The attachment likely contains drawings or blueprints for the office renovations required under this contract opportunity. The solicitation seeks a contractor to perform the necessary office renovations at the specified location. Key details about the contract opportunity include the agency involved (Department of the Navy Naval Facilities Engineering Command), the solicitation number (N4008524R2737), and the location of the work (CEP-177). Interested parties can obtain more details about the contract opportunity by logging into the PIEE.eb.mil website and searching for the solicitation number.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NAVAL STATION - NORFOLK, VIRGINIA
NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
MID-ATLANTIC
PUBLIC WORKS DEPARTMENT
FACILITIES ENGINEERING AND ACQUISITION DIVISION
NORFOLK, VIRGINIA
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:2 :5
P
M
C U s e rs
\e ri c .s u n d e rl a n d \D o c u m e n ts
\R E
V
IT
F ile s \C
E P
A
R e ri c .s u n d e rl a n d .r v t
GI001
B
LD
G C
E P
-1
N C
IS
O
F F
IC
E
R E
N O
V A
T
IO
N
C O
V E
R S
H E
E T
ALP
12,910,590
EJS EJS
05/30/2024
JUNY GIBSON, NCIS
ERIC SUNDERLAND, R.A.
1689103
N/A
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
J. C. MILLER, P.E.
ALP
M
ID
L A
N T
P
W D
N O
R F
O L K
G I0
BLDG CEP-177 NCIS OFFICE
RENOVATION
S Y
M D
E S
C R
IP
T
I O N
D A
T E
A P
P R
WILLOUGHBY BAY
NAVAL SUPPORT
ACTIVITY
U.S. NAVAL STATION
SEWELLS POINT
NORFOLK
U.S. NAVAL
AIR STATION
CHESAPEAKE BAY
LITTLE CREEK
U.S. NAVAL
AMPHIBIOUS BASE
VA BEACH
OCEANA
NAVAL AIR
STATION
CHESAPEAKE
SOUTHERN BRANCH
EASTERN BRANCH
ST. JULIEN'S CREEK
U.S. NAVAL ANNEX
ELIZABETH RIVER
PORTSMOUTH
U.S. ARMY CRANEY
ISLAND DISPOSAL AREA
NANSEMOND RIVER
WESTERN BRANCH
CRANEY
ISLAND NAVY
DEPOT
PROJECT SITE
NORTH
ROOM
ROOM
ROOM IDENTIFIER
DETAIL NUMBER
SHEET WHERE DRAWN
DETAIL TAG
ROOM NAME
ROOM NUMBER
A-401 INTERIOR ELEVATION
INDICATOR
INTERIOR ELEVATION NUMBER
SHEET WHERE DRAWN
DETAIL NUMBER
A1
A-301
WALL / PARTIAL
BUILDING SECTION
INDICATOR
SECTION NUMBER
SHEET WHERE DRAWN
GENERAL PROJECT SYMBOLS
DEMOLITION / NEW WORK
KEYNOTE INDICATOR
KEYNOTE NUMBER
A-901
PHOTOGRAPH
INDICATOR
PHOTOGRAPH NUMBER
SHEET WHERE SHOWN
A1
PLAN
NORTH
TRUE NORTH
A-501
A1
A1
A1
A1
SCALE: 1/8" = 1'-0"
PLAN TITLE
A1
VIEW TITLE
SCALE: 1/8" = 1'-0"
HAZARDOUS MATERIAL WORK
KEYNOTE INDICATOR
KEYNOTE NUMBER
SPECIALTY EQUIPMENT
KEYNOTE INDICATOR
KEYNOTE NUMBER
SHEET REFERENCED FROM
4' 8' 16'0'
4' 8' 16'0'(A-101)
GRAPHIC SCALE
GRAPHIC SCALE
CEP-177
GATE 5
NORTH
H A
M P
T O
N B
LV
D
H A
M P
T O
N B
LV
D
CD-9
CEP-58
SEABEE RD
"B" AVE
V
IR
G
IN
IA
A
V E
"A" AVE
1S T
S T
R E
E T
PROJECT
SITE
CEP-127
CEP-51
CEP-57
CEP-58A
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:2 :5
P
M
C U s e rs
\e ri c .s u n d e rl a n d \D o c u m e n ts
\R E
V
IT
F ile s \C
E P
A
R e ri c .s u n d e rl a n d .r v t
GI002
B
LD
G C
E P
-1
N C
IS
O
F F
IC
E
R E
N O
V A
T
IO
N
LI
S
T O
F S
H E
E
TS
, V
IC
IN
IT
Y
L O
C A
TI
O
N M
A P
S , A
N D
G E
N E
R A
L P
R O
JE
C
T N
O
TE
S
ALP
12,910,591
EJS EJS
05/30/2024
JUNY GIBSON, NCIS
ERIC SUNDERLAND, R.A.
1689103
N/A
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
J. C. MILLER, P.E.
ALP
M
ID
L A
N T
P
W D
N O
R F
O L K
G I0
LIST OF SHEETS
SHEET NO.
NAVFAC DWG. NO. SHEET TITLENO. SHEET
GENERAL
1 GI001 12,910,590 COVER SHEET
2 GI002 12,910,591 LIST OF SHEETS, VICINITY & LOCATION MAPS, AND GENERAL PROJECT NOTES
3 GI101 12,910,592 OVERALL FACILITY PLAN - EXISTING
4 GI102 12,910,593 BUILDING CODE AND LIFE SAFETY ANALYSIS
5 GI103 12,910,594 OVERALL FACILITY PLAN - LIFE SAFETY
HAZARDOUS MATERIALS
6 HM101 12,910,595 OVERALL FLOOR PLAN - HAZARDOUS MATERIALS ABATEMENT
ARCHITECTURAL
7 A-001 12,910,596 ARCHITECTURAL NOTES AND SYMBOLS
8 AD101 12,910,597 OVERALL FLOOR PLAN - DEMOLITION
9 AD102 12,910,598 OVERALL REFLECTED CEILING PLAN - DEMOLITION
10 AD103 12,910,599 OVERALL ROOF PLAN - DEMOLITION
11 AD201 12,910,600 BUILDING ELEVATIONS - DEMOLITION
12 AD401 12,910,601 ENLARGED SLAB PLAN - "CORE" AREA - DEMOLITION
13 AD402 12,910,602 ENLARGED FLOOR PLAN - "CORE" AREA - DEMOLITION
14 AE101 12,910,603 OVERALL FLOOR PLANS - ANNOTATIONS AND DIMENSIONS - NEW WORK
15 AE102 12,910,604 OVERALL REFLECTED CEILING PLAN - NEW WORK
16 AE103 12,910,605 OVERALL ROOF PLAN - NEW WORK
17 AE201 12,910,606 BUILDING ELEVATIONS - NEW WORK
18 AE401 12,910,607 ENLARGED SLAB PLANS - NEW WORK
19 AE402 12,910,608 ENLARGED FLOOR PLANS - ANNOTATIONS - NEW WORK
20 AE403 12,910,609 ENLARGED FLOOR PLANS - DIMENSIONS - NEW WORK
21 AE404 12,910,610 SPECIALTY EQUIPMENT SCHEDULE AND INTERIOR ELEVATIONS
22 AE405 12,910,611 INTERIOR ELEVATIONS
23 AE501 12,910,612 CASEWORK DETAILS
24 AE502 12,910,613 MISCELLANEOUS DETAILS
25 AE503 12,910,614 MISCELLANEOUS DETAILS
26 AE601 12,910,615 DOOR SCHEDULE AND DETAILS
27 AE602 12,910,616 DOOR DETAILS
28 AE603 12,910,617 DOOR DETAILS
29 AE604 12,910,618 PARTITION TYPES
30 AE605 12,910,619 PARTITION TYPES
31 AF101 12,910,620 OVERALL FINISH FLOOR PLAN
32 AF601 12,910,621 INTERIOR FINISH SCHEDULE, LEGEND, AND DETAILS
33 AG501 12,910,622 TYPICAL SIGNAGE TYPES, DOORWAY LOCATIONS, AND SCHEDULE
FIRE PROTECTION
34 F-001 12,910,623 FIRE PROTECTION GENERAL
35 FD101 12,910,624 OVERALL FLOOR PLAN - FIRE ALARM - DEMOLITION
36 FA101 12,910,625 OVERALL FLOOR PLAN - FIRE ALARM - NEW WORK
PLUMBING
37 P-001 12,910,626 PLUMBING LEGEND, ABBREVIATIONS, AND NOTES
38 PD401 12,910,627 ENLARGED FLOOR PLAN - PLUMBING - DEMOLITION
39 PJ401 12,910,628 ENLARGED FLOOR PLAN - PLUMBING - NEW WORK
40 PJ601 12,910,629 PLUMBING SCHEDULES AND DIAGRAMS
MECHANICAL
41 M-001 12,910,630 MECHANICAL LEGEND, SPECIFICATIONS, ABBREVIATIONS AND NOTES
42 MD101 12,910,631 OVERALL FLOOR PLAN - MECHANICAL - DEMOLITION
43 MH101 12,910,632 OVERALL FLOOR PLAN - MECHANICAL DUCTWORK - NEW WORK
44 MP101 12,910,633 OVERALL FLOOR PLAN - MECHANICAL PIPING - NEW WORK
45 MI501 12,910,634 MECHANICAL DETAILS
46 MI601 12,910,635 MECHANICAL SCHEDULES
ELECTRICAL
47 E-001 12,910,636 ELECTRICAL SYMBOLS, ABBREVIATIONS, AND NOTES
48 ED101 12,910,637 OVERALL FLOOR PLAN - DEMOLITION
49 EL101 12,910,638 OVERALL FLOOR PLAN - LIGHTING - NEW WORK
50 EL501 12,910,639 LIGHTING DIAGRAMS AND DETAILS
51 EL601 12,910,640 LUMINAIRE SCHEDULE AND PLATES
52 EP101 12,910,641 OVERALL FLOOR PLAN - POWER - NEW WORK
53 EP401 12,910,642 BUILDING ELEVATIONS - EXISTING EQUIPMENT
54 EP402 12,910,643 ENLARGED FLOOR PLANS - POWER - NEW WORK
55 EP501 12,910,644 ELECTRICAL DETAILS
56 EP601 12,910,645 POWER RISER DIAGRAM
57 EP701 12,910,646 PANELBOARD SCHEDULES
58 EP702 12,910,647 PANELBOARD SCHEDULES
TELECOMMUNICATIONS
59 T-001 12,910,648 TELECOMMUNICATIONS SYMBOLS, LEGEND, ABBREVIATIONS, AND NOTES
60 TD101 12,910,649 OVERALL FLOOR PLAN - TELECOMMUNICATIONS PLAN - DEMOLITION
61 TT101 12,910,650 OVERALL FLOOR PLAN - TELECOMMUNICATIONS PLAN - NEW WORK
62 TT501 12,910,651 TELECOMMUNICATIONS DETAILS
63 TT601 12,910,652 TELECOMMUNICATIONS RISER DIAGRAMS
VICINITY MAP
GENERAL PROJECT NOTES
LOCATION MAP
A WHERE EXISTING CONSTRUCTION IS DAMAGED BY CONSTRUCTION REQUIRED
BY THESE DOCUMENTS. REPAIR THE DAMAGED ITEM(S) WITH MATERIALS TO
MATCH THE ADJACENT MATERIAL, TEXTURE AND COLOR.
