Drawings dtd 8.25.26.pdf

PDF 19 MB Posted

Attached to
FY26 Multiple Location BEQ Chiller Loop Flushing and Chemical Cleaning
Solicitation number
N4008526R9049
Issued by

About this file

Summary of Construction Drawing Documentation for Wallace Creek Regimental Complex, Phase II BEQ C3

These are mechanical construction drawings and schedules for the heating, ventilation, air conditioning (HVAC), and piping systems for the Wallace Creek Regimental Complex, Phase II Building Equipped Quarters (BEQ) C3 at Naval Station Norfolk, MCB Camp Lejeune, Jacksonville, NC. The drawings, dated December 20, 2012, were prepared by Clark Nexsen Architecture & Engineering (License #C-1028) and include detailed floor plans, equipment schedules, and technical specifications for a multi-story residential building. The project contract number is N40085-10-C-5312.

The scope encompasses complete HVAC and hot water systems including air handling units (C3-AHU-1 with 17,300 CFM capacity), ductless split system air conditioning units (C3-AC-1 through C3-AC-4), variable air volume (VAV) and constant air volume (CAV) terminal units for individual spaces, unit heaters, hot water circulation pumping, boiler systems (two 860 MBH gas-fired units), an 81.3-ton air-cooled chiller with heat recovery, exhaust fans, supply fans, relief hoods for elevator smoke relief, and associated piping for chilled water supply/return (CWS/CWR), hot water supply/return (HWS/HWR), refrigerant lines (RS/RL), and condensate drainage. The drawings specify SMACNA duct construction standards, fire and smoke dampers compliant with NFPA-90A, vibration isolation for suspended equipment per anti-terrorism/force protection (ATFP) requirements, and coordination with electrical and plumbing trades. All materials and equipment shall bear seals from ARI, ASME, UL, and ASTM, with installation conforming to ASHRAE and applicable municipal, state, and federal codes and regulations.

View the file

Other files

File Type Posted
Amend 0009.pdf PDF
Amend 0008.pdf PDF
Drawings dtd 8.27.26.pdf PDF
Amend 0007.pdf PDF
Amend 0006.pdf PDF
Amend 0005 Drawings.pdf PDF
Amend 0005.pdf PDF
Amend 0004.pdf PDF
Amend 0003.pdf PDF
Amend 0002.pdf PDF
Amend 0001.pdf PDF
RFP 260431.pdf PDF
26M086CN Multiple BEQ HVAC Chiller Loop Flushing PD.pdf PDF
Contractor Environmental Guide Updated Format_20231009 with ESOP.pdf PDF
26M086CN Multiple BEQ HVAC Chiller Loop Flushing SOW.pdf PDF
Combined DIV 01 DBB specs.pdf PDF
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

# CONSTRUCTION NOTE IDENTIFICATION

INDICATES ITEM TO BE PROVIDED

FLEXIBLE DUCT CONNECTION

VERTICAL FIRE DAMPER

VOLUME DAMPER

CEILING RETURN, EXHAUST OR TRANSFER REGISTER

CEILING SUPPLY DIFFUSER

MITERED ELBOW WITH TURNING VANES

RETURN DUCT TURNING UP

RETURN DUCT TURNING DOWN

EXHAUST DUCT TURNING UP

EXHAUST DUCT TURNING DOWN

SUPPLY DUCT TURNING UP (ROUND OR RECTANGULAR)

SUPPLY DUCT TURNING DOWN (ROUND OR RECTANGULAR)

10"x10" SQUARE OR RECTANGULAR DUCTWORK

PIPE TURNING UP

PIPE TURNING DOWN

T THERMOSTAT (C=COOLING, H=HEATING,

H,T=HEATING AND COOLING

DSD DUCT SMOKE DETECTOR

F10/6

(CFM)

EXHAUST GRILLE DESIGNATION

WITH CFM INDICATED

A6

(CFM)

CEILING DIFFUSER DESIGNATION

WITH CFM INDICATED

G20/20 RETURN GRILLE DESIGNATION

GENERAL

DUCTWORK

MOTORIZED CONTROL DAMPER

INDICATES ROUND DUCTWORK

RETURN, EXHAUST OR TRANSFER AIR FLOW

SUPPLY AIR FLOW

ACCESS DOORAD

ABOVE FINISHED FLOORAFF

ABOVE FINISHED GRADEAFG

ALUMINUMALUM

ARCHITECTURALARCH

DIAMETERDIA

DRAWINGDWG

GAUGEGA

MISCELLANEOUSMISC

NOT IN CONTRACTNIC

TYPICALTYP

UNLESS OTHERWISE NOTEDUON

GALVANIZEDGALV

RUN THRU JOISTSRTJ

AUTOMATIC AIR VENT

VALVES AND ACCESSORIES

AUTOMATIC FLOW CONTROL VALVE

BACKFLOW PREVENTER

BALL VALVE

BOTTOM CONNECTION

BUTTERFLY VALVE

CAPPED PIPE

CHECK VALVE

CLEAN OUT

CONCENTRIC REDUCER

ECCENTRIC REDUCER

FLANGED CONNECTION

FLEXIBLE CONNECTION

FLOW METER

BALL VALVE FOR 2" & UNDER

BUTTERFLY FOR 2.5" AND LARGER

GLOBE VALVE

MANUAL AIR VENT

METERED BALANCING VALVE

WITH PRESSURE TAPS

PRESSURE/TEMPERATURE TEST PLUG

PT

NEEDLE VALVE

PLUG VALVE

PIPE GUIDE

PIPE SLEEVE

PITCH

PRESSURE REDUCING VALVE

PRESSURE RELIEF VALVE

PRESSURE GAUGE WITH GAUGE COCK

SQUARE HEAD COCK

STRAINER

STRAINER WITH BLOW DOWN VALVE

THREE WAY CONTROL VALVE

TWO WAY CONTROL VALVE

THERMOMETER

TOP CONNECTION

UNION

VACUUM BREAKER

V-1 VALVE IDENTIFICATION

CONTROLS

ANALOG INPUT (TO PANEL)

ANALOG OUTPUT (OUT OF PANEL)

DIGITAL INPUT (TO PANEL)

DIGITAL OUTPUT (OUT OF PANEL)

TWO WAY CONTROL VALVE

THREE WAY CONTROL VALVE

BYPASS TIMER SWITCH

COMMON

CONTROL WIRING (SIGNAL PATH)

DATA TERMINAL CABINET

DIFFERENTIAL PRESSURE SWITCH

DIFFERENTIAL PRESSURE SENSOR

DUCT SMOKE DETECTOR

FAN ON-OFF SWITCH

FAN VARIABLE SPEED SWITCH

AI

AO

DI

DO

BT

C

DTC

DP

DPS

DSD

F

VSF

FLOW MEASURING SYSTEMFMS

FIRESTATFS

FREEZESTATFZ

HIGH LIMIT TEMPERATURE SENSORHL

HUMIDISTATH

LOW LIMIT TEMPERATURE SENSORLL

LOCAL TEMPERATURE CONTROL PANELTCP

MOTORM

MOTORIZED CONTROL DAMPER

MOTOR STARTERMS

NORMALLY CLOSEDNC

NORMALLY OPENEDNO

POWER WIRINGEP

SENSORS

STATIC PRESSURE SENSORP

STATIC TOTALIZER STATIONSTS

SWITCHS

T ZONE TEMPERATURE SENSOR

TT TEMPERATURE TRANSMITTER

TC TIME CLOCK

V-1 VALVE IDENTIFICATION

CSR CURRENT SENSING RELAY

NORMALLY OPEN CONTROLS

NORMALLY CLOSED CONTROLS

CWS CHILLED WATER SUPPLY

PIPING

FLEXIBLE DUCT CONNECTION

LEGEND

D1 DUCT AND EQUIPMENT PLAN KEY NOTES

P1 PIPING PLAN KEY NOTES

S1 SECTION PLAN KEY NOTES

E1 ENLARGED PLAN KEY NOTES

BOTTOM ELEVATIONB.E.

