This document is a technical specification sheet for Schneider Electric's Type VR Medium Voltage Vacuum Circuit Breakers, designed for ANSI/NEMA applications. The circuit breakers are available in voltage ratings from 5-15 kV, with current ratings of 1200, 2000, 3000, and 4000 A, and short circuit interrupting ratings from 25-63 kA. Key features include a 3-cycle interrupting rating, spring-charged stored-energy operating mechanism, UL listing, and hermetically sealed vacuum interrupters that provide a longer life cycle. The breakers are compatible with Masterclad medium voltage switchgear and can be used in various applications, including generator circuit breaker scenarios with specific X/R ratio considerations. The document provides detailed technical specifications, dimensional drawings, weight information, and performance characteristics for different voltage and current configurations, including specialized generator circuit breaker models that meet IEEE and IEC standards for short circuit and out-of-phase switching applications.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Type VR Medium Voltage Vacuum Circuit Breaker 6055DB1401, 06/2022 Replaces 6055DB1401 Rev. 01, 03/2014
ANSI/NEMA Vacuum Circuit Breakers 5-15 kV;
1200, 2000, 3000 and 4000 A; 25-63 kA Retain for future use.
© 2014-2022 Schneider Electric All Rights Reserved
EN
G
LI
SH
Square D™ brand, Type VR medium voltage circuit breakers manufactured by Schneider Electric have been on the market for more than 30 years. Their quality, reliability, and performance are widely recognized across North America, as well as everywhere ANSI applications are required worldwide.
Standard features include:
• 3-cycle interrupting rating
• ANSI rated per C37.06, C37.09, C37.54
• UL Listed
• Spring-charged, stored-energy operating mechanism
• Permanently mounted manual charging handle
• Two “a” and “b” spare contacts
• Separate wheels that roll directly to floor level from lower cell for maintenance
The circuit breaker contacts are located where indicators are readily accessible.
The front accessible mechanism allows for ease of maintenance. The circuit breaker operates at a high speed and, because of the hermetically sealed vacuum interrupters, has a longer life cycle.
With their wide range of ratings and benefits, the Type VR circuit breakers are offered not only in Masterclad™ medium voltage switchgear, but also in semi-assembled switchgear and OEM components.
Associated Drawings
• Circuit breaker schematic diagram—drawing no. 46040-651
• Circuit breaker wiring diagram—drawing no. 46040-652
Instruction Bulletins
• Document no. 6055-33
• Document no. 6055-31
NOTE: Refer to the instruction bulletin for important, detailed information regarding handling, storage, installation, operation, and maintenance.
ANSI/NEMA Vacuum Circuit Breakers 5-15 kV; 1200, 2000, 3000 and 4000 A; 25-63 kA
2 6055DB1401© 2014-2022 Schneider Electric All Rights Reserved
EN
G
LISH
Dimensions The following diagram shows typical dimensions for Type VR medium voltage vacuum circuit breakers. A 1200/2000 A circuit breaker is pictured.
Weights
0.50 (ref.) 29.6
(ref.)
28.93 (ref.)
Dimension taken with cage pushed against copper contact.
29.04 (ref.)
0.66 (typ.)
0.62 (typ.)
9.51 (ref.)
11.15 ± 0.15
8.30 ± 0.15
12.00 ± 0.10
24.50 ± 0.10
24.80 ± 0.10
23.47 ± 0.10
4.80 ± 0.1028.75
(ref.) 0.42 (ref.)
0.30 (ref.)
22.30 ± 0.05
8.30 ± 0.05
1.88 min.
travel
0.70
14.80 ± 0.70
Front Side Rear
15 kV Circuit Breaker Rating Weight (lbs.)
