Item 10 - SEL 735 Power Quality Meter.pdf

PDF 4 MB Posted

Attached to
Design-Bid-Build (DBB), Energy Campus Infrastructure at the Philadelphia Navy Yard Annex (PNYA) in Philadelphia, Pennsylvania
Solicitation number
N4008525R2641
Issued by

About this file

This document is a comprehensive product data sheet for the SEL-735 Power Quality and Revenue Meter manufactured by Schweitzer Engineering Laboratories, Inc. The SEL-735 is a high-precision metering device designed for power systems, offering advanced features including power quality monitoring, revenue metering, and extensive communication capabilities. Key specifications include IEC 61000-4-30 Class A compliance, 0.06 percent accuracy, up to 1 GB of onboard storage, simultaneous communication with up to ten devices using protocols like DNP3, IEEE C37.118 synchrophasor measurements, Modbus, and IEC 61850, and flexible configuration options with three variant models (Basic, Intermediate, and Advanced) offering different levels of functionality such as harmonic analysis, interharmonic measurements, and extended memory storage.

The meter provides multiple advanced features including continuous waveform streaming, four-quadrant metering, predictive demand monitoring, programmable logic control, time-of-use recording, and compatibility with various software platforms like ACSELERATOR QuickSet and Synchrowave. It supports wide-area network integration, offers retrofit applications with outdoor enclosures and extractable meter options, and meets numerous compliance standards including ANSI, IEC, IEEE, and UL certifications. The device can be used in diverse applications such as power quality monitoring, distributed generation control, energy optimization, and subcycle transient identification, with operating temperatures ranging from -40° to +85°C and multiple power supply options.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SEL-735 Power Quality and Revenue Meter

Precise Metering for High-Value Power Systems

Five-inch, color touchscreen display model Formattable 1- and 3-line monochromatic LCD display model

Key Features and Benefits The SEL-735 Power Quality and Revenue Meter combines leading power quality capabilities with exceptional revenue metering accuracy at an economical price.

➤ Easily access data. An optional touchscreen interface displays real-time waveforms, metered data, alarms, notifications, and settings.

➤ Accurately allocate energy costs. The SEL‑735 outperforms ANSI and IEC accuracy standard requirements with a 0.06 percent Wh guarantee. It exceeds ANSI C12.20 0.1 and IEC 62053-22 0.1 S accuracy class requirements over its entire service life, eliminating costs associated with field calibration.

➤ Capture every power quality disturbance. Power quality reports with IEC 61000‑4‑30 Class A compliance and as much as 1 GB of onboard storage help visualize system conditions and store years of data. Optional continuous waveform streaming precisely samples voltage and current signals at 3 kilosamples per second (ksps) and sends the data to SEL Synchrowave® software for visualization.

➤ Share critical information securely. Simultaneously communicate with as many as ten other devices by using industry standard protocols, including DNP3, IEEE C37.118 synchrophasor measurements, Modbus, and IEC 61850. Port security settings allow three permission levels that provide controlled read and write access to the ports.

Date Code 20250131 SEL-735 Data Sheet

2 One Package, Three Flexible Solutions

➤ One meter for multiple applications. Standardize on one meter across multiple applications with wide current and voltage measurement ranges, field upgradability, retrofit options, and software-based wiring form changes.

➤ Software Integration. Use SEL software for easy access to metering data. Integrate with optional SEL Synchrowave software for real-time and historic visualization across local and wide-area systems.

One Package, Three Flexible Solutions Three SEL‑735 variants provide a meter for any application and any budget.

Table 1 and Table 2 list the available ordering options.

For more information about IEC 61000-4-30 testing and measurement, see Section 5: Metering in the SEL-735 Instruction Manual.

Table 1 SEL-735 Power Quality and Recording Options

PQ and Recording SEL-735 Basic SEL-735 Intermediate SEL-735 Advanced

Memory 128 MB 256 MB 1 GB

Max Harmonic Order 15th 63rd 63rd

Interharmonic Quantities No No Yes

Harmonic Angles No No Yes

Power Harmonics No No Yes

Waveform Capture Event Reports

Samples Per Cycle 16 16, 128 16, 128, 512

Duration (cycles) 15 15–600 15–600

Number of Events 256 33–6,200 101–10,000

COMTRADE Reports Y Y Y

Load Profile Recorder

Recorders x channels 1 x 16 12 x 16 32 x 16

Acquisition rates 1–120 minutes 3–59 s, 1–120 minutes 3–59 s, 1–120 minutes

Storage duration for 10 minute interval data

16 channels 10 years 20 years 20 years

192 channels N/A 1.5 years 9.5 years

512 channels N/A N/A 3.5 years

Voltage Sag, Swell, Interruption (VSSI) Recorder

Typical number of summary events 260 260 600

Number of detailed rows 60,000 60,000 130,000

Minimum disturbance duration 1/4 cycle 1/4 cycle 1/4 cycle

Sampling rate 4 samples/cycle–1 sample/day, adaptive

4 samples/cycle–1 sample/day, adaptive

4 samples/cycle–1 sample/day, adaptive

Sequential Events Recorder

Number of events >80,000 >80,000 >80,000

Number of channels monitored ≤72 ≤72 ≤72

SEL-735 Data Sheet Date Code 20250131

One Package, Three Flexible Solutions 3

PQ and Recording SEL-735 Basic SEL-735 Intermediate SEL-735 Advanced

Protocols

Continuous Waveform Streaming Protocola

N Y Y

Other Features

Wave View Oscillography Nb Nb Y a Available with the purchase of a device software bundle or as a standalone meter upgrade.

b Color touchscreen app available on all models from the front panel. QuickSet HMI screen only available on advanced power quality models.

