This document appears to be a set of drawings and specifications for a generator replacement project at AS211 location at Camp Lejeune, North Carolina. The key details are:
The project involves demolishing the existing 120kW generator and associated equipment, and installing a new 350kW diesel engine generator with a sub-base fuel tank, automatic transfer switch, and 500kVA pad-mounted transformer. The new electrical work also includes underground duct banks, conduits, and conductors to connect the new generator to the existing electrical distribution system. The project has an estimated completion date of May 2, 2024. Only Mechanical MACC Contractors listed on the General Requirements cover page are eligible to submit proposals for this ROICC Camp Lejeune area project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFP 23-0032.pdf | ||
| 23-0032 DM.pdf | ||
| N4008523B0032 Specs.pdf | ||
| 23-0032 SOW.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONST. CONTR. NO.
FINAL T-1
D. POKHREL
D. POKHREL
J. SIDES, PE
D. POKHREL
J. ORR, PE
PWO 05/02/2024
GENERATOR REPLACEMENT
AT AS211
LOCATION MAPS & DRAWING INDEX
60040127 23-0032
NOTED 1 10
NORTHEAST CREEK
A T L A N T I
C O
C E A N
N E W R I V E R
NEW RIVER
AIR STATION
SCALE OF FEET
( IN FEET )
GRAPHIC SCALE
06000 6000 12000 240003000
LANDFILL
PWD/ROICC
OFFICE
BLDG 1005
DRMO
RIVER
CHERRY POINT
Otway
Beaufort Morehead City
O C
E A
N
US 70
Goldsboro
Seven
Mt. Olive
US 70
Springs
Kinston Dover
Trenton
ComfortPink Hill
Tuscarora New Bern
Pollacksville
Maysville Havelock
OAK GROVE
Warsaw
Magnolia
Rosehill
US 117
Beulaville
Richlands
Jacksonville
Wallace
Burgaw
Words Corner
US 421
Verona
Dixon
Folkstone
Holly Ridge
CAMP LEJUENE
US
Hampstead
Scott Hill
Wilmington Leland
Acme Delco
BoltonUS 7 4 & 76
US 17
SwansboroNEW RIVER
NEUSE
A T
L A
N T
I
C
SCALE OF MILES
0 10 2010
VICINITY MAP - CAMP LEJEUNE, N.C.
DRAWING INDEX
CONTRACT # DRAWING # SHEET # TITLE
230032 60040127 T-1 LOCATION MAPS & DRAWING INDEX
230032 60040128 E-101 LEGEND, ABBREVIATIONS, & GENERAL NOTES
230032 60040129 E-102 EXISTING SITE UTILITIES
230032 60040130 E-103 DEMOLITION PLAN
230032 60040131 E-104 NEW WORK
230032 60040132 E-105 ONE LINE DIAGRAM, DEMOLITION
230032 60040133 E-106 ONE LINE DIAGRAM, NEW WORK
230032 60040134 E-107 DETAILS 1
230032 60040135 E-108 DETAILS 2
230032 60040136 E-109 DETAILS 3
BASE MAP - CAMP LEJEUNE, NC
AS128
AS205
AS214
AS240
AS209
AS1009
AS211
AS208
AS207
AS213
AS212
BAN
C
R O
FT ST
CURTIS RD.
SITE MAP - AS 211, MCAS NEW RIVER, NC
AutoCAD SHX Text
SHEET:
AutoCAD SHX Text 80091
AutoCAD SHX Text E1
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
SPEC#05-23-0032
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
SATISFACTORY TO:
AutoCAD SHX Text
APPROVED: PWO OR OICC:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text %%uJACKSONVILLE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LEJEUNE BLVD
AutoCAD SHX Text
TO WILMINGTON
AutoCAD SHX Text
VERONA LOOP ROAD
AutoCAD SHX Text
NEW RIVER INLET RD
AutoCAD SHX Text
RANGE RD
AutoCAD SHX Text
DIXON-SNEADS FERRY RD
AutoCAD SHX Text
OCEAN DRIVE
AutoCAD SHX Text
BEACH RD
AutoCAD SHX Text
MARINES RD
AutoCAD SHX Text
LYMAN RD
AutoCAD SHX Text
WALLACE CREEK RD
AutoCAD SHX Text
PINEY GREEN RD
AutoCAD SHX Text
HOLCOMB BLVD
AutoCAD SHX Text
BREWSTER BLVD
AutoCAD SHX Text
CURTIS
AutoCAD SHX Text
STONE ST
AutoCAD SHX Text
STONE BAY
AutoCAD SHX Text
FRENCH
AutoCAD SHX Text
CREEK
AutoCAD SHX Text
MAIN SERVICE RD
AutoCAD SHX Text
INTRACOASTAL WATERWAY
AutoCAD SHX Text %%uSNEADS FERRY
AutoCAD SHX Text
MEANS HIGH WATER +1.10
AutoCAD SHX Text
MEANS SEA LEVEL 0.00
AutoCAD SHX Text
MEANS LOW WATER +0.35
AutoCAD SHX Text
LEJEUNE RAILROAD
AutoCAD SHX Text
CAMP
AutoCAD SHX Text
SEABOARD COAST LINE RAILROAD
AutoCAD SHX Text
SNEADS FERRY RD
AutoCAD SHX Text
SETH
AutoCAD SHX Text
WALLACE
AutoCAD SHX Text
CREEK
AutoCAD SHX Text
SOUTHWEST CREEK
AutoCAD SHX Text
WILSON
AutoCAD SHX Text
BAY
AutoCAD SHX Text
TRAPS
AutoCAD SHX Text
BAY
AutoCAD SHX Text
CHADWICK
AutoCAD SHX Text
BAY
AutoCAD SHX Text
HOWARD BAY
AutoCAD SHX Text
COURTHOUSE
AutoCAD SHX Text
BAY
AutoCAD SHX Text
ELLIS
AutoCAD SHX Text
COVE
AutoCAD SHX Text
TO
AutoCAD SHX Text
MOREHEAD CITY
AutoCAD SHX Text
BEAR
AutoCAD SHX Text
CREEK
AutoCAD SHX Text
BEAR
AutoCAD SHX Text
INLET
AutoCAD SHX Text
STONE
AutoCAD SHX Text
CREEK
AutoCAD SHX Text
MILL
AutoCAD SHX Text
STONE CREEK
AutoCAD SHX Text
CREEK
AutoCAD SHX Text
MUDDY
AutoCAD SHX Text
MILL CREEK
AutoCAD SHX Text
TOWN
AutoCAD SHX Text
CREEK
AutoCAD SHX Text
WHITE
AutoCAD SHX Text
HURST
AutoCAD SHX Text
CR.
AutoCAD SHX Text
SNEADS
AutoCAD SHX Text
FERRY
AutoCAD SHX Text
ROAD
AutoCAD SHX Text
TARAWA
AutoCAD SHX Text
TERRACE
AutoCAD SHX Text
KNOX
AutoCAD SHX Text
TR. PARK
AutoCAD SHX Text
MONTFORD
AutoCAD SHX Text
LANDING RD
AutoCAD SHX Text
MIDWAY
AutoCAD SHX Text
PARK
AutoCAD SHX Text
NAVAL
AutoCAD SHX Text
HOSPITAL
AutoCAD SHX Text
FRENCH
AutoCAD SHX Text
CREEK
AutoCAD SHX Text
AREA
AutoCAD SHX Text
MAGAZINE
AutoCAD SHX Text
AREA
AutoCAD SHX Text
HADNOT
AutoCAD SHX Text
POINT
AutoCAD SHX Text
AREA
AutoCAD SHX Text
INDUSTRIAL
AutoCAD SHX Text
AREA
AutoCAD SHX Text
PARADISE
AutoCAD SHX Text
POINT
AutoCAD SHX Text
AREA
AutoCAD SHX Text
RIFLE
AutoCAD SHX Text
RANGE
AutoCAD SHX Text
AMPHIBIAN
AutoCAD SHX Text
BASE
AutoCAD SHX Text
ENGINEER
AutoCAD SHX Text
AREA
AutoCAD SHX Text
TRIANGLE
AutoCAD SHX Text
OUTPOST
AutoCAD SHX Text
BEACH
AutoCAD SHX Text
AREA
AutoCAD SHX Text
BERKELEY
AutoCAD SHX Text
MANOR
AutoCAD SHX Text
WATKINS
AutoCAD SHX Text
VILLAGE
AutoCAD SHX Text
CAMP
AutoCAD SHX Text
GEIGER
AutoCAD SHX Text
CAMP
AutoCAD SHX Text
GEIGER
AutoCAD SHX Text
BROWNS
AutoCAD SHX Text
INLET
AutoCAD SHX Text
EVERETT CREEK
AutoCAD SHX Text
WILLI
AutoCAD SHX Text
AMS
AutoCAD SHX Text
BLVD
AutoCAD SHX Text
GOLF
AutoCAD SHX Text
COURSE
AutoCAD SHX Text
SWAMP
AutoCAD SHX Text
BELL
AutoCAD SHX Text
CREEK
AutoCAD SHX Text
FREEMAN
AutoCAD SHX Text
ROAD
AutoCAD SHX Text
BRINSON CREEK
AutoCAD SHX Text
HOPE ROAD
AutoCAD SHX Text
RIVER
AutoCAD SHX Text
ROAD
AutoCAD SHX Text
DUCK CREEK
AutoCAD SHX Text
HOLCOMB
AutoCAD SHX Text
GATE
AutoCAD SHX Text
MONTFORD
AutoCAD SHX Text
POINT
AutoCAD SHX Text
AREA
AutoCAD SHX Text
PAVILION
AutoCAD SHX Text
MARINA
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
OWL
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
LHA
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
ORIOLE
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
SANDPIPER
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
EGRET
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
CANARY
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
DOVE
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
PLOVER
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
HERON
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
DODO
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
GOOSE
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
FALCON
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
OSPREY
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
QUAIL
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
ALBATROSS
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
BLUEBIRD
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
JAYBIRD
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
CRANE
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
GULL
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
PENGUIN
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
LARK
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
PIGEON
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
TERN
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
COOT
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
SWAN
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
WOODPECKER
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
ROBIN
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
SPARROW
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
MALLARD
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
KIWI
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
CONDOR
AutoCAD SHX Text L
AutoCAD SHX Text T
AutoCAD SHX Text Z
AutoCAD SHX Text
CARDINAL
AutoCAD SHX Text
FRENCH CREEK BORROW PIT
AutoCAD SHX Text
GENERATOR REPLACEMENT AT AS211
AutoCAD SHX Text
MCB CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
SNEADS FERRY RD
AutoCAD SHX Text
AS 211 SITE MAP
AutoCAD SHX Text
AS 211
AutoCAD SHX Text
NOT TO SCALE
FINAL E-101
D. POKHREL
D. POKHREL
J. SIDES, PE
D. POKHREL
J. ORR, PE
PWO 05/02/2024
GENERATOR REPLACEMENT
AT AS211
LEGEND, ABBREVIATIONS, & GENERAL NOTES
60040128 23-0032
NOTED 2 10
ELECTRICAL GENERAL NOTESELECTRICAL LEGEND
SYMBOL DESCRIPTION
1. ALL ELECTRICAL WORK MUST BE IN FULL COMPLIANCE WITH NFPA 70, UFCs, ALL
LOCAL CODES AND ORDINANCES AND IN ACCORDANCE WITH THE REQUIREMENTS
OF THE LOCAL AUTHORITY HAVING JURISDICTION.