1200 A, 25/40 kA 380
2000 A, 25/40 kA 430
3000 A, 25/40 kA 700
1200 A, 50 kA 450
2000 A, 50 kA 500
3000/4000 A, 50 kA 700
1200/2000/3000/4000 A, 63kA 800
36055DB1401 © 2014-2022 Schneider Electric All Rights Reserved
EN
G
LI
SH
5–15 kV Ratings
Control Voltage Operating Range (ANSI 37.06, Table 9)
Nominal Voltage k
Factor
MVA
Rating
Rated Continuous
Current
Insulation Level Rated Withstand Interrupting Ratings
Mechanical Endurance Catalog
Number Power
Frequency Impulse
1.2x50 µs System
Interrupting Close and
Latch Short Time
Short Time Duration
Interrupting Time kV rms A rms kV rms kV peak kA rms kA peak kA rms Seconds Cycles Operations
4.76
1 250 1200 19 60 40 104 40 2 3 10,000 VR-05025-12
1 250 2000 19 60 40 104 40 2 3 10,000 VR-05025-20
1 250 3000 19 60 40 104 40 2 3 5,000 VR-05025-30
1 350 1200 19 60 50 130 50 2 3 5,000 VR-05035-12
1 350 2000 19 60 50 130 50 2 3 5,000 VR-05035-20
1 350 3000 19 60 50 130 50 2 3 5,000 VR-05035-30
1 350 4000● 19 60 50 130 50 2 3 5000 VR-05035-40
1 500 1200 19 60 63 164 63 2 3 2,000 VR-05050-12
1 500 2000 19 60 63 164 63 2 3 2,000 VR-05050-20
1 500 3000 19 60 63 164 63 2 3 2,000 VR-05050-30
1 500 4000● 19 60 63 164 63 2 3 2,000 VR-05050-40
8.25
1 500 1200 36 60 40 104 40 2 3 10,000 VR-08050-12
1 500 2000 36 95 40 104 40 2 3 10,000 VR-08050-20
1 500 3000 36 95 40 104 40 2 3 5,000 VR-08050-30
1 500 1200 36 95 50 130 50 2 3 5,000 VR-08050-12
1 500 2000 36 95 50 130 50 2 3 5,000 VR-08050-20
1 500 3000 36 95 50 130 50 2 3 5,000 VR-08050-30
1 500 4000● 36 95 50 130 50 2 3 5,000 VR-08050-40
1 500 1200 36 95 25 65 25 2 3 10,000 VR-15050-12
1 500 2000 36 95 25 65 25 2 3 10,000 VR-15050-20
1 500 3000 36 95 25 65 25 2 3 5,000 VR-15050-30
1 750 1200 36 95 40 104 40 2 3 10,000 VR-15075-12
1 750 2000 36 95 40 104 40 2 3 10,000 VR-15075-20
1 750 3000 36 95 40 104 40 2 3 5,000 VR-15075-30
1 1000 1200 36 95 50 130 50 2 3 5,000 VR-15100-12
1 1000 2000 36 95 50 130 50 2 3 5,000 VR-15100-20
1 1000 3000 36 95 50 130 50 2 3 5,000 VR-15100-30
1 1500 1200 36 95 63 164 63 2 3 2,000 VR-15150-12
1 1500 2000 36 95 63 164 63 2 3 2,000 VR-15150-20
1 1500 3000 36 95 63 164 63 2 3 2,000 VR-15150-30
▲ This rating is for reference only.
■ Number of no-load mechanical operations.
● 4000 A Circuit Breakers may only be used in Schneider Electric 4000A Masterclad sections with powered fan cooling systems.
Rated Voltage Closing Voltage Range Tripping Voltage Range
24 Vdc 19–28 Vdc 14–28 Vdc
48 Vdc 38–56 Vdc 28–56 Vdc
125 Vdc 100–140 Vdc 70–140 Vdc
250 Vdc 200–280 Vdc 140–280 Vdc
120 Vac 104–127 Vac 104–127 Vac
240 Vac 208–254 Vac 208–254 Vac
4 6055DB1401© 2014-2022 Schneider Electric All Rights Reserved
EN
G
LISH
Control Device Rating Standard
Circuit Breaker-Mounted Auxiliary Contact Ratings Continuous Rating: 20 A, up to 600 V
Circuit Breaker Rating
Control Description
Rated Voltage
Current At Rated Voltage (A) Time Duration Of
Current Flow
Burden (VA) ▲ DC Resistance
(Ohms)Inrush Run Inrush Run
All circuit breakers
Charging motor
24 Vdc ■ 48 Vdc 125 Vdc 250 Vdc 120 Vac 240 Vac
(max.)
2.5 (max.) 5–10 sec. max.
Not applicable
Anti-pump relay
24 Vdc ■ 48 Vdc 125 Vdc 250 Vdc 120 Vac 240 Vac
0.050 0.025 0.009 0.004 0.016 0.008
Not applicable
1.2 1.2 1.2 1.2 2.0 2.0
Not applicable
15 kV, 25 kA, 500 MVA, 1200 A and 2000 A
Closing solenoid
24 Vdc ■ 48 Vdc 125 Vdc 250 Vdc 120 Vac 240 Vac
9.0 1.8 1.8 3.7 6.8 3.5
20–25 msec
1.4 27.5 68.00 68.00 17.60 68.00
Trip solenoid
24 Vdc ■ 48 Vdc 125 Vdc 250 Vdc 120 Vac 240 Vac
9.0 7.1
10.8 5.6
17.8 13.6
15 msec
1.40 6.75 11.60 44.50 6.75 17.60
All other 15 kV circuit breakers
Closing solenoid
24 Vdc ■ 48 Vdc 125 Vdc 250 Vdc 120 Vac 240 Vac
3.6 1.8 0.7 1.4 6.8 3.5
20–25 msec
86.4 86.4 87.5
350.0 816.0 840.0
6.75 27.5
184.00 184.00 17.60 68.00
Trip solenoid
24 Vdc ■ 48 Vdc 125 Vdc 250 Vdc 120 Vac 240 Vac
3.6 1.8 0.7 1.4 4.6 2.1
15 msec
86.4 86.4 87.5
350.0 552.0 504.0
6.75 27.50 184.00 184.00 26.00 115.00
▲ 0.8 PF
■ Customer shall provide a power source without voltage drop at the device.