Table 2 SEL-735 Compliance With IEC 61000-4-30 Power Quality Standarda

IEC 61000-4-30 Requirement SEL-735 Basic PQ SEL-735 Intermediate PQ SEL-735 Advanced PQ

General

150/180-cycle, 10-min. aggregation — A A

2-hour aggregation — A A

Real-time clock uncertainty A A A

Power Quality Parameters

Power frequency A A A

Magnitude of the supply voltage A A A

Flicker — A (10 min, 2 hr updates) A (1 min, 10 min, 2 hr updates)

Supply voltage interruptions, dips, and swells

A A A

Supply voltage unbalance A A A

Voltage harmonics A A A

Voltage interharmonics — — A

Magnitude of current A A A

Harmonic currents A A A

Interharmonic currents — — A

Current unbalance A A A a "A" in the table refers to IEC 61000-4-30:2015 Class A Compliance.

4 Product Overview

Product Overview

Color Touchscreen Customizable Display

Programmable LCD for Single- or Three-Line Display

Custom Controls

Custom Controls

USB Type-C Port

Custom Nameplate and Barcode

Custom Nameplate and Barcode

ANSI Type II Optical or EIA-232 Port

Main Board Ethernet

EIA-232

IRIG-B

EIA-232/485

I/O Board (Expansion Slot #2) 4 Digital Inputs 4 Digital Outputs (solid-state [KYZ] or electromechanical) or 4 Analog Outputs 4 Digital Solid-State Outputs [KYZ]

Sealing Provision

Power Supply and I/O Board 1 Power Supply 3 Digital Outputs 2 Digital Inputs

Communications Board (Expansion Slot #1)

EIA-485

Telephone Modem

EIA-232

PT Board Va, Vb, Vc, Vn

CT Board Ia, Ib, Ic

Figure 1 Product Features

Features High-Accuracy Metering

The SEL‑735 exceeds ANSI 0.1 and IEC 0.1 S class accuracy requirements over a wide current range. The meter outperforms the new non-sinusoidal requirements of ANSI C12.20 and provides guaranteed accuracy over the life of the meter. All meters ship with individual calibration certificates.

Features 5

–0.30 –0.20 –0.10 0.00 0.20 0.300.10

Nu m be r o f S

EL

-7

M et er s

Watt-Hour Error Percentage

ANSI Lower Limit: –0.15%

ANSI Upper Limit: 0.15%

2.5 A, PF = 0.5

Standard Deviation = 0.006% Maximum Error = 0.025%

Accuracy-test results of approximately 1,000 SEL-735 Meters report a maximum error of 0.025 percent, outperforming ANSI 0.1 and IEC 0.1 S accuracy class requirements.

Figure 2 Accuracy Test

Uninterrupted Communications

Advanced communications deliver critical and historical information in real time to virtually any communications system. Simultaneously communicate with as many as ten other devices that use protocols including DNP3, Modbus, and IEC 61850. Improve real-time situational awareness of system conditions with IEEE C37.118.1a-2014 synchrophasors or continuous waveform streaming data.

Wide-Area Network

Ethernet Switch

Modem MV-90

Synchrowave Platform

Figure 3 Flexible Communications Options

6 Features

Power Quality Monitoring1

➤ Measure and record IEC 61000-4-30 Class A-compliant current, voltage, power, frequency, supply voltage interruptions, dips and swells, harmonics, interharmonics, flicker, and unbalance

➤ Measurement aggregation in 50/60 Hz, 3-second, 10-minute, and 120-minute intervals

➤ View real-time waveforms with the Continuous Waveform Streaming protocol or Wave View application.

➤ High-speed load profile recording with 3-second resolution ➤ Harmonic phase angles for voltage and current ➤ High-resolution, 512-samples/cycle waveform capture ➤ Total harmonic distortion (THD), crest factor, and K-factor metering with as much as 63rd harmonic content ➤ Voltage sag, swell, interruption ➤ Symmetrical components ➤ System unbalance

Advanced On-Board Logging Capture and log years of data with 512 logging channels, 10,000 event reports, and more than 130,000 voltage events with 1 GB of storage. Trend averages, minimums, maximums, changes, and snapshots at a rate of once every 3 seconds with independent load profile recorders.

Cyber Secure Four password levels provide controlled access to metering data and ensure protection of critical meter configuration and data. Port security settings allow three permission levels that provide controlled read and write access to the ports. The meter verifies the authenticity and integrity of firmware files during upgrades by using a checksum and cryptographic signature.

Transformer/Line-Loss Compensation When the contractual billing point differs from the meter location, use transformer and line-loss compensation (TLLC) to optimize the metering location and reduce the instrument transformer costs. Both compensated and uncompensated values are stored in the meter to simplify site verification.

BP1

BP2

IN (Delivered)

Transmission Substation

BP4

BP3

IN (Delivered)

OUT (Received)

High Voltage Transmission Lines

Figure 4 Choose From Four Billing and Metering Points With TLLC

1Includes optional features. See Table 1 and Table 2 for details.