2. CONTRACTOR MUST FIELD VERIFY ALL EXISTING UTILITY CONDITIONS AND
PERFORM UTILITY LOCATES PRIOR TO BEGINNING ANY WORK. DRAWINGS ARE A
FUNCTIONAL REPRESENTATION OF RELEVANT SCOPE SPECIFIC CONDITIONS AND
INTENDED FOR GENERAL INFORMATION USE ONLY. ALL UTILITIES IN THE AREA
ARE *NOT* INDICATED ON THE DRAWINGS. DO NOT USE DIGGERS OR TRENCHES
UNTIL A THOROUGH REVIEW OF SITE CONDITIONS AND UTILITY LOCATES ARE
PERFORMED. DO NOT CUT THROUGH ANY EXISTING UTILITIES. FIELD VERIFY ALL
ELECTRICAL CHARACTERISTICS AND SYSTEM VOLTAGES BEFORE ORDERING
MATERIALS OR BEGINNING WORK.
3. ALL EQUIPMENT PROVIDED BY THE CONTRACTOR MUST BE LISTED AND LABELED
BY A NATIONALLY-RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE
AUTHORITY HAVING JURISDICTION, FOR THE CONDITIONS OF INSTALLATION. ALL
MATERIAL, EQUIPMENT AND DEVICES MUST BE NEW CURRENT PRODUCTS OF
MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH
PRODUCTS. EQUIPMENT MUST BE SUITABLE FOR ITS APPLICATION (E.G. WHEN
INSTALLED OUTDOORS, IT MUST BE WEATHERPROOF, ETC.)
4. THE CONTRACTOR MUST REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR
WORK REQUIREMENTS, THE AMOUNT OF SPACE AVAILABLE FOR ELECTRICAL
EQUIPMENT, AND LAYOUT HIS WORK IN A COMPATIBLE AND FUNCTIONAL MANNER.
5. UNLESS SPECIFICALLY NOTED OTHERWISE, SYSTEMS PROVIDED OR INSTALLED
BY THE CONTRACTOR MUST BE COMPLETE AND FULLY-FUNCTIONING AFTER
INSTALLATION. INCIDENTAL COMPONENTS MAY NOT BE SHOWN, AND ALL WORK
WHICH MAY BE REASONABLY IMPLIED AS BEING INCIDENTAL TO THIS WORK, BUT
REQUIRED FOR THE PROPER OPERATION OF THE EQUIPMENT OR SYSTEM MUST
BE PROVIDED BY THE CONTRACTOR AND INCLUDED IN THE BID. ADDITIONAL
CIRCUITS MUST BE INSTALLED WHEREVER NEEDED TO CONFORM TO THE
SPECIFIC REQUIREMENTS OF EQUIPMENT.
6. TEMPORARY POWER CONNECTIONS AS REQUIRED MUST BE PROVIDED BY THE
CONTRACTOR AND INCLUDED IN THE BID. ALL TEMPORARY EQUIPMENT WIRING
MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. THE
CONTRACTOR MUST PROVIDE DETAILS, METHODS, MATERIALS, ETC. FOR REVIEW
PRIOR TO MAKING TEMPORARY CONNECTIONS. FURNISH AND INSTALL ALL
EQUIPMENT AND MATERIALS INCLUDING CONTROL EQUIPMENT, MOTOR
STARTERS, BRANCH AND FEEDER CIRCUIT BREAKERS, PANELBOARDS,
TRANSFORMERS, ETC. FOR TEMPORARY POWER. COORDINATE WITH THE UTILITY
PROVIDER AS REQUIRED.
7. THE WORK MUST INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING
AT THE COMPLETION OF WORK AND ANY MINOR CORRECTIONS, CHANGES OR
ADJUSTMENTS NECESSARY FOR THE PROPER FUNCTIONING OF THE SYSTEM AND
EQUIPMENT.
8. ALL ELECTRICAL EQUIPMENT MUST, AT ALL TIMES DURING CONSTRUCTION, BE
ADEQUATELY PROTECTED AGAINST MECHANICAL INJURY, OR DAMAGE BY WATER
AND/OR THE ELEMENTS. ELECTRICAL EQUIPMENT MUST NOT BE STORED OUT OF
DOORS, BUT MUST BE STORED IN DRY PERMANENT SHELTERS. IF AN APPARATUS
HAS BEEN DAMAGED, OR HAS BEEN SUBJECT TO POSSIBLE INJURY BY WATER OR
THE ELEMENTS, SUCH DAMAGE MUST BE REPLACED AT NO ADDITIONAL COST.
9. DO NOT SCALE ELECTRICAL DRAWINGS. CONTRACTOR MUST FIELD VERIFY ALL
DIMENSIONS.
10. CIRCUIT LAYOUTS ARE NOT INTENDED TO SHOW THE NUMBER OF FITTINGS, OR
OTHER INSTALLATION DETAILS. UNLESS NOTED OTHERWISE, THE EXACT
ROUTING OF FEEDER AND BRANCH CIRCUIT RACEWAYS AND CABLES IS THE
RESPONSIBILITY OF THE CONTRACTOR. RISER AND GENERAL CIRCUIT
ARRANGEMENTS ARE SHOWN SCHEMATICALLY/DIAGRAMMATICALLY ONLY. THE
CONTRACTOR MUST ROUTE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE
INSTALLATION.
11. DEVICE LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE. ADJUST
EXACT LOCATIONS AS REQUIRED TO SERVE THE INTENDED PURPOSE AND TO
AVOID CONFLICTS AND INTERFERENCES WITH OTHER TRADES. IF NOT SHOWN ON
THE ARCHITECTURAL DRAWINGS OR DIMENSIONED ON THE ELECTRICAL
DRAWINGS, VERIFY EXACT LOCATION WITH THE GOVERNMENT PRIOR TO
ROUGH-IN.
12. CONDUIT TERMINATING IN PRESSED STEEL BOXES MUST HAVE DOUBLE
LOCKNUTS AND INSULATED BUSHINGS. CONDUITS TERMINATING IN GASKETED
ENCLOSURES MUST BE TERMINATED WITH GROUNDING TYPE CONDUIT HUBS.
13. BRANCH CIRCUIT HOMERUNS SHOWN ON DRAWINGS INDICATE PHASE
CONDUCTORS, NEUTRAL, EQUIPMENT GROUND CONDUCTORS AS REQUIRED.
ADDITIONAL CONDUCTORS REQUIRED FOR CONTROL MUST BE INCLUDED EVEN IF
NOT EXPLICITLY SHOWN.
14. SEAL ALL CONDUIT OPENINGS THROUGH EXTERIOR BUILDING WALLS AND ROOF
WATERTIGHT.
15. IN WET LOCATIONS AND EXTERIOR, ALL WIRING DEVICES MUST BE
WEATHER-RESISTANT LISTED WITH WEATHERPROOF WHILE IN USE COVER.
16. RACEWAYS PENETRATING FLOORS, CEILINGS OR WALLS MUST BE PROPERLY
SEALED SMOKETIGHT.
