Attachment B - Reference Drawings - REPLACE ROOF MEMBRANE - Building 501 (27JAN2026).pdf
PDF 421 KB Posted
- Solicitation number
- N4008526R0145
About this file
This is a set of architectural design drawings for a roof membrane replacement project at Naval Air Station (NAS) Oceana, Dam Neck Annex in Virginia Beach, Virginia. The project involves complete demolition and replacement of the existing SBS (Styrene-Butadiene-Styrene) modified bitumen roofing system on Building 501 with a new 2-ply, cold-applied, fully-adhered, heat-welded SBS modified bitumen roofing system. The project is under the Naval Facilities Engineering Systems Command (NAVFAC) Mid-Atlantic division, with construction contract number 1819725 and project number 12940796-12940801. The scope includes removal of existing roofing and flashings to the structure, salvage and reinstallation of existing mechanical equipment (including HVAC units and exhaust fans), demolition of existing mechanical curbs and roof pads, and provision of new metal coping, roof curbs, tapered insulation, vapor permeable air barriers, and all necessary flashing details. Design loads are based on UFC (Unified Facilities Criteria) standards with a risk category III classification, including a basic design wind speed of 132 mph, ground snow load of 10 psf, and 100-year rain intensity of 3.5 inches per hour.
The architectural package consists of six sheets including a cover sheet, list of sheets, architectural notes and symbols, roof plan demolition, roof plan, and typical roof details at scales ranging from 1/8" = 1'-0" to 3/4" = 1'-0". Key construction requirements include field verification of existing dimensions prior to material ordering, coordination of lay-down areas with the contracting officer, submission of materials and methods for approval prior to work commencement, observation of building and compound security requirements, and minimization of interference with ongoing operational activities. All materials must be new unless specifically noted as existing or government-furnished. The drawings are dated 1/27/2026 and were prepared by RBH under NAVFAC design form revision 25 August 2020.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SITE VISIT LOG.pdf | ||
| Attachment A - Reference Drawings - REPAIRS ANS ALTERATIONS TO BUILDING 501 (08JULY2004).pdf | ||
| Master Spreadsheet PPIS RESPONSES.pdf | ||
| 26R0145 AMENDMENT 0002.pdf | ||
| eProjects 1907329 Addendum 01.pdf | ||
| 26R0145_AMENDMENT 0001.pdf | ||
| BASE ACCESS INSTRUCTION.pdf | ||
| SECNAV 5512.pdf | ||
| ATTACHMENT K - PIEE Vendor Access Instructions.pdf | ||
| DEVGRU SPREADSHEET.xlsx | XLSX spreadsheet | |
| ATTACHMENT_F_PPI_Spreadsheet.xlsx | XLSX spreadsheet | |
| 1907329 Replace HVAC Equipment DB_RFP (032726).pdf | ||
| ATTACHMENT N Visit Authorization Request.docx | DOCX document | |
| N4008526R0145 GENERAL REQUIREMENTS.pdf | ||
| ATTACHMENT B.pdf | ||
| ATTACHMENT E BLANK SPREADSHEET.xlsx | XLSX spreadsheet |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WILLOUGHBY BAY
NAVAL SUPPORT
ACTIVITY
U.S. NAVAL STATION
SEWELLS POINT
NORFOLK
U.S. NAVAL
AIR STATION
CHESAPEAKE BAY
LITTLE CREEK
U.S. NAVAL
AMPHIBIOUS BASE
VA BEACH
OCEANA
NAVAL AIR
STATION
CHESAPEAKE
SOUTHERN BRANCH
EASTERN BRANCH
ST. JULIEN'S CREEK
U.S. NAVAL ANNEX
ELIZABETH RIVER
PORTSMOUTH
U.S. ARMY CRANEY
ISLAND DISPOSAL AREA
NANSEMOND RIVER
WESTERN BRANCH
CRANEY
ISLAND NAVY
DEPOT
PROJECT SITE
NORTH
NORTH
TE
R
R
IE
R A
V E
PROJECT SITE
BLDG 501
R E
G U
LU
S
A V
E
DN TALOS ST
TARTAR AVE
DAM NECK RD
MAIN GATE
NAS OCEANA, DAM NECK ANNEX, VIRGINIA BEACH, VIRGINIA
NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
MID-ATLANTIC
DESIGN AND CONSTRUCTION
RESIDENT OFFICER IN CHARGE OF CONSTRUCTION
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
S O
C E
A N
A
V
IR
G
IN
IA
B
E A
C H
V
A
AS NOTED
/2
/2
:5 :3
A
M
C R e v it L o c a l F ile s \D
N
-1
-A -R jo h a n
.s ta d le r.