Features 7

Configurable Meter Form Internal connections of meter elements (CT and PT pair) can be changed in the field depending on the type of service. The FORM terminal command configures the meter as Form 5, 9, or 36.

N C B

LO

AD

LI

NE

A

N C B A

Form 36, 2 1/2-Element, Four-Wire WyeForm 9, 3-Element, Four-Wire Wye

N C B

LO

AD

LI

NE

A

N C B A

Form 5, 2-Element, Three-Wire Delta

C

B LO

AD

LI

NE

A

C B A

Figure 5 Software-Configurable Metering Form

Touchscreen Features A real-time display on an 800 x 480 color touchscreen display provides visual indication of power quality and waveform signatures by using a menu-based interface.

Real-Time Oscilloscope

Wave View displays voltage and current waveforms in real time, creating oscilloscope-like functionality.

Figure 6 Wave View Display

8 Features

Phasor Display

Easily access metering phasors for commissioning, troubleshooting, and power system monitoring with real-time phasors. The color display is specially designed to support color-blindness.

Figure 7 Phasor Display

Test Mode

Simplify accuracy testing with visualization of infrared test pulses, accumulated energy, and instantaneous signals. When in Test Mode, the SEL‑735 freezes billing quantities to isolate test input from revenue billing.

Figure 8 Test Mode Display

Four-Quadrant Metering

The SEL‑735 supports four-quadrant metering to monitor power and energy accumulation in each quadrant for bidirectional metering.

Features 9

Figure 9 Four-Quadrant Metering

Large Three-Line Display

Customizable screens with useful defaults and large fonts allow continuous monitoring from a distance.

Figure 10 Three-Line Display

Predictive Demand

The predictive demand function monitors accumulated demand and alarms when the demand exceeds a user-defined limit. The SEL‑735 can then shut down loads or peak-shave with generation to avoid demand charges, as shown in Figure 11.

The predictive demand alarm is available through IEC 61850, Modbus, DNP3, MIRRORED BITS communications, or the front-panel LEDs.

Daily Load Profile

Load

New Peak Predicted

Avoided Demand Charge

Figure 11 Reduce Peak Demand Charges With the Predictive Demand Alarm

10 Features

Programmable Logic (SELOGIC Control Equations)

The meter provides user-programmable logic to combine meter calculations, contact inputs, remote command inputs, and timers to control internal logic and contact outputs. The logic allows the following operations:

➤ Logic (OR, AND, NOT)

➤ Math (+, –, x, /)

➤ Analog compare (>, <, <>, =, >=, <=)

➤ Triggers (RISING EDGE, FALLING EDGE)

➤ Sixteen latches

➤ Sixteen remote-control logic units

➤ Sixteen programmable logic variables with pickup and dropout timers

➤ Sixteen programmable analog variables

Time of Use

Record demand and energy consumption with a user-defined calendar, use time-of-use metering to bill consumption at different rates based on season, day type, and time of day. The program automatically self-reads and resets demand; there is no need to manually reset meters.

Software Features

Monitor the state of the power system by using no-cost ACSELERATOR QuickSet® SEL‑5030 Software or view and analyze event records with SEL-5601-2 SYNCHROWAVE® Event Software. Add SEL-5705 Synchrowave Reports to manage and visualize your meter data from a central server.

Features 11

Waveform Capture and Analysis

Quickly analyze event records, status bits, spectral analysis, and harmonic content by using the Meter QuickSet HMI. View and analyze captured event records with SYNCHROWAVE Event.

Figure 12 Event Report and Analysis

12 Features

Trend Log Monitoring

Independent load profile recorders in the SEL‑735 allow simultaneous meter and power quality logging of as many as 512 data channels. Trend averages, minimums, maximums, changes, and snapshots are recorded at a rate of once every 3 seconds. All possible configurations are shown in Table 1.

QuickSet offers a fast and simple method to retrieve, plot, and export load profile data to .hhf or .csv formats. Itron MV‑90 meter reading software communicates to any SEL‑735 communications port and automates meter reads for large-scale metering installations.

Figure 13 Trend Log in QuickSet HMI

Features 13

VSSI Monitoring

Correlate system disturbances with the VSSI recorder. The SEL‑735 stores and reports residual voltage, duration, affected phases, and time stamp of occurrence.

View and generate VSSI CBEMA/ITIC curves in SEL-5705 Synchrowave Reports.

Figure 14 VSSI Summary in Synchrowave Reports

14 Features

Flicker and Harmonics Monitoring

Monitor, record, and control using individual harmonic values, THD, and K-factor with resolution as high as the 63rd harmonic. Measure, record, and control using Group THD. Measure interharmonics from 1 Hz to 3800 Hz in 1 Hz sampling bins. Retrieve interharmonics with 1 Hz resolution through the Wave View application in QuickSet, which is available with the Advanced PQ ordering option.

Figure 15 Harmonic Spectral Analysis

Application Examples 15

Continuous Waveform Recording

Never miss a disturbance again by recording the 3 kilosamples per second (ksps) continuous waveform stream with Synchrowave Platform software. Applications include archiving, virtual metering, subsynchronous oscillation analysis, and equipment failure analysis.

Figure 16 Continuous Waveform Streaming

Application Examples The SEL‑735 accurately reports bidirectional energy even in the presence of harmonics and distorted waveforms. When tested with peaked waveform distortion, the SEL‑735 reports with a typical error of just 0.006 percent.