17. ALL RACEWAYS MUST BE CONCEALED WHERE POSSIBLE.
18. INSTALL EXPOSED RACEWAYS PARALLEL TO OR AT RIGHT ANGLES TO NEARBY
SURFACES OR STRUCTURAL MEMBERS, AND FOLLOW THE SURFACE CONTOURS
AS MUCH AS POSSIBLE. NO DIAGONAL RUNS WILL BE ALLOWED. ALL CONDUITS
MUST BE RUN STRAIGHT WITH QUALITY WORKMANSHIP-LIKE MANNER. RUN
PARALLEL OR BANKED RACEWAYS TOGETHER ON COMMON SUPPORTS WHERE
PRACTICAL. MAKE BENDS IN PARALLEL OR BANKED RUNS FROM SAME
CENTERLINE TO MAKE BENDS PARALLEL.
19. PATCHING OF WATERPROOFED SURFACES MUST RENDER THE AREA OF THE
PATCHING COMPLETELY WATERPROOF.
20. ALL MOTORS AND OTHER VIBRATING EQUIPMENT MUST BE CONNECTED TO THE
CONDUIT SYSTEM BY MEANS OF A SHORT SECTION (18 INCH MINIMUM) OF
FLEXIBLE CONDUIT UNLESS OTHERWISE INDICATED. AN EQUIPMENT GROUNDING
CONDUCTOR MUST BE INSTALLED INSIDE THE FLEXIBLE CONDUIT AND TERMINATE
AT THE LOAD END WITH AN APPROVED GROUNDING CLAMP OR LUG.
21. SURFACE MOUNTED PANELBOARDS, JUNCTION, OUTLET AND PULL BOXES,
RACEWAYS, ETC., INSTALLED ON EXTERIOR SURFACES OR INSIDE ON EXTERIOR
WALLS MUST BE SUPPORTED BY SPACERS TO PROVIDE A MINIMUM 1/4" MINIMUM
CLEARANCE BETWEEN THE WALL AND EQUIPMENT.
22. TYPED PANELBOARD DIRECTORIES INSTALLED IN THE PANELBOARD DOOR
POCKET MUST REFLECT FINAL CONDITIONS AND ACTUAL ROOM NAMES AND
NUMBERS IN ADDITION TO THE GENERAL DESCRIPTION SHOWN ON THE PANEL
SCHEDULES ON THE DRAWINGS.
23. THE CONTRACTOR MUST VERIFY, PRIOR TO INSTALLATION OF CONDUCTORS OR
CONDUIT FEEDING ANY EQUIPMENT, THE ELECTRICAL EQUIPMENT IS RATED FOR
USE WITH 75 DEGREE C. WIRING. IF ANY EQUIPMENT IS RATED FOR USE WITH
LESS THAN 75 DEGREE C. CONDUCTORS, THE CONTRACTOR MUST NOTIFY THE
GOVERNMENT IMMEDIATELY FOR EVALUATION/CORRECTION.
24. DO NOT PULL CONDUCTORS UNTIL THE CONDUIT SYSTEM IS COMPLETE IN EVERY
DETAIL. IN THE CASE OF CONCEALED WORK, "COMPLETE" MEANS UNTIL ALL
ROUGH PLASTERING OR MASONRY HAS BEEN COMPLETED.
25. WHERE SIZE IS NOT SHOWN ON THE DRAWINGS, BRANCH CIRCUITS MUST
CONSIST OF #12 OR #10 AWG MINIMUM PHASE, NEUTRAL AND EQUIPMENT
GROUND CONDUCTORS IN 3/4” MINIMUM RACEWAY.
26. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS WITH A
TOTAL INSTALLED LENGTH GREATER THAN 75 FEET AND/OR BRANCH CIRCUIT
HOMERUNS LONGER THAN 50 FEET, I.E.; #12 AWG INCREASED TO #10 AWG FOR
RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH (INCLUDING THE
HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET. IF 277 VOLT CIRCUITS ARE
SHOWN, USE #10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH
CIRCUITS WITH TOTAL INSTALLED LENGTH GREATER THAN 200 FEET AND/OR
BRANCH CIRCUIT HOMERUNS LONGER THAN 125 FEET, I.E.; #12 AWG INCREASED
TO #10 AWG FOR RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH
(INCLUDING THE HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET.
27. KEEP CONDUCTOR SPLICES TO A MINIMUM. INSTALL SPLICES AND TAPES THAT
POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION
RATINGS THAN CONDUCTORS BEING SPLICED. USE SPLICE AND TAP
CONNECTORS COMPATIBLE WITH CONDUCTOR MATERIAL. INSTALL CONDUCTORS
AT EACH OUTLET WITH AT LEAST 6 INCHES OF SLACK. CONNECT OUTLETS AND
COMPONENTS TO WIRING AND TO GROUND AS INDICATED AND INSTRUCTED BY
THE MANUFACTURER.
28. DO NOT SPLICE BRANCH CIRCUIT HOMERUNS WITHOUT THE PERMISSION OF THE
GOVERNMENT. HOMERUNS MUST BE CONTINUOUS FROM THE LAST OUTLET BOX
TO THE SERVING PANELBOARD.
29. DO NOT COMBINE BRANCH CIRCUIT HOMERUNS UNLESS SPECIFICALLY INDICATED
ON THE DRAWINGS.
30. DO NOT CHANGE CIRCUITING SHOWN WITHOUT PERMISSION OF THE
GOVERNMENT.
31. INSTALL WIRING DEVICES AT HEIGHTS AS SHOWN ON THE DRAWINGS.
32. PROTECT ALL EXISTING POWER, COMMUNICATIONS, DATA, LIFE SAFETY SYSTEMS,
FIRE ALARM AND PUBLIC ADDRESS SYSTEMS AND MAINTAIN THEM IN OPERATION
THROUGHOUT THE PROGRESS OF THE WORK. NOTIFY THE GOVERNMENT IF
SHUTDOWNS ARE REQUIRED PRIOR TO ANY OUTAGE OF SERVICE. WHERE THE
DURATION OF A PROPOSED OUTAGE CANNOT BE TOLERATED BY THE
GOVERNMENT, PROVIDE TEMPORARY CONNECTIONS AS REQUIRED TO MAINTAIN
SERVICE.
33. PROVIDE GROUND FAULT CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL
IN ACCORDANCE WITH THE NEC INCLUDING EXTERIOR RECEPTACLES AND
RECEPTACLES IN AREAS SUBJECT TO POSSIBLE WET CONDITIONS.
34. COORDINATE LOCATIONS OF MECHANICAL EQUIPMENT WITH THE RESPECTIVE
CONTRACTOR, VENDORS AND THE GOVERNMENT BEFORE ROUGH-IN. ADJUST
LIGHTING FIXTURES, RECEPTACLES AND ELECTRICAL EQUIPMENT TO
ACCOMMODATE THIS EQUIPMENT. ADVISE THE GOVERNMENT OF CONFLICTS
BEFORE ROUGH-IN.
35. BEFORE COMMENCING WORK OR ORDERING MATERIALS, THE CONTRACTOR MUST
COORDINATE WITH OTHER TRADES AND VERIFY THE NAMEPLATE RATINGS OF ALL
EQUIPMENT (MOTORS, HEATERS, COMPRESSORS, ETC.) AND ADJUST THE
RATINGS OF THE ELECTRICAL EQUIPMENT (SWITCHES, FUSES, CIRCUIT
BREAKERS, FEEDERS, ETC.) AS APPROPRIATE TO SERVE THIS EQUIPMENT.
36. ENERGIZE EQUIPMENT ONLY AFTER OBTAINING PERMISSION FROM THE
CONTRACTOR PROVIDING THE EQUIPMENT.
37. UNLESS SPECIFICALLY NOTED OTHERWISE, THE CONTRACTOR MUST MAKE FINAL
CONNECTIONS TO ALL UTILIZATION EQUIPMENT SHOWN ON THE DRAWINGS.
VERIFY THE TYPE OF FINAL CONNECTION AND PROVIDE APPROPRIATE WIRING
METHOD. THE CONTRACTOR MUST COORDINATE WITH THE MECHANICAL TRADE,
PRIOR TO ORDERING OR INSTALLATION OF ANY EQUIPMENT, TO VERIFY
MECHANICAL EQUIPMENT REQUIREMENTS ARE PROVIDED IN THE ELECTRICAL
DESIGN. THE CONTRACTOR WILL NOT BE COMPENSATED FOR COSTS
ASSOCIATED WITH CHANGING THE ELECTRICAL SYSTEMS TO MATCH UTILIZATION
EQUIPMENT, EVEN IF THE ELECTRICAL WORK IS INSTALLED PER THE ELECTRICAL
DRAWINGS.
38. THE CONTRACTOR MUST COORDINATE ALL EQUIPMENT TERMINATIONS, PLUGS
AND CORDSETS WITH VENDOR EQUIPMENT AND VERIFY ALL DEVICE LOCATIONS
FOR SPECIALITY EQUIPMENT WITH CASEWORK PRIOR TO ROUGH-IN.
39. INSTALLATION INFORMATION PACKED WITH DEVICES AND EQUIPMENT MUST BE
RETAINED FOR INCLUSION IN THE OPERATIONS AND MAINTENANCE MANUALS.