HIGH DENSITY POLYETHYLENEHDPE

MOTOR STARTERSD

VARIABLE FREQUENCY DRIVEVFD

HORIZONTAL FIRE DAMPER

ANALOG VALUE

DIGITAL VALUE

AV

DV

D

G NATURAL GAS PIPING

HRR HEAT RECOVERY RETURN

HRS HEAT RECOVERY SUPPLY

HWR HOT WATER RETURN

HWS HOT WATER SUPPLY

RL REFRIGERANT LIQUID

RS REFRIGERANT SUCTION

DIRECTION OF FLOW

CONDENSATE DRAIN LINE

DUCT RISE IN DIRECTION OF AIRFLOWUP

DUCT DROP IN DIRECTION OF AIRFLOWDN

FLOW SWITCHFS

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

1/8" = 1'-0"

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:2

AM

LE

GE

ND

M-001

LGH BMS MLM

12592390

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

PR

http://WWW.CLARKNEXSEN.COM/

1.

2.

3.

4.

5.

7.

8.

9.

13.

12.

11.

10.

6.

GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH

MECHANICAL DRAWING OF THIS SET. NOTES SPECIFIC TO INDIVIDUAL

MECHANICAL DRAWINGS WILL BE SHOWN ON THE RESPECTIVE

MECHANICAL DRAWING.

THE CONTRACTOR SHALL PROVIDE A COMPLETE HVAC SYSTEM TO

INCLUDE ALL LABOR, MATERIALS, TOOLS, AND EQUIPMENT FOR A

COMPLETE AND FUNCTIONAL SYSTEM INCLUDING ALL NECESSARY

APPURTENANCES CUSTOMARILY INCLUDED IF NOT SPECIFICALLY CALLED

OUT.

ENTIRE INSTALLATION, INCLUDING MATERIALS, EQUIPMENT, AND

WORKMANSHIP, SHALL CONFORM WITH ALL APPLICABLE LAWS, CODES,

AND REGULATIONS OF MUNICIPAL, STATE AND FEDERAL AUTHORITIES.

THIS PROJECT SHALL CONFORM TO APPLICABLE ASHRAE, NFPA, AND

SMACNA STANDARDS AND OTHER REGULATORY BODIES HAVING

JURISDICTION OVER THE CLASS OF WORK.

MATERIALS AND EQUIPMENT SHALL HAVE STAMPS OR SEALS OF ARI, ASME,

UL, AND ASTM.

CONCRETE HOUSEKEEPING PADS FOR MECHANICAL EQUIPMENT

SHALL BE PROVIDED, SIZED AND LOCATED BY THE MECHANICAL

CONTRACTOR. MINIMUM CONCRETE PAD THICKNESS SHALL BE 6

INCHES. PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF

6 INCHES ON EACH SIDE.

THE CONTRACTOR SHALL COORDINATE HIS WORK WITH THE OTHER

TRADES IN ORDER TO RESOLVE ANY CONFLICT THAT MIGHT ARISE

DUE TO THE LOCATION OF EQUIPMENT OR THE USE OF SPACE.

PROVIDE ACCESS PANELS FOR INSTALLATION IN WALLS AND

CEILINGS WHERE REQUIRED TO SERVICE DAMPERS, VALVES, SMOKE

DETECTORS AND OTHER CONCEALED MECHANICAL EQUIPMENT.

INSTALL MECHANICAL EQUIPMENT TO FACILITATE SERVICING,

MAINTENANCE, AND REPAIR OR REPLACEMENT OF EQUIPMENT

COMPONENTS. AS MUCH AS PRACTICAL, CONNECT EQUIPMENT FOR

EASE OF DISCONNECTING, WITH A MINIMUM OF INTERFERENCE WITH

OTHER INSTALLATIONS. PIPING SHALL NOT INTERFERE WITH

COMPONENT PULL CLEARANCES

DO NOT INSTALL EQUIPMENT, PIPING OR DUCTWORK OVER ANY

ELECTRICAL EQUIPMENT OR ELECTRICAL SERVICE SPACE.

RUN ALL HORIZONTAL PIPING AND DUCTWORK ABOVE CEILING

UNLESS OTHERWISE NOTED.

THE CONTRACTOR SHALL MAKE TESTS FOR ACCEPTANCE AND

APPROVAL AS REQUIRED BY CODE AND THE REQUIREMENTS OF

APPLICABLE REGULATORY AGENCIES. REQUIRED TESTS SHALL BE

PERFORMED IN THE PRESENCE OF THE GOVERNMENT UNLESS

OTHERWISE WAIVED IN WRITING.

14.

15.

16.

17.

18.

20.

21.

24.

22.

19.

MAKE DUCT PENETRATIONS OF ALL WALLS WITH SHEET METAL DUCTS. FLEXIBLE

DUCT PENETRATIONS OF WALLS ARE NOT ACCEPTABLE.

REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF

DIFFUSERS, REGISTERS, AND GRILLES. FINISH AND COLOR TO BE SELECTED BY

GOVERNMENT.

DUCTWORK SIZES ARE INSIDE CLEAR DIMENSIONS

ALL ELBOWS IN DUCTWORK SHALL BE RADIUS ELBOWS UNLESS OTHERWISE

NOTED. WHERE SQUARE ELBOWS ARE SHOWN, INSTALL TURNING VANES.

PROVIDE DYNAMIC FIRE AND SMOKE DAMPERS IN ACCORDANCE WITH THEIR U.L.

LISTING AND THE REQUIREMENTS OF NFPA-90A.

ALL CONDENSATE DRAIN PIPING SHALL BE TRAPPED AND PITCHED DOWN IN

DIRECTION OF FLOW A MINIMUM OF 1" PER 10 FEET.

LOCATE THERMOSTATS 54" ABOVE FINISHED FLOOR OR AS NOTED ON

THE PLANS. INSTALL NIGHT SETBACK THERMOSTAT ADJACENT TO

ROOM THERMOSTAT UNLESS OTHERWISE NOTED.

GENERAL

CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE

DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND

GENERAL ARRANGEMENT ONLY.

ALL VALVES ARE FULL LINE SIZE EXCEPT CONTROL AND BALANCING

VALVES.

PROVIDE PRESSURE/TEMPERATURE (P/T) PLUGS, WITH CAPS UP AND

DOWNSTREAM OF ALL EQUIPMENT, AT THE SUPPLY AND RETURN TAPS OF

ALL PIPING BRANCHES AND/OR WHERE INDICATED. PROVIDE EXTENDED

PLUGS AND LABELS WHERE PIPING IS INSULATED.

PROVIDE REMOVABLE INSULATION PLUG. PROVIDE MANUAL AIR VENTS AT

ALL HIGH SPOTS AND THE ENDS OF ALL PIPING LOOPS. PROVIDE 1/2" DRAIN

VALVES AT LOW POINTS IN PIPING.

PROVIDE MINIMUM PITCH SUFFICIENT TO INSURE ADEQUATE VENTING AND

DRAINING. PROVIDE FLUSHING VALVES AND TEES AT BOTH SIDES OF ALL

EQUIPMENT. TAPS SHALL MATCH EQUIPMENT PIPING UP TO 1". FOR LARGER

EQUIPMENT AND PIPE LOOPS PROVIDE 1 1/2" TAPS AND VALVES.

1.

2.

3.

4.

5.

7.

8.

6.

ELEVATIONS AS SHOWN ON THE DRAWINGS ARE TO THE BOTTOM OF

ALL PRESSURE PIPING AND TO THE INVERT OF ALL GRAVITY PIPING

UNLESS OTHERWISE NOTED.

UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD AND AS HIGH

AS POSSIBLE TO THE UNDERSIDE OF THE STRUCTURE OR SLAB, WITH

SPACE FOR INSULATION WHERE REQUIRED.

PIPING AND ASSOCIATED APPURTENANCES SHALL CLEAR DOORS AND

WINDOWS.

INSTALL PIPING WITHOUT FORCING OR SPRINGING.

ALL PIPING WORK SHALL BE COORDINATED WITH ALL TRADES

INVOLVED. PROVIDE OFFSETS IN PIPING AROUND OBSTRUCTIONS

ENCOUNTERED IN FIELD.

AIR CONDITIONING CONDENSATE DRAIN LINES FROM EACH AHU AND AC

UNIT SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET WITH “P” TRAP.

SEE THE DETAILS SHOWN IN THE DRAWINGS OR CONTRACT

SPECIFICATIONS FOR THE DEPTH OF THE AIR CONDITIONING CONDENSATE

TRAP.

UNLESS OTHERWISE NOTED, ALL HOT WATER PIPING SHALL BE MINIMUM

3/4 INCH SIZE.

INSTALL PIPING SO ALL VALVES, STRAINERS, UNIONS, TRAPS,

FLANGES AND OTHER APPURTENANCES REQUIRING ACCESS ARE

ACCESSIBLE.