B FIELD VERIFY EXISTING DIMENSIOS (INDICATED AS ±), PRIOR TO BEGINNING OF
DEMOLITION, ORDERING MATERIALS, OR PROCEEDING WITH WORK. NOTIFY
THE CONTRACTING OFFICER, IN WRITING, OF DISCREPANCIES.
C ALL ITEMS NOT INDICATED AS "EXISTING" OR "GFCI" MUST BE PROVIDED AND
INSTALLED UNDER THE REQUIREMENTS OF THIS CONTRACT.
D COORDINATE LAY DOWN AREA WITH THE CONTRACTING OFFICER PRIOR TO
THE PRECONSTRUCTION MEETING. THE ALLOWABLE AREA SIZE MUST BE
ESTABLISHED BY THE CONTRACTING OFFICER.
E MANUFACTURER'S TRADE NAMES LISTED ARE NOT INTENDED TO BE
PROPRIETARY. PRODUCTS OF OTHER MANUFACTURERS WILL BE ACCEPTABLE
PROVIDED THEY MATCH THE COLOR, FINISHES, TEXTURES AND PATTERNS OF
THE MANUFACTURER LISTED, AND MEET THE TECHNICAL REQUIREMENTS OF
THE SPECIFICATIONS.
F OBSERVE AND MAINTAIN BUILDING AND COMPOUND SECURITY
REQUIREMENTS AS DIRECTED BY THE CONTRACTING OFFICER.
G CONSTRUCTION WILL BE ACCOMPLISHED IN AND AROUND AREAS WHICH WILL
REMAIN OPERATIONAL. AVOID INTERFERENCE WITH THE OPERATIONAL WORK
ROUTINE.
H ALL SUBMITTALS REQUIRED BY THESE DRAWINGS AND SPECIFICATIONS MUST
BE SUBMITTED TO THE CONTRACTING OFFICER FOR REVIEW AND APPROVAL
PRIOR TO COMMENCEMENT OF RELATED WORK.
I PROTECT INTERIOR SPACES TO REMAIN FROM CONSTRUCTION DUST AND
DEBRIS THROUGHOUT THE PERIOD OF PERFORMANCE.
J STUDY AND COMPARE THE CONTRACT DOCUMENTS WITH EACH OTHER, AND
AT ONCE, REPORT TO THE CONTRACTING OFFICER ANY ERRORS AND
INCONSISTENCIES OR OMISSIONS DISCOVERED. ANY CONSTRUCTION
ACTIVITY PERFORMED KNOWING IT INVOLVES A RECOGNIZED ERROR,
INCONSISTENCY, OR OMISSION IN THE CONTRACT DOCUMENTS WITHOUT
SUCH NOTICE TO THE CONTRACTING OFFICER, THE CONTRACTOR WILL
ASSUME RESPONSIBILITY FOR SUCH PERFORMANCE AND WILL BEAR THE
AMOUNT OF THE COST OF THE CONSTRUCTION.
K TAKE NOTE THAT BUILDING CEP-177 IS SINGLE STORY, WITH NO INTERIOR
ACCESS BETWEEN NCIS AND BASE TOUR SPACES. THE NCIS SPACES WILL BE
VACATED THROUGHOUT THE ENTIRETY OF THE WORK. THE BASE TOUR
SPACE WILL REMAIN OPERATIONAL THROUGHOUT THE ENTIRETY OF THE
WORK. CARE MUST BE TAKEN TO LIMIT IMPACT OF THE CONSTRUCTION TO
NORMAL OPERATIONS IN THE BASE TOUR SPACES DURING NORMAL BUSINESS
HOURS.
GOVERNING REGULATIONS
BUILDING CODE:
UNIFIED FACILITIES CRITERIA (UFC) 1-200-01 (01 OCT. 2020)
UNIFIED FACILITIES CRITERIA (UFC) 1-200-02 (03 JAN. 2022)
UNIFIED FACILITIES CRITERIA (UFC) 3-101-01 (05 JAN. 2021)
INTERNATIONAL BUILDING CODE (IBC), 2018
ACCESSIBILITY CODE:
UNIFORM ACCESSIBILITY STANDARDS (UFAS)
AMERICANS WITH DISABILITIES ACT (ADA)
ARCHITECTURAL BARRIERS ACT STANDARDS (ABAS)
ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES (ADAAG)
MECHANICAL CODE:
INTERNATIONAL MECHANICAL CODE (IMC) 2018
ELECTRICAL CODE:
NFPA 70, NATIONAL ELECTRIC CODE (NEC), 2020
PLUMBING CODE:
INTERNATIONAL PLUMBING CODE (IPC) 2018
FIRE PREVENTION & LIFE SAFETY CODE:
UNIFIED FACILITIES CRITERIA (UFC) 3-600-01 (06 MAY 2021)
NFPA 101, LIFE SAFETY CODE, 2018
BUILDING DESIGN CRITERIA
USE GROUP (OCCUPANCY) CLASSIFICATION:
MIXED USE: BUSINESS / MERCANTILE
PROJECT PROXIMITY: NEAR USE GROUP A-3 - ASSEMBLY (IBC 304.1)
TYPE OF CONSTRUCTION:
TYPE I (PER IBC CHAPTER 6)
S Y
M D
E S
C R
IP
T
I O N
D A
T E
A P
BASE TOUR OFFICE
PRIMARY AREA OF WORK
OCCUPANT BOUNDARY
NCIS OFFICE
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:2 :0
P
M
C U s e rs
\e ri c .s u n d e rl a n d \D o c u m e n ts
\R E
V
IT
F ile s \C
E P
A
R e ri c .s u n d e rl a n d .r v t
GI101
B
LD
G C
E P
-1
N C
IS
O
F F
IC
E
R E
N O
V A
T
IO
N
O V
E R
A
LL
F A
C
IL
IT
Y
P
LA
N E X
IS
TI
N G
ALP
12,910,592
EJS EJS
05/30/2024
JUNY GIBSON, NCIS
ERIC SUNDERLAND, R.A.
1689103
N/A
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
J. C. MILLER, P.E.
ALP
M
ID
L A
N T
P
W D
N O
R F
O L K
G I1
0 4' 8' 16'
PLAN
NORTH
SCALE: 1/8" = 1'-0"
OVERALL FACILITY PLAN - EXISTING
B1
GENERAL SHEET NOTES
KEYPLAN
PLAN
NORTH
NCIS
OFFICE
BASE
TOUR
A THE OVERALL PLAN SHOWN HERE, AND ELSEWHERE IN THE SUBSEQUENT
DRAWINGS, IS BASED ON BEST AVAILABLE HISTORIC DOCUMENTATION OF THE
FACILITY AS WELL AS FIELD DOCUMENTATION OF EXISTING CONDITIONS. AS
SUCH, ALL CONDITIONS MUST BE FIELD VERIFIED PRIOR TO PERFORMING ANY
WORK. BRING ANY DISCREPANCIES TO THE ATTENTION OF THE CONTRACTING
OFFICER PRIOR TO PERFORMING THE WORK.
B THE WORK INCLUDES BOTH INTERIOR AND EXTERIOR REPAIRS AND
RENOVATIONS FOR THE NCIS SPACES IN BUILDING CEP-177. THE INTENT OF
THIS DRAWING IS TO IDENTIFY THE PRIMARY AREA OF WORK IN THE PROJECT,
AS WELL AS THE GENERAL PROXIMITY OF THE WORK TO OTHER ACTIVE
OCCUPANT SPACES IN THE FACILITY. SOME WORK MAY OCCUR OUTSIDE
NOTED PRIMARY AREA OF WORK. ALL WORK THAT WILL IMPACT NORMAL
FACILITY OPERATIONS OF OTHER FACILITY OCCUPANTS MUST BE
COORDINATED WITH THOSE OCCUPANTS AND THE CONTRACTING OFFICER IN
ADVANCE TO MINIMIZE SUCH IMPACT.
C REFER TO SHEET GI002 FOR GENERAL PROJECT NOTES.
D REFER TO SUBSEQUENT DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND WORK REQUIREMENTS.
S Y
M D
E S
C R
IP
T
I O N
D A
T E
A P
APPLICABLE CODES, STANDARD, AND DESIGN CRITERIA
STANDARD TITLE REVISION DATE NOTES
UFC 1-200-01 GENERAL BUILDING REQUIREMENTS 01 NOVEMBER 2018 --
UFC 3-600-01* FIRE PROTECTION ENGINEERING FOR FACILITIES 25 MARCH 2018 --
IBC INTERNATIONAL BUILDING CODE 2021 APPLICABLE CHAPTERS PER UFC
1-200-01; MEANS OF EGRESS
SHALL BE BASED UPON THE LIFE
SAFETY CODE
NFPA 1 STANDARD - UNIFORM FIRE CODE 2021 --
--NFPA 72 NATIONAL FIRE ALARM SIGNALING CODE 2022
NFPA 101 LIFE SAFETY CODE (LSC) 2021
* UFC 3-600-01 GENERALLY REQUIRES CONSTRUCTION ISSUES TO COMPLY WITH IBC CRITERIA AND LIFE SAFETY/EGRESS ISSUES TO MEET THE REQUIREMENTS OF LSC. CONFLICTS BETWEEN THE IBC AND LSC RELATED TO FIRE RESISTANCE ARE REQUIRED TO COMPLY WITH LSC
CRITERIA AND APPLICABLE PROVISIONS OF THE UFC CODE (UFC 3-600-01 § 2-1.1).
