO
N
C H
E R
R Y
P O
IN
T
N
C
F ile
P ri n t
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
M
A
P.
STCETIHCRA
FB
BERN N.C
.NEW
CERT. NO.
UTCETIHCRA
DERET
SI
G E R
NO
IT
AR
OP
RO
C
LAR
CAROLINANORTH
50679
T
T C
E
TI
HCRAD
R E
G I S
ERE
A N
I
L
ORA
N O
R
T H
C
N
D A
R
N
DE
.J UE
ER
III
C
N
NRB E
E W
AS INDICATED
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
A T
L A
N T
IC
S p ro je c ts
\2
\2
C
P C o n s tr u c t L ib ra ry
\2
D e s ig n \2
D w g s \2
A
R C
H -2
.r v t
/1
/2
:5
:2
A
M
F L O
O R
P L A
N
E N
L A
R G
E D
A R
E A
S F
G
A-107
XXXXXXX
P
C
O N
S T
R U
C T
L
IB
R A
R Y
FINAL SUBMITTAL
12907822
ESS ESS DJG
L. PEED
H. PERRY
7394134
20 MAY 2024
GRAPHIC SCALE: 1/4"=1'-0"
4' 0 2' 4' 8'
SCALE: 1" = 50'-0"
A5
KEY PLAN
SCALE: 1/4" = 1'-0"
C2
FIRST FLOOR PLAN - AREA F
N
SCALE: 1/4" = 1'-0"
A2
FLOOR PLAN - ENLARGED AREA G
N
GENERAL CONSTRUCTION NOTES
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
A m e n d m e n t
.0
.0
SCALE: 1/2" = 1'-0"
C4
ENLARGED RAILING DETAIL
SCALE: 1/2" = 1'-0"
A4
ENLARGED RAILING DETAIL
FIRST FLOOR
0"
GRADE
-1'-9"
Q
BRICK VENEER
VENEER WALL ANCHOR AT
1'-4" ON CENTER
AIR AND MOISTURE BARRIER
8" METAL STUD
5/8" GYPSUM SHEATHING
5/8" GYPSUM WALL BOARD
ACOUSTICAL TILE CEILING
WEEP JOINT
FLASHING
PRECAST CONCRETE
3" RIGID INSULATION
METAL WALL PANEL
THROUGH WALL FLASHING
CONCRETE FOOTER.
SEE STRUCTURAL
DRAWINGS
6X8X16 CONCRETE MASONRY
6" CONCRETE SLAB
AIR AND MOISTURE BARRIER
CONCRETE MASONRY UNIT
WITH GROUT FILL
5" RIGID INSULATION
STEEL ROOF DECK
MODIFIED BITUMEN ROOF
FLASHING
ZEE GIRT AT 4'-0" ON CENTER
COPING
PLYWOOD SHEATHING
BLOCKING
STAINLESS STEEL
CONNECTOR
2 1/2" WEEPS AT 2'-8" ON CENTER
2 1/2" WEEPS AT 2'-8" ON CENTER
14' CEILING
14'-0"
A-303 C2
A-303 C5
A-303 A1
5' -1
'-0
5' -8
'-9
A-303 C4
FIRST FLOOR
0"
GRADE
-1'-9"
LOWER ROOF
12'-0"
C
CONTINUOUS TREATED WOOD NAILERS
3/4" COX PLYWOOD
ROOFING SYSTEM BASE FLASHING
CONTINUOUS FIBERBOARD CANT
PEEL & STICK
UNDERLAYMENT
3/4" COX PLYWOOD
0.080" PREFINISHED
ALUMINUM COPING
MATCH EXISTING
CONTINUOUS CLEAT
FASTENED AT 8" ON
CENTER WITH NO.12
STAINLESS STEEL
SCREWS
RIGID INSULATION
THROUGH WALL FLASHING
WITH TERMINATION BAR
MASONRY VENEER
ANCHORS 1'-4" AT
2'-0" ON CENTER
8" METAL STUD
GYPSUM WALL BOARD
GYPSUM SHEATHING
MASONRY VENEER ANCHORS
AT 1' - 4" ON CENTER
CONCRETE SLAB
AIR AND MOISTURE BARRIER
CAPILLARY FILL
A-505 C1
6X8X16 CONCRETE
MASONRY UNIT
WEEPS AT 2'-0" ON CENTER
PRECAST CONCRETE
CONCRETE FOOTER. SEE
STRUCTURAL DRAWINGS
CONCRETE MASONRY
UNIT WITH GROUT FILL
THROUGH WALL
FLASHING
2 1/2" WEEP AT 2'-8"
ON CENTER
AIR AND MOISTURE BARRIER
'-8
5'
-1
'-9
FIRST FLOOR
0"
GRADE
-1'-9"
R
A-303 C1
AIR AND MOISTURE BARRIER
GYPSUM SHEATHING
8" METAL STUD
3" RIGID INSULATION
GYPSUM WALL BOARD
CONCRETE MASONRY UNIT SILL
WEEP AT 2'-0" ON CENTER
FACE BRICK
ARCHITECTURAL
CONCRETE MASONRY UNIT
THROUGH WALL FLASHING
WITH TERMINATION BAR
AIR AND MOISTURE BARRIER
CONCRETE SLAB
MASONRY VENEER ANCHOR
AT 1'-4" ON CENTER
THROUGH WALL FLASHING WITH
TERMINATION BAR
18'-0"
METAL PANEL TRIM
ZEE GIRT AT 4'-0" ON CENTER
METAL WALL PANEL
SLOPE
AIR AND MOISTURE BARRIER
STANDING SEAM METAL ROOF
GUTTER
STEEL DECK
CAPILLARY FILL
CONCRETE FOOTER.