40. THE CONTRACTOR MUST VISIT THE SITE AND BECOME FAMILIAR WITH THE
EXISTING ELECTRICAL SYSTEMS AND THE EXISTING BUILDING. THE SUBMISSION
OF THE PROPOSAL BY THE CONTRACTOR SHALL BE CONSIDERED EVIDENCE THAT
HE OR HIS REPRESENTATIVE HAS VISITED THE SITE AND BUILDINGS AND NOTED
THE LOCATION AND CONDITIONS UNDER WHICH THE WORK WILL BE PERFORMED
AND THAT HE TAKES FULL RESPONSIBILITY OF ALL FACTORS GOVERNING HIS
WORK. NO EXTRAS WILL BE CONSIDERED BECAUSE OF ADDITIONAL WORK
NECESSITATED BY EXISTING JOB CONDITIONS THAT ARE NOT INDICATED ON THE
DRAWINGS.
41. SAFETY
A. COMPLY WITH OSHA AND NEC ARC FLASH PROTECTION REQUIREMENTS.
B. FOR EQUIPMENT BEING REMOVED AND REPLACED, THE CONTRACTOR SHALL
DE-ENERGIZE THE EQUIPMENT AND MAKE IT SAFE PRIOR TO REMOVAL AND
COMPLY WITH OSHA REQUIREMENTS FOR LOCKING-OUT AND TAGGING
EQUIPMENT TO PREVENT INADVERTENT RE-ENERGIZING.
ABBREVIATIONS
PAD MOUNTED TRANSFORMER WITH KWH METER
DEMOLITION
POLE MOUNTED TRANSFORMER
ELECTRICAL SWITCH POINT, FUSE CUTOUT
ELECTRICAL RISER POINT
EXISTING UTILITY POLE
EXTERIOR LIGHTING
"EQUIPMENT NAME"
SOURCE: PANEL "###"
SOURCE LOCATION "###"
RATING: ### AMPS
VOLTAGE: 208/120V, 3Ø, 4WRATING DESIGNATION 1/4" WHITE
ENGRAVED LETTERS
SOURCE DESIGNATION 1/4" WHITE
ENGRAVED LETTERS
EQUIPMENT DESIGNATION 3/8" WHITE
ENGRAVED LETTERS
VOLTAGE & PHASE DESIGNATION 1/4" WHITE
ENGRAVED LETTERS
Arc Flash and Shock Hazard Appropriate PPE required
NOTES:
1. LABEL SHOWN CAN BE SOURCED FROM SAFETYSIGN.COM, OTHER SUPPLIERS ARE
COMPLIANTSIGNS.COM & SETON.COM
2. THIS WARNING LABEL MINIMALLY COMPLIES WITH NEC, HOWEVER IF ELECTRICAL
EQUIPMENT IS LIKELY TO REQUIRE EXAMINATION OR MAINTENANCE WHILE
ENERGIZED A DETAILED SHORT CIRCUIT AND ARC FLASH HAZARD ANALYSIS IS
RECOMMENDED.
BLACK LETTERS ON WHITE
BACKGROUND
NOT TO SCALE1 ELECTRICAL EQUIPMENT WARNING LABEL DETAIL
BLACK LETTERS AND SYMBOL ON
SAFETY ORANGE BACKGROUND
MACHINE SCREW WITH ACORN NUT AND
LOCKWASHER, TYP.
SOURCE LOCATION DESIGNATION 1/4"
WHITE ENGRAVED LETTERS
NOTE: SEE SPECS. SECTION 260553 FOR NAMEPLATE MATERIAL
AND ENGRAVING COLORS.
NOT TO SCALE3 TYPICAL EQUIPMENT NAMEPLATE DETAIL
WARNING
4 1/2" MINIMUM
7/
8" M
IN
IM
U M
3/
4"
G GENERATOR ON A CONCRETE PAD
AUTOMATIC TRANSFER SWITCH, 4P, 3 PHASE
DISCONNECT SWITCH
JUNCTION BOX, WALL MOUNTED
COMMUNICATION MANHOLE
COMMUNICATION RISER POINT
CIRCUIT BREAKER
ELECTRICAL PANEL
EX. PRIMARY ELECTRIC CABLE, UNDERGROUND
EX. SECONDARY ELECTRIC CABLE, UNDERGROUND
EX. PRIMARY ELECTRIC CABLE, OVERHEAD
EX. SECONDARY ELECTRIC CABLE, OVERHEAD
UG UG
EOS
EX. ELECTRIC CABLE, SURFACE MOUNTED
WASTEWATER CLEANOUT POINT
WASTE WATER MANHOLE
COMMUNICATION SPEAKER
MANHOLE, STORM WATER
VALVE, WASTEWATER
FIRE HYDRANT
WATER VALVE
WASTE WATER, GRAVITY MAIN
WATER LINE, POTABLE
STORM WATER PIPE
WASTE WATER, LATERAL
COMMUNICATION LINE
FENCEX X X
OAK TREE
D.S
CB
AS
MH
EX
PMT
KVA
MDP
ATS
KWH
KW
CND
GND
CU
DISCONNECT SWITCH
CIRCUIT BREAKER
AIR STATION, NEW RIVER
MAN HOLE
EXISTING
PAD MOUNTED TRANSFORMER
KILO-VOLT-AMPERE
MAIN DISTRIBUTION PANEL
AUTOMATIC TRANSFER SWITCH
KILO WATT HOUR
ELECTRICAL PHASE
KILO WATT
CONDUIT
GROUND WIRE
COPPER
ɸ
SD SERVICE DISCONNECT
PULL BOX, WALL MOUNTED
COMMUNICATION TOWER
HH HAND HOLE
NEW UNDERGROUND SECONDARY
NEW UNDERGROUND PRIMARY
AutoCAD SHX Text
SYM.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
SHEET:
AutoCAD SHX Text 80091
AutoCAD SHX Text E1
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
SPEC#05-23-0032
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
SATISFACTORY TO:
AutoCAD SHX Text
APPROVED: PWO OR OICC:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text E
AutoCAD SHX Text
ATS
AutoCAD SHX Text D.S
AutoCAD SHX Text C
AutoCAD SHX Text
SS
AutoCAD SHX Text D
AutoCAD SHX Text J
P
XXXXX
X
X X
X X
X X X X X X X X X X X X
X X
X X
X
XXXXX
X X
X
X X X X X X X X X X X X X X X X X X
X X
X X
X X
AS211
AS212
1-47-10
MH-H
MHG-1
HHG-1-1
MH AS202
MH AS201
UG
UG
EO
S
EO
S
EOS
EOS
EOS
EOS
EO
S
EO
S
EO
S
EO
S
UG UG UG UG
UG
U G
U G
U G
U G
U G
U G
U G
U G
U G
U G
U G
U G
U G
U G
U G
U G
U G
U G
10''
3''
CONST. CONTR. NO.
FINAL E-102
D. POKHREL
D. POKHREL
J. SIDES, PE
D. POKHREL
J. ORR, PE
PWO or OICC 05/02/2024
GENERATOR REPLACEMENT
AT AS211
EXISTING SITE UTILITIES
60040129 23-0032
NOTED 3 10
TENNIS COURT
VEHICLE PARKING
G
G
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text
SS
AutoCAD SHX Text
SS
AutoCAD SHX Text
SS
AutoCAD SHX Text
SS
AutoCAD SHX Text
SS
AutoCAD SHX Text
SS
AutoCAD SHX Text
SHEET:
AutoCAD SHX Text 80091
AutoCAD SHX Text E1
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
SPEC#05-23-0032
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
SATISFACTORY TO:
AutoCAD SHX Text
APPROVED: PWO OR OICC:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text E
AutoCAD SHX Text NOTES: 1. THE LOCATION AND DEPTHS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SCANNING THE AREA OF THE LOCATION AND DEPTHS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SCANNING THE AREA OF WORK TO IDENTIFY TO THEIR OWN SATISFACTION THE EXTENT OF UTILITIES PRESENT INCLUDING THE UTILITIES INDICATED TO BE PRESENT, THOSE NOT SHOWN, AND THOSE SHOWN TO BE IN DIFFERENT LOCATION. 2. MINIMIZATION OF POWER OUTAGES IS A REQUIREMENT DURING CONSTRUCTION BECAUSE OF THE NATURE OF THE BUILDING. PROVIDE A TEMPORARY MINIMIZATION OF POWER OUTAGES IS A REQUIREMENT DURING CONSTRUCTION BECAUSE OF THE NATURE OF THE BUILDING. PROVIDE A TEMPORARY GENERATOR IF THE POWER OUTAGE IS LONGER THAN 48 HOURS. 3. ALL AREAS DISTURBED DURING CONSTRUCTION MUST BE RESTORED. ALL AREAS DISTURBED DURING CONSTRUCTION MUST BE RESTORED. 4. ALL VOIDS OR DEPRESSIONS CREATED BY REMOVAL OF STRUCTURES OR SURFACES MUST BE BACKFILLED WITH COMMON FILL AND GRADED TO PROVIDE ALL VOIDS OR DEPRESSIONS CREATED BY REMOVAL OF STRUCTURES OR SURFACES MUST BE BACKFILLED WITH COMMON FILL AND GRADED TO PROVIDE POSITIVE DRAINAGE.