16 Application Examples

ANSI Test #41 Peaked Current Waveform

ANSI Test #41 Peaked Voltage Waveform

A V

–50 –100 –150 –200

0 ms 5 ms 10 ms 15 ms 20 ms 25 ms

0 ms 5 ms 10 ms 15 ms 20 ms 25 ms

–2 –4 –6 –8

Figure 17 Current and Voltage Waveforms

Table 3 SEL-735 Performance With Peaked Waveform Distortion

Voltage Waveform Current Waveform

0.1 Accuracy

Class Reference Performance (%)

SEL-735 Measured Error (%)

Sinusoidal Sinusoidal ±0.05 0.003

Sinusoidal Peaked Current Waveform

±0.2 0.006

Peaked Voltage Waveform

Peaked Current Waveform

±0.3 0.006

Power Quality Monitoring and Troubleshooting

Use programmable triggers, such as voltage interruptions, to record as many as 10,000 oscillography events. The VSSI recorder time-stamps voltage excursions with as much as 4 ms resolution and records indefinitely by using an adaptive sampling rate. Settings include trigger thresholds and hysteresis as a percentage of the nominal value and an automatic recording duration dependent on the length of the voltage excursion. Configure continuous waveform streaming and Synchrowave software to capture all disturbances without needing to program pickup triggers.

Distributed Generation Control

Provide automatic start and remote control to distributed generation facilities.

SELOGIC control equations support any logical or mathematical combination of measured quantities and set points to control a generator or load switch.

Application Examples 17

Site Load

Control Signal

Power System

SEL-735

Figure 18 Distributed Generation Control

Optimize Energy and Resources

Use Synchrowave Reports to analyze data, identify system trends, and make planning decisions. Trend any signal received from the SEL-735, including measurements from pulse-type devices, to monitor consumption of resources such as water, air, gas, and steam (WAGES). The SEL‑735 includes as many as six pulse inputs. Load profile recorders provide as much as 20 years of storage with 512 channels to assist with tracking efficiency measures, unused resources, and performance efficiency such as kWh per cubic meter of water pumped.

Figure 19 Signals Report

18 Application Examples

Identify Subcycle Transients

Record waveform streaming data with Synchrowave Platform software to identify and visualize subcycle transients not detected by triggered event captures. Compare cycle-by-cycle waveform data to detect sudden abnormal wave shapes, voltage and current transients, and rapid voltage changes.

Figure 20 Waveform Disturbance Detection

Retrofit Applications 19

Retrofit Applications Outdoor Enclosure

➤ Replace socket meters with a low-cost enclosure and prewired FT‑1 test switch.

➤ Quickly install the meter with the support of thoughtful design details, such as DIN rails for accessories; a lockable, stainless steel latching system; wall-mount brackets; prewiring from the meter to the test switch;

and wire clamps. The fully sealed enclosure complies with NEMA 4X, IEC 529, and IP66 protection requirements.

Figure 21 Outdoor Enclosure Mounting

Easily Extractable Meter (EXM)

➤ Extractable in less than one minute.

➤ Safer than draw-out and socket meters.

➤ Self-shorting CT connector.

➤ Clearly marked wires.

➤ Easier to install and half the cost of a draw-out meter.

➤ Simplified field testing with integrated connectors.

➤ Simple retrofit brackets replace draw-out meters.

20 Retrofit Applications

1 2

3 4

Pull quick-release latches. Hinge meter down.

Remove quick disconnects. Easily extract the meter.

Figure 22 EXM Option Instructions

Mounting Options and Accessories

Refer to the Metering Accessory Catalog, available at selinc.com/products/73x/ meter-options/, for more information on brackets, retrofit bezels, cover plates, and other accessories.

Kit 915900063

Kit 915900136

Horizontal Meter and Test Switch Vertical Bezels

Figure 23 Mounting Options and Other Accessories

Diagrams and Dimensions 21

Portable Power Quality Meter

Monitor power quality anywhere with the rugged SEL‑735 Portable Power Quality Meter. You can pinpoint power quality problems and energy consumption on subcircuits with clamp-on CTs and clip-on voltage leads. In addition, the portable meter lets you log years' worth of data with 1 GB of onboard memory.

Power factor, harmonic, imbalance, and flicker trending

Rugged travel enclosure

200:1, 1,000:5, 2,000:5, and 3,000:5 CT options

1 GB of data storage Standard Ethernet port for rapid data retrieval

120/240 Vac line power

Safety jacks for voltage and current

Figure 24 Portable Power Quality Meter

Diagrams and Dimensions

5.67 in (144 mm)

7.

in (1 m m

5.84 in (148.3 mm)

1.38 in (35.0 mm)

7.

in (1 m m

5.47 in (139 mm)

7.

in (1 m m

Figure 25 SEL-735 Vertical Dimensions

22 Specifications

5.

in (1 m m

7.36 in (187 mm)

7.56 in (192 mm)

5.

in (1 m m

0.84 in (21.4 mm)

5.

in (1 m m

5.80 in (147.4 mm)

Figure 26 SEL-735 Horizontal Dimensions

Specifications

CAUTION

Observe ratings prior to commissioning.