rv t
GI001
R E
P
LA
C E
R O
O F
M E
M B
R A
N E
C O
V E
R S
H E
E T
SDM
12940796
AA JS
1/27/2026
TONY PESSIG, RBH
B U
IL
D
IN
G
SDM/AA
1819725
V
IR
G
IN
IA
B
E A
C H
, V
IR
G
IN
IA
N
A S
O C
E A
N A
, D A
M N
E C
K A
N N
E X
HSDC
SDM
N/A
R O
IC
C
O C
E A
N A
G I0
REPLACE ROOF MEMBRANE
BUILDING 501
LOCATION MAPVICINITY MAP
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
GENERAL PROJECT SYMBOLS
A1
A-301
A-401 INTERIOR ELEVATION
INDICATOR
INTERIOR ELEVATION NUMBER
SHEET WHERE DRAWN
EXTERIOR ELEVATION
INDICATOR
ELEVATION NUMBER
DIRECTION OF VIEW
SHEET WHERE DRAWN
A1
A-301
WALL / PARTIAL
BUILDING SECTION
INDICATOR
SECTION NUMBER
SHEET WHERE DRAWN
A1
A-301
BUILDING SECTION
INDICATOR
SECTION NUMBER
SHEET WHERE DRAWN
A1
A-301
BUILDING
A1
A1
A1
A1
DETAIL NUMBER
SHEET WHERE DRAWN
DETAIL
INDICATORA-501
VIEW NUMBERSHEET
BACK-REFERENCE
VIEW
BACK-REFERENCE
ENLARGED PLAN
NUMBER
SHEET
BACK-REFERENCE
VIEW
BACK-REFERENCE
KEYNOTE INDICATOR
KEYNOTE NUMBER
PLAN NUMBER
A1
SCALE: 1/8" = 1'-0"
PLAN TITLE
A1
A1
A-101
ENLARGED PLAN
SCALE: 1/4" = 1'-0"
A1
DETAIL/SECT/ELEV
SCALE: 1/8" = 1'-0"
A1
A-101
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
S O
C E
A N
A
V
IR
G
IN
IA
B
E A
C H
V
A
AS NOTED
/2
/2
:5 :3
A
M
C R e v it L o c a l F ile s \D
N
-1
-A -R jo h a n
.s ta d le r.
rv t
GI002
R E
P
LA
C E
R O
O F
M E
M B
R A
N E
LI
S
T O
F S
H E
E T
S
SDM
12940797
AA JS
1/27/2026
TONY PESSIG, RBH
B U
IL
D
IN
G
SDM/AA
1819725
V
IR
G
IN
IA
B
E A
C H
, V
IR
G
IN
IA
N
A S
O C
E A
N A
, D A
M N
E C
K A
N N
E X
HSDC
SDM
N/A
R O
IC
C
O C
E A
N A
G I0
LIST OF SHEETS
SHEET NO.
NAVFAC DWG. NO. SHEET TITLENO. SHEET
GENERAL
1 GI001 12940796 COVER SHEET
2 GI002 12940797 LIST OF SHEETS
ARCHITECTURE
3 AE001 12940798 ARCHITECTURAL NOTES AND SYMBOLS
4 AD101 12940799 ROOF PLAN - DEMOLITION
5 AE101 12940800 ROOF PLAN
6 AE501 12940801 TYPICAL ROOF DETAILS
DESIGN LOADS AND CRTERIA
1 WHERE EXISTING CONSTRUCTION IS DAMAGED BY CONSTRUCTION
REQUIRED BY THESE DOCUMENTS, REPAIR THE DAMAGED ITEM(S) WITH
MATERIALS TO MATCH THE ADJACENT MATERIAL, TEXTURE AND COLOR.
2 FIELD VERIFY EXISTING DIMENSIONS, PRIOR TO ORDERING MATERIALS OR
BEGINNING DEMOLITION.
3 ITEMS NOT SHOWING AS "EXISTING" MUST BE PROVIDED AND INSTALLED
UNDER THE REQUIREMENTS OF THIS CONTRACT.
4 COORDINATE LAY DOWN AREA WITH THE CONTRACTING OFFICER PRIOR TO
THE PRECONSTRUCTION MEETING. THE ALLOWABLE AREA SIZE MUST BE
ESTABLISHED BY THE CONTRACTING OFFICER.
5 MANUFACTURER'S TRADE NAMES LISTED ARE NOT INTENDED TO BE
PROPRIETARY. PRODUCTS OF OTHER MANUFACTURERS WILL BE
ACCEPTABLE PROVIDED THEY MATCH THE COLOR, FINISHES, TEXTURES
AND PATTERNS OF THE MANUFACTURER LISTED, AND MEET THE
TECHNICAL REQUIREMENTS OF THE SPECIFICATIONS.
6 OBSERVE AND MAINTAIN BUILDING AND COMPOUND SECURITY
REQUIREMENTS AS DIRECTED BY THE CONTRACTING OFFICER.
7 CONSTRUCTION WILL BE ACCOMPLISHED IN AND AROUND AREAS WHICH
WILL REMAIN OPERATIONAL. AVOID INTERFERENCE WITH THE
OPERATIONAL WORK ROUTINE.
8 SUBMITTALS REQUIRED BY THESE DRAWINGS OR SPECIFICATIONS MUST BE
SUBMITTED TO THE CONTRACTING OFFICER FOR APPROVAL PRIOR TO
COMMENCEMENT OF RELATED WORK.
9 ITEMS INDICATED TO BE REMOVED MUST BE DISPOSED OF OFF SITE
UNLESS OTHERWISE NOTED.
10 MATERIALS MUST BE NEW AND PROVIDED BY THE CONTRACTOR UNLESS
SPECIFICALLY NOTED AS EXISTING OR AS PROVIDED BY THE GOVERNMENT.
11 WOOD BLOCKING AND MISCELLANEOUS STEEL SHOWN IN DETAILS AND
SECTIONS MUST BE CONTINUOUS UNLESS SPECIFICALLY NOTED
OTHERWISE.
