This document is a product data sheet for the SEL-2440 Discrete Programmable Automation Controller (DPAC) manufactured by Schweitzer Engineering Laboratories, Inc. The device is a robust control and monitoring system designed for harsh physical and electrical environments, featuring 32 digital inputs, 16 outputs, and 4 communication ports as standard configuration. Key features include microsecond-level event time-stamping, synchronization with multiple time protocols (IRIG-B, PTP, SNTP, DNP), and support for communication protocols like DNP3, Modbus, and IEC 61850.
The DPAC offers flexible configuration through DIP switches or ACSELERATOR QuickSet software, with capabilities to replace traditional latching relays, external timers, and counters. It provides advanced automation functions like sequential event recording, programmable logic, and remote bit control. The device is designed for industrial applications, with specifications including an operating temperature range of -40° to +85°C, UL listing, CE marking, and compliance with various international electromagnetic compatibility and environmental testing standards. It supports multiple mounting options (rack, panel, surface) and can be powered by 24-250 VDC or 110-230 VAC.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Schweitzer Engineering Laboratories, Inc. SEL-2440 DPAC Data Sheet
SEL-2440 Discrete Programmable Automation Controller
Complete System for Control and Monitoring
Major Features and Benefits Fast and Powerful I/O
➤ Use an exceptional and compact combination of inputs, outputs, and communications.
➤ Analyze system events with inputs and other events timed to the microsecond.
➤ Synchronize control with outputs that are synchronized to IRIG-B, PTP, SNTP, or DNP time.
➤ Perform actions quickly with a processing interval of 2 ms.
➤ Program new features with logic, latches, timers, counters, edge-triggers, and math functions.
➤ Ensure safe operation by using an input with logic programmed for local/remote control.
Convenient Maintenance and Support ➤ LEDs provide status for every I/O point and communications port.
➤ Removable terminal blocks make installation and replacement quick and efficient.
➤ Positive retention connectors ensure that connections are not lost due to sagging cables.
➤ Front-panel management port makes device management convenient.
Flexible Communications and Integration ➤ Communicate with DNP3, Modbus®, and IEC
61850 protocols over Ethernet and serial connections. Direct and select-before-operate (SBO) outputs are supported.
➤ Automate systems with flexible communication options that provide easy integration with SCADA.
➤ Configure easily with preprogrammed register or object maps and front-panel control (DIP) switches.
➤ Alternatively, configure with ACSELERATOR QuickSet® SEL-5030 Software.
SEL Quality, Standards, and Global Support ➤ Designed and tested for harsh physical and electrical environments.
➤ Designed and tested to operate with dc grounded batteries and capacitive loads, and to trip breakers and interrupt inductive loads.
➤ Superior specification compliance, high reliability, low price, and worldwide, ten-year warranty.
Rack Panel Surface
32 Inputs 16 Outputs 4 Ports (Standard)
RTAC
DPAC
PAC
Serial or Ethernet Communications
SEL-2440 DPAC Data Sheet Schweitzer Engineering Laboratories, Inc.
Product Summary The SEL-2440 Discrete Programmable Automation Controller (DPAC) withstands harsh physical and electrical environments and is built and tested to meet mission-critical IEEE and IEC protective relay standards. Apply the DPAC to satisfy stand-alone or distributed input, output, and communications needs. Figure 1 shows the DPAC functionality.
Functional Diagram
Figure 1 Functional Diagram
Configuration ➤ Easy Mode. Set address and communications parameters with DIP switches.
➤ Flexible Mode. Access additional flexibility using
QuickSet software, shown in the following figure.
Figure 2 QuickSet Launchpad
Inputs/Outputs DPAC devices can be ordered with different I/O and input voltage ratings as shown in the following tables.
I/O Quantity Options
I/O Input Voltage Options
Communication and Time Many communications ports and protocols are provided.