AutoCAD SHX Text
EXISTING SITE UTILITIES NOT TO SCALE
AutoCAD SHX Text
SYM.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
APPROVED
REVISIONS
FINAL E-103
D. POKHREL
D. POKHREL
J. SIDES, PE
D. POKHREL
J.F. ORR, PE
PWO 05/02/2024
GENERATOR REPLACEMENT
AT AS211
DEMOLITION PLAN
60040130 23-0032
NOTED 4 10
UG
UG UG UG UG UG UG UG
UG UG UG UG UG UG
G
AutoCAD SHX Text
SHEET:
AutoCAD SHX Text 80091
AutoCAD SHX Text E1
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
SPEC#05-23-0032
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
SATISFACTORY TO:
AutoCAD SHX Text
APPROVED: PWO OR OICC:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text
AS211
AutoCAD SHX Text D.S
AutoCAD SHX Text
ATS
AutoCAD SHX Text
EX. 400A 4 POLE ATS
AutoCAD SHX Text
EX. 24"X24" PULLBOX TO REMAIN
AutoCAD SHX Text EX. 500kVA TRANSFORMER W/ CB-1200A
AutoCAD SHX Text
EX. DISCONECT SWITCH
AutoCAD SHX Text
EX. 400A DISTRIBUTION PANEL TO REMAIN
AutoCAD SHX Text
EX. 1200A MAIN DISTRIBUTION PANEL TO REMAIN REMOVE GROUND-NEUTRAL BOND
AutoCAD SHX Text
EX. UTILITY POLE (72107-44743) WITH FUSE CUTOUTS
AutoCAD SHX Text EX. 120kW GENERATOR
AutoCAD SHX Text
ELECTRICAL ROOM
AutoCAD SHX Text
EX. SIDEWALK
AutoCAD SHX Text
EX. 11" LIVE OAK TREE
AutoCAD SHX Text
EX. 30"X30" JUNCTION BOX
AutoCAD SHX Text
EX. CHILLER
AutoCAD SHX Text DEMOLITION NOTES: DISCONNECT THE EX. PRIMARY FEEDER TOP THE EX. PAD MOUNTED TRANSFORMER. REMOVE EX. MEDIUM VOLTAGE INCLUDING RISER CONDUIT, FUSED CUTOUTS, SURGE ARRESTORS AND MOUNTING HARDWARE FOR THE UNDERGROUND PRIMARY FEEDER. REMOVE EX. PRIMARY CONDUCTORS FROM EX. CUTOUTS ON EX. UTILITY POLE (72107-44743) TO EX. 500KVA PAD MOUNTED TRANSFORMER. ABANDON EXISTING CONCRETE ENCASED DUCT BANK AND CONDUITS IN PLACE. DISCONNECT AND REMOVE EX. 500kVA PAD MOUNTED TRANSFORMER, CB-1200A, AND EX. CONCRETE PAD. DISCONNECT AND REMOVE EXISTING SECONDARY CONDUCTORS, CONDUITS AND DUCTBANK FROM CB-1200A TO EX. 36X36 JUNCTION BOX. EX. PAD MOUNTED TRANSFORMER SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND THE CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OFF-SITE IN ACCORDANCE WITH ALL LAWS AND REQUIREMENTS. DEMOLISH EX. METER BASE AND CURRENT TRANSFORMERS. PROTECT THE KWH METER FOR REINSTALLATION. DISCONNECT EXISTING CONDUCTORS IN EX. 30X30 JUNCTION BOX (FROM CB-1200 TO EX. 1200A MDP). DISCONNECT AND REMOVE EXISTING CONDUCTORS AND CONDUIT FROM THE JUNCTION BOX TO EX. 400A DISCONNECT SWITCH. REMOVE THE 30X30 JUNCTION BOX. PROTECT THE CONDUCTORS TO THE 1200 MDP TO BE SPLICED DURING INSTALLATION OF NEW JUNCTION BOX. REMOVE GROUND-NEUTRAL BOND IN THE 1200A MDP. REMOVE CONDUITS AND CONDUCTORS FROM UNUSED 100A CIRCUIT BREAKER LABELED 'PANEL 2B'. EX. ATS TO BE REMOVED AND TURNED IN TO THE GOVERNMENT. CONTACT RANDY GURSSLIN AT SHOP 82 (910-546-0480). DEMOLISH CONDUITS BUT PROTECT THE CONDUCTORS FROM ATS TO 24X24 PULLBOX, TO BE REINSTALLED BY THE CONTRACTOR DURING CONSTRUCTION. DISCONNECT AND REMOVE EX. 120KW GENERATOR WITH ASSOCIATED CONDUCTORS, CONDUITS, AND APPURTENANCES. GENERATOR TO BE TURNED IN TO THE GOVERNMENT. CONTACT RANDY GURSSLIN AT SHOP 82 (910-546-0480). REMOVE EXISTING 400A DISCONNECT SWITCH, CONDUITS AND CONDUCTORS. REMOVE EXISTING 12" AND 11' LIVE OAK TREE AND PREPARE THE AREA TO CONSTRUCT A GENERATOR CONCRETE PAD. SEE E-108 FOR GENERATOR PAD DETAILS. REMOVE 9" OAK TREE ONLY IF NEEDED.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EX. SURFACE MOUNTED CONDUITS, CONDUCTORS TO REMAIN
AutoCAD SHX Text
EX. SURFACE MOUNTED WIREWAY, CONDUCTORS TO REMAIN
AutoCAD SHX Text
DEMOLITION PLAN AS 211 NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text GENERAL NOTES: 1. THE LOCATION AND DEPTHS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE. THE CONTRACTOR SHALL BE THE LOCATION AND DEPTHS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SCANNING THE AREA OF WORK TO IDENTIFY TO THEIR OWN SATISFACTION THE EXTENT OF UTILITIES PRESENT INCLUDING THE UTILITIES INDICATED TO BE PRESENT, THOSE NOT SHOWN, AND THOSE SHOWN TO BE IN DIFFERENT LOCATION. 2. MINIMIZATION OF POWER OUTAGES IS A REQUIREMENT DURING CONSTRUCTION BECAUSE OF THE NATURE OF MINIMIZATION OF POWER OUTAGES IS A REQUIREMENT DURING CONSTRUCTION BECAUSE OF THE NATURE OF THE BUILDING. 3. PROVIDE A TEMPORARY GENERATOR IF A POWER OUTAGE IS ANTICIPATED TO EXCEED A DURATION OF FOUR PROVIDE A TEMPORARY GENERATOR IF A POWER OUTAGE IS ANTICIPATED TO EXCEED A DURATION OF FOUR (4) HOURS DURING REGULAR BUSINESS HOURS ON WEEKDAYS (MONDAY THROUGH FRIDAY); OR TWENTY-FOUR (24) HOURS DURING WEEKENDS (SATURDAY AND SUNDAY). 4. ALL AREAS DISTURBED DURING CONSTRUCTION MUST BE RESTORED. REPAIR DISTURBED VEGETATED AREAS ALL AREAS DISTURBED DURING CONSTRUCTION MUST BE RESTORED. REPAIR DISTURBED VEGETATED AREAS WITH CENTIPEDE SOD. 5. ALL VOIDS OR DEPRESSIONS CREATED BY REMOVAL OF STRUCTURES OR SURFACES MUST BE BACKFILLED ALL VOIDS OR DEPRESSIONS CREATED BY REMOVAL OF STRUCTURES OR SURFACES MUST BE BACKFILLED WITH COMMON FILL AND GRADED TO PROVIDE POSITIVE DRAINAGE.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SYM.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text J
AutoCAD SHX Text P
AutoCAD SHX Text
EX. 12" LIVE OAK TREE
AutoCAD SHX Text
EX. COMMUNICATION TOWER
AutoCAD SHX Text
AutoCAD SHX Text
EX. 9" LIVE OAK TREE
AutoCAD SHX Text
FINAL E-104
D. POKHREL
D. POKHREL
J. SIDES, PE
D. POKHREL
J. ORR, PE
PWO 05/02/2024
GENERATOR REPLACEMENT
AT AS211
NEW ELECTRICAL PLAN
60040131 23-0032
NOTED 5 10
G
AutoCAD SHX Text
SHEET:
AutoCAD SHX Text 80091
AutoCAD SHX Text E1
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
SPEC#05-23-0032
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
SATISFACTORY TO:
AutoCAD SHX Text
APPROVED: PWO OR OICC:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text
EX. 400A DISTRIBUTION PANEL
AutoCAD SHX Text
EX. 1200A MAIN DISTRIBUTION PANEL
AutoCAD SHX Text
EX. UTILITY POLE (72107-44743)
AutoCAD SHX Text
ELECTRICAL ROOM
AutoCAD SHX Text
EX. SIDEWALK
AutoCAD SHX Text
EX. CHILLER