12 VERIFY FIELD CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING WITH
THE WORK. DIMENSIONS FOR EXISTING WORK ARE INDICATED AS "±".
DISCREPANCIES MUST BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
CONTRACTING OFFICER IN WRITING.
13 STUDY AND COMPARE THE CONTRACT DOCUMENTS WITH EACH OTHER,
AND AT ONCE, REPORT TO THE CONTRACTING OFFICER ANY ERRORS AND
INCONSISTENCIES OR OMISSIONS DISCOVERED. ANY CONSTRUCTION
ACTIVITY PERFORMED KNOWING IT INVOLVES A RECOGNIZED ERROR,
INCONSISTENCY OR OMISSION IN THE CONTRACT DOCUMENTS WITHOUT
SUCH NOTICE TO THE ARCHITECT, THE CONTRACTOR WILL ASSUME
RESPONSIBILITY FOR SUCH PERFORMANCE AND WILL BEAR THE AMOUNT
OF THE COST OF THE CONSTRUCTION.
14 AREAS WITHIN THESE CONSTRUCTION DOCUMENTS WHICH ARE UNCLEAR
OR CONFLICTING ARE TO BE BROUGHT TO THE IMMEDIATE ATTENTION OF
THE CONTRACTING OFFICER FOR CLARIFICATION.
15 CONTRACTR SHALL BEAR RESPONSIBILITY FOR CORRECTIVE ACTION DUE
TO THE CONTRACTOR'S FAILURE TO COORDINATE THE WORK.
BUILDING CODE:
• UNIFIED FACILITIES CRITERIA (UFC) DoD BUILDING CODE 1-200-01
WITH Change 4 (26 FEBRUARY 2024)
• UNIFIED FACILITIES CRITERIA (UFC) 1-200-02 HIGH PERFORMANCE AND
SUSTAINABLE BUILDFING REQUIREMENTS W/ CHANGE 3 (8 JULY 2025)
• UNIFIED FACILITIED CRITERIA (UFC) 3-101-01 ARCHITECTURE W/
CHANGE 4 (08 JAN 2024)
• UNIFIED FACILITIES CRITERIA (UFC) 3-110-03 ROOFING W/ CHANGE 5
• (12 JUNE 2020)
• 2021 INTERNATIONAL BUILDING CODE (IBC)
• 2021 IEBC INTERNATIONAL EXISTING BUILDING CODE (IEBC)
MECHANICAL CODE:
• INTERNATIONAL MECHANICAL CODE (IMC)
ELECTRICAL CODE:
• NFPA 70, NATIONAL ELECTRIC CODE
PLUMBING CODE:
• INTERNATIONAL PLUMBING CODE (IPC)
GOVERNING REGULATIONS GENERAL PROJECT NOTES
RISK CATEGORY: III PER UFC 3-301-01 TABLE 2-2.
LIVE LOADS PER UFC 3-301-01 TABLE E-1
ROOFS:
• UNIFORM LOAD: 20 PSF
• CONCENTRATED LOAD: 300 LBS
UNIFORM AND CONCENTRATED LIVE LOADS HAVE NOT BEEN APPLIED
CONCURRENTLY. WHERE BOTH UNIFORM AND CONCENTRATED LOADS ARE
INDICATED, THE SUPPORTING STRUCTURE HAS BEEN DESIGNED FOR THE LOAD
THAT PRODUCES THE GREATER LOAD EFFECTS.
LIVE LOADS FOR ROOF FRAMING MEMBERS HAVE NOT BEEN REDUCED.
ROOF SNOW LOAD DATA
• GROUND SNOW LOAD: pg = 10 PSF
• FLAT-ROOF SNOW LOAD: pf = 7.7 PSF
• SNOW EXPOSURE FACTOR: Ce = 1.0 FOR PARTIALLY EXPOSED AT
TERRAIN CATEGORY C
• SNOW LOAD IMPORTANCE FACTOR: IS = 1.10
• THERMAL FACTOR: Ct = 1.0
• SLOPE FACTOR: Cs = 1.0
• DRIFT SURCHARGE LOAD: pd = 65 PSF
• WIDTH OF SNOW DRIFT: DRIFT APPLIED AS UNIFORM LOAD ACROSS
ENTIRE 10 FOOT WIDTH OF HANGAR BAY DOOR ROOFS.
WIND DESIGN DATA
• BASIC DESIGN WIND SPEED: 132 MPH
• ALLOWABLE STRESS DESIGN WIND SPEED: 102 MPH
• WIND EXPOSURE CATEGORY: C
• INTERNAL PRESSURE COEFFICIENT: +/- 0.55.
• ENCLOSURE CLASSIFICATION: PARTIALLY ENCLOSED
• TOPOGRAPHIC FACTOR: 1.0
EARTHQUAKE DESIGN DATA
• SEISMIC IMPORTANCE FACTOR: IE = 1.25
• MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS:
SS = 0.08g, S1 = 0.0387g
• SITE CLASS: D
• DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS:
SDS = 0.085g, SD1 = 0.061g
• SEISMIC DESIGN CATEGORY: A
THE ASCE 7-16 SEISMIC DESIGN REQUIREMENTS FOR BUILDINGS DO NOT
APPLY TO THIS BUILDING SINCE IT HAS BEEN ASSIGNED TO SEISMIC
DESIGN CATEGORY A.