Interruption Rating
Voltage Non-Inductive Inductive
24 Vdc 18 A 10 A■ 48 Vdc 18 A 10 A■ 125 Vdc 5 A 3 A■ 250 Vdc 2 A 1 A■ 120 Vac 20 A 20 A▲
240 Vac 18 A 18 A▲
▲ 0.8 PF
■ 0.08 H
56055DB1401 © 2014-2022 Schneider Electric All Rights Reserved
EN
G
LI
SH
Capacitor Switching Duty Applies to single bank and back-to-back switching with de-rating factors applied per C37.012.
Catalog Number
Rated Continuous
Current (A)
Rated Short Circuit Current
(kA)
Rated Capacitor Switching
Current - C1 (A)
Test Certificate
5 kV Circuit Breakers
VR-05025-12 1200 40 — TV5D32
VR-05025-20 2000 40 — TV5D32
VR-05025-30 3000 40 — TV5D33
VR-05035-12 1200 50 1260 TV5D42
VR-05035-20 2000 50 1260 TV5D42
VR-05035-30 3000 50 — TV5D43
VR-05050-12 1200 63 660 TV5DC2
VR-05050-20 2000 63 660 TV5DC2
VR-05050-30 3000 63 660 TV5DC3
VR-05050-40 4000 63 660 TV5DC4
15 kV Circuit Breakers
VR-15050-12 1200 25 660 TV5D61
VR-15050-20 2000 25 — TV5D62
VR-15050-30 3000 25 — TV5D63
VR-15075-12 1200 40 — TV5D72
VR-15075-20 2000 40 — TV5D72
VR-15075-30 3000 40 — TV5D73
VR-15100-12 1200 50 1260 TV5D82
VR-15100-20 2000 50 1260 TV5D82
VR-15100-30 3000 50 — TV5D83
VR-15150-12 1200 63 660 TV5DD2
VR-15150-20 2000 63 660 TV5DD2
VR-15150-30 3000 63 660 TV5DD3
VR-15150-40 4000 63 660 TV5DD4
Schneider Electric USA, Inc.
800 Federal Street Andover, MA 01810 USA 888-778-2733 www.se.com/us
ANSI/NEMA Vacuum Circuit Breakers 5-15 kV; 1200, 2000, 3000 and 4000 A; 25-63 kA 6055DB1401
Electrical equipment must be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
Schneider Electric, Masterclad™ and Square D are trademarks and the property of Schneider Electric SE, its subsidiaries, and affiliated companies. All other trademarks are the property of their respective owners.
© 2014-2022 Schneider Electric All Rights Reserved
EN
G
LISH
Generator Circuit Breakers When selecting a circuit breaker for a generator application, there are three different scenarios to consider.
For generator applications in which X/R < 17, all Schneider Electric VR circuit breakers can be used.
For generator applications in which 17 < X/R < 50, Schneider Electric VR 63kA generator circuit breakers can be used for system source faults. These circuit breakers have met the requirements of IEEE C37.013A.
63kA Generator Circuit Breakers
For Class M2 G2 generator applications as defined by IEC/IEEE 62271-37- 013:2015, the circuit breakers listed in the table below have successfully completed testing for:
• System source short circuit for generators rated to 100 MVA
• Generator source short circuit for generators rated to 100 MVA
• Transformers rated to 100 MVA
• Out of phase switching
Class M2 G2 Generator Circuit Breakers
Technical Publications You can download this technical publication and other technical information from our website at www.se.com.
Catalog Number
Rated Voltage (kV)
Continuous Current
(A) MVA rating Power Freq kV Impulse kV
Peak Mech
Endurance System Interrupt Current kA rms
VR-1515G-12 15 1200 1500 36 95 2000 63
VR-1515G-20 15 2000 1500 36 95 2000 63
VR-1515G-30 15 3000 1500 36 95 2000 63
All circuit breakers: K factor = 1.0, Interrupting Time - 3 cycles
Catalog Number
Rated Voltage
(kV)
Continuous Current
(A)
MVA
Rating
Power Freq kV
Impulse kV Peak
System Source Out of Phase SC Breaking Current
(kA Sym)
Generator Source Standard Operating Sequence
SC
Breaking Current
(kA Sym)
DC
Offset
SC
Breaking Current
(kA Sym)
DC
Offset
VR-0502G-12 5 1200 250 19 60 31.5 75 21 21 130 CO-30min-CO
VR-0502G-20 5 2000 250 19 60 31.5 75 21 21 130 CO-30min-CO
VR-1507G-12 15 1200 750 36 95 31.5 75 21 21 130 CO-30min-CO
VR-1507G-20 15 2000 750 36 95 31.5 75 21 21 130 CO-30min-CO
All circuit breakers: K factor = 1.0, Interrupting Time - 3 cycles, Mechanical Endurance = 5000 cycles www.se.com/us