PIPING

PROVIDE VIBRATION ISOLATORS FOR ALL PIPING SUPPORTS

CONNECTED TO, AND WITHIN 50 FEET OF, ISOLATED EQUIPMENT

(EXCEPT AT BASE ELBOW SUPPORTS AND ANCHOR POINTS)

THROUGHOUT MECHANICAL EQUIPMENT ROOMS.

1.

2.

3.

4.

5.

6.

7.

DUCTWORK AND ASSOCIATED APPURTENANCES SHALL CLEAR

DOORS AND WINDOWS.

UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD AND AS

HIGH AS POSSIBLE TO THE UNDERSIDE OF THE STRUCTURE, WITH

SPACE FOR INSULATION WHERE REQUIRED.

LOCATE MECHANICAL EQUIPMENT SUCH THAT UNOBSTRUCTED

ACCESS TO UNIT ACCESS PANELS, CONTROLS AND VALVING IS

PROVIDED.

PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS

CONNECTED TO MECHANICAL EQUIPMENT THAT REQUIRE VIBRATION

ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE

POINT OF CONNECTION TO THE EQUIPMENT UNLESS OTHERWISE

INDICATED.

EXTERIOR LOUVERS ARE INDICATED FOR INFORMATION ONLY.

DETAILED LOCATIONS AND DETAILS SHALL BE COORDINATED WITH

GENERAL CONTRACTOR AND OTHER TRADES INVOLVED.

RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 5 FEET.

HVAC/SHEET METAL

SMOKE DETECTORS SHALL BE FURNISHED AND WIRED BY

ELECTRICAL CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL

BE RESPONSIBLE FOR MOUNTING THE SMOKE DETECTOR IN

DUCTWORK AS SHOWN ON THE DRAWINGS AND IN ACCORDANCE WITH

THE MANUFACTURER'S PRINTED INSTRUCTIONS.

1.

2.

CONTROLS CONTRACTOR SHALL PROVIDE AUTOMATIC CONTROL

DEVICES, SUCH AS TEMPERATURE SENSORS, RELAYS, PRESSURE

SWITCHES WHICH ARE ASSOCIATED WITH MECHANICAL EQUIPMENT

AND ASSOCIATED CONTROL WIRING FROM STARTER TO THE

CONTROL DEVICE. ELECTRICAL CONTRACTOR SHALL PROVIDE

CONDUIT AND WIRING FROM POWER SOURCE TO DISCONNECT

SWITCH, FROM DISCONNECT SWITCH TO STARTER, AND FROM

STARTER TO THE EQUIPMENT.

ALL CONTROL WIRING EXCEPT IN EQUIPMENT ROOMS SHALL BE RUN

CONCEALED. WIRING IN WALLS SHALL BE IN CONDUIT. ALL WIRING

SHALL BE PLENUM RATED. CONTROL WIRING IN EXPOSED AREAS

SHALL BE BUNDLED AND SECURED OR RUN IN CONDUIT. NO WIRING

SHALL BE SURFACE MOUNTED IN FINISHED SPACES. ALL ELECTRICAL

WORK SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE

AND DIVISION 26 OF THE SPECIFICATIONS.

CONTROLS

1.

2.

ALL DISCONNECT SWITCHES, MOTOR STARTERS ASSOCIATED WITH

DIVISION 23 OR DIVISION 22 EQUIPMENT SHALL BE FURNISHED BY THE

DIVISION 23 OR DIVISION 22 CONTRACTOR AS APPLICABLE. WHERE

COMBINATION MOTOR STARTERS ARE PROVIDED WITH INPUT POWER

DISCONNECT SWITCH WITH OPERABLE HANDLE, A SEPARATE

DISCONNECT SWITCH AT MOTOR STARTER IS NOT REQUIRED.

COORDINATE ELECTRICAL POWER REQUIREMENTS OF ALL DIVISION 23

EQUIPMENT WITH DIVISION 26 CONTRACTOR FOR DISCONNECT

SWITCHES, MOTOR STARTERS, FEEDER BREAKER AND CABLE SIZE TO

BE ACCURATE PER EQUIPMENT NAMEPLATE DATA. REFER TO

ELECTRICAL SPECIFICATIONS FOR ELECTRICAL DEVICES

SPECIFICATIONS. VFD'S FOR DIVISION 22 AND 23 WILL PROVIDED BY

THAT DIVISION CONTRACTOR IN ACCORDANCE WITH DIVISION 26

REQUIREMENTS.

ALL DISCONNECT SWITCHES, VFD'S AND MOTOR STARTERS

(REGARDLESS OF WHO FURNISHED) SHALL BE WIRED AND

TERMINATED BY DIVISION 26 CONTRACTOR. ELECTRICAL

CONTRACTOR SHALL PROVIDE CONDUIT AND WIRING FROM POWER

SOURCE TO DISCONNECT SWITCH.

ELECTRICAL

GENERAL NOTES

23.

8. PROVIDE DYNAMIC VOLUME CONTROL DAMPERS IN ACCORDANCE

WITH UFC.9.

25. REFERENCE STRUCTURAL SHEET SF501 DETAIL 10 FOR ALL

DUCTWORK/PIPING AND EQUIPMENT HANGER CONNECTIONS TO STRUCTURE

REQUIREMENTS.

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

12" = 1'-0"

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:2

AM

GE

NE

RA

L N

OT

ES

M-002

LGH BMS MLM

12592391

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

UP UP

UP

M-401 A3

C3-AC-1

C

/ M H

STAIR

TEL

ELEC

VESTIBULE

BUNK

OFFICE

WOMEN'S

MEN'S

RECEP.

JAN

LOBBY

D2

D2

D2

A8

A6

A6

A6

C3-CAV1-1

A6

H3

H3

H3

C3-CAV1-2

C4

MH101

C3-CUH-3

C3-CUH-4

102 CORRIDOR

6x10

6x6

6x6

6x6

UP

C5

MH101

D5

D5

ROOM

MODULE

ROOM

MODULE

***d

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

*ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

*ROOM

MODULE

ROOM

MODULE

6x8

C3-CAV1-4

x1 x1

18x10

18x10 12x8

18x10

12x8

16x10

12x8

12x10 10x8

8x8

12x8

8x6

10x10

6x8

C1/M-401

A8

10x10

D10

D12/24

6x8

12x8

D12

FA DC

D1

D1

H2

DN DN

UP

5ø

28x14

STAIR

C3-CUH-1

A

/ M H

STAIR

A6

C3-CUH-2

103 CORRIDOR

ROOM

MODULE

ROOM

MODULE

*ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

16x10

12x8

12x10 10x8

8x8

C3-CAV1-3

12x8

8x6

6x8

12x8

18x10

6x8

5ø

2 1/2" HWS

8'

0"

2 1/2" HWS

2 1/2" HWS

8'

0"

32x12 28x12

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

As indicated

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:4

AM

FI

RS

T F

LO

OR

D

UC

T P

LA

N

MH101

LGH BMS MLM

12592392

1/8" = 1'-0"

FIRST FLOOR DUCT PLAN - AREA AA1

1/8" = 1'-0"

FIRST FLOOR DUCT PLAN - AREA BC1

KEYNOTES

GRAPHIC SCALE(S)

KEY PLAN

D

AREA A AREA B

AREA C

1/8" = 1' - 0" 0 5' 10' 15' 30'

D1 45 CFM TRANSFER THROUGH 3/4" DOOR UNDERCUT.

D2 50 CFM TRANSFER THROUGH 3/4" DOOR UNDERCUT.

D4 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 1.

D5 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 2.

D12 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 4.