Figure 3 Rear-Panel Communications and IRIG-B Ports
Protocol Processing
Security
Programmable Automation
Engine (2 ms processing)
Sequential Events Recorder
Serial Ethernet
Switch
MAC
Ethernet
IRIG-B
OUT
IRIG-B
IN
In pu t P ro ce ss or (0
.5 m s)
M ic ro se co nd
T im er
O ut pu t R el ay s m s)
32 Discrete Inputs
(typical)
16 Discrete Outputs (typical)
Inputs Outputs
Standard 32 16
Option 1 16 32
Option 2 48 0
Option 3 16 32 (16 Standard and 16 High-Current Interrupting)
Option 4 16 26 (12 Form A, 4 Form C, 10 Fast High-Current Form A)
Option 5 32 10 (10 Fast High-Current Form A)
Digital Input Rating
24 Vac/Vdc 48 Vac/Vdc
110 Vac/Vdc
125 Vac/Vdc 220 Vac/Vdc 250 Vac/Vdc
Port Port Interface
PORT F USB 2.0 physical interface, serial port (e.g., COM1) software interface
PORT 1 Ethernet with switch/failover (copper or fiber)
PORT 2 Serial (EIA-232, EIA-485, or ST fiber)
PORT 3 Serial (EIA-232)
Serial Ethernet
DNP3 Yes Yes
Modbus Yes Yes
IEC 61850 Yes
MIRRORED BITS® Yes
SEL Fast Message Yes
Input/Output Features Inputs (Status and Alarms) Use digital inputs to monitor critical alarms or status points and time-stamp to the microsecond.
Figure 4 Independent and Isolated Inputs
Figure 5 Bussed Inputs
SEL inputs are designed and tested to ensure they operate correctly for dc battery grounds and capacitive discharges.
The bold line in Figure 6 shows how an earth fault completes the battery path through the input, bypassing the output. If the input is rated for 125 Vdc, the 65 Vdc that the fault causes across the input will assert the input.
SEL level-sensitive inputs are designed so that they do not operate for this condition.
The bold line in Figure 7 shows a discharge path from the wiring capacitance through the input when a knife switch is closed. This discharge can cause a temporary assertion of an input. SEL inputs are designed with debounce timers so that they do not operate for this condition.
Figure 6 Secure Against DC Grounds
Figure 7 Secure Against Capacitive Discharges
Outputs (Relays) Outputs are rated for 30 A make and inductive interrupt applications such as trip and close operations and motor control. See the Output specifications for more details.
Figure 8 Independent and Isolated Outputs
Power The POWER terminals on the rear panel must connect to 120–230 Vac or 24–250 Vdc with the proper polarity.
These terminals are isolated from chassis ground. Extra terminals are provided so power can be daisy-chained from DPAC to DPAC.
IRIG-B
A demodulated IRIG-B input and output are provided so this signal can be daisy-chained between DPAC devices.
V B02 B01
IN201
V B04 B03
IN202
V B06 B05
IN203
V B08 B07
IN204
Insensitive to Polarity
V
IN201
IN202
IN203
IN204
Insensitive to Polarity
B02 B01
B04 B03
B06 B05
B08 B07
+62.5 Vdc
125 Vdc
–62.5 Vdc
125 Vdc
+62.5 Vdc
–62.5 Vdc
V
V
V
V
OUT101
OUT102
OUT103
OUT104
A02 A01
A04 A03
A06 A05
A08 A07
Load
Load
Load
Load
Form C Alarm
DC or AC Power Source
Z1
SEL-2440
DPAC
Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9
G
OUT
IN
IRIG
OUT
IN
IRIG
Connectors Removable terminal block connectors make installation and replacement quick and efficient but can result in intermittent or lost connections if positive retention means aren’t provided. The following diagram shows one of the pluggable connectors used on the DPAC and points out the retention screws that ensure connections remain in place.
Conformal Coating The optional conformal coating protects the DPAC printed circuit board from moisture and corrosive elements found in harsh installations. This conformal coating option conforms to Mil-1-46058C Type UR conformal coating requirements.
Communications Ports A rich collection of communications ports and protocols are available with the DPAC as shown in the following figure, which also includes connection examples.
Analyze Sequence–of–Events Record sequence-of-events with the Sequential Events Recorder (SER) function. With this function, you can analyze assertions and deassertions of digital inputs and outputs—as many as 512 state changes to the microsecond for as many as 96 different digital points. The function also captures when the device powers up and a settings change occurs.
Combine SER data from individual SEL-2440 DPAC devices into a system-wide log. Synchronize the system with IRIG-B time code and the report data will align perfectly.