BUILDING DESCRIPTION
TYPE OF CONSTRUCTION IIB
NUMBER OF STORIES 1
BUILDING HEIGHT 16'-0"
NUMBER OF
STORIES
OCCUPANCY
AND USE
(A)
BLDG AREA PER
STORY (ACTUAL)
1 BUSINESS
(B)
TABLE 506.2 AREA
(PER STORY)
(C)
AREA FOR FRONTAGE
INCREASE (100% OPEN)
(E)
ALLOWABLE AREA
9,225 21,000 5,250 33,250
TOTAL -- -- --
ALLOWABLE AREA (TYPE IIB)
ALLOWABLE HEIGHT (TYPE IIB)
ALLOWABLE
(TABLE 504.3)
BUILDING HEIGHT 55'-0"
ACTUAL
16'-0"
NUMBER OF STORIES 3 1
FIRE RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS OF TYPE IIB
BUILDING BASED ON FIRE SEPARATION DISTANCE (IBC TABLE 602)
FIRE SEPARATION DISTANCE TO LOT LINE USE GROUP R-2
FSD < 5 FT
5FT ≥ FSD < 10FT
FSD ≥ 10FT
1 HR
1 HR
0 HR
CODE REFERENCE
STRUCTURAL FRAME, INCLUDING COLUMNS,
GIRDERS, TRUSSES
BUILDING ELEMENT HOURLY RATING
REQ'D TYPE IIB PROVIDED
EXTERIOR WALLS
EXTERIOR BEARING WALLS
INTERIOR NON-BEARING WALLS
IBC TABLE 601
NFPA 101
ROOF CONSTRUCTION INCLUDING
SUPPORTING BEAMS AND JOISTS
EXIT ACCESS CORRIDORS NFPA 101,38.3.6.1
IBC TABLE 601
IBC TABLE 601
TYPE IIB FIRE RESISTANCE RATINGS (IN HOURS) OF STRUCTURAL ELEMENTS
0 0
0 0
0 0
0 0
0 0
OPENING PROTECTIVES
CODE REFERENCE
VERTICAL COMMUNICATING SPACE
BUILDING
ELEMENT/HAZARD
DESCRIPTION
HOURLY RATING
REQ'D LSC PROVIDED
DOOR OPENINGS IN 2 HR FIRE BARRIERS IBC TABLE 715.4
NFPA 101,8.6.6(4)SB SB
1.5 1.5
DOOR OPENINGS IN 1 HR STAIR ENCLOSURES 1 1
DUCT PENETRATIONS IN 30 MIN OR 1 HR FIRE
BARRIERS
NFPA 90A, 5.3.1.1NO RATING NO RATING
DUCT PENETRATIONS IN 2 HR FIRE BARRIERS
AND SHAFT ENCLOSURES
1.5 HR FIRE
DAMPERS
DUCT PENETRATIONS IN RATED FLOOR OR
CEILING ASSEMBLIES
AIR TRANSFER OPENINGS IN ANY FIRE OR
SMOKE BARRIER OR PARTITION
OCCUPANCY CLASSIFICATIONS
OFFICES
LSC
GROUP B
DESCRIPTION OF USE
IBC
NEW BUSINESS
USE AND OCCUPANCY CLASSIFICATIONS
INTERVIEW ROOM
(CONCENTRATED
BUSINESS)
CONFERENCE 105
(ASSEMBLY USE)
STORAGE (TOTAL)
1ST FLR TOTAL
4,676 48
LSC CALCULATED BUILDING OCCUPANT LOAD 48
CODE REFERENCEOCCUPANCY APPROX. AREA OCCUPANT LOAD
FACTOR
OCCUPANT LOAD
FIRST FLOOR
OCCUPANT LOADS NCIS ONLY
MINIMUM
NUMBER OF EXITS
FIRST FLOOR
MINIMUM WIDTH (EXIT
DOORS)
75 FT
NFPA 101, 38.2.4 & 7.4
FIRE SPRINKLER SYSTEM, WET PIPE NO UFC 3-600-01
FIRE ALARM/ MASS NOTIFICATION YES UFC 3-600-01, NFPA 72, UFC 4-010-01, UFC 4-021-01
MANUAL FIRE EXTINGUISHERS YES NFPA 10
BUILDING CODE AND LIFE SAFETY ANALYSIS
FIRE PROTECTION
PROVIDED CODE REFERENCEREQUIRED
MEANS OF EGRESS SUMMARY
MAXIMUM COMMON
PATH OF TRAVEL (B) *
--NFPA 80 STANDARD - FIRE DOORS AND OTHER OPENINGS
PROT
FC 1-300-09N FIRE PROTECTION ENGINEERING 06 JUNE 2018 --
UFC 4-010-01 DOD MINIMUM ANTITERRORISM STANDARDS FOR
BUILDINGS
12 DECEMBER 2018 --
9,225 33,250
IBC TABLE 715.4
1.5 HR FIRE
DAMPERS
NFPA 90A, 5.3.1.1
1.5 HR FIRE
DAMPERS
1.5 HR FIRE
DAMPERS
NFPA 90A, 5.4.4.1
1.5 HR FIRE
DAMPERS
1.5 HR FIRE
DAMPERS
NFPA 90A, 5.3.1.2
SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS AND RATINGS OF DOOR ASSEMBLIES
CONFERENCE GROUP B NEW BUSINESS, OCCUPANT
LOAD LESS THAN 50
IBC TABLE 601
NFPA 101,7.3.1.2BUSINESS (OFFICES
AND COMMON AREA
3,487 150 24
NFPA 101,7.3.1.2
NFPA 101,7.3.1.2
NFPA 101,7.3.1.2
EXIT CAPACITY
FLOOR LEVEL
FIRST FLOOR
OCCUPANT LOAD MIN WIDTH (INCHES) ACTUAL WIDTH
(INCHES)
CODE REFERENCE
48 36" 108" NFPA 101,7.3.3.1
ALL OTHER AREAS
EXIT ACCESS
CORRIDORS
ALL OTHER AREAS
CLASS A,B OR C
CLASS I OR II
CLASS I OR II
REQUIRED PROVIDED
WALL AND CEILING FINISHES
INTERIOR FINISHES
EXIT ACCESS
CORRIDORS
CLASS A OR B
FLOOR FINISHES
CODE REFERENCE
NFPA 101,38.3.3.2.1
NFPA 101,10.2.8.2
NFPA 101,38.3.3.3.1
NFPA 101,2.8.2
CLASS A,B OR C
CLASS I OR II
CLASS I OR II
CLASS A OR B
REQUIRED CODE
REFERENCE
PROVIDED
MAXIMUM DEAD END
CORRIDORS (B) *
MAXIMUM TRAVEL
DISTANCE (B) *
ILLUMINATION
EMERGENCY
LIGHTING
EXIT SIGNS
* SEE LIFE SAFETY DRAWINGS FOR MEASUREMENTS RELATIVE TO MEANS OF EGRESS
SEE ELECTRICAL DRAWINGS FOR ILLUMINATION, EMERGENCY LIGHTING, AND EXIT SIGNS
32 INCHES
70 FT
36 INCHES
20 FT 0 FT
200 FT 74 FT
YES YES
YES YES
YES YES
NFPA 101, 7.2.1.2.3
NFPA 101, 38.2.5.3.1
NFPA 101, 38.2.5.2.1
NFPA 101, 38.2.6.3
NFPA 101, 38.2.8
NFPA 101, 38.2.9
NFPA 101, 38.2.10
NO
YES
YES
FIRE EXTINGUISHERS ARE EXISTING
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:3 :1
P
M
C U s e rs
\e ri c .s u n d e rl a n d \D o c u m e n ts
\R E
V
IT
F ile s \C
E P
F
R e ri c .s u n d e rl a n d .r v t
GI102
B
LD
G C
E P
-1
N C
IS
O
F F
IC
E
R E
N O
V A
T
IO
N
B U
IL
D
IN
G
C O
D E
A N
D L
IF
E
S A
F E
TY
A
N A
LY
S
IS
12,910,593
MWB DMH
05/30/2024
JUVY GIBSON, NCIS
ERIC SUNDERLAND, R.A.
1689103
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
J. C. MILLER, P.E.
M
ID
L A
N T
P
W D
N O
R F
O L K
G I1
S Y
M D
E S
C R
IP
T
I O N
D A
T E
A P
E
F N
IC
1 HOUR FIRE WALL
2 HOUR FIRE WALL
SYMBOL DESCRIPTION
COMMON PATH OF TRAVEL
MAXIMUM TRAVEL DISTANCE
MTD = X'-XX"
CPT = X'-XX"
ENTRY
VESTIBULE
100 ELEC
101B
ADMIN OFFICE
SSA OFFICE
101A
GARAGE
SERVER RM
CONF RM
MEN'S TOILET
WOMEN'S TOILET
FORENSIC
CONSULT
KITCHENETTE
CORRIDOR
DIGITAL LAB
RECEPTION
INTERVIEW RM
DFE OFFICE
STORAGE RM
104A
ADMIN STORAGE
RM
MANAGEMENT
SUITE OFFICE
102A
OFFICE
VAULT /
FORENSICS LAB
JAN CLOSET
TD 56'
CPT 30'
TD 62 '
CPT 58'
TD 74'
CPT 70'
TD 59'
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:3 :1
P
M
C U s e rs
\e ri c .s u n d e rl a n d \D o c u m e n ts
\R E
V
IT
F ile s \C
E P
F
R e ri c .s u n d e rl a n d .r v t
GI103
B
LD
G C
E P
-1
N C
IS
O
F F
IC
E
R E
N O
V A
T
IO
N
O V
E R
A
LL
F A
C
IL
IT
Y
P
LA
N
LI
F
E S
A F
E
TY
12,910,594
MWB DMH
05/30/2024
JUVY GIBSON, NCIS
ERIC SUNDERLAND, R.A.