1/4" = 1'-0" MH101

SECTION - 102

CORRIDOR C4 1/4" = 1'-0" MH101

SECTION - 101 LOBBY C5

1/4" = 1' - 0" 0 5' 10' 15'1'

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

DN UP UPDN

DNUP

C

/ M H

STAIR

STAIR

JAN

RECYCLE

D4D5

202 CORRIDOR

CORRIDOR

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

6x6 6x6

H3

H3

D12 D7

6x8

A3 M-401

A6

C3-CAV2-2

12x6 x1

18x10

12x812x8

18x1016x10

12x8

12x10

12x8 x1

C3-CAV2-1

UP UP

8x6

A6

C4

MH102

C5

MH102

D2

6x8 8x8

10x8

B1/M-402

10x10

D12/24

D10

ELEC

FA DC

H1 x1

28x14

A

/ M H

STAIR

D4 D5

203 CORRIDOR

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

C3-CAV2-3

8x6

6x8

10x8

8x8

12x8

12x1016x10

12x8 A6

16x12 28x12

18x1012x8

6x8

5ø

1 1/2" HWS

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

As indicated

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:4

AM

SE

CO

ND

F

LO

OR

D

UC

T

PL

AN

MH102

LGH BMS MLM

12592393

1/8" = 1'-0"

SECOND FLOOR DUCT PLAN - AREA AA1

1/8" = 1'-0"

SECOND FLOOR DUCT PLAN - AREA BC1

1/4" = 1'-0" MH102

SECTION - 201

CORRIDOR C5 1/4" = 1'-0" MH102

SECTION - 202

CORRIDOR C4

KEYNOTES

GRAPHIC SCALE(S)

KEY PLAN

D

AREA A AREA B

AREA C

1/8" = 1' - 0" 0 5' 10' 15' 30'

D2 50 CFM TRANSFER THROUGH 3/4" DOOR UNDERCUT.

D4 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 1.

D5 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 2.

D7 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 3.

D12 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 4.

1/4" = 1' - 0" 0 5' 10' 15'1'

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

DN UP DN UP

C3-AC-2

C

/ M H

STAIR

STAIR

TEL

JAN

A3 M-401

302 CORRIDOR

CORRIDOR

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

6x6 6x6

H3

H3

D7

6x8

12x6 x1 x1 x1

18x10

12x812x8

18x10

C3-CAV3-2

A6

16x1012x10

D17

D2

C3-CAV3-1

A6

UP UP

12x812x8

8x6

8x8

10x8

ELEC

10x10D12/24

D10

D12

FA DC

H1

28x14

D5 D10 D10

6x8

A

/ M H

STAIR

303 CORRIDOR

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

16x10

12x8

12x10

C3-CAV3-3

12x8

8x8

10x8

6x8

8x6

A6

D5D10D10

6x8

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

1/8" = 1'-0"

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:5

AM

TH

IR

D

FL

OO

R

DU

CT

P

LA

N

MH103

LGH BMS MLM

12592394

1/8" = 1'-0"

THIRD FLOOR DUCT PLAN - AREA AA1

1/8" = 1'-0"

THIRD FLOOR DUCT PLAN - AREA BC1

AREA A AREA B

AREA C

1/8" = 1' - 0" 0 5' 10' 15' 30'

KEYNOTES

GRAPHIC SCALE(S)

KEY PLAN

D

D2 50 CFM TRANSFER THROUGH 3/4" DOOR UNDERCUT.

D4 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 1.

D5 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 2.

D7 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 3.

D10 PROVIDE NON-RATED ACCESS PANEL IN CMU WALL OUTSIDE

OF CHASE. PROVIDE ACCEPTABLE ACCESS DOOR IN DUCT

FOR FIRE DAMPER MAINTENANCE.

D12 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 4.

D17 REFER TO SHEET M-401 FOR CONTINUATION.

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

C

/ M H

STAIR

STAIR

RECYCLE

JAN

A3 M-401

402 CORRIDOR

CORRIDOR

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

D16

6x6 6x6

H3

H3

D7

6x8

D3D11

A6

C3-CAV4-2

D2

UP UP

A6

C3-CAV4-1

6x8

6x8

18x10

12x8

18x10

12x8

16x10

10x8

10x10

10x8 x1 x1

12x6 x1

ELEC

10x10 D12/24

D10

D12

FA DC

H1

28x14

A

/ M H

STAIR

403 CORRIDOR

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

16x10 10x10 A6

C3-CAV4-3

6x8

6x8

10x810x8

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

1/8" = 1'-0"

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:5

AM

FO

UR

TH

F

LO

OR

D

UC

T

PL

AN

MH104

LGH BMS MLM

12592395

1/8" = 1'-0"

FOURTH FLOOR DUCT PLAN - AREA AA1

1/8" = 1'-0"

FOURTH FLOOR DUCT PLAN - AREA BC1

AREA A AREA B

AREA C

1/8" = 1' - 0" 0 5' 10' 15' 30'

KEYNOTES

GRAPHIC SCALE(S)

KEY PLAN

D

D2 50 CFM TRANSFER THROUGH 3/4" DOOR UNDERCUT.

D3 REFER TO SHEET M-704 FOR AHU SUPPLY AIR DUCT RISER.

D4 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 1.

D5 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 2.

D7 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 3.

D11 REFER TO SHEET M-704 FOR RETURN AIR DUCT RISER.

D12 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 4.

D16 26X28 EXHAUST DUCT DOWN TO MECH 214. REFER TO SHEET

M-401 FOR CONTINUATION.

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

DN

DN UP

DN

C3-AC-3

C

/ M H

STAIR

STAIR

TEL

CORRIDOR

JAN

A3 M-401

502 CORRIDOR

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

D16

6x6 6x6

H3

H3

D12 D7

6x8

D3D11

D2

UP UP

C3-CAV5-2

A6

12x6 x1

2 16 x1 x1

18x10

12x812x8

18x1016x10

10x8

10x10

10x8

6x8

6x8

A6

C3-CAV5-1

ELEC

10x10D12/24

D10

FA DC

H1

28x14

A

/ M H

STAIR

503 CORRIDOR

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

C3-CAV5-3

A6

6x8

6x8

16x10

10x8

10x10

10x8

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

1/8" = 1'-0"

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:5

AM

FI

FT

H

FL

OO

R

DU

CT

P

LA

N

MH105

LGH BMS MLM

12592396

1/8" = 1'-0"

FIFTH FLOOR DUCT PLAN - AREA AA1

1/8" = 1'-0"

FIFTH FLOOR DUCT PLAN - AREA BC1

AREA A AREA B

AREA C

1/8" = 1' - 0" 0 5' 10' 15' 30'

KEYNOTES

GRAPHIC SCALE(S)

KEY PLAN

D

D2 50 CFM TRANSFER THROUGH 3/4" DOOR UNDERCUT.

D3 REFER TO SHEET M-704 FOR AHU SUPPLY AIR DUCT RISER.

D4 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 1.

D5 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 2.

D7 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 3.

D11 REFER TO SHEET M-704 FOR RETURN AIR DUCT RISER.

D12 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 4.

D16 26X28 EXHAUST DUCT DOWN TO MECH 214. REFER TO SHEET

M-401 FOR CONTINUATION.

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

8x88x8 8x88x88x810x10

8x88x8 8x88x88x88x8

8x8

STAIR

EP1

x2

16x14

16x16

16x1414x12

14x14

12x10

D4 D4 D4

D5 D4 D4 D4 D4 D4

D4 D4D4

D12 D7

10x10

10x12

16x1620x16

16x14

D13 x2

C

/ M H

P8

P12 P7

D16

D22

FA DC

RS/RL

D

C3-AC-4

C5

MH106

D29

D29

D5

MH106

8x8 8x8 8x8 8x8 8x8 10x10

8x88x8 8x8 8x8 8x8

16x14 14x12

14x14

D4 D4 D4 D4 D4

D4 D4 D4 D4 D4 D5

D4

8x8

10x12

10x10

A

/ M H

16x16

ROOF

74' - 10"

12x36

22x22

C3-RH-1

D30

ROOF

74' - 10"

C3-RH-2

12x36

22x22

D30

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

1/8" = 1'-0"

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:0

AM

EL

EV

AT

OR

P

EN

TH

OU

SE

D

UC

T/P

IP

IN

G

PL

AN

MH106

LGH BMS MLM

12592397

GRAPHIC SCALE(S)

KEY PLAN

AREA A AREA B

AREA C

1/8" = 1' - 0" 0 5' 10' 15' 30'

KEYNOTES

GRAPHIC SCALE(S)

KEY PLAN

D

D4 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 1.

D5 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 2.

D7 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 3.

D12 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 4.

D13 EXHAUST DUCTWORK ABOVE 2 HOUR RATED CEILING.

D16 26X28 EXHAUST DUCT DOWN TO MECH 214. REFER TO SHEET

M-401 FOR CONTINUATION.

D22 INSTALL FIRE DAMPER AT SLAB LEVEL (TYP). REFER TO

SHEET M-502 FOR HORIZONTAL FIRE DAMPER DETAIL.

D29 ELEVATOR SMOKE RELIEF DUCT FROM BELOW/UP TO ROOF.