PC
SEL-2440
DPAC
SEL-2725
Ethernet Switch
SEL Device
MIRRORED BITS
SEL-3010
Event Messenger
1B
1A F
SEL-2440
DPAC
PORT 1B
SEL-3530
RTAC
DNP3
Master
IRIG-B
OUT
IRIG-B
IN
Figure 9 Sample SER Report
SEL-2440 Date: 09/23/2008 Time: 12:13:51
DEVICE
Serial No = 000000000000001
FID = SEL-2440-R001-V0-Z001001-D20081010 CID = B12D
# DATE TIME ELEMENT STATE
150 09/23/2008 12:13:41.000000 TOS Asserted 149 09/23/2008 12:13:41.002000 TOS Deasserted 148 09/23/2008 12:13:41.224180 52_1_Closed Asserted 147 09/23/2008 12:13:41.224180 IN215R Asserted 146 09/23/2008 12:13:41.224180 Fan_Running Asserted 145 09/23/2008 12:13:41.224180 IN213R Asserted 144 09/23/2008 12:13:41.224180 IN212R Asserted 143 09/23/2008 12:13:41.224180 IN211R Asserted 142 09/23/2008 12:13:41.224180 IN210R Asserted 141 09/23/2008 12:13:41.224180 IN209R Asserted 140 09/23/2008 12:13:41.224180 IN208R Asserted 139 09/23/2008 12:13:41.224180 IN207R Asserted 138 09/23/2008 12:13:41.224180 IN206R Asserted 137 09/23/2008 12:13:41.224180 IN205R Asserted
SER
Number
Element or Condition
Element State
SER
Date
SER
Time
Report Date
Report Time
Device Identification
Terminal Identification
Figure 10 Combine SER Data From Multiple SEL-2440 DPAC devices for a System-Wide Log and Display
Figure 11 Example SER Collection Architecture
Automation Features Flexible Control Logic and Integration Features Eases Configuration The DPAC does not require special communications software. Use any system that emulates a standard termi-nal system for engineering access to the device.
Simplifies Communications The SEL-2440 is equipped with three independently operated serial ports. Establish communication by con-necting computers, modems, protocol converters, print-ers, an SEL Communications Processor, SCADA serial port, and an RTU for local or remote communication.
Apply an SEL communications processor as the hub of a star network, with point-to-point fiber or copper connec-tion between the hub and the SEL-2440.
Supports Standard Protocols As with most SEL devices, the DPAC comes standard with the communications protocols listed below.
➤ DNP3
➤ Modbus
➤ SEL ASCII
➤ SEL Compressed ASCII ➤ SEL Fast Meter ➤ SEL Fast Operate
➤ SEL Fast SER ➤ SEL Fast Message
➤ SEL MIRRORED BITS
Time Synchronization Protocols The DPAC supports the following protocols for synchronizing your device to master clocks.
➤ Demodulated IRIG-B ➤ Firmware based PTP (IEEE 1588-2008) ➤ SNTP from High Priority or Low Priority servers
➤ DNP3
Simplifies SCADA SEL devices provide proprietary but open, binary “fast” protocols. These protocols are self-describing and are interleaved with ASCII protocols on the same port. Sim-plify configuration, minimize communications wiring, and improve performance between the DPAC and other devices (e.g., communications processors) with these protocols.
Performs Logic and Math Eliminate PLCs with Boolean logic, rising/falling edge triggers, and math (+, -, *, /).
Replaces Traditional Latching Relays Replace as many as 32 traditional latching relays for such functions as “remote control enable” with latches.
Program latch set and latch reset conditions with SELOGIC® control equations. Set or reset the nonvolatile latches using optoisolated inputs, Remote Bits, latches, or any programmable logic condition. The latches retain their state when the device loses power.
Eliminates External Timers Eliminate external timers for custom protection or con-trol schemes with 32 general purpose SELOGIC control equation timers. Each timer has independent time-delay pickup and dropout settings. Program each timer input with any desired element. Assign the timer output to trip logic, transfer trip communications, or other control scheme logic.
Eliminates External Counters Eliminate external counters for custom control schemes with 32 counters, updated every 2 ms processing interval.