ROOF RAIN LOAD DATA
100-YEAR RAIN INTENSITY: i = 3.5 INCH/HOUR
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
MATERIALS LEGEND
CONCRETE MASONRY UNIT
CAST-IN-PLACE CONCRETE
STEEL
BATT/LOOSE FILL INSULATION
RIGID INSULATION
WOOD - ROUGH
WOOD BLOCKING
EIFS - PAINTED
CMU - PAINTED
SECTION ELEVATION
CMU - PAINTED - ACCENT
GLAZED BLOCK
GLAZING
SPANDREL GLAZING / STEEL PANEL
CONCRETE FOUNDATION
EARTH / COMPACT FILL
POROUS FILL / GRAVEL
ALUMINUM
BRICK
GYPSUM BOARD
PLYWOOD
SAND / MORTAR / PLASTER
ACOUSTICAL TILE CEILING
CERAMIC TILE
FINISHED WOOD
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
S O
C E
A N
A
V
IR
G
IN
IA
B
E A
C H
V
A
AS NOTED
/2
/2
:5 :3
A
M
C R e v it L o c a l F ile s \D
N
-1
-A -R jo h a n
.s ta d le r.
rv t
AE001
R E
P
LA
C E
R O
O F
M E
M B
R A
N E
A R
C H
IT
E
C T
U R
A L
N O
TE
S
A N
D S
Y M
B O
LS
SDM
12940798
AA JS
1/27/2026
TONY PESSIG, RBH
B U
IL
D
IN
G
SDM/AA
1819725
V
IR
G
IN
IA
B
E A
C H
, V
IR
G
IN
IA
N
A S
O C
E A
N A
, D A
M N
E C
K A
N N
E X
HSDC
SDM
N/A
R O
IC
C
O C
E A
N A
A E
AB ANCHOR BOLT
ACM ASBESTOS COVERED METAL
ACS PNL ACCESS PANEL
ADJ ADJUST
ALT ALTERNATE, ALTITUDE
ALUM ALUMINUM
ANOD ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECT
ASPH ASPHALT
ATC ACOUSTICAL TILE CEILING
BD BOARD
BLDG BUILDING
BLW BELOW
BM BEAM
BOS BOTTOM OF SLAB / STEEL
BOT BOTTOM
BRG BEARING
BSMT BASEMENT
BTWN BETWEEN
C TO C CENTER TO CENTER
CAB CABINET
CEM CEMENT
CER CERAMIC
CI CAST IRON
CIP CAST IRON PIPE
CJ CONTROL / CONSTRUCTION JOINT
CLG CEILING
CLG REG CEILING REGISTER
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CND CONDUIT
CNDS CONDENSATE
CNSTR CONSTRUCTION
CNTR CNTR
CO CLEANOUT
COL COLUMN
CONC CONCRETE
CONN CONNECT
CONT CONTINUE / CONTINUOUS
ARCHITECTURAL ABBREVIATIONS
1. REFER TO ATTACHMENT 8.1 FOR EXISTING MODIFIED ROOFING WITH
EXISTING COATING TO BE DEMOLISHED.
2. REMOVE EXISTING ROOFING AND FLASHINGS TO STRUCTURE. WHERE
MECHANICAL, ELECTRICAL AND PLUMBING ITEMS ARE ATTACHED OR
PLACED ON ROOF, REMOVE AND PROTECT ITEMS REQUIRED TO BE
REINSTALLED. IDENTIFY MECHANICAL, ELECTRICAL AND PLUMBING ITEMS
AND LOCATIONS FOR INSTALLATION AT SAME LOCATIONS AFTER ROOFING
IS INSTALLED WITH UPDATED DETAILS.
3. PROVIDE COMPLETE 2-PLY, COLD-APPLIED, FULLY-AHDERED, SBS MODIFIED
BITUMEN ROOFING SYSTEM, HEAT-WELDED, TYPICAL. PROVIDE INTERPLIES
AT PENETRATIONS, ROOF EDGES, AND ALL OTHER PLACES THAT
MANUFACTURER REQUIRED TO PROVIDE 20-YEAR WARRANTY.
4. PENETRATION DETAILS WITH FLASHING MUST MEET APPROVAL OF ROOFING
MANUFACTURER'S REQUIREMENTS TO MEET 20-YEAR WARRANTY.
5. AT ROOF DRAINS, PROVIDE NEW PIPING AND FITTINGS NECESSARY TO
PROVIDE A COMPLETE WATER-TIGHT CONNECTION. PROVIDE NEW
STAINLESS STEEL HARDWARE.
6. PROVIDE NEW METAL PIPE AND VENT ADAPTERS, COLLARS, CAPS, AND
BOOTS. INSTALL WITH NEW ROOFING SYSTEM. PROVIDE METAL OF SAME
MATERIAL, TYPE, AND SIZE AT TALL EXHAUST VENTS.
7 AT ROOF DRAINS (TYP), REMOVE ROOF DRAIN ASSEMBLY FROM EXISTING
RAIN LEADER. DEMOLISH ROOF DRAIN ASSEMBLY. PROVIDE NEW ROOF
DRAIN ASSEMBLY AND CONNECT TO EXISTING RAIN LEADER. REFER TO
UFGS SPECIFICATION 22 00 00 “PLUMBING, GENERAL PURPOSE”.
