OP-2 Tower_Design_Drawings1.pdf
PDF 6 MB Posted
- Attached to
- OP-2 Observation Tower Repairs
- Solicitation number
- N4008525R9024
About this file
The provided document contains detailed engineering and design drawings for a multi-level mechanical, electrical, and lightning protection system for a building project. The technical drawings include multiple floor plans, exterior elevations, mechanical floor plans across levels 1-9, electrical floor plans across levels 1-5, lightning protection floor plans across levels 1-10, single line diagrams, panel schedules, grounding details, and electrical connection specifications. The drawings are prepared by Parsons for a project located in North Carolina, with document dates indicating preparation in October 2020. The technical drawings provide comprehensive architectural and engineering details for infrastructure systems, including mechanical equipment placement, electrical circuitry, lightning protection strategies, conduit and floor penetration details, and mounting specifications for various electrical and mechanical components.
The documents include extensive technical annotations, keynotes, legends, abbreviations, and general notes that provide specific guidance on installation, mounting, grounding, and electrical system configurations. The drawings cover multiple technical domains including mechanical equipment placement, electrical panel layouts, lightning protection strategies, grounding methods, and structural integration details. Specific technical elements include mechanical floor plans showing equipment locations, electrical floor plans detailing circuit layouts and panel placements, lightning protection plans showing conductor and terminal placements, and detailed technical drawings for grounding, conduit penetrations, and equipment mounting across multiple building levels.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OUTLETS CKT CKT OUTLETS
LTS REC MISC POLE AMP LCL A B NO A B NO A B LCL POLE AMP LTS REC MISC
6 1 20 588 588 1 2 240 240 1 20 5
8 1 20 144 144 3 4 - 1 20
14 1 20 672 672 5 6 300 300 1 20 1
1 1 20 500 7 8 540 1 20 3 RECEPTACLES
7 1 20 925 925 9 10 336 336 1 20 6 LIGHTS
1 20 11 12 - 1 20
1 20 13 14 8961 1433 2 100 1
1 20 15 16 8833 445 - -
1 20 17 18 1 20
1 20 19 20 1 20
- - 21 22 - -
- - 23 24 - -
- - 25 26 - -
- - 27 28 - -
- - 29 30 - -
2329 2185 644 9837 9373 2754
L.C.L. LOAD=
L.C.L. LOAD X 1.25=
OTHER LOAD=
SPARE
SPACE
SPACE
SPARE
SPACE
AMPS:
TOTAL PHASE A=
16956
TOTAL CONN LOAD= 22039 23310TOTAL LOAD=
10017
SUBTOTALS
TOTAL PHASE B=
12022
VOLTAGE: 120/240 VAC, 1PH, 3W, 60HZ
EMERGENCY LIGHTS AND EXIT SIGNS
LIGHTS
LIGHTS
DESCRIPTION
LIGHTS
SPACE
SPACE
SPARE
SPACE
SPARE
SPARE
ENCLOSURE: NEMA 3R
SPARE
BREAKERVOLT AMPS
SUB-PANEL "SP"
BUS RATING: 225 A MAIN CIRC. BKR: 150A 2P CB
PANEL SCHEDULE: MAIN DISTRIBUTION PANEL "MDP"
SPACE
SPACE
LOCATION: EXTERIOR
VOLT AMPS
SPARE
MOUNTING: SURFACE
MIN. SYMM. RATING: 10 KAIC
PANEL MDP
BREAKER
SPACE
SPACE
COMMUNICATION PANEL
LIGHTS
SPARE
SPARE
DESCRIPTION
RED RANGE HOT LIGHT
OUTLETS CKT CKT OUTLETS
LTS REC MISC POLE AMP LCL A B NO A B NO A B LCL POLE AMP LTS REC MISC
11 1 20 1141 1141 1 2 540 1 20 3
5 1 20 105 105 3 4 360 - - 2
8 1 20 292 292 5 6 540 1 20 3
1 1 20 500 7 8 1080 1 20 3
1 20 - 9 10 6448 2 70 1
9 1 20 340 340 11 12 6448 - -
1 20 - 13 14 - 1 20
1 20 - 15 16 - 1 20
1 20 - 17 18 - 1 20
- - - 19 20 - - -
1878 1433 945 7528 7888
L.C.L. LOAD=
L.C.L. LOAD X 1.25=
OTHER LOAD=
SUB-PANEL "SP"
BREAKER
COMMUNICATION PANEL
SPARE
LIGHTS
SPARE
DESCRIPTION
ENCLOSURE: NEMA 3R
RECEPTACLES
BREAKERVOLT AMPS
SPARE
RECEPTACLES
SPARE
BUS RATING: 100 A MAIN CIRC. BKR: 100A 2P CB
RECEPTACLES - WORKSTATION
AC-1
VOLT AMPS
MIN. SYMM. RATING: 10 KAIC
SPARE
PANEL SCHEDULE: SUB-PANEL "SP"
VOLTAGE: 120/240 VAC, 1PH, 3W, 60HZ
EMERGENCY LIGHTS
LIGHTS
RECEPTACLES
DESCRIPTION
LIGHTS
LOCATION: LEVEL 9 - OPERATOR'S ROOMMOUNTING: SURFACE
SUBTOTALS
TOTAL PHASE B=
TOTAL CONN LOAD= 17794 TOTAL LOAD= 18264
TOTAL PHASE A=
15916
AMPS:
SPARE
SPACE
SPARE
SPACE
| G-100 |
| 00-C-100 |
| 00-C-101 |
| 00-C-103 |
| 00-C-104 |
| 00-C-105 |
| 00-C-201 |
| 00-C-202 |
| 00-C-501 |
| 00-S-201 |
| 00-M-100 |
| 00-M-101 |
| 00-M-201 |
| 00-M-202 |
| 00-M-301 |
| 00-M-302 |
| 00-E-100 |
| 00-E-201 |
| 00-E-202 |
| 00-E-301 |
| 00-E-302 |
| 00-E-501 |
| 00-E-601 |
| 00-E-602 |
| 00-E-701 |
| 00-E-702 |
File details come from the government source that posted it. Updated .