Each counter element consists of five inputs (preset value; load preset value, count up, count down, and reset to zero) and three outputs (counter value; count as many as preset reached, count down to zero reached).
Eliminates RTU-to-Device Wiring Eliminate RTU-to-Device wiring with 32 Remote Bits.
Set, clear, or pulse Remote Bits using serial or Ethernet port commands. Program the Remote Bits into your con-trol scheme with SELOGIC control equations. Use Remote Bits for SCADA-type control operations such as trip, close, and settings group selection.
Provides Annunciation
Indicators (LEDs) provide annunciation of I/O status for each input and output. In addition, device status and port activity indicators simplify commissioning and troubleshooting.
Figure 12 Annunciation Indicators
Communications Architectures
Figure 13 Typical Ethernet and EIA-485 Communications Architectures
Figure 14 Typical EIA-232 and Fiber-Optic Communications Architecture
10/100BASE-T Ethernet Port
• Modbus TCP
• DNP3 LAN/WAN
• IEC 61850
(A) Ethernet Communications Architecture
EIA-485
• Modbus RTU
• DNP3 Level 2 Slave
(B) EIA-485 Communications Architecture
RTUs Meters and
Monitors Relays and IEDs
Communications Processor
Modbus, DNP3, SEL Protocols
DNP3
Serial Communications
EIA-232 or Fiber Optic
• Modbus RTU
• DNP3 Level 2 Slave
• SEL ASCII
• SEL Fast Message, Fast SER
• SEL Fast Meter, Fast Operate
Additional Ordering Options The following options can be ordered for any SEL-2440 model (see the SEL-2440 Model Option Table for details):
Diagrams and Dimensions
Figure 15 Rack-Mount Drawing
Figure 16 Panel-Mount Drawing
Figure 17 Surface-Mount Drawings
Figure 18 32 Input, 16 Output Rear-Panel Drawing
Port 2 Physical Interface
EIA-232
EIA-485
ST fiber
Mounting
Rack
Panel
Surface
High-current interrupting outputs are polarity sensitive. This is indicated with a + next to the contact on the overlay to indicate the positive side of the contact.
Figure 19 High-Current Interrupting Option Rear-Panel Drawing
Figure 20 Port 2 EIA-485 and Fiber-Optic Ethernet Option Rear-Panel Drawing
Figure 21 48DI Option Rear-Panel Drawing
Figure 22 16 Input, 16 Standard Output, and 10 Fast High-Current Output Rear-Panel Drawing
Figure 23 32 Input and 10 Fast High-Current Output Rear-Panel Drawing
Specifications i9367a
FRONT6.74
[171.1]
19.00 [482.6]
18.19 [461.9]
3.50 [88.9]
SIDE3.50
[88.9]
RACK-MOUNT CHASSIS
i9180b
FRONT
PANEL-MOUNT CHASSIS
6.23 [158.1]
.51 [13.0]
19.00 [482.6]
3.47 [88.1]
18.31 [465.1]
3.00 [76.2]
6.26 [159.0]
.58 [14.6]
4.90 [124.5]
19.80 [502.9]
3.60 [91.4]
17.63 [447.8]
3.00 [76.2]
18.31 [465.1]
#10-32
STUD
FRONT
TOP TOP
PANEL CUTOUT
Compliance Designed and manufactured under an ISO 9001 certified quality management system
UL Listed to U.S. and Canadian safety standards (File E220228; NRAQ, NRAQ7)
Note: DC output ratings not evaluated by UL61010.
CE Mark
UKCA Mark
RCM Mark
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
General Operating Temperature Range
–40° to +85°C (–40° to +185°F) (not applicable to UL installations. UL rated 40°C)
When Powered by 24 V, the SEL-2440 Supports the Following Conditions:
70°C: Operate 32 outputs and 2.5 W max on +5 V pin (Port 2/3)
Conformal Coated: Derate operating temperature by 10°C.