AutoCAD SHX Text NEW WORK KEYED NOTES: PROVIDE A CONCRETE ENCASED UNDERGROUND DUCT BANK, CONDUITS AND CONDUCTORS COMPLETE. AVOID EXISTING UTILITIES. SEE SHEET E-106 AND E-107 FOR DETAILS. PROVIDE RISER CONDUIT, FUSED CUTOUTS, SURGE ARRESTORS AND MOUNTING HARDWARE ASSOCIATED WITH THESE DEVICES ON EXISTING UTILITY POLE (72107-44743). CONNECT PRIMARY CONDUCTORS FROM FUSED CUTOUTS TO THE NEW PAD MOUNTED TRANSFORMER. PROVIDE 350kW, 3ɸ, 208Y/120V DIESEL ENGINE GENERATOR ON A CONCRETE PAD WITH WIRING AND CONDUITS. PROVIDE A SUB BASE FUEL TANK, SIZED TO MEET A 96 HOURS RUNTIME AT 100% LOAD, AND ACCESS PLATFORM. FUEL PORTS OF THE TANK SHOULD FACE NORTH (TOWARDS AS211) FOR EASE OF ACCESS TO FUEL TRUCKS. FACE THE EXHAUST OF THE GENERATOR TOWARDS THE TENNIS COURT. PROVIDE AND CONNECT CONDUITS AND CONDUCTORS FROM GENERATOR TO NEW 1200A ATS. SEE SHEET E-106 AND E108 FOR GENERATOR AND GROUNDING DETAIL. PROVIDE A NEW 500KVA PAD MOUNTED TRANSFORMER ON A PRE-CAST CONCRETE PAD 5' AWAY FROM THE LOCATION OF OLD TRANSFORMER AS SHOWN. SEE SHEET E-106 AND E-107 FOR DETAILS. PROVIDE AND INSTALL A NEW METER BASE AND CURRENT TRANSFORMERS, BUT RE-USE EXISTING KWH METER PROTECTED DURING DEMOLITION. CONNECT PRIMARY CONDUCTORS TO THE TRANSFORMER. PROVIDE 1200A SERVICE DISCONNECT, CONDUIT, CONDUCTOR COMPLETE IN A NEMA 4X ENCLOSURE ON AN EQUIPMENT PAD. CONNECT SECONDARY CONDUCTORS FROM PMT TO THE SERVICE DISCONNECT. SEE SHEET E109 EQUIPMENT MOUNTING DETAIL, AND SHEET E-106 RISER DIAGRAM FOR CONNECTION DETAIL. PROVIDE 1200A, 4 POLE, 208Y/120V ATS, CONDUCTORS, CONDUIT COMPLETE IN A NEMA 3RX ENCLOSURE ON EQUIPMENT PAD. CONNECT EMERGENCY SIDE TO THE GENERATOR, AND NORMAL SIDE TO THE 1200A SERVICE DISCONNECT. SEE SHEET E-109 EQUIPMENT MOUNTING DETAIL, AND SHEET E-106 RISER DIAGRAM FOR CONNECTION DETAIL. PROVIDE A NEW NEMA 4X JUNCTION BOX, SIZED APPROPRIATELY. PROVIDE AND CONNECT NEW CONDUITS AND CONDUCTORS IN A DUCT BANK FROM 1200A ATS TO THE NEW JUNCTION BOX. SEE E-106 FOR WIRING, CONDUITS AND DUCT BANK REQUIREMENTS. CONNECT THE CONDUCTORS TO EX. 1200A MDP IN THE JUNCTION BOX. PROVIDE 2 SETS OF 3" CONDUIT FROM THE NEW JUNCTION BOX TO THE EXISTING PULL BOX. SPLICE THE PRESERVED CONDUCTORS DURING DEMOLITION IN THE JUNCTION BOX. SEE SHEET E-106.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NEW WORK PLAN AS 211 NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text GENERAL NOTES: 1. THE LOCATION AND DEPTHS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE. THE CONTRACTOR SHALL BE THE LOCATION AND DEPTHS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SCANNING THE AREA OF WORK TO IDENTIFY TO THEIR OWN SATISFACTION THE EXTENT OF UTILITIES PRESENT INCLUDING THE UTILITIES INDICATED TO BE PRESENT, THOSE NOT SHOWN, AND THOSE SHOWN TO BE IN DIFFERENT LOCATION. 2. MINIMIZATION OF POWER OUTAGES IS A REQUIREMENT DURING CONSTRUCTION BECAUSE OF THE NATURE OF MINIMIZATION OF POWER OUTAGES IS A REQUIREMENT DURING CONSTRUCTION BECAUSE OF THE NATURE OF THE BUILDING. 3. PROVIDE A TEMPORARY GENERATOR IF A POWER OUTAGE IS ANTICIPATED TO EXCEED A DURATION OF FOUR PROVIDE A TEMPORARY GENERATOR IF A POWER OUTAGE IS ANTICIPATED TO EXCEED A DURATION OF FOUR (4) HOURS DURING REGULAR BUSINESS HOURS ON WEEKDAYS (MONDAY THROUGH FRIDAY); OR TWENTY-FOUR (24) HOURS DURING WEEKENDS (SATURDAY AND SUNDAY). 4. ALL AREAS DISTURBED DURING CONSTRUCTION MUST BE RESTORED. REPAIR DISTURBED VEGETATED AREA ALL AREAS DISTURBED DURING CONSTRUCTION MUST BE RESTORED. REPAIR DISTURBED VEGETATED AREA WITH CENTIPEDE SOD. 5. ALL VOIDS OR DEPRESSIONS CREATED BY REMOVAL OF STRUCTURES OR SURFACES MUST BE BACKFILLED ALL VOIDS OR DEPRESSIONS CREATED BY REMOVAL OF STRUCTURES OR SURFACES MUST BE BACKFILLED WITH COMMON FILL AND GRADED TO PROVIDE POSITIVE DRAINAGE.
AutoCAD SHX Text
EX. PULLBOX TO REMAIN
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SYM.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
AutoCAD SHX Text
SEE RISER DIAGRAM SHEET E-106 FOR CONDUCTORS AND CONDUIT REQUIREMENTS
AutoCAD SHX Text
SEE RISER DIAGRAM SHEET E-106 FOR CONDUCTORS AND CONDUIT REQUIREMENTS
AutoCAD SHX Text
SEE SHEET E-106 FOR CONDUCTORS AND CONDUIT REQUIREMENTS
AutoCAD SHX Text
EX. COMMUNICATION TOWER
AutoCAD SHX Text J
AutoCAD SHX Text P
AutoCAD SHX Text
EX. 9" TREE (REMOVE IF NEEDED)
AutoCAD SHX Text
ATS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
1200A ATS
AutoCAD SHX Text
EQUIPMENT PAD
AutoCAD SHX Text
1200A SERVICE DISCONNCT
FINAL E-105
D. POKHREL
D. POKHREL
J. SIDES, PE
D. POKHREL
J. ORR, PE
PWO 05/02/2024
GENERATOR REPLACEMENT
AT AS211
DEMOLITION - ONE LINE
60040132 23-0032
NOTED 6 10
'NAME'
(N)(E)
AutoCAD SHX Text
SHEET:
AutoCAD SHX Text 80091
AutoCAD SHX Text E1
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
SPEC#05-23-0032
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
SATISFACTORY TO:
AutoCAD SHX Text
APPROVED: PWO OR OICC:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text
500KVA PAD MOUNTED TRANSFORMER 12470Δ:208Y/120VAC, 3PH, 4-WIRE SECONDARY
AutoCAD SHX Text
120KW EMERGENCY GENERATOR 208Y/120 VAC, 3 , 4W, WITHSUB-BASE TANK,
AutoCAD SHX Text
TO CONTROLS
AutoCAD SHX Text
EX. PANEL 400A 120/208V, 3 , 4W400A
AutoCAD SHX Text
EX. PANEL MDP 120/208V, 3 , 4W1200A
AutoCAD SHX Text
AutoCAD SHX Text
EX. AUTOMATIC TRANSFER SWITCH 400A 208Y/120V, 3 , 4W
AutoCAD SHX Text
AutoCAD SHX Text
TO CONTROLS
AutoCAD SHX Text
EX. 36X36 JUNCTION BOX1
AutoCAD SHX Text
EX. 24X24 PULL BOX (TO REMAIN)
AutoCAD SHX Text
EX. 400A DISCONNECT SWITCH
AutoCAD SHX Text
CB-12OOA
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CONDUIT RISER
AutoCAD SHX Text
DEMOLITION RISER DIAGRAM NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SYM.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DISCONNECT AND PROTECT THE CABLES (TO MDP) FOR RE-INSTALLATION
AutoCAD SHX Text
DEMOLISH CONDUITS. PROTECT CONDUCTORS TO BE RE-INSTALLED
AutoCAD SHX Text DEMOLITION NOTES: DISCONNECT THE EX. PRIMARY FEEDER TOP THE EX. PAD MOUNTED TRANSFORMER. REMOVE EX. MEDIUM VOLTAGE INCLUDING RISER CONDUIT, FUSED CUTOUTS, SURGE ARRESTORS AND MOUNTING HARDWARE FOR THE UNDERGROUND PRIMARY FEEDER. REMOVE EX. PRIMARY CONDUCTORS FROM EX. CUTOUTS ON EX. UTILITY POLE (72107-44743) TO EX. 500KVA PAD MOUNTED TRANSFORMER. ABANDON EXISTING CONCRETE ENCASED DUCT BANK AND CONDUITS IN PLACE. DISCONNECT AND REMOVE EX. 500kVA PAD MOUNTED TRANSFORMER, CB-1200A, AND EX. CONCRETE PAD. DISCONNECT AND REMOVE EXISTING SECONDARY CONDUCTORS, CONDUITS AND DUCTBANK FROM CB-1200A TO EX. 36X36 JUNCTION BOX. EX. PAD MOUNTED TRANSFORMER SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND THE CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OFF-SITE IN ACCORDANCE WITH ALL LAWS AND REQUIREMENTS. REMOVE EX. METER BASE AND CURRENT TRANSFORMERS. PROTECT THE KWH METER FOR REINSTALLATION. DISCONNECT EXISTING CONDUCTORS IN EX. 36X36 JUNCTION BOX (FROM CB-1200 TO EX. 1200A MDP). DISCONNECT AND REMOVE EXISTING CONDUCTORS AND CONDUIT FROM THE JUNCTION BOX TO EX. 400A DISCONNECT SWITCH. REMOVE THE 36X36 JUNCTION BOX. PROTECT THE CONDUCTORS TO THE 1200 MDP TO BE SPLICED DURING INSTALLATION OF NEW JUNCTION BOX. EX. ATS TO BE REMOVED AND TURNED IN TO THE GOVERNMENT. CONTACT RANDY GRUSSLING AT SHOP 82 (910-546-0480). DEMOLISH CONDUITS BUT PROTECT THE CONDUCTORS FROM ATS TO 24X24 PULLBOX, TO BE RE-INSTALLED BY THE CONTRACTOR DURING CONSTRUCTION. DISCONNECT AND REMOVE EX. 120KW GENERATOR WITH ASSOCIATED CONDUCTORS, CONDUITS, AND APPURTENANCES. GENERATOR TO BE TURNED IN TO THE GOVERNMENT. CONTACT RANDY GRUSSLING AT SHOP 82 (910-546-0480). REMOVE EXISTING 400A DISCONNECT SWITCH, CONDUITS AND CONDUCTORS. REMOVE CONDUCTORS AND CONDUITS FOR UNUSED 100A CIRCUIT BREAKER LABELED PANEL 2B IN MDP. REMOVE GROUND-NEUTRAL BOND FROM MDP.