WRAP DUCT IN 2-HR RATED ENCLOSURE FROM ABOVE THE

CEILING TO THE ROOF. COORDINATE DUCT POSITION WITH

ROOF TRUSS LOCATIONS.

D30 PROVIDE INTEGRATED MOTORIZED DAMPER WITH RELIEF

HOOD AND INTERLOCK WITH FIRE ALARM.

P7 RS/RL PIPING FROM BELOW. REFER TO MP105 FOR

CONTINUATION.

P8 CONNECT 3/4" DRAIN PIPING TO CONDENSATE PUMP

SUPPLIED WITH AIR CONDITIONING UNIT.

P12 ROUTE 3/4" CONDENSATE DRAIN FROM C3-AC-4 TO HUB

DRAIN IN MECH 214.

1/8" = 1'-0"

ELEVATOR PENTHOUSE DUCT/PIPING PLAN - AREA AA1

1/8" = 1'-0"

ELEVATOR PENTHOUSE DUCT/PIPING PLAN - AREA BC1

1/8" = 1'-0" MH106

ELEVATOR RELIEF (C3-RH-1) D5

1/8" = 1'-0" MH106

ELEVATOR RELIEF (C3-RH-2) C5

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

UP UP

UP

STAIR

STAIR

TEL

ELEC

VESTIBULE

107 BUNK

OFFICE

WOMEN'S

MEN'S

ROOM

MODULE

ROOM

MODULE

***d

102 CORRIDOR

RECEP.

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

*ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

*ROOM

MODULE

ROOM

MODULE

JAN

LOBBY

C

/ M P1

C1/M-401 A3

M-401

C3-AC-1

C3-CUH-1

C3-CAV1-1

C3-CAV1-2

C3-CAV1-4

C4

MH101

T

T

T

C5

MH101

2 1/2" HWS 2 1/2" HWS 2 1/2" HWS 2 1/2" HWS 2 1/2" HWS 2 1/2" HWS

2 1/2" HWS

2 1/2" HWS

2 1/2" HWS

2 1/2" HWS

RS/RL

P4

P8 P9

2 1/2" HWS UP

D

FA DC

DDC

C3-CUH-3

C3-CUH-4

STAIR

103 CORRIDOR

ROOM

MODULE

ROOM

MODULE

*ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

A

/ M P

C3-CUH-2

C3-CAV1-3

2 1/2" HWS 2 1/2" HWS 2 1/2" HWS 2 1/2" HWS

2 1/2" HWS

2 1/2" HWS

2 1/2" HWS FROM ABOVE

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

1/8" = 1'-0"

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:0

AM

FI

RS

T

FL

OO

R

PI

PI

NG

P

LA

N

MP101

LGH BMS MLM

12592398

1/8" = 1'-0"

FIRST FLOOR PIPING PLAN - AREA AA1

1/8" = 1'-0"

FIRST FLOOR PIPING PLAN - AREA BC1

AREA A AREA B

AREA C

1/8" = 1' - 0" 0 5' 10' 15' 30'

GENERAL NOTES

KEYNOTES

GRAPHIC SCALE(S)

KEY PLAN

P

P4 RS/RL PIPING UP TO THIRD AND FIFTH FLOOR TELECOM

ROOMS 312 AND 512 AND ELEVATOR PENTHOUSE. REFER TO

SHEET MP103 FOR CONTINUATION.

P8 CONNECT 3/4" DRAIN PIPING TO CONDENSATE PUMP

SUPPLIED WITH AIR CONDITIONING UNIT.

P9 ROUTE 3/4" CONDENSATE DRAIN FROM C3-AC-1 TO HUB

DRAIN IN MECH 214.

1. REFER TO SHEETS M-701 & M-702 FOR HOT WATER PIPE

RUNOUT SIZES.

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

DN UP UPDN

C

/ M P1

B1/M-402

STAIR

STAIR

202 CORRIDOR

CORRIDOR

JAN

ELEC

213RECYCLE

T

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

1 1/2" HWS 1 1/2" HWS

1 1/2" HWS

1 1/2" HWS

1 1/2" HWS1 1/2" HWS1 1/2" HWS

1 1/2" HWS

FROM BELOW

1 1/2" HWS

DDC

C4

MH102

C5

MH102

C3-CAV2-1

C3-CAV2-2

P4

A3 M-401

P15

FA DC

A

/ M P

STAIR

203 CORRIDOR

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

1 1/2" HWS 1 1/2" HWS 1 1/2" HWS 1 1/2" HWS

1 1/2" HWS

DOWN

1 1/2" HWS

C3-CAV2-3

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

1/8" = 1'-0"

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:1

AM

SE

CO

ND

F

LO

OR

P

IP

IN

G

PL

AN

MP102

LGH BMS MLM

12592399

1/8" = 1'-0"

SECOND FLOOR PIPING PLAN - AREA AA1

1/8" = 1'-0"

SECOND FLOOR PIPING PLAN - AREA BC1

AREA A AREA B

AREA C

1/8" = 1' - 0" 0 5' 10' 15' 30'

P4 RS/RL PIPING UP TO THIRD AND FIFTH FLOOR TELECOM

ROOMS 312 AND 512 AND ELEVATOR PENTHOUSE. REFER TO

SHEET MP103 FOR CONTINUATION.

P15 3/4" CONDENSATE DRAIN FROM AC UNITS DOWN TO HUB

DRAIN IN MECH 214.

GENERAL NOTES

KEYNOTES

GRAPHIC SCALE(S)

KEY PLAN

P

1. REFER TO SHEETS M-701 & M-702 FOR HOT WATER PIPE

RUNOUT SIZES.

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

C

/ M P1

STAIR

STAIR

302 CORRIDOR

TEL

ELEC

CORRIDOR

JAN

C3-AC-2

T

T

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

1 1/2" HWS 1 1/2" HWS 1 1/2" HWS

1 1/2" HWS

1 1/2" HWS1 1/2" HWS1 1/2" HWS

FROM BELOW

1 1/2" HWS

1 1/2" HWS

DDCRS/RL

P5

P8

C3-CAV3-2

C3-CAV3-1

A3 M-401

P10

D

FA DC

A

/ M P

STAIR

303 CORRIDOR

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

1 1/2" HWS 1 1/2" HWS 1 1/2" HWS 1 1/2" HWS

DOWN

1 1/2" HWS

1 1/2" HWS

C3-CAV3-3

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

1/8" = 1'-0"

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:1

AM

TH

IR

D

FL

OO

R

PI

PI

NG

P

LA

N

MP103

LGH BMS MLM

12592400

1/8" = 1'-0"

THIRD FLOOR PIPING PLAN - AREA AA1

1/8" = 1'-0"

THIRD FLOOR PIPING PLAN - AREA BC1

AREA A AREA B

AREA C

1/8" = 1' - 0" 0 5' 10' 15' 30'

P5 RS/RL PIPING UP TO FIFTH FLOOR TELECOM ROOM 512 AND

ELEVATOR PENTHOUSE. REFER TO SHEET MP105 FOR

CONTINUATION.

P8 CONNECT 3/4" DRAIN PIPING TO CONDENSATE PUMP

SUPPLIED WITH AIR CONDITIONING UNIT.

P10 ROUTE 3/4" CONDENSATE DRAIN FROM C3-AC-2 TO HUB

DRAIN IN MECH 214.

GENERAL NOTES

KEYNOTES

GRAPHIC SCALE(S)

KEY PLAN

P

1. REFER TO SHEETS M-701 & M-702 FOR HOT WATER PIPE

RUNOUT SIZES.

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

C

/ M P1

STAIR

STAIR

CORRIDOR

ELEC

413RECYCLE

CORRIDOR

JAN

T

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

1 1/2" HWS 1 1/2" HWS 1 1/2" HWS

1 1/2" HWS

1 1/2" HWS1 1/2" HWS1 1/2" HWS

FROM BELOW

1 1/2" HWS

1 1/2" HWS

DDC

C3-CAV4-2

P5

C3-CAV4-1

A3 M-401

P15

FA DC

A

/ M P

STAIR

CORRIDOR

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

1 1/2" HWS 1 1/2" HWS 1 1/2" HWS 1 1/2" HWS

DOWN

1 1/2" HWS

1 1/2" HWS

C3-CAV4-3

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

1/8" = 1'-0"

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:1

AM

FO

UR

TH

F

LO

OR

P

IP

IN

G

PL

AN

MP104

LGH BMS MLM

12592401

1/8" = 1'-0"

FOURTH FLOOR PIPING PLAN - AREA AA1

1/8" = 1'-0"

FOURTH FLOOR PIPING PLAN - AREA BC1

AREA A AREA B

AREA C

1/8" = 1' - 0" 0 5' 10' 15' 30'

P5 RS/RL PIPING UP TO FIFTH FLOOR TELECOM ROOM 512 AND

ELEVATOR PENTHOUSE. REFER TO SHEET MP105 FOR

CONTINUATION.