Operating Environment
Pollution Degree: 2
Overvoltage Category: II
Insulation Class: 1
Relative Humidity: 5%–95%, noncondensing
Maximum Altitude: 2000 m
Weight
2.0 kg (4.4 lb)
Inputs Optoisolated Control Inputs
When Used With DC Control Signals:
250 V ON for 200–275 Vdc OFF below 150 Vdc 220 V ON for 176–242 Vdc OFF below 132 Vdc 125 V ON for 100–135.5 Vdc OFF below 75 Vdc 110 V ON for 88–121 Vdc OFF below 66 Vdc 48 V ON for 38.4–52.8 Vdc OFF below 28.8 Vdc 24 V ON for 15–30 Vdc OFF below 5 Vdc
When Used With AC Control Signals:
250 V ON for 170.6–275 Vac OFF below 106 Vac 220 V ON for 150.3–264 Vac OFF below 93.2 Vac 125 V ON for 85–150 Vac OFF below 53 Vac 110 V ON for 75.1–132 Vac OFF below 46.6 Vac 48 V ON for 32.8–60 Vac OFF below 20.3 Vac 24 V ON for 14–27 Vac OFF below 5 Vac
Current Draw at Nominal DC Voltage: 2–6 mA (except for 24 V, 8 mA)
Outputs Mechanical Durability
10 M no-load operations
DC Output Ratings
Standard Output Option
Rated Operational Voltage: 24–250 Vdc
Rated Voltage Range: 19.2–275 Vdc
Rated Insulation Voltage: 300 Vdc
Make: 30 A @ 250 Vdc per IEEE C37.90
Continuous Carry: 6 A @ 70°C; 4 A @ 85°C
Thermal: 50 A for 1 s
Contact Protection: 360 Vdc, 40 J MOV protection across open contacts
Operating Time (Coil Energization to Contact Closure, Resistive Load): Pickup/Dropout time 8 ms typical
Breaking Capacity (10,000 Operations) per
IEC 60255-0-20:1974:
24 V 0.75 A L/R = 40 ms 48 V 0.50 A L/R = 40 ms
125 V 0.30 A L/R = 40 ms 250 V 0.20 A L/R = 40 ms
Cyclic Capacity (2.5 Cycles/Second) per
IEC 60255-0-20:1974:
24 V 0.75 A L/R = 40 ms 48 V 0.50 A L/R = 40 ms
125 V 0.30 A L/R = 40 ms 250 V 0.20 A L/R = 40 ms
High-Current Interrupting Output Option
Rated Operational Voltage: 24–250 Vdc
Rated Voltage Range: 19.2–275 Vdc
Rated Insulation Voltage: 300 Vdc
Make: 30 A
Carry: 6 A continuous carry at 70°C 4 A continuous carry at 85°C
1 s Rating: 50 A
MOV Protection: 330 Vdc/145 J
Pickup Time: Less than 5 ms
Dropout Time: Less than 8 ms, typical
Breaking Capacity (10,000 Operations):
24 V 10 A L/R = 40 ms 48 V 10 A L/R = 40 ms
125 V 10 A L/R = 40 ms 250 V 10 A L/R = 20 ms
Cyclic Capacity (4 Cycles in 1 Second, Followed by 2 Minutes Idle for Thermal Dissipation):
24 V 10 A L/R = 40 ms 48 V 10 A L/R = 40 ms
125 V 10 A L/R = 40 ms 250 V 10 A L/R = 20 ms
Note: Make per IEEE C37.90-1989.
Note: Do not use high-current interrupting output contacts to switch ac control signals. These outputs are polarity-dependent.
Note: Breaking and Cyclic Capacity per IEC 60255-0-20:1974.