SEE STRUCTURAL
DRAWINGS
5' -1
'-0
6' -9
'-1
0"
FIRST FLOOR
0"
ROOF
30'-0"
GRADE
-1'-9"
S
WEEP AT 2'-0"
ON CENTER
THROUGH WALL
FLASHING WITH
TERMINATION
BAR
MASONRY VENEER
ANCHOR AT 1'-4"
ON CENTER
ACCENT BRICK
HEADER COURSE
ACCENT BRICK
SOLDIER COURSE
FACE BRICK
FINISH GYPSUM
CEILING
PRECAST CONCRETE
PANEL
A-303 A4
SIM
GROUT FILL
AIR AND
MOISTURE
BARRIER
CONCRETE SLAB
AIR AND MOISTURE
BARRIER ONLY.
CONDITION ONLY
AT VESTIBULE 101
8"
PRECAST PANEL
ANCHOR AND
THROUGH WALL
FLASHING
SATISFACTORY TO
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
STA. PROJ. NO.:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
D E S
IG
N A
N D
C O
N S T R U
C T
IO
N
D C
C O
R E
N A V A L S
T A T
IO
N
N O
R F O
L K V A
M A
R
IN
E C
O R
P S
A
IR
S T
A T
IO
N
C H
E R
R Y
P O
IN
T
N
C
F ile
P ri n t
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
M
A
P.
STCETIHCRA
FB
BERN N.C
.NEW
CERT. NO.
UTCETIHCRA
DERET
SI
G E R
NO
IT
AR
OP
RO
C
LAR
CAROLINANORTH
50679
T
T C
E
TI
HCRAD
R E
G I S
ERE
A N
I
L
ORA
N O
R
T H
C
N
D A
R
N
DE
.J UE
ER
III
C
N
NRB E
E W
AS INDICATED
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
A T
L A
N T
IC
S p ro je c ts
\2
\2
C
P C o n s tr u c t L ib ra ry
\2
D e s ig n \2
D w g s \2
A
R C
H -2
.r v t
/1
/2
:5
:2
A
M
T Y
P
IC
A L
W A
L L
S E
C T
IO
N
S
A-302
XXXXXXX
P
C
O N
S T
R U
C T
L
IB
R A
R Y
FINAL SUBMITTAL
12907829
ESS ESS DJG
L. PEED
H. PERRY
7394134
20 MAY 2024
SCALE: 1/2" = 1'-0"
A1
TYPICAL WALL SECTION
GRAPHIC SCALE: 1/2"=1'-0"
2' 0 1' 2' 4'
SCALE: 1/2" = 1'-0"
A3
TYPICAL WALL SECTION
SCALE: 1/2" = 1'-0"
A4
TYPICAL WALL SECTION
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
A m e n d m e n t
.0
.0
SCALE: 1/2" = 1'-0"
A5
TYPICAL WALL SECTION
| AMEND 2 covers |
| Amend Cover |
| Amendment Page 2 |
| RFI 3 and 4 RESPONSES |
| CONTINUATION SHEET |
| SITE VISIT 7394134 |
| 12907822 |
| Sheets |
| A-107 - FLOOR PLAN - ENLARGED AREAS F & G |
| A-302 - TYPICAL WALL SECTIONS |
| 12907829 |
| Sheets |
| A-107 - FLOOR PLAN - ENLARGED AREAS F & G |
| A-302 - TYPICAL WALL SECTIONS |
File details come from the government source that posted it. Updated .