1689103
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
J. C. MILLER, P.E.
M
ID
L A
N T
P
W D
N O
R F
O L K
G I1
GENERAL SHEET NOTES
LIFE SAFETY LEGEND
KEY PLAN
GRAPHIC SCALE(S)
1/8" = 1' - 0" 0 5' 10' 15' 30'
0 4' 8' 16'
PLAN
NORTH
SCALE: 1/8" = 1'-0"
OVERALL FACILITY PLAN - LIFE SAFETY
NCIS
OFFICE
BASE
TOUR
1. BASE TOUR CENTER IS NOT BEING RENOVATED. SINCE NCIS AND
BASE TOUR CENTER SHARE A FIRE ALARM SYSTEM, THE SYSTEM IN
THE BASE TOUR CENTER MUST BE UPGRADED. THE TWO TENANTS
ARE SEPARATED BY A 2 HR EQUIVALENT CONCRETE WALL, IN
ACCORDANCE WITH IBC 707.3.10, WITH ONLY FIRE ALARM AND
ELECTRICAL PENETRATIONS.
2. PROVIDE FIRESTOPPING TO EXISTING PENETRATIONS IN FIRE RATED
BARRIERS.
S Y
M D
E S
C R
IP
T
I O N
D A
T E
A P
C
A
B
2 3 4 5
D
E
VAULT /
FORENSICS
LAB
GARAGE
IT LAB
RECEPTION
RM
FORENSIC
CONSULT
DARK RM
MEN'S
TOILET
WOMEN'S
TOILET
ENTRY
VESTIBULE
CORRIDOR
ADMIN
OFFICE
FILE RM
101B
PRINTER
RM
101C
CORRIDOR
SSA
OFFICE
101A
OFFICE
CONF RM
STORAGE
RM
SERVER
RM
OFFICE
INTERVIEW
RM
19'-3 1/2" ± 16'-8" ± 20'-1 5/8" ±
153'-9" ±
'-2
/2
'-9
/2
5'
-1
1/ 2"
'-5
/2
'-0
'-4
'-4
59'-1" ± 94'-8" ±
'-3
'-5
/8
'-1
3/
4"
'-8
/4
'-5
/4
1'
-8
/8
'-2
/4
'-8
/4
3/
4"
18'-6 1/4" ±15'-6" ±
4'-5" ±
22'-2" ±
5'-1 1/2" ±
31'-7 1/2"± 28'-1" ± 6'-0 1/2"±18'-4" ±
18'-4" ± 16'-0 1/4" ± 9'-1 1/2" ± 13'-3 3/4" ±
'-3
/2
'-6
'-4
/4
4' -0
/4
3'-0"±
TYP1
TYP
TYP
1 TYP
1 TYP
'-6
'-4
/4
2 5 5 5
6 6
2 7
2 72 7
2 72 72 7
2 7 2 7
12'-0 5/8" ±
2 7 2 7
15'-5"±10'-3 1/2"±5'-7"±5'-3 1/2"±9'-9" ± 4'-6 1/2"±
153'-9" ±
11 12
9 12
9 12
6'-9 3/8"±6'-9 3/8"±11'-10 5/8"±
1/
2"
1 TYP
BASE TOUR OFFICE
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:2 :0
P
M
C U s e rs
\e ri c .s u n d e rl a n d \D o c u m e n ts
\R E
V
IT
F ile s \C
E P
A
R e ri c .s u n d e rl a n d .r v t
HM101
B
LD
G C
E P
-1
N C
IS
O
F F
IC
E
R E
N O
V A
T
IO
N
O V
E R
A
LL
F
LO
O R
P
LA
N
H A
Z A
R D
O U
S M
A
TE
R
IA
LS
A
B A
TE
M
E N
T
ALP
12,910,595
EJS EJS
05/30/2024
JUNY GIBSON, NCIS
ERIC SUNDERLAND, R.A.
1689103
N/A
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
J. C. MILLER, P.E.
ALP
M
ID
L A
N T
P
W D
N O
R F
O L K
H M
0 4' 8' 16'
PLAN
NORTH
SCALE: 1/8" = 1'-0"
OVERALL FLOOR PLAN - HAZARDOUS MATERIAL ABATEMENT
B1
GENERAL SHEET NOTES
HAZARDOUS ABATEMENT KEYNOTES#
KEYPLAN
PLAN
NORTH
1 REMOVE AND DISPOSE OF LOOSE AND FLAKING SUSPECTED LEAD-BASED
PAINT ON EXTERIOR CMU WALL SURFACES. FOR BIDDING PURPOSES,
ASSUME A TOTAL OF 1,100 SF OF THIS TYPE OF ABATEMENT.
2 REMOVE AND DISPOSE OF LOOSE AND FLAKING SUSPECTED LEAD-BASED
PAINT ON INTERIOR CMU AND/OR DRYWALL SURFACES. FOR BIDDING
PURPOSES, ASSUME A TOTAL OF 500 SF OF THIS TYPE OF ABATEMENT.
3 REMOVE AND DISPOSE OF SUSPECTED ASBESTOS AND MOLD
CONTAMINATED VCT FLOORING AND MASTIC ADHESIVE COMPLETE TO
CONCRETE SUBSTRATE BELOW. FOR BIDDING PURPOSES, ASSUME A TOTAL
OF 400 SF OF THIS TYPE OF ABATEMENT.
4 REMOVE AND DISPOSE OF SUSPECTED ASBESTOS AND MOLD
CONTAMINATED VCT FLOORING, CARPET TILE FLOORING, AND MASTIC
ADHESIVE COMPLETE TO CONCRETE SUBSTRATE BELOW. FOR BIDDING
PURPOSES, ASSUME A TOTAL OF 1,200 SF OF THIS TYPE OF ABATEMENT.
5 REMOVE AND DISPOSE OF SUSPECTED ASBESTOS AND MOLD
CONTAMINATED SEALANTS FROM EXISTING DOOR FRAMES AND THRU-WALL
PENETRATIONS. FOR BIDDING PURPOSES, ASSUME A TOTAL OF 100 LF OF
THIS TYPE OF ABATEMENT.
6 REMOVE AND DISPOSE OF SUSPECTED ASBESTOS CONTAMINATED DUCT
INSULATION (ABOVE CEILING) FROM EXISTING MECHANICAL SYSTEM
CONSTRUCTION. FOR BIDDING PURPOSES, ASSUME A TOTAL OF 550 SF OF
THIS TYPE OF ABATEMENT.
7 REMOVE AND DISPOSE OF SUSPECTED MOLD CONTAMINATED INTERIOR
WALL FURRING, INCLUDING GYPSUM WALLBOARD, BATT INSULATION, AND
STUD BACKING COMPLETE TO INTERIOR SIDE OF EXTERIOR WALL, AND FULL
HEIGHT OF INTERIOR WALL FURRING. FOR BIDDING PURPOSES, ASSUME A
TOTAL OF 2,500 SF OF THIS TYPE OF ABATEMENT.
8 REMOVE AND DISPOSE OF SUSPECTED MOLD CONTAMINATED CARPET TILE
FLOORING AND MASTIC ADHESIVE COMPLETE TO CONCRETE SUBSTRATE
BELOW. FOR BIDDING PURPOSES, ASSUME A TOTAL OF 675 SF OF THIS TYPE
OF ABATEMENT.
9 REMOVE AND DISPOSE OF SUSPECTED MOLD CONTAMINATED VCT
FLOORING AND MASTIC ADHESIVE COMPLETE TO CONCRETE SUBSTRATE
BELOW. FOR BIDDING PURPOSES, ASSUME A TOTAL OF 1,070 SF OF THIS
TYPE OF ABATEMENT.
10 REMOVE AND DISPOSE OF SUSPECTED MOLD CONTAMINATED VINYL
FLOORING AND MASTIC ADHESIVE COMPLETE TO CONCRETE SUBSTRATE
BELOW. FOR BIDDING PURPOSES, ASSUME A TOTAL OF 210 SF OF THIS TYPE
OF ABATEMENT.
11 REMOVE AND DISPOSE OF SUSPECTED MOLD CONTAMINATED VCT
FLOORING, CARPET TILE FLOORING, AND MASTIC ADHESIVE COMPLETE TO
CONCRETE SUBSTRATE BELOW. FOR BIDDING PURPOSES, ASSUME A TOTAL
OF 250 SF OF THIS TYPE OF ABATEMENT.
12 REMOVE AND DISPOSE OF SUSPECTED MOLD CONTAMINATED WALLBASE
AND ADHESIVE COMPLETE. FOR BIDDING PURPOSES, ASSUME A TOTAL OF
900 LF OF THIS TYPE OF ABATEMENT.
A REFER TO GENERAL HAZARDOUS MATERIALS NOTES ON THIS SHEET.
B THE ASSUMED QUANTITIES IDENTIFIED IN THE HAZARDOUS ABATEMENT
KEYNOTES ARE FOR BIDDING PURPOSES. ADDITIONAL QUANTITIES OF
SELECT HAZARDOUS MATERIAL ABATEMENT ARE INCLUDED IN THE BID
SCHEDULE. THE QUANTITIES IN THE BID SCHEDULE ARE INTENDED TO BE
SEPARATE FROM (ABOVE AND BEYOND) THOSE INDICATED HEREIN.
C IN THE EVENT THAT ADDITIONAL MATERIALS AND/OR QUANTITIES OF
HAZARDOUS MATERIALS ARE UNCOVERED DURING CONSTRUCTION, ABOVE
AND BEYOND THOSE IDENTIFIED ON THIS SHEET, IMMEDIATELY STOP THE
WORK AND NOTIFY THE CONTRACTING OFFICER FOR FURTHER ACTION.
D REFER TO SUBSEQUENT DRAWINGS AND SPECIFICATIONS FOR LOCATIONS
AND REQUIREMENTS OF ALL WORK ITEMS INCLUDED IN THE PROJECT.
GENERAL HAZARDOUS MATERIALS NOTES
HM-4 REFER TO HAZARDOUS ABATEMENT KEYNOTES ON THIS SHEET FOR
ASSUMED QUANTITIES AND GENERAL LOCATIONS OF SUSPECTED
HAZARDOUS MATERIALS.
HM-5 ABATE AND DISPOSE OF LEAD, ASBESTOS, AND MOLD CONTAMINATED
MATERIALS IN ACCORDANCE WITH FEDERAL, STATE, AND LOCAL
REGULATIONS. REFER TO SPECIFICATIONS SECTIONS 02 82 00 "ASBESTOS
REMEDIATION", 02 83 00 "LEAD REMEDIATION", AND 02 85 00 "MOLD
REMEDIATION" FOR ADDITIONAL HAZARDOUS MATERIALS PROJECT
REQUIREMENTS.