AutoCAD SHX Text
FINAL E-106
D. POKHREL
D. POKHREL
J. SIDES, PE
D. POKHREL
J. ORR, PE
PWO 05/02/2024
GENERATOR REPLACEMENT
AT AS211
NEW WORK - ONE LINE
60040133 23-0032
NOTED 7 10
'NAME'
'NAME'
AutoCAD SHX Text
SHEET:
AutoCAD SHX Text 80091
AutoCAD SHX Text E1
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
SPEC#05-23-0032
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
SATISFACTORY TO:
AutoCAD SHX Text
APPROVED: PWO OR OICC:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text
TO CONTROLS
AutoCAD SHX Text
EX. PANEL 400A 120/208V, 3 , 4W400A
AutoCAD SHX Text
EX. PANEL MDP 120/208V, 3 , 4W1200A
AutoCAD SHX Text
AutoCAD SHX Text
EX. 24X24 PULL BOX (TO REMAIN)
AutoCAD SHX Text (E)
AutoCAD SHX Text (N)
AutoCAD SHX Text
AutoCAD SHX Text
TO CONTROLS
AutoCAD SHX Text
PROVIDE A NEW CONDUIT RISER (SEE E-107 FOR DETIALS)
AutoCAD SHX Text PROVIDE NEW FUSED CUTOUTS, SURGE ARRESTORS, AND MOUNTING HARDWARE (SEE E-107 FOR DETAILS)
AutoCAD SHX Text
NEW WORK RISER DIAGRAM NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text 1200A
AutoCAD SHX Text PROVIDE NEW 500KVA LIQUID FILLED TRANSFORMER ON A PRE-CAST CONCRETE PAD 12470:208Y/120VAC, 3ɸ, 4W SECONDARY (SEE E-106 FOR DETAILS)
AutoCAD SHX Text
PROVIDE 1200A SERVICE DISCONNECT, 25KAIC, NEMA 4X ENCLOSURE
AutoCAD SHX Text
PROVIDE 1200A 4-POLE ATS 208/120V, 3ɸ, 4W NEMA 3RX STAINLESS STEEL
AutoCAD SHX Text
PROVIDE NEW EQUIPMENT PAD. SEE E-108 FOR DETAILS
AutoCAD SHX Text PROVIDE 350KW** EMERGENCY DIESEL GENERATOR 208/120V, 3ɸ, 4W, WITH SUB-BASE FUEL TANK, MINIMUM 96 HR OPERATION AT FULL LOAD, ACCESS PLATFORM ON A CONCRETE PAD
AutoCAD SHX Text
GROUND PER NEC 250
AutoCAD SHX Text
GROUND PER NEC 250
AutoCAD SHX Text
GROUND PER NEC 250
AutoCAD SHX Text
PROVIDE NEW NEMA 4X JUNCTION BOX (SIZED AS REQUIRED)
AutoCAD SHX Text
SPLICE AND CONNECT CONDUCTORS
AutoCAD SHX Text
SYM.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
FACE EXHAUST TOWARDS THE RECREATIONAL AREA
AutoCAD SHX Text
FACE FUEL PORTS TOWARDS AS211 FOR ACCESS TO FUEL TRUCKS
AutoCAD SHX Text LOAD SUMMARY VOLTAGE: 208V PHASE: 3 PHASE: 3 EXISTING DEMAND LOAD (DETERMINED BY PEAK LOAD USAGE IN THE HOTTEST WEEK OF SUMMER OF 2023) 92,000 W 92,000 W ASSUMED POWER FACTOR OF .8 115,000 VA 115,000 VA EXISTING DEMAND AMPS 320 AMPS 320 AMPS X 125% (PER NEC 220.87) 400 AMPS 400 AMPS TOTAL DEMAND BUILDING LOAD 144,000 VA144,000 VA
AutoCAD SHX Text
AutoCAD SHX Text
GENERATOR ELECTRIC PANEL 208/120V 3PH 4W
AutoCAD SHX Text
TO MDP-15 (REMOVE LABEL PANEL 2B FROM MDP. LABEL "GENERATOR PANEL")
AutoCAD SHX Text **GENERATOR SIZE BASED ON 350KW CATERPILLAR MODEL NUMBER C13 WITH A C13 ACERT IN-LINE 6, 4-CYCLE DIESEL ENGINE. IF GENERATOR OTHER THAN CATERPILLAR C13 350kW IS SUBMITTED, GENERATOR SHALL HAVE SAME CHARACTERISTICS AS CAT C13 350kW. GENERATOR SHALL BE UL LISTED.
AutoCAD SHX Text
PROVIDE NEW SPD
AutoCAD SHX Text
SPD
AutoCAD SHX Text
SEE E-109 GENERATOR ELECTRIC PANEL DETAILS
AutoCAD SHX Text
AVAILABLE FAULT CURRENT AT 1200A SERVICE DISCONNECT: 24254 AMPS
NOTE: SHORT CIRCUIT CALCULATION COMPLETED ON 04/23/2024 BASED ON A 500KVA PAD MOUNTED TRANSFORMER @ 5% IMPEDANCE. VERIFY ACTUAL PARAMETER WITH UTILITY COMPANY AND EQUIPMENT CHARACTERISTICS PRIOR TO INSTALLATION.
TRANSFORMER: "T1"
RATING: 150 KVA
PRIM. VOLTAGE: 480/277V, 3Ø
SEC. VOLTAGE: 208/120V, 3Ø, 4W
2 1/2" MINIMUM
1" MINIMUM
CONST. CONTR. NO.