8 AT CONDENSER UNITS (TYP), PERFORM OPERATIONAL TEST OF SPLIT
SYSTEM. RECORD RESULTS OF OPERATIONAL TEST AND REPORT TO
CONSTRUCTION MANAGER. AFTER COMPLETION OF OPERATIONAL TEST,
COORDINATE WITH ELECTRICAL CONTRACTOR FOR LOCKOUT/TAGOUT AND
DISCONNECTION OF CONDENSER UNIT. AFTER SPLIT SYSTEM IS LOCKED
OUT/TAGGED OUT, DISCONNECT REFRIGERANT PIPING AND CAP FOR
FUTURE REINSTALLATION. CAREFULLY REMOVE CONDENSER UNIT FROM
TIMBER SUPPORTS, PROTECT AND RESERVE FOR REINSTALLATION. AFTER
ROOF WORK IS COMPLETE, REINSTALL CONDENSER UNIT FAN ATOP NEW
SUPPORTS. COORDINATE WITH ELECTRICAL CONTRACTOR FOR
ELECTRICAL RECONNECTION OF SPLIT SYSTEM. AFTER RECONNECTION OF
ELECTRICAL, PROVIDE REFRIGERANT CHARGE AND PERFORM
OPERATIONAL TEST. RECORD RESULTS AND REPORT TO CONSTRUCTION
MANAGER.
9 AT EXHAUST FANS ON CURBS WITH ADAPTERS, PERFORM OPERATIONAL
TEST OF EXHAUST FAN ON CURB. RECORD RESULTS OF OPERATIONAL
TEST AND REPORT TO CONSTRUCTION MANAGER. AFTER COMPLETION OF
OPERATIONAL TEST, COORDINATE WITH ELECRICAL CONTRACTOR FOR
LOCKOUT/TAGOUT AND DISCONNECTION OF EXHAUST FAN. AFTER
EXHAUST FAN IS LOCKED OUT/TAGGED OUT, CAREFULLY REMOVE EXHAUST
FAN FROM CURB ADAPTER, PROTECT AND RESERVE FOR REINSTALLATION.
REINSTALL EXHAUST FAN ATOP ROOF CURB ADAPTER. COORDINATE WITH
ELECTRICAL CONTRACTOR FOR RECONNECTION OF EXHAUST FAN. AFTER
RECONNECTION OF ELECTRICAL, PROVIDE OPERATIONAL TEST OF
EXHAUST FAN. RECORD RESULTS AND REPORT TO CONSTRUCTION
MANAGER.
10 SEE AE501 FOR TYPICAL PENETRATION AND EQUIPMENT SUPPORT DETAILS.
11 DEMOLISH AND REPLACE ALL MECHANICAL ROOF TOP GAS PIPE.
GENERAL ARCHITECTURAL NOTES
CORR CORRIDOR
CPT CARPET / COMMON PATH OF TRAVEL
CT CERAMIC TILE
CTR CENTER
D DEPTH / DEEP
DEG DEGREE
DEMO DEMOLITION
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DR DRAIN
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
E EAST
EA EACH
EIFS EXTERIOR INSULATION & FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC / ELECTRICAL
EPDM ETHLENE PROPYLENE DIEN MONOMER
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION / EXPOSED / EXPAND
EXT EXTERIOR
FD FLOOR DRAIN
FDTN FOUNDATION
FF FINISH FACE
FG FIGURE
FHC FIRE HOUSE CABINET
FIN FLR FINISHED FLOOR
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUB / FACE OF SLAB
FR FRAME / FIRE RATING / FIRE RESISTANT
FT FOOT, FEET
FTG FOOTING
GA GAUGE
GALV GALVANIZED
GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED GOVERNMENT INSTALLED
GL GLASS / GROUND LEVEL
GR GROSS
GSU GLAZED STRUCTURAL UNIT
GYP GYPSUM
H HIGH
HB HOSE BIB
HDW HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HT HEIGHT
HVY HEAVY
ID INSIDE DIAMETER
INSUL INSULATION / INSULATED
INT INTERIOR
J-BOX JUNCTION BOX
JAN JANITOR CLOSET
LAV LAVATORY
LB POUND
LT LIGHT
MACH MACHINE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFG MANUFACTURING
MIN MINIMUM / MINUTE
MISC MISCELLANEOUS
ML MATCH LINE
MO MASONRY OPENING / MOTOR OPERATED
MTD MOUNTED
MTG MOUNTING / MEETING
MTL METAL
MWP MEMBRANE WATERPROOFING
N NORTH
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OC ON CENTER
OD OUTSIDE DIAMETER / DIMENSION
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPT OPTIONAL
PCT PERCENT
PEJ PREMOLDED EXPANSION JOINT
PL PROPERTY LINE
PLAS PLASTER / PLASTIC
PLYWD PLYWOOD
PNL PANEL
PRELIM PRELIMINARY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT
QT QUARRY TILE
R RADUIS / RISER
RA RETURN AIR
RAD RETURN AIR DUCT
RB RESILIENT BASE