HM-6 PROVIDE TEMPORARY ENCLOSURES AS REQUIRED TO PERFORM
HAZARDOUS MATERIAL ABATEMENT. TEMPORARY ENCLOSURES MUST
NOT DISRUPT EXISTING BUILDING EGRESS REQUIREMENTS.
HM-7 REFER TO SHEET GI002 FOR ADDITIONAL PROJECT NOTES.
HM-1 LEAD AND ASBESTOS TESTING HAS NOT BEEN COMPLETED FOR ANY
MATERIALS OR BUILDING COMPONENTS LOCATED WITHIN THE PROJECT
AREAS OF BUILDING CEP-177. HOWEVER, LEAD AND ASBESTOS TEST
REPORTS FOR NEARBY NAVFAC FACILITIES WITH SIMILAR AGE,
CONSTRUCTION TYPE, AND MATERIALS HAVE CONFIRMED PRESENCE OF
LEAD AND ASBESTOS IN SELECT BUILDING COMPONENTS. THESE
REPORTS FROM OTHER NAVFAC FACILITIES ARE THE BASIS OF SEVERAL
ASSUMED HAZMAT CONDITIONS IN THIS PROJECT.
HM-2 MOLD TESTING HAS NOT BEEN COMPLETED FOR ANY MATERIALS OR
BUILDING COMPONENTS LOCATED WITHIN THE PROJECT AREAS OF
BUILDING CEP-177. HOWEVER, VISUAL EVIDENCE OF MOLD GROWTH ON
INTERIOR SURFACES OF FURRED EXTERIOR WALLS WAS DETECTED AND
ARE THE BASIS OF SEVERAL ASSUMED HAZMAT CONDITIONS IN THIS
PROJECT.
HM-3 PRIOR TO BEGINNING ANY WORK, COMPLETE REPRESENTATIVE FIELD
SAMPLING AND LABORATORY ANALYSIS OF ALL LEAD, ASBESTOS, AND
MOLD MATERIALS IDENTIFIED IN THE HAZARDOUS MATERIAL KEYNOTES
AS SUSPECTED OF CONTAMINATION. SUBMIT LABORATORY ANALYSIS
REPORT OF THESE MATERIALS TO THE CONTRACTING OFFICER FOR
NAVFAC REVIEW.
NCIS
OFFICE
BASE
TOUR
S Y
M D
E S
C R
IP
T
I O N
D A
T E
A P
DOOR NUMBER
(REFER TO DOOR SCHEDULE)
DOOR TAG
ARCHITECTURAL SYMBOLS
PARTITION TYPE DESIGNATION
(REFER TO PARTITION SCHEDULE)
PARTITION TYPE
INDICATOR
PARTITION IN PLAN
REFER TO SHEET GI002 FOR
ADDITIONAL PROJECT SYMBOLS
SIGNAGE TYPE MARK
(REFER TO SIGNAGE SCHEDULE)
SIGNAGE TYPE TAG1
MATERIALS LEGEND
CONCRETE MASONRY UNIT
CAST-IN-PLACE CONCRETE
STEEL
BATT/LOOSE FILL INSULATION
RIGID INSULATION
WOOD - ROUGH
WOOD BLOCKING
EIFS - PAINTED
CMU - PAINTED
SECTION ELEVATION
CMU - PAINTED - ACCENT
GLAZED BLOCK
GLAZING
SPANDREL GLAZING / STEEL PANEL
CONCRETE FOUNDATION
EARTH / COMPACT FILL
POROUS FILL / GRAVEL
ALUMINUM
BRICK
GYPSUM BOARD
PLYWOOD
SAND / MORTAR / PLASTER
ACOUSTICAL TILE CEILING
CERAMIC TILE
FINISHED WOOD
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:2 :1
P
M
C U s e rs
\e ri c .s u n d e rl a n d \D o c u m e n ts
\R E
V
IT
F ile s \C
E P
A
R e ri c .s u n d e rl a n d .r v t
A-001
B
LD
G C
E P
-1
N C
IS
O
F F
IC
E
R E
N O
V A
T
IO
N
A R
C H
IT
E
C
TU
R A
L N
O
TE
S A
N D
S Y
M B
O
LS
ALP
12,910,596
EJS EJS
05/30/2024
JUNY GIBSON, NCIS
ERIC SUNDERLAND, R.A.
1689103
N/A
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
J. C. MILLER, P.E.
ALP
M
ID
L A
N T
P
W D
N O
R F
O L K
A -0
A ALL ITEMS INDICATED TO BE REMOVED MUST BE DISPOSED OF OFF SITE
UNLESS OTHERWISE NOTED.
B ALL MATERIALS MUST BE NEW AND PROVIDED BY THE CONTRACTOR UNLESS
SPECIFICALLY NOTED AS EXISTING OR AS PROVIDED BY THE GOVERNMENT.
C ALL WOOD BLOCKING AND MISCELLANEOUS STEEL SHOWN IN DETAILS AND
SECTIONS MUST BE CONTINUOUS UNLESS SPECIFICALLY NOTED
OTHERWISE.
D VERIFY ALL FIELD CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING
WITH THE WORK. DIMENSIONS FOR EXISTING WORK ARE INDICATED AS "±".
ALL DISCREPANCIES MUST BE BROUGHT TO THE IMMEDIATE ATTENTION OF
THE CONTRACTING OFFICER IN WRITING.
E DEMOLITION OF PLUMBING, MECHANICAL AND ELECTRICAL ITEMS INDICATED
ON THE ARCHITECTURAL DRAWINGS IS NOT INTENDED TO INCLUDE ALL
NECESSARY DEMOLITION WORK FOR THESE ITEMS. REFER TO PLUMBING,
MECHANICAL AND ELECTRICAL DEMOLITION DRAWINGS FOR ADDITIONAL
INFORMATION.
F DIMENSIONS INDICATED FOR NEW WORK ARE TO FACE OF STUD, FACE OF
MASONRY OR FACE OF EXISTING SURFACES UNLESS OTHERWISE NOTED.
G STUDY AND COMPARE THE CONTRACT DOCUMENTS WITH EACH OTHER, AND
AT ONCE, REPORT TO THE ARCHITECT ANY ERRORS AND INCONSISTENCIES
OR OMISSIONS DISCOVERED. ANY CONSTRUCTION ACTIVITY PERFORMED
KNOWING IT INVOLVES A RECOGNIZED ERROR, INCONSISTENCY OR
OMISSION IN THE CONTRACT DOCUMENTS WITHOUT SUCH NOTICE TO THE
ARCHITECT, THE CONTRACTOR WILL ASSUME RESPONSIBILITY FOR SUCH
PERFORMANCE AND WILL BEAR THE AMOUNT OF THE COST OF THE
CONSTRUCTION.
SF SQUARE FOOT
SH SHINGLES / SINGLE HUNG
SIM SIMILAR
SPC SUSPENDED PLASTER CEILING
SPEC SPECIFICATION
SQ SQUARE
STD STANDARD
STOR STORAGE
STR STRAIGHT STRIKE / STRINGERS
SUSP SUSPENDED
T&B TOP AND BOTTOM
TEL TELEPHONE
THRES THRESHOLD
THRU THROUGH
TOS TOP OF SLAB / STEEL
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLT
VAR VARIATION
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VENT VENTILATION / VENTILATOR
VERT VERTICAL
VEST VESTIBULE
VS VENT STACK
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WASTE / WATT / WEST / WIDE
W/ WITH
W/O WITHOUT
WC WATER CLOSET / WALL COVERING
WD WOOD
WH WATER HEATER
WP WATERPROOFING / WEATHERPROOF / WORKING
POINT
WSCT WAINSCOT
WT WEIGHT
WWF WELDED WIRE FABRIC
XRMR TRANSFORMER
NTS NOT TO SCALE
OA OUTSIDE AIR
OC ON CENTER
OD OUTSIDE DIAMETER / DIMENSION
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPT OPTIONAL
PCT PERCENT
PEJ PREMOLDED EXPANSION JOINT
PL PROPERTY LINE
PLAS PLASTER / PLASTIC
PLYWD PLYWOOD
PNL PANEL
PRELIM PRELIMINARY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT
QT QUARRY TILE
R RADUIS / RISER
RA RETURN AIR
RAD RETURN AIR DUCT
RB RESILIENT BASE
RD ROOF DRAIN / ROAD
REFL REFLECT
REFR REFRIGERATION
REINF REINFORCE
REQD REQUIRED
REV REVISION
RF RESILIENT FLOORING
RL ROOF LEADER
RM ROOM
RND ROUND
RO ROUGH OPENING
RS ROUGH SAWN
RT RIGHT
S SOUTH
SAPC SUSPENDED ACOUSTICAL PANEL CEILING
SCHED SCHEDULE
SECT SECTION
FTG FOOTING
GA GAUGE
GALV GALVANIZED
GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED GOVERNMENT INSTALLED
GL GLASS / GROUND LEVEL
GR GROSS
GSU GLAZED STRUCTURAL UNIT
GYP GYPSUM
H HIGH
HB HOSE BIB
HDW HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HT HEIGHT
HVY HEAVY
ID INSIDE DIAMETER
INSUL INSULATION / INSULATED
INT INTERIOR
J-BOX JUNCTION BOX
JAN JANITOR CLOSET
LAV LAVATORY
LB POUND
LT LIGHT
MACH MACHINE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFG MANUFACTURING
MIN MINIMUM / MINUTE
MISC MISCELLANEOUS
ML MATCH LINE
MO MASONRY OPENING / MOTOR OPERATED
MTD MOUNTED
MTG MOUNTING / MEETING
MTL METAL
MWP MEMBRANE WATERPROOFING
N NORTH
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
CPT CARPET / COMMON PATH OF TRAVEL
CT CERAMIC TILE
CTR CENTER
D DEPTH / DEEP
DEG DEGREE
DEMO DEMOLITION
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DR DRAIN