Compliance

American National Standards Institute

(ANSI)

ANSI C12.1-2014 for Electric Meters, Code for Electricity Metering and ANSI C12.20-2015 for Electricity Meters— 0.1, 0.2, and 0.5 Accuracy Classes verified compliant by an accredited third-party test laboratory

Australian National Measurement Institute

NMI M6-1 Electricity Meters: Part 1: Metrological and Technical Requirements verified by an accredited third-party test laboratory

Australia and New Zealand RCM Mark

California ISO (CAISO) CAISO Compliant (applies to Blondel-compliant Form 5 and Form 9 only)

Canada ICES-001(A) / NMB-001(A)

Comisión Federal de Electricidad (CFE) G0000-48-2010 verified compliant by Laboratorio de Pruebas de Equipos y Materiales (LAPEM)

Electric Reliability Council of Texas

(ERCOT)

ERCOT Compliant (applies to Blondel-compliant Form 5 and Form 9 only)

European Union (EU) CE: Mark—EMC Directive (2014/30/EU), Low Voltage Directive (2014/35/EU)

Federal Institute of Metrology

(METAS)

Certified to IEC 61000-4-30 Ed. 3.0 (2015) Class A, Testing according to IEC 62586-1 Ed. 2.0 (2017) and IEC 62586-2 Ed.

2.0 (2017) Certified to IEC 62052-11:2020, IEC 62053-22:2020, IEC 62053-24:2020, AS 62052.11:2018, AS 62053.22:2018, and AS 62052.31:2017

Specifications 23

International Electrotechnical Commission

IEC 62052-11:2020, Electricity metering equipment (AC) - General requirements, tests and test conditions

ISO 9001 Designed and manufactured under an ISO 9001 certified quality management system

New York New York State Department of Public Service Commission (applies to Blondel-compliant Form 5 and Form 9 only)

Underwriter’s Laboratories, Inc.

(Normal Locations)

UL Listed to U.S. and Canadian safety standards (File E220228, FTRZ, FTRZ7, NRAQ, NRAQ7, PICQ, PICQ7)

Underwriter’s Laboratories, Inc.

(Hazardous Locations)

ANSI/ISA 12.12.01-2015 and CSA C22.2 No. 213-15 Class I Division 2 Hazardous Locations (File E475839, NRAG, NRAG7).

United Kingdom UKCA Mark

General

AC Voltage Inputs

Measurement Category: III

Maximum Rating: 300 VL–N, 520 VL–L continuous 600 VL–N, 1039 VL–L for 10 seconds

PT input has only been evaluated for a maximum of 300 L-N Vac input rating by UL.

Range

Revenue: 28–300 VL–N, 48–520 VL–L

Measurement: 11–300 VL–N, 19–520 VL–L

Burden: 10 MW

AC Current Inputs

Measurement Category: III

Maximum Rating: 20 A continuous, per UL 61010 500 A for 1 second (thermal) 100 A for 25 seconds (thermal)

Range

Current Class CL2/CL10/CL20, optimized for low-end accuracy

Revenue: 0.010–22 A

Measurement: 0.001–22 A continuous

Current Class CL10/CL20, optimized for 100 A fault recording

Revenue: 0.050–22 A

Measurement: 0.005–22 A continuous 22–100 A symmetrical (with saturation)

Burden: ≤0.5 VA

Frequency and Rotation

60 or 50 Hz system frequency specified at time of order. User-selectable ABC/ACB phase rotation.

Frequency tracking range: 40 to 70 Hz based on VA or VC.

Power Supply

UL Ratings

120/240 Vac: 50/60 Hz, 60 VA

125/250 Vdc: 25 W

24/48 Vdc: 22 W

12/24 Vdc: 22 W

24 Specifications

Typical Power Consumption:

<20 VA/7 W typical <30 VA/9 W typical (color touchscreen model)

Startup Time to Begin Energy Metering:

<5 seconds

Continuous Operating Limits

110–240 Vac/Vdc: 85–264 Vac (50/60 Hz) 85–275 Vdc

24/48 Vdc: 19–58 Vdc

12/24 Vdc: 9.6–30 Vdc

Interruption:

(IEC 60255-11:1979)

50 ms at 125 Vac/Vdc 50 ms at 48 Vdc 10 ms at 24 Vdc 2 ms at 12 Vdc

Ripple:

(IEC 60255-11:1979)

12% for dc inputs

Terminal Voltage Dropout: <40 V within 1 minute of power removal

Rated Insulation Voltage (IEC 60664-1:2020): 300 Vac

100BASE-FX Fast Ethernet Fiber-Optic Port

Fiber Type: Multimode

Data Rate: 100 Mbps

Wavelength: 1300 nm

Optical Connector Type: LC

Link Budget: 11.8 dB

Fiber Size: 62.5/125 mm or 50/125 mm

Approximate Range: 2 km

TX Power (Max): –14 dBm average

TX Power (Min): –20 dBm average (62/125)

TX Power (Min): –23.5 dBm average (50/125)

RX Sensitivity: –31 dBm average

RX Power Input (Max): –14 dBm average

Communications Protocols

SEL ASCII/Compressed ASCII, SEL Fast Operate/Fast Meter, MIRRORED BITS, SEL Distributed Port Switch (LMD), Modbus RTU/TCP, DNP3 serial and LAN/WAN, FTP, TCP/IP, Y-Modem, SNTP, IEC 61850, Telnet, MV-90, IEEE C37.118-2014 (Synchrophasor measurements), and Continuous Waveform Streaming (CWS)