RD ROOF DRAIN / ROAD
REFL REFLECT
REFR REFRIGERATION
REINF REINFORCE
REQD REQUIRED
REV REVISION
RF RESILIENT FLOORING
RL ROOF LEADER
RM ROOM
RND ROUND
RO ROUGH OPENING
RS ROUGH SAWN
RT RIGHT
S SOUTH
SAPC SUSPENDED ACOUSTICAL PANEL CEILING
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT
SH SHINGLES / SINGLE HUNG
SIM SIMILAR
SPC SUSPENDED PLASTER CEILING
SPEC SPECIFICATION
SQ SQUARE
STD STANDARD
STOR STORAGE
STR STRAIGHT STRIKE / STRINGERS
SUSP SUSPENDED
T&B TOP AND BOTTOM
TEL TELEPHONE
THRES THRESHOLD
THRU THROUGH
TOS TOP OF SLAB / STEEL
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLT
VAR VARIATION
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VENT VENTILATION / VENTILATOR
VERT VERTICAL
VEST VESTIBULE
VS VENT STACK
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WASTE / WATT / WEST / WIDE
W/ WITH
W/O WITHOUT
WC WATER CLOSET / WALL COVERING
WD WOOD
WH WATER HEATER
WP WATERPROOFING / WEATHERPROOF / WORKING
POINT
WSCT WAINSCOT
WT WEIGHT
WWF WELDED WIRE FABRIC
XRMR TRANSFORMER
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
1 2 3 4 5 6 7 8 9 10 11
A
B
C
D
CONCRETE PROJECTION BELOW
STAIR TOWER ROOF
ELEVATOR ROOF
CANOPY ROOF
EXISTING TO REMAIN
(TYP)
'-8
'-4
'-0
164'-8" ±
6' -8
9'-8" ± 18'-0" ± 19'-2" ±
'-0
6'-4" ±
'-0
7' -0
11'-4" ±
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
S O
C E
A N
A
V
IR
G
IN
IA
B
E A
C H
V
A
AS NOTED
/2
/2
:5 :3
A
M
C R e v it L o c a l F ile s \D
N
-1
-A -R jo h a n
.s ta d le r.
rv t
AD101
R E
P
LA
C E
R O
O F
M E
M B
R A
N E
R O
O F
P
LA
N
D E
M O
LI
T
IO
N
SDM
12940799
AA JS
1/27/2026
TONY PESSIG, RBH
B U
IL
D
IN
G
SDM/AA
1819725
V
IR
G
IN
IA
B
E A
C H
, V
IR
G
IN
IA
N
A S
O C
E A
N A
, D A
M N
E C
K A
N N
E X
HSDC
SDM
N/A
R O
IC
C
O C
E A
N A
A D
SCALE: 1/8" = 1'-0"
C1
ROOF PLAN - DEMOLITION
PLAN
NORTH
1/8" = 1' - 0" 0 5' 10' 15' 30'
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
KEYNOTES#
1 REMOVE EXISTING SBS ROOFING SYSTEM TO CONCRETE DECK.
2 REMOVE AND SALVAGE EXISTING MECHANICAL EQUIPMENT TO
FACILITATE ROOFING. DEMOLISH ALL EXISTING MECHANICAL CURBS.
3 REMOVE EXISTING METAL COPING.
4 DEMOLISH ALL EXISTING ROOF PADS.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
1 2 3 4 5 6 7 8 9 10 11
A
B
C
D
D1
AE501
D3
AE501
C1
AE501
C1
AE501
- - - - - - - - - - - - - - - - - - - - - - - - - - - - TYP
TYP
TYP
C4
AE501
B1
AE501
- - - - - - - - - - - - - - - - - - - - - - - - - - - - TYP
B2
AE501
- - - - - - - - - - - - - - - - - - - - - - - - - - - - TYP
B3
AE501
B4
AE501
A2
AE501
A3
AE501
C2
AE501
TYP
'-8
'-4
'-0
164'-8" ±
6' -8
9'-8" ± 18'-0" ± 19'-2" ±
'-0
6'-4" ±
'-0
7' -0
4C3
AE501
(TYP)
(TYP)
6 (TYP)
11'-4" ±
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
S O
C E
A N
A
V
IR
G
IN
IA
B
E A
C H
V
A
AS NOTED
/2
/2
:5 :3
A
M
C R e v it L o c a l F ile s \D
N
-1
-A -R jo h a n
.s ta d le r.
rv t
AE101
R E
P
LA
C E
R O
O F
M E
M B
R A
N E
R O
O F
P
LA
N
SDM
12940800
AA JS
1/27/2026
TONY PESSIG, RBH
B U
IL
D
IN
G
SDM/AA
1819725
V
IR
G
IN
IA
B
E A
C H
, V
IR
G
IN
IA
N
A S
O C
E A
N A
, D A
M N
E C
K A
N N
E X
HSDC
SDM
N/A
R O
IC
C
O C
E A
N A
A E
PLAN
NORTH
1/8" = 1' - 0" 0 5' 10' 15' 30'
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
KEYNOTES#
SCALE: 1/8" = 1'-0"
C1
ROOF PLAN
1 PROVIDE SBS ROOFING ON EXISTING CONCRETE DECK.
2 PROVIDE ROOF CURB AT ALL MECHANICAL EQUIPMENT LOCATIONS,
TYPICAL. REINSTALL SALVAGED MECHANICAL EQUIPMENT.