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
E EAST
EA EACH
EIFS EXTERIOR INSULATION & FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC / ELECTRICAL
EPDM ETHLENE PROPYLENE DIEN MONOMER
EQ EQUAL
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION / EXPOSED / EXPAND
EXT EXTERIOR
FD FLOOR DRAIN
FDTN FOUNDATION
FF FINISH FACE
FG FIGURE
FHC FIRE HOUSE CABINET
FIN FLR FINISHED FLOOR
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUB / FACE OF SLAB
FR FRAME / FIRE RATING / FIRE RESISTANT
FT FOOT, FEET
AB ANCHOR BOLT
ACS PNL ACCESS PANEL
ADJ ADJUST
ALT ALTERNATE, ALTITUDE
ALUM ALUMINUM
ANOD ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECT
ASPH ASPHALT
ATC ACOUSTICAL TILE CEILING
BD BOARD
BLDG BUILDING
BLW BELOW
BM BEAM
BOS BOTTOM OF SLAB / STEEL
BOT BOTTOM
BRG BEARING
BSMT BASEMENT
BTWN BETWEEN
C TO C CENTER TO CENTER
CAB CABINET
CEM CEMENT
CER CERAMIC
CI CAST IRON
CIP CAST IRON PIPE
CJ CONTROL / CONSTRUCTION JOINT
CLG CEILING
CLG REG CEILING REGISTER
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CND CONDUIT
CNDS CONDENSATE
CNSTR CONSTRUCTION
CNTR CNTR
CO CLEANOUT
COL COLUMN
CONC CONCRETE
CONN CONNECT
CONT CONTINUE / CONTINUOUS
CORR CORRIDOR
ARCHITECTURAL ABBREVIATIONS
GENERAL ARCHITECTURAL NOTES
S Y
M D
E S
C R
IP
T
I O N
D A
T E
A P
REF
NIC
C
A
B
2 3 4 5
VAULT /
FORENSICS
LAB
GARAGE
IT LAB
RECEPTION
RM
FORENSIC
CONSULT
114 DARK RM
MEN'S
TOILET
WOMEN'S
TOILET
ENTRY
VESTIBULE
CORRIDOR
ADMIN
OFFICE
FILE RM
101B
PRINTER
RM
101C
CORRIDOR
SSA
OFFICE
101A
OFFICE
CONF RM
STORAGE
RM
SERVER
RM
OFFICE
INTERVIEW
RM
D
E
19'-3 1/2" ± 16'-8" ± 20'-1 5/8" ±
153'-9" ±
'-2
/2
'-9
/2
5'
-1
1/ 2"
'-5
/2
'-0
'-4
'-4
59'-1" ± 94'-8" ±
'-1
3/
4"
'-5
/4
AD402
B1
'-1
3/
4"
'-8
/4
'-5
/4
1' -8
/8
'-2
/4
'-8
/4
BASE TOUR OFFICE
10 35
B3
AD201
C1
AD201
D1
AD201
B1
AD201
3/
4"
18'-6 1/4" ±15'-6" ±
4'-5" ±
22'-2" ±
5'-1 1/2" ±
31'-7 1/2" ± 28'-1" ± 6'-0 1/2 ±
18'-4" ±
18'-4" ± 16'-0 1/4" ± 9'-1 1/2" ± 13'-3 3/4" ±
'-3
/2
'-6
'-4
/4
4' -0
/4
3'-0"±
'-4
AD401
B1
6'-9 3/8"±6'-9 3/8"±
'-9
/4
11'-10 1/2"± 14'-4"±
4' -6
8'
-9
15'-5"±10'-3 1/2"±
7'-2 1/4"± 4'-8 1/4"±
AD402
A1
AD401
A1
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:2 :1
P
M
C U s e rs
\e ri c .s u n d e rl a n d \D o c u m e n ts
\R E
V
IT
F ile s \C
E P
A
R e ri c .s u n d e rl a n d .r v t
AD101
B
LD
G C
E P
-1
N C
IS
O
F F
IC
E
R E
N O
V A
T
IO
N
O V
E R
A
LL
F
LO
O R
P
LA
N
D E
M O
LI
TI
O N
ALP
12,910,597
EJS EJS
05/30/2024
JUNY GIBSON, NCIS
ERIC SUNDERLAND, R.A.
1689103
N/A
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
J. C. MILLER, P.E.
ALP
M
ID
L A
N T
P
W D
N O
R F
O L K
A D
GENERAL SHEET NOTES
DEMOLITION KEYNOTES#
0 4' 8' 16'
PLAN
NORTH
SCALE: 1/8" = 1'-0"
OVERALL FLOOR PLAN - DEMOLITION
B1
KEYPLAN
PLAN
NORTH
A REFER TO SHEET GI002 FOR ADDITIONAL GENERAL PROJECT NOTES.
B THE GENERAL INTENT OF DEMOLTION WORK IS TO COMPLETELY REMOVE
ALL ITEMS OF EXISTING CONSTRUCTION, WHERE NOTED OR INDICATED,
INCLUDING BUT NOT LIMITED TO: ANCHORS, FASTENERS, BRACKETS, CLIPS,
RODS, HANGERS, AND SUPPORTS COMPLETE.
C DIMENSIONS OF EXISTING CONDITIONS ARE BASED ON HISTORIC
DOCUMENTATION AND FIELD INVESTIGATIONS. VERIFY ALL DIMENSIONS AND
CONDITIONS IN THE FIELD PRIOR TO PERFORMING ANY WORK. BRING
DISCREPANCIES TO THE ATTENTION OF THE CONTRACTING OFFICER PRIOR
TO PERFORMING THE WORK.
D REFER TO FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL
DRAWINGS FOR ADDITIONAL INFORMATION.
E COORDINATE DEMOLITION WORK SHOWN HERE WITH HAZARDOUS MATERIAL
ABATEMENT WORK ON DRAWING HM101. ASSUME ALL ELEMENTS IDENTIFIED
WITH DEMOLITION LINE WORK BUT NOT NOTED ON THIS SHEET ARE WORK
ITEMS ASSOCIATED HAZMAT ABATEMENT.
1 DEMOLISH EXISTING PARTITION COMPLETE.
2 DEMOLISH EXISTING DOOR, FRAME, AND HDW COMPLETE.
3 DEMOLISH EXISTING DOUBLE DOORS, FRAME, AND HDW COMPLETE.
4 EXISTING DOOR, FRAME, AND HDW TO REMAIN.
5 EXISTING DOUBLE DOORS, FRAME, AND HDW TO REMAIN.
6 EXISTING COILING OVERHEAD DOOR TO REMAIN. REFER TO DOOR SCHEDULE
ON AE601 FOR ADDITIONAL REQUIREMENTS.
7 DEMOLISH BASE AND WALL CABINETS AND COUNTERTOP COMPLETE.
8 DEMOLISH CARPET FLOORING, RESILIENT WALL BASE, AND ASSOCIATED
ADHESIVE COMPLETE TO CONCRETE SUBSTRATE BELOW.
9 DEMOLISH RESILIENT TILE FLOORING, RESILIENT WALL BASE, AND
ASSOCIATED ADHESIVE COMPELTE.
10 EXISTING SEALED CONCRETE FLOOR FINISH TO REMAIN..
NCIS
OFFICE
BASE
TOUR
S Y
M D
E S
C R
IP
T
I O N
D A
T E
A P
A
B
2 3 4 5
D
E
114 116
101A
110 108 100
HD
UN
UN
101B 101C
(9'-7"±)
(9'-11"±)
(9'-11"±)
(8'-11"±)
(9'-11"±)
(8'-6"±)(8'-6"±)
(9'-0"±)
(9'-0"±)
(8'-6"±)
(9'-0"±) (9'-0"±) (8'-9"±)
(8'-7"±)
(8'-5"±)
(8'-8"±)
(8'-7"±)
(8'-6"±)
(12'-8"±)
(9'-0"±)
(8'-6"±) M
M
M
M
M
M
M
M
M
M
M
BASE TOUR OFFICE
REFLECTED CEILING PLAN LEGEND
SYMBOL DESCRIPTION
SUSPENDED ACT CEILING ASSEMBLY.
LIGHT FIXTURE.
REFER TO ELECTRICAL DRAWINGS.
EMERGENCY LIGHT FIXTURE.
REFER TO ELECTRICAL DRAWINGS.
CEILING SUPPLY DIFFUSER.
REFER TO MECHANICAL DRAWINGS.
CEILING RETURN OR EXHAUST.
REFER TO MECHANICAL DRAWINGS.
NO CEILING - EXPOSED TO ROOF DECK ABOVE.
GYPSUM BOARD CEILING.
AREA NOT IN CONTRACT.
HORN/STROBE.
REFER TO FIRE PROTECTION DRAWINGS.
EXIT LUMINAIRE.
REFER TO ELECTRICAL DRAWINGS.
MOTION SENSOR.
REFER TO ELECTRICAL DRAWINGS.
FINISHED CEILING HEIGHT ABOVE FINISHED FLOOR(X'-X")
SPRINKLER HEAD.
REFER TO FIRE PROTECTION DRAWINGS.
SYMBOL DESCRIPTION
UN
M
SMOKE DETECTOR.
REFER TO FIRE PROTECTION DRAWINGS.
CLEAR/UNCLEAR SECURITY STROBE.
REFER TO ELECTRICAL DRAWINGS.
EMERGENCY BATTERY POWERED LIGHT FIXTURE.
REFER TO ELECTRICAL DRAWINGS.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:2 :2
P
M
C U s e rs
\e ri c .s u n d e rl a n d \D o c u m e n ts
\R E
V
IT
F ile s \C
E P
A
R e ri c .s u n d e rl a n d .r v t
AD102
B
LD
G C
E P
-1
N C
IS
O
F F
IC
E
R E
N O
V A
T
IO
N
O V
E R
A
LL
R E
F
LE
C
TE
D C
E
IL
IN
G
P
LA
N
D E
M O
LI
TI
O N
ALP
12,910,598
EJS EJS
05/30/2024
JUNY GIBSON, NCIS
ERIC SUNDERLAND, R.A.
1689103
N/A
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
J. C. MILLER, P.E.
ALP
M
ID
L A
N T
P
W D
N O
R F
O L K
A D
GENERAL SHEET NOTES
DEMOLITION KEYNOTES#
0 4' 8' 16'
PLAN
NORTH
SCALE: 1/8" = 1'-0"
REFLECTED CEILING PLAN - DEMOLITION
B1
KEYPLAN
PLAN
NORTH
1 DEMOLISH SUSPENDED ACOUSTICAL CEILING TILE, GRID, SUSPENSION
SYSTEM, AND LOOSE LAID CEILING INSULATION OVERHEAD COMPLETE.