P15 3/4" CONDENSATE DRAIN FROM AC UNITS DOWN TO HUB

DRAIN IN MECH 214.

GENERAL NOTES

KEYNOTES

GRAPHIC SCALE(S)

KEY PLAN

P

1. REFER TO SHEETS M-701 & M-702 FOR HOT WATER PIPE

RUNOUT SIZES.

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

DN UP

DN

C

/ M P1

STAIR

STAIR

CORRIDOR

TEL

ELEC

CORRIDOR

JAN

C3-AC-3

T

T

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

1 1/2" HWS 1 1/2" HWS 1 1/2" HWS

1 1/2" HWS

1 1/2" HWS1 1/2" HWS1 1/2" HWS

1 1/2" HWS

1 1/2" HWS

DDCRS/RL

P6

P8

P11

C3-CAV5-1

A3 M-401

1 1/2" HWS FROM ABOVE

D

C3-CAV5-2

FA DC

A

/ M P

STAIR

CORRIDOR

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

ROOM

MODULE

1 1/2" HWS 1 1/2" HWS 1 1/2" HWS 1 1/2" HWS

1 1/2" HWS

1 1/2" HWS

C3-CAV5-3

1 1/2" HWS DOWN

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

1/8" = 1'-0"

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:2

AM

FI

FT

H

FL

OO

R

PI

PI

NG

P

LA

N

MP105

LGH BMS MLM

12592402

1/8" = 1'-0"

FIFTH FLOOR PIPING PLAN - AREA AA1

1/8" = 1'-0"

FIFTH FLOOR PIPING PLAN - AREA BC1

AREA A AREA B

AREA C

1/8" = 1' - 0" 0 5' 10' 15' 30'

P6 RS/RL PIPING UP TO ELEVATOR PENTHOUSE. REFER TO

SHEET MH106 FOR CONTINUATION.

P8 CONNECT 3/4" DRAIN PIPING TO CONDENSATE PUMP

SUPPLIED WITH AIR CONDITIONING UNIT.

P11 ROUTE 3/4" CONDENSATE DRAIN FROM C3-AC-3 TO HUB

DRAIN IN MECH 214.

GENERAL NOTES

KEYNOTES

GRAPHIC SCALE(S)

KEY PLAN

P

1. REFER TO SHEETS M-701 & M-702 FOR HOT WATER PIPE

RUNOUT SIZES.

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

LOUNGE

LAUNDRY

MECH

C 3-

C U

-2 C

3- C

U -3

C 3-

C U

-4

C3-UH-1

A1/MH101

C3-SF-1

D8

D8

C 3-

B -1

C 3-

B -2

C 3-

C U

-1

C3-UH-3

C3-UH-4

C3-ET-1

36x14

3/4" HWS

3/4" HWS

C3-WH-2

C3-WH-1

C3-WH-4

C3-WH-3

2 1/2" HWS

2 1/2" HWR

D14

T

T

B6

B6

B6

B6

8x8 10x10

C3-VAV1-2

A6

A6

A6

A6

10x8 6x8

G 280J8

D10

F

8x

6ø

6ø

8x

8x8

10x10

28x14 UP

D18 x1

D19

C3-AS-1

P16

P17

P18 P19

D21

C3-VAV1-3

FA DC

C3-LV-2

C3-LV-1

10x10

C3-LV-4

C3-LV-3

WH TANK

1,500 GAL

WH TANK

1,500 GAL

C3-HX-1

C 3-

P -1

C 3-

P -2

C3-P-3

C3-P-4

C3-AS-2

2" DOMESTIC

PREHEAT. SEE

PLUMBING

2" HRR

2" HRS

C3-P-5

D25

D20

D20 D20

D20

D19D19

C3-ET-2

M

D28

D27

D27

3" HWS

3" HWR

3" HWS

4" CWS

4" CWR

3" H

W R

3" H

W S

M

M

C3-CUH-4

A1/MH102

C3-UH-2

C3-EF-1

MECH

C 3-

E R

U -1

D14

2" HWS FROM BELOW

2" HWS FROM ABOVE

4" CWS FROM BELOW

4" CWR DOWN

C3-AHU-1

26x20 x2 x3

30x28 26 x3 x2

36x14

22x22

26x36

28x30 30x30 26x28

P15

P13 x2

36x14 DOWN28x14

FROM

BELOW

10x10 FROM

BELOW

10x10

C3-LV-7

C3-LV-5 C3-LV-6

DSD

28x14

M

D26

D28

2" HWS

2" HWR

4" CWS

4" CWR

74x25

H3

ROOM

MODULE

ROOM

MODULE

***d

C

H3

D4

3/ 4"

H W

R

T T

J6 J6

C

8x

8x

5ø 5ø

8x

8x

D4

3/ 4"

H W

S

3/ 4"

H W

R 3/

4" H

W S

6x

6x

12x6 12x6

H3

D6

D6

D6

D6

H3

H4

H4

TYP. TYP.

6x66x6

C3-VAV1-1

C3-CUH-5

4" C

W R

4" C

W S

2" H

R R

2" H

R S

C3-CH-1

NOTE: CHILLER NOT SHOWN AT CORRECT

POSITION. REFER TO CIVIL DWGS. FOR

CHILLER LOCATION BEHIND BUILDING.

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

1/4" = 1'-0"

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:3

AM

EN

LA

RG

ED

P

LA

N

M-401

LGH BMS MLM

12592403

1/4" = 1'-0"

ENLARGED PLAN - AREA CC1

GENERAL NOTES

KEYNOTES

GRAPHIC SCALE(S)

KEY PLAN

E

1/4" = 1' - 0" 0 5' 10' 15'1'

D4 REFER TO SHEET M-704 FOR EXHAUST DUCT RISER 1.

D6 35 CFM TRANSFER THROUGH 3/4" DOOR UNDERCUT.

D8 4"Ø DUCT DRYER EXHAUST THROUGH WALL TO DISCHARGE

HOODS.

D14 OPEN ENDED DUCT. COVER WITH 1/2" X 1/2" STAINLESS

STEEL MESH.

D18 10X10 EXHAUST DUCT UP TO MECH 214. REFER TO A1/M-401

FOR CONTINUATION.

D19 4"Ø SEALED COMBUSTION AIR INTAKE (TYP).

D20 4"Ø WATER HEATER VENT THROUGH ROOF (TYP). REFER TO

PLUMBING PLANS FOR WATER HEATER DETAILS.

D21 4"Ø BOILER VENT THROUGH ROOF (TYP).

D25 M.O.D. INTERLOCKED WITH DDC. BALANCED AT 1400 CFM.

D26 M.O.D. INTERLOCKED WITH DDC. BALANCED AT 2300 CFM.

D27 M.O.D. INTERLOCKED WITH DDC. BALANCED AT 3960 CFM.

D28 BLANK OFF SECTIONS OF LOUVERS NOT BEING UTILIZED.

P13 ROUTE 3/4" CONDENSATE DRAIN FROM AC UNITS TO HUB

DRAIN.

P15 3/4" CONDENSATE DRAIN FROM AC UNITS DOWN TO HUB

DRAIN IN MECH 214.

P16 2" HWS UP.

P17 2" HWS FROM ABOVE.

P18 4" CWS UP.

P19 4" CWS FROM ABOVE.

AREA A AREA B

AREA C

1/4" = 1'-0"

ENLARGED PLAN - 214 MECHA1 1/4" = 1'-0"

ENLARGED PLAN - ROOM MODULE (TYP)A3

1. REFER TO SHEETS M-701 & M-702 FOR HOT WATER PIPE

RUNOUT SIZES.