3 PROVIDE METAL COPING, TYPICAL.
4 PROVIDE ROOF PADS, TYPICAL.
5 PROVIDE GAS PIPE TO MECHANICAL EQUIPMENT.
6 ROOF DRAIN.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
1'-3 3/4"
9 1/2"
METAL STOP
TREATED WOOD BLOCKING
MEMBRANE FLASHING
2-PLY MODIFIED BITUMEN
ROOF MEMBRANE
TAPERED INSULATION
VAPOR PERMEABLE AIR BARRIER
EXISTING CONCRETE DECK
EXISTING DRAIN PAN
EXISTING RAIN LEADER
PRE-FINISHED ALUMINUM COPING
WITH CONTINUOUS CLEAT (25 GA)
1/2"⌀ ANCHOR BOLTS, COUNTER-SINK
AT 2'-0" O.C.
2"x8" TREATED WOOD BLOCKING
2-PLY MODIFIED BITUMEN
ROOF MEMBRANE
RIGID INSULATION
METAL FACIA
TREATED WOOD
BLOCKING, TYP.
EXISTING CONCRETE
ROOF AT STAIRWAY
VAPOR PERMEABLE
AIR BARRIER
SEALANT AROUND ALL OPENINGS
TERMINATION FLASHING
SCUPPER SLEEVE
2-PLY MODIFIED BITUMEN ROOF
MEMBRANE BASE FLASHING
EXTENDS INTO SCUPPER OPENING
GRAVEL STOP
EXPANSION ANCHOR
6"
EXISTING MECHANICAL EQUIPMENT
ON CURB
CONTINUOUS INTEGRAL METAL
COUNTER FLASHING
TREATED WOOD NAILER
CURB
2-PLY MODIFIED BITUMEN ROOF
MEMBRANE
RIGID INSULATION (R-20)
EXISTING CONCRETE DECK
VAPOR PERMEABLE AIR BARRIER
EXISTING VENT STACK
PIPE (SIZE VARIES)
SET FLANGES
IN MASTIC
LEAD FLASHING, ROLL INTO
PIPE MIN. 1" DIA
SEALANT
2-PLY MODIFIED BITUMEN
ROOF MEMBRANE
2-PLY MODIFIED BITUMEN
MEMBRANE FLASHING
6"
RIGID INSULATION
EXISTING CONCRETE DECK
CONT. TREATED WOOD
BLOCKING
VAPOR PERMEABLE AIR BARRIER
EXISTING MECHANICAL UNIT
LAP FLASHING OVER TOP
AND SIDES OF WOOD NAILER
FASTEN W/ NEOPRENE
WASHERS @ 12" O.C.
BASE FLASING OVER SBS
4" CANT SET IN BITUMEN
OR ROOF CEMENT
2-PLY MODIFIED BITUMEN
ROOF MEMBRANE
RIGID INSULATION
(R-20)
EXISTING CONCRETE
DECK
4" .1"
5 1/2"
CONT. NEOPRENE PAD
2x6 TREATED WOOD NAILER
METAL CAP W/ CONT. METAL
COUNTER FLASHING
RIGID INSULATION SET IN
BITUMEN OR CEMENT
PRE-MANUFACTURED METAL
EQUIPMENT SUPPORT RAIL
CONT. TREATED WOOD BLOCKING AND
PLYWOOD TO MATCH ADJACENT
INSULATION THICKNESS, SECURE TO
EXISTING ROOF DECK W/ TOGGLE BOLTS
@ 12" O.C., TYP. EACH SIDE
1' -0
"5 1/2"
VAPOR PERMEABLE
AIR BARRIER
1' -6
M
IN
MIN. OPENING
10" SQUARE
POWER & REFRIGERANT LINES
METAL COVER
METAL HOOD
SEALANT AROUND PIPE PENETRATIONS
CONT. PAD & ADHESIVE STRIP
METAL BASE
FASTENER WITH WASHER
METAL COUNTER FLASHING
4" CANT SET IN BITUMEN OR ROOF
CEMENT
2-PLY MODIFIED BITUMEN ROOF
MEMBRANE
CUT EDGE SEALANT
RIGID INSULATION (R-20)
EXISTING CONCRETE DECK
TREATED 2x8 CONT. WOOD
BLOCKING
TREATED 2x12 CONT. WOOD CURB
VAPOR PERMEABLE AIR BARRIER
PRE-FINISHED ALUMINUM COPING
EXISTING CONCRETE PARAPET
FLASHING
4" CANT SET IN BITUMEN OR
ROOF CEMENT
2-PLY MODIFIED BITUMEN
ROOF MEMBRANE
TAPERED INSULATION
RIGID INSULATION
EXISTING SUBSTRATE
TREATED WOOD BLOCKING, TYP.
V A
R
IE
S
AE501
D2
VAPOR PERMEABLE AIR BARRIER
V A
R
IE
S 6"
PRE-FINISHED ALUMINUM COPING
EXISTING CONCRETE PARAPET
FLASHING
PRE-FINISHED ALUMINUM SCUPPER
2-PLY MODIFIED BITUMEN
ROOF MEMBRANE
TAPERED INSULATION
RIGID INSULATION
EXISTING SUBSTRATE
TREATED WOOD BLOCKING, TYP.