FINAL E-107
D. POKHREL
D. POKHREL
J. SIDES, PE
D. POKHREL
J. ORR, PE
PWO 05/02/2024
GENERATOR REPLACEMENT
AT AS211
DETAILS 1
60040134 23-0032
NOTED 8 10
POLE LINE MATERIAL LIST
OH-1.5JUNE 2002SKETCH DATE STYLE
POLE LINE MATERIAL LIST
(b)
(a)
CURRENT, BUT NOT LESS THAN NO. 4 AWG
AT 125% OF TRANSFORMER FULL LOAD
CABLE, OR
T0 MATCH OR EXCEED AMPACITY OF CONNECTING
WEATHERPROOF SOFT DRAWN WIRE-SIZE
ANGLE POLE TOP PIN
CROSSARM ANGLE PIN
POLE TOP PIN (RIDGE PIN) - 24 INCHES LONG
SURGE ARRESTER, AS SPECIFIED
FUSED CUTOUT, AS SPECIFIED
HOT LINE CLAMP
PERFORATED STRAPPING, 1-1/2" WIDE
INSULATED BUSHING
CONDUIT BEND
CONDUIT COUPLING
GROUND CLAMP
#4 WP CU. SOFT DRAWN GROUND WIRE
GUY WIRE, SIZE AS SPECIFIED
GUY STRAIN INSULATOR
GUY HOOK
PREFORMED GUY GRIP
U BOLT CLAMP
SPOOL INSULATOR
CLEVIS BRACKET FOR SPOOL INSULATOR
ADAPTER PLATE FOR CLUSTER MOUNTING
SECONDARY LEAD SUPPORT BRACKET
STIRRUP
TRANSFORMER GROUNDING CONNECTION
CLUSTER MOUNTING BRACKET, STEEL
STEEL ANGLE PIN
STRAIN CLAMP
BELL TYPE SUSPENSION INSULATOR WITH CONNECTING HARDWARE
EXTENSION LINK
5/8" EYE BOLT, LENGTH AS NEEDED, WITH WASHER, NUT & LOCKWASHER
5/8" EYE NUT
10' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 3 1/2" X 4 1/2"
ANGLE STEEL BRACE (ONE PIECE)
GRID GAIN, USED ONLY WHEN THERE IS NO POLE GAIN
PIN INSULATOR
STEEL PIN
DEADEND BOX
MACHINE BOLT, 1/2" X LENGTH NEEDED, WITH WASHER, NUT & LOCKWASHER
ANGLE STEEL BRACE (TWO PIECES)
LAGSCREW, 1/2" X 4"
TIMBER CONNECTOR
MACHINE BOLT, 5/8" X LENGTH NEEDED WITH WASHER, NUT AND LOCKWASHER
8' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 3 1/2" X 4 1/2"
MACHINE BOLT, 3/8" X LENGTH NEEDED WITH WASHER, NUT AND LOCKWASHER
FLAT STEEL BRACE (TWO PIECES)1
OH-1.5AJUNE 2002SKETCH DATE STYLE
POLE LINE MATERIAL LIST
BACK-UP CURRENT LIMITING FUSE
10' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 4 3/4" X 5 3/4"
8' WOOD CROSSARM WITH CROSS SECTION DIMENSIONS OF 4 3/4" X 5 3/4"
PVC BACK PLATE
PVC EXTENSION SHIELD
PVC RISER SHIELD
54" FIBERGLASS STRAIN INSULATOR
TIE, SERVICE CABLE
SUSPENSION CLAMP
CONNECTOR
FITTING, POLE TOP
SADDLE CROSSARM
SADDLE, ANGLE
STUD, 7"
MIDSPAN SERVICE CLAMP
WEDGE CLAMP
PULLEY BRACKET
CROSSARM GAIN BRACKET
4' CROSSARM
INSULATOR, LINE POST CLAMP
ANGLE CLAMP
TRIPLE INSULATOR BRACKET
LINE POST INSULATOR
STUD, 3/4" X 1-3/4"
HOSE CLAMP
CABLE GRIP HANGER
MOUNTING BRACKET
TERMINATOR
TRI-MOUNT BRACKET46
OH-34JUNE 2002
(SIZE & TYPE AS INDICATED)
PVC RISER SHIELD
SKETCH DATE STYLE
CONDUIT LOCATION
NOTES
TYPE C
CONCRETE ENCASED
CONDUIT
TYPE B
DIRECT BURIED
CONDUIT
TYPE A
DIRECT BURIED
CABLE
LAGSCREW 3/8" X 1-1/2" LONG
NAIL, ALUMINUM, 1-1/2" LONG
SECURE CONDUCTORS WITH
BASKET TYPE CABLE GRIPS
FINISHED
GRADE
LAGSCREW
NAIL
PVC EXTENSION SHIELD
PVC BACK PLATE
OP OF RISER SHIELD 2"
ABOVE (FOR PRIMARY
RISERS) TO 10" BELOW
(FOR SECONDARY
RISERS) NEUTRAL OR
SECONDARY AS FIELD
CONDITIONS WARRANT
ALTERNATE
RISER
POSITION
PVC BACK PLATE
(NOTE 2)
RISER
POSITION
1. INSTALL RISER ON SIDE OR QUARTER OF POLE AWAY
FROM CLIMBING SURFACE.
2. INSTALL BACK PLATE WITH THE RISER SHIELD FROM
THE BOTTOM OF THE POLE.
ROAD SIDE
DIRECTION
OF TRAVEL
NE
UT
RA
L O
R
TO
P
SE
CO
ND
AR
Y
CO
ND
UC
TO
R
PLAN
ELEVATION
OH-41JUNE 2002SKETCH DATE STYLE
GROUND
1. USE ADDITIONAL GROUND RODS, WHEN REQUIRED, TO OBTAIN
RESISTANCE VALUE, AS REQUIRED BY IEEE C2.
2. MAKE GROUNDING CONNECTIONS TO ALL EQUIPMENT ON POLE AS
REQUIRED BY IEEE C2.
3. FOR SYSTEMS OTHER THAN 4 WIRE, MULTI-GROUNDED, USE
SEPARATE GROUNDING CONDUCTORS AND ELECTRODES FOR
PRIMARY AND SECONDARY SYSTEM DEVICE CONNECTIONS.
4. #4 600V INSULATED COPPER GROUNDING CONDUCTOR REQUIRED
ON PRIMARY SYSTEM WHEN SEPARATE SYSTEMS ARE REQUIRED.
PLASTIC OR FIBER MOLDING
GALVANIZED STAPLES (TYPICAL)
FINISHED
GRADE
GROUND ROD
24"
ADDITIONAL
GROUND RODS
(WHEN REQUIRED)
POLE
ALWAYS CONNECT THE POLE GROUND
LEAD(S) DIRECTLY TO THE NEUTRAL-ENSURE
THAT THE COPPER CONDUCTOR WILL
ALWAYS BE BELOW THE ALUMINUM.
CONNECTOR
10'-0"MIN
24"MIN
#4 BARE
COPPER (SEE
NOTE 4)
ALTERNATE GROUND WIRE
POSITION. (USE WHEN
MULTIPLE GROUNDING
SYSTEMS ARE REQUIRED.)
POLE
GROUND
WIRE
ROAD SIDE
COPPERWELD STAPLES (TYP.)NEUTRAL
18"MAX
10'-0"MIN
12"
NOTES
DIRECTION OF
TRAFFIC
8'-0"MIN
POLE LINE MATERIAL LIST
TOP TIE F NECK75
INSULATOR PIN POLE TOP PIN 20" STEEL76
INSULATOR PIN 15 KV77
INSULATOR BRACKET FBG POST INS BRACKET (BULLHORN) 18"78
DEADEND CLAMP79
INSULATOR SUPPORT EYEBOLT 5/8"X 12"80
CROSSARM, DEADEND, 60", STEEL81
INSULATOR DEADEND/SUSPENSION 15KV POLYMER82
(0-25KV)
U.G. TERMINAL
ALUMINUM ARCHED CLUSTER BRACKET83
CABLE CONCENTRIC NEUTRAL84
4"
36" MIN.48"MAX
29" MIN TO CLOSESTPHASE WIRE
44" MAX
OH-62
REFERENCE OH-60
FOR ADDITIONAL
INFORMATINO
MARCH 2021SKETCH DATE STYLE
NOTES:
1. PROVIDE SELF-ADHESIVE VINYL LABEL TO AFFIX TO ELECTRICAL EQUIPMENT TO WARN OF ARC
FLASH HAZARDS.
2. THE LABEL FORMAT AND TEXT SHALL BE IN ACCORDANCE WITH THE FIGURE.
3. THE LABEL SHALL BE LOCATED ON THE EQUIPMENT TO BE CLEARLY VISIBLE TO QUALIFIED
PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE OF THE
EQUIPMENT.
4. THE SIZE OF THE LABEL SHALL BE MINIMUM:
EQUIPMENT TYPE HEIGHT WIDTH
INDOOR 2" 3"
OUTDOOR 3" 4.5"
WIDTH
HEIGHT
AutoCAD SHX Text
%%UTRANSFORMER NAMEPLATE DETAIL
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
WHITE PLASTIC NAMEPLATE WITH BLACK ENGRAVED LETTERS
AutoCAD SHX Text
MACHINE SCREW WITH ACORN NUT AND LOCKWASHER, TYP.
AutoCAD SHX Text
TRANSFORMER DESIGNATION 1/4" BLACK ENGRAVED LETTERS
AutoCAD SHX Text
RATING DESIGNATION 1/2" BLACK ENGRAVED LETTERS
AutoCAD SHX Text
VOLTAGE AND PHASE DESIGNATION 1/4" BLACK ENGRAVED LETTERS
AutoCAD SHX Text
SHEET:
AutoCAD SHX Text 80091
AutoCAD SHX Text E1
AutoCAD SHX Text
MARINE CORPS BASE
AutoCAD SHX Text
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
AutoCAD SHX Text
CAMP LEJEUNE, NORTH CAROLINA
AutoCAD SHX Text
DESIGN DIR.
AutoCAD SHX Text
SUBMITTED BY:
AutoCAD SHX Text
NAVFAC DRAWING NO.
AutoCAD SHX Text
CODE IDENT. NO
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
SPEC#05-23-0032
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
SATISFACTORY TO:
AutoCAD SHX Text
APPROVED: PWO OR OICC:
AutoCAD SHX Text
DR.
AutoCAD SHX Text
DES.
AutoCAD SHX Text
CHK.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
OF
AutoCAD SHX Text
TOP OF RISER SHIELD 2"
AutoCAD SHX Text
POLE DETAILS NOT TO SCALE
AutoCAD SHX Text
PRE-CAST CONCRETE BOX PAD
AutoCAD SHX Text
GRADE
AutoCAD SHX Text
TERMINATIONS
AutoCAD SHX Text
LOW VOLTAGE CABLE
AutoCAD SHX Text
GROUND PAD (TYP OF 2)
AutoCAD SHX Text
CURRENT TRANSFORMERS
AutoCAD SHX Text
3-POLE FUSE BLOCK
AutoCAD SHX Text
WATTHOUR
AutoCAD SHX Text
DEMAND METER
AutoCAD SHX Text
OIL-IMMERSED
AutoCAD SHX Text
CURRENT-LIMITING
AutoCAD SHX Text
2 POSITION LOAD
AutoCAD SHX Text
BREAK OIL SWITCH
AutoCAD SHX Text
PRIMARY CIRCUIT
AutoCAD SHX Text
SECONDARY CIRCUIT
AutoCAD SHX Text %%u PAD-MOUNTED TRANSFORMER DETAIL