Output Contacts

Ratings determined by IEC 60255-23:1994

Standard (Electromechanical) 250 Vac, 30 Vdc, 3 A resistive

Make: 30 A per IEEE C37.90-1989

3.6 kVA, Cos Φ = 0.3

Break Rating: 360 VA, Cos Φ = 0.3

Specifications 25

Breaking Capacity (10000 Operations):

12/24 Vdc 0.75 A L/R = 40 ms

48 V 0.50 A L/R = 40 ms

125 V 0.30 A L/R = 40 ms

250 Vdc 0.20 A L/R = 40 ms

Carry: 3 A at 120 Vac, 50/60 Hz

1.5 A at 240 Vac, 50/60 Hz

50 A for 1 second

Durability: >10,000 cycles at rated conditions

Pickup/Dropout Time: <16 ms

Maximum Operating Voltage (Ue): 250 V

Current (Ie): 3 A

Rated Insulation Voltage (Ui) (Excluding EN 61010): 300 V

Optional (Solid State)

Voltage: 250 Vdc/Vac

Current: 100 mA maximum

Capacity: 0.6 VA at 25°C, 0.2 VA at 85°C

Pulse Rate: 20 pulses per second

Maximum On Resistance: Typical: 50 Ω Guaranteed: <100 Ω

Minimum Off Resistance: 10 MΩ

Pickup/Dropout Time: <25 ms

Analog Outputs

Maximum Firmware Update Rate: 100 ms

Maximum Settling Time for Full Range Change to 0.1% Full Scale: 500 ms

Bandwidth: 0 to 4 Hz

±1 mA Output

Range: ±1.2 mA

Minimum Output Impedance: 100 MΩ

Maximum Load: 10 kΩ, 100 μH

Accuracy: ±0.15% ± 2.0 μA at 25°C

4–20 mA Output

Range: ±24 mA

Minimum Output Impedance: 100 MΩ

Maximum Load: 500 Ω, 100 μH

Accuracy: ±0.20% ± 10 μA at 25°C

Optoisolated Input Ratings (Digital Input Ratings)

DC Control Signal 250 Vac/Vdc (Signal Level)

250 Vdc: Pickup 200–275 Vdc Dropout 150 Vdc

220 Vdc: Pickup 176–242 Vdc Dropout 132 Vdc

26 Specifications

125 Vdc: Pickup 100–137.5 Vdc Dropout 75 Vdc

110 Vdc: Pickup 88–121 Vdc Dropout 66 Vdc

48 Vdc: Pickup 38.4–52.8 Vdc Dropout 28.8 Vdc

24 Vdc: Pickup 15–30 Vdc Dropout <5 Vdc

12 Vdc: Pickup 9.6–16.7 Vdc Dropout <6 Vdc

AC Control Signal

250 Vac: Pickup 170.6–300 Vac Dropout 106 Vac

220 Vac: Pickup 150.3–264 Vac Dropout 93.2 Vac

125 Vac: Pickup 85–150 Vac Dropout 53 Vac

110 Vac: Pickup 75.1–132 Vac Dropout 46.6 Vac

48 Vac: Pickup 32.8–57.6 Vac Dropout 20.3 Vac

24 Vac: Pickup 14–27 Vac Dropout <5 Vac

Current Draw at Nominal DC Voltage: 2–6 mA

Time-Code Input

Meter accepts demodulated IRIG-B time-code input at EIA-232 Port 3, Port 2, or dedicated IRIG-B port (2-pin Phoenix connector).

IRIG Port Electrical Characteristics

Nominal Voltage: 5 Vdc

Maximum Voltage: 8 Vdc

Input Resistance: >2 kW

Dedicated IRIG Port

On (1) State: Vih ≥ 3.5 V

Off (0) State: Vil ≤ 1.5 V

IRIG Pins on Port 2 and Port 3

On (1) State: Vih ≥ 2.0 V

Off (0) State: Vil ≤ 0.8 V

Time Accuracy

Clock Drift With No Time Input: 4 minutes per year, typical

IRIG Accuracy: ±2 μs

Simple Network Time Protocol (SNTP) Accuracy

Manycast or Unicast: ±5 ms (when directly connected to SNTP server)

Broadcast: No specified accuracy

Operating Temperature

IEC 60068-2-1&2:1993: –40° to +85°C (–40° to +185°F)

Note: Not applicable to UL applications.

Specifications 27

LCD/Color Touchscreen

Operating Temperature: –20° to +70°C (–4° to +158°F)

Dimensions: 3.86" x 0.902"

Operating Environment

Insulation/ Protective Class: 1

Pollution Degree: 2

Overvoltage Category: CAT III: Color touchscreen model Power supply input, output contact, and digital input voltages must all be HLV or must all be SELV (no mixing of HLV and

SELV).

No option cards installed.

CAT II: All other vertical and horizontal configurations.

SELV = non-hazardous low voltage.

HLV = hazardous voltage, >60 Vdc, >30 Vac (specified for dry environments)

Indoor Use (Atmospheric Pressure: 80–110 kPa)

Maximum Humidity: 95% RH non-condensing

Maximum Altitude:

Altitude Working Voltage

0–2000 M 300 Vac

2000–4000 M 150 Vac

Weight

2.3 kg (5.0 lb)

Dimensions

Refer to Diagrams and Dimensions on page 21.