Fast High-Current Interrupting Output Option
Rated Operational Voltage: 24–250 Vdc
Rated Voltage Range: 19.2–275 Vdc
Rated Insulation Voltage: 300 Vdc
Make: 30 A @ 250 Vdc per IEEE C37.90
Continuous Carry: 6 A @ 70°C; 4 A @ 85°C
Continuous Carry (UL/CSA Derating With All Outputs Asserted): 5 A @ < 60°C; 2.5 A 60 to 70°C
Thermal: 50 A for 1 s
Contact Protection: 330 Vdc, 145 J MOV protection across open contacts
Operating Time (Coil Energization to Contact Closure, Resistive Load)
Pickup Time: ~16 µs at 250 Vdc, 22 µs at 125 Vdc, 85 µs at 19.2 Vdc typical (results with 100 k resistive load)
Dropout Time: < 8 ms typical
Inductive Breaking Capacity (100,000 Operations) per IEC 60255-0-20:1974
24 Vdc 10 A L/R = 40 ms 48 Vdc 10 A L/R = 40 ms 125 Vdc 10 A L/R = 40 ms 250 Vdc 10 A L/R = 20 ms
Cyclic Capacity (4 Cycles/Second Followed by 2 Minutes Idle Thermal Dissipation) per IEC 60255-0-20:1974
24 Vdc 10 A L/R = 40 ms 48 Vdc 10 A L/R = 40 ms 125 Vdc 10 A L/R = 40 ms 250 Vdc 10 A L/R = 20 ms
AC Output Ratings
Standard Output Option
Rated Operational Voltage: 110–240 Vac
Rated Voltage Range: 19.2–264 Vac
Rated Insulation Voltage: 270 Vac
Rated Frequency: 50/60 ± 5 Hz
Utilization Category: AC-15 (control of electromagnetic loads >
72 VA)
Contact Rating Designation:
B300 (B = 5 A, 300 = rated insulation voltage)
Contact Protection: 270 Vac, 40 J
Continuous Carry: 6 A @ 70°C; 4 A @ 85°C
Continuous Carry (UL/CSA Derating With All Outputs Asserted): 5 A @ < 60°C; 2.5 A 60–70°C
Operating Time (Coil Energization to Contact Closure): Pickup/Dropout Time: 8 ms
Electrical Durability Make VA Rating: 3600 VA, cos = 0.3
Electrical Durability Break VA Rating: 360 VA, cos = 0.3
Fast High-Current Output Option
Rated Operational Voltage: 110–240 Vac
Voltage Range: 19.2–250 Vac
Rated Insulation Voltage: 250 Vdc
Rated Frequency: 50/60 ± 5 Hz
Make: 30 A @ 240 Vac
Utilization Category: AC-15 (control of electromagnetic loads
> 72 VA)
Contact Rating Designation:
B300 (B = 5 A, 300 = rated insulation voltage)
Continuous Carry: 6 A @ 70°C; 4 A @ 85°C
Continuous Carry (UL/CSA Derating With All Outputs Asserted): 5 A @ < 60°C; 2.5 A 60 to 70°C
Thermal: 50 A for 1 s
Contact Protection: 250 Vac, 145 J MOV protection across open contacts
Operating Time (Coil Energization to Contact Closure, Resistive Load)
Pickup Time: ~16 µs at 250 Vac, 22 µs at 125 Vac, 85 µs at 19.2 Vac typical (results with 100 k resistive load)
Dropout Time: < 8 ms typical
Note: Per IEC 60255-23:1994, using the simplified method of assessment.
Note: Making rating per IEEE C37.90-1989.
48DI Input Derating Curve:
32DO/16DI Output Derating Curve:
Time-Code Input (Demodulated IRIG-B) On (1) State: Vih 2.2 V
Off (0) State: Vil 0.8 V
Input Impedance: 2 k
Accuracy: microsecond
Time-Code Input (SNTP) High-Priority Server
Accuracy: ±1 ms (in an ideal network)
Low-Priority Server Accuracy: ±25 ms
55.00 60.00 65.00 70.00 75.00 80.00 85.00 Temperature (°C)
250 V 220 V 125 V 24 V 110 V48 V
Nu m be r o f A ss er te d In pu ts
55.00 60.00 65.00 70.00 75.00 80.00 85.00 T t (°C)
6 A 2 A 0 A
Nu m be r o f A ss er te d Ou tp ut s
Time-Code Input (PTP) IEEE 1588-2008 Firmware-
Based Accuracy: ±1 ms
Time-Code Output (Demodulated IRIG-B) On (1) State: Voh 2.4 V
Off (0) State: Vol 0.8 V
Load: 50
Communications Communications Ports