AE501
D4
VAPOR PERMEABLE AIR BARRIER
PRE-FINISHED ALUMINUM COPING
4" CANT SET IN BITUMEN OR
ROOF CEMENT
2-PLY MODIFIED BITUMEN
ROOF MEMBRANE
TAPERED INSULATION
RIGID INSULATION
TREATED WOOD BLOCKING, TYP.
EXISTING STEEL BEAM
EXISITNG STEEL DECK
VAPOR PERMEABLE AIR BARRIER
2-PLY MODIFIED BITUMEN ROOF
MEMBRANE
3-2x4 TREATED WOOD BLOCKING
PRE-FINISHED ALUMINUM FLASHING
TAPERED INSULATION
RIGID INSULATION
TREATED WOOD BLOCKING, TYP.
EXISITNG SUBSTRATE
2-PLY MODIFIED BITUMEN ROOF
MEMBRANE
EXISTING CONCRETE PARAPET
FLASHING
TAPERED INSULATION
EXISTING STEEL BEAM
EXISITNG STEEL DECK
VAPOR PERMEABLE
AIR BARRIER
VAPOR PERMEABLE AIR BARRIER
4" CANT SET IN BITUMEN
OR ROOF CEMENT
2-PLY MODIFIED BITUMEN
ROOF MEMBRANE
RIGID INSULATION
EXISTING CONCRETE DECK
TREATED WOOD BLOCKING
EXISTING CONCRETE WALL
ELASTOMERIC COATING
TERMINATION FLASHING
VAPOR PERMEABLE
AIR BARRIER
4" CANT SET IN BITUMEN OR ROOF CEMENT
2-PLY MODIFIED BITUMEN
ROOF MEMBRANE
RIGID INSULATION
EXISTING CONCRETE OVERHANG
EXISTING 14"x8", CONTINUOUS
STEEL BENT PLATE, 14 GA
2"x12" WITH 2"x4" TREATED WOOD BLOCKING, CONTINUOUS
.040 ALUMINUM CLIP, ANCHOR TO WOOD BLOCKING
.040 ALUMINUM REGLET ANCHOR INTO EXISTING SLOT
WITH LEAD WEDGES, PROVIDE CONTINUOUS SEALANT
PROVIDE WEDGES, BACKER ROD
AND SEALANT
ELASTOMERIC COATING
EXISTING CMU WALL
V A
R
IE
S
1' -0
VAPOR PERMEABLE AIR BARRIER
NOTE: PROVIDE ENGINEERED, PREFABRICATED ROOFTOP PIPING SUPPORT SYSTEM DESIGNED FOR INSTALLATION WITHOUT ROOF PENETRATIONS, FLASHING OR DAMAGE TO ROOF SYSTEM COMPONENTS, EATON DURA-BLOK OR APPROVED EQUAL. SELECT & INSTALL ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
NOTE: ALL HARDWARE TO BE STAINLESS OR GALVANIZED STEEL.
GAS PIPE
RECYCLED RUBBER BASE
GALVANIZED
PIPE STRAP
ROOF
GALVANIZED CHANNEL
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
S O
C E
A N
A
V
IR
G
IN
IA
B
E A
C H
V
A
AS NOTED
/2
/2
:5 :3
A
M
C R e v it L o c a l F ile s \D
N
-1
-A -R jo h a n
.s ta d le r.
rv t
AE501
R E
P
LA
C E
R O
O F
M E
M B
R A
N E
TY
P
IC
A
L R
O O
F D
E
TA
IL
S
SDM
12940801
AA JS
1/27/2026
TONY PESSIG, RBH
B U
IL
D
IN
G
SDM/AA
1819725
V
IR
G
IN
IA
B
E A
C H
, V
IR
G
IN
IA
N
A S
O C
E A
N A
, D A
M N
E C
K A
N N
E X
HSDC
SDM
N/A
R O
IC
C
O C
E A
N A
A E
SCALE: 3/4" = 1'-0"
C1
AE101 D1
DETAIL
SCALE: 3/4" = 1'-0"
B1
AE501 D2
DETAIL
SCALE: 3/4" = 1'-0"
C1
AE101 D3
DETAIL
SCALE: 1 1/2" = 1'-0"
B2
AE501 D4
DETAIL
SCALE: 3/4" = 1'-0"
C1
AE101 C1
DETAIL
SCALE: 3/4" = 1'-0"
C2
TYPICAL DETAIL
SCALE: 3/4" = 1'-0"
C1
AE101 C3
DETAIL
SCALE: 3/4" = 1'-0"
C1
AE101 C4
DETAIL
SCALE: 3/4" = 1'-0"
C1
AE101 B1
DETAIL
SCALE: 3/4" = 1'-0"
C1
AE101 B2
DETAIL
SCALE: 3/4" = 1'-0"
C1
AE101 B3
DETAIL
SCALE: 3/4" = 1'-0"
C1
AE101 B4
DETAIL
SCALE: 3/4" = 1'-0"
C1
AE101 A2
DETAIL
SCALE: 3/4" = 1'-0"
C1
AE101 A3
DETAIL 1 1/2" = 1' - 0"
0 6" 1' 2'3" 9"
3/4" = 1' - 0" 0 1' 5'6" 2' 3' 4'
GRAPHIC SCALE(S)
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SCALE: NOT TO SCALE
A4
TYPICAL ROOFTOP
GAS PIPE SUPPORT DETAIL
File details come from the government source that posted it. Updated .