2 DEMOLISH GYPSUM BOARD CEILING, SUPPORTS, AND LOOSE LAID
INSULATION OVERHEAD COMPLETE.
3 NO CEILING, EXPOSED TO STRUCTURE ABOVE.
A REFER TO SHEET GI002 FOR ADDITIONAL GENERAL PROJECT NOTES.
B THE GENERAL INTENT OF DEMOLTION WORK IS TO COMPLETELY REMOVE
ALL ITEMS OF EXISTING CONSTRUCTION, WHERE NOTED OR INDICATED,
INCLUDING BUT NOT LIMITED TO: ANCHORS, FASTENERS, BRACKETS, CLIPS,
RODS, HANGERS, AND SUPPORTS COMPLETE.
C REFER TO FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL
DRAWINGS FOR ADDITIONAL INFORMATION.
D THERE IS EVIDENCE OF LOOSE LAID FIBERGLASS BATT INSULATION ABOVE
ALL CEILING TILES IN EXISTING ACT CEILING AREAS.
NCIS
OFFICE
BASE
TOUR
S Y
M D
E S
C R
IP
T
I O N
D A
T E
A P
A
D
E
HIGH ROOF AREA LOW-ROOF AREA
59'-1"± 94'-8"±
'-0
'-4
5' -1
1/
2"
'-5
/2
16'-0"± 78'-8"±
'-4
9 10
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:2 :2
P
M
C U s e rs
\e ri c .s u n d e rl a n d \D o c u m e n ts
\R E
V
IT
F ile s \C
E P
A
R e ri c .s u n d e rl a n d .r v t
AD103
B
LD
G C
E P
-1
N C
IS
O
F F
IC
E
R E
N O
V A
T
IO
N
O V
E R
A
LL
R O
O F
P
LA
N
D E
M O
LI
TI
O N
ALP
12,910,599
EJS EJS
05/30/2024
JUNY GIBSON, NCIS
ERIC SUNDERLAND, R.A.
1689103
N/A
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
J. C. MILLER, P.E.
ALP
M
ID
L A
N T
P
W D
N O
R F
O L K
A D
GENERAL SHEET NOTES
DEMOLITION KEYNOTES#
A REFER TO SHEET GI002 FOR ADDITIONAL GENERAL PROJECT NOTES.
B THE GENERAL INTENT OF THE ROOF DEMOLITION WORK IS TO COMPLETELY
REMOVE ALL ITEMS OF EXISTING CONSTRUCTION, WHERE NOTED OR
INDICATED, ASSOCIATED WITH AN EXISTING ROOFTOP AHU AND IN
PREPARATION FOR INSTALLATION OF A WATER-TIGHT INSULATED STEEL
ROOF CAP OVER THE EXISTING EQUIPMENT SUPPORT CURBS. OTHER
INCIDENTAL WORK AT THE ROOF LEVEL IS AS NOTED OR INDICATED.
C REFER TO FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL
DRAWINGS FOR ADDITIONAL INFORMATION.
D THE EXISTING LOW- AND HIGH-ROOFS ARE BOTH BUILT-UP BITUMEN ROOF
SYSTEMS THAT INCLUDE RIGID INSULATION, COVERBOARD, BASE AND TOP
MEMBRANES, AND METAL ROOF DECKING UNDERLAYMENT. NEITHER ROOF
AGE, INSULATION DEPTH, ROOF MANUFACTURER, INSTALLING CONTRACTOR,
NOR ROOF WARRANTY STATUS ARE NOT KNOWN. FOR BIDDING PURPOSES,
ASSUME THE FOLLOWING: INSULATION DEPTH IS 2 1/2", COVERBOARD IS 1/2",
AND ROOF WARRANTY STATUS IS INACTIVE. ALL WORK THAT WILL IMPACT
THE ROOF SYSTEMS IS INTENDED TO MAINTAIN AND/OR RESTORE GENERAL
WATER-TIGHTNESS, BUT IS NOT REQUIRED TO MEET ANY ADDITIONAL
SPECIFIC ROOF SYSTEM WARRANTY COVERAGE REQUIREMENTS.
KEYPLAN
PLAN
NORTH
0 4' 8' 16'
PLAN
NORTH
SCALE: 1/8" = 1'-0"
ROOF PLAN - DEMOLITION
B1
NCIS
OFFICE
BASE
TOUR
1 EXISTING BUILT-UP BITUMEN ROOF SYSTEM TO REMAIN, NIC.
2 EXISTING ALUMINUM GUTTER TO REMAIN. REFER TO AD201 FOR ADDITIONAL
WORK REQUIREMENTS.
3 EXISTING ROOF ACCESS LADDER TO REMAIN. REFER TO AD201 FOR
ADDITIONAL WORK REQUIREMENTS.
4 EXISTING ROOF PARAPET TO REMAIN.
5 EXISTING ROOF OPENING COVER PANEL TO REMAIN.
6 EXISTING ROOFTOP AHU TO REMAIN.
7 DEMOLISH EXISTING ROOFTOP AHU COMPLETE TO EQUIPMENT SUPPPORTS
BELOW, INCLUDING CONDUIT, WIRE, AND ASSOCIATED ROOF PENETRATION
POCKETS. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL
INFORMATION.
8 EXISTING CANOPY ROOF OVERHANG BELOW TO REMAIN, NIC.
9 EXISTING VTR TO REMAIN.
10 EXISTING ROOFTOP EQUIPMENT TO REMAIN.
S Y
M D
E S
C R
IP
T
I O N
D A
T E
A P
FIRST FLOOR
0"
LOW ROOF - WEST BAY
12'-7"
TOP OF CANOPY
14'-0"
TOP OF PARAPET - EAST BAY
16'-4"
5 6
NCIS OFFICE
59'-1" ±
NCIS OFFICE
93'-4" ± 1'-4" ±
16 16
1 1
TYP
TYP
334336
17 1718
FIRST FLOOR
0"
LOW ROOF - WEST BAY
12'-7"
5 6
NCIS OFFICE
59'-1" ±
BASE TOUR OFFICE - N.I.C.
94'-8" ±
3 79 6
NAVAL STATION TOURS
FIRST FLOOR
0"
LOW ROOF - WEST BAY
12'-7"
C A
NCIS OFFICE
44'-0" ±
TYP
6 36
FIRST FLOOR
0"
TOP OF CANOPY
14'-0"
TOP OF PARAPET - EAST BAY
16'-4"
A E
NCIS OFFICE
24'-10 3/4" ±
BASE TOUR OFFICE - NIC
35'-5 1/4" ±
1' -0
NAVAL STATION TOURS
ELEVATION LEGEND
SYMBOL DESCRIPTION
EXISTING COATING TO BE REMOVED
EXISTING OVERHEAD DOOR COATING TO BE REMOVED
EXISTING EXTERIOR COATING TO REMAIN, NIC
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:2 :3
P
M
C U s e rs
\e ri c .s u n d e rl a n d \D o c u m e n ts
\R E
V
IT
F ile s \C
E P
A
R e ri c .s u n d e rl a n d .r v t
AD201
B
LD
G C
E P
-1
N C
IS
O
F F
IC
E
R E
N O
V A
T
IO
N
B U
IL
D
IN
G
E
LE
V A
TI
O
N S
D
E M
O
LI
TI
O
N
ALP
12,910,600
EJS EJS
05/30/2024
JUNY GIBSON, NCIS
ERIC SUNDERLAND, R.A.
1689103
N/A
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
J. C. MILLER, P.E.
ALP
M
ID
L A
N T
P
W D
N O
R F
O L K
A D
0 4' 8' 16'SCALE: 1/8" = 1'-0" (AD101)
BUILDING ELEVATION - SOUTH - DEMOLITION
C1
0 4' 8' 16'SCALE: 1/8" = 1'-0" (AD101)
BUILDING ELEVATION - NORTH - DEMOLITION
D1
0 4' 8' 16'SCALE: 1/8" = 1'-0" (AD101)
BUILDING ELEVATION - WEST - DEMOLITION
B30 4' 8' 16'SCALE: 1/8" = 1'-0" (AD101)
BUILDING ELEVATION - EAST - DEMOLITION
B1
GENERAL SHEET NOTES
DEMOLITION KEYNOTES#
A REFER TO SHEET GI002 FOR ADDITIONAL GENERAL NOTES.
B EXISTING EXTERIOR WALL COATING IS SUSPECTED OF CONTAINING
LEAD-BASED PAINT. ALL DEMOLITION WORK ASSOCIATED WITH REMOVAL OF
THIS COATING MUST TREATED AS A HAZARDOUS MATERIAL AND ABATED
ACCORDINGLY. REFER TO SHEET HM101 FOR ADDITIONAL REQUIREMENTS
AND ASSUMED QUANTITIES.
C THE WORK INCLUDES THE DEMOLITION AND REMOVAL OF ALL
CONSTRUCTION INDICATED, NOTED, OR NECESSARY TO ACCOMPLISH THE
WORK AS INDICATED OR SPECIFIED. IT IS THE GENERAL INTENT OF THE
DEMOLITIOIN WORK TO COMPLETELY REMOVE ALL ITEMS OF EXISTING
CONSTRUCTION, WHERE NOTED OR INDICATED ON THE DRAWING,
INCLUDING, BUT NOT LIMITED TO: ANCHORS, FASTENERS, BRACKETS, CLIPS,
RODS, HANGERS, AND SUPPORTS COMPLETE.
D FOR CLARITY PURPOSES, SOME WALL MOUNTED EQUIPMENT & FIXTURES
ARE NOT SHOWN (CONDUITS, JUNCTION BOXES, OUTLETS, GROUNDING
WIRE, ETC.). FIELD VERIFY ALL LOCATIONS. REFER TO REFERENCE PHOTO
SHEETS FOR VISUAL REPRESENTATION OF EXISTING EQUIPMENT AND
CONDITIONS.