USB 2.0 Port: Port F; front-panel port
Ethernet Ports: Port 1A, 1B; rear-panel 10/100BASE-T or 100BASE-FX ports
Optional Port: 300–115200 bps Port 2; rear panel available as:
EIA-232 with IRIG-B EIA-485 with IRIG-B ST fiber with IRIG-B
EIA-232 Port: 300–115200 bps Port 3; rear-panel port with IRIG-B
Fiber-Optic Ports Characteristics
Port 1 (or 1A, 1B) Ethernet
Wavelength: 1300 nm
Data Rate: 100 Mbps
Optical Connector Type: LC
Fiber Type: Multimode
Link Budget: 16.1 dB
Typical TX Power: –15.7 dBm
Min RX Sensitivity: –31.8 dBm
Fiber Size: 50–200 m
Approximate Range: ~6.4 km
Typical Fiber Attenuation: –2 dBm/km
Port 2 Serial ST (SEL-2812 Compatible)
Baud Rate: 300–115200 bps
Wavelength: 850 nm
Optical Connector Type: ST
Fiber Type: Multimode
Link Budget: 16 dBm
Min TX Power: –13 dBm
Max TX Power: –3 dBm
Min RX Sensitivity: –29 dBm
Fiber Size: 50–200 µm
Approximate Range: ~4 km with 62.5 µm ~1 km with 200 µm
Typical Fiber Attenuation: –4 dBm/km
Communications Protocols
Modbus Slave (TCP and RTU) DNP3 Level 2 Outstation (LAN/WAN and Serial) IEC 61850 communications
FTP
SNTP
PTP (firmware based) Telnet
SEL MIRRORED BITS
Ymodem file transfer on the front and rear port Xmodem file transfer on the front port SEL ASCII and Compressed ASCII SEL Fast Meter SEL Fast Operate SEL Fast SER SEL Fast Message unsolicited write SEL Fast Message read request SEL Event Messenger points
Maximum Concurrent Connections
Modbus Slave: 2
DNP3 Level 2 Outstation: 5a
Ethernet FTP: 2
Telnet: 2
IEC 61850 MMS: 7
IEC 61850 Goose: 16 incoming 8 outgoing a Maximum in any combination of serial and/or LAN/WAN links.
Power Supply Input Voltage
Rated Voltage: 24–250 Vdc 110–230 Vac, 50/60 Hz
Voltage Range: 19.2–275 Vdc 85–264 Vac
Inrush Current: < 20 A pk
Power Consumption
AC: < 50 VA
DC: < 20 W
Interruptions: 10 ms @ 24 Vdc 25 ms @ 48 Vdc 125 ms @ 125 Vdc 160 ms @ 120 Vac 600 ms @ 250 Vdc 1000 ms @ 230 Vac
Fuse Rating: 3.15 A, high breaking capacity, time lag T, 250 V (5 x 20 mm, T3.15AH 250 V)
Sampling and Processing Specifications Digital Inputs
Sampling Rate: 2 kHz
Contact Outputs
Refresh Rate: 2 kHz
Logic Update: Every 4 ms
Timer Accuracy
±2 ms and ±0.001% of settings
Processing Specifications Processing Interval: 2 ms
Control Processing: 2 ms (except for math variables and, with default settings, remote analogs which are processed at 100 ms)
Product Standards Electrical Equipment for
Measurement, Control, and Laboratory Use:
IEC 61010-1:2013
UL 508:2018
C22.2 No. 61010-1:12
IEC 61010-2-201:2013
UL 61010-2-201:2017
C22.2 No. 61010-2-201:14
Measuring Relays and Protection Equipment:
IEC 60255-26:2013
IEC 60255-27:2013
Type Tests Note: To ensure good EMI and EMC performance, type tests were performed using shielded copper Ethernet cables with the shell grounded at both ends of the cable. Additionally, digital inputs were configured with 4 millisecond pickup and dropout time settings.
Double-shielded cables and 4 millisecond or greater pickup and dropout times are recommended for best EMI and EMC performance.
Environmental Tests
Enclosure Protection: IEC 60529:1989 + A1:1999 + A2:2013 IP4X Front IP2X Product Note: If rear terminals are accessible during normal use, the product must be mounted in a locked enclosure or restricted area accessible by trained maintenance or operation personnel only.