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

DUCT SLEEVE

CAULK AIRTIGHT BETWEEN

SLEEVE & DUCT ALL AROUND

DUCT

NON-SHRINK GROUT

(ALL AROUND)

DUCT SLEEVE

DUCT

NON-SHRINK GROUT

(ALL AROUND)

1 1/2" x 1 1/2" x 1/8" GALV

CLOSED ANGLE ALL SIDES

WITH SCREWS 12" O.C. MIN

(2 PER SIDE)

INTERIOR WALL

1 1/2" x 1 1/2" x 1/8" GALV

CLOSED ANGLE ALL SIDES

WITH SCREWS 12" O.C. MIN

(2 PER SIDE)

INTERIOR WALL

UN-INSULATED INSULATED

FIELD APPLIED DUCT

INSULATION. RUN

CONTINUOUS THRU WALL

DSD

8" x 8" (MIN.) HINGED

ACCESS DOOR

AIR FLOW

SAMPLING TUBE

(FULL WIDTH OF DUCT)

UL CLASSIFIED SMOKE

DETECTOR WITH

AUXILIARY

CONTACTS

SEAL TUBE

PENETRATION

NOTES:

1. IF DUCT WIDTH EXCEEDS 36" , SAMPLING TUBE SHALL PENETRATE FAR SIDE OF DUCT &

HAVE INTERMEDIATE SUPPORT. PENETRATION SHALL BE SEALED AIRTIGHT.

2. LOCATE SMOKE DETECTOR IN RETURN DUCT UPSTREAM OF OUTSIDE AIR INTAKE AND

SUPPLY DUCT DOWNSTREAM OF OUTSIDE AIR INTAKE IN NON-TURBULENT AIRSTREAM.

INSTALL PER MANUFACTURER'S DETAILED INSTALLATION INSTRUCTIONS.

3. SAMPLING TUBE SHALL BE LEVEL OR SLOPING DOWN AWAY FROM DETECTOR.

4. PROVIDE A CENTRAL VISUAL SIGNALING DEVICE TO ACTIVATE UPON A SMOKE DETECTOR

TROUBLE SIGNAL (SEE PLANS FOR LOCATIONS).

5. SMOKE DETECTOR TROUBLE AND ALARM FUNCTION SHALL BE IN ACCORDANCE WITH N.C.

MECHANICAL CODE SECTION 606.4.1.

SEAL INSULATION ENDS

WITH VAPOR BARRIER

COATING

COMPOUND (TYP)

CAULK AIRTIGHT ALL AROUND

DUCT. BOTH SIDES OF WALL.

NON-SHRINK GROUT ALL

AROUND

FIELD INSULATION (TYP)

ROUND DUCT (TYP)

DOUBLE-WALL INTERNALLY

INSULATED DUCT

CMU WALL

WW

D

45.00°

45.00°

* SMALL SINGLE VANE ELBOW.

USE FOR ELBOWS UP TO 36"

IN WIDTH AND/OR DEPTH.

DIMENSIONS:

W = 1.14" D = 1.5" R = 2.00"

NOTES:

1. ALL SQUARE OR RECTANGULAR ELBOWS SHALL HAVE ONE OF THE TWO

TYPES OF TURNING VANES SHOWN. SINGLE VANE ELBOWS WILL NOT BE

PERMITTED ONLY ON RADIUS ELBOWS FOR ALL DUCTS LESS THAN 12"

WIDE.

2. VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS REQUIRED.

ALL SQUARE OR RECTANGULAR ELBOWS SHOWN ON PLANS FOR EXHAUST

OR RETURN DUCT MAY BE MADE RADIUS ELBOWS PROVIDED SPACE PERMITS

RADIUS INSTALLATION.

3. ALL SQUARE OR RECTANGULAR ELBOWS SHOWN ON PLANS FOR SUPPLY DUCT

MAY BE MADE RADIUS ELBOWS PROVIDED SPACE PERMITS RADIUS INSTALLATION,

AND/OR THERE IS NOT AN OUTLET OR TAKEOFF WITHIN 5 DIAMETERS OF THE

DOWNSTREAM SIDE OF THE ELBOW.

WIDTH

D

EP

TH

SIDE VIEWFRONT VIEW

TYPICAL ELBOW

R

FACTORY INSULATED FLEXIBLE DUCT.

FULL NECK SIZE OF DIFFUSER.

6'-0" MAXIMUM LENGTH

CLAMPINSULATION

SPIN -IN RIGID

DUCT FITTING

WITH AIR SCOOP

CEILING

T-BAR

DIFFUSER

NOTE: SEE ARCHITECTURAL PLANS FOR CEILING AND GRID INSTALLATION DETAIL AND

COORDINATE DIFFUSER INSTALLATION TO MATCH.

VOLUME DAMPER

RIGID ELBOW

45.00°

D

DIMENSIONS:

D = 6"

BRANCH DUCT

BALANCING DAMPER.

EXTEND TO OPERATE

(REQ'D IF BRANCH

SERVES A SINGLE AIR

DISTRIBUTION

DEVICE)

PRIMARY SUPPLY AIR/OUTSIDE AIR

RETURN/EXHAUST AIR

INSULATION

SET SLEEVE IN

WALL AND ANCHOR

DURING WALL

CONSTRUCTION

PIPE

PACK WITH FIBERGLASS

AND SEAL BOTH SIDES

ESCUTCHEON PLATES

(BOTH SIDES

WHERE EXPOSED)

PIPE SLEEVE

STUD WALL

INTAKE LOUVER

WITH MOTORIZED

DAMPER.

INTERLOCK DAMPER

WITH DDC

FLOOR

M

HOT WATER UNIT HEATER

WITH INTEGRAL THERMOSTAT

P P

INTERLOCK DIFF. PRESSURE

SENSOR INTO DDC

GRADE

4" METAL DRYER

EXHAUST DUCT, FLEX

DUCT MAX 4 FT.

STACKED DRYER

COMBO BY

GOVERNMENT

METAL WALL CAP

WITH BACKDRAFT

DAMPER AND NO

SCREEN

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

As indicated

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:3

AM

DE

TA

ILS

M-501

LGH BMS MLM

12592404

NOT TO SCALE

DUCT PENETRATIONS C2 NOT TO SCALE

DUCT SMOKE DETECTOR C4 NOT TO SCALE

INSULATED ROUND DUCT

PENETRATION C5

NOT TO SCALE

SQUARE OR RECTANGULAR ELBOW B5NOT TO SCALE

FLEXIBLE DUCT CONNECTION B4

NOT TO SCALE

RECTANGULAR BRANCH DUCT A4 NOT TO SCALE

PIPE SLEEVE THRU INTERIOR STUD WALL A5

NOT TO SCALE

DRYER EXAHUST & MAKE UP AIR B2

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

BREAKAWAY

JOINT NOTE 6

FIRE PARTITION OR

WALL

TYPICAL DUCT

INSULATION

ACCESS DOOR

NOTE 4

NOTE 5

SLEEVE, NOTE 2

1/4" SHEETMETAL

SCREW (TYP.)

PERIMETER ANGLE, NOTE

3 (NOT FASTENED TO

PARTITION)

PROVIDE 100% FREE AREA FIRE DAMPER. FOLLOW DAMPER MANUFACTURER INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION, NOT OUTSIDE THE PENETRATION.

GALVANIZED SLEEVE GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER FRAME AND PERIMETER ANGLES.

PERIMETER ANGLES = GALVANIZED SLEEVE, NOT LESS THAN 1 1/2 X 1 1/2 INCHES 12 GAGE, TO PROVIDE 1 INCH OVERLAP OF OPENING ON ALL 4 SIDES.

ACCESS DOOR = SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.

PROVIDE HEIGHT AND WIDTH OPENING IN RATED ASSEMBLY WITH MINIMUM CLEARANCE OF 1/8 INCH PER FOOT LARGER THAN THE DAMPER/

SLEEVE ASSEMBLY. FOR FIRESTOP REQUIREMENTS REFER TO GENERAL NOTE THIS SHEET.

PROVIDE BREAKAWAY JOINT AT DUCT TO SLEEVE CONNECTION.

1.

2.

3.

4.

5.

6.

NOTES:

THIS TYPICAL FIRE DAMPER IS GENERIC GUIDANCE ONLY. INSTALL FIRE DAMPER IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION DETAILS. DO NOT VARY FROM THOSE INSTRUCTIONS IN ANY WAY. DO NOT FIRESTOP THE GAP BETWEEN THE FIRE DAMPER SLEEVE AND THE PENETRATION UNLESS SPECIFICALLY REQUIRED BY THE DAMPER MANUFACTURER'S INSTALLATION INSTRUCTIONS USING MANUFACTURER'S RECOMMENDED FIRESTOP MATERIALS.