E WHERE WALL MOUNTED EQUIPMENT AND FIXTURES ARE SET TO BE
DEMOLISHED, PATCH ALL REMAINING ABANDONED WALL
OPENINGS/PENETRATIONS WHERE EQUIPMENT IS REMOVED. FOR BIDDING
PURPOSES, ASSUME THE FOLLOWING WALL PATCH REQUIREMENTS:
A. 20 EA CMU OPENINGS UP TO 4 SQUARE IN
B. 20 EA CMU OPENINGS UP TO 2 SQUARE IN
C. 20 EA CMU OPENINGS UP TO 1 SQUARE IN
F BUILDING ELEVATIONS, INCLUDING EQUIPMENT SHOWN ON THE ELEVATIONS,
ARE A VISUAL REPRESENTATION OF THE CONDITION OF THE BUILDING AT
THE TIME FIELD WORK WAS CONDUCTED. VERIFY ALL DIMENSIONS AND
CONDITIONS IN THE FIELD PRIOR TO PERFORMING ANY WORK. BRING ANY
DISCREPANCIES TO THE ATTENTION OF THE CONTRACTING OFFICER PRIOR
TO PERFORMING ANY WORK.
G FOR WALL INFILL LOCATIONS INDICATED ON THIS SHEET, INFILL WALL WITH
UNITS TO MATCH SIZE AND COURSING OF EXISTING ADJACENT EXTERIOR
CMU AND JOINTS. EXISTING EXTERIOR CMU WALL IS CONSTRUCTED OF 8" X
8" X 16" CMU BLOCKS.
1 REMOVE AND SALVAGE 3" X 4" DOWNSPOUT FOR REINSTALLATION.
2 EXISTING MASONRY WALL CONSTRUCTION TO REMAIN. SCRAPE TO REMOVE
LOOSE EXTERIOR PAINT COATING AND REPOINT DAMAGED CMU JOINTS IN
PREPARATION FOR NEW EXTERIOR WATERPROOFING COATING. FOR
BIDDING PURPOSES, ASSUME 100 LF OF CMU JOINT REPAIRS.
3 DISCONNECT, REMOVE, AND SALVAGE EXISTING EXTERIOR LIGHT FIXTURE
FOR REINSTALLATION.
4 DISCONNECT AND REMOVE EXISTING EXTERIOR LIGHT FIXTURE.
5 DEMOLISH 1/2" CMU EXPANSION JOINT COMPLETE.
6 REMOVE AND SALVAGE 5" X 5" ALUMINUM GUTTER FOR REINSTALLATION.
7 SCRAPE TO REMOVE LOOSE PAINT ON BOTH SIDES OF METAL COILING
OVERHEAD DOOR IN PREPRARATION FOR NEW PAINT COATING.
8 EXISTING BOLLARDS TO REMAIN, N.I.C.
9 REMOVE THRU-WALL POWERED VENTILATOR EXHAUST EQUIPMENT
COMPLETE, AND INFILL RESULTANT OPENING IN EXTERIOR CMU WALL.
10 EXISTING EXTERIOR FACILITY ELEMENTS TO REMAIN, NIC.
11 REMOVE AND SALVAGE EXISTING METAL SIGN FOR REINSTALLATION.
12 EXISTING BOLLARDS TO REMAIN, NIC.
13 DEMOLISH ABANDONED THRU-WALL VENT COMPLETE, AND INFILL
RESULTANT OPENING IN EXTERIOR CMU WALL.
14 EXISTING WALL MOUNTED EQUIPMENT TO REMAIN.
15 REMOVE AND SALVAGE ±8" TALL METAL COPING AS REQUIRED TO REMOVE
WALL COATING TO TOP OF MASONRY COURSING.
16 DEMOLISH INSULATED METAL DUCTWORK COMPLETE TO THRU-WALL
OPENING, AND INFILL RESULTANT OPENING IN EXTERIOR CMU WALL.
17 DEMOLISH EXISTING DOOR, FRAME, AND HDW COMPLETE.
18 SAWCUT AND DEMOLISH MASONRY PARTITION TO EXTENT SHOWN, AS
REQUIRED FOR NEW DOOR OPENING. COORDINATE DOOR OPENING WITH
THAT SHOWN ON NEW WORK DRAWINGS.
19 REMOVE AND SALVAGE EXTERIOR ROOF ACCESS LADDER ASSEMBLY FOR
REINSTALLATION.
20 DISCONNECT AND REMOVE EXISTING WALL-MOUNTED MECHANICAL
EQUIPMENT AND ASSOCIATED APPURTENANCES AS REQUIRED TO REMOVE
EXTERIOR WALL COATING. REFER TO MECHANICAL FOR ADDITIONAL
INFORMATION.
21 DISCONNECT AND REMOVE EXISTING WALL-MOUNTED ELECTRICAL
EQUIPMENT AND ASSOCIATED APPURTENANCES AS REQUIRED TO REMOVE
EXTERIOR WALL COATING. REFER TO ELECTRICAL FOR ADDITIONAL
INFORMATION.
THERE IS NO EXTERIOR WORK REQUIRED AT EAST ELEVATION. IT IS SHOWN
HERE FOR GENERAL REFERENCE AND ORIENTATION PURPOSES ONLY.
S Y
M D
E S
C R
IP
T
I O N
D A
T E
A P
A
B
2 3 4 5
VAULT /
FORENSICS
LAB
IT LAB
RECEPTION
RM
FORENSIC
CONSULT
DARK RM
MEN'S
TOILET
WOMEN'S
TOILET
ENTRY
VESTIBULE
CORRIDOR
ADMIN
OFFICE
INTERVIEW
RM
GARAGE
3"
F
O M
5' -7
/2
3'
/2
3'-2 1/2"± 22'-0"± 14'-2"± 5'-9"± FOP
135.00°
7'- 6"
3'-2"±
9' -9
/4
F
O M
2' -0
4'-0"±
1'- 4"
5'- 0"
14'-6 1/2"±
14'-6 1/2"±
1' -5
1'-5'±
38'-0"±
3"
F
4'
-2
/2
135.00°
225.00°
2'- 0"
2' -0
2'-0"±
2 1
6 6
1 1
TYP
TYP
TYP
135.00°
TYP
TYP
TYP
TYP
BASE
TOUR
OFFICE
2'-0"± FOM
OFFICE
11'-0"±
CL
1' -9
2'-6"±
6"
EQ EQ
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:2 :4
P
M
C U s e rs
\e ri c .s u n d e rl a n d \D o c u m e n ts
\R E
V
IT
F ile s \C
E P
A
R e ri c .s u n d e rl a n d .r v t
AD401
B
LD
G C
E P
-1
N C
IS
O
F F
IC
E
R E
N O
V A
T
IO
N
E N
LA
R
G E
D S
LA
B
P
LA
N
"C O
R E
" A R
E A
D
E M
O
LI
TI
O
N
ALP
12,910,601
EJS EJS
05/30/2024
JUNY GIBSON, NCIS
ERIC SUNDERLAND, R.A.
1689103
N/A
N O
R F
O
LK
, V
IR
G
IN
IA
N
A V
A L
S T
A T
IO
N
N O
R F
O
LK
J. C. MILLER, P.E.
ALP
M
ID
L A
N T
P
W D
N O
R F
O L K
A D
GENERAL SHEET NOTES
DEMOLITION KEYNOTES#
KEYPLAN
CORE NCIS
OFFICE
BASE
TOUR
OFFICE 102
PLAN
NORTH
0 1'-6" 3' 6'
PLAN
NORTH
SCALE: 3/8" = 1'-0" (AD101)
ENLARGED SLAB PLAN - "CORE" AREA - DEMOLITION
B1
A UON, DASHED LINES SHOWN INDICATE WALLS TO BE DEMOLISHED.
DEMOLISHED WALLS SHOWN HERE ARE FOR GENERAL REFERENCE ONLY.
REFER TO SHEET AD402 FOR ADDITIONAL DEMOLITION WORK INFORMATION.
B REFER TO SHEET GI002 FOR ADDITIONAL GENERAL PROJECT NOTES.
C REFER TO FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL
DRAWINGS FOR ADDDITIONAL INFORMATION.
D SLAB DEMOLITION WORK SHOWN ON THIS SHEET IS IN SUPPORT OF
UNDER-SLAB PLUMBING DEMOLITION AND NEW WORK REQUIREMENTS.
REFER TO PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION. REFER TO
SHEET AE401 FOR SLAB PATCH AND REPAIR REQUIREMENTS.
E THE DEMOLITION WORK ON THIS SHEET SHEET IS NOT INTENDED TO
REPRESENT THE COMPLETE ARCHITECTURAL DEMOLITION WORK
REQUIREMENTS. REFER TO SUBSEQUENT ARCHITECTURAL DEMOLITION
SHEETS FOR ADDITIONAL DEMOLITION WORK REQUIREMENTS
F FOR BIDDING PURPOSES, ASSUME EXISTING SLAB BEING DEMOLISHED IS
SLAB ON GRADE CONSTRUCTION, ±4" THICK WITH 6X6 W1.4 X W1.4 W.W.F
REINFORCING, ON 6 MIL POLY VAPOR BARRIER OVER A ±4" DEPTH OF
CAPILLARY WATER BARRIER.
1 PROVIDE 2" DEEP SAWCUT AROUND PERIMETER OF HATCHED AREA.
DEMOLISH EXISTING SECTION OF +/-6" THICK REINFORCED CONCRETE SLAB
COMPLETE WITHIN HATCHED AREA.
2 EXISTING CONCRETE SLAB TO REMAIN.
3 APPROXIMATE LOCATION OF EXISTING SANITARY WASTE LINE TIE-IN. REFER
TO PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
4 DASHED LINE INDICATES LOCATION OF BUILDING EXPANSION JOINT.
5 DASHED LINE INDICATES LOCATION OF EXISTING CONCRETE FOOTING
BELOW REINFORCED CONCRETE SLAB. ASSUME TOP OF CONCRETE
FOOTING IS ±1'-4" BELOW TOP OF CONCRETE SLAB.
6 DASHED LINE INDICATES LOCATION OF EXISTING THICKENED SLAB. ASSUME
THICKENED SLAB IS ±8" THICK X ±16" WIDTH, AND REINFORCED SIMILAR TO
FIELD SLAB CONSTRUCTION PLUS 2-#4 BAR REINFORCING RUNNING
PARALLEL TO WALL CONSTRUCTION ABOVE.
7 DASHED LINE INDICATES WALL TO BE DEMOLISHED. REFER TO SUBSEQUENT
DRAWING…