Vibration Endurance: Class 2
Response: Class 2
Shock Withstand: Class 1
Response: Class 2
Bump Withstand: Class 1
Seismic Response: Class 2
Cold: IEC 60068-2-1:2007 –40°C, 16 hours
Damp Heat, Steady State: IEC 60068-2-78:2001 40°C, 93% relative humidity, 4 days
Damp Heat, Cyclic: IEC 60068-2-30:2005 25°C–55°C, 6 cycles, 95% relative humidity
Dry Heat: IEC 60068-2-2:2007 85°C, 16 hours
Power Interruption Tests
AC Power: 61000-4-11:2004
DC Power: 61000-4-29:2001
Dielectric Strength and Impulse Tests
Dielectric (HiPot): IEC 60255-27:2013
IEEE C37.90-2005
3.6 kVdc on power supply
2.5 kVac on contact I/O
1.5 kVac on Ethernet/IRIG IN
Impulse: IEC 60255-27:2013 5 kV on power supply, contact I/O
2.2 kV on Ethernet
RFI and Interference Tests
EMC Immunity
Electrostatic Discharge Immunity:
IEC 61000-4-2:2008
Severity Level:
2, 4, 6, 8 kV contact discharge 2, 4, 8, 15 kV air discharge
Radiated RF Immunity: IEC 61000-4-3:2006 + A1:2007 + A2:2010 10 V/m
IEEE C37.90.2-2004
20 V/m
Fast Transient, Burst Immunity:
IEC 61000-4-4:2012
4 kV @ 5 kHz on power supply and contact I/O 2 kV @ 5 kHz for communication ports
Surge Immunity: IEC 61000-4-5:2005 1 kV on power supply, contact I/O 2 kV on power supply, contact I/O, Ethernet and serial ports, IRIG
Surge Withstand Capability:
IEC 61000-4-18:2006 + A1:2010
Severity Level:
Power supply and contact I/O
2.5 kV peak common mode
1.0 kV peak differential mode
Communication ports
1.0 kV peak common mode
IEEE C37.90.1-2012
2.5 kV oscillatory, 4 kV fast transient
Conducted RF Immunity: IEC 61000-4-6:2013, 10 Vrms
Power Frequency Magnetic Field:
IEC 61000-4-8:2009
1000A/m for 3 s 100A/m for 1 min
Pulse Magnetic Field: IEC 61000-4-9:2016 1000 A/m
Damped Oscillatory Magnetic Field:
IEC 61000-4-10:2016
100 A/m
EMC Emissions
Note: Test performed using serial cables with shield grounded at both ends.
Conducted and Radiated Severity Level:
Class A
EN 55011:2009 + A1:2010
EN 55022:2010 + AC:2011
EN 55032:2012 + AC:2013
CISPR 11:2009 + A1:2010
CISPR 22:2008
CISPR 32:2015
ANSI C63.4:2014
Canada ICES-001 (A) / NMB-001 (A)
Technical Support
We appreciate your interest in SEL products and services. If you have questions or comments, please contact us at:
Schweitzer Engineering Laboratories, Inc.
2350 NE Hopkins Court Pullman, WA 99163-5603 U.S.A.
Tel: +1.509.338.3838 Fax: +1.509.332.7990 Internet: selinc.com/support Email: info@selinc.com https://selinc.com/support mailto: info@selinc.com
Notes
© 2008—2025 by Schweitzer Engineering Laboratories, Inc.
Content subject to change without notice.
Unless otherwise agreed in writing, all SEL product sales are subject to SEL’s terms and condi-tions located here: https://selinc.com/company/termsandconditions/.
*PDS2440-01*
2350 NE Hopkins Court • Pullman, WA 99163-5603 U.S.A.
Tel: +1.509.332.1890 • Fax: +1.509.332.7990 selinc.com • info@selinc.com
SEL-2440 DPAC Data Sheet Date Code 20250228
| Major Features and Benefits |
| Product Summary |
| Functional Diagram |
| Configuration |
| Inputs/Outputs |
| Communication and Time |
| Input/Output Features |
| Inputs (Status and Alarms) |
| Outputs (Relays) |
| Power |
| IRIG-B |
| Connectors |
| Conformal Coating |
| Communications Ports |
| Analyze Sequence–of–Events |
| Automation Features |
| Flexible Control Logic and Integration Features |
| Communications Architectures |
| Additional Ordering Options |
| Diagrams and Dimensions |
| Specifications |
| Technical Support |