Terminal Connections

Rear Screw-Terminal Tightening Torque

Current Input Terminal Block (Ring Terminals Are Recommended)

Minimum:

Maximum:

0.9 Nm (8 in-lb)

1.4 Nm (12 in-lb)

Connectorized®

Minimum:

Maximum:

0.5 Nm (4.4 in-lb)

1.0 Nm (8.8 in-lb)

Compression Plug Mounting Ear

Minimum:

Maximum:

0.18 Nm (1.6 in-lb)

0.25 Nm (2.2 in-lb)

Connectorized terminals accept wire size 12–24 AWG.

User terminals or stranded copper wire should be at a minimum temperature rating of 105°C (221°F).

Synchrophasor Measurements

Compliance: P Class Synchrophasor data compliant with IEEE C37.118.1-2011 as amended by IEEE C37.118.1a-2014.

Data Transfer: IEEE C37.118.2-2011 (Backward compatible with IEEE C37.118-2005)

Message Rates: 60 Hz: 1, 2, 4, 5, 10, 12, 15, 20, 30, 60 messages per second 50 Hz: 1, 2, 5, 10, 25, 50 messages per second

28 Specifications

Measurement Category

Nominal Voltage:

120 V when VBASE < 180

240 V when 180 < VBASE < 250

250 V when VBASE ≥ 250

Voltage Range:

80%–120% of Nominal Voltage

Nominal Current:

ANSI CL2/20 and IEC 1 A/2 A/5 A nominal configurations. (1 A, 2 A, and 5 A are the preferred nominal current ratings for transformer-connected IEC meters in IEC 62052-11.)

Processing Specifications

AC Voltage and Current Inputs

512 samples per power system cycle.

Control Processing

1/2-cycle processing interval

SELOGIC Pickup and Accuracies

SELOGIC Timers: ±1/2 cycle

Analog Values: ±3%

Metering/Monitoring

Voltage, Current, and Power Accuracy

Unity Power Factor: ±0.06%

0.5 Power Factor: ±0.16%

Energy Accuracy (Form 5 and Form 9 Only)

Unity Power Factor: ±0.06% guaranteed ±0.02% typical

0.5 Power Factor: ±0.16% guaranteed

±0.06% typical

ANSI C12.20-2015 Accuracy Class 0.1

IEC 62053-22 Accuracy Class 0.1 S

IEC 62053-24 Accuracy Class 0.5 S

IEEE 519 PQ Compliance with pre-programmed settings

Frequency Accuracy

FREQ_PQ: ±0.001 Hz

FREQ: ±0.01 Hz

FREQ_PMU: ±0.005 Hz at stable frequency ±0.001 Hz at stable frequency between 59–61 Hz or 49–51 Hz

Power Quality

IEC 61000-4-30:2015 Class A

Flicker

PST: ±5% over the range 0.5–25 PST (10-min interval)

PLT: ±5% over the range 0.5–25 PLT (2-hour interval)

Specifications 29

Type Tests

Electromagnetic Compatibility Immunity

Product Standards: ANSI C12.20-2015

IEC 62052-11:2020

IEC 61000-6-2:2005 + AC:2005

IEC 61000-6-4:2006 + A1:2010

IEEE C37.90-2005

Conducted Radio Frequency Immunity: IEC 61000-4-6, 150 kHz to 80 MHz, 1 kHz 80% AM 10 Vrms Spot Frequencies: 27 MHz and 68 MHz

Damped Oscillatory Wave Immunity: ANSI C12.1

IEC 61000-4-18

IEEE C37.90.1

Current: ±2.5 kV common

Voltage: ±2.5 kV common, ±2.5 kV differential

Power: ±2.5 kV common, ±2.5 kV differential

Input: ±2.5 kV common, ±2.5 kV differential

Output: ±2.5 kV common, ±2.5 kV differential

Communication: ±2.5 kV common

Signal: ±2.5 kV common

Electrical Fast Transient Burst: ANSI C12.1

IEC 61000-4-4

IEEE C37.90.1

Power, Input/Output, Voltage/Current Circuits:

±4 kV @ 5 kHz

Communication: ±2 kV @ 5 kHz

Electrostatic Discharge: ANSI C12.1

IEC 61000-4-2

IEEE C37.90.3

Contact Discharge: ±8 kV Air Discharge: ±15 kV

Emissions: ANSI C63.4

CISPR 11/22/32

EN 55011/22/32

Class A or B (configuration-dependent) Canada ICES-001(A) / NMB-001(A)

Power Frequency Magnetic Field Immunity:

ANSI C12.1

ANSI C12.20

IEC 61000-4-8

100 A/m for 60 seconds 1000 A/m for 3 seconds Maximum deviation as specified in ANSI C12.20

30 Specifications

Radiated RF Immunity: ANSI C12.1

IEC 61000-4-3

IEEE C37.90.2

Frequency (MHz) Field Strength Modulation

0.2–80 15 V/m AM 90% 1 kHz sine

80–2000 20 V/m AM 80% 1 kHz sine AM 90% 1 kHz sine

80–2000 30 V/m Continuous wave

2000–10000 15 V/m Continuous wave

80–2000 20 V/m Keyed 0.5 s on 0.5 s off

80/160/380/450/900/1850/1890/ 2150/2600/3500/3800/5000

20 V/m AM 80% 1 kHz sine

900/1732/1800/1890/2310/ 2450/5800

20 V/m Pulse Mod. 50%

Ring Wave (100 kHz): ANSI C12.1

IEC 61000-4-12

IEEE C62.41.2

(Location Category B, Table 2) Power, Voltage/Current Circuits:

±6 kV (12 Ω) LL ±6 kV (12 Ω) LE ±4 kV with barrier-style Euro plugs installed

Startup and Shutdown: IEC 60255-26 60 s ramp/5 min power off

Surge Immunity: ANSI C12.1

IEC 61000-4-5

IEEE C62.41.2

(Location Category B, Table 3)

Power, Voltage/Current Circuits: ±6 kV (2 Ω) LL ±6 kV (2 Ω) LE ±4 kV with barrier-style Euro plugs installed

Ethernet: ±6 kV

EIA-232, EIA-485, IRIG-B: ±2 kV

Input/Output: ±2 kV LL ±4 kV LE

Environmental

Product Standards: ANSI C12.20-2015

IEC 62052-11:2020

IEC 60255-27:2014

Environmental: ANSI C12.1

IEC 60068-2-1

IEC 60068-2-2

IEC 60068-2-30

–40° to +85°C 5% to 95% relative humidity (37°C dew point)

Object Penetration: IEC 60529

Enclosed in Panel With Available Gasket (P/N: 915900097) (Monochrome Model):

IP65

Enclosed in Panel With Available Gasket (P/N 915900097) and Cover for Front USB-C Port ( Touchscreen Models):

IP54

Without Gasket: IP41

Back (Terminals): IP20

Specifications 31

Portable Power Quality Enclosure (When Door Closed):

IP67

NEMA Enclosure: 4X

Seismic: IEC 60255-21-3 Class 2 Quake Response

Shock/Bump: ANSI C12.1

IEC 60068-2-27

IEC 60255-21-2

Class 1 Shock Withstand Class 2 Shock Response Class 1 Bump

Vibration: ANSI C12.1

IEC 60068-2-6

IEC 60255-21-1

Class 2 Endurance Class 2 Response

Accuracy

ANSI C12.20-2015 Accuracy Class 0.1; CL2/10/20, and CL10/20 (applies to Blondel-compliant Form 5 and Form 9 only)

IEC 62053-22:2020 Class 0.1 S

IEC 62053-24:2020 Class 0.5 S

IEC 61000-4-30:2015

IEC 62586-2:2017

Class A

Safety

Product Standards: ANSI/ISA 12.12.01-2015 and CSA C22.2 No. 213-15 Class I Division 2 Hazardous Locations CAN/CSA-C22.2 No. 61010-1-12:2018

IEC/UL 61010-1:2010

IEC/UL 61010-2-030:2010 (300 V, Measurement Category III)

IEC/UL 61010-2-201:2013

IEC 62052-11:2020

IEEE C37.90-2005

Dielectric Strength/Impulse: IEC 61010-1

IEC 62052-11

IEC 60255-27

IEC 60664-1

IEEE C37.90

Routine Dielectric Test Levels

Current Inputs: 2.2 kVdc

Voltage Inputs: 2.2 kVac

Inputs and Outputs: 2.2 kVac

Analog Outputs: 3.11 kVdc

Power Supply: 3.11 kVdc

EIA-485 Port: 1.50 kVdc

Insulation Resistance: IEC 61010-1

IEC 60255-27

Meets applicable levels

Flammability of Insulating Materials: IEC 61010-1

IEC 62052-11

IEC 60255-27

Meets applicable levels

32 Technical Support

Max Temperature of Parts and Materials:

IEC 61010-1

IEC 62052-11

IEC 60255-27

Meets applicable levels, normal use

Protective Bonding/Continuity: IEC 61010-1

IEC 60255-27

Meets applicable levels

Technical Support We appreciate your interest in SEL products and services. If you have questions or comments, please contact us at:

Schweitzer Engineering Laboratories, Inc.

2350 NE Hopkins Court Pullman, WA 99163-5603 U.S.A.

Tel: +1.509.338.3838 Fax: +1.509.332.7990 Internet: selinc.com/support Email: info@selinc.com

© 2011—2025 by Schweitzer Engineering Laboratories, Inc.

Content subject to change without notice.

Unless otherwise agreed in writing, all SEL product sales are subject to SEL's terms and conditions located here: https://selinc.com/company/termsandconditions/.

*PDS735-01*

https://selinc.com/support mailto:info@selinc.com

Key Features and Benefits
One Package, Three Flexible Solutions
Product Overview
Features
High-Accuracy Metering
Uninterrupted Communications
Power Quality Monitoring
Advanced On-Board Logging
Cyber Secure
Transformer/Line-Loss Compensation
Configurable Meter Form
Touchscreen Features
Real-Time Oscilloscope
Phasor Display
Test Mode
Four-Quadrant Metering
Large Three-Line Display
Predictive Demand
Programmable Logic (SELOGIC Control Equations)
Time of Use
Software Features
Waveform Capture and Analysis
Trend Log Monitoring
VSSI Monitoring
Flicker and Harmonics Monitoring
Continuous Waveform Recording
Application Examples
Power Quality Monitoring and Troubleshooting
Distributed Generation Control
Optimize Energy and Resources
Identify Subcycle Transients
Retrofit Applications
Outdoor Enclosure
Easily Extractable Meter (EXM)
Mounting Options and Accessories
Portable Power Quality Meter
Diagrams and Dimensions
Specifications
Technical Support