GENERAL NOTE FOR HORIZONTAL FIRE DAMPERS:

PROVIDE 100% FREE AREA FIRE DAMPER. FOLLOW DAMPER MANUFACTURER INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION, NOT OUTSIDE THE PENETRATION.

GALVANIZED SLEEVE GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER FRAME AND PERIMETER ANGLES.

PERIMETER ANGLES = GALVANIZED SLEEVE, NOT LESS THAN 1 1/2 X 1 1/2 INCHES 12 GAGE, TO PROVIDE 1 INCH OVERLAP OF OPENING ON ALL 4 SIDES.

ACCESS DOOR = SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.

PROVIDE HEIGHT AND WIDTH OPENING IN RATED ASSEMBLY WITH MINIMUM CLEARANCE OF 1/8 INCH PER FOOT LARGER THAN THE DAMPER/

SLEEVE ASSEMBLY. FOR FIRESTOP REQUIREMENTS REFER TO GENERAL NOTE THIS SHEET.

PROVIDE BREAKAWAY JOINT AT DUCT TO SLEEVE CONNECTION.

1.

2.

3.

4.

5.

6.

NOTES:

THIS TYPICAL FIRE DAMPER IS GENERIC GUIDANCE ONLY. INSTALL FIRE DAMPER IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION DETAILS. DO NOT VARY FROM THOSE INSTRUCTIONS IN ANY WAY. DO NOT FIRESTOP THE GAP BETWEEN THE FIRE DAMPER SLEEVE AND THE PENETRATION UNLESS SPECIFICALLY REQUIRED BY THE DAMPER MANUFACTURER'S INSTALLATION INSTRUCTIONS USING MANUFACTURER'S RECOMMENDED FIRESTOP MATERIALS.

GENERAL NOTE FOR HORIZONTAL FIRE DAMPERS:

FLOOR

SEE NOTE 4

1" MIN TYPICAL OVERLAP

ON ALL SIDES OF DAMPER

GALVANIZED STEEL BLADES WITH

INTERLOCKING JOINTS DROP

CURTAIN TYPE WITH 100% FREE

AREA (U.L. LABELED)

FUSIBLE LINK (U.L.)

INSULATION (TYP.)

DUCT SIZE AS

SHOWN ON PLANS

BLADE LOCK

HEMMED "S" SLIP BREAKAWAY

CONNECTION (TYP.) AND AS

INDICATED IN MANUFACTURER'S

INSTALLATION INSTRUCTIONS

ANGLE FASTENED TO SLEEVE

(TYP.) (SEE NOTE 3)

FRAME BRACE AND

CURTAIN FRAME

STAINLESS STEEL

CLOSURE SPRING

GALVANIZED STEEL SLEEVE

GAUGE IN ACCORDANCE

WITH SMACNA FASTEN TO

FIRE DAMPER FRAME

A P

P R

O X

. 1 5"

TWIST OFF

PRESSURE CAP

APPROX. 10"

3 1/2" MIN.

OPENING

PLUGGED

CROSSES (TYP.)

3/4" TO PUMP

SUCTION

BALL VALVE

3/4" TO PUMP

DISCHARGE

BALL VALVE

DRAIN VALVE

WITH HOSE

CONNECTION

45° CHAMFER (TYP.)

5 GAL. MIN. CAPACITY

4" THICK CONCRETE PAD 16" x 16"

UNION (TYP)

CLEANOUT (TYP)

COOLING

COIL

DRAIN

PAN

DRAIN PIPE TO BE

SLOPED 1/8" MIN PER FT

SEE FLOOR PLANS FOR

CONTINUATION AND SIZE.

FINISH FLOOR

TURN DOWN TO

FLOOR DRAIN WHERE

INDICATED

NOTES:

1. "A" = TOTAL PRESSURE OF FAN PLUS 4" MIN

2. "B" = TOTAL PRESSURE OF FAN (IN OF WATER)

SLOPE

"B"

"A"

2" AIR SPACE

RELIEF VALVE. SEE SCHEDULE

FOR PRESSURE SETTINGS.

FLOOR

4" HOUSEKEEPING PAD

PRESSURE GAUGE

DRAIN VALVE

AIR/DIRT SEPARATOR,

SEE SCHEDULE SHEET

FROM SYSTEM

AUTOMATIC AIR VENT

FULL SIZE TO FLOOR DRAIN

PRESSURE GAUGE

RPPBFP

BLADDER TYPE EXPANSION TANK

SEE SCHEDULE SHEET

TO PUMP

SUCTION

FULL SIZE

BYPASS

FUNNEL DRAIN, ROUTE TO

FLOOR DRAIN

PRESSURE REDUCING VALVE

MOUNT BACKFLOW

PREVENTER 4' A.F.F.

WORK BY PLUMBING

CONTRACTOR

DOMESTIC COLD

WATER MAKE-UP

CONTINUATION

WITH QUICK FILL

VALVE.

3/4"

3/4"

RATED

ASSEMBLY

NOTES: FOR REFERENCE PURPOSES ONLY. CONTRACTOR SHALL VERIFY CONDITIONS IN FIELD PRIOR TO INSTALLATION AND INSTALL FIRE/SMOKE DAMPERS PER MANUFACTURER'S INSTRUCTIONS FOR

ACCESS AND FUNCTIONALITY.

ATTIC SPACE

ACCESS

PANEL

MANUAL BALANCING

DAMPER

EXHAUST DUCT

A

IR

FL

O

W

18" X 18" FIRE

RATED WALL

ACCESS PANEL

ROOF TRUSS.

COORDINATE EXACT

LOCATION WITH TRUSS

MANUFACTURER

8x4 EXHAUST DUCT

HORIZONTAL FIRE DAMPER.

SHOWER

CEILING

VERTICAL FIRE DAMPER.

CEILING ACCESS

PANEL

6x12 DUCT

ACCESS PANEL

RALEIGH, NC 27607

4000 WESTCHASE BLVD.

919·828·1876 FAX 919·828·1877

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

N A

V

AL

S

TA

TI

O

N

N O

R

FO

LK

, V

IR

G

IN

IA

M C

B C

A M

P

LE

JE

U

N E

JA

C

K

SO

N

VI

LL

E, N C

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SEAL

N A

V

AL

F A

C

IL

IT

IE

S E

N G

IN

EE

R

IN

G C

O M

M A

N D

D E

PA

R

TM

E

N T

O F

TH

E

N

AV

Y

DRAWFORM REVISION: 10 MARCH 2009

OF

<<PM/DM>>

BRANCH MANAGER

CHIEF ENG/ARCH

<<XX>>

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

A/E INFO

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

# - N40085 - 10 - C - 5312

W A

LL

A

C E

C R

E E

K R

E G

IM

E

N

TA

L C

O M

P

LE

X

P H

A S

E

II

B E

Q C

(W

C

0)

20 DECEMBER 2012

C3

Architecture & Engineering

WWW.CLARKNEXSEN.COM

CLARK NEXSEN LICENSE # C-1028

BRIAN ABBOTT

RECORD DRAWINGS

INCLUDE AS-BUILT

CONDITIONS PER

THE FIELD SET AND

MAY NOT MATCH

THE ORIGINAL

CONTRACT

DRAWING SHEETS

As indicated

C :\R ev it

P ro je ct s\

_W al la ce C re ek

B

E Q

M

_f jo se y.

rv t

/1

8/

0:

:3

AM

DE

TA

ILS

M-502

LGH BMS MLM

12592405

NOT TO SCALE

VERTICAL FIRE DAMPER C5

NOT TO SCALE

HORIZONTAL FIRE DAMPER A5

12" = 1'-0"

SHOT FEEDER C3

NOT TO SCALE

COOLING COIL CONDENSATE TRAP B3

NOT TO SCALE

EXPANSION TANK/AIR SEPARATOR A3

12" = 1'-0"

TYPICAL 5TH FLOOR EXHAUST

DUCT DETAIL B2

N o.

D E

SC

R

IP

TI

O N

D A

TE

A

P

SUSPENDED EQUIPMENT:

1. ALL SUSPENDED MECHANICAL EQUIPMENT WEIGHING OVER 30 POUNDS SHALL BE INSTALLED TO RESIST FORCES OF

0.5 TIMES THE EQUIPMENT WEIGHT IN ANY DIRECTION AND 1.5 TIMES THE EQUIPMENT WEIGHT IN THE DOWNWARD…

This is the start of the file's text. The full file is on GovTribe.